DG Sizing Calculation for 1 x 70 MW Unit
Table -1: Load List
Description Type of Load Rated Power (kW) Quantity Efficiency
O/G Feeder Emergency Lighting F 36.0 1 36 UPS F 59.5 1 59.5Battery Charger F 100.0 1 100Chimney F 0.16 1 0.16Elevator F 0.16 1 0.16Motor FeederBFP Lube Oil Pump M 15.0 1 13.5 0.8 16.88Air Pre Heaters MAuxiliary Oil Pump M 80.0 1 72 0.88 81.82Jacking Oil Pump M 18.5 1 16.65 0.8 20.81
Total Load 315.33Adding 10% margin 346.86
Total kW requirement ( base load) = 315.33 kW
= 346.86 kW
Alternator Size = 433.57 kVA
Minimum diesel engine output required = 365.11 kW (Generator Eff. 0.95)
= 207.91 kW
= 441.42 kW
= 464.65 kW
Selected Diesel engine size = 470 kW
Selected Alternator Size = 500 kVA
Shaft Power Demand(kW)
Input Power of Individual Load ( kW)
Active Power Requirement ( considering 10% margin)
Active power requirement during to largest motor starting
( starting current =6 times + 20% margin) & starting power factor = 0.3
Active power requirement during largest motor starting at base load
Diesel engine output required during largest motor starting
DG Sizing Calculation for 2 x 35 MW Unit
Table -1: Load List
Description Quantity Efficiency
O/G Feeder Emergency Lighting F 36.0 1 36 UPS F 59.5 1 59.5Battery Charger F 85.0 1 85Chimney F 0.16 1 0.16Elevator F 0.16 1 0.16Motor FeederBFP Lube Oil Pump M 15.0 1 13.5 0.8 16.88Auxiliary Oil Pump M 40.0 2 36 0.88 81.82Jacking Oil Pump M 18.5 1 16.65 0.8 20.81
Total Load 283.45Adding 10% margin 311.80
Total kW requirement ( base load) = 283.45 kW
= 311.80 kW
Alternator Size = 389.74 kVA
Minimum diesel engine output required = 328.21 kW (Generator Eff. 0.95)
= 88.36 kW
= 290.00 kW
= 305.26 kW
Selected Diesel engine size = 350 kW
Selected Alternator Size = 400 kVA
Type of Load
Rated Power (kW)
Shaft Power Demand(kW)
Input Power of Individual Load ( kW)
Active Power Requirement ( considering 10% margin)
Active power requirement during to largest motor starting
( starting current =6 times + 20% margin) & starting power factor = 0.3
Active power requirement during largest motor starting at base load
Diesel engine output required during largest motor starting