dfhadfh

Embed Size (px)

Citation preview

  • 7/30/2019 dfhadfh

    1/48

    American Standard Inc. 1997

    The Trane CompanyLa Crosse, Wisconsin

    Refrigeration System

    Equipment Room Design

  • 7/30/2019 dfhadfh

    2/48

    American Standard Inc. 1997

    ANSI/ASHRAE Standards

    Standard 34-1992

    Number Designation And Safety ClassificationOf Refrigerants

    Standard 15-1994

    Safety Code For Mechanical Refrigeration

  • 7/30/2019 dfhadfh

    3/48

    American Standard Inc. 1997

    Number Designation AndSafety Classification Of Refrigerants

    Purpose? To establish a

    simple means of referring to common refrigerantsinstead of using the chemical name, formula, or tradename.

    uniform system for assigning reference numbersand safety classifications to refrigerants.

    ANSI/ASHRAE Standards

    Standard 34-1992

  • 7/30/2019 dfhadfh

    4/48

    American Standard Inc. 1997

    ASHRAE Standard 34-1992

    Refrigerant Safety Classifications

    Group A3

    Group A2

    Group A1

    Group B3

    Group B2

    Group B1

    higher

    flammability

    lowerflammability

    no flamepropagation

    lower toxicity higher toxicity

  • 7/30/2019 dfhadfh

    5/48

    American Standard Inc. 1997

    ASHRAE Standard 34-1992

    Refrigerant/Blend Data

    Refrigerant Chemical Name OrComposition (% By Weight)

    Methane SeriesCFC (or R) 11 Trichlorofluoromethane 75F A1 1.6 4,000CFC (or R) 12 Dichlorodifluoromethane 22F A1 12.0 40,000HCFC (or R) 22 Chlorodifluoromethane 41F A1 9.4 42,000

    Ethane Series

    CFC (or R) 113 1,1,2Trichlorotrifluoroethane 118F A1 1.9 4,000HCFC (or R) 123 2,2Dichloro1,1,1Trifluoroethane 81F B1 0.4 1,000

    HFC (or R) 134a 1,1,1,2Tetrafluoroethane 15F A1 16.0 60,000HFC (or R) 152a 1,1Difluoroethane 13F A2 1.2 7,000

    Azeotropes

    R500 R12 (73.8) / R152a (26.2) 27F A1 12.0 47,000R502 R22 (48.8) / R115 (51.2) 49F A1 19.0 65,000

    NormalBoiling

    Point

    Safety

    Group

    Lbs/1000

    cu ft

    PPMBy

    Vol

    Refrig Qty PerOccupied Space

  • 7/30/2019 dfhadfh

    6/48

    American Standard Inc. 1997

    ANSI/ASHRAE Standards

    Standard 15-1994

    Purpose?

    to specify safe design, construction, installation,and operation of refrigerating systems.

    Scope?

    This code established safeguards for life, limb, health,

    and property and prescribes safety standards.

    Safety Code ForMechanical Refrigeration

  • 7/30/2019 dfhadfh

    7/48

    American Standard Inc. 1997

    ANSI/ASHRAE Standards

    Standard 15-1994

    It applies to

    mechanical refrigerating systems andheat pumps used in the occupancies definedin Section 4 and installed subsequently toadoption of this code

    Safety Code ForMechanical Refrigeration

  • 7/30/2019 dfhadfh

    8/48

    American Standard Inc. 1997

    ANSI/ASHRAE Standards

    Standard 15-1994

    It also applies to

    parts or components added after adoptionof this code, or a change to a refrigerant of adifferent number designation after adoption ofthis code

    Safety Code ForMechanical Refrigeration

  • 7/30/2019 dfhadfh

    9/48

    American Standard Inc. 1997

    ANSI/ASHRAE Standards

    Standard 15-1994

    Finally, it applies to

    parts or components replaced afteradoption of this code only if they are notidentical in function

    Safety Code ForMechanical Refrigeration

  • 7/30/2019 dfhadfh

    10/48

    American Standard Inc. 1997

    ANSI/ASHRAE Standards

    Standard 15-1994

    Provides classification criteria for

    Safety group Occupancy type

    Refrigerating system probability

    Safety Code ForMechanical Refrigeration

  • 7/30/2019 dfhadfh

    11/48

    American Standard Inc. 1997

    ANSI/ASHRAE Standards

    Standard 15-1994

    Provides classification criteria for

    Safety group Occupancy type

    Refrigerating system probability

    Safety Code ForMechanical Refrigeration

  • 7/30/2019 dfhadfh

    12/48

    American Standard Inc. 1997

    ASHRAE Standard 15-1994

    Safety Group Classification

    Standard 34s refrigerant safety classifications

    Group A3

    Group A2

    Group A1

    Group B3

    Group B2

    Group B1

    higherflammability

    lowerflammability

    no flamepropagation

    lower toxicity higher toxicity

  • 7/30/2019 dfhadfh

    13/48

    American Standard Inc. 1997

    ANSI/ASHRAE Standards

    Standard 15-1994

    Provides classification criteria for

    Safety group Occupancy type

    Refrigerating system probability

    Safety Code ForMechanical Refrigeration

  • 7/30/2019 dfhadfh

    14/48

    American Standard Inc. 1997

    ASHRAE Standard 15-1994

    Occupancy Classification

    Institutional

    Occupants cant readily leave without help

    Public assembly

    Where large numbers of occupants cant vacate quickly

    Residential

    Occupants have complete, independent living facilities

    Industrial

    Occupancy is restricted only to authorized personnel

  • 7/30/2019 dfhadfh

    15/48

    American Standard Inc. 1997

    ASHRAE Standard 15-1994

    Occupancy Classification

    Commercial

    Occupants transact business, receive personal

    services, or purchase food or other goods

    Large mercantile

    Premises where more than 100 people congregate topurchase personal merchandise

    Mixed

    Two or more occupancies share the same building

  • 7/30/2019 dfhadfh

    16/48

    American Standard Inc. 1997

    ANSI/ASHRAE Standards

    Standard 15-1994

    Provides classification criteria for

    Safety group Occupancy type

    Refrigerating system probability

    Safety Code ForMechanical Refrigeration

  • 7/30/2019 dfhadfh

    17/48

    American Standard Inc. 1997

    ASHRAE Standard 15-1994

    Refrigerating System Probability

    High Probability

    Low Probability

    System

    Designation

    Cooling

    Or Heating Source

    Air Or Substance

    To Be Cooled, Heated

    Direct

    IndirectOpen Spray

    Double IndirectOpen Spray

    IndirectClosed

    IndirectVented Closed

  • 7/30/2019 dfhadfh

    18/48

    American Standard Inc. 1997

    ASHRAE Standard 15-1994

    Refrigerant Quantity Rules

    Public Assembly,Refrigerant System Residential, Commercial,

    Group Probability Institutional Large Mercantile Industrial

    A1 High 2 1 3Low 4 4 4

    A2 High 5 5 3Low 7 7 7

    A3 High 9 9 3Low 9 9 7

    B1 High 2, 6 1, 6 3Low 4 4 4

    B2 High 5, 6 5, 6 3Low 7 7 7

    B3 High 9 9 3Low 9 9 7

    Applicable Rules By Occupancy Classification

  • 7/30/2019 dfhadfh

    19/48

    American Standard Inc. 1997

    ASHRAE Standard 15-1994

    Refrigerant Quantity Rules

    Public Assembly,Refrigerant System Residential, Commercial,

    Group Probability Institutional Large Mercantile Industrial

    A1 High 2 1 3Low 4 4 4

    A2 High 5 5 3Low 7 7 7

    A3 High 9 9 3Low 9 9 7

    B1 High 2, 6 1, 6 3Low 4 4 4

    B2 High 5, 6 5, 6 3Low 7 7 7

    B3 High 9 9 3Low 9 9 7

    Applicable Rules By Occupancy Classification

  • 7/30/2019 dfhadfh

    20/48

    American Standard Inc. 1997

    ASHRAE Standard 15-1994

    Refrigerant Quantity Rules

    Rule 4

    When the quantity of refrigerant in anysystem exceeds Table 1 amounts, allrefrigerant-containing parts, except piping andthose parts outside the building, shall beinstalled in a machinery room constructed inaccordance with the provisions of 8.13.

  • 7/30/2019 dfhadfh

    21/48

    American Standard Inc. 1997

    ASHRAE Standard 34-1992

    Refrigerant Safety Classifications

    Refrigerant Chemical Name OrComposition (% By Weight)

    Methane Series

    CFC (or R) 11 Trichlorofluoromethane 75F A1 1.6 4,000CFC (or R) 12 Dichlorodifluoromethane 22F A1 12.0 40,000HCFC (or R) 22 Chlorodifluoromethane 41F A1 9.4 42,000

    Ethane Series

    CFC (or R) 113 1,1,2Trichlorotrifluoroethane 118F A1 1.9 4,000HCFC (or R) 123 2,2Dichloro1,1,1Trifluoroethane 81F B1 0.4 1,000

    HFC (or R) 134a 1,1,1,2Tetrafluoroethane 15F A1 16.0 60,000HFC (or R) 152a 1,1Difluoroethane 13F A2 1.2 7,000

    Azeotropes

    R500 R12 (73.8) / R152a (26.2) 27F A1 12.0 47,000R502 R22 (48.8) / R115 (51.2) 49F A1 19.0 65,000

    NormalBoilingPoint

    SafetyGroup

    lbs/1000cu ft

    PPMByVol

    Refrig Qty PerOccupied Space

  • 7/30/2019 dfhadfh

    22/48

    American Standard Inc. 1997

    Equipment Room Design

    Ventilation

    Refrigeration system placement Doors, passageways and access

    Refrigerant monitoring

    Open-flame devices Pressure-relief piping

    General requirements

  • 7/30/2019 dfhadfh

    23/48

    American Standard Inc. 1997

    Equipment Room Design

    Ventilation

    Refrigeration system placement Doors, passageways and access

    Refrigerant monitoring

    Open-flame devices Pressure-relief piping

    General requirements

  • 7/30/2019 dfhadfh

    24/48

    American Standard Inc. 1997

    equipment room design

    Ventilation

    Volume requirements for

    Natural ventilation Mechanical ventilation

    Normal rate

    Alarm rate

  • 7/30/2019 dfhadfh

    25/48

    American Standard Inc. 1997

    equipment room design

    Ventilation

    Remote machinery room

    Occupied

    Building

    OccupiedBuilding

    RefrigerationSystem

    Lean-to Or OtherStructure WithNatural Ventilation

    More Than20 Feet

  • 7/30/2019 dfhadfh

    26/48

    American Standard Inc. 1997

    equipment room design

    Ventilation

    Natural ventilation

    For refrigerating systems installed outdoors, morethan 20 ft from [any] building openings

    F = G0.5

    where:F = free opening area (sq ft)G = mass of refrigerant (lbs)

  • 7/30/2019 dfhadfh

    27/48

    American Standard Inc. 1997

    equipment room design

    Ventilation

    Normal-rate mechanical ventilation

    Needed whenever the equipment rooms occupied

    Requirements:

    0.5 cfm per sq ftOR20 cfm per person

    Must operate, if necessary for operator comfort, at a volume

    that limits the temperature rise (T) to no more than 18F

  • 7/30/2019 dfhadfh

    28/48

    American Standard Inc. 1997

    equipment room design

    Ventilation

    Alarm-rate mechanical ventilation

    Required to exhaust accumulated refrigerant

    Q = 100 G0.5

    where:Q = airflow (cu ft per minute)G = mass of refrigerant (lbs)

  • 7/30/2019 dfhadfh

    29/48

    American Standard Inc. 1997

    equipment room design

    Ventilation

    Suggested exhaust fan location

    Exhaust Fan

    6 Feet

  • 7/30/2019 dfhadfh

    30/48

    American Standard Inc. 1997

    equipment room design

    Ventilation

    Dual-purposeventilation system

    ExhaustAirflow

    End View

    Plan View

    VentilationAirflow

  • 7/30/2019 dfhadfh

    31/48

    American Standard Inc. 1997

    Equipment Room Design

    Ventilation

    Refrigeration system placement

    Doors, passageways and access

    Refrigerant monitoring

    Open-flame devices Pressure-relief piping

    General requirements

  • 7/30/2019 dfhadfh

    32/48

    American Standard Inc. 1997

    equipment room design

    Refrigeration System Placement

    Unobstructed space for inspecting andservicing equipment

    Must comply with applicable safety standards andrequirements of the presiding regulatory agency

    Clear head room not less than 7.25 ft below

    equipment over passageways

  • 7/30/2019 dfhadfh

    33/48

    American Standard Inc. 1997

    equipment room design

    Refrigeration System Placement

    Multiple-chiller equipment room layouts

    Arrangement BArrangement A

    ExhaustFan

    RefrigerationSystems

    ExhaustFan

    ExhaustFan

    ExhaustFan

    RefrigerationSystems

    RefrigerationSystems

    AirInlet

    AirInlet

    AirInlet

  • 7/30/2019 dfhadfh

    34/48

    American Standard Inc. 1997

    Equipment Room Design

    Ventilation

    Refrigeration system placement

    Doors, passageways and access

    Refrigerant monitoring

    Open-flame devices Pressure-relief piping

    General requirements

  • 7/30/2019 dfhadfh

    35/48

    American Standard Inc. 1997

    equipment room design

    Doors, Passageways And Access

    Equipment room access limited to authorizedpersonnel

    Adequate number and type of doors

    No openings to other parts of the building

    No shared air-handling systems

  • 7/30/2019 dfhadfh

    36/48

    American Standard Inc. 1997

    Equipment Room Design

    Ventilation

    Refrigeration system placement

    Doors, passageways and access

    Refrigerant monitoring

    Open-flame devices Pressure-relief piping

    General requirements

  • 7/30/2019 dfhadfh

    37/48

    American Standard Inc. 1997

    equipment room design

    Refrigerant Monitoring

    Detector must

    Be appropriately sensitive to the refrigerant(s)in use

    Activate alarm and ventilation at TLVTWA

    Threshold Limit ValueTime Weighted Average

  • 7/30/2019 dfhadfh

    38/48

    American Standard Inc. 1997

    equipment room design

    Refrigerant Monitoring

    Sensor location and placement

    Height: 18 inches above the floor Plan

    Continuous ventilation: Between the refrigerationsystem and room exhaust

    Intermittent ventilation: Close to the refrigerationsystem, between it and the room entrance

  • 7/30/2019 dfhadfh

    39/48

    American Standard Inc. 1997

    equipment room design

    Refrigerant Monitoring

    Typical refrigerant monitor installation

    Chiller

    RefrigerantMonitor

    5 Feet

    Roof Or Concrete Floor

    Mechanical Equipment RoomOccupied Space

    Sample-In Tubing

    Particle Filter

    1218 Inches

  • 7/30/2019 dfhadfh

    40/48

    American Standard Inc. 1997

    equipment room design

    Refrigerant Monitoring

    Suggested sensor placement for intermittentventilation

    Identifies refrigerant sampling points

    Refrigeration Systems

  • 7/30/2019 dfhadfh

    41/48

    American Standard Inc. 1997

    equipment room design

    Refrigerant Monitoring

    Typical multichannelscanner application

    Identifies refrigerant sampling points

    Pit

    Refrigerant Monitor

    With Multichannel Option

  • 7/30/2019 dfhadfh

    42/48

    American Standard Inc. 1997

    Equipment Room Design

    Ventilation

    Refrigeration system placement

    Doors, passageways and access

    Refrigerant monitoring

    Open-flame devices Pressure-relief piping

    General requirements

  • 7/30/2019 dfhadfh

    43/48

    American Standard Inc. 1997

    equipment room design

    Open-Flame Devices

    No open flames that use combustion air fromthe machinery room shall be installed where any

    refrigerant is used.

    Exceptions

    Combustion air is ducted from outside and sealed to

    prevent refrigerant leakage into the combustionchamber

    A refrigerant detector is used to shut down combustionautomatically if a refrigerant leak occurs

  • 7/30/2019 dfhadfh

    44/48

    American Standard Inc. 1997

    Equipment Room Design

    Ventilation

    Refrigeration system placement

    Doors, passageways and access

    Refrigerant monitoring

    Open-flame devices Pressure-relief piping

    General requirements

  • 7/30/2019 dfhadfh

    45/48

    American Standard Inc. 1997

    equipment room design

    Pressure-Relief Piping

    Suggested refrigerantvent piping

    15 Feet AboveGround Level

    (Alternate Arrangement)

    Exterior Wall

    Roof

    Purge DischargeVent Line

    Rupture Disc

    Assembly

    Flexible Steel

    Connection

    Drip Leg(Length As

    Needed)

    1/4 FL 1/4 NPTDrain Valve

    Support this pipe!

  • 7/30/2019 dfhadfh

    46/48

    American Standard Inc. 1997

    Equipment Room Design

    Ventilation

    Refrigeration system placement

    Doors, passageways and access

    Refrigerant monitoring

    Open-flame devices Pressure-relief piping

    General requirements

  • 7/30/2019 dfhadfh

    47/48

    American Standard Inc. 1997

    equipment room design

    General Requirements

    Signs

    Changing, charging and storing refrigerants

    Self-contained breathing apparatus

    Two required per equipment room

    Emergency shutdown procedure

    General maintenance

  • 7/30/2019 dfhadfh

    48/48

    An American-Standard Company