Data Sheet 10/63-0.56-EN Rev. C Devices overview FOUNDATION Fieldbus-H1 Operate Engineer Control Field Ex ia P T F Ethernet FOUNDATION Fieldbus-H1 Linking device FOUNDATION Fieldbus-H1 FOUNDATION Fieldbus-H1 Temperature Transmitter Multivariable Field Indicator Pressure and Level Transmitter Multivariable Transmitter Flowmeter Analyzer Positioner Linking Device Network components, Accessories Contents

Devices overview FOUNDATION Fieldbus-H1 · 2018-05-09 · Devices overview FOUNDATION Fieldbus-H1 10/63-0.56-EN 2 Temperature Transmitter Temperature Transmitter Diagnosis & maintenance

  • Upload
    others

  • View
    1

  • Download
    1

Embed Size (px)

Citation preview

Page 1: Devices overview FOUNDATION Fieldbus-H1 · 2018-05-09 · Devices overview FOUNDATION Fieldbus-H1 10/63-0.56-EN 2 Temperature Transmitter Temperature Transmitter Diagnosis & maintenance

Data Sheet 10/63-0.56-EN Rev. C

Devices overview FOUNDATION Fieldbus-H1

Operate

Engineer

Control

Field

Ex ia

PT F

Ethernet

FOUNDATION Fieldbus-H1

Linking

device

FOUNDATION

Fieldbus-H1

FOUNDATION

Fieldbus-H1

Temperature Transmitter Multivariable Field Indicator Pressure and Level Transmitter Multivariable Transmitter Flowmeter Analyzer Positioner Linking Device Network components, Accessories

Contents

Page 2: Devices overview FOUNDATION Fieldbus-H1 · 2018-05-09 · Devices overview FOUNDATION Fieldbus-H1 10/63-0.56-EN 2 Temperature Transmitter Temperature Transmitter Diagnosis & maintenance

Devices overview FOUNDATION Fieldbus-H1 10/63-0.56-EN

2

Temperature Transmitter Temperature Transmitter

M00600 M00601

Diagnosis & maintenance data to increase the plant

availability

= Maintenance req.

= Out of specification

= Check function

= Failure

= No message T

F(2

)02,

TF

(2)0

2-E

X

TF02, TF02-EX TF202, TF202-EX Generic fieldbus diagnosis

Data sheet 10/11-8.25-EN 10/11-8.69-EN (see page 17) Internet www.abb.com/temperature www.abb.com/temperature

- plus - Advanced diagnosis

Application

Device functionality

Sensor 1 out of range - Low, -High •

Sensor 2 out of range - Low, -High •

Reference junction fault •

Head mounted transmitter RTD: Pt10, Pt100, Pt1000, Ni10, Ni100, Ni1000, Cu10, Cu100 Thermocouple: Type B, C, D, E, J, K, L, N, R, S, T, UVoltage: -120 mV … 1200 mV -75 mV ... 75 mV Resistance: 0 … 500 Ω / 0 ... 4000 Ω

Field mounted transmitter RTD: Pt10, Pt100, Pt1000, Ni10, Ni100, Ni1000, Cu10, Cu100 Thermocouple:: Type B, C, D, E, J, K, L, N, R, S, T, UVoltage: -120 mV … 1200 mV -75 mV ... 75 mV Resistance: 0 … 500 Ω / 0 ... 4000 Ω Measuring part fault •

Ambient temperature -40 ... 85 °C -40 ... 85 °C Type of protection IP 00 IP 67

Explosion protection II 1G EEx ia IIC T6 II 1G EEx ia IIC T6

Approvals ATEX, FM, CSA, CE ATEX, FM, CSA, CE FISCO approval Yes Yes

For FNICO usable Yes Yes Overvoltage protection H1 – Via external module

Physics MBP(-IS) (IEC 61158-2) MBP(-IS) (IEC 61158-2)

Baud Rate 31.25 kBit/s fix 31.25 kBit/s fix Device ID 000320-001E-xxxxxxxxx 000320-001E-xxxxxxxxx

[MANUFAC_ID]-[DEV_TYPE]-[Counter] [MANUFAC_ID]-[DEV_TYPE]-[Counter] FF Registration IT015000 (ITK version 4.01) IT015000 (ITK version 4.01) Bus address 16 ... 247 16 ... 247

local adjustment – – central adjustment Software (e. g.: Asset Vision) Software (e. g.: Asset Vision)

Backup LAS Yes Yes Resource Block (RB) 1 RB (Standard) 1 RB (Standard) Transducer Block (TB)

1 TB (Standard / Customized): sensor signal linearization

1 TB (Standard / Customized): sensor signal linearization

Function Block (FB)

2 AI (Standard): Temperature 1, Temperature 2

2 AI (Standard): Temperature 1, Temperature 2

FB Execution time AI = 25 ms AI = 25 ms Device configuration central adjustment EDD EDD local adjustment – – Asset Monitor Yes (for ABB Tools) Yes (for ABB Tools) Us min 9.0 V DC 9,0 V DC Basic current1) 10.5 mA 10,5 mA Δ Error current1) 4.5 mA 4,5 mA Start current after 10 ms = Basic current = Basic current External supply – –

1) Max. permanent current = basic current + Δ error current

Page 3: Devices overview FOUNDATION Fieldbus-H1 · 2018-05-09 · Devices overview FOUNDATION Fieldbus-H1 10/63-0.56-EN 2 Temperature Transmitter Temperature Transmitter Diagnosis & maintenance

Devices overview FOUNDATION Fieldbus-H1 10/63-0.56-EN

3

Temperature Transmitter Temperature Transmitter

M00595

Diagnosis & maintenance data to increase the plant

availability

= Maintenance req.

= Out of specification

= Check function

= Failure

= No message

TT

H3

00

TTH300 Generic fieldbus diagnosis

Data sheet DS/TTH300-EN (see page 17) Internet www.abb.com/temperature

- plus - Advanced diagnosis

Application

Device functionality

Sensor 1 out of range - Low, - High •

Sensor 1 - wire break •

Sensor 1 - short circuit •

Head mounted transmitter RTD: Pt10, Pt50, Pt100, Pt200, Pt1000, Ni50, Ni100, Ni120, Ni1000 Thermocouple: Type B, C, D, E, J, K, L, N, R, S, T, U Voltage: -125 mV … 125 mV / -125 ... 1100mV Reistance: 0 … 500 Ohm / 0 … 5000 Ohm Customer Specific Curve Callendar Van Dusen Coefficients

Sensor 2 out of range - Low, - High •

Ambient temperature -40 ... 85 °C Type of protection IP 20

Sensor 2 - wire break •

Explosion protection II 1G EEx ia IIC T6

Sensor 2 - short circuit •

Approvals ATEX, IECEX, FM, CSA, CE FISCO approval Yes

Reference junction fault •

For FNICO usable Yes Overvoltage protection H1 –

Device error •

Physics MBP(-IS) (IEC 61158-2)

Redundancy active alert •

Baud Rate 31.25 kBit/s fix Device ID 000320-0125-xxxxxxxxx

Drift-value-exceeding •

[MANUFAC_ID]-[DEV_TYPE]-[Counter]FF Registration IT0066100 (ITK version 5.2.0)

Operating hours counter •

Bus address 16 ... 247 local adjustment Keypad and display

Tmin / Tmax Drag-Inductor •

central adjustment Software (e. g.: Asset Vision) Backup LAS Yes Resource Block (RB) 1 RB (Standard) Transducer Block (TB)

3 TB (Standard): Temperature, HMI (LCD display), enhanced Diagnosis

Function Block (FB)

4 AI (Standard): Calculated Value, Sensor 1 or 2, Reference junction, 1 AO (Standard): Display value, 1 PID (Enhanced), 2 DI (Standard): Extended Diagnostic 1 & 2

FB Execution time All = 25 ms Device configuration central adjustment EDD local adjustment Keypad and display Asset Monitor Yes (for ABB Tools) Us min 9.0 V DC Basic current1) 12.0 mA Δ Error current1) 8.0 mA Start current after 10 ms = Basic current External supply –

1) Max. permanent current = basic current + Δ error current

Page 4: Devices overview FOUNDATION Fieldbus-H1 · 2018-05-09 · Devices overview FOUNDATION Fieldbus-H1 10/63-0.56-EN 2 Temperature Transmitter Temperature Transmitter Diagnosis & maintenance

Devices overview FOUNDATION Fieldbus-H1 10/63-0.56-EN

4

130

Pressure and Level Transmitter

M00584 M00585 M00586

2600T(264BS, 264Dx) 2600T(264xx) 2600T(264xx)

Data sheet

SS/264BS, SS/264XS, SS/264XF, SS/264DH

SS/264GS/AS, SS/264HS/NS, SS/264HF/NF, SS/264XS, SS/264XF

SS/264XC, SS/264XG, SS/264HP/NP,SS/264XR, SS/264DL, SS/S264

Internet www.abb.com/pressure www.abb.com/pressure www.abb.com/pressure Application

Differential Pressure / Flow / Level Measuring Range: 0.05 kPa ... 16 MPa, PN up to 41 MPa(0.5 mbar ... 160 bar, PN up to 410 bar)

Gauge / Absolute Pressure Measuring Range: 0.05 kPa ... 60 MPa, OVP up to 90 MPa (0.5 mbar ... 600 bar, OVP up to 900 bar) 0.3 kPa ... 16 MPa abs., OVP up to 21 MPa (3 mbar ... 160 bar abs., OVP up to 210 bar)

Pressures / Level / Density with direct mount or remote seal(s) Measuring Range: 0.2 kPa ... 60 MPa (2 mbar ... 600 bar), PN up to seal fitting rating

Ambient temperature -40 ... 85 °C -40 ... 85 °C -40 ... 85 °C Type of protection IP 67, NEMA 4X IP 67, NEMA 4X IP 67, NEMA 4X Explosion protection EEx ia IIC T4-T6, EEx d IIC T6 EEx ia IIC T4-T6, EEx d IIC T6 EEx ia IIC T4-T6, EEx d IIC T6 XP/IS/NI/DIP Class I, II or III Div.1 or 2 XP/IS/NI/DIP Class I, II or III Div.1 or 2 XP/IS/NI/DIP Class I, II or III Div.1 or 2 Approvals ATEX, FM, CSA, CE, PED ATEX, FM, CSA, CE, PED ATEX, FM, CSA, CE, PED FISCO approval Yes Yes Yes For FNICO usable Yes Yes Yes Overvoltage protection H1 Via external module Via external module Via external module Physics MBP(-IS) (IEC 61158-2) MBP(-IS) (IEC 61158-2) MBP(-IS) (IEC 61158-2) Baud Rate 31.25 kBit/s fix 31.25 kBit/s fix 31.25 kBit/s fix Device ID 000320-0004-xxxxxxxxx 000320-0004-xxxxxxxxx 000320-0004-xxxxxxxxx [MANUFAC_ID]-[DEV_TYPE]-[Counter] [MANUFAC_ID]-[DEV_TYPE]-[Counter] [MANUFAC_ID]-[DEV_TYPE]-[Counter]FF Registration IT032600 (ITK version 4.6) IT032600 (ITK version 4.6) IT032600 (ITK version 4.6) Bus address 16 ... 247 16 ... 247 16 ... 247 local adjustment – – – central adjustment Software (e. g.: Asset Vision) Software (e. g.: Asset Vision) Software (e. g.: Asset Vision) Backup LAS Yes Yes Yes Resource Block (RB) 1 RB (Enhanced) Transducer Block (TB)

1 TB (Enhanced): Pressure with calibration, 1 TB (Customized): Advanced diagnostic with PILD algorithm (Plugged Impulse Line Detection), 1 TB (Customized): Display

Function Block (FB)

AI and PID (Enhanced): 2 AI: Out of Differential, Absolute, Gauge or Static Pressure, Level, Flow or Sensor Temperature and Digital Alarm Signal, 1 PID: Controller Block. All other FB (Standard): 1 AR: Arithmetic Block, 1 IS: Input Selector, 1 CS: Control Selector, 1 SC: Signal Characterization, 1 IT: Integrator / Totalizer

FB Execution time PID = 40 ms, AI / AR / IS / CS / SC / IT = 25 ms Device configuration central adjustment EDD EDD EDD local adjustment Keypad and display Keypad and display Keypad and display Asset Monitor Yes (for ABB Tools) Yes (for ABB Tools) Yes (for ABB Tools) Us min 9.0 V DC 9.0 V DC 9.0 V DC Basic current1) 10.5 mA ± 0.5 mA 10.5 mA ± 0.5 mA 10.5 mA ± 0.5 mA Δ Error current1) 9.5 mA 9.5 mA 9.5 mA Start current after 10 ms = Basic current = Basic current = Basic current External supply – – –

1) Max. permanent current = basic current + Δ error current

Page 5: Devices overview FOUNDATION Fieldbus-H1 · 2018-05-09 · Devices overview FOUNDATION Fieldbus-H1 10/63-0.56-EN 2 Temperature Transmitter Temperature Transmitter Diagnosis & maintenance

Devices overview FOUNDATION Fieldbus-H1 10/63-0.56-EN

5

P and L Transmitter Multivariable Field Indicator

Diagnosis & maintenance data to increase the plant

availability

= Maintenance req.

= Out of specification

= Check function

= Failure

= No message

260

0T(2

64xx

)

M00602

Generic fieldbus diagnosis 2600T(264IB)

(see page 17) Data sheet SS/264IB

Internet www.abb.com/pressure - plus - Advanced diagnosis

Application Device functionality

Static Pressure Sensor

- Failed • Temperature Sensor

- Failed • Pressure Sensor Update

- Failed •

Mechanical Error •

The Multivariable Field Indicator 264IB implements different functions:1-Field Indicator for up to 8 H1 variables (pub/sub) and 1 Host driven variable (client/server). 2-Control FB Container to improve the control strategies in the field when the available transmitters do not allow it. 3-LAS Backup Unit

Ambient temperature -40 ... 85 °C Critical Sensor memory Error •

Type of protection IP 67, NEMA 4X Explosion protection Non-Critical Sensor memory

Error •

EEx ia IIC T4-T6, EEx d IIC T6 XP/IS/NI/DIP Class I, II or III Div.1 or 2

Approvals ATEX, FM, CSA, CE Electronics memory Error •

FISCO approval Yes For FNICO usable Yes

Sensor memory Burn Failure • Overvoltage protection H1 Via external module Electronics memory Burn

Failure • Physics MBP(-IS) (IEC 61158-2) Baud Rate 31.25 kBit/s fix Sensor Database Check

- Failed • Device ID 000320-0006-xxxxxxxxx [MANUFAC_ID]-[DEV_TYPE]-[Counter]Sensor Type Check

- Failed • FF Registration IT025500 (ITK version 4.51) Bus address 16 ... 247

Installation and Process local adjustment – central adjustment Software (e. g.: Asset Vision) Overpressure

- Low, - High • Backup LAS Yes Resource Block (RB) 1 RB (Enhanced) Overtemperature

- Low, - High • Transducer Block (TB) Over static Pressure

- Failed •

1 TB (Customized): Display Block

Function Block (FB) Pressure out of Sensor Limit - Low, - High •

Line H Plugged •

2 PID (Enhanced): Controller Block, 1 MUX (Customized): Multiplexer Block All other FB Standard: 1 AR: Arithmetic, 1 IS: Input Selector, 1 CS: Control Selector

FB Execution time PID = 25 ms, AR/IS/CS =10 ms, MUX =1 ms Line L Plugged •

Device configuration central adjustment EDD

Lines H and L Plugged • local adjustment Keypad and display Asset Monitor – One undetected Line

Plugged • Us min 9.0 V DC Basic current1) 10.5 mA ± 0.5 mA

Δ Error current1) 9.5 mA Start current after 10 ms = Basic current External supply –

1) Max. permanent current = basic current + Δ error current

Page 6: Devices overview FOUNDATION Fieldbus-H1 · 2018-05-09 · Devices overview FOUNDATION Fieldbus-H1 10/63-0.56-EN 2 Temperature Transmitter Temperature Transmitter Diagnosis & maintenance

Devices overview FOUNDATION Fieldbus-H1 10/63-0.56-EN

6

Pressure and Level Transmitter

M00587 M00588 M00587

2600T(265Ax) 2600T(265Dx) 2600T(265Gx)

Data sheet

SS/265GS/AS-EN SS/265Gx/Ax-EN

SS/265DS-EN, SS/265DC-EN, SS/265DR-EN

SS/265GS/AS-EN SS/265Gx/Ax-EN

Internet www.abb.com/pressure www.abb.com/pressure www.abb.com/pressure Application

Absolute Pressure Measuring Range: 2 mbar ... 30 bar abs. 200 Pa ... 3 MPa abs.

Differential Pressure / Flow / Level Differential Pressure: 0.5 mbar ... 100 bar 50 Pa ... 10 MPa Rated Pressure: 6 / 400 bar 0.6 / 40 MPa

Gauge Pressure / Level Measuring Range: 2 mbar ... 600 bar 200 Pa ... 60 MPa

Ambient temperature -40 ... 85 °C -40 ... 85 °C -40 ... 85 °C Type of protection IP 67, NEMA 4X IP 67, NEMA 4X IP 67, NEMA 4X Explosion protection

II 1/2G Ex ia IIC T6 resp. T4 II 1/2D Ex iaD 20 T50 °C resp. T95 °C

II 1/2G Ex ia IIC T6 resp. T4 II 1/2D Ex iaD 20 T50 °C resp. T95 °C

II 1/2G Ex ia IIC T6 resp. T4 II 1/2D Ex iaD 20 T50 °C resp. T95 °C

Approvals ATEX, CE, Oxygen messurement ATEX, CE, Oxygen meas., Overfill prot. ATEX, CE, Oxygen messurement FISCO approval Yes Yes Yes For FNICO usable Yes Yes Yes Overvoltage protection H1 Non-Ex (integrated as option), Ex (via external module) Physics MBP(-IS) (IEC 61158-2) MBP(-IS) (IEC 61158-2) MBP(-IS) (IEC 61158-2) Baud Rate 31.25 kBit/s fix 31.25 kBit/s fix 31.25 kBit/s fix Device ID 000320-0089-xxxxxxxxx 000320-0089-xxxxxxxxx 000320-0089-xxxxxxxxx [MANUFAC_ID]-[DEV_TYPE]-[Counter] [MANUFAC_ID]-[DEV_TYPE]-[Counter] [MANUFAC_ID]-[DEV_TYPE]-[Counter]FF Registration IT023600 (ITK version 4.51) IT023600 (ITK version 4.51) IT023600 (ITK version 4.51) Bus address 16 ... 247 16 ... 247 16 ... 247 local adjustment – – – central adjustment Software (e. g.: Asset Vision) Software (e. g.: Asset Vision) Software (e. g.: Asset Vision) Backup LAS Yes Yes Yes Resource Block (RB) 1 RB (Enhanced) 1 RB (Enhanced) 1 RB (Enhanced) Transducer Block (TB)

1 TB (Customized): Pressure with Calibration

1 TB (Customized): Pressure with Calibration

1 TB (Customized): Pressure with Calibration

Function Block (FB)

2 AI (Standard): Absolute Pressure, Sensor Temperature 1 PID (Standard): Controller Block

2 AI (Standard): Two out of Differential P, Absolute P, Sensor Temp. (shown as Flow, Level, Volume) 1 PID (Standard): Controller Block

2 AI (Standard): Gauge Pressure, Sensor Temperature (shown as Level, Volume) 1 PID (Standard): Controller Block

FB Execution time AI = 80 ms, PID = 100 ms AI = 80 ms, PID = 100 ms AI = 80 ms, PID = 100 ms Device configuration central adjustment EDD EDD EDD local adjustment Keypad and display Keypad and display Keypad and display Asset Monitor Yes (for ABB Tools) Yes (for ABB Tools) Yes (for ABB Tools) Us min 10.2 V DC 10.2 V DC 10.2 V DC Basic current1) 11.7 mA 11.7 mA 11.7 mA Δ Error current1) 5.6 mA 5.6 mA 5.6 mA Start current after 10 ms = Basic current = Basic current = Basic current External supply – – –

1) Max. permanent current = basic current + Δ error current

Page 7: Devices overview FOUNDATION Fieldbus-H1 · 2018-05-09 · Devices overview FOUNDATION Fieldbus-H1 10/63-0.56-EN 2 Temperature Transmitter Temperature Transmitter Diagnosis & maintenance

Devices overview FOUNDATION Fieldbus-H1 10/63-0.56-EN

7

Multivariable Transmitter P, L and MV Transmitter

M00589

Diagnosis & maintenance data to increase the plant

availability

= Maintenance req.

= Out of specification

= Check function

= Failure

= No message

260

0T(2

65xx

)

260

0T(2

67C

x, 2

69C

x)

2600T(267Cx, 269Cx) Generic fieldbus diagnosis

Data sheet 10/15-4.12-EN (see page 17) Internet www.abb.com/pressure

- plus - Advanced diagnosis

Application

Device functionality

Device malfunction • •

Electronic malfunction • •

Device is busy • •

Multivariable Transmitter / Flow Differential Pressure: 0.5 mbar ... 100 bar 50 Pa ... 10 MPa Absolute Pressure: 6 ... 400 bar abs. 0.6 ... 40 MPa abs. Process Temperature: -50 ... 650 °C Device configuration

Ambient temperature -40 ... 85 °C Type of protection IP 67, NEMA 4X

Invalid configuration • •

Explosion protection

II 1/2G Ex ia IIC T6 resp. T4 II 1/2D Ex iaD 20 T50 °C resp. T95 °C Installation and Process

Approvals ATEX, CE, Oxygen messurement FISCO approval Yes

Pressure out of adjusted range • •

For FNICO usable Yes Overvoltage protection H1 Via external module

Pressure out of sensor limits • •

Physics MBP(-IS) (IEC 61158-2)

Temperature pressure sensor out of limits • •

Baud Rate 31.25 kBit/s fix Device ID 000320-008A-xxxxxxxxx

Static Pressure out of sensor limits • •

[MANUFAC_ID]-[DEV_TYPE]-[Counter]FF Registration IT023700 (ITK version 4.51)

Temperature out of adjusted range

Bus address 16 ... 247 local adjustment –

Temperature out of sensor limits

central adjustment Software (e. g.: Asset Vision) Backup LAS Yes

dP out of limits of the flow calculation •

Resource Block (RB) 1 RB (Enhanced) Transducer Block (TB)

Static P out of limits of the flow calculation •

1 TB (Customized): Pressure with Calibration Temperature out of limits

of the flow calculation •

Function Block (FB)

A/D converter value out of limits • •

3 AI (Standard): dP, Absolute Pressure, Sensor / Medium Temperature, 1 PID (Standard): Controller Block, 1 MV (Customized): Mass, Volume Flow

FB Execution time AI = 80 ms, PID / MV =100 ms

Device configuration central adjustment DMA or EDD

local adjustment Keypad and display Asset Monitor Yes (for ABB Tools) Us min 10.2 V DC Basic current1) 11.7 mA Δ Error current1) 5.6 mA Start current after 10 ms = Basic current External supply –

1) Max. permanent current = basic current + Δ error current

Page 8: Devices overview FOUNDATION Fieldbus-H1 · 2018-05-09 · Devices overview FOUNDATION Fieldbus-H1 10/63-0.56-EN 2 Temperature Transmitter Temperature Transmitter Diagnosis & maintenance

Devices overview FOUNDATION Fieldbus-H1 10/63-0.56-EN

8

130

Pressure and Level Transmitter

M00598 M00599 M00598

2600T(266Gxx, 266Hxx, 266Pxx)

2600T(266Dxx, 266Mxx) 2600T(266Axx, 266Nxx, 266Vxx, 266Rxx)

Data sheet

DS/266HSH/NSH, DS/266GSH/ASH, DS/266XSH, DS/266XRH,

DS/266XDH, DS/266GDH/ADH, DS/266GRH/ARH, DS/266GST/AST,

DS/266XDT, DS/266XRT

DS/266XSH, DS/266MSH, DS/266DHH,DS/266XRH, DS/266MRH, DS/266XDH,

DS/266DLH, DS/266MST/RST, DS/266XDT, DS/266XRT

DS/266HSH/NSH, DS/266GSH/ASH, DS/266XSH, DS/266XRH,

DS/266XDH, DS/266GDH/ADH, DS/266GRH/ARH, DS/266GST/AST,

DS/266XDT, DS/266XRT

Internet www.abb.com/pressure www.abb.com/pressure www.abb.com/pressure Application

Gauge Pressure / Level Measuring Range: 0.05 kPa ... 60 MPa, OVP up to 90 MPa (0.5 mbar ... 600 bar, OVP up to 900 bar)

Differential Pressure / Flow / Level Measuring Range: 0.05 kPa ... 16 MPa, PN up to 41 MPa (0.5 mbar ... 160 bar, PN up to 410 bar)

Absolute Pressure / Level Measuring Range: 0.3 kPa ... 16 MPa abs., OVP up to 21 MPa (3 mbar ... 160 bar abs., OVP up to 210 bar)

Ambient temperature -40 ... 85 °C -40 ... 85 °C -40 ... 85 °C Type of protection IP 67, NEMA 4X IP 67, NEMA 4X IP 67, NEMA 4X Explosion protection II 1 G Ex ia IIC T6 & II 1/2 G Ex ia IIC T6 (-40 °C ≤ Ta ≤ 40 °C); II 1 D Ex iaD 20 T 95 °C & II 1/2D Ex iaD 21 T 95 °C. II 1/2 G Ex d IIC T6 & II 1/2 D Ex tD A21 IP67 T 85 °C. II 3 G Ex nL IIC T6 & II 3 D Ex tD A22 IP67 T 85 °C, XP/IS/NI/DIP Class I, II or III Div.1 or 2 Approvals ATEX, FM Approvals (US and Canada), IEC, GOST, CE, PED FISCO approval Yes Yes Yes For FNICO usable Yes Yes Yes Overvoltage protection H1 Yes (integrated) Yes (integrated) Yes (integrated) Physics MBP(-IS) (IEC 61158-2) MBP(-IS) (IEC 61158-2) MBP(-IS) (IEC 61158-2) Baud Rate 31.25 kBit/s fix 31.25 kBit/s fix 31.25 kBit/s fix Device ID 000320-0007-xxxxxxxxx 000320-0007-xxxxxxxxx 000320-0007-xxxxxxxxx [MANUFAC_ID]-[DEV_TYPE]-[Counter] [MANUFAC_ID]-[DEV_TYPE]-[Counter] [MANUFAC_ID]-[DEV_TYPE]-[Counter]FF Registration IT066000 (ITK version 5.2.0) IT066000 (ITK version 5.2.0) IT066000 (ITK version 5.2.0) Bus address 16 ... 247 16 ... 247 16 ... 247 local adjustment Keypad and display Keypad and display Keypad and display central adjustment Software (e. g.: Asset Vision) Software (e. g.: Asset Vision) Software (e. g.: Asset Vision) Backup LAS Yes Yes Yes Resource Block (RB) 1 RB (Enhanced) Transducer Block (TB)

1 TB (Enhanced): Pressure with Calibration, 1 TB (Customized): Advanced Diagnostic with PILD algorithm (Plugged Impulse Line Detection), 1 TB (Customized): Display

Function Block (FB)

AI and PID (Enhanced): 2 AI: Out of Differential, Absolute, Gauge or Static Pressure, Level, Flow or Sensor Temperature and Digital Alarm Signal, 1 PID: Controller Block. All other FB (Standard): 1 AR: Arithmetic Block, 1 IS: Input Selector, 1 CS: Control Selector, 1 SC: Signal Characterization, 1 IT: Integrator / Totalizer

FB Execution time PID = 40 ms, AI / AR / IS / CS / SC / IT = 25 ms Device configuration central adjustment EDD EDD EDD local adjustment Keypad and display Keypad and display Keypad and display Asset Monitor Yes (for ABB Tools) Yes (for ABB Tools) Yes (for ABB Tools) Us min 9.0 V DC 9.0 V DC 9.0 V DC Basic current1) 15.0 mA 15.0 mA 15.0 mA Δ Error current1) 5.0 mA 5.0 mA 5.0 mA Start current after 10 ms = Basic current = Basic current = Basic current External supply – – –

1) Max. permanent current = basic current + Δ error current

Page 9: Devices overview FOUNDATION Fieldbus-H1 · 2018-05-09 · Devices overview FOUNDATION Fieldbus-H1 10/63-0.56-EN 2 Temperature Transmitter Temperature Transmitter Diagnosis & maintenance

Devices overview FOUNDATION Fieldbus-H1 10/63-0.56-EN

9

P and L Transmitter

Diagnosis & maintenance data to increase the plant

availability

= Maintenance req.

= Out of specification

= Check function

= Failure

= No message

260

0T(2

66xx

)

Generic fieldbus diagnosis

(see page 17)

- plus - Advanced diagnosis

Device functionality

Pressure Sensor - Failed •

Temperature Sensor - Failed •

Static Pressure Sensor - Failed •

Wrong or Missing primary sensor signals •

Sensor memory Fail •

Sensor memory Burn Failure •

Electronics memory Fail •

Electronics memory Burn Failure •

Sensor and Electronics incompatible •

Sensor and Electronics interface error •

Sensor or Electronics Replacement failures •

Installation and Process

Sensor Overpressure •

Pressure out of Sensor Limits •

Static Pressure out of Sensor Limits •

Sensor temperature out of operating limits •

Static Pressure Over than installation enviromental limits •

Pressure out of Range •

Simulation Active •

Line H Plugged •

Line L Plugged •

Lines H and L Plugged •

One undetected Line Plugged •

New PILD training required •

Page 10: Devices overview FOUNDATION Fieldbus-H1 · 2018-05-09 · Devices overview FOUNDATION Fieldbus-H1 10/63-0.56-EN 2 Temperature Transmitter Temperature Transmitter Diagnosis & maintenance

Devices overview FOUNDATION Fieldbus-H1 10/63-0.56-EN

10

Flowmeters

M00590 M00596 M00592

FSM4000 FXE4000 FV4000, FS4000

Data sheet D184S073U02 D184S075U02, D184S071U02 D184S035U02 D184B093U32 D184B093U18 D184B093U24 Internet www.abb.com/flow www.abb.com/flow www.abb.com/flow Application

Electromagnetic Flowmeter Specially designed for pulp & paper and food & beverage industry, measure pulp stocks flows, fast changing process, two phase liquids, mining slurries and pulsating flows Accuracy: ≤ ± 0.5 % of rate Range: DN 3 ... 1000 (flanged) DN 1 ... 100 (variabel / wafer / flange)

Electromagnetic Flowmeter Affordable standard instrument in flanged and adapter-flanged versions. Option: Stainless steel with variable process connections Accuracy: ≤ ± 0.5 % of rate Range: DN 3 ... 1000 (flanged) DN 3 ... 100 (variabel / wafer / flange)

Vortex and Swirl Flowmeter. For vapor, gas and liquids Vortex: ≤ ± 1 % of rate for gases ≤ ± 0.75 % of rate for liquids Swirl: ≤ ± 0.5 % of rate Temperature of measuring medium: Vortex: -55 ... 280 °C / 400 °C Swirl: -55 ... 280 °C Range: Vortex: DN 15 ... DN 300 Swirl: DN 15 ... DN 400

Ambient temperature -25 ... 60 °C -25 ... 60 °C -30 ... 70 °C Type of protection IP 67 (IP 68) IP 67 (IP 68) IP 67 Explosion protection

– Model DE47: II 2G EEx emd [ia/ib] IIC T6 Model DE48: II 2G EEx ed [ia] IIC T6

II 2G EEx ia IIC T4

Approvals 3A, FDA, EHEDG ATEX 1173X, 3A, EHEDG, CE ATEX 1771, CE FISCO approval – Yes Yes For FNICO usable – Yes Yes Overvoltage protection H1 Via external module – – Physics MBP(-IS) (IEC 61158-2) MBP(-IS) (IEC 61158-2) MBP(-IS) (IEC 61158-2) Baud Rate 31.25 kBit/s fix 31.25 kBit/s fix 31.25 kBit/s fix Device ID 000320-0017-xxxxxxxxx 000320-0016-xxxxxxxxx 000320-0015-xxxxxxxxx [MANUFAC_ID]-[DEV_TYPE]-[Counter] [MANUFAC_ID]-[DEV_TYPE]-[Counter] [MANUFAC_ID]-[DEV_TYPE]-[Counter]FF Registration IT027200 (ITK version 4.6) IT019500 (ITK version 4.6) IT017300 (ITK version 4.61) Bus address 16 ... 247 16 ... 247 16 ... 247 local adjustment – – – central adjustment Software (e. g.: Asset Vision) Software (e. g.: Asset Vision) Software (e. g.: Asset Vision) Backup LAS Yes Yes Yes Resource Block (RB) 1 RB (Enhanced) 1 RB (Standard) 1 RB (Standard) Transducer Block (TB)

1 TB (Customized): Flow 1 TB (Customized): Flow 1 TB (Customized): Flow

Function Block (FB)

3 AI (Standard): Volume Flow, Totalizer 1, Totalizer 2 1 PID (Enhanced): Controller Block

3 AI (Standard): Volume Flow, Totalizer 1, Totalizer 2 1 PID (Standard): Controller Block

2 AI (Standard): Volume Flow, Totalizer, Temperature

FB Execution time AI = 25 ms, PID = 50 ms AI = 50 ms, PID = 100 ms AI = 50 ms Device configuration central adjustment EDD EDD EDD local adjustment Keypad, DIP switches, display Keypad, DIP switches, display Keypad, DIP switches, display Asset Monitor Yes (for ABB Tools) Yes (for ABB Tools) Yes (for ABB Tools) Us min 9.0 V DC 9.0 V DC 9.0 V DC Basic current1) 10.0 mA 13.0 mA 10.0 mA Δ Error current1) 3.0 mA 4.0 mA 3.0 mA Start current after 10 ms = Basic current = Basic current = Basic current External supply Yes (230 V AC, 24 V DC, < 45 VA) Yes (230 V AC, 24 V DC, < 10 VA) –

1) Max. permanent current = basic current + Δ error current

Page 11: Devices overview FOUNDATION Fieldbus-H1 · 2018-05-09 · Devices overview FOUNDATION Fieldbus-H1 10/63-0.56-EN 2 Temperature Transmitter Temperature Transmitter Diagnosis & maintenance

Devices overview FOUNDATION Fieldbus-H1 10/63-0.56-EN

11

Flowmeters Flowmeters

M00597

Diagnosis & maintenance data to increase the plant

availability

= Maintenance req.

= Out of specification

= Check function

= Failure

= No message

FS

M40

00

FX

E40

00

FV

4000

, F

S40

00

FC

M20

00

FCM2000 CoriolisMaster Generic fieldbus diagnosis

Data sheet D184S068U02 (see page 17) D184B093U34 Internet www.abb.com/flow

- plus - Advanced diagnosis

Application

Device functionality

Electronic failure • • • •

Flow Sensor - Failed • • • •

Database error • • •

Coriolis Mass Flowmeter Multivariable Measurement: - Mass flow (up to 0,1 %) - Density (5 g/l or 1 g/l) - Temperature (-50 ... 200 °C) Special applications: - Concentration measurement Size range: DN 1.5 ... DN 150 Variable Ex concept

Steam calculation error •

Ambient temperature -40 ... 60 °C Type of protection IP 67

Temperature measurement - Failed

• •

Explosion protection Zone 0 ... 2 or Div 1 ... 2

Device configuration

Approvals IECEx, ATEX, cFMus, NEPSI, GOSTFISCO approval Yes

Flow Totalizer Measurement Limits: - Failed (#1, 2, 3) • • •

For FNICO usable Yes Overvoltage protection H1 Via external module

Flow Totalizer - Failed • • •

Physics MBP(-IS) (IEC 61158-2)

Test mode - Active • • •

Baud Rate 31.25 kBit/s fix Device ID 000320-0018-xxxxxxxxx

Flow value simulation - Active • • •

[MANUFAC_ID]-[DEV_TYPE]-[Counter]FF Registration IT045500 (ITK version 5.0)

Installation and Process

Bus address 16 ... 247 local adjustment –

Measurement Limits - Failed (#1, 2) • • • •

central adjustment Software (e. g.: Asset Vision) Backup LAS Yes Resource Block (RB) 1 RB (Enhanced)

Transducer Block (TB)

1 TB (Customized): Flow

Function Block (FB)

6 AI: Mass, Volume flow, Density, Temperature, Volume-, Mass totalizer 1 PID (Enhanced): Controller Block

FB Execution time AI = 25 ms, PID = 50 ms Device configuration central adjustment EDD local adjustment Keypad, DIP switches, display Asset Monitor Yes (for ABB Tools) Us min 9.0 V DC Basic current1) 14.0 mA Δ Error current1) 12.0 mA Start current after 10 ms = Basic current External supply Yes (230 V AC, 24 V AC / DC,< 25 VA)

1) Max. permanent current = basic current + Δ error current

Page 12: Devices overview FOUNDATION Fieldbus-H1 · 2018-05-09 · Devices overview FOUNDATION Fieldbus-H1 10/63-0.56-EN 2 Temperature Transmitter Temperature Transmitter Diagnosis & maintenance

Devices overview FOUNDATION Fieldbus-H1 10/63-0.56-EN

12

Analyzer

M00580 M00581 M00582

TB82EC TB82TC TB82TE

Data sheet D-NCA-TB82 D-NCA-TB82 D-NCA-TB82 Internet www.abb.com/analytical-instruments www.abb.com/analytical-instruments www.abb.com/analytical-instruments Application

Process Analytics - Solution Conductivity Process Display Range: Sensor Group A: 0.0 µS/cm ... 1999 mS/cm B: 0.00 µS/cm ... 1999 µS/cm C: 0.000 µS/cm ... 199.9 µS/cm Concentration: 0.000 ... 1999 Digits (EU configurable) Temperature: -20 ... 300 °C

Process Analytics - Solution Conductivity Process Display Range: 1 µS/cm ... 1999 mS/cm Concentration: 0.000 ... 1999 Digits (EU configurable) Temperature: -20 ... 300 °C

Process Analytics - Solution Conductivity Process Display Range: Sensor Cell Constant 0.01: 0.001 µS/cm … 199.9 µS/cm 0.10: 0.01 µS/cm ... 1999 µS/cm 1.00: 0.1 µS/cm ... 19.99 mS/cm Concentration: 0.000 ... 1999 Digits (EU configurable) Temperature: -20 ... 300 °C

Ambient temperature -20 ... 60 °C -20 ... 60 °C -20 ... 60 °C Type of protection IP 65, NEMA 4X IP 65, NEMA 4X IP 65, NEMA 4X Explosion protection

EEx ia IIC T4, Class I Division 1 up to Class II Division 2, Class III

EEx ia IIC T4, Class I Division 1 up to Class II Division 2, Class III

EEx ia IIC T4, Class I Division 1 up to Class II Division 2, Class III

Approvals ATEX, FM, CSA, CE ATEX, FM, CSA, CE ATEX, FM, CSA, CE FISCO approval – – – For FNICO usable Yes Yes Yes Overvoltage protection H1 Yes (integrated) Yes (integrated) Yes (integrated) Physics MBP(-IS) (IEC 61158-2) MBP(-IS) (IEC 61158-2) MBP(-IS) (IEC 61158-2) Baud Rate 31.25 kBit/s fix 31.25 kBit/s fix 31.25 kBit/s fix Device ID 000320-0051-xxxxxxxxx 000320-0053-xxxxxxxxx 000320-0052-xxxxxxxxx [MANUFAC_ID]-[DEV_TYPE]-[Counter] [MANUFAC_ID]-[DEV_TYPE]-[Counter] [MANUFAC_ID]-[DEV_TYPE]-[Counter]FF Registration IT016200 (ITK version 4.01) IT019300 (ITK version 4.51) IT018100 (ITK version 4.01) Bus address 16 ... 247 16 ... 247 16 ... 247 local adjustment – – – central adjustment Software (e. g.: Asset Vision) Software (e. g.: Asset Vision) Software (e. g.: Asset Vision) Backup LAS – – – Resource Block (RB) 1 RB (Standard) 1 RB (Standard) 1 RB (Standard) Transducer Block (TB)

1 TB (Customized): with Calibration and Function Generator, used for the secondary variable (solute concentration)

1 TB (Customized): with Calibration and Function Generator, used for the secondary variable (solute concentration)

1 TB (Customized): with Calibration and Function Generator, used for the secondary variable (solute concentration)

Function Block (FB)

2 AI (Standard): AI1 / AI2 - Conductivity, Concentration, Temperature or uncompensated Conductivity

2 AI (Standard): AI1 / AI2 - Conductivity, Concentration, Temperature or uncompensated Conductivity

2 AI (Standard): AI1 / AI2 - Conductivity, Concentration, Temperature or uncompensated Conductivity

FB Execution time AI = 150 ms AI = 100 ms AI = 100 ms Device configuration central adjustment EDD or module for FF Device EDD or module for FF Device EDD or module for FF Device local adjustment Keypad and display Keypad and display Keypad and display Asset Monitor Yes (for ABB Tools) Yes (for ABB Tools) Yes (for ABB Tools) Us min 9.0 V DC 9.0 V DC 9.0 V DC Basic current1) 15.0 mA 15.0 mA 15.0 mA Δ Error current1) 10.0 mA 10.0 mA 10.0 mA Start current after 10 ms = Basic current = Basic current = Basic current External supply – – –

1) Max. permanent current = basic current + Δ error current

Page 13: Devices overview FOUNDATION Fieldbus-H1 · 2018-05-09 · Devices overview FOUNDATION Fieldbus-H1 10/63-0.56-EN 2 Temperature Transmitter Temperature Transmitter Diagnosis & maintenance

Devices overview FOUNDATION Fieldbus-H1 10/63-0.56-EN

13

Analyzer Analyzer

M00583

Diagnosis & maintenance data to increase the plant

availability

= Maintenance req.

= Out of specification

= Check function

= Failure

= No message

TB

82E

C (

pend

ing)

TB

82T

C (

pen

ding

)

TB

82T

E (

pend

ing)

TB

82P

H

TB82PH Generic fieldbus diagnosis

Data sheet D-NCA-TB82 (see page 17) Internet www.abb.com/analytical-instruments

- plus - Advanced diagnosis

Application

Device functionality

Electronics Failure • • • •

Incorrect Input PCB • • • •

Process calibration offset warning

Process Analytics - pH/ORP/pION Process Display Range: pH: -2 ... 16 pH ORP: -1999 ... 1999 mV pION: -1999 ... 1999 mV Temperature: -20 ... 300 °C

Process calibration slope warning

Ambient temperature -20 ... 60 °C Type of protection IP 65, NEMA 4X

Calibration Mode •

Explosion protection

EEx ia IIC T4, Class I Division 1 up to Class II Division 2, Class III Device configuration

Approvals ATEX, FM, CSA, CE FISCO approval –

Reference Impedance Limit

For FNICO usable Yes Overvoltage protection H1 Yes (integrated)

Installation and Process

Physics MBP(-IS) (IEC 61158-2)

Low pH Measuring Electrode Impedance

Baud Rate 31.25 kBit/s fix Device ID 000320-0050-xxxxxxxxx

High Reference Electrode Impedance

[MANUFAC_ID]-[DEV_TYPE]-[Counter]FF Registration IT016100 (ITK version 5.0.1)

Ground Loops Present or Shorted Sensor Cable • •

Bus address 16 ... 247 local adjustment –

Open Sensor Cable or Sensor Out of Solution

central adjustment Software (e. g.: Asset Vision) Backup LAS –

Temperature out of limits • • • •

Resource Block (RB) 1 RB (Standard) Transducer Block (TB)

PV out of limits • • • •

1 TB (Customized): with Calibration and Function Generator

Temperature sensor failure • • • •

Function Block (FB)

Dirty Sensor Alarm •

2 AI (Standard): AI1 / AI2 - PV (pH, ORP or pION), Temperature, Sensor input, Reference impedance or Function Generator value Polarized Sensor

FB Execution time AI = 50 ms Device configuration central adjustment EDD or module for FF Device local adjustment Keypad and display Asset Monitor Yes (for ABB Tools) Us min 9.0 V DC Basic current1) 15.0 mA Δ Error current1) 10.0 mA Start current after 10 ms = Basic current External supply –

1) Max. permanent current = basic current + Δ error current

Page 14: Devices overview FOUNDATION Fieldbus-H1 · 2018-05-09 · Devices overview FOUNDATION Fieldbus-H1 10/63-0.56-EN 2 Temperature Transmitter Temperature Transmitter Diagnosis & maintenance

Devices overview FOUNDATION Fieldbus-H1 10/63-0.56-EN

14

Positioner Positioner

M00593 M00594

Diagnosis & maintenance data to increase the plant

availability

= Maintenance req.

= Out of specification

= Check function

= Failure

= No message

TZ

IDC

-120

, T

ZID

C-2

20

TZIDC-120 TZIDC-220 Generic fieldbus diagnosis

Data sheet 10/18-0.24-EN 10/18-0.34-EN (see page 17) Internet www.abb.com/instrumentation www.abb.com/instrumentation

- plus - Advanced diagnosis

Application

Device functionality

Device error •

Position sensor malfunction •

Installation and Process

Intelligent Positioner Precise control of positioning with pneumatic linear and rotary actuators. Interference due to shock and vibration < 1 % up to 10 g. Control pressure: 0 ... 6 bar Housing material: Aluminum

Intelligent Positioner Precise control of positioning with pneumatic linear and rotary actuators. Interference due to shock and vibration < 1 % up to 10 g. Control pressure: 0 ... 6 bar Housing material: Aluminum

Working range adjustment required •

Ambient temperature -40 ... 85 °C -40 ... 85 °C Type of protection IP 65, NEMA 4X IP 65, NEMA 4X

Position sensor out of range •

Explosion protection

II 2G EEx ia IIC T6 II 3G EEx n A II T6

II 2G EEx d IIC T6 II 2G EEx ia IIC T6 Auto adjustment failed •

Approvals ATEX, FM, CSA, IECEx, CE, GOST ATEX, FM, CSA, IECEx, CE, GOST FISCO approval Yes Yes

Position controller not ready for operation (inactive) •

For FNICO usable Yes Yes Overvoltage protection H1 Via external module Via external module

Position out of working range •

Physics MBP(-IS) (IEC 61158-2) MBP(-IS) (IEC 61158-2)

Mechanical end position exceeded •

Baud Rate 31.25 kBit/s fix 31.25 kBit/s fix Device ID 000320-0028-xxxxxxxxx 000320-0028-xxxxxxxxx

Positioning monitoring time exceeded •

[MANUFAC_ID]-[DEV_TYPE]-[Counter] [MANUFAC_ID]-[DEV_TYPE]-[Counter]FF Registration IT023200 (ITK version 4.51) IT023200 (ITK version 4.51)

Temperature limit exceeded •

Bus address 16 ... 247 16 ... 247 local adjustment – –

Cumulated time: Temperature limit exceeded •

central adjustment Software (e. g.: Asset Vision) Software (e. g.: Asset Vision) Backup LAS Yes Yes

Movement counter limit exceeded •

Resource Block (RB) 1 RB (Enhanced) 1 RB (Enhanced) Transducer Block (TB)

Travel counter limit exceeded •

1 TB (Customized): Configuration, Parameterization, Diagnosis, Monitoring, Signaling

1 TB (Customized): Configuration, Parameterization, Diagnosis, Monitoring, Signaling Switch point 1 exceeded •

Function Block (FB)

Switch point 2 exceeded •

1 AO (Standard): Setpoint value, Position value, RCAS_IN, RCAS_OUT 1 PID (Enhanced): Controller Block

1 AO (Standard): Setpoint value, Position value, RCAS_IN, RCAS_OUT 1 PID (Enhanced): Controller Block

Simulation active •

FB Execution time AO = 40 ms, PID = 50 ms AO = 40 ms, PID = 50 ms Device configuration

Local operation active •

central adjustment EDD EDD local adjustment Push Buttons and display Push Buttons and display Asset Monitor Yes (for ABB Tools) Yes (for ABB Tools) Us min 9.0 V DC 9.0 V DC Basic current1) 11.5 mA 11.5 mA Δ Error current1) 3.5 mA 3.5 mA Start current after 10 ms = Basic current = Basic current External supply – –

1) Max. permanent current = basic current + Δ error current

Page 15: Devices overview FOUNDATION Fieldbus-H1 · 2018-05-09 · Devices overview FOUNDATION Fieldbus-H1 10/63-0.56-EN 2 Temperature Transmitter Temperature Transmitter Diagnosis & maintenance

Devices overview FOUNDATION Fieldbus-H1 10/63-0.56-EN

15

Linking Device

M00603

LD 800HSE

Data sheet 3BDD011675Rxx01 Internet www.abb.com/fieldbus Application

Redundant Linking Device for High Speed Ethernet (HSE) and FF-H1. - HSE profile class 42c - Configuration of H1 devices via

HSE - Republishing of process data and

distribution of alarms - Link Master capability - 4 H1 interfaces - HSE interface:

10BaseT/100BaseTX (autosensing)

Ambient temperature 5 ... 55 °C Type of protection IP 20 Explosion protection – Approvals CE, cUL FISCO approval – For FNICO usable – Overvoltage protection H1 – Physics IEEE803.2/IEC 61158-2 Baud Rate 100 Mbit/s (HSE) <-> 31.25 kBit/s (H1) Device ID 000320-0067-xxxxxxxxx [MANUFAC_ID]-[DEV_TYPE]-[Counter] FF Registration CT0054FF, PT-081 Bus address H1: 16 … 19, HSE: any IP address local adjustment – central adjustment Software (e. g.: FBB FF, CBF) Backup LAS Yes Resource Block (RB) – Transducer Block (TB)

Function Block (FB)

FB Execution time – Device configuration central adjustment

Software (e. g.: Fieldbus Builder FF, Control Builder F)

local adjustment – Asset Monitor Yes (for ABB Tools) Us min – U and I Output No Non-Hazardous area (External H1 power supply required) U and I Output No Intrinsic safety (IS) (External H1 power supply required) External supply Yes (24 V DC (+- 20 %), typ. 200 mA)

Page 16: Devices overview FOUNDATION Fieldbus-H1 · 2018-05-09 · Devices overview FOUNDATION Fieldbus-H1 10/63-0.56-EN 2 Temperature Transmitter Temperature Transmitter Diagnosis & maintenance

Devices overview FOUNDATION Fieldbus-H1 10/63-0.56-EN

16

Network components , Accessories for MBP(-IS)

Junctions Con-nectors

Cables Overvoltage protection

NP

J130

-NO

NP

J460

-NO

NF

J12

0-N

E

NF

J42

0-N

E

NP

J130

-EX

NP

J460

-EX

NP

Z10

0-E

X

NG

J100

-NE

Fam

ilie

NF

E10

0-N

E

NF

E30

0-N

E

NF

C08

0-N

O

NF

C15

0-N

O

NF

C25

0-N

O

NF

C08

0-E

X

NF

C15

0-E

X

NF

C25

0-E

X

NG

V21

0-N

O

NG

V21

1-N

O

NG

V21

0-E

X

NG

V21

1-E

X

NG

V22

0-N

O

NG

V22

0-E

X

Data sheet 10/63-6.60-EN 10/63-6.67-EN 10/63-6.15-EN Installation suggestion 10/63-0.50-EN Internet www.abb.com/fieldbus For hazardous areas • • • • • • For Non-Haz. areas • • • • • IP 20 • IP 66 • • • • • • • Bus termination incl. • • • Bus termination ext. (via NPZ100-EX) • • • • Bus termination for hazardous areas • One-way (T) junction • • • Four-way junction • • • X-way junction • Output - cable bushing • • • • Output - socket 7/8“ • • Hazardous areas and Non-Haz. areas • • Plug 7/8“ • Socket 7/8“ • Metal housing • • For hazardous areas • • • 2 x 0.88 mm2 (AWG18/7) • • 2 x 1.30 mm2 (AWG16/7) • • 2 x 2.10 mm2 (AWG14/7) • • For hazardous areas • •Top-hat rail mounting, IP 20 • • Cable gland mounting, M20 x 1.5, IP 67 • •

Page 17: Devices overview FOUNDATION Fieldbus-H1 · 2018-05-09 · Devices overview FOUNDATION Fieldbus-H1 10/63-0.56-EN 2 Temperature Transmitter Temperature Transmitter Diagnosis & maintenance

Devices overview FOUNDATION Fieldbus-H1 10/63-0.56-EN

17

For all

Diagnosis & maintenance data to increase the plant

availability

= Maintenance req.

= Out of specification

= Check function

= Failure

= No message A

ll F

ield

bu

s d

evi

ces

Generic fieldbus diagnosis

Device functionality

Device Out of Service or Initializing •

Block(s) Out of Service or Powering-up •

Input or output failure •

Data or memory error •

Device needs maintenance - soon, - now •

Fault State Set •

Readback Check - Failed •

Unspecified error •

Device configuration

Block configuration error or link configuration error •

Data Sheet Devices overview

FOUNDATION Fieldbus-H1

Page 18: Devices overview FOUNDATION Fieldbus-H1 · 2018-05-09 · Devices overview FOUNDATION Fieldbus-H1 10/63-0.56-EN 2 Temperature Transmitter Temperature Transmitter Diagnosis & maintenance
Page 19: Devices overview FOUNDATION Fieldbus-H1 · 2018-05-09 · Devices overview FOUNDATION Fieldbus-H1 10/63-0.56-EN 2 Temperature Transmitter Temperature Transmitter Diagnosis & maintenance
Page 20: Devices overview FOUNDATION Fieldbus-H1 · 2018-05-09 · Devices overview FOUNDATION Fieldbus-H1 10/63-0.56-EN 2 Temperature Transmitter Temperature Transmitter Diagnosis & maintenance

Contact us

10/6

3-0.

56-E

NR

ev.C

02.2

011Note

We reserve the right to make technical changes or modify the contents of this document without prior notice. With regard to purchase orders, the agreed particulars shall prevail. ABB does not accept any responsibility whatsoever for potential errors or possible lack of information in this document. We reserve all rights in this document and in the subject matter and illustrations contained therein. Any reproduction, disclosure to third parties or utilization of its contents - in whole or in parts – is forbidden without prior written consent of ABB. Copyright© 2011 ABB All rights reserved

ABB Automation Products GmbH Borsigstr. 2 63755 Alzenau Germany Phone: +49 551 905-534 Fax: +49 551 905-555 www.abb.com

3KXN056000R1001