W A Y N E S T A T E U N I V E R S I T Y
V I C I N I T Y P L A N
SCALE: NTS
E L E C T R I C A LA R C H I T E C T U R A L M E C H A N I C A L
RANDS HOUSE RENOVATION
L O C A T I O N P L A N
SCALE: NTS
T-1
MH000 VENTILATION COVER SHEETMHD101 FIRST FLOOR DEMOLITION - VENTILATIONMHD102 SECOND FLOOR DEMOLITION - VENTILATIONMH101 FIRST FLOOR PLAN - VENTILATIONMH102 SECOND FLOOR PLAN VENTILATIONMH300 VENTILATION DETAILSP000 PLUMBING COVER SHEETP101 FIRST FLOOR - PLUMBINGP102 SECOND FLOOR PLAN - PLUMBINGP300 ENLARGED PLANSP500 PLUMBING SCHEDULES
E000 ELECTRICAL COVER SHEETED101 FIRST FLOOR DEMOLITION- ELECTRICALED102 SECOND FLOOR DEMOLITION - ELECTRICALEL101 FIRST FLOOR PLAN - LIGHTINGEL102 SECOND FLOOR PLAN - LIGHTINGEP100 BASEMENT FLOOR PLAN - POWEREP101 FIST FLOOR PLAN - POWEREP102 SECOND FLOOR PLAN - POWEREP-300 POWER DETAILSES100 BASEMENT FLOOR PLAN - SYSTEMSES101 FIRST FLOOR PLAN - SYSTEMSES102 SECOND FLOOR PLAN - SYSTEMSES-300 SYSTEMS DETAILST000 TECHNOLOGY COVER SHEETTD101 FIRST FLOOR DEMOLITION - TECHNOLOGYTD102 SECOND FLOOR DEMOLITION - TECHNOLOGYT-101 FIRST FLOOR PLAN - TECHNOLOGYT102 SECOND FLOOR PLAN - TECHNOLOGYT300 TECHNOLOGY DETAILS, RISERS, AND SCHEDULES
DETROIT, MI 48202
2215 Cole Street
BIRMINGHAM, MICHIGAN 48009
P (248)646-5765 F (248)646-5813
No code variance requests are anticipated.
Contractor to coordinate WORK SCOPE and constructionactivities with WSU construction Project Manager :
W O R K S C O P E
RENOVATE PORTION OF RANDS HOUSE INTO NEW OFFICES, CLASSROOMS AND LABS, CREATENEW ADA TOILET ROOMS.
RANDS HOUSE RENOVATION
A P P L I C A B L E C O D E S
BUILDING CODE:
P R O J E C T A R E A S U M M A R Y
MECHANICAL CODE:
PLUMBING CODE:
FIRE SAFETY CODE:
(FOR CONTRACT DOCUMENTS)
ELECTRICAL CODE:
NFPA 101 LIFE SAFETY CODE
NFPA 13/ 2007 STANDARD FOR THEINSTALLATION OF SPRINKLERSYSTEMS
MICHIGAN REHABILITATION CODE FOR EXISTING BUILDING/ 2015
STATE OF MICHIGAN MECHANICAL CODE/ 2015
STATE OF MICHIGAN ELECTRICAL CODE /2014
MICHIGAN PLUMBING CODE/ 2015
GROSS AREA - 13,000 GSF ±
USE GROUP:
CONSTRUCTION TYPE:
PUBLIC HEALTH CODE:
BARRIER FREE CODES:
MDCIS MINIMUM DESIGN STANDARDS FORCONSTRUCTION AND EQUIPMENT FORHEALTHCARE FACILITIES IN MICHIGAN
UFAS, AMERICANS WITH DISABILITIES ACT ACCESSIBILITYGUIDELINES, MICHIGAN BARRIER FREE - 2010
BUSINESS - B
1A NON-COMBUSTIBLE
Title Sheet, Drawing Index andLocation & Vicinity Maps
T-1 TITLE SHEET, DRAWING INDEX & LOCATION & VICINITY MAPSA-002 ABBREVIATIONS, DRAWING SYMBOLS STANDARDS& STANDARD MOUNTING HEIGHTSA-20 ROOM FINISH SCHEDULEA-30 DOOR SCHEDULE & WALL TYPESAD-101 RANDS HOUSE 1AR FLOOR PLAN - DEMOLITION WORKAD-102 RANDS HOUSE 2ND FLOOR PLAN- DEMOLITION WORKAD-103 RANDS HOUSE 1ST FLOOR REFLECTED CEILING PLAN - DEMOLITION WORKAD-104 RANDS HOUSE 2ND FLOOR REFLECTED CEILING PLAN - DEMOLITION WORKA-201 RANDS HOUSE 2ND FLOOR PLAN- NEW WORKA-202 RANDS HOUSE 2ND FLOOR PLAN- NEW WORKA-301 RANDS HOUSE 1ST FLOOR REFLECTED CEILING PLAN - NEW WORKA-302 RANDS HOUSE 2ND FLOOR REFLECTED CEILING PLAN- NEW WORK
WAYNE STATE UNIVERSITY
PROJECT SITE :
RANDS HOUSE
FOR
BID
S
project number:
sheet title:
sheet number:
approved
project:
coordination checked
location
drawn
checked
designed
issue: date:
key plan:
Rands House - RackhamRelocation
Nov. 13, 2018Owner Review 60% CD's
NM Project Number - 18113.0
WAYNE STATEUNIVERSITY
Facilities Planning and Management
5454 Cass Avenue
Detroit, MI 48202
Rands House
JK
JK
JK
DB
AG
WSU : 00
consultants:
Nov. 27, 2018Owner Review90% CD's
Dec. 04, 2018Review 100% CD's
Dec. 11, 2018For Bids
26200 Town center Drive
NOVI, MICHIGAN 48375
P (248)313-6902 F (248)344-1650
26200 Town center Drive
NOVI, MICHIGAN 48375
P (248)313-6902 F (248)344-1650
ALTERNATES
· DEDUCT NEW CARPET THOUGHOUT THE FIRST FLOOR
FO
R U
P
TO
4
0 L
BS
FO
R M
OR
E
TH
AN
4
0 L
BS
42" M
AX
60" M
AX
48" M
AX
2'-10
" MAX
MOUNTING HEIGHT FORDISPENSERS IS TO TOP OFDISPENSER OR HIGHESTOPERABLE PART
TO
WE
L D
IS
PE
NS
ER
S
& D
IS
PO
SE
RS
SO
AP
D
IS
PE
NS
ER
/ H
AN
D
SA
NIT
IZ
ER
TD
SD
4" MAX
48" T
YPIC
AL
1'-3"
MIN
MOUNTING HEIGHT FOR MIRROR:
BOTTOM EDGE OF MIRROR
PO
WE
R/D
AT
A/
PH
ON
E R
EC
EP
TA
CL
ES
LIG
HT
S
WIT
CH
ES
MIN 1 1/2" BETWEENTOP OF TP HOLDERAND BOT. OF GRABBAR
3'-0"
MAX
34"
HD
HA
ND
D
RY
ER
SND
SA
NIT
AR
Y N
AP
KIN
DIS
PE
NS
ER
FIR
E A
LA
RM
P
UL
L
IN
TE
RC
OM
HV
AC
C
ON
TR
OL
MOUNTINGHEIGHT IS TO TOPOF HIGHESTOPERABLE PARTOR RECEPTACLE
3'-8"
MAX
1'-5"
MAX
1'-3" MIN
SHELF,
WHERE
SPECIFIED
44
" O
VE
R
CO
UN
TE
R O
R
OB
ST
RU
CT
IO
N
WH
EN
OP
EN
TO
C
AB
IN
ET
HA
ND
LE
FILMILLUMINATOR
3'-6"
U.N
.O.
4'-6"
7'-2"
X"
4'-6"
4'-0"
2'-0"
5'-0"
4128
"
5'-0"
2'-0"
6'-6"
1'-6"
6'-0"
MONITOR &BRACKET
REMOTE MONITOR& BRACKET(@ CORRIDORLOCATIONS)
TVBRACKET
OTOSCOPE/SPHYGMOM-ANOMETER
SHARPSCONTAINER
GLOVE &APRON RACK
(S
IN
GL
E
BR
AC
KE
T)
(S
IN
GL
E
BR
AC
KE
T)
ADDITIONAL
BRACKET
SEGMENTS ADDED
AS REQUIRED
IV PUMP BAR(NON-FERROUS)
WALL-MOUNTEDWORKSTATION
FLIP DOWNWORKSTATION
SHOWER CURTAINROD, HOOKS, ANDCURTAIN
SHOWERNICHE
FOLDINGSHOWERSEAT
MOP & BROOMHOLDER - NOSHELF
MARKER BOARD/TACK BOARD
CHART ORMAGAZINERACK
HAIRDRYER
BED PANHOLDER
COATBRACKET& SHELF
SURFACEMOUNTEDPROJECTIONSCREEN
36"X48"
U.N.O.
44
" @
A
DA
48
" A
T
AC
CE
SS
IB
LE
BARRIER FREEEWC & DRINKINGFOUNTAIN
SINKS &LAVATORIES
URINALACCESSIBLE
TOILET, GRAB BAR &TOILET PAPERHOLDER
FOLD DOWNBABY CHANGINGTABLE
WALL MOUNTEDSEMI-RECESSEDFIREEXTINGUISHERCABINET
WALL MOUNTEDFIREEXTINGUISHER
MIRRORS
3'-8" 5'-
0"
3'-6"
48
" M
AX
A
T
AC
CE
SS
IB
LE
TOWEL BAR HOOK
GLOVEDISPENSER
SPECIMENPASS-THRU
6'-2"
3'-4"
3'-6"
3'-6"
3'-8"
MAX
3'-6"
MAX
3'-8"
MAX
4'-10
"
4'-0"
MAX
TO
B
OT
TO
M
OF
T
V
6" MAX9" MIN
9" M
IN
2'-3"
MIN
960"
MOUNTING
HEIGHT IS TO
SPOUT OUTLET
HEIGHT
8"
1 1/2
"
840"
1'-0" 3'-6"
1584
"
1920
"86
4"
6"3'-5"
1'-6"
3'-0"
1'-0"
INTERIOR ELEVATIONS LEGEND
6"
3'-9"
NOTE:REFER TO ARCH PLANS FOR ACCESSORIES AND THEIRLOCATIONS. THIS SHEET IS FOR STANDARD MOUNTING HEIGHTSONLY UNLESS NOTED ELSEWHERE IN THIS DRAWING SET
ABHR
MA
X.
FLOOR
ABHR
LEGEND
1. NO PROJECTION CAN EXTEND OUT MORE THAN 4" INTO
CORRIDOR OR WALKWAY.
2. ALCOHOL BASED HAND RUB SANITIZERS CANNOT BE LOCATED
ABOVE A POTENTIAL IGNITION SOURCE
3. ABHR MUST BE OFFSET A MINIMUM OF 1" HORIZONTALLY FROM
ANY LIGHT SWITCH, ELECTRICAL OR DATA RECEPTACLE,
THERMOSTAT OR OTHER POTENTIAL IGNITION SOURCE.
4. ABHR SANITIZERS CANNOT BE INSTALLED IN A CORRIDOR LESS
THAN 6' WIDE
5. ABHR MUST BE AT LEAST 4' APART
6. ABHR CANNOT BE INSTALLED OVER CARPET IN NON-SPRINKLED
SPACES.
7. MAX. CAPACITY OF DISPENSERS IN CORRIDORS: 0.3 GALLONS
NOTES
ALCOHOL BASED HAND RUB SANITIZER DISPENSER
LIGHT SWITCH/RECEPTACLE OR OTHER POTENTIAL IGNITION SOURCE
44"1"
MIN.
1"MIN.
MA
X.
IF ABHR IS NEXTTO POTENTIALIGNITION SOURCE,IT MUST BEOFFSET 1"HORIZONTALLY.
ABHR CAN BEBELOWPOTENTIALIGNITION SOURCE,NO ISSUES.
ABHR CANNOT BEABOVE POTENTIALIGNITION SOURCE.
ABHR
ABHR
44"
ALCOHOL BASED HAND RUB SANITIZERSMOUNTING REQUIREMENTS
FLOOR
FLOOR
FLOOR
FLOOR
A-002
PLANS
EXISTING WALLS TO REMAIN
NEW WALLS
ACROVYN CORNER GUARD - FULL HEIGHT
END CAP - FULL HEIGHTACG
ECFIRE EXTINGUISHER CABINET -SEMI-RECESSED (ADA)
FEC
EXISTING WALLS TO BE REMOVED
NEW DOOR W/ DOOR NUMBER
EXISTING DOOR TO BE REMOVED
CUBICLE CURTAIN TRACK
2'x2' FLUORESCENT LIGHT FIXTURE
2'x4' FLUORESCENT LIGHT FIXTURE
NEW SUSPENDED ACOUSTICAL CEILING @ 8'-0" AFFU.N.O.
GYPSUM BOARD CEILING @ 7'-6" AFF U.N.O.
RECESSED DOWN LIGHT FIXTURE
TREATMENT ROOM LIGHT FIXTURE
EXIT LIGHT (CEILING MOUNTED)
SMOKE DETECTOR
FIRE SPRINKLER HEAD - NEW SPRINKLER HEADS ARESHOWN FOR COORDINATION PURPOSES ONLY. FINALSPRINKLER HEAD LOCATIONS SHALL BE DETERMINEDBY A CERTIFIED FIRE PROTECTION FIRM, ANDCOORDINATED WITH ARCHITECT & ENGINEERS.
FIRE ALARM - SEE ELECTRICAL DWG.
WIRELESS ANTENNA - SEE ELECTRICAL DWG.
SPEAKER
EXISTING DOOR TO REMAIN
RETURN GRILLE - SEE MECHANICAL DWG.
EXHAUST GRILLE - SEE MECHANICAL DWG.
SUPPLY GRILLE - SEE MECHANICAL DWG.
PLAN IDENTIFICATIONW/NORTH ARROW
SECTION LOCATION IDENTIFICATION
DETAIL LOCATION IDENTIFICATION ATENLARGED SCALE
ELEVATION LOCATION IDENTIFICATION
KEYNOTE IDENTIFICATIONDEMO / NEW / MISC
BULLETIN IDENTIFICATION W/CLOUD
ROOM NAME & NUMBER
1. DO NOT SCALE DRAWING REPRODUCTIONS.2. THIS DRAWING REPRESENTS TYPICALLY ENCOUNTERED
ITEMS. NOT ALL ITEMS SHOWN MAY OCCUR WITHIN THESCOPE OF THIS PROJECT. REFER TO COMPLETESPECIFICATIONS AND DRAWING DOCUMENTATION SET.
GRID BUBBLE
DOOR NUMBER TAG
CEILING HEIGHT TAGEXISTING / NEW
EXISTING SUSPENDED ACOUSTICAL CEILING TO BEREMOVED
ACOUSTICAL CEILING TILEACT
CEILING HEIGHTCH
CEILINGCLG
EXISTING(X)
EXPANSION JOINTEJ
GAUGEGA
HARDWAREHDWR
HOLLOW METALHM
HEIGHTHT
INTERIOR DESIGNID
LAVATORYLAV
MAXIMUMMAX
MANUFACTURERMFR
MINIMUMMIN
MASONRY OPENINGMO
PLASTIC LAMINATEPLAM
SQUARE FEETSF
SIMILARSIM
SPECIFICATIONSSPEC
UNLESS NOTED OTHERWISEUNO
WATER CLOSETWC
WITH
W/O WITHOUT
RO ROUGH OPENING
NTS NOT TO SCALE
CENTER LINECL
OH OVERHEAD
GYPSUM BOARDGB
TYPICALTYP
CONTROL JOINTCJ
VINYL WALL COVERINGVWC
STAINLESS STEELSSTL
GLASSGL
WALL PROTECTIONWP
JC JANITORS CLOSET
RB RESILIENT BASE
CERAMIC TILECT
PT PAINT
CONTRACTOR FURNISHED/ INSTALLEDCFI
CAPITAL EQUIPMENTCE
ABOVE FINISH FLOORAFF
WOODWD
CARPETCPT
VINYL COMPOSITION TILEVCT
LIGHTLT
LINEAL FEETLF
EQUALEQ
BUREAU OF FIRE SAFETYBFS
HEALTH FACILITIES ENGINEERING SECTIONHFES
HOUR, HAND RAILHR
OPPOSITE HANDOPP
W/
FIRE ALARMFA
CJ CONTROL JOINT
KP KICK PLATE
JT JOINT
EACHEA
ELEVATOR, ELEVATIONELEV
FLOOR DRAINFD
UNDERWRITERS LABORATORY INCUL
PVC POLYVINYL CHLORIDE
QTY QUANTITY
CORNER GUARDCG
CARD READERCR
FV FIELD VERIFY
ARCHITECTURAL SYMBOLS LEGEND
FLOOR PLAN LEGEND
SOLID SURFACESSRF
REFLECTED CEILING PLAN LEGEND
GENERAL NOTESABBREVIATIONS LIST
EXISTING SUSPENDED ACOUSTICAL CEILING
DATUM/ELEVATION LOCATION ID
1
EXISTING WINDOW SYSTEM
NEW WINDOW SYSTEM
2'x2' FLUORESCENT INDIRECT LIGHT FIXTURE
~
S
FA
WA
EXISTING DOUBLE DOOR TO BE REMOVED
EXISTING DOUBLE DOOR TO REMAIN
NEW DOUBLE DOOR W/ DOOR NUMBER
TEMPORARY 1-HR PARTITION AND DOOR
LAVATORY SINK
CLINICAL SINK
SQUARE SINK
ROUND SINK
MOP/CORNER SINK
FLOOR TOILET
WALL HUNG TOILET
URINAL
TANK STYLE TOILET
GRAB BAR
XX
XXXX
X'-X"
XXXX
C3
D4
A1
B2
Main Floor LevelEL:100'-0"
0001
XX
XXXX
GRIDGRID
NewExist
NEWROOM NAME000
DXXXX
DXX
XX
DXX
XX
00 06
EQUIPMENT TAG
00 WALL TYPE TAG
CT-1 INTERIOR FINISH TAG
SSTL
RSF
STAINLESS STEEL
RESILIENT SHEET FLOORING
DOOR OPENINGDO
(R) RELOCATE
01Axxxx Scale: 1/8" = 1'-0"
Plan Name - Bottom LinePlan Name - Top Line
DRINKING FOUNTAIN
PTM PATCH TO MATCH
CAM CAMERA - SEE ELECTRICAL DWG.
OS OCCUPANCY SENSOR (CEILING MOUNTED)
OFCI OWNER FURNISHED CONTRACTOR INSTALLED
OFVI OWNER FURNISHED VENDOR INSTALLED
OFOI OWNER FURNISHED OWNER INSTALLED
Abbreviations, Drawing SymbolsStandard & Standard MountingHeights
FOR
BID
S
project number:
sheet title:
sheet number:
approved
project:
coordination checked
location
drawn
checked
designed
issue: date:
key plan:
Rands House - RackhamRelocation
Nov. 13, 2018Owner Review 60% CD's
NM Project Number - 18113.0
WAYNE STATEUNIVERSITY
Facilities Planning and Management
5454 Cass Avenue
Detroit, MI 48202
Rands House
JK
JK
JK
DB
AG
WSU : 00
consultants:
Nov. 27, 2018Owner Review90% CD's
Dec. 04, 2018Review 100% CD's
Dec. 11, 2018For Bids
CEILINGFINISH
ROOM FINISH SCHEDULE
DW
G #
ROOM NAMEROOM NO. TRANSITIONMAT.
ROOM FLOORMAT.
EAST WALL
MAT. FINISH MAT. MAT.FINISH FINISH
NORTH WALLBASE SOUTH WALL
MATERIALMAT.FINISH FINISH TYPE MATERIAL
WINDOW SILLWEST WALL
CABINETS
MILLWORKFINISH MOUNT HEIGHT MATERIAL FINISH
BULKHEADROOM #
REMARKS
A-20
A-2
01COUNTER
INDEX OF FINISH MANUFACTURERS
PAINT- PT-1MANUFACTURER: SHERWIN WILLIAMSTYPE: PAINTCOLOR: SW7568 NEUTRAL GROUNDFINISH: SEMI-GLOSS
FIRE-RATED
CEILING DATA
PLASTER
ACOUSTIC LAY-IN TILEACOUSTIC TEGULAR TILE
GYPSUM WALLBOARDGYPSUM PLASTER
FIBER REINFORCED GYPSUM PANELFIBER REINFORCED GYPSUM PANEL
HUMIDITY RESISTANT LAY IN TILEABUSE RESISTANT LAY IN TILE
TF
CLN
CSH
ST&VS&L
PT
S&V
PREW
S
GRAN
S&W
WDSRF
N
RSF
RTRCONQT
RTFCTSV
CP
TERR
WD
RFRTRCON
RBRSB
SEAL & VARNISHSEAL & LACQUERSTAIN & VARNISH
CONCRETE SEALER/HARDENERTEXTURE FINISH
CLEANPREFINISHED
PAINT
SEAL
WAX
RESILIENT SHEET FLOORINGRESILIENT TILE FLOORING
RUBBER TREAD & RISERRUBBER FLOORING
GRANITE TILE
SEAL & WAXFINISH
SLATEWOODNONE
CERAMIC & PORCELAIN TILE
QUARRY TILECONCRETE
RNS
QT
RUBBER FLOORINGRUBBER TREAD & RISER
RESILIENT BASERESILIENT SHEET BASEQUARRY TILE
RUBBER
WOODSLATE
NONE
CONCRETE
AMCT
FLOOR DATA
SHEET VINYL
CARPET
TERRAZZO
MATERIAL
CPTERR
BASE DATA
CERAMIC TILEAGGLOMERATED MARBLETERRAZZOCARPET
ARCHBARCBCARCBDBARCBSBARCB2ARCB1
CONCRETE MASONRY UNITS
AGGLOMERATED MARBLEACOUSTIC BLOCK - SOUND ABSORBING
FACE BRICK TRIM COURSING
GROUND FACE MASONRY UNITS
FBTCEXISTING FACE BRICK
WALL FABRICQUARRY TILECERAMIC & PORCELAIN TILE
SLATENONE
SN
AMCTQT
EFB
WF
GMFU
FACE BRICKPOLY-RESIN
LIGHTWEIGHT BLOCKPOURED CONCRETE
PRFB
AB
CMU
LBPC
PCPGB
ARCB
VC
FIBER REINFORCED GYPSUM PANEL FIRE-RATEDFIBER REINFORCED GYPSUM PANELGYPSUM WALLBOARD FIRE-RATED
WALL DATA
GYPSUM WALLBOARD-LEAD LINEDGWFRF
GW-LL
FFR
ARCHITECTURAL BLOCK - DOUBLE BULLNOSEARCHITECTURAL BLOCK - SINGLE BULLNOSEARCHITECTURAL BLOCK #2 - SINGLE SCORED FACEARCHITECTURAL BLOCK #1 - SPLIT RIB1 SR-1ARCHITECTURAL BLOCK TYPE "D" TRIM COURSING
ARCHITECTURAL HALF BLOCKARCHITECTURAL BLOCK CAP
GLASS BLOCKPORTLAND CEMENT PLASTER
VINYL COVERED
ARLITHRLIT
PL
ATTACT
GSP
FFFR
GW
MIRROR, FIXED
ROOM ACCESSORIES
TOILET TISSUE DISPENSER
MOP & BROOM HOLDERSSHOWER CURTAIN RODS
GRAB BAR ASSEMBLYROBE HOOKS
FRAMED TILTED MIRROR, FIXEDFRAMED MIRROR, FIXED
SANITARY NAPKIN VENDOR
WASTE RECEPTACLETOWEL BARS
ELECTRIC HAND DRYERPAPER TOWEL DISPENSER
SOAP DISPENSER
SANITARY NAPKIN DISPOSAL
FOLDING SHOWER SEATCERAMIC SOAP DISH
W/ ACOUSTIC BATTSCERAMIC TILE
MOUNTING
SUSPENDEDFURSUS
NCT
FURRED
NONE
EXPOSED STRUCTUREEXPOSED ACOUSTIC DECKEXPOSED METAL DECKACOUSTICAL METAL DECKAMDAB
EADEMD
ES
WR
CSD
SNV SND
FS
GBA RH CR
MF
MBHFTMF FMF
TBSD
TTD HD TD
ITEM
LEGEND OF ABBREVIATIONS
MATERIAL MATERIAL MATERIAL
VCB VINYL COMPOSITE BASE
WOODWD
STAINLESS STEELSSTLGRANITEGRANGLASSGLCURTAIN WALLCWFABRIC SCRIMFAB
GYPSUM WALLBOARDGW
WOODMETAL PRIMEDMETAL PRE-FINISHEDANODIZED ALUMINUM
STAIN GRADEVARNISH GRADE
PREFINISHEDPLASTIC LAMINATEANODIZED ALUMINUMPERMANODICPAINTFACTORY FINISHMATCH EXISTING
HARDBOARD
LOUVREDOOR FINISH
TEMPERED INSULATED
INSULATED HOLLOW METALGEORGIAN POLISHED WIRE
REFLECTIVE INSULATED
TICLEAR INSULATED
RICI
HOLLOW CORE WOODSOLID CORE WOODALUMINUMHOLLOW METAL
GAUGECLEAR FLOATTEMPERED
LAMINATEDREFLECTIVETINTED
GLASS
G
TRL
TCF#
PER
MEFFPT
PLAMPRE
AA
VGSG
HB MP/FAA
MPW HOLLOW METAL WELDED
SEAL & VARNISHS&V
FIXED MULLIONREMOVABLE MULLION
SEAL & LACQUERS&L
RMFM
ALUMINUMTHERMALLY BROKENSOLID WOODHOLLOW METAL
WELDEDSTANDARD
STAIN & VARNISH
PERMANODICANODIZED ALUMINUM
FINISHES
KNOCKDOWN
AA
ST&V
PERP
STD
PAINTSW
WEL
HMKD
HMW
TBAL
REMOVABLE MULLION
THRESHOLDWEATHER STRIPSOUND STRIP
WEATHER CAP
LOCK SEAMWELD SEAM WINDOW TREATMENTS
BARRIER FREE OPERATORBFORM
WSTLS
WS
ASTRAGAL
HARDWAREFRAME CONSTRUCTION
FRAME DATA
SSAWC
HOLLOW METAL WELDED (LEAD)HMW-L
HMIHM
SCWHCW
DOOR CONSTRUCTION
PL PLASTIC LAMINATE
WALL PROTECTION (ACROVYN)WP
PTM PATCH TO MATCHNW NO WORKX EXISTING
AL
CPT CARPET TILEGYPSUM VENEER PLASTERGVPPORTLAN CEMENT PLASTERPCP
GYPSUM PLASTERGSPGYPSUM VENEER PLASTERGVP
FIBERGLASS REINF'D POLYMERFRP
FIBERGLASS REINF'D POLYMERFRP
(SHOP DRAWINGS AND SAMPLES MUST BE SUBMITTED FOR FINAL APPROVAL ON ALL INTERIOR FINISHES)
PAINT- PT-2
WALL BASE - RB-1MANUFACTURER: ROPPETYPE: PINNACLE RUBBER BASECOLOR: 193 BLACK BROWNSIZE: 4"
Room Finish Schedule
FOR
BID
S
project number:
sheet title:
sheet number:
approved
project:
coordination checked
location
drawn
checked
designed
issue: date:
key plan:
Rands House - RackhamRelocation
Nov. 13, 2018Owner Review 60% CD's
NM Project Number - 18113.0
WAYNE STATEUNIVERSITY
Facilities Planning and Management
5454 Cass Avenue
Detroit, MI 48202
Rands House
JK
JK
JK
DB
AG
WSU : 00
consultants:
Nov. 27, 2018Owner Review90% CD's
Dec. 04, 2018Review 100% CD's
Dec. 11, 2018For Bids
A-2
02
MANUFACTURER: SHERWIN WILLIAMSTYPE: PAINTCOLOR: SW7693 STONEBRIARFINISH: SEMI-GLOSS
PAINT- PT-3MANUFACTURER: SHERWIN WILLIAMSTYPE: PAINTCOLOR: SW7006 EXTRA WHITEFINISH: EXTRA WHITE
CARPET TILE - CPT-1MANUFACTURER: BENTLEYTYPE: TECH UPD8 AFIRMA HARDBACKCOLOR: GEOMETRY 400005SIZE: 18"x36"
ACOUSTIC CEILING TILE - ACT-1MANUFACTURER: ARMSTRONGMODEL: ULTIMA 1951 BEVELED TEGULARCOLOR: WHITESIZE: 24" x 24" (15
16" Grid)
100 VESTIBULE CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - PT-3 - CLNG PLAN - - - 100
101 OPEN OFFICE CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - PT-3 - CLNG PLAN - - - 101
103 CONFERENCE ROOM CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - PT-3 - CLNG PLAN - - - 103
106 STORAGE CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - PT-3 - CLNG PLAN - - - 106
107 OFFICE CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - PT-3 - CLNG PLAN - - - 107
110 STAIR EXST - - EXST - EXST EXST EXST EXST EXST EXST EXST EXST - - - ACT-1 - CLNG PLAN - - - 110
112 TYP OFFICE CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - ACT-1 - CLNG PLAN - - - 112
116 LOUNGE CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - ACT-1 - CLNG PLAN - - - 116
118 WAITING/OFFICE CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - ACT-1 - CLNG PLAN - - - 118
120 UNISEX ADA RESTROOM EXST - - EXST - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - ACT-1 - CLNG PLAN - - - 120
134 OBSERVATION CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - ACT-1 - CLNG PLAN - - - 134
136 CHILD PLAYROOM CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - ACT-1 - CLNG PLAN - - - 136
102 OPEN OFFICE CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - PT-3 - CLNG PLAN - - - 102
124 WOMENS RESTROOM EXST - - EXST - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - ACT-1 - CLNG PLAN - - - 124
200 OPEN OFFICE CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - PT-3 - CLNG PLAN - - - 200
200.1 STORAGE CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - PT-3 - CLNG PLAN - - - 200.1
201 OPEN OFFICE CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - PT-3 - CLNG PLAN - - - 201
202 OPEN OFFICE CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - PT-3 - CLNG PLAN - - - 202
203 OFFICE CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - PT-3 - CLNG PLAN - - - 203
205 OFFICE CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - PT-3 - CLNG PLAN - - - 205
207 OFFICE CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - PT-3 - CLNG PLAN - - - 207
212 TYP TREATMENT CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - PT-3 - CLNG PLAN - - - 212
214 TYP OFFICE CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - PT-3 - CLNG PLAN - - - 214
218 CHILDREN GROUP ROOM CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - PT-3 - CLNG PLAN - - - 218
219 TYP OBSERVATION CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - PT-3 - CLNG PLAN - - - 219
220 UNISEX ADA RESTOOM EXST - - EXST - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - PT-3 - CLNG PLAN - - - 220
226 ADULT GROUP ROOM CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - PT-3 - CLNG PLAN - - - 226
227 MECHANICAL ROOM CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - PT-3 - CLNG PLAN - - - 227
229 IT CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - PT-3 - CLNG PLAN - - - 229
224 WOMENS RESTOOM EXST - - EXST - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - PT-3 - CLNG PLAN - - - 224
230 ADULT GROUP ROOM CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - PT-3 - CLNG PLAN - - - 230
243 CONFERENCE/GROUP ROOM CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - PT-3 - CLNG PLAN - - - 243
245 OPEN OFFICE CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - PT-3 - CLNG PLAN - - - 245
104 CORRIDOR CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - PT-3 - CLNG PLAN - - - 104
109 WAITING CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - PT-3 - CLNG PLAN - - - 109
108 CORRIDOR CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - PT-3 - CLNG PLAN - - - 108
111 CORRIDOR CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - ACT-1 - CLNG PLAN - - - 111
148 CORRIDOR CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - ACT-1 - CLNG PLAN - - - 148
204 CORRIDOR CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - PT-3 - CLNG PLAN - - - 204
208 CORRIDOR CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - PT-3 - CLNG PLAN - - - 208
209 CORRIDOR CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - PT-3 - CLNG PLAN - - - 209
150 STAIR EXST - - EXST - EXST EXST EXST EXST EXST EXST EXST EXST - - - ACT-1 - CLNG PLAN - - - 210
210 STAIR EXST - - EXST - EXST EXST EXST EXST EXST EXST EXST EXST - - - PT-3 - CLNG PLAN - - - 210
248 CORRIDOR CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - PT-3 - CLNG PLAN - - - 248
250 STAIR EXST - - EXST - EXST EXST EXST EXST EXST EXST EXST EXST - - - PT-3 - CLNG PLAN - - - 250
varies
see
sche
dule
see schedule
hollow metalframe
F1
see
sche
dule
variessee schedule
D1
see
sche
dule
variessee schedule
D2
inset light tomatch existingdoors. v.i.f.
provide acousticfirestop sealant allthrough-wallpenetrations - typical
SECTION AT DECK
acoustic tile ceiling onmetal suspensionsystem
base refer to roomfinish schedule
PLAN
7 1/4"6"
(actual)
SECTION AT FLOOR
SECTION AT CEILING
provide acousticfirestop sealant bothsides of partition asshown
runner stud atbase of partition
W1
Wall Composite:5
8" type x gyp bd, each side6" metal studs @ 16" o.c.w/ 5 1/2" sound attenuating batt
continuous firestop sealanteach side (typ)
existing structure
runner
1/2"
SMOKE TIGHTWALL
SECTION AT FLOOR
5/8" Soundbreak gyp bd, each side on1" Z channels @ 24" o.c.on existing wall construction
1 5/8"(actual)
provide acousticsealant both sides ofpartition as shown
base refer to roomfinish schedule
W2
PLAN
SECTION AT CEILING
2" (nominal)
runner stud atbase of partition
existing wall
existing structure
runner
continuous acoustic sealant
SECTION AT DECK
acoustic tile ceiling onmetal suspensionsystem
1 5/8"
2"
sound batt insulationabove ceiling. refer toRC plan for locations
note: provide acousticsealant around allelectrical outlets andother wall penetrations
CARPET
TRANSITION STRIP
CERAMIC TILE
T1
refe
r to
plan
2"
1 2"
hollow metal frameattach/anchor per mfgrrecommendations
16 guage doublestuds at doorframes typicalexisting wall1/4" min shimspace (all sides)
continuous sealantall sides of frame
door (refer toschedule)
provide doorsilencers (3 perjamb min)
refer to plan
2"
12"
hollow metalframeattach/anchorper mfgrrecommendations
16 guage doublestuds at doorhead typical
existing wall
continuoussealant allsides of frame
door (refer toschedule)
provide doorsilencers (3 perjamb min)
SERIESDOORMAT.
DOOR AND FRAME SCHEDULE
A-2
01
WIDTH
DOOR DATADW
G. N
o.No. QTY.DOOR DOOR
THICK.HEIGHT TYPESIZE DOOR
LOUVERGAUGESERIES HRS.RATING
TRANSOMGLASS DETAILJAMB
FRAME DATA
FINISH TYPEFRAME
MAT.FRAME No.
DOORHARDWARE
FINISHGLASSHRS.
RATING No.GROUP
REMARKS
Door
Unde
rcut
A-30
03A-100 Scale: 1/4" = 1'-0"
Door Types
NOTE: GENERAL CONTRACTOR TO REVIEW DOOR HARDWARE WITH OWNER PRIOR TO ANY INSTALLATION
DETAILHEAD
D118 1 3'-0" 7'-0" D2 SCW - - 20 min - - - - F1 J1 HM H1 - - - - CLASSROOM 1 - - - D118
DOOR REMARKS:
1. Contractor to coordinate with WSU reuse of existing doors and frames from
storage. Verify quantity, size, fire rating and condition of existing doors prior
to any installation.
02A-100 Scale: 1/4" = 1'-0"
Frame Types
HARDWARE GENERAL NOTES:
General notes:
1. Contractor shall verify all existing field conditions and notify architect
immediately if that which exists differs from that which is shown on
drawings.
2. All work to comply with Federal, State and Local codes, laws and
ordinances.The requirements of ICC/ANSI A117.1 and the Americans with
disabilities act (ADA) are to be fully satisfied. All work shall meet the most
stringent requirements of both including, but not limited to clearances,
limitations, accessories, etc.
3. These drawings are prepared in accordance with the limited services for
which the architect was contracted. The architect makes no representation
that the interpretation of these documents will result in complete compliance
with the ADA.
4. All doors required to be labeled shall be set in labeled frames and identified
with UL label and be provided with approved self-closing devices and
positive latching hardware.
5. All designated exit doors shall be equipped with the required egress
hardware.
6. Supplier shall meet with owner to establish MK keying system and provide a
combinated cylinder for each locking device as direct by owner. Supplier
shall submit key schedule for final approval. Furnish 2 change keys per
cylinder and 2 master keys total.
7. Supplier shall furnish and provide all necessary reinforcements, brackets,
fasteners, spacers and fillers to provide a complete functioning opening.
8. Supplier shall furnish complete shop drawings including; vertical typed
hardware schedule, product data sheets and warranty information following
DHI prescribed methods.
DOOR HARDWARE:
Hardware Set 1 -Classroom Lock (Lock/Unlock) + Closer & Smoke Seal
3 ea. Butt Hinge 35STBB 4545 NRP 26D PDQ
1 ea. Classroom Lock MR 148 DJSJ-SFL 32D PDQ
1 ea. Closer 7101 BC PA Regular Arm (Pull side Mount) AL PDQ
1 ea. Wall Stop 102 26D PDQ
1 ea. Kickplate 98 10 x 2" LDW 32D PDQ
1 set Smoke Seal 797B Blk Reese
Hardware Set 2 -Privacy Set w/ indicator (Lock/Unlock) + Closer & Smoke Seal
3 ea. Butt Hinge 35STBB 4545 NRP 26D PDQ
1 ea. Privacy Set w/ indicator MR 278 PJSJ 32D PDQ
1 ea. Closer 7101 BC PA Regular Arm (Pull side Mount) AL PDQ
1 ea. Wall Stop 102 26D PDQ
1 ea. Kickplate 98 10 x 2" LDW 32D PDQ
1 set Smoke Seal 797B Blk Reese
Hardware Set 3 -Classroom Lock (Lock/Unlock)
3 ea. Butt Hinge 35STBB 4545 NRP 26D PDQ
1 ea. Classroom Lock MR 148 DJSJ-SFL 32D PDQ
1 ea. Wall Stop 102 26D PDQ
Door Schedule & Wall Types
FOR
BID
S
project number:
sheet title:
sheet number:
approved
project:
coordination checked
location
drawn
checked
designed
issue: date:
key plan:
Rands House - RackhamRelocation
Nov. 13, 2018Owner Review 60% CD's
NM Project Number - 18113.0
WAYNE STATEUNIVERSITY
Facilities Planning and Management
5454 Cass Avenue
Detroit, MI 48202
Rands House
JK
JK
JK
DB
AG
WSU : 00
consultants:
Nov. 27, 2018Owner Review90% CD's
Dec. 04, 2018Review 100% CD's
Dec. 11, 2018For Bids
01A-30 Scale: 1 1/2" = 1'-0"
W-2 WALL TYPE 01A-30 Scale: 1 1/2" = 1'-0"
W-1 WALL TYPE
D120 1 3'-6" 7'-0" D1 SCW - - 20 min - - - - F1 J1 HM H1 - - - - PRIVACY 2 - - - D120
A-2
01
D220 1 3'-6" 7'-0" D1 SCW - - 20 min - - - - F1 J1 HM H1 - - - - PRIVACY 2 - - - D220
D224 1 3'-6" 7'-0" D1 SCW - - 20 min - - - - F1 J1 HM H1 - - - - CLASSROOM 1 - - - D224
D230 1 3'-6" 7'-0" D2 SCW - - 20 min - - - - F1 J1 HM H1 - - - - CLASSROOM 1 - - - D230
D245 1 3'-0" 7'-0" D2 SCW - - - - - - - F1 J1 HM H1 - - - - CLASSROOM 3 - - - D245
D246 1 3'-6" 7'-0" D2 SCW - - - - - - - F1 J1 HM H1 - - - - CLASSROOM 3 - - - D246
D247 1 3'-0" 7'-0" D2 SCW - - - - - - - F1 J1 HM H1 - - - - CLASSROOM 3 - - - D247
03A-002 Scale: NTS
Floor Transition
UP
UP
ref.
OFFICE107 CONFERENCE ROOM
103
OPENOFFICE100
PORCH
VEST
OPENOFFICE102
STORAGE106
STORAGE105PLANTER
OFFICE112
LOUNGE116
WAITING118
WOMEN124
UNISEXADA120
JC122
OFFICE126
OFFICE128
TREATMENT130
TREATMENT132
OBSERVATION134 CHILD
PLAYROOM136
TREATMENT140
OFFICE138
OFFICE142
TREATMENT144
OFFICE145
TREATMENT143
OFFICE141
IT137
OFFICE129
RESEARCHLAB125
COVERED AREA
OFFICE117
CL111
UP
UP
DN
2'-0"
5'-0"
3'-7" 5'-0"
CORRIDOR104
STAIR110
CORRIDOR108
WAITING109
CO
RR
IDO
R11
1STAIR150
CORRIDOR148
AD-101 FOR
BID
S
project number:
sheet title:
sheet number:
approved
project:
coordination checked
location
drawn
checked
designed
issue: date:
key plan:
Rands House - RackhamRelocation
Nov. 13, 2018Owner Review 60% CD's
NM Project Number - 18113.0
WAYNE STATEUNIVERSITY
Facilities Planning and Management
5454 Cass Avenue
Detroit, MI 48202
Rands House
JK
JK
JK
DB
AG
WSU : 00
consultants:
Nov. 27, 2018Owner Review90% CD's
Dec. 04, 2018Review 100% CD's
Dec. 11, 2018For Bids
01A-101 Scale: 1/8" = 1'-0"
First Floor Plan - DemolitionRands Building
Rands House 1st Floor Plan -Demolition Work
LEGEND
Remove existing gypsum and metal stud wall full height
walls
floors
01
GENERAL DEMOLITION NOTES
A. Demolition contractor shall be familiar with entire scope of new work prior to startingdemolition work.
B. all demolition floor plans, wall layouts, door and window locations, patterns havebeen shown for reference only. The General Contractor must field verify alldimensions and room layouts prior to new work and notify the architect of anydeviations from what is shown. All site visits must be coordinated with WSUConstruction Project Manager minimum 24 hours in advance of the site visit(s). Allwork outside of defined construction zone must be coordinated with WSUConstruction manager.
C. refer to electrical and mechanical drawings for extent of electrical and mechanicaldemolition work and for additional information.
D. room numbers and room names on all existing drawings relate only to demolitionsheets.
E. all existing items removed shall be returned to the owner for re-use or disposed ofoff site if rejected by the owner. do not damage any millwork during demolition.
F. owner is responsible for removing any loose equipment such as furniture, movableequipment, trash cans, etc.
G. all door hardware shall be removed from demolished doors, cleaned and turnedover to the owner.
H. repair all surfaces and components damaged during demolition and construction.
I. coordinate scope and extent of demolition work with new work plans and details.
J. demolition work required is not necessarily limited to what is shown on thedemolition plans. the intent is to remove all mechanical, electrical, and architecturalitems required to facilitate new construction.
K. unless noted otherwise when removing existing suspended lay-in ceiling assembly,including furring channels, wall angles and suspension wires.
L. where new plumbing is indicated, saw cut & remove existing concrete floor slab forinstallation of new plumbing. coordinate with mechanical and plumbing drawingsfor locations. Contractor must take precautions not to damage existing structuralfloor slab and is responsible to repair any damage due to new work. All slabremoval work must be coordinated with EMU for allowable time of work and perspecifications
items to be removed
existing items to remain
remove existing door & frame assembly, including all relatedhardware.40
doors
50
misc items
DEMOLITION NOTES
all existing furniture, file cabinets, and other movableequipment, not tagged to remain is to be removed by WSU.
30
ceilings
remove existing acoustic tile ceiling, grid to reamin. Coordinateremoval of mechanical, plumbing and electrical items with M&Edemolition drawings.
20Prep existing floor for new finish per specifications. Patch andrepair existing floor as necessary for smooth floor finish.
51 remove existing plumbing fixture. Refer or MEP dwgs for demo plumbing work.
Remove portion of existing gypsum & metal stud wall for new door02
21Existing flooring to be removed. Prep floor for new finish perspecifications. Patch and repair existing concrete floor slab.
22 Existing flooring to remain.
52 remove existing toilet partition.
Remove portion of existing gypsum & metal stud wall for new one-way mirror03
31 remove existing light fixtures. Coordinate removal of othermechanical, plumbing and electrical items with M&E demolitiondrawings.
53 existing cabinets to remain.
54 existing vending machines to be removed
01
02
02
03
03
21
21
21
22
22
22
22
22
22
22
22
22
22
22
22
22
22
22
22
22
22
22
22
22
22 22 22 22 22
22222222
22
22
22
40
40
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50 5050 50 50
5050505050
50
50
51
52
DN
222
225
OFFICE207
UP
OPEN
TREATMENT232
OBSERVATION234
OFFICE205
OFFICE203
OPENOFFICE201
OPENOFFICE200
DN
STORAGE200.1
OPENOFFICE202
UP
DN
TREATMENT212
OFFICE214
CHILDREN'SGROUP ROOM218
UNISEX ADA220
WOMEN224
ADULTGROUP ROOM226
ADULTGROUP ROOM230
TREATMENT236
TREATMENT238
TREATMENT241
OBSERVATION242 COMFERENCE/
GROUP ROOM243
TREATMENT217
OBSERVATION219
TREATMENT225
MECH227
IT229
OPENOFFICE240 OFFICE
244
2'-0"
5'-0"
3'-7" 5'-0"
2'-0"
5'-0"
3'-7" 5'-0"
2'-0"
5'-0"
2'-0"
5'-0"
3'-0"5'-0"
2'-0"5'-0"
CORRIDOR204
CORRIDOR209
STAIR210
CO
RR
IDO
R21
1
CORRIDOR248
STAIR250
CORRIDOR208
OFFICE244
AD-102 FOR
BID
S
project number:
sheet title:
sheet number:
approved
project:
coordination checked
location
drawn
checked
designed
issue: date:
key plan:
Rands House - RackhamRelocation
Nov. 13, 2018Owner Review 60% CD's
NM Project Number - 18113.0
WAYNE STATEUNIVERSITY
Facilities Planning and Management
5454 Cass Avenue
Detroit, MI 48202
Rands House
JK
JK
JK
DB
AG
WSU : 00
consultants:
Nov. 27, 2018Owner Review90% CD's
Dec. 04, 2018Review 100% CD's
Dec. 11, 2018For Bids
01A-101 Scale: 1/8" = 1'-0"
Second Floor Plan - DemolitionRands Building
Rands House 2nd Floor Plan -Demolition Work
LEGEND
Remove existing gypsum and metal stud wall full height
walls
floors
01
GENERAL DEMOLITION NOTES
A. Demolition contractor shall be familiar with entire scope of new work prior to startingdemolition work.
B. all demolition floor plans, wall layouts, door and window locations, patterns havebeen shown for reference only. The General Contractor must field verify alldimensions and room layouts prior to new work and notify the architect of anydeviations from what is shown. All site visits must be coordinated with WSUConstruction Project Manager minimum 24 hours in advance of the site visit(s). Allwork outside of defined construction zone must be coordinated with WSUConstruction manager.
C. refer to electrical and mechanical drawings for extent of electrical and mechanicaldemolition work and for additional information.
D. room numbers and room names on all existing drawings relate only to demolitionsheets.
E. all existing items removed shall be returned to the owner for re-use or disposed ofoff site if rejected by the owner. do not damage any millwork during demolition.
F. owner is responsible for removing any loose equipment such as furniture, movableequipment, trash cans, etc.
G. all door hardware shall be removed from demolished doors, cleaned and turnedover to the owner.
H. repair all surfaces and components damaged during demolition and construction.
I. coordinate scope and extent of demolition work with new work plans and details.
J. demolition work required is not necessarily limited to what is shown on thedemolition plans. the intent is to remove all mechanical, electrical, and architecturalitems required to facilitate new construction.
K. unless noted otherwise when removing existing suspended lay-in ceiling assembly,including furring channels, wall angles and suspension wires.
L. where new plumbing is indicated, saw cut & remove existing concrete floor slab forinstallation of new plumbing. coordinate with mechanical and plumbing drawingsfor locations. Contractor must take precautions not to damage existing structuralfloor slab and is responsible to repair any damage due to new work. All slabremoval work must be coordinated with EMU for allowable time of work and perspecifications
items to be removed
existing items to remain
remove existing door & frame assembly, including all relatedhardware.40
doors
50
misc items
DEMOLITION NOTES
all existing furniture, file cabinets, and other movableequipment, not tagged to remain is to be removed by WSU.
30
ceilings
remove existing acoustic tile ceiling, grid to reamin. Coordinateremoval of mechanical, plumbing and electrical items with M&Edemolition drawings.
20Prep existing floor for new finish per specifications. Patch andrepair existing floor as necessary for smooth floor finish.
51 remove existing plumbing fixture. Refer or MEP dwgs for demo plumbing work.
Remove portion of existing gypsum & metal stud wall for new door02
21Existing flooring to be removed. Prep floor for new finish perspecifications. Patch and repair existing concrete floor slab.
22 Existing flooring to remain.
52 remove existing toilet partition.
Remove portion of existing gypsum & metal stud wall for new one-way mirror03
31 remove existing light fixtures. Coordinate removal of othermechanical, plumbing and electrical items with M&E demolitiondrawings.
53 existing cabinets to remain.
54 existing vending machines to be removed
03
2150
03
03 0301
03 03
03
03
02
02
02
2150 2150
2150
2150
2150
21502150
2150
2150
2150
2150
21502150
2150
2150
2150
2150 21
21
21
2150 2150 2150
2150
2150
2150
21
21
21
22
22
22
22
22
22
22
5151
5151
52
40
40
40
40
53
53
54
54
UP
UP
ref.
OFFICE107 CONFERENCE ROOM
103
OPENOFFICE100
PORCH
VEST
OPENOFFICE102
STORAGE106
STORAGE105PLANTER
OFFICE112
LOUNGE116
WAITING118
WOMEN124
UNISEXADA120
JC122
OFFICE126
OFFICE128
TREATMENT130
TREATMENT132
OBSERVATION134 CHILD
PLAYROOM136
TREATMENT140
OFFICE138
OFFICE142
TREATMENT144
OFFICE145
TREATMENT143
OFFICE141
IT137
OFFICE129
RESEARCHLAB125
COVERED AREA
OFFICE117
CL111
UP
UP
DN
CORRIDOR104
STAIR110
CORRIDOR108
WAITING109
CO
RR
IDO
R11
1STAIR150
CORRIDOR148
EXSTEXSTEXST
EXSTEXSTEXSTEXSTEXST
EXST
EXST
EXST
EXST
EXST
EXST
EXST
EXST
EXST
EXST
EXST
EXST
EXST
EXST
EXST
EXST
EXST
EXST
EXST
EXST
EXSTEXST
EXST
EXST
EXST
xLF
xLF
xLF
xLF
xLF
xLF
xLF
xLF
xLF
xLF
xLF xLF xLF xLF xLF xLF
xLFxLFxLFxLF
xLFxLFxLFxLFxLFxLFxLFxLFxLFxLF
xLFxLFxLF
xLF xLF
xLF xLF
xLF xLF
xLF xLF
xLF
xLF
xLF
xLF
xLF
xLF
xLF
xLFxLF
xLF xLF
xLF xLF xLF xLF xLF
xLF xLF
xLF
xLF
xLF
xLF
xLF
xLF
xLF
AD-103 FOR
BID
S
project number:
sheet title:
sheet number:
approved
project:
coordination checked
location
drawn
checked
designed
issue: date:
key plan:
Rands House - RackhamRelocation
Nov. 13, 2018Owner Review 60% CD's
NM Project Number - 18113.0
WAYNE STATEUNIVERSITY
Facilities Planning and Management
5454 Cass Avenue
Detroit, MI 48202
Rands House
JK
JK
JK
DB
AG
WSU : 00
consultants:
Nov. 27, 2018Owner Review90% CD's
Dec. 04, 2018Review 100% CD's
Dec. 11, 2018For Bids
01A-101 Scale: 1/8" = 1'-0"
First Floor Reflected Ceiling Plan - New WorkRands Building
Rands House 1st Floor ReflectedCeiling Plan - Demolition Work
LEGEND
Remove existing gypsum and metal stud wall full height
walls
floors
01
GENERAL DEMOLITION NOTES
A. Demolition contractor shall be familiar with entire scope of new work prior to startingdemolition work.
B. all demolition floor plans, wall layouts, door and window locations, patterns havebeen shown for reference only. The General Contractor must field verify alldimensions and room layouts prior to new work and notify the architect of anydeviations from what is shown. All site visits must be coordinated with WSUConstruction Project Manager minimum 24 hours in advance of the site visit(s). Allwork outside of defined construction zone must be coordinated with WSUConstruction manager.
C. refer to electrical and mechanical drawings for extent of electrical and mechanicaldemolition work and for additional information.
D. room numbers and room names on all existing drawings relate only to demolitionsheets.
E. all existing items removed shall be returned to the owner for re-use or disposed ofoff site if rejected by the owner. do not damage any millwork during demolition.
F. owner is responsible for removing any loose equipment such as furniture, movableequipment, trash cans, etc.
G. all door hardware shall be removed from demolished doors, cleaned and turnedover to the owner.
H. repair all surfaces and components damaged during demolition and construction.
I. coordinate scope and extent of demolition work with new work plans and details.
J. demolition work required is not necessarily limited to what is shown on thedemolition plans. the intent is to remove all mechanical, electrical, and architecturalitems required to facilitate new construction.
K. unless noted otherwise when removing existing suspended lay-in ceiling assembly,including furring channels, wall angles and suspension wires.
L. where new plumbing is indicated, saw cut & remove existing concrete floor slab forinstallation of new plumbing. coordinate with mechanical and plumbing drawingsfor locations. Contractor must take precautions not to damage existing structuralfloor slab and is responsible to repair any damage due to new work. All slabremoval work must be coordinated with EMU for allowable time of work and perspecifications
items to be removed
existing items to remain
remove existing door & frame assembly, including all relatedhardware.40
doors
50
misc items
DEMOLITION NOTES
all existing furniture, file cabinets, and other movableequipment, not tagged to remain is to be removed by WSU.
30
ceilings
remove existing acoustic tile ceiling, grid to reamin. Coordinateremoval of mechanical, plumbing and electrical items with M&Edemolition drawings.
20Prep existing floor for new finish per specifications. Patch andrepair existing floor as necessary for smooth floor finish.
51 remove existing plumbing fixture. Refer or MEP dwgs for demo plumbing work.
Remove portion of existing gypsum & metal stud wall for new door02
21Existing flooring to be removed. Prep floor for new finish perspecifications. Patch and repair existing concrete floor slab.
22 Existing flooring to remain.
52 remove existing toilet partition.
Remove portion of existing gypsum & metal stud wall for new one-way mirror03
31 remove existing light fixtures. Coordinate removal of othermechanical, plumbing and electrical items with M&E demolitiondrawings.
53 existing cabinets to remain.
54 existing vending machines to be removed
3030
30
30
30
30
30
30
30
30
30 30 30 30 30
30
303030
30
30 30
30
30
30
30
DN
222
225
OFFICE207
UP
OPEN
TREATMENT232
OBSERVATION234
OFFICE205
OFFICE203
OPENOFFICE201
OPENOFFICE200
DN
STORAGE200.1
OPENOFFICE202
UP
DN
TREATMENT212
OFFICE214
CHILDREN'SGROUP ROOM218
UNISEX ADA220
WOMEN224
ADULTGROUP ROOM226
ADULTGROUP ROOM230
TREATMENT236
TREATMENT238
TREATMENT241
OBSERVATION242 COMFERENCE/
GROUP ROOM243
TREATMENT217
OBSERVATION219
TREATMENT225
MECH227
IT229
OPENOFFICE240 OFFICE
244
CORRIDOR204
CORRIDOR209
STAIR210
CO
RR
IDO
R21
1
CORRIDOR248
STAIR250
CORRIDOR208
OFFICE244
xLF
xLF
xLF
xLF
xLFxLFxLFxLFxLFxLFxLF
xLF
xLF
xLF
xLF
xLF
xLF
xLF
xLF
xLF
xLFxLFxLF
xLFxLF
xLF xLF
xLFxLF
xLF xLF
xLF xLF
xLFxLF
xLF xLF
xLF
xLF
xLF xLF
xLFxLF
xLF xLF
xLF xLF
xLF xLF xLF
xLF xLF xLF xLF
xLF xLF xLF xLF
xLFxLF
xLF
xLF
xLF
xLF
xLF
xLF
AD-104 FOR
BID
S
project number:
sheet title:
sheet number:
approved
project:
coordination checked
location
drawn
checked
designed
issue: date:
key plan:
Rands House - RackhamRelocation
Nov. 13, 2018Owner Review 60% CD's
NM Project Number - 18113.0
WAYNE STATEUNIVERSITY
Facilities Planning and Management
5454 Cass Avenue
Detroit, MI 48202
Rands House
JK
JK
JK
DB
AG
WSU : 00
consultants:
Nov. 27, 2018Owner Review90% CD's
Dec. 04, 2018Review 100% CD's
Dec. 11, 2018For Bids
01A-101 Scale: 1/8" = 1'-0"
Second Floor Reflected Ceiling Plan - New WorkRands Building
Rands House 2nd Floor ReflectedCeiling Plan - Demolition Work
LEGEND
Remove existing gypsum and metal stud wall full height
walls
floors
01
GENERAL DEMOLITION NOTES
A. Demolition contractor shall be familiar with entire scope of new work prior to startingdemolition work.
B. all demolition floor plans, wall layouts, door and window locations, patterns havebeen shown for reference only. The General Contractor must field verify alldimensions and room layouts prior to new work and notify the architect of anydeviations from what is shown. All site visits must be coordinated with WSUConstruction Project Manager minimum 24 hours in advance of the site visit(s). Allwork outside of defined construction zone must be coordinated with WSUConstruction manager.
C. refer to electrical and mechanical drawings for extent of electrical and mechanicaldemolition work and for additional information.
D. room numbers and room names on all existing drawings relate only to demolitionsheets.
E. all existing items removed shall be returned to the owner for re-use or disposed ofoff site if rejected by the owner. do not damage any millwork during demolition.
F. owner is responsible for removing any loose equipment such as furniture, movableequipment, trash cans, etc.
G. all door hardware shall be removed from demolished doors, cleaned and turnedover to the owner.
H. repair all surfaces and components damaged during demolition and construction.
I. coordinate scope and extent of demolition work with new work plans and details.
J. demolition work required is not necessarily limited to what is shown on thedemolition plans. the intent is to remove all mechanical, electrical, and architecturalitems required to facilitate new construction.
K. unless noted otherwise when removing existing suspended lay-in ceiling assembly,including furring channels, wall angles and suspension wires.
L. where new plumbing is indicated, saw cut & remove existing concrete floor slab forinstallation of new plumbing. coordinate with mechanical and plumbing drawingsfor locations. Contractor must take precautions not to damage existing structuralfloor slab and is responsible to repair any damage due to new work. All slabremoval work must be coordinated with EMU for allowable time of work and perspecifications
items to be removed
existing items to remain
remove existing door & frame assembly, including all relatedhardware.40
doors
50
misc items
DEMOLITION NOTES
all existing furniture, file cabinets, and other movableequipment, not tagged to remain is to be removed by WSU.
30
ceilings
remove existing acoustic tile ceiling, grid to reamin. Coordinateremoval of mechanical, plumbing and electrical items with M&Edemolition drawings.
20Prep existing floor for new finish per specifications. Patch andrepair existing floor as necessary for smooth floor finish.
51 remove existing plumbing fixture. Refer or MEP dwgs for demo plumbing work.
Remove portion of existing gypsum & metal stud wall for new door02
21Existing flooring to be removed. Prep floor for new finish perspecifications. Patch and repair existing concrete floor slab.
22 Existing flooring to remain.
52 remove existing toilet partition.
Remove portion of existing gypsum & metal stud wall for new one-way mirror03
31 remove existing light fixtures. Coordinate removal of othermechanical, plumbing and electrical items with M&E demolitiondrawings.
53 existing cabinets to remain.
54 existing vending machines to be removed
31313131
31 31 31 31
UP
UP
ref.
copier
OFFICE107 CONFERENCE ROOM
103
OPENOFFICE100
PORCH
VEST
OPENOFFICE102
STORAGE106
STORAGE105PLANTER
OFFICE112
LOUNGE116
WAITING118
WOMEN124
UNISEXADA120
JC122
OFFICE126
OFFICE128
TREATMENT130
TREATMENT132
OBSERVATION134 CHILD
PLAYROOM136
TREATMENT140
OFFICE138
OFFICE142
TREATMENT144
OFFICE145
TREATMENT143
OFFICE141
IT137
OFFICE129
RESEARCHLAB125
COVERED AREA
OFFICE117
CL111
UP
UP
DN
5'-6"
W1
W1
D120
D118
W2
W2roomside only
W2roomside only
W2roomside only
W2roomside only
W2roomside only
W2
W2
W2
W2
W2
W2roomside only
W2
roomside only
W2
roomside only
W2
roomside only
W2
roomside only
W2
roomside only
W2
roomside only
W2W2 W2 W2 W2
W2roomside only
W2roomside only
W2roomside onlyW2
W2 W2
CORRIDOR104
STAIR110
CORRIDOR108
WAITING109
CO
RR
IDO
R11
1STAIR150
CORRIDOR148
A-201 FOR
BID
S
project number:
sheet title:
sheet number:
approved
project:
coordination checked
location
drawn
checked
designed
issue: date:
key plan:
Rands House - RackhamRelocation
Nov. 13, 2018Owner Review 60% CD's
NM Project Number - 18113.0
WAYNE STATEUNIVERSITY
Facilities Planning and Management
5454 Cass Avenue
Detroit, MI 48202
Rands House
JK
JK
JK
DB
AG
WSU : 00
consultants:
Nov. 27, 2018Owner Review90% CD's
Dec. 04, 2018Review 100% CD's
Dec. 11, 2018For Bids
01A-101 Scale: 1/8" = 1'-0"
First Floor Plan - New WorkRands Building
Rands House 1st Floor Plan -New Work
GENERAL NOTES
1) GENERAL CONTRACTOR AND SUB TRADES ARERESPONSIBLE TO VERIFY ALL EXISTING DIMENSIONSAND NOTIFY THE ARCHITECT OF ANY AND ALLDISCREPANCIES.
2) GENERAL CONTRACTOR SHALL BE FAMILIAR WITHENTIRE SCOPE OF NEW WORK AND PROCEED WITHWORK IN ACCORDANCE WITH NEW WORK.
3) NEW WORK FLOOR PLANS, WALL LAYOUTS, DOORAND WINDOW LOCATIONS AND PATTERNS HAVE BEENSHOWN FOR REFERENCE ONLY. THIS DRAWING ISNOT INTENDED TO SHOW ALL CONDITIONS, MATERIALPATTERNS AND LAYOUTS. INSPECT SITE PRIOR TOSTART OF CONSTRUCTION TO DETERMINE THE FULLSCOPE OF WORK.
4) REFER TO ELECTRICAL / MECHANICAL DRAWINGS FOREXTENT OF NEW ELECTRICAL AND MECHANICALWORK. COORDINATE BETWEEN ALL DISCIPLINES.REPORT DISCREPANCIES TO ARCHITECT.
5) ALL PATCH PAINTING TO INCLUDE ENTIRE/COMPLETEWALL - EDGE TO EDGE & CORNER TO CORNER
NEW WORK NOTES:
FLOORS
INSTALL NEW DOOR, REFER TO DOOR SCHEDULE. PROVIDEHARDWARE PER SCHEDULE
DOORS AND WINDOWS
WALLS
NEW FLOOR FINISH, REFER TO FINISH SCHEDULE11
31
32
NEW WALL CONSTRUCTION, PREP AND PAINT, REFER TO WALL TYPESAND DETAILS.
MISC.
01
CEILINGS
PREP AND PAINT GYPSUM CEILING41
72
CLEAN EXISTING WINDOW SYSTEM, REPAIR WINDOW SILL AS NECESSARY
42
LIGHTING
74
NEW FLOOR BASE, REFER TO FINISH SCHEDULE12
RELOCATED PROJECTION SCREEN
PROVIDE NEW ACOUSTIC CEILING TILE AND GRID, REFER TO FINISHSCHEDULE
INSTALL NEW LIGHTING FIXTURES, REFER TO ELECTRICALDRAWINGS FOR FULL EXTENT OF WORK.
51
75
INSTALL NEW LOOSE FURNITURE, REFER WSUFUNITURE LIST
77
INSTALL NEW WHITE BOARD
INSTALL NEW FLAT SCREEN
33 DOOR TO RECEIVE NEW CARD READER, REFER TO ELECTRICAL DRAWINGS
78 INSTALL NEW ONE-WAY MIRROR. ARROW INDICATESDIRECTION OF VIEW
71 INSTALL NEW PLUMBING FIXTURE, REFER TO MEPDRAWINGS
34 WINDOW TO RECEIVE NEW BLACK-OUT SHADE
43 PROVIDE MINIMUM 4" SOUND ATTENUATING INSULATION ABOVECEILING 2 FEET EITHER SIDE OF WALLS AS SHOWN IN HATCHED AREAS.
INFILL AREA WHERE WALL WAS REMOVED WITH NEWFLOORING TO MATCH EXISTING
13
79 RELOCATE EXISTING TOILET ROOM ACCESSORIES(IE. SOAP DISPENSER, TOWEL DISPENSER, MIRRORS,ETC.) FOR NEW LAYOUT
35 DOOR CARD READER TO BE RE-CODED.
44 PROVIDE NEW 2'x2' CEILING ACCESS HATCH. COORDINATE LOCATIONWITH MECHANICAL EQUIPMENT
01
0131
31
3232
32
32
32
32
32
32
32 32 32 32 32 32
323232
32
32
32
32
32
32
32
3232
32 32 32 32
32
3232
32 32
32
32
32
32
32
32
32
323232
3232
32
3232
7474
74
7474
7474
74
74
74
7474
74
74
74
74
7474
74
74 74
74
74
74
74
74
74
74
7474
74
74
74
74
74
7474
74 74
74
7474
7474
747474
74
74
74
74
77
7878
71
34
13
79
35
35
DN
222
225
OFFICE207
UP
OPEN
TREATMENT232
OBSERVATION234
OFFICE205
OFFICE203
OPENOFFICE201
OPENOFFICE200
DN
STORAGE200.1
OPENOFFICE202
UP
DN
TREATMENT212
OFFICE214
CHILDREN'SGROUP ROOM218
UNISEX ADA220
WOMEN224
ADULTGROUP ROOM226
ADULTGROUP ROOM230
TREATMENT236
TREATMENT238 OBSERVATION
247
TREATMENT246
TREATMENT241
OBSERVATION242 COMFERENCE/
GROUP ROOM243
TREATMENT217
OBSERVATION219
TREATMENT225
MECH227
IT229
OPENOFFICE245
OPENOFFICE240 OFFICE
244
7'-8" 8'-5" ±7'-10"
11'-9
"
W1
2'-0"
5'-0"
W1
W1
W1W1
D24
5
D24
6
D24
7
D224
D220
D230
W2
W2
W2
W2roomside only
roomside only
W2roomside only
W2
W2
W2roomside only
W2
W2
W2roomside only
W2
W2
W2
W2
CORRIDOR204
CORRIDOR209
STAIR210
CO
RR
IDO
R21
1
CORRIDOR248
STAIR250
CORRIDOR208
OFFICE244
A-202
01A-101 Scale: 1/8" = 1'-0"
Second Floor Plan - New WorkRands Building
Rands House 2nd Floor Plan - NewWork
GENERAL NOTES
1) GENERAL CONTRACTOR AND SUB TRADES ARERESPONSIBLE TO VERIFY ALL EXISTING DIMENSIONSAND NOTIFY THE ARCHITECT OF ANY AND ALLDISCREPANCIES.
2) GENERAL CONTRACTOR SHALL BE FAMILIAR WITHENTIRE SCOPE OF NEW WORK AND PROCEED WITHWORK IN ACCORDANCE WITH NEW WORK.
3) NEW WORK FLOOR PLANS, WALL LAYOUTS, DOORAND WINDOW LOCATIONS AND PATTERNS HAVE BEENSHOWN FOR REFERENCE ONLY. THIS DRAWING ISNOT INTENDED TO SHOW ALL CONDITIONS, MATERIALPATTERNS AND LAYOUTS. INSPECT SITE PRIOR TOSTART OF CONSTRUCTION TO DETERMINE THE FULLSCOPE OF WORK.
4) REFER TO ELECTRICAL / MECHANICAL DRAWINGS FOREXTENT OF NEW ELECTRICAL AND MECHANICALWORK. COORDINATE BETWEEN ALL DISCIPLINES.REPORT DISCREPANCIES TO ARCHITECT.
5) ALL PATCH PAINTING TO INCLUDE ENTIRE/COMPLETEWALL - EDGE TO EDGE & CORNER TO CORNER
NEW WORK NOTES:
FLOORS
INSTALL NEW DOOR, REFER TO DOOR SCHEDULE. PROVIDEHARDWARE PER SCHEDULE
DOORS AND WINDOWS
WALLS
NEW FLOOR FINISH, REFER TO FINISH SCHEDULE11
31
32
NEW WALL CONSTRUCTION, PREP AND PAINT, REFER TO WALL TYPESAND DETAILS.
MISC.
01
CEILINGS
PREP AND PAINT GYPSUM CEILING41
72
CLEAN EXISTING WINDOW SYSTEM, REPAIR WINDOW SILL AS NECESSARY
42
LIGHTING
74
NEW FLOOR BASE, REFER TO FINISH SCHEDULE12
RELOCATED PROJECTION SCREEN
PROVIDE NEW ACOUSTIC CEILING TILE AND GRID, REFER TO FINISHSCHEDULE
INSTALL NEW LIGHTING FIXTURES, REFER TO ELECTRICALDRAWINGS FOR FULL EXTENT OF WORK.
51
75
INSTALL NEW LOOSE FURNITURE, REFER WSUFUNITURE LIST
77
INSTALL NEW WHITE BOARD
INSTALL NEW FLAT SCREEN
33 DOOR TO RECEIVE NEW CARD READER, REFER TO ELECTRICAL DRAWINGS
78 INSTALL NEW ONE-WAY MIRROR. ARROW INDICATESDIRECTION OF VIEW
71 INSTALL NEW PLUMBING FIXTURE, REFER TO MEPDRAWINGS
34 WINDOW TO RECEIVE NEW BLACK-OUT SHADE
43 PROVIDE MINIMUM 4" SOUND ATTENUATING INSULATION ABOVECEILING 2 FEET EITHER SIDE OF WALLS AS SHOWN IN HATCHED AREAS.
INFILL AREA WHERE WALL WAS REMOVED WITH NEWFLOORING TO MATCH EXISTING
13
79 RELOCATE EXISTING TOILET ROOM ACCESSORIES(IE. SOAP DISPENSER, TOWEL DISPENSER, MIRRORS,ETC.) FOR NEW LAYOUT
35 DOOR CARD READER TO BE RE-CODED.
44 PROVIDE NEW 2'x2' CEILING ACCESS HATCH. COORDINATE LOCATIONWITH MECHANICAL EQUIPMENT
0101
01
01
01
1112
1112
1112
1112
1112
1112
1112
1112
1112
1112
1112
1112
1112
1112
1112
1112
1112
1112
1112
1112
1112
31 31 31
31
31
31
33
32
32
32 32 32
32
32
32
32
32
32
32
32
32
3232
323232
32
32323232
32
32
32
32
32
32
32
32
32 32 32 32 32 32 32
32
32
32
32
32
32323232
3434
34
34
34
32
32
32
32
32
717171
72
75
74
74
74 74
74
74
7474
74
74
74
74
7474
74
74
74
74
74
74
74 74 74 74
74
74
74
74
74
74
74
74
74
7474
74
74
74
74
74
78
78
78 78
7878
78
78
FOR
BID
S
project number:
sheet title:
sheet number:
approved
project:
coordination checked
location
drawn
checked
designed
issue: date:
key plan:
Rands House - RackhamRelocation
Nov. 13, 2018Owner Review 60% CD's
NM Project Number - 18113.0
WAYNE STATEUNIVERSITY
Facilities Planning and Management
5454 Cass Avenue
Detroit, MI 48202
Rands House
JK
JK
JK
DB
AG
WSU : 00
consultants:
Nov. 27, 2018Owner Review90% CD's
Dec. 04, 2018Review 100% CD's
Dec. 11, 2018For Bids
35
35
UP
UP
ref.
OFFICE107 CONFERENCE ROOM
103
OPENOFFICE100
PORCH
VEST
OPENOFFICE102
STORAGE106
STORAGE105PLANTER
OFFICE112
LOUNGE116
WAITING118
WOMEN124
UNISEXADA120
JC122
OFFICE126
OFFICE128
TREATMENT130
TREATMENT132
OBSERVATION134 CHILD
PLAYROOM136
TREATMENT140
OFFICE138
OFFICE142
TREATMENT144
OFFICE145
TREATMENT143
OFFICE141
IT137
OFFICE129
RESEARCHLAB125
COVERED AREA
OFFICE117
CL111
UP
UP
DN
D120
D118
CORRIDOR104
STAIR110
CORRIDOR108
WAITING109
CO
RR
IDO
R11
1STAIR150
CORRIDOR148
EXSTEXSTEXST
EXSTEXSTEXSTEXSTEXST
EXST
EXST
EXST
EXST
EXST
EXST
EXST
EXST
EXST
EXST
EXST
EXST
EXST
EXST
EXST
EXST
EXST
EXST
EXST
EXST
EXSTEXST
EXST
EXST
EXST
2'-0"
typ2'-
0"typ
2'-0"typ
xLF
xLF
xLF
xLF
xLF
xLF
xLF
xLF
xLF
xLF
xLF xLF xLF xLF xLF xLF
xLFxLFxLFxLF
xLFxLFxLFxLFxLFxLFxLFxLFxLFxLF
xLFxLFxLF
xLF xLF
xLF xLF
xLF xLF
xLF xLF
xLF
xLF
xLF
xLF
xLF
xLF
xLF
xLFxLF
xLF xLF
xLF xLF xLF xLF xLF
xLF xLF
xLF
xLF
xLF
xLF
xLF
xLF
xLF
A-301 FOR
BID
S
project number:
sheet title:
sheet number:
approved
project:
coordination checked
location
drawn
checked
designed
issue: date:
key plan:
Rands House - RackhamRelocation
Nov. 13, 2018Owner Review 60% CD's
NM Project Number - 18113.0
WAYNE STATEUNIVERSITY
Facilities Planning and Management
5454 Cass Avenue
Detroit, MI 48202
Rands House
JK
JK
JK
DB
AG
WSU : 00
consultants:
Nov. 27, 2018Owner Review90% CD's
Dec. 04, 2018Review 100% CD's
Dec. 11, 2018For Bids
01A-101 Scale: 1/8" = 1'-0"
First Floor Reflected Ceiling Plan - New WorkRands Building
Rands House 1st Floor ReflectedCeiling Plan - New Work
GENERAL NOTES
1) GENERAL CONTRACTOR AND SUB TRADES ARERESPONSIBLE TO VERIFY ALL EXISTING DIMENSIONSAND NOTIFY THE ARCHITECT OF ANY AND ALLDISCREPANCIES.
2) GENERAL CONTRACTOR SHALL BE FAMILIAR WITHENTIRE SCOPE OF NEW WORK AND PROCEED WITHWORK IN ACCORDANCE WITH NEW WORK.
3) NEW WORK FLOOR PLANS, WALL LAYOUTS, DOORAND WINDOW LOCATIONS AND PATTERNS HAVE BEENSHOWN FOR REFERENCE ONLY. THIS DRAWING ISNOT INTENDED TO SHOW ALL CONDITIONS, MATERIALPATTERNS AND LAYOUTS. INSPECT SITE PRIOR TOSTART OF CONSTRUCTION TO DETERMINE THE FULLSCOPE OF WORK.
4) REFER TO ELECTRICAL / MECHANICAL DRAWINGS FOREXTENT OF NEW ELECTRICAL AND MECHANICALWORK. COORDINATE BETWEEN ALL DISCIPLINES.REPORT DISCREPANCIES TO ARCHITECT.
5) ALL PATCH PAINTING TO INCLUDE ENTIRE/COMPLETEWALL - EDGE TO EDGE & CORNER TO CORNER
NEW WORK NOTES:
FLOORS
INSTALL NEW DOOR, REFER TO DOOR SCHEDULE. PROVIDEHARDWARE PER SCHEDULE
DOORS AND WINDOWS
WALLS
NEW FLOOR FINISH, REFER TO FINISH SCHEDULE11
31
32
NEW WALL CONSTRUCTION, PREP AND PAINT, REFER TO WALL TYPESAND DETAILS.
MISC.
01
CEILINGS
PREP AND PAINT GYPSUM CEILING41
72
CLEAN EXISTING WINDOW SYSTEM, REPAIR WINDOW SILL AS NECESSARY
42
LIGHTING
74
NEW FLOOR BASE, REFER TO FINISH SCHEDULE12
RELOCATED PROJECTION SCREEN
PROVIDE NEW ACOUSTIC CEILING TILE AND GRID, REFER TO FINISHSCHEDULE
INSTALL NEW LIGHTING FIXTURES, REFER TO ELECTRICALDRAWINGS FOR FULL EXTENT OF WORK.
51
75
INSTALL NEW LOOSE FURNITURE, REFER WSUFUNITURE LIST
77
INSTALL NEW WHITE BOARD
INSTALL NEW FLAT SCREEN
33 DOOR TO RECEIVE NEW CARD READER, REFER TO ELECTRICAL DRAWINGS
78 INSTALL NEW ONE-WAY MIRROR. ARROW INDICATESDIRECTION OF VIEW
71 INSTALL NEW PLUMBING FIXTURE, REFER TO MEPDRAWINGS
34 WINDOW TO RECEIVE NEW BLACK-OUT SHADE
43 PROVIDE MINIMUM 4" SOUND ATTENUATING INSULATION ABOVECEILING 2 FEET EITHER SIDE OF WALLS AS SHOWN IN HATCHED AREAS.
INFILL AREA WHERE WALL WAS REMOVED WITH NEWFLOORING TO MATCH EXISTING
13
79 RELOCATE EXISTING TOILET ROOM ACCESSORIES(IE. SOAP DISPENSER, TOWEL DISPENSER, MIRRORS,ETC.) FOR NEW LAYOUT
35 DOOR CARD READER TO BE RE-CODED.
44 PROVIDE NEW 2'x2' CEILING ACCESS HATCH. COORDINATE LOCATIONWITH MECHANICAL EQUIPMENT
41
41
41
41
41
41
41
41
41
41
42
42
42
42
42
42
42
42
42
42 42 42 42 42 42
42
424242
42
42
42
42
42
42
43
43
43
43
43
DN
222
225
OFFICE207
UP
OPEN
TREATMENT232
OBSERVATION234
OFFICE205
OFFICE203
OPENOFFICE201
OPENOFFICE200
DN
STORAGE200.1
OPENOFFICE202
UP
DN
TREATMENT212
OFFICE214
CHILDREN'SGROUP ROOM218
UNISEX ADA220
WOMEN224
ADULTGROUP ROOM226
ADULTGROUP ROOM230
TREATMENT236
TREATMENT238 OBSERVATION
247
TREATMENT246
TREATMENT241
OBSERVATION242 COMFERENCE/
GROUP ROOM243
TREATMENT217
OBSERVATION219
TREATMENT225
MECH227
IT229
OPENOFFICE245
OPENOFFICE240 OFFICE
244
CORRIDOR204
CORRIDOR209
STAIR210
CO
RR
IDO
R21
1
CORRIDOR248
STAIR250
CORRIDOR208
OFFICE244
EXST
LF
LF
LF
LF
LF
LF
EXSTEXST
EXST
EXST
EXST
EXST
EXST
EXST
EXST
EXST
EXST
EXST
EXST
EXST
EXST
EXST
EXST
EXST EXST
EXST EXST EXST
EXST
EXST
EXST
xLF
xLF
xLF
xLF
xLFxLFxLFxLFxLFxLFxLF
xLF
xLF
xLF
xLF
xLF
xLF
xLF
xLF
xLF
xLFxLFxLF
xLFxLF
xLF xLF
xLFxLF
xLF xLF
xLF xLF
xLFxLF
xLF xLF
xLF
xLF
xLF xLF
xLFxLF
xLF xLF
xLF xLF
xLF xLF xLF
xLF xLF xLF xLF
xLF xLF xLF xLF
xLFxLF
xLF
xLF
xLF
xLF
xLF
xLF
A-302 FOR
BID
S
project number:
sheet title:
sheet number:
approved
project:
coordination checked
location
drawn
checked
designed
issue: date:
key plan:
Rands House - RackhamRelocation
Nov. 13, 2018Owner Review 60% CD's
NM Project Number - 18113.0
WAYNE STATEUNIVERSITY
Facilities Planning and Management
5454 Cass Avenue
Detroit, MI 48202
Rands House
JK
JK
JK
DB
AG
WSU : 00
consultants:
Nov. 27, 2018Owner Review90% CD's
Dec. 04, 2018Review 100% CD's
Dec. 11, 2018For Bids
01A-101 Scale: 1/8" = 1'-0"
Second Floor Reflected Ceiling Plan - New WorkRands Building
Rands House 2nd Floor ReflectedCeiling Plan - New Work
GENERAL NOTES
1) GENERAL CONTRACTOR AND SUB TRADES ARERESPONSIBLE TO VERIFY ALL EXISTING DIMENSIONSAND NOTIFY THE ARCHITECT OF ANY AND ALLDISCREPANCIES.
2) GENERAL CONTRACTOR SHALL BE FAMILIAR WITHENTIRE SCOPE OF NEW WORK AND PROCEED WITHWORK IN ACCORDANCE WITH NEW WORK.
3) NEW WORK FLOOR PLANS, WALL LAYOUTS, DOORAND WINDOW LOCATIONS AND PATTERNS HAVE BEENSHOWN FOR REFERENCE ONLY. THIS DRAWING ISNOT INTENDED TO SHOW ALL CONDITIONS, MATERIALPATTERNS AND LAYOUTS. INSPECT SITE PRIOR TOSTART OF CONSTRUCTION TO DETERMINE THE FULLSCOPE OF WORK.
4) REFER TO ELECTRICAL / MECHANICAL DRAWINGS FOREXTENT OF NEW ELECTRICAL AND MECHANICALWORK. COORDINATE BETWEEN ALL DISCIPLINES.REPORT DISCREPANCIES TO ARCHITECT.
5) ALL PATCH PAINTING TO INCLUDE ENTIRE/COMPLETEWALL - EDGE TO EDGE & CORNER TO CORNER
NEW WORK NOTES:
FLOORS
INSTALL NEW DOOR, REFER TO DOOR SCHEDULE. PROVIDEHARDWARE PER SCHEDULE
DOORS AND WINDOWS
WALLS
NEW FLOOR FINISH, REFER TO FINISH SCHEDULE11
31
32
NEW WALL CONSTRUCTION, PREP AND PAINT, REFER TO WALL TYPESAND DETAILS.
MISC.
01
CEILINGS
PREP AND PAINT GYPSUM CEILING41
72
CLEAN EXISTING WINDOW SYSTEM, REPAIR WINDOW SILL AS NECESSARY
42
LIGHTING
74
NEW FLOOR BASE, REFER TO FINISH SCHEDULE12
RELOCATED PROJECTION SCREEN
PROVIDE NEW ACOUSTIC CEILING TILE AND GRID, REFER TO FINISHSCHEDULE
INSTALL NEW LIGHTING FIXTURES, REFER TO ELECTRICALDRAWINGS FOR FULL EXTENT OF WORK.
51
75
INSTALL NEW LOOSE FURNITURE, REFER WSUFUNITURE LIST
77
INSTALL NEW WHITE BOARD
INSTALL NEW FLAT SCREEN
33 DOOR TO RECEIVE NEW CARD READER, REFER TO ELECTRICAL DRAWINGS
78 INSTALL NEW ONE-WAY MIRROR. ARROW INDICATESDIRECTION OF VIEW
71 INSTALL NEW PLUMBING FIXTURE, REFER TO MEPDRAWINGS
34 WINDOW TO RECEIVE NEW BLACK-OUT SHADE
43 PROVIDE MINIMUM 4" SOUND ATTENUATING INSULATION ABOVECEILING 2 FEET EITHER SIDE OF WALLS AS SHOWN IN HATCHED AREAS.
INFILL AREA WHERE WALL WAS REMOVED WITH NEWFLOORING TO MATCH EXISTING
13
79 RELOCATE EXISTING TOILET ROOM ACCESSORIES(IE. SOAP DISPENSER, TOWEL DISPENSER, MIRRORS,ETC.) FOR NEW LAYOUT
35 DOOR CARD READER TO BE RE-CODED.
44 PROVIDE NEW 2'x2' CEILING ACCESS HATCH. COORDINATE LOCATIONWITH MECHANICAL EQUIPMENT
414141
41
41
41
41
41
41
41
41
41
41
41
41
41
41
41
41
41
41 41
41
41
41
4141
414141
41
51
5151
5151
51
44 44 44
DIRECTION OF AIR FLOW
FLEXIBLE DUCT
MANUAL VOLUME DAMPER
RISE IN DIRECTION OF AIR FLOWR
DUCT CAP
DROP IN DIRECTION OF AIR FLOWD
DUCT DOWN
DUCT UP
SUPPLY/OUTSIDE AIR DUCT SECTION
RETURN AIR DUCT SECTION
EXHAUST/RELIEF AIR DUCT SECTION
4-WAY DIFFUSER WITH BLANKOFF IN ONE DIRECTION
CD-16/115
AIR TERMINAL PROPERTIES SYMBOLNECK SIZE/CFM
TERMINAL AIR BOX (REFER TO SCHEDULE)###
### TERMINAL AIR BOX w/REHEAT COIL (REFER TO SCHEDULE)
OPPOSED BLADE DAMPER (REFER TO SCHEDULE)
PARALLEL BLADE DAMPER (REFER TO SCHEDULE)
DIFFERENTIAL PRESSURE SENSOR
CARBON MONOXIDE SENSORC
CARBON DIOXIDE SENSORC2
HUMIDISTAT SENSORH
HUMIDISTAT/SENSOR (DUCT MOUNTED)H
OCCUPANCY SENSORO
PRESSURE SENSOR/MONITORP
PRESSURE SENSOR (DUCT MOUNTED)P
THERMOSTAT/SENSORT
TEMPERATURE SENSOR (DUCT MOUNTED)T
THERMOSTAT/SENSOR WITH HEAVY DUTY ENCLOSURET
VENTILATION SYMBOL LIST
SYMBOL: DESCRIPTION:
AIRFLOW MEASUREMENT SYMBOLXX - AHU SYMBOLY - SEQUENTIAL NUMBER
XX-Y
NOT ALL SYMBOLS MAY APPLY.
VENTILATION ABBREVIATION KEY
ABBR: DESCRIPTION:
AD ACCESS DOOR
ABOVE FINISHED FLOORAFF
NC NEW CONNECTION
CFSD CONTROL/FIRE/SMOKE DAMPER
EA EXHAUST/RELIEF AIR
FD FIRE DAMPER
FOB FLAT ON BOTTOM
FOT FLAT ON TOP
FSD FIRE/SMOKE DAMPER
MA MIXED AIR
OA OUTSIDE AIR
RA RETURN AIR
SA SUPPLY AIR
SD SMOKE DAMPER
UC-1 DOOR UNDERCUT BY OTHERS (1" TYPICAL)
TERMINAL AIR BOXTAB
TYPICALTYP
UNO UNLESS NOTED OTHERWISE
CEILING DIFFUSER - EXISTINGCD-E
N.C. NORMALLY CLOSED
NOT IN CONTRACTNIC
NORMALLY OPENN.O.
PLAN OR DETAIL NUMBER
PLAN OR DETAIL NAME
PLAN OR DETAIL SCALE
NAME
1VIEW NAME1/8" = 1'-0"
LEVEL NAME
10' - 0" HEIGHT ABOVE PROJECT 0' - 0"
1 INDICATES NOTE USED TO DESCRIBE ADDITIONAL INFORMATION ABOUT WORK REQUIRED, SPECIFIC TO THE SHEET AND/OR DETAIL
NO R
HT
INDICATES DIRECTION OF TRUE NORTH
VIEW KEY
NEW WORK BY THIS CONTRACTOR (DARK SOLID LINE)
NEW WORK BY OTHERS AND/OR EXISTING TO REMAIN (LIGHT SOLID LINE)
EXISTING TO BE REMOVED BY THIS CONTRACTOR(DARK SHORT DASHED LINE)
LINE TYPE KEY:TEMPERATURE CONTROLS CONTRACTORT.C.C.
SECURITY CONTRACTORS.C.
AUDIO/VISUAL CONTRACTORA.V.C.
ASBESTOS ABATEMENT CONTRACTOR
PLUMBING CONTRACTORP.C.
GENERAL CONTRACTORG.C.
MECHANICAL CONTRACTORM.C.
VENTILATION CONTRACTORV.C.
ELECTRICAL CONTRACTORE.C.
A.C.
CONTRACTOR ABBREVIATION KEY
ABBR: DESCRIPTION:
TECHNOLOGY CONTRACTORT.C.
HEATING CONTRACTORH.C.
MECHANICAL GENERAL NOTES:THESE NOTES APPLY TO ALL MECHANICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED TO, FIRE PROTECTION, PLUMBING, MEDICAL GAS, VENTILATION, PIPING AND TEMPERATURE CONTROL.
1. DRAWINGS SHOWING LOCATIONS OF EQUIPMENT, DUCTWORK, PIPING, ETC. ARE DIAGRAMMATIC AND MAY NOT ALWAYS REFLECT EXACT INSTALLATION CONDITIONS. DRAWINGS SHOW THE GENERAL ARRANGEMENT OF DUCTWORK, PIPING, EQUIPMENT, ETC., AND MAY NOT INCLUDE ALL OFFSETS AND FITTINGS REQUIRED FOR COMPLETE INSTALLATION. THE DRAWINGS SHALL BE FOLLOWED AS CLOSELY AS ACTUAL BUILDING CONSTRUCTION AND THE WORK OF OTHERS WILL PERMIT.
2. DO NOT SCALE DRAWINGS. VERIFY ALL DIMENSIONS AND CLEARANCES FROM ARCHITECTURAL, STRUCTURAL, SUBMITTALS, AND OTHER APPROPRIATE DRAWINGS OR PHYSICALLY AT SITE. REVIEW ALL DRAWINGS, INCLUDING THOSE OF OTHER TRADES.
3. COORDINATE ALL WORK WITH ALL OTHER TRADES PRIOR TO INSTALLATION TO PROVIDE CLEARANCES REQUIRED FOR OPERATION, MAINTENANCE, CODE COMPLIANCE, AND TO VERIFY NON-INTERFERENCE WITH OTHER WORK. DO NOT FABRICATE PRIOR TO VERIFICATION OF NECESSARY CLEARANCES FOR ALL TRADES. BRING ANY INTERFERENCES OR CONFLICTS TO THE ATTENTION OF THE ARCHITECT/ENGINEER BEFORE PROCEEDING WITH FABRICATION OR EQUIPMENT ORDERS.
4. REVIEW SPACE REQUIREMENTS OF EQUIPMENT SPECIFIED OR SUBSTITUTED AND MAKE REASONABLE ACCOMMODATIONS IN LAYOUT AND POSITIONING TO PROVIDE PROPER ACCESS.
5. ANY CHANGES REQUIRED TO ELIMINATE CONFLICTS OR THAT RESULT FROM A FAILURE TO COORDINATE SHALL BE MADE BY THE CONTRACTOR WITHOUT ADDITIONAL COST OR EXPENSE TO OTHERS.
6. EACH CONTRACTOR IS RESPONSIBLE FOR ALL COSTS ASSOCIATED WITH ELECTRICAL CHANGES REQUIRED FOR EQUIPMENT PROPOSED THAT DIFFERS FROM THE BASIS OF DESIGN.
7. REFER TO ARCHITECTURAL REFLECTED CEILING PLAN, ELECTRICAL, TECHNOLOGY AUDIO/VISUAL, AND OTHER MECHANICAL PLANS FOR EXACT LOCATIONS OF ALL CEILING MOUNTED DEVICES, OTHER THAN SPRINKLERS.
8. EACH CONTRACTOR IS RESPONSIBLE FOR DAMAGE CAUSED BY THEIR ACTIONS TO WALLS, FLOORS, CEILINGS, AND ROOFS. THE CONTRACTOR WHOSE WORK CAUSES DAMAGE IS RESPONSIBLE FOR PATCHING TO MATCH ORIGINAL CONSTRUCTION, FIRE RATING, AND FINISH.
9. IN AREAS WITH DRYWALL CEILINGS COORDINATE LOCATIONS OF ACCESS PANELS WITH THE GC FOR ACCESS TO VALVES, DUCTWORK ACCESSORIES, DAMPERS, ETC. COORDINATE PANEL TYPE AND COLOR WITH ARCHITECT. NOTIFY THE GC OF THE REQUIRED ACCESS PANELS PRIOR TO BIDDING.
10. SEAL ALL FLOOR, WALL, AND ROOF PENETRATIONS AIRTIGHT WHERE CONDUITS, PIPING, AND DUCTS PENETRATE. PENETRATIONS THROUGH EXTERIOR WALLS AND ROOF SHALL BE SEALED AIRTIGHT WITH WATERPROOFING MATERIALS RECOMMENDED BY MANUFACTURER FOR OUTDOOR USE.
11. CAULK ALL PIPE AND DUCT PENETRATIONS OF FULL HEIGHT NON-FIRE RATED WALL, PARTITION, FLOOR, AND ROOF ASSEMBLIES. THIS IS ESSENTIAL TO PREVENT NOISE TRANSMISSION FROM ONE ROOM TO ANOTHER AND TO PROVIDE THE DESIRED NC LEVELS WITHIN ROOMS.
12. WHERE PIPES AND DUCTS ARE SHOWN TO PENETRATE FLOORS, PROVIDE SLEEVED OPENINGS WITH THE TOP EDGE RAISED ABOVE FLOOR SURFACE IN ACCORDANCE WITH ALL RELEVANT SPEC SECTIONS. SEAL SLEEVE PERIMETER TO BE WATERTIGHT.
13. EQUIPMENT SIZES AND SERVICE CLEARANCE REQUIREMENTS VARY AMONG DIFFERENT MANUFACTURERS. CONSULT APPROVED SHOP DRAWINGS FOR EQUIPMENT SIZES AND REQUIRED SERVICE CLEARANCES. COORDINATE WITH LAYOUT OF EQUIPMENT PADS, PIPING, DUCTWORK, ETC.
14. DO NOT BLOCK TUBE PULL OR EQUIPMENT SERVICE CLEARANCES. 15. MAINTAIN MINIMUM 3'-6” CLEARANCE IN FRONT OF ALL ELECTRICAL PANELS, MOTOR
STARTERS, SWITCHES, AND DISCONNECTS.16. PROVIDE CONCRETE EQUIPMENT PAD FOR ALL FLOOR MOUNTED EQUIPMENT. PAD SHALL
EXTEND MINIMUM 6” BEYOND ALL SIDES OF EQUIPMENT.17. DO NOT SUPPORT EQUIPMENT, PIPING, OR DUCTWORK FROM METAL DECKING OR OTHER
NON-STRUCTURAL BUILDING ELEMENTS. ANCHORS EMBEDDED IN CONCRETE SHALL BE CRACKED CONCRETE APPROVED IN ACCORDANCE WITH SPECIFICATIONS.
MECHANICAL PHASING NOTES:THESE NOTES APPLY TO ALL MECHANICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED TO, FIRE PROTECTION, PLUMBING, MEDICAL GAS, VENTILATION, PIPING AND TEMPERATURE CONTROL.
1. REFER TO ARCHITECTURAL DRAWINGS FOR GENERAL DESCRIPTION OF PHASES. REFER TO CONSTRUCTION MANAGER'S/GENERAL CONTRACTOR'S/ARCHITECT'S INSTRUCTIONS FOR MORE DETAILS AND PHASING SCHEDULES AND FOR CONCURRENT WORK. MECHANICAL, ELECTRICAL AND TECHNOLOGY DRAWINGS DEPICT THE INTENT OF THE FINAL DESIGN. THE MECHANICAL, ELECTRICAL, AND TECHNOLOGY DRAWINGS DO NOT DEPICT THE MEANS AND METHODS TO MEET THE REQUIREMENTS OF THE PHASING CRITERIA.
2. REVIEW PROJECT PHASING PLANS TO COORDINATE DEMOLITION WORK, OUTAGES, ETC. WITH AFFECTED ADJACENT AREAS.
3. PROVIDE TEMPORARY DUCTWORK, PIPING, SHUTOFF VALVES, ZONE VALVES, ZONE ALARMS, ETC. AS NEEDED TO MAINTAIN SERVICE TO ALL AREAS DURING ALL PHASES OF PROJECT.
4. INSTALL TEMPORARY DUCTWORK, PIPING, SHUTOFF VALVES, ETC. AS NECESSARY TO KEEP ALL OCCUPIED SPACES OPERATIONAL THROUGHOUT ALL PHASES OF THE PROJECT
5. PHASE DEMOLITION WORK TO MINIMIZE DOWNTIME.
MECHANICAL RENOVATION NOTES:THESE NOTES APPLY TO ALL MECHANICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED TO, FIRE PROTECTION, PLUMBING, MEDICAL GAS, VENTILATION, PIPING AND TEMPERATURE CONTROL.
1. EXISTING CONDITIONS ARE SHOWN BASED ON INFORMATION OBTAINED FROM FIELD SURVEYS, EXISTING BUILDING DOCUMENTS, AND STAFF. VERIFY EXISTING CONDITIONS AND REPORT ANY CONFLICTS BEFORE PROCEEDING.
2. NOT ALL EXISTING DUCTWORK AND PIPING IS SHOWN. VERIFY EXISTING CONDITIONS BEFORE STARTING WORK. NOTIFY ENGINEER OF ANY CONFLICTS WITH NEW WORK.
3. FIELD VERIFY THE AVAILABLE CLEARANCES FOR DUCTWORK AND PIPING BEFORE FABRICATION. RISES AND DROPS MAY BE NECESSARY BECAUSE OF EXISTING FIELD CONDITIONS. EACH CONTRACTOR SHALL FIELD VERIFY ACCESSIBILITY TO THE AREA OF HIS/HER WORK AND SHALL NOTIFY THE GENERAL CONTRACTOR CONSTRUCTION MANAGER ARCHITECT/ENGINEER PRIOR TO BIDDING IF OTHER UTILITIES ARE REQUIRED TO BE REMOVED OR RELOCATED TO ALLOW ACCESS TO HIS/HER AREA OF WORK.
4. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR CUTTING, REMOVAL AND PATCHING OF ROOFS, WALLS, AND FLOORS ASSOCIATED WITH WORK BY ALL CONTRACTORS. CONTRACTORS SHALL NOTIFY THE GC OF AFFECTED AREAS PRIOR TO BIDDING EACH CONTRACTOR SHALL CUT AND PATCH ROOFS, WALLS, AND FLOORS ASSOCIATED WITH HIS WORK.
5. EACH CONTRACTOR SHALL CUT AND PATCH ROOFS, WALLS, AND FLOORS ASSOCIATED WITH HIS WORK.
6. WHERE EXISTING MECHANICAL SYSTEMS ARE LOCATED IN AREAS THAT CONFLICT WITH NEW EQUIPMENT, PIPING, OR DUCTWORK TO BE INSTALLED, EACH CONTRACTOR SHALL EITHER ARRANGE NEW EQUIPMENT, PIPING, OR DUCTWORK IN SUCH A FASHION THAT IT DOES NOT CONFLICT WITH EXISTING SYSTEMS, OR REWORK EXISTING MECHANICAL SYSTEMS TO ALLOW FOR INSTALLATION OF NEW EQUIPMENT, PIPING, OR DUCTWORK.
7. PROVIDE TEMPORARY CONNECTIONS TO MAINTAIN EXISTING SYSTEMS IN SERVICE DURING CONSTRUCTION. MAINTAIN ACCESS TO EXISTING MECHANICAL INSTALLATIONS THAT REMAIN ACTIVE.
8. OBTAIN PERMISSION FROM OWNER BEFORE SHUTTING DOWN ANY SYSTEM FOR ANY REASON. MAINTAIN SERVICE TO ALL COMPONENTS THAT ARE TO REMAIN UNTIL NEW SYSTEMS ARE INSTALLED.
9. MAINTAIN EXISTING SYSTEM IN SERVICE UNTIL NEW SYSTEM IS COMPLETE AND READY FOR TIE IN AND SWITCHOVER. DRAIN SYSTEM ONLY TO MAKE SWITCHOVERS AND CONNECTIONS. OBTAIN PERMISSION FROM OWNER BEFORE PARTIALLY OR COMPLETELY DRAINING SYSTEM. MAKE CHANGEOVER TO NEW SYSTEMS WITH MINIMUM OUTAGE.
10. DISCONNECT AND REMOVE MECHANICAL DEVICES AND EQUIPMENT SERVING EQUIPMENT THAT HAS BEEN REMOVED.
1. THE SIZE OF EACH BRANCH DUCT TO A TERMINAL AIR BOX (TAB) SHALL MATCH THE TAB’S INLET SIZE UNLESS THE BRANCH IS GREATER THAN 6 FEET IN LENGTH, IN WHICH CASE THE BRANCH SHOULD BE INCREASED ONE DUCT SIZE, OR NOTED OTHERWISE.
2. ALIGN TEMPERATURE SENSORS WITH LIGHT SWITCHES AND WHEN IN CLOSE PROXIMITY TO EACH OTHER.
3. PROVIDE ACCESS DOORS AT ALL DUCT MOUNTED EQUIPMENT.4. EXISTING AIR INLET AND OUTLET CFM SHOWN ON DRAWINGS ARE FROM EXISTING
DRAWINGS, AND ARE FOR REFERENCE ONLY. CONTRACTOR SHALL USE PRE-BALANCE VALUES, AND NOT EXISTING CFM SHOWN ON DRAWINGS.
5. CONTRACTOR MAY REUSE PORTIONS OF EXISTING DUCT PROVIDED SIZES AND PRESSURE CLASSES ARE CORRECT, DUCT IS THOROUGHLY CLEANED AND FREE OF DEFECTS, AND ALL TRANSVERSE JOINTS, LONGITUDINAL SEAMS, AND DUCT WALL PENETRATIONS ARE SEALED AS SPECIFIED FOR NEW DUCTWORK.
6. CLEAN ALL SUPPLY, RETURN, AND EXHAUST DUCTWORK UPSTREAM OF ALL NEW CONNECTIONS PER SPECIFICATION SECTION 23 31 00.
VENTILATION GENERAL NOTES:
1. BEFORE ANY DEMOLITION WORK IS BEGUN A COMPLETE AIR BALANCE TEST SHALL BE PERFORMED BY THE TESTING, ADJUSTING AND BALANCING (TAB) CONTRACTOR ON EXISTING AIR HANDLERS AND EXHAUST FANS SERVING THE AREAS AFFECTED BY CONSTRUCTION. EQUIPMENT TO BE DEMOLISHED DOES NOT REQUIRE TESTING. PROVIDE AIR BALANCE TESTING ONLY ON EQUIPMENT THAT WILL CONTINUE TO BE USED TO SERVE RENOVATED AREAS AFTER THE CONSTRUCTION PHASE IS COMPLETED.
2. PROVIDE DUCT TRAVERSE READINGS AT LOCATIONS DESIGNATED ON THE DRAWINGS BY THE "AIRFLOW MEASUREMENT SYMBOL". THOSE MEASUREMENTS SHALL BE INCLUDED IN THE PRE DEMOLITION REPORT AND SHALL BE DESIGNATED WITH THE IDENTIFIER AS MARKED ON THE DRAWINGS. READINGS SHALL BE DESIGNATED WITH THE ROOM NAME AND NUMBER AS MARKED ON THE DRAWINGS. IF FLOOR PLANS DO NOT HAVE UNIQUE ROOM NAMES AND NUMBERS, TAB CONTRACTOR SHALL INCLUDE FLOOR PLAN WITH UNIQUE NUMBER DESIGNATIONS ASSIGNED TO READINGS THAT MATCH THOSE USED IN THE FINAL PRE-DEMOLITION REPORT. DRAWINGS THAT ARE HAND-MARKED WITH RED INK ARE ACCEPTABLE, PROVIDED THEY ARE LEGIBLE.
3. IN THE EVENT A DUCT TRAVERSE LOCATION AS MARKED ON THIS PLAN IS INACCESSIBLE FOR MEASUREMENT, THE TAB CONTRACTOR SHALL PERFORM THE TRAVERSE AT AN ALTERNATE LOCATION OR SHALL TAKE MULTIPLE DUCT TRAVERSES AND/OR READINGS AS REQUIRED TO DETERMINE THE AIRFLOW READING WHERE THE DUCT TRAVERSE SYMBOL IS SHOWN. IN THE EVENT TRAVERSES ARE TAKEN AT ALTERNATE LOCATION(S), TAB CONTRACTOR SHALL INCLUDE A DRAWING THAT SHOWS THE LOCATIONS WHERE THE ACTUAL MEASUREMENTS WERE TAKEN.
4. TAKE A DUCT STATIC PRESSURE READING AT EACH LOCATION WHERE A DUCT TRAVERSE READING IS TAKEN AND INCLUDE IN THE FINAL PRE-DEMOLITION TAB REPORT.
5. TAB CONTRACTOR SHALL COMPILE AND SUBMIT FOUR COPIES OF THE FINAL PRE-DEMOLITION REPORT WITHIN 10 WORKING DAYS AFTER THE FIELD MEASUREMENTS ARE COMPLETED. FINAL TAB REPORT SHALL BE SUBMITTED FOR REVIEW TO THE ARCHITECT/ENGINEER. TESTING SHALL INCLUDE ALL ITEMS REQUIRED IN THE SPECIFICATIONS.
6. TAB CONTRACTOR SHALL PROVIDE DUCT TRAVERSE READINGS AT LOCATIONS DESIGNATED ON THE DRAWINGS BY THE "AIRFLOW MEASUREMENT SYMBOL". THOSE MEASUREMENTS SHALL BE INCLUDED IN THE POST-CONSTRUCTION REPORT AND SHALL BE DESIGNATED WITH THE IDENTIFIER AS MARKED ON THE CONSTRUCTION DRAWINGS. GRILLE AND DIFFUSER READINGS SHALL BE DESIGNATED WITH THE ROOM NAME AND NUMBER AS MARKED ON THE DRAWINGS. IF THE DRAWINGS DO NOT HAVE UNIQUE ROOM NAMES AND NUMBERS, TAB CONTRACTOR SHALL INCLUDE FLOOR PLANS WITH UNIQUE NUMBER DESIGNATIONS ASSIGNED TO TRAVERSES, GRILLES, AND DIFFUSERS THAT MATCH THOSE USED IN THE FINAL PRE-DEMOLITION REPORT. SIMILAR ROOM NAMES, NUMBERS, OR DESIGNATIONS SHALL BE USED TO SIMPLIFY THE CROSS- REFERENCING OF READINGS TAKEN BETWEEN PRE-DEMOLITION AND POST-CONSTRUCTION REPORTS.
7. BALANCING CONTRACTOR SHALL PRE-BALANCE ALL EXISTING SYSTEMS TO REMAIN PER SPECIFICATION SECTION 23 05 93. BALANCE READINGS WILL BE REQUIRED AT AIR OUTLETS AND DUCT TRAVERSES TO VERIFY EXISTING AIRFLOW TO UNAFFECTED SPACES.
TAB PRE-DEMOLITION NOTES:
1. AFTER CONSTRUCTION ACTIVITIES ARE COMPLETE, TESTING, ADJUSTING (TAB) AND BALANCING CONTRACTOR SHALL REBALANCE AIR HANDLING UNITS AND EXHAUST FANS AS REQUIRED TO ACHIEVE THE NEW AIRFLOW VALUES SHOWN ON THE CONSTRUCTION DRAWINGS.
2. AREAS SERVED BY THIS EQUIPMENT WHICH WERE NOT RENOVATED SHALL BE RE-BALANCED TO THE AIRFLOW RATES MEASURED BEFORE THE RENOVATION OCCURRED (REFER TO THE FINAL PRE- DEMOLITION REPORT).
3. IF DUCT TRAVERSE LOCATION AS MARKED ON THE DRAWINGS IS INACCESSIBLE FOR MEASUREMENT, THE TAB CONTRACTOR SHALL PERFORM THE TRAVERSE AT AN ALTERNATE LOCATION OR SHALL TAKE MULTIPLE DUCT TRAVERSES AND/OR GRILLE READINGS AS REQUIRED TO DETERMINE THE FLOW RATE. IN THE EVENT TRAVERSES ARE TAKEN AT AN ALTERNATE LOCATION(S), TAB CONTRACTOR SHALL INCLUDE A DRAWING THAT SHOWS THE LOCATIONS WHERE THE ACTUAL MEASUREMENTS WERE TAKEN.
4. A DUCT STATIC PRESSURE READING SHALL BE TAKEN AT EACH LOCATION WHERE A DUCT TRAVERSE READING IS TAKEN AND SHALL BE INCLUDED IN THE FINAL POST-CONSTRUCTION TAB REPORT.
5. TAB CONTRACTOR SHALL COMPILE AND SUBMIT COPIES OF THE FINAL POST-CONSTRUCTION TAB REPORT AS REQUIRED BY SECTION 23 05 93.
6. THE FINAL POST CONSTRUCTION REPORT SHALL INCLUDE ALL ITEMS REQUIRED IN THE SPECIFICATIONS.
TAB POST-CONSTRUCTION NOTES:
BUILDING CODE: MBC 2015 EDITION
FIRE CODE: NFPA 13: 2013 EDITION
PLUMBING CODE: MBC 2015 EDITION
MECHANICAL CODE: MMC 2015 EDITION
ELECTRICAL CODE: NFPA 70 (NEC) 2016EDITION
LIFE SAFETY CODE: NFPA 101 2015 EDITION
ENERGY CONSERVATION CODE: ASHRAE 90.1 2013
HEALTH DEPARTMENT CODE: CURRENT EDITION
LOCAL BUILDING CODE: CURRENT EDITION
APPLICABLE CODES
CONTRACTOR SHALL COMPLY WITH APPLICABLE CODES AND LOCAL AMENDMENTS.
VENTILATION SHEET INDEXMH-000 VENTILATION COVERSHEET
MHD-101 FIRST FLOOR DEMOLITION - VENTILATION
MHD-102 SECOND FLOOR DEMOLITION - VENTILATION
MH-101 FIRST FLOOR PLAN - VENTILATION
MH-102 SECOND FLOOR PLAN - VENTILATION
MH-300 VENTILATION SCHEDULE
AREA OF WORKNO SCALE
FLOOR LEVEL
project number:
sheet title:
sheet number:
approved
project:
coordination checked
location
drawn
checked
designed
issue: date:
key plan:
WAYNE STATE
UNIVERSITYFacilities Planning and Management
5454 Cass Avenue
Detroit, MI 48202
FO
R B
IDS
consultants:
NM Project Number - 18113.0
Rands Building
IMEG Project Number -
Rands House - RackhamRelocation
WSU : 00
- -
12/1
0/2
018 1
1:4
1:2
3 A
M
MH-000
VENTILATION COVERSHEET
PETPAPPETPAP
KIRSAI
18004050.01
PETPAP
PETPAP
WS
U R
an
ds B
ldg
Rackh
am
Relo
cati
on
18004050.0
1
REFERENCE SCALE IN INCHES
0 1 2 3
PROJECT #
IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
18004050.01
Owner Review 60% CD's Nov. 13, 2018
Owner Review 90% CD's Nov. 27, 2018
100% CD's Dec. 04, 2018
For Bids Dec. 11, 2018
1 2 3 41.9 2.5 3.1 3.2 3.5 3.8
A
b
c
d
e
f
a10
a9
b4
c.1
c.2
c.3
c.4
e.8
1
EXISTING 10x6 EG
200 CFM
EXISTING 10x6 EG
200 CFM
6x6 EG
75 CFM
EXISTING 14x10 TOILET
EXH. DUCT UP
3'-2"
16x1
0 S
A
20x1
8 S
A
10x6 EA
10x6 EA
14x10 EA
(E0 SECURITY FENCE
(E) AIR-COOLED
CONDENSING UNITS
AREA OF WORKNO SCALE
FLOOR LEVEL
project number:
sheet title:
sheet number:
approved
project:
coordination checked
location
drawn
checked
designed
issue: date:
key plan:
WAYNE STATE
UNIVERSITYFacilities Planning and Management
5454 Cass Avenue
Detroit, MI 48202
FO
R B
IDS
consultants:
NM Project Number - 18113.0
Rands Building
IMEG Project Number -
Rands House - RackhamRelocation
WSU : 00
- -
12/1
0/2
018 1
1:4
1:2
8 A
M
MHD-101
FIRST FLOOR DEMOLITION -
VENTILATION
PETPAPPETPAP
KIRSAI
18004050.01
PETPAP
PETPAP
WS
U R
an
ds B
ldg
Rackh
am
Relo
cati
on
18004050.0
1
REFERENCE SCALE IN INCHES
0 1 2 3
PROJECT #
IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
18004050.01
SHEET GENERAL NOTES :
1. COORDINATE ALL DEMOLITION WORK WITH ARCHITECTURAL AND ELECTRICAL AND ELECTRICAL DEMOLITION WITH OWNER'S PROJECT REPRESENTATIVE.
2. COORDINATE ANY SHUTDOWNS OF EXISTING SERVICES OR EQUIPMENT WITH OWNER. PERFORM SHUTDOWNS AT A SCHEDULED TIME AS TO MINIMIZE DISRUPTION OF BUILDING OPERATIONS.
3. REMOVE ALL INDICATED DUCTWORK AND EQUIPMENT COMPLETELY INCLUDING ALL RELATED ITEMS INCLUDING HANGERS, SUPPORTS, CONTROLS AND ACCESSORIES.
4. CAP ALL THE OPEN ENDED DUCTWORK. DO NOT LEAVE ANY ABONDONED DUCT WORK IN THE AREA OF WORK.
KEYNOTES:
1. DISCONNECT AND REMOVE EXISTING FINNED TUBE RADIATOR. CLEAN AND PREPARE FOR NEW INSTALLATION.
#
NO R
HT
1/8" = 1'-0"1 FIRST FLOOR DEMOLITION - VENTILATION
For Bids Dec. 11, 2018
WHITE BOARD
projectionscreen
T
T
1 2 3 41.9 2.5 3.1 3.2 3.5 3.8
A
b
c
d
e
f
a10
a9
b4
c.1
c.2
c.3
c.4
e.8
FD IN FLRFD
1
2
3
4
4
2
AREA OF WORKNO SCALE
FLOOR LEVEL
project number:
sheet title:
sheet number:
approved
project:
coordination checked
location
drawn
checked
designed
issue: date:
key plan:
WAYNE STATE
UNIVERSITYFacilities Planning and Management
5454 Cass Avenue
Detroit, MI 48202
FO
R B
IDS
consultants:
NM Project Number - 18113.0
Rands Building
IMEG Project Number -
Rands House - RackhamRelocation
WSU : 00
- -
12/1
0/2
018 1
1:4
1:2
9 A
M
MHD-102
SECOND FLOOR DEMOLITION -
VENTILATION
PETPAPPETPAP
KIRSAI
18004050.01
PETPAP
PETPAP
WS
U R
an
ds B
ldg
Rackh
am
Relo
cati
on
18004050.0
1
NO R
HT
1/8" = 1'-0"1 SECOND FLOOR DEMOLITION - VENTILATION
REFERENCE SCALE IN INCHES
0 1 2 3
PROJECT #
IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
18004050.01
SHEET GENERAL NOTES :
1. COORDINATE ALL DEMOLITION WORK WITH ARCHITECTURAL AND ELECTRICAL AND ELECTRICAL DEMOLITION WITH OWNER'S PROJECT REPRESENTATIVE.
2. COORDINATE ANY SHUTDOWNS OF EXISTING SERVICES OR EQUIPMENT WITH OWNER. PERFORM SHUTDOWNS AT A SCHEDULED TIME AS TO MINIMIZE DISRUPTION OF BUILDING OPERATIONS.
3. REMOVE ALL INDICATED DUCTWORK AND EQUIPMENT COMPLETELY INCLUDING ALL RELATED ITEMS INCLUDING HANGERS, SUPPORTS, CONTROLS AND ACCESSORIES.
4. CAP ALL THE OPEN ENDED DUCTWORK. DO NOT LEAVE ANY ABONDONED DUCT WORK IN THE AREA OF WORK.
KEYNOTES:
1. DEMOLISH DUCTWORK, CEILING SUPPLY & RETURN DIFFUSERS AND ASSOCIATED ACCESSORIES BACK TO THE POINT SHOWN AND PREPARE FOR NEW CONNECTION.
2. REMOVE EXISTING VAV BOX & ITS ASSOCIATED TEMPERATURE SENSOR, CONTROLS IN ITS ENTIRETY. CAP CONTROLS AT MAIN.
3. DISCONNECT AND REMOVE EXISTING FINNED TUBE RADIATOR. CLEAN AND PREPARE FOR NEW INSTALLATION.
4. PRIOR TO DEMOLITION, MEASURE SUPPLY/ RETURN/ EXHAUST AIR FLOWS AT ALL EXISTING TERMINAL AIR DEVICES IN THE AREA. LABEL ALL DEVICES AND AND CREATE AN AIR BALANCE REPORT DESCRIBED ON SHEET MH-000.
#
Owner Review 60% CD's Nov. 13, 2018
Owner Review 90% CD's Nov. 27, 2018
100% CD's Dec. 04, 2018
For Bids Dec. 11, 2018
111
117
125
129
137 141
143
145
144142138
140136
134
132
130
128
126
122
120
124
118
116
112
108
106
102
100
103107
DN
UP
UP
CL
OFFICE
COVERED AREA
RESEARCHLAB
OFFICE
IT OFFICE
TREATMENT
OFFICE
TREATMENTOFFICEOFFICE
TREATMENTCHILDPLAYROOM
OBSERVATION
TREATMENT
TREATMENT
OFFICE
OFFICE
JC
UNISEXADA
WOMEN
WAITING
WAITING
LOUNGE
OFFICE
PLANTERSTORAGE
STORAGE
OPENOFFICE
VEST
PORCH
OPENOFFICE
CONFERENCE ROOMOFFICE
1 2 3 41.9 2.5 3.1 3.2 3.5 3.8
A
b
c
d
e
f
a10
a9
b4
c.1
c.2
c.3
c.4
e.8
(E)10x6 EG
200 CFM
10x6 EA
10x6 EA
(E)10x6 EG
200 CFM
(E)6x6 EG
75 CFM
(E) 14x10 TOILET
EXH. DUCT UP
(E) AIR-COOLED
CONDENSING UNITS
(E) GAS
METER
4 FT AD
190 CFM
4 FT AD
190 CFM
4 FT AD
190 CFM
30x8 RAG-C
285 CFM
30x8 RAG-C
285 CFM
24x8 RAG-C
335 CFM
8 FT AD
335 CFM
(E)30x8 RAG-C
4 FT AD
(E) 4 FT AD
300 CFM
(E)14x6 RAG-A300 CFM
W/FIRE DAMPER
(E)24x14 RAG-A645 CFM
W/FIRE DAMPER
(E)30x8 RAG
340 CFM
ALTERNATE: CU-1
(E) HHWS&R UP TO 2ND FLOOR
HVAC-2
16x10 SA20x1
8 S
A
COORDINATE W/ ARCH FOR ALTERNATE EXTEND & REWORK
EXISTING SECURITY FENCE
1
(E0 SECURITY FENCE 2
2AREA OF WORKNO SCALE
FLOOR LEVEL
project number:
sheet title:
sheet number:
approved
project:
coordination checked
location
drawn
checked
designed
issue: date:
key plan:
WAYNE STATE
UNIVERSITYFacilities Planning and Management
5454 Cass Avenue
Detroit, MI 48202
FO
R B
IDS
consultants:
NM Project Number - 18113.0
Rands Building
IMEG Project Number -
Rands House - RackhamRelocation
WSU : 00
- -
12/1
0/2
018 1
1:4
1:2
4 A
M
MH-101
FIRST FLOOR PLAN -
VENTILATION
PETPAPPETPAP
KIRSAI
18004050.01
PETPAP
PETPAP
WS
U R
an
ds B
ldg
Rackh
am
Relo
cati
on
18004050.0
1
NO R
HT
1/8" = 1'-0"1 FIRST FLOOR PLAN - VENTILATION
REFERENCE SCALE IN INCHES
0 1 2 3
PROJECT #
IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
18004050.01
KEYNOTES:
1. EXISTING FINNED TUBE RADIATOR TO BE CLEANED AND RELOCATED ALONG NEW WALL. EXTEND EXISTING HHWS&R FROM CEILING TO NEW LOCATION. REPAIR & INSTALL NEW PIPE INSULATION. COORDINATE W/ ARCH FOR THE PIPING INSTALLATION IN THE CEILING & WALL.
2. ALTERNATE: INSTALL NEW OUTDOOR CONDENSING UNIT CU-1 FOR AC-1, CONNECT ALL THE REFRIGERANT PIPING, WIRING & CONTROLS. COORDINATE W/ ARCH FOR SUPPORT CONCRETE PAD & REWORK OF THE EXISTING SECURITY FENCE. INSTALL UNIT PER MANUFACTURER'S INSTRUCTIONS AND CLEARANCE REQUIREMENTS.
#
SHEET GENERAL NOTES :
1. COORDINATE ALL DEMOLITION WORK WITH ARCHITECTURAL AND ELECTRICAL AND ELECTRICAL DEMOLITION WITH OWNER'S PROJECT REPRESENTATIVE.
2. COORDINATE ANY SHUTDOWNS OF EXISTING SERVICES OR EQUIPMENT WITH OWNER. PERFORM SHUTDOWNS AT A SCHEDULED TIME AS TO MINIMIZE DISRUPTION OF BUILDING OPERATIONS.
3. REMOVE ALL INDICATED DUCTWORK AND EQUIPMENT COMPLETELY INCLUDING ALL RELATED ITEMS INCLUDING HANGERS, SUPPORTS, CONTROLS AND ACCESSORIES.
4. CAP ALL THE OPEN ENDED DUCTWORK. DO NOT LEAVE ANY ABONDONED DUCT WORK IN THE AREA OF WORK.
Owner Review 60% CD's Nov. 13, 2018
Owner Review 90% CD's Nov. 27, 2018
100% CD's Dec. 04, 2018
For Bids Dec. 11, 2018
WHITE BOARD
projectionscreen
244
240
245
229
227
225
219
217
243242241
246
247
238236
230
226
224
220
218
214212
202
200.1
200
201
203205
234
232
207
OFFICE
OPENOFFICE
OPENOFFICE
IT
MECH
TREATMENT
OBSERVATION
TREATMENT
COMFERENCE/GROUP ROOMOBSERVATIONTREATMENT
TREATMENT
OBSERVATION
TREATMENTTREATMENT
ADULTGROUP ROOM
ADULTGROUP ROOM
WOMEN
UNISEX ADA
CHILDREN'SGROUP ROOM
OFFICETREATMENT
DN
UP
OPENOFFICE
STORAGE
DN
OPENOFFICE
OPENOFFICE
OFFICEOFFICE
OBSERVATION
TREATMENT
OPEN
UP
OFFICE
T T
T
T
T
1 2 3 41.9 2.5 3.1 3.2 3.5 3.8
A
b
c
d
e
f
a10
a9
b4
c.1
c.2
c.3
c.4
e.8
14x4 SD
155 CFM
14x4 SD
155 CFM
16x4 SD
180 CFM
18x4 SD
190 CFM
14x8 RAG-A
380 CFM
16x4 SD
180 CFMRAG IN CEILING
(TYP.)
14x8 RAG-A
360 CFM
16x4 SD
180 CFM
18x4 SD
195 CFM
14x6 RAG-A
310 CFM
16x4 SD
155 CFM
26x16 RAG-A
1385 CFM
12x10 RAG-A 390 CFM
16x6 SD 390 CFM
14x8 RAG-A
18x4 SD170 CFM
(TYP.4)
(E)AHU
44x22 SA UP
SD-E SD-E SD-E SD-E
SD-E
SD-E
SD-ESD-E
SD-E
SD-E
SD-E
SD-E
SD-E
SD-E
SD-E
TAB-ETAB-E
TAB-E
TAB-E
SD-E
SD-E SD-E
12x10 SA
24x12 SA
28x1
4 S
A
44x2
0 S
A
42x20 SA
30x20 SA
16x1
4 S
A
10x10 SA
10x8 SA
TAB-E
26x1
2 S
A
SD-E SD-E
14x4 SA
18x4 SA
20x6
SA
18x4 SA
22x8 SA
20x8 SA 20x6 SA
18x6
SA
18x4 SA18x4 SA
18x4 SA
14x10 RA
16x4
SA
10x8 RA
20x6 SA 16x16 RA
14x4 SA
14x6 SA
10x8 RA
22x8 SA
16x4 SA
18x4
SA
18x4 SA
6ø RARG-E
14x4 SA
16x4 SA
24x8 TOILETEXH DUCT UP
TO EF-2
14x8 TOILETEXH FROM
BELOW
EG-E
10x6/200
EG-E
10x6/200
RG-E
RG-E
RG-E
RG-E
RG-E
RG-E
RG-E
RG-E
RG-E
RG-E RG-E
RG-E
RG-E
RG-ERG-E
RG-E
14x8 EA
10x6 EA
10x6 EA
10x6 EA
CD-1
6/180
NC
1
CD-1
6/160
8ø8ø
CD-1
6/120
CD-1
6/120
1
1
10x10
8ø
8ø
CD-1
6/120
RG-1
RG-1
ALT: SG-1
12x8/200
ALT: SG-1
12x8/200
10x8
10x8
ALERNATE: HRV-13
ALTERNATE: AC-1
2
SD-E
TAB-E
SD-E
SD-E
FD IN FLRFD
FPB - 2.1 FPB - 2.2
FPB - 2.3
10ø
NC NC
10x8
ALTERNATE: 22"X8" LOUVER
L-1, COORDINATE W/ ARCH
ALTERNATE: 10"Ø EXHAUST AIR THROUGH ROOF W/ RAIN
CAP, COORDINATE W/ ARCH FOR ROOF PENETRATION
FINNED TUBE
HEATER-E
1¼" PUMPED
DRAIN FROM AC-1
1¼" PUMPED DRAIN FROM
AC-1 TO BASEMENT
AREA OF WORKNO SCALE
FLOOR LEVEL
project number:
sheet title:
sheet number:
approved
project:
coordination checked
location
drawn
checked
designed
issue: date:
key plan:
WAYNE STATE
UNIVERSITYFacilities Planning and Management
5454 Cass Avenue
Detroit, MI 48202
FO
R B
IDS
consultants:
NM Project Number - 18113.0
Rands Building
IMEG Project Number -
Rands House - RackhamRelocation
WSU : 00
- -
12/1
0/2
018 1
1:4
1:2
6 A
M
MH-102
SECOND FLOOR PLAN -
VENTILATION
PETPAPPETPAP
KIRSAI
18004050.01
PETPAP
PETPAP
WS
U R
an
ds B
ldg
Rackh
am
Relo
cati
on
18004050.0
1
NO R
HT
1/8" = 1'-0"1 SECOND FLOOR PLAN - VENTILATION
REFERENCE SCALE IN INCHES
0 1 2 3
PROJECT #
IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
18004050.01
SHEET GENERAL NOTES :
1. COORDINATE FINAL DUCT AND PIPING ROUTES WITH EXISTING DUCT, PIPING ON SITE.
2. COORDINATE ANY SHUTDOWNS OF EXISTING SERVICES OR EQUIPMENT WITH OWNER. PERFORM SHUTDOWNS AT A SCHEDULED TIME AS TO MINIMIZE DISRUPTION OF BUILDING OPERATIONS.
3. CAP ALL OPEN ENDED DUCTWORK. DO NOT LEAVE ANY ABONDONED DUCT WORK IN THE AREA OF WORK.
4. PROVIDE ACCESS DOOR IN HARD CEILINGS WHERE NECESSARY TO PROVIDE ACCESS TO TERMINAL AIR BOXES AND OTHER EQUIPMENT LOCATED ABOVE CEILING.
5. PROVIDE ACCESS PANELS WHERE REQUIRED TO ALLOW ACCESS TO BALANCING DAMPER.
KEYNOTES:
1. INSTALL AIR TERMINAL BOXES AND THEIR ASSOCIATED TEMPERATURE SENSORS, CONTROLS AND SUPPLY/RETURN/EXHAUST INLETS/OUTLETS AS SHOWN. INSTALLATION SHALL PER DETAILS ON MH-3.0. AIR TERMINAL BOX INSTALLATION SHALL PER MANUFACTURER AND PROVIDE SUFFICIENT CLEARANCE & SERVICE SPACES. FAN POWER BOX INDUCED AIR INLET SHALL HAVE SILENCER AND BE CLEAR OF ANY AIR BLOCKAGE. UNIT CONTROLS SHALL BE COMPATIBLE WITH EXISTING CONTROL SYSTEM IN THE BUILDING AND TO BE CONFIRMED BY THE OWNER.
2. ALTERNATE: INSTALL NEW RECESSED CEILING MOUNTED AC-1, SEE SCH. CONNECT REFERIGERANT PIPING TO GROUND FLOOR PAD MOUNTED CU-1. SEE MH101. CONNECT PUMPED CONDENSATE LINE IN THE ATTATIC INTO THE DUCT CHASE & DRAIN TO BASEMENT F.D. INSTALL PER MANUFACTURERS RECOMMENDATIONS. COORDINATE WITH ARCH FOR UNIT MOUNTING.
3. ALTERNATE: INSTALL NEW CEILING MOUNTED ENERGY RECOVERY VENTILATOR HRV-1, SEE SCH. CONNNECT EXHAUST AIR, OUTSIDE AIR, RETURN AIR & SUPPLY AIR PER MANUFACTURER RECOMMENDATION. COORDINATE WITH ARCH FOR OUTSIDE LOUVER & ROOF OPENING.
#
Owner Review 60% CD's Nov. 13, 2018
Owner Review 90% CD's Nov. 27, 2018
100% CD's Dec. 04, 2018
For Bids Dec. 11, 2018
AREA OF WORKNO SCALE
FLOOR LEVEL
project number:
sheet title:
sheet number:
approved
project:
coordination checked
location
drawn
checked
designed
issue: date:
key plan:
WAYNE STATE
UNIVERSITYFacilities Planning and Management
5454 Cass Avenue
Detroit, MI 48202
FO
R B
IDS
consultants:
NM Project Number - 18113.0
Rands Building
IMEG Project Number -
Rands House - RackhamRelocation
WSU : 00
- -
12/1
0/2
018 1
1:4
1:2
7 A
M
MH-300
VENTILATION SCHEDULE
PETPAPPETPAP
KIRSAI
18004050.01
PETPAP
PETPAP
WS
U R
an
ds B
ldg
Rackh
am
Relo
cati
on
18004050.0
1
REFERENCE SCALE IN INCHES
0 1 2 3
PROJECT #
IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
18004050.01
NOTES:1. PACKAGED DX AC UNIT, RECESSED CEILING HUNG DUCTLESS. PROVIDE THREE-POLE DISCONNECT SWITCH BETWEEN INDOOR AND OUTDOOR UNIT.2. PROVIDE UNIT WITH REMOTE T-STAT, UNIT MOUNTED DISCONNECT SWITCH, AND REMOTE WALL MOUNTED MICROPROCESSOR BASED PROGRAMMABLE CONTROL PANEL, WIRELESS CONTROLS, CONTROLS TO BE CONFIRMED BY THE OWNER.3. ULTRA LOW AMBIENT PACKAGE. SNOW/ HAIL GUARDS KIT.4. UNIT CONDENSATE PUMP.
AC-01 2ND FLR MEETING SPACE FC 1 DIRECT 2 208 1670-770-880
-10300.79 18,000 - 36,000 16
710-810-920-1060
38,000 2" PPF 500 60 208 1 FEED FROM CU-01
MCA VOLT PHASE % VOLT PHASE FLA MCA MSCP
TYPE FLA DRIVE CFM (WET) SHFCAPACITY RANGE
(BTUH)SEER CFM (DRY)
TOTALCAPACITY
(BUTH) @ 5FTYPE
MAX FACEVELOCITY
(FPM)
EFF
MARK AREA SERVED
SUPPLY FAN
ELECT. DATA
COOILING HEATING AIR FILTER
POWER
INDOOR UNIT
SPLIT SYSTEM AIR COOLED AIR CONDITIONING UNIT SCHEDULE (ALTERNATE)
AC-01 CU-01 SCROLL 1 R410A NO -13 TO 115 208 1 28 40 MITSUBISHI HEAT PUMP PLA-A36 & PUZ-HA36 SEE NOTES 1,2,3, 4
VOLT PHASE MCA MSCP
TYPE QUANTITYREF.TYPE
MARK MARK
COMPRESSOR
HOT GASBYPASS
PROVIDED
AMB. TEMP°F
POWER
INDOOR UNIT OUTDOOR CONDENSING UNIT
MFR/MODEL REMARKS
SPLIT SYSTEM AIR COOLED AIR CONDITIONING UNIT SCHEDULE (CONT.)
NOTES:1. OPERATION MODE: RECOVERY, BYPASS, AUTO.
HRV-1 2ND FLR MTG AIR TO AIR TOTAL LGH-F300 300 260 203 91 63 65 68 79 50 52 55 63 0.60 0.6 1 208 1.8 15 WASHABLE 18-34 MITSUBISHI ELECUNIT CONTROL PZ-60DR LOSSNAY
CONTROLLER
EXTRAHIGH
HIGH LOWEXTRALOW
EXTRAHIGH
HIGH LOWEXTRALOW
MIN. MAX. PH VOLT MCA MOCP
CFM(EXTRAHIGH)
CFM(HIGH)
CFM(LOW)
CFM(EXTRALOW)
HEATING % COOLING % IN.W.C.MARK AREA SERVED TYPE UNIT SIZE
CAPACITY ENTHALPHY RECOVERY EFFICIENCY FAN E.S.P.
ELEC INFO
FILTERSOUND
PRESSURELEVEL (dBA)
DESIGN BASE MODEL REMARKS
ENERGY RECOVERY VENTILATOR SCHEDULE (ALTERNATE)
1. SIZES INIDCATED ARE TYPICAL. REFER TO PLANS FOR ADDITIONAL REQUIRED SIZES AND CFM.
NOTES
ALTERNATEL-1
INTAKE AIR LOUVER 22" X 8" OR EQUAL FACE AREA 350RUSKIN GLAZING LOUVER OR 6 INCH DRAINABLELOUVER
ALUMINUM CONSTRUCTION, BIRD SCREEN,COORDINATE W/ ARCH
EG-1 EXHAUST AIR REGISTERSAME AS DUCT CONNECTION PLUS
FRAME1-600 12" X 12" 30 TITUS WALL MOUNTED SEE FLOOR PLAN
ALUMINUM CONSTRUCTION NECK MOUNTEDOPPOSED BLADE DAMPER
24 X 24 201-2000 22x22 24X24 30
RG-1 RETURN AIR GRILLE
12 X 12 0-200 10X10 12x12 30
TITUS CEILING MOUNTED SEE FLOOR PLAN ALUMINUM CONSTRUCTION
SG-1 SUPPLY AIR REGISTERSAME AS DUCT CONNECTION PLUS
FRAME1-450 12 X 8 30
TITUS DOUBLE DEFLECTION BLADES WALLMOUNTED
ALUMINUM CONSTRUCTION NECK MOUNTEDOPPOSED BLADE DAMPER
201-345 8" 8" 30
CD-1 SUPPLY AIR CEILING DIFFUSER 24 X 241-200 6" 6" 30
TITUS SQUARE LAY -IN CEILING MOUNTINGALUMINUM CONSTRUCTION NECK MOUNTEDOPPOSED BLADE DAMPER
MARK SERVICE MODULE SIZE CFM RANGEMIN DUCT
CONNECTION (IN)
NOMINALNECK SIZE
(IN)MAX NC DESCRIPTION REMARKS
DIFFUSER-REGISTER-GRILLE-LOUVER SCHEDULE
5. INSTALL A SIGN ON THE EXTERIOR OF THE AIR TERMINAL UNITS AT THE SERVICE ACCESS LOCATION INDICATING THE SOURCE AHU THAT IS PROVIDING THE SUPPLY AIR AND THE ROOMS THAT ARE BEING SERVED.
4. COIL ENTERING AIR TEMPS AND HEATING CAPACITIES BASED ON 48F PRIMARY AIR, 68F PLENUM AIR AND 72F ROOM HEATING SETPOINT.
3. FURNISH WITH THERMAL OVERLOAD PROTECTION AND DISCONNECT
OCTAVE BAND AT THE MAXIMUM PRIMARY AIR FLOW INDICATED IN THE SCHEDULE AND WITH 1.5" W.C. INLET STATIC PRESSURE.
2. FOR SINGLE DUCT VAV/CAV TERMINAL UNITS - DISCHARGE SOUND POWER DATA FOR 100% PRIMARY AIR VALVE FLOW IS TO BE ARI CERTIFIED AND IS NOT TO EXCEED 74 DB (REFERENCE 10 -12 WATTS) IN THE 2ND
OCTAVE BAND AT THE MAXIMUM PRIMARY AIR FLOW INDICATED IN THE SCHEDULE AND WITH 1.5" W.C. INLET STATIC PRESSURE.
1. FOR SINGLE DUCT VAV/CAV TERMINAL UNITS - RADIATED SOUND POWER DATA FOR 100% PRIMARY AIR VALVE FLOW IS TO BE ARI CERTIFIED AND IS NOT TO EXCEED 66 DB (REFERENCE 10 -12 WATTS) IN THE 2ND
NOTES:
FPB-2.3 OFFICE 245 SERIES A 6 360 120 360 55 90 4.0 208 1 SCR 360 0.5 1/3 208 1 ECM TITUS TFS, INLET SILENCER
FPB-2.2 TREATMENT 246 SERIES A 6 160 50 160 55 94 2.0 208 1 SCR 160 0.5 1/3 208 1 ECM TITUS TFS, INLET SILENCER
FPB-2.1 RESERVATION 247 SERIES A 6 180 60 180 55 90 2.0 208 1 SCR 180 0.5 1/3 208 1 ECM TITUS TFS, INLET SILENCER
ENTO F
LVGO F
HP VOLT PHMOTORCNTRL
MARK AREA SERVED TYPEUNITSIZE
INLETSIZE(IN)
CFM(MAX)
CFM(MIN)
CFM
AIR TEMP
KW VOLT PH CNTRLFAN
CFM @70 °F
EXTSP
(IWC)
MOTOR(HIGH EFFICIENCY ECM)
REMARKS
MARK AREA SERVED TYPEUNITSIZE
INLETSIZE(IN)
PRIMARY AIRHEATING COIL (ELECTRIC)
(NOTE 4)FAN INFORMATION REMARKS
SERIES FAN POWERED BOX SCHEDULE
Owner Review 60% CD's Nov. 13, 2018
Owner Review 90% CD's Nov. 27, 2018
100% CD's Dec. 04, 2018
For Bids Dec. 11, 2018
PLUMBING SYMBOL LIST
SYMBOL: DESCRIPTION:
PIPE SERVING FIXTURE ON FLOOR ABOVE(EXAMPLE: FD = FLOOR DRAIN)FD
PITCH PIPE IN DIRECTION
DIELECTRIC CONNECTION
UNION/FLANGE
BALANCING VALVE (NUMBER INDICATES GPM)GPM
CHECK VALVE
PIPE CAP
PIPE DOWN
PIPE UP OR UP/DOWN
DIRECTION OF FLOW IN PIPE
NEW CONNECTION
SHUTOFF VALVE NORMALLY OPEN
SHUTOFF VALVE NORMALLY CLOSED
COLD WATER - POTABLECW
HOT WATER - POTABLEHW
HOT WATER CIRCULATING - POTABLEHWC
HOT WATER - POTABLE NUMBER INDICATES TEMPHW140
HOT WATER CIRC. - POTABLE NUMBER INDICATES TEMPHWC140
DRAIND
NOT ALL SYMBOLS MAY APPLY.
SAFETY/RELIEF VALVE
PIPE CONTINUATION
ROUTE TO DRAIN
PLUMBING ABBREVIATION KEY
CO CLEANOUT
E
FLOOR CLEANOUTFCO
FLOOR DRAINFD
LAVATORYL
MOP BASINMB
MIXING VALVEMV
SINKSK
URINALUR
WATER CLOSETWC
WALL CLEANOUTWCO
WATER HEATERWH
VENT THROUGH ROOFVTR
AD ACCESS DOOR
ABOVE FINISHED FLOORAFF
BFP BACKFLOW PREVENTER
NC NEW CONNECTION
NOT IN CONTRACTNIC
ABBR: DESCRIPTION:
TYPICALTYP
UNLESS NOTED OTHERWISEUNO
EXISTING
CAST IRONCI
PLAN OR DETAIL NUMBER
PLAN OR DETAIL NAME
PLAN OR DETAIL SCALE
NAME
1VIEW NAME1/8" = 1'-0"
LEVEL NAME
10' - 0" HEIGHT ABOVE PROJECT 0' - 0"
1 INDICATES NOTE USED TO DESCRIBE ADDITIONAL INFORMATION ABOUT WORK REQUIRED, SPECIFIC TO THE SHEET AND/OR DETAIL
NO R
HT
INDICATES DIRECTION OF TRUE NORTH
VIEW KEY
NEW WORK BY THIS CONTRACTOR (DARK SOLID LINE)
NEW WORK BY OTHERS AND/OR EXISTING TO REMAIN (LIGHT SOLID LINE)
EXISTING TO BE REMOVED BY THIS CONTRACTOR(DARK SHORT DASHED LINE)
LINE TYPE KEY:
TEMPERATURE CONTROLS CONTRACTORT.C.C.
SECURITY CONTRACTORS.C.
AUDIO/VISUAL CONTRACTORA.V.C.
ASBESTOS ABATEMENT CONTRACTOR
PLUMBING CONTRACTORP.C.
GENERAL CONTRACTORG.C.
MECHANICAL CONTRACTORM.C.
VENTILATION CONTRACTORV.C.
ELECTRICAL CONTRACTORE.C.
A.C.
CONTRACTOR ABBREVIATION KEY
ABBR: DESCRIPTION:
TECHNOLOGY CONTRACTORT.C.
HEATING CONTRACTORH.C.
MECHANICAL PHASING NOTES:THESE NOTES APPLY TO ALL MECHANICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED TO, FIRE PROTECTION, PLUMBING, MEDICAL GAS, VENTILATION, PIPING AND TEMPERATURE CONTROL.
1. REFER TO ARCHITECTURAL DRAWINGS FOR GENERAL DESCRIPTION OF PHASES. REFER TO CONSTRUCTION MANAGER'S/GENERAL CONTRACTOR'S/ARCHITECT'S INSTRUCTIONS FOR MORE DETAILS AND PHASING SCHEDULES AND FOR CONCURRENT WORK. MECHANICAL, ELECTRICAL AND TECHNOLOGY DRAWINGS DEPICT THE INTENT OF THE FINAL DESIGN. THE MECHANICAL, ELECTRICAL, AND TECHNOLOGY DRAWINGS DO NOT DEPICT THE MEANS AND METHODS TO MEET THE REQUIREMENTS OF THE PHASING CRITERIA.
2. REVIEW PROJECT PHASING PLANS TO COORDINATE DEMOLITION WORK, OUTAGES, ETC. WITH AFFECTED ADJACENT AREAS.
3. PROVIDE TEMPORARY DUCTWORK, PIPING, SHUTOFF VALVES, ZONE VALVES, ZONE ALARMS, ETC. AS NEEDED TO MAINTAIN SERVICE TO ALL AREAS DURING ALL PHASES OF PROJECT.
4. INSTALL TEMPORARY DUCTWORK, PIPING, SHUTOFF VALVES, ETC. AS NECESSARY TO KEEP ALL OCCUPIED SPACES OPERATIONAL THROUGHOUT ALL PHASES OF THE PROJECT
5. PHASE DEMOLITION WORK TO MINIMIZE DOWNTIME.
MECHANICAL GENERAL NOTES:THESE NOTES APPLY TO ALL MECHANICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED TO, FIRE PROTECTION, PLUMBING, MEDICAL GAS, VENTILATION, PIPING AND TEMPERATURE CONTROL.
1. DRAWINGS SHOWING LOCATIONS OF EQUIPMENT, DUCTWORK, PIPING, ETC. ARE DIAGRAMMATIC AND MAY NOT ALWAYS REFLECT EXACT INSTALLATION CONDITIONS. DRAWINGS SHOW THE GENERAL ARRANGEMENT OF DUCTWORK, PIPING, EQUIPMENT, ETC., AND MAY NOT INCLUDE ALL OFFSETS AND FITTINGS REQUIRED FOR COMPLETE INSTALLATION. THE DRAWINGS SHALL BE FOLLOWED AS CLOSELY AS ACTUAL BUILDING CONSTRUCTION AND THE WORK OF OTHERS WILL PERMIT.
2. DO NOT SCALE DRAWINGS. VERIFY ALL DIMENSIONS AND CLEARANCES FROM ARCHITECTURAL, STRUCTURAL, SUBMITTALS, AND OTHER APPROPRIATE DRAWINGS OR PHYSICALLY AT SITE. REVIEW ALL DRAWINGS, INCLUDING THOSE OF OTHER TRADES.
3. COORDINATE ALL WORK WITH ALL OTHER TRADES PRIOR TO INSTALLATION TO PROVIDE CLEARANCES REQUIRED FOR OPERATION, MAINTENANCE, CODE COMPLIANCE, AND TO VERIFY NON-INTERFERENCE WITH OTHER WORK. DO NOT FABRICATE PRIOR TO VERIFICATION OF NECESSARY CLEARANCES FOR ALL TRADES. BRING ANY INTERFERENCES OR CONFLICTS TO THE ATTENTION OF THE ARCHITECT/ENGINEER BEFORE PROCEEDING WITH FABRICATION OR EQUIPMENT ORDERS.
4. REVIEW SPACE REQUIREMENTS OF EQUIPMENT SPECIFIED OR SUBSTITUTED AND MAKE REASONABLE ACCOMMODATIONS IN LAYOUT AND POSITIONING TO PROVIDE PROPER ACCESS.
5. ANY CHANGES REQUIRED TO ELIMINATE CONFLICTS OR THAT RESULT FROM A FAILURE TO COORDINATE SHALL BE MADE BY THE CONTRACTOR WITHOUT ADDITIONAL COST OR EXPENSE TO OTHERS.
6. EACH CONTRACTOR IS RESPONSIBLE FOR ALL COSTS ASSOCIATED WITH ELECTRICAL CHANGES REQUIRED FOR EQUIPMENT PROPOSED THAT DIFFERS FROM THE BASIS OF DESIGN.
7. REFER TO ARCHITECTURAL REFLECTED CEILING PLAN, ELECTRICAL, TECHNOLOGY AUDIO/VISUAL, AND OTHER MECHANICAL PLANS FOR EXACT LOCATIONS OF ALL CEILING MOUNTED DEVICES, OTHER THAN SPRINKLERS.
8. EACH CONTRACTOR IS RESPONSIBLE FOR DAMAGE CAUSED BY THEIR ACTIONS TO WALLS, FLOORS, CEILINGS, AND ROOFS. THE CONTRACTOR WHOSE WORK CAUSES DAMAGE IS RESPONSIBLE FOR PATCHING TO MATCH ORIGINAL CONSTRUCTION, FIRE RATING, AND FINISH.
9. IN AREAS WITH DRYWALL CEILINGS COORDINATE LOCATIONS OF ACCESS PANELS WITH THE GC FOR ACCESS TO VALVES, DUCTWORK ACCESSORIES, DAMPERS, ETC. COORDINATE PANEL TYPE AND COLOR WITH ARCHITECT. NOTIFY THE GC OF THE REQUIRED ACCESS PANELS PRIOR TO BIDDING.
10. SEAL ALL FLOOR, WALL, AND ROOF PENETRATIONS AIRTIGHT WHERE CONDUITS, PIPING, AND DUCTS PENETRATE. PENETRATIONS THROUGH EXTERIOR WALLS AND ROOF SHALL BE SEALED AIRTIGHT WITH WATERPROOFING MATERIALS RECOMMENDED BY MANUFACTURER FOR OUTDOOR USE.
11. CAULK ALL PIPE AND DUCT PENETRATIONS OF FULL HEIGHT NON-FIRE RATED WALL, PARTITION, FLOOR, AND ROOF ASSEMBLIES. THIS IS ESSENTIAL TO PREVENT NOISE TRANSMISSION FROM ONE ROOM TO ANOTHER AND TO PROVIDE THE DESIRED NC LEVELS WITHIN ROOMS.
12. WHERE PIPES AND DUCTS ARE SHOWN TO PENETRATE FLOORS, PROVIDE SLEEVED OPENINGS WITH THE TOP EDGE RAISED ABOVE FLOOR SURFACE IN ACCORDANCE WITH ALL RELEVANT SPEC SECTIONS. SEAL SLEEVE PERIMETER TO BE WATERTIGHT.
13. EQUIPMENT SIZES AND SERVICE CLEARANCE REQUIREMENTS VARY AMONG DIFFERENT MANUFACTURERS. CONSULT APPROVED SHOP DRAWINGS FOR EQUIPMENT SIZES AND REQUIRED SERVICE CLEARANCES. COORDINATE WITH LAYOUT OF EQUIPMENT PADS, PIPING, DUCTWORK, ETC.
14. DO NOT BLOCK TUBE PULL OR EQUIPMENT SERVICE CLEARANCES. 15. MAINTAIN MINIMUM 3'-6” CLEARANCE IN FRONT OF ALL ELECTRICAL PANELS, MOTOR
STARTERS, SWITCHES, AND DISCONNECTS.16. PROVIDE CONCRETE EQUIPMENT PAD FOR ALL FLOOR MOUNTED EQUIPMENT. PAD SHALL
EXTEND MINIMUM 6” BEYOND ALL SIDES OF EQUIPMENT.17. DO NOT SUPPORT EQUIPMENT, PIPING, OR DUCTWORK FROM METAL DECKING OR OTHER
NON-STRUCTURAL BUILDING ELEMENTS. ANCHORS EMBEDDED IN CONCRETE SHALL BE CRACKED CONCRETE APPROVED IN ACCORDANCE WITH SPECIFICATIONS.
MECHANICAL RENOVATION NOTES:THESE NOTES APPLY TO ALL MECHANICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED TO, FIRE PROTECTION, PLUMBING, MEDICAL GAS, VENTILATION, PIPING AND TEMPERATURE CONTROL.
1. EXISTING CONDITIONS ARE SHOWN BASED ON INFORMATION OBTAINED FROM FIELD SURVEYS, EXISTING BUILDING DOCUMENTS, AND STAFF. VERIFY EXISTING CONDITIONS AND REPORT ANY CONFLICTS BEFORE PROCEEDING.
2. NOT ALL EXISTING DUCTWORK AND PIPING IS SHOWN. VERIFY EXISTING CONDITIONS BEFORE STARTING WORK. NOTIFY ENGINEER OF ANY CONFLICTS WITH NEW WORK.
3. FIELD VERIFY THE AVAILABLE CLEARANCES FOR DUCTWORK AND PIPING BEFORE FABRICATION. RISES AND DROPS MAY BE NECESSARY BECAUSE OF EXISTING FIELD CONDITIONS. EACH CONTRACTOR SHALL FIELD VERIFY ACCESSIBILITY TO THE AREA OF HIS/HER WORK AND SHALL NOTIFY THE GENERAL CONTRACTOR CONSTRUCTION MANAGER ARCHITECT/ENGINEER PRIOR TO BIDDING IF OTHER UTILITIES ARE REQUIRED TO BE REMOVED OR RELOCATED TO ALLOW ACCESS TO HIS/HER AREA OF WORK.
4. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR CUTTING, REMOVAL AND PATCHING OF ROOFS, WALLS, AND FLOORS ASSOCIATED WITH WORK BY ALL CONTRACTORS. CONTRACTORS SHALL NOTIFY THE GC OF AFFECTED AREAS PRIOR TO BIDDING EACH CONTRACTOR SHALL CUT AND PATCH ROOFS, WALLS, AND FLOORS ASSOCIATED WITH HIS WORK.
5. EACH CONTRACTOR SHALL CUT AND PATCH ROOFS, WALLS, AND FLOORS ASSOCIATED WITH HIS WORK.
6. WHERE EXISTING MECHANICAL SYSTEMS ARE LOCATED IN AREAS THAT CONFLICT WITH NEW EQUIPMENT, PIPING, OR DUCTWORK TO BE INSTALLED, EACH CONTRACTOR SHALL EITHER ARRANGE NEW EQUIPMENT, PIPING, OR DUCTWORK IN SUCH A FASHION THAT IT DOES NOT CONFLICT WITH EXISTING SYSTEMS, OR REWORK EXISTING MECHANICAL SYSTEMS TO ALLOW FOR INSTALLATION OF NEW EQUIPMENT, PIPING, OR DUCTWORK.
7. PROVIDE TEMPORARY CONNECTIONS TO MAINTAIN EXISTING SYSTEMS IN SERVICE DURING CONSTRUCTION. MAINTAIN ACCESS TO EXISTING MECHANICAL INSTALLATIONS THAT REMAIN ACTIVE.
8. OBTAIN PERMISSION FROM OWNER BEFORE SHUTTING DOWN ANY SYSTEM FOR ANY REASON. MAINTAIN SERVICE TO ALL COMPONENTS THAT ARE TO REMAIN UNTIL NEW SYSTEMS ARE INSTALLED.
9. MAINTAIN EXISTING SYSTEM IN SERVICE UNTIL NEW SYSTEM IS COMPLETE AND READY FOR TIE IN AND SWITCHOVER. DRAIN SYSTEM ONLY TO MAKE SWITCHOVERS AND CONNECTIONS. OBTAIN PERMISSION FROM OWNER BEFORE PARTIALLY OR COMPLETELY DRAINING SYSTEM. MAKE CHANGEOVER TO NEW SYSTEMS WITH MINIMUM OUTAGE.
10. DISCONNECT AND REMOVE MECHANICAL DEVICES AND EQUIPMENT SERVING EQUIPMENT THAT HAS BEEN REMOVED.
1. THE SYMBOLS AND THE MATERIAL LIST ARE FOR THE CONVENIENCE OF THE CONTRACTOR. CONTRACTOR SHALL VERIFY QUANTITIES AND FURNISH ALL MATERIALS REQUIRED FOR FULLY OPERATIONAL SYSTEMS, WHETHER SPECIFIED OR NOT.
2. CATALOG NUMBERS SHALL NOT BE CONSIDERED COMPLETE, BUT ARE GIVEN AS AN AID TO THE CONTRACTOR AND TO INDICATE THE QUALITY REQUIRED. CONTRACTOR IS RESPONSIBLE FOR A COMPLETE DESCRIPTION OF MATERIAL ON THESE DRAWINGS AND IN THE SPECIFICATIONS BEFORE ORDERING. THE DESCRIPTION OF THE MATERIAL TAKES PRECEDENCE OVER THE CATALOG NUMBER. THE FIRST MANUFACTURER LISTED IS THE BASIS OF DESIGN.
3. CONTRACTOR SHALL VERIFY THAT FIXTURES SUPPLIED ARE APPROVED PER ALL APPLICABLE STATE, LOCAL AND GOVERNING AUTHORITIES.
4. ALL FIXTURES SHALL CONFORM TO FEDERAL ACT S.38745. INVERT ELEVATIONS ARE FROM EXISTING DRAWINGS AND MAY NOT BE ACCURATE. VERIFY
ALL ELEVATIONS BEFORE BEGINNING WORK.6. VERIFY UNDERGROUND PIPE SIZES, INVERT ELEVATIONS, AND LOCATIONS PRIOR TO
BEGINNING ANY WORK.7. REFER TO THE PLUMBING ROUGH-IN SCHEDULE FOR THE SIZES OF BRANCH PIPES TO
PLUMBING FIXTURES.8. FOR CLARITY, NOT ALL VALVES HAVE BEEN SHOWN. PROVIDE SHUTOFF VALVES IN
DOMESTIC WATER PIPING SERVING EACH ROOM WITH FIXTURES. ANGLE STOPS SHALL NOT BE CONSIDERED SHUTOFF VALVES.
9. EXISTING CONDITIONS ON DEMOLITION PLANS ARE PROVIDED TO INDICATE THE GENERAL SCOPE OF ITEMS TO BE REMOVED. REFER TO SPECIFICATION SECTION 22 05 05 FOR ADDITIONAL DEMOLITION INFORMATION.
10. P.C. SHALL CUT AND PATCH EXISTING AS REQUIRED FOR NEW OR DEMOLITION WORK UNLESS NOTED OTHERWISE. REFER TO SPECIFICATION SECTION 22 05 05 FOR ADDITIONAL INFORMATION.
PLUMBING GENERAL NOTES:
BUILDING CODE: MBC 2015 EDITION
FIRE CODE: NFPA 13: 2013 EDITION
PLUMBING CODE: MBC 2015 EDITION
MECHANICAL CODE: MMC 2015 EDITION
ELECTRICAL CODE: NFPA 70 (NEC) 2016EDITION
LIFE SAFETY CODE: NFPA 101 2015 EDITION
ENERGY CONSERVATION CODE: ASHRAE 90.1 2013
HEALTH DEPARTMENT CODE: CURRENT EDITION
LOCAL BUILDING CODE: CURRENT EDITION
APPLICABLE CODES
CONTRACTOR SHALL COMPLY WITH APPLICABLE CODES AND LOCAL AMENDMENTS.
PLUMBING SHEET INDEXP-000 PLUMBING COVERSHEET
P-101 FIRST FLOOR PLAN - PLUMBING
P-102 SECOND FLOOR PLAN - PLUMBING
P-300 ENLARGED PLANS
P-500 PLUMBING SCHEDULES
NOTES: 1) SANITARY RISER UP IN WALL TO FIXTURE SHALL BE A MINUMUM OF 2". 2) 1/2" CW ANDHW APPLIES ONLY TO THE FINAL VERTICAL RISE-DROP TO EACH FIXTURE, BRANCH PIPING TOVERTICAL RISE-DROP SHALL BE A MINIMUM OF 3/4" UNLESS NOTED OTHERWISE. 3) SIZES SHOWNARE MINIMUMS. SIZES SHOWN ON THE DRAWING THAT ARE LARGER THAN THE SIZES LISTED IN THESCHEDULE SHALL DICTATE THE ROUGH-IN SIZE.
PLUMBING FIXTURE ROUGH-IN SCHEDULE
FIXTUREDESCRIPTION
DOMESTICCW
(NOTE 3)
DOMESTICHW
(NOTE 3)SANITARY(NOTE 3)
VENT(NOTE 3) REMARKS
LAVATORY 1/2" 1/2" 1 1/4" 1 1/4" NOTE 1 & 2
WATERCLOSET
1" - 4" 2" -
AREA OF WORKNO SCALE
FLOOR LEVEL
project number:
sheet title:
sheet number:
approved
project:
coordination checked
location
drawn
checked
designed
issue: date:
key plan:
WAYNE STATE
UNIVERSITYFacilities Planning and Management
5454 Cass Avenue
Detroit, MI 48202
FO
R B
IDS
consultants:
NM Project Number - 18113.0
Rands Building
IMEG Project Number -
Rands House - Rackham
Relocation
WSU : 00
- -
12/1
0/2
018 1
1:4
0:2
9 A
M
P-000
PLUMBING COVERSHEET
PETPAPPETPAP
KIRSAI
18004050.01
PETPAP
PETPAP
WS
U R
an
ds B
ldg
Rackh
am
Relo
cati
on
18004050.0
1
REFERENCE SCALE IN INCHES
0 1 2 3
PROJECT #
IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
18004050.01
Owner Review 60% CD's Nov. 13, 2018
Owner Review 90% CD's Nov. 27, 2018
100% CD's Dec. 04, 2018
For Bids Dec. 11, 2018
111
117
125
129
137 141
143
145
144142138
140136
134
132
130
128
126
122
120
124
118
116
112
108
106
102
100
103107
DN
UP
UP
CL
OFFICE
COVERED AREA
RESEARCHLAB
OFFICE
IT OFFICE
TREATMENT
OFFICE
TREATMENTOFFICEOFFICE
TREATMENTCHILDPLAYROOM
OBSERVATION
TREATMENT
TREATMENT
OFFICE
OFFICE
JC
UNISEXADA
WOMEN
WAITING
WAITING
LOUNGE
OFFICE
PLANTERSTORAGE
STORAGE
OPENOFFICE
VEST
PORCH
OPENOFFICE
CONFERENCE ROOMOFFICE
1 2 3 41.9 2.5 3.1 3.2 3.5 3.8
A
b
c
d
e
f
a10
a9
b4
c.1
c.2
c.3
c.4
e.8
P-300
2
ALTERNATE: NEW 1¼" PUMPED
COND. DRAIN FROM AC-1 TO
BASEMENT, SEE MH102
AREA OF WORKNO SCALE
FLOOR LEVEL
project number:
sheet title:
sheet number:
approved
project:
coordination checked
location
drawn
checked
designed
issue: date:
key plan:
WAYNE STATE
UNIVERSITYFacilities Planning and Management
5454 Cass Avenue
Detroit, MI 48202
FO
R B
IDS
consultants:
NM Project Number - 18113.0
Rands Building
IMEG Project Number -
Rands House - Rackham
Relocation
WSU : 00
- -
12/1
0/2
018 1
1:4
0:3
0 A
M
P-101
FIRST FLOOR PLAN - PLUMBING
PETPAPPETPAP
KIRSAI
18004050.01
PETPAP
PETPAP
WS
U R
an
ds B
ldg
Rackh
am
Relo
cati
on
18004050.0
1
NO R
HT
1/8" = 1'-0"1 FIRST FLOOR PLAN - PLUMBING
REFERENCE SCALE IN INCHES
0 1 2 3
PROJECT #
IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
18004050.01
Owner Review 60% CD's Nov. 13, 2018
Owner Review 90% CD's Nov. 27, 2018
100% CD's Dec. 04, 2018
For Bids Dec. 11, 2018
WHITE BOARD
projection
screen
244
240
245
229
227
225
219
217
243242241
246
247
238236
230
226
224
220
218
214212
202
200.1
200
201
203205
234
232
207
OFFICE
OPENOFFICE
OPENOFFICE
IT
MECH
TREATMENT
OBSERVATION
TREATMENT
COMFERENCE/GROUP ROOMOBSERVATIONTREATMENT
TREATMENT
OBSERVATION
TREATMENTTREATMENT
ADULTGROUP ROOM
ADULTGROUP ROOM
WOMEN
UNISEX ADA
CHILDREN'SGROUP ROOM
OFFICETREATMENT
DN
UP
OPENOFFICE
STORAGE
DN
OPENOFFICE
OPENOFFICE
OFFICEOFFICE
OBSERVATION
TREATMENT
OPEN
UP
OFFICE
1 2 3 41.9 2.5 3.1 3.2 3.5 3.8
A
b
c
d
e
f
a10
a9
b4
c.1
c.2
c.3
c.4
e.8
P-300
4
ALTERNATE: NEW 1¼" PUMPED
COND. DRAIN FROM AC-1 TO
BASEMENT, SEE MH-102
AREA OF WORKNO SCALE
FLOOR LEVEL
project number:
sheet title:
sheet number:
approved
project:
coordination checked
location
drawn
checked
designed
issue: date:
key plan:
WAYNE STATE
UNIVERSITYFacilities Planning and Management
5454 Cass Avenue
Detroit, MI 48202
FO
R B
IDS
consultants:
NM Project Number - 18113.0
Rands Building
IMEG Project Number -
Rands House - Rackham
Relocation
WSU : 00
- -
12/1
0/2
018 1
1:4
0:3
1 A
M
P-102
SECOND FLOOR PLAN -
PLUMBING
PETPAPPETPAP
KIRSAI
18004050.01
PETPAP
PETPAP
WS
U R
an
ds B
ldg
Rackh
am
Relo
cati
on
18004050.0
1
NO R HT
1/8" = 1'-0"1 SECOND FLOOR PLAN - PLUMBING
REFERENCE SCALE IN INCHES
0 1 2 3
PROJECT #
IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
18004050.01
Owner Review 60% CD's Nov. 13, 2018
Owner Review 90% CD's Nov. 27, 2018
100% CD's Dec. 04, 2018
For Bids Dec. 11, 2018
122
120
124
JC
UNISEXADA
WOMEN 224
220
WOMEN
UNISEX ADA
1 1.9
c.2
c.3
c.4
FD-E
2"CW
3/4” CW TO
LAV(2)
4” SAN FROM
2ND LEVEL
C.O.
WC-EWC-E
L-E L-E
WC-E
WH-E
ON SHELF
1 1/2” CW TO
(3) WC &
(1) LAV1/2” CW
TO S.S.
4" R.W.C
A.S.C.
4"ST
FD-E
3"SAN
4"SAN
1 1/2"SAN
NC
NC
1 1/2"V
1 1/2"VNEW 1-1/2" VENT ROUTE IN THE WALL & CEILING TO CONNECT TO EXISTING VENT
NEW 1/2" DCWPIPE ABOVE CEILING
1/2"CWUNDERFLOOR
NC
NC
4L-1
1/2"HW
1
c.2
c.3
c.4
FD-EFD-E
4"SAN
2"CW
3/4” CW TO
LAV(2)
3"SAN
4” W FROM
2ND LEVEL
C.O.
WC-E WC-EL-E L-E
L-E
WC-E
WH-E
ON SHELF
1 1/2” CW TO
(3) WC &
(1) LAV
1/2” CW
TO S.S.
4" R.W.C
A.S.C.
4"SAN
4"ST
FD-E
1
1 1.9
c.2
c.3
c.4
WC-E WC-E
WC-E
L-1
3"SAN
3"SAN
2" V FROM
BELOW
1 1/2" CW FROM
BELOW
3/4" HW FROM
BELOW4" V UP
THRU ROOF
L-1 L-1
NC
NCNC
NC
5
NC
1
c.2
c.3
c.4
WC-E
L-E L-E
WC-E
L-EUR-E
FD-E
FD-E
2" V FROM
BELOW
2"V
1 1/2" CW FROM
BELOW
3/4" HW FROM
BELOW
3/4"HW
4" V UP
THRU ROOF
3/4"HW
3/4"CW
1
2
3
2
AREA OF WORKNO SCALE
FLOOR LEVEL
project number:
sheet title:
sheet number:
approved
project:
coordination checked
location
drawn
checked
designed
issue: date:
key plan:
WAYNE STATE
UNIVERSITYFacilities Planning and Management
5454 Cass Avenue
Detroit, MI 48202
FO
R B
IDS
consultants:
NM Project Number - 18113.0
Rands Building
IMEG Project Number -
Rands House - Rackham
Relocation
WSU : 00
- -
12/1
0/2
018 1
1:4
0:3
4 A
M
P-300
ENLARGED PLANS
PETPAPPETPAP
KIRSAI
18004050.01
PETPAP
PETPAP
WS
U R
an
ds B
ldg
Rackh
am
Relo
cati
on
18004050.0
1
REFERENCE SCALE IN INCHES
0 1 2 3
PROJECT #
IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
18004050.01
1/4" = 1'-0"2 FIRST FLOOR ENLARGE NEW PLAN - PLUMBING
1/4" = 1'-0"1 FIRST FLOOR ENLARGE DEMOLITION PLAN - PLUMBING
1/4" = 1'-0"4 SECOND FLOOR ENLARGENEW PLAN - PLUMBING
1/4" = 1'-0"3 SECOND FLOOR ENLARGE DEMOLITION PLAN - PLUMBING
KEYNOTES:
1. REMOVE EXISTING LAV, REMOVE EXISTING SAN, VENT, DCW, DHW PIPE TO THE EXISTING LAV TO BE DEMOED. CAP SAN, DCW & DHW PIPE AT WALL & USE WALL COVER, COORDINATE W/ ARCH. CAP VENT PIPE AT MAIN.
2. REMOVE EXISTING LAV, DISCONNECT EXISTING SAN, DCW & DHW CONNECTION TO THE LAV. PREPARE TO CONNECT TO NEW LAV. SEE NEW WORK.
3. REMOVE EXISTING UR, REMOVE EXISTING SAN, DCW PIPE TO THE EXISTING UR TO BE DEMOED. CAP SAN, DCW.
4. INSTALL NEW 1/2" DHW, DCW PIPING & SHUT OFF VALVES FROM EXISTING BRANCHES TO NEW SINK AS SHOWN. CONNECT NEW 1-1/2" VENT PIPE AS SHOWN. NEW 1-1/2" DRAIN PIPE TO BE INSTALLED UNDERFLOOR. COORDINATE THE SLAB CUTTING & REPAIR WORK W/ ARCH.
5. INSTALL NEW 1/2" DHW, DCW PIPING AND SHUT-OFF VALVES FROM EXISTING BRANCHES TO NEW LAV AS SHOWN. NEW 1-1/2" SANITARY AND VENT.
#
Owner Review 60% CD's Nov. 13, 2018
Owner Review 90% CD's Nov. 27, 2018
100% CD's Dec. 04, 2018
For Bids Dec. 11, 2018
AREA OF WORKNO SCALE
FLOOR LEVEL
project number:
sheet title:
sheet number:
approved
project:
coordination checked
location
drawn
checked
designed
issue: date:
key plan:
WAYNE STATE
UNIVERSITYFacilities Planning and Management
5454 Cass Avenue
Detroit, MI 48202
FO
R B
IDS
consultants:
NM Project Number - 18113.0
Rands Building
IMEG Project Number -
Rands House - Rackham
Relocation
WSU : 00
- -
12/1
0/2
018 1
1:4
0:3
5 A
M
P-500
PLUMBING SCHEDULES
PETPAPPETPAP
KIRSAI
18004050.01
PETPAP
PETPAP
WS
U R
an
ds B
ldg
Rackh
am
Relo
cati
on
18004050.0
1
REFERENCE SCALE IN INCHES
0 1 2 3
PROJECT #
IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
18004050.01
L-1
LAVATORY - ADA WALL MOUNTED, WHITE VITREOUS CHINA, 20"x18", 4" HIGH CONTOURED BACKSPLASH, SINGLE FAUCETHOLE, DRILLED FOR CONCEALED ARM CARRIER.
INSULATION KIT - PRE-MANUFACTURED FOR P-TRAP, STOP VALVES AND SUPPLY LINES.
LAVATORY TRIM - SENSOR ACTIVATED MIXING FAUCET, BATTERY POWERED WITH HYDROELECTRIC GENERATOR, BRASSCONSTRUCTION, CHROME-PLATED FINISH, CONVENTIONAL SPOUT WITH AERATOR, PERFORATED GRID STRAINER WITH1-1/4" 17 GAUGE TAILPIECE, SOLID BRASS SOLENOID WITH BUILT-IN FILTER, SOLID BRASS THERMOSTATIC MIXING VALVEMEETING ASSE 1070 REQUIREMENTS WITH ADJUSTABLE TEMPERATURE LIMIT STOP AND INTEGRAL CHECK VALVES,WATERPROOF CONNECTORS AND CABLE.
MOUNT CONTROLS AND BATTERIES IN WATERPROOF VANDAL-RESISTANT ENCLOSURE BELOW LAVATORY. MOUNTMIXING VALVE UNDER COUNTER/LAVATORY. MAXIMUM FLOW SHALL BE 0.5 GPM IN COMPLIANCE WITH ENERGY POLICYACT OF 2005 AND ASME/ANSI STANDARD A112.18.1M. FAUCET SHALL COMPLY WITH FEDERAL ACT S.3874. PROVIDERESTRICTIVE DEVICE AND ESCUTCHEON PLATE AS REQUIRED. FAUCET SHALL HAVE A MAXIMUM 30 SECONDS OFCONTINUOUS DISCHARGE.
ACCESSORIES - QUARTER-TURN 3/8" CHROME PLATED HEAVY BRASS ANGLE SUPPLY STOPS, CHROME PLATED SOFTCOPPER SUPPLY LINES, DRAIN AND OFFSET TAILPIECE, 1-1/4" 17 GAUGE CAST BRASS P-TRAP, SUPPORT CARRIER.
IN COMPLIANCE WITH LATEST ADA STANDARD. PROVIDE 29" MINIMUM CLEARANCE FROM FLOOR TO BOTTOM OF APRONIN COMPLIANCE WITH LATEST ANSI A117.1 AND ADA STANDARDS. ARMAFLEX WITH TAPE IS NOT ACCEPTABLE IN LIEU OFINSULATION KIT.
LAVATORY -AMERICAN STANDARD (0356.421), KOHLER (K-2007)
INSULATION KIT - TRUEBRO
LAV TRIM -TOTO (TEL105), CHICAGO FAUCET (116.951.AB.1), ZURN (Z6913-GEN-XL)
TAG DESCRIPTION ACCEPTABLE MANUFACTURERS
THE SYMBOLS AND THE MATERIAL LIST ARE FOR THE CONVENIENCE OF THE CONTRACTOR. THE CONTRACTOR SHALL VERIFY QUANTITIES AND FURNISH ALL MATERIALS REQUIRED FOR FULLY OPERATIONAL SYSTEMS, WHETHERSPECIFIED OR NOT.
CATALOG NUMBERS SHALL NOT BE CONSIDERED COMPLETE, BUT ARE GIVEN AS AN AID TO THE CONTRACTOR AND TO INDICATE THE QUALITY REQUIRED. CONTRACTOR IS RESPONSIBLE FOR COMPLETE DESCRIPTION OF MATERIALON THESE DRAWINGS AND IN THE SPECIFICATIONS BEFORE ORDERING. THE DESCRIPTION OF MATERIAL TAKES PRECEDENCE OVER THE CATALOG NUMBER. THE FIRST MANUFACTURER LISTED IS THE BASIS OF DESIGN.
CONTRACTOR SHALL VERIFY THAT FIXTURES SUPPLIED ARE APPROVED PER ALL APPLICABLE STATE, LOCAL AND GOVERNING AUTHORITIES.
ALL FIXTURES SHALL CONFORM TO FEDERAL ACT S.3874
PLUMBING MATERIAL LIST
100% CD's Dec. 04, 2018
For Bids Dec. 11, 2018
1. ##-### INDICATES ELECTRICAL EQUIPMENT DEFINED IN ELECTRICAL SCHEDULES OR SPECIFICATION. REFER TO DRAWINGS CONTAINING ELECTRICAL SCHEDULES. PERMANENT NAMEPLATE SHALL MATCH FINAL EQUIPMENT NOMENCLATURE, NOT ELECTRICAL EQUIPMENT TAG NAME, REFER TO SPECIFICATIONS.
2. {L###} INDICATES THE LIGHTING SEQUENCE OF OPERATION FOR THE SPACE. REFER TO THE
LIGHTING SEQUENCE OF OPERATION MATRIX ON SHEET E-000.
LUMINAIRE KEY:
DEVICE KEY:
ELECTRICAL MOUNTING SUBSCRIPT KEY:A MOUNT AT +6" TO CENTERLINE ABOVE COUNTER OR BACKSPLASHC MOUNT AT CEILING
ELECTRICAL GENERAL NOTES:
LUMINAIRE
F1 = FIXTURE TAG1 = CIRCUIT NUMBERa = SWITCH DESIGNATION
*IF LABEL IS ORIENTED HORIZONTALLY A SLASH WILL SEPARATE THIS INFORMATION. EX: F1 / 1 / a / SE
DEVICEA = MOUNTING (IF APPLICABLE)1 = CIRCUIT NUMBER
*IF LABEL IS ORIENTED HORIZONTALLY A SLASH WILL SEPARATE THIS INFORMATION. EX: A / 1
1. CIRCUIT NUMBERS ARE SHOWN FOR CIRCUIT IDENTIFICATION. CIRCUITING SHALL AGREE WITH NUMBERING ON THE PANEL PROVIDED. COMMON NEUTRALS MAY NOT BE USED FOR BRANCH CIRCUITS. BALANCE THE LOAD ON PANEL AS EVENLY AS POSSIBLE BETWEEN EACH PHASE.
2. CIRCUITS SERVING EMERGENCY LUMINAIRES WILL BE RUN IN A SEPARATE RACEWAY FROM ALL OTHER CIRCUITS.
3. ALL MATERIALS USED TO SEAL PENETRATIONS OF FIRE RATED WALLS AND FLOORS SHALL BE TESTED AND CERTIFIED AS A SYSTEM PER ASTM E814 STANDARDS FOR FIRE TESTS OF THROUGH-PENETRATION FIRESTOPS. REFER TO 26 05 03 FOR ADDITIONAL INFORMATION AND REQUIREMENTS SPECIFIC TO FIRESTOPPING.
4. CONTRACTOR SHALL COORDINATE THE LOCATION OF ALL CEILING MOUNTED DEVICES AND EQUIPMENT WITH LUMINAIRES, SPRINKLER, AND CEILING DIFFUSERS. CENTER ALL DEVICES IN CEILING TILE PATTERN. SMOKE DETECTORS AND OCCUPANCY/VACANCY SENSORS SHALL BE LOCATED NO CLOSER THAN 3 FEET TO AN AIR SUPPLY DIFFUSER OR RETURN GRILLE.
5. CONTRACTOR SHALL VERIFY ALL FURNITURE AND EQUIPMENT LOCATIONS WITH ARCHITECTURAL PLANS, ELEVATIONS, AND REVIEWED SHOP DRAWINGS. PRIOR TO MAKING THE ACTUAL ELECTRICAL INSTALLATION, THIS CONTRACTOR SHALL ADJUST RECEPTACLES, OUTLETS, OR CONNECTION LOCATIONS TO ACCOMMODATE FURNITURE AND EQUIPMENT.
6. ELECTRICAL EQUIPMENT SHALL BE MOUNTED TO AVOID IMPEDANCE OF, OPERATION OF, AND ACCESS TO ELECTRICAL AND MECHANICAL EQUIPMENT. ALL MOUNTING OF ELECTRICAL EQUIPMENT, ON EQUIPMENT SUPPLIED BY ANOTHER CONTRACTOR, SHALL BE APPROVED IN ADVANCE BY THE OTHER CONTRACTOR.
7. REFER TO ARCHITECTURAL REFLECTED CEILING PLAN AND OTHER ELECTRICAL PLANS FOR EXACT LOCATIONS OF ALL CEILING MOUNTED DEVICES, OTHER THAN SPRINKLERS.
8. MOUNTING HEIGHTS SHALL BE AS FOLLOWS: LIGHTING SWITCHES 4'-0" RECEPTACLES (GENERAL AREAS) 1'-6" RECEPTACLES (UTILITY AREAS) 4'-0" TELECOMMUNICATION OUTLETS 1'-6" WALL PHONE 4'-0" FIRE ALARM STATIONS 4'-0" FIRE ALARM SIGNALS 7'-6" CLOCKS/CLOCK OUTLETS 1’-6” BELOW FIN. CEIL. SAFETY SWITCHES 5'-0" TO TOP
ELECTRICAL INSTALLATION NOTES:
1. EXISTING CONDITIONS ARE SHOWN BASED ON INFORMATION OBTAINED FROM FIELD SURVEYS, EXISTING BUILDING DOCUMENTS, AND STAFF. VERIFY EXISTING CONDITIONS AND REPORT ANY CONFLICTS BEFORE PROCEEDING.
2. NOT ALL EXISTING EQUIPMENT, LUMINAIRES, AND CONDUIT ARE SHOWN. VERIFY EXISTING CONDITIONS AND REPORT ANY CONFLICTS WITH NEW WORK BEFORE STARTING WORK.
3. FIELD VERIFY THE AVAILABLE CLEARANCES FOR CONDUITS BEFORE FABRICATION. RISES AND DROPS MAY BE NECESSARY BECAUSE OF EXISTING FIELD CONDITIONS.
4. EACH CONTRACTOR SHALL FIELD VERIFY ACCESSIBILITY TO THE AREA OF HIS/HER WORK AND SHALL NOTIFY THE ARCHITECT/ENGINEER PRIOR TO BIDDING IF OTHER UTILITIES ARE REQUIRED TO BE REMOVED OR RELOCATED TO ALLOW ACCESS TO HIS/HER AREA OF WORK.
5. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR CUTTING, REMOVAL AND PATCHING OF ROOFS, WALLS, AND FLOORS ASSOCIATED WITH WORK BY ALL CONTRACTORS.
6. CONTRACTORS SHALL NOTIFY THE GC OF AFFECTED AREAS PRIOR TO BIDDING7. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR REMOVAL AND REPLACEMENT OF
CEILINGS, CEILING TILES, AND CEILING GRIDS ASSOCIATED WITH AREAS OF WORK BY ALL CONTRACTORS. NOTIFY THE GENERAL CONTRACTOR OF AFFECTED AREAS PRIOR TO BIDDING.
8. WHERE EXISTING ELECTRICAL SYSTEMS ARE LOCATED IN AREAS THAT CONFLICT WITH NEW EQUIPMENT, PIPING, OR DUCTWORK TO BE INSTALLED, EACH CONTRACTOR SHALL EITHER ARRANGE NEW EQUIPMENT, CONDUIT, OR DUCTWORK IN SUCH A FASHION THAT IT DOES NOT CONFLICT WITH EXISTING SYSTEMS, OR REWORK EXISTING ELECTRICAL SYSTEMS TO ALLOW FOR INSTALLATION OF NEW EQUIPMENT, PIPING, OR DUCTWORK.
ELECTRICAL RENOVATION NOTES:THESE NOTES APPLY TO ALL ELECTRICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED TO, LIGHTING, POWER, AND SYSTEMS.
PLAN OR DETAIL NUMBER
PLAN OR DETAIL NAME
PLAN OR DETAIL SCALE
NAME
1VIEW NAME1/8" = 1'-0"
LEVEL NAME
10' - 0" HEIGHT ABOVE PROJECT 0' - 0"
1 INDICATES NOTE USED TO DESCRIBE ADDITIONAL INFORMATION ABOUT WORK REQUIRED, SPECIFIC TO THE SHEET AND/OR DETAIL
NO R
HT
INDICATES DIRECTION OF TRUE NORTH
VIEW KEY
NEW WORK BY THIS CONTRACTOR (DARK SOLID LINE)
NEW WORK BY OTHERS AND/OR EXISTING TO REMAIN (LIGHT SOLID LINE)
EXISTING TO BE REMOVED BY THIS CONTRACTOR(DARK SHORT DASHED LINE)
LINE TYPE KEY:
ELECTRICAL EQUIPMENT TAGS
TAG: DESCRIPTION:RELATED
SPECIFICATION
SW-1P SWITCH - SINGLE POLE
F# TROFFER
F# DOWNLIGHT LUMINAIRE
ECONN ELECTRICAL CONNECTIONE
E
PANEL '###' PANELBOARD - SURFACE MOUNT
REC-DUP 26 27 26 DUPLEX RECEPTACLE, 125V
ELECTRICAL SYMBOL LIST
SYMBOL: TAG:SPEC
SECTION:DESCRIPTION:
F# LINEAR LUMINAIRES
SW-3W SWITCH - THREE WAY3
26 27 26FB-# FLOOR BOX
REC-QUAD 26 27 26 QUAD RECEPTACLE, 125V
X# SINGLE FACE EXIT SIGN
X# DOUBLE FACE EXIT SIGN
XM# EMERGENCY UNIT
F# WALL BRACKET LUMINAIRE
SW-O SWITCH - OCCUPANCY SENSOR WALL SWITCHO 26 09 33
PP PUSH PADPP
DP-# DISTRIBUTION PANEL
FA-200 28 31 00 FIRE ALARM VISUAL NOTIFICATION DEVICE - WALL MOUNTED
V1 V3
V7 VH
FA-211 28 31 00 FIRE ALARM AUDIO/VISUAL NOTIFICATION DEVICE - WALL MOUNTED
A1 A3
A7 AH
AS
FA-201 28 31 00 FIRE ALARM VISUAL NOTIFICATION DEVICE - CEILING MOUNTED
V1 V3
V7 VH
FA-231 28 31 00 FIRE ALARM AUDIO/VISUAL NOTIFICATION DEVICE - CEILING MOUNTED
A1 A3
A7 AH
FA-230 28 31 00 FIRE ALARM AUDIO NOTIFICATION DEVICE - CEILING MOUNTED
A
SD FA-120 28 31 00 FIRE ALARM SMOKE DETECTOR - CEILING MOUNTED
FA-130 28 31 00 FIRE ALARM MANUAL PULL STATIONF
VS
VS
AS
REC-DUP-GFI 26 27 26 DUPLEX GFI RECEPTACLE, 125V
FB-1 26 27 26 FLOOR BOX - DUPLEX RECEPTACLE
F# WALL SCONCE LUMINAIRE
FAP-# FIRE ALARM - CONTROL PANEL 28 31 00
26 27 26
BRANCH CIRCUIT WIRING KEY
WIRE ID 2 WIRE 3 WIRE 4 WIRE
THHW/THWN COPPERCONDUCTORS
EQUIPMENTGROUNDINGCONDUCTOR CONDUIT
A# 2#12 3#12 4#12 1#12 3/4"
B# 2#10 3#10 4#10 1#10 3/4"
C# 2#8 3#8 4#8 1#10 3/4"
D# 2#6 3#6 4#6 1#10 1"
E# 2#4 3#4 4#4 1#8 1 1/4"
G# 2#2 3#2 4#2 1#8 1 1/4"
H# 2#1 3#1 4#1 1#6 1 1/2"
J# 2#1/0 3#1/0 4#1/0 1#6 2"
ALL BRANCH CIRCUITS SHALL INCLUDE THE EQUIPMENT GROUND CONDUCTOR
F# 2#3 3#3 4#3 1#8 1 1/4"
ELECTRICAL SHEET INDEXE-000 ELECTRICAL COVERSHEET
ED-101 FIRST FLOOR DEMOLITION - ELECTRICAL
ED-102 SECOND FLOOR DEMOLITION - ELECTRICAL
EL-101 FIRST FLOOR PLAN - LIGHTING
EL-102 SECOND FLOOR PLAN - LIGHTING
EP-100 BASEMENT FLOOR PLAN - POWER
EP-101 FIRST FLOOR PLAN - POWER
EP-102 SECOND FLOOR PLAN - POWER
EP-300 POWER DETAILS
ES-100 BASEMENT FLOOR PLAN - SYSTEMS
ES-101 FIRST FLOOR PLAN - SYSTEMS
ES-102 SECOND FLOOR PLAN - SYSTEMS
ES-300 SYSTEMS DETAILS
AREA OF WORKNO SCALE
FLOOR LEVEL
project number:
sheet title:
sheet number:
approved
project:
coordination checked
location
drawn
checked
designed
issue: date:
key plan:
WAYNE STATE
UNIVERSITYFacilities Planning and Management
5454 Cass Avenue
Detroit, MI 48202
FO
R B
IDS
consultants:
NM Project Number - 18113.0
Rands Building
IMEG Project Number -
Rands House - Rackham
Relocation
WSU : 00
- -
12/1
0/2
018 1
1:1
5:3
7A
M
E-000
ELECTRICAL COVERSHEET
JEFGLAMIKMIN
MARABR
18004050.01
MIKMIN
JEFGLA
WS
U R
an
ds B
ldg
Rackh
am
Relo
cati
on
18004050.0
1
REFERENCE SCALE IN INCHES
0 1 2 3
PROJECT #
IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
18004050.01
[Key*:] SEE BRANCH CIRCUIT WIRING KEY.
Total Amps: 14.33 26.64 34.97
Total Load: 1.72 kVA 3 kVA 4 kVA
41 2 0 -- -- -- SPACE 42 --
39NEW E-CONNECT. FPB-2.3 30 A 2 B2
2 0 1 20 A ELEC. WATER COOLER 40
37 1 0 1 20 A WOMENS HAND DRYER 38
35NEW E-CONNECT. FPB-2.2 20 A 2 A2
1 0 1 20 A MENS HAND DRYER 36
33 OUTLETS OFFICES CONF. 215 20 A 1 0 0 1 20 A 240 COPY MACH. 34
31 OUTLET RM 219 20 A 1 0 0 1 20 A CORRIDOR OUTLETS 32
29 OUTLETS OFFICES 220-221 20 A 1 0 0 1 20 A OUTLETS OFFICES 201-202 30
27 BATHROOM OUTLETS 20 A 1 0 0 1 20 A OUTLETS OFFICES 204-215 COR... 28
25 OUTLETS OFFICES 212-214 20 A 1 0 0 1 20 A OUTLETS OFFICES 202-203 26
23 OUTLETS OFFICES 211-212 20 A 1 0 0 1 20 A OUTLETS OFFICES 206-211 24
21 OUTLETS OFFICES 210-211 20 A 1 0 0 1 20 A OUTLETS OFFICES... 22
19 COFFEE MAKER 226 20 A 1 0 0 -- -- -- SPACE 20 --
17 MICROWAVE 226 20 A 1 0 1 18
-- 15 SPACE -- -- -- 0 1A2 2 20 A NEW E-CONNECT. FPB-2.1
16
13 NEW RECEPTACLES 20 A 1 A2 0.72 0 1 20 A UNKNOWN LOAD 14
11 EXHAUST FAN #2 20 A 1 0 0 1 20 A RECEPT. 229 12
9 LIGHTING CONF. 215 20 A 1 0 0 1 20 A SANYO RM 227 A/C 10
7 LIGHTING OFFICES 201-203 & 221 20 A 1 0 0 1 20 A LIGHTING OFFICES 204 8
5 LIGHTING OFFICES 212-214 20 A 1 0 0 1 20 A STAIRWELL LIGHTING 6
3 LIGHTING GENERAL OFFICE 211 20 A 1 0 0 1 20 A LIGHTING OFFICES 219-220 4
1 LIGHTING OFFICES 206-210 20 A 1 0 0 1 20 A CORRIDOR LIGHTING 222 2
CKTNO. LOAD DESCRIPTION
OVERCURRENTPROTECTIONAMPS P
WIREID
A B CWIRE
ID
OVERCURRENTPROTECTIONP AMPS LOAD DESCRIPTION
CKTNO.
Panel Notes: EXISTING PANEL. PROVIDE NEW BREAKER IN AVAILABLE SPACE FOR CIRCUIT 13. PROVIDE NEW 2 POLE 20A BREAKERS IN AVAILABLE SPACE FORCIRCUIT 16, 18 AND 35,37. PROVIDE NEW 2 POLE 30A BREAKER IN AVAILABLE SPACE FOR CIRCUIT 39,41.
LOCATION: IT 229 DEMAND: 8.72 kVA
SCCR: EXISTING WIRE: 4
FED FROM: EXISTING SWITCHBOARD GROUND BUS PHASE: 3
MOUNTING: SURFACE SOLID NEUTRAL VOLTS: 120/208 Wye
TYPE: BOLT-ON MAIN: 100 A/MCB
PANEL NAME: LPB CONNECTED 8.7 kVA
[Key*:] SEE BRANCH CIRCUIT WIRING KEY.
Total Amps: 29.32 27.76 1.56
Total Load: 3.1 kVA 2.91 kVA 0.19 kVA
-- 17 SPACE -- -- -- 0 0 -- -- -- SPACE 18 --
-- 15 SPACE -- -- -- 0 0 -- -- -- SPACE 16 --
13 0.19 0 -- -- -- SPACE 14 --
11NEW E-CONNECT. HRV-1 20 A 2 A2
0.19 0 -- -- -- SPACE 12 --
9 SUMP PUMP 20 A 1 0 2.91 10
7 OUTSIDE FRONT WALL PACKS 20 A 1 0 2.91B2 2 40 A NEW E-CONNECT. - AC-01
8
5 FURNACE #4 20 A 1 0 0 1 20 A SUITE 200 RECEPT. 6
3 FURNACE #2 20 A 1 0 0 1 20 A SUITE 200 RECEPT. 4
1 FURNACE #1 20 A 1 0 0 1 20 A SUITE 200 LIGHTS 2
CKTNO. LOAD DESCRIPTION
OVERCURRENTPROTECTIONAMPS P
WIREID
A B CWIRE
ID
OVERCURRENTPROTECTIONP AMPS LOAD DESCRIPTION
CKTNO.
Panel Notes: EXISTING PANEL
LOCATION: BASEMENT DEMAND: 6.2 kVA
SCCR: EXISTING WIRE: 4
FED FROM: GROUND BUS PHASE: 3
MOUNTING: SURFACE SOLID NEUTRAL VOLTS: 120/208 Wye
TYPE: BOLT-ON MAIN: 250 A/MCB
PANEL NAME: LPC2 CONNECTED 6.2 kVA
LIGHTING SEQUENCE OF OPERATIONPLAN ID LIGHTING SWITCHED
{LS1} Sequence: Switched lights are occupancy controlled in this space.ON: The lights are turn on by occupancy sensor.OFF: After the space has been vacant for 15 minutes, the lights will automatically turn off.
Owner Review 60% CD's Nov. 13, 2018
Owner Review 90% CD's Nov. 27, 2018
100% CD's Dec. 04, 2018
For Bids Dec. 11, 2018
REFER TO SPECIFICATION SECTIONS LIGHTING 26 51 00 AND EMERGENCY LIGHTING EQUIPMENT 26 52 00 FOR ADDITIONAL INFORMATION AND REQUIREMENTS.INTERIOR CORRELATED COLOR TEMPERATURE 4100K, COLOR RENDERING INDEX (CRI) AT OR ABOVE 80, UNLESS NOTED OTHERWISE.
CATALOG NUMBER SHALL NOT BE CONSIDERED COMPLETE AND MATERIAL SHALL NOT BE ORDERED BY MANUFACTURER AND CATALOG NUMBER ONLY. THE COMPLETE DESCRIPTION AND THESPECIFICATION SHALL BE COORDINATED WITH THE CATALOG NUMBER TO DETERMINE THE EXACT MATERIAL AND ACCESSORIES TO BE ORDERED. THE FIRST MANUFACTURER LISTED IS THEBASIS OF DESIGN.
VERIFY AND COORDINATE ALL CEILING TYPES WITH LUMINAIRE MOUNTING AND TRIM REQUIREMENTS PRIOR TO THE RELEASE OF THE LUMINAIRE ORDER.CONFIRM ALL COLORS AND FINISHES OF ALL LUMINAIRE COMPONENTS WITH ARCHITECT AND INTERIOR DESIGNER PRIOR TO THE RELEASE OF THE LUMINAIRE ORDER.UNLESS INDICATED ON LIGHTING PLANS OR BELOW, REFER TO ARCHITECTURAL AND INTERIOR DESIGN ELEVATIONS, SECTIONS AND DETAILS FOR ALL SUSPENDED AND WALL MOUNTEDLUMINAIRE MOUNTING HEIGHTS.
EM - EMERGENCY BATTERY
(TYPE) BALLAST/DRIVER:
(WATT) PER: FIX - FIXTURE, FT - FOOT, LAMP
LED - LIGHT EMITTING DIODE WL - WALL
(TYPE) LIGHT SOURCE TECHNOLOGY: (MTG) MOUNTING:
CFSA - COLOR-FINISH SELECTION BY ARCHITECT O - OTHER (SEE DESCRIPTION)
FINISH: (L/L) LENS/LOUVER:
LUMINAIRE SCHEDULE
ITEM DESCRIPTION L/L MTG
DIMENSIONS WATTLIGHT SOURCETECHNOLOGY BALLAST/DRIVER
APPROVEDMANUFACTURERL W H DIA.
MAXANSI PER TYPE QTY
MODEL/ABSOLUTE
LUMENS (MIN) VOLTS TYPE
EM1 EMERGENCY UNIT, TWO ADJUSTABLE LEDHEADS, WHITE THERMOPLASTIC HOUSING.SELF TEST & DIAGNOSTICS OF INVERTERAND LAMPS
O WL 11" 3 1/2" 7 1/2" 3 W FIX LED 2 6 VOLT (2INCLUDED)
120 V EM DUAL-LITE EVHCLITHONIA ELML4
A1
F
F
SD
A1
F
A1 F
PP
SD
J
J
J
J J
J
J
J
J
A1
1 2 3 41.9 2.5 3.1 3.2 3.5 3.8
A
b
c
d
e
f
a10
a9
b4
c.1
c.2
c.3
c.4
e.8
+42
+42
TELEPHONE T
+42
+42
A
EXISTING LPA
FURNITURE FEED
FURNITURE FEED
FURNITURE FEED FURNITURE FEED
FURNITURE FEED
FURNITURE FEED
FURNITURE FEED
FURNITURE FEED
FACP
A
1
AREA OF WORKNO SCALE
FLOOR LEVEL
project number:
sheet title:
sheet number:
approved
project:
coordination checked
location
drawn
checked
designed
issue: date:
key plan:
WAYNE STATE
UNIVERSITYFacilities Planning and Management
5454 Cass Avenue
Detroit, MI 48202
FO
R B
IDS
consultants:
NM Project Number - 18113.0
Rands Building
IMEG Project Number -
Rands House - Rackham
Relocation
WSU : 00
- -
12/1
0/2
018 1
1:1
5:3
8A
M
ED-101
FIRST FLOOR DEMOLITION -
ELECTRICAL
JEFGLAMIKMIN
MARABR
18004050.01
MIKMIN
JEFGLA
WS
U R
an
ds B
ldg
Rackh
am
Relo
cati
on
18004050.0
1
NO R
HT
1/8" = 1'-0"1 FIRST FLOOR DEMOLITION - ELECTRICAL
REFERENCE SCALE IN INCHES
0 1 2 3
PROJECT #
IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
18004050.01
KEYNOTES:
1. REMOVE/REPLACE EXISTING FIRE ALARM PANEL/SYSTEM. RETAIN CIRCUIT FOR NEW FIRE ALARM PANEL.
#
Owner Review 60% CD's Nov. 13, 2018
Owner Review 90% CD's Nov. 27, 2018
100% CD's Dec. 04, 2018
For Bids Dec. 11, 2018
WHITE BOARD
projection
screen
E
J
A1
F V1
SD
V1
F
J
J
J
J
1 2 3 41.9 2.5 3.1 3.2 3.5 3.8
A
b
c
d
e
f
a10
a9
b4
c.1
c.2
c.3
c.4
e.8
EXHAUST FAN CONTROL RELAY
+42
+42
+42
EXISTING PP1
EXISTING LPB
111FURNITURE FEED
FURNITURE FEED FURNITURE FEED
3/a
3/b
3/a3/b
A
FURNITURE FEED
A A
AREA OF WORKNO SCALE
FLOOR LEVEL
project number:
sheet title:
sheet number:
approved
project:
coordination checked
location
drawn
checked
designed
issue: date:
key plan:
WAYNE STATE
UNIVERSITYFacilities Planning and Management
5454 Cass Avenue
Detroit, MI 48202
FO
R B
IDS
consultants:
NM Project Number - 18113.0
Rands Building
IMEG Project Number -
Rands House - Rackham
Relocation
WSU : 00
- -
12/1
0/2
018 1
1:1
5:3
9A
M
ED-102
SECOND FLOOR DEMOLITION -
ELECTRICAL
JEFGLAMIKMIN
MARABR
18004050.01
MIKMIN
JEFGLA
WS
U R
an
ds B
ldg
Rackh
am
Relo
cati
on
18004050.0
1
NO R
HT
1/8" = 1'-0"1 SECOND FLOOR DEMOLITION - ELECTRICAL
REFERENCE SCALE IN INCHES
0 1 2 3
PROJECT #
IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
18004050.01
KEYNOTES:
1. REMOVE EXISTING FIXTURE AND RELOCATED FOR REUSE.
#
Owner Review 60% CD's Nov. 13, 2018
Owner Review 90% CD's Nov. 27, 2018
100% CD's Dec. 04, 2018
For Bids Dec. 11, 2018
111
117
125
129
137 141
143
145
144142138
140136
134
132
130
128
126
122
120
124
118
116
112
108
106
102
100
103107
DN
UP
UP
CL
OFFICE
COVERED AREA
RESEARCHLAB
OFFICE
IT OFFICE
TREATMENT
OFFICE
TREATMENTOFFICEOFFICE
TREATMENTCHILDPLAYROOM
OBSERVATION
TREATMENT
TREATMENT
OFFICE
OFFICE
JC
UNISEXADA
WOMEN
WAITING
WAITING
LOUNGE
OFFICE
PLANTERSTORAGE
STORAGE
OPENOFFICE
VEST
PORCH
OPENOFFICE
CONFERENCE ROOMOFFICE
1 2 3 41.9 2.5 3.1 3.2 3.5 3.8
A
b
c
d
e
f
a10
a9
b4
c.1
c.2
c.3
c.4
e.8
1
O
O
EM1
EM1
EM1
EM1
EM1
2
2
2
2
2
AREA OF WORKNO SCALE
FLOOR LEVEL
project number:
sheet title:
sheet number:
approved
project:
coordination checked
location
drawn
checked
designed
issue: date:
key plan:
WAYNE STATE
UNIVERSITYFacilities Planning and Management
5454 Cass Avenue
Detroit, MI 48202
FO
R B
IDS
consultants:
NM Project Number - 18113.0
Rands Building
IMEG Project Number -
Rands House - Rackham
Relocation
WSU : 00
- -
12/1
0/2
018 1
1:1
5:3
9A
M
EL-101
FIRST FLOOR PLAN - LIGHTING
JEFGLAMIKMIN
MARABR
18004050.01
MIKMIN
JEFGLA
WS
U R
an
ds B
ldg
Rackh
am
Relo
cati
on
18004050.0
1
NO R
HT
1/8" = 1'-0"1 FIRST FLOOR PLAN - LIGHTING
REFERENCE SCALE IN INCHES
0 1 2 3
PROJECT #
IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
18004050.01
SHEET NOTES :
1. CLEAN AND RELAMP ALL FIXTURES. SURFACE 2X4 ARE 3-LAMP, SURFACE 1X4 ARE 2-LAMP, AND DOWNLIGHTS, WALL SCONCES, AND DECORATIVE FIXTURES ARE COMPACT FLUORESCENT.
2. REPLACE LAMPS AND BATTERIES IN EXISTING EXIT SIGNS AND EMERGENCY BATTERY UNITS.
KEYNOTES:
1. REPLACE BALLASTS WITH REDUCED WATTAGE BALLASTS.
2. EXTEND UNSWITCHED PORTION OF BRANCH CIRCUIT SERVING THIS ROOM TO EMERGENCY FIXTURE.
#
Owner Review 60% CD's Nov. 13, 2018
Owner Review 90% CD's Nov. 27, 2018
100% CD's Dec. 04, 2018
For Bids Dec. 11, 2018
WHITE BOARD
projection
screen
244
240
245
229
227
225
219
217
243242241
246
247
238236
230
226
224
220
218
214212
202
200.1
200
201
203205
234
232
207
OFFICE
OPENOFFICE
OPENOFFICE
IT
MECH
TREATMENT
OBSERVATION
TREATMENT
COMFERENCE/GROUP ROOMOBSERVATIONTREATMENT
TREATMENT
OBSERVATION
TREATMENTTREATMENT
ADULTGROUP ROOM
ADULTGROUP ROOM
WOMEN
UNISEX ADA
CHILDREN'SGROUP ROOM
OFFICETREATMENT
DN
UP
OPENOFFICE
STORAGE
DN
OPENOFFICE
OPENOFFICE
OFFICEOFFICE
OBSERVATION
TREATMENT
OPEN
UP
OFFICE
{LS1}{LS1}{LS1}
1 2 3 41.9 2.5 3.1 3.2 3.5 3.8
A
b
c
d
e
f
a10
a9
b4
c.1
c.2
c.3
c.4
e.8
O O
3/a
3/b
3/b 3/a
1 11
EM1EM1
EM1EM1
EM1
EM1
22
2
2
2
2
AREA OF WORKNO SCALE
FLOOR LEVEL
project number:
sheet title:
sheet number:
approved
project:
coordination checked
location
drawn
checked
designed
issue: date:
key plan:
WAYNE STATE
UNIVERSITYFacilities Planning and Management
5454 Cass Avenue
Detroit, MI 48202
FO
R B
IDS
consultants:
NM Project Number - 18113.0
Rands Building
IMEG Project Number -
Rands House - Rackham
Relocation
WSU : 00
- -
12/1
0/2
018 1
1:1
5:4
0A
M
EL-102
SECOND FLOOR PLAN -
LIGHTING
JEFGLAMIKMIN
MARABR
18004050.01
MIKMIN
JEFGLA
WS
U R
an
ds B
ldg
Rackh
am
Relo
cati
on
18004050.0
1
NO R
HT
1/8" = 1'-0"1 SECOND FLOOR PLAN - LIGHTING
REFERENCE SCALE IN INCHES
0 1 2 3
PROJECT #
IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
18004050.01
KEYNOTES:
1. RELOCATED FIXTURE. EXTEND BRANCH CIRCUIT FROM EXISTING LIGHTING.
2. EXTEND UNSWITCHED PORTION OF BRANCH CIRCUIT SERVING THIS ROOM TO EMERGENCY FIXTURE.
#
SHEET NOTES :
1. CLEAN AND RELAMP ALL FIXTURES. SURFACE 2X4 ARE 3-LAMP, SURFACE 1X4 ARE 2-LAMP, AND DOWNLIGHTS, WALL SCONCES, AND DECORATIVE FIXTURES ARE COMPACT FLUORESCENT.
2. REPLACE LAMPS AND BATTERIES IN EXISTING EXIT SIGNS AND EMERGENCY BATTERY UNITS.
Owner Review 60% CD's Nov. 13, 2018
Owner Review 90% CD's Nov. 27, 2018
100% CD's Dec. 04, 2018
For Bids Dec. 11, 2018
HOUSE
43.8
d
e
f
c.3
c.4
e.8
EXISTING DP-1
EXISTING LPC
EXISTING LPC2
AREA OF WORKNO SCALE
FLOOR LEVEL
project number:
sheet title:
sheet number:
approved
project:
coordination checked
location
drawn
checked
designed
issue: date:
key plan:
WAYNE STATE
UNIVERSITYFacilities Planning and Management
5454 Cass Avenue
Detroit, MI 48202
FO
R B
IDS
consultants:
NM Project Number - 18113.0
Rands Building
IMEG Project Number -
Rands House - Rackham
Relocation
WSU : 00
- -
12/1
0/2
018 1
1:1
5:4
0A
M
EP-100
BASEMENT FLOOR PLAN -
POWER
JEFGLAMIKMIN
MARABR
18004050.01
MIKMIN
JEFGLA
WS
U R
an
ds B
ldg
Rackh
am
Relo
cati
on
18004050.0
1
REFERENCE SCALE IN INCHES
0 1 2 3
PROJECT #
IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
18004050.01
NO R
HT
1/8" = 1'-0"1 BASEMENT FLOOR PLAN - POWER
100% CD's Dec. 04, 2018
For Bids Dec. 11, 2018
111
117
125
129
137 141
143
145
144142138
140136
134
132
130
128
126
122
120
124
118
116
112
108
106
102
100
103107
DN
UP
UP
CL
OFFICE
COVERED AREA
RESEARCHLAB
OFFICE
IT OFFICE
TREATMENT
OFFICE
TREATMENTOFFICEOFFICE
TREATMENTCHILDPLAYROOM
OBSERVATION
TREATMENT
TREATMENT
OFFICE
OFFICE
JC
UNISEXADA
WOMEN
WAITING
WAITING
LOUNGE
OFFICE
PLANTERSTORAGE
STORAGE
OPENOFFICE
VEST
PORCH
OPENOFFICE
CONFERENCE ROOMOFFICE
copier
PP
E
1 2 3 41.9 2.5 3.1 3.2 3.5 3.8
A
b
c
d
e
f
a10
a9
b4
c.1
c.2
c.3
c.4
e.8
+42
+42
+60
EXISTING LPA
A
1
1
1
1 1
1
1
2
INTERCOM POWER SUPPLY
ELECTRONIC SENSOR
3
AREA OF WORKNO SCALE
FLOOR LEVEL
project number:
sheet title:
sheet number:
approved
project:
coordination checked
location
drawn
checked
designed
issue: date:
key plan:
WAYNE STATE
UNIVERSITYFacilities Planning and Management
5454 Cass Avenue
Detroit, MI 48202
FO
R B
IDS
consultants:
NM Project Number - 18113.0
Rands Building
IMEG Project Number -
Rands House - Rackham
Relocation
WSU : 00
- -
12/1
0/2
018 1
1:1
5:4
1A
M
EP-101
FIRST FLOOR PLAN - POWER
JEFGLAMIKMIN
MARABR
18004050.01
MIKMIN
JEFGLA
WS
U R
an
ds B
ldg
Rackh
am
Relo
cati
on
18004050.0
1
NO R
HT
1/8" = 1'-0"1 FIRST FLOOR PLAN - POWER
REFERENCE SCALE IN INCHES
0 1 2 3
PROJECT #
IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
18004050.01
KEYNOTES:
1. EXTEND EXISTING BRANCH CIRCUIT IN ROOM TO NEW DEVICE.
2. CIRCUIT RECEPTACLE TO SPARE 20A BREAKER IN PANEL LPA.
3. EXTEND BRANCH CIRCUIT FROM THE RECEPTACLE. REFER TO THE 'ELECTRONIC SENSOR WIRING' DETAIL ON SHEET EP-300.
#
Owner Review 60% CD's Nov. 13, 2018
Owner Review 90% CD's Nov. 27, 2018
100% CD's Dec. 04, 2018
For Bids Dec. 11, 2018
WHITE BOARD
projection
screen
244
240
245
229
227
225
219
217
243242241
246
247
238236
230
226
224
220
218
214212
202
200.1
200
201
203205
234
232
207
OFFICE
OPENOFFICE
OPENOFFICE
IT
MECH
TREATMENT
OBSERVATION
TREATMENT
COMFERENCE/GROUP ROOMOBSERVATIONTREATMENT
TREATMENT
OBSERVATION
TREATMENTTREATMENT
ADULTGROUP ROOM
ADULTGROUP ROOM
WOMEN
UNISEX ADA
CHILDREN'SGROUP ROOM
OFFICETREATMENT
DN
UP
OPENOFFICE
STORAGE
DN
OPENOFFICE
OPENOFFICE
OFFICEOFFICE
OBSERVATION
TREATMENT
OPEN
UP
OFFICE
E
E
E
E E
E
J
E
1 2 3 41.9 2.5 3.1 3.2 3.5 3.8
A
b
c
d
e
f
a10
a9
b4
c.1
c.2
c.3
c.4
e.8
+42
+60
FB-1
EXHAUST FAN CONTROL RELAY
AC-01
FPB-2.1 FPB-2.2
FPB-2.3
HRV-1
EXISTING PP1
EXISTING LPB
+42
+42
+42
LPC2-8,10LPC2-11,13
LPB-39,41
LPB-35,37LPB-16,18
1
1
1
1
1LPB-13LPB-13
2
2
A
AA
33
1
INTERCOM POWER SUPPLY
ELECTRONIC SENSOR
1
AREA OF WORKNO SCALE
FLOOR LEVEL
project number:
sheet title:
sheet number:
approved
project:
coordination checked
location
drawn
checked
designed
issue: date:
key plan:
WAYNE STATE
UNIVERSITYFacilities Planning and Management
5454 Cass Avenue
Detroit, MI 48202
FO
R B
IDS
consultants:
NM Project Number - 18113.0
Rands Building
IMEG Project Number -
Rands House - Rackham
Relocation
WSU : 00
- -
12/1
0/2
018 1
1:1
5:4
2A
M
EP-102
SECOND FLOOR PLAN - POWER
JEFGLAMIKMIN
MARABR
18004050.01
MIKMIN
JEFGLA
WS
U R
an
ds B
ldg
Rackh
am
Relo
cati
on
18004050.0
1
NO R
HT
1/8" = 1'-0"1 SECOND FLOOR PLAN - POWER
REFERENCE SCALE IN INCHES
0 1 2 3
PROJECT #
IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
18004050.01
KEYNOTES:
1. EXTEND EXISTING BRANCH CIRCUIT IN ROOM TO NEW DEVICE.
2. PROVIDE SURFACE RACEWAY FOR RECEPTACLE. REFER TO 'SURFACE WIREWAY DETAIL' ON SHEET EP-300.
3. ADD/ALTERNATE4. EXTEND BRANCH CIRCUIT FROM THE
RECEPTACLE. REFER TO THE 'ELECTRONIC SENSOR WIRING' DETAIL ON SHEET EP-300.
#
Owner Review 60% CD's Nov. 13, 2018
Owner Review 90% CD's Nov. 27, 2018
100% CD's Dec. 04, 2018
For Bids Dec. 11, 2018
SEE ARCHITECTURALPLANS FOR WALL CONSTRUCTION
PLASTER RING TO COMEWITHIN 1/8" OF FINAL SURFACE
STUD
MOUNTING BRACKET SHALL PROVIDESUPPORT FROM STUD AND BACK OFWALL OR TWO STUDS.
NOTES :
1. THE INTENT OF THE DETAIL IS TO ENSURE DEVICE ROUGH-INS ARE ALIGNED, SOLIDLY MOUNTED AND THE SURFACE OF THE TRIM IS EITHER FLUSH WITH THE WALL SURFACE OR WITHIN 1/8" OF THE WALL SURFACE. JUNCTION BOXES LARGER THAN 4" SQUARE SHALL BE MOUNTED IN A MANNER THAT IS SIMILAR TO THE SYSTEM NOTED ABOVE OR ACHIEVES THE SAME RESULTS.
2. PLASTER RINGS DEPTH SHALL BE 1/8" DEEPER THAN THE GYP BOARD APPLIED TO THE WALL. PLASTER RING SHALL BE 3/4" FOR USE WITH 5/8" GYP BOARD.
3. MOUNTING BRACKET FOR 2 1/2" OR 3 1/2" STUDS SHALL BE CADDY #H23, OR B-LINE BB4-23. MOUNTING BRACKET FOR FOR 4" OR 6" STUDS SHALL BE CADDY #H46TC OR B-LINE BB4-# . FOR MULTIPLE BOXES BETWEEN STUDS, BRACKET SHALL BE CADDY #RBS16/#RBS24 OR B-LINE BB6-# OR BBF# FLOOR MOUNT SUPPORT WITH BBFC.
4. WHERE RECEPTACLE AND TECHNOLOGY DEVICES ARE SHOWN SERVING A COMMON COMPUTER OR EQUIPMENT, OR SHOWN IN SIMILAR LOCATIONS ON THE DRAWINGS THE DEVICES SHALL BE INSTALLED ON OPPOSITE SIDES OF A COMMON STUD OR IN ADJACENT OPENINGS WITH MOUNTING BRACKETS.
RATED WALL (CONSTRUCTION VARIES)
NOTE 2
FIRE SEALANT
NOTE 3
FIRE SEALANT
PENETRATING ITEM
NOTE 4
NOTE 3
NOTE 2
PENETRATING ITEM
NOTE 4
NOTE 3
RATED FLOOR (CONSTRUCTION VARIES)
NOTES :
1. THIS GENERAL DETAIL APPLIES TO ALL ITEMS PENETRATING FIRE RATED WALLS OR FLOORS. THE INTENT IS TO MAINTAIN THE FIRE RATING AND TO ALLOW LONGITUDINAL MOVEMENT. REFER TO SPECIFICATION SECTION 07840 (16080) FOR SELECTION OF THROUGH PENETRATION FIRE STOPPING.
2. SCHEDULE 5 PIPE SLEEVE EMBEDDED IN WALL OR FLOOR, OR SMOOTH CORE DRILL. EACH CONTRACTOR FURNISHES SLEEVE TO G.C., COORDINATES SLEEVE LOCATIONS AND DEBURS SLEEVE. G.C. BUILDS SLEEVE INTO WALL OR FLOOR ALLOWING NO GAP AROUND SLEEVE. IF SLEEVE IS NOT PROVIDED WHEN WALL OR FLOOR IS BUILT, CONTRACTOR SHALL INSTALL SLEEVE. SLEEVE SIZE SHALL ALLOW ANNULAR SPACE REQUIRED BY THE SELECTED FIRE STOP SYSTEM.
3. INSTALL BACKING MATERIAL, SUCH AS MINERAL WOOL SAFING, AS REQUIRED FOR FIRE STOP SYSTEM. INSTALL IN ACCORDANCE WITH FIRE STOP SYSTEM APPLICATION LISTING. SECURE TO WALL OR FLOOR TO ALLOW LONGITUDINAL MOVEMENT OF PENETRATING ITEM WITHOUT MOVEMENT OF FIRE BARRIER.
4. WATER-TIGHT WELDED 1"x1" 20 GAUGE MINIMUM GALVANIZED SHEET METAL ANGLE FRAME, BY CONTRACTOR IN EQUIPMENT ROOMS FOR WATER STOP. PLACE A BEAD OF WATERPROOF SEALANT BETWEEN FLOOR AND BOTTOM OF ANGLE FRAME. SECURE TO FLOOR WITH MASONRY ANCHORS IN CORNERS AND ON 12" MAXIMUM CENTERS. MULTIPLE PENETRATING ITEMS MAY BE ENCLOSED IN ONE FRAME.
DUPLEX RECEPTACLE(DESIGNATED ON PLANS)
1 1/4" TELECOMM CONDUIT(S) AS REQUIRED
BRANCH CIRCUIT CONDUIT(S)
SURFACE RACEWAY TOABOVE ACCESSIBLE CEILING
WW-#4 3/4" HIGH X 1 3/4" DEEP SURFACEMETAL RACEWAY WITH LOW VOLTAGE DIVIDER.LENGTH AS SHOWN ON DRAWINGS.
TR
CLASS II LOW VOLTAGE TRANSFORMER, WITH PRIMARY AND SECONDARY FUSING. MOUNT IN NEMA 1 ENCLOSURE ABOVE ACCESSIBLE CEILING.
H
GND
2#14 & 1#14 GND IN 1/2" FLEXFOR LOW VOLTAGE CLASS IIWIRING TO CONTROL MODULES.
MOUNTED ONWALL, BEHINDWATER CLOSET.
MAXIMUM OF SIX MODULESPER TRANSFORMER. MAXIMUM 50' WIRING LENGTH.
LOW VOLTAGESOLENOID VALVE.
WATER CLOSET LOWVOLTAGE SENSOR /CONTROL
N
NOTES :
1. PROVIDE DOUBLE GANG BACKBOXES AND PLASTER RINGS AT LOCATIONS COORDINATED WITH PLUMBING CONTRACTOR (P.C.)
2. E.C. SHALL FIELD VERIFY EXACT SENSOR LOCATION WITH P.C. PRIOR TO ROUGH-IN.
AREA OF WORKNO SCALE
FLOOR LEVEL
project number:
sheet title:
sheet number:
approved
project:
coordination checked
location
drawn
checked
designed
issue: date:
key plan:
WAYNE STATE
UNIVERSITYFacilities Planning and Management
5454 Cass Avenue
Detroit, MI 48202
FO
R B
IDS
consultants:
NM Project Number - 18113.0
Rands Building
IMEG Project Number -
Rands House - Rackham
Relocation
WSU : 00
- -
12/1
0/2
018 1
1:1
5:4
3A
M
EP-300
POWER DETAILS
JEFGLAMIKMIN
MARABR
18004050.01
MIKMIN
JEFGLA
WS
U R
an
ds B
ldg
Rackh
am
Relo
cati
on
18004050.0
1
REFERENCE SCALE IN INCHES
0 1 2 3
PROJECT #
IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
18004050.01
NO SCALE1 BACKBOX MOUNTING DETAIL
NO SCALE3 FIRE BARRIER PENETRATION
NO SCALE2 SURFACE WIREWAY DETAIL
Owner Review 60% CD's Nov. 13, 2018
Owner Review 90% CD's Nov. 27, 2018
100% CD's Dec. 04, 2018
For Bids Dec. 11, 2018
NO SCALE4 ELECTRONIC SENSOR WIRING
HOUSE
A7
V1
A1
43.8
d
e
f
c.3
c.4
e.8
AREA OF WORKNO SCALE
FLOOR LEVEL
project number:
sheet title:
sheet number:
approved
project:
coordination checked
location
drawn
checked
designed
issue: date:
key plan:
WAYNE STATE
UNIVERSITYFacilities Planning and Management
5454 Cass Avenue
Detroit, MI 48202
FO
R B
IDS
consultants:
NM Project Number - 18113.0
Rands Building
IMEG Project Number -
Rands House - Rackham
Relocation
WSU : 00
- -
12/1
0/2
018 1
1:1
5:4
3A
M
ES-100
BASEMENT FLOOR PLAN -
SYSTEMS
JEFGLAMIKMIN
MARABR
18004050.01
MIKMIN
JEFGLA
WS
U R
an
ds B
ldg
Rackh
am
Relo
cati
on
18004050.0
1
REFERENCE SCALE IN INCHES
0 1 2 3
PROJECT #
IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
18004050.01
For Bids Dec. 11, 2018
NO R
HT
1/8" = 1'-0"1 BASEMENT FLOOR PLAN - SYSTEMS
111
117
125
129
137 141
143
145
144142138
140136
134
132
130
128
126
122
120
124
118
116
112
108
106
102
100
103107
DN
UP
UP
CL
OFFICE
COVERED AREA
RESEARCHLAB
OFFICE
IT OFFICE
TREATMENT
OFFICE
TREATMENTOFFICEOFFICE
TREATMENTCHILDPLAYROOM
OBSERVATION
TREATMENT
TREATMENT
OFFICE
OFFICE
JC
UNISEXADA
WOMEN
WAITING
WAITING
LOUNGE
OFFICE
PLANTERSTORAGE
STORAGE
OPENOFFICE
VEST
PORCH
OPENOFFICE
CONFERENCE ROOMOFFICE
copier
F
F
F
F
SD
SD
A1A1
A1
SD
A3
A
A1
A7
A1
V1
V1
A3
A1
V7
A7
A1
A1
A7
AR
F
1 2 3 41.9 2.5 3.1 3.2 3.5 3.8
A
b
c
d
e
f
a10
a9
b4
c.1
c.2
c.3
c.4
e.8
FAP-1
1
ELEVATOR RECALL INMACHINE ROOM
AREA OF WORKNO SCALE
FLOOR LEVEL
project number:
sheet title:
sheet number:
approved
project:
coordination checked
location
drawn
checked
designed
issue: date:
key plan:
WAYNE STATE
UNIVERSITYFacilities Planning and Management
5454 Cass Avenue
Detroit, MI 48202
FO
R B
IDS
consultants:
NM Project Number - 18113.0
Rands Building
IMEG Project Number -
Rands House - Rackham
Relocation
WSU : 00
- -
12/1
0/2
018 1
1:1
5:4
3A
M
ES-101
FIRST FLOOR PLAN - SYSTEMS
JEFGLAMIKMIN
MARABR
18004050.01
MIKMIN
JEFGLA
WS
U R
an
ds B
ldg
Rackh
am
Relo
cati
on
18004050.0
1
NO R
HT
1/8" = 1'-0"1 FIRST FLOOR PLAN - SYSTEMS
REFERENCE SCALE IN INCHES
0 1 2 3
PROJECT #
IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
18004050.01
KEYNOTES:
1. CIRCUIT NEW F.A. PANEL TO EXISTING CIRCUIT RETAINED DURING DEMOLITION.
#
100% CD's Dec. 04, 2018
For Bids Dec. 11, 2018
WHITE BOARD
projection
screen
244
240
245
229
227
225
219
217
243242241
246
247
238236
230
226
224
220
218
214212
202
200.1
200
201
203205
234
232
207
OFFICE
OPENOFFICE
OPENOFFICE
IT
MECH
TREATMENT
OBSERVATION
TREATMENT
COMFERENCE/GROUP ROOMOBSERVATIONTREATMENT
TREATMENT
OBSERVATION
TREATMENTTREATMENT
ADULTGROUP ROOM
ADULTGROUP ROOM
WOMEN
UNISEX ADA
CHILDREN'SGROUP ROOM
OFFICETREATMENT
DN
UP
OPENOFFICE
STORAGE
DN
OPENOFFICE
OPENOFFICE
OFFICEOFFICE
OBSERVATION
TREATMENT
OPEN
UP
OFFICE
SD
SD
F
F
F
A7
V1
V1
A3
A1
A1
A1
A1
AV1
V1
V1
V1
V1
A3
V1
V1
1 2 3 41.9 2.5 3.1 3.2 3.5 3.8
A
b
c
d
e
f
a10
a9
b4
c.1
c.2
c.3
c.4
e.8
AREA OF WORKNO SCALE
FLOOR LEVEL
project number:
sheet title:
sheet number:
approved
project:
coordination checked
location
drawn
checked
designed
issue: date:
key plan:
WAYNE STATE
UNIVERSITYFacilities Planning and Management
5454 Cass Avenue
Detroit, MI 48202
FO
R B
IDS
consultants:
NM Project Number - 18113.0
Rands Building
IMEG Project Number -
Rands House - Rackham
Relocation
WSU : 00
- -
12/1
0/2
018 1
1:1
5:4
4A
M
ES-102
SECOND FLOOR PLAN -
SYSTEMS
JEFGLAMIKMIN
MARABR
18004050.01
MIKMIN
JEFGLA
WS
U R
an
ds B
ldg
Rackh
am
Relo
cati
on
18004050.0
1
NO R
HT
1/8" = 1'-0"1 SECOND FLOOR PLAN - SYSTEMS
REFERENCE SCALE IN INCHES
0 1 2 3
PROJECT #
IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
18004050.01
100% CD's Dec. 04, 2018
For Bids Dec. 11, 2018
J
NEP
SIGNAL LINE CIRCUIT (SLC)
NOTIFICATION APPLIANCE CIRCUIT (NAC)
EVACUATION - SIGNALING ZONE #
NOTIFICATION APPLIANCE CIRCUIT (NAC)
NEW FAP-1
SIGNAL LINE CIRCUIT(SLC)
CIRCUIT INTEGRITY WIRING. (TYPICAL)
AR TO ELEVATOR SHUNT TRIP BREAKER
FT H SD
2 31
SD MM MM
V
A
F
2
J
V1 V1 V11
3
A A MH HW
A1 A11 A11
KEYNOTES:
PROVIDE NOTIFICATION APPLIANCE EXTENDER PANELS AS REQUIRED. DETERMINATION OF NEED TO BE MADE BY FIRE ALARM VENDOR. REFER TO SPECIFICATIONS FOR REQUIREMENTS AND ACCEPTABLE MOUNTING LOCATIONS.
REFER TO SPECIFICATION FOR REQUIREMENTS OF EACH INITIATION LOOP AND WIRING STYLE. REFER TO FLOOR PLANS FOR DEVICES AND THEIR LOCATIONS.
REFER TO SPECIFICATION FOR REQUIREMENTS OF EACH NOTIFICATION APPLIANCE CIRCUIT AND WIRING STYLE. REFER TO FLOOR PLANS FOR DEVICES AND THEIR LOCATIONS.
1
2
3
NOTES :
1. THE RISER DIAGRAM IS INTENDED TO CONVEY THE TYPES OF FIRE ALARM CONNECTIONS AND SPECIFICALLY DOES NOT INDICATE QUANTITIES, NUMBER OF CIRCUITS REQUIRED OR DISTANCES.
2. THE COMPLETE FIRE ALARM SYSTEM SHALL MEET ALL APPLICABLE CODES AND MANUFACTURER'S RECOMMENDATIONS.
3. CONTRACTOR SHALL COORDINATE ALL WIRE SIZES, TYPES AND REQUIREMENTS WITH THE VENDOR PRIOR TO BID. REFER TO SPECIFICATIONS TO DETERMINE CIRCUIT STYLES AND IF CONDUIT IS REQUIRED OR PLENUM RATED CABLE IS ACCEPTABLE.
4. ALL +120VAC WIRING REQUIRED FOR OPERATION OF THE SYSTEM AS DESCRIBED IN THE CONSTRUCTION DOCUMENTS SHALL BE PROVIDED BY THE ELECTRICAL CONTRACTOR.
5. ALL NECESSARY RELAYS MAY NOT BE SHOWN ON THIS PLAN, BUT WHERE REQUIRED FOR PROPER OPERATION OF THE SYSTEM THEY SHALL BE PROVIDED BY THE CONTRACTOR.
AREA OF WORKNO SCALE
FLOOR LEVEL
project number:
sheet title:
sheet number:
approved
project:
coordination checked
location
drawn
checked
designed
issue: date:
key plan:
WAYNE STATE
UNIVERSITYFacilities Planning and Management
5454 Cass Avenue
Detroit, MI 48202
FO
R B
IDS
consultants:
NM Project Number - 18113.0
Rands Building
IMEG Project Number -
Rands House - Rackham
Relocation
WSU : 00
- -
12/1
0/2
018 1
1:1
5:4
4A
M
ES-300
SYSTEMS DETAILS
JEFGLAMIKMIN
MARABR
18004050.01
MIKMIN
JEFGLA
WS
U R
an
ds B
ldg
Rackh
am
Relo
cati
on
18004050.0
1
REFERENCE SCALE IN INCHES
0 1 2 3
PROJECT #
IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
18004050.01
NO SCALE1 FIRE ALARM RISER
100% CD's Dec. 04, 2018
For Bids Dec. 11, 2018
TECHNOLOGY SYMBOL LIST
SYMBOL: DESCRIPTION: NOTE:EQUIPMENT
LIST ABBREV.:
CAM .AV CEILING CAMERAAV-CAM-1
C#1.INFORMATION OUTLET (WALL)SC-IO-W
.POKE THROUGH FOR FURNITURE FEEDN/A
IS1
IM1 .INTERCOM MASTER STATION - TYPE 1 (WALL)IC-IM1-W
.INTERCOM STATION - TYPE 1 (WALL)IC-IS1-W
JB1 .TECHNOLOGY JUNCTION BOX - WALL - TYPE 1AV-JB1-W#
CR1 .CREDENTIAL READER - TYPE 1 - ROUGH INAC-CR1-W
TECHNOLOGY ABBREVIATION KEY
ENTRANCE FACILITYEF-#
MAIN CROSS-CONNECTMC-#
TELECOMMUNICATIONS ROOMTR-#
ABOVE FINISHED FLOORAFF
BELOW FINISHED CEILINGBFC
CONDUITC
SIMILARSIM
TYPICALTYP
MOUNTING HEIGHT ABOVE FINISHED FLOOR+#
JUNCTION BOXJ-BOX
ABBR: DESCRIPTION:
UNLESS NOTED OTHERWISEUNO
TECHNOLOGY GENERAL NOTES:1. ###-### INDICATES GENERAL TECHNOLOGY EQUIPMENT SCHEDULE ITEM LABELED AS
"EQUIPMENT LIST ABBREVIATION"2. REFER TO GENERAL TECHNOLOGY EQUIPMENT SCHEDULE AND SPECIFICATIONS FOR FULL
DESCRIPTIONS AND MANUFACTURERS OF ALL DEVICES.
TECHNOLOGY MOUNTING SUBSCRIPT KEY:A MOUNT AT +6" TO CENTERLINE ABOVE COUNTER OR BACKSPLASHH MOUNT ORIENTED HORIZONTALLYL MOUNT IN CASEWORKM MOUNT IN MODULAR FURNITURES MOUNT IN SURFACE RACEWAY
A SLASH IS USED BETWEEN TWO SUBSCRIPTS, E.G., A/H.
1. THE COMPLETE INSTALLATION SHALL BE IN ACCORDANCE WITH THE ADA STANDARDS FOR ACCESSIBLE DESIGN. REFER TO THE ADA GUIDELINES FOR ALL CONFIGURATION DETAILS ON THIS PAGE FOR ADDITIONAL INFORMATION.
2. CONCEAL ALL CONDUIT IN WALLS, PARTITIONS, ABOVE CEILING, IN FLOOR SLAB, ETC. UNLESS OTHERWISE INDICATED ON THE PLANS OR IN THE SPECIFICATIONS. CONDUIT IN MECHANICAL ROOMS AND STORAGE ROOMS WITHOUT CEILINGS MAY BE EXPOSED ON BUILDING STRUCTURE.
3. BOXES LOCATED ON OPPOSITE SIDES OF NON-RATED WALLS SHALL BE OFFSET A MINIMUM OF 6" HORIZONTALLY. BOXES ON OPPOSITE SIDES OF FIRE RATED WALLS SHALL BE OFFSET A MINIMUM OF 24" HORIZONTALLY. "THRU-THE-WALL" BOXES SHALL NOT BE ALLOWED WITHOUT PRIOR WRITTEN APPROVAL OF THE ARCHITECT/ENGINEER.
4. VERIFY ALL FURNITURE, MODULAR FURNITURE, AND EQUIPMENT LOCATIONS WITH ARCHITECTURAL PLANS, ELEVATIONS, AND REVIEWED SHOP DRAWINGS. PRIOR TO MAKING THE ACTUAL TELECOMMUNICATIONS INSTALLATION, ADJUST OUTLETS OR CONNECTION LOCATIONS TO ACCOMMODATE FURNITURE AND/OR EQUIPMENT.
5. TELECOMMUNICATIONS EQUIPMENT SHALL BE MOUNTED TO ALLOW ACCESS TO ELECTRICAL AND MECHANICAL EQUIPMENT. ALL MOUNTING OF TELECOMMUNICATION DEVICES ON EQUIPMENT SUPPLIED BY ANOTHER CONTRACTOR SHALL BE APPROVED IN ADVANCE BY THE OTHER CONTRACTOR.
6. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL OPENINGS REQUIRED IN WALLS. ALL OPENINGS SHALL BE REPAIRED TO MATCH EXISTING BY A QUALIFIED CONTRACTOR AT THE EXPENSE OF THIS CONTRACTOR. ALL CONDUITS THROUGH WALLS SHALL BE GROUTED OR SEALED INTO OPENINGS.
7. ALL MATERIALS USED TO SEAL PENETRATIONS OF FIRE RATED WALLS AND FLOORS SHALL BE TESTED AND CERTIFIED AS A SYSTEM PER ASTM E814 STANDARDS FOR FIRE TESTS OF THROUGH-PENETRATION FIRESTOPS. REFER TO 26 05 03 FOR ADDITIONAL INFORMATION AND REQUIREMENTS SPECIFIC TO FIRESTOPPING.
8. REMOVE AND REINSTALL ALL CEILING TILES AS REQUIRED FOR THE EXECUTION OF TELECOMMUNICATIONS WORK THAT IS OUTSIDE THE CONTRACT LIMITS OF CONSTRUCTION. REPLACE CEILING TILES WITH IDENTICAL MATERIAL WHERE DAMAGED BY THIS CONTRACTOR.
9. FLUSH MOUNT ALL TELECOMMUNICATION OUTLETS AT +18" FROM FLOOR (CENTERLINE DIMENSION), EXCEPT WHERE OTHERWISE NOTED. OUTLETS MAY BE SURFACE MOUNTED WHEN CONDUIT IS SPECIFIED EXPOSED.
10. MOUNTING HEIGHTS SHALL BE AS FOLLOWS: LIGHTING SWITCHES 4'-0" RECEPTACLES (GENERAL AREAS) 1'-6" RECEPTACLES (UTILITY AREAS) 4'-0" TELECOMMUNICATION OUTLETS 1'-6" WALL PHONE 4'-0" FIRE ALARM STATIONS 4'-0" FIRE ALARM SIGNALS 7'-6" CLOCKS/CLOCK OUTLETS 1’-6” BELOW FIN. CEIL. SAFETY SWITCHES 5'-0" TO TOP
TECHNOLOGY INSTALLATION NOTES:
GENERAL NOTES:
1. ALL SYMBOLS AND ABBREVIATIONS LISTED MAY NOT BE APPLICABLE TO THIS PROJECT. REFER TO THE GENERAL TECHNOLOGY EQUIPMENT SCHEDULE FOR MORE COMPLETE DESCRIPTION AND ITEMS.
2. ALL SYMBOLS AND ABBREVIATIONS REFER TO TECHNOLOGY SHEETS ONLY AS DEFINED ON THE SHEET INDEX. REFER TO THE GENERAL TECHNOLOGY NOTES FOR ADDITIONAL INFORMATION.
3. ALL SYMBOLS LISTED ABOVE ARE FOR REFERENCE ONLY. REFER TO PLANS AND LINE TYPE KEY FOR NEW, EXISTING TO REMAIN AND TO BE REMOVED ITEMS FOR ADDITIONAL INFORMATION.
TECHNOLOGY SYMBOL NOTES:
1. "C#" INDICATES INFORMATION OUTLET FACEPLATE CONFIGURATION. REFER TO INFORMATION OUTLET SCHEDULE ON T-300 FOR ADDITIONAL INFORMATION.
DIAMETERø C CONDUIT
CONDUIT DOWN
CONDUIT UP OR UP/DOWN
CONDUIT SLEEVE
CONTINUATION
PLAN OR DETAIL NUMBER
PLAN OR DETAIL NAME
PLAN OR DETAIL SCALE
NAME
1VIEW NAME1/8" = 1'-0"
LEVEL NAME
10' - 0" HEIGHT ABOVE PROJECT 0' - 0"
1 INDICATES NOTE USED TO DESCRIBE ADDITIONAL INFORMATION ABOUT WORK REQUIRED, SPECIFIC TO THE SHEET AND/OR DETAIL
NO R HT
INDICATES DIRECTION OF TRUE NORTH
VIEW KEY
NEW WORK BY THIS CONTRACTOR (DARK SOLID LINE)
NEW WORK BY OTHERS AND/OR EXISTING TO REMAIN (LIGHT SOLID LINE)
EXISTING TO BE REMOVED BY THIS CONTRACTOR(DARK SHORT DASHED LINE)
LINE TYPE KEY:
BUILDING CODE: MBC 2015 EDITION
FIRE CODE: NFPA 13: 2013 EDITION
PLUMBING CODE: MBC 2015 EDITION
MECHANICAL CODE: MMC 2015 EDITION
ELECTRICAL CODE: NFPA 70 (NEC) 2016EDITION
LIFE SAFETY CODE: NFPA 101 2015 EDITION
ENERGY CONSERVATION CODE: ASHRAE 90.1 2013
HEALTH DEPARTMENT CODE: CURRENT EDITION
LOCAL BUILDING CODE: CURRENT EDITION
APPLICABLE CODES
CONTRACTOR SHALL COMPLY WITH APPLICABLE CODES AND LOCAL AMENDMENTS.
TEMPERATURE CONTROLS CONTRACTORT.C.C.
SECURITY CONTRACTORS.C.
AUDIO/VISUAL CONTRACTORA.V.C.
ASBESTOS ABATEMENT CONTRACTOR
PLUMBING CONTRACTORP.C.
GENERAL CONTRACTORG.C.
MECHANICAL CONTRACTORM.C.
VENTILATION CONTRACTORV.C.
ELECTRICAL CONTRACTORE.C.
A.C.
CONTRACTOR ABBREVIATION KEY
ABBR: DESCRIPTION:
TECHNOLOGY CONTRACTORT.C.
HEATING CONTRACTORH.C.
48
" M
AX
.
20" MAX.
44
" M
AX
.
20"-25" MAX.
48
" M
AX
.
15
" M
IN. 48
" M
AX
.
46
" M
AX
.
10" MAX. 10"-24" MAX.
ADA GUIDELINES - FRONT ACCESS
ADA STANDARDS FOR ACCESSIBLE DESIGN
INSTALL ABOVE COUNTER DEVICE AT 44" ABOVE FINISHED FLOOR.
INSTALL ABOVE COUNTER DEVICE AT 40" ABOVE FINISHED FLOOR.
INSTALL DEVICE AT 18" ABOVE FINISHED FLOOR.
ADA GUIDELINES - SIDE ACCESS
INSTALL DEVICE AT 44" ABOVE FINISHED FLOOR.
INSTALL DEVICE AT 42" ABOVE FINISHED FLOOR.
TECHNOLOGY SHEET INDEXT-000 TECHNOLOGY COVERSHEET
TD-101 FIRST FLOOR DEMOLITION - TECHNOLOGY
TD-102 SECOND FLOOR DEMOLITION - TECHNOLOGY
T-101 FIRST FLOOR PLAN - TECHNOLOGY
T-102 SECOND FLOOR PLAN - TECHNOLOGY
T-300 TECHNOLOGY DETAILS, RISERS AND SCHEDULES
SUGGESTED MATRIX OF RESPONSIBILITY
ITEM: SHOWN ON:FURNISHED
BY:INSTALLED
BY: NOTES:
TECHNOLOGY ROUGH-IN, REFER TOGENERAL TECHNOLOGY EQUIPMENTSCHEDULE AND SPECIFICATIONS FORDEFINITION
T-SERIES E.C. E.C. 3. 4.
INFORMATION OUTLET FACEPLATES,JACKS, AND TERMINATIONS
T-SERIES T.C. T.C.
CONDUIT SLEEVES (WHEN SHOWN ONDRAWINGS)
T-SERIES E.C. E.C.
CONDUIT SLEEVES (NOT SHOWN BUTREQUIRED FOR PROPER INSTALLATIONOF SYSTEM)
N/A T.C. T.C. 2. 4.
TELECOMMUNICATION SYSTEMSROUGH-IN
T-SERIES E.C. E.C. 1.
TELECOMMUNICATION EQUIPMENT,CABLING, AND TERMINATIONS
T-SERIES T.C. T.C.
GROUNDING LUGS ON TECHNOLOGYEQUIPMENT
T-SERIES T.C. E.C. 5.
LINE VOLTAGE POWER (+120V ORGREATER)
E-SERIES E.C. E.C.
LINE VOLTAGE POWER (NOT SHOWNBUT REQUIRED FOR PROPERINSTALLATION OF SYSTEM)
N/A T.C. E.C. 2. 4.
LOW VOLTAGE CABLING FORTECHNOLOGY SYSTEMS
T-SERIES T.C. T.C.
CABLE HANGERS AND SUPPORTS OROTHER CABLE ROUTING METHODS(OTHER THAN CONDUIT AND CABLETRAY)
T-SERIES T.C. T.C. 5.
FLOOR BOX (ROUGH-IN) T & E SERIES E.C. E.C.
SUGGESTED MATRIX OF RESPONSIBILITY NOTES
1. LOCATIONS OF TELECOMMUNICATIONS ROUGH-INS SHALL BE INDICATED BY THE INFORMATIONOUTLET SYMBOLS ON THE DRAWINGS. REFER TO THE TECHNOLOGY SYMBOL LIST FORADDITIONAL INFORMATION.
2. BASED ON THE INHERENT DIFFERENCES IN PRODUCTS FROM VARIOUS MANUFACTURERS, ALLREQUIRED EQUIPMENT MAY NOT BE SHOWN ON THE DRAWINGS FOR ALL ACCEPTABLEMANUFACTURERS.
3. INCLUDES BACKBOXES AND CONDUIT REQUIRED FOR THE TECHNOLOGY SYSTEMSINSTALLATION. THE E.C. SHALL BASE THE BID ON THE BASIS OF DESIGN SHOWN ON THECONTRACT DOCUMENTS.
4. ALL CHANGES TO THE SLEEVES, BACKBOXES, CONDUITS, AND POWER REQUIRED BECAUSE OFTHE T.C.'S SELECTION OF AN ALTERNATE ACCEPTABLE MANUFACTURER OR FROM SYSTEMCONFIGURATIONS THAT ARE LEFT TO THE CHOICE OF THE CONTRACTOR SHALL BE INCLUDEDIN THE T.C.'S BID. THIS BID SHALL INCLUDE INSTALLATION BY A LICENSED ELECTRICIAN.
5. FURNISHED AS PART OF THE EQUIPMENT WHEN POSSIBLE, OR FURNISHED TO THE E.C. FORINSTALLATION IN THE FIELD.
AREA OF WORKNO SCALE
FLOOR LEVEL
project number:
sheet title:
sheet number:
approved
project:
coordination checked
location
drawn
checked
designed
issue: date:
key plan:
WAYNE STATE
UNIVERSITYFacilities Planning and Management
5454 Cass Avenue
Detroit, MI 48202
FO
R B
IDS
consultants:
NM Project Number - 18113.0
Rands Building
IMEG Project Number -
Rands House - Rackham
Relocation
WSU : 00
- -
12/1
0/2
018 1
1:1
8:1
4A
M
T-000
TECHNOLOGY COVERSHEET
JEFGILTIMADA
POOVYA
18004050.01
TIMADA
TIMADA
WS
U R
an
ds B
ldg
Rackh
am
Relo
cati
on
18004050.0
1
REFERENCE SCALE IN INCHES
0 1 2 3
PROJECT #
IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
18004050.01
Owner Review 90% CD's Nov. 27, 2018
100% CD's Dec. 04, 2018
For Bids Dec. 11, 2018
KP
CR CR
CR
CR
KP
WAP
WAP
1 2 3 41.9 2.5 3.1 3.2 3.5 3.8
A
b
c
d
e
f
a10
a9
b4
c.1
c.2
c.3
c.4
e.8
EXISTING
EQUIPMENT RACK
EXISTING TELECOM
ROOM
T
CAMPUS
PHONE
AREA OF WORKNO SCALE
FLOOR LEVEL
project number:
sheet title:
sheet number:
approved
project:
coordination checked
location
drawn
checked
designed
issue: date:
key plan:
WAYNE STATE
UNIVERSITYFacilities Planning and Management
5454 Cass Avenue
Detroit, MI 48202
FO
R B
IDS
consultants:
NM Project Number - 18113.0
Rands Building
IMEG Project Number -
Rands House - Rackham
Relocation
WSU : 00
- -
12/1
0/2
018 1
1:1
8:1
7A
M
TD-101
FIRST FLOOR DEMOLITION -
TECHNOLOGY
JEFGILTIMADA
POOVYA
18004050.01
TIMADA
TIMADA
WS
U R
an
ds B
ldg
Rackh
am
Relo
cati
on
18004050.0
1
NO R
HT
1/8" = 1'-0"1 FIRST FLOOR DEMOLITION - TECHNOLOGY
REFERENCE SCALE IN INCHES
0 1 2 3
PROJECT #
IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
18004050.01
GENERAL NOTES :
1. REFER TO SHEET T-000 FOR TECHNOLOGY SYMBOL LIST AND LINE TYPE KEY.
Owner Review 90% CD's Nov. 27, 2018
100% CD's Dec. 04, 2018
For Bids Dec. 11, 2018
WHITE BOARD
projection
screen
1 2 3 41.9 2.5 3.1 3.2 3.5 3.8
A
b
c
d
e
f
a10
a9
b4
c.1
c.2
c.3
c.4
e.8
EXISTING
EQUIPMENT RACK
EXISTING
TELECOM
ROOM
AREA OF WORKNO SCALE
FLOOR LEVEL
project number:
sheet title:
sheet number:
approved
project:
coordination checked
location
drawn
checked
designed
issue: date:
key plan:
WAYNE STATE
UNIVERSITYFacilities Planning and Management
5454 Cass Avenue
Detroit, MI 48202
FO
R B
IDS
consultants:
NM Project Number - 18113.0
Rands Building
IMEG Project Number -
Rands House - Rackham
Relocation
WSU : 00
- -
12/1
0/2
018 1
1:1
8:1
8A
M
TD-102
SECOND FLOOR DEMOLITION -
TECHNOLOGY
JEFGILTIMADA
POOVYA
18004050.01
TIMADA
TIMADA
WS
U R
an
ds B
ldg
Rackh
am
Relo
cati
on
18004050.0
1
NO R
HT
1/8" = 1'-0"1 SECOND FLOOR DEMOLITION - TECHNOLOGY
REFERENCE SCALE IN INCHES
0 1 2 3
PROJECT #
IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
18004050.01
GENERAL NOTES :
1. REFER TO SHEET T-000 FOR TECHNOLOGY SYMBOL LIST AND LINE TYPE KEY.
Owner Review 90% CD's Nov. 27, 2018
100% CD's Dec. 04, 2018
For Bids Dec. 11, 2018
111
117
125
129
137 141
143
145
144142138
140136
134
132
130
128
126
122
120
124
118
116
112
108
106
102
100
103107
DN
UP
UP
CL
OFFICE
COVERED AREA
RESEARCHLAB
OFFICE
IT OFFICE
TREATMENT
OFFICE
TREATMENTOFFICEOFFICE
TREATMENTCHILDPLAYROOM
OBSERVATION
TREATMENT
TREATMENT
OFFICE
OFFICE
JC
UNISEXADA
WOMEN
WAITING
WAITING
LOUNGE
OFFICE
PLANTERSTORAGE
STORAGE
OPENOFFICE
VEST
PORCH
OPENOFFICE
CONFERENCE ROOMOFFICE
copier C2-1
C2-1
C2-1
C2-1
C2-1
JB
1
CAM
CAM
CAM
CAM
CAM CAM CAM
CAM CAM
CAMCAM
IS1
IM1
CAM
CAM
CAM
KP
CR CR
CR
CR
KP
WAP
WAP
CR
1
1 2 3 41.9 2.5 3.1 3.2 3.5 3.8
A
b
c
d
e
f
a10
a9
b4
c.1
c.2
c.3
c.4
e.8
+60"
+60"
1
1
1
1
1
1
1
EXISTING TELECOM
ROOM
11
1 1
INTERCOM SYSTEM POWER SUPPLY
EXISTING
EQUIPMENT RACK
1
1
1
T
CAMPUS
PHONE
2
2
2
2
2
AREA OF WORKNO SCALE
FLOOR LEVEL
project number:
sheet title:
sheet number:
approved
project:
coordination checked
location
drawn
checked
designed
issue: date:
key plan:
WAYNE STATE
UNIVERSITYFacilities Planning and Management
5454 Cass Avenue
Detroit, MI 48202
FO
R B
IDS
consultants:
NM Project Number - 18113.0
Rands Building
IMEG Project Number -
Rands House - Rackham
Relocation
WSU : 00
- -
12/1
0/2
018 1
1:1
8:1
5A
M
T-101
FIRST FLOOR PLAN -
TECHNOLOGY
JEFGILTIMADA
POOVYA
18004050.01
TIMADA
TIMADA
WS
U R
an
ds B
ldg
Rackh
am
Relo
cati
on
18004050.0
1
NO R
HT
1/8" = 1'-0"1 FIRST FLOOR PLAN - TECHNOLOGY
REFERENCE SCALE IN INCHES
0 1 2 3
PROJECT #
IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
18004050.01
GENERAL NOTES :
1. ALL NEW INFORMATION OUTLET ON THIS SHEET SHALL BE SERVED FROM THE EXISTING FIRST FLOOR TELECOMMUNICATIONS ROOM UNLESS OTHERWISE NOTED. REFER TO 1/T-300 FOR CONNECTIVITY DIAGRAM AND ADDITIONAL REQUIREMENTS.
2. REFER TO T-000 FOR TECHNOLOGY SYMBOL LIST AND GENERAL TECHNOLOGY INSTALLATION NOTES.
3. REFER TO T-300 FOR GENERAL TECHNOLOGY EQUIPMENT SCHEDULE.
KEYNOTES :
1. CAMERA PROVIDED FOR CONNECTION TO OWNER FURNISHED OBSERVATION RECORDING SYSTEM. CONTRACTOR TO PROVIDE CAMERA, MOUNT, AND CABLING TO OFE NETWORK RECORDING SYSTEM.
2. PROVIDE SURFACE RACEWAY FOR TECHNOLOGY OUTLETS INDICATED.
#
Owner Review 90% CD's Nov. 27, 2018
100% CD's Dec. 04, 2018
For Bids Dec. 11, 2018
WHITE BOARD
projection
screen
244
240
245
229
227
225
219
217
243242241
246
247
238236
230
226
224
220
218
214212
202
200.1
200
201
203205
234
232
207
OFFICE
OPENOFFICE
OPENOFFICE
IT
MECH
TREATMENT
OBSERVATION
TREATMENT
COMFERENCE/GROUP ROOMOBSERVATIONTREATMENT
TREATMENT
OBSERVATION
TREATMENTTREATMENT
ADULTGROUP ROOM
ADULTGROUP ROOM
WOMEN
UNISEX ADA
CHILDREN'SGROUP ROOM
OFFICETREATMENT
DN
UP
OPENOFFICE
STORAGE
DN
OPENOFFICE
OPENOFFICE
OFFICEOFFICE
OBSERVATION
TREATMENT
OPEN
UP
OFFICE
C2-1
C2-1
C2-1
C2-1
C2-1C2-1C2-1CAM
CAMCAM
CAM
IM1
IM1
IS1
IS1
IS1
IS1
IM1
IM1
CAM
CAM
CAM
CAMCAM
CAM
IS1
IM1
IM1
IS1
CAM
IS1
IM1
IM1
IS1
CAM
JB1
CR
1
IS1
IM1
1 2 3 41.9 2.5 3.1 3.2 3.5 3.8
A
b
c
d
e
f
a10
a9
b4
c.1
c.2
c.3
c.4
e.8
C2-1
1
1
1
1
1
2
1
EXISTING
TELECOM
ROOM
1
1
1
1
1
1
INTERCOM SYSTEM POWER SUPPLY
EXISTING
EQUIPMENT RACK
+60"
+60"
33
3
3
3
AREA OF WORKNO SCALE
FLOOR LEVEL
project number:
sheet title:
sheet number:
approved
project:
coordination checked
location
drawn
checked
designed
issue: date:
key plan:
WAYNE STATE
UNIVERSITYFacilities Planning and Management
5454 Cass Avenue
Detroit, MI 48202
FO
R B
IDS
consultants:
NM Project Number - 18113.0
Rands Building
IMEG Project Number -
Rands House - Rackham
Relocation
WSU : 00
- -
12/1
0/2
018 1
1:1
8:1
6A
M
T-102
SECOND FLOOR PLAN -
TECHNOLOGY
JEFGILTIMADA
POOVYA
18004050.01
TIMADA
TIMADA
WS
U R
an
ds B
ldg
Rackh
am
Relo
cati
on
18004050.0
1
NO R
HT
1/8" = 1'-0"1 SECOND FLOOR PLAN - TECHNOLOGY
REFERENCE SCALE IN INCHES
0 1 2 3
PROJECT #
IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
18004050.01
GENERAL NOTES :
1. ALL NEW INFORMATION OUTLET ON THIS SHEET SHALL BE SERVED FROM THE EXISTING FIRST FLOOR TELECOMMUNICATIONS ROOM UNLESS OTHERWISE NOTED. REFER TO 1/T-300 FOR CONNECTIVITY DIAGRAM AND ADDITIONAL REQUIREMENTS.
2. REFER TO T-000 FOR TECHNOLOGY SYMBOL LIST AND GENERAL TECHNOLOGY INSTALLATION NOTES.
3. REFER TO T-300 FOR GENERAL TECHNOLOGY EQUIPMENT SCHEDULE.
KEYNOTES :
1. CAMERA PROVIDED FOR CONNECTION TO OWNER FURNISHED OBSERVATION RECORDING SYSTEM. CONTRACTOR TO PROVIDE CAMERA, MOUNT, AND CABLING TO OFE NETWORK RECORDING SYSTEM.
2. PROVIDE (2)2" CONDUITS STUBBED TO ACCESSIBLE CEILING FOR OWNER FURNISHED AV DEVICES.
3. PROVIDE SURFACE RACEWAY FOR TECHNOLOGY OUTLETS INDICATED.
#
Owner Review 90% CD's Nov. 27, 2018
100% CD's Dec. 04, 2018
For Bids Dec. 11, 2018
EXISTING
VOICE PATCH
PANEL(S)
EXISTING
VOICE PATCH
PANEL(S)
SC-MPP-1
EXISTING
NETWORK
EQUIPMENT
EXISTING FIBER
PANEL
2
3-Port Faceplate
IDENTIFICATION
IDENTIFICATION
3
1
PAIR 3
PAIR 1PAIR 2 PAIR 4
WO WGO BL WBL G WBR BR
1 32 4 5 6 7 8
ANSI/TIA/EIA T568BPIN/PAIR ASSIGNMENT
C#
2
2
1
4
EXISTING FIBER BACKBONE
3
EXISTING TELECOM ROOM
NOTES:
1. THIS RISER IS DIAGRAMMATIC AND MAY NOT SHOW ACTUAL ROUTING OR QUANTITIES OF MATERIALS SHOWN. THIS RISER IS SHOWN FOR CLARIFICATION OF CONNECTION LOCATIONS AND CABLE TYPE. ALL INFORMATION OUTLETS ARE TYPICAL OF THE OUTLETS IN THE AREA SHOWN. REFER TO FLOOR PLANS FOR MORE SPECIFIC ROUTING AND QUANTITY INFORMATION. REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION.
2. REFER TO T-300 FOR TECHNOLOGY EQUIPMENT SCHEDULE.
KEYNOTES:
1. 23 GAUGE, 4-PAIR, CATEGORY 6, UNSHIELDED TWISTED PAIR CABLE, SEE SPECIFICATIONS.2. REFER TO INFORMATION OUTLET SCHEDULE ON T-000 AND THE FLOOR PLANS FOR QUANTITY OF
CABLES AND JACKS TO BE INSTALLED AT EACH INFORMATION OUTLET.3. EXISTING RJ-45 TO RJ-45 CATEGORY CAT 6 UTP PATCH CORD. 4. EXISTING FIBER PATCH CORD. 5. CONTRACTOR TO PROVIDE NEW SC-MPP-1 FOR TERMINATION OF OBSERVATION RECORDING
SYSTEM CAMERAS (AV-CAM-1). NEW INFORMATION OUTLETS (SC-IO-W) TO TERMINATE TO AVAILABLE OPEN SPACES ON EXISTING MODULAR PATCH PANELS AND VOICE TERMINATION BLOCKS.
#
5
EXISTING COPPER BACKBONE
CAM
1
EXISTING VOICE CROSS
CONNECT
RECESSED MOUNT TRIM RING
RECESSED MOUNT BRACKET
DOME
DOME CAMERA BODY
STRUCTURE ABOVE
FLEXIBLE METALLIC CONDUIT
4-SQUAREJUNCTION BOX
(1) 3/4"EMT CONDUIT TO NEARESTACCESSIBLE CEILING
ACOUSTICAL CEILING TILE ORGYPSUM WALL BOARD (REFER TOARCHITECTURAL PLANS)
NOTES:
1. COORDINATE EXACT LOCATION ON SITE WITH WORK BY OTHER TRADES TO ENSURE DESIRED VIEWING AREA AND SERVICE ACCESS AFTER COMPLETION OF PROJECT AND TO MINIMIZE ANY POSSIBLE DAMAGE TO INSTALLED CAMERA OR ASSOCIATED CABLING.
2. CONDUIT SHALL STUB TO NEAREST ACCESSIBLE CEILING AND TERMINATE ORIENTED HORIZONTALLY AT THE HEIGHT OF THE ASSOCIATED CABLE TRAY OR J-HOOK ROUTE. CONDUIT RUN SHALL NOT CONTAIN MORE THAN 180 DEGREES OF BEND BETWEEN ACCESSIBLE JUNCTION BOXES OR BETWEEN JUNCTION BOX AND END OF CONDUIT. WHERE CONDUIT STUBS THROUGH A WALL IN TO A CORRIDOR AND TERMINATES AT AN ASSOCIATED J-HOOK ROUTE, THE CONDUIT SHOULD EXTEND NOT MORE THAN 2-4 INCHES IN TO THE CORRIDOR. WHERE CONDUIT STUBS TO AN ASSOCIATED CABLE TRAY, CONDUIT SHOULD EXTEND TO CABLE TRAY. ALL CONDUITS MUST BE FITTED WITH A NYLON BUSHING ON EACH END OF THE CONDUIT.
3. INSTALLING CONTRACTOR SHALL FURNISH AND INSTALL FIRESTOP MATERIALS FOR CAMERA ROUGH-INS PER PROJECT REQUIREMENTS. REFER TO SPECIFICATIONS FOR FIRESTOP REQUIREMENTS.
4. CAMERA MOUNTING ACCESSORY SHALL BE FROM THE SAME MANUFACTURER OF THE CAMERA AND APPROVED BY THE MANUFACTURER FOR USE WITH THE SPECIFIC MODEL NUMBER OF CAMERA INSTALLED. CONTRACTOR SHALL INSTALL CAMERA MOUNTING ACCESSORY AND CAMERA PER MANUFACTURER'S INSTRUCTIONS.
5. MOUNT ENCLOSURE FLUSH IN HARD CEILINGS. MOUNT ENCLOSURE IN ACOUSTICAL CEILING TILE WITH APPROPRIATE BRIDGE BRACE IN ACCESSIBLE CEILINGS. INSTALL SAFETY WIRES OR CABLES FROM ENCLOSURE TO NEAREST STRUCTURE WHERE INSTALLED IN ACOUSTICAL CEILINGS.
6. LOCATE FLEXIBLE METALLIC CONDUIT CONNECTION TO CAMERA ENCLOSURE SUCH THAT THE ASSOCIATED CABLING CAN BE FED IN TO ENCLOSURE WITHOUT INTERFERING WITH CAMERA OPERATION.
REFER TO SPECIFICATIONS FOR IDENTIFICATION REQUIREMENTS (TYP.)
NUMBER INDICATES FACEPLATE POSITION (TYP.)
NOTES:
1. THIS RISER IS DIAGRAMMATIC AND MAY NOT SHOW ACTUAL ROUTING OR QUANTITIES OF MATERIALS. THIS RISER IS SHOWN FOR CLARIFICATION OF CONNECTION LOCATIONS AND CONDUCTOR TYPE. ALL CONNECTIONS AND SYSTEM DEVICES SHOWN ARE TYPICAL AND NOT REPRESENTATIVE OF ACTUAL PROJECT QUANTITIES.REFER TO FLOOR PLANS AND ENLARGED FLOOR PLANS FOR ACTUAL QUANTITIES AND LOCATIONS OF DEVICES AND MORE SPECIFIC ROUTING INFORMATION. REFER TO SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.
IM1 IS1
POWER SUPPLY (AIPHONE PS-1225UL) LOCATED WITHIN TELECOM ROOM. REFER TO FLOOR PLANS.
3C, 18 AWG SHIELDED CABLE
NOTES:1. CONFIGURATIONS SHOWN IN THE DETAIL ABOVE ARE DIAGRAMMATIC, INTENDED TO DESCRIBE THE CONTROLLED SECURITY SCHEME ROUGH-IN
REQUIREMENTS OF THE DOORS. DETAILS ABOVE MAY NOT ACCURATELY REPRESENT DOOR SIZE, DOOR SWING, DOOR HARDWARE, OR DOOR FUNCTIONALITY. REFER TO ARCHITECTURAL DOOR HARDWARE SCHEDULE, DOOR HARDWARE GROUPS AND DOOR HARDWARE SPECIFICATIONS FOR COMPLETE INFORMATION. MIRROR THE DETAIL AS REQUIRED.
2. ROUGH IN SHOWN IN THE DETAIL ABOVE REPRESENTS THE MINIMUM REQUIREMENTS FOR ALL CONTROLLED SECURITY SYSTEM DEVICES AND CABLING UNLESS OTHERWISE NOTED. COORDINATE EXACT REQUIREMENTS WITH SELECTED DOOR MATERIALS, DOOR HARDWARE, AND CONTROLLED SECURITY DEVICES AND CABLING PRIOR TO INSTALLATION.
3. ALL CABLING IN WALLS AND WHERE EXPOSED ON VERTICAL SURFACES SHALL BE INSTALLED IN EMT CONDUIT OR SURFACE MOUNT RACEWAY. CABLING ROUTED HORIZONTALLY ABOVE THE ACCESSIBLE CEILING MAY BE INSTALLED FREE-AIR CABLING PROPERLY RATED FOR THE CEILING ENVIRONMENT.
4. THE ELECTRICAL OR SECURITY CONTRACTOR SHALL NOT MODIFY ANY FIRE RATED DOOR AND/OR DOOR FRAME. REFER TO THE ARCHITECTURAL DOOR SCHEDULE, DOOR HARDWARE SCHEDULE, AND DOOR HARDWARE SPECIFICATION FOR ADDITIONAL INFORMATION. MODIFICATION TO ANY FIRE RATED DOOR AND/OR FRAME WILL REQUIRE A RE-CERTIFICATION OF THE DOOR AND FRAME WITH THE LOCAL AUTHORITY HAVING JURISDICTION (AHJ).
5. INSTALLING CONTRACTOR SHALL FURNISH AND INSTALL FIRESTOP MATERIALS FOR ALL CONTROLLED SECURITY SCHEME ROUGH-INS PER PROJECT REQUIREMENTS. REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION AND REQUIREMENTS.
6. INSTALLATION SHALL INCLUDE ALL POWER REQUIRED FOR SYSTEM OPERATION INCLUDING +120VAC. REFER TO THE SUGGESTED MATRIX OF SCOPE RESPONSIBILITY FOR ADDITIONAL INFORMATION.
KEYNOTES:
1. PROVIDE JUNCTION BOXES IN THE DOOR FRAME WHERE SHOWN ON THIS DETAIL. ROUGH-IN SHALL BE PROVIDED WHETHER THE CURRENT SECURITY SCHEME UTILIZES THEM OR NOT. ALL CONDUITS SHALL BE EMT CONDUIT UNLESS OTHERWISE NOTED. FLEXIBLE CONDUIT OF ANY TYPE WILL NOT BE ACCEPTED. COORDINATE INSTALLATION WITH ON-SITE DOOR FRAME INSTALLATION CONTRACTOR.
2. ALL DOOR POSITION SWITCHES ARE REQUIRED TO BE RECESSED UNLESS OTHERWISE NOTED. ELECTRIC HINGE MONITORS ARE NOT AN ACCEPTABLE REPLACEMENT FOR THE RECESSED DOOR POSITION SWITCH.
3. DOUBLE GANG BACKBOX WITH SINGLE GANG PLASTER RING. REFER TO FLOOR PLAN(S) FOR ACTUAL CREDENTIAL READER TYPE AND ROUGH-IN LOCATIONS.
4. CONDUIT SHALL ROUTE FROM THE CREDENTIAL READER TO THE SECURE SIDE OF THE DOOR. CONDUIT SHALL ROUTE TO THE NEAREST SECURITY PANEL.PROVIDE A NYLON BUSHING ON CONDUIT END.
5. MOUNT A MINIMUM 4" SQUARE 2-1/8" DEEP JUNCTION BOX WITH BLANK COVER PLATE ON THE SECURE SIDE OF THE DOOR ABOVE ACCESSIBLE CEILING. INSTALLING CONTRACTOR SHALL SIZE THE JUNCTION BOXES PER SYSTEM INSTALLATION REQUIREMENTS AND APPLICABLE CODES. MAINTAIN ACCESS TO THE JUNCTION BOX.
6. PROVIDE A HORIZONTALLY MOUNTED SINGLE GANG BACKBOX FOR THE REQUEST TO EXIT SENSOR. 7. CONDUIT SHALL ROUTE TO THE NEAREST SECURITY PANEL. PROVIDE A NYLON BUSHING ON CONDUIT END.
DOOR FRAME ROUGH-IN DIAGRAM (ALL SINGLE DOORS)
DOOR FRAME ROUGH-IN DIAGRAM (ALL DOUBLE DOORS WITH OR WITHOUT MULLION)
FINISHED ACCESSIBLE CEILING
MINIMUM 3/4" EMT CONDUIT TO ABOVE THE ACCESSIBLE CEILING.
FINISHED FLOOR
CREDENTIAL READER ROUGH-IN. 3
DOOR CONTACT ROUGH-IN.
MINIMUM 1" EMT CONDUIT
11
REQUEST TO EXIT DEVICE ROUGH-IN.
FOR DOOR HARDWARE POWER SUPPLIES.
1/2" EMT CONDUIT MINIMUM (TYP.)
4'-0
"
MINIMUM 1" EMT CONDUITFOR DOOR
HARDWARE POWER SUPPLIES.
MINIMUM 3/4" EMT CONDUIT TO ABOVE THE ACCESSIBLE CEILING.
CREDENTIAL READER ROUGH-IN. 3
REQUEST TO EXIT DEVICE ROUGH-IN.
DOOR CONTACT ROUGH-IN.
1
4'-0
"
2
2
4
4
5
5
5
5
66
4" 4" 4"
7 7
6"
6"
#
AREA OF WORKNO SCALE
FLOOR LEVEL
project number:
sheet title:
sheet number:
approved
project:
coordination checked
location
drawn
checked
designed
issue: date:
key plan:
WAYNE STATE
UNIVERSITYFacilities Planning and Management
5454 Cass Avenue
Detroit, MI 48202
FO
R B
IDS
consultants:
NM Project Number - 18113.0
Rands Building
IMEG Project Number -
Rands House - Rackham
Relocation
WSU : 00
- -
12/1
0/2
018 1
1:1
8:1
7A
M
T-300
TECHNOLOGY DETAILS, RISERS
AND SCHEDULES
JEFGILTIMADA
POOVYA
18004050.01
TIMADA
TIMADA
WS
U R
an
ds B
ldg
Rackh
am
Relo
cati
on
18004050.0
1
REFERENCE SCALE IN INCHES
0 1 2 3
PROJECT #
IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
18004050.01
NO SCALE1 CONNECTIVITY RISER DIAGRAM TR-01
NO SCALE4
INTERIOR RECESSED CEILINGCAMERA MOUNT DETAIL
BLANK BLANK FILLER MODULE
2. REFER TO SPECIFICAITONS SECTION 27 05 53 FOR ADDITIONAL INFORMATION ON LABELING REQUIREMENTS. VOICE CAT 6 RJ-45 (WHITE)
1. PROVIDE REMOVABLE BLANK INSERT(S) FOR ALL UNUSED PORTS. DATA CAT 6 RJ-45 (ORANGE)
NOTES: LEGEND
SINGLE GANG WALLPLATES
INFORMATION OUTLET SCHEDULE
CONFIGURATION FA
CE
PL
AT
E P
OR
TS
FACEPLATE PORT IDENTIFICATION
NOTESPO
SIT
ION
1 J
AC
K T
YP
E
PO
SIT
ION
2 J
AC
K T
YP
E
PO
SIT
ION
3 J
AC
K T
YP
E
PO
SIT
ION
4 J
AC
K T
YP
E
PO
SIT
ION
5 J
AC
K T
YP
E
PO
SIT
ION
6 J
AC
K T
YP
E
C2-1 3 DATA DATA VOICE
THE MATERIAL LIST ABBREVIATIONS AND THE TECHNOLOGY EQUIPMENT SCHEDULE ARE FOR THE CONVENIENCE OF THE CONTRACTOR. EACH CONTRACTOR SHALL BERESPONSIBLE FOR VERIFICATION OF QUANTITIES AND SHALL FURNISH ALL MATERIAL REQUIRED, WHETHER SPECIFIED OR NOT, TO PRODUCE A SATISFACTORY WORKINGSYSTEM.
CATALOG NUMBERS ARE NOT TO BE CONSIDERED COMPLETE BUT ARE GIVEN ONLY TO AID THE CONTRACTOR IN THE SEARCH FOR MATERIAL. NO MATERIAL SHALL BEORDERED BY MANUFACTURER AND CATALOG NUMBER ONLY. EACH CONTRACTOR SHALL FIRST READ THE COMPLETE DESCRIPTION OF THE MATERIAL ON THESE DRAWINGSAND SPECIFICATIONS. THE FIRST MANUFACTURER LISTED IS THE BASIS OF DESIGN. "STANDARD COLOR" INDICATES FACTORY FINISH AVAILABLE AT NO ADDITIONAL CHARGE.
GENERAL TECHNOLOGY EQUIPMENT SCHEDULE
EQUIPMENT LISTABBREVIATION EQUIPMENT LIST DESCRIPTION
EQUIPMENT LISTMANUFACTURER AND MODEL
AC-CR1-W ROUGH IN PROVIDED FOR ACCESS CONTROL CREDENTIAL READER. REFER TO 3/T-300 FOR CONTROLLED SECURITYSCHEME DOOR ROUGH-IN DETAIL.
*
AV-CAM-1 AUDIO VISUAL PTZ CAMERA.INDOOR CEILING MOUNT WITH 1920 X 1080 RESOLUTION,FOCAL LENGTH: 4.7-47 MM,1/66500AT 2 SEC ILLUMINATION, 1/2.8" PREGRESSIVE SCAN WITH CMOS, 360 DEGREE UNINTERRUPTED PAN AND WDR.PROVIDE WITH ALL NECESSARY MOUNTING ACCESSORIES.
AXIS M5525 E
OR PRE-APPROVED EQUAL
AV-JB1-W AUDIOVISUAL JUNCTION BOX. PROVIDED FOR CONNECTIONS FOR OWNER-FURNISHED MULTIMEDIA SYSTEM(S). *
IC-IM1 INTERCOM MASTER STATION. DESK OR WALL MOUNT WITH ABS HOUSING AND LED, CALL TONE INDICATORS. 300 mAPOWER CONSUMPTION. INSTALL WITHIN 4" SQUARE BACKBOX WITH PLASTER RING AND PROVIDE (!) 1" C TO NEARESTACCESSIBLE CEILING.
AIPHONE LEF-3
OR PRE-APPROVED EQUAL
IC-IS1 INTERCOMM DOOR STATION. WALL MOUNT. ABS PLASTIC HOUSING. PUSH TO TALK OR OPEN VOICE HANDSFREECOMMUNICATION. INSTALL WITHIN 4" SQUARE BACKBOX WITH PLASTER RING. PROVIDE 1" CONDUIT TO NEARESTACCESSIBLE CEILING.
AIPHONE LE-B
OR PRE-APPROVED EQUAL
SC-IO-W INFORMATION OUTLET, WALL MOUNT, 3 PORT COVERPLATE AS INDICATED ON DRAWINGS.
"#" INDICATES INFORMATION OUTLET FACEPLATE CONFIGURATION AS INDICATED ON THE PLANS. REFER TO T-000 FORINFORMATION OUTLET SCHEDULE FOR PIN CONFIGURATION.
INSTALL INFORMATION OUTLET IN A 4" SQUARE BACKBOX WITH A SINGLE GANG PLASTER RING. INSTALL A 1" EMTCONDUIT TO TELECOM ROOM. PROVIDE REMOVABLE BLANK INSERTS FOR UNUSED PORTS (SYSTIMAX M20AP SERIESOR APPROVED EQUAL)
COVERPLATE:COMMSCOPE SYSTIMAX M13L - 262
JACK:COMMSCOPE SYSTIMAX CAT6 UNJ600-OR (ORANGE) UNJ600-WH (WHITE)
HUBBELLORTRONICS
NO SCALE2 INTERCOM RISER DIAGRAM
NO SCALE3 CONTROLLED SECURITY SCHEME DOOR ROUGH-IN DETAIL
Owner Review 90% CD's Nov. 27, 2018
100% CD's Dec. 04, 2018
For Bids Dec. 11, 2018