W A Y N E S T A T E U N I V E R S I T Y V I C I N I T Y P L A N SCALE: NTS E L E C T R I C A L A R C H I T E C T U R A L M E C H A N I C A L RANDS HOUSE RENOVATION L O C A T I O N P L A N SCALE: NTS T-1 MH000 VENTILATION COVER SHEET MHD101 FIRST FLOOR DEMOLITION - VENTILATION MHD102 SECOND FLOOR DEMOLITION - VENTILATION MH101 FIRST FLOOR PLAN - VENTILATION MH102 SECOND FLOOR PLAN VENTILATION MH300 VENTILATION DETAILS P000 PLUMBING COVER SHEET P101 FIRST FLOOR - PLUMBING P102 SECOND FLOOR PLAN - PLUMBING P300 ENLARGED PLANS P500 PLUMBING SCHEDULES E000 ELECTRICAL COVER SHEET ED101 FIRST FLOOR DEMOLITION- ELECTRICAL ED102 SECOND FLOOR DEMOLITION - ELECTRICAL EL101 FIRST FLOOR PLAN - LIGHTING EL102 SECOND FLOOR PLAN - LIGHTING EP100 BASEMENT FLOOR PLAN - POWER EP101 FIST FLOOR PLAN - POWER EP102 SECOND FLOOR PLAN - POWER EP-300 POWER DETAILS ES100 BASEMENT FLOOR PLAN - SYSTEMS ES101 FIRST FLOOR PLAN - SYSTEMS ES102 SECOND FLOOR PLAN - SYSTEMS ES-300 SYSTEMS DETAILS T000 TECHNOLOGY COVER SHEET TD101 FIRST FLOOR DEMOLITION - TECHNOLOGY TD102 SECOND FLOOR DEMOLITION - TECHNOLOGY T-101 FIRST FLOOR PLAN - TECHNOLOGY T102 SECOND FLOOR PLAN - TECHNOLOGY T300 TECHNOLOGY DETAILS, RISERS, AND SCHEDULES DETROIT, MI 48202 2215 Cole Street BIRMINGHAM, MICHIGAN 48009 P (248)646-5765 F (248)646-5813 No code variance requests are anticipated. Contractor to coordinate WORK SCOPE and construction activities with WSU construction Project Manager : W O R K S C O P E RENOVATE PORTION OF RANDS HOUSE INTO NEW OFFICES, CLASSROOMS AND LABS, CREATE NEW ADA TOILET ROOMS. RANDS HOUSE RENOVATION A P P L I C A B L E C O D E S BUILDING CODE: P R O J E C T A R E A S U M M A R Y MECHANICAL CODE: PLUMBING CODE: FIRE SAFETY CODE: (FOR CONTRACT DOCUMENTS) ELECTRICAL CODE: NFPA 101 LIFE SAFETY CODE NFPA 13/ 2007 STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS MICHIGAN REHABILITATION CODE FOR EXISTING BUILDING/ 2015 STATE OF MICHIGAN MECHANICAL CODE/ 2015 STATE OF MICHIGAN ELECTRICAL CODE /2014 MICHIGAN PLUMBING CODE/ 2015 GROSS AREA - 13,000 GSF ± USE GROUP: CONSTRUCTION TYPE: PUBLIC HEALTH CODE: BARRIER FREE CODES: MDCIS MINIMUM DESIGN STANDARDS FOR CONSTRUCTION AND EQUIPMENT FOR HEALTHCARE FACILITIES IN MICHIGAN UFAS, AMERICANS WITH DISABILITIES ACT ACCESSIBILITY GUIDELINES, MICHIGAN BARRIER FREE - 2010 BUSINESS - B 1A NON-COMBUSTIBLE Title Sheet, Drawing Index and Location & Vicinity Maps T-1 TITLE SHEET, DRAWING INDEX & LOCATION & VICINITY MAPS A-002 ABBREVIATIONS, DRAWING SYMBOLS STANDARDS& STANDARD MOUNTING HEIGHTS A-20 ROOM FINISH SCHEDULE A-30 DOOR SCHEDULE & WALL TYPES AD-101 RANDS HOUSE 1AR FLOOR PLAN - DEMOLITION WORK AD-102 RANDS HOUSE 2ND FLOOR PLAN- DEMOLITION WORK AD-103 RANDS HOUSE 1ST FLOOR REFLECTED CEILING PLAN - DEMOLITION WORK AD-104 RANDS HOUSE 2ND FLOOR REFLECTED CEILING PLAN - DEMOLITION WORK A-201 RANDS HOUSE 2ND FLOOR PLAN- NEW WORK A-202 RANDS HOUSE 2ND FLOOR PLAN- NEW WORK A-301 RANDS HOUSE 1ST FLOOR REFLECTED CEILING PLAN - NEW WORK A-302 RANDS HOUSE 2ND FLOOR REFLECTED CEILING PLAN- NEW WORK WAYNE STATE UNIVERSITY PROJECT SITE : RANDS HOUSE FOR BIDS project number: sheet title: sheet number: approved project: coordination checked location drawn checked designed issue: date: key plan: Rands House - Rackham Relocation Nov. 13, 2018 Owner Review 60% CD's NM Project Number - 18113.0 WAYNE STATE UNIVERSITY Facilities Planning and Management 5454 Cass Avenue Detroit, MI 48202 Rands House JK JK JK DB AG WSU : 00 consultants: Nov. 27, 2018 Owner Review90% CD's Dec. 04, 2018 Review 100% CD's Dec. 11, 2018 For Bids 26200 Town center Drive NOVI, MICHIGAN 48375 P (248)313-6902 F (248)344-1650 26200 Town center Drive NOVI, MICHIGAN 48375 P (248)313-6902 F (248)344-1650 ALTERNATES · DEDUCT NEW CARPET THOUGHOUT THE FIRST FLOOR

DETROIT, MI 48202...above a potential ignition source 3.abhr must be offset a minimum of 1" horizontally from any light switch, electrical or data receptacle, thermostat or other potential

  • Upload
    others

  • View
    1

  • Download
    0

Embed Size (px)

Citation preview

Page 1: DETROIT, MI 48202...above a potential ignition source 3.abhr must be offset a minimum of 1" horizontally from any light switch, electrical or data receptacle, thermostat or other potential

W A Y N E S T A T E U N I V E R S I T Y

V I C I N I T Y P L A N

SCALE: NTS

E L E C T R I C A LA R C H I T E C T U R A L M E C H A N I C A L

RANDS HOUSE RENOVATION

L O C A T I O N P L A N

SCALE: NTS

T-1

MH000 VENTILATION COVER SHEETMHD101 FIRST FLOOR DEMOLITION - VENTILATIONMHD102 SECOND FLOOR DEMOLITION - VENTILATIONMH101 FIRST FLOOR PLAN - VENTILATIONMH102 SECOND FLOOR PLAN VENTILATIONMH300 VENTILATION DETAILSP000 PLUMBING COVER SHEETP101 FIRST FLOOR - PLUMBINGP102 SECOND FLOOR PLAN - PLUMBINGP300 ENLARGED PLANSP500 PLUMBING SCHEDULES

E000 ELECTRICAL COVER SHEETED101 FIRST FLOOR DEMOLITION- ELECTRICALED102 SECOND FLOOR DEMOLITION - ELECTRICALEL101 FIRST FLOOR PLAN - LIGHTINGEL102 SECOND FLOOR PLAN - LIGHTINGEP100 BASEMENT FLOOR PLAN - POWEREP101 FIST FLOOR PLAN - POWEREP102 SECOND FLOOR PLAN - POWEREP-300 POWER DETAILSES100 BASEMENT FLOOR PLAN - SYSTEMSES101 FIRST FLOOR PLAN - SYSTEMSES102 SECOND FLOOR PLAN - SYSTEMSES-300 SYSTEMS DETAILST000 TECHNOLOGY COVER SHEETTD101 FIRST FLOOR DEMOLITION - TECHNOLOGYTD102 SECOND FLOOR DEMOLITION - TECHNOLOGYT-101 FIRST FLOOR PLAN - TECHNOLOGYT102 SECOND FLOOR PLAN - TECHNOLOGYT300 TECHNOLOGY DETAILS, RISERS, AND SCHEDULES

DETROIT, MI 48202

2215 Cole Street

BIRMINGHAM, MICHIGAN 48009

P (248)646-5765 F (248)646-5813

No code variance requests are anticipated.

Contractor to coordinate WORK SCOPE and constructionactivities with WSU construction Project Manager :

W O R K S C O P E

RENOVATE PORTION OF RANDS HOUSE INTO NEW OFFICES, CLASSROOMS AND LABS, CREATENEW ADA TOILET ROOMS.

RANDS HOUSE RENOVATION

A P P L I C A B L E C O D E S

BUILDING CODE:

P R O J E C T A R E A S U M M A R Y

MECHANICAL CODE:

PLUMBING CODE:

FIRE SAFETY CODE:

(FOR CONTRACT DOCUMENTS)

ELECTRICAL CODE:

NFPA 101 LIFE SAFETY CODE

NFPA 13/ 2007 STANDARD FOR THEINSTALLATION OF SPRINKLERSYSTEMS

MICHIGAN REHABILITATION CODE FOR EXISTING BUILDING/ 2015

STATE OF MICHIGAN MECHANICAL CODE/ 2015

STATE OF MICHIGAN ELECTRICAL CODE /2014

MICHIGAN PLUMBING CODE/ 2015

GROSS AREA - 13,000 GSF ±

USE GROUP:

CONSTRUCTION TYPE:

PUBLIC HEALTH CODE:

BARRIER FREE CODES:

MDCIS MINIMUM DESIGN STANDARDS FORCONSTRUCTION AND EQUIPMENT FORHEALTHCARE FACILITIES IN MICHIGAN

UFAS, AMERICANS WITH DISABILITIES ACT ACCESSIBILITYGUIDELINES, MICHIGAN BARRIER FREE - 2010

BUSINESS - B

1A NON-COMBUSTIBLE

Title Sheet, Drawing Index andLocation & Vicinity Maps

T-1 TITLE SHEET, DRAWING INDEX & LOCATION & VICINITY MAPSA-002 ABBREVIATIONS, DRAWING SYMBOLS STANDARDS& STANDARD MOUNTING HEIGHTSA-20 ROOM FINISH SCHEDULEA-30 DOOR SCHEDULE & WALL TYPESAD-101 RANDS HOUSE 1AR FLOOR PLAN - DEMOLITION WORKAD-102 RANDS HOUSE 2ND FLOOR PLAN- DEMOLITION WORKAD-103 RANDS HOUSE 1ST FLOOR REFLECTED CEILING PLAN - DEMOLITION WORKAD-104 RANDS HOUSE 2ND FLOOR REFLECTED CEILING PLAN - DEMOLITION WORKA-201 RANDS HOUSE 2ND FLOOR PLAN- NEW WORKA-202 RANDS HOUSE 2ND FLOOR PLAN- NEW WORKA-301 RANDS HOUSE 1ST FLOOR REFLECTED CEILING PLAN - NEW WORKA-302 RANDS HOUSE 2ND FLOOR REFLECTED CEILING PLAN- NEW WORK

WAYNE STATE UNIVERSITY

PROJECT SITE :

RANDS HOUSE

FOR

BID

S

project number:

sheet title:

sheet number:

approved

project:

coordination checked

location

drawn

checked

designed

issue: date:

key plan:

Rands House - RackhamRelocation

Nov. 13, 2018Owner Review 60% CD's

NM Project Number - 18113.0

WAYNE STATEUNIVERSITY

Facilities Planning and Management

5454 Cass Avenue

Detroit, MI 48202

Rands House

JK

JK

JK

DB

AG

WSU : 00

consultants:

Nov. 27, 2018Owner Review90% CD's

Dec. 04, 2018Review 100% CD's

Dec. 11, 2018For Bids

26200 Town center Drive

NOVI, MICHIGAN 48375

P (248)313-6902 F (248)344-1650

26200 Town center Drive

NOVI, MICHIGAN 48375

P (248)313-6902 F (248)344-1650

ALTERNATES

· DEDUCT NEW CARPET THOUGHOUT THE FIRST FLOOR

Page 2: DETROIT, MI 48202...above a potential ignition source 3.abhr must be offset a minimum of 1" horizontally from any light switch, electrical or data receptacle, thermostat or other potential

FO

R U

P

TO

4

0 L

BS

FO

R M

OR

E

TH

AN

4

0 L

BS

42" M

AX

60" M

AX

48" M

AX

2'-10

" MAX

MOUNTING HEIGHT FORDISPENSERS IS TO TOP OFDISPENSER OR HIGHESTOPERABLE PART

TO

WE

L D

IS

PE

NS

ER

S

& D

IS

PO

SE

RS

SO

AP

D

IS

PE

NS

ER

/ H

AN

D

SA

NIT

IZ

ER

TD

SD

4" MAX

48" T

YPIC

AL

1'-3"

MIN

MOUNTING HEIGHT FOR MIRROR:

BOTTOM EDGE OF MIRROR

PO

WE

R/D

AT

A/

PH

ON

E R

EC

EP

TA

CL

ES

LIG

HT

S

WIT

CH

ES

MIN 1 1/2" BETWEENTOP OF TP HOLDERAND BOT. OF GRABBAR

3'-0"

MAX

34"

HD

HA

ND

D

RY

ER

SND

SA

NIT

AR

Y N

AP

KIN

DIS

PE

NS

ER

FIR

E A

LA

RM

P

UL

L

IN

TE

RC

OM

HV

AC

C

ON

TR

OL

MOUNTINGHEIGHT IS TO TOPOF HIGHESTOPERABLE PARTOR RECEPTACLE

3'-8"

MAX

1'-5"

MAX

1'-3" MIN

SHELF,

WHERE

SPECIFIED

44

" O

VE

R

CO

UN

TE

R O

R

OB

ST

RU

CT

IO

N

WH

EN

OP

EN

TO

C

AB

IN

ET

HA

ND

LE

FILMILLUMINATOR

3'-6"

U.N

.O.

4'-6"

7'-2"

X"

4'-6"

4'-0"

2'-0"

5'-0"

4128

"

5'-0"

2'-0"

6'-6"

1'-6"

6'-0"

MONITOR &BRACKET

REMOTE MONITOR& BRACKET(@ CORRIDORLOCATIONS)

TVBRACKET

OTOSCOPE/SPHYGMOM-ANOMETER

SHARPSCONTAINER

GLOVE &APRON RACK

(S

IN

GL

E

BR

AC

KE

T)

(S

IN

GL

E

BR

AC

KE

T)

ADDITIONAL

BRACKET

SEGMENTS ADDED

AS REQUIRED

IV PUMP BAR(NON-FERROUS)

WALL-MOUNTEDWORKSTATION

FLIP DOWNWORKSTATION

SHOWER CURTAINROD, HOOKS, ANDCURTAIN

SHOWERNICHE

FOLDINGSHOWERSEAT

MOP & BROOMHOLDER - NOSHELF

MARKER BOARD/TACK BOARD

CHART ORMAGAZINERACK

HAIRDRYER

BED PANHOLDER

COATBRACKET& SHELF

SURFACEMOUNTEDPROJECTIONSCREEN

36"X48"

U.N.O.

44

" @

A

DA

48

" A

T

AC

CE

SS

IB

LE

BARRIER FREEEWC & DRINKINGFOUNTAIN

SINKS &LAVATORIES

URINALACCESSIBLE

TOILET, GRAB BAR &TOILET PAPERHOLDER

FOLD DOWNBABY CHANGINGTABLE

WALL MOUNTEDSEMI-RECESSEDFIREEXTINGUISHERCABINET

WALL MOUNTEDFIREEXTINGUISHER

MIRRORS

3'-8" 5'-

0"

3'-6"

48

" M

AX

A

T

AC

CE

SS

IB

LE

TOWEL BAR HOOK

GLOVEDISPENSER

SPECIMENPASS-THRU

6'-2"

3'-4"

3'-6"

3'-6"

3'-8"

MAX

3'-6"

MAX

3'-8"

MAX

4'-10

"

4'-0"

MAX

TO

B

OT

TO

M

OF

T

V

6" MAX9" MIN

9" M

IN

2'-3"

MIN

960"

MOUNTING

HEIGHT IS TO

SPOUT OUTLET

HEIGHT

8"

1 1/2

"

840"

1'-0" 3'-6"

1584

"

1920

"86

4"

6"3'-5"

1'-6"

3'-0"

1'-0"

INTERIOR ELEVATIONS LEGEND

6"

3'-9"

NOTE:REFER TO ARCH PLANS FOR ACCESSORIES AND THEIRLOCATIONS. THIS SHEET IS FOR STANDARD MOUNTING HEIGHTSONLY UNLESS NOTED ELSEWHERE IN THIS DRAWING SET

ABHR

MA

X.

FLOOR

ABHR

LEGEND

1. NO PROJECTION CAN EXTEND OUT MORE THAN 4" INTO

CORRIDOR OR WALKWAY.

2. ALCOHOL BASED HAND RUB SANITIZERS CANNOT BE LOCATED

ABOVE A POTENTIAL IGNITION SOURCE

3. ABHR MUST BE OFFSET A MINIMUM OF 1" HORIZONTALLY FROM

ANY LIGHT SWITCH, ELECTRICAL OR DATA RECEPTACLE,

THERMOSTAT OR OTHER POTENTIAL IGNITION SOURCE.

4. ABHR SANITIZERS CANNOT BE INSTALLED IN A CORRIDOR LESS

THAN 6' WIDE

5. ABHR MUST BE AT LEAST 4' APART

6. ABHR CANNOT BE INSTALLED OVER CARPET IN NON-SPRINKLED

SPACES.

7. MAX. CAPACITY OF DISPENSERS IN CORRIDORS: 0.3 GALLONS

NOTES

ALCOHOL BASED HAND RUB SANITIZER DISPENSER

LIGHT SWITCH/RECEPTACLE OR OTHER POTENTIAL IGNITION SOURCE

44"1"

MIN.

1"MIN.

MA

X.

IF ABHR IS NEXTTO POTENTIALIGNITION SOURCE,IT MUST BEOFFSET 1"HORIZONTALLY.

ABHR CAN BEBELOWPOTENTIALIGNITION SOURCE,NO ISSUES.

ABHR CANNOT BEABOVE POTENTIALIGNITION SOURCE.

ABHR

ABHR

44"

ALCOHOL BASED HAND RUB SANITIZERSMOUNTING REQUIREMENTS

FLOOR

FLOOR

FLOOR

FLOOR

A-002

PLANS

EXISTING WALLS TO REMAIN

NEW WALLS

ACROVYN CORNER GUARD - FULL HEIGHT

END CAP - FULL HEIGHTACG

ECFIRE EXTINGUISHER CABINET -SEMI-RECESSED (ADA)

FEC

EXISTING WALLS TO BE REMOVED

NEW DOOR W/ DOOR NUMBER

EXISTING DOOR TO BE REMOVED

CUBICLE CURTAIN TRACK

2'x2' FLUORESCENT LIGHT FIXTURE

2'x4' FLUORESCENT LIGHT FIXTURE

NEW SUSPENDED ACOUSTICAL CEILING @ 8'-0" AFFU.N.O.

GYPSUM BOARD CEILING @ 7'-6" AFF U.N.O.

RECESSED DOWN LIGHT FIXTURE

TREATMENT ROOM LIGHT FIXTURE

EXIT LIGHT (CEILING MOUNTED)

SMOKE DETECTOR

FIRE SPRINKLER HEAD - NEW SPRINKLER HEADS ARESHOWN FOR COORDINATION PURPOSES ONLY. FINALSPRINKLER HEAD LOCATIONS SHALL BE DETERMINEDBY A CERTIFIED FIRE PROTECTION FIRM, ANDCOORDINATED WITH ARCHITECT & ENGINEERS.

FIRE ALARM - SEE ELECTRICAL DWG.

WIRELESS ANTENNA - SEE ELECTRICAL DWG.

SPEAKER

EXISTING DOOR TO REMAIN

RETURN GRILLE - SEE MECHANICAL DWG.

EXHAUST GRILLE - SEE MECHANICAL DWG.

SUPPLY GRILLE - SEE MECHANICAL DWG.

PLAN IDENTIFICATIONW/NORTH ARROW

SECTION LOCATION IDENTIFICATION

DETAIL LOCATION IDENTIFICATION ATENLARGED SCALE

ELEVATION LOCATION IDENTIFICATION

KEYNOTE IDENTIFICATIONDEMO / NEW / MISC

BULLETIN IDENTIFICATION W/CLOUD

ROOM NAME & NUMBER

1. DO NOT SCALE DRAWING REPRODUCTIONS.2. THIS DRAWING REPRESENTS TYPICALLY ENCOUNTERED

ITEMS. NOT ALL ITEMS SHOWN MAY OCCUR WITHIN THESCOPE OF THIS PROJECT. REFER TO COMPLETESPECIFICATIONS AND DRAWING DOCUMENTATION SET.

GRID BUBBLE

DOOR NUMBER TAG

CEILING HEIGHT TAGEXISTING / NEW

EXISTING SUSPENDED ACOUSTICAL CEILING TO BEREMOVED

ACOUSTICAL CEILING TILEACT

CEILING HEIGHTCH

CEILINGCLG

EXISTING(X)

EXPANSION JOINTEJ

GAUGEGA

HARDWAREHDWR

HOLLOW METALHM

HEIGHTHT

INTERIOR DESIGNID

LAVATORYLAV

MAXIMUMMAX

MANUFACTURERMFR

MINIMUMMIN

MASONRY OPENINGMO

PLASTIC LAMINATEPLAM

SQUARE FEETSF

SIMILARSIM

SPECIFICATIONSSPEC

UNLESS NOTED OTHERWISEUNO

WATER CLOSETWC

WITH

W/O WITHOUT

RO ROUGH OPENING

NTS NOT TO SCALE

CENTER LINECL

OH OVERHEAD

GYPSUM BOARDGB

TYPICALTYP

CONTROL JOINTCJ

VINYL WALL COVERINGVWC

STAINLESS STEELSSTL

GLASSGL

WALL PROTECTIONWP

JC JANITORS CLOSET

RB RESILIENT BASE

CERAMIC TILECT

PT PAINT

CONTRACTOR FURNISHED/ INSTALLEDCFI

CAPITAL EQUIPMENTCE

ABOVE FINISH FLOORAFF

WOODWD

CARPETCPT

VINYL COMPOSITION TILEVCT

LIGHTLT

LINEAL FEETLF

EQUALEQ

BUREAU OF FIRE SAFETYBFS

HEALTH FACILITIES ENGINEERING SECTIONHFES

HOUR, HAND RAILHR

OPPOSITE HANDOPP

W/

FIRE ALARMFA

CJ CONTROL JOINT

KP KICK PLATE

JT JOINT

EACHEA

ELEVATOR, ELEVATIONELEV

FLOOR DRAINFD

UNDERWRITERS LABORATORY INCUL

PVC POLYVINYL CHLORIDE

QTY QUANTITY

CORNER GUARDCG

CARD READERCR

FV FIELD VERIFY

ARCHITECTURAL SYMBOLS LEGEND

FLOOR PLAN LEGEND

SOLID SURFACESSRF

REFLECTED CEILING PLAN LEGEND

GENERAL NOTESABBREVIATIONS LIST

EXISTING SUSPENDED ACOUSTICAL CEILING

DATUM/ELEVATION LOCATION ID

1

EXISTING WINDOW SYSTEM

NEW WINDOW SYSTEM

2'x2' FLUORESCENT INDIRECT LIGHT FIXTURE

~

S

FA

WA

EXISTING DOUBLE DOOR TO BE REMOVED

EXISTING DOUBLE DOOR TO REMAIN

NEW DOUBLE DOOR W/ DOOR NUMBER

TEMPORARY 1-HR PARTITION AND DOOR

LAVATORY SINK

CLINICAL SINK

SQUARE SINK

ROUND SINK

MOP/CORNER SINK

FLOOR TOILET

WALL HUNG TOILET

URINAL

TANK STYLE TOILET

GRAB BAR

XX

XXXX

X'-X"

XXXX

C3

D4

A1

B2

Main Floor LevelEL:100'-0"

0001

XX

XXXX

GRIDGRID

NewExist

NEWROOM NAME000

DXXXX

DXX

XX

DXX

XX

00 06

EQUIPMENT TAG

00 WALL TYPE TAG

CT-1 INTERIOR FINISH TAG

SSTL

RSF

STAINLESS STEEL

RESILIENT SHEET FLOORING

DOOR OPENINGDO

(R) RELOCATE

01Axxxx Scale: 1/8" = 1'-0"

Plan Name - Bottom LinePlan Name - Top Line

DRINKING FOUNTAIN

PTM PATCH TO MATCH

CAM CAMERA - SEE ELECTRICAL DWG.

OS OCCUPANCY SENSOR (CEILING MOUNTED)

OFCI OWNER FURNISHED CONTRACTOR INSTALLED

OFVI OWNER FURNISHED VENDOR INSTALLED

OFOI OWNER FURNISHED OWNER INSTALLED

Abbreviations, Drawing SymbolsStandard & Standard MountingHeights

FOR

BID

S

project number:

sheet title:

sheet number:

approved

project:

coordination checked

location

drawn

checked

designed

issue: date:

key plan:

Rands House - RackhamRelocation

Nov. 13, 2018Owner Review 60% CD's

NM Project Number - 18113.0

WAYNE STATEUNIVERSITY

Facilities Planning and Management

5454 Cass Avenue

Detroit, MI 48202

Rands House

JK

JK

JK

DB

AG

WSU : 00

consultants:

Nov. 27, 2018Owner Review90% CD's

Dec. 04, 2018Review 100% CD's

Dec. 11, 2018For Bids

Page 3: DETROIT, MI 48202...above a potential ignition source 3.abhr must be offset a minimum of 1" horizontally from any light switch, electrical or data receptacle, thermostat or other potential

CEILINGFINISH

ROOM FINISH SCHEDULE

DW

G #

ROOM NAMEROOM NO. TRANSITIONMAT.

ROOM FLOORMAT.

EAST WALL

MAT. FINISH MAT. MAT.FINISH FINISH

NORTH WALLBASE SOUTH WALL

MATERIALMAT.FINISH FINISH TYPE MATERIAL

WINDOW SILLWEST WALL

CABINETS

MILLWORKFINISH MOUNT HEIGHT MATERIAL FINISH

BULKHEADROOM #

REMARKS

A-20

A-2

01COUNTER

INDEX OF FINISH MANUFACTURERS

PAINT- PT-1MANUFACTURER: SHERWIN WILLIAMSTYPE: PAINTCOLOR: SW7568 NEUTRAL GROUNDFINISH: SEMI-GLOSS

FIRE-RATED

CEILING DATA

PLASTER

ACOUSTIC LAY-IN TILEACOUSTIC TEGULAR TILE

GYPSUM WALLBOARDGYPSUM PLASTER

FIBER REINFORCED GYPSUM PANELFIBER REINFORCED GYPSUM PANEL

HUMIDITY RESISTANT LAY IN TILEABUSE RESISTANT LAY IN TILE

TF

CLN

CSH

ST&VS&L

PT

S&V

PREW

S

GRAN

S&W

WDSRF

N

RSF

RTRCONQT

RTFCTSV

CP

TERR

WD

RFRTRCON

RBRSB

SEAL & VARNISHSEAL & LACQUERSTAIN & VARNISH

CONCRETE SEALER/HARDENERTEXTURE FINISH

CLEANPREFINISHED

PAINT

SEAL

WAX

RESILIENT SHEET FLOORINGRESILIENT TILE FLOORING

RUBBER TREAD & RISERRUBBER FLOORING

GRANITE TILE

SEAL & WAXFINISH

SLATEWOODNONE

CERAMIC & PORCELAIN TILE

QUARRY TILECONCRETE

RNS

QT

RUBBER FLOORINGRUBBER TREAD & RISER

RESILIENT BASERESILIENT SHEET BASEQUARRY TILE

RUBBER

WOODSLATE

NONE

CONCRETE

AMCT

FLOOR DATA

SHEET VINYL

CARPET

TERRAZZO

MATERIAL

CPTERR

BASE DATA

CERAMIC TILEAGGLOMERATED MARBLETERRAZZOCARPET

ARCHBARCBCARCBDBARCBSBARCB2ARCB1

CONCRETE MASONRY UNITS

AGGLOMERATED MARBLEACOUSTIC BLOCK - SOUND ABSORBING

FACE BRICK TRIM COURSING

GROUND FACE MASONRY UNITS

FBTCEXISTING FACE BRICK

WALL FABRICQUARRY TILECERAMIC & PORCELAIN TILE

SLATENONE

SN

AMCTQT

EFB

WF

GMFU

FACE BRICKPOLY-RESIN

LIGHTWEIGHT BLOCKPOURED CONCRETE

PRFB

AB

CMU

LBPC

PCPGB

ARCB

VC

FIBER REINFORCED GYPSUM PANEL FIRE-RATEDFIBER REINFORCED GYPSUM PANELGYPSUM WALLBOARD FIRE-RATED

WALL DATA

GYPSUM WALLBOARD-LEAD LINEDGWFRF

GW-LL

FFR

ARCHITECTURAL BLOCK - DOUBLE BULLNOSEARCHITECTURAL BLOCK - SINGLE BULLNOSEARCHITECTURAL BLOCK #2 - SINGLE SCORED FACEARCHITECTURAL BLOCK #1 - SPLIT RIB1 SR-1ARCHITECTURAL BLOCK TYPE "D" TRIM COURSING

ARCHITECTURAL HALF BLOCKARCHITECTURAL BLOCK CAP

GLASS BLOCKPORTLAND CEMENT PLASTER

VINYL COVERED

ARLITHRLIT

PL

ATTACT

GSP

FFFR

GW

MIRROR, FIXED

ROOM ACCESSORIES

TOILET TISSUE DISPENSER

MOP & BROOM HOLDERSSHOWER CURTAIN RODS

GRAB BAR ASSEMBLYROBE HOOKS

FRAMED TILTED MIRROR, FIXEDFRAMED MIRROR, FIXED

SANITARY NAPKIN VENDOR

WASTE RECEPTACLETOWEL BARS

ELECTRIC HAND DRYERPAPER TOWEL DISPENSER

SOAP DISPENSER

SANITARY NAPKIN DISPOSAL

FOLDING SHOWER SEATCERAMIC SOAP DISH

W/ ACOUSTIC BATTSCERAMIC TILE

MOUNTING

SUSPENDEDFURSUS

NCT

FURRED

NONE

EXPOSED STRUCTUREEXPOSED ACOUSTIC DECKEXPOSED METAL DECKACOUSTICAL METAL DECKAMDAB

EADEMD

ES

WR

CSD

SNV SND

FS

GBA RH CR

MF

MBHFTMF FMF

TBSD

TTD HD TD

ITEM

LEGEND OF ABBREVIATIONS

MATERIAL MATERIAL MATERIAL

VCB VINYL COMPOSITE BASE

WOODWD

STAINLESS STEELSSTLGRANITEGRANGLASSGLCURTAIN WALLCWFABRIC SCRIMFAB

GYPSUM WALLBOARDGW

WOODMETAL PRIMEDMETAL PRE-FINISHEDANODIZED ALUMINUM

STAIN GRADEVARNISH GRADE

PREFINISHEDPLASTIC LAMINATEANODIZED ALUMINUMPERMANODICPAINTFACTORY FINISHMATCH EXISTING

HARDBOARD

LOUVREDOOR FINISH

TEMPERED INSULATED

INSULATED HOLLOW METALGEORGIAN POLISHED WIRE

REFLECTIVE INSULATED

TICLEAR INSULATED

RICI

HOLLOW CORE WOODSOLID CORE WOODALUMINUMHOLLOW METAL

GAUGECLEAR FLOATTEMPERED

LAMINATEDREFLECTIVETINTED

GLASS

G

TRL

TCF#

PER

MEFFPT

PLAMPRE

AA

VGSG

HB MP/FAA

MPW HOLLOW METAL WELDED

SEAL & VARNISHS&V

FIXED MULLIONREMOVABLE MULLION

SEAL & LACQUERS&L

RMFM

ALUMINUMTHERMALLY BROKENSOLID WOODHOLLOW METAL

WELDEDSTANDARD

STAIN & VARNISH

PERMANODICANODIZED ALUMINUM

FINISHES

KNOCKDOWN

AA

ST&V

PERP

STD

PAINTSW

WEL

HMKD

HMW

TBAL

REMOVABLE MULLION

THRESHOLDWEATHER STRIPSOUND STRIP

WEATHER CAP

LOCK SEAMWELD SEAM WINDOW TREATMENTS

BARRIER FREE OPERATORBFORM

WSTLS

WS

ASTRAGAL

HARDWAREFRAME CONSTRUCTION

FRAME DATA

SSAWC

HOLLOW METAL WELDED (LEAD)HMW-L

HMIHM

SCWHCW

DOOR CONSTRUCTION

PL PLASTIC LAMINATE

WALL PROTECTION (ACROVYN)WP

PTM PATCH TO MATCHNW NO WORKX EXISTING

AL

CPT CARPET TILEGYPSUM VENEER PLASTERGVPPORTLAN CEMENT PLASTERPCP

GYPSUM PLASTERGSPGYPSUM VENEER PLASTERGVP

FIBERGLASS REINF'D POLYMERFRP

FIBERGLASS REINF'D POLYMERFRP

(SHOP DRAWINGS AND SAMPLES MUST BE SUBMITTED FOR FINAL APPROVAL ON ALL INTERIOR FINISHES)

PAINT- PT-2

WALL BASE - RB-1MANUFACTURER: ROPPETYPE: PINNACLE RUBBER BASECOLOR: 193 BLACK BROWNSIZE: 4"

Room Finish Schedule

FOR

BID

S

project number:

sheet title:

sheet number:

approved

project:

coordination checked

location

drawn

checked

designed

issue: date:

key plan:

Rands House - RackhamRelocation

Nov. 13, 2018Owner Review 60% CD's

NM Project Number - 18113.0

WAYNE STATEUNIVERSITY

Facilities Planning and Management

5454 Cass Avenue

Detroit, MI 48202

Rands House

JK

JK

JK

DB

AG

WSU : 00

consultants:

Nov. 27, 2018Owner Review90% CD's

Dec. 04, 2018Review 100% CD's

Dec. 11, 2018For Bids

A-2

02

MANUFACTURER: SHERWIN WILLIAMSTYPE: PAINTCOLOR: SW7693 STONEBRIARFINISH: SEMI-GLOSS

PAINT- PT-3MANUFACTURER: SHERWIN WILLIAMSTYPE: PAINTCOLOR: SW7006 EXTRA WHITEFINISH: EXTRA WHITE

CARPET TILE - CPT-1MANUFACTURER: BENTLEYTYPE: TECH UPD8 AFIRMA HARDBACKCOLOR: GEOMETRY 400005SIZE: 18"x36"

ACOUSTIC CEILING TILE - ACT-1MANUFACTURER: ARMSTRONGMODEL: ULTIMA 1951 BEVELED TEGULARCOLOR: WHITESIZE: 24" x 24" (15

16" Grid)

100 VESTIBULE CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - PT-3 - CLNG PLAN - - - 100

101 OPEN OFFICE CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - PT-3 - CLNG PLAN - - - 101

103 CONFERENCE ROOM CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - PT-3 - CLNG PLAN - - - 103

106 STORAGE CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - PT-3 - CLNG PLAN - - - 106

107 OFFICE CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - PT-3 - CLNG PLAN - - - 107

110 STAIR EXST - - EXST - EXST EXST EXST EXST EXST EXST EXST EXST - - - ACT-1 - CLNG PLAN - - - 110

112 TYP OFFICE CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - ACT-1 - CLNG PLAN - - - 112

116 LOUNGE CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - ACT-1 - CLNG PLAN - - - 116

118 WAITING/OFFICE CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - ACT-1 - CLNG PLAN - - - 118

120 UNISEX ADA RESTROOM EXST - - EXST - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - ACT-1 - CLNG PLAN - - - 120

134 OBSERVATION CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - ACT-1 - CLNG PLAN - - - 134

136 CHILD PLAYROOM CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - ACT-1 - CLNG PLAN - - - 136

102 OPEN OFFICE CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - PT-3 - CLNG PLAN - - - 102

124 WOMENS RESTROOM EXST - - EXST - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - ACT-1 - CLNG PLAN - - - 124

200 OPEN OFFICE CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - PT-3 - CLNG PLAN - - - 200

200.1 STORAGE CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - PT-3 - CLNG PLAN - - - 200.1

201 OPEN OFFICE CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - PT-3 - CLNG PLAN - - - 201

202 OPEN OFFICE CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - PT-3 - CLNG PLAN - - - 202

203 OFFICE CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - PT-3 - CLNG PLAN - - - 203

205 OFFICE CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - PT-3 - CLNG PLAN - - - 205

207 OFFICE CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - PT-3 - CLNG PLAN - - - 207

212 TYP TREATMENT CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - PT-3 - CLNG PLAN - - - 212

214 TYP OFFICE CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - PT-3 - CLNG PLAN - - - 214

218 CHILDREN GROUP ROOM CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - PT-3 - CLNG PLAN - - - 218

219 TYP OBSERVATION CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - PT-3 - CLNG PLAN - - - 219

220 UNISEX ADA RESTOOM EXST - - EXST - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - PT-3 - CLNG PLAN - - - 220

226 ADULT GROUP ROOM CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - PT-3 - CLNG PLAN - - - 226

227 MECHANICAL ROOM CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - PT-3 - CLNG PLAN - - - 227

229 IT CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - PT-3 - CLNG PLAN - - - 229

224 WOMENS RESTOOM EXST - - EXST - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - PT-3 - CLNG PLAN - - - 224

230 ADULT GROUP ROOM CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - PT-3 - CLNG PLAN - - - 230

243 CONFERENCE/GROUP ROOM CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - PT-3 - CLNG PLAN - - - 243

245 OPEN OFFICE CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - PT-3 - CLNG PLAN - - - 245

104 CORRIDOR CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - PT-3 - CLNG PLAN - - - 104

109 WAITING CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - PT-3 - CLNG PLAN - - - 109

108 CORRIDOR CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - PT-3 - CLNG PLAN - - - 108

111 CORRIDOR CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - ACT-1 - CLNG PLAN - - - 111

148 CORRIDOR CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - ACT-1 - CLNG PLAN - - - 148

204 CORRIDOR CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - PT-3 - CLNG PLAN - - - 204

208 CORRIDOR CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - PT-3 - CLNG PLAN - - - 208

209 CORRIDOR CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - PT-3 - CLNG PLAN - - - 209

150 STAIR EXST - - EXST - EXST EXST EXST EXST EXST EXST EXST EXST - - - ACT-1 - CLNG PLAN - - - 210

210 STAIR EXST - - EXST - EXST EXST EXST EXST EXST EXST EXST EXST - - - PT-3 - CLNG PLAN - - - 210

248 CORRIDOR CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - PT-3 - CLNG PLAN - - - 248

250 STAIR EXST - - EXST - EXST EXST EXST EXST EXST EXST EXST EXST - - - PT-3 - CLNG PLAN - - - 250

Page 4: DETROIT, MI 48202...above a potential ignition source 3.abhr must be offset a minimum of 1" horizontally from any light switch, electrical or data receptacle, thermostat or other potential

varies

see

sche

dule

see schedule

hollow metalframe

F1

see

sche

dule

variessee schedule

D1

see

sche

dule

variessee schedule

D2

inset light tomatch existingdoors. v.i.f.

provide acousticfirestop sealant allthrough-wallpenetrations - typical

SECTION AT DECK

acoustic tile ceiling onmetal suspensionsystem

base refer to roomfinish schedule

PLAN

7 1/4"6"

(actual)

SECTION AT FLOOR

SECTION AT CEILING

provide acousticfirestop sealant bothsides of partition asshown

runner stud atbase of partition

W1

Wall Composite:5

8" type x gyp bd, each side6" metal studs @ 16" o.c.w/ 5 1/2" sound attenuating batt

continuous firestop sealanteach side (typ)

existing structure

runner

1/2"

SMOKE TIGHTWALL

SECTION AT FLOOR

5/8" Soundbreak gyp bd, each side on1" Z channels @ 24" o.c.on existing wall construction

1 5/8"(actual)

provide acousticsealant both sides ofpartition as shown

base refer to roomfinish schedule

W2

PLAN

SECTION AT CEILING

2" (nominal)

runner stud atbase of partition

existing wall

existing structure

runner

continuous acoustic sealant

SECTION AT DECK

acoustic tile ceiling onmetal suspensionsystem

1 5/8"

2"

sound batt insulationabove ceiling. refer toRC plan for locations

note: provide acousticsealant around allelectrical outlets andother wall penetrations

CARPET

TRANSITION STRIP

CERAMIC TILE

T1

refe

r to

plan

2"

1 2"

hollow metal frameattach/anchor per mfgrrecommendations

16 guage doublestuds at doorframes typicalexisting wall1/4" min shimspace (all sides)

continuous sealantall sides of frame

door (refer toschedule)

provide doorsilencers (3 perjamb min)

refer to plan

2"

12"

hollow metalframeattach/anchorper mfgrrecommendations

16 guage doublestuds at doorhead typical

existing wall

continuoussealant allsides of frame

door (refer toschedule)

provide doorsilencers (3 perjamb min)

SERIESDOORMAT.

DOOR AND FRAME SCHEDULE

A-2

01

WIDTH

DOOR DATADW

G. N

o.No. QTY.DOOR DOOR

THICK.HEIGHT TYPESIZE DOOR

LOUVERGAUGESERIES HRS.RATING

TRANSOMGLASS DETAILJAMB

FRAME DATA

FINISH TYPEFRAME

MAT.FRAME No.

DOORHARDWARE

FINISHGLASSHRS.

RATING No.GROUP

REMARKS

Door

Unde

rcut

A-30

03A-100 Scale: 1/4" = 1'-0"

Door Types

NOTE: GENERAL CONTRACTOR TO REVIEW DOOR HARDWARE WITH OWNER PRIOR TO ANY INSTALLATION

DETAILHEAD

D118 1 3'-0" 7'-0" D2 SCW - - 20 min - - - - F1 J1 HM H1 - - - - CLASSROOM 1 - - - D118

DOOR REMARKS:

1. Contractor to coordinate with WSU reuse of existing doors and frames from

storage. Verify quantity, size, fire rating and condition of existing doors prior

to any installation.

02A-100 Scale: 1/4" = 1'-0"

Frame Types

HARDWARE GENERAL NOTES:

General notes:

1. Contractor shall verify all existing field conditions and notify architect

immediately if that which exists differs from that which is shown on

drawings.

2. All work to comply with Federal, State and Local codes, laws and

ordinances.The requirements of ICC/ANSI A117.1 and the Americans with

disabilities act (ADA) are to be fully satisfied. All work shall meet the most

stringent requirements of both including, but not limited to clearances,

limitations, accessories, etc.

3. These drawings are prepared in accordance with the limited services for

which the architect was contracted. The architect makes no representation

that the interpretation of these documents will result in complete compliance

with the ADA.

4. All doors required to be labeled shall be set in labeled frames and identified

with UL label and be provided with approved self-closing devices and

positive latching hardware.

5. All designated exit doors shall be equipped with the required egress

hardware.

6. Supplier shall meet with owner to establish MK keying system and provide a

combinated cylinder for each locking device as direct by owner. Supplier

shall submit key schedule for final approval. Furnish 2 change keys per

cylinder and 2 master keys total.

7. Supplier shall furnish and provide all necessary reinforcements, brackets,

fasteners, spacers and fillers to provide a complete functioning opening.

8. Supplier shall furnish complete shop drawings including; vertical typed

hardware schedule, product data sheets and warranty information following

DHI prescribed methods.

DOOR HARDWARE:

Hardware Set 1 -Classroom Lock (Lock/Unlock) + Closer & Smoke Seal

3 ea. Butt Hinge 35STBB 4545 NRP 26D PDQ

1 ea. Classroom Lock MR 148 DJSJ-SFL 32D PDQ

1 ea. Closer 7101 BC PA Regular Arm (Pull side Mount) AL PDQ

1 ea. Wall Stop 102 26D PDQ

1 ea. Kickplate 98 10 x 2" LDW 32D PDQ

1 set Smoke Seal 797B Blk Reese

Hardware Set 2 -Privacy Set w/ indicator (Lock/Unlock) + Closer & Smoke Seal

3 ea. Butt Hinge 35STBB 4545 NRP 26D PDQ

1 ea. Privacy Set w/ indicator MR 278 PJSJ 32D PDQ

1 ea. Closer 7101 BC PA Regular Arm (Pull side Mount) AL PDQ

1 ea. Wall Stop 102 26D PDQ

1 ea. Kickplate 98 10 x 2" LDW 32D PDQ

1 set Smoke Seal 797B Blk Reese

Hardware Set 3 -Classroom Lock (Lock/Unlock)

3 ea. Butt Hinge 35STBB 4545 NRP 26D PDQ

1 ea. Classroom Lock MR 148 DJSJ-SFL 32D PDQ

1 ea. Wall Stop 102 26D PDQ

Door Schedule & Wall Types

FOR

BID

S

project number:

sheet title:

sheet number:

approved

project:

coordination checked

location

drawn

checked

designed

issue: date:

key plan:

Rands House - RackhamRelocation

Nov. 13, 2018Owner Review 60% CD's

NM Project Number - 18113.0

WAYNE STATEUNIVERSITY

Facilities Planning and Management

5454 Cass Avenue

Detroit, MI 48202

Rands House

JK

JK

JK

DB

AG

WSU : 00

consultants:

Nov. 27, 2018Owner Review90% CD's

Dec. 04, 2018Review 100% CD's

Dec. 11, 2018For Bids

01A-30 Scale: 1 1/2" = 1'-0"

W-2 WALL TYPE 01A-30 Scale: 1 1/2" = 1'-0"

W-1 WALL TYPE

D120 1 3'-6" 7'-0" D1 SCW - - 20 min - - - - F1 J1 HM H1 - - - - PRIVACY 2 - - - D120

A-2

01

D220 1 3'-6" 7'-0" D1 SCW - - 20 min - - - - F1 J1 HM H1 - - - - PRIVACY 2 - - - D220

D224 1 3'-6" 7'-0" D1 SCW - - 20 min - - - - F1 J1 HM H1 - - - - CLASSROOM 1 - - - D224

D230 1 3'-6" 7'-0" D2 SCW - - 20 min - - - - F1 J1 HM H1 - - - - CLASSROOM 1 - - - D230

D245 1 3'-0" 7'-0" D2 SCW - - - - - - - F1 J1 HM H1 - - - - CLASSROOM 3 - - - D245

D246 1 3'-6" 7'-0" D2 SCW - - - - - - - F1 J1 HM H1 - - - - CLASSROOM 3 - - - D246

D247 1 3'-0" 7'-0" D2 SCW - - - - - - - F1 J1 HM H1 - - - - CLASSROOM 3 - - - D247

03A-002 Scale: NTS

Floor Transition

Page 5: DETROIT, MI 48202...above a potential ignition source 3.abhr must be offset a minimum of 1" horizontally from any light switch, electrical or data receptacle, thermostat or other potential

UP

UP

ref.

OFFICE107 CONFERENCE ROOM

103

OPENOFFICE100

PORCH

VEST

OPENOFFICE102

STORAGE106

STORAGE105PLANTER

OFFICE112

LOUNGE116

WAITING118

WOMEN124

UNISEXADA120

JC122

OFFICE126

OFFICE128

TREATMENT130

TREATMENT132

OBSERVATION134 CHILD

PLAYROOM136

TREATMENT140

OFFICE138

OFFICE142

TREATMENT144

OFFICE145

TREATMENT143

OFFICE141

IT137

OFFICE129

RESEARCHLAB125

COVERED AREA

OFFICE117

CL111

UP

UP

DN

2'-0"

5'-0"

3'-7" 5'-0"

CORRIDOR104

STAIR110

CORRIDOR108

WAITING109

CO

RR

IDO

R11

1STAIR150

CORRIDOR148

AD-101 FOR

BID

S

project number:

sheet title:

sheet number:

approved

project:

coordination checked

location

drawn

checked

designed

issue: date:

key plan:

Rands House - RackhamRelocation

Nov. 13, 2018Owner Review 60% CD's

NM Project Number - 18113.0

WAYNE STATEUNIVERSITY

Facilities Planning and Management

5454 Cass Avenue

Detroit, MI 48202

Rands House

JK

JK

JK

DB

AG

WSU : 00

consultants:

Nov. 27, 2018Owner Review90% CD's

Dec. 04, 2018Review 100% CD's

Dec. 11, 2018For Bids

01A-101 Scale: 1/8" = 1'-0"

First Floor Plan - DemolitionRands Building

Rands House 1st Floor Plan -Demolition Work

LEGEND

Remove existing gypsum and metal stud wall full height

walls

floors

01

GENERAL DEMOLITION NOTES

A. Demolition contractor shall be familiar with entire scope of new work prior to startingdemolition work.

B. all demolition floor plans, wall layouts, door and window locations, patterns havebeen shown for reference only. The General Contractor must field verify alldimensions and room layouts prior to new work and notify the architect of anydeviations from what is shown. All site visits must be coordinated with WSUConstruction Project Manager minimum 24 hours in advance of the site visit(s). Allwork outside of defined construction zone must be coordinated with WSUConstruction manager.

C. refer to electrical and mechanical drawings for extent of electrical and mechanicaldemolition work and for additional information.

D. room numbers and room names on all existing drawings relate only to demolitionsheets.

E. all existing items removed shall be returned to the owner for re-use or disposed ofoff site if rejected by the owner. do not damage any millwork during demolition.

F. owner is responsible for removing any loose equipment such as furniture, movableequipment, trash cans, etc.

G. all door hardware shall be removed from demolished doors, cleaned and turnedover to the owner.

H. repair all surfaces and components damaged during demolition and construction.

I. coordinate scope and extent of demolition work with new work plans and details.

J. demolition work required is not necessarily limited to what is shown on thedemolition plans. the intent is to remove all mechanical, electrical, and architecturalitems required to facilitate new construction.

K. unless noted otherwise when removing existing suspended lay-in ceiling assembly,including furring channels, wall angles and suspension wires.

L. where new plumbing is indicated, saw cut & remove existing concrete floor slab forinstallation of new plumbing. coordinate with mechanical and plumbing drawingsfor locations. Contractor must take precautions not to damage existing structuralfloor slab and is responsible to repair any damage due to new work. All slabremoval work must be coordinated with EMU for allowable time of work and perspecifications

items to be removed

existing items to remain

remove existing door & frame assembly, including all relatedhardware.40

doors

50

misc items

DEMOLITION NOTES

all existing furniture, file cabinets, and other movableequipment, not tagged to remain is to be removed by WSU.

30

ceilings

remove existing acoustic tile ceiling, grid to reamin. Coordinateremoval of mechanical, plumbing and electrical items with M&Edemolition drawings.

20Prep existing floor for new finish per specifications. Patch andrepair existing floor as necessary for smooth floor finish.

51 remove existing plumbing fixture. Refer or MEP dwgs for demo plumbing work.

Remove portion of existing gypsum & metal stud wall for new door02

21Existing flooring to be removed. Prep floor for new finish perspecifications. Patch and repair existing concrete floor slab.

22 Existing flooring to remain.

52 remove existing toilet partition.

Remove portion of existing gypsum & metal stud wall for new one-way mirror03

31 remove existing light fixtures. Coordinate removal of othermechanical, plumbing and electrical items with M&E demolitiondrawings.

53 existing cabinets to remain.

54 existing vending machines to be removed

01

02

02

03

03

21

21

21

22

22

22

22

22

22

22

22

22

22

22

22

22

22

22

22

22

22

22

22

22

22 22 22 22 22

22222222

22

22

22

40

40

50

50

50

50

50

50

50

50

50

50

50

50

50

50

50

50 5050 50 50

5050505050

50

50

51

52

Page 6: DETROIT, MI 48202...above a potential ignition source 3.abhr must be offset a minimum of 1" horizontally from any light switch, electrical or data receptacle, thermostat or other potential

DN

222

225

OFFICE207

UP

OPEN

TREATMENT232

OBSERVATION234

OFFICE205

OFFICE203

OPENOFFICE201

OPENOFFICE200

DN

STORAGE200.1

OPENOFFICE202

UP

DN

TREATMENT212

OFFICE214

CHILDREN'SGROUP ROOM218

UNISEX ADA220

WOMEN224

ADULTGROUP ROOM226

ADULTGROUP ROOM230

TREATMENT236

TREATMENT238

TREATMENT241

OBSERVATION242 COMFERENCE/

GROUP ROOM243

TREATMENT217

OBSERVATION219

TREATMENT225

MECH227

IT229

OPENOFFICE240 OFFICE

244

2'-0"

5'-0"

3'-7" 5'-0"

2'-0"

5'-0"

3'-7" 5'-0"

2'-0"

5'-0"

2'-0"

5'-0"

3'-0"5'-0"

2'-0"5'-0"

CORRIDOR204

CORRIDOR209

STAIR210

CO

RR

IDO

R21

1

CORRIDOR248

STAIR250

CORRIDOR208

OFFICE244

AD-102 FOR

BID

S

project number:

sheet title:

sheet number:

approved

project:

coordination checked

location

drawn

checked

designed

issue: date:

key plan:

Rands House - RackhamRelocation

Nov. 13, 2018Owner Review 60% CD's

NM Project Number - 18113.0

WAYNE STATEUNIVERSITY

Facilities Planning and Management

5454 Cass Avenue

Detroit, MI 48202

Rands House

JK

JK

JK

DB

AG

WSU : 00

consultants:

Nov. 27, 2018Owner Review90% CD's

Dec. 04, 2018Review 100% CD's

Dec. 11, 2018For Bids

01A-101 Scale: 1/8" = 1'-0"

Second Floor Plan - DemolitionRands Building

Rands House 2nd Floor Plan -Demolition Work

LEGEND

Remove existing gypsum and metal stud wall full height

walls

floors

01

GENERAL DEMOLITION NOTES

A. Demolition contractor shall be familiar with entire scope of new work prior to startingdemolition work.

B. all demolition floor plans, wall layouts, door and window locations, patterns havebeen shown for reference only. The General Contractor must field verify alldimensions and room layouts prior to new work and notify the architect of anydeviations from what is shown. All site visits must be coordinated with WSUConstruction Project Manager minimum 24 hours in advance of the site visit(s). Allwork outside of defined construction zone must be coordinated with WSUConstruction manager.

C. refer to electrical and mechanical drawings for extent of electrical and mechanicaldemolition work and for additional information.

D. room numbers and room names on all existing drawings relate only to demolitionsheets.

E. all existing items removed shall be returned to the owner for re-use or disposed ofoff site if rejected by the owner. do not damage any millwork during demolition.

F. owner is responsible for removing any loose equipment such as furniture, movableequipment, trash cans, etc.

G. all door hardware shall be removed from demolished doors, cleaned and turnedover to the owner.

H. repair all surfaces and components damaged during demolition and construction.

I. coordinate scope and extent of demolition work with new work plans and details.

J. demolition work required is not necessarily limited to what is shown on thedemolition plans. the intent is to remove all mechanical, electrical, and architecturalitems required to facilitate new construction.

K. unless noted otherwise when removing existing suspended lay-in ceiling assembly,including furring channels, wall angles and suspension wires.

L. where new plumbing is indicated, saw cut & remove existing concrete floor slab forinstallation of new plumbing. coordinate with mechanical and plumbing drawingsfor locations. Contractor must take precautions not to damage existing structuralfloor slab and is responsible to repair any damage due to new work. All slabremoval work must be coordinated with EMU for allowable time of work and perspecifications

items to be removed

existing items to remain

remove existing door & frame assembly, including all relatedhardware.40

doors

50

misc items

DEMOLITION NOTES

all existing furniture, file cabinets, and other movableequipment, not tagged to remain is to be removed by WSU.

30

ceilings

remove existing acoustic tile ceiling, grid to reamin. Coordinateremoval of mechanical, plumbing and electrical items with M&Edemolition drawings.

20Prep existing floor for new finish per specifications. Patch andrepair existing floor as necessary for smooth floor finish.

51 remove existing plumbing fixture. Refer or MEP dwgs for demo plumbing work.

Remove portion of existing gypsum & metal stud wall for new door02

21Existing flooring to be removed. Prep floor for new finish perspecifications. Patch and repair existing concrete floor slab.

22 Existing flooring to remain.

52 remove existing toilet partition.

Remove portion of existing gypsum & metal stud wall for new one-way mirror03

31 remove existing light fixtures. Coordinate removal of othermechanical, plumbing and electrical items with M&E demolitiondrawings.

53 existing cabinets to remain.

54 existing vending machines to be removed

03

2150

03

03 0301

03 03

03

03

02

02

02

2150 2150

2150

2150

2150

21502150

2150

2150

2150

2150

21502150

2150

2150

2150

2150 21

21

21

2150 2150 2150

2150

2150

2150

21

21

21

22

22

22

22

22

22

22

5151

5151

52

40

40

40

40

53

53

54

54

Page 7: DETROIT, MI 48202...above a potential ignition source 3.abhr must be offset a minimum of 1" horizontally from any light switch, electrical or data receptacle, thermostat or other potential

UP

UP

ref.

OFFICE107 CONFERENCE ROOM

103

OPENOFFICE100

PORCH

VEST

OPENOFFICE102

STORAGE106

STORAGE105PLANTER

OFFICE112

LOUNGE116

WAITING118

WOMEN124

UNISEXADA120

JC122

OFFICE126

OFFICE128

TREATMENT130

TREATMENT132

OBSERVATION134 CHILD

PLAYROOM136

TREATMENT140

OFFICE138

OFFICE142

TREATMENT144

OFFICE145

TREATMENT143

OFFICE141

IT137

OFFICE129

RESEARCHLAB125

COVERED AREA

OFFICE117

CL111

UP

UP

DN

CORRIDOR104

STAIR110

CORRIDOR108

WAITING109

CO

RR

IDO

R11

1STAIR150

CORRIDOR148

EXSTEXSTEXST

EXSTEXSTEXSTEXSTEXST

EXST

EXST

EXST

EXST

EXST

EXST

EXST

EXST

EXST

EXST

EXST

EXST

EXST

EXST

EXST

EXST

EXST

EXST

EXST

EXST

EXSTEXST

EXST

EXST

EXST

xLF

xLF

xLF

xLF

xLF

xLF

xLF

xLF

xLF

xLF

xLF xLF xLF xLF xLF xLF

xLFxLFxLFxLF

xLFxLFxLFxLFxLFxLFxLFxLFxLFxLF

xLFxLFxLF

xLF xLF

xLF xLF

xLF xLF

xLF xLF

xLF

xLF

xLF

xLF

xLF

xLF

xLF

xLFxLF

xLF xLF

xLF xLF xLF xLF xLF

xLF xLF

xLF

xLF

xLF

xLF

xLF

xLF

xLF

AD-103 FOR

BID

S

project number:

sheet title:

sheet number:

approved

project:

coordination checked

location

drawn

checked

designed

issue: date:

key plan:

Rands House - RackhamRelocation

Nov. 13, 2018Owner Review 60% CD's

NM Project Number - 18113.0

WAYNE STATEUNIVERSITY

Facilities Planning and Management

5454 Cass Avenue

Detroit, MI 48202

Rands House

JK

JK

JK

DB

AG

WSU : 00

consultants:

Nov. 27, 2018Owner Review90% CD's

Dec. 04, 2018Review 100% CD's

Dec. 11, 2018For Bids

01A-101 Scale: 1/8" = 1'-0"

First Floor Reflected Ceiling Plan - New WorkRands Building

Rands House 1st Floor ReflectedCeiling Plan - Demolition Work

LEGEND

Remove existing gypsum and metal stud wall full height

walls

floors

01

GENERAL DEMOLITION NOTES

A. Demolition contractor shall be familiar with entire scope of new work prior to startingdemolition work.

B. all demolition floor plans, wall layouts, door and window locations, patterns havebeen shown for reference only. The General Contractor must field verify alldimensions and room layouts prior to new work and notify the architect of anydeviations from what is shown. All site visits must be coordinated with WSUConstruction Project Manager minimum 24 hours in advance of the site visit(s). Allwork outside of defined construction zone must be coordinated with WSUConstruction manager.

C. refer to electrical and mechanical drawings for extent of electrical and mechanicaldemolition work and for additional information.

D. room numbers and room names on all existing drawings relate only to demolitionsheets.

E. all existing items removed shall be returned to the owner for re-use or disposed ofoff site if rejected by the owner. do not damage any millwork during demolition.

F. owner is responsible for removing any loose equipment such as furniture, movableequipment, trash cans, etc.

G. all door hardware shall be removed from demolished doors, cleaned and turnedover to the owner.

H. repair all surfaces and components damaged during demolition and construction.

I. coordinate scope and extent of demolition work with new work plans and details.

J. demolition work required is not necessarily limited to what is shown on thedemolition plans. the intent is to remove all mechanical, electrical, and architecturalitems required to facilitate new construction.

K. unless noted otherwise when removing existing suspended lay-in ceiling assembly,including furring channels, wall angles and suspension wires.

L. where new plumbing is indicated, saw cut & remove existing concrete floor slab forinstallation of new plumbing. coordinate with mechanical and plumbing drawingsfor locations. Contractor must take precautions not to damage existing structuralfloor slab and is responsible to repair any damage due to new work. All slabremoval work must be coordinated with EMU for allowable time of work and perspecifications

items to be removed

existing items to remain

remove existing door & frame assembly, including all relatedhardware.40

doors

50

misc items

DEMOLITION NOTES

all existing furniture, file cabinets, and other movableequipment, not tagged to remain is to be removed by WSU.

30

ceilings

remove existing acoustic tile ceiling, grid to reamin. Coordinateremoval of mechanical, plumbing and electrical items with M&Edemolition drawings.

20Prep existing floor for new finish per specifications. Patch andrepair existing floor as necessary for smooth floor finish.

51 remove existing plumbing fixture. Refer or MEP dwgs for demo plumbing work.

Remove portion of existing gypsum & metal stud wall for new door02

21Existing flooring to be removed. Prep floor for new finish perspecifications. Patch and repair existing concrete floor slab.

22 Existing flooring to remain.

52 remove existing toilet partition.

Remove portion of existing gypsum & metal stud wall for new one-way mirror03

31 remove existing light fixtures. Coordinate removal of othermechanical, plumbing and electrical items with M&E demolitiondrawings.

53 existing cabinets to remain.

54 existing vending machines to be removed

3030

30

30

30

30

30

30

30

30

30 30 30 30 30

30

303030

30

30 30

30

30

30

30

Page 8: DETROIT, MI 48202...above a potential ignition source 3.abhr must be offset a minimum of 1" horizontally from any light switch, electrical or data receptacle, thermostat or other potential

DN

222

225

OFFICE207

UP

OPEN

TREATMENT232

OBSERVATION234

OFFICE205

OFFICE203

OPENOFFICE201

OPENOFFICE200

DN

STORAGE200.1

OPENOFFICE202

UP

DN

TREATMENT212

OFFICE214

CHILDREN'SGROUP ROOM218

UNISEX ADA220

WOMEN224

ADULTGROUP ROOM226

ADULTGROUP ROOM230

TREATMENT236

TREATMENT238

TREATMENT241

OBSERVATION242 COMFERENCE/

GROUP ROOM243

TREATMENT217

OBSERVATION219

TREATMENT225

MECH227

IT229

OPENOFFICE240 OFFICE

244

CORRIDOR204

CORRIDOR209

STAIR210

CO

RR

IDO

R21

1

CORRIDOR248

STAIR250

CORRIDOR208

OFFICE244

xLF

xLF

xLF

xLF

xLFxLFxLFxLFxLFxLFxLF

xLF

xLF

xLF

xLF

xLF

xLF

xLF

xLF

xLF

xLFxLFxLF

xLFxLF

xLF xLF

xLFxLF

xLF xLF

xLF xLF

xLFxLF

xLF xLF

xLF

xLF

xLF xLF

xLFxLF

xLF xLF

xLF xLF

xLF xLF xLF

xLF xLF xLF xLF

xLF xLF xLF xLF

xLFxLF

xLF

xLF

xLF

xLF

xLF

xLF

AD-104 FOR

BID

S

project number:

sheet title:

sheet number:

approved

project:

coordination checked

location

drawn

checked

designed

issue: date:

key plan:

Rands House - RackhamRelocation

Nov. 13, 2018Owner Review 60% CD's

NM Project Number - 18113.0

WAYNE STATEUNIVERSITY

Facilities Planning and Management

5454 Cass Avenue

Detroit, MI 48202

Rands House

JK

JK

JK

DB

AG

WSU : 00

consultants:

Nov. 27, 2018Owner Review90% CD's

Dec. 04, 2018Review 100% CD's

Dec. 11, 2018For Bids

01A-101 Scale: 1/8" = 1'-0"

Second Floor Reflected Ceiling Plan - New WorkRands Building

Rands House 2nd Floor ReflectedCeiling Plan - Demolition Work

LEGEND

Remove existing gypsum and metal stud wall full height

walls

floors

01

GENERAL DEMOLITION NOTES

A. Demolition contractor shall be familiar with entire scope of new work prior to startingdemolition work.

B. all demolition floor plans, wall layouts, door and window locations, patterns havebeen shown for reference only. The General Contractor must field verify alldimensions and room layouts prior to new work and notify the architect of anydeviations from what is shown. All site visits must be coordinated with WSUConstruction Project Manager minimum 24 hours in advance of the site visit(s). Allwork outside of defined construction zone must be coordinated with WSUConstruction manager.

C. refer to electrical and mechanical drawings for extent of electrical and mechanicaldemolition work and for additional information.

D. room numbers and room names on all existing drawings relate only to demolitionsheets.

E. all existing items removed shall be returned to the owner for re-use or disposed ofoff site if rejected by the owner. do not damage any millwork during demolition.

F. owner is responsible for removing any loose equipment such as furniture, movableequipment, trash cans, etc.

G. all door hardware shall be removed from demolished doors, cleaned and turnedover to the owner.

H. repair all surfaces and components damaged during demolition and construction.

I. coordinate scope and extent of demolition work with new work plans and details.

J. demolition work required is not necessarily limited to what is shown on thedemolition plans. the intent is to remove all mechanical, electrical, and architecturalitems required to facilitate new construction.

K. unless noted otherwise when removing existing suspended lay-in ceiling assembly,including furring channels, wall angles and suspension wires.

L. where new plumbing is indicated, saw cut & remove existing concrete floor slab forinstallation of new plumbing. coordinate with mechanical and plumbing drawingsfor locations. Contractor must take precautions not to damage existing structuralfloor slab and is responsible to repair any damage due to new work. All slabremoval work must be coordinated with EMU for allowable time of work and perspecifications

items to be removed

existing items to remain

remove existing door & frame assembly, including all relatedhardware.40

doors

50

misc items

DEMOLITION NOTES

all existing furniture, file cabinets, and other movableequipment, not tagged to remain is to be removed by WSU.

30

ceilings

remove existing acoustic tile ceiling, grid to reamin. Coordinateremoval of mechanical, plumbing and electrical items with M&Edemolition drawings.

20Prep existing floor for new finish per specifications. Patch andrepair existing floor as necessary for smooth floor finish.

51 remove existing plumbing fixture. Refer or MEP dwgs for demo plumbing work.

Remove portion of existing gypsum & metal stud wall for new door02

21Existing flooring to be removed. Prep floor for new finish perspecifications. Patch and repair existing concrete floor slab.

22 Existing flooring to remain.

52 remove existing toilet partition.

Remove portion of existing gypsum & metal stud wall for new one-way mirror03

31 remove existing light fixtures. Coordinate removal of othermechanical, plumbing and electrical items with M&E demolitiondrawings.

53 existing cabinets to remain.

54 existing vending machines to be removed

31313131

31 31 31 31

Page 9: DETROIT, MI 48202...above a potential ignition source 3.abhr must be offset a minimum of 1" horizontally from any light switch, electrical or data receptacle, thermostat or other potential

UP

UP

ref.

copier

OFFICE107 CONFERENCE ROOM

103

OPENOFFICE100

PORCH

VEST

OPENOFFICE102

STORAGE106

STORAGE105PLANTER

OFFICE112

LOUNGE116

WAITING118

WOMEN124

UNISEXADA120

JC122

OFFICE126

OFFICE128

TREATMENT130

TREATMENT132

OBSERVATION134 CHILD

PLAYROOM136

TREATMENT140

OFFICE138

OFFICE142

TREATMENT144

OFFICE145

TREATMENT143

OFFICE141

IT137

OFFICE129

RESEARCHLAB125

COVERED AREA

OFFICE117

CL111

UP

UP

DN

5'-6"

W1

W1

D120

D118

W2

W2roomside only

W2roomside only

W2roomside only

W2roomside only

W2roomside only

W2

W2

W2

W2

W2

W2roomside only

W2

roomside only

W2

roomside only

W2

roomside only

W2

roomside only

W2

roomside only

W2

roomside only

W2W2 W2 W2 W2

W2roomside only

W2roomside only

W2roomside onlyW2

W2 W2

CORRIDOR104

STAIR110

CORRIDOR108

WAITING109

CO

RR

IDO

R11

1STAIR150

CORRIDOR148

A-201 FOR

BID

S

project number:

sheet title:

sheet number:

approved

project:

coordination checked

location

drawn

checked

designed

issue: date:

key plan:

Rands House - RackhamRelocation

Nov. 13, 2018Owner Review 60% CD's

NM Project Number - 18113.0

WAYNE STATEUNIVERSITY

Facilities Planning and Management

5454 Cass Avenue

Detroit, MI 48202

Rands House

JK

JK

JK

DB

AG

WSU : 00

consultants:

Nov. 27, 2018Owner Review90% CD's

Dec. 04, 2018Review 100% CD's

Dec. 11, 2018For Bids

01A-101 Scale: 1/8" = 1'-0"

First Floor Plan - New WorkRands Building

Rands House 1st Floor Plan -New Work

GENERAL NOTES

1) GENERAL CONTRACTOR AND SUB TRADES ARERESPONSIBLE TO VERIFY ALL EXISTING DIMENSIONSAND NOTIFY THE ARCHITECT OF ANY AND ALLDISCREPANCIES.

2) GENERAL CONTRACTOR SHALL BE FAMILIAR WITHENTIRE SCOPE OF NEW WORK AND PROCEED WITHWORK IN ACCORDANCE WITH NEW WORK.

3) NEW WORK FLOOR PLANS, WALL LAYOUTS, DOORAND WINDOW LOCATIONS AND PATTERNS HAVE BEENSHOWN FOR REFERENCE ONLY. THIS DRAWING ISNOT INTENDED TO SHOW ALL CONDITIONS, MATERIALPATTERNS AND LAYOUTS. INSPECT SITE PRIOR TOSTART OF CONSTRUCTION TO DETERMINE THE FULLSCOPE OF WORK.

4) REFER TO ELECTRICAL / MECHANICAL DRAWINGS FOREXTENT OF NEW ELECTRICAL AND MECHANICALWORK. COORDINATE BETWEEN ALL DISCIPLINES.REPORT DISCREPANCIES TO ARCHITECT.

5) ALL PATCH PAINTING TO INCLUDE ENTIRE/COMPLETEWALL - EDGE TO EDGE & CORNER TO CORNER

NEW WORK NOTES:

FLOORS

INSTALL NEW DOOR, REFER TO DOOR SCHEDULE. PROVIDEHARDWARE PER SCHEDULE

DOORS AND WINDOWS

WALLS

NEW FLOOR FINISH, REFER TO FINISH SCHEDULE11

31

32

NEW WALL CONSTRUCTION, PREP AND PAINT, REFER TO WALL TYPESAND DETAILS.

MISC.

01

CEILINGS

PREP AND PAINT GYPSUM CEILING41

72

CLEAN EXISTING WINDOW SYSTEM, REPAIR WINDOW SILL AS NECESSARY

42

LIGHTING

74

NEW FLOOR BASE, REFER TO FINISH SCHEDULE12

RELOCATED PROJECTION SCREEN

PROVIDE NEW ACOUSTIC CEILING TILE AND GRID, REFER TO FINISHSCHEDULE

INSTALL NEW LIGHTING FIXTURES, REFER TO ELECTRICALDRAWINGS FOR FULL EXTENT OF WORK.

51

75

INSTALL NEW LOOSE FURNITURE, REFER WSUFUNITURE LIST

77

INSTALL NEW WHITE BOARD

INSTALL NEW FLAT SCREEN

33 DOOR TO RECEIVE NEW CARD READER, REFER TO ELECTRICAL DRAWINGS

78 INSTALL NEW ONE-WAY MIRROR. ARROW INDICATESDIRECTION OF VIEW

71 INSTALL NEW PLUMBING FIXTURE, REFER TO MEPDRAWINGS

34 WINDOW TO RECEIVE NEW BLACK-OUT SHADE

43 PROVIDE MINIMUM 4" SOUND ATTENUATING INSULATION ABOVECEILING 2 FEET EITHER SIDE OF WALLS AS SHOWN IN HATCHED AREAS.

INFILL AREA WHERE WALL WAS REMOVED WITH NEWFLOORING TO MATCH EXISTING

13

79 RELOCATE EXISTING TOILET ROOM ACCESSORIES(IE. SOAP DISPENSER, TOWEL DISPENSER, MIRRORS,ETC.) FOR NEW LAYOUT

35 DOOR CARD READER TO BE RE-CODED.

44 PROVIDE NEW 2'x2' CEILING ACCESS HATCH. COORDINATE LOCATIONWITH MECHANICAL EQUIPMENT

01

0131

31

3232

32

32

32

32

32

32

32 32 32 32 32 32

323232

32

32

32

32

32

32

32

3232

32 32 32 32

32

3232

32 32

32

32

32

32

32

32

32

323232

3232

32

3232

7474

74

7474

7474

74

74

74

7474

74

74

74

74

7474

74

74 74

74

74

74

74

74

74

74

7474

74

74

74

74

74

7474

74 74

74

7474

7474

747474

74

74

74

74

77

7878

71

34

13

79

35

35

Page 10: DETROIT, MI 48202...above a potential ignition source 3.abhr must be offset a minimum of 1" horizontally from any light switch, electrical or data receptacle, thermostat or other potential

DN

222

225

OFFICE207

UP

OPEN

TREATMENT232

OBSERVATION234

OFFICE205

OFFICE203

OPENOFFICE201

OPENOFFICE200

DN

STORAGE200.1

OPENOFFICE202

UP

DN

TREATMENT212

OFFICE214

CHILDREN'SGROUP ROOM218

UNISEX ADA220

WOMEN224

ADULTGROUP ROOM226

ADULTGROUP ROOM230

TREATMENT236

TREATMENT238 OBSERVATION

247

TREATMENT246

TREATMENT241

OBSERVATION242 COMFERENCE/

GROUP ROOM243

TREATMENT217

OBSERVATION219

TREATMENT225

MECH227

IT229

OPENOFFICE245

OPENOFFICE240 OFFICE

244

7'-8" 8'-5" ±7'-10"

11'-9

"

W1

2'-0"

5'-0"

W1

W1

W1W1

D24

5

D24

6

D24

7

D224

D220

D230

W2

W2

W2

W2roomside only

roomside only

W2roomside only

W2

W2

W2roomside only

W2

W2

W2roomside only

W2

W2

W2

W2

CORRIDOR204

CORRIDOR209

STAIR210

CO

RR

IDO

R21

1

CORRIDOR248

STAIR250

CORRIDOR208

OFFICE244

A-202

01A-101 Scale: 1/8" = 1'-0"

Second Floor Plan - New WorkRands Building

Rands House 2nd Floor Plan - NewWork

GENERAL NOTES

1) GENERAL CONTRACTOR AND SUB TRADES ARERESPONSIBLE TO VERIFY ALL EXISTING DIMENSIONSAND NOTIFY THE ARCHITECT OF ANY AND ALLDISCREPANCIES.

2) GENERAL CONTRACTOR SHALL BE FAMILIAR WITHENTIRE SCOPE OF NEW WORK AND PROCEED WITHWORK IN ACCORDANCE WITH NEW WORK.

3) NEW WORK FLOOR PLANS, WALL LAYOUTS, DOORAND WINDOW LOCATIONS AND PATTERNS HAVE BEENSHOWN FOR REFERENCE ONLY. THIS DRAWING ISNOT INTENDED TO SHOW ALL CONDITIONS, MATERIALPATTERNS AND LAYOUTS. INSPECT SITE PRIOR TOSTART OF CONSTRUCTION TO DETERMINE THE FULLSCOPE OF WORK.

4) REFER TO ELECTRICAL / MECHANICAL DRAWINGS FOREXTENT OF NEW ELECTRICAL AND MECHANICALWORK. COORDINATE BETWEEN ALL DISCIPLINES.REPORT DISCREPANCIES TO ARCHITECT.

5) ALL PATCH PAINTING TO INCLUDE ENTIRE/COMPLETEWALL - EDGE TO EDGE & CORNER TO CORNER

NEW WORK NOTES:

FLOORS

INSTALL NEW DOOR, REFER TO DOOR SCHEDULE. PROVIDEHARDWARE PER SCHEDULE

DOORS AND WINDOWS

WALLS

NEW FLOOR FINISH, REFER TO FINISH SCHEDULE11

31

32

NEW WALL CONSTRUCTION, PREP AND PAINT, REFER TO WALL TYPESAND DETAILS.

MISC.

01

CEILINGS

PREP AND PAINT GYPSUM CEILING41

72

CLEAN EXISTING WINDOW SYSTEM, REPAIR WINDOW SILL AS NECESSARY

42

LIGHTING

74

NEW FLOOR BASE, REFER TO FINISH SCHEDULE12

RELOCATED PROJECTION SCREEN

PROVIDE NEW ACOUSTIC CEILING TILE AND GRID, REFER TO FINISHSCHEDULE

INSTALL NEW LIGHTING FIXTURES, REFER TO ELECTRICALDRAWINGS FOR FULL EXTENT OF WORK.

51

75

INSTALL NEW LOOSE FURNITURE, REFER WSUFUNITURE LIST

77

INSTALL NEW WHITE BOARD

INSTALL NEW FLAT SCREEN

33 DOOR TO RECEIVE NEW CARD READER, REFER TO ELECTRICAL DRAWINGS

78 INSTALL NEW ONE-WAY MIRROR. ARROW INDICATESDIRECTION OF VIEW

71 INSTALL NEW PLUMBING FIXTURE, REFER TO MEPDRAWINGS

34 WINDOW TO RECEIVE NEW BLACK-OUT SHADE

43 PROVIDE MINIMUM 4" SOUND ATTENUATING INSULATION ABOVECEILING 2 FEET EITHER SIDE OF WALLS AS SHOWN IN HATCHED AREAS.

INFILL AREA WHERE WALL WAS REMOVED WITH NEWFLOORING TO MATCH EXISTING

13

79 RELOCATE EXISTING TOILET ROOM ACCESSORIES(IE. SOAP DISPENSER, TOWEL DISPENSER, MIRRORS,ETC.) FOR NEW LAYOUT

35 DOOR CARD READER TO BE RE-CODED.

44 PROVIDE NEW 2'x2' CEILING ACCESS HATCH. COORDINATE LOCATIONWITH MECHANICAL EQUIPMENT

0101

01

01

01

1112

1112

1112

1112

1112

1112

1112

1112

1112

1112

1112

1112

1112

1112

1112

1112

1112

1112

1112

1112

1112

31 31 31

31

31

31

33

32

32

32 32 32

32

32

32

32

32

32

32

32

32

3232

323232

32

32323232

32

32

32

32

32

32

32

32

32 32 32 32 32 32 32

32

32

32

32

32

32323232

3434

34

34

34

32

32

32

32

32

717171

72

75

74

74

74 74

74

74

7474

74

74

74

74

7474

74

74

74

74

74

74

74 74 74 74

74

74

74

74

74

74

74

74

74

7474

74

74

74

74

74

78

78

78 78

7878

78

78

FOR

BID

S

project number:

sheet title:

sheet number:

approved

project:

coordination checked

location

drawn

checked

designed

issue: date:

key plan:

Rands House - RackhamRelocation

Nov. 13, 2018Owner Review 60% CD's

NM Project Number - 18113.0

WAYNE STATEUNIVERSITY

Facilities Planning and Management

5454 Cass Avenue

Detroit, MI 48202

Rands House

JK

JK

JK

DB

AG

WSU : 00

consultants:

Nov. 27, 2018Owner Review90% CD's

Dec. 04, 2018Review 100% CD's

Dec. 11, 2018For Bids

35

35

Page 11: DETROIT, MI 48202...above a potential ignition source 3.abhr must be offset a minimum of 1" horizontally from any light switch, electrical or data receptacle, thermostat or other potential

UP

UP

ref.

OFFICE107 CONFERENCE ROOM

103

OPENOFFICE100

PORCH

VEST

OPENOFFICE102

STORAGE106

STORAGE105PLANTER

OFFICE112

LOUNGE116

WAITING118

WOMEN124

UNISEXADA120

JC122

OFFICE126

OFFICE128

TREATMENT130

TREATMENT132

OBSERVATION134 CHILD

PLAYROOM136

TREATMENT140

OFFICE138

OFFICE142

TREATMENT144

OFFICE145

TREATMENT143

OFFICE141

IT137

OFFICE129

RESEARCHLAB125

COVERED AREA

OFFICE117

CL111

UP

UP

DN

D120

D118

CORRIDOR104

STAIR110

CORRIDOR108

WAITING109

CO

RR

IDO

R11

1STAIR150

CORRIDOR148

EXSTEXSTEXST

EXSTEXSTEXSTEXSTEXST

EXST

EXST

EXST

EXST

EXST

EXST

EXST

EXST

EXST

EXST

EXST

EXST

EXST

EXST

EXST

EXST

EXST

EXST

EXST

EXST

EXSTEXST

EXST

EXST

EXST

2'-0"

typ2'-

0"typ

2'-0"typ

xLF

xLF

xLF

xLF

xLF

xLF

xLF

xLF

xLF

xLF

xLF xLF xLF xLF xLF xLF

xLFxLFxLFxLF

xLFxLFxLFxLFxLFxLFxLFxLFxLFxLF

xLFxLFxLF

xLF xLF

xLF xLF

xLF xLF

xLF xLF

xLF

xLF

xLF

xLF

xLF

xLF

xLF

xLFxLF

xLF xLF

xLF xLF xLF xLF xLF

xLF xLF

xLF

xLF

xLF

xLF

xLF

xLF

xLF

A-301 FOR

BID

S

project number:

sheet title:

sheet number:

approved

project:

coordination checked

location

drawn

checked

designed

issue: date:

key plan:

Rands House - RackhamRelocation

Nov. 13, 2018Owner Review 60% CD's

NM Project Number - 18113.0

WAYNE STATEUNIVERSITY

Facilities Planning and Management

5454 Cass Avenue

Detroit, MI 48202

Rands House

JK

JK

JK

DB

AG

WSU : 00

consultants:

Nov. 27, 2018Owner Review90% CD's

Dec. 04, 2018Review 100% CD's

Dec. 11, 2018For Bids

01A-101 Scale: 1/8" = 1'-0"

First Floor Reflected Ceiling Plan - New WorkRands Building

Rands House 1st Floor ReflectedCeiling Plan - New Work

GENERAL NOTES

1) GENERAL CONTRACTOR AND SUB TRADES ARERESPONSIBLE TO VERIFY ALL EXISTING DIMENSIONSAND NOTIFY THE ARCHITECT OF ANY AND ALLDISCREPANCIES.

2) GENERAL CONTRACTOR SHALL BE FAMILIAR WITHENTIRE SCOPE OF NEW WORK AND PROCEED WITHWORK IN ACCORDANCE WITH NEW WORK.

3) NEW WORK FLOOR PLANS, WALL LAYOUTS, DOORAND WINDOW LOCATIONS AND PATTERNS HAVE BEENSHOWN FOR REFERENCE ONLY. THIS DRAWING ISNOT INTENDED TO SHOW ALL CONDITIONS, MATERIALPATTERNS AND LAYOUTS. INSPECT SITE PRIOR TOSTART OF CONSTRUCTION TO DETERMINE THE FULLSCOPE OF WORK.

4) REFER TO ELECTRICAL / MECHANICAL DRAWINGS FOREXTENT OF NEW ELECTRICAL AND MECHANICALWORK. COORDINATE BETWEEN ALL DISCIPLINES.REPORT DISCREPANCIES TO ARCHITECT.

5) ALL PATCH PAINTING TO INCLUDE ENTIRE/COMPLETEWALL - EDGE TO EDGE & CORNER TO CORNER

NEW WORK NOTES:

FLOORS

INSTALL NEW DOOR, REFER TO DOOR SCHEDULE. PROVIDEHARDWARE PER SCHEDULE

DOORS AND WINDOWS

WALLS

NEW FLOOR FINISH, REFER TO FINISH SCHEDULE11

31

32

NEW WALL CONSTRUCTION, PREP AND PAINT, REFER TO WALL TYPESAND DETAILS.

MISC.

01

CEILINGS

PREP AND PAINT GYPSUM CEILING41

72

CLEAN EXISTING WINDOW SYSTEM, REPAIR WINDOW SILL AS NECESSARY

42

LIGHTING

74

NEW FLOOR BASE, REFER TO FINISH SCHEDULE12

RELOCATED PROJECTION SCREEN

PROVIDE NEW ACOUSTIC CEILING TILE AND GRID, REFER TO FINISHSCHEDULE

INSTALL NEW LIGHTING FIXTURES, REFER TO ELECTRICALDRAWINGS FOR FULL EXTENT OF WORK.

51

75

INSTALL NEW LOOSE FURNITURE, REFER WSUFUNITURE LIST

77

INSTALL NEW WHITE BOARD

INSTALL NEW FLAT SCREEN

33 DOOR TO RECEIVE NEW CARD READER, REFER TO ELECTRICAL DRAWINGS

78 INSTALL NEW ONE-WAY MIRROR. ARROW INDICATESDIRECTION OF VIEW

71 INSTALL NEW PLUMBING FIXTURE, REFER TO MEPDRAWINGS

34 WINDOW TO RECEIVE NEW BLACK-OUT SHADE

43 PROVIDE MINIMUM 4" SOUND ATTENUATING INSULATION ABOVECEILING 2 FEET EITHER SIDE OF WALLS AS SHOWN IN HATCHED AREAS.

INFILL AREA WHERE WALL WAS REMOVED WITH NEWFLOORING TO MATCH EXISTING

13

79 RELOCATE EXISTING TOILET ROOM ACCESSORIES(IE. SOAP DISPENSER, TOWEL DISPENSER, MIRRORS,ETC.) FOR NEW LAYOUT

35 DOOR CARD READER TO BE RE-CODED.

44 PROVIDE NEW 2'x2' CEILING ACCESS HATCH. COORDINATE LOCATIONWITH MECHANICAL EQUIPMENT

41

41

41

41

41

41

41

41

41

41

42

42

42

42

42

42

42

42

42

42 42 42 42 42 42

42

424242

42

42

42

42

42

42

43

43

43

43

43

Page 12: DETROIT, MI 48202...above a potential ignition source 3.abhr must be offset a minimum of 1" horizontally from any light switch, electrical or data receptacle, thermostat or other potential

DN

222

225

OFFICE207

UP

OPEN

TREATMENT232

OBSERVATION234

OFFICE205

OFFICE203

OPENOFFICE201

OPENOFFICE200

DN

STORAGE200.1

OPENOFFICE202

UP

DN

TREATMENT212

OFFICE214

CHILDREN'SGROUP ROOM218

UNISEX ADA220

WOMEN224

ADULTGROUP ROOM226

ADULTGROUP ROOM230

TREATMENT236

TREATMENT238 OBSERVATION

247

TREATMENT246

TREATMENT241

OBSERVATION242 COMFERENCE/

GROUP ROOM243

TREATMENT217

OBSERVATION219

TREATMENT225

MECH227

IT229

OPENOFFICE245

OPENOFFICE240 OFFICE

244

CORRIDOR204

CORRIDOR209

STAIR210

CO

RR

IDO

R21

1

CORRIDOR248

STAIR250

CORRIDOR208

OFFICE244

EXST

LF

LF

LF

LF

LF

LF

EXSTEXST

EXST

EXST

EXST

EXST

EXST

EXST

EXST

EXST

EXST

EXST

EXST

EXST

EXST

EXST

EXST

EXST EXST

EXST EXST EXST

EXST

EXST

EXST

xLF

xLF

xLF

xLF

xLFxLFxLFxLFxLFxLFxLF

xLF

xLF

xLF

xLF

xLF

xLF

xLF

xLF

xLF

xLFxLFxLF

xLFxLF

xLF xLF

xLFxLF

xLF xLF

xLF xLF

xLFxLF

xLF xLF

xLF

xLF

xLF xLF

xLFxLF

xLF xLF

xLF xLF

xLF xLF xLF

xLF xLF xLF xLF

xLF xLF xLF xLF

xLFxLF

xLF

xLF

xLF

xLF

xLF

xLF

A-302 FOR

BID

S

project number:

sheet title:

sheet number:

approved

project:

coordination checked

location

drawn

checked

designed

issue: date:

key plan:

Rands House - RackhamRelocation

Nov. 13, 2018Owner Review 60% CD's

NM Project Number - 18113.0

WAYNE STATEUNIVERSITY

Facilities Planning and Management

5454 Cass Avenue

Detroit, MI 48202

Rands House

JK

JK

JK

DB

AG

WSU : 00

consultants:

Nov. 27, 2018Owner Review90% CD's

Dec. 04, 2018Review 100% CD's

Dec. 11, 2018For Bids

01A-101 Scale: 1/8" = 1'-0"

Second Floor Reflected Ceiling Plan - New WorkRands Building

Rands House 2nd Floor ReflectedCeiling Plan - New Work

GENERAL NOTES

1) GENERAL CONTRACTOR AND SUB TRADES ARERESPONSIBLE TO VERIFY ALL EXISTING DIMENSIONSAND NOTIFY THE ARCHITECT OF ANY AND ALLDISCREPANCIES.

2) GENERAL CONTRACTOR SHALL BE FAMILIAR WITHENTIRE SCOPE OF NEW WORK AND PROCEED WITHWORK IN ACCORDANCE WITH NEW WORK.

3) NEW WORK FLOOR PLANS, WALL LAYOUTS, DOORAND WINDOW LOCATIONS AND PATTERNS HAVE BEENSHOWN FOR REFERENCE ONLY. THIS DRAWING ISNOT INTENDED TO SHOW ALL CONDITIONS, MATERIALPATTERNS AND LAYOUTS. INSPECT SITE PRIOR TOSTART OF CONSTRUCTION TO DETERMINE THE FULLSCOPE OF WORK.

4) REFER TO ELECTRICAL / MECHANICAL DRAWINGS FOREXTENT OF NEW ELECTRICAL AND MECHANICALWORK. COORDINATE BETWEEN ALL DISCIPLINES.REPORT DISCREPANCIES TO ARCHITECT.

5) ALL PATCH PAINTING TO INCLUDE ENTIRE/COMPLETEWALL - EDGE TO EDGE & CORNER TO CORNER

NEW WORK NOTES:

FLOORS

INSTALL NEW DOOR, REFER TO DOOR SCHEDULE. PROVIDEHARDWARE PER SCHEDULE

DOORS AND WINDOWS

WALLS

NEW FLOOR FINISH, REFER TO FINISH SCHEDULE11

31

32

NEW WALL CONSTRUCTION, PREP AND PAINT, REFER TO WALL TYPESAND DETAILS.

MISC.

01

CEILINGS

PREP AND PAINT GYPSUM CEILING41

72

CLEAN EXISTING WINDOW SYSTEM, REPAIR WINDOW SILL AS NECESSARY

42

LIGHTING

74

NEW FLOOR BASE, REFER TO FINISH SCHEDULE12

RELOCATED PROJECTION SCREEN

PROVIDE NEW ACOUSTIC CEILING TILE AND GRID, REFER TO FINISHSCHEDULE

INSTALL NEW LIGHTING FIXTURES, REFER TO ELECTRICALDRAWINGS FOR FULL EXTENT OF WORK.

51

75

INSTALL NEW LOOSE FURNITURE, REFER WSUFUNITURE LIST

77

INSTALL NEW WHITE BOARD

INSTALL NEW FLAT SCREEN

33 DOOR TO RECEIVE NEW CARD READER, REFER TO ELECTRICAL DRAWINGS

78 INSTALL NEW ONE-WAY MIRROR. ARROW INDICATESDIRECTION OF VIEW

71 INSTALL NEW PLUMBING FIXTURE, REFER TO MEPDRAWINGS

34 WINDOW TO RECEIVE NEW BLACK-OUT SHADE

43 PROVIDE MINIMUM 4" SOUND ATTENUATING INSULATION ABOVECEILING 2 FEET EITHER SIDE OF WALLS AS SHOWN IN HATCHED AREAS.

INFILL AREA WHERE WALL WAS REMOVED WITH NEWFLOORING TO MATCH EXISTING

13

79 RELOCATE EXISTING TOILET ROOM ACCESSORIES(IE. SOAP DISPENSER, TOWEL DISPENSER, MIRRORS,ETC.) FOR NEW LAYOUT

35 DOOR CARD READER TO BE RE-CODED.

44 PROVIDE NEW 2'x2' CEILING ACCESS HATCH. COORDINATE LOCATIONWITH MECHANICAL EQUIPMENT

414141

41

41

41

41

41

41

41

41

41

41

41

41

41

41

41

41

41

41 41

41

41

41

4141

414141

41

51

5151

5151

51

44 44 44

Page 13: DETROIT, MI 48202...above a potential ignition source 3.abhr must be offset a minimum of 1" horizontally from any light switch, electrical or data receptacle, thermostat or other potential

DIRECTION OF AIR FLOW

FLEXIBLE DUCT

MANUAL VOLUME DAMPER

RISE IN DIRECTION OF AIR FLOWR

DUCT CAP

DROP IN DIRECTION OF AIR FLOWD

DUCT DOWN

DUCT UP

SUPPLY/OUTSIDE AIR DUCT SECTION

RETURN AIR DUCT SECTION

EXHAUST/RELIEF AIR DUCT SECTION

4-WAY DIFFUSER WITH BLANKOFF IN ONE DIRECTION

CD-16/115

AIR TERMINAL PROPERTIES SYMBOLNECK SIZE/CFM

TERMINAL AIR BOX (REFER TO SCHEDULE)###

### TERMINAL AIR BOX w/REHEAT COIL (REFER TO SCHEDULE)

OPPOSED BLADE DAMPER (REFER TO SCHEDULE)

PARALLEL BLADE DAMPER (REFER TO SCHEDULE)

DIFFERENTIAL PRESSURE SENSOR

CARBON MONOXIDE SENSORC

CARBON DIOXIDE SENSORC2

HUMIDISTAT SENSORH

HUMIDISTAT/SENSOR (DUCT MOUNTED)H

OCCUPANCY SENSORO

PRESSURE SENSOR/MONITORP

PRESSURE SENSOR (DUCT MOUNTED)P

THERMOSTAT/SENSORT

TEMPERATURE SENSOR (DUCT MOUNTED)T

THERMOSTAT/SENSOR WITH HEAVY DUTY ENCLOSURET

VENTILATION SYMBOL LIST

SYMBOL: DESCRIPTION:

AIRFLOW MEASUREMENT SYMBOLXX - AHU SYMBOLY - SEQUENTIAL NUMBER

XX-Y

NOT ALL SYMBOLS MAY APPLY.

VENTILATION ABBREVIATION KEY

ABBR: DESCRIPTION:

AD ACCESS DOOR

ABOVE FINISHED FLOORAFF

NC NEW CONNECTION

CFSD CONTROL/FIRE/SMOKE DAMPER

EA EXHAUST/RELIEF AIR

FD FIRE DAMPER

FOB FLAT ON BOTTOM

FOT FLAT ON TOP

FSD FIRE/SMOKE DAMPER

MA MIXED AIR

OA OUTSIDE AIR

RA RETURN AIR

SA SUPPLY AIR

SD SMOKE DAMPER

UC-1 DOOR UNDERCUT BY OTHERS (1" TYPICAL)

TERMINAL AIR BOXTAB

TYPICALTYP

UNO UNLESS NOTED OTHERWISE

CEILING DIFFUSER - EXISTINGCD-E

N.C. NORMALLY CLOSED

NOT IN CONTRACTNIC

NORMALLY OPENN.O.

PLAN OR DETAIL NUMBER

PLAN OR DETAIL NAME

PLAN OR DETAIL SCALE

NAME

1VIEW NAME1/8" = 1'-0"

LEVEL NAME

10' - 0" HEIGHT ABOVE PROJECT 0' - 0"

1 INDICATES NOTE USED TO DESCRIBE ADDITIONAL INFORMATION ABOUT WORK REQUIRED, SPECIFIC TO THE SHEET AND/OR DETAIL

NO R

HT

INDICATES DIRECTION OF TRUE NORTH

VIEW KEY

NEW WORK BY THIS CONTRACTOR (DARK SOLID LINE)

NEW WORK BY OTHERS AND/OR EXISTING TO REMAIN (LIGHT SOLID LINE)

EXISTING TO BE REMOVED BY THIS CONTRACTOR(DARK SHORT DASHED LINE)

LINE TYPE KEY:TEMPERATURE CONTROLS CONTRACTORT.C.C.

SECURITY CONTRACTORS.C.

AUDIO/VISUAL CONTRACTORA.V.C.

ASBESTOS ABATEMENT CONTRACTOR

PLUMBING CONTRACTORP.C.

GENERAL CONTRACTORG.C.

MECHANICAL CONTRACTORM.C.

VENTILATION CONTRACTORV.C.

ELECTRICAL CONTRACTORE.C.

A.C.

CONTRACTOR ABBREVIATION KEY

ABBR: DESCRIPTION:

TECHNOLOGY CONTRACTORT.C.

HEATING CONTRACTORH.C.

MECHANICAL GENERAL NOTES:THESE NOTES APPLY TO ALL MECHANICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED TO, FIRE PROTECTION, PLUMBING, MEDICAL GAS, VENTILATION, PIPING AND TEMPERATURE CONTROL.

1. DRAWINGS SHOWING LOCATIONS OF EQUIPMENT, DUCTWORK, PIPING, ETC. ARE DIAGRAMMATIC AND MAY NOT ALWAYS REFLECT EXACT INSTALLATION CONDITIONS. DRAWINGS SHOW THE GENERAL ARRANGEMENT OF DUCTWORK, PIPING, EQUIPMENT, ETC., AND MAY NOT INCLUDE ALL OFFSETS AND FITTINGS REQUIRED FOR COMPLETE INSTALLATION. THE DRAWINGS SHALL BE FOLLOWED AS CLOSELY AS ACTUAL BUILDING CONSTRUCTION AND THE WORK OF OTHERS WILL PERMIT.

2. DO NOT SCALE DRAWINGS. VERIFY ALL DIMENSIONS AND CLEARANCES FROM ARCHITECTURAL, STRUCTURAL, SUBMITTALS, AND OTHER APPROPRIATE DRAWINGS OR PHYSICALLY AT SITE. REVIEW ALL DRAWINGS, INCLUDING THOSE OF OTHER TRADES.

3. COORDINATE ALL WORK WITH ALL OTHER TRADES PRIOR TO INSTALLATION TO PROVIDE CLEARANCES REQUIRED FOR OPERATION, MAINTENANCE, CODE COMPLIANCE, AND TO VERIFY NON-INTERFERENCE WITH OTHER WORK. DO NOT FABRICATE PRIOR TO VERIFICATION OF NECESSARY CLEARANCES FOR ALL TRADES. BRING ANY INTERFERENCES OR CONFLICTS TO THE ATTENTION OF THE ARCHITECT/ENGINEER BEFORE PROCEEDING WITH FABRICATION OR EQUIPMENT ORDERS.

4. REVIEW SPACE REQUIREMENTS OF EQUIPMENT SPECIFIED OR SUBSTITUTED AND MAKE REASONABLE ACCOMMODATIONS IN LAYOUT AND POSITIONING TO PROVIDE PROPER ACCESS.

5. ANY CHANGES REQUIRED TO ELIMINATE CONFLICTS OR THAT RESULT FROM A FAILURE TO COORDINATE SHALL BE MADE BY THE CONTRACTOR WITHOUT ADDITIONAL COST OR EXPENSE TO OTHERS.

6. EACH CONTRACTOR IS RESPONSIBLE FOR ALL COSTS ASSOCIATED WITH ELECTRICAL CHANGES REQUIRED FOR EQUIPMENT PROPOSED THAT DIFFERS FROM THE BASIS OF DESIGN.

7. REFER TO ARCHITECTURAL REFLECTED CEILING PLAN, ELECTRICAL, TECHNOLOGY AUDIO/VISUAL, AND OTHER MECHANICAL PLANS FOR EXACT LOCATIONS OF ALL CEILING MOUNTED DEVICES, OTHER THAN SPRINKLERS.

8. EACH CONTRACTOR IS RESPONSIBLE FOR DAMAGE CAUSED BY THEIR ACTIONS TO WALLS, FLOORS, CEILINGS, AND ROOFS. THE CONTRACTOR WHOSE WORK CAUSES DAMAGE IS RESPONSIBLE FOR PATCHING TO MATCH ORIGINAL CONSTRUCTION, FIRE RATING, AND FINISH.

9. IN AREAS WITH DRYWALL CEILINGS COORDINATE LOCATIONS OF ACCESS PANELS WITH THE GC FOR ACCESS TO VALVES, DUCTWORK ACCESSORIES, DAMPERS, ETC. COORDINATE PANEL TYPE AND COLOR WITH ARCHITECT. NOTIFY THE GC OF THE REQUIRED ACCESS PANELS PRIOR TO BIDDING.

10. SEAL ALL FLOOR, WALL, AND ROOF PENETRATIONS AIRTIGHT WHERE CONDUITS, PIPING, AND DUCTS PENETRATE. PENETRATIONS THROUGH EXTERIOR WALLS AND ROOF SHALL BE SEALED AIRTIGHT WITH WATERPROOFING MATERIALS RECOMMENDED BY MANUFACTURER FOR OUTDOOR USE.

11. CAULK ALL PIPE AND DUCT PENETRATIONS OF FULL HEIGHT NON-FIRE RATED WALL, PARTITION, FLOOR, AND ROOF ASSEMBLIES. THIS IS ESSENTIAL TO PREVENT NOISE TRANSMISSION FROM ONE ROOM TO ANOTHER AND TO PROVIDE THE DESIRED NC LEVELS WITHIN ROOMS.

12. WHERE PIPES AND DUCTS ARE SHOWN TO PENETRATE FLOORS, PROVIDE SLEEVED OPENINGS WITH THE TOP EDGE RAISED ABOVE FLOOR SURFACE IN ACCORDANCE WITH ALL RELEVANT SPEC SECTIONS. SEAL SLEEVE PERIMETER TO BE WATERTIGHT.

13. EQUIPMENT SIZES AND SERVICE CLEARANCE REQUIREMENTS VARY AMONG DIFFERENT MANUFACTURERS. CONSULT APPROVED SHOP DRAWINGS FOR EQUIPMENT SIZES AND REQUIRED SERVICE CLEARANCES. COORDINATE WITH LAYOUT OF EQUIPMENT PADS, PIPING, DUCTWORK, ETC.

14. DO NOT BLOCK TUBE PULL OR EQUIPMENT SERVICE CLEARANCES. 15. MAINTAIN MINIMUM 3'-6” CLEARANCE IN FRONT OF ALL ELECTRICAL PANELS, MOTOR

STARTERS, SWITCHES, AND DISCONNECTS.16. PROVIDE CONCRETE EQUIPMENT PAD FOR ALL FLOOR MOUNTED EQUIPMENT. PAD SHALL

EXTEND MINIMUM 6” BEYOND ALL SIDES OF EQUIPMENT.17. DO NOT SUPPORT EQUIPMENT, PIPING, OR DUCTWORK FROM METAL DECKING OR OTHER

NON-STRUCTURAL BUILDING ELEMENTS. ANCHORS EMBEDDED IN CONCRETE SHALL BE CRACKED CONCRETE APPROVED IN ACCORDANCE WITH SPECIFICATIONS.

MECHANICAL PHASING NOTES:THESE NOTES APPLY TO ALL MECHANICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED TO, FIRE PROTECTION, PLUMBING, MEDICAL GAS, VENTILATION, PIPING AND TEMPERATURE CONTROL.

1. REFER TO ARCHITECTURAL DRAWINGS FOR GENERAL DESCRIPTION OF PHASES. REFER TO CONSTRUCTION MANAGER'S/GENERAL CONTRACTOR'S/ARCHITECT'S INSTRUCTIONS FOR MORE DETAILS AND PHASING SCHEDULES AND FOR CONCURRENT WORK. MECHANICAL, ELECTRICAL AND TECHNOLOGY DRAWINGS DEPICT THE INTENT OF THE FINAL DESIGN. THE MECHANICAL, ELECTRICAL, AND TECHNOLOGY DRAWINGS DO NOT DEPICT THE MEANS AND METHODS TO MEET THE REQUIREMENTS OF THE PHASING CRITERIA.

2. REVIEW PROJECT PHASING PLANS TO COORDINATE DEMOLITION WORK, OUTAGES, ETC. WITH AFFECTED ADJACENT AREAS.

3. PROVIDE TEMPORARY DUCTWORK, PIPING, SHUTOFF VALVES, ZONE VALVES, ZONE ALARMS, ETC. AS NEEDED TO MAINTAIN SERVICE TO ALL AREAS DURING ALL PHASES OF PROJECT.

4. INSTALL TEMPORARY DUCTWORK, PIPING, SHUTOFF VALVES, ETC. AS NECESSARY TO KEEP ALL OCCUPIED SPACES OPERATIONAL THROUGHOUT ALL PHASES OF THE PROJECT

5. PHASE DEMOLITION WORK TO MINIMIZE DOWNTIME.

MECHANICAL RENOVATION NOTES:THESE NOTES APPLY TO ALL MECHANICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED TO, FIRE PROTECTION, PLUMBING, MEDICAL GAS, VENTILATION, PIPING AND TEMPERATURE CONTROL.

1. EXISTING CONDITIONS ARE SHOWN BASED ON INFORMATION OBTAINED FROM FIELD SURVEYS, EXISTING BUILDING DOCUMENTS, AND STAFF. VERIFY EXISTING CONDITIONS AND REPORT ANY CONFLICTS BEFORE PROCEEDING.

2. NOT ALL EXISTING DUCTWORK AND PIPING IS SHOWN. VERIFY EXISTING CONDITIONS BEFORE STARTING WORK. NOTIFY ENGINEER OF ANY CONFLICTS WITH NEW WORK.

3. FIELD VERIFY THE AVAILABLE CLEARANCES FOR DUCTWORK AND PIPING BEFORE FABRICATION. RISES AND DROPS MAY BE NECESSARY BECAUSE OF EXISTING FIELD CONDITIONS. EACH CONTRACTOR SHALL FIELD VERIFY ACCESSIBILITY TO THE AREA OF HIS/HER WORK AND SHALL NOTIFY THE GENERAL CONTRACTOR CONSTRUCTION MANAGER ARCHITECT/ENGINEER PRIOR TO BIDDING IF OTHER UTILITIES ARE REQUIRED TO BE REMOVED OR RELOCATED TO ALLOW ACCESS TO HIS/HER AREA OF WORK.

4. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR CUTTING, REMOVAL AND PATCHING OF ROOFS, WALLS, AND FLOORS ASSOCIATED WITH WORK BY ALL CONTRACTORS. CONTRACTORS SHALL NOTIFY THE GC OF AFFECTED AREAS PRIOR TO BIDDING EACH CONTRACTOR SHALL CUT AND PATCH ROOFS, WALLS, AND FLOORS ASSOCIATED WITH HIS WORK.

5. EACH CONTRACTOR SHALL CUT AND PATCH ROOFS, WALLS, AND FLOORS ASSOCIATED WITH HIS WORK.

6. WHERE EXISTING MECHANICAL SYSTEMS ARE LOCATED IN AREAS THAT CONFLICT WITH NEW EQUIPMENT, PIPING, OR DUCTWORK TO BE INSTALLED, EACH CONTRACTOR SHALL EITHER ARRANGE NEW EQUIPMENT, PIPING, OR DUCTWORK IN SUCH A FASHION THAT IT DOES NOT CONFLICT WITH EXISTING SYSTEMS, OR REWORK EXISTING MECHANICAL SYSTEMS TO ALLOW FOR INSTALLATION OF NEW EQUIPMENT, PIPING, OR DUCTWORK.

7. PROVIDE TEMPORARY CONNECTIONS TO MAINTAIN EXISTING SYSTEMS IN SERVICE DURING CONSTRUCTION. MAINTAIN ACCESS TO EXISTING MECHANICAL INSTALLATIONS THAT REMAIN ACTIVE.

8. OBTAIN PERMISSION FROM OWNER BEFORE SHUTTING DOWN ANY SYSTEM FOR ANY REASON. MAINTAIN SERVICE TO ALL COMPONENTS THAT ARE TO REMAIN UNTIL NEW SYSTEMS ARE INSTALLED.

9. MAINTAIN EXISTING SYSTEM IN SERVICE UNTIL NEW SYSTEM IS COMPLETE AND READY FOR TIE IN AND SWITCHOVER. DRAIN SYSTEM ONLY TO MAKE SWITCHOVERS AND CONNECTIONS. OBTAIN PERMISSION FROM OWNER BEFORE PARTIALLY OR COMPLETELY DRAINING SYSTEM. MAKE CHANGEOVER TO NEW SYSTEMS WITH MINIMUM OUTAGE.

10. DISCONNECT AND REMOVE MECHANICAL DEVICES AND EQUIPMENT SERVING EQUIPMENT THAT HAS BEEN REMOVED.

1. THE SIZE OF EACH BRANCH DUCT TO A TERMINAL AIR BOX (TAB) SHALL MATCH THE TAB’S INLET SIZE UNLESS THE BRANCH IS GREATER THAN 6 FEET IN LENGTH, IN WHICH CASE THE BRANCH SHOULD BE INCREASED ONE DUCT SIZE, OR NOTED OTHERWISE.

2. ALIGN TEMPERATURE SENSORS WITH LIGHT SWITCHES AND WHEN IN CLOSE PROXIMITY TO EACH OTHER.

3. PROVIDE ACCESS DOORS AT ALL DUCT MOUNTED EQUIPMENT.4. EXISTING AIR INLET AND OUTLET CFM SHOWN ON DRAWINGS ARE FROM EXISTING

DRAWINGS, AND ARE FOR REFERENCE ONLY. CONTRACTOR SHALL USE PRE-BALANCE VALUES, AND NOT EXISTING CFM SHOWN ON DRAWINGS.

5. CONTRACTOR MAY REUSE PORTIONS OF EXISTING DUCT PROVIDED SIZES AND PRESSURE CLASSES ARE CORRECT, DUCT IS THOROUGHLY CLEANED AND FREE OF DEFECTS, AND ALL TRANSVERSE JOINTS, LONGITUDINAL SEAMS, AND DUCT WALL PENETRATIONS ARE SEALED AS SPECIFIED FOR NEW DUCTWORK.

6. CLEAN ALL SUPPLY, RETURN, AND EXHAUST DUCTWORK UPSTREAM OF ALL NEW CONNECTIONS PER SPECIFICATION SECTION 23 31 00.

VENTILATION GENERAL NOTES:

1. BEFORE ANY DEMOLITION WORK IS BEGUN A COMPLETE AIR BALANCE TEST SHALL BE PERFORMED BY THE TESTING, ADJUSTING AND BALANCING (TAB) CONTRACTOR ON EXISTING AIR HANDLERS AND EXHAUST FANS SERVING THE AREAS AFFECTED BY CONSTRUCTION. EQUIPMENT TO BE DEMOLISHED DOES NOT REQUIRE TESTING. PROVIDE AIR BALANCE TESTING ONLY ON EQUIPMENT THAT WILL CONTINUE TO BE USED TO SERVE RENOVATED AREAS AFTER THE CONSTRUCTION PHASE IS COMPLETED.

2. PROVIDE DUCT TRAVERSE READINGS AT LOCATIONS DESIGNATED ON THE DRAWINGS BY THE "AIRFLOW MEASUREMENT SYMBOL". THOSE MEASUREMENTS SHALL BE INCLUDED IN THE PRE DEMOLITION REPORT AND SHALL BE DESIGNATED WITH THE IDENTIFIER AS MARKED ON THE DRAWINGS. READINGS SHALL BE DESIGNATED WITH THE ROOM NAME AND NUMBER AS MARKED ON THE DRAWINGS. IF FLOOR PLANS DO NOT HAVE UNIQUE ROOM NAMES AND NUMBERS, TAB CONTRACTOR SHALL INCLUDE FLOOR PLAN WITH UNIQUE NUMBER DESIGNATIONS ASSIGNED TO READINGS THAT MATCH THOSE USED IN THE FINAL PRE-DEMOLITION REPORT. DRAWINGS THAT ARE HAND-MARKED WITH RED INK ARE ACCEPTABLE, PROVIDED THEY ARE LEGIBLE.

3. IN THE EVENT A DUCT TRAVERSE LOCATION AS MARKED ON THIS PLAN IS INACCESSIBLE FOR MEASUREMENT, THE TAB CONTRACTOR SHALL PERFORM THE TRAVERSE AT AN ALTERNATE LOCATION OR SHALL TAKE MULTIPLE DUCT TRAVERSES AND/OR READINGS AS REQUIRED TO DETERMINE THE AIRFLOW READING WHERE THE DUCT TRAVERSE SYMBOL IS SHOWN. IN THE EVENT TRAVERSES ARE TAKEN AT ALTERNATE LOCATION(S), TAB CONTRACTOR SHALL INCLUDE A DRAWING THAT SHOWS THE LOCATIONS WHERE THE ACTUAL MEASUREMENTS WERE TAKEN.

4. TAKE A DUCT STATIC PRESSURE READING AT EACH LOCATION WHERE A DUCT TRAVERSE READING IS TAKEN AND INCLUDE IN THE FINAL PRE-DEMOLITION TAB REPORT.

5. TAB CONTRACTOR SHALL COMPILE AND SUBMIT FOUR COPIES OF THE FINAL PRE-DEMOLITION REPORT WITHIN 10 WORKING DAYS AFTER THE FIELD MEASUREMENTS ARE COMPLETED. FINAL TAB REPORT SHALL BE SUBMITTED FOR REVIEW TO THE ARCHITECT/ENGINEER. TESTING SHALL INCLUDE ALL ITEMS REQUIRED IN THE SPECIFICATIONS.

6. TAB CONTRACTOR SHALL PROVIDE DUCT TRAVERSE READINGS AT LOCATIONS DESIGNATED ON THE DRAWINGS BY THE "AIRFLOW MEASUREMENT SYMBOL". THOSE MEASUREMENTS SHALL BE INCLUDED IN THE POST-CONSTRUCTION REPORT AND SHALL BE DESIGNATED WITH THE IDENTIFIER AS MARKED ON THE CONSTRUCTION DRAWINGS. GRILLE AND DIFFUSER READINGS SHALL BE DESIGNATED WITH THE ROOM NAME AND NUMBER AS MARKED ON THE DRAWINGS. IF THE DRAWINGS DO NOT HAVE UNIQUE ROOM NAMES AND NUMBERS, TAB CONTRACTOR SHALL INCLUDE FLOOR PLANS WITH UNIQUE NUMBER DESIGNATIONS ASSIGNED TO TRAVERSES, GRILLES, AND DIFFUSERS THAT MATCH THOSE USED IN THE FINAL PRE-DEMOLITION REPORT. SIMILAR ROOM NAMES, NUMBERS, OR DESIGNATIONS SHALL BE USED TO SIMPLIFY THE CROSS- REFERENCING OF READINGS TAKEN BETWEEN PRE-DEMOLITION AND POST-CONSTRUCTION REPORTS.

7. BALANCING CONTRACTOR SHALL PRE-BALANCE ALL EXISTING SYSTEMS TO REMAIN PER SPECIFICATION SECTION 23 05 93. BALANCE READINGS WILL BE REQUIRED AT AIR OUTLETS AND DUCT TRAVERSES TO VERIFY EXISTING AIRFLOW TO UNAFFECTED SPACES.

TAB PRE-DEMOLITION NOTES:

1. AFTER CONSTRUCTION ACTIVITIES ARE COMPLETE, TESTING, ADJUSTING (TAB) AND BALANCING CONTRACTOR SHALL REBALANCE AIR HANDLING UNITS AND EXHAUST FANS AS REQUIRED TO ACHIEVE THE NEW AIRFLOW VALUES SHOWN ON THE CONSTRUCTION DRAWINGS.

2. AREAS SERVED BY THIS EQUIPMENT WHICH WERE NOT RENOVATED SHALL BE RE-BALANCED TO THE AIRFLOW RATES MEASURED BEFORE THE RENOVATION OCCURRED (REFER TO THE FINAL PRE- DEMOLITION REPORT).

3. IF DUCT TRAVERSE LOCATION AS MARKED ON THE DRAWINGS IS INACCESSIBLE FOR MEASUREMENT, THE TAB CONTRACTOR SHALL PERFORM THE TRAVERSE AT AN ALTERNATE LOCATION OR SHALL TAKE MULTIPLE DUCT TRAVERSES AND/OR GRILLE READINGS AS REQUIRED TO DETERMINE THE FLOW RATE. IN THE EVENT TRAVERSES ARE TAKEN AT AN ALTERNATE LOCATION(S), TAB CONTRACTOR SHALL INCLUDE A DRAWING THAT SHOWS THE LOCATIONS WHERE THE ACTUAL MEASUREMENTS WERE TAKEN.

4. A DUCT STATIC PRESSURE READING SHALL BE TAKEN AT EACH LOCATION WHERE A DUCT TRAVERSE READING IS TAKEN AND SHALL BE INCLUDED IN THE FINAL POST-CONSTRUCTION TAB REPORT.

5. TAB CONTRACTOR SHALL COMPILE AND SUBMIT COPIES OF THE FINAL POST-CONSTRUCTION TAB REPORT AS REQUIRED BY SECTION 23 05 93.

6. THE FINAL POST CONSTRUCTION REPORT SHALL INCLUDE ALL ITEMS REQUIRED IN THE SPECIFICATIONS.

TAB POST-CONSTRUCTION NOTES:

BUILDING CODE: MBC 2015 EDITION

FIRE CODE: NFPA 13: 2013 EDITION

PLUMBING CODE: MBC 2015 EDITION

MECHANICAL CODE: MMC 2015 EDITION

ELECTRICAL CODE: NFPA 70 (NEC) 2016EDITION

LIFE SAFETY CODE: NFPA 101 2015 EDITION

ENERGY CONSERVATION CODE: ASHRAE 90.1 2013

HEALTH DEPARTMENT CODE: CURRENT EDITION

LOCAL BUILDING CODE: CURRENT EDITION

APPLICABLE CODES

CONTRACTOR SHALL COMPLY WITH APPLICABLE CODES AND LOCAL AMENDMENTS.

VENTILATION SHEET INDEXMH-000 VENTILATION COVERSHEET

MHD-101 FIRST FLOOR DEMOLITION - VENTILATION

MHD-102 SECOND FLOOR DEMOLITION - VENTILATION

MH-101 FIRST FLOOR PLAN - VENTILATION

MH-102 SECOND FLOOR PLAN - VENTILATION

MH-300 VENTILATION SCHEDULE

AREA OF WORKNO SCALE

FLOOR LEVEL

project number:

sheet title:

sheet number:

approved

project:

coordination checked

location

drawn

checked

designed

issue: date:

key plan:

WAYNE STATE

UNIVERSITYFacilities Planning and Management

5454 Cass Avenue

Detroit, MI 48202

FO

R B

IDS

consultants:

NM Project Number - 18113.0

Rands Building

IMEG Project Number -

Rands House - RackhamRelocation

WSU : 00

- -

12/1

0/2

018 1

1:4

1:2

3 A

M

MH-000

VENTILATION COVERSHEET

PETPAPPETPAP

KIRSAI

18004050.01

PETPAP

PETPAP

WS

U R

an

ds B

ldg

Rackh

am

Relo

cati

on

18004050.0

1

REFERENCE SCALE IN INCHES

0 1 2 3

PROJECT #

IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

18004050.01

Owner Review 60% CD's Nov. 13, 2018

Owner Review 90% CD's Nov. 27, 2018

100% CD's Dec. 04, 2018

For Bids Dec. 11, 2018

Page 14: DETROIT, MI 48202...above a potential ignition source 3.abhr must be offset a minimum of 1" horizontally from any light switch, electrical or data receptacle, thermostat or other potential

1 2 3 41.9 2.5 3.1 3.2 3.5 3.8

A

b

c

d

e

f

a10

a9

b4

c.1

c.2

c.3

c.4

e.8

1

EXISTING 10x6 EG

200 CFM

EXISTING 10x6 EG

200 CFM

6x6 EG

75 CFM

EXISTING 14x10 TOILET

EXH. DUCT UP

3'-2"

16x1

0 S

A

20x1

8 S

A

10x6 EA

10x6 EA

14x10 EA

(E0 SECURITY FENCE

(E) AIR-COOLED

CONDENSING UNITS

AREA OF WORKNO SCALE

FLOOR LEVEL

project number:

sheet title:

sheet number:

approved

project:

coordination checked

location

drawn

checked

designed

issue: date:

key plan:

WAYNE STATE

UNIVERSITYFacilities Planning and Management

5454 Cass Avenue

Detroit, MI 48202

FO

R B

IDS

consultants:

NM Project Number - 18113.0

Rands Building

IMEG Project Number -

Rands House - RackhamRelocation

WSU : 00

- -

12/1

0/2

018 1

1:4

1:2

8 A

M

MHD-101

FIRST FLOOR DEMOLITION -

VENTILATION

PETPAPPETPAP

KIRSAI

18004050.01

PETPAP

PETPAP

WS

U R

an

ds B

ldg

Rackh

am

Relo

cati

on

18004050.0

1

REFERENCE SCALE IN INCHES

0 1 2 3

PROJECT #

IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

18004050.01

SHEET GENERAL NOTES :

1. COORDINATE ALL DEMOLITION WORK WITH ARCHITECTURAL AND ELECTRICAL AND ELECTRICAL DEMOLITION WITH OWNER'S PROJECT REPRESENTATIVE.

2. COORDINATE ANY SHUTDOWNS OF EXISTING SERVICES OR EQUIPMENT WITH OWNER. PERFORM SHUTDOWNS AT A SCHEDULED TIME AS TO MINIMIZE DISRUPTION OF BUILDING OPERATIONS.

3. REMOVE ALL INDICATED DUCTWORK AND EQUIPMENT COMPLETELY INCLUDING ALL RELATED ITEMS INCLUDING HANGERS, SUPPORTS, CONTROLS AND ACCESSORIES.

4. CAP ALL THE OPEN ENDED DUCTWORK. DO NOT LEAVE ANY ABONDONED DUCT WORK IN THE AREA OF WORK.

KEYNOTES:

1. DISCONNECT AND REMOVE EXISTING FINNED TUBE RADIATOR. CLEAN AND PREPARE FOR NEW INSTALLATION.

#

NO R

HT

1/8" = 1'-0"1 FIRST FLOOR DEMOLITION - VENTILATION

For Bids Dec. 11, 2018

Page 15: DETROIT, MI 48202...above a potential ignition source 3.abhr must be offset a minimum of 1" horizontally from any light switch, electrical or data receptacle, thermostat or other potential

WHITE BOARD

projectionscreen

T

T

1 2 3 41.9 2.5 3.1 3.2 3.5 3.8

A

b

c

d

e

f

a10

a9

b4

c.1

c.2

c.3

c.4

e.8

FD IN FLRFD

1

2

3

4

4

2

AREA OF WORKNO SCALE

FLOOR LEVEL

project number:

sheet title:

sheet number:

approved

project:

coordination checked

location

drawn

checked

designed

issue: date:

key plan:

WAYNE STATE

UNIVERSITYFacilities Planning and Management

5454 Cass Avenue

Detroit, MI 48202

FO

R B

IDS

consultants:

NM Project Number - 18113.0

Rands Building

IMEG Project Number -

Rands House - RackhamRelocation

WSU : 00

- -

12/1

0/2

018 1

1:4

1:2

9 A

M

MHD-102

SECOND FLOOR DEMOLITION -

VENTILATION

PETPAPPETPAP

KIRSAI

18004050.01

PETPAP

PETPAP

WS

U R

an

ds B

ldg

Rackh

am

Relo

cati

on

18004050.0

1

NO R

HT

1/8" = 1'-0"1 SECOND FLOOR DEMOLITION - VENTILATION

REFERENCE SCALE IN INCHES

0 1 2 3

PROJECT #

IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

18004050.01

SHEET GENERAL NOTES :

1. COORDINATE ALL DEMOLITION WORK WITH ARCHITECTURAL AND ELECTRICAL AND ELECTRICAL DEMOLITION WITH OWNER'S PROJECT REPRESENTATIVE.

2. COORDINATE ANY SHUTDOWNS OF EXISTING SERVICES OR EQUIPMENT WITH OWNER. PERFORM SHUTDOWNS AT A SCHEDULED TIME AS TO MINIMIZE DISRUPTION OF BUILDING OPERATIONS.

3. REMOVE ALL INDICATED DUCTWORK AND EQUIPMENT COMPLETELY INCLUDING ALL RELATED ITEMS INCLUDING HANGERS, SUPPORTS, CONTROLS AND ACCESSORIES.

4. CAP ALL THE OPEN ENDED DUCTWORK. DO NOT LEAVE ANY ABONDONED DUCT WORK IN THE AREA OF WORK.

KEYNOTES:

1. DEMOLISH DUCTWORK, CEILING SUPPLY & RETURN DIFFUSERS AND ASSOCIATED ACCESSORIES BACK TO THE POINT SHOWN AND PREPARE FOR NEW CONNECTION.

2. REMOVE EXISTING VAV BOX & ITS ASSOCIATED TEMPERATURE SENSOR, CONTROLS IN ITS ENTIRETY. CAP CONTROLS AT MAIN.

3. DISCONNECT AND REMOVE EXISTING FINNED TUBE RADIATOR. CLEAN AND PREPARE FOR NEW INSTALLATION.

4. PRIOR TO DEMOLITION, MEASURE SUPPLY/ RETURN/ EXHAUST AIR FLOWS AT ALL EXISTING TERMINAL AIR DEVICES IN THE AREA. LABEL ALL DEVICES AND AND CREATE AN AIR BALANCE REPORT DESCRIBED ON SHEET MH-000.

#

Owner Review 60% CD's Nov. 13, 2018

Owner Review 90% CD's Nov. 27, 2018

100% CD's Dec. 04, 2018

For Bids Dec. 11, 2018

Page 16: DETROIT, MI 48202...above a potential ignition source 3.abhr must be offset a minimum of 1" horizontally from any light switch, electrical or data receptacle, thermostat or other potential

111

117

125

129

137 141

143

145

144142138

140136

134

132

130

128

126

122

120

124

118

116

112

108

106

102

100

103107

DN

UP

UP

CL

OFFICE

COVERED AREA

RESEARCHLAB

OFFICE

IT OFFICE

TREATMENT

OFFICE

TREATMENTOFFICEOFFICE

TREATMENTCHILDPLAYROOM

OBSERVATION

TREATMENT

TREATMENT

OFFICE

OFFICE

JC

UNISEXADA

WOMEN

WAITING

WAITING

LOUNGE

OFFICE

PLANTERSTORAGE

STORAGE

OPENOFFICE

VEST

PORCH

OPENOFFICE

CONFERENCE ROOMOFFICE

1 2 3 41.9 2.5 3.1 3.2 3.5 3.8

A

b

c

d

e

f

a10

a9

b4

c.1

c.2

c.3

c.4

e.8

(E)10x6 EG

200 CFM

10x6 EA

10x6 EA

(E)10x6 EG

200 CFM

(E)6x6 EG

75 CFM

(E) 14x10 TOILET

EXH. DUCT UP

(E) AIR-COOLED

CONDENSING UNITS

(E) GAS

METER

4 FT AD

190 CFM

4 FT AD

190 CFM

4 FT AD

190 CFM

30x8 RAG-C

285 CFM

30x8 RAG-C

285 CFM

24x8 RAG-C

335 CFM

8 FT AD

335 CFM

(E)30x8 RAG-C

4 FT AD

(E) 4 FT AD

300 CFM

(E)14x6 RAG-A300 CFM

W/FIRE DAMPER

(E)24x14 RAG-A645 CFM

W/FIRE DAMPER

(E)30x8 RAG

340 CFM

ALTERNATE: CU-1

(E) HHWS&R UP TO 2ND FLOOR

HVAC-2

16x10 SA20x1

8 S

A

COORDINATE W/ ARCH FOR ALTERNATE EXTEND & REWORK

EXISTING SECURITY FENCE

1

(E0 SECURITY FENCE 2

2AREA OF WORKNO SCALE

FLOOR LEVEL

project number:

sheet title:

sheet number:

approved

project:

coordination checked

location

drawn

checked

designed

issue: date:

key plan:

WAYNE STATE

UNIVERSITYFacilities Planning and Management

5454 Cass Avenue

Detroit, MI 48202

FO

R B

IDS

consultants:

NM Project Number - 18113.0

Rands Building

IMEG Project Number -

Rands House - RackhamRelocation

WSU : 00

- -

12/1

0/2

018 1

1:4

1:2

4 A

M

MH-101

FIRST FLOOR PLAN -

VENTILATION

PETPAPPETPAP

KIRSAI

18004050.01

PETPAP

PETPAP

WS

U R

an

ds B

ldg

Rackh

am

Relo

cati

on

18004050.0

1

NO R

HT

1/8" = 1'-0"1 FIRST FLOOR PLAN - VENTILATION

REFERENCE SCALE IN INCHES

0 1 2 3

PROJECT #

IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

18004050.01

KEYNOTES:

1. EXISTING FINNED TUBE RADIATOR TO BE CLEANED AND RELOCATED ALONG NEW WALL. EXTEND EXISTING HHWS&R FROM CEILING TO NEW LOCATION. REPAIR & INSTALL NEW PIPE INSULATION. COORDINATE W/ ARCH FOR THE PIPING INSTALLATION IN THE CEILING & WALL.

2. ALTERNATE: INSTALL NEW OUTDOOR CONDENSING UNIT CU-1 FOR AC-1, CONNECT ALL THE REFRIGERANT PIPING, WIRING & CONTROLS. COORDINATE W/ ARCH FOR SUPPORT CONCRETE PAD & REWORK OF THE EXISTING SECURITY FENCE. INSTALL UNIT PER MANUFACTURER'S INSTRUCTIONS AND CLEARANCE REQUIREMENTS.

#

SHEET GENERAL NOTES :

1. COORDINATE ALL DEMOLITION WORK WITH ARCHITECTURAL AND ELECTRICAL AND ELECTRICAL DEMOLITION WITH OWNER'S PROJECT REPRESENTATIVE.

2. COORDINATE ANY SHUTDOWNS OF EXISTING SERVICES OR EQUIPMENT WITH OWNER. PERFORM SHUTDOWNS AT A SCHEDULED TIME AS TO MINIMIZE DISRUPTION OF BUILDING OPERATIONS.

3. REMOVE ALL INDICATED DUCTWORK AND EQUIPMENT COMPLETELY INCLUDING ALL RELATED ITEMS INCLUDING HANGERS, SUPPORTS, CONTROLS AND ACCESSORIES.

4. CAP ALL THE OPEN ENDED DUCTWORK. DO NOT LEAVE ANY ABONDONED DUCT WORK IN THE AREA OF WORK.

Owner Review 60% CD's Nov. 13, 2018

Owner Review 90% CD's Nov. 27, 2018

100% CD's Dec. 04, 2018

For Bids Dec. 11, 2018

Page 17: DETROIT, MI 48202...above a potential ignition source 3.abhr must be offset a minimum of 1" horizontally from any light switch, electrical or data receptacle, thermostat or other potential

WHITE BOARD

projectionscreen

244

240

245

229

227

225

219

217

243242241

246

247

238236

230

226

224

220

218

214212

202

200.1

200

201

203205

234

232

207

OFFICE

OPENOFFICE

OPENOFFICE

IT

MECH

TREATMENT

OBSERVATION

TREATMENT

COMFERENCE/GROUP ROOMOBSERVATIONTREATMENT

TREATMENT

OBSERVATION

TREATMENTTREATMENT

ADULTGROUP ROOM

ADULTGROUP ROOM

WOMEN

UNISEX ADA

CHILDREN'SGROUP ROOM

OFFICETREATMENT

DN

UP

OPENOFFICE

STORAGE

DN

OPENOFFICE

OPENOFFICE

OFFICEOFFICE

OBSERVATION

TREATMENT

OPEN

UP

OFFICE

T T

T

T

T

1 2 3 41.9 2.5 3.1 3.2 3.5 3.8

A

b

c

d

e

f

a10

a9

b4

c.1

c.2

c.3

c.4

e.8

14x4 SD

155 CFM

14x4 SD

155 CFM

16x4 SD

180 CFM

18x4 SD

190 CFM

14x8 RAG-A

380 CFM

16x4 SD

180 CFMRAG IN CEILING

(TYP.)

14x8 RAG-A

360 CFM

16x4 SD

180 CFM

18x4 SD

195 CFM

14x6 RAG-A

310 CFM

16x4 SD

155 CFM

26x16 RAG-A

1385 CFM

12x10 RAG-A 390 CFM

16x6 SD 390 CFM

14x8 RAG-A

18x4 SD170 CFM

(TYP.4)

(E)AHU

44x22 SA UP

SD-E SD-E SD-E SD-E

SD-E

SD-E

SD-ESD-E

SD-E

SD-E

SD-E

SD-E

SD-E

SD-E

SD-E

TAB-ETAB-E

TAB-E

TAB-E

SD-E

SD-E SD-E

12x10 SA

24x12 SA

28x1

4 S

A

44x2

0 S

A

42x20 SA

30x20 SA

16x1

4 S

A

10x10 SA

10x8 SA

TAB-E

26x1

2 S

A

SD-E SD-E

14x4 SA

18x4 SA

20x6

SA

18x4 SA

22x8 SA

20x8 SA 20x6 SA

18x6

SA

18x4 SA18x4 SA

18x4 SA

14x10 RA

16x4

SA

10x8 RA

20x6 SA 16x16 RA

14x4 SA

14x6 SA

10x8 RA

22x8 SA

16x4 SA

18x4

SA

18x4 SA

6ø RARG-E

14x4 SA

16x4 SA

24x8 TOILETEXH DUCT UP

TO EF-2

14x8 TOILETEXH FROM

BELOW

EG-E

10x6/200

EG-E

10x6/200

RG-E

RG-E

RG-E

RG-E

RG-E

RG-E

RG-E

RG-E

RG-E

RG-E RG-E

RG-E

RG-E

RG-ERG-E

RG-E

14x8 EA

10x6 EA

10x6 EA

10x6 EA

CD-1

6/180

NC

1

CD-1

6/160

8ø8ø

CD-1

6/120

CD-1

6/120

1

1

10x10

CD-1

6/120

RG-1

RG-1

ALT: SG-1

12x8/200

ALT: SG-1

12x8/200

10x8

10x8

ALERNATE: HRV-13

ALTERNATE: AC-1

2

SD-E

TAB-E

SD-E

SD-E

FD IN FLRFD

FPB - 2.1 FPB - 2.2

FPB - 2.3

10ø

NC NC

10x8

ALTERNATE: 22"X8" LOUVER

L-1, COORDINATE W/ ARCH

ALTERNATE: 10"Ø EXHAUST AIR THROUGH ROOF W/ RAIN

CAP, COORDINATE W/ ARCH FOR ROOF PENETRATION

FINNED TUBE

HEATER-E

1¼" PUMPED

DRAIN FROM AC-1

1¼" PUMPED DRAIN FROM

AC-1 TO BASEMENT

AREA OF WORKNO SCALE

FLOOR LEVEL

project number:

sheet title:

sheet number:

approved

project:

coordination checked

location

drawn

checked

designed

issue: date:

key plan:

WAYNE STATE

UNIVERSITYFacilities Planning and Management

5454 Cass Avenue

Detroit, MI 48202

FO

R B

IDS

consultants:

NM Project Number - 18113.0

Rands Building

IMEG Project Number -

Rands House - RackhamRelocation

WSU : 00

- -

12/1

0/2

018 1

1:4

1:2

6 A

M

MH-102

SECOND FLOOR PLAN -

VENTILATION

PETPAPPETPAP

KIRSAI

18004050.01

PETPAP

PETPAP

WS

U R

an

ds B

ldg

Rackh

am

Relo

cati

on

18004050.0

1

NO R

HT

1/8" = 1'-0"1 SECOND FLOOR PLAN - VENTILATION

REFERENCE SCALE IN INCHES

0 1 2 3

PROJECT #

IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

18004050.01

SHEET GENERAL NOTES :

1. COORDINATE FINAL DUCT AND PIPING ROUTES WITH EXISTING DUCT, PIPING ON SITE.

2. COORDINATE ANY SHUTDOWNS OF EXISTING SERVICES OR EQUIPMENT WITH OWNER. PERFORM SHUTDOWNS AT A SCHEDULED TIME AS TO MINIMIZE DISRUPTION OF BUILDING OPERATIONS.

3. CAP ALL OPEN ENDED DUCTWORK. DO NOT LEAVE ANY ABONDONED DUCT WORK IN THE AREA OF WORK.

4. PROVIDE ACCESS DOOR IN HARD CEILINGS WHERE NECESSARY TO PROVIDE ACCESS TO TERMINAL AIR BOXES AND OTHER EQUIPMENT LOCATED ABOVE CEILING.

5. PROVIDE ACCESS PANELS WHERE REQUIRED TO ALLOW ACCESS TO BALANCING DAMPER.

KEYNOTES:

1. INSTALL AIR TERMINAL BOXES AND THEIR ASSOCIATED TEMPERATURE SENSORS, CONTROLS AND SUPPLY/RETURN/EXHAUST INLETS/OUTLETS AS SHOWN. INSTALLATION SHALL PER DETAILS ON MH-3.0. AIR TERMINAL BOX INSTALLATION SHALL PER MANUFACTURER AND PROVIDE SUFFICIENT CLEARANCE & SERVICE SPACES. FAN POWER BOX INDUCED AIR INLET SHALL HAVE SILENCER AND BE CLEAR OF ANY AIR BLOCKAGE. UNIT CONTROLS SHALL BE COMPATIBLE WITH EXISTING CONTROL SYSTEM IN THE BUILDING AND TO BE CONFIRMED BY THE OWNER.

2. ALTERNATE: INSTALL NEW RECESSED CEILING MOUNTED AC-1, SEE SCH. CONNECT REFERIGERANT PIPING TO GROUND FLOOR PAD MOUNTED CU-1. SEE MH101. CONNECT PUMPED CONDENSATE LINE IN THE ATTATIC INTO THE DUCT CHASE & DRAIN TO BASEMENT F.D. INSTALL PER MANUFACTURERS RECOMMENDATIONS. COORDINATE WITH ARCH FOR UNIT MOUNTING.

3. ALTERNATE: INSTALL NEW CEILING MOUNTED ENERGY RECOVERY VENTILATOR HRV-1, SEE SCH. CONNNECT EXHAUST AIR, OUTSIDE AIR, RETURN AIR & SUPPLY AIR PER MANUFACTURER RECOMMENDATION. COORDINATE WITH ARCH FOR OUTSIDE LOUVER & ROOF OPENING.

#

Owner Review 60% CD's Nov. 13, 2018

Owner Review 90% CD's Nov. 27, 2018

100% CD's Dec. 04, 2018

For Bids Dec. 11, 2018

Page 18: DETROIT, MI 48202...above a potential ignition source 3.abhr must be offset a minimum of 1" horizontally from any light switch, electrical or data receptacle, thermostat or other potential

AREA OF WORKNO SCALE

FLOOR LEVEL

project number:

sheet title:

sheet number:

approved

project:

coordination checked

location

drawn

checked

designed

issue: date:

key plan:

WAYNE STATE

UNIVERSITYFacilities Planning and Management

5454 Cass Avenue

Detroit, MI 48202

FO

R B

IDS

consultants:

NM Project Number - 18113.0

Rands Building

IMEG Project Number -

Rands House - RackhamRelocation

WSU : 00

- -

12/1

0/2

018 1

1:4

1:2

7 A

M

MH-300

VENTILATION SCHEDULE

PETPAPPETPAP

KIRSAI

18004050.01

PETPAP

PETPAP

WS

U R

an

ds B

ldg

Rackh

am

Relo

cati

on

18004050.0

1

REFERENCE SCALE IN INCHES

0 1 2 3

PROJECT #

IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

18004050.01

NOTES:1. PACKAGED DX AC UNIT, RECESSED CEILING HUNG DUCTLESS. PROVIDE THREE-POLE DISCONNECT SWITCH BETWEEN INDOOR AND OUTDOOR UNIT.2. PROVIDE UNIT WITH REMOTE T-STAT, UNIT MOUNTED DISCONNECT SWITCH, AND REMOTE WALL MOUNTED MICROPROCESSOR BASED PROGRAMMABLE CONTROL PANEL, WIRELESS CONTROLS, CONTROLS TO BE CONFIRMED BY THE OWNER.3. ULTRA LOW AMBIENT PACKAGE. SNOW/ HAIL GUARDS KIT.4. UNIT CONDENSATE PUMP.

AC-01 2ND FLR MEETING SPACE FC 1 DIRECT 2 208 1670-770-880

-10300.79 18,000 - 36,000 16

710-810-920-1060

38,000 2" PPF 500 60 208 1 FEED FROM CU-01

MCA VOLT PHASE % VOLT PHASE FLA MCA MSCP

TYPE FLA DRIVE CFM (WET) SHFCAPACITY RANGE

(BTUH)SEER CFM (DRY)

TOTALCAPACITY

(BUTH) @ 5FTYPE

MAX FACEVELOCITY

(FPM)

EFF

MARK AREA SERVED

SUPPLY FAN

ELECT. DATA

COOILING HEATING AIR FILTER

POWER

INDOOR UNIT

SPLIT SYSTEM AIR COOLED AIR CONDITIONING UNIT SCHEDULE (ALTERNATE)

AC-01 CU-01 SCROLL 1 R410A NO -13 TO 115 208 1 28 40 MITSUBISHI HEAT PUMP PLA-A36 & PUZ-HA36 SEE NOTES 1,2,3, 4

VOLT PHASE MCA MSCP

TYPE QUANTITYREF.TYPE

MARK MARK

COMPRESSOR

HOT GASBYPASS

PROVIDED

AMB. TEMP°F

POWER

INDOOR UNIT OUTDOOR CONDENSING UNIT

MFR/MODEL REMARKS

SPLIT SYSTEM AIR COOLED AIR CONDITIONING UNIT SCHEDULE (CONT.)

NOTES:1. OPERATION MODE: RECOVERY, BYPASS, AUTO.

HRV-1 2ND FLR MTG AIR TO AIR TOTAL LGH-F300 300 260 203 91 63 65 68 79 50 52 55 63 0.60 0.6 1 208 1.8 15 WASHABLE 18-34 MITSUBISHI ELECUNIT CONTROL PZ-60DR LOSSNAY

CONTROLLER

EXTRAHIGH

HIGH LOWEXTRALOW

EXTRAHIGH

HIGH LOWEXTRALOW

MIN. MAX. PH VOLT MCA MOCP

CFM(EXTRAHIGH)

CFM(HIGH)

CFM(LOW)

CFM(EXTRALOW)

HEATING % COOLING % IN.W.C.MARK AREA SERVED TYPE UNIT SIZE

CAPACITY ENTHALPHY RECOVERY EFFICIENCY FAN E.S.P.

ELEC INFO

FILTERSOUND

PRESSURELEVEL (dBA)

DESIGN BASE MODEL REMARKS

ENERGY RECOVERY VENTILATOR SCHEDULE (ALTERNATE)

1. SIZES INIDCATED ARE TYPICAL. REFER TO PLANS FOR ADDITIONAL REQUIRED SIZES AND CFM.

NOTES

ALTERNATEL-1

INTAKE AIR LOUVER 22" X 8" OR EQUAL FACE AREA 350RUSKIN GLAZING LOUVER OR 6 INCH DRAINABLELOUVER

ALUMINUM CONSTRUCTION, BIRD SCREEN,COORDINATE W/ ARCH

EG-1 EXHAUST AIR REGISTERSAME AS DUCT CONNECTION PLUS

FRAME1-600 12" X 12" 30 TITUS WALL MOUNTED SEE FLOOR PLAN

ALUMINUM CONSTRUCTION NECK MOUNTEDOPPOSED BLADE DAMPER

24 X 24 201-2000 22x22 24X24 30

RG-1 RETURN AIR GRILLE

12 X 12 0-200 10X10 12x12 30

TITUS CEILING MOUNTED SEE FLOOR PLAN ALUMINUM CONSTRUCTION

SG-1 SUPPLY AIR REGISTERSAME AS DUCT CONNECTION PLUS

FRAME1-450 12 X 8 30

TITUS DOUBLE DEFLECTION BLADES WALLMOUNTED

ALUMINUM CONSTRUCTION NECK MOUNTEDOPPOSED BLADE DAMPER

201-345 8" 8" 30

CD-1 SUPPLY AIR CEILING DIFFUSER 24 X 241-200 6" 6" 30

TITUS SQUARE LAY -IN CEILING MOUNTINGALUMINUM CONSTRUCTION NECK MOUNTEDOPPOSED BLADE DAMPER

MARK SERVICE MODULE SIZE CFM RANGEMIN DUCT

CONNECTION (IN)

NOMINALNECK SIZE

(IN)MAX NC DESCRIPTION REMARKS

DIFFUSER-REGISTER-GRILLE-LOUVER SCHEDULE

5. INSTALL A SIGN ON THE EXTERIOR OF THE AIR TERMINAL UNITS AT THE SERVICE ACCESS LOCATION INDICATING THE SOURCE AHU THAT IS PROVIDING THE SUPPLY AIR AND THE ROOMS THAT ARE BEING SERVED.

4. COIL ENTERING AIR TEMPS AND HEATING CAPACITIES BASED ON 48F PRIMARY AIR, 68F PLENUM AIR AND 72F ROOM HEATING SETPOINT.

3. FURNISH WITH THERMAL OVERLOAD PROTECTION AND DISCONNECT

OCTAVE BAND AT THE MAXIMUM PRIMARY AIR FLOW INDICATED IN THE SCHEDULE AND WITH 1.5" W.C. INLET STATIC PRESSURE.

2. FOR SINGLE DUCT VAV/CAV TERMINAL UNITS - DISCHARGE SOUND POWER DATA FOR 100% PRIMARY AIR VALVE FLOW IS TO BE ARI CERTIFIED AND IS NOT TO EXCEED 74 DB (REFERENCE 10 -12 WATTS) IN THE 2ND

OCTAVE BAND AT THE MAXIMUM PRIMARY AIR FLOW INDICATED IN THE SCHEDULE AND WITH 1.5" W.C. INLET STATIC PRESSURE.

1. FOR SINGLE DUCT VAV/CAV TERMINAL UNITS - RADIATED SOUND POWER DATA FOR 100% PRIMARY AIR VALVE FLOW IS TO BE ARI CERTIFIED AND IS NOT TO EXCEED 66 DB (REFERENCE 10 -12 WATTS) IN THE 2ND

NOTES:

FPB-2.3 OFFICE 245 SERIES A 6 360 120 360 55 90 4.0 208 1 SCR 360 0.5 1/3 208 1 ECM TITUS TFS, INLET SILENCER

FPB-2.2 TREATMENT 246 SERIES A 6 160 50 160 55 94 2.0 208 1 SCR 160 0.5 1/3 208 1 ECM TITUS TFS, INLET SILENCER

FPB-2.1 RESERVATION 247 SERIES A 6 180 60 180 55 90 2.0 208 1 SCR 180 0.5 1/3 208 1 ECM TITUS TFS, INLET SILENCER

ENTO F

LVGO F

HP VOLT PHMOTORCNTRL

MARK AREA SERVED TYPEUNITSIZE

INLETSIZE(IN)

CFM(MAX)

CFM(MIN)

CFM

AIR TEMP

KW VOLT PH CNTRLFAN

CFM @70 °F

EXTSP

(IWC)

MOTOR(HIGH EFFICIENCY ECM)

REMARKS

MARK AREA SERVED TYPEUNITSIZE

INLETSIZE(IN)

PRIMARY AIRHEATING COIL (ELECTRIC)

(NOTE 4)FAN INFORMATION REMARKS

SERIES FAN POWERED BOX SCHEDULE

Owner Review 60% CD's Nov. 13, 2018

Owner Review 90% CD's Nov. 27, 2018

100% CD's Dec. 04, 2018

For Bids Dec. 11, 2018

Page 19: DETROIT, MI 48202...above a potential ignition source 3.abhr must be offset a minimum of 1" horizontally from any light switch, electrical or data receptacle, thermostat or other potential

PLUMBING SYMBOL LIST

SYMBOL: DESCRIPTION:

PIPE SERVING FIXTURE ON FLOOR ABOVE(EXAMPLE: FD = FLOOR DRAIN)FD

PITCH PIPE IN DIRECTION

DIELECTRIC CONNECTION

UNION/FLANGE

BALANCING VALVE (NUMBER INDICATES GPM)GPM

CHECK VALVE

PIPE CAP

PIPE DOWN

PIPE UP OR UP/DOWN

DIRECTION OF FLOW IN PIPE

NEW CONNECTION

SHUTOFF VALVE NORMALLY OPEN

SHUTOFF VALVE NORMALLY CLOSED

COLD WATER - POTABLECW

HOT WATER - POTABLEHW

HOT WATER CIRCULATING - POTABLEHWC

HOT WATER - POTABLE NUMBER INDICATES TEMPHW140

HOT WATER CIRC. - POTABLE NUMBER INDICATES TEMPHWC140

DRAIND

NOT ALL SYMBOLS MAY APPLY.

SAFETY/RELIEF VALVE

PIPE CONTINUATION

ROUTE TO DRAIN

PLUMBING ABBREVIATION KEY

CO CLEANOUT

E

FLOOR CLEANOUTFCO

FLOOR DRAINFD

LAVATORYL

MOP BASINMB

MIXING VALVEMV

SINKSK

URINALUR

WATER CLOSETWC

WALL CLEANOUTWCO

WATER HEATERWH

VENT THROUGH ROOFVTR

AD ACCESS DOOR

ABOVE FINISHED FLOORAFF

BFP BACKFLOW PREVENTER

NC NEW CONNECTION

NOT IN CONTRACTNIC

ABBR: DESCRIPTION:

TYPICALTYP

UNLESS NOTED OTHERWISEUNO

EXISTING

CAST IRONCI

PLAN OR DETAIL NUMBER

PLAN OR DETAIL NAME

PLAN OR DETAIL SCALE

NAME

1VIEW NAME1/8" = 1'-0"

LEVEL NAME

10' - 0" HEIGHT ABOVE PROJECT 0' - 0"

1 INDICATES NOTE USED TO DESCRIBE ADDITIONAL INFORMATION ABOUT WORK REQUIRED, SPECIFIC TO THE SHEET AND/OR DETAIL

NO R

HT

INDICATES DIRECTION OF TRUE NORTH

VIEW KEY

NEW WORK BY THIS CONTRACTOR (DARK SOLID LINE)

NEW WORK BY OTHERS AND/OR EXISTING TO REMAIN (LIGHT SOLID LINE)

EXISTING TO BE REMOVED BY THIS CONTRACTOR(DARK SHORT DASHED LINE)

LINE TYPE KEY:

TEMPERATURE CONTROLS CONTRACTORT.C.C.

SECURITY CONTRACTORS.C.

AUDIO/VISUAL CONTRACTORA.V.C.

ASBESTOS ABATEMENT CONTRACTOR

PLUMBING CONTRACTORP.C.

GENERAL CONTRACTORG.C.

MECHANICAL CONTRACTORM.C.

VENTILATION CONTRACTORV.C.

ELECTRICAL CONTRACTORE.C.

A.C.

CONTRACTOR ABBREVIATION KEY

ABBR: DESCRIPTION:

TECHNOLOGY CONTRACTORT.C.

HEATING CONTRACTORH.C.

MECHANICAL PHASING NOTES:THESE NOTES APPLY TO ALL MECHANICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED TO, FIRE PROTECTION, PLUMBING, MEDICAL GAS, VENTILATION, PIPING AND TEMPERATURE CONTROL.

1. REFER TO ARCHITECTURAL DRAWINGS FOR GENERAL DESCRIPTION OF PHASES. REFER TO CONSTRUCTION MANAGER'S/GENERAL CONTRACTOR'S/ARCHITECT'S INSTRUCTIONS FOR MORE DETAILS AND PHASING SCHEDULES AND FOR CONCURRENT WORK. MECHANICAL, ELECTRICAL AND TECHNOLOGY DRAWINGS DEPICT THE INTENT OF THE FINAL DESIGN. THE MECHANICAL, ELECTRICAL, AND TECHNOLOGY DRAWINGS DO NOT DEPICT THE MEANS AND METHODS TO MEET THE REQUIREMENTS OF THE PHASING CRITERIA.

2. REVIEW PROJECT PHASING PLANS TO COORDINATE DEMOLITION WORK, OUTAGES, ETC. WITH AFFECTED ADJACENT AREAS.

3. PROVIDE TEMPORARY DUCTWORK, PIPING, SHUTOFF VALVES, ZONE VALVES, ZONE ALARMS, ETC. AS NEEDED TO MAINTAIN SERVICE TO ALL AREAS DURING ALL PHASES OF PROJECT.

4. INSTALL TEMPORARY DUCTWORK, PIPING, SHUTOFF VALVES, ETC. AS NECESSARY TO KEEP ALL OCCUPIED SPACES OPERATIONAL THROUGHOUT ALL PHASES OF THE PROJECT

5. PHASE DEMOLITION WORK TO MINIMIZE DOWNTIME.

MECHANICAL GENERAL NOTES:THESE NOTES APPLY TO ALL MECHANICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED TO, FIRE PROTECTION, PLUMBING, MEDICAL GAS, VENTILATION, PIPING AND TEMPERATURE CONTROL.

1. DRAWINGS SHOWING LOCATIONS OF EQUIPMENT, DUCTWORK, PIPING, ETC. ARE DIAGRAMMATIC AND MAY NOT ALWAYS REFLECT EXACT INSTALLATION CONDITIONS. DRAWINGS SHOW THE GENERAL ARRANGEMENT OF DUCTWORK, PIPING, EQUIPMENT, ETC., AND MAY NOT INCLUDE ALL OFFSETS AND FITTINGS REQUIRED FOR COMPLETE INSTALLATION. THE DRAWINGS SHALL BE FOLLOWED AS CLOSELY AS ACTUAL BUILDING CONSTRUCTION AND THE WORK OF OTHERS WILL PERMIT.

2. DO NOT SCALE DRAWINGS. VERIFY ALL DIMENSIONS AND CLEARANCES FROM ARCHITECTURAL, STRUCTURAL, SUBMITTALS, AND OTHER APPROPRIATE DRAWINGS OR PHYSICALLY AT SITE. REVIEW ALL DRAWINGS, INCLUDING THOSE OF OTHER TRADES.

3. COORDINATE ALL WORK WITH ALL OTHER TRADES PRIOR TO INSTALLATION TO PROVIDE CLEARANCES REQUIRED FOR OPERATION, MAINTENANCE, CODE COMPLIANCE, AND TO VERIFY NON-INTERFERENCE WITH OTHER WORK. DO NOT FABRICATE PRIOR TO VERIFICATION OF NECESSARY CLEARANCES FOR ALL TRADES. BRING ANY INTERFERENCES OR CONFLICTS TO THE ATTENTION OF THE ARCHITECT/ENGINEER BEFORE PROCEEDING WITH FABRICATION OR EQUIPMENT ORDERS.

4. REVIEW SPACE REQUIREMENTS OF EQUIPMENT SPECIFIED OR SUBSTITUTED AND MAKE REASONABLE ACCOMMODATIONS IN LAYOUT AND POSITIONING TO PROVIDE PROPER ACCESS.

5. ANY CHANGES REQUIRED TO ELIMINATE CONFLICTS OR THAT RESULT FROM A FAILURE TO COORDINATE SHALL BE MADE BY THE CONTRACTOR WITHOUT ADDITIONAL COST OR EXPENSE TO OTHERS.

6. EACH CONTRACTOR IS RESPONSIBLE FOR ALL COSTS ASSOCIATED WITH ELECTRICAL CHANGES REQUIRED FOR EQUIPMENT PROPOSED THAT DIFFERS FROM THE BASIS OF DESIGN.

7. REFER TO ARCHITECTURAL REFLECTED CEILING PLAN, ELECTRICAL, TECHNOLOGY AUDIO/VISUAL, AND OTHER MECHANICAL PLANS FOR EXACT LOCATIONS OF ALL CEILING MOUNTED DEVICES, OTHER THAN SPRINKLERS.

8. EACH CONTRACTOR IS RESPONSIBLE FOR DAMAGE CAUSED BY THEIR ACTIONS TO WALLS, FLOORS, CEILINGS, AND ROOFS. THE CONTRACTOR WHOSE WORK CAUSES DAMAGE IS RESPONSIBLE FOR PATCHING TO MATCH ORIGINAL CONSTRUCTION, FIRE RATING, AND FINISH.

9. IN AREAS WITH DRYWALL CEILINGS COORDINATE LOCATIONS OF ACCESS PANELS WITH THE GC FOR ACCESS TO VALVES, DUCTWORK ACCESSORIES, DAMPERS, ETC. COORDINATE PANEL TYPE AND COLOR WITH ARCHITECT. NOTIFY THE GC OF THE REQUIRED ACCESS PANELS PRIOR TO BIDDING.

10. SEAL ALL FLOOR, WALL, AND ROOF PENETRATIONS AIRTIGHT WHERE CONDUITS, PIPING, AND DUCTS PENETRATE. PENETRATIONS THROUGH EXTERIOR WALLS AND ROOF SHALL BE SEALED AIRTIGHT WITH WATERPROOFING MATERIALS RECOMMENDED BY MANUFACTURER FOR OUTDOOR USE.

11. CAULK ALL PIPE AND DUCT PENETRATIONS OF FULL HEIGHT NON-FIRE RATED WALL, PARTITION, FLOOR, AND ROOF ASSEMBLIES. THIS IS ESSENTIAL TO PREVENT NOISE TRANSMISSION FROM ONE ROOM TO ANOTHER AND TO PROVIDE THE DESIRED NC LEVELS WITHIN ROOMS.

12. WHERE PIPES AND DUCTS ARE SHOWN TO PENETRATE FLOORS, PROVIDE SLEEVED OPENINGS WITH THE TOP EDGE RAISED ABOVE FLOOR SURFACE IN ACCORDANCE WITH ALL RELEVANT SPEC SECTIONS. SEAL SLEEVE PERIMETER TO BE WATERTIGHT.

13. EQUIPMENT SIZES AND SERVICE CLEARANCE REQUIREMENTS VARY AMONG DIFFERENT MANUFACTURERS. CONSULT APPROVED SHOP DRAWINGS FOR EQUIPMENT SIZES AND REQUIRED SERVICE CLEARANCES. COORDINATE WITH LAYOUT OF EQUIPMENT PADS, PIPING, DUCTWORK, ETC.

14. DO NOT BLOCK TUBE PULL OR EQUIPMENT SERVICE CLEARANCES. 15. MAINTAIN MINIMUM 3'-6” CLEARANCE IN FRONT OF ALL ELECTRICAL PANELS, MOTOR

STARTERS, SWITCHES, AND DISCONNECTS.16. PROVIDE CONCRETE EQUIPMENT PAD FOR ALL FLOOR MOUNTED EQUIPMENT. PAD SHALL

EXTEND MINIMUM 6” BEYOND ALL SIDES OF EQUIPMENT.17. DO NOT SUPPORT EQUIPMENT, PIPING, OR DUCTWORK FROM METAL DECKING OR OTHER

NON-STRUCTURAL BUILDING ELEMENTS. ANCHORS EMBEDDED IN CONCRETE SHALL BE CRACKED CONCRETE APPROVED IN ACCORDANCE WITH SPECIFICATIONS.

MECHANICAL RENOVATION NOTES:THESE NOTES APPLY TO ALL MECHANICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED TO, FIRE PROTECTION, PLUMBING, MEDICAL GAS, VENTILATION, PIPING AND TEMPERATURE CONTROL.

1. EXISTING CONDITIONS ARE SHOWN BASED ON INFORMATION OBTAINED FROM FIELD SURVEYS, EXISTING BUILDING DOCUMENTS, AND STAFF. VERIFY EXISTING CONDITIONS AND REPORT ANY CONFLICTS BEFORE PROCEEDING.

2. NOT ALL EXISTING DUCTWORK AND PIPING IS SHOWN. VERIFY EXISTING CONDITIONS BEFORE STARTING WORK. NOTIFY ENGINEER OF ANY CONFLICTS WITH NEW WORK.

3. FIELD VERIFY THE AVAILABLE CLEARANCES FOR DUCTWORK AND PIPING BEFORE FABRICATION. RISES AND DROPS MAY BE NECESSARY BECAUSE OF EXISTING FIELD CONDITIONS. EACH CONTRACTOR SHALL FIELD VERIFY ACCESSIBILITY TO THE AREA OF HIS/HER WORK AND SHALL NOTIFY THE GENERAL CONTRACTOR CONSTRUCTION MANAGER ARCHITECT/ENGINEER PRIOR TO BIDDING IF OTHER UTILITIES ARE REQUIRED TO BE REMOVED OR RELOCATED TO ALLOW ACCESS TO HIS/HER AREA OF WORK.

4. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR CUTTING, REMOVAL AND PATCHING OF ROOFS, WALLS, AND FLOORS ASSOCIATED WITH WORK BY ALL CONTRACTORS. CONTRACTORS SHALL NOTIFY THE GC OF AFFECTED AREAS PRIOR TO BIDDING EACH CONTRACTOR SHALL CUT AND PATCH ROOFS, WALLS, AND FLOORS ASSOCIATED WITH HIS WORK.

5. EACH CONTRACTOR SHALL CUT AND PATCH ROOFS, WALLS, AND FLOORS ASSOCIATED WITH HIS WORK.

6. WHERE EXISTING MECHANICAL SYSTEMS ARE LOCATED IN AREAS THAT CONFLICT WITH NEW EQUIPMENT, PIPING, OR DUCTWORK TO BE INSTALLED, EACH CONTRACTOR SHALL EITHER ARRANGE NEW EQUIPMENT, PIPING, OR DUCTWORK IN SUCH A FASHION THAT IT DOES NOT CONFLICT WITH EXISTING SYSTEMS, OR REWORK EXISTING MECHANICAL SYSTEMS TO ALLOW FOR INSTALLATION OF NEW EQUIPMENT, PIPING, OR DUCTWORK.

7. PROVIDE TEMPORARY CONNECTIONS TO MAINTAIN EXISTING SYSTEMS IN SERVICE DURING CONSTRUCTION. MAINTAIN ACCESS TO EXISTING MECHANICAL INSTALLATIONS THAT REMAIN ACTIVE.

8. OBTAIN PERMISSION FROM OWNER BEFORE SHUTTING DOWN ANY SYSTEM FOR ANY REASON. MAINTAIN SERVICE TO ALL COMPONENTS THAT ARE TO REMAIN UNTIL NEW SYSTEMS ARE INSTALLED.

9. MAINTAIN EXISTING SYSTEM IN SERVICE UNTIL NEW SYSTEM IS COMPLETE AND READY FOR TIE IN AND SWITCHOVER. DRAIN SYSTEM ONLY TO MAKE SWITCHOVERS AND CONNECTIONS. OBTAIN PERMISSION FROM OWNER BEFORE PARTIALLY OR COMPLETELY DRAINING SYSTEM. MAKE CHANGEOVER TO NEW SYSTEMS WITH MINIMUM OUTAGE.

10. DISCONNECT AND REMOVE MECHANICAL DEVICES AND EQUIPMENT SERVING EQUIPMENT THAT HAS BEEN REMOVED.

1. THE SYMBOLS AND THE MATERIAL LIST ARE FOR THE CONVENIENCE OF THE CONTRACTOR. CONTRACTOR SHALL VERIFY QUANTITIES AND FURNISH ALL MATERIALS REQUIRED FOR FULLY OPERATIONAL SYSTEMS, WHETHER SPECIFIED OR NOT.

2. CATALOG NUMBERS SHALL NOT BE CONSIDERED COMPLETE, BUT ARE GIVEN AS AN AID TO THE CONTRACTOR AND TO INDICATE THE QUALITY REQUIRED. CONTRACTOR IS RESPONSIBLE FOR A COMPLETE DESCRIPTION OF MATERIAL ON THESE DRAWINGS AND IN THE SPECIFICATIONS BEFORE ORDERING. THE DESCRIPTION OF THE MATERIAL TAKES PRECEDENCE OVER THE CATALOG NUMBER. THE FIRST MANUFACTURER LISTED IS THE BASIS OF DESIGN.

3. CONTRACTOR SHALL VERIFY THAT FIXTURES SUPPLIED ARE APPROVED PER ALL APPLICABLE STATE, LOCAL AND GOVERNING AUTHORITIES.

4. ALL FIXTURES SHALL CONFORM TO FEDERAL ACT S.38745. INVERT ELEVATIONS ARE FROM EXISTING DRAWINGS AND MAY NOT BE ACCURATE. VERIFY

ALL ELEVATIONS BEFORE BEGINNING WORK.6. VERIFY UNDERGROUND PIPE SIZES, INVERT ELEVATIONS, AND LOCATIONS PRIOR TO

BEGINNING ANY WORK.7. REFER TO THE PLUMBING ROUGH-IN SCHEDULE FOR THE SIZES OF BRANCH PIPES TO

PLUMBING FIXTURES.8. FOR CLARITY, NOT ALL VALVES HAVE BEEN SHOWN. PROVIDE SHUTOFF VALVES IN

DOMESTIC WATER PIPING SERVING EACH ROOM WITH FIXTURES. ANGLE STOPS SHALL NOT BE CONSIDERED SHUTOFF VALVES.

9. EXISTING CONDITIONS ON DEMOLITION PLANS ARE PROVIDED TO INDICATE THE GENERAL SCOPE OF ITEMS TO BE REMOVED. REFER TO SPECIFICATION SECTION 22 05 05 FOR ADDITIONAL DEMOLITION INFORMATION.

10. P.C. SHALL CUT AND PATCH EXISTING AS REQUIRED FOR NEW OR DEMOLITION WORK UNLESS NOTED OTHERWISE. REFER TO SPECIFICATION SECTION 22 05 05 FOR ADDITIONAL INFORMATION.

PLUMBING GENERAL NOTES:

BUILDING CODE: MBC 2015 EDITION

FIRE CODE: NFPA 13: 2013 EDITION

PLUMBING CODE: MBC 2015 EDITION

MECHANICAL CODE: MMC 2015 EDITION

ELECTRICAL CODE: NFPA 70 (NEC) 2016EDITION

LIFE SAFETY CODE: NFPA 101 2015 EDITION

ENERGY CONSERVATION CODE: ASHRAE 90.1 2013

HEALTH DEPARTMENT CODE: CURRENT EDITION

LOCAL BUILDING CODE: CURRENT EDITION

APPLICABLE CODES

CONTRACTOR SHALL COMPLY WITH APPLICABLE CODES AND LOCAL AMENDMENTS.

PLUMBING SHEET INDEXP-000 PLUMBING COVERSHEET

P-101 FIRST FLOOR PLAN - PLUMBING

P-102 SECOND FLOOR PLAN - PLUMBING

P-300 ENLARGED PLANS

P-500 PLUMBING SCHEDULES

NOTES: 1) SANITARY RISER UP IN WALL TO FIXTURE SHALL BE A MINUMUM OF 2". 2) 1/2" CW ANDHW APPLIES ONLY TO THE FINAL VERTICAL RISE-DROP TO EACH FIXTURE, BRANCH PIPING TOVERTICAL RISE-DROP SHALL BE A MINIMUM OF 3/4" UNLESS NOTED OTHERWISE. 3) SIZES SHOWNARE MINIMUMS. SIZES SHOWN ON THE DRAWING THAT ARE LARGER THAN THE SIZES LISTED IN THESCHEDULE SHALL DICTATE THE ROUGH-IN SIZE.

PLUMBING FIXTURE ROUGH-IN SCHEDULE

FIXTUREDESCRIPTION

DOMESTICCW

(NOTE 3)

DOMESTICHW

(NOTE 3)SANITARY(NOTE 3)

VENT(NOTE 3) REMARKS

LAVATORY 1/2" 1/2" 1 1/4" 1 1/4" NOTE 1 & 2

WATERCLOSET

1" - 4" 2" -

AREA OF WORKNO SCALE

FLOOR LEVEL

project number:

sheet title:

sheet number:

approved

project:

coordination checked

location

drawn

checked

designed

issue: date:

key plan:

WAYNE STATE

UNIVERSITYFacilities Planning and Management

5454 Cass Avenue

Detroit, MI 48202

FO

R B

IDS

consultants:

NM Project Number - 18113.0

Rands Building

IMEG Project Number -

Rands House - Rackham

Relocation

WSU : 00

- -

12/1

0/2

018 1

1:4

0:2

9 A

M

P-000

PLUMBING COVERSHEET

PETPAPPETPAP

KIRSAI

18004050.01

PETPAP

PETPAP

WS

U R

an

ds B

ldg

Rackh

am

Relo

cati

on

18004050.0

1

REFERENCE SCALE IN INCHES

0 1 2 3

PROJECT #

IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

18004050.01

Owner Review 60% CD's Nov. 13, 2018

Owner Review 90% CD's Nov. 27, 2018

100% CD's Dec. 04, 2018

For Bids Dec. 11, 2018

Page 20: DETROIT, MI 48202...above a potential ignition source 3.abhr must be offset a minimum of 1" horizontally from any light switch, electrical or data receptacle, thermostat or other potential

111

117

125

129

137 141

143

145

144142138

140136

134

132

130

128

126

122

120

124

118

116

112

108

106

102

100

103107

DN

UP

UP

CL

OFFICE

COVERED AREA

RESEARCHLAB

OFFICE

IT OFFICE

TREATMENT

OFFICE

TREATMENTOFFICEOFFICE

TREATMENTCHILDPLAYROOM

OBSERVATION

TREATMENT

TREATMENT

OFFICE

OFFICE

JC

UNISEXADA

WOMEN

WAITING

WAITING

LOUNGE

OFFICE

PLANTERSTORAGE

STORAGE

OPENOFFICE

VEST

PORCH

OPENOFFICE

CONFERENCE ROOMOFFICE

1 2 3 41.9 2.5 3.1 3.2 3.5 3.8

A

b

c

d

e

f

a10

a9

b4

c.1

c.2

c.3

c.4

e.8

P-300

2

ALTERNATE: NEW 1¼" PUMPED

COND. DRAIN FROM AC-1 TO

BASEMENT, SEE MH102

AREA OF WORKNO SCALE

FLOOR LEVEL

project number:

sheet title:

sheet number:

approved

project:

coordination checked

location

drawn

checked

designed

issue: date:

key plan:

WAYNE STATE

UNIVERSITYFacilities Planning and Management

5454 Cass Avenue

Detroit, MI 48202

FO

R B

IDS

consultants:

NM Project Number - 18113.0

Rands Building

IMEG Project Number -

Rands House - Rackham

Relocation

WSU : 00

- -

12/1

0/2

018 1

1:4

0:3

0 A

M

P-101

FIRST FLOOR PLAN - PLUMBING

PETPAPPETPAP

KIRSAI

18004050.01

PETPAP

PETPAP

WS

U R

an

ds B

ldg

Rackh

am

Relo

cati

on

18004050.0

1

NO R

HT

1/8" = 1'-0"1 FIRST FLOOR PLAN - PLUMBING

REFERENCE SCALE IN INCHES

0 1 2 3

PROJECT #

IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

18004050.01

Owner Review 60% CD's Nov. 13, 2018

Owner Review 90% CD's Nov. 27, 2018

100% CD's Dec. 04, 2018

For Bids Dec. 11, 2018

Page 21: DETROIT, MI 48202...above a potential ignition source 3.abhr must be offset a minimum of 1" horizontally from any light switch, electrical or data receptacle, thermostat or other potential

WHITE BOARD

projection

screen

244

240

245

229

227

225

219

217

243242241

246

247

238236

230

226

224

220

218

214212

202

200.1

200

201

203205

234

232

207

OFFICE

OPENOFFICE

OPENOFFICE

IT

MECH

TREATMENT

OBSERVATION

TREATMENT

COMFERENCE/GROUP ROOMOBSERVATIONTREATMENT

TREATMENT

OBSERVATION

TREATMENTTREATMENT

ADULTGROUP ROOM

ADULTGROUP ROOM

WOMEN

UNISEX ADA

CHILDREN'SGROUP ROOM

OFFICETREATMENT

DN

UP

OPENOFFICE

STORAGE

DN

OPENOFFICE

OPENOFFICE

OFFICEOFFICE

OBSERVATION

TREATMENT

OPEN

UP

OFFICE

1 2 3 41.9 2.5 3.1 3.2 3.5 3.8

A

b

c

d

e

f

a10

a9

b4

c.1

c.2

c.3

c.4

e.8

P-300

4

ALTERNATE: NEW 1¼" PUMPED

COND. DRAIN FROM AC-1 TO

BASEMENT, SEE MH-102

AREA OF WORKNO SCALE

FLOOR LEVEL

project number:

sheet title:

sheet number:

approved

project:

coordination checked

location

drawn

checked

designed

issue: date:

key plan:

WAYNE STATE

UNIVERSITYFacilities Planning and Management

5454 Cass Avenue

Detroit, MI 48202

FO

R B

IDS

consultants:

NM Project Number - 18113.0

Rands Building

IMEG Project Number -

Rands House - Rackham

Relocation

WSU : 00

- -

12/1

0/2

018 1

1:4

0:3

1 A

M

P-102

SECOND FLOOR PLAN -

PLUMBING

PETPAPPETPAP

KIRSAI

18004050.01

PETPAP

PETPAP

WS

U R

an

ds B

ldg

Rackh

am

Relo

cati

on

18004050.0

1

NO R HT

1/8" = 1'-0"1 SECOND FLOOR PLAN - PLUMBING

REFERENCE SCALE IN INCHES

0 1 2 3

PROJECT #

IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

18004050.01

Owner Review 60% CD's Nov. 13, 2018

Owner Review 90% CD's Nov. 27, 2018

100% CD's Dec. 04, 2018

For Bids Dec. 11, 2018

Page 22: DETROIT, MI 48202...above a potential ignition source 3.abhr must be offset a minimum of 1" horizontally from any light switch, electrical or data receptacle, thermostat or other potential

122

120

124

JC

UNISEXADA

WOMEN 224

220

WOMEN

UNISEX ADA

1 1.9

c.2

c.3

c.4

FD-E

2"CW

3/4” CW TO

LAV(2)

4” SAN FROM

2ND LEVEL

C.O.

WC-EWC-E

L-E L-E

WC-E

WH-E

ON SHELF

1 1/2” CW TO

(3) WC &

(1) LAV1/2” CW

TO S.S.

4" R.W.C

A.S.C.

4"ST

FD-E

3"SAN

4"SAN

1 1/2"SAN

NC

NC

1 1/2"V

1 1/2"VNEW 1-1/2" VENT ROUTE IN THE WALL & CEILING TO CONNECT TO EXISTING VENT

NEW 1/2" DCWPIPE ABOVE CEILING

1/2"CWUNDERFLOOR

NC

NC

4L-1

1/2"HW

1

c.2

c.3

c.4

FD-EFD-E

4"SAN

2"CW

3/4” CW TO

LAV(2)

3"SAN

4” W FROM

2ND LEVEL

C.O.

WC-E WC-EL-E L-E

L-E

WC-E

WH-E

ON SHELF

1 1/2” CW TO

(3) WC &

(1) LAV

1/2” CW

TO S.S.

4" R.W.C

A.S.C.

4"SAN

4"ST

FD-E

1

1 1.9

c.2

c.3

c.4

WC-E WC-E

WC-E

L-1

3"SAN

3"SAN

2" V FROM

BELOW

1 1/2" CW FROM

BELOW

3/4" HW FROM

BELOW4" V UP

THRU ROOF

L-1 L-1

NC

NCNC

NC

5

NC

1

c.2

c.3

c.4

WC-E

L-E L-E

WC-E

L-EUR-E

FD-E

FD-E

2" V FROM

BELOW

2"V

1 1/2" CW FROM

BELOW

3/4" HW FROM

BELOW

3/4"HW

4" V UP

THRU ROOF

3/4"HW

3/4"CW

1

2

3

2

AREA OF WORKNO SCALE

FLOOR LEVEL

project number:

sheet title:

sheet number:

approved

project:

coordination checked

location

drawn

checked

designed

issue: date:

key plan:

WAYNE STATE

UNIVERSITYFacilities Planning and Management

5454 Cass Avenue

Detroit, MI 48202

FO

R B

IDS

consultants:

NM Project Number - 18113.0

Rands Building

IMEG Project Number -

Rands House - Rackham

Relocation

WSU : 00

- -

12/1

0/2

018 1

1:4

0:3

4 A

M

P-300

ENLARGED PLANS

PETPAPPETPAP

KIRSAI

18004050.01

PETPAP

PETPAP

WS

U R

an

ds B

ldg

Rackh

am

Relo

cati

on

18004050.0

1

REFERENCE SCALE IN INCHES

0 1 2 3

PROJECT #

IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

18004050.01

1/4" = 1'-0"2 FIRST FLOOR ENLARGE NEW PLAN - PLUMBING

1/4" = 1'-0"1 FIRST FLOOR ENLARGE DEMOLITION PLAN - PLUMBING

1/4" = 1'-0"4 SECOND FLOOR ENLARGENEW PLAN - PLUMBING

1/4" = 1'-0"3 SECOND FLOOR ENLARGE DEMOLITION PLAN - PLUMBING

KEYNOTES:

1. REMOVE EXISTING LAV, REMOVE EXISTING SAN, VENT, DCW, DHW PIPE TO THE EXISTING LAV TO BE DEMOED. CAP SAN, DCW & DHW PIPE AT WALL & USE WALL COVER, COORDINATE W/ ARCH. CAP VENT PIPE AT MAIN.

2. REMOVE EXISTING LAV, DISCONNECT EXISTING SAN, DCW & DHW CONNECTION TO THE LAV. PREPARE TO CONNECT TO NEW LAV. SEE NEW WORK.

3. REMOVE EXISTING UR, REMOVE EXISTING SAN, DCW PIPE TO THE EXISTING UR TO BE DEMOED. CAP SAN, DCW.

4. INSTALL NEW 1/2" DHW, DCW PIPING & SHUT OFF VALVES FROM EXISTING BRANCHES TO NEW SINK AS SHOWN. CONNECT NEW 1-1/2" VENT PIPE AS SHOWN. NEW 1-1/2" DRAIN PIPE TO BE INSTALLED UNDERFLOOR. COORDINATE THE SLAB CUTTING & REPAIR WORK W/ ARCH.

5. INSTALL NEW 1/2" DHW, DCW PIPING AND SHUT-OFF VALVES FROM EXISTING BRANCHES TO NEW LAV AS SHOWN. NEW 1-1/2" SANITARY AND VENT.

#

Owner Review 60% CD's Nov. 13, 2018

Owner Review 90% CD's Nov. 27, 2018

100% CD's Dec. 04, 2018

For Bids Dec. 11, 2018

Page 23: DETROIT, MI 48202...above a potential ignition source 3.abhr must be offset a minimum of 1" horizontally from any light switch, electrical or data receptacle, thermostat or other potential

AREA OF WORKNO SCALE

FLOOR LEVEL

project number:

sheet title:

sheet number:

approved

project:

coordination checked

location

drawn

checked

designed

issue: date:

key plan:

WAYNE STATE

UNIVERSITYFacilities Planning and Management

5454 Cass Avenue

Detroit, MI 48202

FO

R B

IDS

consultants:

NM Project Number - 18113.0

Rands Building

IMEG Project Number -

Rands House - Rackham

Relocation

WSU : 00

- -

12/1

0/2

018 1

1:4

0:3

5 A

M

P-500

PLUMBING SCHEDULES

PETPAPPETPAP

KIRSAI

18004050.01

PETPAP

PETPAP

WS

U R

an

ds B

ldg

Rackh

am

Relo

cati

on

18004050.0

1

REFERENCE SCALE IN INCHES

0 1 2 3

PROJECT #

IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

18004050.01

L-1

LAVATORY - ADA WALL MOUNTED, WHITE VITREOUS CHINA, 20"x18", 4" HIGH CONTOURED BACKSPLASH, SINGLE FAUCETHOLE, DRILLED FOR CONCEALED ARM CARRIER.

INSULATION KIT - PRE-MANUFACTURED FOR P-TRAP, STOP VALVES AND SUPPLY LINES.

LAVATORY TRIM - SENSOR ACTIVATED MIXING FAUCET, BATTERY POWERED WITH HYDROELECTRIC GENERATOR, BRASSCONSTRUCTION, CHROME-PLATED FINISH, CONVENTIONAL SPOUT WITH AERATOR, PERFORATED GRID STRAINER WITH1-1/4" 17 GAUGE TAILPIECE, SOLID BRASS SOLENOID WITH BUILT-IN FILTER, SOLID BRASS THERMOSTATIC MIXING VALVEMEETING ASSE 1070 REQUIREMENTS WITH ADJUSTABLE TEMPERATURE LIMIT STOP AND INTEGRAL CHECK VALVES,WATERPROOF CONNECTORS AND CABLE.

MOUNT CONTROLS AND BATTERIES IN WATERPROOF VANDAL-RESISTANT ENCLOSURE BELOW LAVATORY. MOUNTMIXING VALVE UNDER COUNTER/LAVATORY. MAXIMUM FLOW SHALL BE 0.5 GPM IN COMPLIANCE WITH ENERGY POLICYACT OF 2005 AND ASME/ANSI STANDARD A112.18.1M. FAUCET SHALL COMPLY WITH FEDERAL ACT S.3874. PROVIDERESTRICTIVE DEVICE AND ESCUTCHEON PLATE AS REQUIRED. FAUCET SHALL HAVE A MAXIMUM 30 SECONDS OFCONTINUOUS DISCHARGE.

ACCESSORIES - QUARTER-TURN 3/8" CHROME PLATED HEAVY BRASS ANGLE SUPPLY STOPS, CHROME PLATED SOFTCOPPER SUPPLY LINES, DRAIN AND OFFSET TAILPIECE, 1-1/4" 17 GAUGE CAST BRASS P-TRAP, SUPPORT CARRIER.

IN COMPLIANCE WITH LATEST ADA STANDARD. PROVIDE 29" MINIMUM CLEARANCE FROM FLOOR TO BOTTOM OF APRONIN COMPLIANCE WITH LATEST ANSI A117.1 AND ADA STANDARDS. ARMAFLEX WITH TAPE IS NOT ACCEPTABLE IN LIEU OFINSULATION KIT.

LAVATORY -AMERICAN STANDARD (0356.421), KOHLER (K-2007)

INSULATION KIT - TRUEBRO

LAV TRIM -TOTO (TEL105), CHICAGO FAUCET (116.951.AB.1), ZURN (Z6913-GEN-XL)

TAG DESCRIPTION ACCEPTABLE MANUFACTURERS

THE SYMBOLS AND THE MATERIAL LIST ARE FOR THE CONVENIENCE OF THE CONTRACTOR. THE CONTRACTOR SHALL VERIFY QUANTITIES AND FURNISH ALL MATERIALS REQUIRED FOR FULLY OPERATIONAL SYSTEMS, WHETHERSPECIFIED OR NOT.

CATALOG NUMBERS SHALL NOT BE CONSIDERED COMPLETE, BUT ARE GIVEN AS AN AID TO THE CONTRACTOR AND TO INDICATE THE QUALITY REQUIRED. CONTRACTOR IS RESPONSIBLE FOR COMPLETE DESCRIPTION OF MATERIALON THESE DRAWINGS AND IN THE SPECIFICATIONS BEFORE ORDERING. THE DESCRIPTION OF MATERIAL TAKES PRECEDENCE OVER THE CATALOG NUMBER. THE FIRST MANUFACTURER LISTED IS THE BASIS OF DESIGN.

CONTRACTOR SHALL VERIFY THAT FIXTURES SUPPLIED ARE APPROVED PER ALL APPLICABLE STATE, LOCAL AND GOVERNING AUTHORITIES.

ALL FIXTURES SHALL CONFORM TO FEDERAL ACT S.3874

PLUMBING MATERIAL LIST

100% CD's Dec. 04, 2018

For Bids Dec. 11, 2018

Page 24: DETROIT, MI 48202...above a potential ignition source 3.abhr must be offset a minimum of 1" horizontally from any light switch, electrical or data receptacle, thermostat or other potential

1. ##-### INDICATES ELECTRICAL EQUIPMENT DEFINED IN ELECTRICAL SCHEDULES OR SPECIFICATION. REFER TO DRAWINGS CONTAINING ELECTRICAL SCHEDULES. PERMANENT NAMEPLATE SHALL MATCH FINAL EQUIPMENT NOMENCLATURE, NOT ELECTRICAL EQUIPMENT TAG NAME, REFER TO SPECIFICATIONS.

2. {L###} INDICATES THE LIGHTING SEQUENCE OF OPERATION FOR THE SPACE. REFER TO THE

LIGHTING SEQUENCE OF OPERATION MATRIX ON SHEET E-000.

LUMINAIRE KEY:

DEVICE KEY:

ELECTRICAL MOUNTING SUBSCRIPT KEY:A MOUNT AT +6" TO CENTERLINE ABOVE COUNTER OR BACKSPLASHC MOUNT AT CEILING

ELECTRICAL GENERAL NOTES:

LUMINAIRE

F1 = FIXTURE TAG1 = CIRCUIT NUMBERa = SWITCH DESIGNATION

*IF LABEL IS ORIENTED HORIZONTALLY A SLASH WILL SEPARATE THIS INFORMATION. EX: F1 / 1 / a / SE

DEVICEA = MOUNTING (IF APPLICABLE)1 = CIRCUIT NUMBER

*IF LABEL IS ORIENTED HORIZONTALLY A SLASH WILL SEPARATE THIS INFORMATION. EX: A / 1

1. CIRCUIT NUMBERS ARE SHOWN FOR CIRCUIT IDENTIFICATION. CIRCUITING SHALL AGREE WITH NUMBERING ON THE PANEL PROVIDED. COMMON NEUTRALS MAY NOT BE USED FOR BRANCH CIRCUITS. BALANCE THE LOAD ON PANEL AS EVENLY AS POSSIBLE BETWEEN EACH PHASE.

2. CIRCUITS SERVING EMERGENCY LUMINAIRES WILL BE RUN IN A SEPARATE RACEWAY FROM ALL OTHER CIRCUITS.

3. ALL MATERIALS USED TO SEAL PENETRATIONS OF FIRE RATED WALLS AND FLOORS SHALL BE TESTED AND CERTIFIED AS A SYSTEM PER ASTM E814 STANDARDS FOR FIRE TESTS OF THROUGH-PENETRATION FIRESTOPS. REFER TO 26 05 03 FOR ADDITIONAL INFORMATION AND REQUIREMENTS SPECIFIC TO FIRESTOPPING.

4. CONTRACTOR SHALL COORDINATE THE LOCATION OF ALL CEILING MOUNTED DEVICES AND EQUIPMENT WITH LUMINAIRES, SPRINKLER, AND CEILING DIFFUSERS. CENTER ALL DEVICES IN CEILING TILE PATTERN. SMOKE DETECTORS AND OCCUPANCY/VACANCY SENSORS SHALL BE LOCATED NO CLOSER THAN 3 FEET TO AN AIR SUPPLY DIFFUSER OR RETURN GRILLE.

5. CONTRACTOR SHALL VERIFY ALL FURNITURE AND EQUIPMENT LOCATIONS WITH ARCHITECTURAL PLANS, ELEVATIONS, AND REVIEWED SHOP DRAWINGS. PRIOR TO MAKING THE ACTUAL ELECTRICAL INSTALLATION, THIS CONTRACTOR SHALL ADJUST RECEPTACLES, OUTLETS, OR CONNECTION LOCATIONS TO ACCOMMODATE FURNITURE AND EQUIPMENT.

6. ELECTRICAL EQUIPMENT SHALL BE MOUNTED TO AVOID IMPEDANCE OF, OPERATION OF, AND ACCESS TO ELECTRICAL AND MECHANICAL EQUIPMENT. ALL MOUNTING OF ELECTRICAL EQUIPMENT, ON EQUIPMENT SUPPLIED BY ANOTHER CONTRACTOR, SHALL BE APPROVED IN ADVANCE BY THE OTHER CONTRACTOR.

7. REFER TO ARCHITECTURAL REFLECTED CEILING PLAN AND OTHER ELECTRICAL PLANS FOR EXACT LOCATIONS OF ALL CEILING MOUNTED DEVICES, OTHER THAN SPRINKLERS.

8. MOUNTING HEIGHTS SHALL BE AS FOLLOWS: LIGHTING SWITCHES 4'-0" RECEPTACLES (GENERAL AREAS) 1'-6" RECEPTACLES (UTILITY AREAS) 4'-0" TELECOMMUNICATION OUTLETS 1'-6" WALL PHONE 4'-0" FIRE ALARM STATIONS 4'-0" FIRE ALARM SIGNALS 7'-6" CLOCKS/CLOCK OUTLETS 1’-6” BELOW FIN. CEIL. SAFETY SWITCHES 5'-0" TO TOP

ELECTRICAL INSTALLATION NOTES:

1. EXISTING CONDITIONS ARE SHOWN BASED ON INFORMATION OBTAINED FROM FIELD SURVEYS, EXISTING BUILDING DOCUMENTS, AND STAFF. VERIFY EXISTING CONDITIONS AND REPORT ANY CONFLICTS BEFORE PROCEEDING.

2. NOT ALL EXISTING EQUIPMENT, LUMINAIRES, AND CONDUIT ARE SHOWN. VERIFY EXISTING CONDITIONS AND REPORT ANY CONFLICTS WITH NEW WORK BEFORE STARTING WORK.

3. FIELD VERIFY THE AVAILABLE CLEARANCES FOR CONDUITS BEFORE FABRICATION. RISES AND DROPS MAY BE NECESSARY BECAUSE OF EXISTING FIELD CONDITIONS.

4. EACH CONTRACTOR SHALL FIELD VERIFY ACCESSIBILITY TO THE AREA OF HIS/HER WORK AND SHALL NOTIFY THE ARCHITECT/ENGINEER PRIOR TO BIDDING IF OTHER UTILITIES ARE REQUIRED TO BE REMOVED OR RELOCATED TO ALLOW ACCESS TO HIS/HER AREA OF WORK.

5. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR CUTTING, REMOVAL AND PATCHING OF ROOFS, WALLS, AND FLOORS ASSOCIATED WITH WORK BY ALL CONTRACTORS.

6. CONTRACTORS SHALL NOTIFY THE GC OF AFFECTED AREAS PRIOR TO BIDDING7. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR REMOVAL AND REPLACEMENT OF

CEILINGS, CEILING TILES, AND CEILING GRIDS ASSOCIATED WITH AREAS OF WORK BY ALL CONTRACTORS. NOTIFY THE GENERAL CONTRACTOR OF AFFECTED AREAS PRIOR TO BIDDING.

8. WHERE EXISTING ELECTRICAL SYSTEMS ARE LOCATED IN AREAS THAT CONFLICT WITH NEW EQUIPMENT, PIPING, OR DUCTWORK TO BE INSTALLED, EACH CONTRACTOR SHALL EITHER ARRANGE NEW EQUIPMENT, CONDUIT, OR DUCTWORK IN SUCH A FASHION THAT IT DOES NOT CONFLICT WITH EXISTING SYSTEMS, OR REWORK EXISTING ELECTRICAL SYSTEMS TO ALLOW FOR INSTALLATION OF NEW EQUIPMENT, PIPING, OR DUCTWORK.

ELECTRICAL RENOVATION NOTES:THESE NOTES APPLY TO ALL ELECTRICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED TO, LIGHTING, POWER, AND SYSTEMS.

PLAN OR DETAIL NUMBER

PLAN OR DETAIL NAME

PLAN OR DETAIL SCALE

NAME

1VIEW NAME1/8" = 1'-0"

LEVEL NAME

10' - 0" HEIGHT ABOVE PROJECT 0' - 0"

1 INDICATES NOTE USED TO DESCRIBE ADDITIONAL INFORMATION ABOUT WORK REQUIRED, SPECIFIC TO THE SHEET AND/OR DETAIL

NO R

HT

INDICATES DIRECTION OF TRUE NORTH

VIEW KEY

NEW WORK BY THIS CONTRACTOR (DARK SOLID LINE)

NEW WORK BY OTHERS AND/OR EXISTING TO REMAIN (LIGHT SOLID LINE)

EXISTING TO BE REMOVED BY THIS CONTRACTOR(DARK SHORT DASHED LINE)

LINE TYPE KEY:

ELECTRICAL EQUIPMENT TAGS

TAG: DESCRIPTION:RELATED

SPECIFICATION

SW-1P SWITCH - SINGLE POLE

F# TROFFER

F# DOWNLIGHT LUMINAIRE

ECONN ELECTRICAL CONNECTIONE

E

PANEL '###' PANELBOARD - SURFACE MOUNT

REC-DUP 26 27 26 DUPLEX RECEPTACLE, 125V

ELECTRICAL SYMBOL LIST

SYMBOL: TAG:SPEC

SECTION:DESCRIPTION:

F# LINEAR LUMINAIRES

SW-3W SWITCH - THREE WAY3

26 27 26FB-# FLOOR BOX

REC-QUAD 26 27 26 QUAD RECEPTACLE, 125V

X# SINGLE FACE EXIT SIGN

X# DOUBLE FACE EXIT SIGN

XM# EMERGENCY UNIT

F# WALL BRACKET LUMINAIRE

SW-O SWITCH - OCCUPANCY SENSOR WALL SWITCHO 26 09 33

PP PUSH PADPP

DP-# DISTRIBUTION PANEL

FA-200 28 31 00 FIRE ALARM VISUAL NOTIFICATION DEVICE - WALL MOUNTED

V1 V3

V7 VH

FA-211 28 31 00 FIRE ALARM AUDIO/VISUAL NOTIFICATION DEVICE - WALL MOUNTED

A1 A3

A7 AH

AS

FA-201 28 31 00 FIRE ALARM VISUAL NOTIFICATION DEVICE - CEILING MOUNTED

V1 V3

V7 VH

FA-231 28 31 00 FIRE ALARM AUDIO/VISUAL NOTIFICATION DEVICE - CEILING MOUNTED

A1 A3

A7 AH

FA-230 28 31 00 FIRE ALARM AUDIO NOTIFICATION DEVICE - CEILING MOUNTED

A

SD FA-120 28 31 00 FIRE ALARM SMOKE DETECTOR - CEILING MOUNTED

FA-130 28 31 00 FIRE ALARM MANUAL PULL STATIONF

VS

VS

AS

REC-DUP-GFI 26 27 26 DUPLEX GFI RECEPTACLE, 125V

FB-1 26 27 26 FLOOR BOX - DUPLEX RECEPTACLE

F# WALL SCONCE LUMINAIRE

FAP-# FIRE ALARM - CONTROL PANEL 28 31 00

26 27 26

BRANCH CIRCUIT WIRING KEY

WIRE ID 2 WIRE 3 WIRE 4 WIRE

THHW/THWN COPPERCONDUCTORS

EQUIPMENTGROUNDINGCONDUCTOR CONDUIT

A# 2#12 3#12 4#12 1#12 3/4"

B# 2#10 3#10 4#10 1#10 3/4"

C# 2#8 3#8 4#8 1#10 3/4"

D# 2#6 3#6 4#6 1#10 1"

E# 2#4 3#4 4#4 1#8 1 1/4"

G# 2#2 3#2 4#2 1#8 1 1/4"

H# 2#1 3#1 4#1 1#6 1 1/2"

J# 2#1/0 3#1/0 4#1/0 1#6 2"

ALL BRANCH CIRCUITS SHALL INCLUDE THE EQUIPMENT GROUND CONDUCTOR

F# 2#3 3#3 4#3 1#8 1 1/4"

ELECTRICAL SHEET INDEXE-000 ELECTRICAL COVERSHEET

ED-101 FIRST FLOOR DEMOLITION - ELECTRICAL

ED-102 SECOND FLOOR DEMOLITION - ELECTRICAL

EL-101 FIRST FLOOR PLAN - LIGHTING

EL-102 SECOND FLOOR PLAN - LIGHTING

EP-100 BASEMENT FLOOR PLAN - POWER

EP-101 FIRST FLOOR PLAN - POWER

EP-102 SECOND FLOOR PLAN - POWER

EP-300 POWER DETAILS

ES-100 BASEMENT FLOOR PLAN - SYSTEMS

ES-101 FIRST FLOOR PLAN - SYSTEMS

ES-102 SECOND FLOOR PLAN - SYSTEMS

ES-300 SYSTEMS DETAILS

AREA OF WORKNO SCALE

FLOOR LEVEL

project number:

sheet title:

sheet number:

approved

project:

coordination checked

location

drawn

checked

designed

issue: date:

key plan:

WAYNE STATE

UNIVERSITYFacilities Planning and Management

5454 Cass Avenue

Detroit, MI 48202

FO

R B

IDS

consultants:

NM Project Number - 18113.0

Rands Building

IMEG Project Number -

Rands House - Rackham

Relocation

WSU : 00

- -

12/1

0/2

018 1

1:1

5:3

7A

M

E-000

ELECTRICAL COVERSHEET

JEFGLAMIKMIN

MARABR

18004050.01

MIKMIN

JEFGLA

WS

U R

an

ds B

ldg

Rackh

am

Relo

cati

on

18004050.0

1

REFERENCE SCALE IN INCHES

0 1 2 3

PROJECT #

IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

18004050.01

[Key*:] SEE BRANCH CIRCUIT WIRING KEY.

Total Amps: 14.33 26.64 34.97

Total Load: 1.72 kVA 3 kVA 4 kVA

41 2 0 -- -- -- SPACE 42 --

39NEW E-CONNECT. FPB-2.3 30 A 2 B2

2 0 1 20 A ELEC. WATER COOLER 40

37 1 0 1 20 A WOMENS HAND DRYER 38

35NEW E-CONNECT. FPB-2.2 20 A 2 A2

1 0 1 20 A MENS HAND DRYER 36

33 OUTLETS OFFICES CONF. 215 20 A 1 0 0 1 20 A 240 COPY MACH. 34

31 OUTLET RM 219 20 A 1 0 0 1 20 A CORRIDOR OUTLETS 32

29 OUTLETS OFFICES 220-221 20 A 1 0 0 1 20 A OUTLETS OFFICES 201-202 30

27 BATHROOM OUTLETS 20 A 1 0 0 1 20 A OUTLETS OFFICES 204-215 COR... 28

25 OUTLETS OFFICES 212-214 20 A 1 0 0 1 20 A OUTLETS OFFICES 202-203 26

23 OUTLETS OFFICES 211-212 20 A 1 0 0 1 20 A OUTLETS OFFICES 206-211 24

21 OUTLETS OFFICES 210-211 20 A 1 0 0 1 20 A OUTLETS OFFICES... 22

19 COFFEE MAKER 226 20 A 1 0 0 -- -- -- SPACE 20 --

17 MICROWAVE 226 20 A 1 0 1 18

-- 15 SPACE -- -- -- 0 1A2 2 20 A NEW E-CONNECT. FPB-2.1

16

13 NEW RECEPTACLES 20 A 1 A2 0.72 0 1 20 A UNKNOWN LOAD 14

11 EXHAUST FAN #2 20 A 1 0 0 1 20 A RECEPT. 229 12

9 LIGHTING CONF. 215 20 A 1 0 0 1 20 A SANYO RM 227 A/C 10

7 LIGHTING OFFICES 201-203 & 221 20 A 1 0 0 1 20 A LIGHTING OFFICES 204 8

5 LIGHTING OFFICES 212-214 20 A 1 0 0 1 20 A STAIRWELL LIGHTING 6

3 LIGHTING GENERAL OFFICE 211 20 A 1 0 0 1 20 A LIGHTING OFFICES 219-220 4

1 LIGHTING OFFICES 206-210 20 A 1 0 0 1 20 A CORRIDOR LIGHTING 222 2

CKTNO. LOAD DESCRIPTION

OVERCURRENTPROTECTIONAMPS P

WIREID

A B CWIRE

ID

OVERCURRENTPROTECTIONP AMPS LOAD DESCRIPTION

CKTNO.

Panel Notes: EXISTING PANEL. PROVIDE NEW BREAKER IN AVAILABLE SPACE FOR CIRCUIT 13. PROVIDE NEW 2 POLE 20A BREAKERS IN AVAILABLE SPACE FORCIRCUIT 16, 18 AND 35,37. PROVIDE NEW 2 POLE 30A BREAKER IN AVAILABLE SPACE FOR CIRCUIT 39,41.

LOCATION: IT 229 DEMAND: 8.72 kVA

SCCR: EXISTING WIRE: 4

FED FROM: EXISTING SWITCHBOARD GROUND BUS PHASE: 3

MOUNTING: SURFACE SOLID NEUTRAL VOLTS: 120/208 Wye

TYPE: BOLT-ON MAIN: 100 A/MCB

PANEL NAME: LPB CONNECTED 8.7 kVA

[Key*:] SEE BRANCH CIRCUIT WIRING KEY.

Total Amps: 29.32 27.76 1.56

Total Load: 3.1 kVA 2.91 kVA 0.19 kVA

-- 17 SPACE -- -- -- 0 0 -- -- -- SPACE 18 --

-- 15 SPACE -- -- -- 0 0 -- -- -- SPACE 16 --

13 0.19 0 -- -- -- SPACE 14 --

11NEW E-CONNECT. HRV-1 20 A 2 A2

0.19 0 -- -- -- SPACE 12 --

9 SUMP PUMP 20 A 1 0 2.91 10

7 OUTSIDE FRONT WALL PACKS 20 A 1 0 2.91B2 2 40 A NEW E-CONNECT. - AC-01

8

5 FURNACE #4 20 A 1 0 0 1 20 A SUITE 200 RECEPT. 6

3 FURNACE #2 20 A 1 0 0 1 20 A SUITE 200 RECEPT. 4

1 FURNACE #1 20 A 1 0 0 1 20 A SUITE 200 LIGHTS 2

CKTNO. LOAD DESCRIPTION

OVERCURRENTPROTECTIONAMPS P

WIREID

A B CWIRE

ID

OVERCURRENTPROTECTIONP AMPS LOAD DESCRIPTION

CKTNO.

Panel Notes: EXISTING PANEL

LOCATION: BASEMENT DEMAND: 6.2 kVA

SCCR: EXISTING WIRE: 4

FED FROM: GROUND BUS PHASE: 3

MOUNTING: SURFACE SOLID NEUTRAL VOLTS: 120/208 Wye

TYPE: BOLT-ON MAIN: 250 A/MCB

PANEL NAME: LPC2 CONNECTED 6.2 kVA

LIGHTING SEQUENCE OF OPERATIONPLAN ID LIGHTING SWITCHED

{LS1} Sequence: Switched lights are occupancy controlled in this space.ON: The lights are turn on by occupancy sensor.OFF: After the space has been vacant for 15 minutes, the lights will automatically turn off.

Owner Review 60% CD's Nov. 13, 2018

Owner Review 90% CD's Nov. 27, 2018

100% CD's Dec. 04, 2018

For Bids Dec. 11, 2018

REFER TO SPECIFICATION SECTIONS LIGHTING 26 51 00 AND EMERGENCY LIGHTING EQUIPMENT 26 52 00 FOR ADDITIONAL INFORMATION AND REQUIREMENTS.INTERIOR CORRELATED COLOR TEMPERATURE 4100K, COLOR RENDERING INDEX (CRI) AT OR ABOVE 80, UNLESS NOTED OTHERWISE.

CATALOG NUMBER SHALL NOT BE CONSIDERED COMPLETE AND MATERIAL SHALL NOT BE ORDERED BY MANUFACTURER AND CATALOG NUMBER ONLY. THE COMPLETE DESCRIPTION AND THESPECIFICATION SHALL BE COORDINATED WITH THE CATALOG NUMBER TO DETERMINE THE EXACT MATERIAL AND ACCESSORIES TO BE ORDERED. THE FIRST MANUFACTURER LISTED IS THEBASIS OF DESIGN.

VERIFY AND COORDINATE ALL CEILING TYPES WITH LUMINAIRE MOUNTING AND TRIM REQUIREMENTS PRIOR TO THE RELEASE OF THE LUMINAIRE ORDER.CONFIRM ALL COLORS AND FINISHES OF ALL LUMINAIRE COMPONENTS WITH ARCHITECT AND INTERIOR DESIGNER PRIOR TO THE RELEASE OF THE LUMINAIRE ORDER.UNLESS INDICATED ON LIGHTING PLANS OR BELOW, REFER TO ARCHITECTURAL AND INTERIOR DESIGN ELEVATIONS, SECTIONS AND DETAILS FOR ALL SUSPENDED AND WALL MOUNTEDLUMINAIRE MOUNTING HEIGHTS.

EM - EMERGENCY BATTERY

(TYPE) BALLAST/DRIVER:

(WATT) PER: FIX - FIXTURE, FT - FOOT, LAMP

LED - LIGHT EMITTING DIODE WL - WALL

(TYPE) LIGHT SOURCE TECHNOLOGY: (MTG) MOUNTING:

CFSA - COLOR-FINISH SELECTION BY ARCHITECT O - OTHER (SEE DESCRIPTION)

FINISH: (L/L) LENS/LOUVER:

LUMINAIRE SCHEDULE

ITEM DESCRIPTION L/L MTG

DIMENSIONS WATTLIGHT SOURCETECHNOLOGY BALLAST/DRIVER

APPROVEDMANUFACTURERL W H DIA.

MAXANSI PER TYPE QTY

MODEL/ABSOLUTE

LUMENS (MIN) VOLTS TYPE

EM1 EMERGENCY UNIT, TWO ADJUSTABLE LEDHEADS, WHITE THERMOPLASTIC HOUSING.SELF TEST & DIAGNOSTICS OF INVERTERAND LAMPS

O WL 11" 3 1/2" 7 1/2" 3 W FIX LED 2 6 VOLT (2INCLUDED)

120 V EM DUAL-LITE EVHCLITHONIA ELML4

Page 25: DETROIT, MI 48202...above a potential ignition source 3.abhr must be offset a minimum of 1" horizontally from any light switch, electrical or data receptacle, thermostat or other potential

A1

F

F

SD

A1

F

A1 F

PP

SD

J

J

J

J J

J

J

J

J

A1

1 2 3 41.9 2.5 3.1 3.2 3.5 3.8

A

b

c

d

e

f

a10

a9

b4

c.1

c.2

c.3

c.4

e.8

+42

+42

TELEPHONE T

+42

+42

A

EXISTING LPA

FURNITURE FEED

FURNITURE FEED

FURNITURE FEED FURNITURE FEED

FURNITURE FEED

FURNITURE FEED

FURNITURE FEED

FURNITURE FEED

FACP

A

1

AREA OF WORKNO SCALE

FLOOR LEVEL

project number:

sheet title:

sheet number:

approved

project:

coordination checked

location

drawn

checked

designed

issue: date:

key plan:

WAYNE STATE

UNIVERSITYFacilities Planning and Management

5454 Cass Avenue

Detroit, MI 48202

FO

R B

IDS

consultants:

NM Project Number - 18113.0

Rands Building

IMEG Project Number -

Rands House - Rackham

Relocation

WSU : 00

- -

12/1

0/2

018 1

1:1

5:3

8A

M

ED-101

FIRST FLOOR DEMOLITION -

ELECTRICAL

JEFGLAMIKMIN

MARABR

18004050.01

MIKMIN

JEFGLA

WS

U R

an

ds B

ldg

Rackh

am

Relo

cati

on

18004050.0

1

NO R

HT

1/8" = 1'-0"1 FIRST FLOOR DEMOLITION - ELECTRICAL

REFERENCE SCALE IN INCHES

0 1 2 3

PROJECT #

IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

18004050.01

KEYNOTES:

1. REMOVE/REPLACE EXISTING FIRE ALARM PANEL/SYSTEM. RETAIN CIRCUIT FOR NEW FIRE ALARM PANEL.

#

Owner Review 60% CD's Nov. 13, 2018

Owner Review 90% CD's Nov. 27, 2018

100% CD's Dec. 04, 2018

For Bids Dec. 11, 2018

Page 26: DETROIT, MI 48202...above a potential ignition source 3.abhr must be offset a minimum of 1" horizontally from any light switch, electrical or data receptacle, thermostat or other potential

WHITE BOARD

projection

screen

E

J

A1

F V1

SD

V1

F

J

J

J

J

1 2 3 41.9 2.5 3.1 3.2 3.5 3.8

A

b

c

d

e

f

a10

a9

b4

c.1

c.2

c.3

c.4

e.8

EXHAUST FAN CONTROL RELAY

+42

+42

+42

EXISTING PP1

EXISTING LPB

111FURNITURE FEED

FURNITURE FEED FURNITURE FEED

3/a

3/b

3/a3/b

A

FURNITURE FEED

A A

AREA OF WORKNO SCALE

FLOOR LEVEL

project number:

sheet title:

sheet number:

approved

project:

coordination checked

location

drawn

checked

designed

issue: date:

key plan:

WAYNE STATE

UNIVERSITYFacilities Planning and Management

5454 Cass Avenue

Detroit, MI 48202

FO

R B

IDS

consultants:

NM Project Number - 18113.0

Rands Building

IMEG Project Number -

Rands House - Rackham

Relocation

WSU : 00

- -

12/1

0/2

018 1

1:1

5:3

9A

M

ED-102

SECOND FLOOR DEMOLITION -

ELECTRICAL

JEFGLAMIKMIN

MARABR

18004050.01

MIKMIN

JEFGLA

WS

U R

an

ds B

ldg

Rackh

am

Relo

cati

on

18004050.0

1

NO R

HT

1/8" = 1'-0"1 SECOND FLOOR DEMOLITION - ELECTRICAL

REFERENCE SCALE IN INCHES

0 1 2 3

PROJECT #

IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

18004050.01

KEYNOTES:

1. REMOVE EXISTING FIXTURE AND RELOCATED FOR REUSE.

#

Owner Review 60% CD's Nov. 13, 2018

Owner Review 90% CD's Nov. 27, 2018

100% CD's Dec. 04, 2018

For Bids Dec. 11, 2018

Page 27: DETROIT, MI 48202...above a potential ignition source 3.abhr must be offset a minimum of 1" horizontally from any light switch, electrical or data receptacle, thermostat or other potential

111

117

125

129

137 141

143

145

144142138

140136

134

132

130

128

126

122

120

124

118

116

112

108

106

102

100

103107

DN

UP

UP

CL

OFFICE

COVERED AREA

RESEARCHLAB

OFFICE

IT OFFICE

TREATMENT

OFFICE

TREATMENTOFFICEOFFICE

TREATMENTCHILDPLAYROOM

OBSERVATION

TREATMENT

TREATMENT

OFFICE

OFFICE

JC

UNISEXADA

WOMEN

WAITING

WAITING

LOUNGE

OFFICE

PLANTERSTORAGE

STORAGE

OPENOFFICE

VEST

PORCH

OPENOFFICE

CONFERENCE ROOMOFFICE

1 2 3 41.9 2.5 3.1 3.2 3.5 3.8

A

b

c

d

e

f

a10

a9

b4

c.1

c.2

c.3

c.4

e.8

1

O

O

EM1

EM1

EM1

EM1

EM1

2

2

2

2

2

AREA OF WORKNO SCALE

FLOOR LEVEL

project number:

sheet title:

sheet number:

approved

project:

coordination checked

location

drawn

checked

designed

issue: date:

key plan:

WAYNE STATE

UNIVERSITYFacilities Planning and Management

5454 Cass Avenue

Detroit, MI 48202

FO

R B

IDS

consultants:

NM Project Number - 18113.0

Rands Building

IMEG Project Number -

Rands House - Rackham

Relocation

WSU : 00

- -

12/1

0/2

018 1

1:1

5:3

9A

M

EL-101

FIRST FLOOR PLAN - LIGHTING

JEFGLAMIKMIN

MARABR

18004050.01

MIKMIN

JEFGLA

WS

U R

an

ds B

ldg

Rackh

am

Relo

cati

on

18004050.0

1

NO R

HT

1/8" = 1'-0"1 FIRST FLOOR PLAN - LIGHTING

REFERENCE SCALE IN INCHES

0 1 2 3

PROJECT #

IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

18004050.01

SHEET NOTES :

1. CLEAN AND RELAMP ALL FIXTURES. SURFACE 2X4 ARE 3-LAMP, SURFACE 1X4 ARE 2-LAMP, AND DOWNLIGHTS, WALL SCONCES, AND DECORATIVE FIXTURES ARE COMPACT FLUORESCENT.

2. REPLACE LAMPS AND BATTERIES IN EXISTING EXIT SIGNS AND EMERGENCY BATTERY UNITS.

KEYNOTES:

1. REPLACE BALLASTS WITH REDUCED WATTAGE BALLASTS.

2. EXTEND UNSWITCHED PORTION OF BRANCH CIRCUIT SERVING THIS ROOM TO EMERGENCY FIXTURE.

#

Owner Review 60% CD's Nov. 13, 2018

Owner Review 90% CD's Nov. 27, 2018

100% CD's Dec. 04, 2018

For Bids Dec. 11, 2018

Page 28: DETROIT, MI 48202...above a potential ignition source 3.abhr must be offset a minimum of 1" horizontally from any light switch, electrical or data receptacle, thermostat or other potential

WHITE BOARD

projection

screen

244

240

245

229

227

225

219

217

243242241

246

247

238236

230

226

224

220

218

214212

202

200.1

200

201

203205

234

232

207

OFFICE

OPENOFFICE

OPENOFFICE

IT

MECH

TREATMENT

OBSERVATION

TREATMENT

COMFERENCE/GROUP ROOMOBSERVATIONTREATMENT

TREATMENT

OBSERVATION

TREATMENTTREATMENT

ADULTGROUP ROOM

ADULTGROUP ROOM

WOMEN

UNISEX ADA

CHILDREN'SGROUP ROOM

OFFICETREATMENT

DN

UP

OPENOFFICE

STORAGE

DN

OPENOFFICE

OPENOFFICE

OFFICEOFFICE

OBSERVATION

TREATMENT

OPEN

UP

OFFICE

{LS1}{LS1}{LS1}

1 2 3 41.9 2.5 3.1 3.2 3.5 3.8

A

b

c

d

e

f

a10

a9

b4

c.1

c.2

c.3

c.4

e.8

O O

3/a

3/b

3/b 3/a

1 11

EM1EM1

EM1EM1

EM1

EM1

22

2

2

2

2

AREA OF WORKNO SCALE

FLOOR LEVEL

project number:

sheet title:

sheet number:

approved

project:

coordination checked

location

drawn

checked

designed

issue: date:

key plan:

WAYNE STATE

UNIVERSITYFacilities Planning and Management

5454 Cass Avenue

Detroit, MI 48202

FO

R B

IDS

consultants:

NM Project Number - 18113.0

Rands Building

IMEG Project Number -

Rands House - Rackham

Relocation

WSU : 00

- -

12/1

0/2

018 1

1:1

5:4

0A

M

EL-102

SECOND FLOOR PLAN -

LIGHTING

JEFGLAMIKMIN

MARABR

18004050.01

MIKMIN

JEFGLA

WS

U R

an

ds B

ldg

Rackh

am

Relo

cati

on

18004050.0

1

NO R

HT

1/8" = 1'-0"1 SECOND FLOOR PLAN - LIGHTING

REFERENCE SCALE IN INCHES

0 1 2 3

PROJECT #

IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

18004050.01

KEYNOTES:

1. RELOCATED FIXTURE. EXTEND BRANCH CIRCUIT FROM EXISTING LIGHTING.

2. EXTEND UNSWITCHED PORTION OF BRANCH CIRCUIT SERVING THIS ROOM TO EMERGENCY FIXTURE.

#

SHEET NOTES :

1. CLEAN AND RELAMP ALL FIXTURES. SURFACE 2X4 ARE 3-LAMP, SURFACE 1X4 ARE 2-LAMP, AND DOWNLIGHTS, WALL SCONCES, AND DECORATIVE FIXTURES ARE COMPACT FLUORESCENT.

2. REPLACE LAMPS AND BATTERIES IN EXISTING EXIT SIGNS AND EMERGENCY BATTERY UNITS.

Owner Review 60% CD's Nov. 13, 2018

Owner Review 90% CD's Nov. 27, 2018

100% CD's Dec. 04, 2018

For Bids Dec. 11, 2018

Page 29: DETROIT, MI 48202...above a potential ignition source 3.abhr must be offset a minimum of 1" horizontally from any light switch, electrical or data receptacle, thermostat or other potential

HOUSE

43.8

d

e

f

c.3

c.4

e.8

EXISTING DP-1

EXISTING LPC

EXISTING LPC2

AREA OF WORKNO SCALE

FLOOR LEVEL

project number:

sheet title:

sheet number:

approved

project:

coordination checked

location

drawn

checked

designed

issue: date:

key plan:

WAYNE STATE

UNIVERSITYFacilities Planning and Management

5454 Cass Avenue

Detroit, MI 48202

FO

R B

IDS

consultants:

NM Project Number - 18113.0

Rands Building

IMEG Project Number -

Rands House - Rackham

Relocation

WSU : 00

- -

12/1

0/2

018 1

1:1

5:4

0A

M

EP-100

BASEMENT FLOOR PLAN -

POWER

JEFGLAMIKMIN

MARABR

18004050.01

MIKMIN

JEFGLA

WS

U R

an

ds B

ldg

Rackh

am

Relo

cati

on

18004050.0

1

REFERENCE SCALE IN INCHES

0 1 2 3

PROJECT #

IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

18004050.01

NO R

HT

1/8" = 1'-0"1 BASEMENT FLOOR PLAN - POWER

100% CD's Dec. 04, 2018

For Bids Dec. 11, 2018

Page 30: DETROIT, MI 48202...above a potential ignition source 3.abhr must be offset a minimum of 1" horizontally from any light switch, electrical or data receptacle, thermostat or other potential

111

117

125

129

137 141

143

145

144142138

140136

134

132

130

128

126

122

120

124

118

116

112

108

106

102

100

103107

DN

UP

UP

CL

OFFICE

COVERED AREA

RESEARCHLAB

OFFICE

IT OFFICE

TREATMENT

OFFICE

TREATMENTOFFICEOFFICE

TREATMENTCHILDPLAYROOM

OBSERVATION

TREATMENT

TREATMENT

OFFICE

OFFICE

JC

UNISEXADA

WOMEN

WAITING

WAITING

LOUNGE

OFFICE

PLANTERSTORAGE

STORAGE

OPENOFFICE

VEST

PORCH

OPENOFFICE

CONFERENCE ROOMOFFICE

copier

PP

E

1 2 3 41.9 2.5 3.1 3.2 3.5 3.8

A

b

c

d

e

f

a10

a9

b4

c.1

c.2

c.3

c.4

e.8

+42

+42

+60

EXISTING LPA

A

1

1

1

1 1

1

1

2

INTERCOM POWER SUPPLY

ELECTRONIC SENSOR

3

AREA OF WORKNO SCALE

FLOOR LEVEL

project number:

sheet title:

sheet number:

approved

project:

coordination checked

location

drawn

checked

designed

issue: date:

key plan:

WAYNE STATE

UNIVERSITYFacilities Planning and Management

5454 Cass Avenue

Detroit, MI 48202

FO

R B

IDS

consultants:

NM Project Number - 18113.0

Rands Building

IMEG Project Number -

Rands House - Rackham

Relocation

WSU : 00

- -

12/1

0/2

018 1

1:1

5:4

1A

M

EP-101

FIRST FLOOR PLAN - POWER

JEFGLAMIKMIN

MARABR

18004050.01

MIKMIN

JEFGLA

WS

U R

an

ds B

ldg

Rackh

am

Relo

cati

on

18004050.0

1

NO R

HT

1/8" = 1'-0"1 FIRST FLOOR PLAN - POWER

REFERENCE SCALE IN INCHES

0 1 2 3

PROJECT #

IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

18004050.01

KEYNOTES:

1. EXTEND EXISTING BRANCH CIRCUIT IN ROOM TO NEW DEVICE.

2. CIRCUIT RECEPTACLE TO SPARE 20A BREAKER IN PANEL LPA.

3. EXTEND BRANCH CIRCUIT FROM THE RECEPTACLE. REFER TO THE 'ELECTRONIC SENSOR WIRING' DETAIL ON SHEET EP-300.

#

Owner Review 60% CD's Nov. 13, 2018

Owner Review 90% CD's Nov. 27, 2018

100% CD's Dec. 04, 2018

For Bids Dec. 11, 2018

Page 31: DETROIT, MI 48202...above a potential ignition source 3.abhr must be offset a minimum of 1" horizontally from any light switch, electrical or data receptacle, thermostat or other potential

WHITE BOARD

projection

screen

244

240

245

229

227

225

219

217

243242241

246

247

238236

230

226

224

220

218

214212

202

200.1

200

201

203205

234

232

207

OFFICE

OPENOFFICE

OPENOFFICE

IT

MECH

TREATMENT

OBSERVATION

TREATMENT

COMFERENCE/GROUP ROOMOBSERVATIONTREATMENT

TREATMENT

OBSERVATION

TREATMENTTREATMENT

ADULTGROUP ROOM

ADULTGROUP ROOM

WOMEN

UNISEX ADA

CHILDREN'SGROUP ROOM

OFFICETREATMENT

DN

UP

OPENOFFICE

STORAGE

DN

OPENOFFICE

OPENOFFICE

OFFICEOFFICE

OBSERVATION

TREATMENT

OPEN

UP

OFFICE

E

E

E

E E

E

J

E

1 2 3 41.9 2.5 3.1 3.2 3.5 3.8

A

b

c

d

e

f

a10

a9

b4

c.1

c.2

c.3

c.4

e.8

+42

+60

FB-1

EXHAUST FAN CONTROL RELAY

AC-01

FPB-2.1 FPB-2.2

FPB-2.3

HRV-1

EXISTING PP1

EXISTING LPB

+42

+42

+42

LPC2-8,10LPC2-11,13

LPB-39,41

LPB-35,37LPB-16,18

1

1

1

1

1LPB-13LPB-13

2

2

A

AA

33

1

INTERCOM POWER SUPPLY

ELECTRONIC SENSOR

1

AREA OF WORKNO SCALE

FLOOR LEVEL

project number:

sheet title:

sheet number:

approved

project:

coordination checked

location

drawn

checked

designed

issue: date:

key plan:

WAYNE STATE

UNIVERSITYFacilities Planning and Management

5454 Cass Avenue

Detroit, MI 48202

FO

R B

IDS

consultants:

NM Project Number - 18113.0

Rands Building

IMEG Project Number -

Rands House - Rackham

Relocation

WSU : 00

- -

12/1

0/2

018 1

1:1

5:4

2A

M

EP-102

SECOND FLOOR PLAN - POWER

JEFGLAMIKMIN

MARABR

18004050.01

MIKMIN

JEFGLA

WS

U R

an

ds B

ldg

Rackh

am

Relo

cati

on

18004050.0

1

NO R

HT

1/8" = 1'-0"1 SECOND FLOOR PLAN - POWER

REFERENCE SCALE IN INCHES

0 1 2 3

PROJECT #

IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

18004050.01

KEYNOTES:

1. EXTEND EXISTING BRANCH CIRCUIT IN ROOM TO NEW DEVICE.

2. PROVIDE SURFACE RACEWAY FOR RECEPTACLE. REFER TO 'SURFACE WIREWAY DETAIL' ON SHEET EP-300.

3. ADD/ALTERNATE4. EXTEND BRANCH CIRCUIT FROM THE

RECEPTACLE. REFER TO THE 'ELECTRONIC SENSOR WIRING' DETAIL ON SHEET EP-300.

#

Owner Review 60% CD's Nov. 13, 2018

Owner Review 90% CD's Nov. 27, 2018

100% CD's Dec. 04, 2018

For Bids Dec. 11, 2018

Page 32: DETROIT, MI 48202...above a potential ignition source 3.abhr must be offset a minimum of 1" horizontally from any light switch, electrical or data receptacle, thermostat or other potential

SEE ARCHITECTURALPLANS FOR WALL CONSTRUCTION

PLASTER RING TO COMEWITHIN 1/8" OF FINAL SURFACE

STUD

MOUNTING BRACKET SHALL PROVIDESUPPORT FROM STUD AND BACK OFWALL OR TWO STUDS.

NOTES :

1. THE INTENT OF THE DETAIL IS TO ENSURE DEVICE ROUGH-INS ARE ALIGNED, SOLIDLY MOUNTED AND THE SURFACE OF THE TRIM IS EITHER FLUSH WITH THE WALL SURFACE OR WITHIN 1/8" OF THE WALL SURFACE. JUNCTION BOXES LARGER THAN 4" SQUARE SHALL BE MOUNTED IN A MANNER THAT IS SIMILAR TO THE SYSTEM NOTED ABOVE OR ACHIEVES THE SAME RESULTS.

2. PLASTER RINGS DEPTH SHALL BE 1/8" DEEPER THAN THE GYP BOARD APPLIED TO THE WALL. PLASTER RING SHALL BE 3/4" FOR USE WITH 5/8" GYP BOARD.

3. MOUNTING BRACKET FOR 2 1/2" OR 3 1/2" STUDS SHALL BE CADDY #H23, OR B-LINE BB4-23. MOUNTING BRACKET FOR FOR 4" OR 6" STUDS SHALL BE CADDY #H46TC OR B-LINE BB4-# . FOR MULTIPLE BOXES BETWEEN STUDS, BRACKET SHALL BE CADDY #RBS16/#RBS24 OR B-LINE BB6-# OR BBF# FLOOR MOUNT SUPPORT WITH BBFC.

4. WHERE RECEPTACLE AND TECHNOLOGY DEVICES ARE SHOWN SERVING A COMMON COMPUTER OR EQUIPMENT, OR SHOWN IN SIMILAR LOCATIONS ON THE DRAWINGS THE DEVICES SHALL BE INSTALLED ON OPPOSITE SIDES OF A COMMON STUD OR IN ADJACENT OPENINGS WITH MOUNTING BRACKETS.

RATED WALL (CONSTRUCTION VARIES)

NOTE 2

FIRE SEALANT

NOTE 3

FIRE SEALANT

PENETRATING ITEM

NOTE 4

NOTE 3

NOTE 2

PENETRATING ITEM

NOTE 4

NOTE 3

RATED FLOOR (CONSTRUCTION VARIES)

NOTES :

1. THIS GENERAL DETAIL APPLIES TO ALL ITEMS PENETRATING FIRE RATED WALLS OR FLOORS. THE INTENT IS TO MAINTAIN THE FIRE RATING AND TO ALLOW LONGITUDINAL MOVEMENT. REFER TO SPECIFICATION SECTION 07840 (16080) FOR SELECTION OF THROUGH PENETRATION FIRE STOPPING.

2. SCHEDULE 5 PIPE SLEEVE EMBEDDED IN WALL OR FLOOR, OR SMOOTH CORE DRILL. EACH CONTRACTOR FURNISHES SLEEVE TO G.C., COORDINATES SLEEVE LOCATIONS AND DEBURS SLEEVE. G.C. BUILDS SLEEVE INTO WALL OR FLOOR ALLOWING NO GAP AROUND SLEEVE. IF SLEEVE IS NOT PROVIDED WHEN WALL OR FLOOR IS BUILT, CONTRACTOR SHALL INSTALL SLEEVE. SLEEVE SIZE SHALL ALLOW ANNULAR SPACE REQUIRED BY THE SELECTED FIRE STOP SYSTEM.

3. INSTALL BACKING MATERIAL, SUCH AS MINERAL WOOL SAFING, AS REQUIRED FOR FIRE STOP SYSTEM. INSTALL IN ACCORDANCE WITH FIRE STOP SYSTEM APPLICATION LISTING. SECURE TO WALL OR FLOOR TO ALLOW LONGITUDINAL MOVEMENT OF PENETRATING ITEM WITHOUT MOVEMENT OF FIRE BARRIER.

4. WATER-TIGHT WELDED 1"x1" 20 GAUGE MINIMUM GALVANIZED SHEET METAL ANGLE FRAME, BY CONTRACTOR IN EQUIPMENT ROOMS FOR WATER STOP. PLACE A BEAD OF WATERPROOF SEALANT BETWEEN FLOOR AND BOTTOM OF ANGLE FRAME. SECURE TO FLOOR WITH MASONRY ANCHORS IN CORNERS AND ON 12" MAXIMUM CENTERS. MULTIPLE PENETRATING ITEMS MAY BE ENCLOSED IN ONE FRAME.

DUPLEX RECEPTACLE(DESIGNATED ON PLANS)

1 1/4" TELECOMM CONDUIT(S) AS REQUIRED

BRANCH CIRCUIT CONDUIT(S)

SURFACE RACEWAY TOABOVE ACCESSIBLE CEILING

WW-#4 3/4" HIGH X 1 3/4" DEEP SURFACEMETAL RACEWAY WITH LOW VOLTAGE DIVIDER.LENGTH AS SHOWN ON DRAWINGS.

TR

CLASS II LOW VOLTAGE TRANSFORMER, WITH PRIMARY AND SECONDARY FUSING. MOUNT IN NEMA 1 ENCLOSURE ABOVE ACCESSIBLE CEILING.

H

GND

2#14 & 1#14 GND IN 1/2" FLEXFOR LOW VOLTAGE CLASS IIWIRING TO CONTROL MODULES.

MOUNTED ONWALL, BEHINDWATER CLOSET.

MAXIMUM OF SIX MODULESPER TRANSFORMER. MAXIMUM 50' WIRING LENGTH.

LOW VOLTAGESOLENOID VALVE.

WATER CLOSET LOWVOLTAGE SENSOR /CONTROL

N

NOTES :

1. PROVIDE DOUBLE GANG BACKBOXES AND PLASTER RINGS AT LOCATIONS COORDINATED WITH PLUMBING CONTRACTOR (P.C.)

2. E.C. SHALL FIELD VERIFY EXACT SENSOR LOCATION WITH P.C. PRIOR TO ROUGH-IN.

AREA OF WORKNO SCALE

FLOOR LEVEL

project number:

sheet title:

sheet number:

approved

project:

coordination checked

location

drawn

checked

designed

issue: date:

key plan:

WAYNE STATE

UNIVERSITYFacilities Planning and Management

5454 Cass Avenue

Detroit, MI 48202

FO

R B

IDS

consultants:

NM Project Number - 18113.0

Rands Building

IMEG Project Number -

Rands House - Rackham

Relocation

WSU : 00

- -

12/1

0/2

018 1

1:1

5:4

3A

M

EP-300

POWER DETAILS

JEFGLAMIKMIN

MARABR

18004050.01

MIKMIN

JEFGLA

WS

U R

an

ds B

ldg

Rackh

am

Relo

cati

on

18004050.0

1

REFERENCE SCALE IN INCHES

0 1 2 3

PROJECT #

IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

18004050.01

NO SCALE1 BACKBOX MOUNTING DETAIL

NO SCALE3 FIRE BARRIER PENETRATION

NO SCALE2 SURFACE WIREWAY DETAIL

Owner Review 60% CD's Nov. 13, 2018

Owner Review 90% CD's Nov. 27, 2018

100% CD's Dec. 04, 2018

For Bids Dec. 11, 2018

NO SCALE4 ELECTRONIC SENSOR WIRING

Page 33: DETROIT, MI 48202...above a potential ignition source 3.abhr must be offset a minimum of 1" horizontally from any light switch, electrical or data receptacle, thermostat or other potential

HOUSE

A7

V1

A1

43.8

d

e

f

c.3

c.4

e.8

AREA OF WORKNO SCALE

FLOOR LEVEL

project number:

sheet title:

sheet number:

approved

project:

coordination checked

location

drawn

checked

designed

issue: date:

key plan:

WAYNE STATE

UNIVERSITYFacilities Planning and Management

5454 Cass Avenue

Detroit, MI 48202

FO

R B

IDS

consultants:

NM Project Number - 18113.0

Rands Building

IMEG Project Number -

Rands House - Rackham

Relocation

WSU : 00

- -

12/1

0/2

018 1

1:1

5:4

3A

M

ES-100

BASEMENT FLOOR PLAN -

SYSTEMS

JEFGLAMIKMIN

MARABR

18004050.01

MIKMIN

JEFGLA

WS

U R

an

ds B

ldg

Rackh

am

Relo

cati

on

18004050.0

1

REFERENCE SCALE IN INCHES

0 1 2 3

PROJECT #

IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

18004050.01

For Bids Dec. 11, 2018

NO R

HT

1/8" = 1'-0"1 BASEMENT FLOOR PLAN - SYSTEMS

Page 34: DETROIT, MI 48202...above a potential ignition source 3.abhr must be offset a minimum of 1" horizontally from any light switch, electrical or data receptacle, thermostat or other potential

111

117

125

129

137 141

143

145

144142138

140136

134

132

130

128

126

122

120

124

118

116

112

108

106

102

100

103107

DN

UP

UP

CL

OFFICE

COVERED AREA

RESEARCHLAB

OFFICE

IT OFFICE

TREATMENT

OFFICE

TREATMENTOFFICEOFFICE

TREATMENTCHILDPLAYROOM

OBSERVATION

TREATMENT

TREATMENT

OFFICE

OFFICE

JC

UNISEXADA

WOMEN

WAITING

WAITING

LOUNGE

OFFICE

PLANTERSTORAGE

STORAGE

OPENOFFICE

VEST

PORCH

OPENOFFICE

CONFERENCE ROOMOFFICE

copier

F

F

F

F

SD

SD

A1A1

A1

SD

A3

A

A1

A7

A1

V1

V1

A3

A1

V7

A7

A1

A1

A7

AR

F

1 2 3 41.9 2.5 3.1 3.2 3.5 3.8

A

b

c

d

e

f

a10

a9

b4

c.1

c.2

c.3

c.4

e.8

FAP-1

1

ELEVATOR RECALL INMACHINE ROOM

AREA OF WORKNO SCALE

FLOOR LEVEL

project number:

sheet title:

sheet number:

approved

project:

coordination checked

location

drawn

checked

designed

issue: date:

key plan:

WAYNE STATE

UNIVERSITYFacilities Planning and Management

5454 Cass Avenue

Detroit, MI 48202

FO

R B

IDS

consultants:

NM Project Number - 18113.0

Rands Building

IMEG Project Number -

Rands House - Rackham

Relocation

WSU : 00

- -

12/1

0/2

018 1

1:1

5:4

3A

M

ES-101

FIRST FLOOR PLAN - SYSTEMS

JEFGLAMIKMIN

MARABR

18004050.01

MIKMIN

JEFGLA

WS

U R

an

ds B

ldg

Rackh

am

Relo

cati

on

18004050.0

1

NO R

HT

1/8" = 1'-0"1 FIRST FLOOR PLAN - SYSTEMS

REFERENCE SCALE IN INCHES

0 1 2 3

PROJECT #

IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

18004050.01

KEYNOTES:

1. CIRCUIT NEW F.A. PANEL TO EXISTING CIRCUIT RETAINED DURING DEMOLITION.

#

100% CD's Dec. 04, 2018

For Bids Dec. 11, 2018

Page 35: DETROIT, MI 48202...above a potential ignition source 3.abhr must be offset a minimum of 1" horizontally from any light switch, electrical or data receptacle, thermostat or other potential

WHITE BOARD

projection

screen

244

240

245

229

227

225

219

217

243242241

246

247

238236

230

226

224

220

218

214212

202

200.1

200

201

203205

234

232

207

OFFICE

OPENOFFICE

OPENOFFICE

IT

MECH

TREATMENT

OBSERVATION

TREATMENT

COMFERENCE/GROUP ROOMOBSERVATIONTREATMENT

TREATMENT

OBSERVATION

TREATMENTTREATMENT

ADULTGROUP ROOM

ADULTGROUP ROOM

WOMEN

UNISEX ADA

CHILDREN'SGROUP ROOM

OFFICETREATMENT

DN

UP

OPENOFFICE

STORAGE

DN

OPENOFFICE

OPENOFFICE

OFFICEOFFICE

OBSERVATION

TREATMENT

OPEN

UP

OFFICE

SD

SD

F

F

F

A7

V1

V1

A3

A1

A1

A1

A1

AV1

V1

V1

V1

V1

A3

V1

V1

1 2 3 41.9 2.5 3.1 3.2 3.5 3.8

A

b

c

d

e

f

a10

a9

b4

c.1

c.2

c.3

c.4

e.8

AREA OF WORKNO SCALE

FLOOR LEVEL

project number:

sheet title:

sheet number:

approved

project:

coordination checked

location

drawn

checked

designed

issue: date:

key plan:

WAYNE STATE

UNIVERSITYFacilities Planning and Management

5454 Cass Avenue

Detroit, MI 48202

FO

R B

IDS

consultants:

NM Project Number - 18113.0

Rands Building

IMEG Project Number -

Rands House - Rackham

Relocation

WSU : 00

- -

12/1

0/2

018 1

1:1

5:4

4A

M

ES-102

SECOND FLOOR PLAN -

SYSTEMS

JEFGLAMIKMIN

MARABR

18004050.01

MIKMIN

JEFGLA

WS

U R

an

ds B

ldg

Rackh

am

Relo

cati

on

18004050.0

1

NO R

HT

1/8" = 1'-0"1 SECOND FLOOR PLAN - SYSTEMS

REFERENCE SCALE IN INCHES

0 1 2 3

PROJECT #

IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

18004050.01

100% CD's Dec. 04, 2018

For Bids Dec. 11, 2018

Page 36: DETROIT, MI 48202...above a potential ignition source 3.abhr must be offset a minimum of 1" horizontally from any light switch, electrical or data receptacle, thermostat or other potential

J

NEP

SIGNAL LINE CIRCUIT (SLC)

NOTIFICATION APPLIANCE CIRCUIT (NAC)

EVACUATION - SIGNALING ZONE #

NOTIFICATION APPLIANCE CIRCUIT (NAC)

NEW FAP-1

SIGNAL LINE CIRCUIT(SLC)

CIRCUIT INTEGRITY WIRING. (TYPICAL)

AR TO ELEVATOR SHUNT TRIP BREAKER

FT H SD

2 31

SD MM MM

V

A

F

2

J

V1 V1 V11

3

A A MH HW

A1 A11 A11

KEYNOTES:

PROVIDE NOTIFICATION APPLIANCE EXTENDER PANELS AS REQUIRED. DETERMINATION OF NEED TO BE MADE BY FIRE ALARM VENDOR. REFER TO SPECIFICATIONS FOR REQUIREMENTS AND ACCEPTABLE MOUNTING LOCATIONS.

REFER TO SPECIFICATION FOR REQUIREMENTS OF EACH INITIATION LOOP AND WIRING STYLE. REFER TO FLOOR PLANS FOR DEVICES AND THEIR LOCATIONS.

REFER TO SPECIFICATION FOR REQUIREMENTS OF EACH NOTIFICATION APPLIANCE CIRCUIT AND WIRING STYLE. REFER TO FLOOR PLANS FOR DEVICES AND THEIR LOCATIONS.

1

2

3

NOTES :

1. THE RISER DIAGRAM IS INTENDED TO CONVEY THE TYPES OF FIRE ALARM CONNECTIONS AND SPECIFICALLY DOES NOT INDICATE QUANTITIES, NUMBER OF CIRCUITS REQUIRED OR DISTANCES.

2. THE COMPLETE FIRE ALARM SYSTEM SHALL MEET ALL APPLICABLE CODES AND MANUFACTURER'S RECOMMENDATIONS.

3. CONTRACTOR SHALL COORDINATE ALL WIRE SIZES, TYPES AND REQUIREMENTS WITH THE VENDOR PRIOR TO BID. REFER TO SPECIFICATIONS TO DETERMINE CIRCUIT STYLES AND IF CONDUIT IS REQUIRED OR PLENUM RATED CABLE IS ACCEPTABLE.

4. ALL +120VAC WIRING REQUIRED FOR OPERATION OF THE SYSTEM AS DESCRIBED IN THE CONSTRUCTION DOCUMENTS SHALL BE PROVIDED BY THE ELECTRICAL CONTRACTOR.

5. ALL NECESSARY RELAYS MAY NOT BE SHOWN ON THIS PLAN, BUT WHERE REQUIRED FOR PROPER OPERATION OF THE SYSTEM THEY SHALL BE PROVIDED BY THE CONTRACTOR.

AREA OF WORKNO SCALE

FLOOR LEVEL

project number:

sheet title:

sheet number:

approved

project:

coordination checked

location

drawn

checked

designed

issue: date:

key plan:

WAYNE STATE

UNIVERSITYFacilities Planning and Management

5454 Cass Avenue

Detroit, MI 48202

FO

R B

IDS

consultants:

NM Project Number - 18113.0

Rands Building

IMEG Project Number -

Rands House - Rackham

Relocation

WSU : 00

- -

12/1

0/2

018 1

1:1

5:4

4A

M

ES-300

SYSTEMS DETAILS

JEFGLAMIKMIN

MARABR

18004050.01

MIKMIN

JEFGLA

WS

U R

an

ds B

ldg

Rackh

am

Relo

cati

on

18004050.0

1

REFERENCE SCALE IN INCHES

0 1 2 3

PROJECT #

IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

18004050.01

NO SCALE1 FIRE ALARM RISER

100% CD's Dec. 04, 2018

For Bids Dec. 11, 2018

Page 37: DETROIT, MI 48202...above a potential ignition source 3.abhr must be offset a minimum of 1" horizontally from any light switch, electrical or data receptacle, thermostat or other potential

TECHNOLOGY SYMBOL LIST

SYMBOL: DESCRIPTION: NOTE:EQUIPMENT

LIST ABBREV.:

CAM .AV CEILING CAMERAAV-CAM-1

C#1.INFORMATION OUTLET (WALL)SC-IO-W

.POKE THROUGH FOR FURNITURE FEEDN/A

IS1

IM1 .INTERCOM MASTER STATION - TYPE 1 (WALL)IC-IM1-W

.INTERCOM STATION - TYPE 1 (WALL)IC-IS1-W

JB1 .TECHNOLOGY JUNCTION BOX - WALL - TYPE 1AV-JB1-W#

CR1 .CREDENTIAL READER - TYPE 1 - ROUGH INAC-CR1-W

TECHNOLOGY ABBREVIATION KEY

ENTRANCE FACILITYEF-#

MAIN CROSS-CONNECTMC-#

TELECOMMUNICATIONS ROOMTR-#

ABOVE FINISHED FLOORAFF

BELOW FINISHED CEILINGBFC

CONDUITC

SIMILARSIM

TYPICALTYP

MOUNTING HEIGHT ABOVE FINISHED FLOOR+#

JUNCTION BOXJ-BOX

ABBR: DESCRIPTION:

UNLESS NOTED OTHERWISEUNO

TECHNOLOGY GENERAL NOTES:1. ###-### INDICATES GENERAL TECHNOLOGY EQUIPMENT SCHEDULE ITEM LABELED AS

"EQUIPMENT LIST ABBREVIATION"2. REFER TO GENERAL TECHNOLOGY EQUIPMENT SCHEDULE AND SPECIFICATIONS FOR FULL

DESCRIPTIONS AND MANUFACTURERS OF ALL DEVICES.

TECHNOLOGY MOUNTING SUBSCRIPT KEY:A MOUNT AT +6" TO CENTERLINE ABOVE COUNTER OR BACKSPLASHH MOUNT ORIENTED HORIZONTALLYL MOUNT IN CASEWORKM MOUNT IN MODULAR FURNITURES MOUNT IN SURFACE RACEWAY

A SLASH IS USED BETWEEN TWO SUBSCRIPTS, E.G., A/H.

1. THE COMPLETE INSTALLATION SHALL BE IN ACCORDANCE WITH THE ADA STANDARDS FOR ACCESSIBLE DESIGN. REFER TO THE ADA GUIDELINES FOR ALL CONFIGURATION DETAILS ON THIS PAGE FOR ADDITIONAL INFORMATION.

2. CONCEAL ALL CONDUIT IN WALLS, PARTITIONS, ABOVE CEILING, IN FLOOR SLAB, ETC. UNLESS OTHERWISE INDICATED ON THE PLANS OR IN THE SPECIFICATIONS. CONDUIT IN MECHANICAL ROOMS AND STORAGE ROOMS WITHOUT CEILINGS MAY BE EXPOSED ON BUILDING STRUCTURE.

3. BOXES LOCATED ON OPPOSITE SIDES OF NON-RATED WALLS SHALL BE OFFSET A MINIMUM OF 6" HORIZONTALLY. BOXES ON OPPOSITE SIDES OF FIRE RATED WALLS SHALL BE OFFSET A MINIMUM OF 24" HORIZONTALLY. "THRU-THE-WALL" BOXES SHALL NOT BE ALLOWED WITHOUT PRIOR WRITTEN APPROVAL OF THE ARCHITECT/ENGINEER.

4. VERIFY ALL FURNITURE, MODULAR FURNITURE, AND EQUIPMENT LOCATIONS WITH ARCHITECTURAL PLANS, ELEVATIONS, AND REVIEWED SHOP DRAWINGS. PRIOR TO MAKING THE ACTUAL TELECOMMUNICATIONS INSTALLATION, ADJUST OUTLETS OR CONNECTION LOCATIONS TO ACCOMMODATE FURNITURE AND/OR EQUIPMENT.

5. TELECOMMUNICATIONS EQUIPMENT SHALL BE MOUNTED TO ALLOW ACCESS TO ELECTRICAL AND MECHANICAL EQUIPMENT. ALL MOUNTING OF TELECOMMUNICATION DEVICES ON EQUIPMENT SUPPLIED BY ANOTHER CONTRACTOR SHALL BE APPROVED IN ADVANCE BY THE OTHER CONTRACTOR.

6. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL OPENINGS REQUIRED IN WALLS. ALL OPENINGS SHALL BE REPAIRED TO MATCH EXISTING BY A QUALIFIED CONTRACTOR AT THE EXPENSE OF THIS CONTRACTOR. ALL CONDUITS THROUGH WALLS SHALL BE GROUTED OR SEALED INTO OPENINGS.

7. ALL MATERIALS USED TO SEAL PENETRATIONS OF FIRE RATED WALLS AND FLOORS SHALL BE TESTED AND CERTIFIED AS A SYSTEM PER ASTM E814 STANDARDS FOR FIRE TESTS OF THROUGH-PENETRATION FIRESTOPS. REFER TO 26 05 03 FOR ADDITIONAL INFORMATION AND REQUIREMENTS SPECIFIC TO FIRESTOPPING.

8. REMOVE AND REINSTALL ALL CEILING TILES AS REQUIRED FOR THE EXECUTION OF TELECOMMUNICATIONS WORK THAT IS OUTSIDE THE CONTRACT LIMITS OF CONSTRUCTION. REPLACE CEILING TILES WITH IDENTICAL MATERIAL WHERE DAMAGED BY THIS CONTRACTOR.

9. FLUSH MOUNT ALL TELECOMMUNICATION OUTLETS AT +18" FROM FLOOR (CENTERLINE DIMENSION), EXCEPT WHERE OTHERWISE NOTED. OUTLETS MAY BE SURFACE MOUNTED WHEN CONDUIT IS SPECIFIED EXPOSED.

10. MOUNTING HEIGHTS SHALL BE AS FOLLOWS: LIGHTING SWITCHES 4'-0" RECEPTACLES (GENERAL AREAS) 1'-6" RECEPTACLES (UTILITY AREAS) 4'-0" TELECOMMUNICATION OUTLETS 1'-6" WALL PHONE 4'-0" FIRE ALARM STATIONS 4'-0" FIRE ALARM SIGNALS 7'-6" CLOCKS/CLOCK OUTLETS 1’-6” BELOW FIN. CEIL. SAFETY SWITCHES 5'-0" TO TOP

TECHNOLOGY INSTALLATION NOTES:

GENERAL NOTES:

1. ALL SYMBOLS AND ABBREVIATIONS LISTED MAY NOT BE APPLICABLE TO THIS PROJECT. REFER TO THE GENERAL TECHNOLOGY EQUIPMENT SCHEDULE FOR MORE COMPLETE DESCRIPTION AND ITEMS.

2. ALL SYMBOLS AND ABBREVIATIONS REFER TO TECHNOLOGY SHEETS ONLY AS DEFINED ON THE SHEET INDEX. REFER TO THE GENERAL TECHNOLOGY NOTES FOR ADDITIONAL INFORMATION.

3. ALL SYMBOLS LISTED ABOVE ARE FOR REFERENCE ONLY. REFER TO PLANS AND LINE TYPE KEY FOR NEW, EXISTING TO REMAIN AND TO BE REMOVED ITEMS FOR ADDITIONAL INFORMATION.

TECHNOLOGY SYMBOL NOTES:

1. "C#" INDICATES INFORMATION OUTLET FACEPLATE CONFIGURATION. REFER TO INFORMATION OUTLET SCHEDULE ON T-300 FOR ADDITIONAL INFORMATION.

DIAMETERø C CONDUIT

CONDUIT DOWN

CONDUIT UP OR UP/DOWN

CONDUIT SLEEVE

CONTINUATION

PLAN OR DETAIL NUMBER

PLAN OR DETAIL NAME

PLAN OR DETAIL SCALE

NAME

1VIEW NAME1/8" = 1'-0"

LEVEL NAME

10' - 0" HEIGHT ABOVE PROJECT 0' - 0"

1 INDICATES NOTE USED TO DESCRIBE ADDITIONAL INFORMATION ABOUT WORK REQUIRED, SPECIFIC TO THE SHEET AND/OR DETAIL

NO R HT

INDICATES DIRECTION OF TRUE NORTH

VIEW KEY

NEW WORK BY THIS CONTRACTOR (DARK SOLID LINE)

NEW WORK BY OTHERS AND/OR EXISTING TO REMAIN (LIGHT SOLID LINE)

EXISTING TO BE REMOVED BY THIS CONTRACTOR(DARK SHORT DASHED LINE)

LINE TYPE KEY:

BUILDING CODE: MBC 2015 EDITION

FIRE CODE: NFPA 13: 2013 EDITION

PLUMBING CODE: MBC 2015 EDITION

MECHANICAL CODE: MMC 2015 EDITION

ELECTRICAL CODE: NFPA 70 (NEC) 2016EDITION

LIFE SAFETY CODE: NFPA 101 2015 EDITION

ENERGY CONSERVATION CODE: ASHRAE 90.1 2013

HEALTH DEPARTMENT CODE: CURRENT EDITION

LOCAL BUILDING CODE: CURRENT EDITION

APPLICABLE CODES

CONTRACTOR SHALL COMPLY WITH APPLICABLE CODES AND LOCAL AMENDMENTS.

TEMPERATURE CONTROLS CONTRACTORT.C.C.

SECURITY CONTRACTORS.C.

AUDIO/VISUAL CONTRACTORA.V.C.

ASBESTOS ABATEMENT CONTRACTOR

PLUMBING CONTRACTORP.C.

GENERAL CONTRACTORG.C.

MECHANICAL CONTRACTORM.C.

VENTILATION CONTRACTORV.C.

ELECTRICAL CONTRACTORE.C.

A.C.

CONTRACTOR ABBREVIATION KEY

ABBR: DESCRIPTION:

TECHNOLOGY CONTRACTORT.C.

HEATING CONTRACTORH.C.

48

" M

AX

.

20" MAX.

44

" M

AX

.

20"-25" MAX.

48

" M

AX

.

15

" M

IN. 48

" M

AX

.

46

" M

AX

.

10" MAX. 10"-24" MAX.

ADA GUIDELINES - FRONT ACCESS

ADA STANDARDS FOR ACCESSIBLE DESIGN

INSTALL ABOVE COUNTER DEVICE AT 44" ABOVE FINISHED FLOOR.

INSTALL ABOVE COUNTER DEVICE AT 40" ABOVE FINISHED FLOOR.

INSTALL DEVICE AT 18" ABOVE FINISHED FLOOR.

ADA GUIDELINES - SIDE ACCESS

INSTALL DEVICE AT 44" ABOVE FINISHED FLOOR.

INSTALL DEVICE AT 42" ABOVE FINISHED FLOOR.

TECHNOLOGY SHEET INDEXT-000 TECHNOLOGY COVERSHEET

TD-101 FIRST FLOOR DEMOLITION - TECHNOLOGY

TD-102 SECOND FLOOR DEMOLITION - TECHNOLOGY

T-101 FIRST FLOOR PLAN - TECHNOLOGY

T-102 SECOND FLOOR PLAN - TECHNOLOGY

T-300 TECHNOLOGY DETAILS, RISERS AND SCHEDULES

SUGGESTED MATRIX OF RESPONSIBILITY

ITEM: SHOWN ON:FURNISHED

BY:INSTALLED

BY: NOTES:

TECHNOLOGY ROUGH-IN, REFER TOGENERAL TECHNOLOGY EQUIPMENTSCHEDULE AND SPECIFICATIONS FORDEFINITION

T-SERIES E.C. E.C. 3. 4.

INFORMATION OUTLET FACEPLATES,JACKS, AND TERMINATIONS

T-SERIES T.C. T.C.

CONDUIT SLEEVES (WHEN SHOWN ONDRAWINGS)

T-SERIES E.C. E.C.

CONDUIT SLEEVES (NOT SHOWN BUTREQUIRED FOR PROPER INSTALLATIONOF SYSTEM)

N/A T.C. T.C. 2. 4.

TELECOMMUNICATION SYSTEMSROUGH-IN

T-SERIES E.C. E.C. 1.

TELECOMMUNICATION EQUIPMENT,CABLING, AND TERMINATIONS

T-SERIES T.C. T.C.

GROUNDING LUGS ON TECHNOLOGYEQUIPMENT

T-SERIES T.C. E.C. 5.

LINE VOLTAGE POWER (+120V ORGREATER)

E-SERIES E.C. E.C.

LINE VOLTAGE POWER (NOT SHOWNBUT REQUIRED FOR PROPERINSTALLATION OF SYSTEM)

N/A T.C. E.C. 2. 4.

LOW VOLTAGE CABLING FORTECHNOLOGY SYSTEMS

T-SERIES T.C. T.C.

CABLE HANGERS AND SUPPORTS OROTHER CABLE ROUTING METHODS(OTHER THAN CONDUIT AND CABLETRAY)

T-SERIES T.C. T.C. 5.

FLOOR BOX (ROUGH-IN) T & E SERIES E.C. E.C.

SUGGESTED MATRIX OF RESPONSIBILITY NOTES

1. LOCATIONS OF TELECOMMUNICATIONS ROUGH-INS SHALL BE INDICATED BY THE INFORMATIONOUTLET SYMBOLS ON THE DRAWINGS. REFER TO THE TECHNOLOGY SYMBOL LIST FORADDITIONAL INFORMATION.

2. BASED ON THE INHERENT DIFFERENCES IN PRODUCTS FROM VARIOUS MANUFACTURERS, ALLREQUIRED EQUIPMENT MAY NOT BE SHOWN ON THE DRAWINGS FOR ALL ACCEPTABLEMANUFACTURERS.

3. INCLUDES BACKBOXES AND CONDUIT REQUIRED FOR THE TECHNOLOGY SYSTEMSINSTALLATION. THE E.C. SHALL BASE THE BID ON THE BASIS OF DESIGN SHOWN ON THECONTRACT DOCUMENTS.

4. ALL CHANGES TO THE SLEEVES, BACKBOXES, CONDUITS, AND POWER REQUIRED BECAUSE OFTHE T.C.'S SELECTION OF AN ALTERNATE ACCEPTABLE MANUFACTURER OR FROM SYSTEMCONFIGURATIONS THAT ARE LEFT TO THE CHOICE OF THE CONTRACTOR SHALL BE INCLUDEDIN THE T.C.'S BID. THIS BID SHALL INCLUDE INSTALLATION BY A LICENSED ELECTRICIAN.

5. FURNISHED AS PART OF THE EQUIPMENT WHEN POSSIBLE, OR FURNISHED TO THE E.C. FORINSTALLATION IN THE FIELD.

AREA OF WORKNO SCALE

FLOOR LEVEL

project number:

sheet title:

sheet number:

approved

project:

coordination checked

location

drawn

checked

designed

issue: date:

key plan:

WAYNE STATE

UNIVERSITYFacilities Planning and Management

5454 Cass Avenue

Detroit, MI 48202

FO

R B

IDS

consultants:

NM Project Number - 18113.0

Rands Building

IMEG Project Number -

Rands House - Rackham

Relocation

WSU : 00

- -

12/1

0/2

018 1

1:1

8:1

4A

M

T-000

TECHNOLOGY COVERSHEET

JEFGILTIMADA

POOVYA

18004050.01

TIMADA

TIMADA

WS

U R

an

ds B

ldg

Rackh

am

Relo

cati

on

18004050.0

1

REFERENCE SCALE IN INCHES

0 1 2 3

PROJECT #

IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

18004050.01

Owner Review 90% CD's Nov. 27, 2018

100% CD's Dec. 04, 2018

For Bids Dec. 11, 2018

Page 38: DETROIT, MI 48202...above a potential ignition source 3.abhr must be offset a minimum of 1" horizontally from any light switch, electrical or data receptacle, thermostat or other potential

KP

CR CR

CR

CR

KP

WAP

WAP

1 2 3 41.9 2.5 3.1 3.2 3.5 3.8

A

b

c

d

e

f

a10

a9

b4

c.1

c.2

c.3

c.4

e.8

EXISTING

EQUIPMENT RACK

EXISTING TELECOM

ROOM

T

CAMPUS

PHONE

AREA OF WORKNO SCALE

FLOOR LEVEL

project number:

sheet title:

sheet number:

approved

project:

coordination checked

location

drawn

checked

designed

issue: date:

key plan:

WAYNE STATE

UNIVERSITYFacilities Planning and Management

5454 Cass Avenue

Detroit, MI 48202

FO

R B

IDS

consultants:

NM Project Number - 18113.0

Rands Building

IMEG Project Number -

Rands House - Rackham

Relocation

WSU : 00

- -

12/1

0/2

018 1

1:1

8:1

7A

M

TD-101

FIRST FLOOR DEMOLITION -

TECHNOLOGY

JEFGILTIMADA

POOVYA

18004050.01

TIMADA

TIMADA

WS

U R

an

ds B

ldg

Rackh

am

Relo

cati

on

18004050.0

1

NO R

HT

1/8" = 1'-0"1 FIRST FLOOR DEMOLITION - TECHNOLOGY

REFERENCE SCALE IN INCHES

0 1 2 3

PROJECT #

IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

18004050.01

GENERAL NOTES :

1. REFER TO SHEET T-000 FOR TECHNOLOGY SYMBOL LIST AND LINE TYPE KEY.

Owner Review 90% CD's Nov. 27, 2018

100% CD's Dec. 04, 2018

For Bids Dec. 11, 2018

Page 39: DETROIT, MI 48202...above a potential ignition source 3.abhr must be offset a minimum of 1" horizontally from any light switch, electrical or data receptacle, thermostat or other potential

WHITE BOARD

projection

screen

1 2 3 41.9 2.5 3.1 3.2 3.5 3.8

A

b

c

d

e

f

a10

a9

b4

c.1

c.2

c.3

c.4

e.8

EXISTING

EQUIPMENT RACK

EXISTING

TELECOM

ROOM

AREA OF WORKNO SCALE

FLOOR LEVEL

project number:

sheet title:

sheet number:

approved

project:

coordination checked

location

drawn

checked

designed

issue: date:

key plan:

WAYNE STATE

UNIVERSITYFacilities Planning and Management

5454 Cass Avenue

Detroit, MI 48202

FO

R B

IDS

consultants:

NM Project Number - 18113.0

Rands Building

IMEG Project Number -

Rands House - Rackham

Relocation

WSU : 00

- -

12/1

0/2

018 1

1:1

8:1

8A

M

TD-102

SECOND FLOOR DEMOLITION -

TECHNOLOGY

JEFGILTIMADA

POOVYA

18004050.01

TIMADA

TIMADA

WS

U R

an

ds B

ldg

Rackh

am

Relo

cati

on

18004050.0

1

NO R

HT

1/8" = 1'-0"1 SECOND FLOOR DEMOLITION - TECHNOLOGY

REFERENCE SCALE IN INCHES

0 1 2 3

PROJECT #

IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

18004050.01

GENERAL NOTES :

1. REFER TO SHEET T-000 FOR TECHNOLOGY SYMBOL LIST AND LINE TYPE KEY.

Owner Review 90% CD's Nov. 27, 2018

100% CD's Dec. 04, 2018

For Bids Dec. 11, 2018

Page 40: DETROIT, MI 48202...above a potential ignition source 3.abhr must be offset a minimum of 1" horizontally from any light switch, electrical or data receptacle, thermostat or other potential

111

117

125

129

137 141

143

145

144142138

140136

134

132

130

128

126

122

120

124

118

116

112

108

106

102

100

103107

DN

UP

UP

CL

OFFICE

COVERED AREA

RESEARCHLAB

OFFICE

IT OFFICE

TREATMENT

OFFICE

TREATMENTOFFICEOFFICE

TREATMENTCHILDPLAYROOM

OBSERVATION

TREATMENT

TREATMENT

OFFICE

OFFICE

JC

UNISEXADA

WOMEN

WAITING

WAITING

LOUNGE

OFFICE

PLANTERSTORAGE

STORAGE

OPENOFFICE

VEST

PORCH

OPENOFFICE

CONFERENCE ROOMOFFICE

copier C2-1

C2-1

C2-1

C2-1

C2-1

JB

1

CAM

CAM

CAM

CAM

CAM CAM CAM

CAM CAM

CAMCAM

IS1

IM1

CAM

CAM

CAM

KP

CR CR

CR

CR

KP

WAP

WAP

CR

1

1 2 3 41.9 2.5 3.1 3.2 3.5 3.8

A

b

c

d

e

f

a10

a9

b4

c.1

c.2

c.3

c.4

e.8

+60"

+60"

1

1

1

1

1

1

1

EXISTING TELECOM

ROOM

11

1 1

INTERCOM SYSTEM POWER SUPPLY

EXISTING

EQUIPMENT RACK

1

1

1

T

CAMPUS

PHONE

2

2

2

2

2

AREA OF WORKNO SCALE

FLOOR LEVEL

project number:

sheet title:

sheet number:

approved

project:

coordination checked

location

drawn

checked

designed

issue: date:

key plan:

WAYNE STATE

UNIVERSITYFacilities Planning and Management

5454 Cass Avenue

Detroit, MI 48202

FO

R B

IDS

consultants:

NM Project Number - 18113.0

Rands Building

IMEG Project Number -

Rands House - Rackham

Relocation

WSU : 00

- -

12/1

0/2

018 1

1:1

8:1

5A

M

T-101

FIRST FLOOR PLAN -

TECHNOLOGY

JEFGILTIMADA

POOVYA

18004050.01

TIMADA

TIMADA

WS

U R

an

ds B

ldg

Rackh

am

Relo

cati

on

18004050.0

1

NO R

HT

1/8" = 1'-0"1 FIRST FLOOR PLAN - TECHNOLOGY

REFERENCE SCALE IN INCHES

0 1 2 3

PROJECT #

IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

18004050.01

GENERAL NOTES :

1. ALL NEW INFORMATION OUTLET ON THIS SHEET SHALL BE SERVED FROM THE EXISTING FIRST FLOOR TELECOMMUNICATIONS ROOM UNLESS OTHERWISE NOTED. REFER TO 1/T-300 FOR CONNECTIVITY DIAGRAM AND ADDITIONAL REQUIREMENTS.

2. REFER TO T-000 FOR TECHNOLOGY SYMBOL LIST AND GENERAL TECHNOLOGY INSTALLATION NOTES.

3. REFER TO T-300 FOR GENERAL TECHNOLOGY EQUIPMENT SCHEDULE.

KEYNOTES :

1. CAMERA PROVIDED FOR CONNECTION TO OWNER FURNISHED OBSERVATION RECORDING SYSTEM. CONTRACTOR TO PROVIDE CAMERA, MOUNT, AND CABLING TO OFE NETWORK RECORDING SYSTEM.

2. PROVIDE SURFACE RACEWAY FOR TECHNOLOGY OUTLETS INDICATED.

#

Owner Review 90% CD's Nov. 27, 2018

100% CD's Dec. 04, 2018

For Bids Dec. 11, 2018

Page 41: DETROIT, MI 48202...above a potential ignition source 3.abhr must be offset a minimum of 1" horizontally from any light switch, electrical or data receptacle, thermostat or other potential

WHITE BOARD

projection

screen

244

240

245

229

227

225

219

217

243242241

246

247

238236

230

226

224

220

218

214212

202

200.1

200

201

203205

234

232

207

OFFICE

OPENOFFICE

OPENOFFICE

IT

MECH

TREATMENT

OBSERVATION

TREATMENT

COMFERENCE/GROUP ROOMOBSERVATIONTREATMENT

TREATMENT

OBSERVATION

TREATMENTTREATMENT

ADULTGROUP ROOM

ADULTGROUP ROOM

WOMEN

UNISEX ADA

CHILDREN'SGROUP ROOM

OFFICETREATMENT

DN

UP

OPENOFFICE

STORAGE

DN

OPENOFFICE

OPENOFFICE

OFFICEOFFICE

OBSERVATION

TREATMENT

OPEN

UP

OFFICE

C2-1

C2-1

C2-1

C2-1

C2-1C2-1C2-1CAM

CAMCAM

CAM

IM1

IM1

IS1

IS1

IS1

IS1

IM1

IM1

CAM

CAM

CAM

CAMCAM

CAM

IS1

IM1

IM1

IS1

CAM

IS1

IM1

IM1

IS1

CAM

JB1

CR

1

IS1

IM1

1 2 3 41.9 2.5 3.1 3.2 3.5 3.8

A

b

c

d

e

f

a10

a9

b4

c.1

c.2

c.3

c.4

e.8

C2-1

1

1

1

1

1

2

1

EXISTING

TELECOM

ROOM

1

1

1

1

1

1

INTERCOM SYSTEM POWER SUPPLY

EXISTING

EQUIPMENT RACK

+60"

+60"

33

3

3

3

AREA OF WORKNO SCALE

FLOOR LEVEL

project number:

sheet title:

sheet number:

approved

project:

coordination checked

location

drawn

checked

designed

issue: date:

key plan:

WAYNE STATE

UNIVERSITYFacilities Planning and Management

5454 Cass Avenue

Detroit, MI 48202

FO

R B

IDS

consultants:

NM Project Number - 18113.0

Rands Building

IMEG Project Number -

Rands House - Rackham

Relocation

WSU : 00

- -

12/1

0/2

018 1

1:1

8:1

6A

M

T-102

SECOND FLOOR PLAN -

TECHNOLOGY

JEFGILTIMADA

POOVYA

18004050.01

TIMADA

TIMADA

WS

U R

an

ds B

ldg

Rackh

am

Relo

cati

on

18004050.0

1

NO R

HT

1/8" = 1'-0"1 SECOND FLOOR PLAN - TECHNOLOGY

REFERENCE SCALE IN INCHES

0 1 2 3

PROJECT #

IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

18004050.01

GENERAL NOTES :

1. ALL NEW INFORMATION OUTLET ON THIS SHEET SHALL BE SERVED FROM THE EXISTING FIRST FLOOR TELECOMMUNICATIONS ROOM UNLESS OTHERWISE NOTED. REFER TO 1/T-300 FOR CONNECTIVITY DIAGRAM AND ADDITIONAL REQUIREMENTS.

2. REFER TO T-000 FOR TECHNOLOGY SYMBOL LIST AND GENERAL TECHNOLOGY INSTALLATION NOTES.

3. REFER TO T-300 FOR GENERAL TECHNOLOGY EQUIPMENT SCHEDULE.

KEYNOTES :

1. CAMERA PROVIDED FOR CONNECTION TO OWNER FURNISHED OBSERVATION RECORDING SYSTEM. CONTRACTOR TO PROVIDE CAMERA, MOUNT, AND CABLING TO OFE NETWORK RECORDING SYSTEM.

2. PROVIDE (2)2" CONDUITS STUBBED TO ACCESSIBLE CEILING FOR OWNER FURNISHED AV DEVICES.

3. PROVIDE SURFACE RACEWAY FOR TECHNOLOGY OUTLETS INDICATED.

#

Owner Review 90% CD's Nov. 27, 2018

100% CD's Dec. 04, 2018

For Bids Dec. 11, 2018

Page 42: DETROIT, MI 48202...above a potential ignition source 3.abhr must be offset a minimum of 1" horizontally from any light switch, electrical or data receptacle, thermostat or other potential

EXISTING

VOICE PATCH

PANEL(S)

EXISTING

VOICE PATCH

PANEL(S)

SC-MPP-1

EXISTING

NETWORK

EQUIPMENT

EXISTING FIBER

PANEL

2

3-Port Faceplate

IDENTIFICATION

IDENTIFICATION

3

1

PAIR 3

PAIR 1PAIR 2 PAIR 4

WO WGO BL WBL G WBR BR

1 32 4 5 6 7 8

ANSI/TIA/EIA T568BPIN/PAIR ASSIGNMENT

C#

2

2

1

4

EXISTING FIBER BACKBONE

3

EXISTING TELECOM ROOM

NOTES:

1. THIS RISER IS DIAGRAMMATIC AND MAY NOT SHOW ACTUAL ROUTING OR QUANTITIES OF MATERIALS SHOWN. THIS RISER IS SHOWN FOR CLARIFICATION OF CONNECTION LOCATIONS AND CABLE TYPE. ALL INFORMATION OUTLETS ARE TYPICAL OF THE OUTLETS IN THE AREA SHOWN. REFER TO FLOOR PLANS FOR MORE SPECIFIC ROUTING AND QUANTITY INFORMATION. REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION.

2. REFER TO T-300 FOR TECHNOLOGY EQUIPMENT SCHEDULE.

KEYNOTES:

1. 23 GAUGE, 4-PAIR, CATEGORY 6, UNSHIELDED TWISTED PAIR CABLE, SEE SPECIFICATIONS.2. REFER TO INFORMATION OUTLET SCHEDULE ON T-000 AND THE FLOOR PLANS FOR QUANTITY OF

CABLES AND JACKS TO BE INSTALLED AT EACH INFORMATION OUTLET.3. EXISTING RJ-45 TO RJ-45 CATEGORY CAT 6 UTP PATCH CORD. 4. EXISTING FIBER PATCH CORD. 5. CONTRACTOR TO PROVIDE NEW SC-MPP-1 FOR TERMINATION OF OBSERVATION RECORDING

SYSTEM CAMERAS (AV-CAM-1). NEW INFORMATION OUTLETS (SC-IO-W) TO TERMINATE TO AVAILABLE OPEN SPACES ON EXISTING MODULAR PATCH PANELS AND VOICE TERMINATION BLOCKS.

#

5

EXISTING COPPER BACKBONE

CAM

1

EXISTING VOICE CROSS

CONNECT

RECESSED MOUNT TRIM RING

RECESSED MOUNT BRACKET

DOME

DOME CAMERA BODY

STRUCTURE ABOVE

FLEXIBLE METALLIC CONDUIT

4-SQUAREJUNCTION BOX

(1) 3/4"EMT CONDUIT TO NEARESTACCESSIBLE CEILING

ACOUSTICAL CEILING TILE ORGYPSUM WALL BOARD (REFER TOARCHITECTURAL PLANS)

NOTES:

1. COORDINATE EXACT LOCATION ON SITE WITH WORK BY OTHER TRADES TO ENSURE DESIRED VIEWING AREA AND SERVICE ACCESS AFTER COMPLETION OF PROJECT AND TO MINIMIZE ANY POSSIBLE DAMAGE TO INSTALLED CAMERA OR ASSOCIATED CABLING.

2. CONDUIT SHALL STUB TO NEAREST ACCESSIBLE CEILING AND TERMINATE ORIENTED HORIZONTALLY AT THE HEIGHT OF THE ASSOCIATED CABLE TRAY OR J-HOOK ROUTE. CONDUIT RUN SHALL NOT CONTAIN MORE THAN 180 DEGREES OF BEND BETWEEN ACCESSIBLE JUNCTION BOXES OR BETWEEN JUNCTION BOX AND END OF CONDUIT. WHERE CONDUIT STUBS THROUGH A WALL IN TO A CORRIDOR AND TERMINATES AT AN ASSOCIATED J-HOOK ROUTE, THE CONDUIT SHOULD EXTEND NOT MORE THAN 2-4 INCHES IN TO THE CORRIDOR. WHERE CONDUIT STUBS TO AN ASSOCIATED CABLE TRAY, CONDUIT SHOULD EXTEND TO CABLE TRAY. ALL CONDUITS MUST BE FITTED WITH A NYLON BUSHING ON EACH END OF THE CONDUIT.

3. INSTALLING CONTRACTOR SHALL FURNISH AND INSTALL FIRESTOP MATERIALS FOR CAMERA ROUGH-INS PER PROJECT REQUIREMENTS. REFER TO SPECIFICATIONS FOR FIRESTOP REQUIREMENTS.

4. CAMERA MOUNTING ACCESSORY SHALL BE FROM THE SAME MANUFACTURER OF THE CAMERA AND APPROVED BY THE MANUFACTURER FOR USE WITH THE SPECIFIC MODEL NUMBER OF CAMERA INSTALLED. CONTRACTOR SHALL INSTALL CAMERA MOUNTING ACCESSORY AND CAMERA PER MANUFACTURER'S INSTRUCTIONS.

5. MOUNT ENCLOSURE FLUSH IN HARD CEILINGS. MOUNT ENCLOSURE IN ACOUSTICAL CEILING TILE WITH APPROPRIATE BRIDGE BRACE IN ACCESSIBLE CEILINGS. INSTALL SAFETY WIRES OR CABLES FROM ENCLOSURE TO NEAREST STRUCTURE WHERE INSTALLED IN ACOUSTICAL CEILINGS.

6. LOCATE FLEXIBLE METALLIC CONDUIT CONNECTION TO CAMERA ENCLOSURE SUCH THAT THE ASSOCIATED CABLING CAN BE FED IN TO ENCLOSURE WITHOUT INTERFERING WITH CAMERA OPERATION.

REFER TO SPECIFICATIONS FOR IDENTIFICATION REQUIREMENTS (TYP.)

NUMBER INDICATES FACEPLATE POSITION (TYP.)

NOTES:

1. THIS RISER IS DIAGRAMMATIC AND MAY NOT SHOW ACTUAL ROUTING OR QUANTITIES OF MATERIALS. THIS RISER IS SHOWN FOR CLARIFICATION OF CONNECTION LOCATIONS AND CONDUCTOR TYPE. ALL CONNECTIONS AND SYSTEM DEVICES SHOWN ARE TYPICAL AND NOT REPRESENTATIVE OF ACTUAL PROJECT QUANTITIES.REFER TO FLOOR PLANS AND ENLARGED FLOOR PLANS FOR ACTUAL QUANTITIES AND LOCATIONS OF DEVICES AND MORE SPECIFIC ROUTING INFORMATION. REFER TO SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.

IM1 IS1

POWER SUPPLY (AIPHONE PS-1225UL) LOCATED WITHIN TELECOM ROOM. REFER TO FLOOR PLANS.

3C, 18 AWG SHIELDED CABLE

NOTES:1. CONFIGURATIONS SHOWN IN THE DETAIL ABOVE ARE DIAGRAMMATIC, INTENDED TO DESCRIBE THE CONTROLLED SECURITY SCHEME ROUGH-IN

REQUIREMENTS OF THE DOORS. DETAILS ABOVE MAY NOT ACCURATELY REPRESENT DOOR SIZE, DOOR SWING, DOOR HARDWARE, OR DOOR FUNCTIONALITY. REFER TO ARCHITECTURAL DOOR HARDWARE SCHEDULE, DOOR HARDWARE GROUPS AND DOOR HARDWARE SPECIFICATIONS FOR COMPLETE INFORMATION. MIRROR THE DETAIL AS REQUIRED.

2. ROUGH IN SHOWN IN THE DETAIL ABOVE REPRESENTS THE MINIMUM REQUIREMENTS FOR ALL CONTROLLED SECURITY SYSTEM DEVICES AND CABLING UNLESS OTHERWISE NOTED. COORDINATE EXACT REQUIREMENTS WITH SELECTED DOOR MATERIALS, DOOR HARDWARE, AND CONTROLLED SECURITY DEVICES AND CABLING PRIOR TO INSTALLATION.

3. ALL CABLING IN WALLS AND WHERE EXPOSED ON VERTICAL SURFACES SHALL BE INSTALLED IN EMT CONDUIT OR SURFACE MOUNT RACEWAY. CABLING ROUTED HORIZONTALLY ABOVE THE ACCESSIBLE CEILING MAY BE INSTALLED FREE-AIR CABLING PROPERLY RATED FOR THE CEILING ENVIRONMENT.

4. THE ELECTRICAL OR SECURITY CONTRACTOR SHALL NOT MODIFY ANY FIRE RATED DOOR AND/OR DOOR FRAME. REFER TO THE ARCHITECTURAL DOOR SCHEDULE, DOOR HARDWARE SCHEDULE, AND DOOR HARDWARE SPECIFICATION FOR ADDITIONAL INFORMATION. MODIFICATION TO ANY FIRE RATED DOOR AND/OR FRAME WILL REQUIRE A RE-CERTIFICATION OF THE DOOR AND FRAME WITH THE LOCAL AUTHORITY HAVING JURISDICTION (AHJ).

5. INSTALLING CONTRACTOR SHALL FURNISH AND INSTALL FIRESTOP MATERIALS FOR ALL CONTROLLED SECURITY SCHEME ROUGH-INS PER PROJECT REQUIREMENTS. REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION AND REQUIREMENTS.

6. INSTALLATION SHALL INCLUDE ALL POWER REQUIRED FOR SYSTEM OPERATION INCLUDING +120VAC. REFER TO THE SUGGESTED MATRIX OF SCOPE RESPONSIBILITY FOR ADDITIONAL INFORMATION.

KEYNOTES:

1. PROVIDE JUNCTION BOXES IN THE DOOR FRAME WHERE SHOWN ON THIS DETAIL. ROUGH-IN SHALL BE PROVIDED WHETHER THE CURRENT SECURITY SCHEME UTILIZES THEM OR NOT. ALL CONDUITS SHALL BE EMT CONDUIT UNLESS OTHERWISE NOTED. FLEXIBLE CONDUIT OF ANY TYPE WILL NOT BE ACCEPTED. COORDINATE INSTALLATION WITH ON-SITE DOOR FRAME INSTALLATION CONTRACTOR.

2. ALL DOOR POSITION SWITCHES ARE REQUIRED TO BE RECESSED UNLESS OTHERWISE NOTED. ELECTRIC HINGE MONITORS ARE NOT AN ACCEPTABLE REPLACEMENT FOR THE RECESSED DOOR POSITION SWITCH.

3. DOUBLE GANG BACKBOX WITH SINGLE GANG PLASTER RING. REFER TO FLOOR PLAN(S) FOR ACTUAL CREDENTIAL READER TYPE AND ROUGH-IN LOCATIONS.

4. CONDUIT SHALL ROUTE FROM THE CREDENTIAL READER TO THE SECURE SIDE OF THE DOOR. CONDUIT SHALL ROUTE TO THE NEAREST SECURITY PANEL.PROVIDE A NYLON BUSHING ON CONDUIT END.

5. MOUNT A MINIMUM 4" SQUARE 2-1/8" DEEP JUNCTION BOX WITH BLANK COVER PLATE ON THE SECURE SIDE OF THE DOOR ABOVE ACCESSIBLE CEILING. INSTALLING CONTRACTOR SHALL SIZE THE JUNCTION BOXES PER SYSTEM INSTALLATION REQUIREMENTS AND APPLICABLE CODES. MAINTAIN ACCESS TO THE JUNCTION BOX.

6. PROVIDE A HORIZONTALLY MOUNTED SINGLE GANG BACKBOX FOR THE REQUEST TO EXIT SENSOR. 7. CONDUIT SHALL ROUTE TO THE NEAREST SECURITY PANEL. PROVIDE A NYLON BUSHING ON CONDUIT END.

DOOR FRAME ROUGH-IN DIAGRAM (ALL SINGLE DOORS)

DOOR FRAME ROUGH-IN DIAGRAM (ALL DOUBLE DOORS WITH OR WITHOUT MULLION)

FINISHED ACCESSIBLE CEILING

MINIMUM 3/4" EMT CONDUIT TO ABOVE THE ACCESSIBLE CEILING.

FINISHED FLOOR

CREDENTIAL READER ROUGH-IN. 3

DOOR CONTACT ROUGH-IN.

MINIMUM 1" EMT CONDUIT

11

REQUEST TO EXIT DEVICE ROUGH-IN.

FOR DOOR HARDWARE POWER SUPPLIES.

1/2" EMT CONDUIT MINIMUM (TYP.)

4'-0

"

MINIMUM 1" EMT CONDUITFOR DOOR

HARDWARE POWER SUPPLIES.

MINIMUM 3/4" EMT CONDUIT TO ABOVE THE ACCESSIBLE CEILING.

CREDENTIAL READER ROUGH-IN. 3

REQUEST TO EXIT DEVICE ROUGH-IN.

DOOR CONTACT ROUGH-IN.

1

4'-0

"

2

2

4

4

5

5

5

5

66

4" 4" 4"

7 7

6"

6"

#

AREA OF WORKNO SCALE

FLOOR LEVEL

project number:

sheet title:

sheet number:

approved

project:

coordination checked

location

drawn

checked

designed

issue: date:

key plan:

WAYNE STATE

UNIVERSITYFacilities Planning and Management

5454 Cass Avenue

Detroit, MI 48202

FO

R B

IDS

consultants:

NM Project Number - 18113.0

Rands Building

IMEG Project Number -

Rands House - Rackham

Relocation

WSU : 00

- -

12/1

0/2

018 1

1:1

8:1

7A

M

T-300

TECHNOLOGY DETAILS, RISERS

AND SCHEDULES

JEFGILTIMADA

POOVYA

18004050.01

TIMADA

TIMADA

WS

U R

an

ds B

ldg

Rackh

am

Relo

cati

on

18004050.0

1

REFERENCE SCALE IN INCHES

0 1 2 3

PROJECT #

IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

18004050.01

NO SCALE1 CONNECTIVITY RISER DIAGRAM TR-01

NO SCALE4

INTERIOR RECESSED CEILINGCAMERA MOUNT DETAIL

BLANK BLANK FILLER MODULE

2. REFER TO SPECIFICAITONS SECTION 27 05 53 FOR ADDITIONAL INFORMATION ON LABELING REQUIREMENTS. VOICE CAT 6 RJ-45 (WHITE)

1. PROVIDE REMOVABLE BLANK INSERT(S) FOR ALL UNUSED PORTS. DATA CAT 6 RJ-45 (ORANGE)

NOTES: LEGEND

SINGLE GANG WALLPLATES

INFORMATION OUTLET SCHEDULE

CONFIGURATION FA

CE

PL

AT

E P

OR

TS

FACEPLATE PORT IDENTIFICATION

NOTESPO

SIT

ION

1 J

AC

K T

YP

E

PO

SIT

ION

2 J

AC

K T

YP

E

PO

SIT

ION

3 J

AC

K T

YP

E

PO

SIT

ION

4 J

AC

K T

YP

E

PO

SIT

ION

5 J

AC

K T

YP

E

PO

SIT

ION

6 J

AC

K T

YP

E

C2-1 3 DATA DATA VOICE

THE MATERIAL LIST ABBREVIATIONS AND THE TECHNOLOGY EQUIPMENT SCHEDULE ARE FOR THE CONVENIENCE OF THE CONTRACTOR. EACH CONTRACTOR SHALL BERESPONSIBLE FOR VERIFICATION OF QUANTITIES AND SHALL FURNISH ALL MATERIAL REQUIRED, WHETHER SPECIFIED OR NOT, TO PRODUCE A SATISFACTORY WORKINGSYSTEM.

CATALOG NUMBERS ARE NOT TO BE CONSIDERED COMPLETE BUT ARE GIVEN ONLY TO AID THE CONTRACTOR IN THE SEARCH FOR MATERIAL. NO MATERIAL SHALL BEORDERED BY MANUFACTURER AND CATALOG NUMBER ONLY. EACH CONTRACTOR SHALL FIRST READ THE COMPLETE DESCRIPTION OF THE MATERIAL ON THESE DRAWINGSAND SPECIFICATIONS. THE FIRST MANUFACTURER LISTED IS THE BASIS OF DESIGN. "STANDARD COLOR" INDICATES FACTORY FINISH AVAILABLE AT NO ADDITIONAL CHARGE.

GENERAL TECHNOLOGY EQUIPMENT SCHEDULE

EQUIPMENT LISTABBREVIATION EQUIPMENT LIST DESCRIPTION

EQUIPMENT LISTMANUFACTURER AND MODEL

AC-CR1-W ROUGH IN PROVIDED FOR ACCESS CONTROL CREDENTIAL READER. REFER TO 3/T-300 FOR CONTROLLED SECURITYSCHEME DOOR ROUGH-IN DETAIL.

*

AV-CAM-1 AUDIO VISUAL PTZ CAMERA.INDOOR CEILING MOUNT WITH 1920 X 1080 RESOLUTION,FOCAL LENGTH: 4.7-47 MM,1/66500AT 2 SEC ILLUMINATION, 1/2.8" PREGRESSIVE SCAN WITH CMOS, 360 DEGREE UNINTERRUPTED PAN AND WDR.PROVIDE WITH ALL NECESSARY MOUNTING ACCESSORIES.

AXIS M5525 E

OR PRE-APPROVED EQUAL

AV-JB1-W AUDIOVISUAL JUNCTION BOX. PROVIDED FOR CONNECTIONS FOR OWNER-FURNISHED MULTIMEDIA SYSTEM(S). *

IC-IM1 INTERCOM MASTER STATION. DESK OR WALL MOUNT WITH ABS HOUSING AND LED, CALL TONE INDICATORS. 300 mAPOWER CONSUMPTION. INSTALL WITHIN 4" SQUARE BACKBOX WITH PLASTER RING AND PROVIDE (!) 1" C TO NEARESTACCESSIBLE CEILING.

AIPHONE LEF-3

OR PRE-APPROVED EQUAL

IC-IS1 INTERCOMM DOOR STATION. WALL MOUNT. ABS PLASTIC HOUSING. PUSH TO TALK OR OPEN VOICE HANDSFREECOMMUNICATION. INSTALL WITHIN 4" SQUARE BACKBOX WITH PLASTER RING. PROVIDE 1" CONDUIT TO NEARESTACCESSIBLE CEILING.

AIPHONE LE-B

OR PRE-APPROVED EQUAL

SC-IO-W INFORMATION OUTLET, WALL MOUNT, 3 PORT COVERPLATE AS INDICATED ON DRAWINGS.

"#" INDICATES INFORMATION OUTLET FACEPLATE CONFIGURATION AS INDICATED ON THE PLANS. REFER TO T-000 FORINFORMATION OUTLET SCHEDULE FOR PIN CONFIGURATION.

INSTALL INFORMATION OUTLET IN A 4" SQUARE BACKBOX WITH A SINGLE GANG PLASTER RING. INSTALL A 1" EMTCONDUIT TO TELECOM ROOM. PROVIDE REMOVABLE BLANK INSERTS FOR UNUSED PORTS (SYSTIMAX M20AP SERIESOR APPROVED EQUAL)

COVERPLATE:COMMSCOPE SYSTIMAX M13L - 262

JACK:COMMSCOPE SYSTIMAX CAT6 UNJ600-OR (ORANGE) UNJ600-WH (WHITE)

HUBBELLORTRONICS

NO SCALE2 INTERCOM RISER DIAGRAM

NO SCALE3 CONTROLLED SECURITY SCHEME DOOR ROUGH-IN DETAIL

Owner Review 90% CD's Nov. 27, 2018

100% CD's Dec. 04, 2018

For Bids Dec. 11, 2018