Detailed Installer Guide Programmable Thermostats 1 Specifications 2 Installation and Wiring 3 Quick Reference 4 Installer Settings 5 System Testing • Possible electric shock or damage to equipment can occur. • Disconnect power before beginning installation. Caution This thermostat requires 24 Volt AC Power or 2 properly installed “AA” Alkaline batteries for proper operation. When connecting 24 Volt AC Power the batteries may be installed as a backup. For use only as described in this manual. Any other use will void warranty. 5020 Single Stage Heat / Cool Conventional or Heat Pump 5220 Up to 3 Heat / 2 Cool Heat Pump Up to 2 Heat / 2 Cool Conventional Warning For installation by experienced service technicians only. ® This thermostat is compatible with: • Single stage heat / cool conventional and heat pump systems • Conventional systems up to 2 stages of heating and 2 stages of cooling (5220 only) • Heat pump systems up to 3 stages of heating and 2 stages of cooling (5220 only) • 250 – 750 millivolt heating only systems • 2 or 3 wire hydronic zone systems Electrical and control specifications: • Electrical Rating: 24 Volt AC • 1 amp maximum load per terminal • AC Power: 18 – 30 Volts AC • DC Power: 3.0 Volt DC (2 “AA” Alkaline Batteries Included) • Control Range: 45° – 90° F (7° – 32° C) • Temperature Accuracy: +/- 1° F (+/- .5° C) • Outdoor Temperature Display Range: -40° - 120° F (-40° - 49° C) Terminations • 5020: Rc, Rh, G, W1, O/B/V3, Y1, C, S1, S2 • 5220: Rc, Rh, G, W1/E/W3, W2, O/B/V3, Y1, Y2, L, C, S1, S2 1 Specifications 5020W-100-02 Model number is located on back of thermostat. PREMIER SERIES

Detailed SREMIER Installer Guide - Braeburn Systems...NOTES - Conventional Systems [1] Optional 24 Volt AC common connection. [2] Remove factory installed jumper for dual transformer

  • Upload
    others

  • View
    3

  • Download
    0

Embed Size (px)

Citation preview

  • Detailed Installer GuideProgrammable Thermostats

    1 Specifications 2 Installation and Wiring 3 Quick Reference 4 Installer Settings 5 System Testing

    • Possible electric shock or damage to equipment can occur.• Disconnect power before beginning installation.

    Caution

    This thermostat requires 24 Volt AC Power or 2 properly installed “AA” Alkaline batteries for proper operation. When connecting 24 Volt AC Power the batteries may be installed as a backup.

    For use only as described in this manual. Any other use will void warranty.

    5020 Single Stage Heat / Cool Conventional or Heat Pump

    5220 Up to 3 Heat / 2 Cool Heat Pump Up to 2 Heat / 2 Cool Conventional

    Warning For installation by experienced service technicians only.

    ®

    This thermostat is compatible with: • Singlestageheat/coolconventionalandheatpumpsystems • Conventionalsystemsupto2stagesofheatingand2stagesofcooling(5220only) • Heatpumpsystemsupto3stagesofheatingand2stagesofcooling(5220only) • 250–750millivoltheatingonlysystems • 2or3wirehydroniczonesystems

    Electrical and control specifications: • ElectricalRating:24VoltAC • 1ampmaximumloadperterminal • ACPower:18–30VoltsAC • DCPower:3.0VoltDC(2“AA”AlkalineBatteriesIncluded) • ControlRange:45°–90°F(7°–32°C) • TemperatureAccuracy:+/-1°F(+/-.5°C) • OutdoorTemperatureDisplayRange:-40°-120°F(-40°-49°C)

    Terminations • 5020:Rc,Rh,G,W1,O/B/V3,Y1,C,S1,S2 • 5220:Rc,Rh,G,W1/E/W3,W2,O/B/V3,Y1,Y2,L,C,S1,S2

    1 Specifications

    5020W-100-02

    Model number is located on back of thermostat.

    PREMIERSERIES

  • Thermostat LocationInstallthethermostatapproximately5feet(1.5m)abovethefloorinanareathathasagoodamountofaircirculationandmaintainsanaverageroomtemperature.

    Avoidinstallationinlocationswherethethermostatcanbeaffectedbydrafts,deadairspots,hotorcoldairducts,sunlight,appliances,concealedpipes,chimneysandoutsidewalls.

    Installer Guide 2

    Install your new Braeburn thermostat in 4 basic steps:1 InstalltheSub-Base2 ProvidePower3 ConnectYourWires4 AttachThermostattoSub-Base

    Install the Sub-Base: •Removethesub-basefromthebodyofthethermostat.•Mountthesub-baseasshownbelow:

    Warning Disconnect power before beginning installation.

    2 Installation and Wiring

    1

    UP UP

    Drill 3/16” pilot holes in your desired location. Use supplied anchors for drywall or plaster.

  • 3 Installer Guide

    Provide Power

    C

    24VAC Power Terminal (C)

    2

    Wiring Terminations for model 5020

    Terminal Function Description

    Rc Input 24VoltACCoolingTransformer (DualTransformerSystemsOnly)

    Rh Input PowerConnection(24VoltACHeating TransformerorMillivoltPowerSource)

    G Output FanControl

    W1 Output ConventionalHeatRelay

    O/B/V3 Output (O)CoolActiveReversingValve (B)HeatActiveReversingValve (V3)ZoneValvePowerClose

    Y1 Output CompressorRelay

    C Input 24VoltACTransformerCommon

    S1

    S2

    Connect Your Wires3

    Input OptionalRemoteSensor(indoororoutdoor)

    +

    +

    • For24VoltACpower,youmustconnectthecommonsideofthetransformertotheCterminalonthethermostatsub-base.In dualtransformerinstallations,thetransformercommonmustcomefromthecoolingtransformer.

    • Forbatterypower,insertthe2supplied“AA”typealkalinebatteriesintothebatterycompartmentlocatedintherear housingofthethermostat.MakesuretopositionthePositive(+)andNegative(-)sidesofthebatteriescorrectlywith the+/-symbolsinthebatterycompartment.

    Batteries Installed as Shown

  • Installer Guide 4

    Wiring Terminations for model 5220

    Terminal Function Description

    Rc Input 24VoltACCoolingTransformer (DualTransformerSystemsOnly)

    Rh Input PowerConnection(24VoltACHeating TransformerorMillivoltPowerSource)

    G Output FanControl

    W1/E/W3 Output (W1)1stStageConventionalHeat, (E)EmergencyHeat, (W3)3rdStageAuxiliaryHeat

    W2 Output 2ndStageConventionalHeat

    O/B/V3 Output (O)CoolActiveReversingValve (B)HeatActiveReversingValve (V3)ZoneValvePowerClose

    Y1 Output 1stStageCompressor

    Y2 Output 2ndStageCompressor

    L Input SystemMalfunctionIndicator

    C Input 24VoltACTransformerCommon

    S1

    S2

    Connecting Your Wires (continued)3

    Input OptionalRemoteSensor(indoororoutdoor)

  • 5 Installer Guide

    Heat Only or Millivolt Set System Type to 11CONV

    Rh PowerConnection

    W1 HeatRelay

    G FanRelay[note 4]

    C 24VoltACTransformerCommon[note 1, 3]

    1 HEAT / 1 COOL Single or Dual Transformer Set System Type to 11CONV

    Rh 24VoltACPower(heatingtransformer)[note 2]

    Rc 24VoltACPower(coolingtransformer)[note 2]

    W1 HeatRelay

    Y1 CompressorRelay

    G FanRelay

    C 24VoltACTransformerCommon[note 1, 3]

    NOTES - Conventional Systems[1]Optional24VoltACcommonconnection.[2]Removefactoryinstalledjumperfordual transformersystems.[3] Indualtransformersystems,transformer commonmustcomefromcoolingtransformer.[4] Ifneededforsystem.

    Provide disconnect and overload protection as required.

    2 HEAT / 2 COOL Single or Dual transformer Set System Type to 22CONV

    Rh 24VoltACPower(heatingtransformer)[note 2]

    Rc 24VoltACPower(coolingtransformer)[note 2]

    W1 HeatRelayStage1

    W2 HeatRelayStage2

    Y1 CompressorRelayStage1

    Y2 CompressorRelayStage2 [note 4]

    G FanRelay

    C 24VoltACTransformerCommon[note 1, 3]

    Typical Wiring ConfigurationsNOTE: The “System Type” option will be configured in the Installer Settings section. The 5020 is a single stage thermostat and not intended for multi stage equipment.

    Conventional Systems

    NOTE: Additional options are configured in the Installer Settings section.

    S1

    S2

    NOTES - Additional Wiring Options[1]Theseterminalscanbeusedtoconnecta Braeburn® indoororoutdoorremotesensor.

    Additional Wiring Options

    IndoororOutdoorRemoteSensor[note 1]

    Hydronic Heat Only Set System Type to 1HD Rh 24VoltACPower(heatingtransformer)[note 2]

    W1 ZoneValvePowerOpen

    V3 ZoneValvePowerClose

    G FanRelay[note 4]

    C 24VoltACTransformerCommon[note 1]

    Hydronic Heat / 1 Cool Set System Type to 11HD

    Rh 24VoltACPower(heatingtransformer)[note 2]

    Rc 24VoltACPower(coolingtransformer)[note 2]

    W1 ZoneValvePowerOpen

    V3 ZoneValvePowerClose

    Y1 CompressorRelay

    G FanRelay

    C 24VoltACTransformerCommon[note 1, 3]

  • Installer Guide 6

    1 HEAT / 1 COOL - No Auxiliary HeatSet System Type to 11HP

    Rh 24VoltACPower

    Rc ConnectedtoRhwithsuppliedJumperWire

    O/BChangeoverValve [note 2]

    Y1 CompressorRelay

    G FanRelay

    C 24VoltACTransformerCommon [note 1]

    3 HEAT / 2 COOL – Including Auxiliary HeatSet System Type to 32HP

    Rh 24VoltACPower

    Rc ConnectedtoRhwithsuppliedJumperWire

    O/B ChangeoverValve [note 2]

    Y1 Compressor1Relay(1ststageheating/cooling)

    Y2 Compressor2Relay(2ndstageheating/cooling)

    W3 AuxiliaryHeatRelay(3rdstageheating)[note 5]

    G FanRelay

    C 24VoltACTransformerCommon[note 1]

    L OptionalSystemFaultMonitor[note 4]

    2 HEAT / 1 COOL - Including Auxiliary Heat Set System Type to 22HP

    Rh 24VoltACPower

    Rc ConnectedtoRhwithsuppliedJumperWire

    O/BChangeoverValve[note 2]

    Y1 CompressorRelay(1ststageheating/cooling)

    W2 AuxiliaryHeatRelay(2ndstageheating)[note 3]

    E EmergencyHeatRelay[note 3]

    G FanRelay

    C 24VoltACTransformerCommon[note 1]

    L OptionalSystemFaultMonitor[note 4]

    2 HEAT / 2 COOL - No Auxiliary HeatSet System Type to 32HP

    Rh 24VoltACPower

    Rc ConnectedtoRhwithsuppliedJumperWire

    O/BChangeoverValve[note 2]

    Y1 Compressor1Relay(1ststageheating/cooling)

    Y2 Compressor2Relay(2ndstageheating/cooling)

    G FanRelay

    C 24VoltACTransformerCommon[note 1]

    L OptionalSystemFaultMonitor[note 4]

    NOTES - Heat Pump Systems[1] Optional24VoltACcommonconnection.[2] O(coolactive)orB(heatactive)isselectedin theInstallerSettingsmenu.[3] Installafieldsuppliedjumperbetweenthe W2/AUX2andW1/E/AUX1terminalsifthereis noseparateemergencyheatrelayinstalled.

    [4] IftheLterminalisused,the24VoltACcommon mustbeconnected(Cterminal).[5] Ifaseparateemergencyheatrelayisinstalled,the W1/E/AUX1terminalshouldhaveboththeauxiliary heat1relayandemergencyheatrelayconnected.

    Provide disconnect and overload protection as required.

    Typical Wiring Configurations NOTE: The “System Type” option will be configured in the Installer Settings section. The 5020 is a single stage thermostat and not intended for multi stage equipment.

    Heat Pump Systems

    NOTE: Additional options are configured in the Installer Settings section.

    S1

    S2

    NOTES - Additional Wiring Options[1]Theseterminalscanbeusedtoconnecta Braeburn® indoororoutdoorremotesensor.

    Additional Wiring Options

    IndoororOutdoorRemoteSensor[note 1]

  • INSTRUCTIONS

    DAY/TIME

    7 Installer Guide

    NOTE: This thermostat ships configured as a 1H/1C conventional thermostat. Confirm installer settings. See page 10.

    UP UP

    S1

    S2

    G

    Y1

    Y2

    A

    H

    L

    C

    W1/E/AUX1

    W2/AUX2

    W3/O/B

    RH

    RC

    L S1L

    S2

    G

    C

    W1/E/AUX/AUX/AUX/AUX1111

    4 Attach Thermostat to Sub-Base

    3) InsertQuickReferenceCardintoslot ontopofthermostat.

    1) Lineupthethermostatbodywiththesub-base.2) Carefullypushthethermostatbodyagainstthe sub-baseuntilitsnapsinplace.

  • BACK NEXT

    Installer Guide 8

    3 Quick Reference

    1

    2

    3 4

    7 8

    9

    10

    11

    5 6

    12

    13

    14

    Room Temperature...................... Displaysthecurrentroomtemperature

    Set Temperature.......................... Displaysthecurrentsetpointtemperature

    BACK Indicator*........................... BACKbuttonisactive

    NEXT Indicator*............................ NEXTbuttonisactive

    Outdoor Temperature Indicator... Displaysalongwiththeoutdoortemperaturereading**

    Service Indicators ...................... Displaysvariousservice/maintenanceinformation

    Fan Indicator................................ Indicateswhenthesystemfanisrunning

    Low Battery Indicator.................. Indicateswhenthebatteriesneedtobereplaced

    Hold Mode Indicator ................... IndicatesifthethermostatisinHOLDmode

    Lock Mode Indicator ................... Indicatesifthethermostatislocked

    System Status Indicator ............. Displaysinformationaboutthestatusofthesystem

    Day of the Week........................... Displaysthecurrentdayoftheweek

    Program Event Indicator.............. Displaystheprogramevent

    Time of Day ................................. Displaysthecurrenttimeofday

    1

    2

    3

    4

    5

    6

    7

    8

    9

    10

    11

    Thermostat Display

    12

    13

    14

    *BACKand NEXTaresecondaryfunctionsofthePROGandHOLDbuttons.Wheninprogrammingor configurationmodes,BACKandNEXTappearinthedisplayscreenindicatingthatthePROGand HOLDbuttonsnowfunctionasBACKandNEXT.

    **Alsosee#24onpage9.

  • 9 Installer Guide

    INSTRUCTIONS

    DAY/TIME

    BACK NEXT

    15

    16

    23

    17 18 19 20 21

    22

    Room Temperature...................... Displaysthecurrentroomtemperature

    Set Temperature.......................... Displaysthecurrentsetpointtemperature

    BACK Indicator*........................... BACKbuttonisactive

    NEXT Indicator*............................ NEXTbuttonisactive

    Outdoor Temperature Indicator... Displaysalongwiththeoutdoortemperaturereading**

    Service Indicators ...................... Displaysvariousservice/maintenanceinformation

    Fan Indicator................................ Indicateswhenthesystemfanisrunning

    Low Battery Indicator.................. Indicateswhenthebatteriesneedtobereplaced

    Hold Mode Indicator ................... IndicatesifthethermostatisinHOLDmode

    Lock Mode Indicator ................... Indicatesifthethermostatislocked

    System Status Indicator ............. Displaysinformationaboutthestatusofthesystem

    Day of the Week........................... Displaysthecurrentdayoftheweek

    Program Event Indicator.............. Displaystheprogramevent

    Time of Day ................................. Displaysthecurrenttimeofday

    *BACKand NEXTaresecondaryfunctionsofthePROGandHOLDbuttons.Wheninprogrammingor configurationmodes,BACKandNEXTappearinthedisplayscreenindicatingthatthePROGand HOLDbuttonsnowfunctionasBACKandNEXT.

    **Alsosee#24onpage9.

    24

    Reset Button ............................... Resetscurrenttime,programandusersettings SYSTEM Button............................ Selectsthesystemyouwanttocontrol

    DAY/TIME Button.......................... Setsthecurrenttimeanddayoftheweek

    PROG Button................................. Selectsprogrammingmodeorpressfor3secondstoselectSpeedSet® BACK Button*............................... SecondaryfunctionofthePROGbutton-movesbackasetting

    HOLD Button................................. Enters/ExitstheHOLDmode(programbypass) NEXT Button*............................... SecondaryfunctionoftheHOLDbutton-movestonextsetting

    RETURN Button............................ Returnstonormalmodefromprogramorsettingmodes

    FAN Button................................... Selectsthesystemfanmode

    Quick Reference Instructions...... Storedinslotlocatedattopofthermostat

    SpeedBar® ................................... Increasesordecreasessettings(time,temperature,etc.)

    Outdoor Temperature................... IfaBraeburn®outdoorsensorwasconnectedyoucanviewtheoutdoor temperaturebypressingthePROGandHOLDbuttonsatthesametime.

    Installer Clear Button................... Locatedonbackofthermostatbody-clearsallsettings

    Battery Compartment.................. Locatedinthebackofthermostat

    Thermostat15

    16

    17

    18

    19

    20

    21

    22

    23

    24

    *BACKand NEXTaresecondaryfunctionsofthePROGandHOLDbuttons.Wheninprogrammingor configurationmodes,BACKandNEXTappearinthedisplay,indicatingthatthePROGandHOLDbuttons nowfunctionasBACKandNEXT.

  • INSTRUCTIONS

    DAY/TIME

    TheInstallerSettingsmustbeproperlyconfiguredinorderforthisthermostattooperatecorrectly.TheInstallerSettingsaremenudriven.Theportionofthesesettingsthatdonotapplytoyoursetupwillbeskipped.Thesesettingsareindicatedbelowwithcomments.Moredetailoneachsettingfollowsthistable.

    Installer Guide 10

    1. PressandholddowntheRETURNand buttonsfor3seconds.2. Releasebothbuttonsandthefirstinstaller settingwillbedisplayed.3. Changesettingsasrequiredusingthe orportionoftheSpeedBar®.4. PressNEXT (HOLD)orBACK (PROG)to movetothenextorprevioussetting, pressRETURNtoexit.

    No. Installer Setting Factory Setting Comments (Notes follow this table) Default Options (More information follows this table)

    1 Residentialor RES RES SelectforResidentialprofile orCommercialProfile COMM SelectforCommercialprofile2 ProgrammingMode 7PROG 7PROG Selectfor7dayprogrammingmode [note 1] 52PROG Selectfor5-2dayprogrammingmode NOPROG Selectfornon-programmablemode3 ClockFormat 12HR 12HR Selectfor12hourclock 24HR Selectfor24hourclock4 TemperatureScale FDEG FDEG SelectforFahrenheitdisplay CDEG SelectforCelsiusdisplay5 AutoChangeover oFAUTO oFAUTO DisablesAutoChangeovermode ONAUTO EnablesAutoChangeovermode 11CONV Selectfor1H/1CConventionalsystem 22CONV Selectfor2H/2CConventionalsystem 6 SystemType 11CONV 11HP Selectfor1H/1CHeatPumpsystem 22HP Selectfor2H/2CHeatPumpsystem 32HP Selectfor3H/2CHeatPumpsystem 1HD SelectforHeatOnlyHydronicsystem 11HD SelectforHydronicHeat/1Csystem7 1stStageDifferential 0.5DIF1 0.5,1.0or Selecta1ststagetemperaturedifferentialof.5°, 2.0DIF1 1°or2°F(.25°,.5°or2°C)8 2ndStageDifferential 2.0DIF2 1.0,2.0,3.0, Selecta2ndstagetemperaturedifferentialof1°, [note 2] 4.0,5.0or 2°,3°,4°,5°or6°F(.5°,1°,1.5°,2°,2.5°or3°C) 6.0DIF29 3rdStageDifferential 2.0DIF3 1.0,2.0,3.0, Selecta3rdstagetemperaturedifferentialof1°,2°, [note 2] 4.0,5.0or 3°,4°,5°or6°F(.5°,1°,1.5°,2°,2.5°or3°C) 6.0DIF3

    4 Installer Settings

    NOTE: Shaded areas below do not apply to the 5020.

    INSTRUCTIONS

    DAY/TIME

    BACK NEXT

  • 11 Installer Guide

    No. Installer Setting Factory Setting Comments (Notes follow this table) Default Options (More information follows this table)

    10 1stStageFanControl HGFAN1 HGFAN1 Selectfor1ststageGasheating [note 3] HEFAN1 Selectfor1ststageElectricheating 11 EmergencyHeat] HEEMER HEEMER SelectforElectricEmergencyHeat FanControl[note 4] HGEMER SelectforGasEmergencyHeat 12 ReversingValve REVO REVO SelectforcoolactiveReversingValve(Oterminal) (O/BTerminal)[note 5] REVB SelectforheatactiveReversingValve(Bterminal) 13 FossilFuel AEAUX AEAUX SelectforElectricAuxiliaryheat(withcompressor) BackupHeat[note 4] AGAUX SelectforGasAuxiliaryheat(withoutcompressor) 14 CompressorPowerOutage oFCPOP oFCPOP DisablesPowerOutageLockoutDelay Protection [notes 4, 6] onCPOP EnablesPowerOutageLockoutDelay 15 ACPowerInterrupt ACoFMONR ACoFMONR DisablesACPowerInterruptWarning Warning[note 6] AConMONR EnablesACPowerInterruptWarning 16 CompressorShort 5CSCP 5,4,3,2or Selectacompressorshortcycleprotectiondelayof5, CycleProtection[note 7] 0CSCP 4,3,2or0minutes 17 ResidualCooling 60FAN 90,60,30 SelectaResidualCoolingFanDelayof90,60, FanDelay[note 7] or0FAN 30or0seconds. 18 AdaptiveRecovery oFREC oFREC DisablesAdaptive(early)Recoverymode Mode(ARM™) [note 8] onREC EnablesAdaptive(early)Recoverymode 19 IndoorRemoteSensor ISENS ISENS Temperatureissensedfromthermostatonly. Control*[note 9] ESENS Temperatureissensedfromremotesensoronly. ASENS Temperatureiscombinedwiththethermostatand theremotesensor.

    20 LockoutSecurityLevel 2LOCK 2LOCK Iflocked–Completelockoutisenabled 1LOCK Iflocked–Partiallockoutisenabled(SpeedBar®is stillfunctional)

    21 AutoChangeover 3BAND 2,3,4or5 SelectaDeadBandof2°,3°,4°or5˚F DeadBand[note 10] BAND (1°,2°or3°C)forAutoChangeovermode. 22 CompressorBalance NOBALC NOBALC DisablesBalancePoints Point[notes 4, 11] 15-50BALC SelectaCompressorBalancePointof15°-50°F (-9°-10°C) 23 AuxiliaryHeatBalance NOBALA NOBALA DisablesBalancePoints Point[notes 4, 11] 70-40BALA SelectaAuxiliaryHeatBalancePointof70°-40°F (21°-4°C)

    24 HeatSetPointUpperLimit 90LIM 90-60LIM SelectaHeatSetPointUpperLimitof90°-60°F(32°-10°C)

    25 CoolSetPointLowerLimit 45LIM 45-80LIM SelectaCoolSetPointLowerLimitof45°-80°F(7°-27°C) [note 7]

    *WhenaBraeburn®outdoorsensorisconnected,thethermostatautomaticallyrecognizesit.PressPROGandHOLDatthesametimetodisplayoutdoortemperature.

    NOTE: Additional options such as Service Monitors, setting the lock code, etc. are located in the User Settings – See User manual for information on setting these options.

  • Installer Guide 12

    NOTES - Installer Settings

    1 OnlyavailableifResidentialprofilewasselectedinoption1.2 Onlyavailableifa2or3stagesystemtypewasselectedinoption6.3 OnlyavailableifaConventionalsystemwasselectedinoption6.4 Onlyavailableifa2or3stageHeatPumpsystemwasselectedinoption6.5 OnlyavailableifaHeatPumpsystemwasselectedinoption6.6 Onlyavailableifthe24VoltACcommonwireisconnectedtotheCterminal.7 Notavailableifaheatonlyhydronicsystemisselectedinoption6.8 Onlyavailableifaprogrammableprofilewasselectedinoption2.9 OnlyavailableifaBraeburn®indoorremotesensorwasconnected.10 Onlyavailableifautochangeoverwasenabledinoption5.11 OnlyavailableifaBraeburnoutdoorsensorwasconnected.

    Detailed Explanation of Installer Settings (also see NOTES above):

    1 Profile–Selectsaresidential(RES)orcommercial(COMM)profile.Ifresidentialisselected,4programming eventsperdayareavailable.Ifcommercialisselected,2event,7dayprogrammingisavailable.

    2 Programming Mode [note 1]–Selectstheprogrammingmode,eitherfull7dayor5-2day(weekday/ weekend)programmingornon-programmable.

    3 Clock Type–Selectseithera12houror24hourclock.

    4 Temperature Scale–Selectsatemperaturescaleofeither°For°C.

    5 Auto Changeover–Selectsautochangeoveronoroff.Whenautochangeovermodeisenabledand selected,thesystemautomaticallyswitchesbetweenheatingandcoolingmodes.Thereisa5minutedelay whenswitchingfromheatingtocoolingorcoolingtoheatinginautochangeovermode. NOTE: Also see “Auto Changeover Dead Band” in option 21.

    6 System Type–Selectsthesystemtypeforyourinstallation.NOTE: Changes made to this option will reset options 7 through 15 back to their default values dependant on the system type.

    7 1st Stage Differential–Selectsa1ststagetemperaturedifferential.

    8 2nd Stage Differential [note 2]–Selectsa2ndstagetemperaturedifferential.

    9 3rd Stage Differential [note 2]–Selectsa3rdstagetemperaturedifferential.

    10 1st Stage Fan Control [note 3]–Selectsa1ststagefancontrolofeithergasorelectricheat.

    11 Emergency Heat Fan Control [note 4]–Selectsemergencyheatfancontrolofeithergasorelectricheat.

    12 Reversing Valve [note 5]–SelectstheoutputstateoftheO/Bterminal.SelectOforthisterminaltobe activeinthecoolmodeorselectBforthisterminaltobeactiveintheheatmode.

    13 Auxiliary Fossil Fuel Heat Pump Control [note 4]–Whensettoelectric(AEAUX),boththecompressor (1ststage)andauxiliarystage(s)willrunwhenacallforauxiliaryheatismade.Whensettogas(AGAUX), thecompressorstage(s)willbelockedoutoneminuteafteracallforauxiliaryheat.NOTE: This option can be overridden if setting an auxiliary heat balance point in Option 23.

    14 Compressor Power Outage Protection [notes 4, 6]–Selectspoweroutageprotectiononoroff.When enabled,thisthermostatwillprovidecoldweathercompressorprotectionbylockingoutthecompressor stage(s)ofheatingforaperiodoftimeafterapoweroutagegreaterthan60minutes.

  • 13 Installer Guide

    15 AC Power Interrupt Warning [note 6]–Whenenabled,thethermostatwilldisplayanoutagewarning whenACpowertothethermostatislost.

    16 Short Cycle Protection [note 7]–Selectsthenumberofminutesthecoolingcompressorwillbelocked outafterturningoff.Thisshortcycleprotectionisalsoactiveintheheatmodeifaheatpumpsystemwas selectedinOption6.

    17 Residual Cooling Fan Delay [note 7]–Selectsadelayforthesystemfanafterthecoolingcompressor hasturnedoff.Thisdelaywillhelpremovetheremainingcoolairoutoftheductworkprovidingadditional efficiency.

    18 Adaptive Recovery Mode (early recovery) [note 8]–EnablesordisablestheARMTM(adaptiverecovery mode)feature.DuringARM,roomtemperatureisrecoveredbyturningontheheatingorcoolingbeforethe endofthesetbackperiod.Thesetpointtemperatureischangedtothatoftheupcomingprogramtemperature.

    19 Indoor Remote Sensor Control [note 9]–IfaBraeburn®indoorremotesensorisconnectedduring installation,thethermostatwillautomaticallydetectthesensor.Whenanindoorsensorisdetected,youmay selectbetweenthermostatonly(ISENS),remotesensoronly(ESENS)orcombiningthethermostatandthe remotesensor(ASENS).NOTE: This option does not apply to a Braeburn outdoor sensor. When an outdoor sensor is connected the thermostat automatically recognizes it and no further configuration is necessary.

    20 Lockout Security Level–Selectsthelevelofkeypadlockoutwhenthethermostatislocked.Level2locks theentirethermostat(includingthefrontresetbutton).Level1lockseverythingexcepttheSpeedBar® allowingforupanddowntemperatureadjustment.NOTE: The lock code is set in the User Settings mode (see User Manual).

    21 Auto Changeover Dead Band [note 10]–Whenautochangeovermodeisenabledinoption5and selected,thesystemautomaticallyswitchesbetweenheatingandcoolingwhentheroomtemperature meetsthenormalcriteriaforeitheraheatingorcoolingcall.Thereisaforcedseparation(deadband) betweentheheatingandcoolingsetpointssothatthesystemsdonotworkagainsteachother.This optionselectstheamountofthisdeadbandindegreeswiththedefaultbeing3°F.

    22 Compressor Balance Point [notes 4, 11]–Locksouttheuseofthecompressorheatstagewhenthe outsideairtemperatureislessthantheselectedsettingof15°Fto50°F(-9°Cto10°C)

    23 Auxiliary Heat Balance Point [notes 4, 11]–Locksouttheuseoftheauxiliaryheatstagewhenthe outsideairtemperatureexceedstheselectedsettingof70°Fto40°F(21°Cto4°C).NOTE: This balance point overrides the fossil fuel compressor lockout in option 13. If this option is set to gas and the outdoor temperature is over the auxiliary balance point, the compressor will remain on during a call for auxiliary heat.

    24 Heat Set Point Upper Limit–Selectstheheatingsetpointupperadjustmentlimit.

    25 Cool Set Point Lower Limit [note 7]–Selectsthecoolingsetpointloweradjustmentlimit.

  • Installer Guide 14

    Warning Read Before Testing

    • Donotshort(orjumper)acrossterminalsonthegasvalveorattheheatingorcoolingsystemcontrolboard totestthethermostatinstallation.Thiscoulddamagethethermostatandvoidthewarranty.

    • DonotselecttheCOOLmodeofoperationiftheoutsidetemperatureisbelow50ºF(10ºC).Thiscould possiblydamagethecontrolledcoolingsystemandmaycausepersonalinjury.

    • Thisthermostatincludesanautomaticcompressorprotectionfeaturetoavoidpotentialdamagetothe compressorfromshortcycling.Whentestingthesystem,makesuretotakethisdelayintoaccount.

    NOTE: The compressor delay can be bypassed by pressing the reset button on the front of the thermostat. All user settings will be returned to factory default, however all Installer settings will remain as originally programmed in section 4. 1 PresstheSYSTEMbuttonuntilthethermostatisinHEATmode.2 UsingtheSpeedBar®raisethesettemperatureaminimumof3degreesabovethecurrentroom temperature.Thesystemshouldstartwithinafewseconds.Withagasheatingsystem,thefanmay notstartrightaway.3 PressSYSTEMuntilthethermostatisintheOFFmode.Allowtheheatingsystemtofullyshutdown.4 PressSYSTEMuntilthethermostatisintheCOOLmode.5 UsingtheSpeedBarlowerthesettemperatureaminimumof3degreesbelowthecurrentroom temperature.Thesystemshouldstartwithinafewseconds(unlesscompressorshortcycleprotection isactive–Seenoteabove).6 PressSYSTEMuntilthethermostatisintheOFFmode.Allowthecoolingsystemtofullyshutdown.7 PressFANuntilthethermostatisinFANONmode.Thesystemfanshouldstartwithinafewseconds.8 PressFANuntilthethermostatisinFANAUTOmode.Allowthesystemfantoturnoff.

    5 System Testing

  • ®

    Store this manual for future reference.

    Limited WarrantyWheninstalledbyaprofessionalcontractor,thisproductisbackedbya5yearlimitedwarranty.Limitationsapply.Forlimitations,termsandconditions,youmayobtainafullcopyofthiswarranty:

    ·Visitusonline:www.braeburnonline.com/warranty

    ·Phoneus:866.268.5599

    ·Writeus:BraeburnSystemsLLC2215CornellAvenueMontgomery,IL60538

    5 YEAR WARRANT YLIMITED

    BraeburnSystemsLLC2215CornellAvenue•Montgomery,IL60538TechnicalAssistance:www.braeburnonline.comCallustoll-free:866-268-5599(U.S.)630-844-1968(OutsidetheU.S.)

    ©2013BraeburnSystemsLLC•AllRightsReserved•MadeinChina.

    ®

    5020W-100-02