AUGUST 2016 I NEW ZEALAND Design Manual Bracing

Design ManualDIRECT FIX) 36 19 BRACING FIGURES (CAVITY FIX) 39 20 BRACING CONNECTION FIGURES (CAVITY FIX) 41 21 STRUCTUAL CEILING DIAPHRAGM 44 22 FLOOR DIAPHRAGM 45 23 BRACING CALCULATION5.2

  • Upload
    donhu

  • View
    214

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Design ManualDIRECT FIX) 36 19 BRACING FIGURES (CAVITY FIX) 39 20 BRACING CONNECTION FIGURES (CAVITY FIX) 41 21 STRUCTUAL CEILING DIAPHRAGM 44 22 FLOOR DIAPHRAGM 45 23 BRACING CALCULATION5.2

AUGUST 2016 I NEW ZEALAND

Design Manual

Bracing

Page 2: Design ManualDIRECT FIX) 36 19 BRACING FIGURES (CAVITY FIX) 39 20 BRACING CONNECTION FIGURES (CAVITY FIX) 41 21 STRUCTUAL CEILING DIAPHRAGM 44 22 FLOOR DIAPHRAGM 45 23 BRACING CALCULATION5.2

9 PRODUCT INFORMATION 7

9.1 Manufacturing and Classification 7

9.2 Sizes 7

10 SAFE WORKING PRACTICES 8

11 DETAILS 10

12 BRACING TABLE – INTERNAL LININGS 11

13 BRACING FIGURES – INTERNAL LININGS 12

14 BRACING TABLES – PRE-CLADDING 16

15 BRACING FIGURES – PRE-CLADDING 18

16 BRACING TABLES – CLADDINGS 28

17 BRACING FIGURES CLADDINGS (DIRECT FIX) 30

18 BRACING CONNECTION FIGURES (DIRECT FIX) 36

19 BRACING FIGURES (CAVITY FIX) 39

20 BRACING CONNECTION FIGURES (CAVITY FIX) 41

21 STRUCTUAL CEILING DIAPHRAGM 44

22 FLOOR DIAPHRAGM 45

23 BRACING CALCULATION TABLES 46

PRODUCT WARRANTY 51

1 APPLICATION AND SCOPE 3

1.1 Application 3

1.2 Scope 3

1.3 Details 3

1.4 Specific Design and Detailing 3

2 DESIGN 3

2.1 Compliance 3

2.2 Responsibility 3

2.3 Site and Foundation 4

2.4 Ground Clearances 4

2.5 Moisture Management 4

2.6 Wind Loading 4

2.7 Height of Bracing Panels 4

2.8 Bracing Sheets Stopped Below Top Plate 4

2.9 Bracing in Wet Area & Water Splash Areas 4

2.10 Impact Resistance 4

2.11 Maximum Bracing Units 4

2.12 Specific Engineering Design 4

2.13 Bracing Calculation 4

3 TIMBER FRAMING 5

3.1 General 5

3.2 Dimensions 5

3.3 Structural Grade 5

3.4 Tolerances 5

3.5 Durability 5

3.6 Frame Construction 5

3.7 Bottom Plate Fixing 5

4 PREPARATION 5

4.1 General 5

4.2 Flexible Underlay or HomeRAB® Pre-Cladding 5

4.3 Window and Door Installation 5

5 SHEET FIXING 6

5.1 Fastener Durability and Size 6

5.2 Sheet Nailing 6

5.3 Sheet Orientation 6

5.4 Sheet Penetrations 6

6 JOINTING 6

6.1 General 6

7 FINISHING 6

7.1 General 6

7.2 Sealants 6

8 MAINTENANCE 7

8.1 General 7

Contents

WE VALUE YOUR FEEDBACKTo continue with the development of our products and systems, we value your input. Please send any suggestions, including your name, contact details, and relevant sketches to:

Ask James Hardie™ Fax 0800 808 988 [email protected]

Page 3: Design ManualDIRECT FIX) 36 19 BRACING FIGURES (CAVITY FIX) 39 20 BRACING CONNECTION FIGURES (CAVITY FIX) 41 21 STRUCTUAL CEILING DIAPHRAGM 44 22 FLOOR DIAPHRAGM 45 23 BRACING CALCULATION5.2

James Hardie Bracing Design Manual August 2016 New Zealand 3

1 Application and scope

1.1 APPLICATIONThe James Hardie fibre cement products listed below are classified as lightweight cladding materials and are suitable to achieve structural bracing in timber framed buildings as per the requirements of NZS 3604 when installed in accordance with the bracing system requirements.

Refer to Table 2 – 14 for bracing system capacity.

The following James Hardie products can be used to achieve bracing:

• Villaboard™ Lining, internal wall lining with recessed or square edges 6mm and 9mm; suitable for wet and dry areas.

• HardieGroove™ Lining, internal wall lining with a 'tongue & groove' look.

• RAB™ Board 6mm* or HomeRAB™ Pre-Cladding 4.5mm, used as rigid air barrier.

• HardieFlex™ Sheet, 6mm and 7.5mm cladding suitable for board and batten or used with other jointing options.

• Monotek™ Sheet, 7.5mm and 9mm cladding suitable for textured monolithic looks.

• Axon™ Panel, 9mm suitable for external wall claddings. with a ‘Vertical Grooved’ look.

• Linea™ Weatherboard, a 16mm thick external wall cladding in three different widths, 135mm, 150mm and 180mm.

*RAB Board used for stucco plaster is classified as medium weight cladding as per NZS 3604.

If you are a specifier Or other responsible party for a project ensure that the information in this document is appropriate for the application you are planning and that you undertake specific design and detailing for areas which fall outside the scope of these specifications.

If you are an installer Ensure that you follow the design, moisture management principles, associated details and material selection provided by the designer. All details provided in this document must be read in conjunction with this specification.

Make sure your information is up to date When specifying or installing James Hardie products, ensure you have the current manual. If you’re not sure you do, or you need more information, visit www.jameshardie.co.nz or Ask James Hardie on 0800 808 868.

1.2 SCOPEThis manual covers the installation of James Hardie fibre cement sheets and Scyon range of products to achieve structural bracing for timber-framed buildings that fall within the scope of NZS 3604.

To achieve bracing ratings published in this literature, each product must be fixed in accordance with its respective details published in this manual.

1.3 DETAILSThe bracing system details provided in this document are available in CAD format on our website www.jameshardie.co.nz.

1.4 SPECIFIC DESIGN AND DETAILINGFor specific design outside the scope of this literature, the designer / architect or engineer responsible for the project must undertake specific design.

2 Design2.1 COMPLIANCEAll James Hardie products as mentioned in Section 1.1 have been tested at SCION as per BRANZ P21 test method to determine their bracing capacity and bracing systems have been developed to meet the requirements of NZS 3604. James Hardie products, when installed and maintained in accordance to James Hardie technical specification requirements, comply with the requirements of B1/AS1 Structure, B2/AS1 Durability and E2/AS1 External Moisture clauses of the New Zealand Building Code (NZBC).

2.2 RESPONSIBILITYThe specifier or other party responsible for the project must run through a risk matrix analysis as per E2/AS1 to determine which construction method is applicable to install the external cladding on the project. The designer must also ensure that the bracing capacities published in this specification are appropriate for the intended application. The designer is responsible to calculate the bracing requirement for a building. The designers must also ensure that the intent of their design meets the requirements of the NZBC.

Substitution of James Hardie fibre cement product with any other product will change the bracing capacity of a system and James Hardie accepts no liability due to this. James Hardie bracing systems are not generic and therefore they must only be installed as per James Hardie bracing details using a James Hardie product.

All dimensions shown are in millimetres unless noted otherwise. All New Zealand Standards referenced in this manual are current edition and must be complied with.

James Hardie conducts stringent quality checks to ensure that any product manufactured falls within our quality spectrum. It is the responsibility of the builder to ensure that the product meets aesthetic expectation before installation. James Hardie will not be responsible for rectifying the obvious aesthetic surface variations in product after its installation.

Page 4: Design ManualDIRECT FIX) 36 19 BRACING FIGURES (CAVITY FIX) 39 20 BRACING CONNECTION FIGURES (CAVITY FIX) 41 21 STRUCTUAL CEILING DIAPHRAGM 44 22 FLOOR DIAPHRAGM 45 23 BRACING CALCULATION5.2

4 James Hardie Bracing Design Manual August 2016 New Zealand

Minimum Height: For bracing panels which are less than 2.4m height, the bracing rating is to be used as for a 2.4m high wall.

2.8 BRACING SHEETS STOPPED BELOW TOP PLATE

Where a bracing sheet is stopped below the top plate an extra row of nogs (dwangs) must be installed below the top plate to facilitate the bracing sheet fixing. The minimum bracing wall height is 1.8m. Refer to Figure 19 for details.

2.9 BRACING IN WET AREA & WATER SPLASH AREAS

Villaboard Lining can be used to achieve bracing in internal wet areas (shower) when the sheet is covered by an impervious lining eg. HardieGlaze™ Lining / vinyl / acrylic shower lining.

When using tiles over a braced wall, designer/builder must ensure that the water proofing membrane used under the tiles meets 50 years durability requirements as per clause 2.3.1 (a) of B2 of the NZBC.

2.10 IMPACT RESISTANCEThe products covered in this manual have adequate impact resistance which is likely to occur during the normal use of the building.

The impact resistance does not apply to rigid air barriers as they are covered by a cladding.

2.11 MAXIMUM BRACING UNITSA maximum of 150 BU/m can be achieved for concrete floors and 120 BU/m can be achieved for timber floors in buildings within the scope of NZS 3604. Higher bracing ratings will exceed the structural capacity of foundations, slabs and anchors etc and therefore requires a specific engineering design input.

2.12 SPECIFIC ENGINEERING DESIGNFor some bracing systems using James Hardie product, bracing ratings higher than 150BU’s/m can be achieved. Refer to Tables 2 to 14. As mentioned above, a specific engineering design must be undertaken to strengthen the concrete foundation, this may require increasing foundation thickness or the edge distance between hold down bolts and outer edge of slab. The structural engineer should be satisfied that a higher hold down strength of up to 20kN can be achieved through the bottom plate connections in order to achieve higher bracing rating.

2.13 BRACING CALCULATIONRefer to the online James Hardie bracing calculation tool at www.jameshardie.co.nz. This tool enables a quick calculation of bracing demand and the selection of suitable bracing systems.

You can also use manual bracing calculation sheets provided in section 23 of this manual.

2.3 SITE AND FOUNDATIONThe site on which the building is situated must comply with Surface Water Clause E1 of NZBC. The grade of adjacent finished ground must slope away from the building to avoid any possibility of water accumulating.

Foundation design must comply with the requirements of NZS 3604 Timber Framed Buildings.

2.4 GROUND CLEARANCESThe clearance between the bottom edge of claddings and paved/unpaved ground must comply with section 9.1.3 of E2/AS1. The finished floor level must also comply with these requirements. These clearances must be maintained throughout the life of the building.

James Hardie claddings must overhang the bottom plate by a minimum of 50mm as required by NZS 3604 and E2/AS1 of NZBC.

On the roofs and decks the minimum clearance must be 50mm.

Do not install external cladding such that it may remain in contact with the ground.

2.5 MOISTURE MANAGEMENTIt is the responsibility of the specifier to identify moisture related risks associated with any particular building design.

Wall construction design must effectively manage moisture, considering both the interior and exterior environments of the building, particularly in buildings that have a higher risk of wind driven rain penetration or that are artificially heated or cooled.

Walls shall include those provisions as required by NZBC Acceptable Solution E2/AS1 External Moisture. In addition, all wall openings, penetrations, junctions, connections, window sills, heads and jambs must incorporate appropriate flashings for waterproofing. The other materials, components and installation methods used to manage moisture in external walls, must comply with the requirements of relevant standards and NZBC.

2.6 WIND LOADINGJames Hardie bracing systems are suitable for use in all wind zones as defined in NZS 3604. For wind speeds more than 55m/sec, (EH wind zone) a specific engineering design must be undertaken by the designer to calculate the bracing capacity required.

2.7 HEIGHT OF BRACING PANELSMaximum Height: The standard height of James Hardie bracing systems is 2.4m. For bracing panels which exceed the 2.4m height, the bracing rating is to be reduced by a multiplication factor of 2.4/H, where H is the bracing panel height. Dimension H, however, must be limited to maximum of 4.8m. Refer also to clauses 8.3.1.4 (a) and (b) of NZS 3604.

Page 5: Design ManualDIRECT FIX) 36 19 BRACING FIGURES (CAVITY FIX) 39 20 BRACING CONNECTION FIGURES (CAVITY FIX) 41 21 STRUCTUAL CEILING DIAPHRAGM 44 22 FLOOR DIAPHRAGM 45 23 BRACING CALCULATION5.2

James Hardie Bracing Design Manual August 2016 New Zealand 5

3.7 BOTTOM PLATE FIXING / HOLD DOWN RESTRAINTS

The bottom plate must be fixed in accordance to table 8.19 of NZS 3604. Bracing hold down restraints must be provided as per bracing system’s requirements. Refer to bracing systems details.

3.7.1 Concrete foundationPydra brace anchor kits or GIB Handibrac® with a 15kN minimum uplift capacity holding down bolt can be used as end restraints.

3.7.2 Timber foundationPydra brace anchor kits or GIB Handibrac® with a 15kN minimum uplift capacity holding down bolt can be used as end restraints. Alternatively holding down straps can also be used. Refer to Figure 23.

4Preparation4.1 GENERAL All fibre cement sheets and Scyon range of products must be kept dry and under cover whilst in storage prior to fixing.

4.2 FLEXI LE UNDERLAY OR HOMERAB PRE-CLADDING

Flexible underlay used must comply with the performance requirements of Table 23 of E2/AS1. The underlay must be installed in accordance with E2/AS1 and their manufacturer’s requirements.

In buildings within the scope of NZS 3604 HomeRAB Pre-Cladding can also be used to replace flexible underlay. HomeRAB Pre-Cladding has been tested and complies with the requirements of Table 23 of E2/AS1. Walls which are not lined on inside face e.g. garage walls or gable ends etc. must include a rigid sheathing or an air barrier behind the wall cladding. HomeRAB Pre-Cladding is suitable for use in these applications, up to and including VH wind zone.

4.3 WINDOW AND DOOR INSTALLATIONAll windows and doors must be detailed such that they meet the requirements of E2/AS1, Clause 2.0.1. Refer also to NZS 3604 and the joinery provider.

3 Timber framing

3.1 GENERALThese James Hardie bracing systems are suitable for timber framed buildings within the scope of NZS 3604. The framing must comply with the minimum requirements of NZS 3604 Timber Framed Buildings. Where the framing is provided as per the specific engineering design, the minimum framing stiffness must be equivalent to or more than the stiffness requirements of NZS 3604.

Bracing capacities/ratings and fixing specifications are provided for each system in the respective details developed for each product.

3.2 DIMENSIONSA minimum 90x45mm stud size is required for bracing systems. Refer to James Hardie product technical specification for specific framing requirements.

3.3 STRUCTURAL GRADEMinimum timber grade requirement is SG8 framing grade used as per NZS 3604. The grading of timber should comply with NZS 3631 and AS/NZS 1748 requirements. Higher stress grade such as MSG10 can be used where needed.

3.4 TOLERANCESIn order to achieve an acceptable wall finish, it is imperative that framing is straight and true.

Framing tolerances must comply with the requirements of NZS 3604. All framing shall be made flush.

3.5 DURABILITYThe external framing must be treated to a minimum H1.2 treatment. Refer to NZBC Acceptable Solution B2/AS1 Durability for further information about the durability requirements.

For timber treatment and allowable moisture content information refer to NZS 3602 (Timber and Wood-Based Products for use in Buildings) and NZS 3640 (Chemical Preservation of Round Sawn Timber) for minimum timber treatment selection and treatment requirements.

3.6 FRAME CONSTRUCTIONTimber framing must comply with NZS 3604 Section 8 and provided as per the following requirements.

Also refer to framing manufacturers’ specifications before installation.

• Studs must be provided at 600mm centres maximum.

• Nogs or dwangs must be provided at 1200mm centres maximum.

• When a cladding is fixed over the cavity battens, the nogs spacing is required to be provided at 800mm centres maximum. Refer to Section 9.1.8.5 of E2/AS1.

Page 6: Design ManualDIRECT FIX) 36 19 BRACING FIGURES (CAVITY FIX) 39 20 BRACING CONNECTION FIGURES (CAVITY FIX) 41 21 STRUCTUAL CEILING DIAPHRAGM 44 22 FLOOR DIAPHRAGM 45 23 BRACING CALCULATION5.2

6 James Hardie Bracing Design Manual August 2016 New Zealand

5Sheet fixing

5.1 FASTENER DURABILITY AND SIZECoach screws and holding down (HD) bolts, where used, must be M12 hot-dipped galvanised steel fitted with 50 x 50 x 3mm galvanised washers. These must have a protective coating as per Table 4.2 of NZS 3604.

PRE-CLADDINGS:All nails for fixing the pre-cladding bracing panels for Zone D must be Grade 304/316 stainless steel in accordance with NZS 3604.

All nails for fixing the pre-cladding bracing panels for Zone B and Zone C can be Grade 304/316 stainless steel or hot dipped galvanised steel nail.

CLADDINGS:All nails for fixing the bracing panels in external cladding applications must be Grade 304/316 stainless steel in accordance with NZS 3604.

LININGS:For dry area internal applications the standard hot dipped galvanised nails can be used. For wet area internal applications stainless steel nails must be used.

Note: Fastener sizes are given in the respective details section for each product or system.

5.2 SHEET NAILINGNails must be hand driven at a minimum edge distance as shown in the bracing details within this specification. This also applies to dimensions from corners, vertically and horizontally. The sheets must be held hard against the framing during nailing to minimise sheet break-out at the back of sheet. Always drive all nails flush with the sheet surface. For sheet/panel systems do not punch the nail below the surface as it reduces the nail’s holding power.

Fix all sheets from the centre working towards outer edges to avoid drumminess.

Note: Do not use gun nails for bracing applications.

5.3 SHEET ORIENTATIONFor the bracing systems specified in this manual, all flat sheets must be fixed vertically with the exception of Villaboard Lining, which can either be fixed vertically or horizontally as per the bracing systems details.

Full-height sheets without joints must be used for walls up to 3000mm in height. When bracing walls exceed 3000mm in height, only one horizontal sheet joint is permitted within the element height. The maximum height of bracing wall is limited to 4800mm.

A site cut bracing sheet must be minimum 300mm wide when used in a bracing element.

Always ensure that the sheet joint is on the centre line of the stud or nog to achieve sufficient cover of fixings.

In internal walls the lining sheet used for bracing must stop 6mm up from the bottom of the bottom plate.

5.4 SERVICE PENETRATIONSHoles/penetrations up to 100 x 100mm positioned no closer than 200mm to the edge of lining or another penetration, are allowed for services. Maximum of two service penetrations are recommended per sheet.

No window/door penetrations are allowed within the bracing elements.

6 Jointing

6.1 GENERALControl joints in flush finished or monolithic claddings are required to accommodate movement created by shrinkage and thermal movement of plasters.

Expansion joints are provided in timber walls to allow for long-term frame movement that occurs due to structural loading and timber shrinkage.

Control joints and expansion joints must be determined at the design stage. For further guidance on jointing refer to the BRANZ publication ‘Good Stucco Practice’.

When bracing walls contain control joint and expansion joints, the panels must be separated into separate bracing elements on either side of the joint.

7Finishing7.1 GENERALProtective coating of James Hardie fibre cement sheet cladding and Linea Weatherboards is required in order to meet the durability requirements of the NZBC and to be covered under the James Hardie Product Warranty. Claddings must be painted within 90 days of installation. Use only quality exterior paints complying with AS 3730. Manufacturer’s specification for the selected paint must be followed. Note that certain special paints require an undercoat before applying the finish coat. Refer to the relevant paint manufacturer for preparation required before commencing the coating work.

7.2 SEALANTSAll sealants must demonstrate they meet the relevant requirements of NZBC. Application and use of sealants must comply with the manufacturer’s instructions. Check with the sealant manufacturer prior to coating over sealants as some sealant manufacturers do not recommend coating over their product.

Page 7: Design ManualDIRECT FIX) 36 19 BRACING FIGURES (CAVITY FIX) 39 20 BRACING CONNECTION FIGURES (CAVITY FIX) 41 21 STRUCTUAL CEILING DIAPHRAGM 44 22 FLOOR DIAPHRAGM 45 23 BRACING CALCULATION5.2

James Hardie Bracing Design Manual August 2016 New Zealand 7

8Maintenance

8.1 GENERALThe extent and nature of maintenance will depend on the geographical location and exposure of the building. As a guide, it is recommended that basic normal external maintenance tasks shall include but not be limited to;

FOR EXTERNAL CLADDINGS:• Washing down exterior surfaces every 6-12 months*

• Re-applying of exterior protective finishes if necessary**

• Maintaining the exterior envelope and connections including joints, penetrations, flashings and sealants that may provide a means of moisture entry beyond the exterior cladding

• Cleaning out gutters, blocked pipes and overflows as required

• Pruning back vegetation that is close to or touching the building

• The clearances between the bottom of cladding and top of ground or paved surface must always be maintained

• Any surface drains running next to a wall cladding must be kept clear of debris to avoid blockage and flooding.

* Do not use a water blaster to wash down the claddings

* In extreme coastal conditions or sea spray zones, wash every 3-4 months. ** Refer to your paint manufacturer for washing down and recoating requirements related to paint performance.

FOR INTERNAL CLADDINGS:It is recommended that basic normal internal maintenance tasks shall include but not be limited to;

• Integrity of various coatings maintained* **

• Maintaining the interior envelope and connections including joints, penetrations, flashings and sealants that may provide a means of moisture ingress

* Do not use a water blaster to wash down the lining ** Refer to your paint manufacturer for washing down and recoating requirements related to paint performance.

9 Product information

9.1 MANUFACTURING AND CLASSIFICATION

James Hardie New Zealand Limited is an ISO 9001 Telarc certified manufacturer. Linea Weatherboards and flat sheets are manufactured in accordance with AS/NZS 2908.2. ‘Cellulose Cement Products’, which is equivalent to ISO 8336 ‘Fibre Cement Flat Sheets’.

Each of the products covered by this manual are identified by its name embossed or printed on either the front or back face of the sheet.

9.2 SIZESRefer to respective current product technical specification for further information about available product sizes.

Page 8: Design ManualDIRECT FIX) 36 19 BRACING FIGURES (CAVITY FIX) 39 20 BRACING CONNECTION FIGURES (CAVITY FIX) 41 21 STRUCTUAL CEILING DIAPHRAGM 44 22 FLOOR DIAPHRAGM 45 23 BRACING CALCULATION5.2

8 James Hardie Bracing Design Manual August 2016 New Zealand

10Safe working practices

WARNING — DO NOT BREATHE DUST AND CUT ONLY IN WELL VENTILATED AREAJames Hardie products contain sand, a source of respirable crystalline silica which is considered by some international authorities to be a cause of cancer from some occupational sources. Breathing excessive amounts of respirable silica dust can also cause a disabling and potentially fatal lung disease called silicosis, and has been linked with other diseases. Some studies suggest smoking may increase these risks. During installation or handling: (1) work in outdoor areas with ample ventilation; (2) minimise dust when cutting by using either ‘Score and Snap’ knife, fibre cement shears or, where not feasible, use a HardieBlade™ Saw Blade and dust-reducing circular saw attached to a HEPA vacuum; (3) warn others in the immediate area to avoid breathing dust; (4) wear a properly-fitted, approved dust mask or respirator (e.g. P1 or P2) in accordance with applicable government regulations and manufacturer instructions to further limit respirable silica exposures. During clean-up, use HEPA vacuums or wet cleanup methods — never dry sweep. For further information, refer to our installation instructions and Safety Data Sheets available at www.jameshardie.co.nz

FAILURE TO ADHERE TO OUR WARNINGS, SAFETY DATA SHEETS, AND INSTALLATION INSTRUCTIONS MAY LEAD TO SERIOUS PERSONAL INJURY OR DEATH.

James Hardie recommended safe working practices

CUTTING OUTDOORS

1. Position cutting station so that wind will blow dust away from user or others in working area.

2. Use one of the following methods based on the required cutting rate:

BESTn Score and snap n Hand guillotine n FibreshearBETTERn Dust reducing circular saw equipped with HardieBlade™

Saw Blade and HEPA vacuum extraction.GOODn Dust reducing circular saw equipped with

HardieBlade™ Saw Blade

CUTTING INDOORS

n Cut only using score and snap, hand guillotine or fibreshears (manual, electric or pneumatic).

n Position cutting station in well-ventilated area

DRILLING/OTHER MACHINING

When drilling or machining you should always wear a P1 or P2 dust mask and warn others in the immediate area.

IMPORTANT NOTES

1. For maximum protection (lowest respirable dust production), James Hardie recommends always using “Best” — level cutting methods where feasible

2. NEVER use a power saw indoors 3. NEVER use a circular saw blade that does not carry the

HardieBlade™ logo4. NEVER dry sweep — Use wet suppression or HEPA

Vacuum5. NEVER use grinders6. ALWAYS follow tool manufacturer’s safety

recommendations

P1 or P2 respirators can be used in conjunction with above cutting practices to further reduce dust exposures. Additional exposure information is available at www.jameshardie.co.nz to help you determine the most appropriate cutting method for your job requirements. If concern still exists about exposure levels or you do not comply with the above practices, you should always consult a qualified industrial hygienist or contact James Hardie for further information.

Page 9: Design ManualDIRECT FIX) 36 19 BRACING FIGURES (CAVITY FIX) 39 20 BRACING CONNECTION FIGURES (CAVITY FIX) 41 21 STRUCTUAL CEILING DIAPHRAGM 44 22 FLOOR DIAPHRAGM 45 23 BRACING CALCULATION5.2

James Hardie Bracing Design Manual August 2016 New Zealand 9

WORKING INSTRUCTIONSRefer to recommended Safe Working Practices before starting any cutting or machining of product.

SCORE AND SNAPScore and Snap is a fast and efficient method of cutting the product using special tungsten tipped Score and Snap Knife.

Preferably score on the face side of the product. Score against a straight edge and repeat the action to obtain adequate depth for clean break — normally 1/3 of sheet thickness. Snap upwards to achieve break. Smooth any rough edges with a rasp.

HAND GUILLOTINEMake guillotine cut on the off-cut side of line to allow for the thickness of the blade.

FIBRESHEAR HEAVY DUTY An electrically powered, fast, clean and effortless way of cutting James Hardie building products, especially around curves such as archways. Make Fibreshear cut on the “off-cut” side of the line to allow for the thickness of the shear.

HARDIEBLADE SAW BLADEThe HardieBlade Saw Blade used with a dust-reducing saw and HEPA vacuum extraction allows for fast, clean cutting of James Hardie fibre cement products. A dust-reducing saw uses a dust deflector or a dust collector connected to a vacuum system. When sawing, clamp a straight-edge to the sheet as a guide and run the saw base plate along the straight edge when making the cut.

HOLE-FORMINGFor smooth clean cut circular holes:Mark the centre of the hole on the sheet. Pre-drill a ‘pilot’ hole.

Using the pilot hole as a guide, cut the hole to the appropriate diameter with a hole saw fitted to a heavy duty electric drill.

For irregular holes:Small rectangular or circular holes can be cut by drilling a series of small holes around the perimeter of the hole then tapping out the waste piece from the sheet face. Tap carefully to avoid damage to sheets, ensuring that the sheet edges are properly supported.

STORAGE AND HANDLINGAll James Hardie building products should be stored to avoid damage, with edges and corners of the sheets protected from chipping.

James Hardie building products must be installed in a dry state and be protected from rain during transport and storage. The product must be laid flat under cover on a smooth level surface clear of the ground to avoid exposure to water or moisture, etc.

QUALITYJames Hardie conducts stringent quality checks to ensure that any product manufactured falls within our quality spectrum. It is the responsibility of the builder to ensure that the product meets aesthetic requirements before installation. James Hardie will not be responsible for rectifying obvious aesthetic surface variations following installation.

Page 10: Design ManualDIRECT FIX) 36 19 BRACING FIGURES (CAVITY FIX) 39 20 BRACING CONNECTION FIGURES (CAVITY FIX) 41 21 STRUCTUAL CEILING DIAPHRAGM 44 22 FLOOR DIAPHRAGM 45 23 BRACING CALCULATION5.2

10 James Hardie Bracing Design Manual August 2016 New Zealand

11DetailsVarious details outlined in the following table are available on Pages 12 to 43.

Table 1DESCRIPTION PAGE

Figure 1: 1200mm Villaboard Lining/HardieGroove Lining with no hold down brackets 12

Figure 2: 400mm or 600mm Villaboard Lining to concrete or timber floor 13

Figure 3: 1200mm or more Villaboard Lining/HardieGroove Lining to concrete or timber floor 14

Figure 4: Villaboard Lining laid horizontally to concrete or timber floor 15

Figure 5: 400mm HomeRAB Pre-Cladding or RAB Board to concrete or timber floor - no hold down brackets 18

Figure 6: 1200mm HomeRAB Pre-Cladding or RAB Board to concrete or timber floor - no hold down brackets 19

Figure 7: 400/600mm HomeRAB Pre-Cladding or RAB Board to concrete or timber floor 20

Figure 8: 1200mm HomeRAB Pre-Cladding or RAB Board to concrete or timber floor 21

Figure 9: HomeRAB Pre-Cladding 400mm to concrete or timber floor - Villaboard Lining side - no hold down brackets

22

Figure 10: HomeRAB Pre-Cladding 1200mm to concrete or timber floor - Villaboard Lining side - no hold down brackets

23

Figure 11: HomeRAB Pre-Cladding/RAB Board 400mm to concrete or timber floor - GIB® Standard Plasterboard - no hold down brackets

24

Figure 12: HomeRAB Pre-Cladding/RAB Board 1200mm to concrete or timber floor - GIB® Standard Plasterboard - no hold down brackets

25

Figure 13: 400mm/600mm HomeRAB Pre-Cladding with 10mm GIB® Standard Plasterboard 26

Figure 14: 1200mm HomeRAB Pre-Cladding with 10mm GIB® Standard Plasterboard 27

Figure 15: 1200mm Panel no hold down brackets 30

Figure 16: 400mm or 600mm Panel to concrete or timber floor 31

Figure 17: 1200mm or more Panel to concrete or timber floor 32

Figure 18: Linea Weatherboard to concrete or timber floor 33

Figure 19: Linea Weatherboard to concrete or timber floor - Villaboard Lining side 34

Figure 20: Linea Weatherboard to concrete or timber floor — GIB® Standard Plasterboard 35

Figure 21: End bracket to concrete slab 36

Figure 22: End bracket to timber joist 36

Figure 23: Hold down straps to timber joist 37

Figure 24: Linea Weatherboard face fixing for bracing 38

Figure 25: Bracing panel stopped below top plate 38

Figure 26: 1200mm or more Panel to concrete or timber floor 39

Figure 27: 2400mm or more Panel to concrete or timber floor 40

Figure 28: 1200mm wide panel to concrete or timber floor 41

Figure 29: Panel to concrete or timber floor — centre paling packer 41

Figure 30: All bracing panel top plate detail 42

Figure 31: 2400mm long panel to concrete or timber floor — centre paling packer 42

Figure 32: Typical vent strip installation 43

Figure 33: Structural ceiling diaphragm 44

Figure 34: Secura Interior Flooring diaphragm floor 45

Page 11: Design ManualDIRECT FIX) 36 19 BRACING FIGURES (CAVITY FIX) 39 20 BRACING CONNECTION FIGURES (CAVITY FIX) 41 21 STRUCTUAL CEILING DIAPHRAGM 44 22 FLOOR DIAPHRAGM 45 23 BRACING CALCULATION5.2

James Hardie Bracing Design Manual August 2016 New Zealand 11

12Bracing table — Internal linings

Table 2

Villaboard Lining Vertically Fixed bracing ratings

SYSTEM NUMBER

BRACING ELEMENT LENGTH (mm)

BRACKETS REFER FIGURES

FLOORING CONSTRUCTION

NZS 3604 RATING IN BRACING UNITS PER METRE OF ELEMENT LENGTH

TIMBER CONCRETE WIND EARTHQUAKE

Vvn 1200 N 1 √ √ 99 86

Vv

400 Y 2, 21, 22 √ √ 81 105

600 Y 2, 21, 22 √ √ 88 85

1200 to 2400 Y 3, 21, 22 √ √ 130* 101

2400 or more Y 3, 21, 22 √ √ 125* 98

Villaboard Lining Horizontally Fixed bracing ratings

Vh 2400 or more Y 4, 21, 22 √ √ 161* 135*

*A limit of 120BUs/m maximum applies to timber floors and 150BUs/m maximum to concrete floors built as per NZS 3604: 2011 unless a specific engineering design is carried out to ensure the uplift force generated by bracing elements does not exceed the maximum limit for each floor type.

Table 3

HardieGroove Lining bracing ratings

SYSTEM NUMBER

BRACING ELEMENT LENGTH (mm)

BRACKETS REFER FIGURES

FLOORING CONSTRUCTION

NZS 3604 RATING IN BRACING UNITS PER METRE OF ELEMENT LENGTH

TIMBER CONCRETE WIND EARTHQUAKE

HGn 1200 N 1 √ √ 101 96

HG 1200 Y 3, 21, 22 √ √ 154* 153*

*A limit of 120BUs/m maximum applies to timber floors and 150BUs/m maximum to concrete floors built as per NZS 3604: 2011 unless a specific engineering design is carried out to ensure the uplift force generated by bracing elements does not exceed the maximum limit for each floor type.

Page 12: Design ManualDIRECT FIX) 36 19 BRACING FIGURES (CAVITY FIX) 39 20 BRACING CONNECTION FIGURES (CAVITY FIX) 41 21 STRUCTUAL CEILING DIAPHRAGM 44 22 FLOOR DIAPHRAGM 45 23 BRACING CALCULATION5.2

12 James Hardie Bracing Design Manual August 2016 New Zealand

13Bracing figures — Internal liningsFigure 1: 1200mm Villaboard™ Lining/HardieGroove™ Lining with no hold down brackets

40 x 2.8mm galvanised or 316 stainless steel HardieFlex™

nails

Timber framing

Villaboard™ Lining I HardieGoove TM Lining

Bottom plate fixed as per NZS 3604

Concrete or timber floor

1601 Wall

Product System Number Minimum Length

Villaboard® Lining Vvn

HardieGroove™ Lining HGn

jhl brce d wall vila01.dwg ®

James Hardie a smarter way™

1200mm

1200mm

August 2016

Bracing Design Details www.ja�:s��:��c�:;�

1200MM OR MORE VILLABOARD®/ LINING/HARDIEGROOVE™ LINING WITH NO HOLDING DOWN BOLTS FIGURE: 1

Product System Minimum length

Villaboard™ Lining Vvn 1200mm

HardieGroove™ Lining HGn 1200mm

Page 13: Design ManualDIRECT FIX) 36 19 BRACING FIGURES (CAVITY FIX) 39 20 BRACING CONNECTION FIGURES (CAVITY FIX) 41 21 STRUCTUAL CEILING DIAPHRAGM 44 22 FLOOR DIAPHRAGM 45 23 BRACING CALCULATION5.2

James Hardie Bracing Design Manual August 2016 New Zealand 13

Product System Minimum length

Villaboard™ Lining Vv 400 or 600mm

Figure 2: 400mm or 600mm Villaboard™ Lining to concrete or timber floor

FIBRE CEMENT FIXING DETAILS Notes for Figure 2:

40 x 2.8mm galvanised or 3 16 stainless steel HardieFlex™

nails

12mm minimum edge distance

Timber framing

Villaboard™ Lining

Bottom plate fixed as per NZS 3604

Concrete or timber floor

• Concrete floor bottom plate fixing:- Ramset bracing anchor kit Concrete or GIB Handibrac® with 15kN anchor at each end of bracing element

• Timber floor bottom plate fixing:- Ramset bracing anchor kit Wood or GIB Handibrac® with a 12x150mm galvanised coach screw at each end of bracing element

Product System Number Minimum Length

Villaboard® Lining Vv 400 or600mm

jhl brce d wall vila02.dwg

1601 Wall

August 2016 ®

James Hardie Bracing Design Details www.ja�:s��:��c�:;�

a smarter way™ 400MM OR 600MM VILLABOARD® LINING TO CONCRETE OR TIMBER FLOOR FIGURE: 2

Page 14: Design ManualDIRECT FIX) 36 19 BRACING FIGURES (CAVITY FIX) 39 20 BRACING CONNECTION FIGURES (CAVITY FIX) 41 21 STRUCTUAL CEILING DIAPHRAGM 44 22 FLOOR DIAPHRAGM 45 23 BRACING CALCULATION5.2

14 James Hardie Bracing Design Manual August 2016 New Zealand

Figure 3: 1200mm or more Villaboard™ Lining/HardieGroove™ Lining to concrete or timber floor

FIBRE CEMENT FIXING DETAILS Notes for Figure 3:

40 x 2.8mm galvanised or 316 stainless steel HardieFlex™

nails

Timber framing

Villaboard™ Lining I HardieGroove ™ Lining

Bottom plate fixed as per NZS 3604

Proprietary hold down �m±�_,,£..--�;i,;-- bolt/bracket at end of bracing

element

Concrete or timber floor

1601 Wall

• Concrete floor bottom plate fixing:- Ramset bracing anchor kit Concrete or GIB Handibrac® with 15kN anchor at each end of bracing element • Timber floor bottom plate fixing:- Ramset bracing anchor kit Wood or GIB Handibrac® with a 12x150mm galvanised coach screw at each end of

bracing element

Product

Villaboard® Lining

HardieGroove™ Lining jhl brce d wall vila03.dwg

®

James Hardie a smarter way™

System Number Minimum Length

Vv 1200mm

HG 1200mm August 2016

Bracing Design Details www.ja�:s��:��c�:;�

1200MM OR MORE VILLABOARD® LINING/HARDIEGROOVE™ LINING TO TIMBER OR CONCRETE FLOOR FIGURE: 3

Product System Minimum length

Villaboard™ Lining Vv 1200mm

HardieGroove™ Lining HG 1200mm

Page 15: Design ManualDIRECT FIX) 36 19 BRACING FIGURES (CAVITY FIX) 39 20 BRACING CONNECTION FIGURES (CAVITY FIX) 41 21 STRUCTUAL CEILING DIAPHRAGM 44 22 FLOOR DIAPHRAGM 45 23 BRACING CALCULATION5.2

James Hardie Bracing Design Manual August 2016 New Zealand 15

Figure 4: Villaboard™ Lining laid horizontally to concrete or timber floor

Product System Minimum length

Villaboard™ Lining Vh 2400mm

rJ)

:E ro Cl .9 "ai rJ) .c

� Ql Ql E Ql E ai E Cl 0 C ll) ·13 e! 1ii

rJ) Cl C ·x

1':J��

�� 1::i 0e'I. e,e '<,� �'l>� c}.0

Proprietary hold down bolt/bracket at end of bracing element

Product

Villaboard® Lining

jhl brce d wall vila04.dwg ®

System Number

Vh

James Hardie a smarter way™

40 x 2.8mm galvanised or 316 stainless steel HardieFlex™ nails

Timber framing

Villaboard™ Lining

1601 Wall

Proprietary hold down bolt/bracket at end of bracing element

Bottom plate fixed as per NZS 3604

HD bolt I coach screw

FIBRE CEMENT FIXING DETAILS Notes for Figure 4:

for bottom plate fixing as per NZS 3604

• Concrete floor bottom plate fixing:- Ramset bracinganchor kit Concrete or GIB Handibrac® with 15kN anchor at each end of bracing element

• Timber floor bottom plate fixing:- Ramset bracing anchor kit Wood or GIB Handibrac® with a 12x150mm galvanised coach screw at each end of bracing element

Minimum Length

2400mm

August 2016 www.jameshardie.co.nz Bracing Design Details CADScale1:20

VILLABOARD® LINING LAID HORIZONTALLY CONCRETE OR TIMBER FLOOR FIGURE: 4

Page 16: Design ManualDIRECT FIX) 36 19 BRACING FIGURES (CAVITY FIX) 39 20 BRACING CONNECTION FIGURES (CAVITY FIX) 41 21 STRUCTUAL CEILING DIAPHRAGM 44 22 FLOOR DIAPHRAGM 45 23 BRACING CALCULATION5.2

16 James Hardie Bracing Design Manual August 2016 New Zealand

Table 4

HomeRAB Pre-Cladding bracing ratings

SYSTEM NUMBER

BRACING ELEMENT LENGTH (mm)

BRACKETS REFER FIGURES

FLOORING CONSTRUCTION

NZS 3604 RATING IN BRACING UNITS PER METRE OF ELEMENT LENGTH

TIMBER CONCRETE WIND EARTHQUAKE

HPn 1200 N 6 √ √ 67 71

HP

400 Y 7, 21, 22, 23 √ √ 85 91

600 Y 7, 21, 22, 23 √ √ 99 103

1200 to 2400 Y 8, 21, 22, 23 √ √ 133* 104

2400 or more Y 8, 21, 22, 23 √ √ 141* 67

Table 6

HomeRAB Pre-Cladding with 10mm GIB® Standard plasterboard bracing ratings

SYSTEM NUMBER

BRACING ELEMENT LENGTH (mm)

BRACKETS REFER FIGURES

FLOORING CONSTRUCTION

NZS 3604 RATING IN BRACING UNITS PER METRE OF ELEMENT LENGTH

TIMBER CONCRETE WIND EARTHQUAKE

HPgn400 N 5, 11 √ √ 73 66

1200 N 6, 12 √ √ 69 58

Table 5

HomeRAB Pre-Cladding with 4.5mm Villaboard Lining, no hold down bracket

SYSTEM NUMBER

BRACING ELEMENT LENGTH (mm)

BRACKETS REFER FIGURES

FLOORING CONSTRUCTION

NZS 3604 RATING IN BRACING UNITS PER METRE OF ELEMENT LENGTH

TIMBER CONCRETE WIND EARTHQUAKE

HPVn400 N 5, 9 √ √ 73 67

1200 N 6, 10 √ √ 84 73

14Bracing tables – Pre-cladding

*A limit of 120BUs/m maximum applies to timber floors and 150BUs/m maximum to concrete floors built as per NZS 3604: 2011 unless a specific engineering design is carried out to ensure the uplift force generated by bracing elements does not exceed the maximum limit for each floor type.

*A limit of 120BUs/m maximum applies to timber floors and 150BUs/m maximum to concrete floors built as per NZS 3604: 2011 unless a specific engineering design is carried out to ensure the uplift force generated by bracing elements does not exceed the maximum limit for each floor type.

*A limit of 120BUs/m maximum applies to timber floors and 150BUs/m maximum to concrete floors built as per NZS 3604: 2011 unless a specific engineering design is carried out to ensure the uplift force generated by bracing elements does not exceed the maximum limit for each floor type.

Page 17: Design ManualDIRECT FIX) 36 19 BRACING FIGURES (CAVITY FIX) 39 20 BRACING CONNECTION FIGURES (CAVITY FIX) 41 21 STRUCTUAL CEILING DIAPHRAGM 44 22 FLOOR DIAPHRAGM 45 23 BRACING CALCULATION5.2

James Hardie Bracing Design Manual August 2016 New Zealand 17

Table 8

RAB Board 6mm

SYSTEM NUMBER

BRACING ELEMENT LENGTH (mm)

BRACKETS REFER FIGURES

FLOORING CONSTRUCTION

NZS 3604 RATING IN BRACING UNITS PER METRE OF ELEMENT LENGTH

TIMBER CONCRETE WIND EARTHQUAKE

JHDn 1200 N 6 √ √ 118 102

JHD

400 Y 7, 21, 22, 23 √ √ 83 107

600 Y 7, 21, 22, 23 √ √ 99 107

1200 to 2400 Y 8, 21, 22, 23 √ √ 154* 140*

2400 or more Y 8, 21, 22, 23 √ √ 135* 150*

Table 7

HomeRAB Pre-Cladding with 10mm GIB® Standard plasterboard bracing ratings

SYSTEM NUMBER

BRACING ELEMENT LENGTH (mm)

BRACKETS REFER FIGURES

FLOORING CONSTRUCTION

NZS 3604 RATING IN BRACING UNITS PER METRE OF ELEMENT LENGTH

TIMBER CONCRETE WIND EARTHQUAKE

HPg

400 Y 7, 13, 21, 22, 23 √ √ 90 98

600 Y 7, 13, 21, 22, 23 √ √ 127* 136*

1200 Y 8, 14, 21, 22, 23 √ √ 164* 138*

Table 9

RAB Board 6mm with 10mm GIB® Standard plasterboard, no hold down bracket

SYSTEM NUMBER

BRACING ELEMENT LENGTH (mm)

BRACKETS REFER FIGURES

FLOORING CONSTRUCTION

NZS 3604 RATING IN BRACING UNITS PER METRE OF ELEMENT LENGTH

TIMBER CONCRETE WIND EARTHQUAKE

JHDgn400 N 5, 11 √ √ 69 64

1200 N 6, 12 √ √ 86 72

*A limit of 120BUs/m maximum applies to timber floors and 150BUs/m maximum to concrete floors built as per NZS 3604: 2011 unless a specific engineering design is carried out to ensure the uplift force generated by bracing elements does not exceed the maximum limit for each floor type.

Page 18: Design ManualDIRECT FIX) 36 19 BRACING FIGURES (CAVITY FIX) 39 20 BRACING CONNECTION FIGURES (CAVITY FIX) 41 21 STRUCTUAL CEILING DIAPHRAGM 44 22 FLOOR DIAPHRAGM 45 23 BRACING CALCULATION5.2

18 James Hardie Bracing Design Manual August 2016 New Zealand

15Bracing figures - Pre-claddingFigure 5: 400mm HomeRAB™ Pre-Cladding or RAB™ Board to concrete or timber floor - no hold down brackets

Product

t � 'l% � -§: �

� 40 x2.8mm" stainless steel, or � hot dip galvanised !Ii HardieFlex™ nails,-� fixing centres as ll:; indicated

System Number

40 X 2.8mm stainless steel, or hot dip galvanised HardieFlex™ nails fixing centres as indicated

12mm minimum edge distance

Timber framing

___ RABHomeRAB

™ Board ™ Pre-Cladding I

Bottom plate fixed as perNZS 3604

Concrete or timber floor

Minimum Length

1601 WALL

HomeRAB® Pre-Cladding I GIB® Standard Plasterboard HPgn 400mm

RAB®Board I GIB® Standard Plasterboard JHDgn 400mm

jhl brce d wall rab01.dwg®

James Hardie a smarter way™

August 2016

Bracing Design Details www.ja�:s��:��c�:;�

400MM HOMERAB® PRE-CLADDING OR RAB BOARD® TO CONCRETE OR TIMBER FLOOR - NO HOLD DOWN BRACKETS FIGURE: 5

Product System Minimum length

HomeRAB™ Pre-Cladding / GIB® Standard Plasterboard HPgn 400mm

RAB™ Board/GIB® Standard Plasterboard JHDgn 400mm

Page 19: Design ManualDIRECT FIX) 36 19 BRACING FIGURES (CAVITY FIX) 39 20 BRACING CONNECTION FIGURES (CAVITY FIX) 41 21 STRUCTUAL CEILING DIAPHRAGM 44 22 FLOOR DIAPHRAGM 45 23 BRACING CALCULATION5.2

James Hardie Bracing Design Manual August 2016 New Zealand 19

Figure 6: 1200mm HomeRAB™ Pre-Cladding or RAB™ Board to concrete or timber floor - no hold down brackets

Product System Number

HomeRAB® Pre-Cladding HPn

RAB® Board JHDn

40 x 2.8mm stainless steel nail, or hot dip galvanised HardieFlex™ nails fixing centres as indicated

12mm minimum edge distance

Timber framing

™ Pre-Cladding IRAB™HomeRAB

Board

Bottom plate fixed as per NZS 3604

Concrete or timber floor

Minimum Length

1200mm

1200mm

1601 WALL

HomeRAB® Pre-Cladding I Villaboard® Lining HPvn 1200mm

HomeRAB® Pre-Cladding I GIB® Standard Plasterboard HPgn 1200mm

RAB® Board I GIB® Standard Plasterboard JHDgn 1200mm

jhl brce d wall rab02.dwg ®

James Hardie a smarter way™

August 2016

Bracing Design Details www.ja�:s��:��c�:;�

1200MM HOMERAB® PRE-CLADDING OR RAB BOARD® TO CONCRETE OR TIMBER FLOOR - NO HOLD DOWN BRACKETS FIGURE: 6

Product System Minimum length

HomeRAB™ Pre-Cladding HPn 1200mm

RAB™ Board JHDn 1200mm

HomeRAB™ Pre-Cladding / Villaboard™ Lining HPvn 1200mm

HomeRAB™ Pre-Cladding / GIB® Standard Plasterboard HPgn 1200mm

RAB™ Board / GIB® Standard Plasterboard JHDgn 1200mm

Page 20: Design ManualDIRECT FIX) 36 19 BRACING FIGURES (CAVITY FIX) 39 20 BRACING CONNECTION FIGURES (CAVITY FIX) 41 21 STRUCTUAL CEILING DIAPHRAGM 44 22 FLOOR DIAPHRAGM 45 23 BRACING CALCULATION5.2

20 James Hardie Bracing Design Manual August 2016 New Zealand

Figure 7: 400/600mm HomeRAB™ Pre-Cladding or RAB™ Board to concrete or timber floor

stainless steel, or hot dip galvanised HardieFlex™ nails,

.� fixing centres as j>'. indicated

FIBRE CEMENT FIXING DETAILS Notes for Figure 7:

40 X 2.8mm stainless steel, or hot dip galvanised HardieFlex™ nails fixing centres as indicated

12mm minimum edge distance

Timber framing

RAB___ HomeRAB

™ Pre-Cladding IBoard

Bottom plate fixed as per NZS 3604

Concrete or timber floor

Proprietary hold down --- bolt/bracket at end of bracing

element

Proprietary hold down ----- bolt/bracket at end of bracing

element

• Concrete floor bottom plate fixing:- Ramset bracing anchor kit Concrete or GIB Handibrac® with 15kN anchor at each end of bracing element

• Timber floor bottom plate fixing:- Ramset bracing anchor kit Wood or GIB Handibrac® with a 12x150mm galvanised coach screw at each end of bracing element

Product System Number Minimum Length

HomeRAB® Pre-Cladding HP 400 or600mm

HomeRAB® Pre-Cladding with 1 0mm GIB® Standard plasterboard HPg 400 or600mm

RAB® Board JHD 400 or600mm

jhl brce d wall rab03.dwg

1601 Wall

August 2016 ®

James Hardie Bracing Design Details www.ja�:s��:��c�:;�

a smarter way™ HOMERAB® PRE-CLADDING OR RAB® BOARD CONCRETE OR TIMBER FLOOR FIGURE: 7

Product System Minimum length

HomeRAB™ Pre-Cladding HP 400 or 600mm

HomeRAB™ Pre-Cladding with 10mm GIB® Standard plasterboard HPg 400 or 600mm

RAB™ Board JHD 400 or 600mm

Page 21: Design ManualDIRECT FIX) 36 19 BRACING FIGURES (CAVITY FIX) 39 20 BRACING CONNECTION FIGURES (CAVITY FIX) 41 21 STRUCTUAL CEILING DIAPHRAGM 44 22 FLOOR DIAPHRAGM 45 23 BRACING CALCULATION5.2

James Hardie Bracing Design Manual August 2016 New Zealand 21

Figure 8: 1200mm HomeRAB™ Pre-Cladding or RAB™ Board to concrete or timber floor

Product System Minimum length

HomeRAB™ Pre-Cladding HP 1200mm

HomeRAB™ Pre-Cladding with 10mm GIB® Standard plasterboard HPg 1200mm

RAB™ Board JHD 1200mm

HomeRAB™ Pre-Cladding / RAB™ Board

Page 22: Design ManualDIRECT FIX) 36 19 BRACING FIGURES (CAVITY FIX) 39 20 BRACING CONNECTION FIGURES (CAVITY FIX) 41 21 STRUCTUAL CEILING DIAPHRAGM 44 22 FLOOR DIAPHRAGM 45 23 BRACING CALCULATION5.2

22 James Hardie Bracing Design Manual August 2016 New Zealand

Figure 9: HomeRAB™ Pre-Cladding 400mm to concrete or timber floor - Villaboard™ Lining side - no hold down brackets

12mm minimum edge �-- distance

James Hardie 6mm Villaboard™ Lining. Fixed with 40 x 2.8mm

�-!------ HadieFlex™ hot dip galvanised nails to all framing at 150mm centres.

Timber framing

Bottom plate

1601 WALL

Timber flooring or concrete slab

Product System Number Minimum Length

HomeRAB® Pre-Cladding I Villaboard® Lining HPVn 400 mm

jhl brce d wall rab06.dwg ®

James Hardie a smarter way™

August 2016 www.jameshardie.co.nz Bracing Design Details CADScale1:20

400MM HOMERAB® PRE-CLADDING TO CONCRETE OR TIMBER FLOOR -VILLABOARD® LININGS SIDE - NO HOLD DOWN BRACKETS FIGURE: 9

Product System Minimum length

HomeRAB™ Pre-Cladding / Villaboard™ Lining HPVn 400mm

Page 23: Design ManualDIRECT FIX) 36 19 BRACING FIGURES (CAVITY FIX) 39 20 BRACING CONNECTION FIGURES (CAVITY FIX) 41 21 STRUCTUAL CEILING DIAPHRAGM 44 22 FLOOR DIAPHRAGM 45 23 BRACING CALCULATION5.2

James Hardie Bracing Design Manual August 2016 New Zealand 23

Figure 10: HomeRAB™ Pre-Cladding 1200mm to concrete or timber floor - Villaboard™ Lining side - no hold down brackets

Timber flooring or concrete slab

Bottom plate fixed as per NZS 3604

Product System Number

12mm minimum edge distance

James Hardie 6mm Villaboard™ Lining. Fixed with 40 x 2.8mm

--- HardieFlex™ hot dip galvanised nails to all framing at 150mm centres.

Timber framing

Bottom plate

Minimum Length

1601 WALL

HomeRAB® Pre-Cladding I Villaboard® Lining HPVn 1200mm

jhl brce d wall rab07.dwg ®

James Hardie a smarter way™

August 2016 www.jameshardie.co.nz Bracing Design Details CADScale1:20

1200MM HOMERAB® PRE-CLADDING TO CONCRETE OR TIMBER FLOOR -VILLABOARD® LININGS SIDE - NO HOLD DOWN BRACKETS FIGURE: 10

Product System Minimum length

HomeRAB™ Pre-Cladding / Villaboard™ Lining HPVn 1200mm

Page 24: Design ManualDIRECT FIX) 36 19 BRACING FIGURES (CAVITY FIX) 39 20 BRACING CONNECTION FIGURES (CAVITY FIX) 41 21 STRUCTUAL CEILING DIAPHRAGM 44 22 FLOOR DIAPHRAGM 45 23 BRACING CALCULATION5.2

24 James Hardie Bracing Design Manual August 2016 New Zealand

Figure 11: HomeRAB™ Pre-Cladding/RAB™ Board 400mm to concrete or timber floor - GIB® Standard Plasterboard - no hold down brackets

Product System Minimum length

HomeRAB™ Pre-Cladding HPgn 400mm

RAB™ Board JHDgn 400mm

Page 25: Design ManualDIRECT FIX) 36 19 BRACING FIGURES (CAVITY FIX) 39 20 BRACING CONNECTION FIGURES (CAVITY FIX) 41 21 STRUCTUAL CEILING DIAPHRAGM 44 22 FLOOR DIAPHRAGM 45 23 BRACING CALCULATION5.2

James Hardie Bracing Design Manual August 2016 New Zealand 25

Figure 12: HomeRAB™ Pre-Cladding/RAB™ Board 1200mm to concrete or timber floor - GIB® Standard Plasterboard - no hold down brackets

Flooring

Timber flooring or concrete slab

See HomeRAB™ Pre-Cladding IRAB™ Board side for bottom plate to --­joist fixing

STANDARD GIB® FIXING DETAILS Notes for Figure 12: • All GIB® standard sheets to be fixed to Winstone Wallboards Ltd specifications. GIB®

Bracing Systems.• All GIB® bracing sheets to be stopped to Winstone Wallboards Ltd specifications.

GIB® Site Guide.• Refer Winstone Wallboards Ltd specifications for edge distance.

Product System Number

HomeRAB® Pre-Cladding I GIB® Standard Plasterboard HPgn

RAB® Board I GIB® Standard Plasterboard HPDgn

JHL BRCE D WALL RAB09.DWG

E E

GIB® Standard Plasterboard. Fixed with 32mm GIB® Grabbers®

screws

Timber framing

12mm from cut sheet edge Fasteners: Minimum 32mm x 6g GJB• Grabber" screws

18mm from cut sheet edge ,lso� 50� 5oJ 75 J 75 �

15ommcrs�

Bottom plate

Minimum Length

1200mm

1200mm

1601 WALL

AUGUST 2016 ®

James Hardie Bracing Design Details www.j�:�s;�1�,t�:;�

a smarter way™ 1200MM HOMERAB® PRE-CLADDING - RAB® BOARD TO CONCRETE OR TIMBER FLOOR - GIB® STANDARD PLASTERBOARD - NO HOLD DOWN FIGURE: 12

Product System Minimum length

HomeRAB™ Pre-Cladding / GIB® Standard Plasterboard HPgn 1200mm

RAB™ Board / GIB® Standard Plasterboard HPDgn 1200mm

Page 26: Design ManualDIRECT FIX) 36 19 BRACING FIGURES (CAVITY FIX) 39 20 BRACING CONNECTION FIGURES (CAVITY FIX) 41 21 STRUCTUAL CEILING DIAPHRAGM 44 22 FLOOR DIAPHRAGM 45 23 BRACING CALCULATION5.2

26 James Hardie Bracing Design Manual August 2016 New Zealand

Figure 13: 400mm/600mm HomeRAB™ Pre-Cladding with 10mm GIB® Standard Plasterboard

Product System Minimum length

HomeRAB™ Pre-Cladding HPg 400 or 600mm

� -�� � -� � � � s: � �

� -� �� " � 1\i �

s3i -��

Flooring

Timber flooring or concrete slab

See HomeRAB™ Pre-Cladding side�_� for bottom plate to joist fixing

STANDARD GIB® FIXING DETAILS Notes for Figure 13:

"' ....

t � E E

GIB® Standard Plasterboard. Fixed with 32mm GIB® Grabbers®

screws

Timber framing

12mm from cut sheet edge Fasteners: Minimum 32mm x 6g G1s• Grabber" screws

18mm from cut sheet edge ,l 50 J 50 ,l 50 ,l 75 � 75 ,l 150mm crs �

Bottom plate

• All GIB® standard sheets to be fixed to Winstone Wallboards Ltd specifications. GIB®

Bracing Systems.• All GIB® bracing sheets to be stopped to Winstone Wallboards Ltd specifications.

GIB® Site Guide. • Refer Winstone Wallboards Ltd specifications for edge distance.

Product System Number

HomeRAB® Pre-Cladding HPg

jhl brce d wall hrab01.dwg

Minimum Length

400 or600mm

1601 Wall

August 2016 ® Bracing Design Details www.jameshardie.co.nz

CAD Scale 1 :20

James Hardie a smarter way™ HOMERAB® PRE-CLADDING - INTERIOR LINING SIDE

FIGURE: 13

Page 27: Design ManualDIRECT FIX) 36 19 BRACING FIGURES (CAVITY FIX) 39 20 BRACING CONNECTION FIGURES (CAVITY FIX) 41 21 STRUCTUAL CEILING DIAPHRAGM 44 22 FLOOR DIAPHRAGM 45 23 BRACING CALCULATION5.2

James Hardie Bracing Design Manual August 2016 New Zealand 27

Figure 14: 1200mm HomeRAB™ Pre-Cladding with 10mm GIB® Standard Plasterboard

Product System Minimum length

HomeRAB™ Pre-Cladding / GIB® Standard Plasterboard HPg 1200mm

Flooring

Timber flooring or concrete slab

See HomeRAB™ Pre-Cladding side_ �-­ for bottom plate to joist fixing

STANDARD GIB® FIXING DETAILS Notes for Figure 14: • All GIB® standard sheets to be fixed to Winstone Wallboards Ltd specifications. GIB®

Bracing Systems. • All GIB® bracing sheets to be stopped to Winstone Wallboards Ltd specifications.

GIB® Site Guide.• Refer Winstone Wallboards Ltd specifications for edge distance.

Product System Number

HomeRAB® Pre-Cladding I Gib® Standard Plasterboard HPg

jhl brce d wall hrab02.dwg ® Bracing Design Details

"' .... 0 "' 0 "'

GIB® Standard Plasterboard. Fixed with 32mm GIB® Grabbers®

screws

Timber framing

i lj

12mm from cut sheet edge Fasteners: E

E 0 "'

Minimum 32mm x 6g GIBliil Grabber® screws

18mm from cut sheet edge ,L 50 I 50 I 50 � 75 I 75 �

150mmcrs-+

Bottom plate

Minimum Length

1200mm

1601 Wall

August 2016 www.jameshardie.co.nz

CAD Scale 1 :20

James Hardie a smarter way™ HOMERAB® PRE-CLADDING - INTERIOR LINING SIDE

FIGURE: 14

Page 28: Design ManualDIRECT FIX) 36 19 BRACING FIGURES (CAVITY FIX) 39 20 BRACING CONNECTION FIGURES (CAVITY FIX) 41 21 STRUCTUAL CEILING DIAPHRAGM 44 22 FLOOR DIAPHRAGM 45 23 BRACING CALCULATION5.2

28 James Hardie Bracing Design Manual August 2016 New Zealand

Table 10

HardieFlex Sheet 6mm or 7.5mm bracing ratings

SYSTEM NUMBER

BRACING ELEMENT LENGTH (mm)

BRACKETS REFER FIGURES

FLOORING CONSTRUCTION

NZS 3604 RATING IN BRACING UNITS PER METRE OF ELEMENT LENGTH

TIMBER CONCRETE WIND EARTHQUAKE

JHDn 1200 N 15 √ √ 118 102

JHD

400 Y 16, 21, 22, 23 √ √ 83 107

600 Y 16, 21, 22, 23 √ √ 99 107

1200 to 2400 Y 16, 21, 22, 23 √ √ 154* 140*

2400 or more Y 16, 21, 22, 23 √ √ 135* 150*

*A limit of 120BUs/m maximum applies to timber floors and 150BUs/m maximum to concrete floors built as per NZS 3604: 2011 unless a specific engineering design is carried out to ensure the uplift force generated by bracing elements does not exceed the maximum limit for each floor type.

Table 11

Axon Panel bracing ratings

SYSTEM NUMBER

BRACING ELEMENT LENGTH (mm)

BRACKETS REFER FIGURES

FLOORING CONSTRUCTION

NZS 3604 RATING IN BRACING UNITS PER METRE OF ELEMENT LENGTH

TIMBER CONCRETE WIND EARTHQUAKE

APn 1200 N 15 √ √ 122* 106

AP1200 to 2400 Y 17, 21, 23 √ √ 150* 157*

2400 or more Y 17, 21, 23 √ √ 149* 135*

*A limit of 120BUs/m maximum applies to timber floors and 150BUs/m maximum to concrete floors built as per NZS 3604: 2011 unless a specific engineering design is carried out to ensure the uplift force generated by bracing elements does not exceed the maximum limit for each floor type.

16Bracing tables – Claddings

Page 29: Design ManualDIRECT FIX) 36 19 BRACING FIGURES (CAVITY FIX) 39 20 BRACING CONNECTION FIGURES (CAVITY FIX) 41 21 STRUCTUAL CEILING DIAPHRAGM 44 22 FLOOR DIAPHRAGM 45 23 BRACING CALCULATION5.2

James Hardie Bracing Design Manual August 2016 New Zealand 29

Table 13

RAB Board 6mm / HardieFlex Sheet 6mm or 7.5mm / Monotek Sheet bracing ratings

SYSTEM NUMBER

BRACING ELEMENT LENGTH (mm)

REFER FIGURES FLOORING CONSTRUCTION NZS 3604 RATING IN BRACING UNITS PER METRE OF ELEMENT LENGTH

TIMBER CONCRETE WIND EARTHQUAKE

CAVITY FIXED CONSTRUCTION

JHC1200 to 2400 23, 26, 28, 29, 30 √ √ 147* 121*

2400 or more 23, 27, 28, 30, 31 √ √ 157* 142*

*A limit of 120BUs/m maximum applies to timber floors and 150BUs/m maximum to concrete floors built as per NZS 3604: 2011 unless a specific engineering design is carried out to ensure the uplift force generated by bracing elements does not exceed the maximum limit for each floor type.

Table 14

Axon Panel bracing ratings

SYSTEM NUMBER

BRACING ELEMENT LENGTH (mm)

REFER FIGURES

FLOORING CONSTRUCTION NZS 3604 RATING IN BRACING UNITS PER METRE OF ELEMENT LENGTH

TIMBER CONCRETE WIND EARTHQUAKE

CAVITY FIXED CONSTRUCTION

APC 1200 to 2400 23, 26, 28, 29, 31 √ √ 154* 166*

*A limit of 120BUs/m maximum applies to timber floors and 150BUs/m maximum to concrete floors built as per NZS 3604: 2011 unless a specific engineering design is carried out to ensure the uplift force generated by bracing elements does not exceed the maximum limit for each floor type.

Table 12

Linea Weatherboard bracing ratings

SYSTEM NUMBER

BRACING ELEMENT LENGTH (mm)

REFER FIGURES

FLOORING CONSTRUCTION NZS 3604 RATING IN BRACING UNITS PER METRE OF ELEMENT LENGTH

TIMBER CONCRETE WIND EARTHQUAKE

DIRECT FIXED CONSTRUCTION

LWV

1200 to 2400 18, 19, 21, 22, 23, 24 √ √ 130* 101

2400 or more 18, 19, 21, 22, 23, 24 √ √ 125* 98

LWG

1200 to 2400 18, 20, 21, 22, 23, 24 √ √ 91 80

2400 or more 18, 20, 21, 22, 23, 24 √ √ 75 67

‘V’ at end of System number = Villaboard Lining used as lining‘G’ at end of system number = GIB® Standard plasterboard used as lining.

*A limit of 120BUs/m maximum applies to timber floors and 150BUs/m maximum to concrete floors built as per NZS 3604: 2011 unless a specific engineering design is carried out to ensure the uplift force generated by bracing elements does not exceed the maximum limit for each floor type.

Page 30: Design ManualDIRECT FIX) 36 19 BRACING FIGURES (CAVITY FIX) 39 20 BRACING CONNECTION FIGURES (CAVITY FIX) 41 21 STRUCTUAL CEILING DIAPHRAGM 44 22 FLOOR DIAPHRAGM 45 23 BRACING CALCULATION5.2

30 James Hardie Bracing Design Manual August 2016 New Zealand

Figure 15: 1200mm Panel no hold down brackets

17Bracing figures claddings (direct fix)

Product System Number Minimum length

Axon™ Panel APn 1200mm

HardieFlex™ Sheet JHDn 1200mm

Product

Axon® Panel

HardieFlex™ Sheet

jhl brce d wall panl.dwg ®

James Hardie a smarter way™

System Number

APn

JHDn

Notes for Figure 15:

40 X 2.8mm stainless steel nails fixing centres as indicated

12mm minimum edge distance

Timber framing

HardieFlex™ Sheet/ Axon™ Panel

Bottom plate fixed as per NZS 3604

Concrete or timber floor

• For internal walls these systems can have the sheet stopped at the underside of the bottom plate and achieve the same rating given in the tables.

• Edge Fixing Distance: Axon™ Panel Minimum

• Overhang Distance:

18mm HardieFlex™ Sheet -minimum 12mm. HardieFlex™ Sheet, and Axon™ Panel - 50mm.

Minimum Length

1200mm

1200mm

1601 Wall

August 2016

Bracing Design Details www.jameshardie.co.nz CAD Scale 1 :20

1200MM PANEL - NO HOLD DOWN BRACKETS FIGURE: 15

Page 31: Design ManualDIRECT FIX) 36 19 BRACING FIGURES (CAVITY FIX) 39 20 BRACING CONNECTION FIGURES (CAVITY FIX) 41 21 STRUCTUAL CEILING DIAPHRAGM 44 22 FLOOR DIAPHRAGM 45 23 BRACING CALCULATION5.2

James Hardie Bracing Design Manual August 2016 New Zealand 31

Figure 16: 400mm or 600mm Panel to concrete or timber floor

Product System Number Minimum length

HardieFlex™ Sheet JHD 400 or 600mm

HardieFlex™ Sheet

Page 32: Design ManualDIRECT FIX) 36 19 BRACING FIGURES (CAVITY FIX) 39 20 BRACING CONNECTION FIGURES (CAVITY FIX) 41 21 STRUCTUAL CEILING DIAPHRAGM 44 22 FLOOR DIAPHRAGM 45 23 BRACING CALCULATION5.2

32 James Hardie Bracing Design Manual August 2016 New Zealand

bracing element

Product

Axon® Panel

HardieFlex™ Sheet

jhl brce d flor tim-conc2.dwg ®

James Hardie a smarter way™

40 x 2.8mm 316 stainless steel HardieFlex™ nails, fixing centres as per notes below

Minimum edge distance refer notes

Timber framing

HardieFlex™ Sheet I Axon™ Panel

Bottom plate fixed as per NZS 3604

Proprietary hold down --� bolt/bracket at end of bracing

FIBRE CEMENT FIXING DETAILS Notes for Figure 17:

element

Concrete or timber floor

1601 Wall

• Concrete floor bottom plate fixing:- Ramset bracing anchor kit Concrete or GIB Handibrac® with 15kN anchor at each end of bracing element

• Timber floor botto m plate fixing:- Ramset bracing anchor kit Wood or GIB Handibrac® with a 12x150mm galvanised coach screw at each end of bracing element

• For internal walls these systems can have the sheet stopped at the underside of the bottom plate and achieve the same rating given in the tables.

• Edge Fixing Distance: Axon™ Panel - minimum 18mm HardieFlex™ Sheet, - minimum 12mm.

• Overhang Distance: HardieFlex™ Sheet,and Axon™ Panel - 50mm.

System Number Minimum Length

AP 1200mm

JHD 1200mm

Bracing Design Details 1200MM OR MORE SHEET TO CONCRETE OR TIMBER FLOORS

August 2016 www.jameshardie.co.nz

CAD Scale 1 :20

FIGURE: 17

Product System Number Minimum length

Axon™ Panel AP 1200mm

HardieFlex™ Sheet JHD 1200mm

Figure 17: 1200mm or more Panel to concrete or timber floor

Page 33: Design ManualDIRECT FIX) 36 19 BRACING FIGURES (CAVITY FIX) 39 20 BRACING CONNECTION FIGURES (CAVITY FIX) 41 21 STRUCTUAL CEILING DIAPHRAGM 44 22 FLOOR DIAPHRAGM 45 23 BRACING CALCULATION5.2

James Hardie Bracing Design Manual August 2016 New Zealand 33

Product System Number Minimum length

Linea™ Weatherboard / Villaboard™ Lining LW V 1200mm

Linea™ Weatherboard / GIB® Standard plasterboard LWG 1200mm

Figure 18: Linea™ Weatherboard to concrete or timber floor

:E 0) 'iii

Q) E Q) "iii 0) C: ·13�co

Concrete Floor

LINEA® WEATHERBOARD FIXING DETAILS TO TIMBER JOISTS

Notes for Figure 18:

Additional top fixing to --- uppermost weatherboard

75 x 3.15mm jolt head 316 ___ stainless steel nail through both

layers

Timber framing

Selected Linea™ Weatherboard

Bottom plate fixed as per NZS 3604 Table 8.19

Concrete foundation

Proprietary hold down bolt/bracket at end of bracing element

• Concrete floor bottom plate fixing:- Ramset bracing anchor kit Concrete or GIB Handibrac® with 15kN anchor at each end of bracing element

• Timber floor bottom plate fixing:- Ramset bracing anchor kit Wood or GIB Handibrac® with a 12x150mm galvanised coach screw at each end of bracing element

• Linea™ Weatherboards to be bottom fixed through both layers with 75 x 3.15mm jolt head 316 Stainless Steel nail per board at every stud. Refer Figure 18.

• Bracing panels can contain Tongue and Groove end jointed weatherboards. These must be limited to one third of the Linea™ Weatherboard in the height of a bracing wall, the rest must be continuous lengths.

• There must be a minimum of one full Linea™ Weatherboard at bottom plate for this bracing element.

Product System Number

Linea® Weatherboard I Villaboard® Lining LWV

Linea® Weatherboard I Gib® Standard Plasterboard LWG

Minimum Length

1200mm

1200mm

1601 Wall

jhl brce d wall lina01.dwg August 2016 ®

James Hardie a smarter way™

Bracing Design Details LINEA® WEATHERBOARD TO CONCRETE OR TIMBER FLOOR

www.jameshardie.co.nz CAD Scale 1 :20

FIGURE: 18

Page 34: Design ManualDIRECT FIX) 36 19 BRACING FIGURES (CAVITY FIX) 39 20 BRACING CONNECTION FIGURES (CAVITY FIX) 41 21 STRUCTUAL CEILING DIAPHRAGM 44 22 FLOOR DIAPHRAGM 45 23 BRACING CALCULATION5.2

34 James Hardie Bracing Design Manual August 2016 New Zealand

Timber flooring or concrete slab

Bottom plate fixed as per NZS 3604

12mm minimum edge distance

James Hardie 6mm Villaboard™ Lining. Fixed with 40 x 2.8mm

--� HardieFlex™ hot dip galvanised nails to all framing at 150mm centres.

Timber framing

Bottom plate

1601 Wall

VILLABOARD® LINING FIXING DETAILS

Product System Number Minimum Length

Linea® Weatherboard I Villaboard® Lining LWV 1200mm

jhl brce d wall lina02.dwg ®

James Hardie a smarter way™

August 2016

Bracing Design Details www.ja�:s��:��c�:;�

LINEA® WEATHERBOARD TO TIMBER OR CONCRETE FLOOR VILLABOARD® LINING FIGURE: 19

Product System Number Minimum length

Linea™ Weatherboard / Villaboard™ Lining LW V 1200mm

Figure 19: Linea™ Weatherboard to concrete or timber floor - Villaboard™ Lining side

VILLABOARD™ LINING FIXING DETAILS

Page 35: Design ManualDIRECT FIX) 36 19 BRACING FIGURES (CAVITY FIX) 39 20 BRACING CONNECTION FIGURES (CAVITY FIX) 41 21 STRUCTUAL CEILING DIAPHRAGM 44 22 FLOOR DIAPHRAGM 45 23 BRACING CALCULATION5.2

James Hardie Bracing Design Manual August 2016 New Zealand 35

E ·xro E en �c� E E 00

C')

roen 0) C: ·xii:

GIB® Standard Plasterboard. Fixed with 32mm GIB® Grabbers®

screws or 30mm GIB®

Nails

Timber framing

Note! No fixing to inner studs or nogs is mandatory for this

1601 Wall

_.ill--+-----� bracing element. Sheetmay be fixed by either 'GIB' approved nailing or gluing.

Flooring

Timber flooring or concrete slab

See Linea™ Weatherboard side for�-­bottom plate to joist fixing

STANDARD GIB® FIXING DETAILS Notes for Figure 20: • All GIB® standard sheets to be fixed to Winstone Wallboards Ltd specifications. GIB®

Bracing Systems.• All GIB® bracing sheets to be stopped to Winstone Wallboards Ltd specifications.

GIB"' Site Guide.• Refer Winstone Wallboards Ltd specifications for edge distance.

Product System Number

Linea® Weatherboard I Gib® Standard Plasterboard LWG

jhl brce d wall lina03.dwg ®

James Hardie a smarter way™

Bracing Design Details LINEA® WEATHERBOARD - INTERIOR LINING SIDE

Bottom plate

Minimum Length

1200mm

August 2016 www.jameshardie.co.nz

CAD Scale 1 :20

FIGURE: 20

Product System Number Minimum length

Linea™ Weatherboard / GIB® Standard plasterboard LWG 1200mm

Figure 20: Linea™ Weatherboard to concrete or timber floor — GIB® Standard Plasterboard

Page 36: Design ManualDIRECT FIX) 36 19 BRACING FIGURES (CAVITY FIX) 39 20 BRACING CONNECTION FIGURES (CAVITY FIX) 41 21 STRUCTUAL CEILING DIAPHRAGM 44 22 FLOOR DIAPHRAGM 45 23 BRACING CALCULATION5.2

36 James Hardie Bracing Design Manual August 2016 New Zealand

18Bracing connection figures (direct fix)

Figure 22: End bracket to timber joist

Figure 21: End bracket to concrete slab

Page 37: Design ManualDIRECT FIX) 36 19 BRACING FIGURES (CAVITY FIX) 39 20 BRACING CONNECTION FIGURES (CAVITY FIX) 41 21 STRUCTUAL CEILING DIAPHRAGM 44 22 FLOOR DIAPHRAGM 45 23 BRACING CALCULATION5.2

James Hardie Bracing Design Manual August 2016 New Zealand 37

Figure 23: Hold down straps to timber joists

Page 38: Design ManualDIRECT FIX) 36 19 BRACING FIGURES (CAVITY FIX) 39 20 BRACING CONNECTION FIGURES (CAVITY FIX) 41 21 STRUCTUAL CEILING DIAPHRAGM 44 22 FLOOR DIAPHRAGM 45 23 BRACING CALCULATION5.2

38 James Hardie Bracing Design Manual August 2016 New Zealand

E E -�EEE

0 0 (")

·II·1·II

Extra nag at top of bracing sheet and under top plate to be same size as framing studs and plates

I-�I

Bracing sheet

I · I I I stainless steel• HardieFlex™

I I nails, minimum

I · I edge distancerefer notes

I I I I

-----j , I-- -. - .------l I-- - - -

I I

Notes for Figure 25: Fixings: 1. All sheet nailing shown must be as for the

various bracing systems2. The bracing values for full height sheet for

each system can be used when this detail is followed.

3. Edge Fixing Distance:-Axon™ Panel - minimum 18mm

HardieFlex™ Sheet and RAB™ Board -minimum 12mm.

Figure 25: Bracing panel stopped below top plate

75 x 3.15mm jolt head nails 316 stainless steel

Selected Linea™

Weatherboard

Notes for Figure 24: Linea™ Weatherboards to be face fixed through both layers using 75 x 3.15mm jolt head nails at 90° to face, punch 2mm below surface and fill.

� Building underlay

Stud

Figure 24: Linea™ Weatherboard face fixing for bracing

Page 39: Design ManualDIRECT FIX) 36 19 BRACING FIGURES (CAVITY FIX) 39 20 BRACING CONNECTION FIGURES (CAVITY FIX) 41 21 STRUCTUAL CEILING DIAPHRAGM 44 22 FLOOR DIAPHRAGM 45 23 BRACING CALCULATION5.2

James Hardie Bracing Design Manual August 2016 New Zealand 39

19Bracing figures (cavity fix)Figure 26: 1200mm or more Panel to concrete or timber floor

:E

Note: All bottom packers must be set to a slope of 5° minimum

E E00co

Refer Figure 30

60 x 3.15mm 316 stainless steel HardieFlex™ nails to fix paling packer

150 x 19mm paling packer treated H3.1 minimum

All vertical fixings at 150mm

___ centres using 60 X 3.15mm316 stainless steel HardieFlex™ nails

�----==-- Minimum edge distance

refer notes Timber framing treated H1 .2

/-.,J.----- minimum Fix battens with 40 x 2.8mm 316 stainless steel J�0��------- HardieFlex™ nails to plates and nogs 45 x 19mm timber cavity

�---1----,H=1-+------- battens at 300mm centres treated H3.1 minimum

Bracing sheet

Bracket at end of bracing element

Bottom plate fixed as per NZS 3604

75 x 19mm paling packer treated H3.1 minimum

0) E"cii E ..c c 0 0Q) co

Concrete or timber floor

EQ)

0)

60 x 3.15mm 316 stainless "]""-----1---- steel HardieFlex™ nails to

fix cladding at 150mm centres to bottom plate

C ·u

0) C

E E00co

Refer Figure 28 60 x 3.15mm 316 stainless steel HardieFlex™ nails to fix paling packer

E� E cii 0 >LO 0

end of bracing element

FIBRE CEMENT FIXING DETAILS Notes for Figure 26: • Concrete floor bottom plate fixing:- Ramset bracing anchor kit Concrete or GIB Handibrac® with 15kN anchor at each

end of bracing element• Timber floor bottom plate fixing:- Ramset bracing anchor kit Wood or GIB Handibrac® with a 12x150mm galvanised

coach screw at each end of bracing element• Edge Fixing Distance:- HardieFlex™ Sheet, Monotek™ Sheet and RAB™ Board - minimum 12mm.

System Number

JHC

Axon™ Panel - minimum 18mm

Product

HardieFlex™ Sheet I RAB® Board I Monotek® Sheet Axon®

Panel APC

Minimum Length

1200mm

1200mm

Product System Number Minimum length

HardieFlex™ Sheet / RAB™ Board / Monotek™ Sheet JHC 1200mm

Axon™ Panel APC 1200mm

Page 40: Design ManualDIRECT FIX) 36 19 BRACING FIGURES (CAVITY FIX) 39 20 BRACING CONNECTION FIGURES (CAVITY FIX) 41 21 STRUCTUAL CEILING DIAPHRAGM 44 22 FLOOR DIAPHRAGM 45 23 BRACING CALCULATION5.2

40 James Hardie Bracing Design Manual August 2016 New Zealand

Figure 27: 2400mm or more Panel to concrete or timber floor

Note: All bottom packers must be set to a slope of 5° minimum

Refer Figure 30

Vertical fixings at 100mm centres where sheets butt together

.c Cl ·w.c "E (I)

E (I)

Cl

·13

Cl C

E� E m

O> LO 0

E E 0 0

CX)

E E 0 0

CX)

E E 0 0

CX)

Proprietary hold down bolUbracket at end of bracing element

FIBRE CEMENT FIXING DETAILS Notes for Figure 27:

60 x 3.15mm 316 stainless steel HardieFlex™ nails to fix paling packer

150 x 19mm paling packer treated H3.1 minimum

All vertical fixings at 150mm centres using 60 X 3.15mm

--- 316 stainless steel HardieFlex™ nails

�-----===-- Minimum edge distance refer notes Timber framing treated H1 .2

��---- minimum Fix battens with 40 x 2.8mm 316 stainless steel

����------- HardieFlex™ nails to platesand nags 45 x 19mm timber cavity

----'-�------- battens at 300mm centres treated H3.1 minimum

Bracing sheet

Bracket at end of bracing element

Bottom plate fixed as per NZS 3604

75 x 19mm paling packer treated H3.1 minimum

Concrete or timber floor

60 x 3.15mm 316 stainless --:i ------1---- steel HardieFlex™ nails to

fix cladding at 150mm centres to bottom plate

60 x 3.15mm 316 stainless steel HardieFlex™ nails to fix paling packer

• Concrete floor bottom plate fixing:- Ramset bracing anchor kit Concrete or GIB Handibrac® with 15kN anchor at each end of bracing element

• Timber floor bottom plate fixing:- Ramset bracing anchor kit Wood or GIB Handibrac® with a 12x150mm galvanised coach screw at each end of bracing element

• Edge Fixing Distance:- HardieFlex™ Sheet, Monotek™ Sheet and RAB™ Board - minimum 12mm.

Product System Number

HardieFlex™ Sheet I RAB® Board I Monotek® Sheet JHC

Minimum Length

2400mm Product System Number Minimum length

HardieFlex™ Sheet / RAB™ Board / Monotek™ Sheet

JHC 2400mm

Page 41: Design ManualDIRECT FIX) 36 19 BRACING FIGURES (CAVITY FIX) 39 20 BRACING CONNECTION FIGURES (CAVITY FIX) 41 21 STRUCTUAL CEILING DIAPHRAGM 44 22 FLOOR DIAPHRAGM 45 23 BRACING CALCULATION5.2

James Hardie Bracing Design Manual August 2016 New Zealand 41

Figure 29: Panel to concrete or timber floor — centre paling packer

Figure 28: 1200mm wide panel to concrete or timber floor

20Bracing connection figures (cavity fix)

Page 42: Design ManualDIRECT FIX) 36 19 BRACING FIGURES (CAVITY FIX) 39 20 BRACING CONNECTION FIGURES (CAVITY FIX) 41 21 STRUCTUAL CEILING DIAPHRAGM 44 22 FLOOR DIAPHRAGM 45 23 BRACING CALCULATION5.2

42 James Hardie Bracing Design Manual August 2016 New Zealand

Figure 31: 2400mm long panel to concrete or timber floor — centre paling packer

Figure 30: All bracing panel top plate detail

Page 43: Design ManualDIRECT FIX) 36 19 BRACING FIGURES (CAVITY FIX) 39 20 BRACING CONNECTION FIGURES (CAVITY FIX) 41 21 STRUCTUAL CEILING DIAPHRAGM 44 22 FLOOR DIAPHRAGM 45 23 BRACING CALCULATION5.2

James Hardie Bracing Design Manual August 2016 New Zealand 43

Figure 32: Typical vent strip installation

Page 44: Design ManualDIRECT FIX) 36 19 BRACING FIGURES (CAVITY FIX) 39 20 BRACING CONNECTION FIGURES (CAVITY FIX) 41 21 STRUCTUAL CEILING DIAPHRAGM 44 22 FLOOR DIAPHRAGM 45 23 BRACING CALCULATION5.2

44 James Hardie Bracing Design Manual August 2016 New Zealand

21Structural ceiling diaphragm

James Hardie ceiling lining products can also be used for a ceiling diaphragm construction in accordance with NZS 3604.

• The following products can be used as a structural diaphragm

• Villaboard Lining 6mm and 9mm or

• HardieFlex Sheet 4.5mm and 6mm.

The ceiling diaphragm shall be constructed to comply with the following requirements;

• The length of a ceiling diaphragm must not exceed twice its width. The length and width will be measured between supporting walls. They shall be no longer than 12m with an aspect ratio (length divided by width) no greater than 2.

• The sheet size must not be less than 1800 x 900mm except where building’s dimensions restricts the use of this size.

• The sheets are to be installed as per Figure 27.

• All sheet edges must be supported with framing behind. Always maintain a minimum 12mm edge distance for sheet fixing.

• James Hardie sheets can also be used to construct sloping ceiling diaphragms where the slope of ceiling is not over 45 degree from the horizontal plane.

• The sheets must be laid in a staggered pattern as shown.

• Each bracing line along length = L or along width = W shall have a bracing capacity of not less than 15bu/m of L or W measured at right angles to the line being considered.

• Refer to NZS 3604, section 5.6 for further information on diaphragms

• For dry area internal applications the standard hot dipped galvanised nails can be used. For wet area internal applications stainless steel nails must be used.

jhl brce roof ceil.dwg

w

Braced wall

Fix sheets with 40 x 2.8mm HardieFlex™ nails • at 150mm centres around diaphragm boundary and

sheet perimeter and • at 200mm centres to intermediate supports and • 12mm from the edge of the sheet.• to batten spacing at maximum 600mm centres

Battens to suit diaphragm material

Braced wall

Villaboard™ Lining or HardieFlex™

Sheet

Minimum sheet size 1800 x 900mm. Cut sheets permitted to complete diaphragm.

Note: Flat ceiling shown, similar criteria apply for raking ceilings

®

James Hardie Bracing Design Details

a smarter way™ CEILING DIAPHRAGMS

1601 Roof

August 2016 www.jameshardie.co.nz

CAD Scale 1 :50

FIGURE: 33

jhl brce roof ceil.dwg

w

Braced wall

Fix sheets with 40 x 2.8mm HardieFlex™ nails • at 150mm centres around diaphragm boundary and

sheet perimeter and • at 200mm centres to intermediate supports and • 12mm from the edge of the sheet.• to batten spacing at maximum 600mm centres

Battens to suit diaphragm material

Braced wall

Villaboard™ Lining or HardieFlex™

Sheet

Minimum sheet size 1800 x 900mm. Cut sheets permitted to complete diaphragm.

Note: Flat ceiling shown, similar criteria apply for raking ceilings

®

James Hardie Bracing Design Details

a smarter way™ CEILING DIAPHRAGMS

1601 Roof

August 2016 www.jameshardie.co.nz

CAD Scale 1 :50

FIGURE: 33

jhl brce roof ceil.dwg

w

Braced wall

Fix sheets with 40 x 2.8mm HardieFlex™ nails • at 150mm centres around diaphragm boundary and

sheet perimeter and • at 200mm centres to intermediate supports and • 12mm from the edge of the sheet.• to batten spacing at maximum 600mm centres

Battens to suit diaphragm material

Braced wall

Villaboard™ Lining or HardieFlex™

Sheet

Minimum sheet size 1800 x 900mm. Cut sheets permitted to complete diaphragm.

Note: Flat ceiling shown, similar criteria apply for raking ceilings

®

James Hardie Bracing Design Details

a smarter way™ CEILING DIAPHRAGMS

1601 Roof

August 2016 www.jameshardie.co.nz

CAD Scale 1 :50

FIGURE: 33

Line A and B must have minimum bracing capacity 100 bus or 15 x W, whichever is higher.

Line L and M must have minimum bracing capacity 100 bu's or 15 x L, whichever is higher.

L = Length

W =

Wid

th

A

B

L M

Figure 33: Structural ceiling diaphragm

Page 45: Design ManualDIRECT FIX) 36 19 BRACING FIGURES (CAVITY FIX) 39 20 BRACING CONNECTION FIGURES (CAVITY FIX) 41 21 STRUCTUAL CEILING DIAPHRAGM 44 22 FLOOR DIAPHRAGM 45 23 BRACING CALCULATION5.2

James Hardie Bracing Design Manual August 2016 New Zealand 45

22Floor diaphragm

Figure 34: Secura™ Interior Flooring diaphragm floor

. , �· . . .. . . , : ,

Fix plate to foundation wall at 1.4 m crs. (see 6.11.9.1 of NZS 3604)

Lateral support for floor joists around perimeter of diaphragm

Note-1) Floor diaphragm to cover entire floor area (see 7.3.1 (c) of NZS 3604)2) Diaphragm size (see 7.3.1(b) of NZS 3604) for:

(a) Single storey maximum length shall not be greater than 2.5 times the width; (b) Double storey maximum length shall not be greater than 2.0 times the width.

(3) See section 4 of NZS 3604 for durability requirements.

jhl brce wall secu.dwg ®

James Hardie a smarter way™

Bracing Design Details SEGURA INTERIOR FLOORING DIAPHRAGM

Secura™ Interior Flooring 2700 x 600mm

Short edge to be supported over the floor joists

50mm 1 Og screws at centres as per enlargement below.

Foundation wall in conjunction with perimeter bracing system

Fixed joist to plate with 12/100 x 3.75 mm skew nails per 1.5 m length (see table 7.5 of NZS 3604)

1601 Foundation

25mm 25mm 25mm

EQ.

EQ.

August 2016 www.jameshardie.co.nz

CAD Scale 1 :20

FIGURE: 34

Page 46: Design ManualDIRECT FIX) 36 19 BRACING FIGURES (CAVITY FIX) 39 20 BRACING CONNECTION FIGURES (CAVITY FIX) 41 21 STRUCTUAL CEILING DIAPHRAGM 44 22 FLOOR DIAPHRAGM 45 23 BRACING CALCULATION5.2

46 James Hardie Bracing Design Manual August 2016 New Zealand

WALL BRACING CALCULATION SHEET

For use in conjunction with NZS 3604

Name of Project: ..................................................................................................................................................................................

Site of Address: ....................................................................................................................................................................................

Lot and DP Number: ............................................................................................................................................................................

BRACING DESIGN INFORMATION AS PER NZS 36041. WIND BRACING DEMAND:

Determine wind region A / W Refer Figure-5.1

Determine ground roughness: Urban / Open Refer Clause 5.2.3

Determine site exposure: Sheltered / Exposed Refer Clause 5.2.4

Determine topographic class: T1, T2, T3, T4 Refer Clause 5.2.5, Figure 5.2, Table 5.2 and 5.3

Determine wind zone: L, M, H, VH, EH Refer Table 5.1

Wind zone from Table 5.4 Minimum Number of BU’s/m for building length and width from table 5.5, 5.6, and 5.7.

Building height to apex: H =W Across = BU/m Length of wall(Applies across ridge for gable roof, Applies across and along for hip roof)

W Along = BU/m Length of wall(Applies along ridge for gable roof)

Total Bracing Required For Wind:

W Across x Length of Wall Across =

W Along x Length of Wall Along =

Roof height above eaves: h =

Stud height: =

Storey location:(Strike out which is not applicable)

Wall in foundation

Wall above subfloor structure — single storey or upper storey

Wall above subfloor structure —lower of two storeys

*Use separate sheet for each storey.

2. EARTHQUAKE BRACING DESIGN:

Refer to Figure 5.4 and select the Earthquake Zone. Zone: .................................

Wall cladding weight: n Lightn Mediumn Heavy

Roof cladding weight:n Lightn Heavy

Roof slope:n 0°-25°n 26°-45°n 46°-60°

Select storey location to be assessed as per Table 5.8, 5.9 and 5.10

n Single storey building on subfloor frame. Refer Table 5.8n Two storey building on subfloor frame. Refer Table 5.9n Single or two storey building on concrete slab-on-ground. Refer Table 5.10

Select bracing demand in BU’s/m² of floor area from one ofthe above mentioned Tables ……............ BU/m2*

Part storey in roof space Yes / No If yes, increase bracing demand obtained above by 4 BU’s/m². Refer to NZS 3604 Section 5.3.4.3

Part storey in basement Yes / No If yes, building shall be regarded as two buildings, refer section 5.3.4.4 of NZS 3604 for information

Total floor area : ………… m² Total bracing required for earthquake:

Area ……............ x ……............ BU’s/m2* = ……............ BU’s

*Use separate sheet for each storey.

23Bracing calculation tables

Page 47: Design ManualDIRECT FIX) 36 19 BRACING FIGURES (CAVITY FIX) 39 20 BRACING CONNECTION FIGURES (CAVITY FIX) 41 21 STRUCTUAL CEILING DIAPHRAGM 44 22 FLOOR DIAPHRAGM 45 23 BRACING CALCULATION5.2

James Hardie Bracing Design Manual August 2016 New Zealand 47

WALL BRACING CALCULATION SHEET B

Name of Project: ..................................................................................................................................................................................

Page 48: Design ManualDIRECT FIX) 36 19 BRACING FIGURES (CAVITY FIX) 39 20 BRACING CONNECTION FIGURES (CAVITY FIX) 41 21 STRUCTUAL CEILING DIAPHRAGM 44 22 FLOOR DIAPHRAGM 45 23 BRACING CALCULATION5.2

48 James Hardie Bracing Design Manual August 2016 New Zealand

Notes

Page 49: Design ManualDIRECT FIX) 36 19 BRACING FIGURES (CAVITY FIX) 39 20 BRACING CONNECTION FIGURES (CAVITY FIX) 41 21 STRUCTUAL CEILING DIAPHRAGM 44 22 FLOOR DIAPHRAGM 45 23 BRACING CALCULATION5.2

James Hardie Bracing Design Manual August 2016 New Zealand 49

Notes

Page 50: Design ManualDIRECT FIX) 36 19 BRACING FIGURES (CAVITY FIX) 39 20 BRACING CONNECTION FIGURES (CAVITY FIX) 41 21 STRUCTUAL CEILING DIAPHRAGM 44 22 FLOOR DIAPHRAGM 45 23 BRACING CALCULATION5.2

50 James Hardie Bracing Design Manual August 2016 New Zealand

Notes

Page 51: Design ManualDIRECT FIX) 36 19 BRACING FIGURES (CAVITY FIX) 39 20 BRACING CONNECTION FIGURES (CAVITY FIX) 41 21 STRUCTUAL CEILING DIAPHRAGM 44 22 FLOOR DIAPHRAGM 45 23 BRACING CALCULATION5.2

All James Hardie products have a standard product warranty. Refer to the relevant literature for the product warranties

Product Warranty