Upload
siva-kumar-tutika
View
218
Download
0
Embed Size (px)
Citation preview
8/8/2019 Design Guideline for Hydraulic Fluid Cleanliness Applications_Rev-F_03-2003
1/24
x = ?
x = ?
Design Guidelinefor Hydraulic FluidCleanliness
TechnicalInformation
10075
50
10
10 20
5
0.5 1 5
10
-value
Differential pressure (bar)E
x = ?
Back
8/8/2019 Design Guideline for Hydraulic Fluid Cleanliness Applications_Rev-F_03-2003
2/24
2 DKMH.PN.980.D1.02 520L0467 Rev. F 03/2003
Design Guideline for Hydraulic Fluid CleanlinessTechnical InformationPurpose of this Leaet, Contents
2003, Sauer-Danfoss
Sauer-Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Sauer -Danfoss reserves theright to alter its products without prior notice. This also applies to products already ordered provided that such alterations can be made withoutsubsequent changes being necessary in specications already agreed. All trademarks in this material are properties of the respective companies.Sauer-Danfoss and the Sauer-Danfoss logotype are trademarks of the Sauer-Danfoss Group. All rights reserved.
PURPOSE OF THIS
LEAFLET
This leaet is intended to assist the designer of an installation, a set or a hydrostatic driveto ensure that the requirement for a specic minimum cleanliness of the hydraulic uid
is met by means of design measures such as the selection of an optimal lter, or prefer-ably of an economically efcient ltration concept. This includes start-up, operation andtopping up of hydraulic uid.
Why is ltration necessary? .......................................................................................................................3Where does the dirt come from?.............................................................................................................3
Assembly dirt ............................................................................................................................................3Operating dirt ...........................................................................................................................................4
How can the required cleanliness level be achieved? .....................................................................4Denition of: -ratio, efciency, lter neness ..................................................................................6
Cleanliness Features.....................................................................................................................................8Denition of cleanliness levels per ISO 4406 .................................................................................8New particle size denition .............................................................................................................. 10Recommendation for lter neness / retaining rates (Beta-ratios) ....................................10Technical Requirements of Hydraulic Fluids............................................................................... 11Required uid cleanliness diagram................................................................................................ 12
Closed circuit ............................................................................................................................................... 13Design of a lter in the suction line ............................................................................................... 13Design of a lter in the charge circuit ........................................................................................... 13
Open circuit.................................................................................................................................................. 14Design of a lter in the suction line ............................................................................................... 14Design of a lter in the return line ................................................................................................. 14Filtration in circuits with multiple pumps.................................................................................... 14Dirt absorption capacity, maximum differential pressure ..................................................... 15
Why a bypass? ............................................................................................................................................. 16Contamination indicator ......................................................................................................................... 17
Air breather............................................................................................................................................. 17What is to be done if the required cleanliness class is not achieved?............................... 18Why loop ushing? .............................................................................................................................. 18
Sampling according to ISO 4021 from a system in operation ................................................... 19
Sampling device ................................................................................................................................... 19Sampling method ................................................................................................................................ 19Sampling from a tank according to CETOP RP 95 H................................................................ 20
Scavenging and running in............................................................................................................... 21Monitoring of contamination................................................................................................................ 22
Topping up hydraulic uid................................................................................................................ 22Changing the element........................................................................................................................ 23
CONTENTS
INITIAL QUESTIONS AND
ANSWERS
REQUIRED FLUID
CLEANLINESS
SELECTION OF AN
APPROPRIATE FILTER AND
FILTRATION SYSTEM
TAKING OF FLUID SAMPLES
WORKING HINTS
Back
8/8/2019 Design Guideline for Hydraulic Fluid Cleanliness Applications_Rev-F_03-2003
3/24
3DKMH.PN.980.D1.02 520L0467 Rev. F 03/2003
Design Guideline for Hydraulic Fluid CleanlinessTechnical Information
In hydrostatic systems a series of sliding surfaces act as hydrostatic-hydrodynamic bear-ings with gap heights in the range of 10 m. That is why dirt is the greatest enemy of
hydraulic systems, since depending on its nature and composition it generates wear andthus shortens service lives.
This is true for all elds of mechanical engineering and it cannot be repeated oftenenough. At the present time it is not possible to predict the length of the service life of ahydrostatic unit as a function of the cleanliness of the hydraulic uid. The fact that theseconstraints are not known for roller bearings either, even though very many parametershave been researched for these parts in particular, shows just how complicated thesewear mechanisms are.
Although more effort is currently being concentrated on trying to measure dirt sensitivityof hydrostatic units in short-term contamination tests, such experiments are unsuccessfulbecause contamination sensitivity cannot be measured like pressures or speeds. Theleading manufacturers of hydrostatic equipment have therefore decided to give priorityto investigating the fundamentals of wear caused by contamination in hydrostatic unitswithin the framework of a joint research project.
It is uncertain to what extent service life prognoses will be possible at the end of theresearch project, if at all. It can, however, be stated that the cleaner a system, the higherits service life expectancy.
A satisfactory service life is achieved if the cleanliness level as required below ismaintained.
We distinguish between two essential sources of dirt:
contamination occurring during assembly assembly dirt contamination occurring during operation operating dirt
Assembly dirt
Different kinds of dirt occur during the various production operations: chips, mouldingsand, core residues, cleaning-rag lint, welding beads, scale etc. Products supplied bySauer-Danfoss are therefore cleaned in modern cleaning installations after completion ofmachining operations on the individual parts. Careful attention is also paid to cleanlinesswhen these clean individual parts are assembled to form highgrade hydrostatic units.
Initial Questions and Answers
WHY IS FILTRATION
NECESSARY?
WHERE DOES THE DIRTCOME FROM?
Back
8/8/2019 Design Guideline for Hydraulic Fluid Cleanliness Applications_Rev-F_03-2003
4/24
4 DKMH.PN.980.D1.02 520L0467 Rev. F 03/2003
Design Guideline for Hydraulic Fluid CleanlinessTechnical InformationInitial Questions and Answers
WHERE DOES THE DIRT
COME FROM?
(continued)
HOW CAN THE REQUIRED
CLEANLINESS LEVEL BE
ACHIEVED?
However, since dirt occurs during the nal assembly in a vehicle, of a set etc., especiallyduring the piping work, it is advisable to ush the whole system prior to commissioning.
The basic contamination of the clean hydraulic uid supplied must also be added to theassembly dirt. As investigations have shown, new hydraulic uid can contain basic dirtlevels in excess of the cleanliness level admissible for optimum operation (see Cleanlinessrequirements section). That is why a system should always be lled up via a lter assembly.Particles of the same order of magnitude as the gap widths are to be considered asespecially critical.
Operating dirt
Fine dirt from the surrounding environment is drawn into the hydraulic system duringoperation via piston rods or other moving seals. Abrasive particles from the componentsare also pumped through the system with the uid. A frequently underestimated sourceof contamination is from unsuitable venting facilities of uid tanks. Fluctuations involume cause ne dust to be drawn into the tanks, from where it causes abrasion of thesliding combinations in the system.
A ltration system must be designed in such a way that it is able to retain the new dirtentering the overall system in the lter in order to maintain the required cleanliness levelthroughout the whole operating life.
An exampleof this is described below:If a lter is used in the suction line or the charge circuit, the charge pump size selected -in our example 17 cm3 - determines the volume ow available for ltering as a function ofthe speed. The following theoretical calculation serves to illustrate this (see an illustration
P001 318):
Assuming that the pump runs at a nominal speed of 1500 min-1, then at an assumedvolumetric efciency of 90 %, a charge pump volume ow of approx. 23 l/min results. Acontamination level of 230 particles larger than 10 m/ml has developed in the oil tankand a lter with 35 = 75,10 = 2 (= 50 % ltration efciency, see table below) is tted in thesuction line. The contamination is also distributed uniformly in the uid. Approximately5.3 x 106 particles larger than 10 m per minute are now drawn from the tank with thecharge pump ow. The lter element holds back 50 % of the particles larger than 10 m,so that 2.65 x 106 particles larger than 10 m reach the charge pump each minute.
If 2.65 x 106 particles larger than 10 m are also passed to the system per minute (via
ventilation lters, piston rods or abrasion), there is no change in the cleanliness level. Iffewer than 2.65 x106 particles larger than 10 m are passed to the system, a lower i.e. abetter cleanliness level is achieved. However if more than 2.65 x106 particles larger than10 m are passed to the system, a higher i.e. a worse cleanliness level is achieved.
As mentioned at the beginning, this calculation is very close to conditions encounteredin practice, but these will never be so exact because particles will settle at the bottom ofthe tank in areas with a low ow velocity. Nor are the particles so uniformly distributedwhen they pass through the lter. This example is merely intended to illustrate theprinciple and it can be established that:
Back
8/8/2019 Design Guideline for Hydraulic Fluid Cleanliness Applications_Rev-F_03-2003
5/24
5DKMH.PN.980.D1.02 520L0467 Rev. F 03/2003
Design Guideline for Hydraulic Fluid CleanlinessTechnical InformationInitial Questions and Answers
HOW CAN THE REQUIRED
CLEANLINESS LEVEL BE
ACHIEVED?(continued)
The cleanliness level is improved if:
the lter neness is improved
(higher -value for a certain particle size, i.e.10 = 2 becomes 10 = 2.5). the volume ow* via the lter is increased.
The cleanliness level deteriorates if:
the lter neness deteriorates(lower -value for a certain particle size, i.e.10 = 2 becomes 10 = 1.8).
the volume ow* via the lter is reduced.
The ow volume cannot generally be selected freely since it is determined in a closedcircuit by the size of the charge pump. However other operating factors take prioritywhen the charge pump size is selected. In these cases, therefore, the -value must bevaried. However, if the -value is increased (different lter material) without the structuraldimensions of the lter being increased, then the consequence is that: the differential pressure rises (applies for new, uncontaminated lter element) the dirt absorption capacity drops (reduced service life).
* Note the change of the -value shown on page 14, diagram P001 332E. The alteration of the volume ow alsochanges the differential pressure and hence the value too. However the volume ow has more inuenceon the cleanliness level.
Schematic Series 90 variable pump with suction lter
P001 318E
2.65 x 106 particles > 10 m/min
35 = 75 (10 = 2 equivalent 50 %)
Q = 23 l/min
5.3 x 106 particles > 10 m/min
230 particles > 10 m/ml
L2 S
Servo
M
A
B
L1
Back
8/8/2019 Design Guideline for Hydraulic Fluid Cleanliness Applications_Rev-F_03-2003
6/24
6 DKMH.PN.980.D1.02 520L0467 Rev. F 03/2003
Design Guideline for Hydraulic Fluid CleanlinessTechnical InformationInitial Questions and Answers
The -ratio is dened and determined in ISO 16 889-1999 Multi-pass test(old: ISO 4572-1982) as:
Number of particles > x m upstream of the lterX = Number of particles > x m downstream of the lter
As a characteristic number the 10-ratio is to be specied.
Example: 500 particles > 10 mm upstream of the lter10 = = 50 10 particles > 10 mm downstream of the lter
This number denes the ratio of the number of particles before and after the lter. Thismeans from 500 particles larger than 10 m before the lter, 490 particles are retainedin the element and only 10 pass through or from 50 particles before the lter, 49 areretained and only 1 passes through. This can be expressed as lter efciency:
500 - 10 50 - 1Filter efciency = = = 98 % 500 50
or: 1 1Filter efciency = 1 - = 1 - = 98 % 10 50
This efciency makes the lter performance more understandable. Table below showsclearly the relationship between -ratio and efciency. In practice the following term isoften used:
X = 75 (= 98,67 % efciency)
The observant reader will notice that increasing the -ratio by 50 % (from 50 to 75) theefciency only increases by 0.67 %. Thereforex-ratios above 75 are not reasonable.In some lter manufacturers catalogues you sometimes nd X larger than 2000. A look inthe table below shows the real efciency increase. The 10 = 75-ratio has been establishedas a standard. This species the particle size (indicated as x) were the -ratio is equal to75. This particle size is used to classify the lter neness.
Example: 35 = 75 equals a lter neness of 35 m
The term absolute lter neness may not be used for this.
Together with the -ratio the related differential pressure at the lter element has to bespecied. Unfortunately this is not always specied in the lter manufacturers catalogue.
DEFINITION OF:
-RATIO, EFFICIENCY,
FILTER FINENESS
Back
8/8/2019 Design Guideline for Hydraulic Fluid Cleanliness Applications_Rev-F_03-2003
7/24
7DKMH.PN.980.D1.02 520L0467 Rev. F 03/2003
Design Guideline for Hydraulic Fluid CleanlinessTechnical InformationInitial Questions and Answers
DEFINITION OF:
-RATIO, EFFICIENCY,
FILTER FINENESS(continued)
nosirapmoC susrevoitar- i
oitar- ycneiciffe oitar- ycneiciffe
1 0.0 4.6 4.48
1.1 1.9 8.6 3.58
2.1 7.61 0.7 7.58
3.1 1.32 2.7 1.68
4.1 6.82 4.7 5.68
5.1 3.33 6.7 8.68
6.1 5.73 8.7 2.78
7.1 1.14 0.8 5.78
8.1 4.44 2.8 8.78
9.1 3.74 4.8 1.88
0.2 0.05 6.8 4.88
1.2 4.25 8.8 6.88
2.2 5.45 0.9 9.88
3.2 5.65 2.9 1.98
4.2 3.85 4.9 4.98
5.2 0.06 6.9 6.98
6.2 5.16 8.9 8.98
7.2 9.26 0.01 0.09
8.2 3.46 0.11 9.09
9.2 5.56 0.21 6.19
0.3 6.66 0.31 3.29
1.3 7.76 0.41 9.29
2.3 8.86 0.51 3.39
3.3 7.96 0.61 8.39
4.3 6.07 0.71 1.49
5.3 4.17 0.81 4.496.3 2.27 0.91 5.49
7.3 9.27 0.02 0.59
8.3 7.37 0.03 7.69
9.3 4.47 0.04 5.79
0.4 0.57 0.05 0.89
2.4 2.67 0.06 3.89
4.4 3.77 0.07 6.89
6.4 3.87 0.57 76.89
8.4 2.97 0.08 7.89
0.5 0.08 0.09 9.89
2.5 8.08 0.001 0.99
4.5 5.18 0.002 5.99
6.5 1.28 0.005 8.99
8.5 8.28 0.0001 9.99
0.6 3.38 0.0002 59.99
2.6 8.38
"efficiency"
Back
8/8/2019 Design Guideline for Hydraulic Fluid Cleanliness Applications_Rev-F_03-2003
8/24
8 DKMH.PN.980.D1.02 520L0467 Rev. F 03/2003
Design Guideline for Hydraulic Fluid CleanlinessTechnical Information
The old ISO 4406-1987 denes the cleanliness level of particles larger than 5 m and15 m. As an example: if 1910 particles/ml larger than 5 m and 71 particles/ml largerthan 15 m are counted, the ISO 4406-1987 code level is 18/13.In 1999 both,the denition for particle counting and the denition of ISO code was
changed. The required cleanliness class denition is now determined by ISO 4406-1999.The allocated particle sizes are:
Please note, that (c) must be added to the new denition in order to identify that it isthe new ISO 4406. The old method for particle counting may still be used.
The ISO 4406-1999 cleanliness class 22/18/13 means:
22 species the number of particles larger than 4 m (c),18 species the number of particles larger than 6 m (c),and13 species the number of particles larger than 14 m (c) related to 1 ml respectively100 ml of the inspected uid.
CLEANLINESS FEATURES Denition of cleanliness levels per ISO 4406
The cleanliness level of a hydraulic uid is determined by counting number and size of
particles in the uid. The number of particles is dened as a cleanliness level according toISO 4406.
selcitrapforebmuN
lm001rep
selcitrapforebmuN
lm1rep
levelssenilnaelC
6044OSIrep
2-1 20.0-10.0 1
4-2 40.0-20.0 2
8-4 80.0-40.0 3
61-8 61.0-80.0 4
23-61 23.0-61.0 5
46-23 46.0-23.0 6
.cte .cte .cte
01x4 3 01x8- 3 08-04 31
01x8 3 01x61- 3 061-08 41
01x61 3 01x23- 3 023-061 51
01x23 3 01x46- 3 046-023 61
01x46 3 01x031- 3 0031-046 71
01x031 3 01x052- 3 0052-0031 81
01x052 3 01x005- 3 0005-0052 91
.selcitrapforebmunehtflahroelbuodsnaemlevelssenilnaelctxenehtotpetsehT
Definition of cleanliness levels per ISO 4406
denifedton )c(m4
m5 )c(m6
m51 )c(m41
Old ISO 4406-1987 New ISO 4406-1999
Required Fluid Cleanliness
Back
8/8/2019 Design Guideline for Hydraulic Fluid Cleanliness Applications_Rev-F_03-2003
9/24
9DKMH.PN.980.D1.02 520L0467 Rev. F 03/2003
Design Guideline for Hydraulic Fluid CleanlinessTechnical Information
The new method counts more smallerparticles and less larger particles.For better understanding please see thegraph beside. This graph demonstratesthe effect of the change to the newparticle sizes 4 m (c), 6 m (c), and14 m (c).Again, the actual number of par ticles ofa sample is of course the same, only thecounting method is different. Althoughit may look like, the new method doesnot allow more particles!
CLEANLINESS FEATURES
(continued)
Measurements with the same uid sample will result in the same cleanliness class forboth methods as shown in the table below.
Together with this ISO 4406 change a new calibration standard ISO 11 171-1999 and anew Multipass test ISO 16 889-1999 for lters have been developed.
ISO 4406-1999 versus prior cleanliness classes
00
5 10
1000
2000
3000
4000
5000
15 17
Particle size (m)
Numberofparticlesp
erml
ISO 4406-1987ISO 4406-1999
P001948E
Number of particles per milliliter, particle count comparison
eziselcitraP m1 )c(m4 m5 )c(m6 )c(m41 m51
dezidradnatstoN 0004 - - - - -
7891-6044OSIdlO - - 0002 - - 081
9991-6044OSIweN - 0004 - 0002 081 -
ssalcssenilnaelc6044OSI 91 91 81 81 51 51
sdradnatsdlO noitpircsedtseT sdradnatsweN
1991-2044OSI noitarbilac)CPA(retnuocelcitrapcitamotuA 9991-17111OSI
7891-6044OSI edocssenilnaelC 9991-6044OSI
2891-2745OSI sretlifroftsetssapitluM 9991-98861OSI
Comparison between old and new standards
Required Fluid Cleanliness
Back
8/8/2019 Design Guideline for Hydraulic Fluid Cleanliness Applications_Rev-F_03-2003
10/24
10 DKMH.PN.980.D1.02 520L0467 Rev. F 03/2003
Design Guideline for Hydraulic Fluid CleanlinessTechnical InformationRequired Fluid Cleanliness
For charge pressure and return line ltration a suction screen with a mesh width of100 - 125 m must be used in the suction line to prevent sudden damage due to largeparticles.Please see Design Guideline for Hydraulic Fluid CleanlinessTechnical Information for furtherinformation on how the cleanliness requirements can be achieved.
Recommendation for lter neness / retaining rates (Beta-ratios)
CLEANLINESS FEATURES
(continued)
13 m
d = 13 m
Square 78.5 m2
d = 10 m
Old: New:
P001 935E
New particle size denition
The particle size denition has been changed also. The old standard dened the largest
particle extension as the particle size. The new standard uses the projected square areaand converts this to an equivalent diameter. Please see the picture below.
78.5 m2 4d = = 10 m
ISO 4407 (under revision) species particle counting with a microscope. Only particleslarger 5 m and 15 m are manually counted and specied as /18/13. The is used inplace of the rst scale number, while 18 is allocated to 5 m and 13 to 15 m.
)tiucricnepo+desolc(noitartlifnoitcuS 54-53
(57= 01> )2
)tiucricdesolc(noitartliferusserpegrahC 02-51 (57= 01 > )01
)tiucricnepo(noitartlifenilnruteRlareneg
54-53(57=
01> )2
srotomdnaspmupraegrof 02-51
(57= 01> )01
Recommended-ratios
Back
8/8/2019 Design Guideline for Hydraulic Fluid Cleanliness Applications_Rev-F_03-2003
11/24
11DKMH.PN.980.D1.02 520L0467 Rev. F 03/2003
Design Guideline for Hydraulic Fluid CleanlinessTechnical InformationRequired Fluid Cleanliness
Fluid cleanliness requirements
To achieve the specied unit life a cleanliness level as shown below must be met. Fluid
samples shall be taken either in the loop or at the entry to the pump which is typicallythe suction line.Fluid cleanliness requirements depends on the product and the products acceptablecontinuous or rated pressure limits.
TECHNICAL
REQUIREMENTS OF
HYDRAULIC FLUIDS
In general for uid change and new uid top up minimum cleanliness class 23/21/15 andfor rst machine start up at the factory minimum cleanliness 25/22/16 must be met ifnot otherwise specied. Exceeding these levels may result in start-up damage.
The before mentioned requirements reect the experience gained from a broad range ofapplications. For very high lifetime requirements or contamination sensitive components(e.g. servo valves) better cleanliness levels are necessary.
tcudorPssalcssenilnaelcderiuqeR
9991-6044OSI
margaidnievruC
woleb
ertnecnepohtiwstnenopmocgnireetS 71/02/22 A
srotomlatibrO 61/02/22 B
ertnecdesolcdnaSLhtiwstnenopmocgnireetS61/91/12 C
evlavloopslanoitroporP
s, ASC-valverotomdnaspmupnotsiplaidar+laixA31/81/22 D
srotomdnaspmupraeG
evlavciluardyhortcelednaegdirtraC 31/61/81 E
Fluid cleanliness requirements
Back
8/8/2019 Design Guideline for Hydraulic Fluid Cleanliness Applications_Rev-F_03-2003
12/24
8/8/2019 Design Guideline for Hydraulic Fluid Cleanliness Applications_Rev-F_03-2003
13/24
13DKMH.PN.980.D1.02 520L0467 Rev. F 03/2003
Design Guideline for Hydraulic Fluid CleanlinessTechnical Information
The design is explained below taking an SPV 9/075 with a charge pump volume of17 cm3 by way of example. A continuous pressure of 240 bar is assumed. Accordingly in
section 3 the cleanliness class 18/13 to ISO 4406 results from curve A.
Design of a lter in the suction line
Examinations have revealed that a lter in the suction line with a 35 - 45 = 75 at a dif-ferential pressure of 0.25 bar achieves the required cleanliness level18/13 under normaloperating conditions. In some applications even better cleanliness levels are achieved.In order to assure that the cleanliness class is maintained we recommend that samplesof the hydraulic uid be drawn during the running-in time and that the particles becounted. A certain, constant cleanliness level will emerge during the operating time (seethe illustration below).
Cleanliness level evolving as a function of operating hours for particles larger than 15 m
Selection of an Appropriate Filter and Filtration System
EXAMPLE
CLOSED CIRCUIT
Filter A
Filter B
16
15
14
13
12
11
10
Cleanlinesslevel(ISO4406)
1 10 100
P001 320EOperating hours
An analogous graph can be drawn up forany particle size.The following reference can serve as afurther guide.
A lter element with a 10 = 2.0 - 1.5 at0.25 bar differential pressure (50 % - 33 %ltration efciency for particles > 10 m)generally reaches the above mentioned35 - 45 = 75 value.
Design of a lter in the charge circuit
We recommend using lter elements with 15 - 20 = 75 (10 = 10 corresponding to 90 %ltration efciency) at the differential pressure occurring in the application. A strainerwith a mesh of 100 m - 125 m has to be used to protect the charge pump againstcoarse contamination. However the actual ltering work has to be performed by thelter in the charge circuit.
On the basis of what has been said so far the question arises:Why is a higher lter neness (-value) necessary in a lter in the charge circuit?
Answer:
The Multi-pass-test per ISO 16 889 determines the -values at constant volume ow andalmost constant differential pressure increase. These optimal conditions do not existin the charge circuit so that a reduced -value sets in as a result of volume ow andpressure uctuations. The lter industry and research institutes are in the process ofdeveloping practice-oriented test methods to solve this problem. Furthermore, thepossible level of pressure uctuations is much lower in a suction lter. Moreover incertain circuits the lter is arranged behind the charge circuit pressure limiting valve, sothat the whole charge pump volume ow does not constantly pass the lter. Related tothe whole charge pump volume ow, an arithmetically lower -value emerges here too.
As already said above for the lter in the suction line, it is recommended that the clean-liness level actually existing or evolving in the course of time be determined here too.
Back
8/8/2019 Design Guideline for Hydraulic Fluid Cleanliness Applications_Rev-F_03-2003
14/24
14 DKMH.PN.980.D1.02 520L0467 Rev. F 03/2003
Design Guideline for Hydraulic Fluid CleanlinessTechnical Information
Design of a lter in the suction line
Unlike the situation in the closed circuit, the whole main volume ow is taken from
the tank. That is why these suction lters must be adequately dimensioned in order toachieve appropriate differential pressures and service lives. On the other hand a lowerlter neness can be selected, since a higher volume ow is available.(For further information please see next page.
Design of a lter in the return line
In the case of return line lters in open circuits, special attention must be paid to discon-tinuous volume ows through working cylinders with differing area ratio. Under certaincircumstances it might therefore be advisable to select a larger lter than would benecessitated by the suction line alone. In any case a strainer with a mesh size of 100 - 125m should be provided in the suction line.
Filtration in circuits with multiple pumps
A machine with several pumps using the same reservoir may use one lter only to savecosts. Every circuit must be protected by a suction strainer with 100 -125 m mesh.
This mesh equals theoretically: 100-150 = 75This term should not be used for a screen.The off-line ltration may feed other functions and circuits like the steering equipment.
Recommendations for differential pressure (pressure drop) of a new lter element
and -ratios for closed and open circuit
In suction line (closed and open circuit): Differential pressure: 0,1 bar (clean element) at: Viscosity: 30 mm2/s Flow: closed circuit: charge pump displacement x rated speed
open circuit: pump displacement x rated speed -ratio: 35 - 45 = 75 (10> 2)
In charge line(for closed circuit): Differential pressure: 0,7 bar (clean element) at: Viscosity: 30 mm2/s Flow: charge pump displacement x rated speed -ratio: 15 - 20 = 75 (10> 10)
In return line (only open circuit): Differential pressure: 0,5 bar (clean element) at: Viscosity: 30 mm2/s Flow: charge pump displacement x rated speed -ratio: general: 35 - 45 = 75 (10> 2)
for gear pumps and motors: 15 - 20 = 75 (10> 10)
By-pass ltration: as in Charge line
There will and must be exceptions to these recommendations to ensure an economicltration system.
Selection of an Appropriate Filter and Filtration System
OPEN CIRCUIT
Back
8/8/2019 Design Guideline for Hydraulic Fluid Cleanliness Applications_Rev-F_03-2003
15/24
15DKMH.PN.980.D1.02 520L0467 Rev. F 03/2003
Design Guideline for Hydraulic Fluid CleanlinessTechnical Information
Dirt absorption capacity, maximum differential pressure
A further criterion for selecting the lter size is the dirt absorption capacity and differen-
tial pressure rise in the case of increasing contamination, see illustration below.
When the Multi-pass-test to ISO 16 889 is performed, the dirt absorption capacity is alsodetermined. It is important to distinguish between the apparent dirt absorption capacity,which is the amount of dirt added during the test, and the real dirt absorption capacity,which is the amount of dirt actually retained in the lter.
The following equation applies:
Added dirt quantity (apparent dirt absorption capacity) minus dirt quantity
remaining in the oil is the actual dirt absorption capacity.
Selection of an Appropriate Filter and Filtration System
OPEN CIRCUIT
(continued)
Change filter!
6
4
3
2
Differentialpressure
bar
10 20 30
P001 321E
Dirt Capacity (g)
5
1
In the illustration beside the rise inthe differential pressure starts in anapproximately linear manner beforerising exponentially.
Once this zone is reached it is timeto change the lter, since a little dirtmeans a large increase in the differentialpressure. In the case of the above lterelement, the contamination indicatorshould respond either optically orelectrically at approximately 2.2 bar and
indicate that it is time to change theelements concerned.
Rise of the differential pressure when dirt is
added
Depending on the lter material, certainmaximum differential pressures must notbe exceeded since the lter material maybe damaged and dirt already retainedwill be released again, i.e. the dirtis pumped through.
The curve of the -value versus the
differential pressure shows this(see illustration besides).
If it is expected that the lter elementwill not be changed in time beforethe rupture point is achieved, a bypassvalve (see below) must be installed.A bypass valve must also be providedif the differential pressure rises to aninadmissible level during cold starts,which is usually the case.
Retention rate as a function of the differential
pressure
10075
50
10
10 20
5
0.5 1 5
10
-value
Differential pressure (bar)P001322E
Back
8/8/2019 Design Guideline for Hydraulic Fluid Cleanliness Applications_Rev-F_03-2003
16/24
16 DKMH.PN.980.D1.02 520L0467 Rev. F 03/2003
Design Guideline for Hydraulic Fluid CleanlinessTechnical InformationSelection of an Appropriate Filter and Filtration System
Although the effective lter efciency is reduced by the short opening of the bypassduring cold starts, the hydrostatic unit is not immediately damaged as a result of this. Thecleanliness level simply deteriorates as a function of the time during which the bypass isin operation and as a function of the newly generated particles. Working with an openbypass for several hours or days should be avoided. This condition can be monitoredreliably with a contamination indicator (see below). The system operator thus determinesthe service life of the hydrostatic units and the rest of the system by regularly checkingthe contamination level of the lter and changing the lter elements in time.
It is important to understand that if used as explained above, a bypass is always betterthan the sudden release of a particle or a dirt cloud due to damage to an elementwhereby the cloud is passed through the whole system (including the high-pressure
circuit) and nally lands in the tank after irreparable damage is sustained by the slidingparts. If there is no contamination indicator either, this damage is not noticed and it maybe that the system is operated for a long time with this unintentional bypass (afterthe element has been destroyed!) until overheating caused by reduced efciency of thehydrostatic units is recognized. This then turns out to be much more expensive than theadditional bypass and the contamination indicator would have been (see section on page15 for contamination indicator).
Note: A bypass should be arranged as shown above or even further away from the element if the design allowsthis. Under certain circumstances it may even be a design advantage if the lter elements are to be bolteddirectly on to the pump (charge circuit ltration). A bypass may never be situated in the base of the lterelement since the dirt settles in this area and is ushed into the system again.
WHY A BYPASS? Function of a bypassDuring operation the differential pressureat the lter element rises due to contami-
nation. Without a bypass, especiallyduring cold starts, this would lead todemage to the lter element or collapseof the support elements. This can beeffectively prevented by the use of abypass.
P001 324E
Back
8/8/2019 Design Guideline for Hydraulic Fluid Cleanliness Applications_Rev-F_03-2003
17/24
17DKMH.PN.980.D1.02 520L0467 Rev. F 03/2003
Design Guideline for Hydraulic Fluid CleanlinessTechnical InformationSelection of an Appropriate Filter and Filtration System
CONTAMINATION
INDICATOR
AIR BREATHER
The contamination indicator responds when a predetermined differential pressureoccurs as a result of growing contamination of the lter element. An optical signal
appears, or an electrical contact is energized.
Function of the contamination indicator (differential pressure)
1. Pressure before the lter element2. Pressure behind the lter element3. Position of the magnets in a clean
element4. Position of the magnets in a contami-
nated element.
P001 323
Sufcient attention must also be devoted to air breathers, since a considerable portionof the contamination makes its way into hydraulic systems via unsuitable ventilationsystems. Design measures such as pressurizing reservoirs are often not economicallyefcient by comparison with todays air breathers. Under certain circumstances it maybe necessary to observe the Pressurized Container Regulations if the pressure content
product derived from tank volume times pressure exceeds a certain value.
Unfortunately there is no standard for air breathers corresponding to the Multi-pass testto ISO 16 889. The lter neness quoted by the manufacturer of the air breathers has tobe relied on. This does not permit comparisons between manufacturers A and B since,as already mentioned, there are no standardized tests. Generally speaking the neness ofthe air breathers must be equivalent to or better than the working lters present in thesystem. Therefore only the x = 75 values and the given lter neness of the air breatherscan be taken as standard values.
Back
8/8/2019 Design Guideline for Hydraulic Fluid Cleanliness Applications_Rev-F_03-2003
18/24
18 DKMH.PN.980.D1.02 520L0467 Rev. F 03/2003
Design Guideline for Hydraulic Fluid CleanlinessTechnical InformationSelection of an Appropriate Filter and Filtration System
As a brief reminder:It was explained before that the cleanliness level is inuenced by:
the -value (lter neness, ltration ratio) the volume ow through the lter.
If the required cleanliness level is not achieved using the 17 cm3/U charge pump andthe 10 = 75 lter, it is not necessarily expedient to use a larger charge pump. This maynecessitate a larger lter since the differential pressure more quickly reaches the limitof p = 0.25 bar (risk of cavitation) with a clean lter element, which leads to insufcientservice life of the element. The energy balance also deteriorates as a result of the higherpower loss.
In this case lters with a higher -value must be used. However, since the higher -valuesgenerally also involve higher differential pressures, it is often also necessary to movethe lter to the charge circuit. If the lter elements are designed accordingly, higherdifferential pressures are admissible here so that the overall dimensions of the lter canbe reduced - representing an installation advantage. It must also be claried and checkedto what extent new contamination can be reduced and prevented.
It was explained before that inadequate ventilation facilities are a cause of freshcontamination. An improvement of the cleanliness level can often be achieved by usingventilation lters with better lter neness, especially for applications with workingcylinders with differing area ratios.
For the design of the ventilation lter the differential pressure (caused by the differentialair volume ow) must be kept as low as possible in order to prevent cavitation in the
suction area of the pumps. It should also be checked whether unsuitable piston rod sealsor leaks are the cause.
Remember: Dirt which does not enter the system or is not caused by wear need not beremoved by ltration.
Filtration is intended to remove contamination from the hydraulic uid. For this, however,the contamination must be passed to the lter element. In a closed circuit withoutcircuit purging, existing contamination can only be removed from the system with the oilleaking from the pistons, the control valve etc. Since only particles smaller than the leakgap width can leave the closed circuit, the remaining particles stay in the circuit and can
lead to erosion damage in areas with high ow velocities.
This can be avoided by circuit purging, i.e. by forcing 5 - 6 l/min from the low pressurecircuit via an spool valve and a purge relief valve.
The contamination ushed out in this way (including particles larger than the leak gapwidth) can now be passed to the lter element installed in the system and be removed.
WHAT IS TO BE DONE
IF THE REQUIRED
CLEANLINESS CLASSIS NOT ACHIEVED?
WHY LOOP FLUSHING?
Back
8/8/2019 Design Guideline for Hydraulic Fluid Cleanliness Applications_Rev-F_03-2003
19/24
19DKMH.PN.980.D1.02 520L0467 Rev. F 03/2003
Design Guideline for Hydraulic Fluid CleanlinessTechnical InformationTaking of Fluid Samples
Fluid samples must be drawn very carefully into appropriate bottles to preventextraneous dirt from, falsifying the sample result.
The sample bottle should contain a label with the following information: Sample number Source of sample Sampling method Date and time of sampling Nature of uid Comments/remarks if necessary
Sampling points should be provided at the design stage of the hydraulic installation.They should be arranged in the turbulent main ow.
Sampling device
Important: Take precautionary measures to protect personnel and equipment. If turbulent ow conditions prevail in the main ow, a typical sampling device as
illustrated in the illustration P001 325 A quick fastening coupling 6 is permanently attached to the opening through which
the sample is to be withdrawn. A dust protection cap 1 is provided for the part 6. The remaining part of the unit 2-5 is secured for sampling. The inner diameter and length of the capillary tube are selected in agreement with
the desired sample quantity. Capillary tubes with an inner diameter of less than 1.25 mm may not be used. Other
cross-sectional forms (e.g. rectangular) can be used, provided that the smallest internal
dimension is not less than 1 mm. The end of the capillary tube is sharpened and deburred in order to facilitate the
subsequent penetration of the lm which covers the opening of the sample bottles. If no turbulence can be guaranteed in the ow, a device for generating turbulence
must be used, e.g. a turbulent sampler.
Sampling method
Ball valve 5 is opened. Allow at least 200 ml uid to ow through the sampling device before collecting the
uid. Without closing the ball valve, place the sample bottle in the position for collecting
the uid. Pierce the protective lm covering the bottle opening with the sharp end of thecapillary tube.
Draw a sample of not more than 90 % and not less than 50 % of the bottle volume. When a sufcient sample quantity has been collected, remove the sample bottle
before stopping the ow with the ball valve. Seal the sample bottle immediately after withdrawing the capillary tube. If a sampling device with quick-fastening coupling is used, the removable parts of the
sampling device are to be dismantled and all other uid traces are to be removed byushing with a suitable solvent.
Immediately after dismantling the dust protection cap is replaced on the permanentlymounted part of the quick fastening coupling.
TAKING OF FLUID
SAMPLES
SAMPLING ACCORDING
TO ISO 4021 FROM
A SYSTEM IN OPERATION
Back
8/8/2019 Design Guideline for Hydraulic Fluid Cleanliness Applications_Rev-F_03-2003
20/24
8/8/2019 Design Guideline for Hydraulic Fluid Cleanliness Applications_Rev-F_03-2003
21/24
21DKMH.PN.980.D1.02 520L0467 Rev. F 03/2003
Design Guideline for Hydraulic Fluid CleanlinessTechnical Information
The frequency and intensity of the maintenance work to be performed depend on theburden generated by environmental inuences and on the workload.
Special attention must always be paid to the operational suitability and cleanness of thehydraulic uid.
Scavenging and running in
Before a hydraulic system is commissioned, the assembly dirt must be removed. Thisis best done by ushing the whole installation with a portable lter unit. Mineral oil(or another medium compatible with the hydraulic uid to be used subsequently) ispumped through the whole system or parts of the system at the highest possible owvelocity. The assembly dirt is ltered in the lter unit.
During this process the elements of the built-in lters are to be removed. Small or lesssensitive systems can also be scavenged with the built-in lters during the running-inprocess. It must be ensured that the system is run without load but with a displacementwhich is gradually increased up to maximum. The illustration belowshows the relationbetween the design-specic, admissible cleanliness level and the actual cleanliness priorto commissioning.
Working Hints
WORKING HINTS
Typical relation between the design-specic, admissible cleanliness level Aand the actual cleanliness level prior tocommissioning D.
It is vital that the system be ushed andrun at low pressure until the requiredcleanliness level is achieved.
Particlecountperunitvolume
Particle size in m (log2)
102
10 15 5025 100
P001 326E
5
103
104
105
106
D
A
Back
8/8/2019 Design Guideline for Hydraulic Fluid Cleanliness Applications_Rev-F_03-2003
22/24
22 DKMH.PN.980.D1.02 520L0467 Rev. F 03/2003
Design Guideline for Hydraulic Fluid CleanlinessTechnical Information
Permanent
Every lter should be equipped with an optical/electrical indicator of the contamination
level at the lter. In this way it is possible to establish at any time whether there is still anydirt absorption capacity or whether the elements have to be changed. The checks shouldbe carried out daily once the operating temperature is achieved.
If a contamination indicator with electrical signal device is used, the selected signal isemitted at operating temperature when the lter element is contaminated. During thewarming up phase a contaminated signal is nearly always emitted due to the higherdifferential pressure unless the contamination indicator is equipped with a signal cut-outfor the cold start phase.
Cyclical
With regular monitoring, lters are suitable as wear surveillance elements for thecomponents of the hydraulic system. If the operator keeps a log of lter changes, itcan be assumed in the event of shorter changing intervals that the wear of the systemcomponents is increasing. The origin of the main contamination can be ascertained byanalysing a uid sample and the contaminated element. A comparison of the results withthe materials used allows preventive maintenance before a complete failure interruptsproduction or operation. Adherence to the required cleanliness level is checked bymeasuring the contamination and this ensures that no premature wear or failure occurs.
These samples must be drawn at specially designed sampling points as explained before.
Topping up hydraulic uid
Any uid used to top up losses should always be poured in via a ne lter in order to
maintain the cleanliness class. Where appropriate facilities are available, the returnow lter can be used. It is advisable to provide a permanent connection which shouldbe included in considerations at the design stage. Any opening of the tank/reservoirfor maintenance purposes (topping up hydraulic uid, sampling, changing lter ele-ments in built-in tanks etc.) should always be avoided as far as possible by an expedientdesign. Even though some ventilation lters have a so-called lling screen (mesh width> 100 m), this still does not afford any protection against the penetration of particles ofthe order of magnitude of 10 - 100 m.
MONITORING
OF CONTAMINATION
Working Hints
Back
8/8/2019 Design Guideline for Hydraulic Fluid Cleanliness Applications_Rev-F_03-2003
23/24
23DKMH.PN.980.D1.02 520L0467 Rev. F 03/2003
Design Guideline for Hydraulic Fluid CleanlinessTechnical Information
Changing the element
If the contamination indicator shows a contaminated element, this must be changed
without delay due to the high rate of increase of pressure drop as the element becomesmore contaminated.Extreme care must be taken when changing the element. The operating instructionsmust be followed precisely.
The following standard values apply for lter maintenance intervals:
1. 24 hours after commissioning the system2. After the running-in period (50 - 100 hours of service)3 Normal maintenance after 300 - 500 hours of service
Literature:
1. Guidelines to Contamination Control in Hydraulic Fluid Power Systems (1985),AHEM (The Association of Hydraulic Equipment Manufacturers, London)
2. Filterbel fr Hydraulikssigkeiten und Schmierstoffe,MAHLE Industrielter, hringen
3. Leitfaden zur Optimalen Auswahl von Argo Filtertypen fr Hydrauliksysteme,ARGO Filter, Kraichtal-Menzingen.
Figure and text source: 9, 17, 18, 20, 21, 22, 23 MAHLE Industrielter
MONITORING
OF CONTAMINATION
(continued)
Working Hints
Back
8/8/2019 Design Guideline for Hydraulic Fluid Cleanliness Applications_Rev-F_03-2003
24/24
Sauer-Danfoss Hydraulic Power Systems
Market Leaders Worldwide
Sauer-Danfoss is a comprehensive supplier providing completesystems to the global mobile market.
Sauer-Danfoss serves markets such as agriculture, construction, roadbuilding, material handling, municipal, forestry, turf care, and manyothers.
We offer our customers optimum solutions for their needs anddevelop new products and systems in close cooperation andpartnership with them.
Sauer-Danfoss specializes in integrating a full range of systemcomponents to provide vehicle designers with the most advancedtotal system design.
Sauer-Danfoss provides comprehensive worldwide service for its
products through an extensive network of Authorized ServiceCenters strategically located in all parts of the world.
OUR PRODUCTS
Hydrostatic transmissions
Hydraulic power steering
Electro-hydraulic power steering
Electric power steering
Closed and open circuit axial piston
pumps and motors
Gear pumps and motors
Bent axis motors
Orbital motors
Transit mixer drives
Planetary compact gears
Proportional valves
Directional spool valves
Cartridge valves
Hydraulic integrated circuits
Hydrostatic transaxles
Integrated systems
Fan drive systemsElectrohydraulic controls
Digital electronics and software
Electric motors and inverters
Sensors
Sauer-Danfoss (US) Company2800 East 13th StreetAmes, IA 50010, USAPhone: +1 515 239-6000, Fax: +1 515 239 6618
Sauer-Danfoss (Neumnster) GmbH & Co. OHGPostfach 2460, D-24531 NeumnsterKrokamp 35, D-24539 Neumnster, GermanyPhone +49 4321 871-0, Fax: +49 4321 871 122
Sauer-Danfoss (Nordborg) A/SDK-6430 Nordborg, DenmarkPhone: +45 7488 4444, Fax: +45 7488 4400
Back