38
i DESIGN A FILTER FOR HARMONICS CAUSED BY NON-LINEAR LOAD AND RESONANCE CAUSED BY POWER FACTOR CORRECTION CAPACITOR NOR FAEZAH BINTI ADAN A thesis submitted in fulfillment of the requirement for the award of the Degree of Master of Electrical Engineering Faculty of Electrical and Electronic Engineering Universiti Tun Hussein Onn Malaysia JANUARY 2016

DESIGN A FILTER FOR HARMONICS CAUSED BY NON …eprints.uthm.edu.my/8812/1/NOR_FAEZAH_BINTI_ADAN.pdf · resonance and overall harmonics in the PS through simulation using PSCAD software

Embed Size (px)

Citation preview

Page 1: DESIGN A FILTER FOR HARMONICS CAUSED BY NON …eprints.uthm.edu.my/8812/1/NOR_FAEZAH_BINTI_ADAN.pdf · resonance and overall harmonics in the PS through simulation using PSCAD software

i

DESIGN A FILTER FOR HARMONICS CAUSED BY NON-LINEAR LOAD AND

RESONANCE CAUSED BY POWER FACTOR CORRECTION CAPACITOR

NOR FAEZAH BINTI ADAN

A thesis submitted in

fulfillment of the requirement for the award of the

Degree of Master of Electrical Engineering

Faculty of Electrical and Electronic Engineering

Universiti Tun Hussein Onn Malaysia

JANUARY 2016

Page 2: DESIGN A FILTER FOR HARMONICS CAUSED BY NON …eprints.uthm.edu.my/8812/1/NOR_FAEZAH_BINTI_ADAN.pdf · resonance and overall harmonics in the PS through simulation using PSCAD software

ii

I hereby declare that the work in this thesis is my own except for quotations and

summaries which have been duly acknowledged.

Student : __________________________________________________

NOR FAEZAH BINTI ADAN

Date : __________________________________________________

Supervisor : __________________________________________________

DR. DUR MUHAMMAD SOOMRO

Page 3: DESIGN A FILTER FOR HARMONICS CAUSED BY NON …eprints.uthm.edu.my/8812/1/NOR_FAEZAH_BINTI_ADAN.pdf · resonance and overall harmonics in the PS through simulation using PSCAD software

iii

For my beloved mother and father

Page 4: DESIGN A FILTER FOR HARMONICS CAUSED BY NON …eprints.uthm.edu.my/8812/1/NOR_FAEZAH_BINTI_ADAN.pdf · resonance and overall harmonics in the PS through simulation using PSCAD software

iv

ACKNOWLEDGEMENT

Alhamdulillah, praise be upon Him whom has given me a good health, body and mind to

complete this Projek Sarjana. I would like to express my sincere gratitude to

Dr. Dur Muhammad Soomro, my supervisor for the support and guidance given throughout the

duration of this project.

The co-operation given by the Faculty of Electrical and Electronic Engineering, UTHM

is also highly appreciated. Appreciation also goes to everyone involved directly or indirectly

towards the compilation of this thesis. Last but not least, thank you to all my friends and family

for the generous moral support given throughout completing this task.

Page 5: DESIGN A FILTER FOR HARMONICS CAUSED BY NON …eprints.uthm.edu.my/8812/1/NOR_FAEZAH_BINTI_ADAN.pdf · resonance and overall harmonics in the PS through simulation using PSCAD software

v

ABSTRACT

The traditional approach to power factor correction (PFC) in industrial applications

involves installation of power factor correction capacitor banks (PFCC). However, with the

expanding use of non-linear equipment such as adjustable speed drives (ASDs), power

converters etc., power factor (PF) improvement has become difficult due to the presence of

harmonics generated by the non-linear equipment. The resulting capacitive impedance of

the PFCC may form a resonant circuit with the source inductive reactance at a certain

frequency, which is likely to coincide with one of the harmonic frequency of the load. This

condition will trigger large oscillatory currents and voltages that may stress the insulation

and cause subsequent damage to the PFCC and equipment connected to the power system

(PS). Besides that, high PF cannot be achieved due to power distortion. These have imposed

the need for an approach to PFC by addressing the harmonics problem. This project

analyzes both passive filter and shunt active power filter (SAPF) techniques to mitigate

resonance and overall harmonics in the PS through simulation using PSCAD software. A

test case is presented to demonstrate the applicability of the proposed techniques for

harmonics reduction and PFC at the same time. The implementation of SAPF together with

passive filter have resulted in significant improvement on both total harmonic distortion for

voltage (THDV) and total demand distortion for current (TDDI) with maximum values of

only 2.93% and 9.84% respectively which are within the IEEE 519-2014 standard limits.

In terms of PF improvement, the combined filters have excellently achieved the desired PF,

0.95 for firing angle, α values up to 40o.

Page 6: DESIGN A FILTER FOR HARMONICS CAUSED BY NON …eprints.uthm.edu.my/8812/1/NOR_FAEZAH_BINTI_ADAN.pdf · resonance and overall harmonics in the PS through simulation using PSCAD software

vi

ABSTRAK

Bank kapasitor seringkali digunakan di industri untuk menambahbaik faktor kuasa. Namun,

dengan peningkatan penggunaan alatan-alatan tidak linear seperti pemacu kelajuan boleh laras

(ASDs), penukar kuasa dan sebagainya, penambahbaikan faktor kuasa menjadi lebih sukar. Ini

adalah kerana kehadiran harmonik yang dihasilkan oleh alatan-alatan tidak linear tersebut.

Bank kapasitor menghasilkan galangan kapasitif yang mungkin akan bertembung dengan

galangan induktif punca kuasa pada salah satu frekuensi harmonik yang dihasilkan oleh beban

lantas menyebabkan terjadinya resonan. Keadaan ini akan menyebabkan terhasilnya ayunan

besar arus and voltan yang akan menyebabkan kerosakan kepada penebat seterusnya bank

kapasitor dan alatan-alatan lain yang terdapat di dalam sistem kuasa. Selain itu, herotan kuasa

menyebabkan faktor kuasa yang tinggi tidak dapat dicapai. Oleh kerana itu, satu langkah perlu

diambil untuk penambahbaikan faktor kuasa dengan cara mengurangkan harmonik. Projek ini

telah menganalisis teknik passive filter dan shunt active power filter (SAPF) dalam

mengurangkan masalah resonan dan keseluruhan harmonik melalui simulasi menggunakan

perisian PSCAD. Satu kes ujian telah dibentangkan untuk menunjukkan kesesuaian teknik

yang telah dicadangkan dalam mengurangkan harmonik dan pada masa yang sama

meningkatkan faktor kuasa. Hasil implementasi SAPF dan passive filter telah menunjukkan

penambahbaikan yang tinggi terhadap jumlah keseluruhan herotan harmonik bagi voltan

(THDV) dan arus (TDDI), kepada hanya 2.93% dan 9.84% nilai maksimum yakni di bawah

paras yang ditetapkan oleh standard IEEE 519-2014. Dari segi penambahbaikan faktor

kuasa, gabungan kedua-duanya telah berjaya mencapai faktor kuasa sasaran iaitu 0.95

untuk firing angle, α dari 0o-40o.

Page 7: DESIGN A FILTER FOR HARMONICS CAUSED BY NON …eprints.uthm.edu.my/8812/1/NOR_FAEZAH_BINTI_ADAN.pdf · resonance and overall harmonics in the PS through simulation using PSCAD software

vii

CONTENTS

TITLE i

DECLARATION ii

DEDICATION iii

ACKNOWLEDGEMENT iv

ABSTRACT v

CONTENTS vii

LIST OF FIGURES ix

LIST OF TABLES xii

LIST OF ABBREVIATIONS xiii

CHAPTER 1 INTRODUCTION 1

1.1 Background of study 1

1.2 Problem statement 2

1.3 Objectives of study 3

1.4 Scopes of study 3

1.5 Thesis outline 4

CHAPTER 2 LITERATURE REVIEW 5

2.1 Introduction 5

2.2 Related works 5

2.2.1 Test model 6

2.2.2 Passive filters 7

2.2.3 Active power filters 9

2.2.4 Hybrid active power filters 11

2.2.5 Phase shifting method 13

Page 8: DESIGN A FILTER FOR HARMONICS CAUSED BY NON …eprints.uthm.edu.my/8812/1/NOR_FAEZAH_BINTI_ADAN.pdf · resonance and overall harmonics in the PS through simulation using PSCAD software

viii

2.3 PF correction (PFC) 14

2.4 IEEE Standard for Harmonic Control 15

CHAPTER 3 METHODOLOGY 17

3.1 Introduction 17

3.2 Circuit topology 17

3.3 Design circuit elements 18

3.3.1 Distribution system 18

3.3.2 PFCC 20

3.3.3 Passive filter 20

3.3.4 SAPF 21

3.4 Control techniques 22

3.4.1 Calculation of reference compensations

currents 22

3.4.1.1 P-Q theory 22

3.4.1.2 High pass filter 26

3.4.2 SAPF firing pulses generation 26

CHAPTER 4 RESULTS AND DISCUSSION 30

4.1 Introduction 30

4.2 Distribution system without PFCC 30

4.3 Distribution system with PFCC 33

4.3.1 Calculated PFCC 33

4.3.2 Effects of PFCC on distribution system 34

4.3.2.1 Reference distribution system 34

4.3.2.2 Main distribution system 35

4.4 Power filter implementation 37

4.4.1 Passive filter 37

4.4.2 Passive filter + SAPF 41

CHAPTER 5 CONCLUSION 44

REFERENCES 46

Page 9: DESIGN A FILTER FOR HARMONICS CAUSED BY NON …eprints.uthm.edu.my/8812/1/NOR_FAEZAH_BINTI_ADAN.pdf · resonance and overall harmonics in the PS through simulation using PSCAD software

ix

LIST OF FIGURES

2.1(a)(b) STPF, DTPF - Shunt passive filters 7

2.2 5th, 7th, 11th and 13th order STF in plastic plant

distribution system

8

2.3 Single phase shunt active filter configuration 9

2.4 Block diagram of SAPF controller using p-q

theory

10

2.5(a)(b) STHF, DTHF in 3-phase distribution system 11

2.6 Hybrid filter system set-up 12

2.7 Phase shifting approach for VSDs PFC and

harmonics mitigation

13

2.8 Relationship between S, P and Q 14

2.9 Addition of capacitors to correct PF 14

3.1 Passive filter and SAPF topology 18

3.2 Distribution system 19

3.3 Calculation of current reference based on p-q

theory

22

3.4 PSCAD models for Clarke transformation 23

3.4(a) Vα calculation 23

3.4(b) Vβ calculation 23

3.4(c) Iα calculation 23

3.4(d) Iβ calculation 23

3.5

PSCAD models for p-q instantaneous power

components calculation and HPF to obtain px

and qx

24

3.5(a) p calculation 24

Page 10: DESIGN A FILTER FOR HARMONICS CAUSED BY NON …eprints.uthm.edu.my/8812/1/NOR_FAEZAH_BINTI_ADAN.pdf · resonance and overall harmonics in the PS through simulation using PSCAD software

x

3.5(b) q calculation 24

3.6 PSCAD models for compensation current

calculation in α-β coordinates

24

3.6(a) Icα calculation 24

3.6(b) Icβ calculation 24

3.7 PSCAD models for compensation current

calculation in a-b-c coordinates

25

3.7(a) Ica calculation 25

3.7(b) Icb calculation 25

3.7(c) Icc calculation 25

3.8 HPF configuration 26

3.9 Filter current 27

3.10 Measuring the difference between actual filter

currents and reference currents

27

3.11 Generation of SAPF switches firing pulses 28

3.11(a) Reference signals 28

3.11(b) Interpolated firing pulses block 28

3.12 Reference signals fed to interpolated firing

pulses block

28

3.13 Actual firing pulses generated 29

3.13(a) S1 and S4 switches 29

3.13(b) S3 and S6 switches 29

3.13(c) S5 and S2 switches 29

4.1 Reference system, supply with Rs = 0.002Ω,

Ls = 0

31

4.2 Main system, supply with Rs = 0.002Ω,

Ls = 0.5mH

31

4.3

4.3(a)

4.3(b)

Lower fundamental current at supply at α = 60o

No PFCC

40 kVAR PFCC

35

35

35

4.4

4.4(a)

4.4(b)

Resonance occurrence at 5th harmonic at α = 60o

30 kVAR PFCC

40 kVAR PFCC

36

36

36

4.5

4.5(a)

Load fundamental current

30 kVAR PFCC

37

37

Page 11: DESIGN A FILTER FOR HARMONICS CAUSED BY NON …eprints.uthm.edu.my/8812/1/NOR_FAEZAH_BINTI_ADAN.pdf · resonance and overall harmonics in the PS through simulation using PSCAD software

xi

4.5(b) 40 kVAR PFCC 37

4.6 Passive filter implementation 37

4.7 Passive filter performance at Q = 15 38

4.8 Passive filter, Q=15 - voltage and current

waveforms at α = 60o

39

4.9 Passive filter performance at Q = 20 39

4.10 Passive filter, Q=20 - voltage and current

waveforms at α = 60o

40

4.11 Passive filter performance at Q = 30 40

4.12 Passive filter, Q=30 - voltage and current

waveforms at α = 60o

41

4.13 Passive filter and SAPF implementation 41

4.14 Current and voltage waveforms after filters

implementation at α = 60o

42

4.14(a) Supply current against load current 42

4.14(b) PCC voltage against supply voltage 42

4.15 SAPF compensated current at α = 60o 43

Page 12: DESIGN A FILTER FOR HARMONICS CAUSED BY NON …eprints.uthm.edu.my/8812/1/NOR_FAEZAH_BINTI_ADAN.pdf · resonance and overall harmonics in the PS through simulation using PSCAD software

xii

LIST OF TABLES

1.1 PF surcharge rate for users at 132kV and below 2

2.1 Voltage distortion limit 15

2.2 Current distortion limits for system rated 120 V

through 69 kV

16

2.3 Current distortion limits for system rated above

69 kV through 161 kV

16

2.4 Current distortion limits for system rated above

161 kV

16

4.1 Simulated results without PFCC 32

4.2 Voltage and current harmonics distribution on

main system

33

4.3 Reference system - Calculated PFCC 34

4.4 Main system - Calculated PFCC 34

4.5 Reference system with PFCC 35

4.6 Main system with PFCC 36

4.7 RLC values for passive filter 38

4.8 Passive filter and SAPF implementation 43

Page 13: DESIGN A FILTER FOR HARMONICS CAUSED BY NON …eprints.uthm.edu.my/8812/1/NOR_FAEZAH_BINTI_ADAN.pdf · resonance and overall harmonics in the PS through simulation using PSCAD software

xiii

LIST OF ABBREVIATIONS

ωn Harmonic frequency

AC Alternating current

ASDs Adjustable speed drives

C Capacitor

CCA Conventional control algorithm

DC Direct current

DF Distortion factor

DPF Displacement power factor

DTHF Double tuned hybrid active power filter

DTPF Double tuned passive filter

FFT Fast Fourier transform

fo Fundamental frequency

fr Resonance frequency

HAPF Hybrid active power filter

HPF High pass filter

HVAC Heating, ventilating and air conditioning

L Inductor

P Active power

PC Personal computer

PCA Proposed control algorithm

PCC Point of common coupling

PE Power electronics

PF Power factor

PFC Power factor correction

PFCC Power factor correction capacitor

Page 14: DESIGN A FILTER FOR HARMONICS CAUSED BY NON …eprints.uthm.edu.my/8812/1/NOR_FAEZAH_BINTI_ADAN.pdf · resonance and overall harmonics in the PS through simulation using PSCAD software

xiv

PLL Phase locked loop

PQ Power quality

PS Power system

Q Reactive power

R Resistor

ROF Reactance one-port filter

S Apparent power

SAPF Shunt active power filter

SCC Sinusoidal current control

SeAPF Series active power filter

SMPS Switched-mode power supplies

SPWM Sinusoidal pulse width modulation

STHF Single tuned hybrid active power filter

STPF Single tuned passive filter

TDD Total demand distortion

TDDI Total harmonic distortion for current

THD Total harmonic distortion

THDV Total harmonic distortion for voltage

TNB Tenaga Nasional Berhad

UPS Uninterruptible power supply

VSC Voltage source converter

VSDs Variable speed drives

Page 15: DESIGN A FILTER FOR HARMONICS CAUSED BY NON …eprints.uthm.edu.my/8812/1/NOR_FAEZAH_BINTI_ADAN.pdf · resonance and overall harmonics in the PS through simulation using PSCAD software

CHAPTER 1

INTRODUCTION

1.1 Background of study

In the past, harmonics represented less of a problem due to the conservative design of power

equipment. When electronic power converters first became commonplace in the late 1970s,

many utility engineers became quite concerned about the ability of power system (PS) to

accommodate the harmonic distortion as the harmonics problems defy many of the

conventional rules of PS design and operation that consider only the fundamental frequency

[1]. Results of their concern have sparked the research that has eventually led to much of

the knowledge about all aspects of power quality (PQ).

Harmonics in PS is defined as a sinusoidal component of a periodic wave or

quantity having a frequency that is an integral multiple of the fundamental frequency.

Malaysia uses a 50 Hz fundamental frequency, thus a 3rd harmonic frequency will be 3

times 50 Hz, or 150 Hz. Likewise, a 5th harmonic frequency is 250 Hz and so on. The odd

integer harmonics frequencies (3rd, 5th, 7th and so on) are the most predominant [2-4]. The

waveform of electric power at generation stage is purely sinusoidal and free from any

distortion but this situation is hardly achievable at consumer’s end that has a lot of non-

linear equipment in operation.

Non-linear equipment like power electronics (PE) devices are the most significant

cause of harmonics and inter-harmonics. They generate harmonic frequencies by drawing

non-linear current waveforms. Rectifiers, adjustable speed drives (ASDs), soft starters,

Page 16: DESIGN A FILTER FOR HARMONICS CAUSED BY NON …eprints.uthm.edu.my/8812/1/NOR_FAEZAH_BINTI_ADAN.pdf · resonance and overall harmonics in the PS through simulation using PSCAD software

2

electronic ballast for discharge lamps, switched-mode power supplies (SMPS), and heating,

ventilating, and air conditioning (HVAC) system using ASDs among the list of common

PE devices used which generate harmonics. Meanwhile, inter-harmonics are produced by

static frequency converters, cyclo-converters, induction motors & arcing devices. The

effects of harmonics on a PS include equipment premature failure and degradation, low

power factor (PF) [5], nuisance trips, resonance etc. Equipment affected by harmonics

includes transformers, motors, cables, interrupters, and power factor correction capacitors

(PFCC).

Large industrial equipment like transformers, induction motors, generators etc. are

among the equipment that may contribute to lower PF. Ideally, users would want to ensure

their PS to maintain a unity PF but it is not easily achievable especially for larger

commercial buildings or plants that have different sizes and types of loads. Lower PF

causes higher apparent power required by the equipment to achieve the same amount of

output. Thus, overloading the component. The continuous additional work if not mitigated

will shortens the life of the equipment. In worse cases, equipment may work excessively

beyond rated parameters and thus lead to total failure. In Malaysia, penalties will be charged

on users that fail to meet the PF requirement set by the Tenaga Nasional Berhad (TNB).

Table 1.1 shows the surcharge imposed on users with electricity supply below 132kV.

Table 1.1: PF surcharge rate for users at 132kV and below

PF requirement Surcharge rate

For every 0.01 less than 0.85 1.5 % of current bill

For every 0.01 less than 0.75 3 % of current bill

1.2 Problem statement

PFCC is commonly used in the industry to improve PF of the PS due to its lower cost.

However, when harmonics are present, the resulting reactive impedance of the PFCC may

form a resonant circuit with the source or system inductive reactance at a certain frequency,

which is likely to coincide with one of the harmonic frequency of the load. This condition

will trigger large oscillatory currents and voltages that may stress the insulation and cause

subsequent damage to the capacitor banks and equipment connected to the PS [6]. In order

Page 17: DESIGN A FILTER FOR HARMONICS CAUSED BY NON …eprints.uthm.edu.my/8812/1/NOR_FAEZAH_BINTI_ADAN.pdf · resonance and overall harmonics in the PS through simulation using PSCAD software

3

to solve this issue and optimize the operating cost, a practical approach must be

implemented to reduce the problem to an acceptable level. In this case, harmonics filters

such as passive, active or hybrid can be applied at the point of common coupling (PCC) to

absorb the large oscillatory currents caused by resonance and reduces the overall current

and voltage harmonics.

From literature review, there are fewer references that are focused on mitigating

resonance effect caused by PFCC on the PS with harmonics presence. Therefore, this

project has been undertaken to study the harmonic amplification problem caused by PFCC

and the overall effects of harmonics on PF. The result of the study is used to develop the

necessary passive filter to reduce or eliminate resonance and also used to design an active

filter to reduce the other harmonic components in order to improve the PF.

1.3 Objectives of study

1) To simulate the effects of PF correction (PFC) on PS frequency.

2) To design passive and active power filter separately to mitigate harmonics and

resonance problem caused by PFCC.

1.4 Scopes of study

1) Simulation models are developed using PSCAD software.

2) The test case [7] consists of a bridge rectifier and an RL load.

3) Single tuned passive filter is designed to address the resonance problem.

4) Shunt active power filter (SAPF) is designed to address the other harmonic components.

5) P-Q theory is implemented to calculate the compensation reference current for the

SAPF.

Page 18: DESIGN A FILTER FOR HARMONICS CAUSED BY NON …eprints.uthm.edu.my/8812/1/NOR_FAEZAH_BINTI_ADAN.pdf · resonance and overall harmonics in the PS through simulation using PSCAD software

4

1.5 Thesis outline

After the introduction section, the outline of the thesis is organized as follows;

Chapter 2 presents reviews of past researches on harmonic analysis of domestic and

industrial non-linear PS, application of harmonic filters to improve PF, mitigate harmonics

and harmonics resonance caused by non-linear loads and PFCC followed by a brief

introduction to PFC theory. The literature review is concluded with details of harmonic

limits outlined by IEEE 519-2014 standard.

Chapter 3 describes modeling of a 3 phase distribution system with non-linear load

and PFCC, passive filter and SAPF using PSCAD software. This chapter also includes

mathematical equations of PFCC and passive filter.

Chapter 4 discusses voltage and current harmonics caused by the non-linear load on

the distribution system with and without PFCC implementation. The results of the

implemented passive filter and SAPF are also presented.

In Chapter 5, the conclusions of the thesis are given and the future work studies are

proposed.

Finally all references used in this thesis study are presented.

Page 19: DESIGN A FILTER FOR HARMONICS CAUSED BY NON …eprints.uthm.edu.my/8812/1/NOR_FAEZAH_BINTI_ADAN.pdf · resonance and overall harmonics in the PS through simulation using PSCAD software

5

CHAPTER 2

LITERATURE REVIEW

2.1 Introduction

This chapter presents reviews of past researches on harmonic analysis of domestic and

industrial non-linear PS, application of harmonic filters to improve PF, mitigate harmonics

and harmonics resonance caused by non-linear loads and PFCC followed by a brief

introduction to PFC theory. The literature review is concluded with details of harmonic

limits outlined by IEEE 519-2014 standard.

2.2 Related works

The traditional approach to PFC in industrial applications involves installation of PFCC.

But with the widespread use of non-linear loads, PF improvement has becoming more

difficult. It is known that a circuit consisting both capacitors (C) and inductors (L) will

generate resonance at a certain frequency [6]. For a purely sinusoidal PS, resonance may

not even happen, but not in the case where the PS contains harmonics profile whereby the

integral multiple of the fundamental frequency (fo) have a high probability to coincide with

the resonance frequency (fr).

Page 20: DESIGN A FILTER FOR HARMONICS CAUSED BY NON …eprints.uthm.edu.my/8812/1/NOR_FAEZAH_BINTI_ADAN.pdf · resonance and overall harmonics in the PS through simulation using PSCAD software

6

Harmonics filter is essential in PS that contains harmonics profile drawn by the non-

linear loads. They are designed to provide a bypass for the harmonic currents, to block them

from entering the PS or to compensate them by locally supplying harmonic currents and/or

harmonic voltages. Different methods have been proposed to overcome harmonics and

harmonics resonance such as by using passive filter, active power filters, hybrid active

power filters (HAPF) and other method like phase shifting approach.

2.2.1 Test model

Prior to developing a solution to eliminate the harmonics and its adjacent effects, it is

critical to identify the harmonics profile produced by each of the non-linear loads and also

the overall harmonics profile at PCC. Studies conducted by [7-8] have developed several

simulation models of typical domestic and industrial non-linear loads. It is more convenient

to perform harmonics analysis using computer simulation given the system components are

modeled accurately. Models developed in [7] include television, refrigerator, washing

machine, battery charger, lamps, fans, air-conditioner, antenna using servomotors, air

heating unit, adjustable speed drive (ASD) and uninterruptable power supply (UPS) which

were implemented to estimate the harmonics characteristics of a distribution system of

CARTOSAT-2A satellite launching station at ISRO, Bangalore, India.

On the other hand, research conducted in [8] performed harmonic analysis on a

residential house, small residential area and a small-scale industrial supply system. The

study concluded that, a residential house having all types of electronics and electrical home

appliances performed within the total harmonic distortion for voltage (THDV), and total

demand distortion for current (TDDI) limits respectively. Analysis performed on a small

residential area consisting three villages have shown that Village 2 and 3 with lower income

residents, did not contribute to high harmonics compared to Village 1 as they can’t afford

expensive equipment like air-conditioners, water heaters, dryer etc. Village 1 produces

acceptable TDDI but high THDV (9.4%) thus requires harmonics filter to reduce the voltage

harmonics. Meanwhile, harmonics analysis performed on the small-scale industrial supply

system, which comprises of ASDs, DC motors, arc welders, cyclo-converter, personal

computer (PC), air conditioners, fans and lamps resulted in both THDV and TDDI

exceeding the limits at 6.1% and 61.6% respectively.

Page 21: DESIGN A FILTER FOR HARMONICS CAUSED BY NON …eprints.uthm.edu.my/8812/1/NOR_FAEZAH_BINTI_ADAN.pdf · resonance and overall harmonics in the PS through simulation using PSCAD software

7

Based on [8], it is profound to assume that an office building may also produce high

THDV as the equipment used is similar to residential houses while mechanical and electrical

laboratories in the university which has a close resemblance to the small scale industrial

system may also exceed both its TDDI and THDV limits. Therefore, harmonics filters are

definitely required to reduce the total harmonic distortion (THD) to an acceptable level.

2.2.2 Passive filters

Passive filters can be broadly classified into two types, series and shunt filter. Series filters

with high series impedance are used to block the relevant harmonic currents. Therefore

they must carry the full load current and be insulated for full line voltage. On the other

hand, shunt filters are used to divert the relevant harmonic currents to the ground by

providing a low impedance bypass path. The latter carry only a fraction of the current that

a series filter must carry, making the cost cheaper, thus more attractive to users [9-10].

Figure 2.1 illustrates the configuration of single tuned passive filter (STPF) and double

tuned passive filter (DTPF). STPF is specifically designed to eliminate distortion of one

harmonic order only while DTPF as the name imply, eliminates two harmonics components

simultaneously.

(a) STPF (b) DTPF

Figure 2.1: Shunt passive filters

The research in [11] focused on designing passive filters to mitigate harmonics

problem on a small-scale industrial loads i.e. 13-bus medium voltage industrial distribution

system. Similar non-linear models in [7-8] were adopted. Two types of passive filters were

designed and discussed in this paper, single/double tuned passive filter (STPF / DTPF) and

reactance one-port (ROF) arrangement. ASDs loads were connected to bus 7 and 10, PFCC

connected to bus 3 and active filter connected at PCC. Initial simulation with the PFCC

offline and no filters application has shown that both the ASD load buses exceeded the 5%

Page 22: DESIGN A FILTER FOR HARMONICS CAUSED BY NON …eprints.uthm.edu.my/8812/1/NOR_FAEZAH_BINTI_ADAN.pdf · resonance and overall harmonics in the PS through simulation using PSCAD software

8

and 20% THDV and TDDI limits with 6.1% and 7.3% THDV and 24.9% and 26.2% TDDI

respectively. The other buses monitored include bus 3 and 9 with bus 3 readings well below

the limits and bus 9 exceeds TDDI limits at 25.6%. It was found that DTPF reduces THD

better than STPF. The researcher has also simulated the effect of PFCC to the distribution

system. As expected, the THD level is higher when PFCC is energized.

The simplicity and cost-effective of STPF are the main reasons why they are often

installed to mitigate harmonic problem. However, they are not always the most practical

solution. A study conducted by [12] have identified that STPF can be a culprit to harmonic

amplification. The problem started when four STPFs of 5th, 7th, 11th and 13th were

commissioned as shown in Figure 2.2, many cases of STPF capacitor failures were

reported. Through computer simulation, it was found that there was a parallel resonance

between the LC filters and the PS. Simulation on different filter structures have also shown

that the resonant frequency varied accordingly i.e. 4th order harmonic were amplified when

the 13th order filter was disconnected and both 4th and 8th order harmonic decreases

reasonably when the 11th and 13th order STPFs were offline. It was concluded that the filter

set-up were not suitable for a PS experiencing very infrequent unequal loading condition

and thus proposed a more practical solution, a 17th and 35th order high pass damped filters

as replacement to the original set-up.

Figure 2.2: 5th, 7th, 11th and 13th order STPF in plastic plant distribution system

The system parameters are dynamically changed according to the power system

configurations and loads. Therefore, even with passive filters implemented other harmonics

problems can still appear which means for a wider range of harmonic frequencies, an STPF

or DTPF alone is not sufficient to reduce the THD.

Page 23: DESIGN A FILTER FOR HARMONICS CAUSED BY NON …eprints.uthm.edu.my/8812/1/NOR_FAEZAH_BINTI_ADAN.pdf · resonance and overall harmonics in the PS through simulation using PSCAD software

9

2.2.3 Active power filters

Active filters are the new trend in harmonic filtering technology. They make use of power

electronic switches and advanced control techniques. Hence, their responses are much

quicker than passive filters. The basic principle of operation of an active filter is to inject a

suitable non-sinusoidal voltage and current into the system in order to compensate the

harmonic contents. Active filters are still characterized by their relatively high cost

compared to the cost of passive filters [13]. According to their connection to the network,

active filters can be a series type (SeAPF), which prevents the transfer of harmonic current

or the shunt type (SAPF), which reduces harmonic content in the network.

The function of passive series filter and SeAPF is identical and thus faced the same

issues related to higher implementation cost especially for application in severe harmonics

conditions. Mainly because they must be designed to withstand the full load current and

full line voltage. In order to make it more practical, it has to be combined with some type

of passive filtering. The passive filter is there to absorb the harmonic currents while the

active filter blocks the transfer of harmonics to the rest of the PS. Details of this

combination will be covered in hybrid filter. Meanwhile the SAPF’s main function is to

reduce or cancel the harmonic currents produced by the non-linear load by injecting a

compensating current into the utility system. Figure 2.3 showed the configuration of a shunt

active filter where it is connected in parallel to the non-linear loads.

Figure 2.3: Single phase shunt active filter configuration

The filter above consists of four power electronic switches which produce an output

current that will be injected to the PS for harmonic compensation. The switches are

controlled by an integrated circuit. A lot of control methods have been studied by past

Page 24: DESIGN A FILTER FOR HARMONICS CAUSED BY NON …eprints.uthm.edu.my/8812/1/NOR_FAEZAH_BINTI_ADAN.pdf · resonance and overall harmonics in the PS through simulation using PSCAD software

10

researchers, which includes neural network, instantaneous p-q theory (instantaneous

reactive power theory), synchronous d-q reference frame theory, fast Fourier transform

technique (FFT) etc. Among all, the most commonly used due to their accuracy, robustness

and simple calculation are the p-q and d-q theory [14].

The p-q theory is implemented to control a single phase SAPF in [15]. The block

diagram of the implemented SAPF controller using p-q theory is shown in Figure 2.4. The

designed control system is then implemented on the ATMEL NGW100 development board

to ensure simultaneous real-time acquisition of voltage and current data.

Figure 2.4: Block diagram of SAPF controller using p-q theory

Similar approach using p-q theory to control an SAPF has also been conducted on

[16]. The proposed filter is designed to improve PF and generate harmonics current

compensation. The SAPF controller which is based on p-q theory has been proven to be a

powerful tool through experimental results. The set-up is also simple enough to allow

digital implementation using a standard and inexpensive 16-bits microcontroller

(Intel 80296SA) with minimum additional hardware.

In [17], a d-q theory is used instead to control the 3 phase voltage source converter

(VSC) based SAPF. This method was chosen because it has greater and better performance

when the supply voltage is distorted. The main difference of this method from p-q theory

is that the d-q method requires the determination of the angular position of the synchronous

reference of the source voltages. Phase locked loop (PLL) algorithm is used in this research

to determine the angular position and a decoupled controller is used to generate the required

firing pulses to the SAPF. The d-q based SAPF simulated in MATLAB/Simulink was

capable in compensating the reactive power and thus mitigate harmonics.

The d-q theory has also been implemented on a VSC based SAPF in [18]. The only

difference with [17] was that, the filter designed used sinusoidal pulse width modulation

Page 25: DESIGN A FILTER FOR HARMONICS CAUSED BY NON …eprints.uthm.edu.my/8812/1/NOR_FAEZAH_BINTI_ADAN.pdf · resonance and overall harmonics in the PS through simulation using PSCAD software

11

(SPWM) to generate the required firing pulses to the SAPF switches. This research has also

proven the capability of d-q based SAPF in mitigating harmonics.

It is critical to decide the most suitable control method to mitigate harmonics on a

PS. A study conducted on [19] evaluates the performance of a 3 phase 3 wire SAPF using

both p-q theory and d-q theory under distorted supply and non-linear load conditions. The

SAPF performance under both control methods were validated using MATLAB/Simulink.

Based on the simulation result, p-q theory gives a better approach than d-q theory for

compensation of harmonic currents and thus improving THD.

Other than the common control method, a novel control method introduced in [20]

have successfully employed SAPF to mitigate harmonics distortion while also improving

the PF. The methods, namely proposed control algorithm (PCA) and conventional control

algorithm (CCA) were carried out and the result have shown that both control methods

improved the PF up to 0.982 while keeping the total demand distortion (TDD) within an

acceptable level. Another novel control method called sinusoidal current control strategy

(SCC) was developed in [21]. This control method was modified from the p-q theory. The

main advantage of this new method is that it can also be applied to unbalanced supply

condition.

2.2.4 Hybrid active power filters (HAPF)

This filter combines both active and passive shunt filters. There are many possible

combinations in hybrid filter design like the single tuned hybrid active power filter (STHF)

and double tuned hybrid active power filter (DTHF) as shown in Figure 2.5. Hybrid filters

provide a viable alternative to the use of active filters only, since the unit may be sized to

only a fraction of the total compensating power [22], thus limiting the overall cost.

(a) (b)

Figure 2.5: (a) STHF, (b) DTHF in 3-phase distribution system [23]

Page 26: DESIGN A FILTER FOR HARMONICS CAUSED BY NON …eprints.uthm.edu.my/8812/1/NOR_FAEZAH_BINTI_ADAN.pdf · resonance and overall harmonics in the PS through simulation using PSCAD software

12

The effectiveness of a HAPF has been studied in [22] to dampen harmonic

resonance caused by PFCC as well as to mitigate harmonics voltages and currents in

industrial PS. It is a combination of a small rated active filter and a 5th tuned passive filter,

which are connected in series. The hybrid filter was developed with the assumption that

only the 5th harmonics voltage exists at PCC. Figure 2.6 shows the system configuration.

Figure 2.6: Hybrid filter system set-up

When harmonics resonance occurs, a substantial 5th harmonic current (IF5) will flow

into the passive filter. To avoid the passive filter from absorbing the excessive current, the

active filter which has also detected the overcurrent across the passive filter will adjusts its

gain K to be greater than zero. Among the three different harmonic detection methods

employed by the active filter, the harmonic current through the passive filter (IFh) detecting

method is substantially stable and accurate compared to the other two mainly because the

ratio of the extracted harmonic component is the highest. IFh detecting method is applied on

the PS to further study the impact of an active filter in dampening harmonics resonance in

a hybrid filter operation. The PS was set with an initial 2.3% 5th harmonic voltage at VBUS.

When both filters were disconnected, the 5th harmonic voltage appearing on the VBUS was

magnified by 6.3 due to harmonic resonance versus 2.7 magnification factor when only the

passive filter was installed. Next, the hybrid filter was installed and the result have shown

that the filter was able to reduce the 5th harmonic voltage appearing at VBUS to one-sixth of

the voltage produced when only the passive filter is used. The above result was achieved

with the active filter designed at a required rating of less than 1% of the rated load.

A broader performance criterion of hybrid filters was studied in [23] whereby it

focuses on comparing the performance of STHF against DTHF. The filters were tested

under the same loading conditions and control method in order to compare its performance

Page 27: DESIGN A FILTER FOR HARMONICS CAUSED BY NON …eprints.uthm.edu.my/8812/1/NOR_FAEZAH_BINTI_ADAN.pdf · resonance and overall harmonics in the PS through simulation using PSCAD software

13

in terms of THD, PFC and the power processed by the converter. The end result have shown

that both performed well in mitigating THD and PFC. However, in terms of active power

processed, 3rd harmonic mitigation and neutral current reduction, DTHF managed to

outperform STHF.

2.2.5 Phase shifting method

Apart from the methods mentioned earlier, PFC and harmonics mitigation can also be done

using phase shifting approach [5]. The research is focused on solving power harmonics

problem related to 3 phase diode-bridge rectifiers commonly used as input stage in low

voltage VSDs. The method proposed involves capturing harmonics generated from

separate sources, shifting one source of harmonics 180o with respect to the other source and

then adding them together. Equal harmonic amplitudes will result in harmonics

cancellation. The experimental set-up consists of 2 identical VSDs, which were fed by

separate power transformers with phase shifted output voltages as shown in Figure 2.7.

This technique under certain conditions eliminates dominant 5th and 7th current harmonics,

achieved THD below IEEE 519 limits and thus leading to an improvement of the PS PF i.e.

PF close to unity achieved at PCC2.

Figure 2.7: Phase shifting approach for VSDs PFC and harmonics mitigation

Page 28: DESIGN A FILTER FOR HARMONICS CAUSED BY NON …eprints.uthm.edu.my/8812/1/NOR_FAEZAH_BINTI_ADAN.pdf · resonance and overall harmonics in the PS through simulation using PSCAD software

14

2.3 PF Correction (PFC)

PF is the ratio of the active power (working power, P) to the apparent power (total power

delivered by the utility or consumed by the load, S). A low PF means that only a fraction

of the total power delivered or consumed is used to do the actual work while the rest is

consumed by the reactive components of the load. The relationship between apparent power

(S), active power (P) and reactive power (Q) is shown in Figure 2.8 where φ is the phase

difference between supply voltage and current.

Figure 2.8: Relationship between S, P and Q

The most common way to correct PF is by adding shunt capacitors in parallel with

the loads. Usually they are placed at the PCC. The best way to visualize how capacitors

correct PF is by using the power triangle shown in Figure 2.9.

Figure 2.9: Addition of capacitors to correct PF

Page 29: DESIGN A FILTER FOR HARMONICS CAUSED BY NON …eprints.uthm.edu.my/8812/1/NOR_FAEZAH_BINTI_ADAN.pdf · resonance and overall harmonics in the PS through simulation using PSCAD software

15

2.4 IEEE Standard for Harmonic Control

IEEE Standard 519-2014 [24] specifies the recommended line-to-neutral harmonic voltage

limits as shown in Table 2.1. All values should be in percent of the rated frequency voltage

at PCC.

Table 2.1: Voltage distortion limit

Bus voltage V at PCC Individual harmonic (%) Total harmonic

distortion THD (%)

V ≤ 1 kV 5.0 8.0

1 kV ˂ V ≤ 69 kV 3.0 5.0

69 kV ˂ V ≤ 161 kV 1.5 2.5

161 kV ˂ V 1.0 1.5a

aHigh voltage systems can have up to 2.0% THD where the cause is an HVDC

terminal whose effects will have attenuated at points in the network where future

users may be connected.

Meanwhile the recommended current distortion limits for systems nominally rated

120 V through 69 kV, for systems nominally rated above 69 kV through 161 kV and for

systems nominally rated above 161 kV are shown in Table 2.2, 2.3 and 2.4 respectively.

The TDD usage is similar to THD except that the distortion is expressed as a percent of the

maximum demand load current instead of as a percent of the fundamental current

magnitude. TDD is defined in Eq. 2.1.

= ∑ () × 100% (2.1)

where is the rms value of individual harmonic current, is the maximum rms demand

current and ℎ is the harmonic order.

Page 30: DESIGN A FILTER FOR HARMONICS CAUSED BY NON …eprints.uthm.edu.my/8812/1/NOR_FAEZAH_BINTI_ADAN.pdf · resonance and overall harmonics in the PS through simulation using PSCAD software

16

Table 2.2: Current distortion limits for system rated 120 V through 69 kV

Maximum harmonic current distortion in percent of IL

Individual harmonic order (odd harmonics)a,b

ISC / IL 3 ≤ h ˂ 11 11 ≤ h ˂ 17 17 ≤ h ˂ 23 23 ≤ h ˂ 35 35 ≤ h ˂ 50 TDD

˂ 20c 4.0 2.0 1.5 0.6 0.3 5.0

20 ˂ 50 7.0 3.5 2.5 1.0 0.5 8.0

50 ˂ 100 10.0 4.5 4.0 1.5 0.7 12.0

100 ˂ 1000 12.0 5.5 5.0 2.0 1.0 15.0

˃ 1000 15.0 7.0 6.0 2.5 1.4 20.0

Table 2.3: Current distortion limits for system rated above 69 kV through 161 kV

Maximum harmonic current distortion in percent of IL

Individual harmonic order (odd harmonics)a,b

ISC / IL 3 ≤ h ˂ 11 11 ≤ h ˂ 17 17 ≤ h ˂ 23 23 ≤ h ˂ 35 35 ≤ h ˂ 50 TDD

˂ 20c 2.0 1.0 0.75 0.3 0.15 2.5

20 ˂ 50 3.5 1.75 1.25 0.5 0.25 4.0

50 ˂ 100 5.0 2.25 2.0 0.75 0.35 6.0

100 ˂ 1000 6.0 2.75 2.5 1.0 0.5 7.5

˃ 1000 7.5 3.5 3.0 1.25 0.7 10.0

Table 2.4: Current distortion limits for system rated above 161 kV

Maximum harmonic current distortion in percent of IL

Individual harmonic order (odd harmonics)a,b

ISC / IL 3 ≤ h ˂ 11 11 ≤ h ˂ 17 17 ≤ h ˂ 23 23 ≤ h ˂ 35 35 ≤ h ˂ 50 TDD

˂ 25c 1.0 0.5 0.38 0.15 0.1 1.5

25 ˂ 50 2.0 1.0 0.75 0.3 0.15 2.5

≥ 50 3.0 1.5 1.15 0.45 0.22 3.75

Page 31: DESIGN A FILTER FOR HARMONICS CAUSED BY NON …eprints.uthm.edu.my/8812/1/NOR_FAEZAH_BINTI_ADAN.pdf · resonance and overall harmonics in the PS through simulation using PSCAD software

17

CHAPTER 3

METHODOLOGY

3.1 Introduction

This chapter describes modeling of a 3 phase distribution system with non-linear load and

PFCC, passive filter and SAPF using PSCAD software. This chapter also includes

mathematical equations of PFCC and passive filter.

3.2 Circuit topology

The 3 phase distribution system is formed by a balanced 3 phase source, a non-linear load

and PFCC. The SAPF consists of 6 controllable semiconductor switches with their

antiparallel diodes, and also an energy storage element, DC link capacitor (Cdc). An RLC

passive filter is also connected to the PCC. Figure 3.1 illustrates the circuit topology.

Page 32: DESIGN A FILTER FOR HARMONICS CAUSED BY NON …eprints.uthm.edu.my/8812/1/NOR_FAEZAH_BINTI_ADAN.pdf · resonance and overall harmonics in the PS through simulation using PSCAD software

18

Figure 3.1: Passive filter and SAPF topology

The application of PFCC on the power system may cause harmonic resonance as a

result of a series resonance between capacitive reactance of PFCC and the inductive

reactance of the source. Therefore, the RLC passive filter was tuned to the harmonic

resonance frequency of the non-linear load to absorb the harmonic current resonance

arising from the non-linear load. Meanwhile, the SAPF injects compensation currents to

the power system to reduce/eliminate the overall harmonic components to prevent

harmonic current propagation to the source.

3.3 Design circuit elements

3.3.1 Distribution system

The 3 phase source modeled is 400V, 20kVA, 50Hz while the non-linear load consists of a

3 phase 6-pulse bridge rectifier using 6 thyristors and an RL load as shown in Figure 3.2.

In practical, most DC drives use the 6-pulse bridge rectifier due to its relatively simple

control systems [1].

Page 33: DESIGN A FILTER FOR HARMONICS CAUSED BY NON …eprints.uthm.edu.my/8812/1/NOR_FAEZAH_BINTI_ADAN.pdf · resonance and overall harmonics in the PS through simulation using PSCAD software

19

Figure 3.2: Distribution system

The firing angle, of the thyristors is varied between 0 to 60o [25]. Due to the

presence of source inductance , the current commutation through the thyristors cannot

change instantaneously. Thus during the commutation angle , all four thyristors are

conducting simultaneously. The commutation process reduces the average load voltage

. From Eq. (3.1), the following relationship for the commutation angle is obtained,

where is the load current.

( + ) = () − 2 √2 (3.1)

As the source modeled has of 0.0005H, the expression for the average load

voltage is given by Eq. (3.2), where is source line to line voltage and is the

fundamental frequency.

= 3√2# cos() − 3 # (3.2)

In many applications, a load with series inductance results in a load current that is

essentially DC [26]. For a DC load current, the AC line current '( of the bridge rectifier

can be expressed in terms of its Fourier components as per Eq. (3.3), where ) is the source

fundamental frequency. The line currents consists harmonics of order 6k ± 1, k = 1,2,3…

Page 34: DESIGN A FILTER FOR HARMONICS CAUSED BY NON …eprints.uthm.edu.my/8812/1/NOR_FAEZAH_BINTI_ADAN.pdf · resonance and overall harmonics in the PS through simulation using PSCAD software

20

'((+) = 2√3# ,cos( )+) − 15 cos(5 )+)+ 17 cos(7 )+) − 111 cos(11 )+) + 113 cos(13 )+) − ⋯0

(3.3)

3.3.2 PFCC

PF of the system is given by Eq. (3.4), where 1, 1, are the fundamental rms voltage,

fundamental rms current and supply rms current respectively,

34 = 35 = 11 cos(61 − 71)1 = 1 cos(61 − 71) 34 = 8'+9+':;<+9 × 8'=><?@?:+34 (3.4)

The distortion factor (DF) is defined as the ratio of 1to . Since DPF can never be

greater than unity, the PF of a non-linear system has an upper bound defined by DF.

Referring to Figure 2.5, the required capacity of PFCC is given by Eq. (3.5), where AB is

the compensating reactive power in kVAR, 3 (kW) is the active power absorbed by the

system, 6)C as the initial PF angle and 6DEF, the desired or final PF angle.

PFCC in kVAR, AB = 3tan(6)C − 6DEF) (3.5)

Old PF angle, 6)C = J1(34)C × 1) (3.6)

Final PF angle, 6DEF = J1(34DEF × 1) (3.7)

3.3.3 Passive filter

The passive filter consists of a resistor, inductor and capacitor connected in series. An ideal

single tuned filter is said to be tuned on the frequency D, that makes its inductive and

capacitive reactance to be equal.

Page 35: DESIGN A FILTER FOR HARMONICS CAUSED BY NON …eprints.uthm.edu.my/8812/1/NOR_FAEZAH_BINTI_ADAN.pdf · resonance and overall harmonics in the PS through simulation using PSCAD software

21

Tuned frequency, D = 1√K (3.8)

The sharpness of filter tuning is determined by the quality factor A, and is defined

as the ratio of inductance (or capacitance) LD, to resistance M, at resonant frequency (Eq.

(3.9)). Thus, higher Q can be achieved with smaller M. Typical values of A fluctuate

between 15 and 80 for filters that are used in the industry. Low voltage filters (480 to 600V)

are associated with low A values while medium voltage filters (4.16 to 13.8kV) have A

values in the upper range [27-28].

Quality factor, A = LDM (3.9)

For a filter tuned to harmonic :, the reactance of inductor and capacitor is expressed

in Eq. (3.10), where is the inductance, K is the capacitance and D is the harmonic

frequency. The value of and K can be calculated using Eq. (3.11) and (3.12).

Reactance, LD = D = 1 DK (3.10)

Substituting Eq. (3.10) into (3.9),

= MA D (3.11)

K = 1MA D (3.12)

3.3.4 SAPF

The SAPF is modeled using 6 gate turn-off thyristors (GTO). GTO is selected as it only

requires a pulse for switching thus simplifying the SAPF control. The DC link capacitor is

used to supply a constant input current to the SAPF. In this simulation, the DC link

capacitor is represented by an ideal DC voltage source with rated voltage of 400kV. The

ideal voltage source will provide any active power required in simulation, meaning that it

is capable of supplying an infinite amount of energy for an infinite amount of time.

Page 36: DESIGN A FILTER FOR HARMONICS CAUSED BY NON …eprints.uthm.edu.my/8812/1/NOR_FAEZAH_BINTI_ADAN.pdf · resonance and overall harmonics in the PS through simulation using PSCAD software

22

3.4 Control techniques

3.4.1 Calculation of reference compensations currents

3.4.1.1 PQ theory

The instantaneous and reactive power method, p-q theory approach has been implemented

in this project. The process flowchart using p-q theory is illustrated in Figure 3.3.

Figure 3.3: Calculation of current reference based on p-q theory

Load current and voltage measurement

Clarke transformation (Calculate α-β voltage and current) Eq. (3.13) and (3.14), Figure 3.4

Calculate instantaneous real power, p and reactive power, q

Eq. (3.15), Figure 3.5

High pass filter for px calculation Eq. (3.18)

High pass filter for qx calculation Eq. (3.18)

Compensation currents calculation Eq. (3.16), Figure 3.6

Inverse Clarke transformation Eq. (3.17), Figure 3.7

Page 37: DESIGN A FILTER FOR HARMONICS CAUSED BY NON …eprints.uthm.edu.my/8812/1/NOR_FAEZAH_BINTI_ADAN.pdf · resonance and overall harmonics in the PS through simulation using PSCAD software

23

The p-q theory consists of a Clarke transformation of the 3 phase system voltages

((, N, B) and load currents ((, N, B) in the a-b-c coordinates to the α-β coordinates as

expressed by Eq. (3.13) and (3.14) and demonstrated by Figure 3.4.

OPQ = R23STTU1 −12 −120 √32 −√32 VW

WXY(NB Z (3.13)

OPQ = R23STTU1 −12 −120 √32 −√32 VW

WXY(NBZ (3.14)

(a) Vα calculation (b) Vβ calculation

(c) Iα calculation (d) Iβ calculation

Figure 3.4: PSCAD models for Clarke transformation

Page 38: DESIGN A FILTER FOR HARMONICS CAUSED BY NON …eprints.uthm.edu.my/8812/1/NOR_FAEZAH_BINTI_ADAN.pdf · resonance and overall harmonics in the PS through simulation using PSCAD software

24

After the transformation, p-q theory instantaneous power components are calculated

using Eq. (3.15), where = is the instantaneous real power, and [ is the instantaneous

imaginary power. Figure 3.5 shows the corresponding PSCAD model.

\=[] = O P−P Q OPQ (3.15)

(a) p calculation (b) q calculation

Figure 3.5: PSCAD models for p-q instantaneous power components calculation and

HPF to obtain px and qx

Each of the active and reactive power is composed of continuous and alternating

terms. The continuous term corresponds to the fundamental current and voltage. The

alternating part represents power related to the sum of the harmonic components of current

and voltage. In order to calculate the reference compensation currents that the active filter

should inject, it is necessary to separate the desired power components from the undesired

ones denoted by =^ and [^. Specifically, a high pass filter (HPF) is used in this project to

separate the desired power components from the undesired ones [3.5]. The undesired power

components are used to determine the compensation currents in the α-β coordinates as per

Eq. (3.16) while Figure 3.6 shows the corresponding PSCAD model.

OBBPQ = 1 + P O −PP Q \=^[^] (3.16)

(a) Icα calculation (b) Icβ calculation

Figure 3.6: PSCAD models for compensation current calculation in α-β coordinates