Upload
others
View
5
Download
0
Embed Size (px)
Citation preview
Deployment and Initial Experience with Oscillation Detection Application at
Bonneville Power Administration
Dmitry Kosterev, Ashley Donahoo, Nick Leitschuh – BPA
Jeff Dagle, Frank Tuffner – PNNL
Dan Trudnowski – Montana Tech
2016 IEEE Meeting
BPA Overview• Bonneville Power
Administration (BPA) is a federal Power Marketing Agency in Pacific Northwest
• BPA markets power from 31 Federal dams and the Columbia Generating Station Nuclear Plant
• BPA operates more than 15,000 miles of transmission, including 4,735 miles of 500-kV lines
BPA operates several large paths in the Western Interconnection – California Oregon AC Intertie (4,800 MW), Pacific HVDC Intertie (3,100 MW), Northern Intertie (3,100 MW), and Montana Intertie (2,200 MW)
2
History of Syncrophasors at BPA
• BPA has been one of the earliest adopters of synchrophasortechnology since early 1990s
0 10 20 30 40 50 60 70 80 90 1003600
3800
4000
4200
4400
4600
4800
5000
Time (sec) from 15:47:30
Pow
er
(MW
)
COI Power, August 10 1996
BPA has greatly expanded PMU coverage and networking following 1996 outages
BPA researched, prototyped and deployed several PMU applications for engineering analysis
However, that PMU network was research-grade and was not reliable or secure for real-time control room applications
3
2010 Synchrophasor Investment Project
BPA initiated a capital investment project in 2010 to build a secure, reliable, control-grade synchrophasornetwork:• 5-year, $35M project • Part of DOE Smart Grid Program
• “Control” PMUs• Fully redundant architecture• 32 substations• 110 PMUs (55 redundant pairs)
• “Data” PMUs• 15 wind sites
• Total of 3,322 signals
4
Platt’s Global Energy Award
BPA synchrophasor investment project received 2013 Platt’s Global Energy Award for Industry Leadership in Grid Optimization
5
BPA Oscillation Detection Application
6
Control Room: Oscillation Detection
BPA deployed Oscillation Detection in its control room in October 2013
Scans 100+ signals for signs of growing or sustained power oscillations
Alarms dispatchers when an oscillation is detected
Dispatcher training sessions are performed
7
Operating procedures are developed in 2016
How are Oscillations detected?The magnitude of the oscillation is calculated in 4 frequency bands
8
100+
signals
scanned
Band 4 Energy
Band 3 Energy
Band 2 Energy
Band 1 Energy
How alarm is generated
9
If the oscillation is strong enough, and lasts long enough then an alarm is issued
Band 1 – (0.01- 0.15 Hz) >> 400 seconds
Band 2 – (0.15 - 1.0 Hz) >> 120 seconds
Band 3 – (1.0 - 5.0 Hz) >> 120 seconds
Band 4 – (5.0 - 14.0 Hz) >> 120 seconds
Must persist for this long:
120 sec
Oscillation Detection Events
• Multiple events of oscillation are detected monthly
• Examples:
– Generator control interactions
– Wind generation oscillations
– Bad operating point on a power plant
– Pacific HVDC Intertie controls
– Generator rotor angle oscillations
– Etc
10
(a) Central Oregon Oscillation on February 20, 2014 Overview display
Detailed display
(a) Central Oregon Oscillation on February 20, 2014
0 60 120 180 240 300 360 420-200
-150
-100
-50
0Active Power
Pow
er
(MW
)
0 60 120 180 240 300 360 42080
100
120
140
160
180Reactive Power
Time (sec)
Rea
ctive
(M
VA
R)
40 45 50 55 60 65 70-150
-100
-50
0Active Power
Pow
er
(MW
)
40 45 50 55 60 65 70100
110
120
130
140Reactive Power
Time (sec)
Rea
ctive
(M
VA
R)
CT failure resulted in
plant developing a large
power oscillations at 1.2
Hz frequency
7 minute plot
30-second plot
(b) Hydro Power Plant Oscillation
SYNCHROPHASOR: 10/30/2014 8:15:00 AMOSCILLATION DETECTION SUMMARY CLOSE
CUSTER
MONROE
CAPT JACK
ECHO LAKE
SUMMER LAKE
SCHULTZ
GRIZZLY
PAUL
MARION
ALVEY
NORTH
KEELER
BONNEVILLE
GARRISON
COULEE
GRAND
BELL
JOSEPH
CHIEF
ENERGY BAND KEY
.01 - .15 Hz
5.0 - 14 Hz
1.0 - 5.0 Hz
.15 - 1.0 Hz
CLICK ON A PMU
TO VIEW DETAILS
Generator, HVDC or SVC
Local Plant Controls
Inter-Area Oscil lations
Local Plant Controls or AGC
MALIN
EDDY
BIG
ROCK CREEK
SLATT
MCNARY
DAY
JOHN
SUMMARY TRENDS
500KV
500KV
230KV
500KV
500KV
230KV
500KV
230KV230KV
500KV
500KV
230KV
500KV
230KV
500KV500KV
500KV
500KV
500KV
500KV
230KV
500KV
230KV
230KV
500KV
500KV
500KV
500KV
CENTRAL
FERRY
500KV
ASHE
500KV
LOWER
MONUMENTAL
500KV
10/30/2014 8:15:00 AM10/30/2014 7:15:00 AM 60.00 minutes
ENERGY BAND 2
0.00
3.50
10/30/2014 8:15:00 AM10/30/2014 7:15:00 AM 60.00 minutes
ENERGY BAND 1
0.00
6.00
OSCILLATION ENERGY DETAILS:
JOHN DAY:POWERHOUSE #2 500KV LINE POWER10/30/2014 8:15:00 AM
10/30/2014 8:15:00 AM10/30/2014 7:15:00 AM 60.00 minutes
ENERGY BAND 3
0.00
3.00
10/30/2014 8:15:00 AM10/30/2014 7:15:00 AM 60.00 minutes
ENERGY BAND 4
0.00
0.70
JOHN DAY: POWERHOUSE #2 500KV MW-1 SEC
10/30/2014 8:15:00 AM10/30/2014 7:15:00 AM 60.00 minutes
MW
410.00
440.00
10/30/2014 8:15:00 AM10/30/2014 7:15:00 AM 60.00 minutes
-7
-2
3
-5
5
-3
7
-1
9BAND1 (.01-.15 Hz)
BAND2 (.15-1.0 Hz)
BAND3 (1.0-5.0 Hz)
BAND4 ( 5 -14 Hz)
MW
433.88
CLOSE
BAND1 ENERGY
0.7 MW
HI LIMIT
5.4 MW
BAND2 ENERGY
2.7 MW
HI LIMIT
1.6 MW
BAND4 ENERGY
0.1 MW
HI LIMIT
0.7 MW
BAND3 ENERGY
0.3 MW
HI LIMIT
2.8 MW
Oscillation Details
Overview Display
410
412
414
416
418
420
422
424
0 6 12 18 24 30 36 42 48 54 60
Po
we
r (M
W)
Time (sec)
Power
-255
-250
-245
-240
-235
-230
0 6 12 18 24 30 36 42 48 54 60
Re
acti
ve P
ow
er
(MV
AR
)
Time (sec)
Reactive Power
Period of oscillation is
3 seconds, oscillation
frequency is 0.33 Hz,
seen in both active
and reactive power
The oscillation is
caused by a surging
water vortex in one of
the turbines operating
at a partial load
Plant was re-
dispatched to a stable
operating point
(b) Hydro Power Plant Oscillation
(c) Wind Power Oscillation
(c) Wind Power Oscillations
9:00 8:30 8:00 6:30 6:00 5:30
1/30/2014 9:21:56 AMJOHN DAY - BIGLOW MVAR
10
20
30
40
50
60
70
80
9:00 8:30 8:00 6:30 6:00 5:30
1/30/2014 9:21:56 AMJOHN DAY - BIGLOW MW
-400
-360
-340
-320
-300
-280
-240
9:00 8:30 8:00 6:30 6:00 5:30
1/30/2014 9:21:56 AMJOHN DAY VOLTAGE
237,000
237,500
238,000
238,500
239,000
239,500
9:00 8:30 8:00 6:30 6:00 5:30
1/30/2014 9:21:56 AMFREQUENCY
59.95
59.97
59.98
59.99
60
60.01
60.02
60.03
60.05FREQUENCY VOLTAGE
ACTIVE POWER REACTIVE POWER
FREQUENCY VOLTAGE
ACTIVE POWER REACTIVE POWER
Oscillation is at 14
Hz, most visible in
reactive power,
indication of
voltage control
issues
Oscillations
reached 80 MVAR
peak to peak
(c) Wind Power Oscillations
Manufacturer upgraded the controls in April 2014 to fix
the oscillation problem
16:00 17:00
4/15/2014 4:14:59 PMJOHN DAY - BIGLOW MVAR
-20
0
10
20
30
40
60
16:00 17:00
4/15/2014 4:14:59 PMJOHN DAY - BIGLOW MW
-450
-350
-300
-250
-200
-150
-50
16:00 17:00
4/15/2014 4:14:59 PMJOHN DAY VOLTAGE
236,000
237,000
238,000
239,000
240,000
241,000
242,000
16:00 17:00
4/15/2014 4:14:59 PMFREQUENCY
59.95
59.97
59.98
59.99
60
60.01
60.02
60.03
60.05FREQUENCY VOLTAGE
ACTIVE POWER REACTIVE POWER
(d) Hydro Plant Control Interaction
Oscillation Details
Overview Display
Oscillation is caused by interactions between generator UEL and PSS
UEL was retuned in January 2016
-69.050
MW
10/21/2015 3:30:10 AM10/21/2015 3:30:00 AM 10.00 seconds
THE DALLES PH4 ACTIVE POWER
-90
-80
-70
-55
52.724
MV
10/21/2015 3:30:10 AM10/21/2015 3:30:00 AM 10.00 seconds
The DALLES PH4 REACTIVE POWER
35
45
50
55
65
(d) Hydro Plant Control Interaction
Success Story• BPA successfully deployed Oscillation Detection Module (ODM) in its control
room
• ODM is developed by Dan Trudnowski at MTU
• ODM scans for 100+ signals for sustained high energy oscillations
• ODM was implemented in 2013, and displays have been in the control rooms since October 2013 – log alarm only
• Several dispatcher training sessions have been performed
• Dispatchers took actions based on ODM results
• Operating procedures are developed, in effect June 1, 2016
• Several control improvements are implemented, including UEL tuning at a hydro-power plant and control firmware upgrades at a wind power plant
20