18
DENS: Data Center Energy- Efficient Network-Aware Scheduling Dzmitry Kliazovich University of Luxembourg Pascal Bouvry University of Luxembourg Samee Ullah Khan North Dakota State University Dec 20, 2010

DENS: Data Center Energy-Efficient Network-Aware Scheduling Dzmitry Kliazovich University of Luxembourg Pascal Bouvry University of Luxembourg Samee Ullah

Embed Size (px)

Citation preview

DENS: Data Center Energy-Efficient

Network-Aware Scheduling

Dzmitry Kliazovich University of Luxembourg

Pascal Bouvry University of Luxembourg

Samee Ullah Khan North Dakota State University

Dec 20, 2010

GreenCom 2010

Why energy is important? Increased computing demand

Data centers are rapidly growing Consume 10 to 100 times more energy per square foot

than a typical office building

Energy cost dynamics Energy accounts for 10% of data center operational

expenses (OPEX) and can rise to 50% in the next few years

Accompanying cooling system costs $2-$5 million per year

December 20, 2010 2Pascal Bouvry ([email protected])

GreenCom 2010

Distribution of data center energy consumption

December 20, 2010 3Pascal Bouvry ([email protected])

GreenCom 2010

Data center architectures Three-tier data center architecture

Most Widely Used Nowadays Access, Aggregation, and Core layers Scales to over 10,000 servers

December 20, 2010

S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S

CoreNetwork

AggregationNetwork

AccessNetwork

S

Links

10 GE 1 GE

Nodes

L3 Switch L2/L3 Rack Switch Computing Server

4Pascal Bouvry ([email protected])

GreenCom 2010

Data center components Servers’ Energy Model

Pascal Bouvry ([email protected]) 5December 20, 2010

Fmin

Fmax

0

0.2

0.4

0.6

0.8

1

Pfixed

Ppeak

CPU FrequencyServer load

Pow

er c

onsu

mpt

ion

CPUmemory modules, disks, I/O resources

Idle server consumes about 66% of the peak load for all CPU frequencies

GreenCom 2010

Data center components Switches

Most common Top-of-Rack (ToR) switches typically operate at Layer-2 interconnecting gigabit links in the access network

Aggregation and core networks host Layer-3 switches operating at 10 GE (or 100 GE)

Links Transceivers’ power consumption depends on the quality of signal

transmission in cables and is proportional to their cost 1 GE links consume 0.4W for 100 meter transmissions over twisted

pair 10 GE links consume 1W for 300 meter transmission over optical fiber

Supported power management modes DVFS, DNS, or both

Pascal Bouvry ([email protected]) 6December 20, 2010

GreenCom 2010

Simulator components Switches’ Energy Model

Pascal Bouvry ([email protected]) 7December 20, 2010

Chassis~ 36%

Linecards~ 53%

Port transceivers~ 11%

GreenCom 2010

DENS methodology DENS achieves balance between

Energy consumed by the data center Individual job performances Job QoS requirements Data center traffic demands

DENS is architecture specific

Pascal Bouvry ([email protected]) 8December 20, 2010

CoreNetwork

AggregationNetwork

AccessNetwork

Rack Rack Rack

Module

Data Center Architecture

GreenCom 2010

0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 10

0.2

0.4

0.6

0.8

1

L s(l)

Server load, l

DENS methodology Computing server selection

Pascal Bouvry ([email protected]) 9December 20, 2010

Penalize Under-loaded

Servers

Favor High Server

Utilization

Avoid Overloading

GreenCom 2010

0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 10

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1

Q(q

)

Queue size, q/Qmax

DENS methodology Computing server selection

Pascal Bouvry ([email protected]) 10December 20, 2010

Favor Low Congestion

Levels

Penalize Congested

Queues

GreenCom 2010

00.2

0.40.6

0.81

0

0.5

10

0.1

0.2

0.3

0.4

0.5

Server load, lQueue load, q

Fs(l

,q)

DENS methodology Computing server selection

Pascal Bouvry ([email protected]) 11December 20, 2010

Maximize Server Load,Minimizing Network

Congestion

GreenCom 2010

Performance Evaluation GreenCloud simulator is developed Three-tier data center topology

1536 nodes, 32 racks, 4 core and 8 aggregation switches

Pascal Bouvry ([email protected]) 12December 20, 2010

CoreNetwork

AggregationNetwork

AccessNetwork

Computing Server

1 RU Rack Switch

L3 Switch

TaskSchedulerTask

Scheduler

Links

10 GE 1 GE

WorkloadGenerator

CloudUserCloud

User

Data Center

Data CenterCharacteristics

TaskScheduler

TaskComAgent

L3 Energymodel

L2 Energymodel

ServerCharacteristics

TaskComSink

Connect ()

SchedulerServerEnergy model

S S S S S S S S S

WorkloadTrace File

GreenCom 2010

Performance Evaluation Server workload distribution

Pascal Bouvry ([email protected]) 13December 20, 2010

0 200 400 600 800 1000 1200 1400 16000

0.2

0.4

0.6

0.8

1

Server #

Ser

ver

load

Green scheduler

DENS scheduler

Round-robin scheduler

Redistributing Computing

Load

GreenCom 2010

0 5 10 15 20 25 30 350

0.5

1

1.5

Top-of-Rack switch #

Com

bine

d up

link

load

leve

l

Performance Evaluation Network workload distribution

Pascal Bouvry ([email protected]) 14December 20, 2010

Green scheduler

DENS scheduler

Round-robin scheduler

Redistributing Load to

Satisfy QoS

Network congestion

GreenCom 2010

Performance Evaluation Top-of-Rack (ToR) switch load

Pascal Bouvry ([email protected]) 15December 20, 2010

0 5 10 150

0.2

0.4

0.6

0.8

1

Simulation time (s)

ToR

sw

itch

uplin

k lo

ad le

vel

0 5 10 150

200

400

600

800

1000

Simulation time (s)

Upl

ink

queu

e si

ze (

pack

ets)

Network congestion

Green scheduler

DENS scheduler

Green scheduler

DENS scheduler

GreenCom 2010

Data center energy consumption

Pascal Bouvry ([email protected]) 16December 20, 2010

Parameter

Power Consumption (kW·h)

Round Robinscheduler

GreenScheduler

DENSscheduler

Data centerServersNetwork switches

417.5K353.7K63.8K

203.3K (48%)161.8K (45%)41.5K (65%)

212.1K (50%)168.2K (47%)43.9K (68%)

EnergyQoS

Performance Evaluation

GreenCom 2010

Conclusions We acknowledge

Funding form Luxembourg FNR in the framework of GreenIT project

Research fellowship provided by the European Research Consortium for Informatics and Mathematics (ERCIM)

Related publications "GreenCloud: A Packet-level Simulator of Energy-aware Cloud Computing

Data Centers," in Journal of Supercomputing, special issue on Green Networks, 2011.

“GreenCloud: A Packet-level Simulator of Energy-aware Cloud Computing Data Centers,” IEEE Global Communications Conference (GLOBECOM), Miami, FL, USA, December 2010.

Pascal Bouvry ([email protected]) 17December 20, 2010

GreenCloud

GreenCom 2010

Thank you!