30
FISHER -ROSEMOUNT SYSTEMS Classic I/O Redundancy 16-1 Course 7009 -- Rev 3 - 4/15/01 TM Classic I/O Redundancy

Delta v Course 7009-16

Embed Size (px)

Citation preview

Page 1: Delta v Course 7009-16

FISHER-ROSEMOUNT SYSTEMS Classic I/O Redundancy

16-1Course 7009 -- Rev 3 - 4/15/01

TM

Classic I/O Redundancy

Page 2: Delta v Course 7009-16

FISHER-ROSEMOUNT SYSTEMS Classic I/O Redundancy

16-2Course 7009 -- Rev 3 - 4/15/01

Page 3: Delta v Course 7009-16

FISHER-ROSEMOUNT SYSTEMS Classic I/O Redundancy

16-3Course 7009 -- Rev 3 - 4/15/01

Upon completion of this module you will be able to:

Define Classic I/O Redundancy functionality

Define Classic I/O Redundancy components

Define Classic I/O Redundancy wiring connections

Configure Classic I/O Redundancy modules

Define Classic I/O Redundancy user interface

Objectives

Page 4: Delta v Course 7009-16

FISHER-ROSEMOUNT SYSTEMS Classic I/O Redundancy

16-4Course 7009 -- Rev 3 - 4/15/01

Classic I/O RedundancyController Primary Backup

(-) (+)Field Wiring

Classic I/OSwitchover Panel

••••••••••••••••

Field Instrument

Page 5: Delta v Course 7009-16

FISHER-ROSEMOUNT SYSTEMS Classic I/O Redundancy

16-5Course 7009 -- Rev 3 - 4/15/01

Classic I/O RedundancyClassic I/O Redundancy provides 1:1 redundancy for classic I/O cards as shown above. The following I/O cards are supported:

AI, 8-channel, 4-20mA (without HART)(2-wire only)

AO, 8-channel, 4-20mA (without HART)

DI, 8-channel, 24 VDC, Isolated

DI, 8-channel, 24 VDC, Dry Contact

DO, 8-channel, 24 VDC, Isolated

DO, 8-channel, 24 VDC, High-side

Automatic switchover will occur in the event of a primary I/O card failure. The operator is given notification of a switchover at the operator display.

Note: Outputs to process equipment will be interrupted during switchover. (Two millisecond is typical if the card is configured to Hold Last Value) In addition, outputs to process equipment may be at an indeterminate state during switchover. Inputs to the controller remain at last value during switchover.

Page 6: Delta v Course 7009-16

FISHER-ROSEMOUNT SYSTEMS Classic I/O Redundancy

16-6Course 7009 -- Rev 3 - 4/15/01

Classic I/O RedundancyRedundancy Control Module

••••••••

• • • • • • • •• • • • • • • •

DO24VDC High Side

Controller Primary Switch Card Backup

1 3 5 7 9 11 13 15

(+)

2 4 6 8 10 12 14 16

(-)

Redundancy Switchover Panel

Field Wiring

Pri. Bkup

(+) (-)

Mass Term.Field Wiring

Option

16-pin mass termination blocks• • • • • • • •• • • • • • • •

• • • • • • • •• • • • • • • •

••••••••

(-) (+)

Field Instrument

Page 7: Delta v Course 7009-16

FISHER-ROSEMOUNT SYSTEMS Classic I/O Redundancy

16-7Course 7009 -- Rev 3 - 4/15/01

Classic I/O RedundancyThe primary and backup I/O cards shown above are connected to the redundancy panel using mass termination blocks and two cables. The switchover panel has eight relays that switch the eight channels from one card to another. A discrete output signal is wired to the switchover panel to trigger the switchover. A redundancy control module in the controller monitors the integrity of the primary and backup card to determine when a switchover should be triggered.

Switchovers are caused by the following events:

Hardware failure within the active card.

Bad integrity on an individual channel.

Communications failure between the active card and the controller.

Removal of the active card from the carrier.

Manual Switch.

The redundancy control module is created from one of four module templates to simplify configuration. The type of module template that should be used is based on the type of I/O cards. For example, if the primary and backup cards are discrete outputs, the OUTPUT_DISCRETE template should be used.

Page 8: Delta v Course 7009-16

FISHER-ROSEMOUNT SYSTEMS Classic I/O Redundancy

16-8Course 7009 -- Rev 3 - 4/15/01

Redundancy Example

••••••••

• • • • • • • •• • • • • • • •

DO24VDC High Side

Controller Primary Switch Card Backup

1 3 5 7 9 11 13 15

(+)

2 4 6 8 10 12 14 16

(-)

Redundancy Switchover Panel

Field Wiring

Pri. Bkup

(+) (-)

Mass Term.Field Wiring

Option

16-pin mass termination blocks• • • • • • • •• • • • • • • •

• • • • • • • •• • • • • • • •

••••••••

(-) (+)

Field Instrument

Redundancy Control Module

Page 9: Delta v Course 7009-16

FISHER-ROSEMOUNT SYSTEMS Classic I/O Redundancy

16-9Course 7009 -- Rev 3 - 4/15/01

Workshop -Setting Up Classic I/O Redundancy

The following workshop steps you through the hardware and configuration setup necessary to implement redundant I/O. The example shown above provides a redundant discrete output to a critical discrete device. The following tasks are required.

Task 1. Install the I/O Hardware.

Task 2. Configure the I/O cards.

Task 3. Configure the redundancy control module.

Task 4. Download the controller.

Task 5. Verify operation.

Page 10: Delta v Course 7009-16

FISHER-ROSEMOUNT SYSTEMS Classic I/O Redundancy

16-10Course 7009 -- Rev 3 - 4/15/01

Workshop - I/O Hardware Installation

••••••••

• • • • • • • •• • • • • • • •

1 3 5 7 9 11 13 15

(+)

2 4 6 8 10 12 14 16

(-)

Redundancy Switchover Panel

Field Wiring

Pri. Bkup

(+) (-)

Mass Term.Field Wiring

Option

16-pin mass termination blocks• • • • • • • •• • • • • • • •

• • • • • • • •• • • • • • • •

••••••••

(-) (+)

Field Instrument

PrimaryDO 24VDCHigh SideSlot 1

BackupDO 24VDCHigh SideSlot 3

DO 24VDCHigh Side

Switch CardSlot 2

Page 11: Delta v Course 7009-16

FISHER-ROSEMOUNT SYSTEMS Classic I/O Redundancy

16-11Course 7009 -- Rev 3 - 4/15/01

Step 1. Install the primary discrete output card in slot 1 with a 16 pin mass termination block.

Step 2. Install the backup discrete output card in slot 3 with a 16 pin mass termination block.

Step 3. Connect the primary and backup cards to the redundancy switchoverpanel using a 16 pin mass termination block cable as shown above.

Step 4. Install the switch card in slot 2 with an I/O termination block.

Workshop - I/O Hardware Installation

Page 12: Delta v Course 7009-16

FISHER-ROSEMOUNT SYSTEMS Classic I/O Redundancy

16-12Course 7009 -- Rev 3 - 4/15/01

Step 5. Wire slot 2, terminal block connection 1 to the + connector on the redundancy switch panel. Wire slot 2, terminal block connection 2to the — connector on the redundancy switch panel. This example uses channel 1 on card 2 as the switch signal.

Step 6. Wire the field instrument + connection to terminal block connection 1. Wire the field instrument — connection to terminal blockconnection 2. This example uses channel 1 to control the Field Instrument.

Note: The mass termination block in the lower right hand corner of the redundancy switchover panel would be used if the field instrument were wired to the control system through mass terminations.

Workshop - I/O Hardware Installation

Page 13: Delta v Course 7009-16

FISHER-ROSEMOUNT SYSTEMS Classic I/O Redundancy

16-13Course 7009 -- Rev 3 - 4/15/01

Page 14: Delta v Course 7009-16

FISHER-ROSEMOUNT SYSTEMS Classic I/O Redundancy

16-14Course 7009 -- Rev 3 - 4/15/01

Workshop - I/O Card Configuration

••••••••

1 3 5 7 9 11 13 15

(+)

2 4 6 8 10 12 14 16

(-)

Redundancy Switchover Panel

Field Wiring

Pri. Bkup

(+) (-)

• • • • • • • •• • • • • • • •

• • • • • • • •• • • • • • • •

••••••••

(-) (+)

Field Instrument

PrimaryDO 24VDCHigh SideSlot 1

BackupDO 24VDCHigh SideSlot 3

DO 24VDCHigh Side

Switch CardSlot 2

Page 15: Delta v Course 7009-16

FISHER-ROSEMOUNT SYSTEMS Classic I/O Redundancy

16-15Course 7009 -- Rev 3 - 4/15/01

Configuring I/O cards for redundancy does not require any special card configuration. Define the primary, secondary and switch cards as standard I/Ocards. The redundancy functionality will be provided with the redundancycontrol module. The figure below shows the cards configured as a classic DO Card, 8 Ch, 24VDC, High Side.

Workshop - I/O Card Configuration

Page 16: Delta v Course 7009-16

FISHER-ROSEMOUNT SYSTEMS Classic I/O Redundancy

16-16Course 7009 -- Rev 3 - 4/15/01

Workshop - I/O Channel Configuration

••••••••

1 3 5 7 9 11 13 15

(+)

2 4 6 8 10 12 14 16

(-)

Redundancy Switchover Panel

Field Wiring

Pri. Bkup

(+) (-)

• • • • • • • •• • • • • • • •

• • • • • • • •• • • • • • • •

••••••••

(-) (+)

Field Instrument

Channel 1XV1_PRI

Channel 1XV1_BACKUP

Channel 1XV1_SWITCH

Page 17: Delta v Course 7009-16

FISHER-ROSEMOUNT SYSTEMS Classic I/O Redundancy

16-17Course 7009 -- Rev 3 - 4/15/01

The most important part of channel configuration is that they are enabled as shown below. XV1 is the name of the device in the example below. Naming conventions used for the DSTs are shown below:

XV1_PRI for the primary channel (recommend Fail_Action_Mode=Hold last value)

XV1_SWITCH for the switch channel

XV1_BACKUP for the backup channel

Workshop - I/O Channel Configuration

Page 18: Delta v Course 7009-16

FISHER-ROSEMOUNT SYSTEMS Classic I/O Redundancy

16-18Course 7009 -- Rev 3 - 4/15/01

Workshop - Redundancy Control Module

••••••••

1 3 5 7 9 11 13 15

(+)

2 4 6 8 10 12 14 16

(-)

Redundancy Switchover Panel

Field Wiring

Pri. Bkup

(+) (-)

• • • • • • • •• • • • • • • •

• • • • • • • •• • • • • • • •

••••••••

(-) (+)

Field Instrument

Channel 1XV1_PRI

Channel 1XV1_BACKUP

Channel 1XV1_SWITCH

ControllerCTLR1

Redundancy Control Module

Page 19: Delta v Course 7009-16

FISHER-ROSEMOUNT SYSTEMS Classic I/O Redundancy

16-19Course 7009 -- Rev 3 - 4/15/01

Workshop - Redundancy Control ModuleThe redundancy control module monitors the overall integrity of the primary and backup cards. In the event of an integrity error on the primary card the control module energizes the switch channel and switches the relays to the backup card.

The redundancy control module should be created from one of the module templates based on the primary and backup card types. The example below uses the OUTPUT_DISCRETE since the primary and backup cards are discrete outputs.

Drag ‘n drop PUTPUT_DISCRETE to a plan area and rename the module RED_OUT_DIS

Page 20: Delta v Course 7009-16

FISHER-ROSEMOUNT SYSTEMS Classic I/O Redundancy

16-20Course 7009 -- Rev 3 - 4/15/01

Workshop -Redundancy Module Configuration

Page 21: Delta v Course 7009-16

FISHER-ROSEMOUNT SYSTEMS Classic I/O Redundancy

16-21Course 7009 -- Rev 3 - 4/15/01

Workshop -Redundancy Module Configuration

The parameters to be modified are shown above.

Step 1. Modify the PRI_OINTEG and BCK_OINTEG diagnostic parameters that evaluate the overall integrity of the primary and backup cards.PRI_OINTEG = CTLR1/IO1/C01/OINTEG (Card 1)BCK_OINTEG = CTLR1/IO1/C03/OINTEG (Card 3)

Step 2. Modify the PRI_DESC and BCK_DESC description fields that appear on the faceplate.PRI_DESC = CTLR1 Slot 1BCK_DESC = CTLR1 Slot 3

Step 3. Modify DO, an External Reference that identifies the switch channel.DO = CTLR1/IO1/C02/CH01/OUT_D (Card 2)

Step 4. Modify PRI_CH1 and BCK_CH1, External References that identify the primary and backup channels.PRI_CH1 = CTLR/IO1/C01/CH01/OUT_DBCK_CH1 = CTLR1/IO1/C03/CH01/OUT_D

Page 22: Delta v Course 7009-16

FISHER-ROSEMOUNT SYSTEMS Classic I/O Redundancy

16-22Course 7009 -- Rev 3 - 4/15/01

Workshop -Redundancy Module Configuration

Page 23: Delta v Course 7009-16

FISHER-ROSEMOUNT SYSTEMS Classic I/O Redundancy

16-23Course 7009 -- Rev 3 - 4/15/01

In the following, all references to channels 2-8 will be deleted. All channel 2references are selected for deletion in the figure above. Complete the module configuration as follows:

Step 1. Assign the module to CTLR1.

Step 2. Define module properties.

Primary Control Display = users choiceDetail Display = REDDO_DTFaceplate Display = REDIO_fpExecution Scan Rate = 1 sec

Note: FRSI recommends that you set the scan rate equal to the fastest module that will utilize this redundancy module (to reduce unnecessary controller loading)

Step 3. Save the module, name it RED_OUT_DIS.

Step 4. Download the controller.

Workshop -Redundancy Module Configuration

Page 24: Delta v Course 7009-16

FISHER-ROSEMOUNT SYSTEMS Classic I/O Redundancy

16-24Course 7009 -- Rev 3 - 4/15/01

Workshop - Verify Functionality

Page 25: Delta v Course 7009-16

FISHER-ROSEMOUNT SYSTEMS Classic I/O Redundancy

16-25Course 7009 -- Rev 3 - 4/15/01

The figure above illustrates the pre-configured faceplate used for the redundancy control module.

Note the following:

The arrow indicates which card is connected to the field instrument through the redundancy switchover panel. When the switch signal isde-energized the primary card is connected to the field instrument. This is the normal mode of operation.

Redundancy Status = Enabled which means an automatic switchover willoccur in the event of a primary card failure.

The user may force a switchover by pressing Use Primary Card, UseBackup Card. Normally the Automatic button should be selected which will Enable a switchover in the event of a failure.

Workshop - Verify Functionality

Page 26: Delta v Course 7009-16

FISHER-ROSEMOUNT SYSTEMS Classic I/O Redundancy

16-26Course 7009 -- Rev 3 - 4/15/01

Workshop - Switchover Indication

Page 27: Delta v Course 7009-16

FISHER-ROSEMOUNT SYSTEMS Classic I/O Redundancy

16-27Course 7009 -- Rev 3 - 4/15/01

Workshop - Switchover IndicationThe figure above illustrates a switchover indication.

Note the following:

The arrow indicates the backup card is connected to the field instrument through the redundancy switchover panel which means the switch signalis energized.

Redundancy Status indicates a switchover has occurred. Also notice a primary integrity alarm is active on the bottom of the faceplate.

The following sequence should be performed to get the system back to a normal redundancy mode with auto switch enabled.

Step 1. Replace the bad primary card.

Step 2. Press the Reset button on the faceplate. This will switch back to theprimary card as well as Enable Redundancy status for automatic switchover.

Page 28: Delta v Course 7009-16

FISHER-ROSEMOUNT SYSTEMS Classic I/O Redundancy

16-28Course 7009 -- Rev 3 - 4/15/01

Workshop - Control Module Configuration

Page 29: Delta v Course 7009-16

FISHER-ROSEMOUNT SYSTEMS Classic I/O Redundancy

16-29Course 7009 -- Rev 3 - 4/15/01

Workshop - Control Module ConfigurationThis example has covered the installation and configuration of the redundant I/O scheme. The last topic to mention is the control modules that will utilize the redundancy scheme. XV1 is the device tag of the critical instrument.

Control module XV-101 has been configured to to OPEN and CLOSE this valve. This module was configured the same as other modules with one exception. The output of the DC1 block is not be tied directly to a DST. The output is exposed F_OUT_D1 and wired to the DO1 parameter on the module block referencing the redundancy module.

By configuring the module in this manner the output is always sent through the redundancy control module to determine which card should send the signal to the field based on overall card integrity.

Page 30: Delta v Course 7009-16

FISHER-ROSEMOUNT SYSTEMS Classic I/O Redundancy

16-30Course 7009 -- Rev 3 - 4/15/01

Summary

You should now be able to:

Define Classic I/O Redundancy functionality

Define Classic I/O Redundancy components

Define Classic I/O Redundancy wiring connections

Configure Classic I/O redundancy modules

Define Classic I/O redundancy user interface