A DVANCED T ECHNOLOGY I N

INDUCED DRAFT, AX IA L FAN CONDENSER S

215 till 16000 kW nominal capacity

D E L I V E R I N G Q U A L I T Y. . . F O C U S E D O N P E R F E C T I O N !

Bulletin 172-E Metric

C E R T I F I E D E N I S O 9 0 0 1

Mr. GoodTower®

InternationalInstitute of Ammonia Refrigeration

Page 2: DELIVERING Q F OCUSED ON PERFECTION · During fabrication, all panel edges are coated with a 95% pure zinc-rich compound for extended corrosion resistance. ... The innovative design

2 ©2010 EVAPCO, Inc.

The ATC line of evaporative condensers reflectsEVAPCO’s commitment to product development.Their advanced design provides owners with manyoperational and performance advantages.

These induced draft, counterflow condensers are designedfor easy maintenance and long, trouble-free operation.

PVC Spray DistributionHeader with ZM II™Nozzles• Large orifice nozzles pre-

vent clogging (no moving parts)

• Nozzles are threadedinto header at properorientation

• Fixed position nozzlesrequire zero maintenance

• Guaranteed for life

Stainless Steel Strainers• Resists corrosion better than other materials

Totally Enclosed Pump Motors• Help assure long, trouble-free operation

Easy to Service Motor Mount Design• All normal maintenance can be performedquickly from outside the unit

• Designed for easy belt adjustment

• Extended lube lines for easy bearing lubrication

• If required, motor may swing to outside for easy removal

Z-725 Heavy Mill Hot-DipGalvanized Steel Construction(Stainless steel available asaffordable option)

DESIGN

AND CONSTRUCTION FEATURES

T H E A D VA N C E D T E C H N O L O G Y D E S I G N

S ince its founding in 1976, EVAP-CO, Inc. has become a world-wideleader in supplying quality cool-

ing equipment for thousands of cus-tomers in both the commercial andindustrial markets.

EVAPCO’s success has been the result of acontinual commitment to productimprovement, quality workmanship anda dedication to providing unparalleledservice.

Our emphasis on research and develop-ment has led to many product innova-tions – a hallmark of EVAPCO throughthe years.

The ongoing R & D Program enablesEVAPCO to provide the most advancedproducts in the industry – technology forthe future, available today.

EVAPCO products are manufactured onfive continents around the world anddistributed through hundreds of factoryauthorized sales representatives.

Water Saver DriftEliminators• New patented designreduces drift rate to< 0.001%

• Saves water and reduceswater treatment cost

• Greater structural integri-ty vs. old style blade-type

• Recessed into casing forgreater protection

• Drift rate certificationsEurovent OM-14-2009

Page 3: DELIVERING Q F OCUSED ON PERFECTION · During fabrication, all panel edges are coated with a 95% pure zinc-rich compound for extended corrosion resistance. ... The innovative design

3

“Clean Pan” Basin Design• Access from all four sides• Large open area simplifies

maintenance• Basin may be inspected with

pumps running• Sloped basin design prevents

sediment buildup, biologicalfilm and standing water

• Optional: full stainless steelwelded basin

Advanced Design SmoothFlow Fans• Totally Enclosed Fan Motors assures long life• Power-Band Belts for Better Lateral Rigidity• Advanced Design Aluminum Fan Blades• Non-corroding Cast Aluminum Sheaves• Heavy-Duty Fan Shaft Bearings with L-10 life

of 75000 - 135000 hrs• All Other Components Corrosion Resistant

Materials

WST Air Inlet Louvers(Water and Sight Tight)• Easily removable for access• Patented design keeps

sunlight out–preventingbiological growth

• Keeps water in while keepingdirt and debris outU.S. Patent No. 7927196

Super Low Sound Fan(optional) • Extremely wide sloped fan

blades for sound sensitiveapplications

• One piece molded heavyduty construction

• 9-15 dB(A) sound reduction

Patented Thermal-Pak® Coil DesignFeatures EVAPCO’s exclusive CROSSCOOL™EVAPCO’S Thermal-Pak® II condensing coils now featuresexclusive CROSSCOOL™ tube enhancement for greaterinternal heat transfer. This unique coil design utilizes coun-terflow heat transfer. The rows of elliptical tubes are stag-gered and angled in the direction of airflow to enhanceair turbulance, thereby increasing heat transfer while mini-mizing airside pressure drop. The design features ofEVAPCO’s Thermal-Pak® II condensing coils ensure the enduser will receive the best evaporative heat transfer effi-ciency. These characteristics and other engineeringadvancements of the Thermal-Pak® II have been proven inEVAPCO’S world-class research and development laborato-ry resulting in the following end user benefits:• Lower Operating Refrigerant Charge• Low Power Consumption• Lower Operating Weight• Small Plan AreaThe coils are manufactured from high quality internallyenhanced CROSSCOOL™ carbon steel tubing following themost stringent quality control procedures. Each circuit isinspected to assure the material quality and then testedbefore being assembled into a coil. Finally, the assembledcoil is tested in accordance with the “Pressure EquipmentDirective” (PED) 97/23/EC.To protect the coil against corrosion, it is placed in aheavy-duty steel frame and the entire assembly isdipped in molten zinc (hot dip galvanized) at a tem-perature of approximately 430°C.

Louver Access Door• Hinged access panel with

quick release mechanism• Allows easy access to per-

form routine maintenanceand inspection of the make-up assembly, strainer screenand basin

• Available on larger models

Easy Field Assembly• A new field assembly seam

design which ensures easierassembly and reduced poten-tial for field seam leaks

• Self-guided channels guidethe fan casing section intoposition improving thequality of the field seam

• Eliminates up to 66% offasteners

Low SoundOptions available

Refer to page 11

DESIG

NOPTIO

NS

APPLICATIONS

IBC

ENGINEERING

SPECIFICATIONS

SOUND

P R O V I D I N G E A S I E R S O L U T I O N S A N D B E T T E R C H O I C E S

Thermal-Pak® Coil by EVAPCO

Round Tube Coil by Others

IBC Compliant DesignRefer to page 17

Certificate of ComplianceAT, USS, UAT, UT Cooling Towers

eco-ATW/WE, ATW(B) and ESWA Closed Circuit Coolerseco-ATC, ATC-E Evaporative Condensers

Are certified to meet or exceed the Seismic and Wind Load Provisions set forth in the applicable building codes for this project.

These products have been manufactured following all applicable quality assurance programs.

Applicable Building Codes:IBC 2012ASCE-7NFPA 5000

Referenced Report:VMA-43387

Approval Agency:VMC Seismic Consulting Group

EVAPCO...Specialists in Heat Transfer Products and Services. ID IBC COC 001

Page 4: DELIVERING Q F OCUSED ON PERFECTION · During fabrication, all panel edges are coated with a 95% pure zinc-rich compound for extended corrosion resistance. ... The innovative design

4

EVAPCO, long known for using premium materials ofconstruction, has developed the ultimate system for cor-rosion protection in galvanized steel construction – theEVAPCOAT Corrosion Protection System. Marrying cor-rosion free materials with heavy gauge mill hot-dip gal-vanized steel construction to provide the longest lifeproduct with the best value.

The Evapcoat Corrosion Protection System consist of:

• Z-725 Mill Hot-Dip Galvanized Steel Construction

Mill hot-dip galvanized steel has been successfully usedfor over 25 years for the protection of evaporative con-densers against corrosion. There are various grades ofmill galvanized steel each with differing amounts ofzinc protection. EVAPCO has been a leader in theindustry in developing heavier galvanizing, and was thefirst to standardize on Z-600 mill hot-dip galvanizedsteel. Now, EVAPCO is, once again, increasing the levelof corrosion protection by being the first and only man-ufacturer in Europe to use Z-725 mill hot-dip galvanizedsteel.

Z-725 designation means there is a minimum of 725 gof zinc per m2 of surface area present on the steel.Z-725 is the heaviest level of galvanizing available formanufacturing evaporative condensers and has over 2.5times more zinc protection than competitive designsusing Z-275 steel. With Z-725 mill hot-dip galvanizedsteel construction, EVAPCO provides galvanized steelpanels with corrosion protection that approaches thelevel of the hot-dip galvanized heat exchanger coils.

During fabrication, all panel edges are coated with a95% pure zinc-rich compound for extended corrosionresistance.

• Type 304 Stainless Steel Strainers

Subjected to excessive wear and corrosion, the sump strai-ner is critical to the successful operation of the condenser.EVAPCO uses only stainless steel for this very importantcomponent.

• PVC Air Inlet Louvers

The innovative design uses corrosion free materialswhile effectively eliminating splash out and reducingthe potential for algae formation inside the condenser.

• PVC Drift Eliminators

The final elements in the upper part of the condenserare moisture eliminators which strip the entrainedwater droplets from the leaving air stream.

EVAPCO eliminators are constructed entirely of inert,corrosion-free PVC. This PVC material has been speciallytreated to resist damaging ultraviolet light. The elimina-tors are assembled in easily handled sections to facilitateremoval thereby exposing the upper portion of the unitand water distribution system for periodic inspection.

• PVC Water Distribution System, ZM II™ Spray Nozzle

The fixed position ZM II™ Spray Nozzles are mounted incorrosion-free PVC water distribution pipes. Together,these elements combine to provide unequaled coil cov-erage, scale prevention and make the industries bestperforming non-corrosive, maintenance-free water dis-tribution system.

• Totally Enclosed Motors

EVAPCO uses totally enclosed motors for all fan andpump motors as standard. These superior motors helpto assure longer equipment life without motor failures,which result in costly downtime.

• Alternate Materials of Construction

EVAPCO induced draft condensers have a modular designwhich allows for specific areas to be enhanced forincreased corrosion protection. For particularly corrosiveenvironments, EVAPCO condensers are available withStainless Steel construction for the basin, casing and/or coil.

• Stainless Steel Basin - welded execution

The basin area of a condenser is often subjected to highconcentrations of impurities and silt. In addition to theEVAPCOAT Corrosion Protection System, EVAPCO offersoptional welded stainless steel construction for superiorcorrosion resistance. This option provides Type 304 orType 316 stainless steel for the entire basin section -including the support columns and air inlet louverframes.

• Stainless Steel Coils

The heat exchanger coil is the heart of the evaporativecondenser. For this critical component, EVAPCO offersthe options of Type 304 or type 316 stainless steelconstruction.

EVAPCOAT Corrosion Protection System

ZINC

ZINC

STEELZ-725

Z-600

Z-275

OVER250%MORE

EVAPCOEUROPE

Few EuropeanManufacturers

Other EuropeanManufacturers

OVEROVER20%20%

MOREMORE

OVER20%

MORE

DES IGN FEATURES

DESIG

NE A S Y S O L U T I O N S , B E T T E R C H O I C E S !

Page 5: DELIVERING Q F OCUSED ON PERFECTION · During fabrication, all panel edges are coated with a 95% pure zinc-rich compound for extended corrosion resistance. ... The innovative design

5

Axial Fan Drive SystemDirect Drive Units – 1.2 m Wide ModelsATC 50E to ATC 165E

The T.E.F.C. motors are located on the outside of theunit and are protected by a hinged cover.

Belt Drive Units – 2.3 m and 2.4 mWide ModelsATC M170E to ATC M844E

The fan motor and drive assembly on these units aredesigned to allow easy servicing of the motor andadjustment of the belt tension from the exterior of theunit. The T.E.F.C. fan motor is mounted on the outsideof these models.

A large hinged access door with a “quick release” latchprovide access to the fan section for maintenance.

Belt Drive Units – 3 m & 3.6 m WideModelsATC XE298E to ATC XC1340E - ATC 428E to ATC 3714E

Designed as the ideal replacement condenser, thesemodels provide both cost effective and energy efficientalternatives to obsolete centrifugal fan designs. The 3 mwide plan areas are also well suited for new installationsand provide more layout flexibility. The unique beltdrive design features are detailed below.

The fan motor and drive assembly is designed to alloweasy servicing of the motor and adjustment of the belttension from the exterior of the unit. The T.E.A.O. fanmotor is located inside the fan casing on a rugged heavyduty motor base. The innovative motor base also fea-tures a unique locking mechanism for a positive adjust-ment.

The motor base isdesigned to swing outthrough a very large1.3 m2 access opening.This allows for easy ser-vicing of the motor.

Power- Band Drive Belt: The Power-Band is a solid-back,multigroove belt system that has high lateral rigidity.The belt is constructed of neoprene with polyester cords.The drive belt is designed for 150 percent of the motornameplate kW for long life and durability.

Fan Shaft Bearings: The fan shaft bearings in ATC unitsare specially selected for long, trouble-free life. Theyare rated for an L-10 life of 75.000 to 135.000 hours andare the heaviest pillow block bearings available.

Aluminum Alloy Pulleys: Fan pulleys are constructed ofcorrosion free aluminum for long life. The aluminumalso helps belts last longer.

External Motor Mount

External Motor Mount (with optional ladder)

Motor Base Assembly

Motor Access

DES IGN FEATURES

DESIG

N

E A S Y S O L U T I O N S , B E T T E R C H O I C E S !

Page 6: DELIVERING Q F OCUSED ON PERFECTION · During fabrication, all panel edges are coated with a 95% pure zinc-rich compound for extended corrosion resistance. ... The innovative design

6

Water ManagementHigh Efficient Water Saver Drift EliminatorsAn extremely efficient drift eliminator system is stan-dard on EVAPCO condensers. The patented systemremoves entrained water droplets from the air streamto limit the drift rate to less than 0.001% of the recircu-lating water rate. With a low drift rate, EVAPCO con-densers save valuable water and water treatmentchemicals. The drift eliminators are constructed of aninert polyvinyl chloride (PVC) plastic material whicheffectively eliminates corrosion of these vital compo-nents. They are assembled in sections to facilitate easyremoval for inspection of the water distribution system.

Superior WST Air Inlet Louverand Screen DesignEVAPCO’s patented WST Inlet Louvers keep water inand sunlight out of the basins of induced draftproducts. The unique non-planar design is made fromlight-weight PVC sections which easily fit together andhave no loose hardware, enabling easy basin access.

Developed with computational fluid dynamics (CFD)software, the louver’s air channels are optimized tomaintain fluid dynamic and thermodynamic efficiencyand block all line-of-sight paths into the basin elimi-nating splash-out; even when the fans are off.Additionally, algae growth is minimized by blocking allsunlight.

The combination of easy basin access, no splash-out andminimized algae growth saves the end user money onmaintenance hours, water consumption and watertreatment costs.

“Clean Pan” Basin DesignEVAPCO condensers features a completely sloped basinfrom the upper to lower pan section. This “Clean Pan”design allows the water to be completely drained fromthe basin. The water will drain from the upper sectionto the depressed lower basin section where the dirt anddebris can be easily flushed out through the drain. Thisdesign helps prevent buildup of sedimentary deposits,biological films and minimizes standing water.

ZM II™ Spray NozzleWater DistributionSystemEven and constant water distri-bution is paramount for reli-able, scale-free evaporativecooling. EVAPCO’s ZeroMaintenance ZM II™ SprayNozze, mounted in a PVC distri-bution pipe remains clog-freeunder the toughest conditionsto deliver approximately 4 l/s toevery square meter of coil planarea.

The heavy-duty nylon ZM II™Spray nozzles have a 33 mmdiameter opening and a 38 mmsplash plate clearance, enablingEVAPCO to use 75% fewernozzles.

Inlet Louver Material

Sloped Basin

DES IGN FEATURES

DESIG

N

ZM II™ Nozzle

E A S Y S O L U T I O N S , B E T T E R C H O I C E S !

Page 7: DELIVERING Q F OCUSED ON PERFECTION · During fabrication, all panel edges are coated with a 95% pure zinc-rich compound for extended corrosion resistance. ... The innovative design

7

Two Speed MotorsTwo speed fan motors can provide an excellentmeans of capacity control. In periods of lightenedloads or reduced wet bulb temperatures, the fanscan operate at low speed, which will provide about60% of full speed capacity, yet consume only about15% of the power compared with high speed. Inaddition to the energy savings, the sound levels ofthe units will be greatly reduced at low speed.

Inverter Duty MotorsInverter Duty motors are available for condenserapplications which utilize variable frequency drivesystems for capacity control. Inverter Duty motorsoffer totally enclosed premium efficiency construc-tion which is designed for variable frequency driveapplications.

Note: Other special motor configurations are avail-able to meet specific proper requirements. Contactyour local EVAPCO sales representative for applica-tion assistance and motor availability.

Remote Sump ConfigurationFor units operating in areas where temperaturesmay be very low,or where lowtemperatures mayoccur duringperiods when theunit is not opera-ting, a sump loca-ted inside thebuilding is thepreferred meansof ensuring thatthe basin waterwill not freeze.For these applica-tions, the conden-ser will be supplied without the spray pump,suction strainers and all associated piping, but withan oversize bottom outlet.

Dual Fan OptionEvapco now offers a Dual Fan arrangement on10x18, 12x18 and 12x20 nominal box sizes.

The Dual Fanoption gives usersredundancy inlarge box sizes byproviding indepen-dant motors, fans,and drives thatpreviously onlyhad a single fanand motor.

Basin Heater PackageIf a remote sump configurationis not practical, electric basinheater packages are availableto help prevent freeze-up ofthe basin water. The packagesinclude electric heater ele-ments and a combination withthermostat and low water cut-off. (Consult EVAPCO forheater size and application)

Electric Water Level ControlEvaporative condensersmay be ordered with anelectric water level controlin lieu of the standardmechanical float andmake-up assembly.This package providesaccurate control of waterlevels and does notrequire field adjustment.

Multiple Circuit CoilsCondensers may be supplied with multiple circuit coils tomatch various system requirements such as split systems.

Self Supporting Service PlatformsCondensers are available with self-supporting serviceplatforms that include access ladders which are designed foreasy field installation. This option offers significant savingsin comparison to field constructed, externally supportedcatwalks. The EVAPCO service platform option will beinstalled in front of the fan access doors.

Motor DavitIn the event that a fan and/or fan motor should need to bereplaced, a motor davit is available from which a chain fallcan be mounted to easily lower the motor/fan to theground.

ATC Condenser with Optional Service Platform and Motor Davit

OPT IONAL EQUIPMENT

Remote sumpby others

Optionalremote sumpconnection(s)by EVAPCO

OPTIO

NS

E A S Y S O L U T I O N S , B E T T E R C H O I C E S !

Page 8: DELIVERING Q F OCUSED ON PERFECTION · During fabrication, all panel edges are coated with a 95% pure zinc-rich compound for extended corrosion resistance. ... The innovative design

8

DesignEvapco units are of heavy-duty construction and designed forlong trouble-free operation. Proper equipment selection,installation and maintenance is, however, necessary toensure full unit performance. Some of the major considera-tions in the application of a cooler are presented below. Foradditional information, please contact the factory.

Air CirculationIt is important that proper air circulation be provided. Thebest location is on an unobstructed roof top or on groundlevel away from walls and other barriers. Those condenserslocated in wells, enclosures or adjacent to high walls mustbe properly located to avoid the problems associated withrecirculation.Recirculation raises the wet bulb temperature of the ente-ring air causing the water temperature to rise above thedesign. For these cases, the discharge of the fan should belocated at a height even with the adjacent wall, therebyreducing the chance of recirculation. For additional infor-mation, see the Evapco Equipment Layout Manual.Good engineering practice dictates that the condenserdischarge air not be directed or located close to or in thevicinity of building air intakes.

Recirculating Water SystemThe surest way to protect the recirculating water systemfrom freezing is with a remote sump. The remote sumpshould be located inside the building and below the unit.When a remote sump arrangement is selected, the spraypump is provided by others and installed at the remotesump. All water in the condenser basin should drain to theremote sump when the spray pump cycles off.Other freeze protection methods are available when aremote sump is not feasible. Electric pan heaters can be usedto keep the pan water from freezing when the unit cyclesoff. Water lines to and from the unit, spray pump and relat-ed piping should be heat traced and insulated up to theoverflow level in order to protect from freezing.The unit should not be operated dry (fans on, pump off)unless the basin is completely drained and the unit has beendesigned for dry operation. Consult the factory when dryoperation is a requirement.

Maintaining the Recirculated WaterSystemThe heat rejection in a condenser is accomplished by theevaporation of a portion of the recirculated spray water. Asthis water evaporates, it leaves behind all of its mineral con-tent and impurities. Therefore, it is important to bleed-off anamount of water equal to that which is evaporated to pre-vent the build-up of these impurities. If this is not done, themineral or the acidic nature of the water will continue toincrease. This will ultimately result in heavy scaling or a cor-rosive condition.

Bleed-offEach unit supplied with a pump mounted on the side is fur-nished with a clear bleed line for visual inspection and a valvewhich, when fully open, will bleed-off the proper amount ofwater. If the make-up water supplying to the unit is relativelyfree of impurities, it may be possible to cut back the bleed,but the unit must be checked frequently to make sure scale isnot forming. Make-up water pressure should be maintainedbetween 140 and 340 kPa.

Water TreatmentIn some cases the make-up water will be so high in mineralcontent that a normal bleed-off will not prevent scaling. Inthis case, water treatment will be required and a reputablewater treatment company familiar with the local water con-ditions should be consulted.Units constructed of galvanized steel operating withcirculating water having a pH of 8,3 or higher will requireperiodic passivation of the galvanized steel to prevent theformation of “white rust”.Any chemical water treatment used must be compatible withthe galvanized construction of the unit. If acid is used fortreatment, it should be accurately metered and the concen-tration properly controlled. The pH of the water should bemaintained between 7 and 8,8. Batch chemical feeding is notrecommended because it does not afford the proper degreeof control. If acid cleaning is required, extreme caution mustbe exercised and only inhibited acids recommended for usewith galvanized construction should be used.

Control of Biological ContaminationWater quality should be checked regularly for biological con-tamination. If biological contamination is detected, a moreaggressive water treatment and mechanical cleaning pro-gram is required. The water treatment program should beperformed in accordance with local legislation and in con-junction with a qualified water treatment company.It is important that all internal surfaces be kept clean ofaccumulated dirt or sludge. In addition, the drift eliminatorsshould be kept in good operating condition to minimizewater from exiting the condenser unit in the discharge air.To minimize the risk of biological contamination, at initialstart up or after an extended shut down, it is recommendedthat the condenser be properly treated. Clean all debris suchas leaves and dirt from the unit. Completely fill the basin tothe overflow level with fresh water. Initiate a biocide watertreatment or shock treatment program prior to operatingthe unit. It is preferable that all such procedures be conduct-ed or supervised by a water treatment specialist.

APPL ICAT ION

APPLICATIONS

E A S Y S O L U T I O N S , B E T T E R C H O I C E S !

Page 9: DELIVERING Q F OCUSED ON PERFECTION · During fabrication, all panel edges are coated with a 95% pure zinc-rich compound for extended corrosion resistance. ... The innovative design

9

PipingEvaporative condensers are used in refrigeration systemsas an efficient means of heat rejection. Their installationand specifically the installation of the piping to and fromthe evaporative condenser has a direct effect on theiroperation and the overall energy efficiency of the refrig-eration system. In this manual, we will explore the princi-ples of piping evaporative condensers, beginning withsingle condensers and exploring multiple condenserinstallations as well as thermosiphon and sub-cooling pip-ing systems.

BackgroundEvaporative condensers came into common use for nearly allrefrigeration systems because of their operating advantagesover the combination of cooling towers and condensers.They, of course, have also replaced the old "once through"water cooled condensing systems which are obsolete todaybecause of the restrictions on the unlimited use of watercoupled with its high cost.Although, shell and tube condensing systems performed thesame job of condensing the hot discharge gas into a saturat-ed liquid as evaporative condensers; a small difference in theoperating characteristics, namely pressure drop, requiressome modification in the refrigerant piping hookup to andfrom the evaporative condenser. These changes are particu-larly important when dealing with multiple unit installations.In order to understand why the piping hookup is important,let's first take a brief look at the basic design differences ofthe two types of condensers to see why there is a differencein the pressure drop characteristics.

The shell type refrigerant condensers allow the refrigerant toflow around and condense on the outside of the watertubes. (See Figure 1) The refrigerant flow is almost entirelyunimpeded resulting in a very low or nearly zero pressuredrop through the condenser.

APPL ICAT ION

Technical Support Services

EVAPCO’s evapselect™ Equipment Selection ProgramEvapSelect™ is a web based computer selection program which allowsthe design engineer to choose EVAPCO models and optimize unit selec-tions. The program allows the engineer to evaluate the equipment’s ther-mal performance, space, energy requirements and water consumption.Once the model is selected and optional equipment features are inserted,the engineer may output a complete specification AND a unit drawingfrom this program.The software is designed to provide the user with maximum flexibility inanalyzing the various selection parameters while in a friendly and familiarWindows format.The EvapSelect™ software is available to all consulting engineeringoffices and design-build contractors. The programs are distributedthrough the local EVAPCO sales representative or the EVAPCO offices.

EVAPCO’s WebsiteLog on to EVAPCO’s new and improved website http://www.evapco.eufor expanded product information. Product literature, Rigging andMaintenance Instructions are all accessible online from your computer.The EvapSelect™ Equipment Selection Software program may beaccessed using Microsoft Internet Explorer after contacting your localEVAPCO sales representative.Users may make Requests for Quotation through the website or by e-mailing EVAPCO at this address: [email protected]

With the EvapSelect™ program, equipment selections, writtenspecifications, unit drawing files and EVAPCO on-line informationare readily available from the comfort of your own office!

APPLICATIONS

E A S Y S O L U T I O N S , B E T T E R C H O I C E S !

Contrasting, most evaporative condensers (See Figure 2) uti-lize some type of serpentine coil design where the hot refrig-erant gas enters the top of the coil traveling back and forththrough several rows as it is cooled and changed from a hotsuperheated gas to a saturated liquid. This longer travel pathgenerally produces a small pressure drop which, thoughinsignificant to the overall operation of the refrigeration sys-tem, does require proper attention be given to the con-denser piping. Most of this attention needs to be focused onthe liquid drain line from the outlet of the evaporative con-denser to the high pressure receiver. The reason for this isdescribed in the “Piping Brochure”.

Piping BrochureFor additional information refer to EVAPCO Bulletin 131-E“Piping Evaporative Condensers” or consult your nearestRepresentative.

LIQUID

DISCHARGE GAS

WATER OUT

WATER IN

TYPICAL SHELL AND TUBE WATER COOLED CONDENSER

Figure 1

Figure 2

LIQUID

DISCHARGE GAS

TYPICAL EVAPORATIVE CONDENSER COIL

Page 10: DELIVERING Q F OCUSED ON PERFECTION · During fabrication, all panel edges are coated with a 95% pure zinc-rich compound for extended corrosion resistance. ... The innovative design

10

Notes:

E A S Y S O L U T I O N S , B E T T E R C H O I C E S !

Page 11: DELIVERING Q F OCUSED ON PERFECTION · During fabrication, all panel edges are coated with a 95% pure zinc-rich compound for extended corrosion resistance. ... The innovative design

11

Ultra QuietEvaporativeCondensers

Ultra Quiet operationfor induced draft

counterflowEvaporative Condensers

SOUND

The ATC Evaporative

Condenser is now

available with three (3)

equipment options to

reduce the overall

sound generated

from the side

or top of the

ATC-E

Evaporative

Condenser.

Each option pro-

vides various levels of

sound reduction and

can be used in combination to

provide the lowest sound level.

E A S Y S O L U T I O N S , B E T T E R C H O I C E S !

Page 12: DELIVERING Q F OCUSED ON PERFECTION · During fabrication, all panel edges are coated with a 95% pure zinc-rich compound for extended corrosion resistance. ... The innovative design

12

ADVANCED TECHNOLOGYLOW SOUND SOLUT IONS

Super Low Sound Solution for Sound Sensitive Applications

The Super Low Sound FanReduced Sound Levels versus Model ATC-E Standard FanEVAPCO's Super Low Sound Fan on the ATC-E Evaporative Condensers utilizes an extremely wide chordblade design applied for sound sensitive applications where the lowest sound levels are desired. The fanis one piece molded heavy duty FRP construction utilizing a forward swept blade design. The Super LowSound Fan reduces sound levels 9 to 15 dB(A) compared to the Model ATC-E standard fan.

Narrow Band Spectrum Analysis

Frequency (Hz)

Sou

nd

Pre

ssu

re L

evel

(d

B)

Standard Axial Fan

Super Low Sound Fan

Blade Passing Frequencies Blade Passing Frequencies Blade Passing Frequencies Improved Sound Quality versus Model ATC-E Standard Fan

The SUPER Low Sound Fan on the ATC-E Condenserreduces sound levels 9-15 dB(A) and eliminates audibleblade passing frequencies indicative of straight bladedaxial type fans.

Refer to the Narrow Band Spectrum graph which showshow straight bladed axial fans produce blade passingfrequencies – the same phenomena that produce thesignature pulsating helicopter noise.

The blade passing frequencies are audible spikes insound pressure levels, but are not apparent in theoctave band sound spectrum.

Family of Super Low Sound Fans

The Super Low Sound Fan on the ATC-E Evaporative Condensers reduces sound levels and betters the sound quality!

NOTE: These low sound options may impact the overall installed dimensions of the ATC-EEvaporative Condenser selected.

SOUND

E A S Y S O L U T I O N S , B E T T E R C H O I C E S !

Page 13: DELIVERING Q F OCUSED ON PERFECTION · During fabrication, all panel edges are coated with a 95% pure zinc-rich compound for extended corrosion resistance. ... The innovative design

13

Additional Solutions for Sound Sensitive Applications

Low Sound Fan 4 – 7 dB(A) Reduction!

The Low Sound Fan offered by EVAPCO is a wide chordblade design for sound sensitive applications where lowsound levels are desired. The Low Sound Fan shall uti-lize a unique soft-connect blade-to-hub design that iscompatible with Variable Speed Drives.

The Low Sound Fan is capable of reducing the unitsound pressure levels 4 dB(A) to 7 dB(A), dependingupon specific unit selection and measurement location.The fans are high efficiency axial propeller type and areavailable on 2.4 m wide and larger ATC EvaporativeCondensers.

Water SilencerReduces Water Noise in the Cold Water Basin up to 7dB(A)!The water silencer option is available for all induceddraft models and is located in the falling water area ofthe cold water basin. The water silencer will reduce thehigh frequency noise associated with the falling waterand is capable of reducing overall sound levels 4 dB(A)to 7 dB(A) measured at 1.5 m from the side or end ofthe unit. The water silencers reduce overall sound levels9 dB(A) to 12 dB(A) (depending on water loading andlouver height) measured 1.5 m from the side or end ofthe unit when water is circulated with fans off.

The water silencers are constructed of lightweight PVCsections and can be easily removed for access to thebasin area. The water silencer will have no impact onunit thermal performance.

The Water Silencer is available on ALL ATC EvaporativeCondensers.

Consult EVAPCO’s EvapSelect™ selection software for unit sound levels. If a detailed analysis or fulloctave band data sheet is required for your application, please consult your EVAPCO SalesRepresentative.

ADVANCED TECHNOLOGYLOW SOUND SOLUT IONS

SOUND

E A S Y S O L U T I O N S , B E T T E R C H O I C E S !

Page 14: DELIVERING Q F OCUSED ON PERFECTION · During fabrication, all panel edges are coated with a 95% pure zinc-rich compound for extended corrosion resistance. ... The innovative design

14

SOUND BAS IC

SoundSound is the alteration in pressure, stress, particle displace-ment and particle velocity, which is propagated in an elasticmaterial. Audible sound is the sensation produced at the earby very small pressure fluctuations in the air.

Sound PressureSound pressure is the intensity of sound. Sound pressure, Lp

in decibels is the ratio of measured pressure, P in the air to areference sound pressure, PO = 2x10–5 Pascal following thefollowing formula:

Lp (dB) = 10 log10 ( P2/ PO2)

The most important point to understand about sound pressure level is that sound pressure level is what is actually being measured when sound data is recorded.Microphones that measure sound are pressure sensitivedevices that are calibrated to convert the sound pressurewaves into decibels.

Sound PowerSound Power is the energy of sound. Sound power, Lw indecibels is the ratio of the calculated sound power, W to a reference power, Wo =1 picowatt, according to the following formula:

Lw (dB) = 10 log10 (W/Wo)

The most important point to remember about sound power level is that sound power level is not a measuredvalue, but is calculated based on the measured sound pres-sure.

Adding Multiple Sound SourcesSince the decibel is a logarithmic function, the numbers arenot added linearly. Therefore, two 73 dB sound sourcesadded together do not equal 146 dB. The resultant soundwould actually be 76 dB. The following table shows how toadd decibels from two sound sources.

Difference in Add to the higherdB Level dB Level

0 to 1 32 to 3 24 to 8 1

9 or greater 0

62 lx

250 lx

30 m 30 m7.5 m 0 7.5 m15 m 15 m

1000 lx

“SOUND PRESSURE”

76 dB(A)

73 dB(A) 73 dB(A)

7676 d dB(B((A)A)

7373 d d dBB(B((AA)A)A) 737337 d d dB(B(B(A)A)

100W

“SOUND POWER”

Similar to the intensity coming from a light bulbwhich gets dimmer as one gets further and furtheraway, sound pressure decreases in decibels as yourear gets further from the sound source.

Background in Sound Basics

Similar to the wattage of a light bulb that doesnot change the farther one is away from the lightbulb, sound power does not vary with distance.

SOUND

E A S Y S O L U T I O N S , B E T T E R C H O I C E S !

Page 15: DELIVERING Q F OCUSED ON PERFECTION · During fabrication, all panel edges are coated with a 95% pure zinc-rich compound for extended corrosion resistance. ... The innovative design

15

SOUND BAS IC

Sound Science and Condensers

dB(A) Formula and Conversions:

f=8000

dB(A) =10 log10 10 ((dB+Cf) /10)

f=63

Typical Sound Pressure Levels of Well Known Noises:

Jet Airplane, 45 meters away 140 dB(A)Painful 130 dB(A)Very Uncomfortable 120 dB(A)Circular Saw 110 dB(A)Nightclub 100 dB(A)Semi Truck 90 dB(A)Sidewalk of a Busy Road 80 dB(A)Household Vacuum, 1 meter away 70 dB(A)Normal Conversation 60 dB(A)Inside Average Home 50 dB(A)Quiet Library 40 dB(A)Bedroom at Night 30 dB(A)

High Frequency Self Attenuating

Low-Mid Frequencies Travel through and around Obstructions

Low-

Trav

araroa u

HH

SSe

Fan Noise

WaterNoise

Sound Frequency

Fan Noise• Low / Mid frequencies that travel long distances,

through walls, and around obstructions.

• Very difficult to attenuate. Reduce fan noise byusing Low Sound Fans.

• Dominates what is measured and heard at theCondenser and at the sound sensitive location.

Water Noise• High frequencies that attenuate naturally with

distance. Attenuated easily by walls, trees or other obstructions.

• Totally masked and drowned out by fan noise at ashort distance away from the Condenser.

Notable Facts about Sound:

• +/- 1 dB(A) is inaudible to the human ear • Decreasing a noise source by 10 dB(A) sounds

half as loud to the human ear

Sound Pressure – The A-Weighted ScaleThe A-weighted scale, dB(A) is a means to translate what a sound meter microphone

measures to how the human ear perceives the sound.

where: Cf = correction factor per banddB = measured sound pressure

let: Zf = (dB + Cf)/10

Band Center Frequency Sample Cf ZfFreq. (Hz) Range (Hz) Data (dB) (dB)

1 63 44-88 68 -26.2 4.18

2 125 89-175 76 -16.1 5.99

3 250 176-350 77 -8.6 6.84

4 500 351-700 73 -3.2 6.98

5 1000 701-1400 70 0 7.00

6 2000 1401-2800 68 +1.2 6.92

7 4000 2801-5600 71 +1.0 7.20

8 8000 5601-11200 73 -1.1 7.19

Example calculation of the dB(A) formula using the Sample Data above.

dB(A) = 10 log10 10(Z1) + 10(Z2) + 10(Z3) + 10(Z4) + 10(Z5) + 10(Z6) + 10(Z7) + 10(Z8)

= 10 log10 (67114245.2) = 78.3 dB(A)

SOUND

E A S Y S O L U T I O N S , B E T T E R C H O I C E S !

Page 16: DELIVERING Q F OCUSED ON PERFECTION · During fabrication, all panel edges are coated with a 95% pure zinc-rich compound for extended corrosion resistance. ... The innovative design

16

SPEC I FY ING SOUND

SoundVerifications

Specify sound pressure in dB(A) measured 1,5 m above the fan discharge during full speed operation.• All manufacturers can meet a performance specification with Low Sound Options• Fan noise is what matters. 1,5 m above the fan is where it matters.

Measurement LocationPer Cooling Technology Institute Standard ATC-128

Sound Microphone location 1,5 m above the evaporative condenserfan cowl edge at a 45° angle.

This position assures accurate sound measurements by eliminatinga source of uncertainty by taking the microphone out of thehigh velocity fan discharge air.

Easy VerificationAt 1,5 m from the Evaporative Condenser, a sound meter records only condenser noise. Interested parties can easilyverify the actual noise coming from the condenser against the specified sound data with good certainty.

If sound were specified at 15 meters or some greater distance fromthe sound sensitive location, there is increased uncertainty in themeasured data due to other possible sound sources within the 15meters radius of the sound microphone.

Sound QualitySound coming from the top of the condenser is comprised of low-and mid-frequency fan noise. Low- and mid-frequency fan “rumble”is very difficult to attenuate. Fan rumble travels through everythingand around everything and what is audible at any sound sensitivelocation.

Sound coming from the sides of the condenser is comprised of highfrequency water noise, is much less objectionable than fan noise andattenuates naturally with distance.

Acoustical Shadow*“Subjective reactions to the overall noise generated byCondensers indicate that as one walks away from a towerintake, a point is reached where the water noise is masked bythe fan noise. The point coincides with the point at which oneemerges from the acoustical shadow of the condenser structure,which shields intake water noise from discharge fan noise.” *Seelbach & Oran, “What To Do About Cooling Tower Noise”, Industrial Acoustics Company.

Sound measured at the side of an Evaporative Condenser isinside the acoustical shadow of the noise emitted from the top.Outside the acoustical shadow, the low- and mid-frequency fannoise completely masks the high frequency water noise.

High Frequency Self Attenuating

Low-Mid Frequencies Travel through and around Obstructions

Acoustical Shadow

Fan Noise

WaterNoise

Microphone

NewCoolingTower

RooftopAir

Handler

ExistingCoolingTower

RoadTraffic

50 Feet

50 Feet

15 meters

50 Feet

50 Feet

15 meters50

Feet

50 Fe

et

15 m

eter

s

50 Fe

et

50 Fe

et

15 m

eter

s

Specify fan noise because it matters! Specify fan noise where it matters!

45°

Microphone Location

1,5 m

SOUND

E A S Y S O L U T I O N S , B E T T E R C H O I C E S !

Page 17: DELIVERING Q F OCUSED ON PERFECTION · During fabrication, all panel edges are coated with a 95% pure zinc-rich compound for extended corrosion resistance. ... The innovative design

17

IBC

E A S Y S O L U T I O N S , B E T T E R C H O I C E S !

EVAPCO Evaporative Condensers…designed to withstand seismic

or wind load forces.

The International Building Code (IBC)

is a comprehensive set of regulations

addressing the structural design and

installation requirements for building

systems – including HVAC and

industrial refrigeration equipment.

With the advent of the IBC,

EVAPCO is proud to introduce the

new and improved line of ATC-E

Evaporative Condensers with IBC 2012

compliance standard.

Wind, Rain, Earthquake and

Hurricane

We Stand Tall Through it All!

Page 18: DELIVERING Q F OCUSED ON PERFECTION · During fabrication, all panel edges are coated with a 95% pure zinc-rich compound for extended corrosion resistance. ... The innovative design

18

What is IBC?

International Building CodeThe International Building Code (IBC) is a comprehensiveset of regulations addressing both the structural design andthe installation requirements for building systems – includ-ing HVAC and industrial refrigeration equipment. Compared to previous building codes that considered onlythe building structure and component anchorage, therequirements contained within the IBC address anchorage,structural integrity, and the operational capability of acomponent following either a seismic or wind load event.Simply stated, the IBC code provisions require that evapo-rative cooling equipment, and all other components per-manently installed on a structure, must be designed tomeet the same seismic or wind load forces as the buildingto which they are attached.

How Does IBC 2012 Apply to EvaporativeCondensers?Based on site design factors, calculations are made todetermine the equivalent seismic “g force” and wind load(kilo-Newton per square meter, kN/m2) on the unit. Theevaporative condenser must be designed to withstand thegreater of either the seismic or wind load.

All locations with design criteria resulting in a seismicdesign force of up to 1.0g or a wind load of 6,94 kN/m2 orbelow will be provided with the standard ATC-E structuraldesign. An upgraded structural design is available forinstallations with design criteria resulting in “g forces”greater than 1.0g. The highest “g force” location in NorthAmerica is 5.12g. The highest wind load shown on themaps is 273 km/h, which is approximately equal to 6,94kN/m2 velocity pressure. Therefore, the upgraded structuraldesign package option for the New ATC-E is designed for5.12 g and 6,94 kN/m2 making it applicable to ALL buildinglocations in North America.

Design ImplementationEVAPCO applies the seismic design and wind load informa-tion provided for the project to determine the equipmentdesign necessary to meet IBC requirements. This processensures that the mechanical equipment and its componentsare compliant per the provisions of the IBC as given in theplans and specifications for the project.

Independent CertificationAlthough the IBC references and is based on the structuralbuilding code ASCE 7, many chapters and paragraphs ofASCE 7 are superceded by the IBC, independent certifica-tion and methods of analysis are such paragraphs. Per themost recent edition of the code, the EVAPCO complianceprocess included an exhaustive analysis by an independentapproval agency. As required by the International BuildingCode, EVAPCO supplies a certificate of compliance as partof its submittal documents. The certificate of compliancedemonstrates that the equipment has been independentlytested and analyzed in accordance with the IBC seismic andwind load requirements. Evapco has worked closely withthe independent approval agency, The VMC Group, to com-plete the independent equipment testing and analysis.

If the seismic “g force” or wind load psf requirements forthe project site are known, EVAPCO’s online equipmentselection software, EvapSelect™, will allow you to choose therequired structural design package – either standard con-struction or upgraded construction.

For further questions regarding IBC compliance, please con-tact your local EVAPCO Representative.

In its continuing commitment to be the leaders in evaporative cooling equipmentdesign and services, EVAPCO ATC-E Evaporative Condensers are now Independently

Certified to withstand Seismic and Wind Loads in accordance with IBC 2012.

IBC COMPL IANCE

The New ATC-E is offered with a choice of TWO structuraldesign packages:

• Standard Structural Design – For projects with ≤1.0g seismic or 6,94 kN/m2 wind loads

• Upgraded Structural Design – Required for projects with>1.0 g seismic or 6,94 kN/m2 wind loads

IBC

E A S Y S O L U T I O N S , B E T T E R C H O I C E S !

Certificate of ComplianceAT, USS, UAT, UT Cooling Towers

eco-ATW/WE, ATW(B) and ESWA Closed Circuit Coolerseco-ATC, ATC-E Evaporative Condensers

Are certified to meet or exceed the Seismic and Wind Load Provisions set forth in the applicable building codes for this project.

These products have been manufactured following all applicable quality assurance programs.

Applicable Building Codes:IBC 2012ASCE-7NFPA 5000

Referenced Report:VMA-43387

Approval Agency:VMC Seismic Consulting Group

EVAPCO...Specialists in Heat Transfer Products and Services. ID IBC COC 001

Page 19: DELIVERING Q F OCUSED ON PERFECTION · During fabrication, all panel edges are coated with a 95% pure zinc-rich compound for extended corrosion resistance. ... The innovative design

19

EngineeringData

& Dimensions

ENGINEERING

E A S Y S O L U T I O N S , B E T T E R C H O I C E S !

Page 20: DELIVERING Q F OCUSED ON PERFECTION · During fabrication, all panel edges are coated with a 95% pure zinc-rich compound for extended corrosion resistance. ... The innovative design

20

ENGINEERING

100 BFW

100 BFW

M

25 MPT MAKE-UP

50 FPT OVERFLOW

50 MPT DRAIN

H

32 1231

ACCESSDOOR

M

255

A

130

E

U

L

ACCESSDOOR

ACCESSDOOR

MM

265 L

† Heaviest section is the coil / fan section†† When a remote sump arrangement is selected, the spray pump, suction strainer and associated piping are omitted; the unit is provided with an oversized outlet to facilitatedrainage to the remote sump

* Liters shown is water in suspension in unit and piping. Allow for additional water in bottom of remote sump to cover pump suction and strainer during operation. (300mm would normally be sufficient).

** Refrigerant charge is shown for R-717. Multiply by 1.93 for R22, 1.98 for R134A and 1.7 for R404A, R410A and R507A.Δ Unit dimensions and coil connections may vary slightly from catalog. See factory certified prints for dimensions, quantity of coil connections, and piping configuration.

Coil connections are 4” bevel for weld (BFW).

MODELS: 50E TO 165E

Fans Weights (kg) Refrigerant Remote Sump†† DimensionsΔ (mm)ATC-E Operating Coil SprayModel Heaviest Charge** Volume Pump Liters Conn. Operating Height Upper Lower Coil Length

No. kW m3/s Shipping Operating Section† (kg) (l) kW Req’d* Size(mm) Weight H U E A L

50E 2,2 5,6 1260 1795 1030 23 198 0,55 455 150 1590 2778 1822 956 495 1822

65E 4 5,9 1435 1980 1200 30 255 0,55 455 150 1775 2969 2013 956 686 1822

80E 4 5,7 1620 2180 1390 37 313 0,55 455 150 1975 3159 2203 956 876 1822

90E (2) 2,2 10,0 1865 2640 1560 34 288 0,75 680 150 2360 2778 1822 956 495 2737

105E (2) 2,2 9,3 2115 2910 1810 44 376 0,75 680 150 2615 2969 2013 956 686 2737

120E (2) 2,2 9,0 2380 3200 2075 54 463 0,75 680 150 2915 3159 2203 956 876 2737

135E (2) 2,2 11,9 2580 3630 2210 58 496 1,1 870 200 3275 2969 2013 956 686 3651

150E (2) 2,2 11,2 2945 4020 2570 72 613 1,1 870 200 3665 3159 2203 956 876 3651

165E (2) 4 12,2 2955 4030 2580 72 613 1,1 870 200 3675 3159 2203 956 876 3651

ATC 50E to 80E ATC 90E to 165E

ENGINEERING DATA & DIMENSIONS

Page 21: DELIVERING Q F OCUSED ON PERFECTION · During fabrication, all panel edges are coated with a 95% pure zinc-rich compound for extended corrosion resistance. ... The innovative design

21

ENGINEERING

ENGINEERING DATA & DIMENSIONS

228350 M.P.T. DRAIN

50 M.P.T. MAKE-UP

75 M.P.T. OVERFLOW

H

U

E130

(2)100 BFW(2)100 BFW A

498

L

ACCESSDOOR

376

L

ACCESSDOOR

485238850 M.P.T. DRAIN

50 M.P.T. MAKE-UP

75 M.P.T. OVERFLOW

H

U

E130

(2)100 BFW(2)100 BFW A

498

The motors are shipped loose for field mounting.† Heaviest section is the coil / fan section†† When a remote sump arrangement is selected, the spray pump, suction strainer and associated piping are omitted; the unit is provided with an oversized outlet to facilitatedrainage to the remote sump

* Liters shown is water in suspension in unit and piping. Allow for additional water in bottom of remote sump to cover pump suction and strainer during operation. (300mm would normally be sufficient).

** Refrigerant charge is shown for R-717. Multiply by 1.93 for R22, 1.98 for R134A and 1.7 for R404A, R410A and R507A.Δ Unit dimensions and coil connections may vary slightly from catalog. See factory certified prints for dimensions, quantity of coil connections, and piping configuration.

Coil connections are 4” bevel for weld (BFW).

MODELS: M170E TO M331E

Fans Weights (kg) Refrigerant Remote Sump†† DimensionsΔ (mm)ATC-E Operating Coil SprayModel Heaviest Charge** Volume Pump Liters Conn. Operating Height Upper Lower Coil Length

No. kW m3/s Shipping Operating Section† (kg) (l) kW Req’d* Size(mm) Weight H U E A L

M170E 4 14,0 3505 4675 2915 83 707 1,5 835 200 4180 3423 2197 1226 686 2578

M187E 5,5 16,0 3530 4700 2940 83 707 1,5 835 200 4200 3423 2197 1226 686 2578

M199E 7,5 17,6 3535 4705 2945 83 707 1,5 835 200 4205 3423 2197 1226 686 2578

M188E 4 13,6 3980 5185 3390 103 872 1,5 835 200 4685 3613 2388 1226 876 2578

M221E 7,5 17,0 4005 5210 3415 103 872 1,5 835 200 4715 3613 2388 1226 876 2578

M238E 11 19,1 4065 5270 3475 103 872 1,5 835 200 4770 3613 2388 1226 876 2578

M195E 4 13,2 4445 5690 3855 122 1038 1,5 835 200 5190 3804 2578 1226 1067 2578

M247E 11 18,5 4530 5775 3940 122 1038 1,5 835 200 5275 3804 2578 1226 1067 2578

M203E 5,5 17,2 3975 5255 3340 88 751 1,5 910 200 4695 3629 2311 1318 686 2731

M225E 5,5 16,7 4505 5825 3870 109 926 1,5 910 200 5265 3820 2502 1318 876 2731

M233E 5,5 16,1 5025 6380 4390 130 1102 1,5 910 200 5825 4010 2692 1318 1067 2731

M252E 7,5 21,0 4585 6095 3860 102 871 2,2 1060 250 5440 3629 2311 1318 686 3188

M274E 11 23,6 4640 6150 3915 102 871 2,2 1060 250 5495 3629 2311 1318 686 3188

M278E 7,5 20,3 5205 6765 4480 127 1076 2,2 1060 250 6105 3820 2502 1318 876 3188

M303E 11 22,9 5260 6815 4535 127 1076 2,2 1060 250 6160 3820 2502 1318 876 3188

M320E 15 24,9 5290 6845 4565 127 1076 2,2 1060 250 6185 3820 2502 1318 876 3188

M331E 15 24,1 5895 7500 5170 151 1282 2,2 1060 250 6840 4010 2692 1318 1067 3188

ATC M203E to M331E

ATC M170E to M247E

Page 22: DELIVERING Q F OCUSED ON PERFECTION · During fabrication, all panel edges are coated with a 95% pure zinc-rich compound for extended corrosion resistance. ... The innovative design

22

ENGINEERING DATA & DIMENSIONS

L

ACCESSDOOR

4852388

50 M.P.T. DRAIN

50 M.P.T. MAKE-UP

75 M.P.T. OVERFLOW

H

U

E130

(2)100 BFW(2)100 BFW A

498

The motors are shipped loose for field mounting.† Heaviest section is the coil / fan section†† When a remote sump arrangement is selected, the spray pump, suction strainer and associated piping are omitted; the unit is provided with an oversized outlet to facilitatedrainage to the remote sump

* Liters shown is water in suspension in unit and piping. Allow for additional water in bottom of remote sump to cover pump suction and strainer during operation. (300mm would normally be sufficient).

** Refrigerant charge is shown for R-717. Multiply by 1.93 for R22, 1.98 for R134A and 1.7 for R404A, R410A and R507A.Δ Unit dimensions and coil connections may vary slightly from catalog. See factory certified prints for dimensions, quantity of coil connections, and piping configuration.

Coil connections are 4” bevel for weld (BFW).

L

ACCESSDOOR

485

ACCESSDOOR

238850 M.P.T. DRAIN

50 M.P.T. MAKE-UP

75 M.P.T. OVERFLOW

H

U

E130

(2)100 BFW(2)100 BFW A

498

MODELS: M301E TO M591E

ENGINEERING

Fans Weights (kg) Refrigerant Remote Sump†† DimensionsΔ (mm)ATC-E Operating Coil SprayModel Heaviest Charge** Volume Pump Liters Conn. Operating Height Upper Lower Coil Length

No. kW m3/s Shipping Operating Section† (kg) (l) kW Req’d* Size(mm) Weight H U E A LM301E 11 24,8 5060 6820 4255 117 991 2,2 1210 250 6085 3629 2311 1318 686 3651M304E 7,5 21,1 5670 7490 4865 144 1227 2,2 1210 250 6750 3820 2502 1318 876 3651M352E 15 26,0 5750 7570 4950 144 1227 2,2 1210 250 6830 3820 2502 1318 876 3651M314E 7,5 20,5 6375 8240 5570 172 1462 2,2 1210 250 7500 4010 2692 1318 1067 3651M344E 11 23,3 6425 8295 5625 172 1462 2,2 1210 250 7555 4010 2692 1318 1067 3651M380E 18,5 26,9 6470 8335 5665 172 1462 2,2 1210 250 7600 4010 2692 1318 1067 3651M337E 11 24,1 5715 7770 4820 135 1152 2,2 1365 250 6920 3740 2311 1429 686 4261M358E 15 27,6 5740 7795 4850 135 1152 2,2 1365 250 6950 3740 2311 1429 686 4261M373E 18,5 30,0 5755 7810 4865 135 1152 2,2 1365 250 6965 3740 2311 1429 686 4261M371E 11 23,4 6485 8605 5595 168 1427 2,2 1365 250 7755 3931 2502 1429 876 4261M393E 15 26,8 6515 8630 5620 168 1427 2,2 1365 250 7785 3931 2502 1429 876 4261M410E 18,5 29,1 6525 8645 5635 168 1427 2,2 1365 250 7795 3931 2502 1429 876 4261M383E 11 22,7 7300 9475 6405 200 1702 2,2 1365 250 8625 4121 2692 1429 1067 4261M407E 15 26,0 7325 9505 6430 200 1702 2,2 1365 250 8655 4121 2692 1429 1067 4261M424E 18,5 28,2 7340 9515 6445 200 1702 2,2 1365 250 8670 4121 2692 1429 1067 4261M439E 22 30,0 7360 9540 6470 200 1702 2,2 1365 250 8690 4121 2692 1429 1067 4261M426E (2) 5,5 28,5 7620 10285 6380 173 1472 4 1815 300 9185 3842 2311 1530 686 5486M456E (2) 7,5 32,6 7635 10300 6395 173 1472 4 1815 300 9200 3842 2311 1530 686 5486M494E (2) 11 35,9 7745 10415 6510 173 1472 4 1815 300 9310 3842 2311 1530 686 5486M467E (2) 5,5 27,6 8605 11355 7365 215 1827 4 1815 300 10250 4032 2502 1530 876 5486M500E (2) 7,5 31,6 8620 11365 7380 215 1827 4 1815 300 10265 4032 2502 1530 876 5486M541E (2) 11 34,8 8730 11480 7495 215 1827 4 1815 300 10380 4032 2502 1530 876 5486M483E (2) 5,5 26,8 9655 12485 8420 257 2183 4 1815 300 11380 4223 2692 1530 1067 5486M591E (2) 15 37,8 9840 12665 8600 257 2183 4 1815 300 11560 4223 2692 1530 1067 5486

ATC M426E to M591E

ATC M301E to M439E

Page 23: DELIVERING Q F OCUSED ON PERFECTION · During fabrication, all panel edges are coated with a 95% pure zinc-rich compound for extended corrosion resistance. ... The innovative design

23

ENGINEERING DATA & DIMENSIONS

ENGINEERING

L

ACCESSDOOR

660

ACCESSDOOR

238850 M.P.T. DRAIN

50 M.P.T. MAKE-UP

75 M.P.T. OVERFLOW

H

U

E130

(2)100 BFW(2)100 BFW A

498

238850 M.P.T. DRAIN

50 M.P.T. MAKE-UP

75 M.P.T. OVERFLOW

H

U

E130

(2)100 BFW(2)100 BFW A

498

L

ACCESSDOOR

485 485

ACCESSDOOR

The motors are shipped loose for field mounting.† Heaviest section is the coil / fan section†† When a remote sump arrangement is selected, the spray pump, suction strainer and associated piping are omitted; the unit is provided with an oversized outlet to facilitatedrainage to the remote sump

* Liters shown is water in suspension in unit and piping. Allow for additional water in bottom of remote sump to cover pump suction and strainer during operation. (300mm would normally be sufficient).

** Refrigerant charge is shown for R-717. Multiply by 1.93 for R22, 1.98 for R134A and 1.7 for R404A, R410A and R507A.Δ Unit dimensions and coil connections may vary slightly from catalog. See factory certified prints for dimensions, quantity of coil connections, and piping configuration.

Coil connections are 4” bevel for weld (BFW).

MODELS: M523E TO M877E

Fans Weights (kg) Refrigerant Remote Sump†† DimensionsΔ (mm)ATC-E Operating Coil SprayModel Heaviest Charge** Volume Pump Liters Conn. Operating Height Upper Lower Coil Length

No. kW m3/s Shipping Operating Section† (kg) (l) kW Req’d* Size(mm) Weight H U E A LM523E (2) 7,5 47,5 8670 11825 7305 201 1712 5,5 2120 300 10535 3842 2311 1530 686 6401M570E (2) 11 47,5 8780 11940 7420 201 1712 5,5 2120 300 10650 3842 2311 1530 686 6401M572E (2) 7,5 46,1 9805 13055 8445 250 2128 5,5 2120 300 11765 4032 2502 1530 876 6401M624E (2) 11 46,1 9920 13170 8560 250 2128 5,5 2120 300 11880 4032 2502 1530 876 6401M659E (2) 15 49,9 9975 13220 8615 250 2128 5,5 2120 300 11935 4032 2502 1530 876 6401M590E (2) 7,5 44,6 11020 14360 9655 299 2543 5,5 2120 300 13075 4223 2692 1530 1067 6401M643E (2) 11 44,6 11130 14475 9770 299 2543 5,5 2120 300 13185 4223 2692 1530 1067 6401M679E (2) 15 48,4 11185 14530 9825 299 2543 5,5 2120 300 13240 4223 2692 1530 1067 6401M637E (2) 15 56,6 10170 13700 4280 233 1983 (2) 2,2 2425 (2) 250 12220 3842 2311 1530 686 7366M607E (2) 7,5 44,5 11340 14980 4865 288 2453 (2) 2,2 2425 (2) 250 13500 4032 2502 1530 876 7366M666E (2) 11 50,6 11450 15085 4920 288 2453 (2) 2,2 2425 (2) 250 13610 4032 2502 1530 876 7366M704E (2) 15 54,9 11505 15140 4950 288 2453 (2) 2,2 2425 (2) 250 13660 4032 2502 1530 876 7366M628E (2) 7,5 43,1 12745 16485 5570 344 2924 (2) 2,2 2425 (2) 250 15005 4223 2692 1530 1067 7366M689E (2) 11 49,1 12855 16590 5625 344 2924 (2) 2,2 2425 (2) 250 15115 4223 2692 1530 1067 7366M759E (2) 18,5 56,6 12935 16675 5665 344 2924 (2) 2,2 2425 (2) 250 15195 4223 2692 1530 1067 7366M674E (2) 11 58,2 11430 15540 4820 271 2303 (2) 2,2 2725 (2) 250 13845 3994 2311 1683 686 8585M715E (2) 15 63,2 11485 15595 4850 271 2303 (2) 2,2 2725 (2) 250 13900 3994 2311 1683 686 8585M746E (2) 18,5 67,3 11510 15620 4865 271 2303 (2) 2,2 2725 (2) 250 13925 3994 2311 1683 686 8585M741E (2) 11 56,6 12975 17210 5595 336 2854 (2) 2,2 2725 (2) 250 15515 4185 2502 1683 876 8585M786E (2) 15 61,4 13025 17265 5620 336 2854 (2) 2,2 2725 (2) 250 15565 4185 2502 1683 876 8585M819E (2) 18,5 65,3 13055 17290 5635 336 2854 (2) 2,2 2725 (2) 250 15595 4185 2502 1683 876 8585M767E (2) 11 54,8 14595 18950 6405 400 3404 (2) 2,2 2725 (2) 250 17255 4375 2692 1683 1067 8585M813E (2) 15 59,5 14650 19005 6430 400 3404 (2) 2,2 2725 (2) 250 17310 4375 2692 1683 1067 8585M848E (2) 18,5 63,2 14680 19035 6445 400 3404 (2) 2,2 2725 (2) 250 17335 4375 2692 1683 1067 8585M877E (2) 22 66,6 14725 19080 6470 400 3404 (2) 2,2 2725 (2) 250 17380 4375 2692 1683 1067 8585

ATC M523E to M679E

ATC M637E to M877E

Page 24: DELIVERING Q F OCUSED ON PERFECTION · During fabrication, all panel edges are coated with a 95% pure zinc-rich compound for extended corrosion resistance. ... The innovative design

24

ENGINEERING DATA & DIMENSIONS

238850 M.P.T. DRAIN

50 M.P.T. MAKE-UP

75 M.P.T. OVERFLOW

H

U

E130

(2)100 BFW

(2)100 BFW A

498

L

ACCESSDOOR

QΔΔ

ACCESSDOOR

QΔΔ

ACCESSDOOR

ACCESSDOOR

The motors are shipped loose for field mounting.† Heaviest section is the coil / fan section†† When a remote sump arrangement is selected, the spray pump, suction strainer and associated piping are omitted; the unit is provided with an oversized outlet to facilitatedrainage to the remote sump

* Liters shown is water in suspension in unit and piping. Allow for additional water in bottom of remote sump to cover pump suction and strainer during operation. (300mm would normally be sufficient).

** Refrigerant charge is shown for R-717. Multiply by 1.93 for R22, 1.98 for R134A and 1.7 for R404A, R410A and R507A.Δ Unit dimensions and coil connections may vary slightly from catalog. See factory certified prints for dimensions, quantity of coil connections, and piping configuration.

Coil connections are 4” bevel for weld (BFW).ΔΔ Q is 485 mm for 4 kW pumps, 660 mm for 5 and 7,5 kW pumps.

MODELS: M852E TO M1358E

ENGINEERING

Fans Weights (kg) Refrigerant Remote Sump†† DimensionsΔ (mm)ATC-E Operating Coil SprayModel Heaviest Charge** Volume Pump Liters Conn. Operating Height Upper Lower Coil Length

No. kW m3/s Shipping Operating Section† (kg) (l) kW Req’d* Size(mm) Weight H U E A L

M852E (4) 5,5 68,7 15240 20575 6380 346 2944 (2) 4 3635 (2) 300 18370 3994 2311 1683 686 11036

M912E (4) 7,5 75,5 15270 20600 6395 346 2944 (2) 4 3635 (2) 300 18400 3994 2311 1683 686 11036

M987E (4) 11 84,6 15495 20830 6510 346 2944 (2) 4 3635 (2) 300 18625 3994 2311 1683 686 11036

M934E (4) 5,5 66,7 17210 22705 7365 430 3655 (2) 4 3635 (2) 300 20500 4185 2502 1683 876 11036

M1000E (4) 7,5 73,4 17235 22735 7380 430 3655 (2) 4 3635 (2) 300 20530 4185 2502 1683 876 11036

M1083E (4) 11 82,1 17465 22960 7495 430 3655 (2) 4 3635 (2) 300 20755 4185 2502 1683 876 11036

M1179E (4) 15 86,2 19675 25330 8600 513 4365 (2) 4 3635 (2) 300 23125 4375 2692 1683 1067 11036

M1046E (4) 7,5 84,0 17335 23650 7305 403 3424 (2) 5,5 4240 (2) 300 21075 3994 2311 1683 686 12865

M1140E (4) 11 95,0 17565 23875 7420 403 3424 (2) 5,5 4240 (2) 300 21300 3994 2311 1683 686 12865

M1144E (4) 7,5 81,5 19615 26110 8445 500 4255 (2) 5,5 4240 (2) 300 23530 4185 2502 1683 876 12865

M1248E (4) 11 92,2 19840 26335 8560 500 4255 (2) 5,5 4240 (2) 300 23760 4185 2502 1683 876 12865

M1317E (4) 15 99,9 19950 26445 8615 500 4255 (2) 5,5 4240 (2) 300 23870 4185 2502 1683 876 12865

M1180E (4) 7,5 79,0 22035 28720 9655 598 5086 (2) 5,5 4240 (2) 300 26145 4375 2692 1683 1067 12865

M1287E (4) 11 89,2 22260 28950 9770 598 5086 (2) 5,5 4240 (2) 300 26370 4375 2692 1683 1067 12865

M1358E (4) 15 96,7 22370 29055 9825 598 5086 (2) 5,5 4240 (2) 300 26480 4375 2692 1683 1067 12865

ATC M852E to M1358E

Page 25: DELIVERING Q F OCUSED ON PERFECTION · During fabrication, all panel edges are coated with a 95% pure zinc-rich compound for extended corrosion resistance. ... The innovative design

25

ENGINEERING DATA & DIMENSIONS

ENGINEERING

485 L

ACCESSDOOR

ACCESSDOOR

490650 M.P.T. DRAIN50 M.P.T. DRAIN

75 M.P.T. OVERFLOW

H

U

E130

(2)100 BFW(2)100 BFW A

670

498498

50 M.P.T. MAKE-UP

75 M.P.T. OVERFLOW

50 M.P.T. MAKE-UP

(2)100 BFW(2)100 BFW

The motors are shipped loose for field mounting.† Heaviest section is the coil / fan section†† When a remote sump arrangement is selected, the spray pump, suction strainer and associated piping are omitted; the unit is provided with an oversized outlet to facilitatedrainage to the remote sump

* Liters shown is water in suspension in unit and piping. Allow for additional water in bottom of remote sump to cover pump suction and strainer during operation. (300mm would normally be sufficient).

** Refrigerant charge is shown for R-717. Multiply by 1.93 for R22, 1.98 for R134A and 1.7 for R404A, R410A and R507A.Δ Unit dimensions and coil connections may vary slightly from catalog. See factory certified prints for dimensions, quantity of coil connections, and piping configuration.

Coil connections are 4” bevel for weld (BFW).

MODELS: M501E TO M844E

Fans Weights (kg) Refrigerant Remote Sump†† DimensionsΔ (mm)ATC-E Operating Coil SprayModel Heaviest Charge** Volume Pump Liters Conn. Operating Height Upper Lower Coil Length

No. kW m3/s Shipping Operating Section† (kg) (l) kW Req’d* Size(mm) Weight H U E A LM501E (2) 7,5 41,9 9170 12195 3860 205 1743 (2) 2,2 2120 (2) 250 10875 3842 2311 1530 686 3188M546E (2) 11 47,3 9280 12300 3915 205 1743 (2) 2,2 2120 (2) 250 10985 3842 2311 1530 686 3188M603E (2) 11 45,9 10525 13635 4535 253 2153 (2) 2,2 2120 (2) 250 12320 4032 2502 1530 876 3188M636E (2) 15 49,8 10580 13690 4565 253 2153 (2) 2,2 2120 (2) 250 12375 4032 2502 1530 876 3188M658E (2) 15 48,2 11795 14995 5170 301 2563 (2) 2,2 2120 (2) 250 13680 4223 2692 1530 1067 3188M634E (2) 15 56,6 10170 13700 4280 233 1983 (2) 2,2 2425 (2) 250 12220 3842 2311 1530 686 3651M604E (2) 7,5 44,5 11340 14980 4865 288 2453 (2) 2,2 2425 (2) 250 13500 4032 2502 1530 876 3651M663E (2) 11 50,6 11450 15085 4920 288 2453 (2) 2,2 2425 (2) 250 13610 4032 2502 1530 876 3651M701E (2) 15 54,9 11505 15140 4950 288 2453 (2) 2,2 2425 (2) 250 13660 4032 2502 1530 876 3651M625E (2) 7,5 43,1 12745 16485 5570 344 2924 (2) 2,2 2425 (2) 250 15005 4223 2692 1530 1067 3651M685E (2) 11 49,1 12855 16590 5625 344 2924 (2) 2,2 2425 (2) 250 15115 4223 2692 1530 1067 3651M755E (2) 18,5 56,6 12935 16675 5665 344 2924 (2) 2,2 2425 (2) 250 15195 4223 2692 1530 1067 3651M712E (2) 15 63,2 11485 15595 4850 271 2303 (2) 2,2 2725 (2) 250 13900 3994 2311 1683 686 4261M742E (2) 18,5 67,3 11510 15620 4865 271 2303 (2) 2,2 2725 (2) 250 13925 3994 2311 1683 686 4261M782E (2) 15 61,4 13025 17265 5620 336 2854 (2) 2,2 2725 (2) 250 15565 4185 2502 1683 876 4261M815E (2) 18,5 65,3 13055 17290 5635 336 2854 (2) 2,2 2725 (2) 250 15595 4185 2502 1683 876 4261M809E (2) 15 59,5 14650 19005 6430 400 3404 (2) 2,2 2725 (2) 250 17310 4375 2692 1683 1067 4261M844E (2) 18,5 63,2 14680 19035 6445 400 3404 (2) 2,2 2725 (2) 250 17335 4375 2692 1683 1067 4261

ATC M501E to M844E

Page 26: DELIVERING Q F OCUSED ON PERFECTION · During fabrication, all panel edges are coated with a 95% pure zinc-rich compound for extended corrosion resistance. ... The innovative design

26

ENGINEERING DATA & DIMENSIONS

(2)100 BFW

(2)100 BFW

E

U

E

A

80 M.P.T. OVERFLOW

80 M.P.T. DRAIN

50 M.P.T. MAKE-UP 124

2991

178

H

QΔΔ

L

ACCESS DOOR

A DOOR

MODELS: XE298E TO XC669E

ENGINEERING

The motors are shipped loose for field mounting.† Heaviest section is the coil / fan section†† When a remote sump arrangement is selected, the spray pump, suction strainer and associated piping are omitted; the unit is provided with an oversized outlet to facilitatedrainage to the remote sump

* Liters shown is water in suspension in unit and piping. Allow for additional water in bottom of remote sump to cover pump suction and strainer during operation. (300mm would normally be sufficient).

** Refrigerant charge is shown for R-717. Multiply by 1.93 for R22, 1.98 for R134A and 1.7 for R404A, R410A and R507A.Δ Unit dimensions and coil connections may vary slightly from catalog. See factory certified prints for dimensions, quantity of coil connections, and piping configuration.

Coil connections are 4” bevel for weld (BFW).ΔΔ Q is 485 mm for 4 kW pumps, 660 mm for 5 and 7,5 kW pumps.

Fans Weights (kg) Refrigerant Remote Sump†† DimensionsΔ (mm)ATC-E Operating Coil SprayModel Heaviest Charge** Volume Pump Liters Conn. Operating Height Upper Lower Coil Length

No. kW m3/s Shipping Operating Section† (kg) (l) kW Req’d* Size(mm) Weight H U E A LXE298E 7,5 26,2 5620 8285 4465 113 959 4 1590 300 6665 4112 2530 1581 565 3651XE333E 7,5 25,8 6475 9205 5315 148 1258 4 1590 300 7585 4328 2746 1581 781 3651XC346E 15 33,0 5705 8370 4550 113 959 4 1590 300 6750 4112 2530 1581 565 3651XE356E 7,5 25,4 7280 10080 6125 183 1557 4 1590 300 8460 4543 2962 1581 997 3651XC360E 18,5 35,6 5720 8380 4565 113 959 4 1590 300 6765 4112 2530 1581 565 3651XE368E 7,5 25,1 8150 11020 6995 218 1855 4 1590 300 9400 4759 3178 1581 1213 3651XE387E 11 29,1 7340 10140 6180 183 1557 4 1590 300 8520 4543 2962 1581 997 3651XC388E 15 32,5 6560 9290 5400 148 1258 4 1590 300 7670 4328 2746 1581 781 3651XC402E 18,5 35,0 6575 9305 5415 148 1258 4 1590 300 7685 4328 2746 1581 781 3651XC427E 18,5 34,5 7380 10180 6225 183 1557 4 1590 300 8560 4543 2962 1581 997 3651XC443E 22 36,7 7405 10200 6245 183 1557 4 1590 300 8580 4543 2962 1581 997 3651XC462E 22 36,2 8275 11140 7115 218 1855 4 1590 300 9520 4759 3178 1581 1213 3651XE406E 7,5 35,1 7995 12015 6340 167 1417 5,5 2385 300 9635 4112 2530 1581 565 5486XE448E 7,5 34,6 9260 13385 7605 220 1868 5,5 2385 300 11005 4328 2746 1581 781 5486XE472E 7,5 34,1 10490 14715 8835 273 2320 5,5 2385 300 12335 4543 2962 1581 997 5486XE492E 11 39,6 9320 13445 7665 220 1868 5,5 2385 300 11065 4328 2746 1581 781 5486XC504E 18,5 47,6 8095 12115 6440 167 1417 5,5 2385 300 9735 4112 2530 1581 565 5486XE516E 11 39,0 10550 14775 8895 273 2320 5,5 2385 300 12390 4543 2962 1581 997 5486XC525E 22 50,6 8120 12140 6465 167 1417 5,5 2385 300 9755 4112 2530 1581 565 5486XE528E 15 43,6 9350 13470 7695 220 1868 5,5 2385 300 11090 4328 2746 1581 781 5486XE542E 11 38,4 11850 16170 10190 326 2771 5,5 2385 300 13790 4759 3178 1581 1213 5486XE553E 15 42,9 10580 14800 8920 273 2320 5,5 2385 300 12420 4543 2962 1581 997 5486XC558E 18,5 46,9 9360 13485 7705 220 1868 5,5 2385 300 11105 4328 2746 1581 781 5486XC579E 18,5 46,3 10590 14815 8935 273 2320 5,5 2385 300 12435 4543 2962 1581 997 5486XE608E 18,5 45,5 11890 16210 10235 326 2771 5,5 2385 300 13830 4759 3178 1581 1213 5486XC611E 30 54,9 9455 13580 7800 220 1868 5,5 2385 300 11200 4328 2746 1581 781 5486XC641E 30 54,1 10685 14910 9030 273 2320 5,5 2385 300 12530 4543 2962 1581 997 5486XC669E 30 53,3 11985 16305 10330 326 2771 5,5 2385 300 13925 4759 3178 1581 1213 5486

ATC XE298E to XC669E

The motors are shipped loose for field mounting.† Heaviest section is the coil / fan section†† When a remote sump arrangement is selected, the spray pump, suction strainer and associated piping are omitted; the unit is provided with an oversized outlet to facilitatedrainage to the remote sump

* Liters shown is water in suspension in unit and piping. Allow for additional water in bottom of remote sump to cover pump suction and strainer during operation. (300mm would normally be sufficient).

** Refrigerant charge is shown for R-717. Multiply by 1.93 for R22, 1.98 for R134A and 1.7 for R404A, R410A and R507A.Δ Unit dimensions and coil connections may vary slightly from catalog. See factory certified prints for dimensions, quantity of coil connections, and piping configuration.

Coil connections are 4” bevel for weld (BFW).ΔΔ Q is 485 mm for 4 kW pumps, 660 mm for 5 and 7,5 kW pumps.

Optional Dual Fan units will have a "-DF" at the end of the model number. Fan kW and weights may vary.

Page 27: DELIVERING Q F OCUSED ON PERFECTION · During fabrication, all panel edges are coated with a 95% pure zinc-rich compound for extended corrosion resistance. ... The innovative design

27

ENGINEERING DATA & DIMENSIONS

ENGINEERING

(4)100 BFW

(4)100 BFW

E

U

A

(2) 80 M.P.T. OVERFLOW

(2) 80 M.P.T. DRAIN

(2) 50 M.P.T. MAKE-UP

124

2991

178

H

QΔΔ QΔΔ

L

ACCESS DOOR ACCESS DOOR

A

MODELS: XE596E TO XC1340E

The motors are shipped loose for field mounting.† Heaviest section is the coil / fan section†† When a remote sump arrangement is selected, the spray pump, suction strainer and associated piping are omitted; the unit is provided with an oversized outlet to facilitatedrainage to the remote sump

* Liters shown is water in suspension in unit and piping. Allow for additional water in bottom of remote sump to cover pump suction and strainer during operation. (300mm would normally be sufficient).

** Refrigerant charge is shown for R-717. Multiply by 1.93 for R22, 1.98 for R134A and 1.7 for R404A, R410A and R507A.Δ Unit dimensions and coil connections may vary slightly from catalog. See factory certified prints for dimensions, quantity of coil connections, and piping configuration.

Coil connections are 4” bevel for weld (BFW).ΔΔ Q is 485 mm for 4 kW pumps, 660 mm for 5 and 7,5 kW pumps.

Fans Weights (kg) Refrigerant Remote Sump†† DimensionsΔ (mm)ATC-E Operating Coil SprayModel Heaviest Charge** Volume Pump Liters Conn. Operating Height Upper Lower Coil Length

No. kW m3/s Shipping Operating Section† (kg) (l) kW Req’d* Size(mm) Weight H U E A LXE596E (2) 7,5 52,4 11240 16565 4465 225 1918 (2) 4 3180 (2) 300 13325 4416 2530 1886 565 7366XE665E (2) 7,5 51,6 12945 18405 5315 296 2515 (2) 4 3180 (2) 300 15170 4632 2746 1886 781 7366XE709E (2) 7,5 50,9 14560 20160 6125 366 3113 (2) 4 3180 (2) 300 16920 4848 2962 1886 997 7366XC720E (2) 18.5 71,1 11440 16765 4565 225 1918 (2) 4 3180 (2) 300 13525 4416 2530 1886 565 7366XE742E (2) 7.5 50,1 16300 22035 6995 436 3711 (2) 4 3180 (2) 300 18795 5064 3178 1886 1213 7366XC775E (2) 15 65,0 13120 18580 5400 296 2515 (2) 4 3180 (2) 300 15340 4632 2746 1886 781 7366XC804E (2) 18,5 70,1 13145 18605 5415 296 2515 (2) 4 3180 (2) 300 15370 4632 2746 1886 781 7366XC855E (2) 18,5 69,0 14760 20355 6225 366 3113 (2) 4 3180 (2) 300 17120 4848 2962 1886 997 7366XC884E (2) 22 73,4 14805 20405 6245 366 3113 (2) 4 3180 (2) 300 17165 4848 2962 1886 997 7366XC897E (2) 18,5 68,0 16500 22235 7095 436 3711 (2) 4 3180 (2) 300 18995 5064 3178 1886 1213 7366XC925E (2) 22 72,3 16545 22280 7115 436 3711 (2) 4 3180 (2) 300 19040 5064 3178 1886 1213 7366XE812E (2) 7.5 70,2 15995 24030 6340 333 2833 (2) 5,5 4770 (2) 300 19270 4416 2530 1886 565 11036XE896E (2) 7,5 69,1 18525 26770 7605 439 3736 (2) 5,5 4770 (2) 300 22.010 4632 2746 1886 781 11036XE947E (2) 7,5 68,1 20985 29430 8835 545 4639 (2) 5.5 4770 (2) 300 24665 4848 2962 1886 997 11036XE984E (2) 11 79,1 18645 26890 7665 439 3736 (2) 5,5 4770 (2) 300 22.125 4632 2746 1886 781 11036XC1011E (2) 18.5 95,2 16195 24230 6440 333 2833 (2) 5,5 4770 (2) 300 19470 4416 2530 1886 565 11036XE1032E (2) 11 78,0 21100 29545 8895 545 4639 (2) 5,5 4770 (2) 300 24785 4848 2962 1886 997 11036XC1049E (2) 22 101,2 16240 24275 6465 333 2833 (2) 5,5 4770 (2) 300 19515 4416 2530 1886 565 11036XC1112E (2) 18.5 93,9 18725 26970 7705 439 3736 (2) 5,5 4770 (2) 300 22210 4632 2746 1886 781 11036XC1153E (2) 22 99,7 18770 27015 7730 439 3736 (2) 5,5 4770 (2) 300 22255 4632 2746 1886 781 11036XE1157E (2) 15 84,6 23750 32395 10220 652 5542 (2) 5,5 4770 (2) 300 27635 5064 3178 1886 1213 11036XC1210E (2) 22 98,3 21230 29675 8960 545 4639 (2) 5,5 4770 (2) 300 24910 4848 2962 1886 997 11036XC1222E (2) 30 109,8 18915 27160 7800 439 3736 (2) 5,5 4770 (2) 300 22400 4632 2746 1886 781 11036XC1264E (2) 22 96,8 23825 32470 10255 652 5542 (2) 5,5 4770 (2) 300 27705 5064 3178 1886 1213 11036XC1282E (2) 30 108,2 21375 29820 9030 545 4639 (2) 5,5 4770 (2) 300 25055 4848 2962 1886 997 11036XC1340E (2) 30 106,6 23970 32615 10330 652 5542 (2) 5,5 4770 (2) 300 27850 5064 3178 1886 1213 11036

ATC XE596E to XC1340E

Optional Dual Fan units will have a "-DF" at the end of the model number. Fan kW and weights may vary.

Page 28: DELIVERING Q F OCUSED ON PERFECTION · During fabrication, all panel edges are coated with a 95% pure zinc-rich compound for extended corrosion resistance. ... The innovative design

28

ENGINEERING DATA & DIMENSIONS

ENGINEERING

3607

133

75 M.P.T. DRAIN

50 M.P.T. MAKE-UP

75 M.P.T. OVERFLOW

178

H

U

E

A(2)100 BFW

(2)100 BFW

LQΔΔ

ACCESS DOOR

MODELS: 428E TO 967E

The motors are shipped loose for field mounting.† Heaviest section is the coil / fan section†† When a remote sump arrangement is selected, the spray pump, suction strainer and associated piping are omitted; the unit is provided with an oversized outlet to facilitatedrainage to the remote sump

* Liters shown is water in suspension in unit and piping. Allow for additional water in bottom of remote sump to cover pump suction and strainer during operation. (300mm would normally be sufficient).

** Refrigerant charge is shown for R-717. Multiply by 1.93 for R22, 1.98 for R134A and 1.7 for R404A, R410A and R507A.Δ Unit dimensions and coil connections may vary slightly from catalog. See factory certified prints for dimensions, quantity of coil connections, and piping configuration.

Coil connections are 4” bevel for weld (BFW).ΔΔ Q is 485 mm for 4 kW pumps, 660 mm for 5 and 7,5 kW pumps.

Fans Weights (kg) Refrigerant Remote Sump†† DimensionsΔ (mm)ATC-E Operating Coil SprayModel Heaviest Charge** Volume Pump Liters Conn. Operating Height Upper Lower Coil Length

No. kW m3/s Shipping Operating Section† (kg) (l) kW Req’d* Size(mm) Weight H U E A L428E 11 34,8 7510 10595 6280 182 1548 4 1855 300 8805 4328 2746 1581 781 3651456E 15 38,3 7540 10625 6310 182 1548 4 1855 300 8830 4328 2746 1581 781 3651474E 18,5 40,9 7550 10635 6325 182 1548 4 1855 300 8845 4328 2746 1581 781 3651503E 15 37,2 8530 11695 7300 225 1917 4 1855 300 9900 4543 2962 1581 997 3651523E 5 39,6 8540 11705 7310 225 1917 4 1855 300 9915 4543 2962 1581 997 3651539E 22 41,8 8565 11730 7335 225 1917 4 1855 300 9940 4543 2962 1581 997 3651559E 22 40,4 9635 12880 8405 269 2286 4 1855 300 11090 4759 3178 1581 1213 3651583E 30 43,8 9705 12955 8480 269 2286 4 1855 300 11165 4759 3178 1581 1213 3651545E 22 48,1 8590 12220 7205 212 1799 4 2160 300 10145 4480 2746 1734 781 4261556E 15 41,2 9690 13415 8300 262 2231 4 2160 300 11345 4696 2962 1734 997 4261581E 18,5 44,4 9700 13430 8315 262 2231 4 2160 300 11360 4696 2962 1734 997 4261601E 18,5 43,0 11065 14885 9675 313 2662 4 2160 300 12815 4912 3178 1734 1213 4261620E 22 45,2 11085 14910 9700 313 2662 4 2160 300 12835 4912 3178 1734 1213 4261647E 30 49,0 11160 14980 9770 313 2662 4 2160 300 12910 4912 3178 1734 1213 4261642E 15 51,9 10745 15390 8970 271 2301 5,5 2725 300 12730 4632 2746 1886 781 5486682E 18,5 55,9 10760 15405 8980 271 2301 5,5 2725 300 12740 4632 2746 1886 781 5486713E 22 59,5 10780 15425 9005 271 2301 5,5 2725 300 12765 4632 2746 1886 781 5486747E 18,5 54,2 12255 17030 10480 336 2858 5,5 2725 300 14365 4848 2962 1886 997 5486781E 22 57,6 12280 17050 10500 336 2858 5,5 2725 300 14390 4848 2962 1886 997 5486806E 22 55,9 13815 18715 12040 402 3416 5,5 2725 300 16055 5064 3178 1886 1213 5486827E 30 62,6 12350 17125 10575 336 2858 5,5 2725 300 14460 4848 2962 1886 997 5486854E 30 60,6 13890 18790 12110 402 3416 5,5 2725 300 16125 5064 3178 1886 1213 5486892E 37 64,5 13895 18790 12115 402 3416 5,5 2725 300 16130 5064 3178 1886 1213 5486791E 30 69,7 11950 17165 9905 300 2552 7,5 3030 350 14125 4632 2746 1886 781 6096816E 22 61,9 13550 18895 11505 373 3172 7,5 3030 350 15860 4848 2962 1886 997 6096842E 22 59,9 15430 20920 13385 446 3792 7,5 3030 350 17880 5064 3178 1886 1213 6096869E 30 67,6 13620 18970 11575 373 3172 7,5 3030 350 15930 4848 2962 1886 997 6096907E 37 71,9 13625 18975 11580 373 3172 7,5 3030 350 15935 4848 2962 1886 997 6096935E 37 69,7 15510 20995 13465 446 3792 7,5 3030 350 17960 5064 3178 1886 1213 6096967E 45 73,3 15600 21090 13555 446 3792 7,5 3030 350 18050 5064 3178 1886 1213 6096

ATC 428E to 967E

Optional Dual Fan units will have a "-DF" at the end of the model number. Fan kW and weights may vary.

Page 29: DELIVERING Q F OCUSED ON PERFECTION · During fabrication, all panel edges are coated with a 95% pure zinc-rich compound for extended corrosion resistance. ... The innovative design

29

ENGINEERING DATA & DIMENSIONS

ENGINEERING

LQΔΔ QΔΔ

ACCESS DOOR ACCESS DOOR

3607

133

(2)75 M.P.T. DRAIN

(2)50 M.P.T. MAKE-UP

(2)75 M.P.T. OVERFLOW

178

H

U

E

A(2)100 BFW

(2)100 BFW

The motors are shipped loose for field mounting.† Heaviest section is the coil / fan section†† When a remote sump arrangement is selected, the spray pump, suction strainer and associated piping are omitted; the unit is provided with an oversized outlet to facilitatedrainage to the remote sump

* Liters shown is water in suspension in unit and piping. Allow for additional water in bottom of remote sump to cover pump suction and strainer during operation. (300mm would normally be sufficient).

** Refrigerant charge is shown for R-717. Multiply by 1.93 for R22, 1.98 for R134A and 1.7 for R404A, R410A and R507A.Δ Unit dimensions and coil connections may vary slightly from catalog. See factory certified prints for dimensions, quantity of coil connections, and piping configuration.

Coil connections are 4” bevel for weld (BFW).ΔΔ Q is 485 mm for 4 kW pumps, 660 mm for 5 and 7,5 kW pumps.

MODELS: 858E TO 1925E

Fans Weights (kg) Refrigerant Remote Sump†† DimensionsΔ (mm)ATC-E Operating Coil SprayModel Heaviest Charge** Volume Pump Liters Conn. Operating Height Upper Lower Coil Length

No. kW m3/s Shipping Operating Section† (kg) (l) kW Req’d* Size(mm) Weight H U E A L858E (2) 11 69,7 15025 21190 6280 364 3096 (2) 4 3710 (2) 300 17610 4632 2746 1886 781 7366913E (2) 15 76,7 15075 21245 6310 364 3096 (2) 4 3710 (2) 300 17665 4632 2746 1886 781 7366949E (2) 18,5 81,7 15105 21275 6325 364 3096 (2) 4 3710 (2) 300 17690 4632 2746 1886 781 7366980E (2) 11 65,6 19140 25635 8340 538 4571 (2) 4 3710 (2) 300 22055 5064 3178 1886 1213 73661007E (2) 15 74,5 17055 23385 7300 451 3834 (2) 4 3710 (2) 300 19805 4848 2962 1886 997 73661047E (2) 18,5 79,3 17080 23415 7310 451 3834 (2) 4 3710 (2) 300 19830 4848 2962 1886 997 73661078E (2) 22 83,5 17130 23460 7335 451 3834 (2) 4 3710 (2) 300 19875 4848 2962 1886 997 73661085E (2) 18,5 76,8 19225 25720 8380 538 4571 (2) 4 3710 (2) 300 22135 5064 3178 1886 1213 73661118E (2) 22 80,9 19270 25765 8405 538 4571 (2) 4 3710 (2) 300 22180 5064 3178 1886 1213 73661167E (2) 30 87,6 19415 25910 8480 538 4571 (2) 4 3710 (2) 300 22325 5064 3178 1886 1213 73661164E (2) 18,5 88,7 19405 26860 8315 525 4462 (2) 4 4315 (2) 300 22715 5153 2962 2191 997 85851204E (2) 18,5 85,9 22125 29775 9675 626 5325 (2) 4 4315 (2) 300 25630 5369 3178 2191 1213 85851240E (2) 22 90,4 22170 29820 9700 626 5325 (2) 4 4315 (2) 300 25675 5369 3178 2191 1213 85851294E (2) 30 98,0 22315 29965 9770 626 5325 (2) 4 4315 (2) 300 25820 5369 3178 2191 1213 85851192E (2) 22 122,5 18450 27490 7450 410 3489 (2) 5,5 5450 (2) 300 22165 4721 2530 2191 565 110361284E (2) 15 103,9 21490 30780 8970 541 4603 (2) 5,5 5450 (2) 300 25455 4937 2746 2191 781 110361365E (2) 18,5 111,7 21520 30810 8980 541 4603 (2) 5,5 5450 (2) 300 25485 4937 2746 2191 781 110361426E (2) 22 118,9 21565 30855 9005 541 4603 (2) 5,5 5450 (2) 300 25530 4937 2746 2191 781 110361496E (2) 18,5 108,5 24510 34055 10480 672 5717 (2) 5,5 5450 (2) 300 28730 5153 2962 2191 997 110361562E (2) 22 115,2 24555 34100 10500 672 5717 (2) 5,5 5450 (2) 300 28775 5153 2962 2191 997 110361655E (2) 30 125,1 24705 34245 10575 672 5717 (2) 5,5 5450 (2) 300 28920 5153 2962 2191 997 110361709E (2) 30 121,2 27780 37575 12110 803 6831 (2) 5,5 5450 (2) 300 32250 5369 3178 2191 1213 110361784E (2) 37 129,0 27785 37585 12115 803 6831 (2) 5,5 5450 (2) 300 32260 5369 3178 2191 1213 110361625E (2) 22 123,7 27100 37795 11505 746 6345 (2) 7,5 6055 (2) 350 31715 5153 2962 2191 997 122561729E (2) 30 135,2 27245 37940 11575 746 6345 (2) 7,5 6055 (2) 350 31860 5153 2962 2191 997 122561805E (2) 37 143,8 27250 37950 11580 746 6345 (2) 7,5 6055 (2) 350 31870 5153 2962 2191 997 122561861E (2) 37 139,3 31015 41995 13465 892 7584 (2) 7,5 6055 (2) 350 35915 5369 3178 2191 1213 122561925E (2) 45 146,6 31200 42175 13555 892 7584 (2) 7,5 6055 (2) 350 36095 5369 3178 2191 1213 12256

ATC 858E to 1925E

Optional Dual Fan units will have a "-DF" at the end of the model number. Fan kW and weights may vary.

Page 30: DELIVERING Q F OCUSED ON PERFECTION · During fabrication, all panel edges are coated with a 95% pure zinc-rich compound for extended corrosion resistance. ... The innovative design

30

7344

133

75 M.P.T. DRAIN75 M.P.T. DRAIN

75 M.P.T. OVERFLOW

75 M.P.T. OVERFLOW

178

H

U

E

A(2)100 BFW

(2)100 BFW

(2)100 BFW

(2)100 BFW

50 M.P.T. MAKE-UP

50 M.P.T. MAKE-UP

LQΔΔ

ACCESS DOORACCESS DOOR

MODELS: 857E TO 1915E

The motors are shipped loose for field mounting.† Heaviest section is the coil / fan section†† When a remote sump arrangement is selected, the spray pump, suction strainer and associated piping are omitted; the unit is provided with an oversized outlet to facilitatedrainage to the remote sump

* Liters shown is water in suspension in unit and piping. Allow for additional water in bottom of remote sump to cover pump suction and strainer during operation. (300mm would normally be sufficient).

** Refrigerant charge is shown for R-717. Multiply by 1.93 for R22, 1.98 for R134A and 1.7 for R404A, R410A and R507A.Δ Unit dimensions and coil connections may vary slightly from catalog. See factory certified prints for dimensions, quantity of coil connections, and piping configuration.

Coil connections are 4” bevel for weld (BFW).ΔΔ Q is 485 mm for 4 kW pumps, 660 mm for 5 and 7,5 kW pumps.

Fans Weights (kg) Refrigerant Remote Sump†† DimensionsΔ (mm)ATC-E Operating Coil SprayModel Heaviest Charge** Volume Pump Liters Conn. Operating Height Upper Lower Coil Length

No. kW m3/s Shipping Operating Section† (kg) (l) kW Req’d* Size(mm) Weight H U E A L857E (2) 11 69,7 15025 21190 6280 364 3096 (2) 4 3710 (2) 300 17610 4632 2746 1886 781 3651912E (2) 15 76,7 15075 21245 6310 364 3096 (2) 4 3710 (2) 300 17665 4632 2746 1886 781 3651979E (2) 11 65,6 19140 25635 8340 538 4572 (2) 4 3710 (2) 300 22055 5064 3178 1886 1213 36511006E (2) 15 74,5 17055 23385 7300 451 3834 (2) 4 3710 (2) 300 19805 4848 2962 1886 997 36511046E (2) 18,5 79,3 17080 23415 7310 451 3834 (2) 4 3710 (2) 300 19830 4848 2962 1886 997 36511077E (2) 22 83,5 17130 23460 7335 451 3834 (2) 4 3710 (2) 300 19875 4848 2962 1886 997 36511117E (2) 22 80,9 19270 25765 8405 538 4571 (2) 4 3710 (2) 300 22180 5064 3178 1886 1213 36511166E (2) 30 87,6 19415 25910 8480 538 4571 (2) 4 3710 (2) 300 22325 5064 3178 1886 1213 36511163E (2) 18,5 88,7 19405 26860 8315 525 4462 (2) 4 4315 (2) 300 22715 5153 2962 2191 997 42611203E (2) 18,5 85,9 22125 29775 9675 626 5325 (2) 4 4315 (2) 300 25630 5369 3178 2191 1213 42611239E (2) 22 90,4 22170 29820 9700 626 5325 (2) 4 4315 (2) 300 25675 5369 3178 2191 1213 42611293E (2) 30 98,0 22315 29965 9770 626 5325 (2) 4 4315 (2) 300 25820 5369 3178 2191 1213 42611191E (2) 22 122,5 18450 27490 7450 410 3489 (2) 5,5 5450 (2) 300 22165 5026 2530 2496 565 54861283E (2) 15 103,9 21490 30780 8970 541 4603 (2) 5,5 5450 (2) 300 25455 5242 2746 2496 781 54861364E (2) 18,5 111,7 21520 30810 8980 541 4603 (2) 5,5 5450 (2) 300 25485 5242 2746 2496 781 54861425E (2) 22 118,9 21565 30855 9005 541 4603 (2) 5,5 5450 (2) 300 25530 5242 2746 2496 781 54861495E (2) 18,5 108,5 24510 34055 10480 672 5717 (2) 5,5 5450 (2) 300 28730 5458 2962 2496 997 54861561E (2) 22 115,2 24555 34100 10500 672 5717 (2) 5,5 5450 (2) 300 28775 5458 2962 2496 997 54861654E (2) 30 125,1 24705 34245 10575 672 5717 (2) 5,5 5450 (2) 300 28920 5458 2962 2496 997 54861708E (2) 30 121,2 27780 37575 12110 803 6831 (2) 5,5 5450 (2) 300 32250 5674 3178 2496 1213 54861783E (2) 37 129,0 27785 37585 12115 803 6831 (2) 5,5 5450 (2) 300 32260 5674 3178 2496 1213 54861616E (2) 22 123,1 27100 37795 11505 746 6345 (2) 7,5 6055 (2) 350 31715 5458 2962 2496 997 60961720E (2) 30 134,5 27245 37940 11575 746 6345 (2) 7,5 6055 (2) 350 31860 5458 2962 2496 997 60961795E (2) 37 143,1 27250 37950 11580 746 6345 (2) 7,5 6055 (2) 350 31870 5458 2962 2496 997 60961851E (2) 37 138,6 31015 41995 13465 892 7584 (2) 7,5 6055 (2) 350 35915 5674 3178 2496 1213 60961915E (2) 45 145,9 31200 42175 13555 892 7584 (2) 7,5 6055 (2) 350 36095 5674 3178 2496 1213 6096

ATC 857E to 1915E

ENGINEERING DATA & DIMENSIONS

ENGINEERING

Optional Dual Fan units will have a "-DF" at the end of the model number. Fan kW and weights may vary.

Page 31: DELIVERING Q F OCUSED ON PERFECTION · During fabrication, all panel edges are coated with a 95% pure zinc-rich compound for extended corrosion resistance. ... The innovative design

31

ENGINEERING DATA & DIMENSIONS

ENGINEERING

QΔΔ QΔΔL

ACCESS DOORACCESS DOOR ACCESS DOORACCESS DOOR

7344

133

(2)75 M.P.T. DRAIN(2)75 M.P.T. DRAIN

(2)75 M.P.T. OVERFLOW

(2)75 M.P.T. OVERFLOW

178

H

U

E

A(2)100 BFW

(2)100 BFW

(2)100 BFW

(2)100 BFW

50 M.P.T. MAKE-UP

50 M.P.T. MAKE-UP

MODELS: 1879E TO 3714E

The motors are shipped loose for field mounting.† Heaviest section is the coil / fan section†† When a remote sump arrangement is selected, the spray pump, suction strainer and associated piping are omitted; the unit is provided with an oversized outlet to facilitatedrainage to the remote sump

* Liters shown is water in suspension in unit and piping. Allow for additional water in bottom of remote sump to cover pump suction and strainer during operation. (300mm would normally be sufficient).

** Refrigerant charge is shown for R-717. Multiply by 1.93 for R22, 1.98 for R134A and 1.7 for R404A, R410A and R507A.Δ Unit dimensions and coil connections may vary slightly from catalog. See factory certified prints for dimensions, quantity of coil connections, and piping configuration.

Coil connections are 4” bevel for weld (BFW).ΔΔ Q is 485 mm for 4 kW pumps, 660 mm for 5 and 7,5 kW pumps.

Fans Weights (kg) Refrigerant Remote Sump†† DimensionsΔ (mm)ATC-E Operating Coil SprayModel Heaviest Charge** Volume Pump Liters Conn. Operating Height Upper Lower Coil Length

No. kW m3/s Shipping Operating Section† (kg) (l) kW Req’d* Size(mm) Weight H U E A L1879E (4) 11 135,3 34155 46830 7270 902 7668 (4) 4 7420 (4) 300 39545 5458 2962 2496 997 73662002E (4) 15 148,9 34265 46940 7300 902 7668 (4) 4 7420 (4) 300 39655 5458 2962 2496 997 73662082E (4) 18,5 158,6 34320 46990 7310 902 7668 (4) 4 7420 (4) 300 39705 5458 2962 2496 997 73662158E (4) 18,5 153,6 38600 51600 8380 1075 9143 (4) 4 7420 (4) 300 44315 5674 3178 2496 1213 73662223E (4) 22 161,8 38690 51690 8405 1075 9143 (4) 4 7420 (4) 300 44405 5674 3178 2496 1213 73662320E (4) 30 175,3 38980 51980 8480 1075 9143 (4) 4 7420 (4) 300 44695 5674 3178 2496 1213 73662256E (4) 18,5 174,7 38900 53880 8315 1049 8923 (4) 4 8630 (4) 300 45460 5458 2962 2496 997 85852324E (4) 22 183,8 38990 53970 8335 1049 8923 (4) 4 8630 (4) 300 45550 5458 2962 2496 997 85852404E (4) 22 178,2 44435 59795 9700 1252 10649 (4) 4 8630 (4) 300 51375 5674 3178 2496 1213 85852509E (4) 30 193,0 44725 60085 9770 1252 10649 (4) 4 8630 (4) 300 51665 5674 3178 2496 1213 85852490E (4) 15 204,7 43255 61925 8970 1082 9205 (4) 5,5 10900 (4) 300 51140 5242 2746 2496 781 110362647E (4) 18,5 220,1 43310 61980 8980 1082 9205 (4) 5,5 10900 (4) 300 51190 5242 2746 2496 781 110362765E (4) 22 234,3 43400 62070 9005 1082 9205 (4) 5,5 10900 (4) 300 51285 5242 2746 2496 781 110362900E (4) 18,5 213,6 49295 68475 10480 1345 11434 (4) 5,5 10900 (4) 300 57690 5458 2962 2496 997 110363029E (4) 22 227,0 49385 68565 10500 1345 11434 (4) 5,5 10900 (4) 300 57780 5458 2962 2496 997 110363210E (4) 30 246,5 49675 68855 10575 1345 11434 (4) 5,5 10900 (4) 300 58070 5458 2962 2496 997 110363313E (4) 30 238,8 55830 75515 12110 1607 13662 (4) 5,5 10900 (4) 300 64730 5674 3178 2496 1213 110363459E (4) 37 254,2 55845 75530 12115 1607 13662 (4) 5,5 10900 (4) 300 64745 5674 3178 2496 1213 110362855E (4) 22 250,1 47565 68490 9835 1201 10210 (4) 7,5 12115 (4) 350 56200 5242 2746 2496 781 122563232E (4) 22 234,8 61770 83805 13385 1784 15169 (4) 7,5 12115 (4) 350 71515 5674 3178 2496 1213 122563336E (4) 30 264,9 54530 76005 11575 1492 12689 (4) 7,5 12115 (4) 350 63710 5458 2962 2496 997 122563482E (4) 37 281,9 54550 76020 11580 1492 12690 (4) 7,5 12115 (4) 350 63730 5458 2962 2496 997 122563591E (4) 37 273,0 62080 84115 13465 1784 15169 (4) 7,5 12115 (4) 350 71820 5674 3178 2496 1213 122563714E (4) 45 287,4 62440 84475 13555 1784 15169 (4) 7,5 12115 (4) 350 72185 5674 3178 2496 1213 12256

ATC 1879E to 3714E

Optional Dual Fan units will have a "-DF" at the end of the model number. Fan kW and weights may vary.

Page 32: DELIVERING Q F OCUSED ON PERFECTION · During fabrication, all panel edges are coated with a 95% pure zinc-rich compound for extended corrosion resistance. ... The innovative design

32

The recommended support for EVAPCO condensers isstructural “I” beams located under the outer flangesand running the entire length of the unit.Mounting holes, 19 mm in diameter are located inthe bottom channels of the pan section to provide forbolting to the structural steel. (Refer to certifieddrawings from the factory for bolt hole locations.)

Beams should be level to within 3 mm per 2 m beforesetting the unit in place. Do not level the unit byshimming between it and the “I” beams as this willnot provide proper longitudinal support.

A

A

4' to 12' WIDE MODELS

17' to 24' WIDE MODELS

Plan Views

B

B

End Elevations

UP TO 4m WIDE MODELS

GREATER THAN 4m WIDE MODELS

ENGINEERING

ATC-E DIMENSIONSModels A B

ATC-E 50E to 80E 1826 122690E to 120E 2731 1226135E to 165E 3651 1226

ATC-E M170E to M247E 2578 2283M203E to M233E 2731 2388M252E to M331E 3188 2388M301E to M380E 3651 2388M337E to M439E 4261 2388M426E to M591E 5486 2388M523E to M679E 6401 2388M637E to M759E 7366 2388M674E to M877E 8585 2388M852E to M1179E 11036 2388

M10468E to M1358E 12865 2388

ATC-E M501E to M658E 3188 4905M634E to M755E 3651 4905M712E to M844E 4261 4905

ATC-E XE298E to XC462E 3652 2991XE406E to XC669E 5487 2991XE596E to XC925E 7366 2991XE812E to XC1340E 11037 2991

ATC-E 428E to 583E 3651 3607545E to 647E 4261 3607642E to 892E 5486 3607791E to 967E 6096 3607858E to 1167E 7366 36071164E to 1294E 8585 36071192E to 1784E 11036 36071625E to 1925E 12256 3607

ATC-E 857E to 1166E 3651 73441163E to 1293E 4261 73441191E to 1783E 5486 73441616E to 1915E 6096 73441879E to 2320E 7366 73442256E to 2509E 8585 73442490E to 3459E 11036 73442855E to 3714E 12256 7344

RECOMMENDED STEEL SUPPORT

Page 33: DELIVERING Q F OCUSED ON PERFECTION · During fabrication, all panel edges are coated with a 95% pure zinc-rich compound for extended corrosion resistance. ... The innovative design

33

SPECIFICATIONS

SPECIFICATIONS

GeneralFurnish and install factory assembled evaporative condenserof induced draft counterflow design with a horizontal multi-ple side air entry and a vertical air discharge.The unit shall be completely factory assembled and conformto the specifications and schedules.

The condenser shall reject ______ kW of heat with_______asrefrigerant and _____°C condensation temperature at a wetbulb temperature of _____ °C .

The total fan power should not exceed ______kW.The total pump power should not exceed _____ kW.

The total overall unit dimensions should not exceed thefollowing:Length: _____ mm Width: _____ mm Height: _____ mm

The maximum operating weight should not exceed _____ kg.

The unit will be delivered in two parts: the bottom basin -louver section and the heat transfer - fan section.The unit (top and bottom section) shall be joined togetherwith elastic sealer and bolted together with corrosion resis-tant fasteners.

Approved manufacturer Evapco – model ATC-E ________

Thermal Performance – Performance Warranty The tower shall be capable of performing the thermal dutiesas shown in the schedule and on drawings and its designthermal rating shall be guaranteed by the manufacturer.

Applicable Standards CTI ATC 128 Test Code for Measurement of Sound fromWater Cooling Towers

Submittalsa) The manufacturer shall submit a five year history of the

proposed type of evaporative condenser with a minimumof 10 installations for similar sized equipment.

b) Shop drawings: submit shop drawings indicatingdimensions, weight loadings and required clearances.

c) Product data: submit manufacturers technical product data, original selection printouts and clearancerequirements.

d) Complete noise data sheet for the selected evaporative condenser(s).

e) Maintenance data for the evaporative condenser(s) and accessories.

f) The manufacturer shall provide factory test runcertificates of the fans and fan motor.

Product Delivery – Storage and Handlinga) a)The contractor shall make the provisions for proper

storage at site before installation and handle theproduct per the instructions of the manufacturer.

b) Once installed provide the necessary measures to keep units clean and protected from any dust and mechanical damage.

Quality Assurancea) The manufacturer shall have a quality assurance system

in place which is certified by an accredited registrar and complying with the requirements of ISO 9001. This is to guarantee a consistant level of product and service quality.

b) Manufacturers without ISO 9001 certification are not acceptable.

Warranty a) The products will be warranted for a period of minimum

two years from the date of shipment.

PRODUCTConstruction – Corrosion Resistance a) The structure and all steel elements of the pan and

casing shall be constructed of Z 725 hot dip galvanized steel for long life and durability. Alternatives with lower zinc layer thickness and external paint or coating are notaccepted as equal.

b) The strainer shall be made of stainless steel type 304. c) During fabrication all panel edges shall be coated with a

95% pure zinc compound. d) Casing materials shall be of non flammable construction only.

OPTIONAL EXECUTION – BASIN IN AISI 304 Construction – Corrosion Resistance a) The structure and all steel elements of the Basin and

Louver section up to the water level shall be made ofstainless steel AISI 304. Cold water basin will be a weldedstainless steel construction.

b) Alternatives with hot dip galvanized steel and epoxy coatings in lieu of the stainless steel AISI 304 are notconsidered to be equal and are not accepted.

c) All other steel components of the casing shall beconstructed of Z 725 hot dip galvanized steel for long life and durability. Alternatives with lower zinc layer thickness and external paint or coating or FRP materials are not accepted as equal.

d) The strainer shall be made of stainless steel AISI 304. e) During fabrication all galvanized steel panel edges shall

be coated with a 95 % pure zinc compound. f) Casing materials shall be of non flammable

construction only.

OPTIONAL EXECUTION – COMPLETE UNIT INSTAINLESS STEEL AISI 304 (except heat exchange coil(s))

Construction – Corrosion Resistancea) The structure and all steel elements shall be made of

AISI 304. Cold water basin will be a welded stainlesssteel construction.

b) Alternatives with hot dip galvanized steel and epoxy coatings in lieu of the AISI 304 are not considered to be equal and are not accepted.

c) The strainer shall be made of stainless steel AISI 304.d) Casing materials shall be of non flammable construction only.

Evaporative Condenser Basin a) Standard basin accessories include: overflow, drain,

strainer and brass make up valve with plastic float ball.b) The strainer shall be made of AISI 304.c) The entire pan area shall incorporate a sloped and

stepped basin design to prevent sediment built up,biological film and standing water.

d) Upper and lower basin bottoms shall be sloped toprovide drainage of the complete basin section.

e) The basin can be inspected while the unit is in operation with the fan(s) and pump(s) running.

Air Inlet Louvers a) The air inlet louvers shall be constructed of UV inhibited

polyvinyl chloride (PVC), mounted in easily removable frames for easy access to the basin.

b) The louvers shall be at four sides to provide easy access to the basin interior.

c) The louvers shall have a minimum of two changes in air direction to prevent splash out and block direct sunlight from entering the basin.

d) The louvers will have a 19 mm opening to prevent debrisfrom entering the basin.

Casing Section Heat Transfer Coil a) The evaporative condenser shall use internally enhanced

heat exchange coils of an elliptical tube design to obtain lower air flow resistance and allow higher water loadings around the tubes.

FACTORY FABRICATED INDUCED DRAFT ATC-E EVAPORATIVE CONDENSER

Page 34: DELIVERING Q F OCUSED ON PERFECTION · During fabrication, all panel edges are coated with a 95% pure zinc-rich compound for extended corrosion resistance. ... The innovative design

34

SPECIFICATIONS

SPECIFICATIONS

b) The heat transfer coil(s) shall be made of all primesurface, encased in a steel framework and hot dipgalvanized after fabrication as a complete assembly.

c) The tubes shall be arranged in a self spacing, staggered pattern in the direction of air flow for maximum heat transfer efficiency and minimum pressure drop.

d) The heat exchange coils shall be air pressure tested under water.

e) The design and manufacturing process shall be approvedand in accordance with the “Pressure Equipment Directive “ – PED 97 / 23 EC.

f) The manufacturer shall be responsible for themanufacturing and performance testing of the entire heat transfer coil. This is to assure single sourceresponsibility.

g) The casing shall totally encase the complete coil section to protect the complete coil from direct atmospheric contact.

Water Distribution a) The water distribution system shall be completely

enclosed and protected from sunlight exposure,environmental elements and debris. Water distribution systems with direct exposure to the environment are not allowed.

b) The spray header and branches shall be constructed of Schedule 40, Polyvinyl Chloride (PVC) pipe forcorrosion resistance.

c) The water shall be distributed over the coil by precision molded ZM II™ spray nozzles with large minimum orificeopenings and integral sludge ring to eliminate clogging.

d) The nozzles shall be threaded into the water distributionpiping to assure positive positioning and easy removal for maintenance. Snap in or strapped on nozzles are not accepted.

Water Circulation Pump a) The pump(s) shall be a close coupled , centrifugal type

with mechanical seal , installed vertically at the factory to allow free drainage on shut down.

b) A ____ kW totally enclosed motor(s) suitable for outdoor service shall be furnished.

c) The motor shall be suitable for the following powersupply: ____volts, ____hertz and ____ phase and ____ kW.

Drift Eliminators a) The drift eliminators shall be constructed of entirely inert

polyvinyl (PVC) that has been specially treated to resist ultra violet light.

b) Assembled in easily handled sections, the eliminator blades shall be spaced on 25 mm centers and shallincorporate three changes in air direction to assureefficient removal of entrained moisture from thedischarge air stream.

c) The maximum drift rate shall not exceed 0,001 % of the circulating water rate.

d) The drift eliminators shall be Eurovent OM-14-2009certified.

Access Door a) A large hinged access door shall provide access to the

fan section for maintenance.

Mechanical EquipmentAxial Propeller Fan(s) (Standard)a) Fan shall be heavy duty wide chord axial propeller type,

statically balanced and constructed of extrudedaluminum alloy blades.

b) Fans shall be installed in a closely fitted cowl withventuri air inlet for maximum fan efficiency.

c) The fans shall utilize a soft connect blade to hub design, compatible with variable speed drives, to avoidtransmission of vertical forces to the unit structure.

d) Each fan blade shall be individually adjustable.e) The fan cowl shall be covered with a heavy gauge hot

dip galvanized steel wire fan guard.

f) The fan – drive system (fan – drive – motor) shall befactory mounted, adjusted and undergo a trial run in thefactory before shipment.

Axial Propeller Fan(s) - Low Sound Fan (Alternative)a) Fan shall be heavy duty wide chord axial propeller type,

statically balanced and constructed of extrudedaluminum alloy blades.

b) Fans shall be installed in a closely fitted cowl withventuri air inlet for maximum fan efficiency.

c) The fans shall utilize a soft connect blade to hub design, compatible with variable speed drives, to avoidtransmission of vertical forces to the unit structure.

d) Each fan blade shall be individually adjustable.e) The fan cowl shall be covered with a heavy gauge hot

dip galvanized steel wire fan guard.f) The fan – drive system (fan – drive – motor) shall be

factory mounted, adjusted and undergo a trial run in thefactory before shipment.

Axial Propoller Fan(s) - Super Low Sound Fan (Alternative) a) Fan shall be extremely wide chord axial, one piece heavy

duty propeller type, statically balanced and made of FRP.b) Fans will be installed in a closely fitted cowl with venturi

air inlet for maximum fan efficiency.c) The fan cowl shall be covered with a heavy gauge hot

dip galvanized steel wire fan guard.d) The fan – drive system (fan – drive – motor) shall be

factory mounted, adjusted and undergo a trial run inthe factory before shipment.

e) The fans are high efficiency and operate with no loss of thermal performance

Bearings and Drivea) The fan shaft (s) shall be supported by heavy duty, self

aligning ball type bearings with cast iron housings.b) The bearings shall be rated for an L-10 life of 75000 hours.c) The fan drive sheaves shall be aluminum alloy.d) The belt shall be a multigroove belt system, constructed

of neoprene with polyester cords and designed for150% of the motor nameplate horsepower.

e) The grease fittings shall be extended to a location just inside the access door.

Motor (1.2 and 2.4 meter wide Models)a) The fan motor shall be Totally Enclosed Fan Cooled

(TEFC), squirrel cage, ball bearing type motor. b) The motor shall be specially designed for cooling tower

use with moisture protection on the winding, shaft and bearings.

c) The motor shall be minimum IP 55 degree of protection, Class F insulation, Service Factor 1 and selected for the appropriate cooling tower duty and the correct ambient temperature but minimum 40°C.

d) Motors bearings shall be double sealed non-relubricable or external grease nipples shall be provided.

e) The motor shall be mounted on an adjustable heavy duty steel motor base.

f) A hinged protective cover shall shield the motor and sheave from the weather.

g) The motor power supply shall be ____ volts, ____ hertz and ___ phase.

Motor (3 and 3.6 meter wide Models) a) The fan motor shall be Totally Enclosed Air Over (TEAO),

squirrel cage, ball bearing type motor. b) The motor shall be specially designed for cooling tower

use with moisture protection on the windings, shaft and bearings.

c) The motor shall be minimum IP 55 degree of protection, Class F insulation, Service Factor 1 and selected for the appropriate cooling tower duty and the correct ambient temperature but minimum 40°C.

d) Motor bearings shall be double sealed non-relubricable or external grease nipples shall be provided.

e) The motor shall be mounted on an adjustable heavy

Page 35: DELIVERING Q F OCUSED ON PERFECTION · During fabrication, all panel edges are coated with a 95% pure zinc-rich compound for extended corrosion resistance. ... The innovative design

35

SPECIFICATIONS

SPECIFICATIONS

duty steel motor base.f) The motor base shall be able to swing to the outside of

the unit for repair or removal. g) The motor power supply shall be ____ volts, ____ hertz

and ____ phase.

Sound LevelsSound LevelThe maximum sound pressure levels (dB) measured 1.5 m 45°from the top of the evaporative condenser operating at fullfan speed shall not exceed the sound levels detailed below.

Location 63 125 250 500 1000 2000 4000 8000 dB(A)Hz Hz Hz Hz Hz Hz Hz Hz

Fan dischargeAir inlet / end

ACCESSORIES (Optional)

Electric Heatersa) The evaporative condenser cold water basin shall be

provided with an electric heater package to prevent freezing of the water in the cold water basin, when the pump is shut down.

b) The electric heater package includes: electric heater element(s), thermostat and low water level cutoff.

c) The heaters shall be selected to maintain 4 °C basin water temperature at ____ °C ambient

d) The heater(s) shall be ____V / ____ phase / ____ Hzelectric power supply.

Three Probe Electric Water Level Control Package a) The evaporative condenser manufacturer shall provide

an electric water level control package instead of the mechanical float valve arrangement.

b) The package consist of the following elements :• Multiple heavy duty stainless steel 316 static sensors

mounted in a stilling chamber outside the unit.Electrodes or sensors mounted inside the unit are notaccepted as their operation will be disturbed by themoving water in the basin.

• An ABS, IP 56 case contains all the contactors for thedifferent level probes and will provide an output sig-nal of a relay for automatic filling and one relay foralarm level.

• The power supply to the control package is 24 Vac /230 Vac - ____ Hz .

• A weather protected solenoid valve (PN16) for thewater make up ready for piping to a water supplywith pressure between 140 kPa and 340 kPa.

Vibration Switcha) A vibration limit switch shall be installed on the

mechanical equipment support and wired into the control panel. The purpose of this switch is to interrupt power to the motor in the event of excessive vibration.

b) The switch shall be adjustable for sensitivity and shall require manual reset.

Service Platforma) The evaporative condenser shall be supplied with an

external service platform.b) The external service platform will be self supporting and

include access ladders and safety cage to the platform. c) The external service platform will be installed in front of

the fan access doors. d) The platform shall meet OSHA - CE requirements.

Motor Davita) The evaporative condenser shall be supplied with a motor

davit to facilitate the removal of fan motor(s) and fan(s).b) The davit and braket are constructed of aluminum and

are mounted on the side of the unit.c) The fan motor davit ships loose with the unit and is

installed in the field.

Water Silencera) The water silencers are located in the falling water area

of the cold water basin.b) The water silencers will reduce the overall sound levels

4 dB (A) to 7 dB (A) measured at 1.5 m from the side or end of the unit, when the fans are running, and 9 dB (A)

to 12 dB (A) when fans are off. c) The water silencers are constructed of lightweight PVC

sections and can be easily removed for access to the basin area.

d) The water silencers will have no impact on the unit’s thermal performance.

Page 36: DELIVERING Q F OCUSED ON PERFECTION · During fabrication, all panel edges are coated with a 95% pure zinc-rich compound for extended corrosion resistance. ... The innovative design

Evapco Products are Manufactured Worldwide

EVAPCO, Inc. - World Headquarters & Research / Development Center

EVAPCO, Inc.World HeadquartersP.O. Box 1300Westminster, MD 21158 USAPh: 410-756-2600 - Fx: [email protected]

EVAPCO East5151 Allendale LaneTaneytown, MD 21787 USAPh: 410-756-2600 - Fx: [email protected]

EVAPCO Midwest1723 York RoadGreenup, IL 62428 USAPh: 217-923-3431 - Fx: [email protected]

EVAPCO West1900 West Almond AvenueMadera, CA 93637 USAPh: 559-673-2207 - Fx: [email protected]

EVAPCO Iowa925 Quality DriveLake View, IA 51450 USAPh: 712-657-3223 - Fx: 712-657-3226

EVAPCO IowaSales & Engineering215 1st Street, NEP.O. Box 88Medford, MN 55049 USAPh: 507-446-8005 - Fx: [email protected]

EVAPCO Newton701 East Jourdan StreetNewton, IL 62448 USAPh: 618-783-3433 - Fx: [email protected]

EVAPCOLD521 Evapco DriveGreenup, IL 62428 USAPh: [email protected]

EVAPCO-Dry Cooling, Inc.981 US Highway 22 WestBridgewater, NJ 08807 USAPh: [email protected]

Refrigeration Valves &Systems CorporationA wholly owned subsidiary of EVAPCO, Inc.1520 Crosswind Dr.Bryan, TX 77808 USAPh: 979-778-0095 - Fx: [email protected]

Evapco Northwest5775 S.W. Jean Road, Suite 104Lake Oswego, OR 97035 USAPh: 503-639-2137 - Fx: 503-639-1800

EvapTech, Inc.A wholly owned subsidiary of EVAPCO, Inc.8331 Nieman RoadLenexa, KS 66214 USAPh: 913-322-5165 - Fx: [email protected]

Tower Components, Inc.A wholly owned subsidiary of EVAPCO, Inc.5960 US HWY 64ERamseur, NC 27316Ph: 336-824-2102 - Fx: [email protected]

South America

Evapco BrasilEquipamentos Industriais LtdaRua Alexandre Dumas 160104717-004 Sao Paulo - SP - BrazilPh: (55) 11-5184-0067

EVAPCO Europe BVBAEuropean HeadquartersHeersterveldweg 19, Industrieterrein Oost3700 Tongeren, BelgiumPh: (32) 12-395029 -Fx: (32) [email protected]

EVAPCO Europe, S.r.l.Via Ciro Menotti 10I-20017 Passirana di Rho, Milan, ItalyPh: (39) 02-939-9041- Fx: (39) [email protected]

EVAPCO Europe, S.r.l.Via Dosso 2 - 23020 Piateda Sondrio, Italy

EVAPCO Europe, GmbHInsterburger Straße, 18D-40670 Meerbusch, GermanyPh: (49) 2159-69560 - Fx: (49) [email protected]

EVAPCO Middle East DMCCReef Tower, 29th Level, Cluster O,Jumeirah Lake Towers, P.O. Box 5003310Dubai, United Arab EmiratesPh: (971) 4448-7242 - Fx: (971) [email protected]

EVAPCO Air Solutions a/sA wholly owned subsidiary of EVAPCO, Inc.Knøsgårdvej 115, 9440 Aabybro, DenmarkPh: (45) 9824-4999 - Fx: (45) 9824-4990 [email protected]

EVAPCO S.A. (Pty.) Ltd.A licensed manufacturer of Evapco, Inc.18 Quality Rd, Isando 1600, Rep. of S. AfricaPh: (27) 11 392-6630 - Fx: (27) [email protected]

Evap Egypt Engineering Industries Co.A licensed manufacturer of Evapco, Inc.5 Al Nasr Road St., Nasr City, Cairo, EgyptPh: (20) 2-24022866 / (20) 2-24044997/8Fx: (20) 2-404-4667/ Mob: (20) [email protected] / [email protected]

EVAPCO ChinaAsia/Pacific Headquarters1159 Luoning Rd. Baoshan Industrial ZoneShanghai, P. R. China, Postal Code: 200949Ph: (86) 21-6687-7786 - Fx: (86) [email protected]

Evapco (Shanghai) RefrigerationEquipment Co., Ltd.1159 Louning Rd., Baoshan Industrial ZoneShanghai, P.R. China, Postal Code: 200949Ph: (86) 21-6687-7786 - Fx: (86) [email protected]

Beijing EVAPCO RefrigerationEquipment Co., Ltd.Yan Qi Industrial Development DistrictHuai Rou CountyBeijing, P.R. China, Postal Code: 101407Ph: (86) 10 6166-7238 - Fx: (86) 10 [email protected]

EVAPCO Australia Pty Ltd.34-42 Melbourne Road - P.O. Box 436Riverstone, N.S.W. Australia 2765Ph: (61) 29 627-3322 - Fx: (61) 29 [email protected]

EvapTech Composites Sdn. BhdNo. 70 (Lot 1289) Jalan Industri 2/3Rawang Integrated Industrial ParkRawang, Selangor, 48000 MalaysiaPh: 60 3 6092-2209 - Fx: 60 3 6092-2210

EvapTech Asia Pacific Sdn. BhdA wholly owned subsidiary of EvapTech, Inc.IOI Business Park, 2/F Unit 20Persiaran Puchong Jaya SelatanBandar Puchong Jaya,47170 Puchong, Selangor, MalaysiaPh: +(60-3) 8070 7255 - Fx: +(60-3) 8070 [email protected]

North America

P.O. Box 1300 • Westminster, MD 21158 USAPh: +1 410-756-2600 • Fx: +1 410-756-6450 • [email protected]

Europe Asia/Pacífic

EVAPCO... Specialists in Heat Transfer Products and Services.Visit EVAPCO’s Websites at: www.evapco.eu / www.mrgoodtower.eu

World Headquarters/Research and Development Center

EVAPCO ManufacturingLocations

©2014 EVAPCO, Inc.

Bulletin 172-E Metric 0919