Delhi Building Bye Law Related Fire 11.1 No building shall be erected so as to deprive any other building of the means of access. 11.2 Every person who erects a building shall not at any time erect or cause or permit to erect or re-erect any building, which in any way encroaches upon or diminishes the area set apart as means of access. 11.3 For buildings identified in Bye-law No. 6.2.4.1, the following provisions of means of access shall be ensured 1. The width of the main street on which the building abuts shall not be less than 9 meters, 2. A building shall abut on a street or streets or upon spaces directly connected from the street by a hard surface approach road, width of which is not less than 9 meters, 3. If there are any bends or curves on the approach road, a sufficient width shall be provided at the curve to enable the fire appliances to turn, the turning circle being atleast of 9.0 m radius, 4. The approach road to the building and open spaces on its all sides (See Bye-law No. 12.4) unto 6 m width and the layout for the same shall be done in consultation with Chief Fire Officer, Delhi Fire Service and the same shall be of hard surface capable of taking the weight of Fire engine, weighing unto 1(18 tones. The said open space shall be kept free of obstructions and shall be motorable, 5. Main entrances to the premises shall be of adequate width to allow easy access to the fire engine and in no case it shall measure less than 5 meters. The entrance gate shall fold back against the compound wall of the premises, thus leaving the exterior access way within the plot free for movement of fire service vehicles. If archway is provided over the main entrance the height of the archway shall not be at a height less than 4 m, and 6. For multi-storeyed group housing schemes on one plot, the approach road shall be 9 m in width and between individual buildings; there shall be a space of 6 m around. 12.4 (B) For buildings identified in 8ye-law No. 6.2.4.1 the provisions of exterior open spaces around the buildings shall be as given below: S. No. Ht. of the building up to Exterior Open spaces to be left our on all sides* (front, rear and sides in each plot) 1. 10 m 3m 2. 15 m 5m

Delhi Building Bye Law Related Fire · 2019-05-28 · Delhi Building Bye Law Related Fire 11.1 No building shall be erected so as to deprive any other building of the means of access

  • Upload
    others

  • View
    6

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Delhi Building Bye Law Related Fire · 2019-05-28 · Delhi Building Bye Law Related Fire 11.1 No building shall be erected so as to deprive any other building of the means of access

DelhiBuildingByeLawRelatedFire

11.1Nobuildingshallbeerectedsoastodepriveanyotherbuildingofthemeansofaccess.

11.2Everypersonwhoerectsabuildingshallnotatanytimeerectorcauseorpermittoerector

re-erect anybuilding,which in anyway encroachesuponor diminishes the area set apart as

meansofaccess.

11.3ForbuildingsidentifiedinBye-lawNo.6.2.4.1,thefollowingprovisionsofmeansofaccess

shallbeensured

1. Thewidthofthemainstreetonwhichthebuildingabutsshallnotbelessthan9meters,

2. Abuildingshallabutonastreetorstreetsoruponspacesdirectlyconnected fromthe

streetbyahardsurfaceapproachroad,widthofwhichisnotlessthan9meters,

3. Ifthereareanybendsorcurvesontheapproachroad,asufficientwidthshallbeprovided

atthecurvetoenablethefireappliancestoturn,theturningcirclebeingatleastof9.0m

radius,

4. Theapproachroadtothebuildingandopenspacesonitsallsides(SeeBye-lawNo.12.4)

unto6mwidthandthelayoutforthesameshallbedoneinconsultationwithChiefFire

Officer, Delhi Fire Service and the same shall be of hard surface capable of taking the

weightofFireengine,weighingunto1(18tones.Thesaidopenspaceshallbekeptfreeof

obstructionsandshallbemotorable,

5. Mainentrancestothepremisesshallbeofadequatewidthtoalloweasyaccesstothefire

engineandinnocaseitshallmeasurelessthan5meters.Theentrancegateshallfoldback

againstthecompoundwallofthepremises,thusleavingtheexterioraccesswaywithin

theplotfreeformovementoffireservicevehicles.Ifarchwayisprovidedoverthemain

entrancetheheightofthearchwayshallnotbeataheightlessthan4m,and

6. Formulti-storeyedgrouphousingschemesononeplot,theapproachroadshallbe9min

widthandbetweenindividualbuildings;thereshallbeaspaceof6maround.

12.4 (B) Forbuildings identified in8ye-lawNo. 6.2.4.1 theprovisionsof exterioropen spaces

aroundthebuildingsshallbeasgivenbelow:

S.No.

Ht.ofthe

buildingupto

ExteriorOpenspacestobeleftouronallsides*(front,rearandsidesineachplot)

1. 10m 3m

2. 15m 5m

Page 2: Delhi Building Bye Law Related Fire · 2019-05-28 · Delhi Building Bye Law Related Fire 11.1 No building shall be erected so as to deprive any other building of the means of access

S.No.

Ht.ofthe

buildingupto

ExteriorOpenspacestobeleftouronallsides*(front,rearandsidesineachplot)

3 18m 6m

4 21m 7m

5 24m 8m

6 27m 9m

7 30m 10m

8 35m 11m

9 40m 12m

10 45m 13m

11 50m 15m

1255mandabove

16m

12.7

1. Themaximumheightofbuildingshallnotexceed1.5timesthewidthofroadabuttingplus

thefrontopenspaces.

2. Ifabuildingabutsontwoormorestreetsofdifferentwidths,thebuildingshallbedeemed

tofaceuponthestreetthathasthegreaterwidthandtheheightofthebuildingshallbe

regulatedbythewidthofthestreetandmaybecontinuedtothisheighttoadepthof24

malongthenarrowerstreetsubjecttoconformityofBye-lawNo.12.4

14.12Basement

14.12.1TheconstructionofthebasementshallbeallowedbytheAuthorityinaccordancewith

thelanduseandotherprovisionsspecifiedundertheMasterPlan.*

14.12.1.1Wheretheuse,setbacksandcoverageisnotprovidedintheMasterPlanprovisions,

thesameshallbeallowedtobeconstructedintheplotleavingmandatorysetbacksandcanbe

puttoanyofthefollowinguses:

Page 3: Delhi Building Bye Law Related Fire · 2019-05-28 · Delhi Building Bye Law Related Fire 11.1 No building shall be erected so as to deprive any other building of the means of access

1. Storageofhouseholdorothergoodsofnon-flammablematerials;

2. Darkroom;

3. Strongrooms,bankcellarsetc.;

4. Air-conditioningequipmentandothermachinesusedforservicesandbuilding;

5. Parkingplacesandgarages;.

6. stackroomsoflibraries;and

7. Officeorcommercialpurposeprovideditisair-conditioned..

Note:Usesofbasementfrom14.12.1.1(i)to(vi)shallnotbereckonedforthepurposesofFAR

whereasforusesin14.12.1.1(vii),thebasementcoverageshallbereckonedforthepurposeof

F.A.R.**

14.12.1.2Thebasementshallnotbeusedforresidentialpurposes.

14.12.2Thebasementshallhavethefollowingrequirements:

1. Every basement shall be in every part at least 2.4 m in height from the floor to the

undersideoftheroofslaborceiling.

2. Adequateventilationshallbeprovidedforthebasement.Thestandardofventilationshall

bethesameasrequiredbytheparticularoccupancyaccordingtoBye-laws.Anydeficiency

maybemetbyprovidingadequatemechanical!Ventilationintheformofblowers,exhaust

fans(oneexhaustfanfor50sq.m.ofbasementarea),air-conditioningsystemetc.

3. Theminimumheightoftheceilingofanybasementshallbe0.9mandmaximumof1;2m

abovetheaveragesurroundinggroundlevel.

4. Adequate arrangement shall be made such that surface drainage does not enter the

basement.

5. Thewallsandfloorsofthebasementshallbewater-tightandbesodesignedthattheeffect

ofthesurroundingsoilandmoisture,ifany,aretakenintoaccountindesignandadequate

dampproofingtreatmentisgiven.

6. The access to the basement shall be separate from themain and alternate stair-case

providingaccessandexitfromhigherfloors.Wherethestaircaseiscontinuousthesame

Page 4: Delhi Building Bye Law Related Fire · 2019-05-28 · Delhi Building Bye Law Related Fire 11.1 No building shall be erected so as to deprive any other building of the means of access

shallbeenclosed typeservingasa fire separation fromthebasement floorandhigher

floors. Open ramps shall be permitted if they are constructedwithin the building line

subjecttotheprovisionof(iv).

7. Inthecaseofbasementsforofficeandcommercialoccupanciessufficientnumberofexit

waysandaccesswaysshallbeprovidedwithatraveldistancenotmorethan15m.

8. Thebasementshallnotbepartitioned.Incasethepartitionsinthebasementsareallowed

by the Authority, no compartment shall tie less than 500 sq. ft. in area and each

compartment shallhaveventilationstandardsas laiddown in sub-clause (ii) separately

and independently. The basement partitions shall however conform to the norms laid

downbytheChiefFireOfficerDelhi.

9. Kitchen,bathroomand toilet shall notbepermitted in thebasementunless the sewer

levelspermitthesameandthereisnochanceofbackflowandfloodingofsewerage.If

permitted,thisshallbeplacedagainstanexternalwallofthebasement(whichshallalso

beexternalwallofthebuilding)andshallbeadequatelylightedandventilated.Thearea

ofkitchen,bathroomandtoiletsopermittedinthebasementshallbecountedtowards

FARcalculations.

10. Akitchenwhenpermittedinthebasementshallbeequippedwithelectricovens,stoves,

gasorsimilarequipments.

*TheMasterPlan2001provisionsrelatingtobasementeregiveninAppendixJ.Alsosee

undercomments.

**Under theMPD2001asamendedon15.5.1995,basement is tobe included inFAR

calculations.

16.ExitRequirements

16.1General-Thefollowinggeneralrequirementsshallapplytoexits.

1. Everybuildingmeantforhumanoccupancyshallbeprovidedwithexitssufficienttopermit

safeescapeofoccupantsincaseoffireorotheremergency;

2. Ineverybuildingexits shall complywith theminimumrequirementof thispart,except

thosenotaccessibleforgeneralpublicuse;

Page 5: Delhi Building Bye Law Related Fire · 2019-05-28 · Delhi Building Bye Law Related Fire 11.1 No building shall be erected so as to deprive any other building of the means of access

3. Allexitsshallbefreeofobstructions;

4. Nobuildingsshallbealteredsoastoreducethenumber,widthorprotectionofexitsto

lessthanthatrequired;

5. Exitsshallbeclearlyvisibleandtheroutestoreachtheexitshallbeclearlymarkedand

signpostedtoguidethepopulationoffloorconcerned;

6. Allexitwaysshallbeproperlyilluminated;

7. Firefightingequipmentwhereprovidedalongexitsshallbesuitablylocatedclearlymarked

butmustnotobstructtheexitwayandyetthereshouldbeckindicationaboutitslocation

fromeithersideoftheexitway;

8. Alarmdevicesshallbeinstalledtoensurepromptevacuationofthepopulationconcerned

throughtheexits;

9. Allexitsshallprovidecontinuousmeansofegresstotheexteriorofabuildingor toan

exterioropenspaceleadingtoastreet;

10. Exits shall be so arranged that theymay be reachedwithout passing through another

occupiedunit,exceptinthecaseofresidentialbuildings.

16.2TypesofExits

1. Exitsshallbeeitherofhorizontalorverticaltype.Anexitmaybedoorway,corridor,and

passagewaystoaninternalstaircaseorexternalstaircase,rampsortoaverandahand/or

terraces,whichhaveaccesstothestreetortoroofofabuilding.Anexitmayalsoinclude

horizontalexitleadingtoanadjoiningbuildingatthesamelevel.

2. Liftsandescalatorsshallnotbeconsideredasexits.

16.3NumberandSizeofExits-Therequisitenumberandsizeofvariousexistsshallbeprovided,

basedonthepopulationineachroom,areaandfloorbasedontheoccupantload,capacityof

exits,traveldistanceandheightofbuildingsasperprovisionsofBye-LawsNos.16.3.1to16.3.3.

16.3.1ArrangementofExits-Exitsshallbesolocatedsothatthetraveldistanceonthefloorshall

notexceed22.Smforresidential,educational,institutionalandhazardousoccupanciesand30m

forassembly,business,mercantile,industrialandstorageoccupancies.Whenevermorethanone

Page 6: Delhi Building Bye Law Related Fire · 2019-05-28 · Delhi Building Bye Law Related Fire 11.1 No building shall be erected so as to deprive any other building of the means of access

exitisrequiredforafloorofbuilding,exitsshallbeplacedasremotefromeachotheraspossible.

Alltheexitsshallbeaccessiblefromtheentirefloorareaatallfloorlevels.

16.3.2OccupantLoad-Thepopulationinrooms,areasoffloorsshallbecalculatedbasedonthe

occupantloadgiveninthetablegivenbelow.

OccupantLoad:TABLE5*

S.No.

GroupofOccupancy

OccupantLoadGrossArea*insqm/person

1. Residential 12.5

2. Educational 4

3. Institutional 15**

4.

Assembly:(a)withfixedor

looseseatsanddancefloors

(b)withoutseatingfacilitiesincludingdinningrooms

0.6***l.5***

5.

Mercantile:(a)Streetfloorandsales

basement(b)Uppersalefloors

36

6.Businessand

Industrial10

7. Storage 30

8. Hazardous 10

*Thegrossareashallmeanplinthareaorcoveredarea.

Page 7: Delhi Building Bye Law Related Fire · 2019-05-28 · Delhi Building Bye Law Related Fire 11.1 No building shall be erected so as to deprive any other building of the means of access

**Occupantloadindormitoryportionsofhomesfortheaged,orphanages,insaneasylumsetc.

where sleeping accommodation is provided, shall be calculated y not less than 75-sqm gross

area/person.

***Thegrossareashallinclude,inadditiontothemainassemblyroomorspace,anyoccupied

connectionopenorspaceinthesamestoreyorinthestoreyaboveorbelow,whereentranceis

common to such rooms and spaced and they are available for use by the occupants of the

assemblyplace.Nodeductionsshallbemadeinthegrossareaforcorridors,closetsorothersub-

divisions;oneareashallincludeallspaceservingtheparticularassemblyoccupancy.

16.3.3 Capacityof Exits -The capacityof exits (doors and stairways) indicating thenumberof

personsthatcouldbesafelyevacuatedthroughaunitexitwidthof50cmshallbeasgivenbelow.

OccupantsPerUnitExitWidth:TABLE6

NUMBEROFOCCUPANTS

Sl.No

GroupofOccupancy Stairways Doorways/HorizontalExit

1 Residential 25 75

2 Educational 25 75

3 Institutional 25 75

4 Assembly 60 90

5 Business 50 75

6 Mercantile 50 75

7 Industrial 50 75

8 Storage 50 75

9 Hazardous 25 40

Notes:

1. SprinklerAllowances-

Page 8: Delhi Building Bye Law Related Fire · 2019-05-28 · Delhi Building Bye Law Related Fire 11.1 No building shall be erected so as to deprive any other building of the means of access

Whenabuilding isprotectedwithautomaticsprinklersystemandsuchasystemisnot

requiredspecificallybytheCode,thecapacityperstoreyperunitwidthofexitofstairways

inTable6maybeincreasedby5O%.

2. HorizontalExitAllowance-

Whenhorizontalexitisprovidedinbuildingofmercantile,storage,industrial,businessand

assemblyoccupancies,thecapacityperstoreyperunitwidthofexitofstairwaysinTable

6maybeincreasedby50%andinbuildingsofinstitutionaloccupancyby100%.

3. CombineTotalAllowance-

Whenbothautomaticsprinklersandhorizontalexistsareprovided,thecapacityperunit

widthofexitofstairwaysmaybedoublethevaluesspecifiedinTable6.

16.3.4ForbuildingidentifiedinBye-lawNo.6.2.4.1,thereshallbeaminimumoftwostaircase

andonefothemshallbeanenclosedstairwayandtheothershallbeontheexternalwallsof

buildings and shall opendirectly to the exterior, interior open spaceor to anyopenplaceof

safety.

16.3.5NotwithstandingthedetailedprovisionforexitsasperBye-lawNos.16.3.1to16.3.3,the

followingminimumwidthprovisionsshallbemadeforeachstairways:

1. (i) Residential building upto 3-1/2 storey ht. 0.9m

(ii)Otherresidentialbuildinge.g.hotels,flats,grouphousingetc.1.25m

2. Assemblybuildingslikeauditorium,theatresandcinemas1.5m

3. Allotherbuildings1.25m

4. Institutionalbuildingslikehospitals2.0m

5. Educationalbuildingslikeschools,colleges1.5m

16.3.6Notwithstandingthedetailedprovisionsasperbye-lawNos.16.3to16.3.3,thefollowing

minimumwidthprovisionsshallbemadeforeachpassageway:

1. (i) residential buildings, dwelling unit type 0.9m

(ii)residentialbuildingse.g.hostels,hotelsetc.1.25m

2. assemblybuildingslikeauditorium,theatresandcinemas1.5m

3. allotherbuildings1.25m

Page 9: Delhi Building Bye Law Related Fire · 2019-05-28 · Delhi Building Bye Law Related Fire 11.1 No building shall be erected so as to deprive any other building of the means of access

16.4.1Doorways

1. Everydoorwaysshallopenintoanenclosedstairway,ahorizontalexit,onacorridoror

passagewayprovidingcontinuousandprotectedmeansofegress.

2. Noexitdoorwayshallbelessthan100cminwidth.Doorwaysshallbenotlessthan200cm

doorway shall be less than 100cm inwidth.Doorways shall be not less than 200cm in

height.Doorwaysforbathrooms,watercloset,storesetc.shallbenotlessthan75cmwide.

3. Exitdoorwaysshallopenoutwards,thatis,awayfromtheroombutshallnotobstructthe

travelalonganyexit.Nodoor,whenopened,shallreducetherequiredwidthofstairway

orlandingtolessthan90cm,overheadorslidingdoorsshallnotbeinstalled.

4. Exitdoorshallnotopenimmediatelyuponaflightorstairs;alandingequaltoatleastthe

widthofthedoorshallbeprovidedinthestairwayateachdoorway,leveloflandingshall

bethesameasthatofthefloorwhichitserves.

5. Exitdoorwaysshallbeopenablefromthesidewhichtheyservewithouttheuseofakey.

16.4.2RevolvingDoors

1. Revolving doors shall not be used as required exits except in residential, business and

mercantileoccupancies,butshallnotconstitutemorethanhalf thetotalrequireddoor

width.

2. Whenrevolvingdoorsareconsideredasrequiredexistwaythefollowingassumptionsshall

bemade-

1. eachrevolvingdoorshallbecountedonehalfaunitexitwidth.

2. Revolvingdoorsshallnotbelocatedatthefootofastairway.Anystairwayserved

byarevolvingdoorshalldischargethroughlobbyorfoyer.

16.4.3Stairways

1. Interiorstairsshallbeconstructedofnon-combustiblematerialsthroughout.

2. Interior staircase shall be constructed as a self contained unit with at least one side

adjacent toanexternalwallandshallbecompletelyenclosed.Forbuildingsmorethan

15mheight,allstaircasesshallbeenclosed.

Page 10: Delhi Building Bye Law Related Fire · 2019-05-28 · Delhi Building Bye Law Related Fire 11.1 No building shall be erected so as to deprive any other building of the means of access

3. Astaircaseshallnotbearrangedroundaliftshaftunlessthelatterisentirelyenclosedby

amaterialoffire-resistanceratingasthatfortypeofconstructionitself.Forbuildingsmore

than15minheight,thestaircaselocationshallbetothesatisfactionofChieffireOfficer,

DelhiFireService.

4. Hollowcombustibleconstructionshallnotbepermitted.

5. Theminimumwidthofinternalstaircaseshallbe1.00mandasgiveninBye-lawNo.16.3.5

6. Theminimumwidthoftreadswithoutnosingshallbe25cmforaninternalstaircasefor

residentialbuildings.Inthecaseofotherbuildingstheminimumtreadshallbe30cm.The

treadsshallbeconstructedandmaintainedinamannertopreventslipping.Windersshall

beallowedinresidentialbuildingsprovidedtheyarenotattheheadofadownwardflight.

7. Themaximumheightofrisershallbe19cminthecaseofresidentialbuildingsand15cm

inthecaseofotherbuildings.Theyshallbelimitedto12perflight.

8. Handrailsshallbeprovidedwithaminimumheightof90cmfromthecenterofthetread.

9. The minimum headroom in a passage under the lading of a staircase and under the

staircaseshallbe2.2m.

10. Forbuildingsmore than24mhigher, access tomain staircase shall begained through

atleasthalfanhourfireresistingautomaticclosingdoorsplacedintheenclosingwallsof

thestaircases.Itshallbeaswingtypedooropeninginthedirectionoftheescape.

11. Nolivingspace,storeorotherfireriskshallopendirectlyintothestaircaseorstaircases.

12. Externalexitdoorofstaircaseenclosureatgroundlevelshallopendirectlytotheopen

spacesorcanbereachedwithoutpassingthroughanydoorotherthanadoorprovidedto

formadraughtlobby.

13. Theexitsignwitharrowindicatingthewaytotheescaperouteshallbeprovidedataheight

of0.5mfromthefloorlevelonthewallandshallbeilluminatedbyelectriclightconnected

to corridor circuits.All existwaymarking signs shouldbe flushedwith thewall and so

designedthatnomechanicaldamageshalloccurtothemduetomovingoffurnitureor

otherheavyequipments.Furtherall landingsof floor shallhave floor indicationboards

indicatingthenumberoffloorasperBye-lawNo.2.35.Thefloorindicationboardshallbe

Page 11: Delhi Building Bye Law Related Fire · 2019-05-28 · Delhi Building Bye Law Related Fire 11.1 No building shall be erected so as to deprive any other building of the means of access

placedonthewallimmediatelyfacingtheflightofstairsandnearesttothelanding.Itshall

beofsizenotlessthan0.5x0.5m

14. Individualfloorshallbeprominentlyonthewallfacingthestaircase.

15. Incaseofsinglestaircaseitshallterminateatthegroundfloorlevelandtheaccesstothe

basement shall be by a separate staircase.However, the second staircasemay lead to

basement levels provided the same is separated at ground level by either a ventilated

lobbywithdischargepointsattwodifferentendsorthroughenclosures[SeeBye-lawNo.

14.22(vii)]

16.4.2FireEscapesorExternalStairs

1. Fireescapesshallnotbetakenintoaccountincalculatingtheevacuationtimeofabuilding.

2. Allfireescapesshallbedirectlyconnectedtotheground.

3. Entrancetofireescapeshallbeseparateandremotefromtheinternalstaircase.

4. Theroutetofireescapeshallbefreeofobstructionsatalltimes,exceptadoorwayleading

tothefireescapewhichshallhavetherequiredfireresistance.

5. Fireescapeshallbeconstructedofnon-combustiblematerials.

6. Fireescapesstairsshallhavestraightflightnotlessthan75cmwidewith25cmtreadsand

risersnotmorethan19cm.Thenumberofrisersshallbelimitedto16perflight.

7. Handrailsshallbeofaheightnotlessthan90cm.

16.4.5SpiralStairs(fireescape)-Theuseofspiralstaircaseshallbelimitedtolowoccupantload

andtoabuildingofheight9munlesstheyareconnectedtoplatforms,suchasbalconiesand

terracestoallowescapestopause.

A spiral fire escape shall be not less than 150cm in diameter and shall be designed to give

adequateheadroom.

16.4.6Ramps

1. Rampswithaslopeofnotmorethan1in10maybesubstitutedforandshallcomplywith

alltheapplicablerequirementsofrequiredstairwayastoenclosure,capacityandlimiting

dimensions.,Largeslopesshallbeprovidedforspecialusesbutinnocasegreaterthan1

Page 12: Delhi Building Bye Law Related Fire · 2019-05-28 · Delhi Building Bye Law Related Fire 11.1 No building shall be erected so as to deprive any other building of the means of access

in8.Forallslopesexceeding1 in10andwheretheuse issuchasto involvedangerof

slipping,therampshallbesurfacedwithapprovednon-slippingmaterial.

2. Theminimumwidthoftherampsinhospitalsshallbe2.25m.

3. Handrailsshallbeprovidedopnbothsidesoftheramp.

4. Rampsshallleaddirectlytooutsideopenspaceatgroundlevelorcourtyardsorsafeplace.

5. Forbuildingabove24minheight,accesstorampsfromanyfloorofthebuildingshallbe

throughsmokestopdoor.

16.4.7Corridors

1. Theminimumwidthofacorridorinaresidentialbuildingshallbe1.0mandinallother

buildingsshallbe1.5m

2. Incaseofmorethanonemainstaircaseofthebuildinginter-connectedbyacorridoror

otherenclosedspace,thereshallbeatleastonesmokestopdooracrossthecorridoror

enclosedspacebetweenthedoorsintheenclosingwallsofanytwostaircases.

16.4.8RefugeArea-Forallbuildingsexceeding15minheight,refugeareashallbeprovidedas

follows:

1. for floorsabove15mandupto24m-onerefugeareaonthe floor immediatelyabove

18m.

2. forfloorsabove24mandupto36m-onerefugeareaonthefloorimmediatelyabove24m.

3. forfloorsabove36m-onerefugeareapereveryfivefloorsabove36m

16.4.8.1Refugeareashallbeprovidedontheexternalwallsascantileverprojectionsorinany

othermanner(whichwillnotbecoveredinFAR)withaminimumareaof15sqmtr.Andtobe

calculatedbasedonthepopulationoneachfloorattherateof1sq.m.perperson.

16.4.9Lifts

1. Allthefloorsshallbeaccessiblefor24hoursbythelifts.Theliftsprovidedinthebuildings

shallnotbeconsideredasameansofescapeincaseofemergency.

Page 13: Delhi Building Bye Law Related Fire · 2019-05-28 · Delhi Building Bye Law Related Fire 11.1 No building shall be erected so as to deprive any other building of the means of access

2. Groundingswitchatgroundfloorleveltoenablethefireservicetogroundtheliftincase

ofanemergencyshallalsobeprovided.

3. Theliftmachineroomshallbeseparateandnoothermachineryshallbeinstalledtherein.

17FireProtectionRequirements

17.1Buildingsshallbeplanned,designedandconstructedtoensurefiresafetyandthisshallbe

done in accordance with para IV Fire Protection of national Building code of India, unless

otherwisespecifiedinthesebye-laws.Inthecaseofbuildings(identifiedinBye-lawsNo.6.2.4.1),

thebuildingschemesshallalsobeclearedbytheChiefFireOfficer,DelhiFireService.

17.2TheadditionalProvisionsrelatedtofireprotectionofbuildingsmorethan15misheightand

buildingsidentifiedinBye-lawNo.6.2.4.1,shallbeasgiveninAppendix-K

APPENDIX K

(Bye-LawNo.17.1)

AdditionalFireProtectionRequirementsforBuildingsmorethan15m.inHeight&Buildingsas

CoveredbyBye-lawNo.6.2.4.1

K-1General

K-1.1.InadditiontotheprovisionsofpartIVFireProtectionofNationalBuildingCodeofIndia,

theChiefFireOfficer,DelhiFireServicemayinsistonsuitableprovisionsinthebuildingsfromfire

safetyandfirefightingpointofviewdependingontheoccupancyandheightofbuildings.

K-2StaircaseEnclosures

K-2.1TheinternalenclosingwallsofstaircaseshallbeofbrickorR.C.C.constructionhavingfire

resistanceofnotlessthantwohours.Allenclosedstaircasesshallhaveaccessthroughself-closing

doors of at least half-hour fire resistance- These shall be single swing doors opening in the

directionoftheescape.Thedoorshallbefittedwithcheckactiondoorclosers.

K-2.2Thestaircaseenclosureonexternalwallofthebuildingshallbeventilatedtoatmosphere

ateachlanding.

K-2.3Permanentventatthetopequalto5%ofthecrosssectionalareaoftheenclosureand

openablesashes'ateach floor levelwithareaequal to15%of thecrosssectionalareaof the

enclosureofexternalwallshallbeprovided.Theroofoftheshaftshallbeatleastlmabovethe

surrounding roof. There shall be no glazing or glass bricks in any internal enclosingwall of a

Page 14: Delhi Building Bye Law Related Fire · 2019-05-28 · Delhi Building Bye Law Related Fire 11.1 No building shall be erected so as to deprive any other building of the means of access

staircase.1fthestaircaseisinthecoreofthebuildingandcannotbeventilatedateachlanding,

apositivepressureof5-mm.w.g.byanelectricallyoperatedblower/blowersshallbemaintained.

K-2.4Themechanismforpressurizingthestaircaseshaftshallbesoinstalledthatthesameshall

operateautomaticallyandalsowithmanualoperationfacilities,whentheautomaticfirealarm

(SeeBye-lawNo.K.11)operates.

K-3LiftEnclosures

K-3.1Thewallsenclosingliftshaftsshallhaveafireresistanceofnotlessthantwohours.Shafts

shallhavepermanentventsatthetopnotlessthan1800sq.mm.incleararea.Liftmotorrooms

preferablybesitedatthetopoftheshaftandshallbeseparatedfromliftshaftsbytheenclosing

walloftheshaftorbythefloorofthemotorrooms.

K-3.2Landingdoorsinliftenclosuresshallopenintheventilatedorpressurizedcorridor/lobby

andshallhavefireresistanceofnotlessthanonehour.

K-3.3Thenumberofliftsinoneliftbankshallnotexceedfour.Shaftforfireliftinaliftbankshall

beseparatedfromeachotherbyabrickmasonryorRCCwalloffireresistanceofnotlessthan

twohours.

K-3.4Iftheliftshaftandliftlobbyareinthecoreofthebuildingapositivepressureofnotless

than2.5mmandnotmorethan3mm.w.g.byanelectricallyoperatedblowershallbemaintained

intheliftlobbyandpositivepressureofnotlessthan5mmw.g.shallbemaintainedinthelift

shaft.Themechanismforpressurisingtheliftshaftandliftlobbyshallbesoinstalledthatthey

shalloperateautomaticallywhentheautomaticfirealarmoperates.Themechanismshallhave

facilitiestooperatemanually.

K-3.5 Exit fromthe lift lobbyshallbe througha self-closing smokestopdoorofhalf-hour fire

resistance.

K-3.6Theliftmachineroomshallbeseparateandnoothermachineryshallbeinstalledtherein.

K-3.7Liftsshallnotnormallycommunicate,withthebasement.However,oneoftheliftsmaybe

permitted to reach the basement levels provided the lift lobby at each basement level is

pressurizedandseparatedfromtherestofthebasementareas,bysmokeactuatedfireresisting

dooroftwohoursfireresistance.

K-4Basements

K-4.1Eachbasementshallbeseparatelyventilated.Ventswithcrosssectionalarea(aggregate)

notlessthan2.5%ofthefloorareaspreadevenlyroundtheperimeterofthebasementshallbe

providedintheformofgrillsorbreakablestall-boardslightorpaymentlightorbywayofshafts.

Page 15: Delhi Building Bye Law Related Fire · 2019-05-28 · Delhi Building Bye Law Related Fire 11.1 No building shall be erected so as to deprive any other building of the means of access

K-4.2Thestaircaseofbasementsshallbeofenclosedtypehavingfireresistanceofnotlessthan

twohoursandshallbesituatedattheperipheryofthebasementandshallcommunicatewith

basement through a lobby provided with fire resisting self-closing doors of half-hour fire

resistance.Ifthetraveldistanceexceeds18.50madditionalstaircasesatproperplacesshallbe

provided.

K-5ServiceDucts

K-5.1 Service ducts for electrical conduits, cables etc.shall be enclosed bywalls having a fire

resistance of not less than two hours. Doors for inspection or access shall also have a fire

resistanceofnotlessthantwohours.

K-5.2 If the.Cross-sectionalareaexceeds1sq.m. itshallbesealedwhere itpassesafloorby

carryingthefloorthroughtheduct.Thefloorwithintheductshallbepiercedforanyservicepipe

orventilationtrunkandshallfitascloselyaspossiblearoundanysuchpipeortrunk.

K-6.RefuseChutesandRefuseChambers

K-6.1Hopperstorefusechutesshallbesituatedinwellventilatedpositionsandthechutesshall

be continued upwards with an outlet above roof level and with an enclosure wall of non-

combustiblematerialwithfireresistanceofnotlessthantwohours.Thehoppersshallnotbe

locatedwithinthestaircaseenclosure.

K-6.2 Inspectionpanel andhopper (charging station) opening shall be fittedwith tight fitting

metaldoors,covers,havingafireresistanceofnotlessthanonehour.

K-6.3Refusechutes shallnotbeprovided in staircasewalls,air-conditioningshafts,etc.K-6.4

Refuse chambers shall have walls and floors of roofs constructed of non-combustible and

imperviousmaterialandshallhavea fire resistanceofnot less than twohours.Theyshallbe

locatedatasafedistancefromexitroutes.

K-7.LiftsandFireLifts

K-7.1Publicaddresssystemintheliftcarwithspeaker/telephoneassemblyshallbeprovided.

K-7.2Provisionsforafireliftshallbemadeasperthefollowingdetails:

1. ToenableFireServicespersonneltoreachtotheupperfloorswiththeminimumdelay,

oneoftheliftsshallbesodesignedsoastobeavailablefortheexclusiveuseoftheFiremen

inanemergencyandbedirectlyaccessibletoeverydwellinglettablefloorspaceoneach

floor.

Page 16: Delhi Building Bye Law Related Fire · 2019-05-28 · Delhi Building Bye Law Related Fire 11.1 No building shall be erected so as to deprive any other building of the means of access

2. Theliftshallhaveafloorareaofnotlessthanl.5sq.m.Itshallhaveloadingcapacityofnot

lessthan500kg.(8personslift)withautomaticclosingdoors.

3. Theelectricsupplyshallbeonaseparateservicefromelectricsupplymainsinabuilding

andcables run in routesafe from fire, that is,within the lift shaft. Incaseof failureof

normalelectricsupplyitshallautomaticallytripovertoalternatesupply.

4. Theoperationofafireliftisasimpletoggleortwobuttonswitchsituatedinaglassfronted

boxadjacenttotheliftattheentrancelevel.Whentheswitchison,landingcall-pointswill

becomeinoperativeandtheliftwillbeoncarcontrolonly.Whentheswitchisoff,thelift

willreturntonormalworking.Thisliftcanbeusedbytheoccupantsinnormaltimes.

5. Thewords "FIRE LIFT" shall be conspicuously displayed in fluorescent paint on the lift

landingdoorsateachfloorlevel.

6. Forbuildingsabove15m inheightcollapsiblegatesshallnotbepermittedfor liftsand

shallhavesoliddoorswithfireresistanceof2hours.

K-8.BuildingServices

K-8.1ElectricalServices

1. Theelectricdistributioncables/wiringshallbelaidinseparateduct(SeeBye-lawNo.K-5-

1).Theductshallbesealedateveryalterativefloorwithnon-combustiblematerialshaving

thesamefireresistanceasthatoftheduct.

2. Watermains,telephonelines,intercomlines,gaspipesoranyotherservicelineshallnot

belaidintheductforelectriccables.

3. Separate circuits forwaterpumps lifts, staircasesandcorridor lightingandblowers for

pressurizingsystemshallbeprovideddirectlyfromthemainswitchgearpanel.

K-8.2StaircaseandCorridorLighting

1. Thestaircaseandcorridorlightingshallbeonseparateserviceandshallbeindependently

connectedsoasitcouldbeoperatedbyoneswitchinstallationonthegroundfloor,easily

accessibletofirefightingstaffatanytimeirrespectiveofthepositionoftheindividuate

controlofthelightpoints,ifany.

Page 17: Delhi Building Bye Law Related Fire · 2019-05-28 · Delhi Building Bye Law Related Fire 11.1 No building shall be erected so as to deprive any other building of the means of access

2. Staircaseandcorridor lightingshallalsobeconnectedtoalternatesupply fromparallel

high-tensionsupplyortothesupplyfromthestand-bygenerator.

3. Emergencylightsshallbeprovidedinstaircasecorridor.

K-8.3AlternateSourceofElectricSupply-Astand-byelectricgeneratorshallbeinstalledtosupply

powertostaircaseandcorridorlightingcircuits,firelifts,thestand-byfirepump,pressurization

fans and blowers, smoke extraction and damper system in case of failure of normal electric

supply.Thegeneratorshallbecapableoftakingstartingcurrentofallthemachinesandcircuits

stated above simultaneously. If the stand-by pump is driven by diesel engine, the generator

supplyneednotbeconnectedtothestand-bypump.WhereparallelHV/LVsupplyisprovided

with appropriate transformer for emergency, the provision o1 generator may be waived in

consultationwithChiefFireOfficer,DelhiFireService.

K-8.4Transformers

1. Iftransformersarehousedinthebuildingbelowthegroundlevelitshallbenecessarilyin

the first basement in separate fire resistance room of 4 hours rating. The room shall

necessarily be at the periphery of the basement. The entrance to the room shall be

provided with a steel door of 2 hours fire rating. A curb of a suitable height shall be

providedattheentranceinordertopreventtheflowofoilfromruptured,transformer

into other parts of the basement. The direct access to that transformer room shall be

providedpreferably fromoutside. The switchgears shall behoused in a separate room

separatedfromthetransformerbaysbyafire-resistingwallwithfireresistancenotless

thanfourhours.

2. Thetransformershallbeprotectedbyanautomatichigh-pressurewatersprayorafoam

sprinklersystem.Whenhousedatgroundfloorlevelit/theyshallbecut-offfromtheother

portionofpremisesbyFireResistingWallsof4hours fire resistance.Theyshallnotbe

housedonupperfloors.

3. AtankofRCCconstructionofadequatecapacityshallbeprovidedatlowerba9ementlevel,

tocollecttheoilfromthecatchpitincaseofemergency.Thepipeconnectingthecatch-

pittothetankshallbeofnon-combustibleconstructionandshallbeprovidedwithaflame-

arrester.

K-8.5Air-conditioning

Page 18: Delhi Building Bye Law Related Fire · 2019-05-28 · Delhi Building Bye Law Related Fire 11.1 No building shall be erected so as to deprive any other building of the means of access

1. Properarrangementsbywayofautomaticfiredampersworkingonsmoke/heatdetectors

forisolatingallductingateveryfloorfromthemainrisershallbemade.

2. When the automatic fire alarm operates, the respective air handling units of the air

conditioningsystemshallautomaticallybeswitchedoff.

3. Automaticfiredampersshallbesoarrangedsoastoclosebygravityinthedirectionofthe

airmovementandtoremaintightlycloseduponoperationofasmoke/heatdetector-cum-

firealarm.

4. Airductssavingmainfloorareascorridors,ete.shallnotpassthroughthestairwall.

5. Wherevertheductspassthroughfirewallsorfloorstheopeningaroundtheductsshallbe

seatedwithfireresistingmaterialssuchasropeasbestos,mineralwool,etc.Theairfilters

oftheair-handlingunitsshallbeofnon-combustiblematerials.

6. Automaticfiredampersshall.beprovidedattheinletofthefreshairductandthereturn

airductofeachcompartment/stoponeveryfloor.

Note:Theuseof typeofdetectors shallbe to the satisfactionofChief FireOfficer,Delhi Fire

Service.

K-8.6BoilerRoom-ProvisionsofBoilerandBoilerRoomsshallconformtoIndianBoilerAct.

Further, the following additional aspects may be taken into account in the location of

Boiler/BoilerRoom:

1. Theboilershallnotbeallowedinsub-basementbutbeallowedinthebasementsaway

fromtheescaperoutes.

2. Theboilersshallbeinstalledinafireresistingroomof4hoursfireresistancerating,and

thisroomshallbesituatedontheperipheryofthebasement.Catchpitshallbeprovided

atthelowlevel.

3. Theboilerroomshallbeprovidedwithfreshairinletsandsmokeexhaustsdirectlytothe

atmosphere.

4. Foaminletsshallbeprovidedontheexternalwallsofthebuildingatthegroundfloorlevel

toenablethefireservicestousefoamincaseoffire.

Page 19: Delhi Building Bye Law Related Fire · 2019-05-28 · Delhi Building Bye Law Related Fire 11.1 No building shall be erected so as to deprive any other building of the means of access

K-9ProvisionofFirstAidFireFightingAppliances

K-9.1The firstaid fire fightingequipmentsshallbeprovidedonall floor includingbasements,

occupiedterrace,liftroomsinaccordancewithIS:2217-1982Recommendationsforproviding

FirstAidFireFightingArrangementsinPublicBuildingsinconsultationwiththeChiefFireOfficer.

K-9.2ThefirefightingappliancesshallbedistributedoverthebuildinginaccordancewithIS2190

CodeofPracticeforselection,installationandmaintenanceofportablefirstaidfireappliances.

K-10.FixedFireFightingInstallations

K-10.1Buildingsabove15minheightdependingupontheoccupancyuseshallbeprotectedby

wetriserorsprinklerinstallationsystemwiththefireserviceconnectionsatthebaseorsprinkler

installa6onasperdetailsgivenbelow:

Detailsgivenbelow

TypeoftheBuildingOccupancy Requirements

(a)Apartmentbuildingbelow15m.inheightirrespectiveoffloorarea Nil

(b)Apartmentbuildingsexceeding15m.inheight WetRisersand(or)DownComers

(c)Non-apartmentsbuildings15m.andaboveinheightirrespectiveof

floorareaWetRisersand(or)DownComers

(d)Allbasements,sub-basementshavingspecialriskslikestorageofhazardous

Sprinkler"Systemandexplosivematerialinabuilding15m.andabove

HighPressureWaterSprayorfoam

(e)Anyoftheabovecategoriesmayincorporateanautomaticsprinkler*/drenchersystemifthe

protectivemethods.

*Those buildings provided with smoke/heat detection system backed by 24 hour caretaker

(trainedinfirefighting)staff,theinstallationofsprinklersneednotbeinsisted.

Thehydrantsshallbeprovidedwithinthecourtyard,the locationofwhichshallbedecidedin

consultationwiththeChiefFireOfficer.

Page 20: Delhi Building Bye Law Related Fire · 2019-05-28 · Delhi Building Bye Law Related Fire 11.1 No building shall be erected so as to deprive any other building of the means of access

Note:TheDryRiserinstallationsmaybepermittedbytheChiefFireOfficer,DelhiFireService,for

buildingsunder (b) and (c) forheights above15m. andbelow24m. if he is satisfiedwith the

arrangementsforwatersupply

K-10.2TheWetRiserinstallationsshallconformtolS:3844-1966CodeofPracticeforInstallation

ofinternalfirehydrantsinmulti-storeybuildings.

Inaddition,WetRisersshallbedesignedforZonaldistributionensuringthatundulyhighpressure

arenotdevelopedinrisersandhaveripes.

Inadditiontowetrisers,firstaidhosereelsshallbeinstalledonallthefloorsofthebuildingsand

shall conform to IS: 884-1969 specification for first aid hose reel for fire fighting (fixed

installations).Thefirstaidhosereelshallbeconnectedtooneofthefemalecouplingsoftwin

couplingsoflandingvalvesofthewetriserinstallationsbymeansofadopter.

K-10.2.1Therisershallbefedthroughtheboosterpumpfromeitherofthetwowatersources

roundtheclock:

1. Townmainsofsuitablesizewhichcansupplyrequisitequantityofwater.

2. Statictanks.Thecapacityofthestatictankshallbegivenasbelow:

1. Apartment building 15m. and above in height 50,000 liters but below 24m. in

height.

2. Non-apartmentbuilding15m.andabovebutbelowl,00000liters24m.inheight

usedformixedoccupancieslikeoffices,shops,departmentstores

3. Apartmentbuildings24m.andaboveinheightl,00000liters

4. Non-apartmentbuildings24m.andaboveinheight2,00,000liters

Note1.Incaseofgrouphousingofapartmentbuildings15mandaboveinheightbutbelow24m.

acentrallylocatedtankhavingacapacityof2,00,000litersmaybeprovided.

Note2.Theabovequantitiesofwatershallbeexclusivelyforfirefightingandshallnotbeutilized

fordomesticorotheruse.

K-10.2.2StaticWaterStorageTank-Asatisfactorysupplyofwaterforthepurposeoffirefighting

shallalwaysbeavailableintheformofundergroundstaticstoragetankwithcapacityspecified

Page 21: Delhi Building Bye Law Related Fire · 2019-05-28 · Delhi Building Bye Law Related Fire 11.1 No building shall be erected so as to deprive any other building of the means of access

foreachbuildingbythelocalFireAuthoritywitharrangementsofreplenishmentbytown'smain

or alternative source of supply @ 1,0001itres per minute. The static storage water supply

requiredfortheabovementionedpurposeshouldentirelybeaccessibletothefireenginesofthe

local Fire Service. Provision of suitable number of manholes shall be made available for

inspection,repairs,andinsertionofsuctionhoseetc.Thecoveringslabshallbeabletowithstand

thevehicularloadof18tons.

K-10.2.3Topreventstagnationofwaterinthestaticwaterstoragetankthesuctiontankofthe

domesticwatersupplyshallbefedonlythroughanoverflowarrangementtomaintainthelevel

thereinattheminimumspecifiedcapacity.

K-10.2.4Thestaticwaterstoragetankshallbeprovidedwithafirebrigadecollectingbreaching

with4Nos.-65mmdia.instantaneousmaleinletsarrangedinavalveboxatasuitablepointat

streetlevelandconnectedtothestatictankbyasuitablefixedpipenotlessthan15cm.dia.to

dischargewaterintothetankwhenrequiredatarateof1,000litersperminute.

K-10.3AutomaticSprinklers-Automatichighpressurewatersprayorfoamsprinklerssystemshall

beinstalled.

1. Inbasements,sub-basementswhichareusedascarparks,storageofcombustiblearticle,

laundryetc.

2. Onfloorsusedasdepartmentalstores,shopsandtradersinvolvingfirerisks.

3. Onallfloorsofthebuildingsotherthanapartmentbuildings,iftheheightofthebuilding

exceeds45m.

Note:SeeFootnoteunderTableK-1D.1acrossSl.Nos.(d)&(e).

K-10.4Carbon-Di-OxideFireExtinguishingSystem.FixedCO2fireextinguishinginstallationshall

beprovidedasper IS:6382-1971CodeofPracticefordesignandinstallationoffixedCO2fire

extinguishingsystemonpremiseswherewaterorfoamcannotbeusedforfireextinguishments

becauseofthespecialnatureofthecontentsofthebuildings/areastobeprotected.

K-11FireAlarmSystem

K-11.1Allbuildingsabove15m.inheightshallbeequippedwithfirealarmsystemasgiveninbye-

lawsNo.K-11.1.1&K-11.1.2.

K-11.1.1ResidentialBuilding(DwellingHouses,Boardinghouses&Hotels)

Page 22: Delhi Building Bye Law Related Fire · 2019-05-28 · Delhi Building Bye Law Related Fire 11.1 No building shall be erected so as to deprive any other building of the means of access

1. Allresidentialbuildingslikedwellinghouses(includingflats),boardinghousesandhostels

shallbeequippedwithmanuallyoperatedelectricalfirealarmsystemwithoneormore

callboxeslocatedateachfloor.Thelocationofthecallboxesshallbedecidedaftertaking

intoconsiderationthefloorplanwithaviewtoensurethatoneortheothercallboxshall

be readily accessible to all occupants of the floor without having to travelmore than

22.5m.

2. Thecallboxesshallbeofthe'break-glass'typewithoutanymovingparts,wherethecall

istransmittedautomaticallytothecontrolroomwithoutanyotheractiononthepartof

thepersonoperatingthecallbox.

3. Allcallboxesshallbewiredinaclosecircuittoacontrolpanelinthecontrolroom,located

asperBye-lawNo.K-12sothatthefloorNo.fromwherethecallboxisactuatedisclearly

indicatedonthecontrolpanel.Thecircuitshallalsoincludeoneormorebatterieswitha

capacity of 48 hrs. normal working at full load. The battery shall be arranged to be a

continuouslytricklechargedfromtheelectricmains.

4. Thecallboxesshallbearrangedtosoundoneormoresounderssoastoensurethatall

occupantsofthebuildingshallbewarnedwheneveranycallboxisactuated.

5. Thecallboxesshallbesoinstalledthattheydonotobstructtheexitwaysandyettheir

locationcaneasilybenoticedfromeitherdirection.Thebaseofthecallboxshallbeata

heightof1mfromthefloorlevel.

K-11.1.2AllotherBuildings-AllbuildingsotherthanasindicatedunderBye-lawNo.K-11.1.1shall,

inadditiontothemanuallyoperatedelectricalfirealarmsystem,beequippedwithanautomatic

firea1armsystem.The lattershallbe inadditiontothealarm,whichmaybesoundedbythe

actuationofanyautomatic fireextinguishingsystem,whichmaybe installed inanyparticular

occupancyinaccordancewiththesebyelaws.UnlessotherwisedecidedbytheChiefFireOfficer,

DelhiFireService,thedetectorsfortheautomaticfirealarmsystemshallconformto1S:217S-

1962HeatSensitiveFireDetectorsandthesystemshallbeinstalledinaccordancewithIS:2189-

1962CodeofPracticeforAutomaticFireAlarmsystem,oranyotherrelevantIndianStandards

preparedfromtimetotime.

Note:Severaltypesoffiredetectorsareavailableinthemarket,buttheapplicationofeachtype

is limitedandhas tobe carefully considered in relation to the typeof risk and the structural

featuresofthebuildingwheretheyaretobeinstalled.

Page 23: Delhi Building Bye Law Related Fire · 2019-05-28 · Delhi Building Bye Law Related Fire 11.1 No building shall be erected so as to deprive any other building of the means of access

K.12ControlRoom

K.12.1Thereshallbeacontrolroomontheentrancefloorofthebuildingwithcommunication

system(suitablepublicaddresssystem)toallfloorsandfacilitiesforreceivingthemessagefrom

differentfloors.Detailsofal1floorplansalongwiththedetailsof firefightingequipmentand

installationsshallbemaintainedintheControlRoom.Thecontrolroomshallalsohavefacilities

to detect the fire on any floor through Indicator Boards connecting fire detecting and alarm

systemonallfloors.Thestaffinchargeofcontrolroomshallberesponsibleforthemaintenance

ofthevariousservicesandfirefightingequipmentandinstallations.

K-13HouseKeeping

K-13.1Toeliminatefirehazardsagoodhousekeepinginsidethebuildingandoutsidethebuilding

shallbestrictlymaintainedbytheoccupant'sand/ortheownerofthebuilding.

K-14FireDrillsandFireOrders

K-14.1Firenotices/ordersshallbepreparedtofulfilltherequirementsofthefirefightingand

evacuationfromthebuildingintheeventoffireandotherincidents.Theoccupantsshallbemade

thoroughlyconversantwiththeiractionintheeventoftheemergency,bydisplayingfirenotices

atvantagepoints.Suchnoticesshouldbedisplayedprominentlyinbroadlettering.