22
4–45 CDS-PRM001-EN • TRACE 700 User’s Manual System Design Options Dedicated outdoor-air systems Dedicated outdoor-air systems A dedicated outdoor-air system (DOAS) (dedicated ventilation unit) uses a separate air handler to dehumidify, cool, heat, and sometimes humidify the incoming outdoor air before delivering it to other HVAC units or directly to the occupied zones. In either case, the local HVAC units handle the zone cooling and heating loads. Treating the outdoor air separately from recirculated return air makes it easy to verify sufficient ventilation airflow and enables enforcement of a maximum humidity limit in occupied zones. Application considerations Always provide conditioned air that is drier than the air in the space. This practice minimizes the cooling capacity required from the local HVAC terminals and adequately controls the indoor relative humidity without additional, zone-level dehumidification enhancements. Deliver “cold” conditioned air whenever possible, and use recovered energy to reheat during mild weather. Providing “cold” conditioned air from the DOAS minimizes the cooling loads at the local HVAC terminals. During mild weather (spring and fall), modulate the amount of recovered energy used by the DOAS for reheat; only warm the conditioned air enough to minimize inefficient reheat at the local HVAC terminals. “Neutral”- temperature conditioned air (which has a dry-bulb temperature approximating that of the air in the space) increases the cooling conditioned air to local terminal units Figure 4–15 Dedicated outdoor-air systems

Dedicated outdoor-air systems - Trane DOA do… · bulb during the cooling season, or heats the outdoor air to 68°F dry bulb during the heating season, before delivering the conditioned

  • Upload
    others

  • View
    9

  • Download
    0

Embed Size (px)

Citation preview

  • 4–45CDS-PRM001-EN • TRACE 700 User’s Manual System Design OptionsDedicated outdoor-air systems

    Dedicated outdoor-air systems

    A dedicated outdoor-air system (DOAS) (dedicated ventilation

    unit) uses a separate air handler to dehumidify, cool, heat, and

    sometimes humidify the incoming outdoor air before delivering it

    to other HVAC units or directly to the occupied zones. In either

    case, the local HVAC units handle the zone cooling and heating

    loads. Treating the outdoor air separately from recirculated return

    air makes it easy to verify sufficient ventilation airflow and

    enables enforcement of a maximum humidity limit in occupied

    zones.

    Application considerations� Always provide conditioned air that is drier than the air in the

    space. This practice minimizes the cooling capacity required from

    the local HVAC terminals and adequately controls the indoor

    relative humidity without additional, zone-level dehumidification

    enhancements.

    � Deliver “cold” conditioned air whenever possible, and use

    recovered energy to reheat during mild weather. Providing “cold”

    conditioned air from the DOAS minimizes the cooling loads at the

    local HVAC terminals. During mild weather (spring and fall),

    modulate the amount of recovered energy used by the DOAS for

    reheat; only warm the conditioned air enough to minimize

    inefficient reheat at the local HVAC terminals. “Neutral”-

    temperature conditioned air (which has a dry-bulb temperature

    approximating that of the air in the space) increases the cooling

    conditioned air to

    local terminal units

    Figure 4–15 Dedicated outdoor-air systems

  • 4–46 System Design Options TRACE 700 User’s Manual • CDS-PRM001-ENDedicated outdoor-air systems

    capacity required from the local HVAC terminals and requires

    more reheat at the dedicated outdoor-air unit.

    � Select equipment to limit indoor relative humidity to

    60–65 percent. Targeting a drier condition in the space will

    require larger equipment and consume more energy.

    � Employ communicating controls to optimize energy use.

    Dynamically resetting the dew point or dry-bulb temperature

    delivered by the DOAS can minimize the energy use by the

    overall system.

    Related reading� “Dedicated Ventilation Systems,” Engineers Newsletter (volume

    30, number 3)

    � Dehumidification in HVAC Systems Applications Engineering

    Manual (Trane literature number SYS-APM004-EN)

    � Designing Dedicated Outdoor-Air Systems Application Guide

    (Trane literature number SYS-APG001-EN.

    Sample scenarios

    Scenario 1. A building is served by a fan-coil system and a dedicated outdoor-air unit that cools the outdoor air to 70°F dry

    bulb during the cooling season, or heats the outdoor air to 68°F

    dry bulb during the heating season, before delivering the

    conditioned outdoor air directly to the individual spaces. (Note: In

    non-arid climates, this approach may not adequately dehumidify

    the outdoor air.)

    � When the outdoor dry-bulb temperature is greater than the

    cooling supply-air dry-bulb setpoint, the dedicated outdoor-air unit

    will cool the entering outdoor air to the cooling supply-air dry-bulb

    setpoint.

    Table 4–5 Sample Scenarios

    Topic

    Scenario 1 (page 46) Cool/Heat (Fixed Setpoints)

    Scenario 2 (page 51) Dehumidify and Reheat/Heat (Fixed Setpoints)

    Scenario 3 (page 56) Dehumidify (Priority) or Cool/Heat (Optimized SADP)

    Scenario 4 (page 62) Dehumidify and Reheat/Heat (Optimized SADB))

  • 4–47CDS-PRM001-EN • TRACE 700 User’s Manual System Design OptionsDedicated outdoor-air systems

    � When the outdoor dry-bulb temperature is less than the cooling

    supply-air dry-bulb setpoint, the dedicated outdoor-air unit will

    heat the entering outdoor air to the heating supply-air dry-bulb

    setpoint.

    This example will cover how to model the air-distribution system

    (steps 1–8), model the cooling and heating equipment (steps 9–

    11), and assign the loads from the coils to the equipment (step

    12).

    1 Start by selecting Fan

    Coil as the system type.

    2 On the Dedicated OA

    tab, select the type of

    dedicated ventilation unit

    to be modeled. In this

    example, the dedicated

    ventilation unit will supply

    air to spaces at a specific

    dry bulb. Therefore,

    Cool / Heat will be

    selected.

    None – no dedicated ventilation unit

    Cool / heat – a dedicated ventilation unit is used to cool the outdoor air to the

    user-input cooling dry bulb during the cooling season or heat the outdoor air to

    the user-input heating dry bulb during the heating season.

    Dehumidify (priority) or Cool / Heat – a dedicated ventilation unit is used to

    dehumidify the outdoor air to the user-input cooling dew point (not reheated)

    during the cooling season or heat the outdoor air to the user-input heating dry

    bulb during the heating season.

    Dehumidify and Reheat / Heat – a dedicated ventilation unit is used to

    dehumidify the outdoor air to the user-input cooling dew point (then reheat it

    to the user-input cooling dry bulb) during the cooling season or heat the

    outdoor air to the user-input heating dry bulb during the heating season.

  • 4–48 System Design Options TRACE 700 User’s Manual • CDS-PRM001-ENDedicated outdoor-air systems

    3 Select the control method

    for the unit. Because the

    dedicated ventilation

    cooling coil cools the

    outdoor air to the cooling

    supply-air dry bulb, or the

    dedicated ventilation

    heating coil heats the

    outdoor air to the heating

    supply-air dry bulb, Fixed

    Setpoints will be used.

    4 Input the Cooling and

    Heating Design

    Setpoints. In this

    scenario, 70°F should be

    input for the cooling

    supply-air dry bulb, and

    68°F for the heating

    supply-air dry bulb.

    5 Select the schedule for

    the coils and fan in the

    dedicated outdoor-air unit.

    Note: For additional

    information related to the other

    Control Methods, press F1 and

    click Control Method.

    If the ventilation air is to be precooled, the

    Dedicated Ventilation Cooling Coil

    schedule defines the hours of available

    operation of the ventilation cooling coil. The

    optional ventilation cooling coil is available

    for any hour that this schedule reads

    1 percent or greater.

    If the ventilation air is to be preheated, the

    Dedicated Ventilation Heating Coil

    schedule defines the hours of available

    operation of the ventilation heating coil. The

    optional ventilation heating coil is available

    for any hour that this schedule reads

    1 percent or greater.

    The Optional ventilation fan schedule

    defines the hours that the ventilation unit

    can operate. If the Optional ventilation fan

    schedule reads 1 percent or greater, the fan

    is available that hour.

    Note: If a custom schedule is created for

    the fan or coils, it is recommended to use

    values of 0 percent for hours off and

    100 percent for hours available to run to

    avoid confusion.

  • 4–49CDS-PRM001-EN • TRACE 700 User’s Manual System Design OptionsDedicated outdoor-air systems

    6 Select the dedicated

    ventilation-deck location.

    This tells TRACE 700

    where to supply the

    preconditioned outdoor

    air. For this scenario, the

    outdoor air will be

    delivered directly to the

    spaces. As a result,

    Room Direct will be

    selected.

    7 Select the level of the

    ventilation-deck location.

    For this scenario, one

    large dedicated

    ventilation unit will

    condition the outdoor air

    for all of the rooms

    assigned to the fan-coil

    system, so the coils

    should be set at the

    System level.

    Return/Outdoor Deck – conditioned

    outdoor air is mixed with the return air in the

    main unit(s).

    Plenum – conditioned outdoor air is

    delivered to the plenum above the spaces.

    Room Direct – conditioned outdoor air is

    delivered directly to the spaces. This can

    also be used to model the delivery of

    conditioned outdoor air to dual-duct VAV

    boxes where it mixes locally with

    recirculated return air.

    System – The dedicated ventilation unit will be placed at the system level. It

    will pretreat the outdoor air for all of the rooms and zones assigned to the

    airside system. This is the most common choice for dedicated ventilation

    systems. The System Checksums or System Component Selection reports

    should be used to size the dedicated ventilation unit.

    Zone – Each zone (or room assigned directly to the system) will get a separate

    dedicated ventilation system. The Zone Checksums or System Component

    Selection reports should be used to size the dedicated ventilation unit.

    Room – Each room will get a separate dedicated ventilation system. The Room

    Checksums or System Component Selection reports should be used to size

    the dedicated ventilation unit.

    Same level as main cooling coil – The dedicated ventilation unit will be placed

    at the same level as the main cooling coil. The System Component Selection

    report should be used to size the dedicated ventilation unit.

    Same level as main heating coil – The dedicated ventilation unit will be

    placed at the same level as the main heating coil. The System Component

    Selection report should be used to size the dedicated ventilation unit.

  • 4–50 System Design Options TRACE 700 User’s Manual • CDS-PRM001-ENDedicated outdoor-air systems

    8 On the Fans tab, input

    the fan type and the total

    static pressure for the

    primary fan (the fans in

    the fan-coil units) and the

    optional ventilation fan

    (the fan in the dedicated

    ventilation unit).

    Next, define the

    cooling and heating plants

    represented by the fan-coil

    system and the rooftop air

    conditioner:

    9 Add two new cooling

    plants and two new

    heating plants to the

    Configuration pane.

    10Drag the appropriate

    icons from the

    Equipment Category

    section to define each

    plant.

    11To finish defining this

    equipment, enter the

    information from

    Table 4–6 on page 4–51

    on the appropriate

    equipment tab.

    Finally, assign the coil

    loads of the air-distribution

    system to the proper

    cooling and heating plants:

    12Drag each coil in the

    Unassigned Systems/

    Coils pane to the

    appropriate plant in the

    Systems and Plants

    pane.

    The illustration labeled

    After shows the

    completed assignments.

    For cooling, use water-cooled chiller

    and air-cooled unitary.

    For heating, use boiler and gas-fired

    heat exchanger.

    Before…

    After…

  • 4–51CDS-PRM001-EN • TRACE 700 User’s Manual System Design OptionsDedicated outdoor-air systems

    Scenario 2. A building is served by a water-source heat pump (WSHP) system and a dedicated outdoor-air unit that delivers

    conditioned outdoor air to the individual heat pumps. During the

    cooling season, the dedicated outdoor-air unit dehumidifies the

    outdoor air to 55°F dew point and then reheats it to a “neutral”

    70°F dry bulb. During the heating season, the dedicated unit

    heats the outdoor air to 68°F dry bulb.

    � When the outdoor dew point is greater than the cooling supply-

    air dew point setpoint, the dedicated outdoor-air unit will

    dehumidify the entering outdoor air to the cooling supply-air dew

    point setpoint, then reheat it to the cooling supply-air dry-bulb

    setpoint.

    � When the outdoor dew point is less than the cooling supply-air

    dew point setpoint and the outdoor dry-bulb temperature is

    greater than the cooling supply-air dry-bulb setpoint, the

    dedicated outdoor-air unit will cool the entering outdoor air to the

    cooling supply-air dry-bulb setpoint.

    � When the outdoor dew point is less than the cooling supply-air

    dew point setpoint and the outdoor dry-bulb temperature is less

    than the cooling supply-air dry-bulb setpoint, the dedicated

    outdoor-air unit will heat the entering outdoor air to the heating

    supply-air dry-bulb setpoint.

    This example will cover how to model the air-distribution system

    (steps 1–8), model the cooling and heating equipment (steps 9–

    11), and assign the loads from the coils to the equipment (step

    12)

    .

    Table 4–6 Equipment types

    Cooling Equipment tab Heating Equipment tab

    Water-cooled chiller 2-stage centrifugal gas-fired hot water boiler

    Air-cooled unitary split system RAUC-20+ ton scroll

    rooftop gas heat

  • 4–52 System Design Options TRACE 700 User’s Manual • CDS-PRM001-ENDedicated outdoor-air systems

    1 Start by selecting Water

    source heat pump as the

    system type.

    2 On the Dedicated OA

    tab, select the type of

    dedicated ventilation unit

    to be modeled. In this

    example, the dedicated

    ventilation unit will supply

    low dew-point air

    reheated to a room-

    neutral dry bulb in cooling

    mode, and air at a specific

    dry bulb in heating mode.

    Therefore, Dehumidify

    and Reheat / Heat will

    be selected.None – no dedicated ventilation unit

    Cool / heat – a dedicated ventilation unit is used to cool the outdoor air to the

    user-input cooling dry bulb during the cooling season, or heat the outdoor air to

    the user-input heating dry bulb during the heating season.

    Dehumidify (priority) or Cool / Heat – a dedicated ventilation unit is used to

    dehumidify the outdoor air to the user-input cooling dew point (not reheated)

    during the cooling season, or heat the outdoor air to the user-input heating dry

    bulb during the heating season.

    Dehumidify and Reheat / Heat – a dedicated ventilation unit is used to

    dehumidify the outdoor air to the user-input cooling dew point (then reheat it to

    the user-input cooling dry bulb) during the cooling season, or heat the outdoor air

    to the user-input heating dry bulb during the heating season.

  • 4–53CDS-PRM001-EN • TRACE 700 User’s Manual System Design OptionsDedicated outdoor-air systems

    3 Select the control method

    for the unit. Because the

    dedicated ventilation

    cooling coil dehumidifies

    the outdoor air to cooling

    supply-air dew point and

    reheats it to room neutral,

    or the dedicated

    ventilation heating coil

    heats the outdoor air to

    heating supply-air dry

    bulb, Fixed Setpoints

    will be used.

    4 Input the Cooling and

    Heating Design

    Setpoints. In this

    scenario, 55°F should be

    input for the cooling

    supply-air dew point, 70°F

    for the cooling supply-air

    dry bulb, and 68°F for the

    heating supply-air dry

    bulb.

    5 Select the schedule for

    the coils and fan in the

    dedicated outdoor-air unit.

    Note: If a custom schedule

    is created for the fan or

    coils, it is recommended to

    use values of 0 percent for

    hours off and 100 percent

    for hours available to run to

    avoid confusion.

    Note: For additional

    information related to the other

    Control Methods, press the F1

    key and click Control Method.

    If the ventilation air is to be precooled, the

    Dedicated Ventilation Cooling Coil schedule

    defines the hours of available operation of the

    ventilation cooling coil. The optional ventilation

    cooling coil is available for any hour that this

    schedule reads 1 percent or greater.

    If the ventilation air is to be preheated, the

    Dedicated Ventilation Heating Coil

    schedule defines the hours of available

    operation of the ventilation heating coil. The

    optional ventilation heating coil is available for

    any hour that this schedule reads 1 percent or

    greater.

    The Optional ventilation fan schedule

    defines the hours that the ventilation unit can

    operate. If the Optional ventilation fan

    schedule reads 1 percent or greater, the fan is

    available that hour.

  • 4–54 System Design Options TRACE 700 User’s Manual • CDS-PRM001-ENDedicated outdoor-air systems

    6 Select the dedicated

    ventilation deck location.

    This tells TRACE 700

    where to supply the

    preconditioned outdoor

    air. For this scenario, the

    outdoor air will be

    delivered to the heat

    pumps. As a result,

    Return/Outdoor Deck

    will be selected.

    7 Select the level of the

    ventilation deck location.

    For this scenario, one

    large dedicated

    ventilation unit will

    condition the outdoor air

    for all of the rooms

    assigned to the WSHP

    airside system, so the

    coils should be set at the

    System level.

    Note: For additional details

    on Systems, refer to the

    System Type:

    Characteristics in online

    Help.

    Return/Outdoor Deck – conditioned outdoor air is

    mixed with the return air in the main unit(s).

    Plenum – conditioned outdoor air is delivered to the

    plenum above the spaces.

    Room Direct – conditioned outdoor air is delivered

    directly to the spaces. This can also be used to model

    the delivery of conditioned outdoor air to dual-duct

    VAV boxes where it mixes with conditioned

    recirculated return air.

    System – The dedicated ventilation unit will be placed at the system level. It

    will pretreat the outdoor air for all of the rooms and zones assigned to the

    airside system. This is the most common choice for dedicated ventilation

    systems. The System Checksums or System Component Selection reports

    should be used to size the dedicated ventilation unit.

    Zone – Each zone (or room assigned directly to the system) will get a separate

    dedicated ventilation system. The Zone Checksums or System Component

    Selection reports should be used to size the dedicated ventilation unit.

    Room – Each room will get a separate dedicated ventilation system. The Room

    Checksums or System Component Selection reports should be used to size

    the dedicated ventilation unit.

    Same level as main cooling coil – The dedicated ventilation unit will be placed

    at the same level as the main cooling coil. The System Component Selection

    report should be used to size the dedicated ventilation unit.

    Same level as main heating coil – The dedicated ventilation unit will be placed

    at the same level as the main heating coil. The System Component Selection

    report should be used to size the dedicated ventilation unit.

  • 4–55CDS-PRM001-EN • TRACE 700 User’s Manual System Design OptionsDedicated outdoor-air systems

    8 On the Fans tab, input

    the fan type and the total

    static pressure for the

    primary fan (the fans in

    the WSHP units) and the

    optional ventilation fan

    (the fan in the dedicated

    ventilation unit).

    Next, define the

    cooling and heating plants

    represented by the WSHP

    system and the rooftop air

    conditioner.

    9 Add two new cooling

    plants and two new

    heating plants to the

    Configuration pane.

    10Drag the appropriate

    icons from the

    Equipment Category

    section to define each

    plant.

    11To finish defining this

    equipment, enter the

    information from

    Table 4–7 on page 4–56

    on the appropriate

    equipment tab.

    Finally, assign the coil

    loads of the air distribution

    system to the proper

    cooling and heating plants.

    12Drag each coil in the

    Unassigned Systems/

    Coils pane to the

    appropriate plant in the

    Systems and Plants pane.

    The illustration labeled

    “After” shows the

    completed assignments.

    For cooling, use water-source heat

    pump and air-cooled unitary.

    For heating, use boiler (for the WSHP

    system) and gas-fired heat

    exchanger.

    Before…

    After…

  • 4–56 System Design Options TRACE 700 User’s Manual • CDS-PRM001-ENDedicated outdoor-air systems

    Scenario 3. A building is served by a VAV air-handling system on each floor. A dedicated outdoor-air unit delivers conditioned

    outdoor air to the intake of each air handler. During the cooling

    season, the dedicated outdoor-air unit dehumidifies the outdoor

    air to 55°F dew point, but does not reheat it. During the heating

    season, the dedicated unit heats the outdoor air to 68°F dry bulb.

    In addition, the system-level controller polls the humidity sensors

    located in each room and resets the dew point leaving the

    dedicated outdoor-air unit, to prevent the relative humidity in the

    worst-case room from rising above 60% while minimizing energy

    use.

    � The system controller determines the highest possible cooling

    supply-air dew point setpoint that still avoids the relative humidity

    from rising above the maximum upper limit (60%, in our

    example) in any room.

    � When the outdoor dew point is greater than the current cooling

    supply-air dew point setpoint, the dedicated outdoor-air unit will

    dehumidify the entering outdoor air to the cooling supply-air dew

    point setpoint.

    � When the outdoor dew point is less than the current supply-air

    dew point setpoint and the outdoor dry-bulb temperature is

    greater than the cooling supply-air dry-bulb setpoint, the

    dedicated outdoor-air unit will cool the entering outdoor air to the

    cooling supply-air dry-bulb setpoint.

    � When the outdoor dew point is less than the current cooling

    supply-air dew point setpoint and the outdoor dry-bulb

    temperature is less than the cooling supply-air dry-bulb setpoint,

    the dedicated outdoor-air unit will heat the entering outdoor air to

    the heating supply-air dry-bulb setpoint.

    Table 4–7 Equipment types

    Cooling Equipment tab Heating Equipment tab

    Water-source heat pump

    water source HP–high efficiency

    gas-fired hot water boiler

    Air-cooled unitary split system RAUC-20+ ton scroll

    rooftop gas heat

  • 4–57CDS-PRM001-EN • TRACE 700 User’s Manual System Design OptionsDedicated outdoor-air systems

    This example will cover how to model the air-distribution system

    (steps 1–8), model the cooling and heating equipment (steps 9–

    11), and assign the loads from the coils to the equipment (step

    12).

    1 Start by selecting

    Variable Volume Reheat

    as the system type.

    2 On the Dedicated OA

    tab, select the type of

    dedicated ventilation unit

    to be modeled. In this

    example, the dedicated

    ventilation unit will supply

    low dew-point air (not

    reheated) in cooling

    mode, and air at a specific

    dry bulb in heating mode.

    Therefore, Dehumidify

    (priority) or Cool / Heat

    will be selected. None – no dedicated ventilation unit

    Cool / heat – a dedicated ventilation unit is used to cool the outdoor air to the

    user-input cooling dry bulb during the cooling season, or heat the outdoor air to

    the user-input heating dry bulb during the heating season.

    Dehumidify (priority) or Cool / Heat – a dedicated ventilation unit is used to

    dehumidify the outdoor air to the user-input cooling dew point (not reheated)

    during the cooling season, or heat the outdoor air to the user-input heating dry

    bulb during the heating season.

    Dehumidify and Reheat / Heat – a dedicated ventilation unit is used to

    dehumidify the outdoor air to the user-input cooling dew point (then reheat it to

    the user-input cooling dry bulb) during the cooling season, or heat the outdoor air

    to the user-input heating dry bulb during the heating season.

  • 4–58 System Design Options TRACE 700 User’s Manual • CDS-PRM001-ENDedicated outdoor-air systems

    3 Select the control method

    for the unit. Because the

    dew point delivered by

    the dedicated ventilation

    cooling coil is reset based

    on the worst-case room,

    Optimize Supply Air

    Dew Point will be used.

    4 Input the Cooling and

    Heating Design

    Setpoints. In this

    scenario, 65°F should be

    input for the cooling

    supply-air dry bulb, 68°F

    for the heating supply-air

    dry bulb, 65°F for the

    cooling supply-air dew

    point high limit, and 55°F

    for the cooling supply-air

    dew point low limit.

    5 Select the schedule for

    the coils and fan in the

    dedicated outdoor-air unit.

    Note: If a custom schedule

    is created for the fan or

    coils, it is recommended to

    use values of 0 percent for

    hours off and 100 percent

    for hours available to run to

    avoid confusion.

    Note: For additional

    information related to the other

    Control Methods, press the F1

    key and click Control Method.

    If the ventilation air is to be precooled, the

    Dedicated Ventilation Cooling Coil

    schedule defines the hours of available

    operation of the ventilation cooling coil. The

    optional ventilation cooling coil is available for

    any hour that this schedule reads 1 percent or

    greater.

    If the ventilation air is to be preheated, the

    Dedicated Ventilation Heating Coil

    schedule defines the hours of available

    operation of the ventilation heating coil. The

    optional ventilation heating coil is available for

    any hour that this schedule reads 1 percent or

    greater.

    The Optional ventilation fan schedule

    defines the hours that the ventilation unit can

    operate. If the Optional ventilation fan

    schedule reads 1 percent or greater, the fan is

    available that hour.

  • 4–59CDS-PRM001-EN • TRACE 700 User’s Manual System Design OptionsDedicated outdoor-air systems

    6 Select the dedicated

    ventilation deck location.

    This tells TRACE 700

    where to supply the

    preconditioned outdoor

    air. For this scenario, the

    outdoor air will be

    delivered to the mixing

    box of the VAV air handler.

    As a result, Return /

    Outdoor Deck will be

    selected.

    7 Select the level of the

    ventilation deck location.

    For this scenario, one

    large dedicated

    ventilation unit will

    condition the outdoor air

    for all of the rooms

    assigned to the VAV

    airside system, so the

    coils should be set at the

    System level.

    Note: For additional details

    on Systems, refer to the

    System Type:

    Characteristics in online

    Help.

    Return/Outdoor Deck – conditioned

    outdoor air is mixed with the return air in the

    main unit(s).

    Plenum – conditioned outdoor air is

    delivered to the plenum above the spaces.

    Room Direct – conditioned outdoor air is

    delivered directly to the spaces. This can

    also be used to model the delivery of

    conditioned outdoor air to dual-duct VAV

    boxes where it mixes with conditioned

    recirculated return air.

    System – The dedicated ventilation unit will be placed at the system level. It

    will pretreat the outdoor air for all of the rooms and zones assigned to the

    airside system. This is the most common choice for dedicated ventilation

    systems. The System Checksums or System Component Selection reports

    should be used to size the dedicated ventilation unit.

    Zone – Each zone (or room assigned directly to the system) will get a separate

    dedicated ventilation system. The Zone Checksums or System Component

    Selection reports should be used to size the dedicated ventilation unit.

    Room – Each room will get a separate dedicated ventilation system. The Room

    Checksums or System Component Selection reports should be used to size

    the dedicated ventilation unit.

    Same level as main cooling coil – The dedicated ventilation unit will be placed

    at the same level as the main cooling coil. The System Component Selection

    report should be used to size the dedicated ventilation unit.

    Same level as main heating coil – The dedicated ventilation unit will be placed

    at the same level as the main heating coil. The System Component Selection

    report should be used to size the dedicated ventilation unit.

  • 4–60 System Design Options TRACE 700 User’s Manual • CDS-PRM001-ENDedicated outdoor-air systems

    8 On the Temp/Humidity

    tab, specify a Maximum

    room relative humidity

    of 60%.

    9 On the Fans tab, input

    the fan type and the total

    static pressure for the

    primary fan (the fans in

    the VAV air handler) and

    the optional ventilation

    fan (the fan in the

    dedicated ventilation

    unit).

    Next, define the

    cooling and heating plants

    represented by the VAV

    system and the rooftop air

    conditioner.

    10Add two new cooling

    plants and two new

    heating plants to the

    Configuration pane.

    11Drag the appropriate

    icons from the

    Equipment Category

    section to define each

    plant.

    12To finish defining this

    equipment, enter the

    information from

    Table 4–8 on page 4–61

    on the appropriate

    equipment tab.

    For cooling, use air-cooled chiller

    and air-cooled unitary.

    For heating, use boiler (for the WSHP

    system) and gas-fired heat

    exchanger.

  • 4–61CDS-PRM001-EN • TRACE 700 User’s Manual System Design OptionsDedicated outdoor-air systems

    Before…

    After…

    Finally, assign the coil

    loads of the air distribution

    system to the proper

    cooling and heating plants.

    13Drag each coil in the

    Unassigned Systems/

    Coils pane to the

    appropriate plant in the

    Systems and Plants pane.

    The illustration labeled

    “After” shows the

    completed assignments.

    Table 4–8 Equipment types

    Cooling Equipment tab Heating Equipment tab

    Air-cooled chiller air-cooled helical-rotary chiller

    gas-fired hot water boiler

    Air-cooled unitary split system RAUC-20+ ton scroll

    rooftop gas heat

  • 4–62 System Design Options TRACE 700 User’s Manual • CDS-PRM001-ENDedicated outdoor-air systems

    Scenario 4. A building is served by a fan-coil system and a dedicated outdoor-air unit that delivers conditioned outdoor air

    directly to the individual spaces. The system-level controller polls

    the fan-coils and resets the dry-bulb temperature leaving the

    dedicated outdoor-air unit to avoid overcooling or overheating any

    room.

    During the cooling season, the dedicated outdoor-air unit

    dehumidifies the outdoor air to 55°F dew point and then, if

    necessary, reheats it just enough to avoid overcooling the room

    with the lowest sensible cooling load. During the heating season,

    the dedicated unit heats the outdoor air as much as possible,

    without overheating the room with the lowest sensible heating

    load.

    � The system controller determines the current supply-air dry-bulb

    setpoint needed to avoid overcooling or overheating any room.

    � When the outdoor dew point is greater than the cooling supply-

    air dew point setpoint, the dedicated outdoor-air unit will

    dehumidify the entering outdoor air to the cooling supply-air dew

    point setpoint, then reheat it to the current supply-air dry-bulb

    setpoint.

    � When the outdoor dew point is less than the cooling supply-air

    dew point setpoint and the outdoor dry-bulb temperature is

    greater than the current supply-air dry-bulb setpoint, the

    dedicated outdoor-air unit will cool the entering outdoor air to the

    current supply-air dry-bulb setpoint.

    � When the outdoor dew point is less than the cooling supply-air

    dew point setpoint and the outdoor dry-bulb temperature is less

    than the current supply-air dry-bulb setpoint, the dedicated

    outdoor-air unit will heat the entering outdoor air to the current

    supply-air dry-bulb setpoint.

    This example will cover how to model the air-distribution system

    (steps 1–8), model the cooling and heating equipment (steps 9–

    11), and assign the loads from the coils to the equipment (step

    12).

  • 4–63CDS-PRM001-EN • TRACE 700 User’s Manual System Design OptionsDedicated outdoor-air systems

    1 Start by selecting Fan

    Coil as the system type.

    2 On the Dedicated OA

    tab, select the type of

    dedicated ventilation unit

    to be modeled. In this

    example, the dedicated

    ventilation unit will supply

    low dew-point air (and

    possibly reheated) in

    cooling mode, and air at a

    specific dry bulb in

    heating mode. Therefore,

    Dehumidify and Reheat

    / Heat will be selected.

    3 Select the control method

    for the unit. Because the

    dedicated ventilation

    cooling coil dehumidifies

    the outdoor air to cooling

    supply-air dew point and

    reheats it based on the

    worst-case room, or the

    dedicated ventilation

    heating coil heats the

    outdoor air to heating

    supply-air dry bulb,

    Optimize SADB will be

    used.

    Note: For additional

    information related to the other

    Control Methods, press the F1

    key and click Control Method.

    None – no dedicated ventilation unit

    Cool / heat – a dedicated ventilation unit is

    used to cool the outdoor air to the user-input

    cooling dry bulb during the cooling season, or

    heat the outdoor air to the user-input heating

    dry bulb during the heating season.

    Dehumidify (priority) or Cool / Heat – a

    dedicated ventilation unit is used to dehumidify

    the outdoor air to the user-input cooling dew

    point (not reheated) during the cooling season,

    or heat the outdoor air to the user-input heating

    dry bulb during the heating season.

    Dehumidify and Reheat / Heat – a dedicated

    ventilation unit is used to dehumidify the

    outdoor air to the user-input cooling dew point

    (then reheat it to the user-input cooling dry

    bulb) during the cooling season, or heat the

    outdoor air to the user-input heating dry bulb

    during the heating season.

  • 4–64 System Design Options TRACE 700 User’s Manual • CDS-PRM001-ENDedicated outdoor-air systems

    4 Input the Cooling and

    Heating Design

    Setpoints. In this

    scenario, 55°F should be

    input for the cooling

    supply-air dew point, 55°F

    for the supply-air dry bulb

    low limit, and 70°F for the

    supply-air dry bulb high

    limit.

    5 Select the schedule for

    the coils and fan in the

    dedicated outdoor-air unit.

    Note: If a custom schedule

    is created for the fan or

    coils, it is recommended to

    use values of 0 percent for

    hours off and 100 percent

    for hours available to run to

    avoid confusion.

    6 Select the dedicated

    ventilation deck location.

    This tells TRACE 700

    where to supply the

    preconditioned outdoor

    air. For this scenario, the

    outdoor air will be

    delivered directly to the

    spaces. As a result,

    Room Direct will be

    selected.

    Return/Outdoor Deck – conditioned

    outdoor air is mixed with the return air in the

    main unit(s).

    Plenum – conditioned outdoor air is

    delivered to the plenum above the spaces.

    Room Direct – conditioned outdoor air is

    delivered directly to the spaces. This can

    also be used to model the delivery of

    conditioned outdoor air to dual-duct VAV

    boxes where it mixes with conditioned

    recirculated return air.

    If the ventilation air is to be precooled, the

    Dedicated Ventilation Cooling Coil schedule

    defines the hours of available operation of the

    ventilation cooling coil. The optional ventilation

    cooling coil is available for any hour that this

    schedule reads 1 percent or greater.

    If the ventilation air is to be preheated, the

    Dedicated Ventilation Heating Coil schedule

    defines the hours of available operation of the

    ventilation heating coil. The optional ventilation

    heating coil is available for any hour that this

    schedule reads 1 percent or greater. The

    Optional ventilation fan schedule defines the

    hours that the ventilation unit can operate.

    If the Optional ventilation fan schedule reads

    1 percent or greater, the fan is available that

    hour.

  • 4–65CDS-PRM001-EN • TRACE 700 User’s Manual System Design OptionsDedicated outdoor-air systems

    7 Select the level of the

    ventilation deck location.

    For this scenario, one

    large dedicated

    ventilation unit will

    condition the outdoor air

    for all of the rooms

    assigned to the Fan Coil

    system, so the coils

    should be set at the

    System level.

    Note: For additional details

    on Systems, refer to the

    System Type:

    Characteristics in online

    Help.

    8 On the Fans tab, input

    the fan type and the total

    static pressure for the

    primary fan (the fans in

    the Fan Coil units) and the

    optional ventilation fan

    (the fan in the dedicated

    ventilation unit).

    System – The dedicated ventilation unit will be placed at the system level. It

    will pretreat the outdoor air for all of the rooms and zones assigned to the

    airside system. This is the most common choice for dedicated ventilation

    systems. The System Checksums or System Component Selection reports

    should be used to size the dedicated ventilation unit.

    Zone – Each zone (or room assigned directly to the system) will get a separate

    dedicated ventilation system. The Zone Checksums or System Component

    Selection reports should be used to size the dedicated ventilation unit.

    Room – Each room will get a separate dedicated ventilation system. The Room

    Checksums or System Component Selection reports should be used to size

    the dedicated ventilation unit.

    Same level as main cooling coil – The dedicated ventilation unit will be placed

    at the same level as the main cooling coil. The System Component Selection

    report should be used to size the dedicated ventilation unit.

    Same level as main heating coil – The dedicated ventilation unit will be placed

    at the same level as the main heating coil. The System Component Selection

    report should be used to size the dedicated ventilation unit.

  • 4–66 System Design Options TRACE 700 User’s Manual • CDS-PRM001-ENDedicated outdoor-air systems

    Next, define the

    cooling and heating plants

    represented by the fan coil

    system and the rooftop air

    conditioner.

    9 Add two new cooling

    plants and two new

    heating plants to the

    Configuration pane.

    10Drag the appropriate

    icons from the

    Equipment Category

    section to define each

    plant.

    11To finish defining this

    equipment, enter the

    information from

    Table 4–9 on page 4–66

    on the appropriate

    equipment tab.

    Finally, assign the coil

    loads of the air distribution

    system to the proper

    cooling and heating plants.

    12Drag each coil in the

    Unassigned Systems/

    Coils pane to the

    appropriate plant in the

    Systems and Plants pane.

    The illustration labeled

    “After” shows the

    completed assignments.

    For cooling, use water-source hea

    pump and air-cooled unitary.

    For heating, use boiler (for the WS

    system) and gas-fired heat

    exchanger.

    Before…

    After…

    Table 4–9 Equipment types

    Cooling Equipment tab Heating Equipment tab

    Water-source heat pump

    3-stage centrifugal chiller

    gas-fired hot water boiler

    Air-cooled unitary split system RAUC-20+ ton scroll

    rooftop gas heat