Dear FLC-OPS Committee, If you plan to attend the NFPA 30 Second Draft meeting remotely, please use the following: Audio NOTE: For audio you MUST dial in on your phone. I will not be enabling the use of computer microphones, as this often causes feedback problems. Conference Number: US (Toll Free): 1-877-860-3058 Participant Code: 556009 URL to additional access numbers: https://www.mymeetingroom.com/cnums.asp?bwebid=8369444&ppc=556009&num=1-719-867-1571 Visual To join the meeting: http://nfpa.adobeconnect.com/jshapiro/ ---------------- If you have never attended an Adobe Connect meeting before: Test your connection: http://nfpa.adobeconnect.com/common/help/en/support/meeting_test.htm Get a quick overview: http://www.adobe.com/go/connectpro_overview Adobe, the Adobe logo and Adobe Connect are either registered trademarks or trademarks of Adobe Systems Incorporated in the United States and/or other countries. Best regards, Janna Shapiro Associate Engineer National Fire Protection Association [email protected] Office: (617)-984-7136 Cell: (617)-990-2827

Dear FLC-OPS Committee, - NFPA · 2016-06-17 · Dear FLC-OPS Committee, If you plan to attend the NFPA 30 Second Draft meeting remotely, please use the following: Audio NOTE: For

  • Upload
    others

  • View
    0

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Dear FLC-OPS Committee, - NFPA · 2016-06-17 · Dear FLC-OPS Committee, If you plan to attend the NFPA 30 Second Draft meeting remotely, please use the following: Audio NOTE: For

Dear FLC-OPS Committee, If you plan to attend the NFPA 30 Second Draft meeting remotely, please use the following: Audio NOTE: For audio you MUST dial in on your phone. I will not be enabling the use of computer microphones, as this often causes feedback problems. Conference Number: US (Toll Free): 1-877-860-3058 Participant Code: 556009 URL to additional access numbers: https://www.mymeetingroom.com/cnums.asp?bwebid=8369444&ppc=556009&num=1-719-867-1571 Visual To join the meeting: http://nfpa.adobeconnect.com/jshapiro/ ---------------- If you have never attended an Adobe Connect meeting before: Test your connection: http://nfpa.adobeconnect.com/common/help/en/support/meeting_test.htm Get a quick overview: http://www.adobe.com/go/connectpro_overview Adobe, the Adobe logo and Adobe Connect are either registered trademarks or trademarks of Adobe Systems Incorporated in the United States and/or other countries. Best regards, Janna Shapiro Associate Engineer National Fire Protection Association [email protected] Office: (617)-984-7136 Cell: (617)-990-2827

Page 2: Dear FLC-OPS Committee, - NFPA · 2016-06-17 · Dear FLC-OPS Committee, If you plan to attend the NFPA 30 Second Draft meeting remotely, please use the following: Audio NOTE: For

FLCOPS.2016-06 Agenda.doc

FLAMMABLE AND COMBUSTIBLE LIQUIDS CODE COMMITTEE

MEMORANDUM

TO: NFPA 30 Technical Committee on Operations

FROM: R. P. Benedetti

DATE: June 9, 2016

SUBJECT: Agenda for NFPA 30 Second Draft Meeting Wednesday June 22, 2016 — 8:00 AM to 12:00 PM

_________________________________________________________________________________ Ladies and Gentlemen: Attached is the Agenda for the NFPA 30, Flammable and Combustible Liquids Code, Second Draft meeting of the NFPA 30 Technical Committee on Operations, to be held 8:00 AM to 12:00 PM, Wednesday, June 22, 2016, at the Marriott Hotel, Charleston SC. This Agenda will also be posted to the NFPA 30 Document Information Page at http://www.nfpa.org/30 If you have additional items for the Agenda, please bring them with you to the meeting. P.S. The last page of the Agenda is a summary of the motions and actions that can be taken on Public

Comments at the Second Draft Meeting. rpb/ cc FLCC Meeting Folder FLCOPS/NM

Page 3: Dear FLC-OPS Committee, - NFPA · 2016-06-17 · Dear FLC-OPS Committee, If you plan to attend the NFPA 30 Second Draft meeting remotely, please use the following: Audio NOTE: For

FLCOPS.2016-06 Agenda.doc

FLAMMABLE AND COMBUSTIBLE LIQUIDS CODE COMMITTEE

AGENDA — NFPA 30 Second Draft Meeting

NFPA 30 Technical Committee on Operations

Marriott Hotel, Charleston SC Wednesday, June 22, 2016, 8:00 AM to 12:00 PM

1. Call to Order. 2. Introduction of Attendees. Update of Committee Roster. [Attachment № A1] 3. Approval of Minutes of Last Meeting. (September, 2015, Austin TX) [Attachment № A2] 4. Report of Committee Chair. 5. Report of Staff Liaison.

Staff Presentation Technical Committee Membership Status. [Attachment № A3] Document Revision Schedule for Annual 2014 Cycle. [Attachment № A4]

6. Member Reports on Current Issues. [As Necessary] 7. Review and Act on Public Comments to the First Draft Report for the 2018 edition of NFPA 30.

Encl.: Public Comments - Chapters 17 – 20, 28, 29 & Annex F [Attachment № A5] First Revisions & Committee Inputs [Attachment № A6]

8. Global Comment: Definitions of Container and Intermediate Bulk Container. Deletion of term “portable tank” in certain chapters.

[Attachment № A7] 9. Planning for Next Edition of NFPA 30: Annual 2020 Revision Cycle / NFPA 30-2021. [Public Input Closing Date is June 27, 2018] 10. Old Business. [NONE] 11. New Business. [NONE] 12. Schedule Next Meeting(s). 13. Adjournment.

Page 4: Dear FLC-OPS Committee, - NFPA · 2016-06-17 · Dear FLC-OPS Committee, If you plan to attend the NFPA 30 Second Draft meeting remotely, please use the following: Audio NOTE: For

Address List No PhoneOperations FLC-OPS

Flammable and Combustible Liquids

Janna E. Shapiro04/27/2016

FLC-OPS

Peter J. Willse

ChairGlobal Asset Protection Services100 Constitution Plaza, 12th FloorHartford, CT 06103XL Global Asset Protection ServicesAlternate: Mark Driscoll

I 3/21/2006FLC-OPS

William V. F. Cosey

PrincipalSavannah River Nuclear Solutions, LLC2705 Roses RunAiken, SC 29803-7634

U 04/05/2016

FLC-OPS

Claire V. De Taeye

PrincipalTravelers Insurance Company75 Town Centre DriveRochester, NY 14623Alternate: Timothy S. Murphy

I 10/4/2001FLC-OPS

Douglas W. Fisher

PrincipalFisher Engineering, Inc.10475 Medlock Bridge Road, Suite 520Johns Creek, GA 30097-4437

SE 10/23/2013

FLC-OPS

Harold E. Grossman II

PrincipalAlcoa, Inc.Warrick Operations4000 West State Route 66, Bldg. 05Newburgh, IN 47630

U 9/30/2004FLC-OPS

Dwight H. Havens

PrincipalBechtel Marine Propulsion Corporation20 Bellflower RoadMalta, NY 12020-4431

U 7/24/1997

FLC-OPS

Richard J. Hild

PrincipalAxalta Coating Systems1003 Bogart CircleBel Air, MD 21014

M 10/1/1993FLC-OPS

Jay J. Jablonski

PrincipalHSB PLC1 State Street, 9th FloorHartford, CT 06103-3199Alternate: David Upchurch

I 4/1/1996

FLC-OPS

Alwin A Kelly

PrincipalJENSEN HUGHES3610 Commerce Dr Ste 817Baltimore, MD 21227Alternate: Joseph L. Scheffey

SE 08/11/2014FLC-OPS

Todd M. Kidd

PrincipalLiberty Mutual Insurance Companies520 Mainsail RoadSalisbury, NC 28146-1402Alternate: Joshua Goodson

I 08/11/2014

FLC-OPS

David C. Kirby

PrincipalBaker Engineering & Risk Consultants, Inc.1560 Clearview HeightsCharleston, WV 25312-5948Alternate: Duane L. Rehmeyer

SE 1/1/1991FLC-OPS

Gregory D. Kirby

PrincipalCytec Solvay Group1 Heilman AvenueWillow Island, WV 26134

M 1/17/1997

FLC-OPS

Richard S. Kraus

PrincipalAPI/Petroleum Safety Consultants210 East Fairfax Street, Apt. 600Falls Church, VA 22046-2909American Petroleum InstituteAlternate: Tim D. Blackford

M 10/1/1995FLC-OPS

John A. LeBlanc

PrincipalFM Global1151 Boston-Providence TurnpikePO Box 9102Norwood, MA 02062-9102Alternate: Christopher J. Wieczorek

I 10/10/1997

1

bbenedetti
Text Box
Attachment No. A1
Page 5: Dear FLC-OPS Committee, - NFPA · 2016-06-17 · Dear FLC-OPS Committee, If you plan to attend the NFPA 30 Second Draft meeting remotely, please use the following: Audio NOTE: For

Address List No PhoneOperations FLC-OPS

Flammable and Combustible Liquids

Janna E. Shapiro04/27/2016

FLC-OPS

David P. Nugent

PrincipalGlobal Risk Consultants2037 Clover RoadNorthbrook, IL 60062-6422

SE 04/08/2015FLC-OPS

Leo T. Old

PrincipalEnsafe, Inc.5724 Summer Trees DriveMemphis, TN 38134

SE 10/28/2014

FLC-OPS

Anthony M. Ordile

PrincipalHaines Fire & Risk Consulting Corporation1 Linda Lane, Suite BSouthampton, NJ 08088Alternate: Stephen W. Haines

SE 10/1/1993FLC-OPS

Alfredo M. Ramirez

PrincipalUL LLC333 Pfingsten RoadNorthbrook, IL 60062-2096Alternate: Roland A. Riegel

RT 4/15/2004

FLC-OPS

Robert N. Renkes

PrincipalPetroleum Equipment Institute6514 East 69th StreetTulsa, OK 74133Alternate: Robert H. Young

M 1/1/1984FLC-OPS

John W. Richmond, Sr.

PrincipalEastman Chemical CompanyPO Box 511 (B-54)Kingsport, TN 37662

M 4/14/2005

FLC-OPS

Ronald G. Schaffhauser

PrincipalPPG Industries, Inc.Monroeville Business and Technology Center440 College Park DriveMonroeville, PA 15146-1536

M 1/15/2004FLC-OPS

George A. Seuss, Jr.

PrincipalThe Hanover Insurance GroupVerlan Fire Insurance Company10480 Little Patuxent ParkwaySuite 500Columbia, MD 21044-3506

I 7/22/1999

FLC-OPS

Clark D. Shepard

PrincipalExxonMobil CorporationResearch & Engineering3225 Gallows Road, Room 3A2111Fairfax, VA 22037Alternate: David W. Owen

M 7/12/2001FLC-OPS

Brian Sickinger

PrincipalMitsui Sumitomo Marine ManagementS22 W36040 Country Meadow CourtDousman, WI 60555

I 08/11/2014

FLC-OPS

Glen E. Smith

PrincipalArgus Consulting, Inc.6363 College Boulevard, Suite 600Overland Park, KS 66211-1882American Railway Engineering & Maintenance-of-WayAssn.

U 10/23/2013FLC-OPS

Michael D. Snyder

PrincipalDow Corning Corporation2200 West Salzburg Road (Mail #CO2244)Midland, MI 48686-0994NFPA Industrial Fire Protection SectionAlternate: Donald B. Hicks

U 7/28/2006

2

Page 6: Dear FLC-OPS Committee, - NFPA · 2016-06-17 · Dear FLC-OPS Committee, If you plan to attend the NFPA 30 Second Draft meeting remotely, please use the following: Audio NOTE: For

Address List No PhoneOperations FLC-OPS

Flammable and Combustible Liquids

Janna E. Shapiro04/27/2016

FLC-OPS

David C. Swenson

PrincipalThe Sherwin-Williams Company333 Republic Building101 Prospect AvenueCleveland, OH 44115-1093The Sherwin-Williams CompanyAlternate: Randy Slama

M 04/05/2016FLC-OPS

Scott M. Tyler

PrincipalSasol North America1716 N. Woodland Forest DriveLake Charles, LA 70611Edison Electric Institute

U 4/16/1999

FLC-OPS

David B. Wechsler

PrincipalConsultant27706 Dalton Bluff CourtKaty, TX 77494-2729American Chemistry Council

U 3/2/2010FLC-OPS

Scott Wright

Principal3M Company3M CenterBuilding 224 6W 28St. Paul, MN 55144-1000Alternate: Richard E. Stutzki

U 12/08/2015

FLC-OPS

Tim D. Blackford

AlternateChevron Energy Technology Company1200 Smith Street, Room 31050Houston, TX 77002American Petroleum InstitutePrincipal: Richard S. Kraus

M 3/1/2011FLC-OPS

Mark Driscoll

AlternateGlobal Asset Protection Services135 Highland Avenue, Unit 3Winthrop, MA 02152Principal: Peter J. Willse

I 10/23/2003

FLC-OPS

Joshua Goodson

AlternateLiberty MutualAccount Engineer102 Founders Pointe BoulevardFranklin, TN 37064Principal: Todd M. Kidd

I 12/08/2015FLC-OPS

Stephen W. Haines

AlternateHaines Fire & Risk Consulting Corp.1 Linda Lane, Suite BSouthampton, NJ 08088Principal: Anthony M. Ordile

SE 8/2/2010

FLC-OPS

Donald B. Hicks

AlternateDow Corning Corporation3901 South Saginaw RoadPO Box 995, Mail #60Midland, MI 48686-0995NFPA Industrial Fire Protection SectionPrincipal: Michael D. Snyder

U 4/14/2005FLC-OPS

Timothy S. Murphy

AlternateTravelers Insurance Company1000 Windward ConcourseAlpharetta, GA 30005-2052Principal: Claire V. De Taeye

I 03/03/2014

FLC-OPS

David W. Owen

AlternateExxonMobil CorporationResearch and Engineering2800 Decker Drive MOB 541Baytown, TX 77520Principal: Clark D. Shepard

M 7/12/2001FLC-OPS

Duane L. Rehmeyer

AlternateBaker Engineering & Risk Consultants, Inc.709 Highspire RoadGlenmore, PA 19343Principal: David C. Kirby

SE 8/2/2010

3

Page 7: Dear FLC-OPS Committee, - NFPA · 2016-06-17 · Dear FLC-OPS Committee, If you plan to attend the NFPA 30 Second Draft meeting remotely, please use the following: Audio NOTE: For

Address List No PhoneOperations FLC-OPS

Flammable and Combustible Liquids

Janna E. Shapiro04/27/2016

FLC-OPS

Roland A. Riegel

AlternateUL LLC1285 Walt Whitman RoadMelville, NY 11747-3085Principal: Alfredo M. Ramirez

RT 4/15/2004FLC-OPS

Joseph L. Scheffey

AlternateJENSEN HUGHES3610 Commerce Drive, Suite 817Baltimore, MD 21227-1652Principal: Alwin A Kelly

SE 1/10/2002

FLC-OPS

Randy Slama

AlternateSherwin Williams Co101 Prospect Ave Nw333 RepublicCleveland, OH 44115 UsThe Sherwin-Williams CompanyPrincipal: David C. Swenson

M 04/05/2016FLC-OPS

Richard E. Stutzki

Alternate3M Company22614 Route 84 NorthCordova, IL 61242-9779Principal: Scott Wright

U 10/29/2012

FLC-OPS

David Upchurch

AlternateHSB PLCPO Box 1088Cornelia, GA 30531Principal: Jay J. Jablonski

I 10/29/2012FLC-OPS

Christopher J. Wieczorek

AlternateFM Global1151 Boston-Providence TurnpikePO Box 9102Norwood, MA 02062-9102Principal: John A. LeBlanc

I 1/14/2005

FLC-OPS

Robert H. Young

AlternatePetroleum Equipment InstitutePO Box 2380Tulsa, OK 74101-2380Principal: Robert N. Renkes

M 12/08/2015FLC-OPS

William R. Hamilton

Nonvoting MemberUS Department of LaborOccupational Safety & Health Administration200 Constitution Ave. NW, Room N3609Washington, DC 20210

E 3/4/2009

FLC-OPS

Jack Woycheese

Member Emeritus1649 Constable StreetPrescott, AZ 86301

SE 1/1/1991FLC-OPS

Janna E. Shapiro

Staff LiaisonNational Fire Protection Association1 Batterymarch ParkQuincy, MA 02169-7471

08/04/2015

4

Page 8: Dear FLC-OPS Committee, - NFPA · 2016-06-17 · Dear FLC-OPS Committee, If you plan to attend the NFPA 30 Second Draft meeting remotely, please use the following: Audio NOTE: For

FLAMMABLE AND COMBUSTIBLE LIQUIDS CODE COMMITTEE

Minutes of NFPA 30 First Draft Meeting

NFPA 30 Technical Committee on Operations

Crowne Plaza Hotel, Austin TX Thursday, September 10, 2015, 8:00 AM to 12:00 PM

I. Participation T. D. Blackford, Chevron Energy Technology Company

(Alternate to R. S. Kraus - Rep. American Petroleum Institute) C. V. De Taeye, Travelers Insurance Company (via web conference)

D. W. Fisher, Fisher Engineering Inc. (via web conference) S. W. Haines, Haines Fire & Risk Consulting Corporation (Alternate to A. M. Ordile) D. H. Havens, Bechtel Marine Propulsion Corporation D. B. Hicks, Dow Corning Corporation (via web conference)

(Alternate to M. Snyder - Rep. NFPA Industrial Fire Protection Section) R. J. Hild, Axalta Coating Systems J. J. Jablonski, HSB PLC A. A. Kelly, JENSEN HUGHES T. M. Kidd, Liberty Mutual Insurance Company G. D. Kirby, Cytec Solvay Group R. S. Kraus, Petroleum Safety Consultants (Rep. American Petroleum Institute) J. A. LeBlanc, FM Global T. S. Murphy, Travelers Insurance Company (Alternate to C. V. De Taeye) D. P. Nugent, Global Risk Consultants L. T. Old, Ensafe, Inc. A. M. Ordile, Haines Fire & Risk Consulting Corporation A. M. Ramirez, UL LLC R. N. Renkes, Petroleum Equipment Institute J. W. Richmond, Sr., Eastman Chemical Company R. A. Riegel, UL LLC (Alternate to A. M. Ramirez) R. G. Schaffhauser, PPG Industries, Inc. J. L. Scheffey, JENSEN HUGHES (Alternate to A. A. Kelly) (via web conference) G. A. Seuss Jr., Hanover Insurance Group / Verlan Fire Insurance Company

G. E. Smith, Argus Consulting Inc. (Rep. American Railway Engineering & Maintenance-of-Way Association) M. D. Snyder, Dow Corning Corporation (via web conference) (Rep. NFPA Industrial Fire Protection Section)

R. E. Stutzki, 3M Company (Alternate to S. Wright) (via web conference) D. B. Wechsler, Katy TX (Rep. American Chemistry Council) R. P. Benedetti, National Fire Protection Association, STAFF LIAISON J. Shapiro, National Fire Protection Association, STAFF LIAISON GUESTS: A. Burke, Restaurant Technologies, Inc. G. Carter, Justrite Manufacturing Company LLC J. V. Cignatta, Datanet Engineering Inc. G. R. Colonna, National Fire Protection Association

bbenedetti
Text Box
Attachment No. A2
Page 9: Dear FLC-OPS Committee, - NFPA · 2016-06-17 · Dear FLC-OPS Committee, If you plan to attend the NFPA 30 Second Draft meeting remotely, please use the following: Audio NOTE: For

W. V. Cosey, Savannah River Nuclear Solutions LLC J. J. Foley, JENSENHUGHES P. E. Myers, PEMY Consulting LLC K. Nicolello, UL LLC L. Rindfuss, Marsh Risk Consulting D. C. Swenson, The Sherwin-Williams Company S. M. Tyler, Sasol North America J. J. Wanko, U. S. Occupational Safety and Health Administration R. Young, Petroleum Equipment Institute Members Unable to Attend M. Driscoll, Global Asset Protection Services (Alternate to P. J. Willse) H. E. Grossman II, Alcoa, Inc. W. R. Hamilton, U. S. Occupational Safety and Health Administration D. C. Kirby, Baker Engineering & Risk Consultants, Inc. D. W. Owen, ExxonMobil Corporation (Alternate to C. Shepard) D. L. Rehmeyer, Baker Engineering & Risk Consultants, Inc. (Alternate to D. C. Kirby) C. D. Shepard, ExxonMobil Corporation B. Sickinger, Mitsui Sumitomo Marine Management D. Upchurch, HSB PLC (Alternate to J. J. Jablonski) C. J. Wieczorek, FM Global (Alternate to J. LeBlanc) P. J. Willse, Global Asset Protection Services, CHAIR II. Minutes 1. The meeting was called to order at 8:00 AM on September 10, 2015 by Technical Committee

Chair pro Tempore Dwight Havens. 2. Attendees introduced themselves. The Technical Committee roster was corrected as needed. 3. The Minutes of the last meeting (June 2013, San Antonio TX) were unanimously approved as

corrected; the meeting was chaired by Dwight Havens, in the absence of Pete Willse. 4. Technical Committee Chair had nothing to report. 5. Staff Liaison Janna Shapiro reported on the following:

Scopes of Technical Correlating Committee and Technical Committees. The proposed amendments to the Committee scope statement were agreed upon. The Staff Liaison was directed to ballot the new scope statement.

Membership Status. The Staff Liaison reported on recent changes to committee membership and on the balance of interests on the committees.

Document Revision Schedule for NFPA 30-2018. The Staff Liaison reviewed the revision schedule for the Annual 2017 revision schedule.

6. Technical Committee member Dick Kraus reported on activities at the recent meeting of the

International Fire Code Committee. 7. The Technical Committee reviewed and took action on all public inputs to amend those chapters of

the 2015 edition of NFPA 30 that are under this Technical Committee’s jurisdiction. These included Public Inputs to Chapters 17, 18, 19, and 29, as well as two Global Inputs (low pressure dispensing containers; referenced standards). These resulted in 4 First Revisions and 1 Committee Inputs. With respect to the Global Input on low pressure dispensing containers, the Technical Committee determined that these were beyond the scope of NFPA 30 and should be dealt with under another Technical Committee project. The Staff Liaison was directed to proceed with the First Draft ballot.

Page 10: Dear FLC-OPS Committee, - NFPA · 2016-06-17 · Dear FLC-OPS Committee, If you plan to attend the NFPA 30 Second Draft meeting remotely, please use the following: Audio NOTE: For

8. There was no recent correspondence requiring the Technical Correlating Committee’s attention. 9. Under “Old Business”:

- The Technical Committee discussed the value of defining two terms: “liquids in process” and “staged liquids”. - The Technical Committee decided to establish a Task Group to draft a proposal for consideration at the 2nd Draft meeting to eliminate a conflict between the quantities allowed in Subsection 18.5.4 for incidental storage and use and the maximum allowable quantities given in Chapter 9.

10. There was no new business requiring the Technical Committee’s attention. 11. The Technical Committee deferred to the Correlating Committee on scheduling the 2nd Draft

Meeting. 12. The meeting adjourned at 1:30 PM.

Page 11: Dear FLC-OPS Committee, - NFPA · 2016-06-17 · Dear FLC-OPS Committee, If you plan to attend the NFPA 30 Second Draft meeting remotely, please use the following: Audio NOTE: For

FLCC Scope Statements & Member Balance.doc - 5/3/2016

FLAMMABLE AND COMBUSTIBLE LIQUIDS CODE COMMITTEE

COMMITTEE MEMBERSHIP BALANCE

TCC on Flammable & Combustible Liquids - FLC-AAC Principals: 12 M: 2 (17%)* U: 4 (33%) Voting Alternates: 0 I/M: 0 L/C: 0 Alternates: 4 R/T: 1 (8%) E: 0 Non-Voting: 5 I: 1 (8%) SE: 4 (33%) Emeritus: 3

Task Group: 0 Hold List: 1 Balance: OK

*(containers: 0 liquids: 2)

T/C on Fundamentals of Flammable & Combustible Liquids - FLC-FUN Principals: 27 M: 6 (22%)* U: 6 (22%)** Voting Alternates: 0 I/M: 0 L/C: 0 Alternates: 8 R/T: 1 (4%) E: 1 (4%) Non-Voting: 1 I: 6 (22%) SE: 7 (26%)

Emeritus: 1 Task Group: 0 Hold List: 6 Balance: OK

*(containers: 1 fire suppression equipment: 1 liquids: 4 tanks: 0) **(end user: 3 warehousing: 1)

T/C on Operations - FLC-OPS Principals: 30 M: 8 (27%)* U: 8 (27%) Voting Alternates: 0 I/M: 0 L/C: 0 Alternates: 15 R/T: 1 (3%) E: 0 Non-Voting: 1 I: 7 (23%) SE: 6 (20%) Emeritus: 1

Task Group: 0 Hold List: 5 Balance: OK

*(liquid handling equipment: 1 liquids: 7)

bbenedetti
Text Box
Attachment No. A3
Page 12: Dear FLC-OPS Committee, - NFPA · 2016-06-17 · Dear FLC-OPS Committee, If you plan to attend the NFPA 30 Second Draft meeting remotely, please use the following: Audio NOTE: For

FLCC Scope Statements & Member Balance.doc - 5/3/2016

T/C on Storage & Warehousing of Containers & Portable Tanks - FLC-SWC

Principals: 29 M: 6 (21%)* U: 7 (25%) Voting Alternates: 0 I/M: 2 (4%)** L/C: 0 Alternates: 14 R/T: 1 (4%) E: 0 Non-Voting: 0 I: 7 (25%) SE: 6 (21%)

Emeritus: 1 Task Group: 0 Hold List: 4 Balance: OK

*(containers: 1 fire suppression systems: 1 liquids: 3 safety cabinets & cans: 1) **(fire suppression systems: 2)

T/C on Tank Storage & Piping Systems - FLC-TAN Principals: 27 M: 5 (18%)* U: 8 (30%) Voting Alternates: 0 I/M: 0 L/C: 0 Alternates: 13 R/T: 1 (4%) E: 1 (4%) Non-Voting: 1 I: 3 (11%) SE: 9 (33%) Emeritus: 4

Task Group: 0 Hold List: 4 Balance: OK

*(fire suppression systems: 0 liquid handling equipment: 2 tanks: 2

tank appurtenances: 1)

Page 13: Dear FLC-OPS Committee, - NFPA · 2016-06-17 · Dear FLC-OPS Committee, If you plan to attend the NFPA 30 Second Draft meeting remotely, please use the following: Audio NOTE: For

2017 ANNUAL REVISION CYCLE *Public Input Dates may vary according to standards and schedules for Revision Cycles may change.  Please check the NFPA Website for the most up‐to‐date information on Public Input Closing Dates and schedules at 

www.nfpa.org/document # (i.e. www.nfpa.org/101) and click on the Next Edition tab. 

Process Stage 

 

Process Step  

Dates for TC 

Dates forTC with 

CC   Public Input Closing Date*  7/6/15  7/6/15 

  Final Date for TC First Draft Meeting  12/14/15  9/14/15 

Public Input  Posting of First Draft and TC Ballot  2/1/16  10/26/15 

Stage  Final date for Receipt of TC First Draft ballot  2/22/16  11/16/15 

`(First Draft)  Final date for Receipt of TC First Draft ballot ‐ recirc  2/29/16  11/23/15 

  Posting of First Draft for CC Meeting    11/30/15 

  Final date for CC First Draft Meeting    1/11/16 

  Posting of First Draft and CC Ballot    2/1/16 

  Final date for Receipt of CC First Draft ballot    2/22/16 

  Final date for Receipt of CC First Draft ballot ‐ recirc    2/29/16 

  Post First Draft Report for Public Comment  3/7/16  3/7/16 

 

  Public Comment closing date   5/16/16  5/16/16 

  Final Date to Publish Notice of Consent Standards (Standards that received no Comments) 

5/30/16  5/30/16 

  Appeal Closing Date for Consent Standards (Standards that received no Comments) 

6/13/16  6/13/16 

  Final date for TC Second Draft Meeting  10/31/16  7/25/16 

Comment  Posting of Second Draft and TC Ballot  12/12/16  9/5/16 

Stage    Final date for Receipt of TC Second Draft ballot  1/2/17  9/26/16 

(Second  Final date for receipt of TC Second Draft ballot ‐ recirc  1/9/17  10/3/16 

Draft)  Posting of Second Draft for CC Meeting    10/10/16 

  Final date for CC Second Draft Meeting    11/21/16 

  Posting of Second Draft for CC Ballot    12/12/16 

  Final date for Receipt of CC Second Draft ballot    1/2/17 

  Final date for Receipt of CC Second Draft ballot ‐ recirc    1/9/17 

  Post Second Draft Report for NITMAM Review  1/16/17  1/16/17 

 

Tech Session  Notice of Intent to Make a Motion (NITMAM) Closing Date  2/20/17  2/20/17 

Preparation  Posting of Certified Amending Motions (CAMs) and Consent Standards 

4/17/17  4/17/17 

(& Issuance)  Appeal Closing Date for Consent Standards   5/2/17  5/2/17 

  SC Issuance Date for Consent Standards   5/12/17  5/12/17 

 

Tech Session  Association Meeting for Standards with CAMs  6/4‐7/2017  6/4‐7/2017 

 

Appeals and  Appeal Closing Date for Standards with CAMs  6/27/17  6/27/17 

Issuance  SC  Issuance Date for Standards with CAMs  8/10/17  8/10/17 

 

Approved:  October 30, 2012                                                       Revised________________________ 

bbenedetti
Text Box
Attachment No. A4
Page 14: Dear FLC-OPS Committee, - NFPA · 2016-06-17 · Dear FLC-OPS Committee, If you plan to attend the NFPA 30 Second Draft meeting remotely, please use the following: Audio NOTE: For

Public Comment No. 41-NFPA 30-2016 [ Section No. 18.5.4 [Excluding any

Sub-Sections] ]

The quantity of liquid located outside of identified storage areas, such as storage cabinets, other insideliquid storage areas, general-purpose warehouses, or other specific processing areas that are cut off fromthe general plant area by at least a 2-hour fire separation in operational areas separated from dedicatedstorage areas in accordance with Section 9.9, or separated from specific processing areas in accordancewith Section 17.6 , shall meet the requirements of 18.5.4.1.

Statement of Problem and Substantiation for Public Comment

Provides clearer lead-in text for the quantity limits in 18.5.4.1, coordinates with the proposal to Section 11.3, and adds reference to related requirements in Chapters 9 and 17.

Related Public Comments for This Document

Related Comment Relationship

Public Comment No. 39-NFPA 30-2016 [Section No. 11.3] Complement each other.

Public Comment No. 43-NFPA 30-2016 [Section No. 18.5.4.1]

Related Item

Committee Input No. 107-NFPA 30-2015 [Section No. 18.5.4]

Submitter Information Verification

Submitter Full Name: Alwin Kelly

Organization: Jensen Hughes

Affilliation: N/A

Street Address:

City:

State:

Zip:

Submittal Date: Fri May 13 14:30:46 EDT 2016

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

154 of 176 6/13/2016 1:09 AM

bbenedetti
Text Box
Attachment No. A5
Page 15: Dear FLC-OPS Committee, - NFPA · 2016-06-17 · Dear FLC-OPS Committee, If you plan to attend the NFPA 30 Second Draft meeting remotely, please use the following: Audio NOTE: For

Public Comment No. 43-NFPA 30-2016 [ Section No. 18.5.4.1 ]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

155 of 176 6/13/2016 1:09 AM

Page 16: Dear FLC-OPS Committee, - NFPA · 2016-06-17 · Dear FLC-OPS Committee, If you plan to attend the NFPA 30 Second Draft meeting remotely, please use the following: Audio NOTE: For

18.5.4.1

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

156 of 176 6/13/2016 1:09 AM

Page 17: Dear FLC-OPS Committee, - NFPA · 2016-06-17 · Dear FLC-OPS Committee, If you plan to attend the NFPA 30 Second Draft meeting remotely, please use the following: Audio NOTE: For

The maximum quantity of liquids permitted for incidental operations in a single fire area shall not exceed thegreater of the following:

(1)the hazard analysis required in Chapter 6 accounts for these quantities.

(2) The aggregate sum of the following in containers :

25

(a) 10 gal (

95

(a) 38 L) of Class IA liquids

in containers

(a)

120

(a) 30 gal (

454

(a) 115 L) of Class IB

,

(a) and/or Class IC

, Class II, or Class III

(a) liquids

in containers

(a)

1585

(a) 30 gal (

6000

(a) 115 L) of

any combination of the following:

(a) Class

IB, IC,

(a) II

, or IIIA liquids in metal portable tanks or metal intermediate bulk containers, each not exceeding 793gal (3000 L)

(3) Class II or Class IIIA liquids in nonmetallic intermediate bulk containers, each not exceeding 793 gal(3000 L)

(4) 20 portable tanks or intermediate bulk containers each not exceeding 793 gal (3000 L) of Class IIIBliquids

(a) liquids

(b) 80 gal (303 L) of Class IIIA liquids

(c) 3,300 gal (12,500 L) of Class IIIB liquids

18.5.4.1.1 The quantities in 18.5.4.1(2) shall be permitted to be increased 100 percent where

* The amount required to supply incidental operations for one continuous 24-hour period, provided

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

157 of 176 6/13/2016 1:09 AM

Page 18: Dear FLC-OPS Committee, - NFPA · 2016-06-17 · Dear FLC-OPS Committee, If you plan to attend the NFPA 30 Second Draft meeting remotely, please use the following: Audio NOTE: For

stored in approved flammable liquids storage cabinets or in safety cans in accordance with the firecode.

18.5.4.1.2 The quantities in 18.5.4.1(2) shall be permitted to be increased 100percent in buildings equipped throughout with an approved automatic sprinklersystem installed in accordance with NFPA 13, with protection at least equivalent tothat for Extra Hazard (Group 2) occupancies .

18.5.4.1.3 Where both 18.5.4.1.1 and 18.5.4.1.2 are applicable , the increaseshall be permitted to be applied accumulatively.

Additional Proposed Changes

File Name Description Approved

NFPA_30_-_proposed_revisions_to_Section_18-5-4.docx

Microsoft Word 2013 version document with track changes to code text.

Statement of Problem and Substantiation for Public Comment

Coordinate quantity limits for incidental operations (potentially open use of liquids) with the storage maximum allowable quantities (MAQs) in NFPA 30 Chapter 9, and the MAQ in fire codes (including IFC). IFC open use scenarios are considered to be comparable to the NFPA 30 incidental operations scenarios. The prior quantity limits in 18.5.4.1 potentially permitted significantly greater quantities of Class I liquids in incidental operational areas than permitted in Chapter 9 for storage areas, which are generally closed containers.

Related Public Comments for This Document

Related Comment Relationship

Public Comment No. 41-NFPA 30-2016 [Section No. 18.5.4 [Excluding anySub-Sections]]

Parent and childsections

Public Comment No. 39-NFPA 30-2016 [Section No. 11.3] Complementary content

Related Item

Committee Input No. 107-NFPA 30-2015 [Section No. 18.5.4]

Submitter Information Verification

Submitter Full Name: Alwin Kelly

Organization: Jensen Hughes

Affilliation: N/A

Street Address:

City:

State:

Zip:

Submittal Date: Fri May 13 14:59:15 EDT 2016

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

158 of 176 6/13/2016 1:09 AM

Page 19: Dear FLC-OPS Committee, - NFPA · 2016-06-17 · Dear FLC-OPS Committee, If you plan to attend the NFPA 30 Second Draft meeting remotely, please use the following: Audio NOTE: For

Public Comment No. 28-NFPA 30-2016 [ Section No. 19.7.2.2.2 ]

19.7.2.2.2

Nonmetallic cooking oil storage tanks shall meet the following requirements:Tanks shall be listed for usewith cooking oil, unless otherwise approved.Tanks in accordance with UL 2152, Outline of Investigation forSpecial Purpose NonMetalic Containers and Tanks for Specific Combustible or Noncombustible Liquids. Nonmetalic tanks shall not exceed 200 gal (757 L) per tank.

Statement of Problem and Substantiation for Public Comment

Public Comment – The committee raised 2 points at the 1st Draft meeting, which we have responses to, for re-consideration of the original proposal (PI#79) to reference UL2152 in the Code body under 9.7.2.2:

The standard has not yet been published - Since discussion of this proposal at the first draft meeting, UL2152 was published on October 2, 2015 so is no longer a draft document, and is available for members to verify the comprehensive tank requirements developed in collaboration with this technical committee during the last Code cycle to support revisions to the new Ch 19.7.

The proposal would eliminate the opportunity for other listings - First, there is no other standard currently available to address the specific use of nonmetallic tanks for the storage of new or used cooking oil in restaurants or similar commercial food preparing applications having engineered transfer systems. We worked with industry, the fire service and this committee to develop the UL2152 requirements, and one manufacturer has already been Listed to them. Second, UL has a number of product safety standards adopted in the NFPA family of codes, and this does not eliminate the opportunity for other product certifiers, who are competitors of UL, to test to UL standards and certify products, which is done on a regular basis. Nor does it prohibit anyone else to propose addition of another standard with an equivalent level of safety, should it exist in the future.

Related Item

Public Input No. 79-NFPA 30-2015 [Section No. 19.7.2.2]

Submitter Information Verification

Submitter Full Name: Ronald Farr

Organization: UL LLC

Street Address:

City:

State:

Zip:

Submittal Date: Wed May 11 14:41:59 EDT 2016

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

159 of 176 6/13/2016 1:09 AM

Page 20: Dear FLC-OPS Committee, - NFPA · 2016-06-17 · Dear FLC-OPS Committee, If you plan to attend the NFPA 30 Second Draft meeting remotely, please use the following: Audio NOTE: For

Public Comment No. 40-NFPA 30-2016 [ Section No. 19.7.2.2.2 ]

19.7.2.2.2

Nonmetallic cooking oil storage tanks shall meet the following requirements:Tanks shall shall be listed foruse with cooking oil, unless otherwise approved.Tanks shall in accordance with UL 2152, Outline ofInvestigation for Special Purpose Nonmetallic Containers and Tanks for Specific Combustible orNoncombustible Liquids . Nonmetallic tanks shall not exceed 200 gal (757 L) per tank.

Statement of Problem and Substantiation for Public Comment

Public Input No. 79-NFPA 30-2015 [Section 19.7.2.2] was rejected by the Committee because the standard referenced, UL 2152, had not been issued at the time. This standard has since been issued. This Public Comment proposes that the language from PI-79 be reinstated, as doing so will simplify the code enforcers ability to determine compliance to construction and performance criteria listed in the code.

Related Item

Public Input No. 79-NFPA 30-2015 [Section No. 19.7.2.2]

Submitter Information Verification

Submitter Full Name: Andrew Burke

Organization: Restaurant Technologies Inc

Street Address:

City:

State:

Zip:

Submittal Date: Fri May 13 14:29:35 EDT 2016

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

160 of 176 6/13/2016 1:09 AM

Page 21: Dear FLC-OPS Committee, - NFPA · 2016-06-17 · Dear FLC-OPS Committee, If you plan to attend the NFPA 30 Second Draft meeting remotely, please use the following: Audio NOTE: For

First Revision No. 104-NFPA 30-2015 [ Section No. 17.10 ]

17.10 Containment, Drainage, and Spill Control.

17.10.1

A facility shall be designed and operated to prevent the discharge of liquids to public waterways, publicsewers, or adjoining property.

17.10.1*

Emergency drainage systems shall be provided to direct liquid leakage and fire protection water to asafe location.

17.10.2*

Emergency drainage systems shall be provided to direct liquid leakage and fire protection water to a safelocation.

17.10.3

Emergency drainage systems, if connected to public sewers or discharged into public waterways, shall beequipped with traps or separators.

17.10.2

Emergency drainage systems, if connected to public sewers or discharged into public waterways, shallbe equipped with traps or separators.

17.10.3

A facility shall be designed and operated to prevent the discharge of liquids to public waterways, publicsewers, or adjoining property.

Submitter Information Verification

Submitter Full Name: FLC-OPS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Sep 10 09:54:31 EDT 2015

Committee Statement

Committee Statement: This section has been renumbered in a more logical order.

Response Message:

Public Input No. 50-NFPA 30-2015 [Section No. 17.10]

Ballot Results

This item has passed ballot

26 Eligible Voters

1 Not Returned

25 Affirmative All

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

100 of 163 6/9/2016 11:19 AM

bbenedetti
Text Box
Attachment No. A6
Page 22: Dear FLC-OPS Committee, - NFPA · 2016-06-17 · Dear FLC-OPS Committee, If you plan to attend the NFPA 30 Second Draft meeting remotely, please use the following: Audio NOTE: For

0 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

Shepard, Clark D.

Affirmative All

De Taeye, Claire V.

Fisher, Douglas W.

Grossman II, Harold E.

Havens, Dwight H.

Hild, Richard J.

Jablonski, Jay J.

Kelly, Alwin A

Kidd, Todd M.

Kirby, Gregory D.

Kirby, David C.

Kraus, Richard S.

LeBlanc, John A.

Nugent, David P.

Old, Leo T.

Ordile, Anthony M.

Ramirez, Alfredo M.

Renkes, Robert N.

Richmond, Sr., John W.

Schaffhauser, Ronald G.

Seuss, Jr., George A.

Smith, Glen E.

Snyder, Michael D.

Stutzki, Richard E.

Wechsler, David B.

Willse, Peter J.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

101 of 163 6/9/2016 11:19 AM

Page 23: Dear FLC-OPS Committee, - NFPA · 2016-06-17 · Dear FLC-OPS Committee, If you plan to attend the NFPA 30 Second Draft meeting remotely, please use the following: Audio NOTE: For

First Revision No. 108-NFPA 30-2015 [ Section No. 18.4.7 ]

18.4.7

Listed flexible connectors shall be permitted to be used where vibration exists. Approved hose shall bepermitted to be used at transfer stations.

Submitter Information Verification

Submitter Full Name: FLC-OPS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Sep 10 13:03:47 EDT 2015

Committee Statement

Committee Statement: The deleted information covering flexible connectors is covered by 27.5.2.

Response Message:

Ballot Results

This item has passed ballot

26 Eligible Voters

1 Not Returned

25 Affirmative All

0 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

Shepard, Clark D.

Affirmative All

De Taeye, Claire V.

Fisher, Douglas W.

Grossman II, Harold E.

Havens, Dwight H.

Hild, Richard J.

Jablonski, Jay J.

Kelly, Alwin A

Kidd, Todd M.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

102 of 163 6/9/2016 11:19 AM

Page 24: Dear FLC-OPS Committee, - NFPA · 2016-06-17 · Dear FLC-OPS Committee, If you plan to attend the NFPA 30 Second Draft meeting remotely, please use the following: Audio NOTE: For

Kirby, Gregory D.

Kirby, David C.

Kraus, Richard S.

LeBlanc, John A.

Nugent, David P.

Old, Leo T.

Ordile, Anthony M.

Ramirez, Alfredo M.

Renkes, Robert N.

Richmond, Sr., John W.

Schaffhauser, Ronald G.

Seuss, Jr., George A.

Smith, Glen E.

Snyder, Michael D.

Stutzki, Richard E.

Wechsler, David B.

Willse, Peter J.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

103 of 163 6/9/2016 11:19 AM

Page 25: Dear FLC-OPS Committee, - NFPA · 2016-06-17 · Dear FLC-OPS Committee, If you plan to attend the NFPA 30 Second Draft meeting remotely, please use the following: Audio NOTE: For

Committee Input No. 107-NFPA 30-2015 [ Section No. 18.5.4 ]

18.5.4

The quantity of liquid located outside of identified storage areas, such as storage cabinets, other insideliquid storage areas, general-purpose warehouses, or other specific processing areas that are cut off fromthe general plant area by at least a 2-hour fire separation, shall meet the requirements of 18.5.4.1.

18.5.4.1

The maximum quantity of liquids permitted for incidental operations in a single fire area shall not exceedthe greater of the following:

(1)

(2) The aggregate sum of the following:

(a) 25 gal (95 L) of Class IA liquids in containers

(b) 120 gal (454 L) of Class IB, Class IC, Class II, or Class III liquids in containers

(c) 1585 gal (6000 L) of any combination of the following:

i. Class IB, IC, II, or IIIA liquids in metal portable tanks or metal intermediate bulk containers,each not exceeding 793 gal (3000 L)

ii. Class II or Class IIIA liquids in nonmetallic intermediate bulk containers, each not exceeding793 gal (3000 L)

(d) 20 portable tanks or intermediate bulk containers each not exceeding 793 gal (3000 L) of ClassIIIB liquids

Submitter Information Verification

Submitter Full Name: FLC-OPS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Sep 10 12:43:40 EDT 2015

Committee Statement

CommitteeStatement:

The technical committee is organizing a task group jointly with FLC-SWC to coordinate theallowable quantities in 18.5.4 with the MAQ's in chapter 9 and NFPA 1. Interested parties areencouraged to provide the task group with any suggestions or comments deemed appropriate.

ResponseMessage:

Ballot Results

This item has not been balloted

* The amount required to supply incidental operations for one continuous 24-hour period

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

104 of 163 6/9/2016 11:19 AM

Page 26: Dear FLC-OPS Committee, - NFPA · 2016-06-17 · Dear FLC-OPS Committee, If you plan to attend the NFPA 30 Second Draft meeting remotely, please use the following: Audio NOTE: For

First Revision No. 109-NFPA 30-2015 [ Section No. 19.7.3.2 ]

19.7.3.2 Foundations for and Anchoring of Cooking Oil Storage Tanks.

19.7.3.2.1*

Tank supports Tanks shall be secured to the tank and to the floor to prevent the tank from tipping over.For a flat-bottom tank resting directly on the floor, the tank shall be secured to the floor to prevent the tankfrom tipping over.

19.7.3.2.2

In areas subject to earthquakes, tank supports, the foundation, and anchoring shall meet the requirementsof the applicable building code for the specific seismic zone. Engineering evaluation by a qualified,impartial outside agency shall be an acceptable method of meeting this requirement.

19.7.3.2.3

Where a tank is located in areas subject to flooding, the method for anchoring the tank to the floor shallbe capable of preventing the tank, either full or empty, from floating during a rise in water level up to theestablished maximum flood stage. Engineering evaluation by a qualified, impartial outside agency shall bean acceptable method of meeting this requirement.

Supplemental Information

File Name Description

Annex_Material_A.19.7.3.2.1.docx New annex material added for A.19.7.3.2.1

Submitter Information Verification

Submitter Full Name: FLC-OPS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Sep 18 08:16:10 EDT 2015

Committee Statement

CommitteeStatement:

With respect to PI 35:

19.7.2.5: The committee discussed this issue extensively in the development of this section.There is a potential hazard for large spills and the means for automatic and fail-safe controls areneeded.

19.7.2.6.3: Electric immersion heaters are the source of frequent plastic tank ignitions. Thecommittee recognized this with the development of the criteria and intended to exclude the use ofimmersion heaters in non-metallic tanks.

19.7.3.2 Clarifies the application of the code with respect to permissible means of securing tanks.The change allows for additional means of securing the tank as proposed by PI 35.

ResponseMessage:

Public Input No. 35-NFPA 30-2015 [Section No. 19.7]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

105 of 163 6/9/2016 11:19 AM

Page 27: Dear FLC-OPS Committee, - NFPA · 2016-06-17 · Dear FLC-OPS Committee, If you plan to attend the NFPA 30 Second Draft meeting remotely, please use the following: Audio NOTE: For

Ballot Results

This item has passed ballot

26 Eligible Voters

1 Not Returned

24 Affirmative All

0 Affirmative with Comments

0 Negative with Comments

1 Abstention

Not Returned

Shepard, Clark D.

Affirmative All

De Taeye, Claire V.

Fisher, Douglas W.

Grossman II, Harold E.

Havens, Dwight H.

Hild, Richard J.

Jablonski, Jay J.

Kidd, Todd M.

Kirby, Gregory D.

Kirby, David C.

Kraus, Richard S.

LeBlanc, John A.

Nugent, David P.

Old, Leo T.

Ordile, Anthony M.

Ramirez, Alfredo M.

Renkes, Robert N.

Richmond, Sr., John W.

Schaffhauser, Ronald G.

Seuss, Jr., George A.

Smith, Glen E.

Snyder, Michael D.

Stutzki, Richard E.

Wechsler, David B.

Willse, Peter J.

Abstention

Kelly, Alwin A

Abstain due to client representation.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

106 of 163 6/9/2016 11:19 AM

Page 28: Dear FLC-OPS Committee, - NFPA · 2016-06-17 · Dear FLC-OPS Committee, If you plan to attend the NFPA 30 Second Draft meeting remotely, please use the following: Audio NOTE: For

First Revision No. 110-NFPA 30-2015 [ Section No. 29.3.28.4 ]

29.3.28.4

Where no fire water main is provided, at least two 150 lb (68 kg) a minimum of two wheeled dry chemicalextinguishers with minimum ratings of 240-B:C each shall be provided. The extinguishers shall be locatedwithin 50 ft (15 m) of pump or manifold areas and shall be easily reached along emergency access paths.Existing 150 lb (68 kg) dry chemical extinguishers that continue to be maintained in accordance withNFPA 10 shall be permitted to remain in service.

Submitter Information Verification

Submitter Full Name: FLC-OPS

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Sep 18 08:27:31 EDT 2015

Committee Statement

CommitteeStatement:

The rating is the appropriate method to identify the extinguishers. Clarification was provided toallow existing 150 lb extinguishers to remain in service.

ResponseMessage:

Public Input No. 24-NFPA 30-2015 [Section No. 29.3.28.4]

Ballot Results

This item has passed ballot

26 Eligible Voters

1 Not Returned

25 Affirmative All

0 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

Shepard, Clark D.

Affirmative All

De Taeye, Claire V.

Fisher, Douglas W.

Grossman II, Harold E.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

141 of 163 6/13/2016 1:30 AM

Page 29: Dear FLC-OPS Committee, - NFPA · 2016-06-17 · Dear FLC-OPS Committee, If you plan to attend the NFPA 30 Second Draft meeting remotely, please use the following: Audio NOTE: For

Havens, Dwight H.

Hild, Richard J.

Jablonski, Jay J.

Kelly, Alwin A

Kidd, Todd M.

Kirby, Gregory D.

Kirby, David C.

Kraus, Richard S.

LeBlanc, John A.

Nugent, David P.

Old, Leo T.

Ordile, Anthony M.

Ramirez, Alfredo M.

Renkes, Robert N.

Richmond, Sr., John W.

Schaffhauser, Ronald G.

Seuss, Jr., George A.

Smith, Glen E.

Snyder, Michael D.

Stutzki, Richard E.

Wechsler, David B.

Willse, Peter J.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

142 of 163 6/13/2016 1:30 AM

Page 30: Dear FLC-OPS Committee, - NFPA · 2016-06-17 · Dear FLC-OPS Committee, If you plan to attend the NFPA 30 Second Draft meeting remotely, please use the following: Audio NOTE: For

First Revision No. 106-NFPA 30-2015 [ Section No. A.29.3.28 ]

A.29.3.28

Because of the many variables involved, exact requirements cannot be provided. However, TableA.29.3.28 provides guidance on the level of fire protection typically provided at wharves and marineterminals handling flammable liquids.

Table A.29.3.28 Typical Fire Protection for Wharves and Marine Terminals

Locations

WaterDemand

(gpm)

Hydrant

Monitorsa

(gpm)HoseReels

Fire Extinguisher DryChemical

InternationalShore

Connection

EmergencyEquipment

Lockers30

lb 120-B:C

150 lbWheeled 240-B:C

Wheeled

Bargeterminals

500–1000 Two 500Two11⁄4

2 NR NR 1

Tankers20,000 DWTand under

1000–2000 Two 500Two11⁄4

2 1 1 1

20,001–70,000DWT

2000 Two 1000Four

11⁄4c2 2d 2 1

70,001 DWTand over 2000e Two 1000

Four

11⁄4c3 2d 2 1

Sea islands 2000–4000e Three 1000Four

11⁄4c4 2 3 2

For SI units, 1 gpm = 3.8 L/min; 1 gal = 3.8 L; 1 lb = 0.45 kg.

NR: Not required.

aA minimum of two 11⁄2 in. (38 mm) hydrant outlets should be provided at each monitor riser.

bC This c an be provided by onshore mobile equipment.

cOne hose reel at each berth should have foam capability.

dThe proximity of adjacent berths can reduce the total required.

eUnder-dock systems are optional. Add water for under-dock system (0.16 × area).

fUnder-dock systems are optional. Add foam for under-dock system (0.16 × 0.3 × 30 × area).

Supplemental Information

File Name Description

FR_106_Table.docxcorrect formatting of table

Submitter Information Verification

Submitter Full Name: FLC-OPS

Organization: [ Not Specified ]

Street Address:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

145 of 163 6/13/2016 1:30 AM

Page 31: Dear FLC-OPS Committee, - NFPA · 2016-06-17 · Dear FLC-OPS Committee, If you plan to attend the NFPA 30 Second Draft meeting remotely, please use the following: Audio NOTE: For

City:

State:

Zip:

Submittal Date: Thu Sep 10 12:14:20 EDT 2015

Committee Statement

CommitteeStatement:

The rating is the appropriate method to identify the extinguishers. Table A.29.3.28 has beenamended to designate the appropriate extinguisher rating instead of designating extinguishers byweight.

ResponseMessage:

Public Input No. 25-NFPA 30-2015 [Section No. A.29.3.28]

Ballot Results

This item has passed ballot

26 Eligible Voters

1 Not Returned

25 Affirmative All

0 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

Shepard, Clark D.

Affirmative All

De Taeye, Claire V.

Fisher, Douglas W.

Grossman II, Harold E.

Havens, Dwight H.

Hild, Richard J.

Jablonski, Jay J.

Kelly, Alwin A

Kidd, Todd M.

Kirby, Gregory D.

Kirby, David C.

Kraus, Richard S.

LeBlanc, John A.

Nugent, David P.

Old, Leo T.

Ordile, Anthony M.

Ramirez, Alfredo M.

Renkes, Robert N.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

146 of 163 6/13/2016 1:30 AM

Page 32: Dear FLC-OPS Committee, - NFPA · 2016-06-17 · Dear FLC-OPS Committee, If you plan to attend the NFPA 30 Second Draft meeting remotely, please use the following: Audio NOTE: For

Richmond, Sr., John W.

Schaffhauser, Ronald G.

Seuss, Jr., George A.

Smith, Glen E.

Snyder, Michael D.

Stutzki, Richard E.

Wechsler, David B.

Willse, Peter J.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

147 of 163 6/13/2016 1:30 AM

Page 33: Dear FLC-OPS Committee, - NFPA · 2016-06-17 · Dear FLC-OPS Committee, If you plan to attend the NFPA 30 Second Draft meeting remotely, please use the following: Audio NOTE: For

Recommended changes to NFPA 30, 2015 Edition (track changes)

Chapter 1

1.3.2 Chapters 9 through 12 shall apply to the storage of flammable or combustible liquids in containers , portable tanks, and intermediate bulk containers in the occupancies covered by the scope of each chapter.

1.3.3 Chapter 13 shall apply to the storage of flammable or combustible liquids in containers , portable tanks, and intermediate bulk containers in detached unprotected buildings.

1.3.4 Chapter 14 shall apply to the storage of flammable or combustible liquids in containers, portable

tanks, and intermediate bulk containers in hazardous materials storage lockers.

1.3.5 Chapter 15 shall apply to the outdoor storage of flammable or combustible liquids in containers , portable tanks, and intermediate bulk containers.

1.3.6 Chapter 16 shall apply to fire protection design criteria used to protect storage of flammable or combustible liquids in containers, portable tanks, and intermediate bulk containers.

Chapter 3

3.3.2.3 Inside Liquid Storage Area. A room or building used for the storage of liquids in containers or portable tanks, separated from other types of occupancies.

3.3.12* Container. Any vessel of 119 gal (450 L) or less capacity used for transporting or storing liquids

having a capacity that does not exceed 3000 L (793 gal).

3.3.12.1 Closed Container. A container, as herein defined, so sealed by means of a lid or other device that neither liquid nor vapor will escape from it at ordinary temperatures.

3.3.12.2 Intermediate Bulk Container. Any container closed vessel having a liquid capacity greater than 450 L (119 gal) but not greater than exceeding 3000 L (793 gal) and intended for storing and transporting liquids, as defined in Title 49, Code of Federal Regulations, Parts 100

through199 or in Part 6 of the United Nations’ Recommendations on the Transport of Dangerous Goods.

3.3.12.3* Non-Bulk Container. Any container having a capacity that does not exceed 450 L (119

gal).

3.3.12.34* Nonmetallic Container. Any container, as defined in 3.3.12, constructed of glass, plastic, fiber, or a combination thereof, and which might include metal componentsa material

other than metal.

3.3.12.4* Nonmetallic Intermediate Bulk Container. An intermediate bulk container, as defined in 3.3.12.2, constructed of glass, plastic, fiber, or a material other than metal.

A.3.3.12.3 Non-Bulk Container. The U.S. DOT defines non-bulk packaging as having up to 119 gal (450 L) capacity in 49 CFR 171.8.

bbenedetti
Text Box
Attachment No. A7
Page 34: Dear FLC-OPS Committee, - NFPA · 2016-06-17 · Dear FLC-OPS Committee, If you plan to attend the NFPA 30 Second Draft meeting remotely, please use the following: Audio NOTE: For

A.3.3.12.3 Nonmetallic Container. Permissible nonmetallic containers for shipping Class I, Class II, and Class IIIA liquids are governed by the hazardous materials transportation regulations promulgated by

the United Nations publication, Recommendations on the Transport of Dangerous Goods , and the U.S. Department of Transportation's Hazardous Materials Regulations, Title 49, Code of Federal Regulations. Small tanks for Class IIIB liquids are not governed by these regulations. Fiber portable tanks for Class IIIB

liquids include composite designs consisting of a multi-ply cardboard box with a rigid or flexible plastic bladder.

A.3.3.12.4 Nonmetallic Intermediate Bulk Container. Permissible nonmetallic intermediate bulk

containers for shipping Class I, Class II, and Class IIIA liquids are governed by the hazardous materials transportation regulations promulgated by the United Nations publication, Recommendations on the Transport of Dangerous Goods, and the U.S. Department of Transportation's Hazardous Materials

Regulations, Title 49, Code of Federal Regulations. Intermediate bulk cContainers for Class IIIB liquids are not governed by these regulations. Fiber intermediate bulk containers for Class IIIB liquids include composite designs consisting of single- or multi-ply a cardboard boxes with a flexible plastic bladders,

which is commonly referred to as a “bag-in-box” containers.

3.3.34 Liquid Storage Room. A room that is used for the storage of liquids in containers, portable tanks, or intermediate bulk containers, has a floor area that does not exceed 500 ft2 (46 m2), and might be totally

enclosed within a building —that is, the room might have no exterior walls.

3.3.50 Staging. Temporary storage in a process area of liquids in containers in a process area, intermediate bulk containers, and portable tanks.

3.3.52 Terminal. That portion of a property where liquids are received by tank vessel, pipelines, tank car, or tank vehicle and are stored or blended in bulk for the purpose of distributing such liquids by tank vessel, pipeline, tank car, tank vehicle, portable tank, or container.

Chapter 9

9.1.1 This chapter shall apply to the storage of flammable and combustible liquids in containers as defined in section 3.3.12.:

(1) Drums or other containers that do not exceed 119 gal (450 L) individual capacity

(2) Portable tanks that do not exceed 660 gal (2500 L) individual capacity

(3) Intermediate bulk containers that do not exceed 793 gal (3000 L)

9.1.4 This chapter shall not apply to the following:

(1) Containers, intermediate bulk containers, and portable tanks that are used in operations areas, as covered by Chapter 17

[(2) through (7) remain as is]

9.3.9 Where containers, intermediate bulk containers, or portable tanks are stacked, they shall be stacked so that stability is maintained and excessive stress on container walls is prevented.

9.3.9.1 Portable tanks and iIntermediate bulk containers stored more than one high shall be designed to

stack securely, without the use of dunnage.

Page 35: Dear FLC-OPS Committee, - NFPA · 2016-06-17 · Dear FLC-OPS Committee, If you plan to attend the NFPA 30 Second Draft meeting remotely, please use the following: Audio NOTE: For

9.3.9.2 Materials-handling equipment shall be capable of handling containers, portable tanks, and intermediate bulk containers that are stored at all storage levels.

9.3.10 Containers, intermediate bulk containers, and portable tanks in unprotected liquid storage areas shall not be stored closer than 36 in. (915 mm) to the nearest beam, chord, girder, or other roof or ceiling member.

9.4.1* Only the following approved containers, intermediate bulk containers, and portable tanks shall be used for Class I, Class II, and Class IIIA liquids:

(1) Metal containers, metal intermediate bulk containers, and metal portable tanks meeting the

requirements of and containing products authorized by the U.S. Department of Transportation Hazardous Materials Regulations in Title 49, Code of Federal Regulations, Parts 100–199, or by Part 6 of the UN Recommendations on the Transport of Dangerous Goods

[(2) through (7) remain as is]

9.4.2 Each portable tank or intermediate bulk container shall be provided with one or more devices installed in the top with sufficient emergency venting capacity to limit internal pressure under fire

exposure conditions to a gauge pressure of 10 psi (70 kPa) or 30 percent of the bursting pressure of the portable tank, whichever is greater.

9.4.3 The maximum allowable size of a container, intermediate bulk container, or metal portable tank for

Class I, Class II, and Class IIIA liquids shall not exceed that specified in Table 9.4.3.

Table 9.4.3 Maximum Allowable Size of— Containers, Intermediate Bulk Containers (IBCs),

and Portable Tanks

Flammable Liquids Combustible Liquids

Container Type Class IA Class IB Class IC Class II Class IIIA

Glass 1 pt (0.5 L) 1 qt (1 L) 1.3 gal (5 L) 1.3 gal (5 L) 5.3 gal (20 L)

Metal (other than

drums) or approved plastic

1.3 gal (5 L) 5.3 gal (20 L) 5.3 gal (20 L) 5.3 gal (20 L) 5.3 gal (20 L)

Safety cans 2.6 gal (10 L) 5.3 gal (20 L) 5.3 gal (20 L) 5.3 gal (20 L) 5.3 gal (20 L)

Metal drum (e.g., UN 1A1/1A2)

119 gal (450 L)

119 gal (450 L)

119 gal (450 L)

119 gal (450 L)

119 gal (450 L)

Approved metal portable tanks and IBCs

793 gal (3000 L)

793 gal (3000 L)

793 gal (3000 L)

793 gal (3000 L)

793 gal (3000 L)

Rigid plastic IBCs (UN 31H1 or 31H2) and

NP NP NP 793 gal (3000 L)

793 gal (3000 L)

Page 36: Dear FLC-OPS Committee, - NFPA · 2016-06-17 · Dear FLC-OPS Committee, If you plan to attend the NFPA 30 Second Draft meeting remotely, please use the following: Audio NOTE: For

composite IBCs with rigid inner receptacle (UN31HZ1)

Composite IBCs with flexible inner receptacle (UN31HZ2) and

DOT/UN-approved flexible IBCs

NP NP NP NP NP

Non-bulk Bag-in-Box NP NP NP NP NP

Polyethylene UN1H1

and UN1H2, or as authorized by DOT exemption

1.3 gal (5 L) 5.3 gal (20

L)*

5.3 gal (20 L)* 119 gal (450

L)

119 gal (450 L)

Fiber drum NMFC or UFC Type 2A; Types 3A, 3B-H, or 3B-

L; or Type 4A

NP NP NP 119 gal (450 L)

119 gal (450 L)

NP: Not permitted for the container categories so classified unless a fire protection system is provided that is developed in accordance with 16.3.6 and is approved for the specific container and protection against static electricity is provided.

*See 9.4.3.1.

Exception: As provided for in Section 9.1, 9.4.3.1, 9.4.3.2, and 9.4.3.3.

9.12.1 Electrical area classification shall not be required for liquid storage areas where all containers,

intermediate bulk containers, and portable tanks are sealed and are not opened, except as provided for in 9.12.2.

Chapter 10

10.1.1 This chapter shall apply to mercantile occupancies that handle, store, and display liquids in non-

bulk containers, as defined in 3.3.12.3 that do not exceed 119 gal (450 L) individual capacity.

10.1.3 This chapter shall not apply to the following:

(1) Containers, intermediate bulk containers, and portable tanks that are used in operations, as

covered by Chapter 17

10.12.2 Electrical area classification shall not be required for liquid storage areas where all containers, intermediate bulk containers, and portable tanks are sealed and are not opened, except as provided for in

9.12.2.

Page 37: Dear FLC-OPS Committee, - NFPA · 2016-06-17 · Dear FLC-OPS Committee, If you plan to attend the NFPA 30 Second Draft meeting remotely, please use the following: Audio NOTE: For

Chapter 11

11.1 Scope. This chapter shall apply to the storage of flammable and combustible liquids in containers, as defined in 3.3.12, in industrial occupancies. in the following:

(1) Containers that do not exceed 119 gal (450 L) individual capacity

(2) Portable tanks that do not exceed 660 gal (2500 L) individual capacity

(3) Intermediate bulk containers that do not exceed 793 gal (3000 L)

Chapter 12

12.1 Scope. This chapter shall apply to the storage of liquids in in containers, as defined in 3.3.12, in liquid storage rooms, liquid warehouses, and general purpose warehouses. in the following:

(1) Drums or other containers that do not exceed 119 gal (450 L) individual capacity

(2) Portable tanks that do not exceed 660 gal (2500 L) individual capacity

(3) Intermediate bulk containers that do not exceed 793 gal (3000 L) individual capacity

12.3.5 Protected and unprotected solid pile and palletized storage shall be provided with aisles that are

arranged so that no container, portable tank, or intermediate bulk container is more than 20 ft (6 m) from an aisle.

Table 12.6.2.2 Quantity Limitations for Unprotected Liquid Warehouses

Non-Bulk Containers Metal Portable Tanks and Metal IBCs

Rigid Nonmetallic IBCs and Composite IBCs

Liquid Class

Maximu

m Storage Height (ft)

Maximum Total Quantity

per Pile or Rack Section (gal)

Maximum Total Quantity (gal)

Maximu

m Storage Height (ft)

Maximum Total Quantity

per Pile or Rack Section (gal)

Maximum Total Quantity (gal)

Maximu

m Storage Height (ft)

Maximum Total Quantity

per Pile or Rack Section (gal)

Maximum Total Quantity (gal)

IA 5 660 660 NP NP NP NP NP NP

IB 5 1,375 1,375 7 2,000 2,000 NP NP NP

IC 5 2,750 2,750 7 4,000 4,000 NP NP NP

II 10 4,125 8,250 7 5,500 11,000 7 4,125 8,250

Page 38: Dear FLC-OPS Committee, - NFPA · 2016-06-17 · Dear FLC-OPS Committee, If you plan to attend the NFPA 30 Second Draft meeting remotely, please use the following: Audio NOTE: For

IIIA 15 13,750 27,500 7 22,000 44,000 7 13,750 27,500

IIIB 15 13,750 55,000 7 22,000 88,000 7 13,750 55,000

12.8.1* Class IB and IC liquids in containers of 1.3 gal (5 L) or less capacity, Class II liquids in containers

of 5.3 gal (20 L) or less capacity, Class IIIA liquids in containers of 60 gal (230 L) or less capacity, and Class IIIB liquids in containers, intermediate bulk containers, or portable tanks of 275 gal (1040 L) or less capacity shall be permitted to be stored in warehouses that handle combustible commodities, as defined

in NFPA 13, Standard for the Installation of Sprink ler Systems , provided that the storage area for liquids is protected with automatic sprinklers in accordance with either of the following:

12.8.4* Liquids in Plastic Non-Bulk Containers

12.8.5 The following shall apply to the storage of liquids and ordinary combustible commodities in general purpose warehouses:

(1) Liquids shall not be stored in the same pile or in the same rack sections as ordinary combustible

commodities. Where liquids are packaged together with ordinary combustibles, as in kits, the storage shall be considered on the basis of whichever commodity predominates.

(2) Except as provided for in 12.8.5(1), ordinary combustible commodities shall be separated from

liquids in non-bulk containers by a minimum distance of 8 ft (2.4 m).

Chapter 13

13.1 Scope. This chapter shall apply to the storage of liquids in containers, as defined in 3.3.12, in

detached, unprotected buildings., in the following:

(1) Drums or other containers that do not exceed 119 gal (450 L) individual capacity

(2) Portable tanks that do not exceed 660 gal (2500 L) individual capacity

(3) Intermediate bulk containers that do not exceed 793 gal (3000 L)

13.3.5 Solid pile and palletized storage shall be arranged so that piles are separated from each other by at least 4 ft (1.2 m). Aisles shall be provided and arranged so that no container or portable tank is more

than 20 ft (6 m) from an aisle.

13.3.8 Containers, intermediate bulk containers, and portable tanks shall not be stored closer than 36 in. (915 mm) to the nearest beam, chord, girder, or other roof member.

Chapter 14

14.1* Scope. This chapter shall apply to the storage of liquids in containers, as defined in 3.3.12, within movable, modular, prefabricated storage lockers, also known as hazardous materials storage lockers (hereinafter referred to as lockers), specifically designed and manufactured for storage of hazardous

materials., in the following:

Page 39: Dear FLC-OPS Committee, - NFPA · 2016-06-17 · Dear FLC-OPS Committee, If you plan to attend the NFPA 30 Second Draft meeting remotely, please use the following: Audio NOTE: For

(1) Containers that do not exceed 119 gal (450 L) individual capacity

(2) Portable tanks that do not exceed 660 gal (2500 L) individual capacity

(3) Intermediate bulk containers that do not exceed 793 gal (3000 L) individual capacity

Chapter 15

15.1 Scope. This chapter shall apply to the storage of liquids outdoors in containers, as defined in

3.3.12.the following:

(1) Drums or other containers that do not exceed 119 gal (450 L) individual capacity

(2) Portable tanks that do not exceed 660 gal (2500 L) individual capacity

(3) Intermediate bulk containers that do not exceed 793 gal (3000 L) individual capacity

15.2 Definitions Specific to Chapter 15. (Reserved)

15.3 General Requirements. Outdoor storage of liquids in containers, intermediate bulk containers, and

portable tanks shall comply with Table 15.3 and with all applicable requirements of this chapter.

Table 15.3 Storage Limitations for Outside Storage

Liquid Class

Non-Bulk Containers

Portable Tanks and Metal IBCs

Rigid Plastic and Composite IBCs

Minimum Separation Distance (ft)

Maximum

Quantity per Pile (gal)a,b,c

Maximum

Storage Height (ft)

Maximum

Quantity per Pile (gal)

Maximum

Storage Height (ft)

Maximum

Quantity per Pile (gal)a,c

Maximum

Storage Height (ft)

Between Piles

or Rack Sections

To Propert

y Line That Is or Can

Be Built Uponb,d

To Street

, Alley, or

Public Wayb

IA 1,100 10 2,200 7 NP NP 5 50 10

IB 2,200 12 4,400 14 NP NP 5 50 10

IC 4,400 12 8,800 14 NP NP 5 50 10

II 8,800 12 17,600 14 8,800 14 5 25 5

III 22,000 18 44,000 14 22,000 18 5 10 5

Page 40: Dear FLC-OPS Committee, - NFPA · 2016-06-17 · Dear FLC-OPS Committee, If you plan to attend the NFPA 30 Second Draft meeting remotely, please use the following: Audio NOTE: For

15.3.2 No container, intermediate bulk container, or portable tank in a pile shall be more than 200 ft (60

m) from a minimum 20 ft (6 m) wide access way to permit approach of fire control apparatus under all weather conditions.

15.4.1 A maximum of 1100 gal (4160 L) of liquids in containers, intermediate bulk containers, or

portable tanks shall be permitted to be stored adjacent to a building under the same management, provided the following conditions apply:

15.4.4 The quantity of liquid stored shall be permitted to exceed the 1100 gal (4160 L) quantity specified

by 15.4.1 where a minimum distance equal to that specified by Table 15.3 for distance to property line shall be maintained between buildings and the nearest container or portable tank.

15.4.5 Where the provisions of 15.4.1 cannot be met, a minimum distance equal to that specified by

Table 15.3 for distance to property line shall be maintained between buildings and the nearest container or portable tank.

Chapter 16

16.1.1* This chapter shall apply to automatic fire protection systems for all inside storage of flammable and combustible liquids in containers, intermediate bulk containers, and portable tanks as specified in Section 9.4.

A.16.1.1 See Annex E for limitations of the protection criteria of Table 16.5.2.1 through Table 16.5.2.12, particularly for intermediate bulk containers and portable tanks having capacities greater than 60 gal (230 L)

Protected storage allowed under previous editions of this code can be continued if the class of liquids stored, the quantity of liquids stored, fire protection, and building configuration remain unchanged. Table A.16.1.1(a) and Table A.16.1.1(b), reprinted here from the 1993 edition of this code, can be used as a

reference for storage arrangements in previously approved, protected, inside liquid storage areas. It should be noted that the reference to portable tanks is retained in Tables A.16.1.1(a) and A.16.1.1(b), as the reference existed in the source tables.

16.2.3* Relieving-Style Container. A metal container, a metal intermediate bulk container, or a metal

portable tank that is equipped with at least one pressure-relieving mechanism at its top that is designed, sized, and arranged to relieve the internal pressure generated due to exposure to fire so that violent rupture is prevented.

Table A.16.2.3 Common Relieving- and Nonrelieving-Style Metal Containers

Container Type Relieving Style Nonrelieving Style

≤1 qta All N/A

>1 qt and ≤6 gala Metal containers with plastic cap, or flexible or rigid plastic spout

with plastic cap

Metal containers with steel spout and steel screw cap

Page 41: Dear FLC-OPS Committee, - NFPA · 2016-06-17 · Dear FLC-OPS Committee, If you plan to attend the NFPA 30 Second Draft meeting remotely, please use the following: Audio NOTE: For

≤1 gal, friction lid Metal containers with metal friction-fit covers (e.g., paint can lid)

N/A

1 gal and ≤6 gal (lug cover) Metal containers with metal covers held in place with a mechanical friction-fit (e.g., lug-

type) closure mechanism

N/A

>6 gal and ≤60 galb,c (drums) Metal containers, tight or open-

head (drums) having at least one 2 in. plastic plug (Note: Cap seals, if used, need to be plastic

and nonmetallic.)

Open head metal containers with

steel covers having no steel flange openings; or open head and tight head metal containers

with steel flange openings where only steel plugs and/or cap seals are used

>60 gal and ≤793 gal Metal portable tanks or metal intermediate bulk containers with

at least one relief device conforming to the design, construction, and capacity of the

container's section

N/A

16.4.1.1 Figure 16.4.1(a) shall be used for miscible and nonmiscible flammable and combustible liquids in metal containers, metal portable tanks, and metal intermediate bulk containers .

16.4.1.2 Figure 16.4.1(b) shall be used for miscible and nonmiscible flammable and combustible liquids

in nonmetallic containers and in nonmetallic intermediate bulk containers.

16.4.1.3 Figure 16.4.1(c) shall be used for water-miscible flammable and combustible liquids in nonmetallic containers and in nonmetallic intermediate bulk containers.

16.5.2.1 Table 16.5.2.1 shall apply to the following:

(1) Automatic sprinkler protection

(2) Single- or double-row rack storage

(3) Nonmiscible liquids and miscible liquids with concentration of flammable or combustible component greater than 50 percent by volume

(4) Metal containers, metal portable tanks, metal intermediate bulk containers

(5) Relieving- or nonrelieving-style containers

Table 16.5.2.1 Design Criteria for Sprinkler Protection of Single - and Double-Row Rack Storage of Liquids in Metal Containers, Portable Tanks, and IBCs

Page 42: Dear FLC-OPS Committee, - NFPA · 2016-06-17 · Dear FLC-OPS Committee, If you plan to attend the NFPA 30 Second Draft meeting remotely, please use the following: Audio NOTE: For

Contain

er Style and Capacit

y (gal)

Maximum

Storage Height

(ft)

Maxim

um Ceiling Height

(ft)

Ceiling Sprinkler Protection In-Rack Sprinkler Protection

Not

es

Fire

Test Ref. [See

Table D.2(

a)]

Sprinkler Design Sprinkler Minimum

Discharge Flow

(gpm)

Layout (See 16.5.1.

10) Type

Respo

nse

Density (gpm/f

t2)

Area (ft2

)

Typ

e

Respo

nse

NONRELIEVING-STYLE CONTAINERS — LIQUID CLASSES IB, IC, II, IIIA

≤1 16 30 K≥11.2

QR (HT)

0.60 2000

K≥5.6

QR(OT) 30 1 1, 2, 7

1

20 30 K≥11.2

SR or QR (HT)

0.60 2000

K≥5.6

QR(OT) 30 2 1, 2, 7

2

≤5 25 30 K≥8.0 SR or QR (HT)

0.30 3000

K≥5.6

QR(OT) 30 3 1, 7 3

>5 and ≤60

25 30 K≥11.2

SR (HT)

0.40 3000

K≥5.6

QR or SR(OT)

30 5 1, 7 5

NONRELIEVING-STYLE CONTAINERS — LIQUID CLASS IIIB

≤5 40 50 K≥8.0 SR or

QR (HT)

0.30 200

0

K≥5

.6

QR(OT) 30 4 1, 3,

7

4

>5 and ≤60

40 50 K≥8.0 SR (HT)

0.30 3000

K≥5.6

QR(OT) 30 4 1, 3, 7

6

RELIEVING-STYLE CONTAINERS — LIQUID CLASSES IB, IC, II, IIIA

≤5 14 18 K≥11.2

pendent only

QR (HT)

0.65 2000

No in-rack sprinklers required 4 7

25 30 K≥8.0 SR or QR (HT)

0.30 3000

K≥5.6

QR(OT) 30 4,7 1, 5 8

Page 43: Dear FLC-OPS Committee, - NFPA · 2016-06-17 · Dear FLC-OPS Committee, If you plan to attend the NFPA 30 Second Draft meeting remotely, please use the following: Audio NOTE: For

>5 and ≤60

25 30 K≥11.2

SR (HT)

0.60 3000

K≥5.6

QR(OT) 30 6, 7 1 10

Portabl

e tanks and IBCs

25 30 K≥11.

2

SR

(HT)

0.60 300

0

K≥5

.6

QR or

SR(OT)

30 5, 7 1 12

RELIEVING-STYLE CONTAINERS — LIQUID CLASS IIIB

≤ 5 gal 40 50 K≥8.0 SR or QR (HT)

0.30 2000

K≥5.6

QR(OT) 30 4, 7 1 9

>5 and ≤60

40 50 K≥8.0 SR (HT)

0.30 3000

K≥5.6

QR(OT) 30 4, 7 1, 3 11

Portable tanks and

IBCs

40 50 K≥8.0 SR (HT)

0.30 3000

K≥5.6

QR(OT) 30 4, 7 1, 6 13

16.5.2.2 Table 16.5.2.2 shall apply to the following:

(1) Automatic sprinkler protection

(2) Palletized or stacked storage

(3) Nonmiscible liquids and miscible liquids with concentration of flammable or combustible component greater than 50 percent by volume

(4) Metal containers, metal portable tanks, metal intermediate bulk containers

(5) Relieving- or nonrelieving-style containers

Table 16.5.2.2 Design Criteria for Sprinkler Protection of Palletized and Stacked Storage of

Liquids in Metal Containers, Portable Tanks, and IBCs

Container Style and Capacity

(gal)

Maximum Storage Height

(ft)

Maximum Ceiling Height

(ft)

Ceiling Sprinkler Protection

Notes

Fire Test Ref. [See Table

D.2(b)]

Sprinkler Design

Type Response

Density

(gpm/ft2)

Area

(ft2)

NONRELIEVING-STYLE CONTAINERS — LIQUID CLASSES IB, IC, II, IIIA

Page 44: Dear FLC-OPS Committee, - NFPA · 2016-06-17 · Dear FLC-OPS Committee, If you plan to attend the NFPA 30 Second Draft meeting remotely, please use the following: Audio NOTE: For

≤5 4 18 K≥8.0 SR or QR (HT)

0.21 1500 1 1

5 18 K≥8.0 SR or QR

(HT)

0.30 3000 — 2

6.5 30 K≥11.2 QR (HT) 0.45 3000 — 3

>5 and ≤60

5 18 K≥11.2 SR (HT) 0.40 3000 — 4

NONRELIEVING-STYLE CONTAINERS — LIQUID CLASS IIIB

≤5 18 30 K≥8.0 SR or QR

(HT)

0.25 3000 — 5

>5 and ≤60

10 20 K≥8.0 SR (HT) 0.25 3000 — 6

18 30 K≥8.0 SR (HT) 0.35 3000 — 7

RELIEVING-STYLE CONTAINERS — LIQUID CLASSES IB, IC, II, IIIA

≤5 12 30 K≥11.2 pendent

only

QR (HT) 0.60 3000 2 8

>5 and

≤60

5 30 K≥11.2 SR (HT) 0.40 3000 — 9

6.5 30 K≥11.2 SR (HT) 0.60 3000 3 10

Portable tanks

1-high 30 K≥8.0 SR (HT) 0.30 3000 — 14

and IBCs 2-high 30 K≥11.2 SR (HT) 0.60 3000 — 15

RELIEVING-STYLE CONTAINERS — LIQUID CLASS IIIB

≤5 18 30 K≥8.0 SR or QR (HT)

0.25 3000 — 11

>5 and

≤60

10 20 K≥8.0 SR (HT) 0.25 3000 — 12

Page 45: Dear FLC-OPS Committee, - NFPA · 2016-06-17 · Dear FLC-OPS Committee, If you plan to attend the NFPA 30 Second Draft meeting remotely, please use the following: Audio NOTE: For

18 30 K≥8.0 SR (HT) 0.35 3000 — 13

Portable tanks

1-high 30 K≥8.0 SR (HT) 0.25 3000 — 16

and IBCs 2-high 30 K≥11.2 SR (HT) 0.50 3000 — 17

16.5.2.3 Table 16.5.2.3 shall apply to the following:

(1) Foam-water sprinkler protection

(2) Single- or double-row rack storage

(3) Nonmiscible liquids and miscible liquids with concentration of flammable or combustible

component greater than 50 percent by volume

(4) Metal containers, metal portable tanks, metal intermediate bulk containers

(5) Relieving- or nonrelieving-style containers

Table 16.5.2.3 Design Criteria for Foam-Water Sprinkler Protection of Single- or Double-Row Rack Storage of Liquids in Metal Containers, Portable Tanks, and IBCs

Contain

er Style and Capacit

y (gal)

Maximu

m Storage Height

(ft)

Maxim

um Ceiling Height

(ft)

Ceiling Sprinkler

Protection In-Rack Sprinkler Protection

Not

es

Fire Test Ref. [See

Table D.2(c)]

Sprinkler Design Sprinkler Minimum

Discharge Flow

(gpm)

Layout (See 16.5.1.

10)

Typ

e

Respo

nse

Density (gpm/ft

2)

Area (ft2

)

Typ

e

Respo

nse

NONRELIEVING-STYLE CONTAINERS — LIQUID CLASSES IB, IC, II, IIIA

≤5 25 30 K≥8.0

SR or QR (HT)

0.30 2000

K≥5.6

QR or SR (OT)

30 3 1, 2, 4, 5

1

>5 and ≤60

25 30 K≥8.0

SR (HT)

0.30 3000

K≥5.6

QR or SR (OT)

30 3 1, 3, 4, 5

2

NONRELIEVING-STYLE CONTAINERS — LIQUID CLASS IIIB

Page 46: Dear FLC-OPS Committee, - NFPA · 2016-06-17 · Dear FLC-OPS Committee, If you plan to attend the NFPA 30 Second Draft meeting remotely, please use the following: Audio NOTE: For

≤60 40 50 K≥8.0

SR (HT)

0.30 2000

K≥5.6

QR or SR (OT)

30 4 1,5 3

RELIEVING-STYLE CONTAINERS — LIQUID CLASSES IB, IC, II, IIIA

≤5 25 30 K≥8.

0

SR or

QR (HT)

0.30 200

0

K≥5.

6

QR or

SR (OT)

30 4 1, 2,

4, 5

4

>5 and ≤60, portable

tanks and IBCs

25 30 K≥8.0

SR (HT)

0.30 3000

K≥5.6

30 4 1, 3, 4, 5

5

RELIEVING-STYLE CONTAINERS — LIQUID CLASS IIIB

≤60 40 50 K≥8.

0

SR

(HT)

0.30 200

0

K≥5.

6

QR or

SR (OT)

30 4 1, 5 6

16.5.2.4 Table 16.5.2.4 shall apply to the following:

(1) Foam-water sprinkler protection

(2) Palletized or stacked storage

(3) Nonmiscible liquids and miscible liquids with concentration of flammable or combustible

component greater than 50 percent by volume

(4) Metal containers, metal portable tanks, metal intermediate bulk containers

(5) Relieving- or nonrelieving-style containers

Table 16.5.2.4 Design Criteria for Foam-Water Sprinkler Protection of Palletized and Stacked Storage of Liquids in Metal Containers, Portable Tanks, and IBCs

Container

Style and

Maximum

Storage

Maximum

Ceiling

Ceiling Sprinkler Protection

Notes

Fire Test

Ref. [See Sprinkler Design

Page 47: Dear FLC-OPS Committee, - NFPA · 2016-06-17 · Dear FLC-OPS Committee, If you plan to attend the NFPA 30 Second Draft meeting remotely, please use the following: Audio NOTE: For

Capacity (gal)

Height (ft)

Height (ft)

Type Response Density (gpm/ft2)

Area (ft2)

Table D.2(d)]

NONRELIEVING-STYLE CONTAINERS — LIQUID CLASSES IB, IC, II, IIIA

≤5, cartoned

11 30 K≥11.2 SR or QR (HT)

0.40 3000 1 1

≤5, uncartoned

12 30 K≥8.0 SR or QR (HT)

0.30 3000 1 2

>5 and ≤60

5 (1-high) 30 K≥8.0 SR (HT) 0.30 3000 1 3

RELIEVING-STYLE CONTAINERS — LIQUID CLASSES IB, IC, II, IIIA

>5 and ≤60

6.5 (2-high)

30 K≥8.0 SR (HT) 0.30 3000 2, 3 4

10 (3-high)

33 K≥11.2 SR (HT) 0.45 3000 2, 3 6

13.75 (4-high)

33 K≥11.2 SR (HT) 0.60 3000 2, 3 7

Portable tanks and IBCs

1- or 2-high

30 K≥8.0 SR (HT) 0.30 3000 5

16.5.2.5 Table 16.5.2.5 shall apply to the following:

(1) Automatic sprinkler protection

(2) Single-, double-, or multiple-row rack storage

(3) Class IIIB nonmiscible liquids and Class IIIB miscible liquids with concentration of flammable or

combustible component greater than 50 percent by volume

(4) Nonmetallic containers or intermediate bulk containers

(5) Cartoned or uncartoned

Table 16.5.2.5 Design Criteria for Sprinkler Protection of Single-, Double-, and Multiple-Row Rack Storage of Class IIIB Liquids

Closed-Cup

Container or IBC Packaging

Maximum Storage

Maximum Ceiling

Rack

Sprinkler Protection

Fire Test

Page 48: Dear FLC-OPS Committee, - NFPA · 2016-06-17 · Dear FLC-OPS Committee, If you plan to attend the NFPA 30 Second Draft meeting remotely, please use the following: Audio NOTE: For

Flash Point (°F)

Capacity (gal)

Height (ft)

Height (ft) Minimum

Aisle Width (ft)

Depth (ft) Ceiling

Sprinkler Type Design

Ref. [See Table

D.2(e)]

≥200 ≤5 Plastic containers, cartoned or

uncartoned

Unlimited Unlimited 4 Any Any See 16.6.1, Fire

Protection System Design

Scheme “A”

1

≥375 ≤275 Flexible plastic liner within a

composite continuously wound

corrugated paperboard intermediate

bulk container (See Note 1)

28 30 8 Any Any See 16.6.3, Fire

Protection System Design

Scheme “C”

2

≥375 ≤6 Flexible plastic liner

within a composite corrugated paperboard

box

Unlimited Unlimited 8 Any Any See 16.6.3,

Fire Protection System Design

Scheme “C”

2

Chapter 18

18.4.8* The staging of liquids in containers, intermediate bulk containers, and portable tanks shall be

limited to the following:

(1) Containers, intermediate bulk containers, and portable tanks that are in use

(2) Containers, intermediate bulk containers, and portable tanks that were filled during a single shift

(3) Containers, intermediate bulk containers, and portable tanks needed to supply the process for one continuous 24-hour period

(4) Containers, intermediate bulk containers, and portable tanks that are stored in accordance with

Chapter 9

Page 49: Dear FLC-OPS Committee, - NFPA · 2016-06-17 · Dear FLC-OPS Committee, If you plan to attend the NFPA 30 Second Draft meeting remotely, please use the following: Audio NOTE: For

18.4.9 Class I, Class II, or Class IIIA liquids used in a process and staged in the process area shall not be filled in the process area.

Exception No. 1: Intermediate bulk containers and portable tanks that meet the requirements of Chapter 9.

Exception No. 2: Intermediate products that are manufactured in the process area.

18.5.2 Class I liquids or Class II and Class III liquids that are heated up to or above their flash points shall be drawn from or transferred into vessels or, containers, or portable tanks as follows:

(1) From original shipping containers with a capacity of 5.3 gal (20 L) or less

(2) From safety cans

(3) Through a closed piping system

(4) From portable tanks or containers by means of a device that has antisiphoning protection and

that draws through an opening in the top of the tank or container

(5) By gravity through a listed self-closing valve or self-closing faucet

[18.5.4 and 18.5.5 done in MAQ TG]

Chapter 21

21.1 Scope. This chapter shall apply to the following:

(1) The storage of flammable and combustible liquids, as defined in 3.3.33 and Chapter 4, in fixed

storage tanks as defined in 3.3.51.6 that exceed 60 gal (230 L) capacity

(2) The storage of flammable and combustible liquids in portable tanks as defined in 3.3.51.4 that exceed 660 gal (2500 L) capacity

(3) The storage of flammable and combustible liquids in shipping vessels intermediate bulk containers that exceed 793 gal (3000 L) capacity

(4) The design, installation, testing, operation, and maintenance of such tanks, portable tanks, and

shipping vesselsbulk containers

Chapter 22

22.1 Scope. This chapter shall apply to the following:

(1) The storage of flammable and combustible liquids, as defined in 3.3.33 and Chapter 4, in fixed

storage tanks that exceed 60 gal (230 L) capacityas defined in 3.3.51.6

(2) The storage of flammable and combustible liquids in portable tanks as defined in 3.3.51.4 that exceed 660 gal (2500 L) capacity

Page 50: Dear FLC-OPS Committee, - NFPA · 2016-06-17 · Dear FLC-OPS Committee, If you plan to attend the NFPA 30 Second Draft meeting remotely, please use the following: Audio NOTE: For

(3) The storage of flammable and combustible liquids in shipping vessels intermediate bulk containers that exceed 793 gal (3000 L)

(4) The design, installation, testing, operation, and maintenance of such tanks, portable tanks, and shipping vesselsbulk containers

Chapter 23

23.1 Scope. This chapter shall apply to the following:

(1) The storage of flammable and combustible liquids, as defined in 3.3.33 and Chapter 4, in fixed underground tanks

(2) The installation and operation of underground tanks

Page 51: Dear FLC-OPS Committee, - NFPA · 2016-06-17 · Dear FLC-OPS Committee, If you plan to attend the NFPA 30 Second Draft meeting remotely, please use the following: Audio NOTE: For

“I make a motion to…”

“Create a Second Revision by…” “Resolve the Public Comment by…”

“Accepting the Public

Comment”

(This means accepting

EXACTLY what the

comment proposes! If

you want to make ANY

changes to the proposed

language, even as simple

as a comma, you MUST

choose “Reject but

see…”)

“Rejecting the Public

Comment, but see

related Second

Revision”

(This creates a SR based

on the comment, but

allows you to revise the

proposed language)

“Rejecting the Public

Comment”

(This means the

committee does not want

to make any changes

based on the Public

Comment)

“Rejecting the Public

Comment, but hold”

(This means the

committee does not want

to make any changes at

the moment, but the

proposal is held over and

considered during the

next revision cycle)