Upload
others
View
0
Download
0
Embed Size (px)
Citation preview
A S H R A E J O U R N A L a s h r a e . o r g M AY 2 0 2 04 8
2020 ASHRAE TECHNOLOGY AWARD CASE STUDIES
BY BENJAMIN D. HOBBS, MEMBER ASHRAE
DCV, Geothermal Systems Drive Building Design
PHOTO COURTESY FRANK DÖRING
The Lexington, Kentucky, high school currently operates with an energy use intensity of 18.3 kBtu/ft2 (207.8 MJ/m2), 60% lower than the average K–12 school.
©ASHRAE www.ashrae.org. Used with permission from ASHRAE Journal at www.cmta.com. This article may not be copied nor distributed in either paper or digital form without ASHRAE’s permission. For more information about ASHRAE, visit www.ashrae.org.
SECOND PLACE | 2020 ASHRAE TECHNOLOGY AWARD CASE STUDIES
Building at a GlanceFrederick Douglass High SchoolLocation: Lexington, Ky.
Owner: Fayette County Public Schools
Principal Use: Educational facility
Gross Square Feet: 287,125
Conditioned Square Feet: 287,125
Substantial Completion/Occupancy: July 2017/August 2017
Architect Tate Hill Jacobs/Perkins+WillBenjamin D. Hobbs is a mechanical engineer at CMTA, Inc., Lexington, Ky.
The new Frederick Douglass High School is a two-story, 287,125 ft2 (26 675 m2) facility serving 1,800 students and 150 staff in the Fayette County Public School District in Lexington, Kentucky. The facility added the capacity required in the rapidly growing school district with the intent of being the district’s first net zero energy–ready high school. It also is home to the Carter G. Woodson Academy, a 6th–12th grade academy focused on high-potential minority males in the district.
Energy EfficiencyThe high school was designed
through parametric energy analysis
based on accumulated metered data
and knowledge of ANSI/ASHRAE/
IES Standard 90.1 Energy Standard for
Buildings Except Low-Rise Residential
Buildings, design parameters to
select highly efficient systems and
equipment.
A geothermal field under
the parking lot consists of
452, 300 ft (91 m) deep bores on
20 ft (6 m) centers and serves as the
building’s heat source/sink for the
heat pump system. The earth either
absorbs heat from or rejects heat to
the system’s building loop piping
as required to keep the loop within
design parameters, negating the
need for a boiler or cooling tower.
Most of the system’s heat pumps are
two-speed so that the units can cycle
to low speed at part-load condition.
All of the heat pumps have an EER
over 21. The two-way valve on each
heat pump closes when the com-
pressor is off to minimize pumping
energy.
A single centralized geothermal
pump with a 100% backup pump
circulates the geothermal water
through the field and building.
Three pressure sensors located in
remote parts of the piping circuit
measure the differential pressure
between the heat pump supply and
the heat pump return to regulate
the variable frequency drive on the
main centralized pump (Figure 1).
High-volume low-velocity fans
were provided to supplement air
circulation in the two-story cafeteria,
gymnasium, and auxiliary gymna-
sium. These fans draw only 5 A at
120 V, and the increased air velocity
allows for a higher space tempera-
ture setpoint during the warm sea-
sons, thus saving compressor cooling
energy. The fans alone have proven
to keep the gymnasium and auxiliary
gymnasium sufficiently cool during
after-school and weekend activities,
saving additional energy.
With the use of efficient systems
M AY 2 0 2 0 a s h r a e . o r g A S H R A E J O U R N A L 4 9
A S H R A E J O U R N A L a s h r a e . o r g M AY 2 0 2 05 0
ASHRAE TECHNOLOGY AWARD CASE STUDIES20
20
Energy Performance EUI (kBtu/ft2)
Average Fayette County High School 89.9
Best Performing Fayette County High School (2017) 57.2
Average K-12 School 48.5
High School with 75 Energy Star Score 35
Frederick Douglass High School 18.3
FIGURE 1 Hydronic piping schematic.
Geothermal Vault With Purge Ports
Geothermal Well Field
Air Separator
Pumps with VFD
Two-Way Control Valve
Water Source Heat Pump
Differential Pressure Sensor
10Ӯ GS10Ӯ GS
10Ӯ HPS10Ӯ HPR
and equipment, the school currently
operates at an energy use intensity
(EUI) of 18.3 kBtu/ft2 (207.8 MJ/m2).
It has achieved a 100 Energy Star rat-
ing, making it the first perfect score
Energy Star high school in Kentucky
and the most energy-efficient high
school in the state. This outcome has
exceeded the design team’s expecta-
tions and projected energy perfor-
mance compared not only to the
district’s previously best-performing
high school but also to the average K–12 school and the
average Energy Star high school score of 75. According to
Energy Star, the average site EUI for K–12 schools is 48.5
kBtu/ft2 (550.8 MJ/m2), so this building represents a 60%
savings over the average.
Indoor Air QualityThe building was designed around a demand-control
ventilation system. This system utilizes individual CO2
sensors in each occupied space that direct the outside
air supply based on the location of the occupants. Each
space has a variable air volume (VAV) box that modu-
lates to maintain a room CO2 level of 700 ppm above the
ambient CO2 level. This approach allowed the outside
air unit to be right-sized for the number of occupants
and square footage of the building and to deliver fresh
air directly where it is required, while still meeting the
requirements of ANSI/ASHRAE Standard 62.1-2010,
Ventilation and Acceptable Indoor Air Quality. A single
30,000 cfm (14 158 L/s) VAV air-handling unit provides
clean, filtered, neutral room temperature outside air
to every occupied space in the building. The building
relief air and exhaust are drawn back to this unit, and
the outgoing airstream’s sensible and latent energy is
reclaimed with a desiccant energy recovery wheel. A
positive building air pressure relationship to the outside
is maintained to eliminate infiltration of warm, moist
air to prohibit mold spore growth. This unit also uses the
geothermal field as its thermal energy source.
ANSI/ASHRAE Standard 55-2010 Thermal Environmental
Conditions for Human Occupancy, was utilized to ensure
occupant comfort within the building. Shortly after the
school was occupied, the school district enacted new
security protocols, one of which involved screening
all students through metal detectors as they enter the
school. This required that exterior doors in multiple
locations be held open for an hour each morning as stu-
dents lined up for screening. The occupants complained
of high temperatures and humidity every morning, so
the design team investigated. After reviewing several
space temperature trends, they found that the screening
process was allowing the building temperature to spike
right before the building went into occupied mode. An
adjustment was made to enter occupied mode thirty
minutes earlier, resolving the comfort issue.
InnovationTubular daylighting devices and clerestories are used to
daylight the interior corridors. The building’s north-south
orientation allows overhangs to control sunlight entering
the building, with particular attention given to window
exposure. The building has 26% glazing on the verti-
cal surfaces, with 80% of the glazing in the north/south
directions and 20% in the east/west directions to take
advantage of daylighting while minimizing heat gain and
glare. The building orientation also maximized the roof
area for photovoltaic panels, which are optimized with
southern sun exposure. This 240 kW solar array was bid
as an alternate for $491,000, but was not accepted on bid
day. When the array is approved, the roof design can sup-
port all projected panels with no supplemental structures
needed. The design team also took special care to avoid
A S H R A E J O U R N A L a s h r a e . o r g M AY 2 0 2 05 2
ASHRAE TECHNOLOGY AWARD CASE STUDIES20
20
FIGURE 2 Life-cycle cost comparisons—HVAC systems.
37.7
33.7
29.7
25.7
21.7
17.7
13.7
9.7
5.7
1.7
Cost
(In M
illion
s)
0 5 10 15 20 25 30Years
WSHP—Geothermal 4-Pipe
WSHP—Boiler/Cooling Tower
equipment on the roof as much as possible and installed
spare conduits and panel capacity to facilitate the future
installation of these solar panels.
Each classroom has a “green button” as part of the
lighting controls to minimize energy consumption.
The teachers or students can select this button, which
resets the classroom lighting level from 50 footcandles
to 30 footcandles to reduce the illumination. It also
widens the room temperature dead band by 2°F (1.1°C)
up and 2°F (1.1°C) down. This meets the Kentucky
Department of Education building design guides while
allowing the staff and students to become part of the
energy-saving initiative.
A geothermal water-to-water heat pump produces
domestic hot water. The hot water recirculation pump
is turned off during unoccupied hours to reduce heat
loss through the piping. The kitchen cooler and freezers
do not have conventional air-cooled condensing units
but rather utilize the geothermal well field to reject
condenser heat. The cooler/freezer system also has a
dedicated 1/3 hp (0.25 kW) circulating geothermal loop
pump, backed up by emergency generator, to allow the
main centralized 60 hp (45 kW) pump to be shut off
during unoccupied hours and/or summer occupancy.
A domestic water connection was also provided to cycle
water through the compressors should the geothermal
loop need to be drained for maintenance.
Operation and MaintenanceTo maintain HVAC equipment, an additional 12 in.
(305 mm) was added to the above-ceiling space after
design development was complete. All service clearances
are shown on the HVAC equipment. During construc-
tion, engineers walked through the building with facili-
ties maintenance staff to confirm that service clearances
were maintained. The LED lights installed throughout
the school (along with LED theatrical lighting) not only
save energy but have lamp lives measured in decades
and not hours, so relamping is required rarely, if ever.
The electric panels serving lighting, HVAC, and plug
loads are separately submetered so the owner can moni-
tor and control energy usage.
The design team explored three system types during
design: four-pipe hot/chilled water, water source heat
pumps with a boiler and cooling tower central plant,
and water source heat pumps with a geothermal cen-
tral plant. With a payback of six years compared to the
four-pipe system, the geothermal central plant was the
preferred option. Compared to the boiler and cooling
tower central plant, the geothermal central plant had a
payback of 9 years (Figure 2).
The school board hired a third-party commissioning
agent as part of the construction progress, but the design
team performed retro-commissioning as a follow-up
to the original agent. The retro-commissioning was
performed using an experimental method, with full
permission of the owner’s representative and school
principals. This allowed the design team to try multiple
approaches to energy reduction, and if one was found to
adversely affect the occupants, the design team scaled
back to a previous set point that made the occupants
comfortable. One tried approach was to reduce the dif-
ferential pressure set point on the main centralized
geothermal loop pump. The design team initially low-
ered the set point by 5 psi (34 kPa) and found that the
building operated smoothly. An additional decrease of
5 psi (34 kPa) was attempted, but it was quickly found
that the lower set point did not provide adequate flow to
the gymnasium heat pumps.
During the construction process, the building enve-
lope was pressure tested through a series of limited-area
tests. The design team identified a stairwell in the ini-
tial stages of construction that could represent a small
sample of construction methods, with roof, window, and
wall elements. This stairwell failed the initial pressure
test, and the contractor and design team collaborated to
find the problem areas and adjust construction meth-
ods to meet the leakage requirements. The stairwell
was tested three times before passing the pressure test,
and the lessons learned were applied throughout the
M AY 2 0 2 0 a s h r a e . o r g A S H R A E J O U R N A L 5 3
2020 ASHRAE TECHNOLOGY AWARD CASE STUDIES
TOP The building’s energy efficient LED lighting was designed to mimic the pattern of the canopy ceiling at the student entry.
BOTTOM Each classroom has a “green button” as part of the lighting controls to minimize energy consumption. The teachers or students can select this button, which resets the classroom lighting levels and temperatures.
remainder of the construction. This
trial-and-error method of testing
and adjusting a small portion of the
building allowed the entire build-
ing to pressure test to just 0.152
cfm/ft2 (0.772 L/s·m2) of building
envelope at project completion. The
standard testing allows a maximum
of 0.25 cfm/ft2 (1.3 L/s·m2)of building envelope, which
would have allowed a total additional infiltration of over
46,000 cfm (21 710 L/s) to the building. The rigorous
testing procedure undertaken resulted in a 34% reduc-
tion in air infiltration. This process also ensured that the
design team properly met ASHRAE Standard 55-2010
thermal comfort requirements.
Cost EffectivenessThe cost of this energy-efficient school was $206/ft2
($2217/m2), which is within the average range for this
area. The utility cost for the past 12 months has been
$0.58/ft2 ($6.24/m2), which is the lowest cost of any
Fayette County Public Schools high school. The outside
air, LED lighting, and window glazing systems were
some of the design options that the design team took
into consideration to ensure initial cost and utility costs
were minimized. Some choices had a higher initial cost
but resulted in a lower life-cycle cost (Figure 2). The out-
side air system consists of a single external air unit with
air distributed throughout the entire building rather
than multiple outdoor air units, which increased the
initial cost. Individual CO2 sensors were used to control
the appropriate amount of outside air being condi-
tioned. Illuminating with LED light fixtures cost more
initially, but there is also an offset since the HVAC system
can be sized for the reduced heat output. The choice to
use LED lighting allowed for a designed lighting load
of 0.6 W/ft2 (6.5 W/m2), a 50% decrease from the 2012
International Energy Conservation Code allowance of
1.2 W/ft2 (13 W/m2). The cafeteria had vast expanses
of west-facing glass that could have caused significant
heat gain from the late-afternoon sun, so blinds were
installed. East- and west-facing glazing were minimized,
but where deemed architecturally necessary, as in the
large cafeteria, the windows were equipped with motor-
ized shades to allow the occupants to shield the space
from the heat during evening hours.
Environmental ImpactTraditionally, Fayette County Public Schools utilized
variable refrigerant flow (VRF) systems for heating and
cooling in all their buildings. The design team’s selection
of a geothermal system instead of a VRF system reduced
the total amount of refrigerant in the building. If the
HVAC system utilized VRF equipment, there would be
approximately 3,400 lb (1542 kg) of refrigerant in use for
the building. The total refrigerant in all heat pumps in
the geothermal system is approximately 970 lb (440 kg),
a reduction of 2,430 lb (1102 kg) of refrigerant. Utilizing
a central geothermal plant instead of cooling towers also
eliminated the use of any process water
for mechanical cooling.
The reduced energy use at Frederick
Douglass High School saves approxi-
mately 582 metric tons of CO2 annually. https://bit.ly/2V8P31I
Rate this Article