DESCRIPTION YORK Sunline 2000 units are convertible single packages with a common footprint cabinet and common roof curb for all 7-1/2 thru 12-1/2 ton sizes. All units have dual compressors with dual independent refrigeration circuits. The units were designed for light commercial applications and can easily be installed on a roof curb, slab, roof jack or frame. All units are self-contained and assembled on rigid full perimeter base rails allowing for 3-way fork lift access and overhead rigging. Every unit is completely charged, wired, piped and tested at the factory to provide for a quick and easy field installation. The units are available in the following configurations: cooling only, cooling with electric heat and cooling with gas heat. Electric heaters are available as field-installed accessories. Both down and side discharge airflows are available without having to swap panels. The installer simply removes the duct covers for the desired configuration. Economizers may be used on either side or down discharge applications with no modifications required. All models include a 1-year limited warranty on the complete unit. Compressors and electric heater elements each carry an additional 4-year warranty. Aluminized steel tubular heat exchangers carry an additional 9-year warranty. FEATURES COMMON FOOTPRINT / COMMON CABINET - All model sizes and configurations share the exact same footprint cabinet - and therefore the same roof curb. You now have the flexibility of setting one curb and, after the internal load has been determined, placing the proper tonnage unit on that curb. You can even decide between gas or electric heat after the curb has been set. HIGH EFFICIENCY - All units have a minimum EER of 8.5. Gas / electric units have electronic spark ignition and power vented combustion with steady state efficiencies as high as 81.0%. These efficiencies exceed all legislated minimum levels and provide low operating costs. CONVERTIBLE AIRFLOW DESIGN - Both the side and bottom duct openings are covered when they leave the factory. If a side supply / side return is desired you simply remove the two side duct covers from the outside of the unit and discard them. If a bottom supply / return is desired you simply remove the two bottom duct covers and discard them. No panel cutting or swapping is required! Convertible airflow design allows maximum field flexibility and minimum inventory. FACTORY INSTALLED OPTIONS - Economizers,and alternate indoor fan motors can be installed at the factory. The economizers are shipped installed and wired. The outdoor air hood needs only to be field assembled and installed. Field labor dollars can be saved by having the components arrive already installed. FIELD INSTALLED ACCESSORIES - Accessories were designed for quick and easy installation. The motorized damper and economizers simply slide in and electrical connections are made by modular plugs. Electric heaters mount easily and knockouts are provided in the internal partitions to connect the elements to the control box single point kit. The 14" high roof curb is shipped knocked down. The roof curb has an insulated deck. Low ambient controls are available to provide stable unit operation at outdoor temperatures down to 0°F. Propane and high altitude kits are also available to cover all gas heating applications. MOTORIZED AIR DAMPER - Includes slide-in/plug-in damper assembly with rainhood and filters. The outdoor air dampers open when the indoor fan motor is energized. Damper is capable of providing 0% thru 100% outdoor return air opening. MANUAL OUTDOOR DAMPER - Provides 0% thru 35% or 0% thru 100% of return air opening (field adjustable). Designed for duct mounted side or bottom supply/return applications. Includes rain hood assembly and filters WIDE RANGE OF INDOOR AIRFLOWS - All indoor fan motors are belt-drive type providing maximum flexibility to handle most airflow requirements. Factory-installed alternate indoor fan motors are available on some models for high static applications. FULL PERIMETER BASE RAILS - The permanently attached base rails provide a solid foundation for the entire unit and protect the unit during shipment. The rails provide fork lift access from 3 sides and rigging holes are also provided so that an overhead crane can be used to place the units on a roof. 530.18-TG2Y (598) Cont’d. DCG MODEL SHOWN SINGLE PACKAGE GAS / ELECTRIC UNITS AND SINGLE PACKAGE AIR CONDITIONERS D3CE/D3CG102 & D4CE/D4CG090, 120 & 150 7-1/2, 8-1/2, 10 AND 12-1/2 NOMINAL TONS 8.5-9.0 EER SUNLINE 2000

DCE, DCG TECHNICAL GUIDE - upgnet.netupgnet.net/Site/InformationCenter/York/Archive_CDs/York_1999/March... · dce dcg 090 102 120 150 090 102 120 150 evaporator blower centrifugal

  • Upload
    trantu

  • View
    717

  • Download
    35

Embed Size (px)

Citation preview

Page 1: DCE, DCG TECHNICAL GUIDE - upgnet.netupgnet.net/Site/InformationCenter/York/Archive_CDs/York_1999/March... · dce dcg 090 102 120 150 090 102 120 150 evaporator blower centrifugal

DESCRIPTIONYORK Sunline 2000 units are convertible single packages witha common footprint cabinet and common roof curb for all 7-1/2thru 12-1/2 ton sizes. All units have dual compressors with dualindependent refrigeration circuits. The units were designed forlight commercial applications and can easily be installed on aroof curb, slab, roof jack or frame.All units are self-contained and assembled on rigid fullperimeter base rails allowing for 3-way fork lift access andoverhead rigging. Every unit is completely charged, wired,piped and tested at the factory to provide for a quick and easyfield installation.The units are available in the following configurations: coolingonly, cooling with electric heat and cooling with gas heat.Electric heaters are available as field-installed accessories.Both down and side discharge airflows are available withouthaving to swap panels. The installer simply removes the ductcovers for the desired configuration. Economizers may be usedon either side or down discharge applications with nomodifications required.All models include a 1-year limited warranty on the completeunit. Compressors and electric heater elements each carry anadditional 4-year warranty. Aluminized steel tubular heatexchangers carry an additional 9-year warranty.

FEATURESCOMMON FOOTPRINT / COMMON CABINET - All modelsizes and configurations share the exact same footprint cabinet- and therefore the same roof curb. You now have the flexibilityof setting one curb and, after the internal load has beendetermined, placing the proper tonnage unit on that curb. Youcan even decide between gas or electric heat after the curb hasbeen set.HIGH EFFICIENCY - All units have a minimum EER of 8.5. Gas/ electric units have electronic spark ignition and power ventedcombustion with steady state efficiencies as high as 81.0%.These efficiencies exceed all legislated minimum levels andprovide low operating costs.

CONVERTIBLE AIRFLOW DESIGN - Both the side andbottom duct openings are covered when they leave the factory.If a side supply / side return is desired you simply remove thetwo side duct covers from the outside of the unit and discardthem. If a bottom supply / return is desired you simply removethe two bottom duct covers and discard them. No panel cutting

or swapping is required! Convertible airflow design allowsmaximum field flexibility and minimum inventory.

FACTORY INSTALLED OPTIONS - Economizers,andalternate indoor fan motors can be installed at the factory. Theeconomizers are shipped installed and wired. The outdoor airhood needs only to be field assembled and installed. Field labordollars can be saved by having the components arrive alreadyinstalled.

FIELD INSTALLED ACCESSORIES - Accessories weredesigned for quick and easy installation. The motorized damperand economizers simply slide in and electrical connections aremade by modular plugs. Electric heaters mount easily andknockouts are provided in the internal partitions to connect theelements to the control box single point kit.

The 14" high roof curb is shipped knocked down. The roof curbhas an insulated deck.

Low ambient controls are available to provide stable unitoperation at outdoor temperatures down to 0°F.

Propane and high altitude kits are also available to cover allgas heating applications.

MOTORIZED AIR DAMPER - Includes slide-in/plug-in damperassembly with rainhood and filters. The outdoor air dampersopen when the indoor fan motor is energized. Damper iscapable of providing 0% thru 100% outdoor return air opening.

MANUAL OUTDOOR DAMPER - Provides 0% thru 35% or 0%thru 100% of return air opening (field adjustable). Designed forduct mounted side or bottom supply/return applications.Includes rain hood assembly and filters

WIDE RANGE OF INDOOR AIRFLOWS - All indoor fan motorsare belt-drive type providing maximum flexibility to handle mostairflow requirements. Factory-installed alternate indoor fanmotors are available on some models for high staticapplications.

FULL PERIMETER BASE RAILS - The permanently attachedbase rails provide a solid foundation for the entire unit andprotect the unit during shipment. The rails provide fork liftaccess from 3 sides and rigging holes are also provided so thatan overhead crane can be used to place the units on a roof.

530.18-TG2Y (598)

®

Cont’d.

DCG MODELSHOWN

SINGLE PACKAGEGAS / ELECTRIC UNITS ANDSINGLE PACKAGE AIR CONDITIONERS

D3CE/D3CG102 & D4CE/D4CG090, 120 & 1507-1/2, 8-1/2, 10 AND 12-1/2 NOMINAL TONS8.5-9.0 EER

SUNLINE 2000

Page 2: DCE, DCG TECHNICAL GUIDE - upgnet.netupgnet.net/Site/InformationCenter/York/Archive_CDs/York_1999/March... · dce dcg 090 102 120 150 090 102 120 150 evaporator blower centrifugal

UTILITY CONNECTIONS MADE EASY - Gas and electricutility knockouts are provided in the unit underside as well asthe side of the unit. A clearly identified location is provided tomount a field supplied electrical disconnect switch. Utilityconnections can be made quickly and with a minimum amountof field labor.

SIMPLE CONTROL CIRCUIT - A low voltage printed circuitboard contains a low voltage terminal strip. An additional set ofpin connectors is also provided so that field interface of externalcontrols will be simplified. A suction line freezestat is suppliedon all units to protect against loss of charge and coil frostingdue to low economizer outdoor air temperature while thecompressors are running. The electrical control box is not

located in the compressor compartment so the access covercan be removed for troubleshooting without affecting thenormal system operating pressures.

AIR FILTERS - Units come standard with 2" throwaway filters.The unit filter racks can accommodate 1" or 2" filters withoutany modifications.

SYSTEM PROTECTION - Crankcase heaters and internalcompressor protection are standard on all compressors. Everyunit has liquid line filter-driers, high pressure switches andsuction line freezestats to protect all system components. Theunits will operate down to 45°F without any additional lowambient controls.

TABLE OF CONTENTS

®

SUNLINE 2000

FEATURES - CONT’D.

Component Weights...........................................................12Field Wiring ........................................................................13Electrical Data - Basic Units...............................................13Electrical Data - Cooling / Electric Heating ............... 14 & 15Options and Accessories....................................................16Unit Dimensions .................................................................17Roof Curb Dimensions .......................................................19Typical Applications............................................................20

Description ...........................................................................1Features ...............................................................................1Ratings .................................................................................3Physical Data .......................................................................3Cooling Capacities ...............................................................4Blower Performance.............................................................8Blower Motor and Drive Data .............................................12Accessory Static Resistances............................................12

MODEL DCG10 TON

(Gas Heating)

530.18-TG2Y

2 Unitary Products Group

Page 3: DCE, DCG TECHNICAL GUIDE - upgnet.netupgnet.net/Site/InformationCenter/York/Archive_CDs/York_1999/March... · dce dcg 090 102 120 150 090 102 120 150 evaporator blower centrifugal

CAPACITY RATINGS - Cooling / Electric Heating

MODEL

ARI RATINGS GAS HEAT CAPACITYCOOLING CAPACITY

80 / 67-95°FSOUNDRATING(dbels)

INPUT(MBH)

OUTPUT(MBH)

S.S.E.(%)

TEMP.RISE(°F)

GASLINE SIZE

(in. OD)MBH EER IPLV Std. CFMD4CG090N130D4CG090N165

8787

9.009.00

9.609.60 3,000 90 163

204130163

80.080.0

30 - 6030 - 60

3/43/4

D3CG102N130D3CG102N165

102102

9.009.00

9.509.50 3,400 90 163

204130163

80.080.0

30 - 6030 - 60

3/43/4

D4CG120N165D4CG120N200

117117

9.509.50

10.010.0 4,000 90 204

245163198

80.081.0

30 - 6030 - 60

3/43/4

D4CG150N165D4CG150N200

142142

8.508.50

8.308.30 4,600 - 204

245163198

80.080.6

30 - 6030 - 60

3/43/4

NOTES: 1. All gas units are two-stage heating. First stage is 70% of total.2. All 090 -120 units are rated in accordance with ARI Standard 210.3. All 150 units are rated in accordance with ARI Standard 360.4. Sound ratings are in accordance with ARI Standard 270.5. Heaters available as accessories - all with single point power supply.6. EER = Energy Efficiency Ratio - the cooling capacity in BTU’s per hour (BTUH) divided by the power input in watts at any given set of rating conditions, expressed in BTUH per watt (BTUH/watt).7. S.S.E. = Steady State Efficiency. (Percent Output).8 I.P.L.V. = Integrated Part Load Value

RATINGS

MODEL

ARI RATINGS NOMINALELECTRIC

HEATCAPACITY

(KW)

COOLING CAPACITY80 / 67-95°F

SOUNDRATING(dbels)MBH EER IPLV Std. CFM

D4CE090 87 9.00 9.60 3,000 90 9, 18, 24, 36D3CE102 102 9.00 9.50 3,400 90 9, 18, 24, 36D4CE120 117 9.50 10.0 4,000 90 18, 24, 36, 54D4CE150 142 8.50 8.30 4,600 - 18, 24, 36, 54

CAPACITY RATINGS - Cooling / Gas Heating

12-1/2 TON208/230, 575V MODELS ONLY 7-1/2 – 10 TON

208/230, 460V MODELS ONLY

UnitSize CFM

ESP BlowerSound Power (db 10-12 Watts)

Octave Band Centerline Frequency (Hz) SWLdb(A)

db(A)@

10 Ft*IWG RPM BHP 63 125 250 500 1,000 2,000 4,000 8,000

090102120150

3,0003,4004,0005,000

0.800.650.800.80

1,1451,215960

1,100

1.852.352.202.20

92949498

92949498

82848488

75777781

77797983

70727276

65676771

60626266

82848488

49515155

*At a distance of 10 ft.from the blower.NOTE: These values have been derived using a model of sound propagation, measuring the indoor ambient sound levels ten feet from the source. The dBA values provided are for referenceonly. Calculation of dBA values cover matters of system design and application. This constitutes an exception to any specification or guarantee requiring a dBA value or sound data in any otherform than sound power level ratings.

INDOOR SOUND POWER RATINGS

530.18-TG2Y

Unitary Products Group 3

Page 4: DCE, DCG TECHNICAL GUIDE - upgnet.netupgnet.net/Site/InformationCenter/York/Archive_CDs/York_1999/March... · dce dcg 090 102 120 150 090 102 120 150 evaporator blower centrifugal

MODELSDCE DCG

090 102 120 150 090 102 120 150

EVAPORATORBLOWER

CENTRIFUGAL BLOWER (Dia. x Wd. in.) 12 x 12 15 x 12 12 x 12 15 x 12FAN MOTOR HP (STANDARD) 11⁄2 2 2 3 2 2 2 3FAN MOTOR HP (ALTERNATE) 2 3 3 5 - 3 3 5

EVAPORATORCOIL

ROWS DEEP 4 4 4 4FINS PER INCH 15 15 15 15FACE AREA (Sq. Ft.) 7.8 9.1 10.9 13.4 7.8 9.1 10.9 13.4

CONDENSERFAN

(Two Per Unit)

PROPELLER DIA. (in.) (Each) 24 24 24 24FAN MOTOR HP (Each) 1⁄2 1⁄2 1⁄2 3⁄4 1⁄2 1⁄2 1⁄2 3⁄4NOM. CFM TOTAL (Each) 2900 3200 3600 4400 2900 3200 3600 4400

CONDENSERCOIL

ROWS DEEP 2 2 2 2FINS PER INCH 13 13 13 13FACE AREA (Sq. Ft.) 16.7 20.0 24.0 29.3 16.7 20.0 24.0 29.3

AIRFILTERS(SEE NOTE)

QUANTITY PER UNIT (12" x 24" x 2") 2 2 - - 2 2 - -QUANTITY PER UNIT (16" X 24" X 2") 2 2 2 3 2 2 2 3QUANTITY PER UNIT (18" X 24" X 2") - - 2 2 - - 2 2TOTAL FACE AREA (sq. ft.) 9.3 9.3 11.3 14.0 9.3 9.3 11.3 14.0

CHARGE REFRIGERANT-22 (lbs./oz.)

SYSTEM NO. 1 6/8 7/4 8/0* 10/4 6/8 7/4 8/0* 10/4SYSTEM NO. 2 6/8 7/11 8/0 10/8 6/8 7/11 8/0 10/8

COMPRESSORQTY./TYPE HERMETIC 2

SCROLL2

RECIP2

SCROLL2

RECIP2

SCROLL2

RECIP2

SCROLL2

RECIPNOTE: Filter racks are adapted for 1" or 2" thick filters..

PHYSICAL DATABASIC UNITS

MODEL POWERSUPPLY

COMPRESSOR(#1 and #2)1

OUTDOORFAN

MOTOR,(#1 & #2)

FLAEACH

SUPPLYAIR

BLOWERMOTOR,

FLA

TOTALUNIT

AMPACITY,AMPS

MAX.FUSESIZE2

AMPSRLA

EACHLRA

EACH 1.5HP 2HP 3HP 5HP 1.5HP 2HP 3HP 5HP

DCE090DCG090

208/230-3-60460-3-60575-3-60

13.16.75.8

904536

2.31.31.3

5.72.62.1

7.53.42.7

———

———

39.820.317.8

41.621.118.4

———

———

502520

DCE102DCG102

208/230-3-60460-3-60575-3-60

16.08.37.1

1376958

2.31.31.3

———

7.53.42.7

10.64.83.9

———

———

48.224.821.2

51.326.222.4

———

603025

DCE120DCG120

208/230-3-60460-3-60575-3-60

17.28.56.4

1256750

2.31.31.3

———

7.53.42.7

10.64.83.9

———

———

50.825.119.7

53.926.520.9

———

60/7030/35

25

DCE150DCG150

208/230-3-60460-3-60575-3-60

21.89.69.0

1587965

3.52.52.5

———

———

10.64.83.9

15.17.55.9

———

———

66.631.429.1

71.134.131.1

80/9040

35/40NOTES: 1. Dual numbers shown as “28.2/17.3" amps indicates compressor #1 / #2 respectively.

2. Dual element, time delay type. Amps shown as “90/100" indicates rating for LO HP / HI HP respectively. Maximum HACR breaker of the same AMP size is applicable, except 575 volt units.

ELECTRICAL DATA - Basic Units

VOLTAGELIMITATIONS*

POWER SUPPLYVOLTAGE

MIN. MAX.208/230-3-60 187 253

460-3-60 414 506575-3-60 518 630

530.18-TG2Y

4 Unitary Products Group

Page 5: DCE, DCG TECHNICAL GUIDE - upgnet.netupgnet.net/Site/InformationCenter/York/Archive_CDs/York_1999/March... · dce dcg 090 102 120 150 090 102 120 150 evaporator blower centrifugal

COOLING CAPACITIES - 7-1/2 TON (DCE / DCG090)

Air OnEvaporator

Coil

Temperature of Air on Condenser Coil105°F 115°F

TotalCap.1

MBH

PowerInput2

KW

Sensible Capacity1, MBH TotalCap.1

MBH

PowerInput2

KW

Sensible Capacity1, MBH

CFMWB°F

Entering Dry Bulb, °F Entering Dry Bulb, °F86 83 80 77 74 71 68 86 83 80 77 74 71 68

3750

72 98 9.1 77 67 57 47 37 - - 93 10.0 75 65 55 45 35 - -67 88 9.0 88 84 74 64 53 43 33 83 9.8 83 81 71 61 51 41 3162 81 8.9 81 81 81 71 61 51 41 76 9.6 76 76 76 66 56 46 3657 80 9.0 80 80 80 70 60 50 40 75 9.8 75 75 75 65 55 45 35

3375

72 96 9.1 72 63 54 44 35 - - 91 10.0 70 61 52 42 33 - -67 86 9.0 85 78 69 60 51 42 33 81 9.8 81 76 67 58 49 39 3062 79 8.8 79 79 79 70 60 51 42 74 9.6 74 74 74 65 56 46 3757 79 8.9 79 79 78 68 59 50 41 74 9.8 74 74 73 64 54 45 36

3000

72 94 9.0 67 59 50 42 34 - - 90 10.0 65 56 48 40 32 - -67 85 8.9 82 73 65 57 48 40 32 79 9.8 79 71 62 54 46 38 2962 78 8.8 78 78 77 68 60 52 43 73 9.6 73 73 72 64 55 47 3957 77 8.9 77 77 75 67 59 50 42 72 9.8 72 72 70 62 54 45 37

2625

72 91 9.0 61 54 47 39 32 - - 86 10.0 59 52 44 37 30 - -67 82 8.9 75 67 60 53 46 38 31 77 9.8 72 65 58 50 43 36 2862 75 8.8 75 75 71 64 56 49 42 70 9.6 70 70 65 59 52 44 3757 75 8.9 75 74 70 62 55 48 40 69 9.8 69 69 65 58 50 43 36

2250

72 89 9.1 55 49 43 36 30 - - 83 10.0 53 47 41 34 28 - -67 79 9.0 68 62 55 49 43 36 30 74 9.8 66 59 53 47 40 34 2762 73 8.8 73 72 65 59 53 46 40 68 9.6 68 67 61 55 48 42 3557 72 8.9 72 71 64 58 51 45 39 67 9.8 67 66 59 53 47 40 34

1These capacities are gross ratings. For net capacity, deduct the heat of the supply air blower motor, MBH = 3.415 x KW. Refer to the appropriate Blower Performance Table for the KW of the supply air blower motor.2These ratings include the condenser fan motors (Total 1 KW) and the compressor motors but not the supply air blower motor.

Air OnEvaporator

Coil

Temperature of Air on Condenser Coil85°F 95°F

TotalCap.1

MBH

PowerInput2

KW

Sensible Capacity1, MBH TotalCap.1

MBH

PowerInput2

KW

Sensible Capacity1, MBH

CFM WB°F

Entering Dry Bulb, °F Entering Dry Bulb, °F86 83 80 77 74 71 68 86 83 80 77 74 71 68

3750

72 104 7.4 79 68 58 48 38 - - 103 8.2 79 69 59 49 39 - -67 97 7.3 97 87 77 66 56 46 36 93 8.1 93 86 76 66 56 46 3662 90 7.3 90 90 90 80 70 60 50 86 8.1 86 86 86 76 66 56 4657 87 7.3 87 87 87 77 67 57 47 85 8.1 85 85 85 75 65 55 45

3375

72 103 7.4 74 65 56 46 37 - - 101 8.1 74 65 56 46 37 - -67 96 7.3 91 82 73 64 54 45 36 91 8.1 89 81 72 62 53 44 3562 89 7.3 89 89 87 78 69 60 51 84 8.0 84 84 84 74 65 56 4757 86 7.2 86 86 86 76 67 58 49 83 8.0 83 83 83 73 64 55 46

3000

72 102 7.3 69 61 53 44 36 - - 99 8.1 69 61 52 44 36 - -67 95 7.3 86 77 69 61 52 44 36 90 8.0 84 76 67 59 51 43 3462 88 7.2 88 88 85 76 68 60 52 83 8.0 83 83 81 73 65 56 4857 86 7.2 86 86 84 76 67 59 51 82 8.0 82 82 80 72 64 56 47

2625

72 99 7.3 64 57 49 42 35 - - 97 8.1 63 56 49 41 34 - -67 92 7.2 79 72 65 57 50 43 35 88 8.0 77 70 63 55 48 41 3362 86 7.2 86 84 79 72 65 57 50 81 8.0 81 79 75 68 61 54 4657 83 7.2 83 83 79 71 64 57 49 80 8.0 80 79 75 67 60 53 45

2250

72 96 7.3 59 53 46 40 33 - - 94 8.1 58 51 45 39 32 - -67 89 7.2 73 67 60 54 48 41 35 85 8.1 71 64 58 51 45 39 3262 83 7.2 83 80 74 68 61 55 49 79 8.0 79 76 70 63 57 51 4457 81 7.1 81 80 73 67 61 54 48 78 8.1 78 75 69 62 56 50 43

ALL SENSIBLE CAPACITYNOMINAL RATING

530.18-TG2Y

Unitary Products Group 5

Page 6: DCE, DCG TECHNICAL GUIDE - upgnet.netupgnet.net/Site/InformationCenter/York/Archive_CDs/York_1999/March... · dce dcg 090 102 120 150 090 102 120 150 evaporator blower centrifugal

COOLING CAPACITIES - 8-1/2 TON (DCE / DCG 102)

Air OnEvaporator

Coil

Temperature of Air on Condenser Coil85°F 95°F

TotalCap.1

MBH

PowerInput2

KW

Sensible Capacity1, MBH TotalCap.1

MBH

PowerInput2

KW

Sensible Capacity1, MBH

CFM WB°F

Entering Dry Bulb, °F Entering Dry Bulb, °F86 83 80 77 74 71 68 86 83 80 77 74 71 68

4250

72 133 9.2 96 83 70 57 - - - 130 9.8 97 84 71 59 - - -67 120 9.0 116 103 91 78 65 52 - 119 9.5 119 107 95 82 69 56 -62 110 8.8 110 110 110 97 85 72 59 104 9.3 104 104 104 91 79 66 5357 109 8.8 109 109 109 96 83 70 58 99 9.3 99 99 99 86 74 61 48

3825

72 130 9.1 89 78 66 55 - - - 125 9.8 89 77 66 54 - - -67 119 8.9 110 98 87 75 64 53 - 116 9.5 110 99 88 77 65 54 -62 108 8.7 108 108 105 93 82 71 59 100 9.3 100 100 99 87 76 65 5357 106 8.7 106 106 105 94 82 71 59 95 9.3 95 95 94 83 71 60 49

3400

72 127 9.1 83 73 63 53 - - - 120 9.8 80 70 60 50 - - -67 118 8.8 103 93 83 73 63 53 - 113 9.5 102 92 81 71 61 51 -62 105 8.6 105 105 100 90 79 69 59 96 9.2 96 96 94 83 73 63 5357 104 8.6 104 104 102 91 81 71 61 92 9.2 92 92 89 79 69 59 49

2975

72 123 9.0 76 67 58 49 - - - 116 9.7 74 65 56 47 - - -67 113 8.8 94 85 76 67 58 49 - 107 9.4 93 84 75 66 57 48 -62 102 8.6 102 100 93 84 75 66 57 93 9.2 93 92 87 78 69 60 5157 100 8.6 100 100 95 86 77 68 59 88 9.2 88 88 83 74 65 56 47

2550

72 119 9.0 70 62 54 46 - - - 112 9.6 67 60 52 44 - - -67 108 8.7 86 78 70 62 54 46 - 102 9.4 84 76 68 61 53 45 -62 99 8.6 99 94 86 78 70 62 55 89 9.1 89 88 81 73 65 57 4957 97 8.5 97 96 88 80 72 64 56 85 9.1 85 85 77 69 61 53 46

Air OnEvaporator

Coil

Temperature of Air on Condenser Coil105°F 115°F

TotalCap.1

MBH

PowerInput2

KW

Sensible Capacity1, MBH TotalCap.1

MBH

PowerInput2

KW

Sensible Capacity1, MBH

CFMWB°F

Entering Dry Bulb, °F Entering Dry Bulb, °F86 83 80 77 74 71 68 86 83 80 77 74 71 68

4250

72 117 10.5 90 78 65 52 - - - 104 11.1 84 71 59 46 - - -67 106 10.1 106 100 88 75 62 49 - 93 10.7 93 93 81 68 55 42 -62 97 9.9 97 97 97 84 71 59 46 90 10.5 90 90 90 77 64 52 3957 90 9.9 90 90 90 77 65 52 39 81 10.5 81 81 81 68 56 43 30

3825

72 115 10.4 84 73 61 50 - - - 105 11.0 79 68 57 45 - - -67 105 10.1 103 95 84 72 61 49 - 95 10.6 95 90 79 68 56 45 -62 95 9.8 95 95 94 83 71 60 49 90 10.4 90 90 89 78 67 55 4457 89 9.8 89 89 87 76 65 53 42 82 10.4 82 82 81 69 58 46 35

3400

72 113 10.3 78 68 57 47 - - - 106 10.9 75 65 55 45 - - -67 105 10.0 99 90 79 69 59 49 - 97 10.5 97 87 77 67 57 47 -62 94 9.8 94 94 92 81 71 61 51 91 10.4 91 91 90 79 69 59 4957 87 9.8 87 87 85 75 65 55 44 82 10.3 82 82 80 70 60 50 40

2975

72 108 10.3 71 62 53 44 - - - 99 10.8 67 58 49 40 - - -67 99 9.9 90 81 72 63 54 45 - 90 10.5 86 78 69 60 51 42 -62 89 9.7 89 89 84 75 66 57 48 86 10.3 86 85 81 72 63 54 4557 83 9.7 83 83 78 69 60 51 42 77 10.3 77 77 72 63 54 45 36

2550

72 102 10.2 63 56 48 40 - - - 93 10.8 59 52 44 36 - - -67 92 9.9 80 72 64 56 49 41 - 83 10.4 76 68 60 52 45 37 -62 85 9.6 85 84 76 68 60 52 45 80 10.2 80 79 72 64 56 48 4057 79 9.6 79 79 71 63 55 47 39 72 10.2 72 72 64 56 48 41 33

1These capacities are gross ratings. For net capacity, deduct the heat of the supply air blower motor, MBH = 3.415 x KW. Refer to the appropriate Blower Performance Table for the KW of the supply air blower motor.2These ratings include the condenser fan motors (Total 1 KW) and the compressor motors but not the supply air blower motor.

ALL SENSIBLE CAPACITYNOMINAL RATING

530.18-TG2Y

6 Unitary Products Group

Page 7: DCE, DCG TECHNICAL GUIDE - upgnet.netupgnet.net/Site/InformationCenter/York/Archive_CDs/York_1999/March... · dce dcg 090 102 120 150 090 102 120 150 evaporator blower centrifugal

COOLING CAPACITIES - 10 TON (DCE / DCG120)

Air OnEvaporator

Coil

Temperature of Air on Condenser Coil85°F 95°F

TotalCap.1

MBH

PowerInput2

KW

Sensible Capacity1, MBH TotalCap.1

MBH

PowerInput2

KW

Sensible Capacity1, MBH

CFM WB°F

Entering Dry Bulb, °F Entering Dry Bulb, °F86 83 80 77 74 71 68 86 83 80 77 74 71 68

5000

72 139 9.6 106 92 79 65 52 - - 135 10.6 105 92 78 64 51 - -67 131 9.4 130 117 103 90 76 63 49 127 10.4 127 116 102 89 75 62 4862 121 9.4 121 121 121 107 94 80 67 117 10.4 117 117 117 104 90 77 6357 119 9.5 119 119 119 106 92 79 65 116 10.4 116 116 116 102 89 75 62

4500

72 137 9.5 101 88 76 63 51 - - 133 10.5 99 87 74 62 49 - -67 130 9.3 124 112 99 87 74 62 50 125 10.2 121 110 97 85 72 60 4762 119 9.3 119 119 117 104 92 80 67 115 10.3 115 115 115 102 90 77 6557 118 9.4 118 118 118 106 93 81 68 114 10.3 114 114 114 101 89 77 64

4000

72 136 9.4 95 84 73 61 50 - - 131 10.4 93 82 70 59 48 - -67 128 9.1 118 107 95 84 73 61 50 123 10.1 115 103 92 81 69 58 4762 118 9.2 118 118 113 102 90 79 68 113 10.2 113 113 112 101 90 78 6757 117 9.3 117 117 117 105 94 83 71 112 10.2 112 112 112 100 89 78 66

3500

72 131 9.4 88 78 67 57 47 - - 126 10.4 85 75 63 55 45 - -67 124 9.2 108 98 88 78 68 58 48 119 10.2 105 95 85 75 65 55 4562 114 9.2 114 112 105 95 85 75 65 109 10.2 109 109 104 94 84 74 6457 113 9.3 113 113 108 98 88 78 68 108 10.2 108 108 103 93 83 73 63

3000

72 127 9.5 80 71 62 53 45 - - 121 10.5 77 69 60 51 42 - -67 120 9.3 99 90 81 73 64 55 46 114 10.2 96 87 78 69 61 52 4362 110 9.3 110 105 97 88 79 70 61 105 10.3 105 104 95 87 78 69 6057 109 9.4 109 109 100 91 82 73 65 104 10.3 104 104 95 86 77 69 60

Air OnEvaporator

Coil

Temperature of Air on Condenser Coil105°F 115°F

TotalCap.1

MBH

PowerInput2

KW

Sensible Capacity1, MBH TotalCap.1

MBH

PowerInput2

KW

Sensible Capacity1, MBH

CFMWB°F

Entering Dry Bulb, °F Entering Dry Bulb, °F86 83 80 77 74 71 68 86 83 80 77 74 71 68

5000

72 128 11.7 103 89 76 62 49 - - 122 12.9 101 87 74 60 46 - -67 119 11.5 119 113 99 86 72 59 45 110 12.7 110 110 96 83 69 56 4262 110 11.5 110 110 110 96 83 69 55 102 12.6 102 102 102 88 75 61 4857 109 11.6 109 109 109 95 82 68 55 102 12.7 102 102 102 88 75 61 48

4500

72 126 11.6 97 84 72 59 47 - - 120 12.8 94 82 69 57 44 - -67 117 11.5 114 106 94 81 69 57 44 108 12.7 108 103 91 78 66 53 4162 108 11.4 108 108 108 95 83 70 58 100 12.6 100 100 100 88 75 63 5157 107 11.5 107 107 107 95 82 70 57 100 12.7 100 100 100 88 75 63 50

4000

72 124 11.6 90 79 68 56 45 - - 118 12.8 88 76 65 54 42 - -67 115 11.4 110 100 89 77 66 55 43 106 12.6 106 96 85 74 62 51 4062 106 11.3 106 106 105 94 83 71 60 99 12.5 99 99 99 87 76 65 5357 105 11.4 105 105 105 94 82 71 60 99 12.6 99 99 98 87 76 64 53

3500

72 120 11.6 83 72 62 52 42 - - 114 12.7 80 70 60 50 40 - -67 111 11.4 101 92 82 72 62 51 41 102 12.6 98 88 78 68 58 48 3862 102 11.4 102 102 97 87 77 67 57 95 12.5 95 95 91 81 71 60 5057 102 11.4 102 101 97 87 77 67 57 95 12.6 95 95 91 80 70 60 50

3000

72 115 11.6 75 66 57 48 39 - - 109 12.7 72 63 55 46 37 - -67 106 11.4 92 84 75 66 57 48 40 98 12.6 89 80 71 63 54 45 3662 98 11.4 98 98 89 80 71 63 54 92 12.5 92 92 83 74 65 56 4757 98 11.4 98 98 89 80 71 62 54 92 12.6 92 91 83 74 65 56 47

1These capacities are gross ratings. For net capacity, deduct the heat of the supply air blower motor, MBH = 3.415 x KW. Refer to the appropriate Blower Performance Table for the KW of the supply air blower motor.2These ratings include the condenser fan motors (Total 1 KW) and the compressor motors but not the supply air blower motor.

ALL SENSIBLE CAPACITYNOMINAL RATING

530.18-TG2Y

Unitary Products Group 7

Page 8: DCE, DCG TECHNICAL GUIDE - upgnet.netupgnet.net/Site/InformationCenter/York/Archive_CDs/York_1999/March... · dce dcg 090 102 120 150 090 102 120 150 evaporator blower centrifugal

COOLING CAPACITIES - 12-1/2 TON (DCE / DCG 150)Air On

EvaporatorCoil

Temperature of Air on Condenser Coil85°F 95°F

TotalCap.1

MBH

PowerInput2

KW

Sensible Capacity1, MBH TotalCap.1

MBH

PowerInput2

KW

Sensible Capacity1, MBH

CFM WB°F

Entering Dry Bulb, °F Entering Dry Bulb, °F86 83 80 77 74 71 68 86 83 80 77 74 71 68

5500

72 171 12.9 120 105 88 73 - - - 169 14.0 117 102 85 70 - - -67 157 12.7 148 132 116 100 84 68 - 152 13.6 146 131 114 99 83 67 -62 145 12.4 145 145 145 129 113 98 82 140 13.3 140 140 140 124 108 92 7757 145 12.4 145 145 145 130 114 98 83 140 13.3 140 140 140 127 110 95 79

5250

72 169 12.9 116 101 85 71 - - - 165 14.0 113 99 84 68 - - -67 157 12.7 144 129 114 99 84 69 - 151 13.6 143 129 113 98 84 68 -62 143 12.4 143 143 141 126 110 96 81 137 13.2 137 137 137 122 107 92 7757 143 12.4 143 143 143 129 113 98 84 137 13.2 137 137 137 125 109 94 80

5000

72 167 13.0 112 98 84 69 - - - 162 14.0 110 96 82 67 - - -67 157 12.7 140 126 111 98 84 69 - 151 13.6 140 127 112 98 84 69 -62 142 12.4 142 142 136 122 108 93 80 135 13.2 135 135 134 120 106 91 7757 142 12.4 142 142 141 127 112 99 84 135 13.2 135 135 135 123 108 94 80

4375

72 162 12.9 104 91 78 65 - - - 157 13.9 101 88 75 62 - - -67 151 12.7 129 116 104 91 78 65 - 144 13.5 128 115 102 89 77 64 -62 137 12.3 137 136 128 115 103 90 77 131 13.1 131 130 124 111 98 85 7357 137 12.3 137 137 132 120 108 94 82 131 13.1 131 131 126 113 101 88 76

3750

72 156 12.8 95 84 73 61 - - - 152 13.8 91 80 69 58 - - -67 144 12.6 117 107 95 84 73 62 - 137 13.4 114 103 92 81 70 59 -62 132 12.3 132 131 119 108 97 86 75 126 13.1 126 124 113 102 91 80 6957 132 12.2 132 132 124 112 102 90 80 126 13.1 126 126 115 105 93 83 71

Air OnEvaporator

Coil

Temperature of Air on Condenser Coil105°F 115°F

TotalCap.1

MBH

PowerInput2

KW

Sensible Capacity1, MBH TotalCap.1

MBH

PowerInput2

KW

Sensible Capacity1, MBH

CFMWB°F

Entering Dry Bulb, °F Entering Dry Bulb, °F86 83 80 77 74 71 68 86 83 80 77 74 71 68

5500

72 160 14.9 116 100 84 68 - - - 152 15.9 115 99 84 67 - - -67 138 14.4 135 127 111 95 80 63 - 125 15.2 125 123 108 91 76 60 -62 128 14.0 128 128 128 111 96 81 64 115 14.8 115 115 115 100 84 68 5257 128 14.0 128 128 128 117 101 85 69 115 14.8 115 115 115 108 91 76 60

5250

72 156 14.9 111 97 82 66 - - - 148 15.8 109 95 80 64 - - -67 137 14.3 133 124 108 94 79 63 - 123 15.2 123 119 105 89 74 60 -62 125 14.0 125 125 125 109 95 80 64 112 14.7 112 112 112 97 83 67 5257 125 14.0 125 125 125 114 99 84 69 112 14.7 112 112 112 104 88 74 59

5000

72 154 14.8 108 93 79 64 - - - 144 15.8 105 90 76 62 - - -67 136 14.3 131 121 107 92 78 63 - 121 15.0 121 115 101 86 72 58 -62 122 14.0 122 122 121 108 93 79 64 109 14.7 109 109 108 95 81 66 5257 122 14.0 122 122 122 111 97 83 68 109 14.7 109 109 109 100 86 72 58

4375

72 149 14.7 98 85 73 60 - - - 140 15.7 96 84 70 58 - - -67 130 14.2 121 109 97 84 72 60 - 116 14.9 113 105 92 80 67 54 -62 118 13.9 118 118 112 100 87 74 61 107 14.6 107 107 101 88 76 63 5057 118 13.9 118 118 116 104 90 78 65 107 14.6 107 107 106 93 91 68 55

3750

72 144 14.6 89 78 67 56 - - - 135 15.6 87 76 64 54 - - -67 124 14.1 110 99 87 77 65 55 - 111 14.8 106 95 84 72 61 50 -62 114 13.8 114 113 103 92 81 70 59 103 14.5 103 102 93 82 71 60 4957 114 13.8 114 114 107 95 84 73 62 103 14.5 103 103 97 86 75 64 53

1These capacities are gross ratings. For net capacity, deduct the heat of the supply air blower motor, MBH = 3.415 x KW. Refer to the appropriate Blower Performance Table for the KW of the supply air blower motor.2These ratings include the condenser fan motors (Total 1.3 KW) and the compressor motors but not the supply air blower motor.

ALL SENSIBLE CAPACITYNOMINAL RATING

530.18-TG2Y

8 Unitary Products Group

Page 9: DCE, DCG TECHNICAL GUIDE - upgnet.netupgnet.net/Site/InformationCenter/York/Archive_CDs/York_1999/March... · dce dcg 090 102 120 150 090 102 120 150 evaporator blower centrifugal

BLOWERSPEED,

RPM

CFM2250 2550 3000 3400 3750

ESP BHP KW ESP BHP KW ESP BHP KW ESP BHP KW ESP BHP KW975 0.93 1.16 1.08 0.79 1.27 1.18 0.53 1.45 1.35 0.29 1.65 1.54 - - -

1025 1.08 1.21 1.13 0.95 1.34 1.25 0.68 1.54 1.44 0.42 1.75 1.63 0.17 1.97 1.841070 1.22 1.32 1.23 1.08 1.46 1.36 0.83 1.68 1.57 0.58 1.89 1.76 0.32 2.11 1.971130 1.41 1.43 1.33 1.29 1.57 1.46 1.02 1.83 1.71 0.77 2.04 1.90 - - -1175 1.61 1.51 1.41 1.49 1.67 1.56 1.23 1.92 1.79 0.96 2.18 2.03 - - -1220 1.78 1.66 1.55 1.66 1.81 1.69 1.39 2.10 1.96 - - - - - -

MODEL DCE090 - (SIDE DUCT APPLICATIONS)

BLOWER PERFORMANCE - (7-1/2 TON SUPPLY AIR)

BLOWERSPEED,

RPM

CFM2250 2550 3000 3400 3750

ESP BHP KW ESP BHP KW ESP BHP KW ESP BHP KW ESP BHP KW975 0.86 1.16 1.08 0.70 1.27 1.18 0.40 1.45 1.35 0.12 1.65 1.54 - - -1025 1.01 1.21 1.13 0.86 1.34 1.25 0.55 1.54 1.44 0.25 1.75 1.63 - - -1070 1.15 1.32 1.23 0.99 1.46 1.36 0.70 1.68 1.57 0.41 1.89 1.76 0.12 2.11 1.971130 1.34 1.43 1.33 1.20 1.57 1.46 0.89 1.83 1.71 0.60 2.04 1.90 - - -1175 1.54 1.51 1.41 1.40 1.67 1.56 1.10 1.92 1.79 0.79 2.18 2.03 - - -1220 1.71 1.66 1.55 1.57 1.81 1.69 1.26 2.10 1.96 - - - - - -

MODEL DCE090 - (BOTTOM DUCT APPLICATIONS)

BLOWERSPEED,

RPM

CFM2250 2550 3000 3400 3750

ESP BHP KW ESP BHP KW ESP BHP KW ESP BHP KW ESP BHP KW975 0.83 1.16 1.08 0.66 1.27 1.18 0.37 1.45 1.35 0.08 1.65 1.54 - - -

1025 0.98 1.21 1.13 0.82 1.34 1.25 0.52 1.54 1.44 0.21 1.75 1.63 - - -1070 1.12 1.32 1.23 0.95 1.46 1.36 0.67 1.68 1.57 0.37 1.89 1.76 0.07 2.11 1.971130 1.31 1.43 1.33 1.16 1.57 1.46 0.86 1.83 1.71 0.56 2.04 1.90 - - -1175 1.51 1.51 1.41 1.36 1.67 1.56 1.07 1.92 1.79 0.75 2.18 2.03 - - -1220 1.68 1.66 1.55 1.53 1.81 1.69 1.23 2.10 1.96 - - - - - -

MODEL DCG090 - (SIDE DUCT APPLICATIONS)

BLOWERSPEED,

RPM

CFM2250 2550 3000 3400 3750

ESP BHP KW ESP BHP KW ESP BHP KW ESP BHP KW ESP BHP KW975 0.76 1.16 1.08 0.57 1.27 1.18 0.24 1.45 1.35 - - - - - -1025 0.91 1.21 1.13 0.73 1.34 1.25 0.39 1.54 1.44 0.04 1.75 1.63 - - -1070 1.05 1.32 1.23 0.86 1.46 1.36 0.54 1.68 1.57 0.20 1.89 1.76 - - -1130 1.24 1.43 1.33 1.07 1.57 1.46 0.73 1.83 1.71 0.39 2.04 1.90 - - -1175 1.44 1.51 1.41 1.27 1.67 1.56 0.94 1.92 1.79 0.58 2.18 2.03 - - -1220 1.61 1.66 1.55 1.44 1.81 1.69 1.10 2.10 1.96 - - - - - -

NOTES: 1. Blower performance includes a wet evaporator coil and 2" filters.2. For DCG units, blower performance includes the maximum number of heat exchangers.3. Refer to the Accessory Static Resistances table. ESP = External Static Pressure available for the supply and return air duct sytem. All internal unit resistances have been deducted from the total static pressure of the blower.4. DCE models include a baffle to direct the proper flow of air across our electric heaters. On “cooling only” applications, this baffle MUST be removed to get the ESP values listed in the above tables.

MODEL DCG090 - (BOTTOM DUCT APPLICATIONS)

= Larger Horsepower Alternate Motor Required.

530.18-TG2Y

Unitary Products Group 9

Page 10: DCE, DCG TECHNICAL GUIDE - upgnet.netupgnet.net/Site/InformationCenter/York/Archive_CDs/York_1999/March... · dce dcg 090 102 120 150 090 102 120 150 evaporator blower centrifugal

BLOWER PERFORMANCE - (8-1/2 TON SUPPLY AIR)

BLOWERSPEED,

RPM

CFM2550 3000 3400 3750

ESP BHP KW ESP BHP KW ESP BHP KW ESP BHP KW975 0.79 1.27 1.18 0.53 1.45 1.35 0.29 1.65 1.54 0.08 1.62 1.421025 0.95 1.34 1.25 0.68 1.54 1.44 0.42 1.75 1.63 0.17 1.97 1.841070 1.08 1.46 1.36 0.83 1.68 1.57 0.58 1.89 1.76 0.32 2.11 1.971130 1.29 1.57 1.46 1.02 1.83 1.71 0.77 2.04 1.90 0.52 2.22 2.061175 1.49 1.67 1.56 1.23 1.92 1.79 0.96 2.18 2.03 0.72 2.34 2.161220 1.66 1.81 1.69 1.39 2.10 1.96 1.20 2.37 2.15 0.95 2.78 2.56

MODEL DCE102 - (SIDE DUCT APPLICATIONS)

BLOWERSPEED,

RPM

CFM2550 3000 3400 3750

ESP BHP KW ESP BHP KW ESP BHP KW ESP BHP KW975 0.70 1.27 1.18 0.40 1.45 1.35 0.12 1.65 1.54 - - -

1025 0.86 1.34 1.25 0.55 1.54 1.44 0.25 1.75 1.63 - - -1070 0.99 1.46 1.36 0.70 1.68 1.57 0.41 1.89 1.76 0.12 2.11 1.971130 1.20 1.57 1.46 0.89 1.83 1.71 0.60 2.04 1.90 0.24 2.22 2.061175 1.40 1.67 1.56 1.10 1.92 1.79 0.79 2.18 2.03 0.42 2.34 2.161220 1.57 1.81 1.69 1.26 2.10 1.96 0.91 2.37 2.15 0.58 2.78 2.56

MODEL DCE102 - (BOTTOM DUCT APPLICATIONS)

BLOWERSPEED,

RPM

CFM2550 3000 3400 3750

ESP BHP KW ESP BHP KW ESP BHP KW ESP BHP KW975 0.66 1.27 1.18 0.37 1.45 1.35 0.08 1.65 1.54 - - -1025 0.82 1.34 1.25 0.52 1.54 1.44 0.21 1.75 1.63 - - -1070 0.95 1.46 1.36 0.67 1.68 1.57 0.37 1.89 1.76 0.07 2.11 1.971130 1.16 1.57 1.46 0.86 1.83 1.71 0.56 2.04 1.90 0.16 2.22 2.061175 1.36 1.67 1.56 1.07 1.92 1.79 0.75 2.18 2.03 0.31 2.34 2.161220 1.53 1.81 1.69 1.23 2.10 1.96 0.86 2.37 2.15 0.48 2.78 2.56

MODEL DCG102 - (SIDE DUCT APPLICATIONS)

BLOWERSPEED,

RPM

CFM2550 3000 3400 3750

ESP BHP KW ESP BHP KW ESP BHP KW ESP BHP KW975 0.57 1.27 1.18 0.24 1.45 1.35 - - - - - -1025 0.73 1.34 1.25 0.39 1.54 1.44 0.04 1.75 1.63 - - -1070 0.86 1.46 1.36 0.54 1.68 1.57 0.20 1.89 1.76 0.04 2.11 1.971130 1.07 1.57 1.46 0.73 1.83 1.71 0.39 2.04 1.90 0.13 2.22 2.061175 1.27 1.67 1.56 0.94 1.92 1.79 0.58 2.18 2.03 0.28 2.34 2.161220 1.44 1.81 1.69 1.10 2.10 1.96 0.66 2.37 2.15 0.36 2.78 2.56

NOTES: 1. Blower performance includes a wet evaporator coil and 2" filters.2. For DCG units, blower performance includes the maximum number of heat exchangers.3. Refer to the Accessory Static Resistances table. ESP = External Static Pressure available for the supply and return air duct sytem. All internal unit resistances have been deducted from the total static pressure of the blower.4. DCE models include a baffle to direct the proper flow of air across our electric heaters. On “cooling only” applications, this baffle MUST be removed to get the ESP values listed in the above tables.

MODEL DCG102 - (BOTTOM DUCT APPLICATIONS)

= Larger Horsepower Alternate Motor Required.

530.18-TG2Y

10 Unitary Products Group

Page 11: DCE, DCG TECHNICAL GUIDE - upgnet.netupgnet.net/Site/InformationCenter/York/Archive_CDs/York_1999/March... · dce dcg 090 102 120 150 090 102 120 150 evaporator blower centrifugal

BLOWERSPEED,

RPM

CFM3000 3500 4000 4500 5000

ESP BHP KW ESP BHP KW ESP BHP KW ESP BHP KW ESP BHP KW860 1.14 1.40 1.31 0.98 1.58 1.48 0.77 1.80 1.68 0.53 2.05 1.91 0.25 2.31 2.15915 1.32 1.55 1.45 1.18 1.76 1.64 0.95 1.98 1.85 0.72 2.23 2.08 0.49 2.48 2.31950 1.51 1.68 1.57 1.37 1.91 1.78 1.15 2.14 2.00 0.91 2.43 2.27 0.67 2.72 2.54

1000 1.69 1.83 1.71 1.57 2.07 1.93 1.35 2.33 2.17 1.14 2.62 2.45 0.92 2.91 2.721050 1.89 1.98 1.84 1.78 2.25 2.10 1.57 2.55 2.37 1.35 2.86 2.67 1.12 3.17 2.961090 2.08 2.12 1.97 1.97 2.41 2.24 1.78 2.72 2.54 1.55 3.06 2.86 - - -

MODEL DCE120 - (SIDE DUCT APPLICATIONS)

BLOWER PERFORMANCE - (10 TON SUPPLY AIR)

BLOWERSPEED,

RPM

CFM3000 3500 4000 4500 5000

ESP BHP KW ESP BHP KW ESP BHP KW ESP BHP KW ESP BHP KW860 1.01 1.40 1.31 0.80 1.58 1.48 0.54 1.80 1.68 0.23 2.05 1.91 - - -915 1.19 1.55 1.45 1.00 1.76 1.64 0.72 1.98 1.85 0.42 2.23 2.08 0.13 2.48 2.31950 1.38 1.68 1.57 1.19 1.91 1.78 0.92 2.14 2.00 0.61 2.43 2.27 0.31 2.72 2.541000 1.56 1.83 1.71 1.39 2.07 1.93 1.12 2.33 2.17 0.84 2.62 2.45 0.56 2.91 2.721050 1.76 1.98 1.84 1.60 2.25 2.10 1.34 2.55 2.37 1.05 2.86 2.67 0.76 3.17 2.961090 1.95 2.12 1.97 1.79 2.41 2.24 1.55 2.72 2.54 1.25 3.06 2.86 - - -

MODEL DCE120 - (BOTTOM DUCT APPLICATIONS)

BLOWERSPEED,

RPM

CFM3000 3500 4000 4500 5000

ESP BHP KW ESP BHP KW ESP BHP KW ESP BHP KW ESP BHP KW860 1.05 1.40 1.31 0.85 1.58 1.48 0.62 1.80 1.68 0.32 2.05 1.91 - - -915 1.23 1.55 1.45 1.05 1.76 1.64 0.80 1.98 1.85 0.51 2.23 2.08 0.22 2.48 2.31950 1.42 1.68 1.57 1.24 1.91 1.78 1.00 2.14 2.00 0.70 2.43 2.27 0.40 2.72 2.54

1000 1.60 1.83 1.71 1.44 2.07 1.93 1.20 2.33 2.17 0.93 2.62 2.45 0.65 2.91 2.721050 1.80 1.98 1.84 1.65 2.25 2.10 1.42 2.55 2.37 1.14 2.86 2.67 0.85 3.17 2.961090 1.99 2.12 1.97 1.84 2.41 2.24 1.63 2.72 2.54 1.34 3.06 2.86 - - -

MODEL DCG120 - (SIDE DUCT APPLICATIONS)

BLOWERSPEED,

RPM

CFM3000 3500 4000 4500 5000

ESP BHP KW ESP BHP KW ESP BHP KW ESP BHP KW ESP BHP KW860 0.92 1.40 1.31 0.67 1.58 1.48 0.39 1.80 1.68 0.02 2.05 1.91 - - -915 1.10 1.55 1.45 0.87 1.76 1.64 0.57 1.98 1.85 0.21 2.23 2.08 - - -950 1.29 1.68 1.57 1.06 1.91 1.78 0.77 2.14 2.00 0.40 2.43 2.27 0.04 2.72 2.54

1000 1.47 1.83 1.71 1.26 2.07 1.93 0.97 2.33 2.17 0.63 2.62 2.45 0.29 2.91 2.721050 1.67 1.98 1.84 1.47 2.25 2.10 1.19 2.55 2.37 0.84 2.86 2.67 0.49 3.17 2.961090 1.86 2.12 1.97 1.66 2.41 2.24 1.40 2.72 2.54 1.04 3.06 2.86 - - -

NOTES: 1. Blower performance includes a wet evaporator coil and 2" filters.2. For DCG units, blower performance includes the maximum number of heat exchangers.3. Refer to the Accessory Static Resistances table. ESP = External Static Pressure available for the supply and return air duct sytem. All internal unit resistances have been deducted from the total static pressure of the blower.4. DCE models include a baffle to direct the proper flow of air across our electric heaters. On “cooling only” applications, this baffle MUST be removed to get the ESP values listed in the above tables.

MODEL DCG120 - (BOTTOM DUCT APPLICATIONS)

= Larger Horsepower Alternate Motor Required.

530.18-TG2Y

Unitary Products Group 11

Page 12: DCE, DCG TECHNICAL GUIDE - upgnet.netupgnet.net/Site/InformationCenter/York/Archive_CDs/York_1999/March... · dce dcg 090 102 120 150 090 102 120 150 evaporator blower centrifugal

BLOWERSPEED,

RPM

CFM4000 4500 5000 5500 6000

ESP BHP KW ESP BHP KW ESP BHP KW ESP BHP KW ESP BHP KW960 1.15 2.14 2.00 0.91 2.43 2.27 0.67 2.72 2.54 0.38 3.03 2.83 0.28 3.94 3.671000 1.35 2.33 2.17 1.14 2.62 2.45 0.92 2.91 2.72 0.62 3.24 3.03 0.46 4.20 3.911050 1.57 2.55 2.37 1.35 2.86 2.67 1.12 3.17 2.96 0.89 4.06 3.79 0.69 4.53 4.221090 1.78 2.72 2.54 1.55 3.06 2.86 1.37 3.78 3.53 1.05 4.28 3.99 0.88 4.79 4.461105 1.89 3.08 2.87 1.68 3.45 3.22 1.45 3.88 3.62 1.12 4.35 4.06 0.96 4.89 4.561140 2.06 3.25 3.03 1.84 3.66 3.41 1.62 4.11 3.83 1.29 4.53 4.22 1.15 5.12 4.77

MODEL DCE150 - (SIDE DUCT APPLICATIONS)

BLOWER PERFORMANCE - (12-1/2 TON SUPPLY AIR)

BLOWERSPEED,

RPM

CFM4000 4500 5000 5500 6000

ESP BHP KW ESP BHP KW ESP BHP KW ESP BHP KW ESP BHP KW960 0.92 2.14 2.00 0.61 2.43 2.27 0.31 2.72 2.54 0.02 3.03 2.83 - - -

1000 1.12 2.33 2.17 0.84 2.62 2.45 0.56 2.91 2.72 0.26 3.24 3.03 - - -1050 1.34 2.55 2.37 1.05 2.86 2.67 0.76 3.17 2.96 0.53 4.06 3.79 0.27 4.53 4.221090 1.55 2.72 2.54 1.25 3.06 2.86 1.01 3.78 3.53 0.69 4.28 3.99 0.46 4.79 4.461105 1.66 3.08 2.87 1.38 3.45 3.22 1.09 3.88 3.62 0.76 4.35 4.06 0.54 4.89 4.561140 1.83 3.25 3.03 1.54 3.66 3.41 1.26 4.11 3.83 0.93 4.53 4.22 0.73 5.12 4.77

MODEL DCE150 - (BOTTOM DUCT APPLICATIONS)

BLOWERSPEED,

RPM

CFM4000 4500 5000 5500 6000

ESP BHP KW ESP BHP KW ESP BHP KW ESP BHP KW ESP BHP KW960 1.00 2.14 2.00 0.70 2.43 2.27 0.40 2.72 2.54 0.11 3.03 2.83 - - -1000 1.20 2.33 2.17 0.93 2.62 2.45 0.65 2.91 2.72 0.35 3.24 3.03 0.16 4.20 3.911050 1.42 2.55 2.37 1.14 2.86 2.67 0.85 3.17 2.96 0.62 4.06 3.79 0.39 4.53 4.221090 1.63 2.72 2.54 1.34 3.06 2.86 1.10 3.78 3.53 0.78 4.28 3.99 0.58 4.79 4.461105 1.74 3.08 2.87 1.47 3.45 3.22 1.18 3.88 3.62 0.85 4.35 4.06 0.66 4.89 4.561140 1.91 3.25 3.03 1.63 3.66 3.41 1.35 4.11 3.83 1.02 4.53 4.22 0.85 5.12 4.77

MODEL DCG150 - (SIDE DUCT APPLICATIONS)

BLOWERSPEED,

RPM

CFM4000 4500 5000 5500 6000

ESP BHP KW ESP BHP KW ESP BHP KW ESP BHP KW ESP BHP KW960 0.77 2.14 2.00 0.40 2.43 2.27 0.04 2.72 2.54 - - - - - -1000 0.97 2.33 2.17 0.63 2.62 2.45 0.29 2.91 2.72 - - - - - -1050 1.19 2.55 2.37 0.84 2.86 2.67 0.49 3.17 2.96 0.26 4.06 3.79 - - -1090 1.40 2.72 2.54 1.04 3.06 2.86 0.74 3.78 3.53 0.42 4.28 3.99 0.18 4.79 4.461105 1.51 3.08 2.87 1.17 3.45 3.22 0.82 3.88 3.62 0.49 4.35 4.06 0.26 4.89 4.561140 1.68 3.25 3.03 1.33 3.66 3.41 0.99 4.11 3.83 0.66 4.53 4.22 0.45 5.12 4.77

NOTES: 1. Blower performance includes a wet evaporator coil and 2" filters.2. For DCG units, blower performance includes the maximum number of heat exchangers.3. Refer to the Accessory Static Resistances table. ESP = External Static Pressure available for the supply and return air duct sytem. All internal unit resistances have been deducted from the total static pressure of the blower.4. DCE models include a baffle to direct the proper flow of air across our electric heaters. On “cooling only” applications, this baffle MUST be removed to get the ESP values listed in the above tables.

MODEL DCG150 - (BOTTOM DUCT APPLICATIONS)

= Larger Horsepower Alternate Motor Required.

530.18-TG2Y

12 Unitary Products Group

Page 13: DCE, DCG TECHNICAL GUIDE - upgnet.netupgnet.net/Site/InformationCenter/York/Archive_CDs/York_1999/March... · dce dcg 090 102 120 150 090 102 120 150 evaporator blower centrifugal

EXTERNAL STATIC PRESSURE DROP

MODELS DESCRIPTIONRESISTANCE, IWG

CFM2250 3000 4000 5000 6000

DCEDCG Economizer 0.02 0.02 0.03 0.05 0.07

DCE Electric Heaters

9 KW**0.06

0.11 0.20 0.31 0.4518 KW24 KW 0.12 0.21 0.33 0.4836 KW 0.07 0.13 0.23 0.35 0.5254 KW*** - 0.15 0.26 0.40 0.58

*Deduct these resistance values from the available unit external static pressure shown in the respective Blower Performance Table.

**9 KW Heater is only available on 7-1/2 and 8-1/2 Ton Units.

***54 KW Heater is only available on 10 and 12-1/2 Ton Units.

ACCESSORY STATIC RESISTANCES*

BLOWER MOTOR AND DRIVE DATA

COMPONENT WEIGHTS

MODELSBLOWERRANGE(RPM)

MOTOR* ADJUSTABLEMOTOR PULLEY

FIXEDBLOWER PULLEY BELTS

HP SERVICEFACTOR

FRAMESIZE

EFFICIENCY(%)

PITCHDIA.(IN.)

BORE(IN.)

PITCHDIA.(IN.)

BORE(IN.)

PITCHLENGTH

(IN.)

DESIG-NATION QTY.

DCE090

975-1220

1-1/2, 2

1.20 56 82.0 3.4 - 4.4 7/8 6.2 1 50.3 A48 1DCG090 2DCE102

2, 3DCG102DCE120

860-10902, 3

1.20 56 82.0 3.4 - 4.4 7/8 7.0 1 57.3 A55 1DCG120DCE150

3DCG150DCE150

960-1140 5 1.15 184 82.0 4.9 - 5.9 1-1/8 8.9 1 62.8 BX61(Notched) 1

DCG150* All motors are 1750 RPM, have solid bases and are inherently protected. These motors can be selected to operate into their service factor because they are located in the moving air, upstream of any heating device.

COMPONENTMODELS DCE & DCG

7-1/2 TON 8-1/2 TON 10 TON 12-1/2 TON

Basic Unit

DCE (Cooling only) 940 1025 1060 1250

DCG (Gas / Electric)130 Mbh 1020 1105 - -165 Mbh 1040 1125 1160 1450200 Mbh - - 1180 1470

Optionsand

Accessories

Economizer 77 77 77 77Motorized Outdoor Air Damper 97 97 97 97Oversized Motor 10 15 15 35

Electric Heat(Nominal KW)(DCE only)

9 KW 19 19 - -18 KW 24 24 24 2424 KW 27 27 27 2736 KW 30 30 30 3054 KW - - 37 37

Roof Mounting Curb 155 155 155 155NOTE: Weights are given in pounds.

530.18-TG2Y

Unitary Products Group 13

Page 14: DCE, DCG TECHNICAL GUIDE - upgnet.netupgnet.net/Site/InformationCenter/York/Archive_CDs/York_1999/March... · dce dcg 090 102 120 150 090 102 120 150 evaporator blower centrifugal

FIELD WIRING - DCE/DCG Electric/Electric and Gas/Electric Units

530.18-TG2Y

14 Unitary Products Group

Page 15: DCE, DCG TECHNICAL GUIDE - upgnet.netupgnet.net/Site/InformationCenter/York/Archive_CDs/York_1999/March... · dce dcg 090 102 120 150 090 102 120 150 evaporator blower centrifugal

ELECTRICAL DATA - Cooling / Electric Heating (DCE090 & 102)

UNITSIZE,D3CE

POWERSUPPLY

SUPPLY AIRBLOWER

FLAACCESSORY ELECTRIC HEATERS

TOTAL UNITAMPACITY,

AMPS

MAXIMUMFUSE

SIZE,1, 2

AMPSMOTOR HPMODEL NO. KW STAGES TOTAL

AMPSMOTOR HP

LO HI LO HI LO HI

090

7-1/2 TONUNIT with1-1/2 OR 2

HPBLOWER

208-3-60 5.7 7.5

2HE045109252HE045118252HE045124252HE04513625

6.813.518.027.0

1222

18.837.550.075.1

39.854.069.7100.9

41.656.371.9103.2

506070110

506080110

230-3-60 5.7 7.5

2HE045109252HE045118252HE045124252HE04513625

9.018.024.036.0

1222

21.743.357.786.6

39.861.379.3115.4

41.663.581.5117.6

507080125

507090125

460-3-60 2.6 3.4

2HE04510946*2HE04511846*2HE045124462HE04513646

9.018.024.036.0

1222

10.821.728.943.3

20.330.339.357.4

21.131.340.358.4

25354060

25354560

575-3-60 2.1 2.7

2HE045109582HE045118582HE045124582HE04513658

9.018.024.036.0

1222

8.717.323.134.6

17.824.331.545.9

18.425.032.246.7

20253550

20303550

102

8-1/2 TONUNIT with2 OR 3 HPBLOWER

208-3-60 7.5 10.6

2HE045109252HE045118252HE045124252HE04513625

6.813.518.027.0

1222

18.837.550.075.1

48.256.371.9103.2

51.360.275.8107.1

606080110

607080110

230-3-60 7.5 10.6

2HE045109252HE045118252HE045124252HE04513625

9.018.024.036.0

1222

21.743.357.786.6

48.263.581.5117.6

51.367.485.4121.5

607090125

607090125

460-3-60 3.4 4.8

2HE04510946*2HE04511846*2HE045124462HE04513646

9.018.024.036.0

1222

10.821.728.943.3

24.831.340.358.4

26.233.142.160.1

30354560

30354570

575-3-60 2.7 3.9

2HE045109582HE045118582HE045124582HE04513658

9.018.024.036.0

1222

8.717.323.134.6

21.225.032.246.7

22.426.533.748.2

25253550

25303550

1Dual element, time delay type.2Maximum HACR breaker of the same AMP size is applicable, except 575 voltages. Standard circuit breakers may be used in Canada and on applications over 60 amps where the heaters are separately fused..

*These electric heaters do NOT include fuses. If fuses are required to meet a local code (eg. Chicago), an accessory fuse box with fuses (2FB04700346) is available for field installation.

ELECTRIC HEATCORRECTION

FACTORS

NOMINAL VOLTAGE VOLTAGE KW CAP. MULTIPLIER208 208 1.00240 230 0.92480 460 0.92600 575 0.92

530.18-TG2Y

Unitary Products Group 15

Page 16: DCE, DCG TECHNICAL GUIDE - upgnet.netupgnet.net/Site/InformationCenter/York/Archive_CDs/York_1999/March... · dce dcg 090 102 120 150 090 102 120 150 evaporator blower centrifugal

UNITSIZE,D3CE

POWERSUPPLY

SUPPLY AIRBLOWER

FLAACCESSORY ELECTRIC HEATERS

TOTAL UNITAMPACITY,

AMPS

MAXIMUMFUSE

SIZE,1, 2

AMPSMOTOR HPMODEL NO. KW STAGES TOTAL

AMPSMOTOR HP

LO HI LO HI LO HI

120

10 TONUNIT with2 OR 3 HPBLOWER

208-3-60 7.5 10.6

2HE045118252HE045124252HE045136252HH04515425

13.518.027.040.6

2222

37.550.075.1112.6

56.371.9103.2150.1

60.275.8107.1154.0

6080110175

7080110175

230-3-60 7.5 10.6

2HE045118252HE045124252HE045136252HH04515425

18.024.036.054.0

2222

43.357.786.6129.9

63.581.5117.6139.3

67.485.4121.5143.2

7090

125150

7090125175

460-3-60 3.4 4.8

2HE04511846*2HE045124462HE045136462HE04515446

18.024.036.054.0

2222

21.728.943.365.0

31.340.358.469.2

33.142.160.171.0

35456080

35457080

575-3-60 2.7 3.9

2HE045118582HE045124582HE045136582HE04515458

18.024.036.054.0

2222

17.323.134.652.0

25.032.246.755.3

26.533.748.256.8

30355060

30355070

150

12 TONUNIT with3 OR 5 HPBLOWER

208-3-60 10.6 15.1

2HE045118252HE045124252HE045136252HH04515425

13.518.027.040.6

2222

37.550.075.1112.6

66.675.8107.1154.0

71.181.4112.7159.6

8080110175

9090125175

230-3-60 10.6 15.1

2HE045118252HE045124252HE045134252HH04515425

18.024.036.054.0

2222

43.357.786.6129.9

67.485.4121.5143.2

73.091.0127.1148.8

8090

125175

90100150175

460-3-60 4.8 7.5

2HE04511846*2HE045124462HE045136462HE04515446

18.024.036.054.0

2222

21.728.943.365.0

33.142.160.171.0

36.445.563.574.3

40457080

40507090

575-3-60 3.9 5.9

2HE045118582HE045124582HE045136582HE04515458

18.024.036.054.0

2222

17.323.134.652.0

29.133.748.256.8

31.136.250.759.3

35355070

40406070

1Dual element, time delay type.2Maximum HACR breaker of the same AMP size is applicable, except 575 voltages. Standard circuit breakers may be used in Canada and on applications over 60 amps where the heaters are separately fused..

*These electric heaters do NOT include fuses. If fuses are required to meet a local code (eg. Chicago), an accessory fuse box with fuses (2FB04700346) is available for field installation.

ELECTRIC HEATCORRECTION

FACTORS

NOMINAL VOLTAGE VOLTAGE KW CAP. MULTIPLIER208 208 1.00240 230 0.92480 460 0.92600 575 0.92

ELECTRICAL DATA- Cont’d. - Cooling / Electric Heating (DCE120 & 150)

530.18-TG2Y

16 Unitary Products Group

Page 17: DCE, DCG TECHNICAL GUIDE - upgnet.netupgnet.net/Site/InformationCenter/York/Archive_CDs/York_1999/March... · dce dcg 090 102 120 150 090 102 120 150 evaporator blower centrifugal

All dimensions are in inches. They aresubject to change without notice. Certifieddimensions will be provided upon request.

CLEARANCES

HOLEOPENING

SIZE(DIA.)

USED FOR

A3/4" KO Control

WiringSide

7/8" KO Bottom*

B 2" KO Power Wiring(Side or Bottom)*

C 2" KO Gas Piping (Front)D 1-11/16" Hole Gas Piping (Bottom)*

*Openings in the bottom of the unit can be located by the slice in the insulation.

UTILITIES ENTRY DATA

UNIT DIMENSIONS (DCE AND DCG - 7-1/2 THRU 12-1/2 TON)

RETURN AIR

SUPPLY AIR

CONDENSER AIR

OUTDOOR AIR(Economizer)

Front 24"

Back12" (Less Economizer)36" (With Economizer/ Outdoor Air Damper)

Left Side (Filter Access) 24" (Less Economizer)54" (With Economizer)3

Right Side (Cond. Coil) 24"Below Unit1 20"

Above Unit272" With 36" Maximum Horizontal Overhang (For Condenser Air Discharge)

1 Units may be installed on combustible floors made from wood or class A, B or C roof covering material.2 Units must be installed oudoors. Overhanging structures or shrubs should not obstruct condenser air discharge outlet.3 If economizer is factory installed, the assembled hood kit must be removed prior to final installation. This hood is 54" long.

NOTE:DCE Models: Units and ductwork are approved for zero clearance tocombustible materials when equipped with electric heaters.

DCG Models: A 1" clearance must be provided between any combustiblematerial and the supply air ductwork for a distance of 3 feet from the unit.

The products of combustion must not be allowed to accumulate within aconfined space and recirculate.

Locate unit so that the vent air outlet hood is at least:• Three (3) feet above any forced air inlet located within 10 horizontal feet

(excluding those integral to the unit).

• Four (4) feet below, 4 horizontal feet from, or 1 foot above any door orgravity air inlet into the building.

• Four (4) feet from electric meters, gas meters, regulators and reliefequipment.

530.18-TG2Y

Unitary Products Group 17

Page 18: DCE, DCG TECHNICAL GUIDE - upgnet.netupgnet.net/Site/InformationCenter/York/Archive_CDs/York_1999/March... · dce dcg 090 102 120 150 090 102 120 150 evaporator blower centrifugal

CENTER OF GRAVITY

DUCT COVERS - Units are shipped with all air ductopenings covered.For side duct applications;1.Remove and discard the supply and return air duct covers.2.Connect ductwork to duct flanges on the rear of the unit.For bottom duct applications;1. Remove the side supply and return air duct covers to gain access to the bottom supply and return air duct covers.2. Remove and discard the bottom duct covers.3. Replace the side duct covers.

DETAIL “X”SIDE SUPPLY AND RETURN AIR DUCT OPENINGS

DETAIL “Y”UNIT WITH ECONOMIZER AND FIXED OUTDOOR AIR HOODS

UNIT DIMENSIONS - Cont’d. -(DCE and DCG - 7-1/2 THRU 12-1/2 TON)

B A R O M E T R I C R E L I E F R A I N H O O D

R E A R V I E W L . H . E N D V I E W

2 3 - 3 / 8 " 2 "3 - 3 / 4 " A

2 7 "

3 / 4 " C O N D E N S A T ED R A I N( M U S T B E T R A P P E D )

7 "

( B ) P O W E R W I R I N G E N T R Y

2 9 - 5 / 8 "

3 - 1 / 2 "

4 - 1 / 2 "

7 1 "

E C O N O M I Z E R R A I N H O O D

D I M " A "2 83 13 12 4

E C O N O M I Z E RM O T O R I Z E D D A M P E RM A N U A L D A M P E R 0 - 1 0 0 %M A N U A L D A M P E R 0 - 3 5 %

DIM.UNIT

7-1/2 TON 8-1/2 TON 10 TON 12-1/2 TONA 33-1/4" 32" 32-1/2" 32-1/2"B 47-1/2" 44-1/2" 46-3/4" 45"

530.18-TG2Y

18 Unitary Products Group

Page 19: DCE, DCG TECHNICAL GUIDE - upgnet.netupgnet.net/Site/InformationCenter/York/Archive_CDs/York_1999/March... · dce dcg 090 102 120 150 090 102 120 150 evaporator blower centrifugal

POINT LOADS

A

D

C

B

F R O N T

4 POINT LOADS

DCEUNIT

4 - POINT LOADS (LBS)TOTAL A B C D

090 1077 238 266 303 270102 1102 219 277 338 268120 1177 250 289 342 296150 1327 271 336 398 322

DCEUNIT

6 - POINT LOADS (LBS)TOTAL A B C D E F

090 1077 158 168 178 202 191 180102 1102 146 166 185 225 202 178120 1177 167 179 193 228 213 197150 1327 181 202 224 266 240 214

NOTE: These weights are with economizer and 24kW electric heat.

A

E

D

B

C

F

F R O N T

6 POINT LOADS

DCGUNIT

4 - POINT LOADS (LBS)TOTAL A B C D

090 1187 262 298 333 294102 1202 239 292 369 302120 1312 279 330 381 322150 1582 323 383 475 401

DCGUNIT

6 - POINT LOADS (LBS)TOTAL A B C D E F

090 1187 175 198 210 222 196 186102 1202 160 194 220 245 202 181120 1312 186 220 237 254 215 201150 1582 215 256 286 317 267 241

NOTE: These weights are with economizer, high heat and oversized motor.

530.18-TG2Y

Unitary Products Group 19

Page 20: DCE, DCG TECHNICAL GUIDE - upgnet.netupgnet.net/Site/InformationCenter/York/Archive_CDs/York_1999/March... · dce dcg 090 102 120 150 090 102 120 150 evaporator blower centrifugal

ROOF CURB DIMENSIONS - (DCE and DCG - 7-1/2 THRU 12-1/2 TON)

➀ The 4" space between the ducts allows for “jumping” an existing roof joist.

➁ The 41" overall dimension of the ducts allows ductwork penetration between roof joists that are spaced on 48" centers.

NOTE: Ducts can be installed onto the curb from the roof. All electrical and gas line connections can be made inside the curb.

ROOF CURB BENEFITS

UNIT AND CURB APPLICATION

*Supply and Return Air (including duct support rails) as shown, are typical for bottom duct applications.

For location of horizontal duct applications (on back of unit), refer to Unit Dimension details.

9/16

BASE RAIL3.56"

3.69"

530.18-TG2Y

20 Unitary Products Group

Page 21: DCE, DCG TECHNICAL GUIDE - upgnet.netupgnet.net/Site/InformationCenter/York/Archive_CDs/York_1999/March... · dce dcg 090 102 120 150 090 102 120 150 evaporator blower centrifugal

TYPICAL APPLICATIONS

TYPICAL ROOF-TOP INSTALLATION (ELECTRIC/ELECTRIC UNIT SHOWN)

530.18-TG2Y

Unitary Products Group 21

Page 22: DCE, DCG TECHNICAL GUIDE - upgnet.netupgnet.net/Site/InformationCenter/York/Archive_CDs/York_1999/March... · dce dcg 090 102 120 150 090 102 120 150 evaporator blower centrifugal

FACTORY INSTALLED OPTIONS

FIELD-INSTALLED ACCESSORIES

ECONOMIZERS: Units equipped with the factory-installedeconomizer option have dampers that are positioned by aspring return, fully modulating damper actuator capable ofintroducing up to 100% outdoor air. As the outdoor air intakedampers open, the return air dampers close. The changeoverfrom mechanical refrigeration to economizer operation isdetermined by a single input electronic enthalpy control or by adual input electronic enthalpy control. Simultaneouscompressor and economizer operation is also possible.Economizer dampers are 2% low leakage type. A barometricrelief damper is shipped in the return air compartment for fieldinstallation.The single enthalpy system contains a sensor that monitors theoutdoor air which automatically operates the damper actuatorallowing the dampers to open or close.

The dual enthalpy system contains a second sensor thatmonitors the return air in addition to monitoring the outdoorair described above for a single enthalpy system. The logicmodule compares these two values and modulates thedampers providing the maximum efficiency of theeconomizer system.

The economizer is completely wired and installed at the factory.Only the outdoor air hood, including its filters, need beassembled and installed in the field.

ALTERNATE INDOOR FAN MOTORS: Larger horsepowermotors are available on most models to handle higher staticpressure applications.

SINGLE INPUT ELECTRONIC ENTHALPY ECONOMIZER -Includes a slide-in / plug-in damper assembly with fullymodulating spring return motor actuator capable of introducingup to 100% outdoor air, one outdoor air electronic enthalpysensor and a rainhood with filters. The rainhood is painted tomatch the basic unit and must be field-assembled beforeinstallation. Economizer dampers are 2% low leakage type.

DUAL INPUT ELECTRONIC ENTHALPY ECONOMIZER -Includes the same damper system and rainhood with filters asdescribed for a single enthalpy economizer above except thisaccessory contains two enthalpy sensors. It uses a differentialenthalpy control that compares the outdoor air versus the returnair. The logic module then optimizes the economizer operationfor additional savings over the single input economizer.

MOTORIZED AIR DAMPER - Includes slide-in / plug-in damperassembly with rainhood and filters. The outdoor air dampersopen when the indoor fan motor is energized. Damper capableof providing 0% thru 100% of outdoor return air opening.

MANUAL OUTDOOR DAMPER - Provides 0% thru 35% or 0%thru 100% of outdoor return air opening (field adjustable).Designed for duct mounted side or bottom supply/returnapplications. includes both hood assembly and filters.

ELECTRIC HEATERS - Include nickel chromium elements, aterminal block, fuses (where required by UL), all the necessaryconnectors and hardware. All heaters utilize single point powersupply hookup. Capacities of 9, 18, 24, 36 and 54 KW heatingare available.

FUSE BLOCK KIT - This kit contains a fuse block including thefuses and is available for the 9 and 18 KW 460-volt heater kits.This kit satisfies the Chicago code requirements.

ROOF CURB - This 14" high full perimeter roof curb is shippedknocked down for field assembly. Its duct supports andinsulated condensing section deck can be reversed to connectthe ductwork on the opposite end.

LOW AMBIENT KIT - Head pressure controllers maintainstable operation by reducing the speed of the condenser fanmotors when the outdoor temperature is between 45 and 0°F.Condenser fan motors with ball bearings and heavier windingsare available for these low ambient applications.

ANTI-RECYCLE TIMER - A timer to prevent unit compressorsfrom short cycling. It assures a 5-minute “off-time” betweencompressor cycles.

PROPANE CONVERSION KIT - Converts a gas-fired heaterfrom natural gas to propane. It contains main burner orifices, apilot orifice and a gas valve.

GAS PIPING - This kit contains 3/4" pipe nipples, fittings andgas cock (including panel access gaskets) required for bottomgas supply connection with external shut-off.

HIGH ALTITUDE CONVERSION (NATURAL AND PROPANE)- Provides orifices for proper furnace operation at altitudes upto 6,000 ft. For propane applications, the propane conversionkit will also be required.

WALL THERMOSTAT - The units are designed to operate with24-volt electronic and electro-mechanical thermostats. Allelectric / electric and gas / electric units operate with two stageheat / two stage cool thermostats (with or without aneconomizer).

530.18-TG2Y

22 Unitary Products Group

Page 23: DCE, DCG TECHNICAL GUIDE - upgnet.netupgnet.net/Site/InformationCenter/York/Archive_CDs/York_1999/March... · dce dcg 090 102 120 150 090 102 120 150 evaporator blower centrifugal

530.18-TG2Y

Unitary Products Group 23

Page 24: DCE, DCG TECHNICAL GUIDE - upgnet.netupgnet.net/Site/InformationCenter/York/Archive_CDs/York_1999/March... · dce dcg 090 102 120 150 090 102 120 150 evaporator blower centrifugal

Unitary Products GroupP.O. Box 1592, York, Pennsylvania USA 17405-1592Subject to change without notice. Printed in U.S.ACopyright by York International Corporation 1998. All Rights Reserved. Codes: EBY,EGY

530.18-TG2YSupersedes: 530.18-TG2Y (1095)