DC solutions for Data CentersDC solutions for Data Centers2011-09-06

M k S kMarek Szpek

Page 2: DC solutions for Data Centers - dcforum.rudcforum.ru/sites/default/files/09_-_14.20-14.40_marek_shpek... · 9/6/2011 · NetSure™ ITM Row-Based 48V DC UPS It td t ti lti NetSure™

AgendaAgendaAgendaAgendaAgendaAgendaAgendaAgendaAdvantages of DC power in Data Centers

-48V DC

400V DC400V DC

Conclusion

2

Emerson Electric Co; Proprietary Information

Page 3: DC solutions for Data Centers - dcforum.rudcforum.ru/sites/default/files/09_-_14.20-14.40_marek_shpek... · 9/6/2011 · NetSure™ ITM Row-Based 48V DC UPS It td t ti lti NetSure™

Why DC in Data Centers?Why DC in Data Centers?Why DC in Data Centers?Why DC in Data Centers?Why DC in Data Centers?Why DC in Data Centers?Why DC in Data Centers?Why DC in Data Centers?Datacenter trends in the marketplace show needs for:

more efficient & more dense power solutions– more efficient & more dense power solutions – diversification between functions with various needs of availability – Wide range of different backup times

DC Power is a good alternative to AC backup when– efficiency savings and TCO are important

High requirements on redundancy and availability– High requirements on redundancy and availability– Extended backup time is needed – Modularity is required to allow gradual expansion

NetSure™ ITM – an Emerson DC Power solution developed especially for Datacenters

3

Emerson Electric Co; Proprietary Information

Page 4: DC solutions for Data Centers - dcforum.rudcforum.ru/sites/default/files/09_-_14.20-14.40_marek_shpek... · 9/6/2011 · NetSure™ ITM Row-Based 48V DC UPS It td t ti lti NetSure™

48V IT Equipment Available Today48V IT Equipment Available Today48V IT Equipment Available Today48V IT Equipment Available Today48V IT Equipment Available Today48V IT Equipment Available Today48V IT Equipment Available Today48V IT Equipment Available TodayMajor manufacturers offer 200+ models available with DC input– HP, Cisco, Sun, Rackable (SGI), IBM, Juniper, Brocade, EMC

– Switches, Servers, Storage, Routers

4

Emerson Electric Co; Proprietary Information

Page 5: DC solutions for Data Centers - dcforum.rudcforum.ru/sites/default/files/09_-_14.20-14.40_marek_shpek... · 9/6/2011 · NetSure™ ITM Row-Based 48V DC UPS It td t ti lti NetSure™

Power Protection ArchitecturePower Protection ArchitecturePower Protection ArchitecturePower Protection ArchitectureTraditional AC-UPS

Power Protection ArchitecturePower Protection ArchitecturePower Protection ArchitecturePower Protection Architecture

- 48V DC 48V DC

400 VDC 400V DC

Fewer conversions higher efficiency & less complexity – Fewer points of failure– Increased availability & reliability

5

Emerson Electric Co; Proprietary Information

Page 6: DC solutions for Data Centers - dcforum.rudcforum.ru/sites/default/files/09_-_14.20-14.40_marek_shpek... · 9/6/2011 · NetSure™ ITM Row-Based 48V DC UPS It td t ti lti NetSure™

AgendaAgendaAgendaAgendaAgendaAgendaAgendaAgendaAdvantages of DC power in Data Centers

-48V DC

400V DC400V DC

Conclusion

6

Emerson Electric Co; Proprietary Information

Page 7: DC solutions for Data Centers - dcforum.rudcforum.ru/sites/default/files/09_-_14.20-14.40_marek_shpek... · 9/6/2011 · NetSure™ ITM Row-Based 48V DC UPS It td t ti lti NetSure™

BackgroundBackgroundDC Power System for Data CentersDC Power System for Data CentersBackgroundBackgroundDC Power System for Data CentersDC Power System for Data CentersDC Power System for Data CentersDC Power System for Data CentersDC Power System for Data CentersDC Power System for Data Centers

First NetSure prototype for data centers built 4 years agocenters built 4 years ago

Main objective for this system was to

S– Save energy

– Save footprint

R d i iti l i t t– Reduce initial investment compared to traditional UPS’s

First system installed at an Amazon data centerFirst system installed at an Amazon data center

The concept is further developed in NetSure ITM

7

Emerson Electric Co; Proprietary Information

Page 8: DC solutions for Data Centers - dcforum.rudcforum.ru/sites/default/files/09_-_14.20-14.40_marek_shpek... · 9/6/2011 · NetSure™ ITM Row-Based 48V DC UPS It td t ti lti NetSure™

NetSure™ ITMNetSure™ ITMNetSure™ ITMNetSure™ ITMRow-Based 48V DC UPS

I t t d t ti l ti

NetSure™ ITMNetSure™ ITMNetSure™ ITMNetSure™ ITM

Integrated power protection solution

– connect up to 4 x 70 kW modules per system

– Redundancy in 5.8kW increments• Hot swappable

– 3 battery strings per module– 3 battery strings per module• 5-10 minutes of backup at full load• 10 year life time VRLA batteries

– Branch distribution: 22 output circuit breakers

– Rack form-factor: 600mm (w) x 1040mm (d); 24” x 41”N tS ™ ITM ith 2 70kW d l

– Top, bottom or mixed cable entry

– Single or dual AC inputs

NetSure™ ITM with 2 x 70kW modules

8

Emerson Electric Co; Proprietary Information

Page 9: DC solutions for Data Centers - dcforum.rudcforum.ru/sites/default/files/09_-_14.20-14.40_marek_shpek... · 9/6/2011 · NetSure™ ITM Row-Based 48V DC UPS It td t ti lti NetSure™

Slab Floor Deployment ExampleSlab Floor Deployment ExampleSlab Floor Deployment ExampleSlab Floor Deployment Example120A AC feed to each module120A AC feed to each module

Slab Floor Deployment ExampleSlab Floor Deployment ExampleSlab Floor Deployment ExampleSlab Floor Deployment Example

|PrimaryModule

|E i

Ladder rack supported by IT racksor suspended from ceilingLadder rack supported by IT racksor suspended from ceilingLadder rack supported by IT racksor suspended from ceilingLadder rack supported by IT racksor suspended from ceilingModule

63kWExpansion

Module70kW

or suspended from ceilingor suspended from ceilingor suspended from ceilingor suspended from ceiling

Schematic overviewSchematic overview

9

Emerson Electric Co; Proprietary Information

Page 10: DC solutions for Data Centers - dcforum.rudcforum.ru/sites/default/files/09_-_14.20-14.40_marek_shpek... · 9/6/2011 · NetSure™ ITM Row-Based 48V DC UPS It td t ti lti NetSure™

Scalable Capacity with NetSure ITMScalable Capacity with NetSure ITMScalable Capacity with NetSure ITMScalable Capacity with NetSure ITMScalable Capacity with NetSure ITMScalable Capacity with NetSure ITMScalable Capacity with NetSure ITMScalable Capacity with NetSure ITM

Connect (1) to (4) DC UPS modules to a single controller

10

Emerson Electric Co; Proprietary Information

Connect (1) to (4) DC UPS modules to a single controller

Page 11: DC solutions for Data Centers - dcforum.rudcforum.ru/sites/default/files/09_-_14.20-14.40_marek_shpek... · 9/6/2011 · NetSure™ ITM Row-Based 48V DC UPS It td t ti lti NetSure™

AgendaAgendaAgendaAgendaAgendaAgendaAgendaAgendaAdvantages of DC power in Data Centers

-48V DC

400V DC400V DC

Conclusion

11

Emerson Electric Co; Proprietary Information

Page 12: DC solutions for Data Centers - dcforum.rudcforum.ru/sites/default/files/09_-_14.20-14.40_marek_shpek... · 9/6/2011 · NetSure™ ITM Row-Based 48V DC UPS It td t ti lti NetSure™

400VDC400VDC DriversDrivers400VDC400VDC DriversDrivers400VDC 400VDC -- DriversDrivers400VDC 400VDC -- DriversDrivers

Source: CPES

12

Emerson Electric Co; Proprietary Information

Source: CPES

Page 13: DC solutions for Data Centers - dcforum.rudcforum.ru/sites/default/files/09_-_14.20-14.40_marek_shpek... · 9/6/2011 · NetSure™ ITM Row-Based 48V DC UPS It td t ti lti NetSure™

400V DC vs AC UPS in Data Centers400V DC vs AC UPS in Data Centers400V DC vs AC UPS in Data Centers400V DC vs AC UPS in Data Centers400V DC vs AC UPS in Data Centers 400V DC vs AC UPS in Data Centers 400V DC vs AC UPS in Data Centers 400V DC vs AC UPS in Data Centers

70

75

[%]

Facility 400Vdc

S i li d

Facility 48VdcIncreased overall efficiency 5-10%(less conversion stages)

60

65

deliv

ery

effic

ienc

y [ Specialized

AC UPS

High efficiency 480Vac, Rack 400Vdc, Rack 48Vdc

Facility 550V/48Vdc, 400Vac

(less conversion stages)

Higher availability > 10x

Lower footprint ≈ 30%

50

55

0 20 40 60 80 100

Load [%]

Pow

er

Baseline 480VacLower footprint, ≈ 30%

Lower heat load

E i i t ti f R bl Load [%]Source: Intel studyEasier integration of Renewable

Energy and micro-grid

13

Emerson Electric Co; Proprietary Information

Source: NTT-Facilities

Page 14: DC solutions for Data Centers - dcforum.rudcforum.ru/sites/default/files/09_-_14.20-14.40_marek_shpek... · 9/6/2011 · NetSure™ ITM Row-Based 48V DC UPS It td t ti lti NetSure™

Emerson’s 400V pilot cabinetEmerson’s 400V pilot cabinetEmerson’s 400V pilot cabinetEmerson’s 400V pilot cabinetEmerson s 400V pilot cabinetEmerson s 400V pilot cabinetEmerson s 400V pilot cabinetEmerson s 400V pilot cabinetInput: 480VAC with 3 phase 4 wire

Output: 297 to 400V

Provides up to 80KW

High resistance mid-point grounding concept (+200V, -200V)

L d i l ti d t ti f tiLoad insulation detection function

Max 7 output load connection with load measurement

Standard server rack 600(w)*1000(D)*2000(H) :mm

14

Emerson Electric Co; Proprietary Information

Page 15: DC solutions for Data Centers - dcforum.rudcforum.ru/sites/default/files/09_-_14.20-14.40_marek_shpek... · 9/6/2011 · NetSure™ ITM Row-Based 48V DC UPS It td t ti lti NetSure™

Examples of Emerson 400V pilot installationsExamples of Emerson 400V pilot installationsExamples of Emerson 400V pilot installationsExamples of Emerson 400V pilot installationsExamples of Emerson 400V pilot installations Examples of Emerson 400V pilot installations Examples of Emerson 400V pilot installations Examples of Emerson 400V pilot installations

A

BB

A+B configuration

IBM Blade server

A+B configuration400V+Lithium-ion

Battery

15

Emerson Electric Co; Proprietary Information

Page 16: DC solutions for Data Centers - dcforum.rudcforum.ru/sites/default/files/09_-_14.20-14.40_marek_shpek... · 9/6/2011 · NetSure™ ITM Row-Based 48V DC UPS It td t ti lti NetSure™

400VDC sub400VDC sub--rack for embedded rack for embedded applicationsapplications400VDC sub400VDC sub--rack for embedded rack for embedded applicationsapplicationsapplicationsapplicationsapplicationsapplications

2 X 10kW 400VDC2 X 10kW 400VDC•Controller•Output Breakers•400V-48V Converter•400V-48V Converter

16

Emerson Electric Co; Proprietary Information16

Page 17: DC solutions for Data Centers - dcforum.rudcforum.ru/sites/default/files/09_-_14.20-14.40_marek_shpek... · 9/6/2011 · NetSure™ ITM Row-Based 48V DC UPS It td t ti lti NetSure™

AgendaAgendaAgendaAgendaAgendaAgendaAgendaAgendaAdvantages of DC power in Data Centers

-48V DC

400V DC400V DC

Conclusion

17

Emerson Electric Co; Proprietary Information

Page 18: DC solutions for Data Centers - dcforum.rudcforum.ru/sites/default/files/09_-_14.20-14.40_marek_shpek... · 9/6/2011 · NetSure™ ITM Row-Based 48V DC UPS It td t ti lti NetSure™

ConclusionsConclusionsConclusionsConclusionsConclusionsConclusionsConclusionsConclusionsDC solutions in data centers vs traditional UPS’s

– higher total efficiency

– higher availability

l fl– less floor space

48V solutions – well established especially for telecom applications

Wide range of ICT equipment available for data centers with either AC or 48V interface

400VDC is on its way to become a new power interface standard400VDC is on its way to become a new power interface standard

– Standardization work is underway within ETSI, IEC, ITU

– 400V mass deployment is expected in ~2 years400V mass deployment is expected in 2 years

18