www.raycap.com INSTALL INSTRUCTIONS RRFDC-3315-PF-48 Installation Instructions: RRFDC-3315-PF-48 (DB-B1-6C-12AB-0Z)

(DB-B1-6C-12AB-0Z) - Talley Inc. INSTALL INSTRUCTIONS RRFDC-3315-PF-48 Installation Instructions: RRFDC-3315-PF-48 (DB-B1-6C-12AB-0Z)

Embed Size (px)

Citation preview

Page 1: (DB-B1-6C-12AB-0Z) - Talley Inc. INSTALL INSTRUCTIONS RRFDC-3315-PF-48 Installation Instructions: RRFDC-3315-PF-48 (DB-B1-6C-12AB-0Z)

www.raycap.com

INSTALL INSTRUCTIONS RRFDC-3315-PF-48

Installation Instructions:

RRFDC-3315-PF-48(DB-B1-6C-12AB-0Z)

Page 2: (DB-B1-6C-12AB-0Z) - Talley Inc. INSTALL INSTRUCTIONS RRFDC-3315-PF-48 Installation Instructions: RRFDC-3315-PF-48 (DB-B1-6C-12AB-0Z)
Page 3: (DB-B1-6C-12AB-0Z) - Talley Inc. INSTALL INSTRUCTIONS RRFDC-3315-PF-48 Installation Instructions: RRFDC-3315-PF-48 (DB-B1-6C-12AB-0Z)

www.raycap.com

©Raycap • All rights reserved320-0799 Rev.C

Page 1 of 46

INSTALL INSTRUCTIONS RRFDC-3315-PF-48 (DB-B1-6C-12AB-0Z)

Contents

1. Copyright 2

1.1 Disclaimer 2

1.2 Warnings 2

2. Introduction 3

3. Overvoltage Protection Package Contents 3

3.1 Prerequisites 3

3.2 Required Tools and Supplies 3

4.1 Mounting Procedures 4

5.1 Gland/InsertDefinitions 4

6.1 Pre-wiring Preparation Procedure 5

7.1 Cable Installation Instructions 7

8.1 Installing Ground Cable 8

8.1 Installing Hybrid Cable-Power (In) 8

9.1 Hybrid Cable 9

10.1 Installing 6/12 Hybrid Cable 10

11.1 Installing 4/8 Hybrid Cable 11

12.1 Installing 2/4 Hybrid Cable 12

13.1 Installing Alarm for RRFDC-3315-PF-48 13

14.1 The RTFI (Real Time Fault Indicator) PCB 24

15.1 Installing Hybrid Cable-Fiber (In) 25

16.1 Installing Hybrid Cable-Fiber (Out) 26

17.1 Voltage Monitor Operation 27

18.1 Removing a Strikesorb Module 28

19.1 Optional90˚ElbowInstallation 29

20.1 Installation Complete. Closing and Securing Unit 31

21.1 Appendix 33

Page 4: (DB-B1-6C-12AB-0Z) - Talley Inc. INSTALL INSTRUCTIONS RRFDC-3315-PF-48 Installation Instructions: RRFDC-3315-PF-48 (DB-B1-6C-12AB-0Z)

www.raycap.com

©Raycap • All rights reserved320-0799 Rev.C

Page 2 of 46

RRFDC-3315-PF-48 INSTALL INSTRUCTIONS (DB-B1-6C-12AB-0Z)

1.0 Copyright© Raycap, Inc. 2014 - All Rights Reserved

1.1 DisclaimerThe information in this document is subject to change without notice and describes only the product defined in the introduction of this documentation. This documentation is intended for the use of Raycap customers only for the purposes of the agreement under which the document is submitted, and no part may be used, reproduced, modified or transmitted in any form or means without the prior written permission of Raycap. The documentation has been prepared to be used by professional and properly trained personnel, and the customer assumes full responsibility when using it. Raycap welcomes customer comments as part of the process of continuous development and improvement of the documentation.

Raycap has made all reasonable efforts to ensure that the instructions contained in this document are adequate and free of material errors and omissions. Raycap will, if deemed necessary, explain issues which may not be covered by this document.

The contents of this document are subject to revision without notice due to continued progress in methodology, design and manufacturing. Raycap shall have no liability for any error damage of any kind resulting from the use of this document.

1.2 WarningsPlease read this manual prior to use to become familiar with the product’s numerous features and operating procedures. To maintain the maximum degree of safety, follow the sequences as outlined.  Before using the product, read all instructions and cautionary markings on the product and on any equipment connected to the product.

CAUTION – Unless otherwise noted, product usage that is not recommended or sold by the product manufacturer can result in risk of fire, electric shock, or injury to persons.

CAUTION – Do not operate the product if it has been damaged in any way. Return damaged products to their manufacturer for repair or replacement.

CAUTION – Do not disassemble the product as incorrect reassembling can risk electrical shock or fire.

WARNING – Disconnect or disable the DC power source to the product prior to beginning its installation. Ensure that the DC power source to the product remains de-energized until the completion of the installation and after all connections have been verified to be correctly configured.

ATTENTION – Electrostatic sensitive devices. ESD mitigative procedures, such as wearing wriststraps are to be used during installation and maintenance.

CAUTION – Do not bend fiber-optic cables beyond their minimum bend radius. Bending the cables beyond their minimum bend radius can damage the cables and cause problems that are difficult to diagnose. (See pg. 5 for typical bend radius’)

CAUTION – Do not let fiber-optic cables hang free from the connector. All fiber must be secured against movement in wind while maintaining enough slack to prevent any tension along the run. Do not allow fastened loops of cables to dangle, which stresses the cables at the fastening point.

WARNING – Do not look directly into a fiber-optic transceiver or into the ends of fiber-optic cables. Fiber-optic transceivers and fiber-optic cables connected to transceivers emit laser light that can damage your eyes.

Page 5: (DB-B1-6C-12AB-0Z) - Talley Inc. INSTALL INSTRUCTIONS RRFDC-3315-PF-48 Installation Instructions: RRFDC-3315-PF-48 (DB-B1-6C-12AB-0Z)

www.raycap.com

©Raycap • All rights reserved320-0799 Rev.C

Page 3 of 46

INSTALL INSTRUCTIONS RRFDC-3315-PF-48 (DB-B1-6C-12AB-0Z)

WARNING: Do not stare into the laser beam or view it directly with optical instruments even if the interface has been disabled.

1. If the fiber-optic cable connector is covered by a rubber safety cap, remove the cap. Save the cap.2. If the optical transceiver is covered by a rubber safety cap, remove the cap. Save the cap.3. Prior to connecting the fiber to the device, clean it using proper industry accepted cleaning methods.4. Insert the cable connector into the optical transceiver.5. Secure the cables so that they are not supporting their own weight. Place excess cable out of the way in

a neatly coiled loop. Placing fasteners on a loop helps cables maintain their shape.

For conditions other than those described above, please contact a Raycap Account Representative at +1 (208) 777-1166, (800) 890-2569, [email protected], or www.raycap.com

Thank you for choosing quality products from Raycap.

2.0 IntroductionIn a split Radio Base Station (RBS) architecture the typical RBS consists of a Base Band Unit (BBU) and Remote Radio Heads (RRH) connected by cabling. Power to the RRH is provided through copper cables traveling from the base station to the top of the tower or roof top. This creates a conductive path, making the active equipment at the top and the base of the site vulnerable to damage by direct lightning strikes. Protection systems installed in front of both the BBU and the RRH must be able to withstand direct lightning currents in order to protect the sensitive equipment.

Raycap’s RRH solutions featuring Strikesorb® SPD technology significantly enhance the reliability & availability of the RRH site by providing superior electrical protection at the RRH and BBU, and also enable flexible fiber optic and power cable management solutions.

3.0 Overvoltage Protection Package Contents• One (1) Enclosure including the SPDs, cable glands, the DC distribution and fiber management parts.• Incorporated Mounting bracket and related accessories.• Mounting hardware accessories (bolts, washers and nuts).

3.1 PrerequisitesThis document describes how to install the RRFDC-3315-PF-48 on-site and how to mount, and connect it to external interfaces.

Installers of Raycap’s RRH surge protective and fiber/power management solutions must be industry professionals who have attended training on the proper installation of the equipment by Raycap and/or the mobile operator. Installers are required to read this installation guide thoroughly prior to installation of the Raycap RRH protection equipment.

Installers shall obey all general and regional installation and safety regulations related to work on high voltage installations, as well as regulations covering correct use of tools and personal protective equipment. Use this equipment only for the purpose specified by the manufacturer. Do not carry out any modifications or fit any parts that are not recommended by the manufacturer. This could cause electric shock or other injuries.

3.2 Required Tools & SuppliesWire cutterWire strippersFlat head screwdriverSmall flat head screwdriver

Cross head screwdriverAdjustable wrench 5/32" Hex key/driver

Page 6: (DB-B1-6C-12AB-0Z) - Talley Inc. INSTALL INSTRUCTIONS RRFDC-3315-PF-48 Installation Instructions: RRFDC-3315-PF-48 (DB-B1-6C-12AB-0Z)

www.raycap.com

©Raycap • All rights reserved320-0799 Rev.C

Page 4 of 46

RRFDC-3315-PF-48 INSTALL INSTRUCTIONS (DB-B1-6C-12AB-0Z)

ProcedureMounting Procedures

4.1 A mounting base is delivered with the unit. The base allows either wall/ladder or pole mounted installation. See picture to identify the holes for each installation method.

4.2 Option 1: Pole Mount Using supplied hardware, mount Bracket to 2” to 4” diameter pole.

4.3 Option 2: Unistrut

4.4 Option 3: Monopole Use 1” stainless steel bands (not supplied) through slots on bracket to mount to Monopole.

Gland/InsertDefinitions

5.1 See picture to identify Base Gland Assembly Definitions.

• Pole Mount• Unistrut

• Monopole

• Metal mounting frame

Included in kit shipped with unit:

Pos Connector Size

InsertQty

InsertP/N

InsertRange

Cable CableTypeOD (in) mm

A M75 1 190-0644 26-29mm 1.107" 28.12x4 #6 & #8

4x8 #8

B M75 2 190-0620 37-40mm 1.551" 39.46x12 #6 & #8

4x8 #6

B M75 2 190-0621 3x 19-22mm 0.846" 21.5 1x1

B M75 1 190-0657 6x 4.6-6.1mm Fiber

C M63 1 190-0635 3x 12-13.5mm Power

Note: Remove inserts to accommodate the following cables:

Pos Connector Size

InsertQty

InsertP/N

InsertRange

Cable CableTypeOD (in) mm

A M75 NONE 48-55mm 1.996" 50.78x8 #86x6 #6

C M63 NONE 37-44mm 1.551" 39.44x4 #8 & #6

4x8 #6

Assembled in unit as shipped:

Pos Connector Size

InsertQty

InsertP/N

InsertRange

Cable CableTypeOD (in) mm

A M75 1 190-0620 37-40mm 1.551" 39.46x12 #6 & #8

4x8 #6

B M75 2 190-0644 26-29mm 1.107" 28.12x4 #6 & #8

4x8 #8

C M63 2 190-0643 26-29mm 1.107" 28.12x4 #6 & #8

4x8 #8

CB

B A

C

Page 7: (DB-B1-6C-12AB-0Z) - Talley Inc. INSTALL INSTRUCTIONS RRFDC-3315-PF-48 Installation Instructions: RRFDC-3315-PF-48 (DB-B1-6C-12AB-0Z)

www.raycap.com

©Raycap • All rights reserved320-0799 Rev.C

Page 5 of 46

INSTALL INSTRUCTIONS RRFDC-3315-PF-48 (DB-B1-6C-12AB-0Z)

Pre-wiring Preparation Procedure

6.1 Ensure the lanyard from enclosure lid to enclosure base is secure.

Note: Use metal mounting frame to secure hoist when lifting to tower top.

Warning: Holes in lid for lanyard and padlock must NOT be used as hoist locations.

6.2 Open up clamps on all sides of the enclosure cabinet by lifting the hinged clamp tabs.

6.3 Remove enclosure lid.

Page 8: (DB-B1-6C-12AB-0Z) - Talley Inc. INSTALL INSTRUCTIONS RRFDC-3315-PF-48 Installation Instructions: RRFDC-3315-PF-48 (DB-B1-6C-12AB-0Z)

www.raycap.com

©Raycap • All rights reserved320-0799 Rev.C

Page 6 of 46

RRFDC-3315-PF-48 INSTALL INSTRUCTIONS (DB-B1-6C-12AB-0Z)

Pre-wiring preparation procedure

6.4 To access power and fiber connections, unclasp 1/4 turn latches, then fold down fiber tray.

6.5

Return Connection

Fiber ConnectionPanel

FiberManagement

Fiber PanelLabel

Alarm Board

Alarm Connector

Voltage MonitorConnections

Voltage MonitorPass-Thru

Connections

MoistureSensor

IntrusionSensor

StrikesorbModule

-48V Connection

VoltageMonitor

Return Connection

-48V Connection

Page 9: (DB-B1-6C-12AB-0Z) - Talley Inc. INSTALL INSTRUCTIONS RRFDC-3315-PF-48 Installation Instructions: RRFDC-3315-PF-48 (DB-B1-6C-12AB-0Z)

www.raycap.com

©Raycap • All rights reserved320-0799 Rev.C

Page 7 of 46

INSTALL INSTRUCTIONS RRFDC-3315-PF-48 (DB-B1-6C-12AB-0Z)

Cable installation instructions

7.1 At the base of the OVP boxes there are cable glands that provide weatherproofing for the enclosure. The following steps will show how to install the Hybrid cable properly.

7.2 Remove compression nut.

7.3 Remove center insert from cable gland.

7.4 Slide compression nut and insert over the cable breakout. Be careful not to damage the fiber connectors. Insert needs to be 1" behind heat shrink tube.

7.5 Carefully feed fiber and power conductors into the OVP box and tighten the compression nut.

Torque: 44 in-lbs

Note: Should the process of installing cables loosen the gland, then the inner nut needs to be retightened (66 in-lb [7.5 N-m]) to maintain the environmental seal of the enclosure.

Page 10: (DB-B1-6C-12AB-0Z) - Talley Inc. INSTALL INSTRUCTIONS RRFDC-3315-PF-48 Installation Instructions: RRFDC-3315-PF-48 (DB-B1-6C-12AB-0Z)

www.raycap.com

©Raycap • All rights reserved320-0799 Rev.C

Page 8 of 46

RRFDC-3315-PF-48 INSTALL INSTRUCTIONS (DB-B1-6C-12AB-0Z)

7.6 For more access to the printed circuit boards, the Fiber Panel can be temporarily removed. See illustrations below.

7.7 Attach lanyard to Mounting Bracket.

Installing Ground Cable

8.1 There are two grounding placement options available. See below.

Optional Cable Grounds

Main Ground

Page 11: (DB-B1-6C-12AB-0Z) - Talley Inc. INSTALL INSTRUCTIONS RRFDC-3315-PF-48 Installation Instructions: RRFDC-3315-PF-48 (DB-B1-6C-12AB-0Z)

www.raycap.com

©Raycap • All rights reserved320-0799 Rev.C

Page 9 of 46

INSTALL INSTRUCTIONS RRFDC-3315-PF-48 (DB-B1-6C-12AB-0Z)

Power Pair IdentificationColor -48V RTN

x1 Blue

x2 Violet

x3 Green

x4 Brown

x5 Yellow

x6 White

Power Pair IdentificationColor -48V RTN

x1 Blue

x2 Violet

x3 Green

x4 Brown

Power Pair IdentificationColor -48V RTN

x1 Blue

x2 Violet

Hybrid cable

9.1 The approved Verizon color codes for the power cable within each hybrid cable is as follows:

6/12 Hybrid Cable

4/8 Hybrid Cable

2/4 Hybrid Cable

Page 12: (DB-B1-6C-12AB-0Z) - Talley Inc. INSTALL INSTRUCTIONS RRFDC-3315-PF-48 Installation Instructions: RRFDC-3315-PF-48 (DB-B1-6C-12AB-0Z)

www.raycap.com

©Raycap • All rights reserved320-0799 Rev.C

Page 10 of 46

RRFDC-3315-PF-48 INSTALL INSTRUCTIONS (DB-B1-6C-12AB-0Z)

Power Pair IdentificationColor -48V RTN

x1 Blue

x2 Violet

x3 Green

x4 Brown

x5 Yellow

x6 White

4

5

6

1

2

3

1

2

3

4

5

6

Installing 6/12 Hybrid Cable

10.1 Feed Hybrid trunk through Insert.

10.2 Feed enough of the cable to strip and connect to power connectors.

10.3 Connect wires according to the guide below.

Note: Bring all cables through cable glands.

Ensureallfiberisseperatedandoutof thewayduringcopperwireinstallation. Toassistineaseofwiring,proceed bywiringinthefollowingorder:

1st: OVP #1 and OVP #4 2nd: OVP #2 and OVP #5 3rd: OVP #3 and OVP #6

Torque: 40 in-lbs (10-6 AWG)

Page 13: (DB-B1-6C-12AB-0Z) - Talley Inc. INSTALL INSTRUCTIONS RRFDC-3315-PF-48 Installation Instructions: RRFDC-3315-PF-48 (DB-B1-6C-12AB-0Z)

www.raycap.com

©Raycap • All rights reserved320-0799 Rev.C

Page 11 of 46

INSTALL INSTRUCTIONS RRFDC-3315-PF-48 (DB-B1-6C-12AB-0Z)

41

2

3

41

2

3

Installing 4/8 Hybrid Cable

11.1 Feed Hybrid trunk through Insert.

11.2 Feed enough of the cable to strip and connect to power connectors.

11.3 Connect wires according to the guide below.

Note: Bring all cables through cable glands.

Ensureallfiberisseperatedandoutof thewayduringcopperwireinstallation. Toassistineaseofwiring,proceed bywiringinthefollowingorder:

1st: OVP #1 and OVP #4 2nd: OVP #2 3rd: OVP #3

Torque: 40 in-lbs (10-6 AWG)

Power Pair IdentificationColor -48V RTN

x1 Blue

x2 Violet

x3 Green

x4 Brown

Page 14: (DB-B1-6C-12AB-0Z) - Talley Inc. INSTALL INSTRUCTIONS RRFDC-3315-PF-48 Installation Instructions: RRFDC-3315-PF-48 (DB-B1-6C-12AB-0Z)

www.raycap.com

©Raycap • All rights reserved320-0799 Rev.C

Page 12 of 46

RRFDC-3315-PF-48 INSTALL INSTRUCTIONS (DB-B1-6C-12AB-0Z)

Power Pair IdentificationColor -48V RTN

x1 Blue

x2 Violet

4

5

6

1

2

3

1

2

3

4

5

6

Installing 2/4 Hybrid Cable (X3)

12.1 Feed Hybrid trunk through Insert.

12.2 Feed enough of the cable to strip and connect to power connectors.

12.3 Connect wires according to the guide below.

Note: Bring all cables through cable glands.

Ensureallfiberisseperatedandoutof thewayduringcopperwireinstallation. Toassistineaseofwiring,proceed bywiringinthefollowingorder:

1st: OVP #1 and OVP #4 2nd: OVP #2 and OVP #5 3rd: OVP #3 and OVP #6

Torque: 40 in-lbs (10-6 AWG)

Page 15: (DB-B1-6C-12AB-0Z) - Talley Inc. INSTALL INSTRUCTIONS RRFDC-3315-PF-48 Installation Instructions: RRFDC-3315-PF-48 (DB-B1-6C-12AB-0Z)

www.raycap.com

©Raycap • All rights reserved320-0799 Rev.C

Page 13 of 46

INSTALL INSTRUCTIONS RRFDC-3315-PF-48 (DB-B1-6C-12AB-0Z)

Installing Alarm for RRFDC-3315-PF-48

13.1 Alarm connections for RRFDC-3315-PF-48

BASE/TOWER-TOP UNIT

4 H2O-COM

5 PWR-NC

6 PWR-COM

6

MAIN

OU

TPUT TO

BTS

1 INTR-NC

2 INTR-COM

3 H2O-NC

2

1

ALARM IN

PUT 3

23

34

456

OU

TPUT TO

BASE OVP

1

5

1

ALARM IN

PUT 2

23456

1

ALARM IN

PUT 1

RTN 2INTR 3H20 4PWR 5

6

-48V

COM

Alar

m-O

utpu

ts

Avai

labl

e to

Sys

tem

RTN

INTR

H20

PWR

-48V

COM

RTN

INTR

H20

PWR

-48V

COM

PWR

H20

INTR

SP2

SP1

COM

Alarm Location LEDInput 1

Alarm Location LEDInput 2

Alarm Location LEDInput 3

Power Alarm LED

IntrusionAlarm LED

H2O Alarm LED

Location of Alarm:Alarm Type:

Clear = OK Red = Alarm

If alarm is indicated, then check Location LED.

If no location is indicated, then Alarm is located inside this box.

Note: Intrusion alarm will activate when lid is removed. Manually toggle the Intrusion Switch to verify function.

If using a spade connector, use #6 18-22 AWG.

IntrusionSwitch

Page 16: (DB-B1-6C-12AB-0Z) - Talley Inc. INSTALL INSTRUCTIONS RRFDC-3315-PF-48 Installation Instructions: RRFDC-3315-PF-48 (DB-B1-6C-12AB-0Z)

www.raycap.com

©Raycap • All rights reserved320-0799 Rev.C

Page 14 of 46

RRFDC-3315-PF-48 INSTALL INSTRUCTIONS (DB-B1-6C-12AB-0Z)

Installing Alarm for Rooftop (Tenant Improvement)

13.2 Refer to diagram 13.4 for Alarm wiring connections.

13.3 Rooftop (Tenant Improvement) Application Guide.

RRFDC-1064-PF-482 Circuit OVP Box

(Patent Pending)(2 units needed per site)

RRFDC-2260-RM-486 Circuit OVP Rack

(Patent Pending)(1 unit needed per site)

RRFDC-3315-PF-486 Circuit OVP Box

(Patent Pending)(1 unit needed per site)

RTF-4575Fiber Management Tray(1 unit needed per site)

OR

RTF-4501Fiber Management Tray(1 unit needed per site)

DC BBU Fiber

RRH

Page 17: (DB-B1-6C-12AB-0Z) - Talley Inc. INSTALL INSTRUCTIONS RRFDC-3315-PF-48 Installation Instructions: RRFDC-3315-PF-48 (DB-B1-6C-12AB-0Z)

www.raycap.com

©Raycap • All rights reserved320-0799 Rev.C

Page 15 of 46

INSTALL INSTRUCTIONS RRFDC-3315-PF-48 (DB-B1-6C-12AB-0Z)

13.4 Rooftop (Tenant Improvement) Wiring Diagram. These instructions are for interconnecting the alarms for the Raycap products. (Voltage monitoring circuit on seperate page) Wire the alarms using the Verizon approved color code.

Gam

ma

Beta

Alpha

PWR

COM

COM

PWR

H20

INTR

RTN

-48V

RTN

INTR

H20

COM

-48V

PWR

H20

INTR

SP2

SP1

COM

RTN

INTR

H20

PWR

2

OU

TPUT TO

BASE OVP

1

543

ALARM IN

PUT 3

RTN

INTR

H20

PWR

-48V

COM

COM

6

1

6

MAIN

OU

TPUT TO

BTS

2345

123456

ALARM IN

PUT 2

SECTOR O

UTPU

T

1

ALARM IN

PUT 1

2345

123456

65PWR

H20

INTR

RTN

-48V

4321-48V

6

SECTOR O

UTPU

T

123456

RTN

INTR

H20

PWR

-48V

COM

RTN

INTR

H20

PWR

-48V

COM

RTN

INTR

H20

PWR

-48V

COM

RACK UNIT ALARM BOARD

1

ALARM IN

PUT 3

23456

1

ALARM IN

PUT 2

23456

1

ALARM IN

PUT 1

23456

REMO

TE VOLTAG

E INPU

TS 1-3REM

OTE VO

LTAGE IN

PUTS 4-6

4H2O

-COM

5PW

R-NC

6PW

R-COM

6

MAIN OUTPUT TO BTS

1IN

TR-NC

2IN

TR-COM

3H2O

-NC

234

OUTPUT TO BASE OVP

15PW

R

H20

INTR

SP2

SP1

COM

Alarm-Outputs Available to System

Pair Color Alarm Input

1

Black -48V

Black/White RTN

2

Orange INTR

Black H2O

3

Violet PWR

Black COM

Page 18: (DB-B1-6C-12AB-0Z) - Talley Inc. INSTALL INSTRUCTIONS RRFDC-3315-PF-48 Installation Instructions: RRFDC-3315-PF-48 (DB-B1-6C-12AB-0Z)

www.raycap.com

©Raycap • All rights reserved320-0799 Rev.C

Page 16 of 46

RRFDC-3315-PF-48 INSTALL INSTRUCTIONS (DB-B1-6C-12AB-0Z)

Remote Volt Meter Wiring (when employing rack unit)

13.5 The Remote Voltage Monitor signal wires connect to the tower-top domes at the radio jumper connection and allow the voltages at the tower-top to be measured with the voltmeter provided in the rack suppression unit.

There are two six contact terminal blocks provided on the rack to connect the wires from the tower top (refer to 13.6).

Connect the Voltage signal wires to the terminal blocks by stripping the wires back 3/8" and connect the Return and -48V for each radio in the correct input terminal using a standard 1/4" or a #1 Phillips screwdriver. When power is applied, the voltmeter should display the voltage between each -48V and Return pair. If the circuit is connected backwards, the voltmeter will display “PL” for “PoLarity”.

The approved Verizon color code within each hybrid cable is as follows:

6/12 Cable - 6 Voltage monitor pairs

4/8 Cable- 4 Voltage monitor pairs

2/4 Cable- 2 Voltage monitor pairs

Pair Color Alarm Input

1

Yellow RTN (1)

Black -48V (1)

2

Red RTN (2)

Black -48V (2)

3

Slate RTN (3)

Black -48V (3)

4

Blue RTN (4)

Black -48V (4)

5

Brown RTN (5)

Black -48V (5)

6

White RTN (6)

White/Black -48V (6)

Pair Color Alarm Input

1

Yellow RTN (1)

Black -48V (1)

2

Red RTN (2)

Black -48V (2)

3

Slate RTN (3)

Black -48V (3)

4

Blue RTN (4)

Black -48V (4)

Pair Color Alarm Input

1

Yellow RTN (1)

Black -48V (1)

2

Red RTN (2)

Black -48V (2)

Page 19: (DB-B1-6C-12AB-0Z) - Talley Inc. INSTALL INSTRUCTIONS RRFDC-3315-PF-48 Installation Instructions: RRFDC-3315-PF-48 (DB-B1-6C-12AB-0Z)

www.raycap.com

©Raycap • All rights reserved320-0799 Rev.C

Page 17 of 46

INSTALL INSTRUCTIONS RRFDC-3315-PF-48 (DB-B1-6C-12AB-0Z)

Volt Meter Wiring Diagram (Rooftop Distribution)

13.6 Refer to diagram below for wiring the Volt Meter System.

Note: The diagram shows the color code for the 2/4 hybrid cable used between the sector units and the distribution unit and the 6/12 hybrid cable used between the distribution unit and the rack mount unit.

2/4 Cable - 2 Voltage monitor pairs 6/12 Cable - 6 Voltage monitor pairs

SECTOR UNIT 1

RTN

(1)

-48V

(1)

RTN

(2)

-48V

(2)

SECTOR UNIT 2

RTN

(1)

-48V

(1)

RTN

(2)

-48V

(2)

PCB TERMINAL BLOCK DISTRIBUTION UNIT1 2 3

PCB TERMINAL BLOCK4 5 6

-48V (4)RTN (4)-48V (5)RTN (5)-48V (6)RTN (6)

PASS-THRU

CIRCUITS 4-6

-48V (3)RTN (3)-48V (2)RTN (2)-48V (1)RTN (1)

PASS-THRU

CIRCUITS 1-3

RTN

(1)

-48V

(1)

RTN

(2)

-48V

(2)

RTN

(3)

-48V

(3)

MAIN

OU

TPUT TO

BTSO

UTPU

T TO BASE O

VP

ALARM OUTPUT 1 ALARM OUTPUT 2

RACK MOUNT UNIT ALARM BOARD

ALARM OUTPUT 3REMOTE VOLTAGE MONITOR INPUTS

1 2 3

RTN

(4)

-48V

(4)

RTN

(5)

-48V

(5)

RTN

(6)

-48V

(6)

4 5 6

Pair Color Alarm Input

1

Yellow RTN (1)

Black -48V (1)

2

Red RTN (2)

Black -48V (2)

3

Slate RTN (3)

Black -48V (3)

4

Blue RTN (4)

Black -48V (4)

5

Brown RTN (5)

Black -48V (5)

6

White RTN (6)

White/Black -48V (6)

Pair Color Alarm Input

1

Yellow RTN (1)

Black -48V (1)

2

Red RTN (2)

Black -48V (2)

Page 20: (DB-B1-6C-12AB-0Z) - Talley Inc. INSTALL INSTRUCTIONS RRFDC-3315-PF-48 Installation Instructions: RRFDC-3315-PF-48 (DB-B1-6C-12AB-0Z)

www.raycap.com

©Raycap • All rights reserved320-0799 Rev.C

Page 18 of 46

RRFDC-3315-PF-48 INSTALL INSTRUCTIONS (DB-B1-6C-12AB-0Z)

Installing Alarm for Rooftop (Tenant Improvement)-Alternateconfigurationforhighradiocount

13.7 Refer to diagram 13.15 for Alarm wiring connections.

13.8 Rooftop (Tenant Improvement) Application Guide.

DC BBU Fiber

RRH

RRFDC-2260-RM-486 Circuit OVP Rack

(Patent Pending)(3 units needed per site)

RTF-4575Fiber Management Tray(3 units needed per site)

OR

RTF-4501Fiber Management Tray(3 units needed per site)

RRFDC-3315-PF-486 Circuit OVP Box

(Patent Pending)(3 units needed per site)

Page 21: (DB-B1-6C-12AB-0Z) - Talley Inc. INSTALL INSTRUCTIONS RRFDC-3315-PF-48 Installation Instructions: RRFDC-3315-PF-48 (DB-B1-6C-12AB-0Z)

www.raycap.com

©Raycap • All rights reserved320-0799 Rev.C

Page 19 of 46

INSTALL INSTRUCTIONS RRFDC-3315-PF-48 (DB-B1-6C-12AB-0Z)

Installing Alarm for Rooftop (Penthouse) -Alternateconfigurationforhighradiocount

13.9 Refer to diagram 13.15 for Alarm wiring connections.

13.10 Rooftop (Penthouse) Application Guide.

RRH

RRFDC-2260-RM-486 Circuit OVP Rack

(Patent Pending)(3 units needed per site)

RTF-4575Fiber Management Tray(3 units needed per site)

OR

RTF-4501Fiber Management Tray(3 units needed per site)

RRFDC-3315-PF-486 Circuit OVP Box

(Patent Pending)(3 units needed per site)

DC BBU Fiber

Page 22: (DB-B1-6C-12AB-0Z) - Talley Inc. INSTALL INSTRUCTIONS RRFDC-3315-PF-48 Installation Instructions: RRFDC-3315-PF-48 (DB-B1-6C-12AB-0Z)

www.raycap.com

©Raycap • All rights reserved320-0799 Rev.C

Page 20 of 46

RRFDC-3315-PF-48 INSTALL INSTRUCTIONS (DB-B1-6C-12AB-0Z)

Installing Alarm for Tower Top

13.11 Refer to diagram 13.15 for Alarm wiring connections.

13.12 Tower Top Application Guide.

RRH

RRFDC-2260-RM-486 Circuit OVP Rack

(Patent Pending)(1 unit needed per site)

RTF-4575Fiber Management Tray(1 unit needed per site)

OR

RTF-4501Fiber Management Tray(1 unit needed per site)

RRFDC-3315-PF-486 Circuit OVP Box

(Patent Pending)(1 unit needed per site)

DC BBU Fiber

Page 23: (DB-B1-6C-12AB-0Z) - Talley Inc. INSTALL INSTRUCTIONS RRFDC-3315-PF-48 Installation Instructions: RRFDC-3315-PF-48 (DB-B1-6C-12AB-0Z)

www.raycap.com

©Raycap • All rights reserved320-0799 Rev.C

Page 21 of 46

INSTALL INSTRUCTIONS RRFDC-3315-PF-48 (DB-B1-6C-12AB-0Z)

Installing Alarm for Tower Top

13.13 Refer to diagram 13.15 for Alarm wiring connections.

13.14 Tower Top Application Guide.

RRH

RRFDC-2260-RM-486 Circuit OVP Rack

(Patent Pending)(2 units needed per site)

RTF-4575Fiber Management Tray(2 units needed per site)

OR

RTF-4501Fiber Management Tray(2 units needed per site)

RRFDC-3315-PF-486 Circuit OVP Box

(Patent Pending)(2 units needed per site)

DC BBU Fiber

Page 24: (DB-B1-6C-12AB-0Z) - Talley Inc. INSTALL INSTRUCTIONS RRFDC-3315-PF-48 Installation Instructions: RRFDC-3315-PF-48 (DB-B1-6C-12AB-0Z)

www.raycap.com

©Raycap • All rights reserved320-0799 Rev.C

Page 22 of 46

RRFDC-3315-PF-48 INSTALL INSTRUCTIONS (DB-B1-6C-12AB-0Z)

Pair Color Alarm Input

1

Black -48V

Black/White RTN

2

Orange INTR

Black H2O

3

Violet PWR

Black COM

COM

-48V

PWR

H20

INTR

SP2

SP1

COM

RTN

INTR

H20

PWR

2

OU

TPUT TO

BASE OVP

1

543

ALARM IN

PUT 3

RTN

INTR

H20

PWR

-48V

COM

COM

6

1

6

MAIN

OU

TPUT TO

BTS

2345

123456

ALARM IN

PUT 2

ALARM IN

PUT 1

123456

65PWR

H20

INTR

RTN

-48V

4321

RTN

INTR

H20

PWR

-48V

COM

RTN

INTR

H20

PWR

-48V

COM

RTN

INTR

H20

PWR

-48V

COM

RACK UNIT ALARM BOARD

1

ALARM IN

PUT 3

23456

1

ALARM IN

PUT 2

23456

1

ALARM IN

PUT 1

23456

REMO

TE VOLTAG

E INPU

TS 1-3REM

OTE VO

LTAGE IN

PUTS 4-6

4H2O

-COM

5PW

R-NC

6PW

R-COM

6

MAIN OUTPUT TO BTS

1IN

TR-NC

2IN

TR-COM

3H2O

-NC

234

OUTPUT TO BASE OVP

15PW

R

H20

INTR

SP2

SP1

COM

Alarm-Outputs Available to System

RTN (1)

-48V (1)

RTN (2)

-48V (2)

RTN (3)

-48V (3)

RTN (4)

-48V (4)

RTN (5)

-48V (5)

RTN (6)

-48V (6)

123456

123456

TOWER TOPOVP UNIT

13.15 Tower Top Wiring Diagram. These instructions are for interconnecting the alarms for the Raycap products. (Voltage monitoring circuit on separate page) Wire the alarms using the Verizon approved color code.

Page 25: (DB-B1-6C-12AB-0Z) - Talley Inc. INSTALL INSTRUCTIONS RRFDC-3315-PF-48 Installation Instructions: RRFDC-3315-PF-48 (DB-B1-6C-12AB-0Z)

www.raycap.com

©Raycap • All rights reserved320-0799 Rev.C

Page 23 of 46

INSTALL INSTRUCTIONS RRFDC-3315-PF-48 (DB-B1-6C-12AB-0Z)

Volt Meter Wiring Diagram (when employing rack unit) (Towertop)

13.16 Refer to diagram for wiring the Volt Meter System.

Note: The diagram shows the color code for the 6/12 hybrid cable used between the tower top unit and the rack mount unit.

6/12 Cable - 6 Voltage monitor Pairs

PCB TERMINAL BLOCK DISTRIBUTION UNIT1 2 3

PCB TERMINAL BLOCK4 5 6

PASS-THRU

CIRCUITS 4-6

RTN

(1)

-48V

(1)

RTN

(2)

-48V

(2)

RTN

(3)

-48V

(3)

RTN

(4)

-48V

(4)

RTN

(5)

-48V

(5)

RTN

(6)

-48V

(6)

PASS-THRU

CIRCUITS 1-3

RTN

(1)

-48V

(1)

RTN

(2)

-48V

(2)

RTN

(3)

-48V

(3)

MAIN

OU

TPUT TO

BTSO

UTPU

T TO BASE O

VP

ALARM OUTPUT 1 ALARM OUTPUT 2

RACK MOUNT UNIT ALARM BOARD

ALARM OUTPUT 3REMOTE VOLTAGE MONITOR INPUTS

1 2 3

RTN

(4)

-48V

(4)

RTN

(5)

-48V

(5)

RTN

(6)

-48V

(6)

4 5 6

Pair Color Alarm Input

1

Yellow RTN (1)

Black -48V (1)

2

Red RTN (2)

Black -48V (2)

3

Slate RTN (3)

Black -48V (3)

4

Blue RTN (4)

Black -48V (4)

5

Brown RTN (5)

Black -48V (5)

6

White RTN (6)

White/Black -48V (6)

Page 26: (DB-B1-6C-12AB-0Z) - Talley Inc. INSTALL INSTRUCTIONS RRFDC-3315-PF-48 Installation Instructions: RRFDC-3315-PF-48 (DB-B1-6C-12AB-0Z)

www.raycap.com

©Raycap • All rights reserved320-0799 Rev.C

Page 24 of 46

RRFDC-3315-PF-48 INSTALL INSTRUCTIONS (DB-B1-6C-12AB-0Z)

The RTFI (Real Time Fault Indicator) PCB Notice:All wiring must be connected per the installation instructions for this unit. Failure to follow the wiring instructions may cause an alarm.

The RTFI PCB is located above the alarm board, and provides a Visual Indication and added protections to the unit for alarm mis-wiring events.

Instructions:

14.1 Confirm all alarm wiring is correct according to the installation instructions.

14.2 With the lid removed from the unit, apply power.

14.3 Inspect the RTFI PCB and Alarm PCB for an illuminated Red LED indicating an incorrect wiring of the alarm signals.

Note: Intrusion alarm will activate when the lid is removed from the unit. Manually toggle the intrusion switch located at the top of the unit to verify functionality and ensure that all alarms are cleared.

14.4 Inspect Main OVP Board to ensure the Green LEDs are on for all powered circuits.

14.5 Last, the alarm output can be verified by checking continuity on the terminal strip labeled “Main Output to BTS”. When the unit is powered, continuity exists between the NC and COM contacts for Power, H2O, and Intrusion. If any of these alarm contacts have an open circuit, then the unit is in alarm.

14.6 If the RTFI board Red LED or the Alarm board Red LEDs are on, then the unit is in alarm. Power should be removed from the system and the alarm wiring checked again for proper connections per the installation instruction.

14.7 If the alarms cannot be cleared after confirming the wiring with the installation instruction, please contact a Raycap Account Representative at (208) 777-1166, (800) 890-2569 or www.raycap.com

Page 27: (DB-B1-6C-12AB-0Z) - Talley Inc. INSTALL INSTRUCTIONS RRFDC-3315-PF-48 Installation Instructions: RRFDC-3315-PF-48 (DB-B1-6C-12AB-0Z)

www.raycap.com

©Raycap • All rights reserved320-0799 Rev.C

Page 25 of 46

INSTALL INSTRUCTIONS RRFDC-3315-PF-48 (DB-B1-6C-12AB-0Z)

Installing Hybrid Cable-Fiber (In)

15.1 Loosely route fiber cables around the cable guides.

Note: Secure fiber cables using either the supplied fiber clips or Velcro. (Velcro not pictured)

15.2 Remove the plugs in the fiber connectors to be used – To avoid contamination, do not remove any plugs until fiber is immediately ready to be installed.

Example: pull one plug, plug in fiber, repeat.

15.3 Connect the cables into the fiber connection panel starting with the row closest to the back plate, and feed through the cable guides.

15.4 Connect fiber according to the Verizon Wireless established guide.

Plugs

Cable Guides

Fiber Clips

Page 28: (DB-B1-6C-12AB-0Z) - Talley Inc. INSTALL INSTRUCTIONS RRFDC-3315-PF-48 Installation Instructions: RRFDC-3315-PF-48 (DB-B1-6C-12AB-0Z)

www.raycap.com

©Raycap • All rights reserved320-0799 Rev.C

Page 26 of 46

RRFDC-3315-PF-48 INSTALL INSTRUCTIONS (DB-B1-6C-12AB-0Z)

Installing Hybrid Cable-Fiber (Out)

16.1 Feed cables through gland assembly.

Note: Secure fiber cables using either the supplied fiber clips or Velcro. (Velcro not pictured)

16.2 Remove plugs in fiber connectors that will be used – To avoid contamination, do not remove any plugs until fiber is immediately ready to be installed. Example: pull one plug, plug in fiber, then do the next one, repeat.

Note:Alwayskeepun-used connectorsplugged.

16.3 Connect the cables into the fiber connection bar starting with the row closest to the back plate, and feed through the cable guides as shown.

16.4 Connect fiber according to the Verizon Wireless established guide.

Fiber Clips

Page 29: (DB-B1-6C-12AB-0Z) - Talley Inc. INSTALL INSTRUCTIONS RRFDC-3315-PF-48 Installation Instructions: RRFDC-3315-PF-48 (DB-B1-6C-12AB-0Z)

www.raycap.com

©Raycap • All rights reserved320-0799 Rev.C

Page 27 of 46

INSTALL INSTRUCTIONS RRFDC-3315-PF-48 (DB-B1-6C-12AB-0Z)

Voltage Monitor Operation

17.1 Once cabling is complete and power is supplied to the unit, the voltage can be verified for each DC circuit.

17.2 To monitor each individual circuit, turn the selector knob to corresponding circuit indicated next to the dial.

Note: The voltage monitor function includes an automatic sleep mode that “turns-off” the LED digits after two minutes.

To “turn-on” the digits to the LED display, turn the selector knob to any powered DC circuit.

When complete, place the voltage monitor dial back to the DC circuit 1 position.

Page 30: (DB-B1-6C-12AB-0Z) - Talley Inc. INSTALL INSTRUCTIONS RRFDC-3315-PF-48 Installation Instructions: RRFDC-3315-PF-48 (DB-B1-6C-12AB-0Z)

www.raycap.com

©Raycap • All rights reserved320-0799 Rev.C

Page 28 of 46

RRFDC-3315-PF-48 INSTALL INSTRUCTIONS (DB-B1-6C-12AB-0Z)

Removing a Strikesorb Module

18.1 Release Velcro strap from Strikesorb Module.

18.2 Grab the Strikesorb module by ends and depress lever on both sides.

18.3 Rock the Strikesorb module side to side, and pull it out.

Note:Youhavetoovercomeastrong springcontacttoremovemodule.

Page 31: (DB-B1-6C-12AB-0Z) - Talley Inc. INSTALL INSTRUCTIONS RRFDC-3315-PF-48 Installation Instructions: RRFDC-3315-PF-48 (DB-B1-6C-12AB-0Z)

www.raycap.com

©Raycap • All rights reserved320-0799 Rev.C

Page 29 of 46

INSTALL INSTRUCTIONS RRFDC-3315-PF-48 (DB-B1-6C-12AB-0Z)

Optional90˚ElbowInstallation

19.1 Place included gasket onto elbow as shown.

19.2 Note: 90˚Elbow can be installed on left or right side of unit.

Remove the gland which is being replaced from unit by loosening gland nut. Set both nut and gland aside.

19.3 Place elbow into position through gland hole, lining up the 2 mounting holes to the units metal frame. Secure elbow to unit with gland nut.

Torque: 66 in-lbs

Page 32: (DB-B1-6C-12AB-0Z) - Talley Inc. INSTALL INSTRUCTIONS RRFDC-3315-PF-48 Installation Instructions: RRFDC-3315-PF-48 (DB-B1-6C-12AB-0Z)

www.raycap.com

©Raycap • All rights reserved320-0799 Rev.C

Page 30 of 46

RRFDC-3315-PF-48 INSTALL INSTRUCTIONS (DB-B1-6C-12AB-0Z)

19.4 Secure elbow to frame with the 2 supplied mounting screws.

19.5 Secure gland to elbow.

Torque: 66 in-lbs

19.6 90˚Elbow installation complete.

Page 33: (DB-B1-6C-12AB-0Z) - Talley Inc. INSTALL INSTRUCTIONS RRFDC-3315-PF-48 Installation Instructions: RRFDC-3315-PF-48 (DB-B1-6C-12AB-0Z)

www.raycap.com

©Raycap • All rights reserved320-0799 Rev.C

Page 31 of 46

INSTALL INSTRUCTIONS RRFDC-3315-PF-48 (DB-B1-6C-12AB-0Z)

Installation Complete. Closing and Securing Unit.

20.1 Slide enclosure lid into place.

20.2 As pictured, Lid IS NOT properly aligned. Red must be completely covered for proper lid alignment.

20.3 As pictured, Lid IS properly aligned.

Page 34: (DB-B1-6C-12AB-0Z) - Talley Inc. INSTALL INSTRUCTIONS RRFDC-3315-PF-48 Installation Instructions: RRFDC-3315-PF-48 (DB-B1-6C-12AB-0Z)

www.raycap.com

©Raycap • All rights reserved320-0799 Rev.C

Page 32 of 46

RRFDC-3315-PF-48 INSTALL INSTRUCTIONS (DB-B1-6C-12AB-0Z)

20.4 If installation requires padlocks, (not provided) secure “bottom right” of enclosure.

Note: If padlock holes are NOT aligned, the lid is NOT properly aligned.

20.5 When alignment of lid is comfirmed, close and secure all clamps.

Installation complete.

Page 35: (DB-B1-6C-12AB-0Z) - Talley Inc. INSTALL INSTRUCTIONS RRFDC-3315-PF-48 Installation Instructions: RRFDC-3315-PF-48 (DB-B1-6C-12AB-0Z)

www.raycap.com

©Raycap • All rights reserved320-0799 Rev.C

Page 33 of 46

INSTALL INSTRUCTIONS RRFDC-3315-PF-48 (DB-B1-6C-12AB-0Z)

AppendixInstructions for using legacy cables prior to Verizon standardized cable color code.

Installing 6/12 Hybrid Feeder Cable

21.1 For more access to the printed circuit boards, the Fiber Panel can be temporarily removed. See illustrations below.

21.2 Attach lanyard to Mounting Bracket.

21.3 Feed Hybrid trunk through Insert.

21.4 Feed enough of the cable to strip and connect to power connectors.

21.5 Connect wires according to the Verizon Wireless established color guide.

Note: Bring all cables through cable glands.

Ensureallfiberisseperatedandoutof thewayduringcopperwireinstallation. Toassistineaseofwiring,proceed bywiringinthefollowingorder:

1st: OVP #1 and OVP #4 2nd: OVP #2 and OVP #5 3rd: OVP #3 and OVP #6

Torque: 40 in-lbs (10-6 AWG)

CircuitNumber

Color

-48V Return

1 Yellow/Black Stripe Black

2 Red/Black Stripe Blue

3 Brown/Red Stripe Red

4 Purple/Red Stripe Yellow

5 Black/White Stripe Orange

6 Grey/Red Stripe Purple

Page 36: (DB-B1-6C-12AB-0Z) - Talley Inc. INSTALL INSTRUCTIONS RRFDC-3315-PF-48 Installation Instructions: RRFDC-3315-PF-48 (DB-B1-6C-12AB-0Z)

www.raycap.com

©Raycap • All rights reserved320-0799 Rev.C

Page 34 of 46

RRFDC-3315-PF-48 INSTALL INSTRUCTIONS (DB-B1-6C-12AB-0Z)

Installing Hybrid Cable-Power (Out) to Sectors

23.1 Feed Hybrid jumpers through insert.

23.2 Feed enough of the cable to strip and connect to power connectors.

23.3 Connect wires according to the Verizon Wireless established color guide.

Note: Toassistineaseofwiring,proceed bywiringinthefollowingorder:

1st: OVP #1 and OVP #4 2nd: OVP #2 and OVP #5 3rd: OVP #3 and OVP #6

Torque: 40 in-lbs (10-6 AWG)

Installing Hybrid Cable-Power (Out) to Distribution Unit

22.1 Feed Hybrid jumpers through insert.

22.2 Feed enough of the cable to strip and connect to power connectors.

22.3 Connect wires according to the Verizon Wireless established color guide.

Note: Toassistineaseofwiring,proceed bywiringinthefollowingorder:

1st: OVP #1 and OVP #4 2nd: OVP #2 and OVP #5 3rd: OVP #3 and OVP #6

Torque: 40 in-lbs (10-6 AWG)

Sector CircuitNumber

Color

-48V Return

Alpha1 Yellow/Black Stripe Black

2 Red/Black Stripe Blue

Beta3 Yellow/Black Stripe Black

4 Red/Black Stripe Blue

Gam-ma

5 Yellow/Black Stripe Black

6 Red/Black Stripe Blue

CircuitNumber

Color

-48V Return

1 Yellow/Black Stripe Black

2 Red/Black Stripe Blue

3 Brown/Red Stripe Red

4 Purple/Red Stripe Yellow

5 Black/White Stripe Orange

6 Grey/Red Stripe Purple

Page 37: (DB-B1-6C-12AB-0Z) - Talley Inc. INSTALL INSTRUCTIONS RRFDC-3315-PF-48 Installation Instructions: RRFDC-3315-PF-48 (DB-B1-6C-12AB-0Z)

www.raycap.com

©Raycap • All rights reserved320-0799 Rev.C

Page 35 of 46

INSTALL INSTRUCTIONS RRFDC-3315-PF-48 (DB-B1-6C-12AB-0Z)

Installing Ground Cable

25.1 There are two grounding placement options available. See below.

Optional Cable Grounds

Main Ground

Installing Hybrid Jumper (Out) to RRHs

24.1 Feed Hybrid jumpers through insert.

24.2 Feed enough of the cable to strip and connect to power connectors.

24.3 Connect wires according to the Verizon Wireless established color guide.

Note: Toassistineaseofwiring,proceed bywiringinthefollowingorder:

1st: OVP #1 and OVP #4 2nd: OVP #2 and OVP #5 3rd: OVP #3 and OVP #6

Torque: 40 in-lbs (10-6 AWG)

Sector CircuitNumber

Color

-48V Return

Alpha1 Red Black

2 Red Black

Beta3 Red Black

4 Red Black

Gamma5 Red Black

6 Red Black

Page 38: (DB-B1-6C-12AB-0Z) - Talley Inc. INSTALL INSTRUCTIONS RRFDC-3315-PF-48 Installation Instructions: RRFDC-3315-PF-48 (DB-B1-6C-12AB-0Z)

www.raycap.com

©Raycap • All rights reserved320-0799 Rev.C

Page 36 of 46

RRFDC-3315-PF-48 INSTALL INSTRUCTIONS (DB-B1-6C-12AB-0Z)

Alarm OutputThree pairs of Alarm Cable are provided in the 6/12 Hybrid Feeder and 2/4 Hybrid Branch Cables. Circuits to bedesignated per the table below:

Note: N/O or N/C contact should be used per Verizon Wireless Standards.

Installing Alarm for RRFDC-3315-PF-48

26.1 Alarm connections for RRFDC-3315-PF-48

BASE/TOWER-TOP UNIT

4 H2O-COM

5 PWR-NC

6 PWR-COM

6

MAIN

OU

TPUT TO

BTS

1 INTR-NC

2 INTR-COM

3 H2O-NC

2

1

ALARM IN

PUT 3

23

34

456

OU

TPUT TO

BASE OVP

1

5

1

ALARM IN

PUT 2

23456

1

ALARM IN

PUT 1

RTN 2INTR 3H20 4PWR 5

6

-48V

COM

Alar

m-O

utpu

ts

Avai

labl

e to

Sys

tem

RTN

INTR

H20

PWR

-48V

COM

RTN

INTR

H20

PWR

-48V

COM

PWR

H20

INTR

SP2

SP1

COM

Alarm Location LEDInput 1

Alarm Location LEDInput 2

Alarm Location LEDInput 3

Power Alarm LED

IntrusionAlarm LED

H2O Alarm LED

Location of Alarm:Alarm Type:

Clear = OK Red = Alarm

If alarm is indicated, then check Location LED.

If no location is indicated, then Alarm is located inside this box.

Note: Intrusion alarm will activate when lid is removed. Manually toggle the Intrusion Switch to verify function.

IntrusionSwitch

AlarmColor

N/C N/O COM

Power Black Red

H2O Blue Orange

Intrusion Brown Yellow

Page 39: (DB-B1-6C-12AB-0Z) - Talley Inc. INSTALL INSTRUCTIONS RRFDC-3315-PF-48 Installation Instructions: RRFDC-3315-PF-48 (DB-B1-6C-12AB-0Z)

www.raycap.com

©Raycap • All rights reserved320-0799 Rev.C

Page 37 of 46

INSTALL INSTRUCTIONS RRFDC-3315-PF-48 (DB-B1-6C-12AB-0Z)

26.2 Rooftop (Tenant Improvement) Wiring Diagram. These instructions are for interconnecting the alarms for the current Raycap products.

Input Color

1 Black

2 Red

3 Blue

4 Orange

5 Brown

6 Yellow

BASE UNIT

Gam

ma

Beta

Alph

a

ROOF-TOP DISTRIBUTION UNIT

4 H2O-COM

5 PWR-NC

6 PWR-COM

6

MAIN

OU

TPUT TO

BTS

1 INTR-NC

2 INTR-COM

3 H2O-NC

2

1

ALARM IN

PUT 3

23

34

456

OU

TPUT TO

BASE OVP

1

5

1

ALARM IN

PUT 2

23456

1

ALARM IN

PUT 1

RTN 2INTR 3H20 4PWR 5

6

-48V

COM

PWR

COM

-48V

RTN

INTR

H20

COM

PWR

H20

INTR

RTN

-48V

RTN

INTR

H20

COM

-48V

PWR

H20

INTR

SP2

SP1

COM

RTN

INTR

H20

PWR

2

OU

TPUT TO

BASE OVP

1

543

ALARM IN

PUT 3

RTN

INTR

H20

PWR

-48V

COM

COM

6

1

6

MAIN

OU

TPUT TO

BTS

2345

SECTOR O

UTPU

T

123456

123456

PWR

COM

ALARM IN

PUT 2

SECTOR O

UTPU

T

1ALARM

INPU

T 12345

123456

65PWR

H20

INTR

RTN

-48V

4321-48V

6

SECTOR O

UTPU

T

123456

Alar

m-O

utpu

ts

Avai

labl

e to

Sys

tem

Instructions for connecting this unit to the following legacy units are found in the appendix:

RRFDC-4750-PF-48

Page 40: (DB-B1-6C-12AB-0Z) - Talley Inc. INSTALL INSTRUCTIONS RRFDC-3315-PF-48 Installation Instructions: RRFDC-3315-PF-48 (DB-B1-6C-12AB-0Z)

www.raycap.com

©Raycap • All rights reserved320-0799 Rev.C

Page 38 of 46

RRFDC-3315-PF-48 INSTALL INSTRUCTIONS (DB-B1-6C-12AB-0Z)

26.3 Rooftop (Penthouse) Wiring Diagram. These instructions are for interconnecting the alarms for the current Raycap products.

BASE UNIT

5 PWR-NC

6 PWR-COM

3 H2O-NC

4 H2O-COM

MAIN

OU

TPUT TO

BTS

1 INTR-NC

2 INTR-COM

56

34

OU

TPUT TO

BASE OVP

12

Gam

ma

SECTOR O

UTPU

T1 -48V -48V 1

3 INTR INTR 3

6 COM COM 65 PWR PWR 54 H20 H20 4

PWR 54 H20 H20 4

ALARM IN

PUT 3

2 RTN RTN 2

H20 H20 4ALARM

INPU

T 2

2 RTN RTN 2

Beta

SECTOR O

UTPU

T

1 -48V -48V 1

3 INTR INTR 3

6 COM COM 65 PWR

ALARM IN

PUT 1

2 RTN RTN 2

Alph

a

SECTOR O

UTPU

T

1 -48V -48V 1

3 INTR INTR 3

6 COM COM 65 PWR PWR 54

Alar

m-O

utpu

ts

Avai

labl

e to

Sys

tem

Input Color

1 Black

2 Red

3 Blue

4 Orange

5 Brown

6 Yellow

Instructions for connecting this unit to the following legacy units are found in the appendix:

RRFDC-1064-PF-48

Page 41: (DB-B1-6C-12AB-0Z) - Talley Inc. INSTALL INSTRUCTIONS RRFDC-3315-PF-48 Installation Instructions: RRFDC-3315-PF-48 (DB-B1-6C-12AB-0Z)

www.raycap.com

©Raycap • All rights reserved320-0799 Rev.C

Page 39 of 46

INSTALL INSTRUCTIONS RRFDC-3315-PF-48 (DB-B1-6C-12AB-0Z)

26.4 Tower Top Wiring Diagram. These instructions are for interconnecting the alarms for the current Raycap products.

TOWER-TOP UNIT BASE UNIT

5 5 PWR-NC

6 6 PWR-COM

3 3 H2O-NC

4 4 H2O-COM

MAIN

OU

TPUT TO

BTS

1 MAIN

OU

TPUT TO

BTS

1 INTR-NC

2 2 INTR-COM

3 INTR 34 H20 4

2 SP2 2

5 PWR 5

4 4

ALARM IN

PUT 3

1

OU

TPUT TO

BASE OVP

1 SP1

OU

TPUT TO

BASE OVP

1

6 COM 6

4

ALARM IN

PUT 2

1

ALARM IN

PUT 3

2 21

3

6 65 5

3

-48V 1

ALARM IN

PUT 2

2 21

3

6 65 5

34

ALARM IN

PUT 1

2 RTN 21

3

6 COM 65 PWR 5

INTR 34 H20 4

ALARM IN

PUT 1

Alar

m-O

utpu

ts

Avai

labl

e to

Sys

tem

Gam

ma

Beta

Alph

a

Input Color

1 Black

2 Red

3 Blue

4 Orange

5 Brown

6 Yellow

Instructions for connecting this unit to the following legacy units are found in the appendix:

RRFDC-3315-PF-48

Page 42: (DB-B1-6C-12AB-0Z) - Talley Inc. INSTALL INSTRUCTIONS RRFDC-3315-PF-48 Installation Instructions: RRFDC-3315-PF-48 (DB-B1-6C-12AB-0Z)

www.raycap.com

©Raycap • All rights reserved320-0799 Rev.C

Page 40 of 46

RRFDC-3315-PF-48 INSTALL INSTRUCTIONS (DB-B1-6C-12AB-0Z)

Alarm board on Legacy products

26.5 Alarm board on Legacy units:

RxxDC-3315-PF-48 RxxDC-4750-PF-48

25.6 Alarm board on Legacy unit:

RxxDC-1064-PF-48

Sector-A-Input

Alarm-Output

Alarm-Outputs Available to SystemCommon, Normally Closed and Normally Open

for PWR, H2O and Intrusion

1 2 3 4 5 6 7 8 91 2 3 4 5 6

Sector-B-Input

1 2 3 4 5 6

Sector-C-Input

1 2 3 4 5 6

PW

R–C

OM

PW

R–N

/CP

WR

–N/O

H2O

–CO

MH

2O–N

/CH

2O–N

/OIN

TR

–CO

MIN

TR

–N/C

INT

R–N

/O

SE

CTO

R–A

–CO

MS

EC

TOR

–A–P

WR

–NO

SE

CTO

R–A

–H2O

–NO

SE

CTO

R–A

–IN

TR

–NO

SE

CTO

R–B

–CO

MS

EC

TOR

–B–P

WR

–NO

SE

CTO

R–B

–H2O

–NO

SE

CTO

R–B

–IN

TR

–NO

SE

CTO

R–C

–CO

MS

EC

TOR

–C–P

WR

–NO

SE

CTO

R–C

–H2O

–NO

SE

CTO

R–C

–IN

TR

–NO

Sector-Output

1 2 3 4 5 6 7 8 9

CO

MP

WR

–N/C

PW

R–N

/OH

20–N

/CH

20–N

/OIN

TR

–N/C

INT

R–N

/OP

WR

GN

D

Alarm-Outputs Available to SystemCommon, Normally Closed and Normally Open

for PWR, H2O and Intrusion

Power Alarm LED

IntrusionAlarm LED

H2O Alarm LED

Sector-A-Input

Alarm-Output

Alarm-Outputs Available to SystemCommon, Normally Closed and Normally Open

for PWR, H2O and Intrusion

1 2 3 4 5 6 7 8 91 2 3 4 5 6

Sector-B-Input

1 2 3 4 5 6

Sector-C-Input

1 2 3 4 5 6

PW

R–C

OM

PW

R–N

/CP

WR

–N/O

H2O

–CO

MH

2O–N

/CH

2O–N

/OIN

TR

–CO

MIN

TR

–N/C

INT

R–N

/O

SE

CTO

R–A

–CO

MS

EC

TOR

–A–P

WR

–NO

SE

CTO

R–A

–H2O

–NO

SE

CTO

R–A

–IN

TR

–NO

SE

CTO

R–B

–CO

MS

EC

TOR

–B–P

WR

–NO

SE

CTO

R–B

–H2O

–NO

SE

CTO

R–B

–IN

TR

–NO

SE

CTO

R–C

–CO

MS

EC

TOR

–C–P

WR

–NO

SE

CTO

R–C

–H2O

–NO

SE

CTO

R–C

–IN

TR

–NO

Sector-Output

1 2 3 4 5 6 7 8 9

CO

MP

WR

–N/C

PW

R–N

/OH

20–N

/CH

20–N

/OIN

TR

–N/C

INT

R–N

/OP

WR

GN

D

Alarm-Outputs Available to SystemCommon, Normally Closed and Normally Open

for PWR, H2O and Intrusion

Power Alarm LED

IntrusionAlarm LED

H2O Alarm LED

Alarm Type:

Location of Alarm:

Alarm Location LED Input 2

Alarm Location LED Input 1

Alarm Location LED Input 3

Page 43: (DB-B1-6C-12AB-0Z) - Talley Inc. INSTALL INSTRUCTIONS RRFDC-3315-PF-48 Installation Instructions: RRFDC-3315-PF-48 (DB-B1-6C-12AB-0Z)

www.raycap.com

©Raycap • All rights reserved320-0799 Rev.C

Page 41 of 46

INSTALL INSTRUCTIONS RRFDC-3315-PF-48 (DB-B1-6C-12AB-0Z)

26.7 Connecting the RRFDC-3315-PF-48 to Raycap Legacy Products.

The following diagram illustrates connection between a current RRFDC-3315-PF-48 to the following legacy Tower/Rooftop products:

RRFDC-3315-PF-48 RRFDC-4750-PF-48

COM

H2O

PWR

INTR

RTN

-48

RTN

-48

RTN

-48

Alar

m In

put 1

COM

H2O

PWR

INTR

Alar

m In

put 2

COM

H2O

PWR

INTR

Alar

m In

put 3

COM

H2O

PWR

INTR

-48

RTN

Out

put t

o Ba

se O

VP

PWR-COM

H2O-COM

PWR-NC

H2O-NC

INTR-COM

INTR-NC

Out

put t

o BT

S

NEW

331

5 AL

ARM

BO

ARD

PWR-

COM

PWR-

-NO

H2O

-CO

M

H2O

-NO

INTR

-CO

M

INTR

-NO

INTR

-NC

H2O

-NC

PWR-

NC

COM

H2O

-NO

INTR

-NO

GN

DA

PWRA

PWR-

NO

COM

H2O

-NO

INTR

-NO

GN

DB

PWRB

PW

R-N

O

COM

H2O

-NO

INTR

-NO

GN

DC

PWRC

PWR-

NO

Sector-A Input Sector-B Input Sector-C Input

LEGACY 3315/4750 ALARM BOARDMain Output

Page 44: (DB-B1-6C-12AB-0Z) - Talley Inc. INSTALL INSTRUCTIONS RRFDC-3315-PF-48 Installation Instructions: RRFDC-3315-PF-48 (DB-B1-6C-12AB-0Z)

www.raycap.com

©Raycap • All rights reserved320-0799 Rev.C

Page 42 of 46

RRFDC-3315-PF-48 INSTALL INSTRUCTIONS (DB-B1-6C-12AB-0Z)

26.8 Connecting the RRFDC-3315-PF-48 to Raycap Legacy Products.

The following diagram illustrates connection between a current RRFDC-3315-PF-48 to the following legacy Tower Base and Sector products:

RRFDC-3315-PF-48 RRFDC-1064-PF-48

COM

MO

N

PWR-

-NO

H2 O

-NC

INTR

-NC

INTR

-NO

GN

D

PWR

H2 O

-NO

PWR-

NC

LEGACY 1064 ALARM BOARDMain Output

COM

H2O

PWR

INTR

RTN

-48

RTN

-48

RTN

-48

Alar

m In

put 1

COM

H2O

PWR

INTR

Alar

m In

put 2

COM

H2O

PWR

INTR

Alar

m In

put 3

COM

H2O

PWR

INTR

-48

RTN

Out

put t

o Ba

se O

VP

PWR-COM

H2O-COM

PWR-NC

H2O-NC

INTR-COM

INTR-NC

Out

put t

o BT

S

NEW

331

5 AL

ARM

BO

ARD

PWR-

COM

PWR-

-NO

H2 O

-CO

M

H2 O

-NO

INTR

-CO

M

INTR

-NO

INTR

-NC

H2 O

-NC

PWR-

NC

COM

H2 O

-NO

INTR

-NO

GN

DA

PWRA

PWR-

NO

COM

H2 O

-NO

INTR

-NO

GN

DB

PWRB

PWR-

NO

COM

H2 O

-NO

INTR

-NO

GN

DC

PWRC

PWR-

NO

Sector-A Input Sector-B Input Sector-C Input

LEGACY 3315 ALARM BOARD

Main Output

Notes

Page 45: (DB-B1-6C-12AB-0Z) - Talley Inc. INSTALL INSTRUCTIONS RRFDC-3315-PF-48 Installation Instructions: RRFDC-3315-PF-48 (DB-B1-6C-12AB-0Z)

www.raycap.com

©Raycap • All rights reserved320-0799 Rev.C

Page 43 of 46

INSTALL INSTRUCTIONS RRFDC-3315-PF-48 (DB-B1-6C-12AB-0Z)

Notes

Page 46: (DB-B1-6C-12AB-0Z) - Talley Inc. INSTALL INSTRUCTIONS RRFDC-3315-PF-48 Installation Instructions: RRFDC-3315-PF-48 (DB-B1-6C-12AB-0Z)

www.raycap.com

©Raycap • All rights reserved320-0799 Rev.C

Page 44 of 46

RRFDC-3315-PF-48 INSTALL INSTRUCTIONS (DB-B1-6C-12AB-0Z)

Notes

Page 47: (DB-B1-6C-12AB-0Z) - Talley Inc. INSTALL INSTRUCTIONS RRFDC-3315-PF-48 Installation Instructions: RRFDC-3315-PF-48 (DB-B1-6C-12AB-0Z)
Page 48: (DB-B1-6C-12AB-0Z) - Talley Inc. INSTALL INSTRUCTIONS RRFDC-3315-PF-48 Installation Instructions: RRFDC-3315-PF-48 (DB-B1-6C-12AB-0Z)

www.raycap.com

©Raycap • All rights reserved320-0799 Rev.C

RRFDC-3315-PF-48 INSTALL INSTRUCTIONS (DB-B1-6C-12AB-0Z)