further information webcode: GW-4242 GEMÜ 4242 Combi switchbox with integrated pilot valve Features Fieldbus connection AS-Interface and DeviceNet (optional) Communication and programming interface IO-Link Adjustable switch point tolerances Speed -AP function for fast mounting and initialisation High visibility position indicator by LED Can be fitted to GEMÜ valves or third-party actuators On-site or remote end position programming via programming input Integrated manual override Description The GEMÜ 4242 combi switchbox is suitable for mounting to pneumatically operated linear actuators. The position of the valve spindle is reliably electronically detected and evaluated using play-free and non-positive mounting. Integrated pilot valves enable direct activation of the process valve connected to them. Intelligent microprocessor controlled functions make commissioning and support during operation easier. The current position of the valve is displayed via high visibility LEDs and fed back via electrical signals. Technical specifications Ambient temperature: 0 to 60 °C Linear measuring range: 2 to 75 mm Flow rate: 14 Nl/min l 23 Nl/min l 250 Nl/min Communication modes: AS-Interface l DeviceNet l IO-Link Electrical connection types: M12 plug Protection class: IP 65, IP 67 Conformities: ATEX l EAC l ETL Listed C US l IECEx l SIL Technical data depends on the respective configuration

db 4242 gb - GEMU Valves, Measurement and …EN 61000-6-2acc. to AS-Interface Spec. 3.0 EN 61000-6-2EN 61000-6-2 NEC marking:Class I, Division II, Groups C & D, T4 Approvals: 24 VAS-InterfaceIO-LinkDeviceNet

  • Upload
    others

  • View
    7

  • Download
    0

Embed Size (px)

Citation preview

Page 1: db 4242 gb - GEMU Valves, Measurement and …EN 61000-6-2acc. to AS-Interface Spec. 3.0 EN 61000-6-2EN 61000-6-2 NEC marking:Class I, Division II, Groups C & D, T4 Approvals: 24 VAS-InterfaceIO-LinkDeviceNet

further informationwebcode: GW-4242

GEMÜ 4242Combi switchbox with integrated pilot valve

Features• Fieldbus connection AS-Interface and DeviceNet (optional)• Communication and programming interface IO-Link• Adjustable switch point tolerances• Speed-AP function for fast mounting and initialisation• High visibility position indicator by LED• Can be fitted to GEMÜ valves or third-party actuators• On-site or remote end position programming via

programming input• Integrated manual override

DescriptionThe GEMÜ 4242 combi switchbox is suitable for mounting to pneumatically operated linear actuators. The position of thevalve spindle is reliably electronically detected and evaluated using play-free and non-positive mounting. Integrated pilotvalves enable direct activation of the process valve connected to them. Intelligent microprocessor controlled functions makecommissioning and support during operation easier. The current position of the valve is displayed via high visibility LEDs andfed back via electrical signals.

Technical specifications• Ambient temperature: 0 to 60 °C• Linear measuring range: 2 to 75 mm• Flow rate: 14 Nl/min l 23 Nl/min l 250 Nl/min• Communication modes: AS-Interface l DeviceNet l IO-Link• Electrical connection types: M12 plug• Protection class: IP 65, IP 67• Conformities: ATEX l EAC l ETL Listed C US l IECEx l SILTechnical data depends on the respective configuration

Page 2: db 4242 gb - GEMU Valves, Measurement and …EN 61000-6-2acc. to AS-Interface Spec. 3.0 EN 61000-6-2EN 61000-6-2 NEC marking:Class I, Division II, Groups C & D, T4 Approvals: 24 VAS-InterfaceIO-LinkDeviceNet

www.gemu-group.com2 / 28GEMÜ 4242

Product description

1

24

3

5

Size 1 Size 2

1

2

5

34

Item Name Materials

Size 1 Size 21 Housing cover - standard version: PC PC

Housing cover - compact version: PP -2 Housing base Anodised aluminium or SS PPS3 Electrical connection SS, PP SS, PP4 Adapter piece SS SS5 Mounting kit, valve specific SS SS

Seals EPDM and NBR NBR

Product description

Page 3: db 4242 gb - GEMU Valves, Measurement and …EN 61000-6-2acc. to AS-Interface Spec. 3.0 EN 61000-6-2EN 61000-6-2 NEC marking:Class I, Division II, Groups C & D, T4 Approvals: 24 VAS-InterfaceIO-LinkDeviceNet

GEMÜ 4242www.gemu-group.com 3 / 28

Status LEDsAs well as the electrical position feedback and error analysis a visual signal is emitted by LEDs that can be seen from above.

24 V / AS-Interface / IO-Link version DeviceNet version

LED Colour Function

Standard 1) Inversed 2)

CLOSED green orange Process valve in CLOSEDposition

ERROR red red Error

OPEN orange green Process valve in OPENposition

MNS green green Communication existingred red Communication error

PWR/FAULT green green Communication existingred red Communication error

High visibility LED green orange Process valve in CLOSEDposition

orange green Process valve in OPENposition

green / orange green / orange Programming mode

1) OptionCode 00: WithoutCode 01: Manual override

2) OptionCode 40: Inversed LED coloursCode 41: Inversed LED colours, manual override

For order codes see chapter "Order data"

Product description

Page 4: db 4242 gb - GEMU Valves, Measurement and …EN 61000-6-2acc. to AS-Interface Spec. 3.0 EN 61000-6-2EN 61000-6-2 NEC marking:Class I, Division II, Groups C & D, T4 Approvals: 24 VAS-InterfaceIO-LinkDeviceNet

www.gemu-group.com4 / 28GEMÜ 4242

GEMÜ CONEXOThe interaction of valve components that are equipped with RFID chips and an associated IT infrastructure actively increaseprocess reliability.

Thanks to serialization, every valve and every relevant valve component such as the body, actuator or diaphragm, and evenautomation components, can be clearly traced and read using the CONEXO pen RFID reader. The CONEXO app, which can beinstalled on mobile devices, not only facilitates and improves the "installation qualification" process, but also makes the main-tenance process much more transparent and easier to document. The app actively guides the maintenance technician throughthe maintenance schedule and directly provides him with all the information assigned to the valve, such as test reports, testingdocumentation and maintenance histories. The CONEXO portal acts as a central element, helping to collect, manage and pro-cess all data.

For further information on GEMÜ CONEXO please visit:www.gemu-group.com/conexo

OrderingGEMÜ Conexo must be ordered separately with the ordering option "CONEXO" (see order data).Installing the RFID chip (1)

1

1

GEMÜ CONEXO

Page 5: db 4242 gb - GEMU Valves, Measurement and …EN 61000-6-2acc. to AS-Interface Spec. 3.0 EN 61000-6-2EN 61000-6-2 NEC marking:Class I, Division II, Groups C & D, T4 Approvals: 24 VAS-InterfaceIO-LinkDeviceNet

GEMÜ 4242www.gemu-group.com 5 / 28

AvailabilityOption Code Size 1 Size 2

Housing material 1) 01 - X

07 X -

14 X -

Function 2) 01 X X

02 X X

K1 X -

Flow rate 3) 01 X -

02 X -

03 - X

Special version 4) Y X X

X X X

1) Housing materialCode 01: PPS base, PC coverCode 07: Stainless steel base, PC coverCode 14: Aluminium base, PC cover

2) FunctionCode 01: Combi switchbox, single actingCode 02: Combi switchbox, double actingCode K1: Combi switchbox, compact version, single acting

3) Flow rateCode 01: 14 Nl/min, size 1Code 02: 23 Nl/min (Booster), size 1Code 03: 250 Nl/min, size 2

4) Special versionCode Y: NEC 500 and UL/CSA approval

Availability

Page 6: db 4242 gb - GEMU Valves, Measurement and …EN 61000-6-2acc. to AS-Interface Spec. 3.0 EN 61000-6-2EN 61000-6-2 NEC marking:Class I, Division II, Groups C & D, T4 Approvals: 24 VAS-InterfaceIO-LinkDeviceNet

www.gemu-group.com6 / 28GEMÜ 4242

Overview of available functionsFunction Version

24 V IO-Link AS-Interface DeviceNet

A2 A3 A4Optical high visibility position indicator X X X X X XDeactivation of high visibility positionindicator

- X - - X X

Manual override X X X X X XOn-site programming X X X X X XDeactivation of on-site programming - X - - X XPosition feedback Open X X X X X XPosition feedback Closed X X X X X XFeedback for operating mode - X X X X XLocation function - X - - X XInversion of LED colours - X - - X XInversion of feedback signals - X - - X XSwitch point setting (tolerance) - X X X X XSetting stroke reduction alarm - X - - - XFeedback stroke reduction alarm - X - - X XFeedback programmed positions - X - - - XFeedback current positions - X - - - XFeedback internal error - X X X X XFeedback sensor error - X X X X XFeedback programming error - X X X X XSetting pneumatic fault time - X - - - XFeedback pneumatic fault - X X X X XFeedback over-temperature - X - - - -Counter Powerfail - X - - - -Counter Power on - X - - - -Programming counter - X - - - -Counter programming error - X - - - -Counter pneumatic fault - X - - - -Counter sensor error - X - - -Counter over-temperature - X - - - -Cycle counter (on-site) - X - - - XTotal cycle counter - X - - - XDefault - X - - - Via

DeviceNet

Overview of available functions

Page 7: db 4242 gb - GEMU Valves, Measurement and …EN 61000-6-2acc. to AS-Interface Spec. 3.0 EN 61000-6-2EN 61000-6-2 NEC marking:Class I, Division II, Groups C & D, T4 Approvals: 24 VAS-InterfaceIO-LinkDeviceNet

Order dataThe order data provide an overview of standard configurations.

Please check the availability before ordering. Other configurations available on request.

Note: A valve specific mounting kit is required for assembly. For designing the mounting kit, the valve type, nominal size, con-trol function and actuator size must be stated.

Order codes1 Type CodeCombi switchbox 4242

2 Fieldbus CodeWithout, 24 V DC version 000AS-Interface, 31 slaves, 4I/4O A2AS-Interface, 62 slaves, 4I/3O A3AS-Interface, 62 slaves, 8I/8O A4DeviceNet DNIO-Link IOL

3 Accessory CodeAccessory Z

4 Housing material CodeStainless steel base, PC cover 07Aluminium base, PC cover 14PPS base, PC cover 01

5 Function CodeCombi switchbox, single acting 01Combi switchbox, double acting 02Combi switchbox, compact version,single acting

K1

6 Electrical connection CodeM12 plug, 5-pin 01M12 plug, 8-pin 02M12 plug, 5-pin, stainless steel, size 2 S1M12 plug, 8-pin, stainless steel, size 2 S2

7 Pneumatic connection CodeConnection thread M5 for size 1,connection thread G1/8 for size 2

01

Air supply 4 mm angled connection,exhaust air 4 mm angled connection

02

Air supply 4 mm T-connection,exhaust air 4 mm angled connection

03

Air supply 6 mm angled connection,exhaust air 6 mm angled connection

04

Air supply 6 mm T-connection,exhaust air 6 mm angled connection

05

Connection thread M5 for size 1,connection thread G1/8 for size 2(for IP67 or piped air outlet)

E1

Air supply 6 mm angled connection,exhaust air 6 mm angled connection(for IP67 or piped air outlet)

E4

7 Continuation of Pneumatic connection CodeAir supply 1/4" angled connection,exhaust air 1/4" angled connection

U8

8 Option CodeWithout 00Manual override 01Inversed LED colours 40Inversed LED colours, manual override 41Inversed LED coloursdeactivated high visibility position feedback

80

9 Flow rate Code14 Nl/min, size 1 0123 Nl/min (Booster), size 1 02250 Nl/min, size 2 03

10 Travel sensor version CodePotentiometer 30 mm length, size 1 030Potentiometer 75 mm length, size 2 075

11 Special version CodeWithoutATEX (2014/34/EU), IECEx XNEC 500 and UL/CSA approval Y

Order data

GEMÜ 4242www.gemu-group.com 7 / 28

Page 8: db 4242 gb - GEMU Valves, Measurement and …EN 61000-6-2acc. to AS-Interface Spec. 3.0 EN 61000-6-2EN 61000-6-2 NEC marking:Class I, Division II, Groups C & D, T4 Approvals: 24 VAS-InterfaceIO-LinkDeviceNet

Order exampleOrder option Code Description

1 Type 4242 Combi switchbox2 Fieldbus 000 Without, 24 V DC version3 Accessory Z Accessory4 Housing material 07 Stainless steel base, PC cover5 Function 01 Combi switchbox, single acting6 Electrical connection 01 M12 plug, 5-pin7 Pneumatic connection 01 Connection thread M5 for size 1,

connection thread G1/8 for size 28 Option 01 Manual override9 Flow rate 01 14 Nl/min, size 110 Travel sensor version 030 Potentiometer 30 mm length, size 111 Special version Without

Order data

www.gemu-group.com8 / 28GEMÜ 4242

Page 9: db 4242 gb - GEMU Valves, Measurement and …EN 61000-6-2acc. to AS-Interface Spec. 3.0 EN 61000-6-2EN 61000-6-2 NEC marking:Class I, Division II, Groups C & D, T4 Approvals: 24 VAS-InterfaceIO-LinkDeviceNet

GEMÜ 4242www.gemu-group.com 9 / 28

Technical data

MediumWorking medium: Quality classes to DIN ISO 8573-1

Dust content: Class 3, max. particle size 5 μm, max. particle density 5 mg/m³

Oil content: Class 5, max. oil concentration 25 mg/m³

TemperatureAmbient temperature: Standard or with special version code Y 0 to 60 °C

Special version code X 0 to 40 °C

Media temperature: 0 to 50 °C

Storage temperature: -10 to 70 °C

PressureOperating pressure: Size 1 Size 2

1 to 9 bar (at 40 °C)1 to 8 bar (at 60 °C)

2 to 7 bar

Observe the maximum control pressure of the valve actuator.

Flow rate: Size 1 Size 214 Nl/min23 Nl/min

250 Nl/min

Product conformitiesEMC Directive: 2014/30/EU

Technical standards used:

24 V AS-Interface IO-Link DeviceNet

Interferenceemission

EN 61000-6-3 acc. to AS-Interface Spec.3.0

EN 61000-6-3 EN 61000-6-3

Interferenceresistance

EN 61000-6-2 acc. to AS-Interface Spec.3.0

EN 61000-6-2 EN 61000-6-2

Explosion protection: ATEX (2014/34/EU) and IECEx, order code Special version XNEC 500 (ISA 12.12.01), order code for special version Y

ATEX marking: Gas: II 3G Ex ec nC IIC T4 Gc XDust: II 3D Ex tc IIIC T 80 °C Dc X

IECEx marking: Gas: Ex ec nC IIC T4 GcDust: Ex tc IIIC T80°C DcCertificate: IECEx IBE 19.0011 X

NEC marking: Class I, Division II, Groups C & D, T4

Technical data

Page 10: db 4242 gb - GEMU Valves, Measurement and …EN 61000-6-2acc. to AS-Interface Spec. 3.0 EN 61000-6-2EN 61000-6-2 NEC marking:Class I, Division II, Groups C & D, T4 Approvals: 24 VAS-InterfaceIO-LinkDeviceNet

www.gemu-group.com10 / 28GEMÜ 4242

Approvals: 24 V AS-Interface IO-Link DeviceNet

Fieldbus / Communication

- Travel sensorversion 030: AS-Interfacecertificate No.96001Travel sensorversion 075: AS-Interfacecertificate No.125601

Travel sensorversion 030: IO-Link specificationV1.0Travel sensorversion 075: IO-Link specificationV1.1

n.n.

SIL: SIL2 (IEC 61508/IEC 61511)only fieldbus code 000

Mechanical dataInstallation position: Optional

Weight: Size 1 Size 2Aluminium: 320 gStainless steel: 600 g

420 g

Protection class: IP 65 acc. to EN 60529IP 67 acc. to EN 60529, is reached with piped air outletIP NEMA 4X (UL 61010-1, UL 50E), only available as special version code Y

Travel sensor: Size 1 Size 2

Minimum stroke: 2 mm 5 mm

Maximum stroke: 30 mm 75 mm

Hysteresis: 0.2 mm 0.5 mm

Accuracy: 0.2 % Full Scale

Electrical dataSupply voltage: 24 V IO-Link AS-Interface DeviceNet

24 V DC(18 to 30 V DC)

24 V DC(18 to 30 V DC)

26.5 to 31.6 V DC 24 V DC (11 to 25 V DC)

Duty cycle: Continuous duty

Reverse batteryprotection:

yes

Electrical protectionclass:

III

Line fuse: 630 mA medium time lag, for order code Fieldbus 000

Current consumption: Flow rate code 24 V IO-Link AS-Interface DeviceNet

01 typically 80 mA typically 80 mA typically 100 mA typically 65 mA

02 typically 120 mA typically 120 mA typically 150 mA typically 100 mA

03 typically 100 mA typically 100 mA typically 120 mA typically 85 mA

Technical data

Page 11: db 4242 gb - GEMU Valves, Measurement and …EN 61000-6-2acc. to AS-Interface Spec. 3.0 EN 61000-6-2EN 61000-6-2 NEC marking:Class I, Division II, Groups C & D, T4 Approvals: 24 VAS-InterfaceIO-LinkDeviceNet

GEMÜ 4242www.gemu-group.com 11 / 28

Electrical connectiontype:

24 V IO-Link / AS-Interface /DeviceNet

1 x 8-pin M12plug

(A-coded)

1 x 5-pin M12plug

(A-coded)

Switching characteristic:

100%

0%

td1 td1

td1 td2td1

tat/ms

t/ms

t/ms

Stroke %

Switch point "Open"Switching hysteresis

Switching hysteresis

Switching output "Open"

Switch point "Closed"

active

inactive

active

inactive

Switching output "Closed"

td1: Signal delaytd2: Signal delayta: Signal interval

Switch points: The data in percent refer to the programmed stroke, before each end position

Switch points: Size 1 Size 2

Default setting switch point CLOSED 12 % 12 %

Default setting switch point OPEN 25 % 25 %

Min. switch point CLOSED 0.8 mm 2 mm

Min. switch point OPEN 0.5 mm 1.25 mm

If the percentage switch points dependent on the programmed stroke are smaller than the per-missible min. switch points, the min. switch points apply automatically.

Technical data

Page 12: db 4242 gb - GEMU Valves, Measurement and …EN 61000-6-2acc. to AS-Interface Spec. 3.0 EN 61000-6-2EN 61000-6-2 NEC marking:Class I, Division II, Groups C & D, T4 Approvals: 24 VAS-InterfaceIO-LinkDeviceNet

www.gemu-group.com12 / 28GEMÜ 4242

Dimensions

Size 1

98

Ø57

X

13

16,647

WAF 20 for mounting kit M12x1,x = 9 mm WAF 24 for mounting kit M16x1,x = 11 mm dependent on valve used

X

□42

95

20

13,6

WAF 20 for mounting kit M12x1,x = 9 mm WAF 24 for mounting kit M16x1,x = 11 mm dependent on valve used

Standard Compact

Dimensions in mm

Size 2

142

Ø 90

14,

5

86,5 19

X

WAF 20 for mounting kit M12x1,x = 9 mm WAF 24 for mounting kit M16x1,x = 11 mm dependent on valve used

Dimensions in mm

Dimensions

Page 13: db 4242 gb - GEMU Valves, Measurement and …EN 61000-6-2acc. to AS-Interface Spec. 3.0 EN 61000-6-2EN 61000-6-2 NEC marking:Class I, Division II, Groups C & D, T4 Approvals: 24 VAS-InterfaceIO-LinkDeviceNet

GEMÜ 4242www.gemu-group.com 13 / 28

Pneumatic connection

Size 1, standard, single acting

E E

Connection Designation Connection size1 Air supply connection M52 Working connection for process valve M53 Venting connection with integrated check valve M6 x 0.75 1)

E Housing ventilation with integrated check valve M6 x 0.75 1)

1) only relevant for exhaust air duct and/or increase of protection class

Size 1, standard, double acting

E

Connection Designation Connection size1 Air supply connection M52 Working connection for process valve M53 Venting connection with integrated check valve M6 x 0.75 1)

4 Working connection for process valve M5E Housing ventilation with integrated check valve M6 x 0.75 1)

1) only relevant for exhaust air duct and/or increase of protection class

Size 1, compact version

E1

Connection Designation Connection size1 Air supply connection M52 Working connection for process valve M53 Venting connection with integrated check valve M6 x 0.75 1)

E1 Housing ventilation with integrated check valve M6 x 0.75 1)

1) only relevant for exhaust air duct and/or increase of protection class

Pneumatic connection

Page 14: db 4242 gb - GEMU Valves, Measurement and …EN 61000-6-2acc. to AS-Interface Spec. 3.0 EN 61000-6-2EN 61000-6-2 NEC marking:Class I, Division II, Groups C & D, T4 Approvals: 24 VAS-InterfaceIO-LinkDeviceNet

www.gemu-group.com14 / 28GEMÜ 4242

Size 2, standard, single acting

Connection Designation Connection size1 Air supply connection G 1/82 Working connection for process valve G 1/83 Venting connection with silencer (integrated housing ventilation) G 1/8 1)

1) only relevant for exhaust air duct and/or increase of protection class

Size 2, standard, double acting

Connection Designation Connection size1 Air supply connection G 1/82 Working connection for process valve G 1/83 Venting connection with silencer (integrated housing ventilation) G 1/8 1)

4 Working connection for process valve G 1/8

1) only relevant for exhaust air duct and/or increase of protection class

Pneumatic connection

Page 15: db 4242 gb - GEMU Valves, Measurement and …EN 61000-6-2acc. to AS-Interface Spec. 3.0 EN 61000-6-2EN 61000-6-2 NEC marking:Class I, Division II, Groups C & D, T4 Approvals: 24 VAS-InterfaceIO-LinkDeviceNet

GEMÜ 4242www.gemu-group.com 15 / 28

Electrical connection

24 V, ordering option Fieldbus, code 000Pin assignment

65

32

4 78

1

Pin Signal name1 U, 24 V DC, supply voltage2 24 V DC, Open end position output3 U, GND4 24 V DC, Closed end position output5 24 V DC, programming input6 24 V DC, control input7 24 V DC, error output8 n.c.

Pin 5 and pin 6 are highly active. If not used, connect to GND or leave open.

Inputs (pin 5, 6)Input impedance: Size 1 Size 2

min. 6 kΩ min. 27 kΩ

Input voltage: max. 30 V DC

High level: ≥ 18 V DC

Low level: ≤ 5 V DC

Outputs (pin 2, 4, 7)Internal wiring: Size 1 Size 2

Error output Output Open/Closed Internal wiring

Push-Pull Push with Pull down resistance68 kΩ

Push-Pull

Max. switching current: ± 100 mA

Max. voltage drop Vdrop: 3 V DC at 100 mA

Switching voltage: +Uv - Vdrop push high-Uv + Vdrop pull low

Electrical connection

Page 16: db 4242 gb - GEMU Valves, Measurement and …EN 61000-6-2acc. to AS-Interface Spec. 3.0 EN 61000-6-2EN 61000-6-2 NEC marking:Class I, Division II, Groups C & D, T4 Approvals: 24 VAS-InterfaceIO-LinkDeviceNet

www.gemu-group.com16 / 28GEMÜ 4242

IO-Link, ordering option Fieldbus, code IOLPin assignment

1

4

3

2

Pin Signal name1 U, 24 V DC, supply voltage2 n.c.3 U, GND4 C/Q IO-Link5 -

AS-Interface, ordering option Fieldbus, code A2, A3, A4Pin assignment

1

4

3

Pin Signal name1 AS-Interface +2 -3 AS-Interface -4 n.c.5 -

Carry out potential equalisation via pre-assembled earthing kit.Connect yellow/green stranded wire H07 V-K 4.0 on site.

DeviceNet, ordering option Fieldbus, code DNPin assignment

1

4

3

2

5

Pin Signal name1 Shield2 V+3 V-4 CAN_H5 CAN_L

Electrical connection

Page 17: db 4242 gb - GEMU Valves, Measurement and …EN 61000-6-2acc. to AS-Interface Spec. 3.0 EN 61000-6-2EN 61000-6-2 NEC marking:Class I, Division II, Groups C & D, T4 Approvals: 24 VAS-InterfaceIO-LinkDeviceNet

GEMÜ 4242www.gemu-group.com 17 / 28

Specific data - IO-LinkFrame type in Operate: 2.5

Transmission rate: 38400 baud

Min. cycle time: 2.3 ms

Physics: Physics 2 (3-wire design)

Port configuration: Port type A

Vendor-ID: 401

Device-ID: 424201

Product-ID: 4242 IO-LINK

ISDU support: yes

SIO operation: yes

IO-Link specification: Size 1 Size 2V1.1 V1.1 when using IODD 1.1 1)

1) When using IODD 1.0.1 the device works in accordance with IO-Link specification V1.0 (compatibilitymode)

Note for IO Link: Download IODD files from www.gemu-group.com.

InputsBit Default Designation Function Logic0 0 Valve position Feedback OPEN position 0 = process valve not in OPEN position

1 = process valve in OPEN position1 0 Valve position Feedback CLOSED position 0 = process valve not in CLOSED position

1 = process valve in CLOSED position2 0 Programing mode Indication of operating mode 0 = normal operation

1 = programing mode3...7 not used

OutputsBit Default Designation Function Logic0 0 Pneumatic outlet

(valve)Activation of pneumatic outlet 2 (pilot valve 1 = pneumatic outlet 2)

0 = pneumatic outlet 2 vented1 = pneumatic outlet 2 pressurized

0 0 Pneumatic outlet(valve)

Activation of pneumatic outlet 2 / 4 1) (pilot valve 1 = pneumatic outlet 2) (pilot valve 2 = pneumatic outlet 4)

0 = pneumatic outlet 2 vented, pneumaticoutlet 4 1) pressurized1 = pneumatic outlet 2 pressurized,pneumatic outlet 4 1) vented

1 0 Programing mode Selection of operating mode 0 = normal operation 1 = programing mode

2 0 Location function Location function 0 = not active 1 = active

3 … 7 not used

1) Activation of outlet 4, only for double acting function (code 02)

ParameterIndex[Hex]

Su-bindex

Parameter Length

Datatype

Ac-cess

Standardvalue

Value range

0x10 0 Vendor Name 6 byte StringT ro GEMUE -

Specific data - IO-Link

Page 18: db 4242 gb - GEMU Valves, Measurement and …EN 61000-6-2acc. to AS-Interface Spec. 3.0 EN 61000-6-2EN 61000-6-2 NEC marking:Class I, Division II, Groups C & D, T4 Approvals: 24 VAS-InterfaceIO-LinkDeviceNet

www.gemu-group.com18 / 28GEMÜ 4242

Index[Hex]

Su-bindex

Parameter Length

Datatype

Ac-cess

Standardvalue

Value range

0x12 0 Product Name 13byte

StringT ro 4242 IO-Link -

0x13 0 Product ID 8 byte StringT ro 4242 IO-Link -0x15 0 Serial number 9 byte StringT ro 0 –

4294967296-

0x16 0 Hardware Revision 8 byte StringT ro Rev. xx -0x17 0 Firmware Revision 10

byteStringT ro V x.x.x.x -

0x50 1 Inversion of LED colours 1 bit Boolean rw 0 0 = standard1 = inversed

2 Inversion of feedback signals 1bit Boolean rw 0 0 = standard1 = inversed

3 Function of high visibility 3 bit UIntegerT rw 3 0 = off1 = open/closed (33 %)2 = open/closed (66 %)3 = open/closed (100 %)

4 Programming mode 1 bit Boolean rw 0 0 = automatic1 = manual

5 On site programming 1 bit Boolean rw 0 0 = enabled1 = disabled

6 Inversion of Outputs 1 bit Boolean rw 0 0 = standard1 = inversed

0x51 1 Switch Point OPEN request 8 bit UIntegerT rw 25 % 3% - 97%2 Switch Point CLOSED request 8 bit UIntegerT rw 12 % 3% - 97%3 Switch Point OPEN real 8 bit UIntegerT ro 25 % Display of values 3 % - 97 %4 Switch Point CLOSED real 8 bit UIntegerT ro 12 % Display of values 3 % - 97 %

0x52 1 Alarm Stroke reduction OPEN 4 bit UIntegerT rw 1 0 = disabled1 = 25 % of Switch Point2 = 50 % of Switch Point3 = 75 % of Switch Point

2 Alarm Stroke reduction CLOSED 4 bit UIntegerT rw 1 0 = disabled1 = 25 % of Switch Point2 = 50 % of Switch Point3 = 75 % of Switch Point

3 Alarm opening time 8 bit UIntegerT rw 0 0 = disabled1-255 s

4 Alarm closing time 8 bit UIntegerT rw 0 0 = disabled1-255 s

5 Valve type 8 bit UIntegerT rw 0 0 = unknown1 = normaly closed2 = normaly open

0x53 1 Programmed position OPEN 16 bit UIntegerT ro 0 Display of numerical values 0- 40922 Programmed position CLOSED 16 bit UIntegerT ro 0

3 Programmed position STROKE 16 bit UIntegerT ro 00x54 1 Last position OPEN 16 bit UIntegerT ro 0

2 Last position CLOSED 16 bit UIntegerT ro 03 Last position STROKE 16 bit UIntegerT ro 0

0x56 1 Valve cycles user 24 bit UIntegerT rw 0 Resettable to 0, display of numerical values0 - 16777215

Specific data - IO-Link

Page 19: db 4242 gb - GEMU Valves, Measurement and …EN 61000-6-2acc. to AS-Interface Spec. 3.0 EN 61000-6-2EN 61000-6-2 NEC marking:Class I, Division II, Groups C & D, T4 Approvals: 24 VAS-InterfaceIO-LinkDeviceNet

GEMÜ 4242www.gemu-group.com 19 / 28

Index[Hex]

Su-bindex

Parameter Length

Datatype

Ac-cess

Standardvalue

Value range

2 Valve cycles total 24 bit UIntegerT ro 0 Display of numerical values 0 - 16777215

0x57 1 Counter Powerfail 16 bit UIntegerT ro 0 Display of numerical values 0- 655352 Counter Power on 16 bit UIntegerT ro 0

3 Counter Programming 16 bit UIntegerT ro 04 Counter Sensor calibration 16 bit UIntegerT ro 05 Counter Prog error no stroke 16 bit UIntegerT ro 06 Counter Prog error less stroke 16 bit UIntegerT ro 07 Counter Prog error after sensor

error16 bit UIntegerT ro 0

8 Counter Pneumatic fault open 16 bit UIntegerT ro 09 Counter Pneumatic fault closed 16 bit UIntegerT ro 0

10 Counter Pneumatic fault middlepostition

16 bit UIntegerT ro 0

11 Counter Sensor error open 16 bit UIntegerT ro 012 Counter Sensor error closed 16 bit UIntegerT ro 016 Counter Over temperature 16 bit UIntegerT ro 0

0x60 0 Actual AD-value 16 bit UIntegerT ro 0 Display of numerical values 0- 4092

Diagnostic messages (Event Codes)Meaning Value Type Mode

Internal error 0x8CA2 Error Appear / DisappearSensor error in position OPEN 0x8CA4 Error Appear / DisappearSensor error in position CLOSED 0x8CA5 Error Appear / DisappearProgramming error with no stroke 0x8CA6 Error Appear / DisappearProgramming error with to less stroke 0x8CA7 Error Appear / DisappearProgramming error after sensor error 0x8CA8 Error Appear / DisappearNot calibrated 0x8CA9 Error Appear / DisappearPneumatic error in position OPEN 0x8CB0 Warning Appear / DisappearPneumatic error in position CLOSED 0x8CB1 Warning Appear / DisappearPneumatic error between position 0x8CB2 Warning Appear / DisappearStroke reduction OPEN 0x8CB5 Warning Appear / DisappearStroke reduction CLOSED 0x8CB6 Warning Appear / DisappearParameter value out of Range 0x8DE0 Notification Single ShotParameter value changed 0x8DE1 Notification Single Shot

Specific data - IO-Link

Page 20: db 4242 gb - GEMU Valves, Measurement and …EN 61000-6-2acc. to AS-Interface Spec. 3.0 EN 61000-6-2EN 61000-6-2 NEC marking:Class I, Division II, Groups C & D, T4 Approvals: 24 VAS-InterfaceIO-LinkDeviceNet

www.gemu-group.com20 / 28GEMÜ 4242

Specific data - AS-InterfaceA2 version A3 version A4 version

AS-Interface specification 3.0; max. 31 slaves 3.0; max. 62 slaves 3.0; max. 62 slaves

AS-Interface profile S 7.F.E (4I/4O) S 7.A.E (4I/3O) S 7.A.A (8I/8O)

I/O configuration 7 7 7

ID code F A A

ID2 code E E A

AS-Interface approval Size 1: AS-Interface certificate No. 96001Size 2: AS-Interface certificate No. 125601

InputsBit Default Function Version Logic

A2 A3 A4DI0 0 Indication of OPEN position X X X 0 = process valve not in OPEN position

1 = process valve in OPEN positionDI1 0 Indication of CLOSED position X X X 0 = process valve not in CLOSED position

1 = process valve in CLOSED positionDI2 0 Indication of operating mode X X X 0 = normal operation

1 = programming modeDI3 0 Error 2 X X X see error analysisDI4 0 Error 3 - - XDI5 0 Error 4 - - XDI6,DI7

not used - - X

PF 0 Error 1 X X X see error analysis

OutputsBit Default Function Version Logic

A2 A3 A4DO0 0 Activation of pneumatic outlet 2 X - - 0 = pneumatic outlet 2 vented

1 = pneumatic outlet 2 pressurized0 Activation of pneumatic outlet 2 / 4 X X X 0 = pneumatic outlet 2 vented, pneumatic

outlet 4 1) pressurized1 = pneumatic outlet 2 pressurized,pneumatic outlet 4 1) vented

DO1 0 Activation of pneumatic outlet 4 1) (pilot valve 2)

X - - 0 = pneumatic outlet 4 1)vented1 = pneumatic outlet 4 1)pressurized

not used X - -0 Programming mode - X - 0 = manual programming

1 = automatic programming0 - - X 0 = automatic programming

1 = manual programmingDO2 0 Setting slave in programming mode X X X 0 = normal operation

1 = programming modeDO3 0 Programming mode X - - 0 = manual programming

1 = automatic programming0 Function of high visibility position

indicator- - X 0 = activated

1 = deactivatedDO4 0 Inversion of feedback signals - - X 0 = standard

1 = inversed

Specific data - AS-Interface

Page 21: db 4242 gb - GEMU Valves, Measurement and …EN 61000-6-2acc. to AS-Interface Spec. 3.0 EN 61000-6-2EN 61000-6-2 NEC marking:Class I, Division II, Groups C & D, T4 Approvals: 24 VAS-InterfaceIO-LinkDeviceNet

GEMÜ 4242www.gemu-group.com 21 / 28

Bit Default Function Version Logic

A2 A3 A4DO5 0 Inversion of LED colours - - X 0 = standard

1 = inversedDO6 0 Location function - - X 0 = deactivated

1 = activatedDO7 0 On-site programming - - X 0 = enabled

1 = disabled

1) Activation of outlet 4, only for double acting function (code 02)

Specific data - AS-Interface

Page 22: db 4242 gb - GEMU Valves, Measurement and …EN 61000-6-2acc. to AS-Interface Spec. 3.0 EN 61000-6-2EN 61000-6-2 NEC marking:Class I, Division II, Groups C & D, T4 Approvals: 24 VAS-InterfaceIO-LinkDeviceNet

www.gemu-group.com22 / 28GEMÜ 4242

Specific data - DeviceNet

General dataCommunication modes: Function, Polling, Change of state, Cyclic, Bit strobe

Identity

Class Inst. Attr. Function Value1h 1h 1h Vendor ID 869

2h Product Type 483h Product Code 42424h Rev. 2.2 1)

5h Status Device status according to DeviceNet specifications6h Series No. Continuous serial number7h Name 4242 DN combi switchbox

1) Use EDS file in accordance with revision status of the device

Note: Download EDS files from www.gemu-group.com

Net topology - DeviceNet systemTo avoid malfunction the trunk cable is fitted with resistors on both sides. The drop cables do not require bus ends.

V+V-

CAN_H120 Ω 1/4 W

CAN_LShield

Protectiveearth

Protectiveearth

Drop cable

120 Ω 1/4 W

Trunk cable

Maximum cable length

Baud rate [kBaud] Trunk cable Drop cable

Thick cable Thin cable Max. cable length perdrop cable

Max. drop cable accu-mulated length

125 500 m 100 m 6 m 156 m250 250 m 100 m 6 m 78 m500 100 m 100 m 6 m 39 m

Specific data - DeviceNet

Page 23: db 4242 gb - GEMU Valves, Measurement and …EN 61000-6-2acc. to AS-Interface Spec. 3.0 EN 61000-6-2EN 61000-6-2 NEC marking:Class I, Division II, Groups C & D, T4 Approvals: 24 VAS-InterfaceIO-LinkDeviceNet

GEMÜ 4242www.gemu-group.com 23 / 28

InputsBit Default Designation Function Logic0 0 State Valve 1 Status query pneumatic outlet 2

(pilot valve 1)0 = pneumatic outlet 2 vented1 = pneumatic outlet 2 pressurized

1 0 State Valve 2 Status query pneumatic outlet 4(pilot valve 2)

0 = pneumatic outlet 4 vented1 = pneumatic outlet 4 pressurized

2 0 Programmingmode Feedback for operating mode 0 = normal operation1 = programming mode

3 0 Position Closed Feedback CLOSED position 0 = process valve not in CLOSED position1 = process valve in CLOSED position

4 0 Position Open Feedback OPEN position 0 = process valve not in OPEN position1 = process valve in OPEN position

5 0 Calibrationmode Feedback calibration mode 0 = normal operation1 = calibration mode

6 0 Global warnings General warning 0 = warning not active1 = warning active

7 0 Global errors General error 0 = error not active1 = error active

As seen from the DeviceNet master, Class 64h, Inst. 1h, Attr. 1h

OutputsBit Default Designation Function Logic0 0 active valve 1 Activation of pneumatic outlet 2

(pilot valve 1)0 = pneumatic outlet 2 vented1 = pneumatic outlet 2 pressurized

1 0 active valve 2 Activation of pneumatic outlet 4 1)

(pilot valve 2)0 = pneumatic outlet 4 1)vented1 = pneumatic outlet 4 1)pressurized

2 not used3 0 Location function Location function 0 = location function not active

1 = location function active4 not used5 0 Manual

programmingManual programming mode 0 = manual programming mode not

active1 = manual programming mode active

6 0 Automaticprogramming

Automatic programming mode: 0 = automatic programming mode notactive1 = automatic programming mode active

7 not used

As seen from the DeviceNet master, Class 64h, Inst. 1h, Attr. 1h1) Activation of outlet 4, only for double acting function (code 02)

Specific data - DeviceNet

Page 24: db 4242 gb - GEMU Valves, Measurement and …EN 61000-6-2acc. to AS-Interface Spec. 3.0 EN 61000-6-2EN 61000-6-2 NEC marking:Class I, Division II, Groups C & D, T4 Approvals: 24 VAS-InterfaceIO-LinkDeviceNet

www.gemu-group.com24 / 28GEMÜ 4242

ParameterClass Inst. Attr. Parameter Lengt

hDatatype

Ac-cess

Stand-ard

value

Value range

Fh 1h 1h Inversion of LED colours 1 byte Boolean Get/Set 0 0 = standard1 = inversed

Fh 2h 1h Inversion of signals 1 byte Boolean Get/Set 0 0 = standard1 = inversed

Fh 3h 1h Function of high visibility 1 byte USINT Get/Set 3 0 = OFF1 = 33 %2 = 66 %3 = 100 %4 = Closed 100%; Open OFF5 = Closed OFF; Open 100%

Fh 4h 1h On site programming 1 byte Boolean Get/Set 0 0 = enabled1 = disabled

Fh 5h 1h Switch Point OPEN request 1 byte USINT Get/Set 25 3 % – 97 %Fh 6h 1h Switch Point OPEN real 1 byte USINT Get 0 Display of values 0 % – 100 %Fh 7h 1h Switch Point CLOSED request 1 byte USINT Get/Set 12 3 % – 97 %Fh 8h 1h Switch Point CLOSED real 1 byte USINT Get 0 Display of values 0 % – 100 %Fh 9h 1h Alarm stroke reduction OPEN 1 byte USINT Get/Set 1 0 = disabled

1 = 25 %2 = 50 %3 = 75 %

Fh Ah 1h Alarm stroke reductionCLOSED

1 byte USINT Get/Set 1 0 = disabled1 = 25 %2 = 50 %3 = 75 %

Fh Bh 1h Alarm opening time 1 byte USINT Get/Set 0 0 - 255 (0 = off)Fh Ch 1h Alarm closing time 1 byte USINT Get/Set 0 0 - 255 (0 = off)Fh Dh 1h Valve type 1 byte USINT Get/Set 0 0 = disabled

1 = valve NC2 = valve NO

Fh Eh 1h Fail state 1 byte USINT Get/Set 0 012

Fh Fh 1h Programmed position OPEN 2 byte UINT Get 0 Display of numerical values 0 -4092Fh 10h 1h Programmed position CLOSED 2 byte UINT Get 0

Fh 11h 1h Programmed stroke 2 byte UINT Get 0Fh 12h 1h Last position OPEN 2 byte UINT Get 0Fh 13h 1h Last position CLOSED 2 byte UINT Get 0Fh 14h 1h Last stroke 2 byte UINT Get 0Fh 15h 1h Valve position 2 byte UINT Get 0Fh 16h 1h Sensor error 1 byte USINT Get 0 0 = Sensor OK

1 = Sensor error position closed2 = Sensor error position open

Specific data - DeviceNet

Page 25: db 4242 gb - GEMU Valves, Measurement and …EN 61000-6-2acc. to AS-Interface Spec. 3.0 EN 61000-6-2EN 61000-6-2 NEC marking:Class I, Division II, Groups C & D, T4 Approvals: 24 VAS-InterfaceIO-LinkDeviceNet

GEMÜ 4242www.gemu-group.com 25 / 28

Class Inst. Attr. Parameter Length

Datatype

Ac-cess

Stand-ard

value

Value range

Fh 17h 1h Programing error 1 byte USINT Get 1 0 = Programming OK1 = not calibrated2 = no stroke3 = stroke < min. stroke4 = Sensor error position closed5 = Sensor error position open6 = Sensor error position closed+ open

Fh 18h 1h Pneumatic error 1 byte USINT Get 0 0 = Pneumatic OK1 = Pneumatic error positionclosed2 = Pneumatic error positionopen3 = Pneumatic error middleposition

Fh 19h 1h Internal error 1 byte USINT Get 0 0 = Device OK1 = un-valid crc-check2 = un-valid serial number3 = Memory error

Fh 1Ah 1h Stroke reduction warning 1 byte USINT Get 0 0 = Stroke OK1 = Stroke reduction positionclosed2 = Stroke reduction positionopen3 = Stroke reduction positionclosed + open

Fh 1Bh 1h Valve cycles user 4 byte UDINT Get/Set 0 Resettable to 0, display of numerical values 0 - 429496729

Fh 1Ch 1h Valve cycles total 4 byte UDINT Get 0 Display of numerical values 0 - 429496729

Specific data - DeviceNet

Page 26: db 4242 gb - GEMU Valves, Measurement and …EN 61000-6-2acc. to AS-Interface Spec. 3.0 EN 61000-6-2EN 61000-6-2 NEC marking:Class I, Division II, Groups C & D, T4 Approvals: 24 VAS-InterfaceIO-LinkDeviceNet

www.gemu-group.com26 / 28GEMÜ 4242

AccessoriesGEMÜ 4242000ZMA

Programming magnet

Ordering informationOrder number: 88377537

GEMÜ 1219

Cable socket / cable plug M12The GEMÜ 1219 is a connector (cable socket / cable plug) M12, 5-pin. Straight and/or 90° angled plugtype. Defined cable length or with threaded connection without cable. Various materials available for thefixing nut.

Ordering information

Description Length Order number5-pin, angle without cable 88205545

2 m cable 882055345 m cable 8820554010 m cable 8821091115 m cable 88244667

5-pin, straight without cable 882055442 m cable 882055425 m cable 8820554310 m cable 8827097215 m cable 88346791

8-pin, angle 5 m cable 883745748-pin, straight without cable 88304829

GEMÜ 4150

AS-Interface extension plugThe AS Interface Extension Plug serves to extend the network cable length from the current 100 m to 200m without a repeater. This is a passive component without an address in the AS-Interface fieldbus sys-tem. At the same time, the extension plug serves as a voltage monitor. Low voltages are signalled by theintegrated LED. The extension plug can also be employed in a standard network in order to improve thesignal quality and to reduce possible existing telegram error rate.

Ordering informationOrder number: 88262994

GEMÜ 4180

AS-Interface connectorAS-Interface connector (M12 on AS-Interface, flat cable)

Ordering informationOrder number: 88073531

Accessories

Page 27: db 4242 gb - GEMU Valves, Measurement and …EN 61000-6-2acc. to AS-Interface Spec. 3.0 EN 61000-6-2EN 61000-6-2 NEC marking:Class I, Division II, Groups C & D, T4 Approvals: 24 VAS-InterfaceIO-LinkDeviceNet

GEMÜ 4242www.gemu-group.com 27 / 28

GEMÜ SERVICE-IO-LINK-KIT

Programming setThe GEMÜ service IO-Link programming set comprises an IO-Link master, adapter and cable gland. Theprogramming kit is suitable for all GEMÜ IO-Link interfaces.

Ordering informationOrder number: 99072365

Accessories