50
Operation Manual OM AGS-1 Group: Chiller Part Number: 330412001 Date: July 2002 Supersedes: New GeneSys Air-Cooled Screw Compressor Chiller AGS 230A through AGS 475A Software Version AGSU30101B 60 Hertz

Date: July 2002 Supersedes: New - Daikin AppliedOperation Manual OM AGS-1 Group: Chiller Part Number: 330412001 Date: July 2002 Supersedes: New GeneSys Air-Cooled Screw Compressor

  • Upload
    others

  • View
    2

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Date: July 2002 Supersedes: New - Daikin AppliedOperation Manual OM AGS-1 Group: Chiller Part Number: 330412001 Date: July 2002 Supersedes: New GeneSys Air-Cooled Screw Compressor

Operation Manual OM AGS-1

Group: Chiller

Part Number: 330412001Date: July 2002Supersedes: New

GeneSys Air-Cooled Screw Compressor Chiller

AGS 230A through AGS 475ASoftware Version AGSU30101B60 Hertz

Page 2: Date: July 2002 Supersedes: New - Daikin AppliedOperation Manual OM AGS-1 Group: Chiller Part Number: 330412001 Date: July 2002 Supersedes: New GeneSys Air-Cooled Screw Compressor

OM AGS-1 2

Table Of ContentsFEATURES OF THE CONTROL PANEL.....................................................................4

GENERAL DESCRIPTION.............................................................................................5

General Description ............................................................................. 5Control Architecture ............................................................................ 5

COMPONENT DESCRIPTION ......................................................................................6

Unit and Circuit Controller Description .............................................. 6

CONTROL OPERATION................................................................................................7

CIRCUIT CONTROLLER...............................................................................................7

Inputs/Outputs...................................................................................... 7Set Points ............................................................................................. 8Stop Alarms ......................................................................................... 10Events .................................................................................................. 11Circuit Operating Mode....................................................................... 12Compressor Staging............................................................................. 12Compressor Capacity Control.............................................................. 12Capacity Overrides – Limits of Operation........................................... 13Pumpdown........................................................................................... 14Condenser Fan Control ........................................................................ 15Oil Return Solenoid ............................................................................. 16EXV Control........................................................................................ 17

UNIT CONTROLLER......................................................................................................19

Inputs/Outputs...................................................................................... 19Events .................................................................................................. 23Unit Mode Selection ............................................................................ 23Unit Enable .......................................................................................... 24Evaporator Pump State Control ........................................................... 24Evaporator Heater Control................................................................... 24Leaving Water Temperature (LWT) Reset ........................................... 25Building Automation System (BAS) Interface .................................... 27

FIELD WIRING DIAGRAM ...........................................................................................28

USING THE CONTROLLER..........................................................................................29

Security................................................................................................ 31Unit Controller Menus ......................................................................... 32SET Screen Definitions ....................................................................... 35Circuit Controller Menus ..................................................................... 38Screen Definitions ............................................................................... 38

SEQUENCE OF OPERATION........................................................................................43

START-UP AND SHUTDOWN .......................................................................................46

Seasonal Start-up ................................................................................. 46Temporary Shutdown........................................................................... 46Start-up After Temporary Shutdown.................................................... 47Extended (Seasonal) Shutdown ........................................................... 47Start-up After Extended (Seasonal) Shutdown .................................... 48

Our facility is ISO CertifiedInitial Issue February 2002

"McQuay" is a registered trademark of McQuay International, "Information covers the McQuay International products at the time ofpublication and we reserve the right to make changes in design and construction at anytime without notice"

Page 3: Date: July 2002 Supersedes: New - Daikin AppliedOperation Manual OM AGS-1 Group: Chiller Part Number: 330412001 Date: July 2002 Supersedes: New GeneSys Air-Cooled Screw Compressor

OM AGS-1 3

This manual provides setup, operating, and troubleshooting information for the McQuayMicroTech ΙΙ controller for Model AGS air-cooled rotary screw compressor chillers.Please refer to the current version of IMM AGS for information relating to the unit itself.

NOTE: This manual covers units with Software Version AGSU30101B. The softwareversion number can be viewed by pressing the MENU and ENTER keys (the two right keys)simultaneously. Then, pressing the MENU key will return to the Menu screen.

WARNINGElectric shock hazard. Can cause personal injury or equipment damage. This

equipment must be properly grounded. Connections to and service of the MicroTechcontrol panel must be performed only by personnel that are knowledgeable

in the operation of the equipment being controlled.

CAUTIONStatic sensitive components. A static discharge while handling electronic circuit

boards can cause damage to the components. Discharge any static electrical chargeby touching the bare metal inside the control panel before performing any service

work. Never unplug any cables, circuit board terminal blocks, or power plugs whilepower is applied to the panel.

NOTICEThis equipment generates, uses and can radiate radio frequency energy and, if not

installed and used in accordance with this instruction manual, may causeinterference to radio communications. Operation of this equipment in a residential

area is likely to cause harmful interference in which case the user will be required tocorrect the interference at his own expense.

McQuay International Corporation disclaims any liability resulting from anyinterference or for the correction thereof.

Temperature and Humidity ConsiderationsThe MicroTech ΙΙ controller is designed to operate within an ambient temperature range of -20°F to +149°F (-29°C to +65.1°C) with a maximum relative humidity of 95% (non-condensing).

Page 4: Date: July 2002 Supersedes: New - Daikin AppliedOperation Manual OM AGS-1 Group: Chiller Part Number: 330412001 Date: July 2002 Supersedes: New GeneSys Air-Cooled Screw Compressor

OM AGS-1 4

Features of the Control Panel

• Control of leaving chilled water within a ±0.2°F (±0.1°C) tolerance.• Readout of the following temperature and pressure readings:

• Entering and leaving chilled water temperature• Saturated evaporator refrigerant temperature and pressure• Saturated condenser temperature and pressure• Outside air temperature• Suction line, liquid line and discharge line temperatures - calculated superheat for discharge

and suction lines – calculated subcooling for liquid line

• Automatic control of primary and standby evaporator pumps.• History trend feature will constantly log chiller functions and set points. The controller will store

and display all accumulated data for recall.• Three levels of security protection against unauthorized changing of setpoints and other control

parameters.• Warning and fault diagnostics to inform operators of warning and fault conditions in plain

language. Al1 warnings, problems and faults are time and date stamped so there is no guessing ofwhen the fault condition occurred. In addition, the operating conditions that existed just prior toshutdown can be recalled to aid in isolating the cause of the problem.

• Twenty-five previous faults and related operating conditions are available.• Remote input signals for chilled water reset, demand limiting and unit enable.• Manual control mode allows the service technician to command the unit to different operating

states. Useful for system checkout.• BAS communication capability via LONMARK or BACnet standard protocols for all BAS

manufacturers.• Service Test mode for troubleshooting controller hardware.• Pressure transducers for direct reading of system pressures. Preemptive control of low evaporator

pressure conditions and high discharge temperature to take corrective action prior to a fault trip.

Page 5: Date: July 2002 Supersedes: New - Daikin AppliedOperation Manual OM AGS-1 Group: Chiller Part Number: 330412001 Date: July 2002 Supersedes: New GeneSys Air-Cooled Screw Compressor

OM AGS-1

General DescriptionGeneral DescriptionThe AGS MicroTech ΙΙ control system consists of microprocessor-based controllers thatprovide all monitoring and control functions required for the controlled, efficient operationof the chiller. The system consists of the following components:

• Unit Controller, one per chiller-controls unit functions and communicates with all othercontrollers. It is located in the control panel for circuit #1.

• Circuit Controller for each compressor/circuit on the chiller (two or three)-controlscompressor functions and can operate a compressor without the unit controller. Thecontrollers are located in their circuit's control panel that is mounted between condensercoil sections.

In addition to providing all normal operating controls, the MicroTech II control systemmonitors equipment protection devices on the unit and will take corrective action if thechiller is operating outside of it’s normal design conditions. If a fault condition develops,the controller will shut the compressor down and activate an alarm output. Importantoperating conditions at the time an alarm condition occurs are retained in the controller’smemory to aid in troubleshooting and fault analysis.

The system is protected by a password scheme that only allows access by authorizedpersonnel. The operator must enter the operator password into the controller's keypadbefore any setpoints can be altered.

Control ArchitectureFigure 1, Major Control Components

Chiller AACnet MS/TP

B

5

UnitController

Circuit #1Controller4x20 LCD

SolidState

Starter

pLAN

BACnet IPBACnet EthernetLonTalk

RS485/LON/Ethernet

RS485

(future)

4x20 LCD

(future)

EXV

Page 6: Date: July 2002 Supersedes: New - Daikin AppliedOperation Manual OM AGS-1 Group: Chiller Part Number: 330412001 Date: July 2002 Supersedes: New GeneSys Air-Cooled Screw Compressor

OM AGS-1 6

Component DescriptionUnit and Circuit Controller Description

Hardware StructureThe controllers are fitted with a 16-bit microprocessor for running the control program.There are terminals for connection to the controlled devices (for example: solenoid valves,expansion valves, chilled water pumps). The program and settings are saved permanently inFLASH memory, preventing data loss in the event of power failure without requiring aback-up battery. It also has remote communication access capability for BAS interface.

Each chiller has one unit controller and a circuit controller for each compressor circuit (twoor three depending on unit size). The controllers are connected and communicate via apLAN. The circuit controllers communicate with, and control the operation of, thecompressor's solid state starter and the circuit electronic expansion valve (EXV).

KeypadA 4 line by 20 character/line liquid crystal display and 6-button keypad is mounted on theunit and compressor controllers. Its layout is shown below.

Air Conditioning

ALARMVIEW

SET

<<<

The four arrow keys (UP, DOWN, LEFT, RIGHT) have three modes of use.• Scroll between data screens in the direction indicated by the arrows (default mode).• Select a specific data screen in the menu matrix using dynamic labels on the right side

of the display such as ALARM, VIEW, etc (this mode is entered by pressing the MENUkey). For ease of use, a pathway connects the appropriate button to its respective labelon the screen.

• Change field values in setpoint programming mode according to the following table:LEFT key = Default RIGHT key = CancelUP key = Increase (+) DOWN key = Decrease (-)

These four programming functions are indicated by one-character abbreviation on theright side of the display. This programming mode is entered by pressing the ENTERkey.

ENTER Key

MENU Key

ARROW Keys

Key-to-Screen Pathway

Page 7: Date: July 2002 Supersedes: New - Daikin AppliedOperation Manual OM AGS-1 Group: Chiller Part Number: 330412001 Date: July 2002 Supersedes: New GeneSys Air-Cooled Screw Compressor

OM AGS-1 7

Control OperationThis section on MicroTech II control is divided into five subsections:

• Circuit Controller, explains the functions of the circuit controller, see page 7.

• Unit Controller, explains the functions of the unit controller, see page 14.

• Using the Controller, explains how to navigate through the menus and how to makeentries, see page 29.

• Screen Description, details the content on the menu screens and how to use them, seepage 33

• Quick Reference Guide, brief description on how to perform commonly used tasks

Circuit Controller

Inputs/OutputsTable 1, Analog Inputs

# Description Signal Source Range1 Evaporator Pressure 0.1 to 0.9 VDC 0 to 132 psi2 Condenser Pressure 0.1 to 0.9 VDC 3.6 to 410 psi3 Liquid Pressure 0.1 to 0.9 VDC 3.6 to 410 psi4 Suction Temperature NTC Thermistor (10k@25°C) -58°F to 212°F5 Discharge Temperature NTC Thermistor (10k@25°C) -58° to 212°F6 Liquid Temperature NTC Thermistor (10k@25°C) -58 to 212°F7 Slide Load Indicator 4 to 20 mA 0 to 100%8 Open

These parameters are analog inputs to this controller. They are used internally as neededand are sent to the correct pLAN addresses for use by other controllers or displays.

Table 2, Analog Outputs# Description Output Signal Range1 Fan 1&2 VFD 0 to 10 VDC 20 to 60 Hz2 Open3 EXV Driver 0 to 10 VDC 0 to 1000 steps4 Open

These parameters are analog outputs from this controller. The values are sent to the correctpLAN addresses for use by other controllers or displays.

Table 3, Digital Inputs# Description Signal Signal1 Circuit Switch 0 VAC (Off) 24 VAC (Auto)2 Open3 Starter Fault 0 VAC (Fault) 24 VAC (No Fault)4 VFD Fault 0 VAC (Fault) 24 VAC (No Fault)

5 Oil DifferentialPressure Switch 0 VAC (Fault) 24 VAC (No Fault)

6 Mech High Pressure 0 VAC (Fault) 24 VAC (No Fault)7 Low Pressure Switch 0 VAC (Fault) 24 VAC (No Fault)8 Open9 Oil Level Sensor 0 VAC (Fault) 24 VAC (No Fault)

10 Open11 Open

Page 8: Date: July 2002 Supersedes: New - Daikin AppliedOperation Manual OM AGS-1 Group: Chiller Part Number: 330412001 Date: July 2002 Supersedes: New GeneSys Air-Cooled Screw Compressor

OM AGS-1 8

Table 4, Digital Outputs# Description Load Output OFF Output ON Voltage1 Compressor SSS Contact Relay Compressor off Compressor on 1202 M1 Contactor (fan 1) Contactor Coil Fans off Fans on 1203 M2 Contactor (fan 2) Contactor Coil Fans off Fans on 1204 M3 Contactor (fan 3) Contactor Coil Fans off Fans on 1205 M4 Contactor (fan 4) Contactor Coil Fans off Fans on 1206 M5 Contactor (fan 5 & 6) Contactor Coil Fans off Fans on 1207 Load/Unload Pulse Solenoid Hold load slide Move load slide 248 Load/Unload Select Relay Unload Load 249 M7 Contactor (fan 7 & 8) Contactor Coil Fans off Fans on 120

10 Oil Return Line Solenoid Closed Open11 Open12 Open

13 EXV Close Signal Contact EXV Follows0 – 10 VDC

EXV Closed, Ignores0 – 10 VDC 10

These parameters are digital outputs from this controller. Their values are sent to the correctpLAN addresses for use by other controllers or displays.

Set PointsThe following parameters in Table 5 are remembered during power off, are factory setto the Default value, and can be adjusted to any value in the Range column.

The PW (password) column indicates the password that must be active in order tochange the set point. Codes are as follows:

O = Operator,

M = Manager,

F = Factory setpoints not available for field adjustment

Page 9: Date: July 2002 Supersedes: New - Daikin AppliedOperation Manual OM AGS-1 Group: Chiller Part Number: 330412001 Date: July 2002 Supersedes: New GeneSys Air-Cooled Screw Compressor

OM AGS-1 9

Table 5, Circuit Controller Set PointsDescription Default Range PWCompressorCircuit mode enable Disable, enable, test MSlide control auto Auto, manual MSlide position 0 0-100 MCompressor Size 205 205,220,235 MClear Cycle Timers no No, yes MMaximum Slide Target 100.0 0-100.0% M

EXVEXV control auto Auto, manual MEXV position 0 0-6386 MPre-open timer 60 20-120 sec M

FansFan VFD enable Yes No, Yes MNumber of fans 6 6,8 MSaturated Condenser Temp Target 110.0 90.0 – 130.0 oF MStage 1 Up Deadband 5.0 1.0-20.0 oF MStage 2 Up Deadband 8.0 1.0-20.0 oF MStage 3 Up Deadband 10.0 1.0-20.0 oF MStage 4 Up Deadband 12.0 1.0-20.0 oF MStage 1 Down Deadband 8.0 1.0-20.0 oF MStage 2 Down Deadband 7.0 1.0-20.0 oF MStage 3 Down Deadband 6.0 1.0-20.0 oF MStage 4 Down Deadband 5.0 1.0-20.0 oF MVFD Max Speed 100% 90 to 110% MVFD Min Speed 25% 20 to 60% MForced Fantrol 1 1 1-8 MForced Fantrol 2 2 1-8 MForced Fantrol 3 3 1-8 M

SensorsEvap pressure offset 0 -10.0 to 10.0 psi MCond pressure offset 0 -10.0 to 10.0 psi MLiquid pressure offset 0 -10.0 to 10.0 psi MSuction temp offset 0 -5.0 to 5.0 deg MDischarge temp offset 0 -5.0 to 5.0 deg MLiquid temp offset 0 -5.0 to 5.0 deg MSlide Minimum Position 0 -15 to 15% MSlide Maximum Position 0 -15 to 15% M

Page 10: Date: July 2002 Supersedes: New - Daikin AppliedOperation Manual OM AGS-1 Group: Chiller Part Number: 330412001 Date: July 2002 Supersedes: New GeneSys Air-Cooled Screw Compressor

OM AGS-1 10

Circuit Operating ModeThe circuits on the chiller can each be individually enable or disabled. Test mode on eachcircuit can also be entered independent of the all other circuits. With the circuit switch on,the circuit mode set point offers settings of either enable or disable. This simply allows thecircuit to be disabled through a keypad setting.

Slide PositionEach compressor will estimate its slide load percentage from the present value of the slideload indicator. The percentage is based on the 4-20mA signal from the slide load indicator.A percentage value of 0 corresponds to approximately a 4mA signal, a percentage value of100 corresponds to approximately a 20mA signal.

Table 6, Automatically Adjusted LimitsThe following set point ranges will be adjusted based on selected options.

Low Evaporator PressureMode Range

Unit Mode = Cool 27 to 45 PsigUnit Mode = Cool w/Glycol, Ice w/ Glycol 10 to 45 Psig

Low Evaporator Pressure Hold and UnloadMode Range

Unit Mode = Cool 30 to 45 PsigUnit Mode = Cool w/Glycol, Ice w/ Glycol 20 to 45 Psig

Stop AlarmsStop Alarms (also known as "Faults" or "Equipment Protection Alarms") result in rapidcompressor shutdown, bypassing sequences such as pumpdown.

The following table identifies each shutdown alarm, gives the condition that causes thealarm to occur, and states the action taken because of the alarm. All stop alarms requiremanual reset. . Rapid stop alarms do not do a pumpdown before shutting off. All otheralarms will do a pumpdown. The occurrence of a circuit stop alarm only affects the circuiton which it occurred.

Table 7, Circuit Controller Stop AlarmsDescription Occurs When: Action Taken

Low Evaporator Pressure[Evaporator Press < Low Evap Pressure SP for time > Low

Evap Press Delay OR Evaporator Press < 5 psi ] ANDCompressor State = Run

Rapid Stop

High Condenser Pressure Cond Press > High Condenser Pressure Value (Note 1) Rapid StopMechanical High Pressure Digital Input 6 = Open Rapid Stop

Below Minimum Lift Pressure Cond Press < Min Sat Cond Value for time > Min Lift Delay SP(Note 2) Rapid Stop

High Discharge Temperature Temp > High Discharge Temperature SP Rapid StopLow Subcooling Calculated Subcooling < Low Subcooling SP for 300 seconds Rapid StopLow Oil Level DI 9 = Open for Time greater than Low Oil Level Delay AND the

Low Oil Level Event has occurred in the past hour Rapid Stop

High Oil Pressure Difference Digital Input 5 = Open for time greater than HighPressDiffDelay Rapid StopVFD Fault VFD option enabled and Digital Input 4 = Open PumpdownStarter Fault Digital Input 3 = Open Rapid StopEvap Pressure Sensor Fault Sensor shorted or open Rapid StopCond Pressure Sensor Fault Sensor shorted or open Rapid StopLiquid Line Pressure SensorFault Sensor shorted or open Rapid Stop

Suction Temperature SensorFault Sensor shorted or open Rapid Stop

Discharge TemperatureSensor Fault Sensor shorted or open Rapid Stop

Liquid Line TemperatureSensor Fault Sensor shorted or open Rapid Stop

Page 11: Date: July 2002 Supersedes: New - Daikin AppliedOperation Manual OM AGS-1 Group: Chiller Part Number: 330412001 Date: July 2002 Supersedes: New GeneSys Air-Cooled Screw Compressor

OM AGS-1 11

NOTES:1. Maximum Condenser Pressure Value

• If Sat Evap Temp < 32 thenShutdown value = 155 + 1.588(Sat Evap Temp – 32)

• If Sat Evap Temp >= 32 AND Sat Evap Temp < 40 thenShutdown value = 155

• If Sat Evap Temp >= 40 AND Sat Evap Temp < 55 thenShutdown value = 155 – 0.667(Sat Evap Temp – 40)

• If Sat Evap Temp >=55 thenShutdown value = 145

2. Minimum Saturated Condenser Value• If Sat Evap Temp < 35, then

Min Lift Value = 73• If Sat Evap Temp >= 35 and < 55, then

Min Lift Value = (6/5)(Sat Evap Temp – 35) + 73;• If Sat Evap Temp >= 55 then

Min Lift Value = 97

EventsAlso know as "Limit Alarms" or "Problems", these alarms do not cause compressorshutdown but instead limit operation of the chiller in some way as described in the “Action”column. . The occurrence of a circuit event only affects the circuit on which it occurred.

Table 8, Circuit Controller Event AlarmsDescription Occurs When: Action Reset

Low Evaporator Pressure -Hold

Pressure < Low Evap Pressure -Hold SP

Inhibitloading

Evap Press rises above(SP + 3psi)

Low Evaporator Pressure -Unload

Pressure < Low Evap Pressure -Unload SP Unload Evap Press rises above

(SP + 5psi)

High Lift Pressure - Hold Pressure > High Sat Cond Pressure- Hold Value

Inhibitloading

Cond Press drops below(Hold Value – 10psi)

High Lift Pressure - Unload Pressure > High sat Cond Pressure- Unload Value Unload Cond Press drops below

(Unload Value – 10psi)

Subcooling Low

EXV = Pressure Control ANDSubcool < Low Subcool SP OR

EXV = Subcool Control ANDSubcool < (the lowest of the Low

Subcool SP and sc target – 0.5oF)for longer than 5 minutes

None Subcool > set point orComp state = off

Discharge Superheat LowEXV Control = Pressure Control

AND Disc SH < Min SH Set Pointfor 10 minutes

Pumpdownand stop Comp state = off

Low Oil LevelDI9 = Open for Time greater than

Low Oil Level Delay AND more thanone hour since last occurrence

Rapid stop Comp state = off

Failed Pumpdown Circuit state = pumpdown for morethan the Pumpdown Time SP Stop N/A

Power Loss While RunningCircuit controller is powered up afterlosing power while compressor was

running

Delay start ofcompressor N/A

NOTES:

1. High Saturated Condenser Pressure – Hold Value• High Cond Hold Value = High Cond Pressure Value – 4oF

2. High Saturated Condenser Pressure – Unload Value• High Cond Unload Value = High Cond Pressure Value – 2oF

Page 12: Date: July 2002 Supersedes: New - Daikin AppliedOperation Manual OM AGS-1 Group: Chiller Part Number: 330412001 Date: July 2002 Supersedes: New GeneSys Air-Cooled Screw Compressor

OM AGS-1 12

Circuit Operating ModeThe circuits on the chiller can each be individually enabled or disabled. Test mode on each circuitcan also be entered independent of the all other circuits. With the circuit switch on, the circuit modeset point offers settings of either enable or disable. This simply allows the circuit to be disabledthrough a keypad setting.

Compressor StagingSlide Load IndicatorEach compressor estimates its slide load percentage from the present value of the slide load indicator.The percentage is based on the 4-20mA signal from the slide load indicator. A percentage value of 0corresponds to approximately a 4mA signal, a percentage value of 100 corresponds to approximatelya 20mA signal.

Multiple Compressor StagingThis section defines which compressor is the next one to start or stop.1. Can start/stop compressors according to an operator defined sequence.2. Can start compressors based on the number of starts (run hours if starts are equal) and

stop on run hours3. The above two modes can be combined so that there are two or more groups where all

compressors in the first group are started (based on number of starts/hours) before anyin the second group, etc. Conversely, all compressors in a group are stopped (based onrun hours) before any in the preceding group, etc.

Compressor Capacity ControlLeaving Water Control ModeCompressor capacity is determined by calculating a slide position target. Adjustment to theslide target for normal running conditions occurs every 10 seconds. For loading a maximumchange of 1% is allowed, and for unloading a maximum change of 2% is allowed. Thechange to the target is calculated as follows.

Chiller Mode = COOLWhen the chiller is in COOL mode, capacity of the compressor is adjusted to maintainleaving water temperature at the Active LWT set point while balancing the load betweenrunning circuits. Load balance offset, lwt error, and lwt slope are used to calculate a changein slide position as described below.

Load Balance Offset:Balance Offset = [Present slide load % – Average slide load %] (more than one compressorrunning)

where: Present slide load % = The present slide target value of this compressor.

Average slide load % = Average slide target of all other runningcompressors on the same chiller.

LWT Error = (Leaving Evaporator Water Temp) – (Active LWT set point).LWT Slope:Slope (deg/minute) = sum of last five LWT changes as calculated every 12 seconds

Slide target adjustment = [LWT Error + (LWT Slope x 2) – Load Balance Offset] / #Compressors Running

Chiller Mode = ICEIn ICE mode, the compressor capacity is increased at the maximum rate continuously until reachingthe maximum slide position. Load balancing, LWT error, and LWT slope are ignored.

Page 13: Date: July 2002 Supersedes: New - Daikin AppliedOperation Manual OM AGS-1 Group: Chiller Part Number: 330412001 Date: July 2002 Supersedes: New GeneSys Air-Cooled Screw Compressor

OM AGS-1 13

Capacity Overrides – Limits of OperationThe following two conditions override the automatic slide control when the chiller is inCOOL mode or ICE mode. These overrides keep the circuit from entering a condition inwhich it is not designed to run. Any compressor running with capacity limits because ofthese conditions will be considered to be at full load in the compressor staging logic.

1) Low Evaporator Pressure OverrideIf the compressor is running and the evaporator pressure drops below the Low EvaporatorPressure-Hold set point, the compressor will not be allowed to increase capacity. The slideposition target will be limited to a maximum value equal to the target at the time the holdcondition was triggered. This limit shall be active until the evaporator pressure reaches thehold set point plus 3 psi.

If the compressor is running above minimum load capacity and the evaporator pressuredrops below the Low Evaporator Pressure-Unload set point, the compressor will beginreducing capacity. The maximum allowed slide target will be adjusted down 5% every 5seconds until the evaporator pressure rises above the Low Evaporator Pressure-Unload setpoint. The slide target shall then be limited to the current value until the evaporator pressurerises to the unload set point plus 3 psi.

2) High Condenser Pressure OverrideIf the compressor is running and the condenser pressure rises above the High Lift PressureHold set point, the compressor will not be allowed to increase capacity. The slide positiontarget will be limited to a maximum value equal to the target at the time the hold conditionwas triggered. This limit shall be active until the condenser pressure drops 10 psi below thehold set point.

If the compressor is running above minimum load capacity and the condenser pressure risesabove the High Condenser Pressure Unload set point, the compressor will begin reducingcapacity. The maximum allowed slide target will be adjusted down 5% every 5 secondsuntil the condenser pressure drops below the High Condenser Pressure-Unload set point.The slide target shall then be limited to the current value until the condenser pressure dropsto 10 psi below the unload set point.

Maximum LWT Pulldown RateThe maximum rate at which the leaving water temperature can drop shall be limited by theMaximum Rate set point. A slope unload factor is used to reduce the slide target if thepulldown rate exceeds the Maximum Rate set point.

Soft LoadSoft Loading is a configurable function used to ramp up the unit capacity over a given time.The set points that control this function are:

• Soft Load – (ON/OFF)

• Begin Capacity Limit – (Unit %)

• Soft Load Ramp – (seconds)

The Soft Load Unit Limit increases linearly from the Begin Capacity Limit set-point to100% over the amount of time specified by the Soft Load Ramp set-point.

Page 14: Date: July 2002 Supersedes: New - Daikin AppliedOperation Manual OM AGS-1 Group: Chiller Part Number: 330412001 Date: July 2002 Supersedes: New GeneSys Air-Cooled Screw Compressor

OM AGS-1 14

Demand LimitThe maximum unit capacity can be limited by a 4 to 20 mA signal on the Demand Limitanalog input. This function is only enabled if the Demand Limit set point is set to ON. Themaximum unit capacity decreases linearly from 100% (at 20 mA) to the 0% (at 0mA).

Network LimitThe maximum slide load percentage of the compressor can be limited by a value sentthrough a BAS network connection and stored in the Network Limit variable. Thisfunction will be enabled if the Network Limit set point is set to ON.

Digital Output ControlEach digital output is controlled according to the following rules/algorithms and inaccordance with whether the Compressor Mode set point is set to AUTO or MANUAL(normal operation) or TEST (test mode). All outputs shall be initialized to OFF at poweron.

PumpdownWhen a circuit reaches a condition where the compressor needs to shut down normally, apumpdown will be performed. The slide target will automatically go to 0 while pumpingdown, and the compressor will run until the pumpdown pressure has been reached, or thepumpdown time has been exceeded.

Manual Slide Control ModeThe slide position on each circuit may be controlled manually. A setting on the compressorset points screen in each circuit controller allows the operator to select manual slide control.On the same screen, a slide target can be selected, from 0% to 100%.

Compressor SSS Contact• Normal Operation, This output is ON when the compressor is running or pumping

down. It is OFF for all other cases.

• Test Mode, This output cannot be turned on when in test mode.

Load and Unload Pulse• Normal Operation (AUTO), This output controls the compressor slide position in

order to reach the desired compressor capacity. Whenever a change in capacity isneeded, this output will pulse for 200 ms every 3 seconds until the slide position iswithin the deadband around the target.

• Test Mode, These outputs are set ON or OFF manually when Unit Mode = Test.

Load/Unload Select• Normal Operation (AUTO), The load/unload selector determines which solenoid will

be pulsed for a change in capacity. When unloading is required, this output should beoff. When loading of the compressor is required, the output should be on.

• Test Mode, These outputs are set ON or OFF manually when Unit Mode = Test.

Page 15: Date: July 2002 Supersedes: New - Daikin AppliedOperation Manual OM AGS-1 Group: Chiller Part Number: 330412001 Date: July 2002 Supersedes: New GeneSys Air-Cooled Screw Compressor

OM AGS-1 15

Condenser Fan ControlThe compressor must be running in order to stage fans on.

VFDCondenser pressure trim control is accomplished using an optional Low Ambient VFD onthe first two fans that turn on. This VFD control uses a proportional integral function todrive the saturated condenser temperature to a target value by changing the fan speed. Thetarget value is normally the same as the saturated condenser temperature target set point.

If a fan VFD is present on the circuit, the VFD will start the fans when the saturatedcondenser temperature goes above the temperature target.

Stage Up CompensationIn order to create a smoother transition when another fan is staged on, the VFD compensatesby slowing down initially. This is accomplished by adding the new fan stage up deadbandto the VFD target. The higher target causes the VFD logic to decrease fan speed. Then,every 10 seconds, 0.5oF is subtracted from the VFD target until it is equal to the saturatedcondenser temperature target set point. This will allow the VFD to slowly bring thesaturated condenser temperature back down.

Fantrol

Fan Stages Without VFD OptionIf the VFD option is not enabled, there are 8 stages of fantrol available with 8 fan circuits,and 6 stages available on 6 fan circuits. Although fans 5/6 and 7/8 are controlled by onecontactor each, more stages are created by using virtual stages. See the table below:

Table 9, Fantrol StagingFantrol Stage Fans On

1 12 1,23 1,2,34 1,2,3,45 1,2,4,5,66 1,2,3,4,5,67 1,2,3,5,6,7,88 1,2,3,4,5,6,7,8

Fan Stages With VFD OptionWhen the VFD option is enabled, the first two fans are controlled by the fan VFD. Thisleaves 6 stages of fantrol available with 8 fan circuits, and 4 stages available on 6 fancircuits. Although fans 5/6 and 7/8 are controlled by one contactor each, more stages arecreated by using virtual stages. See the table below:

Table 10, Fantrol Staging with VFDFantrol Stage Fans On

1 1,2,32 1,2,3,43 1,2,4,5,64 1,2,3,4,5,65 1,2,3,5,6,7,86 1,2,3,4,5,6,7,8

Page 16: Date: July 2002 Supersedes: New - Daikin AppliedOperation Manual OM AGS-1 Group: Chiller Part Number: 330412001 Date: July 2002 Supersedes: New GeneSys Air-Cooled Screw Compressor

OM AGS-1 16

Staging UpThere are four Stage Up dead bands that apply to the Fantrol stages. Stages one throughthree use their respective dead bands. Stage four to eight share the fourth Stage-Up deadband.

When the saturated condenser temperature is above the Target + the active deadband, aStage Up error is accumulated.

Stage Up Error Step = Saturated Condenser Refrigerant temperature – (Target + Stage Updead band)

The Stage Up Error Step is added to Stage Up Accumulator once every Stage Up ErrorDelay seconds. When Stage Up Error Accumulator is greater than the Stage Up Error SetPoint another stage is added.

When a stage up occurs or the saturated condenser temperature falls back within the StageUp dead band the Stage Up Accumulator is reset to zero.

Forced Fan Stage At StartFans may be started simultaneously with the compressor based on outdoor ambienttemperature. When the compressor starts, a fantrol stage is forced based on the followingtable.

Table 11, Startup Fan StagingOAT Fantrol Stage At Start

> 75 oF Forced Fantrol 1 SP> 90 oF Forced Fantrol 2 SP

> 105 oF Forced Fantrol 3 SP

Staging DownThere are four Stage Down dead bands. Stages one through three use their respective deadbands. Stages four to eight share the fourth Stage Down dead band.

When the saturated condenser refrigerant temperature is below the Target – the activedeadband, a Stage Down error is accumulated.

Stage Down Error Step = (Target - Stage Down dead band) - Saturated CondenserRefrigerant temperature

The Stage Down Error Step is added to Stage Down Accumulator once every Stage DownError Delay seconds. When the Stage Down Error Accumulator is greater than the StageDown Error Set Point another stage of condenser fans turned off.

When a stage down occurs or the saturated temperature rises back within the Stage Downdead band the Stage Down Error Accumulator is reset to zero.

Oil Return SolenoidThe oil return solenoid is on any time the compressor is running and any of the followingoccurs:

Slide position target < 60 AND Discharge superheat > 20

Slide position target >= 60 AND Discharge superheat > 50

Oil Level input = open AND Discharge superheat > 20

Test ModeThis output is set ON or OFF manually when Unit Mode = Test.

Page 17: Date: July 2002 Supersedes: New - Daikin AppliedOperation Manual OM AGS-1 Group: Chiller Part Number: 330412001 Date: July 2002 Supersedes: New GeneSys Air-Cooled Screw Compressor

OM AGS-1 17

Analog Output ControlEach analog output is controlled according to the following rules/algorithms. All outputsshall be initialized to 0 at power on.

EXV ControlThree different EXV control modes are used. Any time the EXV is not in one of thesecontrol modes, it will be closed. For any of the control modes, the EXV position is limitedto a range based on the slide position target. The table below shows the EXV range for eachsize compressor at minimum and maximum capacity. The minimum and maximum valuesvary linearly with slide position, defining a new EXV control range for every change inslide position.

Table 12, EXV/Slide PercentageCompressor Size

EXV Slide %205MM 220mm 235mm

Min 0 250 250 250Max 0 3000 3000 3000Min 100 870 1080 1300Max 100 3400 4200 5000

Based on the values in the above table, the EXV control range varies as shown in the tablebelow. The shaded area the control range.

Figure 2, EXV Control Range

Max EXV@ 100%

100

Max EXV@ 0%

Min EXV@ 0%

EXV Control Range

0 Slide Position (%)

EXVSteps

Min EXV@ 100%

Pre-OpenAt the time of a start request, if the evaporator saturated temperature is less than or equal toLWT + 5 oF the EXV will perform a pre-open function. This process insures that sufficientliquid refrigerant resides in the evaporator to avoid low pressure situations at startup.During pre-open, the EXV will open to 3000 steps while the saturated evaporatortemperature is less than the LWT. The EXV will move to 250 steps when the saturatedevaporator temperature is equal to or greater than the LWT.

The EXV must be in the pre-open state for a time equal to the pre-open timer set pointbefore the compressor will start. This state may be skipped if the start request occurs andthe evaporator saturated temperature is greater than LWT + 5 oF. In this case, the EXVwould go straight to pressure control.

Page 18: Date: July 2002 Supersedes: New - Daikin AppliedOperation Manual OM AGS-1 Group: Chiller Part Number: 330412001 Date: July 2002 Supersedes: New GeneSys Air-Cooled Screw Compressor

OM AGS-1

Pressure ControlThe EXV will be in pressure control mode after startup. In this mode, the EXV controlsdischarge superheat with adjustments to the evaporator pressure target. A proportionalintegral function is used to keep the evaporator pressure at the target. If the evaporator LWTis less than or equal to 60oF, then the base control pressure will be equal to the lowevaporator pressure inhibit set point. If the evaporator LWT is more than 60oF, then the basecontrol pressure will be higher. This pressure value varies as shown by the following graph,until it reaches a maximum of 52 psi.

Figure 3, Pressure Control

52

PRESSURE(PSI)

18

The pressure control target may be adjusted if the discharge superheat is not within anacceptable range. If the superheat is less than 20oF, the pressure target will be reduced by avalue equal to the low superheat error. If the superheat is more than 40oF, the pressure targetwill be increased by a value equal to the high superheat error. At any time, the adjustedtarget pressure cannot go below the low evaporator inhibit set point, or above 52 psi.

This mode of EXV control will transition to Subcool Control when two conditions are met.The evaporator LWT must be less than or equal to 60oF and the discharge superheat must bemore than 20oF. If the discharge superheat reaches 20oF and the LWT is still higher than60oF, the compressor may begin increasing capacity. If the superheat reaches 20oF while theLWT is less than 60oF, then the EXV will begin subcool control.

Subcool ControlAfter completing pressure control, the EXV transitions to the primary mode of operation,subcool control. In this mode, subcooling is controlled by the EXV, with adjustments to thesubcool target based on discharge superheat. The base subcool target varies linearly from 9to 20oF as slide position changes from 0 to 100%.

The base subcool target value is adjusted when the discharge superheat is less than 20oF orgreater than 40oF. For every degree below the minimum, the subcool target is adjusted uptwo degrees. Similarly, for every degree above the maximum, the subcool target is adjusteddown two degrees. The adjusted subcool target is limited to a minimum of 2oF.

The EXV may transition from subcool control back to pressure control. This occurs whenthe LWT is greater than 60oF.

LowEvapINH SP

90 60 LWT (oF)

Page 19: Date: July 2002 Supersedes: New - Daikin AppliedOperation Manual OM AGS-1 Group: Chiller Part Number: 330412001 Date: July 2002 Supersedes: New GeneSys Air-Cooled Screw Compressor

OM AGS-1 19

Manual EXV ControlThe EXV position can be set manually. When this option is turned on, the EXV position isequal to the manual EXV position setting any time the compressor is in the run state. Whilein manual EXV control, the EXV will still automatically go fully closed when thecompressor is off or pumping down.

History StorageThe number of starts and total compressor run hours is maintained in non-volatile memoryand placed on the pLAN.

Unit Controller

Inputs/OutputsTable 13, Analog InputsThe following parameters are analog inputs to this controller. They are used internally asneeded and are sent to the correct pLAN addresses for use by other controllers or displays.

# Description Signal Source Range1 Outdoor Ambient Temperature NTC Thermistor (10k@25°C) -58°F to 212°F2 Leaving Evaporator Water Temperature NTC Thermistor (10k@25°C) -58°F to 212°F3 Entering Evaporator Water Temperature NTC Thermistor (10k@25°C) -58°F to 212°F4 Demand Limit 4-20 mA Current 25-100 %RLA5 Chilled Water Reset 4-20 mA Current 0 to max reset

Table 14, Digital InputsThe following parameters are digital inputs to this controller. They are used internally asneeded and are sent to the correct pLAN addresses for use by other controllers or displays.

# Description Signal Signal1 Unit Switch 0 VAC (Stop) 24 VAC (On)2 Remote Switch 0 VAC (Stop) 24 VAC (Start)3 Evaporator Water Flow Switch 0 VAC (No Flow) 24 VAC (Flow)4 Mode Switch 0 VAC (Cool) 24 VAC (Ice)5 Open6 Open

Table 15, Digital OutputsThese parameters are digital outputs from this controller. Their values are sent to the correctpLAN addresses for use by other controllers or displays.

# Description Load Output OFF Output ON1 Open2 Evaporator Water Pump 1 Pump Contactor Pump OFF Pump ON3 Evaporator Water Pump 2 Pump Contactor Pump OFF Pump ON4 Evap Heaters Heater relay Heater OFF Heater ON5 Open6 Open7 Open8 Alarm Remote A;arm No Alarm Stop Alarm

Page 20: Date: July 2002 Supersedes: New - Daikin AppliedOperation Manual OM AGS-1 Group: Chiller Part Number: 330412001 Date: July 2002 Supersedes: New GeneSys Air-Cooled Screw Compressor

OM AGS-1 20

Set PointsThe “Type: column defines whether the set point is part of a coordinated set of duplicate setpoints in different controllers. There are three possibilities as given below:

• N = Normal set point - Not copied from, or copied to, any other controller

• M = Master set point - Set point is copied to all controllers in the “Sent To” column

• S = Slave set point - Set point is a copy of the master set point (in the Unit controller)

At power-up the slave node checks if the master node is operational and if so, it sets its copyof the set point equal to the master’s. Otherwise, the set point remains unchanged. Duringnormal operation, any time the master set point changes the slave is updated as well.

The PW (password) column indicates the password that must be active in order to changethe set point. Codes are as follows:

• O = Operator

• M = Manager

Page 21: Date: July 2002 Supersedes: New - Daikin AppliedOperation Manual OM AGS-1 Group: Chiller Part Number: 330412001 Date: July 2002 Supersedes: New GeneSys Air-Cooled Screw Compressor

OM AGS-1 21

Table 16, Unit Controller Set PointsDescription Default Range Type PWUnitUnit Enable OFF OFF, ON N O

Unit Mode COOL COOL, COOL w/Glycol, ICEw/Glycol, TEST M O

Available Modes COOLCOOL, COOL w/Glycol,

COOL/ICE w/Glycol,ICE w/Glycol, TEST

N M

Control source SWITCHES SWITCHES, KEYPAD,NETWORK N O

Display UnitsLanguage

BAS Protocol NONE NONE, BACnet, LonWorks,CAREL, MODBUS, N2 N M

Ident numberBaud Rate

UnitCool LWT 44. 0°F 20.0(40.0) to 60.0 °F M OIce LWT 25.0°F 20.0 to 38.0°F M OStartup Delta T 10.0°F 0.0 to 10.0 °F M OStop Delta T 3.0°F 0.0 to 3.0 °F M OStage Delta T 2.0°F 0.0 to 3.0 °F M OMax Pulldown 0.5 0.1-5.0 deg/min M MEvap pump control #1 Only #1 Only, #2 Only N MEvap Recirculate 30 sec 0 to 300 sec N MLWT Reset Type NONE NONE, RETURN, 4-20mA, OAT N MMax Reset 0.0°F 0.0 to 20.0 °F N MStart Reset Delta T 10. 0°F 0.0 to 20.0 °F N MSoft Load no No,yes N MBegin Capacity Limit 40 20-100% N MSoft Load Ramp 20 1-60 minutes N MDemand Limit no No,yes N M

CompressorsSequence # Cir 1 1 1-3 M MSequence # Cir 2 1 1-3 M MSequence # Cir 3 1 1-3 M MMax Compressors On 3 1-3 M MStart-start timer 20 15-60 minutes M MStop-start timer 5 3-20 minutes M MPumpdown pressure 25.0 10.0-30.0 psi M MPumpdown time limit 120 0-180 sec M M

AlarmsLow Evap Pressure-Unload 28 psi 15(28) to 45 psi M MLow Evap Pressure-Hold 30 psi 15(30) to 45 psi M MLow Oil Level Delay 120 10-180 sec M MHigh Oil Press Diff Delay 15 0-60 sec M MMin Lift Delay 30 10-120 sec M MHigh Discharge Temperature 200 F 150 to 200 F M MLow Subcooling 5 F 0 to 10 F M MEvap Flow Proof 3 sec 3 to 120 sec N MLow Ambient Lockout 55 °F 0(35) to 70 °F N MEvaporator Water Freeze 36 °F 15(34) to 42 °F N M

SensorsOAT sensor offset 0 -5.0 to 5.0 deg N MLWT sensor offset 0 -5.0 to 5.0 deg N MEWT sensor offset 0 -5.0 to 5.0 deg N M

These parameters are remembered during power off, are factory set to the Default value, and canbe adjusted to any value in the Range column.

Page 22: Date: July 2002 Supersedes: New - Daikin AppliedOperation Manual OM AGS-1 Group: Chiller Part Number: 330412001 Date: July 2002 Supersedes: New GeneSys Air-Cooled Screw Compressor

OM AGS-1 22

Automatic Adjusted LimitsThe following set point ranges will be adjusted based on selected options.

Table 17, Evaporator Leaving Water Temperature RangeMode Range

Unit Mode = Cool 40 to 60°FUnit Mode = Cool w/Glycol, Ice, Ice w/Glycol 20 to 60°F

Table 18, Evaporator Freeze Temperature RangeMode Range

Unit Mode = Cool 34 to 42°FUnit Mode = Cool w/Glycol, Ice, Ice w/Glycol 15 to 42°F

Table 19, Low Evaporator Pressure InhibitMode Range

Unit Mode = Cool 30 to 45 PsigUnit Mode = Cool w/Glycol, Ice w/Glycol 15 to 45 Psig

Table 20, Low Evaporator Pressure UnloadMode Range

Unit Mode = Cool 28 to 45 PsigUnit Mode = Cool w/Glycol, Ice w/Glycol 15 to 45 Psig

Table 21, Low Ambient Lockout Temperature RangeFan VFD Range

Fan VFD = N 35– 60°FFan VFD = Y 0 – 60°F

Stop (Shutdown) AlarmsThis table identifies each shutdown alarm, gives the condition that causes the alarm tooccur, and states the action taken as a result of the alarm. (See the “Stop Alarms” sectionunder the Circuit Controller for a description of these alarms.)

Table 22, Unit Stop AlarmsDescription Occurs When: Action Taken

No Evaporator Water Flow Evap Pump State = RUN AND Evap Flow DigitalInput = No Flow for time > Flow Proof SP Rapid Stop

Evaporator Freeze Protect Evap LWT goes below evap freeze protect setpoint Rapid Stop

Leaving Evaporator WaterTemperature Sensor Fault Sensor shorted or open Rapid Stop

Outside Air Temperature SensorFault Sensor shorted or open Normal Shutdown

pLAN Failure No other controller found on the pLAN for 60seconds Rapid Stop

Page 23: Date: July 2002 Supersedes: New - Daikin AppliedOperation Manual OM AGS-1 Group: Chiller Part Number: 330412001 Date: July 2002 Supersedes: New GeneSys Air-Cooled Screw Compressor

OM AGS-1 23

EventsThe following “alarms” only generate a warning message to the operator. Chiller operationis not affected. They are logged in the Event Log with a time stamp.

Table 23, Unit Event AlarmsDescription Occurs When: Action Taken Reset

Entering Evaporator TemperatureSensor Fault

Sensor is open orshorted

Cannot use return watertemperature control Automatic

Unit Mode SelectionThe overall operating mode of the chiller is set by the Unit Mode Set Point with options ofCOOL, COOL w/Glycol, ICE w/Glycol, and TEST. This set point can be altered by thekeypad, BAS, and Mode input. Changes to the Unit Mode Set Point are controlled by twoadditional set points.

• Available Modes Set Point: Determines the operational modes available at any timewith options of COOL, COOL w/Glycol, COOL/ICE w/Glycol, and TEST

• Control Source Set Point: Determines the source that can change the Unit Mode SetPoint with options of KEYPAD (pCO2), NETWORK, or SWITCHES.

When the Control source is set to KEYPAD, the Unit Mode stays at its previous setting untilchanged by the operator. When the Control source is set to BAS, the most recent BASmode request goes into effect even if it changed while the Control source was set toKEYPAD or DIGITAL INPUTS.

Changing the Unit Mode Set Point can be accomplished according to the following table.NOTE: An “x” indicates that the value is ignored.

Control SourceSet Point

ModeInput Keypad Entry BAS

RequestAvailable Modes

Set Point Unit Mode

x x x x COOL COOLx x x x COOL w/Glycol COOL w/Glycol

SWITCHES OFF x x COOL/ICE w/Glycol COOL w/GlycolSWITCHES ON x x COOL/ICE w/Glycol ICE w/Glycol

KEYPAD x COOL w/Glycol x COOL/ICE w/Glycol COOL w/GlycolKEYPAD x ICE w/Glycol x COOL/ICE w/Glycol ICE w/Glycol

NETWORK x x COOL COOL/ICE w/Glycol COOL w/GlycolNETWORK x x ICE COOL/ICE w/Glycol ICE w/Glycol

x x x x TEST TEST

Unit Test ModeThe unit test mode allows manual testing of all controller outputs. Entering this moderequires the following conditions.

• Unit OFF input = OFF (i.e. entire chiller is shut down).• Manager password active.• Available Unit Mode set point = TESTA test menu can then be selected to allow activation of the outputs. It is possible to switcheach digital output ON or OFF and set the analog outputs to any value.

Page 24: Date: July 2002 Supersedes: New - Daikin AppliedOperation Manual OM AGS-1 Group: Chiller Part Number: 330412001 Date: July 2002 Supersedes: New GeneSys Air-Cooled Screw Compressor

OM AGS-1

Unit EnableEnabling and disabling the chiller is controlled by the Unit Enable Set Point with options ofOFF and ON. This set point can be altered by the Unit OFF input, Remote input, keypadentry, and BAS request. The Control Source Set Point determines which sources can changethe Unit Enable Set Point with options of SWITCHES, KEYPAD or NETWORK.

Changing the Unit Enable Set Point can be accomplished according to the following table.NOTE: An “x” indicates that the value is ignored.

Unit OffInput

Control SourceSetPoint

RemoteInput

KeypadEntry

BASRequest

UnitEnable

OFF x x x x OFFx SWITCHES OFF x x OFF

ON SWITCHES ON x x ONON KEYPAD x OFF x OFFON KEYPAD x ON x ONON NETWORK x x OFF OFFON NETWORK OFF x x OFFON NETWORK ON x ON ON

Evaporator Pump State ControlOperation of the evaporator pump is controlled by the state-transition diagram shown below.

The pump output used will be determallows the operator to select either puthe Evap State is set to START or RUOFF.

Evaporator Heater CoEvaporator heaters are controlled by evaporator LWT is less than the watethe LWT is more than the freeze set p

OFF

RUNTEST:

TEST: Unit State=OFF & All Comp State=OFF &NO Evap water freeze condition

TEST: Unit State = AUTO ANDAt least one circuit is enabled for startOREvap water freeze condition

T N

Power ON

EST: Unit State=OFF & All Comp State=OFF &O Evap water freeze condition

24

ined by the Evap Pump Control set point. This settingmp #1 or pump #2. The selected output will be ON ifN. Both outputs will be OFF if the Evap State is set to

ntrolthe unit controller. This output is turned on when ther freeze set point + 2oF. The output is turned off whenoint + 4oF.

START Flow OK for Evap Recirc Time

Page 25: Date: July 2002 Supersedes: New - Daikin AppliedOperation Manual OM AGS-1 Group: Chiller Part Number: 330412001 Date: July 2002 Supersedes: New GeneSys Air-Cooled Screw Compressor

OM AGS-1 25

Leaving Water Temperature (LWT) ResetThe Active Leaving Water variable is set to the current Leaving Water Temperature (LWT)set point unless modified by one of the reset methods below. (The current LWT set point isCool LWT or Ice LWT as determined by the chiller mode.) The type of reset in effect isdetermined by the LWT Reset Type set point.

Reset Type – NONEThe Active Leaving Water variable is set equal to the current LWT set point.

Reset Type – RETURNThe return water temperature adjusts the Active Leaving Water variable. When the chillermode = COOL, the Active Leaving Water variable is reset using the following parameters:

1. Cool LWT set-point2. Max Reset Delta T set-point3. Start Reset Delta T set-point4. Evap Delts-TReset is accomplished by changing the Active Leaving Water variable from the Cool LWTset point to the Cool LWT set-point + Max Reset set-point as the EWT – LWT (Evap delta t)varies from the Start Reset Delta T set-point to 0.

Figure 4, Return Water Reset

Start Reset Delta T

Cool LWT+Max Reset(54)

Cool LWT Set-Point(44)

Return Reset

0

Max Reset(10)

Evap Delta T (oF)

ActiveLWT(oF)

Page 26: Date: July 2002 Supersedes: New - Daikin AppliedOperation Manual OM AGS-1 Group: Chiller Part Number: 330412001 Date: July 2002 Supersedes: New GeneSys Air-Cooled Screw Compressor

OM AGS-1 26

Reset Type – 4-20 mAThe Active Leaving Water variable is adjusted by the 4 to 20 mA reset analog input.

Figure 5, 4-20 mA Reset

20 ma

(54.0°F)

Cool LWT Set-Point(44.0°F)

4 ma

LWT Reset (Cool mode)(temperatures are examples only)

0 ma

Max Reset Delta T(10.0°F)

Reset Type – Outside Air Temperature (OAT)The Active Leaving Water variable is reset based on the outdoor ambient temperature.Parameters used:

1. Cool LWT set point

2. Max Reset set point

3. OAT

Reset is 0 if the outdoor ambient temperature is greater than 75 F. From 75 down to 60 Fthe reset varies linearly from no reset to the max reset at 60 F. At ambient temperatures lessthan 60 F, reset is equal to the Max Reset set point.

Figure 6, Outside Air Reset

75

Cool LWT+Max Reset(54)

Cool LWT Set-Point(44)

OAT Reset

60

Max Reset(10)

OAT (oF)

ActiveLWT(oF)

Page 27: Date: July 2002 Supersedes: New - Daikin AppliedOperation Manual OM AGS-1 Group: Chiller Part Number: 330412001 Date: July 2002 Supersedes: New GeneSys Air-Cooled Screw Compressor

OM AGS-1 27

Building Automation System (BAS) InterfaceProtocols SupportedThe following building automation system (BAS) protocols are supported. It shall bepossible to change the building automation interface without loading different software.

Table 24, Standard Protocol DataProtocol Physical Layer Data Rate Controller Other

BACnet/IP Ethernet 10 Base-T 10 Megabits/sec Color graphics SBC Conformance Class 3BACnet MSTP RS485 (TBD) pCO2 Unit Controller Conformance Class 2

LONworks FTT-10A 78kbits/sec pCO2 Unit Controller Chiller Profile

MODBUS RTU RS-485 (TBD) pCO2 Unit Controller

The following functions are available through the BAS where possible. Exact capabilitiesmay vary depending on the protocol in use.

• Enable/Disable chiller operation by setting the Unit Enable set point.

• Select the operating mode by setting the Unit Mode set point.

• Set the Cool LWT and Ice LWT set points.

• Set the Network Limit variable.

• Read all digital and analog I/O values.

• Read Enable status of chiller

• Read current operating mode and status (state) of chiller.

• Send a description of each alarm when it occurs.

NOTE: When ordered, detailed installation and operating manuals for the specific protocolordered will be included with the unit.

Page 28: Date: July 2002 Supersedes: New - Daikin AppliedOperation Manual OM AGS-1 Group: Chiller Part Number: 330412001 Date: July 2002 Supersedes: New GeneSys Air-Cooled Screw Compressor

OM AGS-1 28

Field Wiring Diagram

Figure 7, Typical Field Wiring Diagram, Circuit #1 Control Box

UNIT MAINTERMINAL BLOCK

DISCONNECT (BY OTHERS)

3 PHASEPOWERSUPPLY

GND LUG

TO COMPRESSOR(S)AND FAN MOTORS

TB1

1

120 VAC

TB1-2

81

2

BY OTHERS

ALARM BELLOPTION 120VAC

ALARM BELL RELAY

GND

TB1

60

66

897IF REMOTE STOP CONTROL IS USED, REMOVE LEAD 897

60

68

AUTOOFF

MANUAL

ON(BY OTHERS)

FROM TERM 60 TO 66.

ICE MODE SWITCH

GND

69

70

PE

4-20 MA FOR

(BY OTHERS)DEMAND LIMIT

AUTOOFF

MANUAL

ON

TIMECLOCK

(BY OTHERS)REMOTE STOP SWITCH

NOR. OPEN PUMP AUX.CONTACTS (OPTIONAL)

60

67

(BY OTHERS)

CHW FLOW SWITCH--MANDATORY--

4-20 MA FORCHW RESET

(BY OTHERS)

GND

71

72

PE

*

J11

COMMUNICATIONPORT

Rx-/Tx-

Rx+/Tx+

GND

CONTROLLER

FUSED CONTROLCIRCUIT TRANSFORMER

BLACK

WHITE

GREEN

85

2

(BY OTHERS)120 VAC 1.0 AMP MAX

N

120 VAC

82

2

(BY OTHERS)120 VAC 1.0 AMP MAX

N

120 VAC

CHW PUMP RELAY #1

CHW PUMP RELAY #2

330803901

Page 29: Date: July 2002 Supersedes: New - Daikin AppliedOperation Manual OM AGS-1 Group: Chiller Part Number: 330412001 Date: July 2002 Supersedes: New GeneSys Air-Cooled Screw Compressor

OM AGS-1 29

Using the Controller

4x20 Display & KeypadLayoutThe 4-line by 20-character/line liquid crystal display and 6-key keypad for both the circuitcontroller and unit controller is shown below.

Figure 8, Display (in MENU mode) and Keypad Layout

Air Conditioning

ALARMVIEW

SET

<<<

Note that each ARROW key has a pathway to a line in the display. Pressing an ARROWkey will activate the associated line when in the MENU mode.

Getting Started-Press the MENU key to get started The navigating procedures are thesame for both the unit controller and the circuit controller.

MENU KeyThe MENU key is used to switch between the MENU mode as shown in Figure 8 and theSCROLL mode as shown in Figure 9. The MENU mode is basically a shortcut to specificgroups of menus used for checking ALARMS, for VIEWING information, or to SETsetpoint values. The SCROLL mode allows the user to move about the matrix (from onemenu to another, one at a time) by using the four ARROW keys.

When in the MENU mode (as shown in Figure 8), pressing the LEFT ARROW key willselect the ALARM menus, the RIGHT ARROW key will select the VIEW menus and theUP key the SET menus. The controller will go the next lower menu in the hierarchy, andthen other menus can be accessed by using the ARROW keys. Pressing the MENU keyfrom any menu screen will automatically return to the MENU mode as shown in Figure 8.

Another way to navigate through the menus is to press the MENU key when in the MENUmode (as above). This will switch the controller to the SCROLL mode. The controller willautomatically go to the first screen as shown below (the upper-left menu on the menu matrixshown in Table 25 on page 32. From there the four ARROW keys can be used to scroll up,down, or across to any other menu.

ENTER Key

MENU Key

ARROW Keys (4)

Key to Screen

Page 30: Date: July 2002 Supersedes: New - Daikin AppliedOperation Manual OM AGS-1 Group: Chiller Part Number: 330412001 Date: July 2002 Supersedes: New GeneSys Air-Cooled Screw Compressor

OM AGS-1 30

Figure 9, Display (in SCROLL Mode) and Keypad Layout

Air Conditioning

VIEW UNIT STATUSUnit = COOLCompr. #1/#2=OFF/OFFEvap Pump = RUN

ENTER KeyPressing the ENTER key changes the function of the ARROW keys to the editing functionas shown below:

LEFT key, Default, changes a value to the factory-set default value.

RIGHT key, Cancel, cancels any change made to a value and returns to the originalsetting.

UP key, Increment, increases the value of the setting

DOWN key, Decrement decreases the value of a setting.

These four edit functions are indicated by one-character abbreviation on the right side of thedisplay (this mode is entered by pressing the ENTER key).

Most menus containing setpoint values have several different setpoints shown on one menu.When in a setpoint menu, the ENTER key is used to proceed from the top line to the secondline and on downward. The cursor will blink at the entry point for making a change. TheARROW keys (now in the edit mode) are used to change the setpoint as described above.When the change has been made, press the ENTER key to enter it. Nothing is changed untilthe ENTER key is pressed.

For example, to change the chilled water setpoint:

1. Press MENU key to go to the MENU mode (see Figure 8).

2. Press SET (the UP Key) to go to the setpoint menus.

3. Press UNIT SPs (the Right key) to go to setpoints associated with unit operation.

4. Press the DOWN key to scroll down through the setpoint menus to the third menu whichcontains Evap LWT=XX.X°F

5. Press the ENTER key to move the cursor down from the top line to the second line inorder to make the change.

6. Use the ARROW keys (now in the edit mode as shown above) to change the setting.

7. When the desired value is achieved, press ENTER to enter it and also move the cursordown.

At this point, the following actions can be taken:

1. Change another setpoint in this menu by scrolling to it with the ENTER key

2. Using the ENTER key, scroll to the first line in the menu. From there the ARROW keyscan be used to scroll to different menus.

MENU Key

ENTER KeyARROW Keys (4)

Page 31: Date: July 2002 Supersedes: New - Daikin AppliedOperation Manual OM AGS-1 Group: Chiller Part Number: 330412001 Date: July 2002 Supersedes: New GeneSys Air-Cooled Screw Compressor

OM AGS-1 31

SecurityAll set points on the unit controller as well as the circuit controllers are protected usingpasswords. Two four-digit passwords shall provide OPERATOR and MANAGER levels ofaccess to changeable parameters.

Entering PasswordsPasswords can be entered using the ENTER PASSWORD screen on the unit controller,which is the last screen in the Unit SPs column. The password is entered by pressing theENTER key, scrolling to the correct value with the UP and DOWN arrow keys, and pressingENTER again. The entered password shall not be shown after the enter key is pressed.

Once the correct password has been entered, the ENTER PASSWORD screen shall indicatewhich password is active (none, operator, or manager). If the wrong password is entered, amessage will temporarily appear stating this. If no valid password is active the activepassword level displays “none”.

Entering an incorrect password while a password is active will render that passwordinactive. Entering a valid password that is not the same as the active password will result inthe active password level being changed to reflect the new password level.

Editing Set PointsAfter a valid password has been entered at the unit controller, set points on the circuitcontrollers and the unit controller may be changed. If the operator attempts to edit a setpoint for which the necessary password level is not active, no action will be taken.

Once a password has been entered, it shall remain valid for 60 minutes after the last key-press on the unit controller.

Clearing AlarmsAlarms may be cleared at the unit controller if any password level is active. If the userattempts to clear an alarm while no password is active, then the controller will automaticallygo to the ENTER PASSWORD screen. The user can then enter a password normally, andscroll back to the active alarm column to clear the active alarm(s).

Page 32: Date: July 2002 Supersedes: New - Daikin AppliedOperation Manual OM AGS-1 Group: Chiller Part Number: 330412001 Date: July 2002 Supersedes: New GeneSys Air-Cooled Screw Compressor

OM AGS-1 32

Unit Controller MenusVarious menus are shown in the controller display. Each menu screen shows specificinformation. In some cases menus are used only to view status of the unit, in some casesthey are used for checking alarms, and in some case they are used to set the setpoint valuesthat can be changed.

The menus are arranged in a matrix of screens across a top horizontal row. Some of thesetop-level screens have sub-screens located under them. The content of each screen and itslocation in the matrix are shown in Table 25. A description of each menu begins on page33.

The ARROW keys on the controller are used to navigate through the menus. The keys arealso used to change numerical setpoint values contained in certain menus.

As an alternate to selecting screens with the menu function, it is possible to scroll throughall of them with the 4 arrow keys. For this use, the screens shall be arranged logically in amatrix as shown below.

Table 25, Unit Controller Menu StructureVIEW MENUS

VIEWUNIT

STATUS(1)

VIEWUNITTEMP

(2)

VIEWCOMP

#1(1)

VIEWCOMP

#2(1)

VIEWCOMP

#3(1)

VIEWREFRGCIR 1

(1)

VIEWREFRGCIR 2

(1)

VIEWREFRGCIR 3

(1)

VIEWFANSOn-Off

(1)VIEWUNIT

STATUS(2)

VIEWUNITTEMP

(2)

VIEWCOMP

#1(2)

VIEWCOMP

#2(2)

VIEWCOMP

#3(2)

VIEWREFRGCIR 1

(2)

VIEWREFRGCIR 2

(2)

VIEWREFRGCIR 3

(2)

VIEWFANSVFD(2)

VIEWUNIT

STATUS(3)

� � �

VIEWREFRGCIR 1

(5)

VIEWREFRGCIR 2

(5)

VIEWREFRGCIR 3

(5)

Right halfof table

continuedbelow

ALARM MENUS SET MENUSEVENT

LOG(1)

ALARMLOG(1)

ALARMACTIVE

(1)

SET UNITSPs (1)

SETCOMP SP

(1)

SETALARM

LMTS (1)

SETSENSOROFFSET

TESTUNIT

� � �SET UNIT

SPs(2)

SETCOMP SP

(2)

SETALARMLMTS

(2)

EVENTLOG(25)

ALARMLOG(25)

ALARMACTIVE

(n)

SET UNITSPs(3)

SETCOMP SP

(3)

SETALARMLMTS

(3)

SET UNITSPs(4)

SETALARMLMTS

(4)

Right half oftable

continuedfrom above

SET UNITSPs(5)

SET UNITSPs(6)

�SET UNIT

SPs(to 12)

Continued

Page 33: Date: July 2002 Supersedes: New - Daikin AppliedOperation Manual OM AGS-1 Group: Chiller Part Number: 330412001 Date: July 2002 Supersedes: New GeneSys Air-Cooled Screw Compressor

OM AGS-1 33

Selection can then be made by using the LEFT/RIGHT keys to move between columns andthe UP/DOWN keys to move between rows. The memory allows the return to the lastscreen viewed in each column. (This feature also applies to navigation using the functionkeys.) As an example:

If the VIEW COMP#2 (3) screen is being viewed and the RIGHT arrow key ispressed, the display will show VIEW EVAP. If the LEFT arrow key is then pressed,the display will show VIEW COMP#2 (3) again (not VIEW COMP (1)).

Attempts to scroll past the limits of the matrix are ignored.

Screen DefinitionsThe following section illustrates all the "unit" screens. The screens are listed in the order ofthe matrix, starting from the upper-left. Unit "view" screens are used to view the operationof a circuit's compressor, refrigerant condition, EXV position, and fan operation. Nosettings are made to these screens.

View Unit StatusVIEW UNIT STATUS (1)Auto

Evap Pump= run

VIEW UNIT STATUS (2)Softload Limit=100.0Demand Limit=100.0Network Limit=100.0The unit will limit loading to the lowest of the three limit values that are active.

VIEW UNIT STATUS (3)1 2 3 4

D.O. 0 1 0 0D.I. 1 1 1 0

This screen gives the status of Digital Outputs (D.O.) and Digital Inputs (D.I.) as defined inTable 14 and Table 15 on page 19. 0=Off, 1=On.

VIEW UNIT TEMP (1)Evap LWT= XXX.X FEvap EWT= XXX.X FActive SP= XXX.X F

VIEW UNIT TEMP (2)LWT Pulldn= 0.0 F/mEvap Delta T=XX.X FOutdoor Air=XXX.X F

Page 34: Date: July 2002 Supersedes: New - Daikin AppliedOperation Manual OM AGS-1 Group: Chiller Part Number: 330412001 Date: July 2002 Supersedes: New GeneSys Air-Cooled Screw Compressor

OM AGS-1 34

NOTE: In the following VIEW CIRCUIT screens, the N field indicates which compressor(#1, #2, etc.) is being viewed.

VIEW CIR N STATUS(1)Off:ReadySlide Position=000.0%Slide Target=000.0%

Slide position and slide target are explained on page 12.

VIEW CIR N STATUS(2)Hours = XXXXXStarts = XXXXX

VIEW REFR CIR N (1)Evap Press=XXX.X psiCond Press=XXX.X psiLiq Press= XXX.X psi

VIEW REFRG CIR N (2)Sat Evap= XXX.X °°°°FSat Cond= XXX.X °°°°FSat LiqLine= XXX.X°°°°F

VIEW REFRG CIR N (3)Suct Temp = XXX.X °°°°FDisc Temp = XXX.X °°°°FLiq Temp = XXX.X °°°°F

VIEW REFRG CIR N (4)Suct SH = XXX.X °°°°FDisc SH= XXX.X °°°°FLiquid SC= XXX.X °°°°F

VIEW REFRG CIR N (5)Evap Approach=XX.X°°°°FCond Approach=XX.X°°°°FEXV position = XXXX

VIEW FANS (1)Fans On, Cir 1= 0Fans On, Cir 2= 0Fans On, Cir 3= 0

Page 35: Date: July 2002 Supersedes: New - Daikin AppliedOperation Manual OM AGS-1 Group: Chiller Part Number: 330412001 Date: July 2002 Supersedes: New GeneSys Air-Cooled Screw Compressor

OM AGS-1 35

VIEW FANS (2)VFD Cir 1= 000.0 %VFD Cir 2= 000.0 %VFD Cir 3= 000.0%

ALARM and EVENT Screen DefinitionsThe alarms and events shown are examples only. Any possible alarm or event could beshown. The alarm log and event log can show up to 25 most recent occurrences.

ALARM LOG: (1)High Condenser Presshh:mm:ss dd/mmm/yyyyUnit State= Auto

ALARM ACTIVE (1)hh:mm:ss dd/mmm/yyyyMech High Press

EVENT LOG (1)Oil Level Low Cir nhh:mm:ssdd/mmm/yyyyUnit State- Auto

SET Screen DefinitionsSetpoints shown are typical. Entries can be selected by scrolling through the availablepossibilities. Setpoint ranges and choices are show in Table 16 on page 21.

SET UNIT SPs (1)Enable=OnMode= COOLSource = KEYPAD

SET UNIT SPs (2)Available Modes = COOL

Select w/Unit Off

SET UNIT SPs (3)Cool LWT = XX.X°°°°FIce LWT – XX.X°°°°F

The unit will only use the setpoint for the Mode selected.

Page 36: Date: July 2002 Supersedes: New - Daikin AppliedOperation Manual OM AGS-1 Group: Chiller Part Number: 330412001 Date: July 2002 Supersedes: New GeneSys Air-Cooled Screw Compressor

OM AGS-1 36

SET UNIT SPs (4)StartDelta= XX.X°°°°FStopDelta= XX.X°°°°FStageDeltaT= XX.X°°°°F

SET UNIT SPs (5)Max Pulldn=X.X°°°°F/minEvapRecTimer=XXX secEvap Pump= #1 only

The unit can start either of two chilled water pumps. This menu selects which pump willstart.

SET UNIT SPs (6)Reset Type =none

MaxResetDT =XX.X°°°°FStrtResetDT=XX.X°°°°F

SET UNIT SPs (7)Soft Load = OffBegin Capacity= XXX%SoftLoadRamp= XXmin

SET UNIT SPs (8)Demand Limit= Off

SET UNIT SPs (9)CLOCK

dd/mmm/yyyyhh:mm:ss

SET UNIT SPs (10)Units = °°°°F/psiLang = ENGLISH

Inch-Pound units of measure and English language are the only options available in thisversion.

SET UNIT SPs (11)Protocol=Ident Number=Baud Rate=

SET UNIT SPs (12)Enter Password:0000Active PasswordLevel:none

Page 37: Date: July 2002 Supersedes: New - Daikin AppliedOperation Manual OM AGS-1 Group: Chiller Part Number: 330412001 Date: July 2002 Supersedes: New GeneSys Air-Cooled Screw Compressor

OM AGS-1 37

SET COMP SPs (1)Seq # Comp 1=Seq # Comp 2=Seq # Comp 3=

SET COMP SPs (2)Max Comprs On = XStart-Start = XXminStop-Start = XXmin

SET COMP SPs (3)Pumpdn press=25.0psiPumpdn time= 120 sec

SET ALARM LMTS (1)LowEvPrHold=XXXpsiLowEvPrUnld=XXXpsi

SET ALARM LIMITS (2)LowEvPrDel= XXX secLowOilDelay= XXX secHighOilDpDel=XXX sec

SET ALARM LIMITS (3)MinLiftDel= XXX sec

Low Subcool= XX.X°°°°FHigh Disc Temp=XXX°°°°F

SET ALARM LIMTIS (4)Evap Freeze= XX.X°°°°FLow Amb Lock= XX.X°°°°FEvap Flow Proof=XXX

SET SENSOR OFFSETOAT= XX.X°°°°FEvap LWT= XX.X°°°°FEvap EWT= XX.X°°°°F

TEST Screen DefinitionsTEST UNITAlarm Out=OffEvap Heaters=OffPump1=Off Pump 2=Off

Page 38: Date: July 2002 Supersedes: New - Daikin AppliedOperation Manual OM AGS-1 Group: Chiller Part Number: 330412001 Date: July 2002 Supersedes: New GeneSys Air-Cooled Screw Compressor

OM AGS-1 38

Circuit Controller MenusSee "Using the Controller" on page 29 for information on how to navigate and use the menuscreens as well as changing setpoints. As an alternate to selecting screens with the menufunction, it is possible to scroll through all of them with the 4 arrow keys. For this use, thecircuit controllers' screens are arranged logically in a matrix as shown below.

Table 26, Circuit Controller Screen Matrix

"VIEW" SCREENS "SET" SCREENS "TEST"SCREENS

VIEWUNIT

VIEWCIR(1)

VIEWREFRG

(1)

VIEWFANS

(1)

SETCOMP

SPs

SETEXV SPs

(1)

SETFANS

(1)

SETSENSOROFFSETS

(1)

TESTCOMP

(1)

VIEWCIR (2)

VIEWREFRG

(2)

VIEWFANS

(2)

SETCOMPSPs (2)

SETEXV SPs

(2)

SETFANS

(2)

SETSENSOROFFSETS

(2)

TESTCOMP

(2)

VIEWCIR (3)

VIEWREFRG

(3)

SETCOMPSPs (3)

SETEXV SPs

(3)SET

FANS(3)TESTCOMP

(3)VIEWCIR (4)

VIEWREFRG

(4)

SETCOMPSPs (4)

SETEXV SPs

(4)

SETFANS

(4)VIEWCIR (5)

SETCOMPSPs (5)

SETEXV SPs

(5)�

VIEWREFRG

(7

SETFANS

(7)

Screen DefinitionsVIEW ScreensCircuit "VIEW" screens are used to view the operation of a circuit's compressor, refrigerantcondition, EXV position, and fan operation. No settings are made on these screens.

VIEW UNIT (1)Auto

Evap pump = Run

VIEW UNIT (2)Evap LWT= XXX.X°°°°FActive SP= XX.X°°°°FLWT pulldn= XX.X°°°°F/m

VIEW CIR STATUS (1)Off:ReadySlide Pos= XXX.X%Slide Target= XXX.X%

Page 39: Date: July 2002 Supersedes: New - Daikin AppliedOperation Manual OM AGS-1 Group: Chiller Part Number: 330412001 Date: July 2002 Supersedes: New GeneSys Air-Cooled Screw Compressor

OM AGS-1 39

VIEW CIR STATUS (2)Slide AIN= XXXXHours = XXXXXStarts = XXXXX

AIN is the analog input from the slide position indicator expressed in “counts”

VIEW CIR STATUS (3)Digital Outputs

1 2 3 4 5 6 7 8 9 100 0 0 0 0 0 0 0 0 0

The digital outputs in menu 3 and the analog outputs in menu 4 are defined in Table 2 andTable 4 beginning on page 7.

VIEW CIR STATUS (4)Analog Outputs(volts X 100)

1=XXXX 3=XXXX

VIEW REFRIGERANT (1)Evap Press=XXX.X psiCond Press=XXX.X psiLiq Press= XXX.X psi

VIEW REFRIGERANT (2)Sat Evap = XXX.X °°°°FSat Cond = XXX.X °°°°FSat LiqLine= XXX.X °°°°F

VIEW REFRIGERANT (3)Suct Temp = XXX.X °°°°FDisc Temp = XXX.X °°°°FLiq Temp = XXX.X °°°°F

VIEW REFRIGERANT (4)Suct SH = XXX.X °°°°FDisc SH= XXX.X °°°°FLiquid SC= XXX.X °°°°F

VIEW REFRIGERANT (5)Evap Approach=XX.X °°°°FCond Approach=XX.X °°°°F

Page 40: Date: July 2002 Supersedes: New - Daikin AppliedOperation Manual OM AGS-1 Group: Chiller Part Number: 330412001 Date: July 2002 Supersedes: New GeneSys Air-Cooled Screw Compressor

OM AGS-1 40

VIEW REFRIGERANT (6)MaxCondSatT=XXX.X°°°°FEXV Control=PressurePress target=XX,X°°°°F

VIEW REFRIGERANT (7)EXV Steps= XXXXEXV ctrl range:XXXX – XXXX steps

VIEW FANS (1)VFD Speed= XXX.X%Fans Running= X

VFD Target=XXX.X °°°°F

VIEW FANS (2)Target Sat T=XXX.X °°°°FStage Up Err= XXXStage Dn Err= XXX

SET Screen Definitions

SET COMP SPs (1)Clear Cycle Tmr=noComp Size=XXXMax Slide- XXX.X%

Clearing the anti-recycle timer is a one-time event. If “yes” is selected, the timer will go tozero but will then revert back to the original setting for any future occurrances.

SET COMP SPs (2)Circuit Mode=EnableSlide Control=autoSlide Pos= XXX.X%

SET EXV SPsEXV Control=autoManual EXV Pos=XXXXPre-open time=XXX sec

SET FAN SPs (1)Fan VFD = noNumber of fans = X

Page 41: Date: July 2002 Supersedes: New - Daikin AppliedOperation Manual OM AGS-1 Group: Chiller Part Number: 330412001 Date: July 2002 Supersedes: New GeneSys Air-Cooled Screw Compressor

OM AGS-1 41

SET FAN SPs (2)Stg Up Deadband(°°°°F)Stg1=XXX Stg2=XXXStg3=XXX Stg4=XXX

SET FAN SPs (3)Stg Down Deadband(°°°°F)Stg1=XXX Stg2=XXXStg3=XXX Stg4=XXX

SET FAN SPs (4)VFD Min speed= XXX%VFD Max speed= XXX%

SET FAN SPs (5)Cond Sat Temp TargetSet Point= XXX.X °°°°F

SET FAN SPs (6)# Fans On At Startup>75°°°°F >90°°°°F >105°°°°FX X X

SET SENSOR OFFSET (1)Evap Press= XX.X psiCond Press= XX.X psiLiq Press= XX.X psi

SET SENSOR OFFSET (2)Suct Temp= X.X FDisch Temp= X.X FLiq Temp= X.X F

SET SENSOR OFFSET (3)Slide min pos=XX%Slide max pos=XX%Slide Pos=XXX.X%

TEST CIRCUIT (1)Fans:1=Off 2=Off

3=Off 4=Off5/6=Off 7/8=Off

Page 42: Date: July 2002 Supersedes: New - Daikin AppliedOperation Manual OM AGS-1 Group: Chiller Part Number: 330412001 Date: July 2002 Supersedes: New GeneSys Air-Cooled Screw Compressor

OM AGS-1 42

TEST CIRCUIT (2)Slide Dir= UnloadSlide Pulse= Off

TEST CIRCUIT (3)Oil Return= OffEXV Closed= Off

TEST CIRCUIT (4)Fan VFD Spd%= XXX.XEXV Position=XXXX

Page 43: Date: July 2002 Supersedes: New - Daikin AppliedOperation Manual OM AGS-1 Group: Chiller Part Number: 330412001 Date: July 2002 Supersedes: New GeneSys Air-Cooled Screw Compressor

OM AGS-1 43

Sequence of Operation

The following sequence of operation is typical for McQuay models AGS chillers. Thesequence may vary depending on the software revision or various options that may beinstalled on the chiller.

Off ConditionsPower is supplied to each power panel located between condenser sections. Optionally, thepower may be supplied to a single power connection in a terminal box located on the base ofthe unit.

With power supplied to the unit, 115 VAC power is applied through the control fuse F1 tothe compressor heaters (HTR1, HTR2, (and HTR3), and evaporator heater and the primaryof the 24V control circuit transformer.

CAUTION:Compressor heaters must be on for at least 12 hours prior to start-up to

avoid compressor damage.The 24V transformer provides power to the MicroTech II controller and related components.With 24V power applied, the controller will check the position of the front panel systemswitch. If the switch is in the "stop" position the chiller will remain off and the display willindicate the operating mode to be OFF: System Sw. The controller will then check thepumpdown switches. If any of the switches are in the "stop" position, that circuit’soperating mode will be displayed as OFF: PumpDwnSw. If the switches for both circuitsare in the "Stop" position the unit status will display OFF: PumpdownSw’s. If the remotestart/stop switch is open the chiller will be OFF: RemoteSw. The chiller may also becommanded off via communications from a separate communicating panel such a BASprotocol interface. The display will show OFF: RemoteComm if this operating mode is ineffect. If an alarm condition exists which prevents normal operation of both refrigerantcircuits, the chiller will be disabled and the display will indicate OFF: Alarm. If thecontrol mode on the keypad is set to "Manual Unit Off," the chiller will be disabled and theunit status will display OFF: ManualMode. Assuming none of the above stop conditionsare true, the controller will examine the internal time schedule to determine whether thechiller should be permitted to start. The operating mode will be OFF: TimeClock if thetime schedule indicates time remaining in an "off" time period.

AlarmThe alarm light in back of the left arrow button on the controller will be illuminated whenone or more of the cooling circuits has an active alarm condition which results in the circuitbeing locked out. Unless the alarm condition affects all circuits the remaining circuits willoperate as required.

Start-upIf none of the above "off" conditions are true, the MicroTech II controller will initiate a startsequence and energize the chiller water pump output relay. The chiller will remain in theWaitForFlow mode until the field installed flow switch indicates the presence of chilledwater flow. If flow is not proven within 30 seconds, the alarm output will be turned on, thekeypad display will be WaitForFlow and the chiller will continue to wait for proof ofchilled water flow. Once flow is established, the controller will sample the chilled watertemperature and compare it against the Leaving Chilled Water Set Point, the Control Band,and the Start-up Delta Temperature, which have been programmed into the controller’smemory.

Page 44: Date: July 2002 Supersedes: New - Daikin AppliedOperation Manual OM AGS-1 Group: Chiller Part Number: 330412001 Date: July 2002 Supersedes: New GeneSys Air-Cooled Screw Compressor

OM AGS-1 44

If the leaving chilled water temperature is above the Leaving Chilled Water Set Point plus ½the Control Band plus the adjustable Start-up Delta Temperature, the controller will selectthe refrigerant circuit with the lowest number of starts as the lead circuit and energize thefirst stage of the Cool Staging mode. The controller will start the compressor and energizethe evaporator oil return solenoid. The controller will delay the opening of the electronicexpansion valve until the evaporator pressure decreases to a preset value. This is theevaporator prepurge mode and the display will show Pre-Purge. The valve will then openallowing refrigerant to flow through the expansion valve and into the evaporator and thedisplay will show Opened EXV. If additional cooling capacity is required, the controllerwill energize the additional cooling capacity by activating the first compressor’s capacitycontrol solenoids. As the system load increases, the controller will start the lag refrigerantcircuit in the same manner after interstage timers are satisfied. The compressors andcapacity control solenoids will automatically be controlled as required to meet the coolingneeds of the system. The electronic expansion valves are operated by the MicroTech IIcontroller to maintain precise refrigerant control to the evaporator at all conditions.

Standard FanTrol Condenser Fan ControlThe first condenser fan stage will be started along with the first compressor to provide initialcondenser head pressure control. The MicroTech II controller will activate the remainingcondenser fans as needed to maintain proper condenser pressure. The MicroTech IIcontroller continuously monitors the condenser minus evaporator lift pressure and willadjust the number of operating condenser fans as required. The number of condenser fansoperating will vary with outdoor temperature and system load. The condenser fans arematched to the operating compressors so that when a compressor is off all fans for thatcircuit will also be off.

Optional VFD Condenser Fan Control

PumpdownAs the system chilled water requirements diminish. The compressors will be unloaded. Asthe system load continues to drop, the electronic expansion valves will be stepped closedand the refrigerant circuits will go through a pumpdown sequence. As the evaporatorpressure falls below the pumpdown pressure set point while pumping down, thecompressor(s) and condenser fans will stop. The unit has a one-time pumpdown controllogic; therefore, if the evaporator pressure rises while the refrigerant circuit is in apumpdown mode, the controller will not initiate another pumpdown sequence. Thecontroller will keep the unit off until a call for cooling occurs.

The chilled water pump output relay will remain energized until the time schedule’s "on"time expires, the remote stop switch is opened, the system switch is moved to the stopposition, or a separate communications panel such as the Remote Monitoring andSequencing Panel or an Open Protocol interface deactivates the chilled water pump output.

CAUTION

The screw compressor must not be used as a pump out compressor for service work involvingremoval of refrigerant from the compressor or evaporator. That is, the compressor must not berun with the liquid line valve (king valve) closed. Portable recovery equipment must be used toremove the refrigerant. Serious damage to the compressor could result.

Page 45: Date: July 2002 Supersedes: New - Daikin AppliedOperation Manual OM AGS-1 Group: Chiller Part Number: 330412001 Date: July 2002 Supersedes: New GeneSys Air-Cooled Screw Compressor

OM AGS-1 45

Figure 10, AGS Piping Schematic

DISCHARGETUBING

SIGHTGLASS

AIRFLOW

WATER OUT

WATER IN

LIQUIDTUBING

EXPANSIONVALVE

SCHRADERVALVE

CHARGINGVALVE

SIGHTGLASS

CONDENSERASSEMBLY

AIRFLOW

AIRFLOWAIR

FLOW

CONDENSERASSEMBLY

CHARGING VALVE

LIQUID SHUT-OFF VALVE

SCHRADER VALVEFILTER DRIER

OIL FILTER

OILSEPARATOR

OILRETURN

DISCHARGETUBING SCHRADER

(EACH DISCHHEADER)

TO REAR OFCOMPRESSOR

SUCTION

BUTTERFLY VALVE(OPTION)

SIGHTGLASS

RELIEF VALVE(EVAP SHELL)

RELIEFVALVE

CHECKVALVE

ANGLEVALVE

S

Page 46: Date: July 2002 Supersedes: New - Daikin AppliedOperation Manual OM AGS-1 Group: Chiller Part Number: 330412001 Date: July 2002 Supersedes: New GeneSys Air-Cooled Screw Compressor

OM AGS-1 46

Start-up and Shutdown

NOTICE

McQuayService personnel or factory authorized service agencymust perform initial start-up.

CAUTION

Most relays and terminals in the unit control center are powered when S1 is closed and thecontrol circuit disconnect is on. Therefore do not close S1 until ready for start-up.

Seasonal Start-up1. Double check that the optional compressor suction butterfly valve is open. There is a check

valve between the oil separator and condenser..2. Check that the manual liquid-line shutoff valves at the outlet of the subcooler coils on each side

of the unit are open.3. Adjust the leaving chilled water temperature set point on the MicroTech II controller to the

desired chilled water temperature. The control band is preset for 10 degrees Delta-T between theentering and leaving evaporator water temperature at full load. If the Delta-T is outside an 8°-12°F range, at full load, reset the control band as per the instructions found in the Control sectionof this manual.

4. Start the auxiliary equipment for the installation by turning on the time clock, and/or remoteon/off switch, and chilled water pump.

5. Check to see that pumpdown switches PS1 and PS2 are in the "Pumpdown and Stop" (open)position. Throw the S1 switch to the "auto" position.

6. Under the "Control Mode" menu of the keypad place the unit into the automatic cool mode.7. Start the system by moving pumpdown switch PS1 to the "auto" position.8. After running circuit #1 for a short time, check for flashing in the refrigerant sightglass under

stable conditions.9. Repeat steps 8 and 9 for PS2.10. Superheat is factory adjusted to maintain between 0° and 3°F.

CAUTIONThe superheat should be between 0°F and 3°F, with the liquid line sightglass full, once thesystem temperatures have stabilized at the MicroTech II set point temperatures.

Temporary ShutdownMove pumpdown switches PS1 and PS2 to the "Pumpdown and Stop" position. After thecompressors have pumped down, turn off the chilled water pump.

Caution:Do not turn the unit off using the "S1" switch, without first moving PS1 and PS2 to the"Stop" position, unless it is an emergency as this will prevent the unit from going through aproper shutdown sequence.

Page 47: Date: July 2002 Supersedes: New - Daikin AppliedOperation Manual OM AGS-1 Group: Chiller Part Number: 330412001 Date: July 2002 Supersedes: New GeneSys Air-Cooled Screw Compressor

OM AGS-1 47

CAUTIONThe unit has one time pumpdown operation. When PS1 and PS2 are in the "Pumpdown andStop" position the unit will pumpdown once and not run again until the PS1 and PS2switches are moved to the auto position. If PS1 and PS2 are in the auto position and theload has been satisfied the unit will go into one time pumpdown and will remain off untilMicroTech II senses a call for cooling and starts the unit. Under no circumstance use thecompressors for pumpdown with the liquid line valves closed.

It is important that the water flow to the unit is not interrupted before the compressorspumpdown to avoid freeze-up in the evaporator.

If all power is turned off to the unit the compressor heaters will become inoperable. Oncepower is resumed to the unit it is important that the compressor and oil separator heaters areenergized a minimum of 12 hours before attempting to start the unit. Failure to do so coulddamage the compressors due to excessive accumulation of liquid in the compressor.

Start-up After Temporary Shutdown1. Insure that the compressor heaters have been energized for at least 12 hours prior to starting the

unit.2. Start the chilled water pump.3. With System switch S1 in the "on" position, move pumpdown switches PS1 and PS2 to the

"auto" position.4. Observe the unit operation until the system has stabilized.

WARNINGIf shutdown occurs or will continue through periods below freezing ambient temperatures,protect the chiller vessel from freezing. See Freeze Up Protection in this manual for moreinformation.

Extended (Seasonal) Shutdown1. Move the PS1 and PS2 switches to the manual pumpdown position.2. After the compressors have pumped down, turn off the chilled water pump.3. Turn off all power to the unit and to the chilled water pump.4. Move the emergency stop switch S1 to the "off" position.5. Close the optional compressor suction valve (if so equipped) as well as the liquid line shutoff

valves.6. Tag all opened compressor disconnect switches to warn against start-up before opening the

compressor suction valve and liquid line shutoff valves.7. If glycol is not used in the system, drain all water from the unit evaporator and chilled water

piping if the unit is to be shutdown during winter. Do not leave the vessels or piping open to theatmosphere over the shutdown period.

8. Leave power applied to the evaporator heaters if a separate disconnect is used.

Page 48: Date: July 2002 Supersedes: New - Daikin AppliedOperation Manual OM AGS-1 Group: Chiller Part Number: 330412001 Date: July 2002 Supersedes: New GeneSys Air-Cooled Screw Compressor

OM AGS-1 48

Start-up After Extended (Seasonal) Shutdown1. With all electrical disconnects open, check all screw or lug type electrical connections to be sure

they are tight for good electrical contact.2. Check the voltage of the unit power supply and see that it is within the ±10% tolerance that is

allowed. Voltage unbalance between phases must be within ±3%.3. See that all auxiliary control equipment is operative and that an adequate cooling load is

available for start-up.4. Check all compressor flange connections for tightness to avoid refrigerant loss. Always replace

valve seal caps.5. Make sure system switch S1 is in the "Stop" position and pumpdown switches PS1 and PS2 are

set to "Pumpdown and Stop," throw the main power and control disconnect switches to "on."This will energize crankcase heaters. Wait a minimum of 12 hours before starting up unit. Turncompressor circuit breakers to "off" position until ready to start unit.

6. Open the optional compressor suction butterfly as well as the liquid line shutoff valves.7. Vent the air from the evaporator water side as well as from the system piping. Open all water

flow valves and start the chilled water pump. Check all piping for leaks and recheck for air inthe system.

Page 49: Date: July 2002 Supersedes: New - Daikin AppliedOperation Manual OM AGS-1 Group: Chiller Part Number: 330412001 Date: July 2002 Supersedes: New GeneSys Air-Cooled Screw Compressor
Page 50: Date: July 2002 Supersedes: New - Daikin AppliedOperation Manual OM AGS-1 Group: Chiller Part Number: 330412001 Date: July 2002 Supersedes: New GeneSys Air-Cooled Screw Compressor

Post Office Box 2510, Staunton, Virginia 24402 USA • (800) 432-1342 • www.mcquay.com