Cooling Solutions

Presented byPaul Almond – Datacentre UK

Page 2: Datacentre Uk

The Facts

Energy costs are rising

The cost to power and cool server room equipmentnow exceeds the purchase cost on a 3-year life-cycle, based on a traditional server room / data centre configuration.

Page 3: Datacentre Uk

Source IDC

Cooling Solutions

Page 4: Datacentre Uk

•  Reduce energy usage

•  Create more efficient rack space

Cooling Solutions

The Aim

The government will be introducing a carbon tax in 2009All companies will have to report power usage by law

Page 5: Datacentre Uk

Recent studies reveal that data centre power densities have increased ten-fold in the last 10 years and that cooling represents upwards of 60-70% of the total data centre power spend for the majority of customers. These costs are driven by the data centre power requirements and the volume of cooling airflow required

Source HP

Industry Studies

Page 6: Datacentre Uk

• Agility – the ability of a system to adapt to change – increasing and unpredictable power densities driven by ever-changing business requirements.

• Availability – to eliminate hotspots and vertical temperature gradients at the face of the rack and to assure redundancy when required.

• Lifecycle costs – to optimise capital investment and available space – the ability to accelerate speed of deployment and lower maintenance costs, increase ROI and maximise operational efficiency.

• Manageability – Simple and intuitive configuration – predictive failure analysis and provision of cooling performance data.

• Serviceability – Decrease mean time to recover – simplify complexity – easier service procedures – minimise multi-vendor solutions.

What are the cooling challenges in today’s data centres?

Cooling Challenges

Page 7: Datacentre Uk

49.6 l/s/kW(223.2 l/s @ 4.5kW)

Typical 7U Blade Server

22oC

38-42oC

32oC

Typical 1U Server

75.5 l/s/kW22oC

It is not only direction of airflow that must be taken into consideration, but alsotemperature rise across the server and the air volume required by the server fans.

Blade servers are the most electrically efficient form of server. Available blade types for a given blade server system can vary dramatically in performance and power consumption

Cooling Solutions

Page 8: Datacentre Uk

The predominant architecture for cooling data centres since the inception of the mainframe has been raised floor air delivery from perimeter computer room air conditioners (CRAC).

At lower densities (1 – 5 kW / rack), adequate cooling is provided to IT equipment, despite the mixing of air throughout the room.

Existing Configurations

Room Based Cooling

Page 9: Datacentre Uk

Cooling Solutions

Page 10: Datacentre Uk

Note: In-row cooling architecture, as depicted, utilises a free air discharge without ducting or any containment of hot or cold air streams.

• Place the air conditioning units in the row of rack enclosures.

• Incorporating a hot / cold aisle design, heat is removed from the hot aisle as it is dispelled from the IT equipment. The hot air is then cooled and discharged to the cold aisle.

• Inherent energy efficiency advantages:- fan power reduction to move the air

- shift in mindset from cold air supply to heat removal

- removal of heat before it has a chance to mix with surrounding air in the room

makes the remaining areas in the room a large available volume of supply air

- length scale for air delivery is only a few metres or less (varies on number of racks) rather than tens of metres

Existing Configurations

Row Based Cooling

Page 11: Datacentre Uk

Cooling Solutions

• Eliminate the supply air from the equation• Capture all the heat where it is generated, from the hot aisle• Remove the heat before it mixes with air streams outside the

hot aisle• No obstructions to block the air path

• Avoid complex engineering• Variable speed fans to match cooling capacity to power load

in each aisle• Room temperatures will be easier to maintain with less warm

air escaping the hot aisle

Close Coupled Cooling

Page 12: Datacentre Uk

Cooling Solutions

How do I cool my data centre for FREE?

Page 13: Datacentre Uk

Cooling Solutions

• Use ambient air to cool the warm return water

• Ideally suited to new designs, but free-cooling options can be retro-fitted to existing installations

Free-Cooling Chillers

Page 14: Datacentre Uk

TRADITIONAL Chiller Water Circuit Schematic

Cooling Solutions

Page 15: Datacentre Uk

Free-Cooling Solutions

FREE-COOLING Chiller Water Circuit Schematic

Extra bits

Page 16: Datacentre Uk

10-Year South-East UK Average Daily Temperatures

0

2

4

6

8

10

12

14

16

18

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec

Month

degC Average Daily Temp

Free-Cooling Solutions

Free-Cooling – AverageAir Temperature

Page 17: Datacentre Uk

Free-Cooling Solutions

Free-Cooling – Air Temperaturevs Free-Cooling %

10-Year South-East UK Average Daily Temperaturesvs Free-Cooling %

0

2

4

6

8

10

12

14

16

18

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec

Month

degC

0

20

40

60

80

100

120

% F

ree-

Coo

ling

Average Daily TempFree-Cooling %

Page 18: Datacentre Uk

Free-Cooling Solutions

Free-Cooling Chillers• Air cooled systems: typically 100kW-1200kW

• Uses condenser fans only (i.e. no compressors) to pre-cool the returning chilled water (in free cooling mode)

• Compressors only run if the required leaving water temperature cannot be achieved with free-cooling system

• Lower compressor run time = less maintenance and less down- time

• Capital payback typically <18 months EVEN FOR WORST CASE N+1: real bottom-line savings thereafter

• Maximised benefits using elevated chilled water temperatures, e.g. Hot Aisle Containment applications

Page 19: Datacentre Uk

What do I need to do to be able to utilise free cooling?

• Create predictable air flow• Capture and Contain hot air to maximise return air temp• Raise entering water temperature

Water is 350% more efficient than air at transferring and transporting heat

Free-Cooling Chillers

Free-Cooling Solutions

Page 20: Datacentre Uk

Raised Floor Airflow

Air Containment

Page 21: Datacentre Uk

.

Air Containment

Row Based Cooling With HAC

Page 22: Datacentre Uk

Hot Aisle Airflow

Air Containment

Page 23: Datacentre Uk

Free-Cooling Solutions

Free-Cooling Cost Saving Summary•120kW N+1 installation with Free-Cooling Chillers

•Achieve pay-back of the cost difference to standardchillers in <10 months for one machine; 18 months for worst-

case, two-machine N+1 installations

•Typically achieve 100% Free-Cooling of data centre 26% (>3 months) of the year

•Achieve a useable level of Free-Cooling for >75%of the year

Based on UK average daily temperatures measured in the SE region, 1997 to 2006 inclusive

Page 24: Datacentre Uk

Alternative options for energy efficient cooling solutions

Turbocor Chillers•Very high efficiency, especially at lower loads•Centrifugal compressor with magnetic bearings eliminates oil and the maintenance / efficiency losses associated with traditional systems•Combine with FREE-COOLING for maximum effect

Cooling Solutions

Page 25: Datacentre Uk

• Government ECA approval status • Excellent full load energy efficiency• Further improved part load performance• Lower energy bills, reduced carbon footprint• Virtually no mechanical wear• Unrivalled reliability• No oil to degrade the system over time• Low noise• No vibration• Full remote monitoring capability• 30% lower overall life cycle costs

Turbocor Summary Benefits

Cooling Solutions

Page 26: Datacentre Uk

* Carbon Trust

Energy–Efficiency LoansInterest-free unsecured loans of between £5,000 and £100,000 are available for small and medium sized businesses who are investing in an energy-saving project. Coupled with the ECA scheme this offers business really significant savings. *

Free Energy SurveysIf your energy bill is higher than £50,000 per year, then you may qualify for a FREE energy survey to provide you with a practical action plan of energy saving measures tailored to your business. *

Free Cooling - If you’re still not convinced...

Cooling Solutions

Page 27: Datacentre Uk

Two major benefits for business •The Enhanced Capital Allowance (ECA) Scheme and the Energy Technology List • Energy savings

Products listed on the ETL are highly energy efficient, and should produce significant long-term financial benefits by reducing your energy bills and Climate Change Levy payments.

The Bottom Line

Cooling Solutions