DATACENTERS Electrical Design

Embed Size (px)

Citation preview

  • 7/31/2019 DATACENTERS Electrical Design

    1/46

    ENERGY EFFICIENT DATACENTERS

    ELECTRICAL DESIGNMichael Ryan, Brett Rucker, Dean Nelson, Petr Vlasaty,Ramesh KV, Serena DeVito, and Brian DaySun Global Lab & Datacenter Design Services

    Sun BluePrints Online

    Part No 820-6213-10

    Revision 1.0, 3/11/09

  • 7/31/2019 DATACENTERS Electrical Design

    2/46

    Sun Microsystems, Inc.

    Table of Contents

    Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1About This Article . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

    Traditional Datacenter Electrical Design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3

    Utility Power and Transformer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

    Switchgear . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

    Backup Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

    Power Distribution . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

    Rack Power Distribution . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

    Datacenter Tier Levels. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

    Suns Approach to Electrical Design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

    Increasing Electrical Distribution Efficiency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8

    Component Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

    Equipment Power Supplies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

    Power Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

    Appropriate Levels of Redundancy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

    Flexibility Through Modularity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

    Datacenter Power Distribution . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

    Extending the Datacenter Lifecycle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

    Electrical Yard. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21Building Infrastructure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22

    Pod Power Distribution . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22

    Suns Electrical Design At Work. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24

    Santa Clara, California . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24

    Broomfield, Colorado . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29

    Sun Modular Datacenter. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34

    Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37

    About The Authors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38

    Acknowledgments. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43

    Ordering Sun Documents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43

    Accessing Sun Documentation Online . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43

    http://dcelectricaldgn-080310.pdf/http://dcelectricaldgn-080310.pdf/http://dcelectricaldgn-080310.pdf/http://dcelectricaldgn-080310.pdf/http://dcelectricaldgn-080310.pdf/http://dcelectricaldgn-080310.pdf/http://dcelectricaldgn-080310.pdf/http://dcelectricaldgn-080310.pdf/http://dcelectricaldgn-080310.pdf/http://dcelectricaldgn-080310.pdf/http://dcelectricaldgn-080310.pdf/http://dcelectricaldgn-080310.pdf/http://dcelectricaldgn-080310.pdf/http://dcelectricaldgn-080310.pdf/http://dcelectricaldgn-080310.pdf/http://dcelectricaldgn-080310.pdf/http://dcelectricaldgn-080310.pdf/http://dcelectricaldgn-080310.pdf/http://dcelectricaldgn-080310.pdf/http://dcelectricaldgn-080310.pdf/http://dcelectricaldgn-080310.pdf/http://dcelectricaldgn-080310.pdf/http://dcelectricaldgn-080310.pdf/http://dcelectricaldgn-080310.pdf/http://dcelectricaldgn-080310.pdf/http://dcelectricaldgn-080310.pdf/http://dcelectricaldgn-080310.pdf/http://dcelectricaldgn-080310.pdf/http://dcelectricaldgn-080310.pdf/http://dcelectricaldgn-080310.pdf/http://dcelectricaldgn-080310.pdf/http://dcelectricaldgn-080310.pdf/http://dcelectricaldgn-080310.pdf/http://dcelectricaldgn-080310.pdf/http://dcelectricaldgn-080310.pdf/http://dcelectricaldgn-080310.pdf/http://dcelectricaldgn-080310.pdf/http://dcelectricaldgn-080310.pdf/http://dcelectricaldgn-080310.pdf/http://dcelectricaldgn-080310.pdf/http://dcelectricaldgn-080310.pdf/http://dcelectricaldgn-080310.pdf/http://dcelectricaldgn-080310.pdf/http://dcelectricaldgn-080310.pdf/http://dcelectricaldgn-080310.pdf/http://dcelectricaldgn-080310.pdf/http://dcelectricaldgn-080310.pdf/http://dcelectricaldgn-080310.pdf/http://dcelectricaldgn-080310.pdf/http://dcelectricaldgn-080310.pdf/http://dcelectricaldgn-080310.pdf/http://dcelectricaldgn-080310.pdf/http://dcelectricaldgn-080310.pdf/http://dcelectricaldgn-080310.pdf/http://dcelectricaldgn-080310.pdf/http://dcelectricaldgn-080310.pdf/http://dcelectricaldgn-080310.pdf/http://dcelectricaldgn-080310.pdf/http://dcelectricaldgn-080310.pdf/http://dcelectricaldgn-080310.pdf/http://dcelectricaldgn-080310.pdf/http://dcelectricaldgn-080310.pdf/
  • 7/31/2019 DATACENTERS Electrical Design

    3/46

    1 Introduction Sun Microsystems, Inc.

    Chapter 1

    Introduction

    Good datacenter electrical design supports increased energy efficiency, stability, long-

    term growth, and business agility. As the following examples indicate, electrical design

    has become paramount in this equation:

    Electrical design that supports growth gives datacenters a longer life. Many

    datacenters built even as recently as 510 years ago have reached a premature end of

    life because their infrastructure was overtaken by density, power, and cooling

    demands that were not planned for.

    Modular designs, from the electrical yard to server racks themselves, can support

    both rapid growth and rapid change, giving organizations the agility they need to

    adapt to changing business conditions.

    System efficiency can be increased while not comprising availability by careful system

    design and component selection, such as choosing high-efficiency transformers and

    uninterruptible power supplies (UPS).

    Appropriate use and implementation of redundancy can raise efficiency and reduce

    construction and operational cost over the life cycle of the datacenter. Everyone

    wants a Tier 4 datacenter, but there is inherent capital and operational inefficiency in

    having two complete distribution systems. Instead, a flexible and modular electrical

    design can support multiple Tier levels in the same datacenter, allowing the cost of

    the higher service level to be spent only on the systems requiring it.

    Metering at the right places in the electrical distribution system is a key feature

    thats needed in order to assess operating conditions of the system and components.

    Good metering design practices are imperative in the datacenter to continuously

    assess system heath datacenter efficiency. Metering should be implemented starting

    at the utility feeds and cascading through the system down to the rack level.

    About This ArticleThis Sun BluePrints article discusses the electrical design principles that Suns Global

    Lab & Datacenter Design Services (GDS) organization incorporated into its energy-

    efficient, pod-based datacenters. Suns GDS organization is responsible for Suns

    technical infrastructure (datacenters, labs, server and communication rooms and

    wiring closets) worldwide, and has ushered in a new generation of energy-efficient

    datacenters at Sun.

    Chapter 2, Traditional Datacenter Electrical Design on page 3, discusses how

    datacenter electrical systems are typically designed.

    Chapter 3, Increasing Electrical Distribution Efficiency on page 8, highlights the

    opportunities that we have found to improve modularity and efficiency in datacenter

    electrical design.

  • 7/31/2019 DATACENTERS Electrical Design

    4/46

    2 Introduction Sun Microsystems, Inc.

    Chapter 4, Flexibility Through Modularity on page 17, shows how our design

    choices create flexible datacenters that contribute to business agility.

    Chapter 5, Extending the Datacenter Lifecycle on page 21, discusses the

    importance of coordinating expected datacenter lifecycles with equipment refresh

    cycles. The chapter shows the many ways in which datacenters can be built from day

    one to support future expansion

    Chapter 6, Suns Electrical Design At Work on page 24, provides a tour of our

    datacenter designs from the perspective of the one-line diagrams that describe their

    electrical systems. We focus on Suns Santa Clara, California datacenters, including

    our most recent addition of Sun Modular Datacenters at the site.

  • 7/31/2019 DATACENTERS Electrical Design

    5/46

    3 Traditional Datacenter Electrical Design Sun Microsystems, Inc.

    Chapter 2

    Traditional Datacenter Electrical Design

    From an electrical design standpoint, a datacenter is a hierarchy of electrical devices

    that transmit power from a utility feed to server racks (Figure 1). One or more feeds

    arrive from the electrical utility before or after their voltages are transformed to usable

    levels. Switchgear provides, among other things, a disconnect point for the utility feed.

    Where needed, UPS and generators provide transient and longer-term backup power.

    Conduit and wireways feed distribution systems in the datacenters themselves. Power

    distribution mechanisms deliver electricity to racks and standalone systems. Within

    racks, smaller distribution systems provide power to individual servers. This chapter

    describes the various steps in the distribution chain; the next chapter describes the

    ways in which efficiency, modularity, and flexibility can be introduced into each step.

    480V

    SWITCHGEAR

    UPSSWITCHGEAR PDUs RACKSFACILITYPOWER

    TRANSFORMER

    GENERATOR

    MORE THAN ONE OF EACH DEVICE INSTALLED AT EACH LAYER

    Figure 1. A typical datacenter power distribution system transforms and delivers utility power to equipment racks.

    Utility Power and TransformerPower from the electric utility is usually delivered at voltages anywhere from 480V to

    21 kV and higher. The first step in the distribution process is to transform this voltage to

    a level that is usable by the building and datacenter equipment. The transformer may

    be owned by the utility but installed on a pad provided by the customer or it may be

    owned by the customer. Both models are used at Sun, and Figure 2 illustrates

    transformers owned by Sun at Suns Santa Clara, California campus.

    In many parts of the world, a single transformer reduces medium voltage from the

    utility to 400/230V, with 230 the final voltage supplied to datacenter equipment. (The

    400/230V notation indicates three-phase power where the first number indicates phase

    to phase and the second number indicates phase to neutral voltage). In the United

    States, voltage is reduced in two steps. A first step to 480/277V is used to supply devices

  • 7/31/2019 DATACENTERS Electrical Design

    6/46

    4 Traditional Datacenter Electrical Design Sun Microsystems, Inc.

    including HVAC equipment and lighting throughout the building. A second step to

    208/120V brings the voltage down to that used by compute equipment. Each time

    voltage is reduced, some energy losses are introduced into the power distribution

    system.

    Transformers

    Generators

    Figure 2. This view of the main switch yard in Suns Santa Clara, California facility

    shows four transformers connected to three separate utility feeds and switchgear,

    Backup generators are in the background.

    SwitchgearIn industrial electrical design terminology,

    medium voltage ranges from 1-33kV.

    Datacenters use switchgear and distribution boards to safely distribute power from the

    utility to the datacenter floor. The switchgear includes circuit breakers and switches for

    managing medium and low voltages and they are typically used to distribute large

    amounts of power to various locations within datacenters and buildings.

    The circuit breakers installed in switchgear tend to be more sophisticated than breakers

    in distribution panels. Switchgear breakers typically have intelligence for monitoring

    and control, have configurable trip points, and can include ground fault interruption

    circuitry (depending on the design). The purpose of the breakers is to interrupt and

    disconnect the load from the power source in the event of abnormally high current

    conditions that could damage the electrical system or create unsafe operating

    conditions such as a phase-to-phase or phase-to-ground faults. Switchgear may also

    include tie breakers and cross-connection schemes that allow the power path to be

    reconfigured through the same set of switchgear, or around it in case of a fault. For

    example, in a dual-path power system design, it is important to be able to re-route

  • 7/31/2019 DATACENTERS Electrical Design

    7/46

    5 Traditional Datacenter Electrical Design Sun Microsystems, Inc.

    power around a fault in the system. Tie breaker schemes allow switchgear that would

    normally be fed from one source to be switched over to a secondary source. Automatic

    transfer switches can also be used to automate this process.

    At Sun, a tie breaker scheme allows power supplied to buildings to be doubled. By

    installing double-ended switchgear with internal tie breakers, an additional power feed

    can be incorporated by installing a new transformer at the opposite end of the

    switchgear. The tie breakers then separate the switchgear from one bus into two

    distinct buses.

    Backup PowerBackup generators are used to power critical equipment in the event of a utility power

    failure. Backup power is sometimes supplied to the main switchgear, sometimes it is

    provided further down in the distribution system.

    Backup power generators cannot start instantly, so another form of backup power

    needs to continue to power datacenter equipment during the interval of eight seconds

    or less that is needed to start the generators and ready them to carry the datacenter

    and support loads. The traditional approach is to use battery backup to support the

    datacenter load during this time. Rotational UPS that draw power from a flywheel are

    starting to prove themselves superior to battery backup. Both approaches introduce

    losses that can be mitigated as discussed in the next chapter.

    Power DistributionConduit and wireway distribute the conductors that run from the switchgear to thedatacenter itself, where typically one of three techniques are used to distribute power

    to racks. The trade-offs between these approaches are discussed in detail in Datacenter

    Power Distribution on page 17.

    Distribution panel boards use standard wall-mounted distribution panels at the

    datacenters perimeter with any combination of conduit, wire mold, raceways,

    and armored cable whips running from the breaker panels to individual racks.

    Power is typically delivered underneath a raised floor in the datacenter, but also

    can be delivered overhead.

    Power distribution units (PDUs) typically consist of multiple distribution panelboards and can also include internal transformers. (PDUs without transformers are

    typically called remote power panels (RPPs). PDUs tend to have a significant

    amount of built-in intelligence and monitoring capabilities. PDUs are typically

    installed on the datacenter floor throughout the space. PDUs can be used in both

    slab and raised-floor datacenters.

  • 7/31/2019 DATACENTERS Electrical Design

    8/46

    6 Traditional Datacenter Electrical Design Sun Microsystems, Inc.

    Buswayprovides a modular track above or below rows of racks. Cans combine

    breakers and short whips that can be plugged into the busway to provide power

    directly to rack-mounted power strips. Busways are capable of distributing three-

    phase power across the datacenter floor. The cans are designed to use any

    combination of the three phases, allowing different types of equipment to be

    powered by plugging in different cans, and for power consumption to be balanced

    across phases. Sun has found that busway power distribution provides the most

    efficient and modular way to distribute power to the racks and has standardized

    on technology for new datacenters.

    Rack Power DistributionInside each rack is a power strip or rack-mounted power distribution unit (rPDU) that

    distributes power to the IT equipment installed in the rack. Sun has standardized on

    rPDUs that monitor power and allow each plug to be powered on and off over the

    network. These rPDUs provide data for power monitoring as well as allowing remote

    users the ability to power cycle equipment. As the datacenter continues to evolve,

    power monitoring and control of individual outlets will increase in importance.

    Knowing actual power loads at the server and rack level enables the datacenter

    manager to see the power utilization and distribution across the datacenter space. This

    information can then be used in the IT equipment provisioning process. It can also be

    used to dynamically adjust loads based on server utilization as compute load changes.

    Datacenter Tier LevelsAs defined by Uptime Institute's white

    paper Tier Classifications Define Site

    Infrastructure Performance, Tier levels

    range from 14, with Tier 4 being the most

    fault tolerant.

    Datacenters typically are classified into four Tier levels that are defined by the levels of

    redundancy in their power and cooling systems. From the perspective of electrical

    design, the Tier levels are defined as follows:

    Tier 1 uses a single path for power distribution, without redundant components.

    Tier 2 uses a single path for power distribution. Redundant components include

    multiple UPS and generator power.

    Tier 3 uses multiple power distribution paths along with redundant components.

    This allows one distribution path to be taken out of service for maintenance or

    repairs without having to take the datacenter offline.

    Tier 4 uses fault tolerant multiple power system and system distribution paths,

    redundant components, and uses only equipment with dual power supplies so

    that any distribution path or complete system can fail completely without

    affecting datacenter uptime.

  • 7/31/2019 DATACENTERS Electrical Design

    9/46

    7 Traditional Datacenter Electrical Design Sun Microsystems, Inc.

    Suns Approach to Electrical DesignThe Green Grids definition of PUE and DCiE is

    available in their white paper Data Center

    Power Efficiency Metrics at:

    http://www.thegreengrid.org

    Suns approach is to use the opportunities that exist within a datacenters electrical

    design to increase efficiency, flexibility, and provide room for growth. Efficiency

    increases help to reduce power consumption and increase the datacenters Power

    Usage Effectiveness (PUE) or its reciprocal DCiE. Building in flexibility allows a

    datacenter to change rack power configurations in minutes, rather than days or

    months, contributing to the companys ability to quickly adapt to changing business

    conditions and product development efforts. Preparing for future growth extends

    datacenter life by anticipating rapid hardware refresh cycles and the increased power

    requirements that accompany them.

    http://www.thegreengrid.org/http://www.thegreengrid.org/
  • 7/31/2019 DATACENTERS Electrical Design

    10/46

    8 Increasing Electrical Distribution Efficiency Sun Microsystems, Inc.

    Chapter 3

    Increasing Electrical Distribution Efficiency

    A typical datacenter can easily lose 10 percent of its power in the power distribution

    system. Transformers, UPS, and distribution contribute to power loss. Using a number

    of the techniques discussed in this section, we have reduced the power distribution

    system loss in our Santa Clara, California software organization datacenter from ten

    percent to approximately four percent of the total datacenter facility load.

    The calculation is as follows:800 kW x .06 = 48 kW48 kW x 8760 hours x $0.08 = $33,638

    A savings of six percent may not seem particularly significant. Consider one of our

    datacenters that has an IT load of 800 kilowatts (kW). Reducing overhead by six percent

    is a savings of 48 kW, or $33,638 per year. Any loss due to inefficiency is converted to

    heat, so the savings is even greater when one considers that greater efficiency means

    less cooling is needed to remove that heat, another cost reduction.

    Component SelectionThe low-hanging fruit for increasing electrical system efficiency is choosing high-

    efficiency components from transformers and UPS to server power supplies. This

    straightforward choice is often overlooked due to higher initial costs. However, if the

    total cost of ownership is evaluated, the payback period proves to be very short. With

    the current green initiative trend, these component costs are starting to come down,

    making the decision easier to justify.

    High-Efficiency TransformersIn the United States, most datacenters have at least two power conversion steps that

    require transformers. Typical transformers impose about a 3 percent loss, making them

    around 97 percent efficient. Using a high-efficiency NEMA TP1-rated transformer can

    increase performance to the mid-98 percent efficient range. This not only saves energy

    in the electrical system but since all transformer loss are converted to heat it also

    reduces electrical room cooling loads.

    High-Efficiency UPS

    There are many factors that contribute to the efficiency of UPS systems. However, a

    common factor across most UPS systems is that the higher the utilization, the more

    efficiently they operate. For example, if we look at a typical UPS efficiency curve, the

    rated efficiency of the unit is usually stated for loads greater 70% of capacity. Because

    of UPS redundancy requirements, UPS system are rarely operated in such a high region.

    Performance of the UPS begins to drop off when loads are 50 percent or less of rated

    loads. At around 30 percent utilization, UPS efficiency drops very quickly as utilization is

    reduced. Since UPS systems are a major contributor to electrical system losses it is

  • 7/31/2019 DATACENTERS Electrical Design

    11/46

    9 Increasing Electrical Distribution Efficiency Sun Microsystems, Inc.

    important to make sure the UPS system is designed so that it can be operated at a

    higher utilization level and that the efficiency of the unit is maximized for the expected

    design operations.

    APC white paper #1 describes UPS topologies.

    Please refer to: http://www.apc.com

    There are many different UPS topologies that can be used in datacenter applications,

    including double on-line conversion, delta conversion, and line interactive. In our Santa

    Clara datacenter, we chose to use a delta-conversion UPS that uses a modular approach

    to support capacity increases. This allows us to right size the UPS for day one needs and

    then grow the UPS using 200 kW power modules as the load increases, all without

    major construction. This choice provides us with UPS efficiency into the 97 percent

    range which is typically about 34 percent better than the traditional double-

    conversion UPS.

    Alternatives to Battery-Based UPSBattery-based UPS are costly to maintain. Batteries must be replaced over time,

    sometimes as early as when they are five years old; rooms must be vented to prevent

    hydrogen gas build up; catch pans must be in place to protect against acid spills; and

    battery-based UPS take a significant amount of space. Batteries are also not very

    environmentally friendly and require controls on the hazardous materials both when

    handling and disposing of them.

    A low-maintenance, more environmentally friendly approach uses the rotational inertia

    of a flywheel to generate electricity during the gap between a power failure and

    generator startup (Figure 3). There are two common approaches to rotational UPS:

    Figure 3. A line-interaction UPS is

    in use at Suns Broomfield,

    Colorado datacenter.

    The traditional approach uses a typical UPS topology, such as a double-conversion or

    line-interactive model, replacing the batteries with a flywheel that stores energy

    through rotational inertia. When utility power is lost, the energy stored in the

    flywheel powers the datacenter. It can substitute directly for a battery-based UPS

    within a building or datacenter.

    Another approach couples a diesel generator with an induction clutch. When power

    fails, the flywheel turns the generator until the diesel engine starts and comes up to

    speed.

    Flywheel-based UPS are finding increasing acceptance throughout the industry because

    they greatly reduce maintenance costs and require less space in the UPS room than

    traditional battery-based UPS systems. The biggest concern of datacenter operators is

    the relatively short ride-through time provided by the flywheel. Battery UPS system are

    typically sized to support loads for 1015 minutes while the generators come on line. A

    typical generator, however, is ready to accept full load in 810 seconds.

    If a generator does not start up in 810 seconds, there is typically very little that can be

    done to repair it during the 15 minutes the batteries can deliver power. While rotational

    UPS do require maintenance on mechanical parts such as bearings, they take far less

    http://www.apc.com/http://www.apc.com/http://www.apc.com/http://www.apc.com/http://www.apc.com/http://www.apc.com/http://www.apcmedia.com/
  • 7/31/2019 DATACENTERS Electrical Design

    12/46

    10 Increasing Electrical Distribution Efficiency Sun Microsystems, Inc.

    space and maintenance than battery backup systems. The current drawback is that

    flywheel UPS systems tend to have a higher initial cost as compared to a traditional

    battery UPS. Reduced maintenance costs usually offset the difference in a short time.

    Equipment Power SuppliesThe power supplies on server, storage, and networking equipment also contribute to

    power distribution losses. Power supplies are always sized to handle the worst-case

    scenario: a server with the maximum memory, internal disk, and peripheral cards

    installed and with the CPUs and fans running at full power. Many servers, however,

    actually operate at 50 percent or less of their name plate power (Figure 4), a range

    where historically, average power supplies can be relatively inefficient.

    Percent of Name Plate Power Output

    Efficient

    45100

    100

    Average

    PercentEfficiency

    0

    Figure 4. Power supplies such as those used by Sun are more efficient across a

    broader output range.

    Information on the 80 Plus program is

    available at http://www.80plus.org.

    With todays focus on energy efficiency, server vendors including Sun are striving to

    make their power supplies more efficient at low utilization levels. In the U.S., an electric

    utility-funded program called 80 Plus is promoting the use of power supplies that are

    at least 80 percent efficient at 20, 50, and 100 percent of their rated load. Most of the

    power supplies on servers from Sun exceed this specification, with some of them 93

    percent efficient at an 80 percent load.

    Another issue to consider is the fact that systems with redundant power suppliesoperate at far less than 50 percent load, often putting them into an inefficient range of

    operation. If the application supported by the systems is designed to be resilient to

    single points of failure, then servers with single power supplies can be used. This allows

    their power supplies to run in a much more efficient portion of their operating range.

    Regardless of whether single or dual power supplies are used, care needs to be taken to

    ensure that each power supply is plugged into a dedicated circuit.

    http://www.80plus.org/http://www.80plus.org/http://www.80plus.org/http://www.80plus.org/
  • 7/31/2019 DATACENTERS Electrical Design

    13/46

    11 Increasing Electrical Distribution Efficiency Sun Microsystems, Inc.

    Power CharacteristicsAn organizations choice of power characteristics voltages and AC vs. DC has an

    impact on datacenter power distribution efficiency.

    208V Vs. 230V

    This topic is discussed in detail in the Green

    Grids white paper 16 titled: Quantitative

    Efficiency Analysis of Power Distribution

    Systems for Data Centers The paper is

    available at: http://www.thegreengrid.org

    In the U.S., we typically reduce the utilitys medium-voltage supply in two steps, using

    two stages of transformers, down to 208/120V. Other parts of the world use higher

    voltages, such as single-phase 230V (line to neutral), yielding some efficiency benefits.

    The higher voltage can eliminate the inefficiency of a second transformer step, and it

    allows the use of less copper, as distribution paths internal to the datacenter can carry

    more power at lower amperage.

    Virtually all datacenter equipment is built to accept a range of input power from 100

    240V, so the choice of which voltage to use is one that is dependent on comfort levelsand local electrical codes. Had we had more time to evaluate, test and educate the

    project team when we built our datacenters in California, we may have been able to

    increase efficiency even further by deploying 230V throughout.

    Alternating Vs. Direct Current

    There is a long-running controversy regarding the relative merits of using high-voltage

    DC versus AC power in the datacenter. The argument is this: high-voltage (380575V) DC

    eliminates the requirement for large amounts of copper in the distribution system,

    making this aspect competitive with AC power. Using DC throughout the datacenter

    eliminates three AC-DC power conversions that add to inefficiency (Figure 5): 480 VAC is converted to direct current at the UPS to charge the batteries.

    Battery power is inverted to 480 VAC to supply the datacenter.

    The first stage of datacenter equipment power supplies converts incoming AC power

    to high-voltage DC, which is then regulated down to the low DC voltages used within

    the server, storage, or networking equipment.

    UPS PDU

    AC/DC DC/AC AC/DC DC/DC

    Power Supply Unit (PSU)

    Internal

    Voltages480 VAC

    SupplyPower

    Power Inefficiencies 380 VDC (typical)

    ServerLead-Acid Batteries

    Figure 5. The argument for DC power in the datacenter is that using DC power

    throughout eliminates multiple inefficient AC-DC power conversions.

    http://www.thegreengrid.org/~/media/WhitePapers/White_Paper_16_-_Quantitative_Efficiency_Analysis_30DEC08.ashx?lang=enhttp://www.thegreengrid.org/~/media/WhitePapers/White_Paper_16_-_Quantitative_Efficiency_Analysis_30DEC08.ashx?lang=enhttp://www.thegreengrid.org/http://www.thegreengrid.org/~/media/WhitePapers/White_Paper_16_-_Quantitative_Efficiency_Analysis_30DEC08.ashx?lang=enhttp://www.thegreengrid.org/~/media/WhitePapers/White_Paper_16_-_Quantitative_Efficiency_Analysis_30DEC08.ashx?lang=enhttp://www.thegreengrid.org/
  • 7/31/2019 DATACENTERS Electrical Design

    14/46

    12 Increasing Electrical Distribution Efficiency Sun Microsystems, Inc.

    The final report resulting from this project is

    available at:

    http://hightech.lbl.gov/documents/DATA_CENTERS/DCDemoFinalReport.pdf

    In conjunction with a California Energy Commission-sponsored project, Sun

    implemented a proof-of-concept that demonstrated the power savings of using DC in

    the datacenter environment. Sun created two identical datacenters, one with AC and

    one with DC power distribution. Off-the-shelf equipment from Sun, Cisco, and Intel was

    used, with the power supplies modified by hand to eliminate the power conversion

    circuitry that converts alternating to direct current. Incoming power was rectified,

    distributed at 380 VDC, and fed directly into the modified power supplies. This was a

    proof-of-concept demonstration only, as 380 VDC power supplies are not available as

    products from Sun. (Sun does offer 48 VDC-powered equipment through its Netra

    product line designed for communication-carrier environments). The results showed a

    25 percent improvement in power supply efficiency, and up to a 1020 percent

    improvement when the use of a flywheel vs. a battery-based UPS was factored into the

    equation.

    We believe that the benefits demonstrated by this experiment are superseded by

    improvements in power supply efficiency and that similar improvements are possible

    without the use of DC power. The equipment used in this experiment used older

    equipment equipped with power supplies where a greater improvement could be

    shown compared to todays more efficient power supplies.

    Another approach that is being discussed is using the telco standard of 48 VDC.

    Regardless of which DC power approach is used, we see some key disadvantages:

    Equipment that accepts high-voltage DC directly is not available on the market today.

    There is a limited selection of equipment that can use 48 VDC.

    There is a relative lack of experience and comfort using DC power in the datacenter.Distribution systems, system power connections, and breakers are all different, and

    everyone from electrical contractors to system administrators would need training.

    Maintenance and arc-flash suppression has not been uniformly addressed.

    For most companies, the ability to leverage the newest and best server, storage, and

    network technology is key to maintaining a competitive edge. Today, the choice of DC

    power restricts equipment choices from almost all major manufacturers.

    Appropriate Levels of RedundancyDatacenter power efficiency can be increased by using redundancy in appropriate ways.

    First, choosing a level of redundancy that is matched to the organizations mission, and

    their level of accepted risk, increases efficiency by reducing the amount of redundant

    equipment that is necessary, and also by reducing layers of components (such as UPS)

    that add to inefficiency. Second, redundancy can be implemented so that equipment is

    used in a more efficient part of its operating range.

    http://hightech.lbl.gov/documents/DATA_CENTERS/DCDemoFinalReport.pdfhttp://hightech.lbl.gov/documents/DATA_CENTERS/DCDemoFinalReport.pdfhttp://hightech.lbl.gov/documents/DATA_CENTERS/DCDemoFinalReport.pdfhttp://hightech.lbl.gov/documents/DATA_CENTERS/DCDemoFinalReport.pdfhttp://hightech.lbl.gov/documents/DATA_CENTERS/DCDemoFinalReport.pdf
  • 7/31/2019 DATACENTERS Electrical Design

    15/46

    13 Increasing Electrical Distribution Efficiency Sun Microsystems, Inc.

    Choosing Tier Levels

    Everyone wants to have a Tier 4 datacenter, with two complete power distribution

    systems so that either can be taken out of service without affecting datacenter uptime.

    In fact, most organizations only require a small portion of their datacenter to be built to

    Tier 4 specifications if any at all. The cost of implementing a Tier 4 design and

    continuous operation at that level can be more than five times greater than a Tier 1

    facility.

    Although our electrical design approach can support any Tier level, our datacenters at

    Sun are used for internal product development and typically require Tier 1 or Tier 2

    support. Our IT specific datacenters provide more critical services, and therefore require

    a Tier 3 level of service.

    A pod, as defined in the Sun BluePrints Series

    article The Role of Modularity in Datacenter

    Design, is a small, self-contained group of

    racks and/or benches that optimize power,

    cooling, and cabling efficiencies. A typical

    pod is a collection of 2024 racks with a

    common hot or cold aisle along with a

    modular set of infrastructure for it to handle

    its own power, cooling, and cabling.

    Our datacenters can support multiple Tier levels in the same room. Different

    configurations of our modular busway can feed multiple parallel power distribution

    paths down to individual racks. Since most of our equipment does not actually require

    UPS power, we can run two busways, one with UPS power and one without, to each of

    our pods. Racks that require redundancy and UPS power can connect to both busways.

    Those that dont require UPS power do not. In the end, only approximately 20 percent

    of our systems actually require UPS power, helping to increase efficiency and

    significantly reduce the capital and operating costs associated with uninterruptible

    power.

    Our pods are self-sufficient from a power, cooling, and cabling perspective, so a Tier 3

    pod can be placed in the same room with Tier 1 and Tier 2 equipment. The same wouldbe true if the corporation required Tier 4 as long as a dual-path system with or without

    redundancy was carried back to the central plant.

    Using Distributed Redundancy

    Using an appropriate level of redundancy in the electrical distribution system is one

    means to increase efficiency; the way in which you implement redundancy also has an

    impact on efficiency.

    2N Redundancy

    A typical UPS configuration uses 2N redundancy, where one of two UPS systems can

    support the entire load should one UPS fail. This model operates each UPS at less than

    50 percent utilization. Typical maximum utilization levels are 4050 percent so that

    when the UPS has to support 100 percent of the datacenter load it does not exceed its

    full capacity rating and trip offline. It should also be noted that UPS systems operating

    in this range are relatively inefficient especially if operated at less than expected full

    design loads. A hypothetical configuration illustrated in Figure 6 shows two UPS

    powering a datacenter consisting of three racks.

    http://wikis.sun.com/display/BluePrints/Energy+Efficient+Datacenters+-+The+Role+of+Modularity+in+Datacenter+Designhttp://wikis.sun.com/display/BluePrints/Energy+Efficient+Datacenters+-+The+Role+of+Modularity+in+Datacenter+Designhttp://wikis.sun.com/display/BluePrints/Energy+Efficient+Datacenters+-+The+Role+of+Modularity+in+Datacenter+Designhttp://wikis.sun.com/display/BluePrints/Energy+Efficient+Datacenters+-+The+Role+of+Modularity+in+Datacenter+Design
  • 7/31/2019 DATACENTERS Electrical Design

    16/46

    14 Increasing Electrical Distribution Efficiency Sun Microsystems, Inc.

    Figure 6. In a 2N redundant model, each UPS is sized to support 100 percent of the

    workload but operates at less than a 50 percent utilization level.

    N+1 Redundancy (Parallel Redundant)

    This model uses N+1 UPS to support a load where one UPS can fail and the remaining N

    are sufficient. The example in Figure 7 shows a three UPS N+1 UPS system, each UPS

    supports 33 percent of the power draw, but is sized to support 50 percent in the event

    that one fails. This puts each UPS at a more favorable 66 utilization level. Because each

    UPS is sized too small to power the entire server workload, the outputs must be

    synchronized to a common bus, and it is a single point of failure for this model.

    Distributed Redundancy

    A distributed redundancy model uses three or more UPS connected with multiple paths

    to servers. A distributed redundancy UPS system model can be used to achieve multiple

    distribution path redundancy where required without the need for a 2N system.

    (Figure 8). For example, a three-UPS distributed system can achieve a utilization level of

    66 percent. This is the same utilization level as the N+1 model, but the configuration

    eliminates the need to tie outputs together and eliminates the bus as a single point of

    failure. The benefits can include lower capital cost as compared to a 2N system,

    increased efficiency, and dual power paths to servers.

  • 7/31/2019 DATACENTERS Electrical Design

    17/46

    15 Increasing Electrical Distribution Efficiency Sun Microsystems, Inc.

    Figure 7. In an N+1 redundant model, all UPS are connected to all servers, but the

    bus is a single point of failure.

    Figure 8. In a distributed redundant model, each UPS supports one third of the

    servers and operates at a 66 percent utilization level. There is no single point of

    failure.

  • 7/31/2019 DATACENTERS Electrical Design

    18/46

    16 Increasing Electrical Distribution Efficiency Sun Microsystems, Inc.

    As with all approaches to UPS redundancy, distributed redundancy requires adjusting

    the balance of servers to UPS, and this requires a flexible, modular power distribution

    system that can adapt as a datacenter grows. Modularity and Flexibility are the topics

    of the next chapter.

  • 7/31/2019 DATACENTERS Electrical Design

    19/46

    17 Flexibility Through Modularity Sun Microsystems, Inc.

    Chapter 4

    Flexibility Through Modularity

    Modularity is a key datacenter design principle that enables flexibility and the ability to

    grow. At Sun, our modular, pod-based design creates energy-efficient building blocks

    that can be duplicated easily in any size or Tier-level datacenter worldwide. The pod

    design allows different modules to be selected and configured to best meet client

    requirements as a datacenter changes over time. Following our modular, pod-based

    approach, different pods in the same room can to be built to different Tier-level

    specifications because our electrical design can support it. The modular approach

    allows pods, and racks within pods, to have radically different densities, with a rack

    using 4 kW next to one that requires 30 kW. The modular approach is flexible so that a

    4 kW rack can be replaced with one using 30 kW or vice versa in a matter

    of hours. The same modular design that supports brick-and-mortar datacenters also can

    be used to support Sun Modular Datacenters as discussed in Sun Modular Datacenter

    on page 34

    Datacenter Power DistributionFor a more detailed discussion of the trade-

    offs summarized here, see the Sun BluePrints

    article:Energy Efficient Datacenters: The

    Benefits of Modular Design.

    The feature that most supports the day-to-day flexibility of our datacenters is our choice

    of power distribution on the datacenter floor itself. The challenge here is two-fold: the

    power distribution system must be able to support growth so that the datacenter can

    handle increased density at every equipment refresh cycle. The power distribution

    system also must be able to handle day-to-day equipment churn that significantly

    changes the power draw at the rack level. At Sun, this is extremely important, as spaces

    used for new hardware bring-up must allow for the next generation of products and

    even higher densities to be rolled in and powered up without long delays. Our power

    distribution system helps future Sun products to get to market faster because all outlet

    types and loads are supported. Our datacenters have products in them today that our

    customers won't see for two years.

    Hard-Wired Power Distribution

    The oldest, and the least-flexible power distribution system is one that uses circuit

    breaker panels at the datacenter perimeter with conduit, wire moulding, or armored-

    cable whips running from the breaker panels to individual racks or groups of racks.

    This approach limits flexibility, as a significant amount of electrical work is

    necessary in order to add or change service to a rack. Every time a panel is opened,

    all of the equipment attached to it is at risk.

    http://wikis.sun.com/display/BluePrints/Energy+Efficient+Datacenters+-+The+Role+of+Modularity+in+Datacenter+Designhttp://wikis.sun.com/display/BluePrints/Energy+Efficient+Datacenters+-+The+Role+of+Modularity+in+Datacenter+Designhttp://wikis.sun.com/display/BluePrints/Energy+Efficient+Datacenters+-+The+Role+of+Modularity+in+Datacenter+Designhttp://wikis.sun.com/display/BluePrints/Energy+Efficient+Datacenters+-+The+Role+of+Modularity+in+Datacenter+Designhttp://wikis.sun.com/display/BluePrints/Energy+Efficient+Datacenters+-+The+Role+of+Modularity+in+Datacenter+Design
  • 7/31/2019 DATACENTERS Electrical Design

    20/46

    18 Flexibility Through Modularity Sun Microsystems, Inc.

    Power Distribution Units

    PDUs combine transformers and breaker panels in units that are placed on the

    datacenter floor. PDUs are typically installed throughout the datacenter floor, with

    individual flexible whips powering individual racks. PDUs occupy valuable

    datacenter floor space and add to the datacenters heat load. Whips are difficult to

    manage, and every time that a PDU is opened to add or change a configuration, it

    introduces the possibility of human error, putting everything the PDU powers at risk.

    Although we have used PDUs in some of our earlier designs, we now see it as a

    limiting factor in those datacenters flexibility. This is because all changes require an

    electrician, the PDU must be powered down, much more time is required for changes,

    and the cost can be up to ten times more over the life of the electrical system when

    compared to busway systems.

    The Benefits of Modular Busway

    Our pod design removes all transformers and power distribution units from the

    datacenter floor. Instead, we use a hot-pluggable busway overhead or under a raised

    access floor to distribute power to each rack (Figure 9).

    Figure 9. Modular busway is installed overhead or under a raised access floor that

    is not used for air distribution.

    Each busway includes three phases, one neutral, and one ground conductors that are

    accessed by cans that tap into the right combinations for the power to be delivered.

    The busway supports an intermixing of 120V, single-phase power up to 208V, three-

    phase power (or the equivalent geographical power configuration for datacenters

  • 7/31/2019 DATACENTERS Electrical Design

    21/46

    19 Flexibility Through Modularity Sun Microsystems, Inc.

    located outside of the U.S.). Despite its capacity to handle up to 100A through a single

    can, an electrician can install a new circuit in a matter of minutes. This flexibility is key

    in our datacenters where equipment churn occurs on a regular basis.

    This modular approach can be used to support different Tier levels of service on a pod-

    by-pod basis. A Tier 1 pod can be supported with two busways, one over each row of

    racks in a pod. Tiers 24 can be supported with four busways, with the second pair of

    busways providing access to a redundant power source. This allows us to provide the

    required level of service to our customers while saving the cost and inefficiency of

    providing redundant power to every single rack. The pod illustrated in Figure 10 shows

    four busways delivering redundant power to the pod.

    Two busways above

    each rackBusway cans

    Figure 10. A pod using four busways provides two redundant power paths that

    support Tier 2-4 levels of availability.

    We have found busway to work equally well whether used with the in-row cooling

    approach illustrated in Figure 10, or with overhead cooling units as illustrated in

    Figure 11.

  • 7/31/2019 DATACENTERS Electrical Design

    22/46

    Two busways aboveeach rack

    Busway cans

    20 Flexibility Through Modularity Sun Microsystems, Inc.

    Figure 11. Busway can be used with overhead cooling units as easily as with in-

    row cooling.

  • 7/31/2019 DATACENTERS Electrical Design

    23/46

    21 Extending the Datacenter Lifecycle Sun Microsystems, Inc.

    Chapter 5

    Extending the Datacenter Lifecycle

    The industry is seeing a new wave of datacenter construction that is driven by

    premature obsolescence of existing datacenters that has resulted from the high

    demand driven by the global consumption of technology and services. Facilities built

    during the late 1990s were expected to last 1520 years, and most have reached a

    premature end of life. While these facilities may have sufficient space, their power and

    cooling systems no longer can support the IT equipment in them.

    The well-known reason for this problem is a mismatch between the datacenters

    projected life span and the frequency and impact of equipment refresh cycles. If a

    datacenter is built to last 15 years, then it must be built to accommodate equipment

    refresh cycles that range from 35 years. For example, a high-density datacenter in theyear 2000 consumed around 34 kW per rack. Now 34 kW per rack is below the

    industry average, and todays high-density racks are exceeding 2030 kW per rack!

    In our datacenters at Sun, we have incorporated expansion capacity to support three-

    year equipment refresh cycles. From day one, we have built a modular system that can

    accommodate growth through the addition of new modules, and we have built extra

    capacity in terms of additional equipment locations and power paths. This future

    proofing of infrastructure required an additional investment of 1015 percent in pipe

    work for the mechanical/electrical systems. But this scalability enabled Sun's agility

    and paid for itself within the first year.

    This chapter follows the path of electricity from the utility to servers. It illustrates how

    datacenters can be built to support the rapid change and increases in density that

    occur over time without requiring major construction inside or outside of in the

    datacenter itself.

    Electrical YardThe electrical yard is where the utility power is provided to the datacenter. When

    building a datacenter, or retrofitting an existing building, its important to plan for the

    future with the electrical utility: be sure that long-term power needs can be satisfied by

    the utility and under what terms. In other words, design backwards from the amount of

    power you will require or can receive to reach your end state. Build your electrical yard

    with expansion in mind:

    Plan for additional transformers that connect to new utility feeds by preparing

    concrete pads for them from the beginning.

    Design switchgear so that new feeds can be installed and cut over seamlessly.

  • 7/31/2019 DATACENTERS Electrical Design

    24/46

    22 Extending the Datacenter Lifecycle Sun Microsystems, Inc.

    Configure switchgear so that there is room for growth. One technique is to use cross-

    connect (cross tie) schemes to allow a bus to be split in half and powered by two

    separate utility feeds in the future.

    Leave room in the switchgear for additional breakers, and run empty conduits

    sized to accommodate the largest possible wire from the electrical yard to future

    equipment locations in buildings. Trench and run conduit underground only once. At

    Suns Santa Clara facility, we have installed conduit from the electrical yard to

    datacenter spaces to accommodate growth within datacenters. We also have run

    conduit from the electrical yard to existing office spaces that may become

    datacenters in the future.

    The electrical yard is typically home to one or more backup generators; plan space for

    growth by allowing space for additional generator capacity to support your end state.

    Building InfrastructureEach datacenter has a significant amount of electrical distribution infrastructure that

    needs to be designed and sized with room for expansion:

    Prepare to expand UPS systems as electrical loads grow. This requires not only a UPS

    design that is modular and can be expanded, but also floor space for additional UPS

    modules and battery racks or flywheel cabinets.

    Use transformers, not PDUs. Our modular, pod-based design uses transformers in

    separate rooms rather than PDUs on the datacenter floor. Reserve space for

    additional transformers that growth in electrical loads will require.

    Design power distribution with room for expansion and preinstall conduit to support

    the future growth. For example, if the goal is to support 100 percent growth over the

    datacenter lifecycle, then design distribution boards to be 50 percent full on day one

    to allow for easy expansion over time. Empty conduits to support future expansion

    should also be run at the time of original construction to reduce the impact of the

    expansion on the operating datacenter.

    Use industrial busway to provide power from the distribution panels to the pods. This

    allows power feeds to be changed as power consumption within pods grows.

    Pod Power DistributionEach of our pods use a modular overhead busway to deliver power from the distribution

    system to the equipment racks. Modular busway contributes to a datacenters agility by

    making it possible to reconfigure equipment racks for completely different power

    requirements voltage, phase, and amperage in a matter of minutes rather than

    hours, days, weeks, or months. Busway also enables a datacenters expansion capacity

    by supporting increasing power draws as equipment is replaced gradually over time.

    Rather than sizing the overhead busway to the maximum expected power draw, we

    have designed a strategy that can double the power provided to a pod in two phases

    allowing the power draw to increase by a factor of four over time.

  • 7/31/2019 DATACENTERS Electrical Design

    25/46

    23 Extending the Datacenter Lifecycle Sun Microsystems, Inc.

    For example, consider a pod with two busways, one above each row of racks (Figure 12).

    Our initial configuration is to jumper the two busways together through a conduit

    bridge and provide a single power feed for each pair of busways.

    Phase One:One feed for twobusways using

    Phase Two:One feed foreach busway

    Phase Three:One feed foreach splitbusway

    jumper

    Figure 12. As a pods power draw increases, its supply can be increased in two

    phases, each phase doubling the previous power capacity.

    The pods power feed can be doubled by removing the jumper and providing a power

    feed to each busway. The pods power feed can be doubled again by splitting each busway in half and

    providing a separate feed for each half.

    This expansion strategy avoids the up-front cost of purchasing high-amperage busway,

    while providing a way to support a four-fold increase in power consumption over time

    with minimal disruption or construction costs. This level of expansion in a traditional

    datacenter electrical distribution system would require a complete repowering of the

    datacenter space along with significant downtime and expense. Keep in mind that this

    strategy requires your conduit to be larger and pathways to be pre-defined to support

    the end state quantity and size of conductors. Choosing one size busway that supports

    the final load will allow the re-use of cans over the functional life of the datacenter.

    These busways also support higher voltages as discussed in the previous chapter.

  • 7/31/2019 DATACENTERS Electrical Design

    26/46

    24 Suns Electrical Design At Work Sun Microsystems, Inc.

    Chapter 6

    Suns Electrical Design At Work

    The design principles that we have discussed to this point are embodied in our

    datacenter designs worldwide. This chapter provides a top-to-bottom overview of our

    Santa Clara, California datacenters followed by a discussion of Suns newest facility in

    Broomfield, Colorado, and an overview of Suns use of Sun Modular Datacenters at the

    Santa Clara site.

    Santa Clara, CaliforniaOur electrical design tour of our Santa Clara datacenter is through a series of one-line

    diagrams. These diagrams illustrate the various components and how they are

    connected without the detail of showing each wire for each phase hence the termone line diagram.

    Electrical Yard

    Our Santa Clara project, one of the largest datacenter consolidation efforts in Suns

    history, allowed us to construct an entirely new electrical service yard to supply power

    to new datacenters and buildings.

    This electrical yard receives two 12 kV power feeds from Silicon Valley Power, each of

    which allows us to draw 4.5 MVA of continuous power. To ensure that we have power to

    grow over time, we have negotiated with the local utility to provide up to 24 MW of

    additional power to the electrical yard through additional 4.5 MVA feeders.

    A set of medium-voltage switchgear allows the additional feeds to be incorporated into

    the electrical yard without disrupting existing service. The medium-voltage switchgear

    feeds three similar sets of 480V switchgear through step-down transformers, one of

    which is illustrated in Figure 13.

    The switchgear supplies 480V power to office buildings and datacenters on the Santa

    Clara campus. The switchgear includes breakers for existing spaces and for future

    expansion, with conduit runs already installed to the future spaces.

    We accommodate expansion at this level of the distribution hierarchy by supportingeach of the three sets of switchgear with a single transformer. Each set of switchgear is

    configured with two halves that are connected with a tie breaker that is currently

    closed. When the time comes to double the power supply, a second transformer will be

    connected to a new utility power feed, and the tie breaker will be opened. Now each

    half of the switchgear has a 3 MW continuous operating capacity.

  • 7/31/2019 DATACENTERS Electrical Design

    27/46

    Existing transformer suppliesswitchgear with 480/277V

    Future transformer allowsa doubling of capacity

    Tie breaker remains closeduntil future transformer is installed

    Breakers, future breaker locations, and power feeds to buildings and datacenters

    25 Suns Electrical Design At Work Sun Microsystems, Inc.

    Figure 13. Each of three sets of 480V switchgear can support a doubling of power by adding a second transformer and

    opening a tie breaker.

    A photograph of the Santa Clara switch yard gives a visual perspective (Figure 14).

    In the foreground are three rows of similar switchgear. From right to left is the 12 kV

    switching upstream of the transformer. Next is the transformer, followed by the 480V

    switchgear. Note the empty space at the end of two of the rows to accommodate an

    additional transformer and switchgear. One already has been installed.

    Behind the 480V switchgear is the medium-voltage, 12 kV switchgear that

    accommodates existing and future utility feeds.

    Also visible in the photograph are two diesel backup generators.

    12kV Switchgearand Transformers

    Generators

    480VSwitchgearExpansion

    Locations

    12 kV Utility Feedsand Switchgear

    LoadBank

    Figure 14. A view of the Santa Clara electrical yard shows the 12 kV to 480V

    transformers and switchgear in the foreground.

  • 7/31/2019 DATACENTERS Electrical Design

    28/46

    26 Suns Electrical Design At Work Sun Microsystems, Inc.

    Backup Generators

    Because the majority of our datacenters are for research and development efforts, the

    pods in them are designed to Tier 12 specifications. For 20 percent of the load, we

    deploy UPS to support more critical operations. As operational risks increase, we deploy

    generators behind the UPS to provide continuous power.

    Figure 15 shows a portion of the one-line diagram showing our backup generator

    configuration. Two backup generators are currently installed, with space, conduit, and

    breaker positions for a third. This provides 2 MVA of power today, with 3 MVA when the

    third generator is installed. The generators provide power to a set of paralleling

    switchgear that combines the generator outputs. A 1000 kW load bank is installed to

    provide a full load when testing the generators. Regular 100 percent load testing of

    generators is important to make sure the generators are operating correctly and always

    ready to accept load.

    The paralleling switchgear currently feeds one 800 kVA UPS with provisions for future

    growth. In the event of a failure, the feed is switched through automatic transfer

    switches (ATS). Two automatic transfer switches (ATS) switch the power feed for the UPS

    from utility power to generator power in the event of a power failure. A third ATS

    supplies power to keep the cooling system operating.

    Existing twogenerators

    Futuregenerator

    Feed from480Vswitchgear

    Supply to UPS

    Automatictransferswitch

    Figure 15. Our Santa Clara electrical yard includes three generators that provide

    backup power to UPS.

  • 7/31/2019 DATACENTERS Electrical Design

    29/46

    27 Suns Electrical Design At Work Sun Microsystems, Inc.

    Battery-Based UPS

    Our Santa Clara site is equipped to accommodate a fourth UPS to bring the total to

    3.2 MVA. The site uses three 800 kVA UPS capable of providing up to 2.4 MVA of

    uninterruptible power. We chose APC Symmetra MW units for the Santa Clara site for

    their modularity and efficiency. The APC UPS is unique in that it enables the UPS system

    to grow in 200 kW increments. At the Santa Clara site, two of the three UPS are sized

    with 800 kW frames with only 400 kW of power modules installed, right sizing the UPS

    to our day one needs. As our loads grow, we will add additional power modules that

    grow the UPS to its full 800 kW capacity with only minimal construction in the UPS

    room to match battery capacity to UPS capacity.

    Power supply fromautomatic transfer

    switch

    To transformers anddistribution panels

    Overhead busways providing uninterruptiblepower to pods

    Figure 16. An 800 kVA UPS supplies power to three transformers, each of which

    supplies 208/120V uninterruptible power to a set of busways.

    The UPS illustrated in Figure 16 takes its input power from the automatic transfer

    switch illustrated in Figure 15. Its output feeds a distribution panel that connects to

    three transformers that step down the 480/277V power to the 208/120V power that

  • 7/31/2019 DATACENTERS Electrical Design

    30/46

    28 Suns Electrical Design At Work Sun Microsystems, Inc.

    feeds the busways. One transformer is illustrated in Figure 16. It supplies power to a

    distribution panel that feeds a set of 225A and 400A busways inside the datacenter

    spaces.

    Pod Power Distribution

    For the majority of our pods that only require Tier 1 service, a single 480V feed from the

    switchgear supports multiple transformers that bring the voltage down to the 208/120V

    supplied to pods. The example shown in Figure 17 illustrates pairs of busway jumpered

    together as described in Pod Power Distribution on page 22.

    Supply from480V switchgear

    480V transformer

    Figure 17. Power is distributed to non-critical loads through transformers that

    feed 208/120V power to overhead busways.

    Metering and Power Management

    One of the most important aspects of datacenter electrical design is an integrated

    metering and energy management system. These systems are critical because they

    provide the ability to evaluate how power is being used in the datacenter, power

    quality or disturbance events, how efficiently the datacenter is operating, and what

    impact any energy-saving measures have on overall efficiency.

  • 7/31/2019 DATACENTERS Electrical Design

    31/46

    29 Suns Electrical Design At Work Sun Microsystems, Inc.

    As we discussed in the Sun BluePrints Series article Energy Efficient Datacenters: The

    Role of Modularity in Datacenter Design, power usage effectiveness (PUE) is the ratio of

    total facility power to the IT equipment load. In order to obtain this ratio, and to be

    able to observe energy consumption of the various datacenter subsystems, appropriate

    metering capabilities must be placed at strategic locations cascaded through the

    electrical system. In our Santa Clara datacenters, we have metering and power

    management in place at the following locations:

    The utility switchgear

    All major switchgear

    All UPS, ATS, and generators

    Each overhead busway

    Each rack is equipped with a rack-mounted power distribution unit (rPDU) that

    monitors overall power consumption and also provides remote on/off per-outlet

    control. These rPDUs can be monitored over the network, providing fine-grained data

    on IT equipment loads.

    Broomfield, ColoradoOur Broomfield, Colorado location is the site of our most recent datacenter

    construction project. Spurred by the need to consolidate the former StorageTek site into

    our Broomfield campus, there are two significant differences between this datacenters

    electrical design and the Santa Clara design described above:

    No electrical yard. In Broomfield, the utility provides 480V power through a set of

    primary voltage transformers located at the campus perimeter. For redundancy

    purposes, these transformers are loop fed through utility company-owned switch

    cabinets. This is an example of where the utility owns the primary voltage feeders,

    transformers, and switch cabinets.

    Flywheel UPS. The Broomfield campus is the largest installation of rotational UPS

    at Sun. The double-conversion UPS used in Broomfield supplies 900 kVA of backup

    power, sufficient to power critical loads between the time of a power failure and

    diesel generator startup. The UPS pictured in Figure 18 provides 15 seconds of

    backup power to critical loads, sufficient to cover the 8 seconds between a power

    failure and diesel generator startup.

    Main Power Distribution

    Power to datacenter equipment located on floors 14 of the Broomfield building

    originates from utility transformers located at one end of the building. One

    transformer feeds power to a 4000A, 480V main distribution board that serves

    equipment loads on the first and fourth floors. The second transformer feeds power to

    a 5000A, 480V main distribution board that serves equipment loads on the second and

    third floors. The two electrical services combined are capable of delivering 7.1 MW to

  • 7/31/2019 DATACENTERS Electrical Design

    32/46

    30 Suns Electrical Design At Work Sun Microsystems, Inc.

    datacenter equipment on floors 14. A transient voltage surge suppression device is

    installed at each service entry point to protect the building electrical system from

    voltage surges generated outside the building.

    Figure 18. The rotational UPS used in Broomfield supplies 960 KW kVA of backup

    power, sufficient to power critical loads between the time of a power failure and

    diesel generator startup.

    The main switchboards are equipped with spare circuit breakers and spaces with

    conduit runs to the secondary electrical rooms located on the second and fourth floors

    for future expansion. A one-line diagram illustrating this design is illustrated in

    Figure 19.

    The central plant transformers are fed from a new utility transformer located northeast

    of the building. It feeds power to a 2500A, 480V main distribution board which serves

    mechanical loads supporting the datacenter. The electrical service is capable of

    delivering 2.2 MW to mechanical load in the central plant.

    Pod Power Distribution

    The two main distribution switchboards distribute 480V power to a series of 225 kVA

    and 500 kVA high-efficiency dry-type transformers located in secondary electrical rooms

    on each floor. We sized these transformers so the would have a much greater load than

    the industry standard of 30 percent. High-efficiency transformers were selected because

    at a higher load factor, efficiency tends to remain constant and at a higher level. In

    contrast, the efficiency of standard dry-type transformers decline sharply beyond the 30

    percent load factor.

  • 7/31/2019 DATACENTERS Electrical Design

    33/46

    31 Suns Electrical Design At Work Sun Microsystems, Inc.

    Figure 19. Broomfield datacenter main power distribution

    Each transformer feeds a large 120/208V distribution panelboard also located in the

    secondary electrical rooms. A transient voltage suppression system (TVSS) device is

    installed at each distribution panelboard which protects sensitive datacenterequipment downstream from voltage surges internally generated within the building.

    The distribution panelboards are equipped with spare circuit breakers, spaces, and

    conduits routed to locations of future datacenter panelboards. The distribution

    panelboards feed 120/208V panelboards that distribute power to all 225A busways in

    the datacenter. The diagram shown in Figure 20 illustrates how pod power is distributed

    from a typical secondary electrical room to datacenter busway.

  • 7/31/2019 DATACENTERS Electrical Design

    34/46

    32 Suns Electrical Design At Work Sun Microsystems, Inc.

    Figure 20. Pod power is supplied from a 500 kVA transformer located in a

    secondary electrical room.

    Rotational UPS

    A 960 kW/1200 kVA, 480V centralized rotational UPS provides approximately 15 seconds

    of back-up power for critical datacenter equipment located in the mainframe, server

    room and one pod in the CTC lab located on the second floor. The UPS has four

    modular 240 kW/300 kVA flywheels in which three of the four flywheels are needed to

    support the critical loads. This N+1 design approach provides redundancy where one

    flywheel can be completely taken offline for maintenance purposes. The UPS is

    equipped with a full-maintenance wrap-around bypass so that it can be taken out of

    service without interrupting power to critical loads. At 97 percent, the efficiency of the

    rotational UPS is higher than a traditional battery-based system due to the fact that the

    two electrical conversions do not occur under normal operating conditions only

    when the flywheel is carrying the critical load.

    The UPS illustrated in Figure 21 takes its input and maintenance by-pass power from a

    1600A, 480V emergency distribution panel. This distribution panel is equipped with a

    TVSS device which protects sensitive datacenter equipment downstream from voltage

    surges internally generated within the building. The UPS output feeds a 1600A, 480V

    main distribution panel that distributes power to a large 225 kVA and 500 kVA high-

    efficiency dry-type step-down transformers. The transformers feed 120/208V

    panelboards that distribute power to all 225A busway in the datacenter.

    Back-up Generator

    Emergency back-up power to the datacenter and central plan is served from an existing

    1250 kW/1562.5 kVA diesel generator located outside the building. The back-up

    generator feeds three emergency main distribution boards located in main electrical

    room which supports life safety loads and critical secondary mechanical equipment

  • 7/31/2019 DATACENTERS Electrical Design

    35/46

    33 Suns Electrical Design At Work Sun Microsystems, Inc.

    that supports cooling to critical datacenter and the rotational UPS. It also feeds an

    emergency main distribution board that supports critical primary mechanical

    equipment in the new central chiller plant.

    Metering and Power Management

    The Broomfield datacenter has metering and power management throughout. Three-

    phase energy and power measurement with data logging and power quality analysis

    can be obtained locally from each meter location or remotely from the campus central

    control room or off campus from a Web browser. Metering has been installed at the

    following locations:

    The two 480V main distribution switchboards are monitored to determine total power

    consumption for the four floors of the datacenter.

    Each branch distribution feeder in the 480V main distribution switchboards is

    monitored.

    Figure 21. The Broomfield rotational UPS are integrated into the power design so

    that any one of them can be taken out of service without disrupting loads.

  • 7/31/2019 DATACENTERS Electrical Design

    36/46

    34 Suns Electrical Design At Work Sun Microsystems, Inc.

    Input and output distribution panelboards monitor the flywheel UPS power and

    quality.

    Each overhead busway incorporates power monitoring, allowing a per-pod evaluation

    of power consumption of equipment.

    Each rack is equipped with an rPDU that monitors overall rack power consumption.

    These in-rack PDUs can be monitored over the network, providing fine-grained data

    on IT equipment loads.

    Sun Modular DatacenterFor more information on the Sun Modular

    Datacenter, please visit

    http://www.sun.com/sunmd

    Recent expansion at our Santa Clara site has used two Sun Modular Datacenters (Sun

    MDs). This unit is a self-contained containerized datacenter configured in an enhanced

    20-foot shipping container with integrated high-efficiency cooling and power

    infrastructure. Sun MD is available in 2 configurations: the original eight-rack S20

    model, and a new seven-rack D20 edition. Both support a 200 kW capacity in only 160

    square feet of space. The Sun MD can typically be deployed much more quickly than a

    traditional datacenter; all that is required is to provide appropriate chilled water,

    networking and power. This section describes the product power features and an

    overview of the external power requirements for deploying a Sun MD.

    Power Overview

    The Sun MD is available in two different electrical configurations. The low-voltage

    version operates on 190 to 220 VAC, three-phase, 50 or 60 Hz electrical service. The high-

    voltage version operates on 380 to 415 VAC, three-phase, 50 or 60 Hz electrical service

    Power Distribution in the Sun MD

    Poweris routed into the Sun MD through two electrical feeder entrances, one on each

    side of the container, and can be provided by one or two external power sources.

    The Sun MD has a primary and a secondary internal power distribution panel

    corresponding to the two electrical feeder entrances (Figure 22). The internal power

    panels provide redundant power to each of the racks. Each panel supplies power

    through a set of circuit breakers to each of the racks and to each of the HX fan control

    units in the Sun MD.

    Supplying Power to the Sun MD

    Power can be supplied to a Sun MD through a commercial utility, an on-site utility

    power generator, or a standalone power generator in any combination. There are

    several factors to consider in designing and deploying external power infrastructure for

    the Sun MD, including requirements for redundancy, uptime, mobility, and existing site

    power infrastructure.

    http://www.sun.com/sunmdhttp://www.sun.com/sunmdhttp://www.sun.com/sunmdhttp://www.sun.com/sunmdhttp://www.sun.com/sunmd
  • 7/31/2019 DATACENTERS Electrical Design

    37/46

    35 Suns Electrical Design At Work Sun Microsystems, Inc.

    Figure 22. Sun Modular Datacenter power distribution panels. This view of a low-

    voltage unit is from the back of the Sun MD, with A panel on the left and the B

    panel on the right.

    Uptime is typically a primary concern in the deployment of a datacenter. In order to

    provide the highest levels of service, a means of maintaining power in the event that an

    external power source fails is highly recommended. This involves a design using an

    automatic transfer switch to switch from the primary source of power to a secondary or

    backup source of power such as a generator. A UPS is used to supply power to the SunMD during the time interval when the primary power fails and when the secondary

    source comes online.

    While the actual configuration of the electrical power distribution system will vary, a

    typical external power infrastructure will have many of the following components:

    Commercial electric utility service

    Site distribution panel

    Automatic transfer switch (if required)

    Chiller/heater sub-panel (if required by building code)

    Transformer (if required to match line voltage)

    Generator (optional)

    Uninterruptible power supply (optional)

    UPS power distribution panel (if required by building code)

    When we deployed Sun Modular Datacenters at our Santa Clara site, we utilized the

    flexibility of the electrical infrastructure described in previous sections and literally

    snapped in the modular datacenters. We installed high-efficiency transformers outside

    next to each container to convert 480V to 208V. Installing the transformers outside

  • 7/31/2019 DATACENTERS Electrical Design

    38/46

    36 Suns Electrical Design At Work Sun Microsystems, Inc.

    eliminated the need to provide cooling for the transformers. The containers in Santa

    Clara are installed downstream of our UPS system which is currently providing power to

    both the Sun MDs as well as our building-based datacenters.

  • 7/31/2019 DATACENTERS Electrical Design

    39/46

    37 Summary Sun Microsystems, Inc.

    Chapter 7

    Summary

    A datacenters electrical design plays a critical role whose influence ranges from

    protecting real estate investments to reducing day-to-day power consumption.

    Traditional electrical designs can limit growth, reduce business agility, and add, rather

    than subtract, from skyrocketing utility bills. In contrast, the datacenter designs that

    we have used at Sun facilitate growth, increase agility, and provide significant savings

    in energy consumption. Rather than being a static aspect of datacenter design that

    hampers business operations, our datacenter electrical design flexibility helps to better

    align our datacenters and business operations.

    Our modular electrical design provides greater flexibility that helps our datacenters

    better support our business operations. Our modular design allows our engineeringorganization to roll in and power a next-generation server in a matter of minutes. The

    same modularity that allows us to support different Tier levels within the same

    datacenter also saves costs by delivering only the required amount of redundancy.

    Our philosophy of preparing for future growth from day one has a dramatic impact on

    the datacenter lifecycle. By building a datacenter electrical system that can support

    future generations of IT equipment, we have better matched equipment refresh cycles

    with our planned datacenter life cycles. This not only helps prepare our business for the

    future, it helps to protect the immense investment in real estate by increasing the

    longevity of our datacenters. This agility has become a competitive advantage for Sun.

    Ultimately, a datacenter electrical system must deliver power from the electric utility to

    each piece of IT equipment. Taking advantages of the opportunities to increase

    efficiency along the way, making sure not to overprovision for day-one capacity, and

    through careful monitoring, we have been able to achieve about a six percent greater

    efficiency that amounts to an annual savings of $33,638 in one datacenter alone. From

    energy-efficient transformers to appropriate implementations of redundancy,

    datacenter electrical designs offer abundant opportunity to reduce power consumption

    and overall operating costs.

    One of the best aspects of our datacenter electrical design principles is that they are

    straightforward and easy to implement, so organizations outside of Sun can reap

    similar benefits. While our designs initially seemed radical compared to traditional

    designs, the choices that we have made are now embodied in mainstream practices

    at Sun. These practices are also starting to become prevalent in the industry.

  • 7/31/2019 DATACENTERS Electrical Design

    40/46

    38 Summary Sun Microsystems, Inc.

    About The Authors

    Michael Ryan

    Mike Ryan is a Senior Staff Engineer in Suns Global Lab & Datacenter Design Services

    organization. Mike graduated from San Jose State University with a degree in

    mechanical engineering. He is a licensed professional mechanical engineer and has

    been involved in the design, construction, and operation of mission-critical facilities for

    the past 18 years. His experience spans numerous industries such as gas turbine co-

    generation, semi-conductor manufacturing, and mission-critical datacenters. For the

    last seven years he has focused on the design and operation of mechanical and

    electrical infrastructure systems supporting high-availability datacenters. Mike joined

    Sun as a Staff Engineer for the GDS organization in March of 2006. Mike is the primary

    author of the GDS physical standards and was the lead design engineer for the Santa

    Clara, California datacenter project, one of the largest and most complex in Sun's

    history. He also provided supporting engineering services for the Broomfield, Colorado

    datacenter project. Mike's design work supports the Act portion of Sun's Eco strategy,

    and was showcased at Sun's Eco Launch in August 2007.

    Mike is a member of ASHRAE (American Society of Heating, Refrigeration, and Air-

    conditioning Engineers). He also participates in the Data Center Pulse and the Critical

    Facilities Round Table group. Mike was the recipient of Sun's prestigious Innovation

    Award presented by Sun's CEO, Jonathan Schwartz ad CTO, Greg Papadopoulos in July of

    2008.

    Dean Nelson

    Dean is the Senior Director of Global Lab & Datacenter Design Services (GDS) in the

    Work Environments (WE) business unit of Sun Microsystems. The GDS organization

    bridges the gap between Facilities, IT, and Engineering, and is responsible for managing

    Suns multi-billion dollar global technical infrastructure portfolio including datacenter

    design, standards and strategy. The GDS work resides in the Act portion of Suns Eco

    strategy, and was showcased at Suns Eco Launch in August, 2007, and the Colorado

    Data Center grand opening in January, 2009.

    Dean has been in the technology industry for 19 years, of which 16 have been with Sun.

    He spent four years in Sun manufacturing in roles ranging from component-level debugto managing quality. This included helping the drive to achieve ISO 9002 certification.

    Dean joined the Sun Engineering community in 1993. He led systems and network

    administration support for some of Suns largest and most complex R&D lab

    environments.

    Dean left Sun in 2000 to join a networking startup company called Allegro Networks. At

    Allegro, he built a world-class QA team, state of the art global R&D lab environments

    and fully integrated automation system.

  • 7/31/2019 DATACENTERS Electrical Design

    41/46

    39 Summary Sun Microsystems, Inc.

    In 2003, Dean returned to Sun joining the newly formed N1 Software organization. He

    orchestrated the integration of Terraspring and Center Run R&D labs and the merger of

    Sun Cluster software into N1 technology. In mid-2003, Dean took over management all

    of the N1 organizations R&D labs, build engineering, automation, and capital budget

    responsibilities world-wide. In 2004, he became a leading member of the Global Lab &

    Datacenter Design Services (GDS) team tasked with creating a strategy to standardize

    Suns multi-billion dollar technical infrastructure portfolio. He was the architect of the

    GDS operating model and lead design engineer for lab and datacenter projects world-

    wide. In 2006, he became the GDS Director. Since taking over the group, Dean has

    delivered the GDS strategy, executing the largest technical infrastructure consolidation

    in Suns history compressing the 1.4 million square foot portfolio by 48 percent, a $250

    million dollar investment.

    Dean holds numerous industry technical and business board positions including

    Founder of Data Center Pulse (http://datacenterpulse.org) - an exclusive datacenter

    owner community. Dean was featured in Contrarian Minds, a focus on the engineers,

    scientists and dreamers of Sun Microsystems. Dean was also the recipient of Suns

    prestigious Innovation Award presented by Suns CEO, Jonathan Schwartz and CTO,

    Greg Papadopoulos in July of 2008. Dean lives in Northern California with his wife and

    daughter.

    Serena Devito

    Serena DeVito is a Datacenter Design Engineer in Suns Global Lab & Datacenter Design

    Services organization. Serena joined Sun over ten years ago and has spent the bulk of

    her career as a system administrator within the IT organization where she designed,

    deployed, and supported critical infrastructure for the company. She then moved to the

    Software organization and managed the beta testing project for the Sun Cluster

    product group. Serena acted in a customer capacity run