Data sheet
DH-SMT/SI ED.96.N6.02 © Danfoss 12/2008 1
Electrical actuatorsAMB 162, AMB 182
AMB 162 and AMB 182 actuators are used for temperature control in central heating systems together with 3-way and 4-way rotary valves of the types HRB and HFE.
The actuators are applicable with: - Controllers with 3-point outlet (e.g. ECL)- Controllers with standard voltage or current output (e.g. ECL)
Main data:. 24 V or 230 V. 3-point control. Voltage signal of 0-10 V or 2-10 V (factory setting: 2-10 V).. With or without adjustable actuator limit
switches
A 2m wire is supplied with the actuators.
Description
Ordering Type Supply voltage Torque Speed Control signal Remark Code No.
AMB 162
24 V a.c.
5 Nm
140 s
3-point
- 082G4030
S* 082G4031
230 V a.c.
70 s-
082G4032
140 s082G4034
S* 082G4035
670 s-
082G4040
24 V a.c./V d.c. 140 s 0-10 V 082G4050
AMB 182
24 V a.c./V d.c. 15 Nm140 s
0-10 V -082G4055
280 s 082G4056
24 V a.c.10 Nm 70 s
3-point-
082G4062
15 Nm 280 s 082G4064
230 V a.c.
10 Nm 70 s 082G4067
15 Nm 280 s082G4069
S* 082G4079* Actuator with built-in auxiliary signal switch
Two couplings (linkage kits) are delivered with the actuators:- 082G4235 (MS-NRE6-D) , to be used with HRB valves- 082G4230 (MS-NRE), to be used with HFE valves
Accessories
Type Designation Code No.
AUX switch Auxiliary signal switch 082G4012
2 ED.96.N6.02 © Danfoss 12/2008 DH-SMT/SI
Data sheet Actuator AMB 162 and AMB 182
Technical data Supply voltage 24 V a.c./V d.c. or 230 V a.c., 50/60 Hz
Power consumption 2.5 VA (5 Nm) and 3.5 VA (10/15 Nm)
Operating torque 5, 10, or 15 Nm
Wire 2 m (3 × 0.5 mm2)
Actuator limit switch 2 A/250 V a.c.
Control mode 3-point or 0-10 V/2-10 V
Rotation angle Electrically limited to 90°
Manual operation Mechanical disengagement
Ambient temperature (during operation) 0 °C … +50 °C
Transport and stock temperature −10 °C … +80 °C
Protection class II (without earthing wire)
Enclosure IP 42
Weight AMB 162: 0.46 kgAMB 182: 0.54 kg
- marking in acc. with standardsLow Voltage Directive 73/23/EEC, EMC-Directive 2004/108/EEC:EN 60730-1, EN 60730-2-14
Installation The actuators can be mounted directly on the rotary valve by means of the supplied mounting kit.
The rotating angle is limited to 90° and when the actuator reaches the actuator limit, the voltage supply to the actuator is disconnected.
Application principle
Boiler system with ECL electronic controller and HRB rotary valve.
Linkage
Mounting kit Make Type Code No.
MS-NRE
Danfoss HFE (HRE old, HRB old)
082G4230ESBE
MG, G, F, T, TM
H, HG
TA VRTE
Termomix B, C, D
Sauter MH32, MH42
MS-NRE6-D Danfoss HRB 082G4235
MS-NRC CENTRA ZR, DR 082G4255
MS-NRL L&G VCI 31, VBG 31, VBF 21 082G4270
Ordering (continuous)
DH-SMT/SI ED.96.N6.02 © Danfoss 12/2008 3
Data sheet Actuator AMB 162 and AMB 182
Wiring 3-point control
1 = brown, 2 = blue, 3 = white + AUX switch
0-10 V
1 = black, 2 = red, 3 = white, 4 = whiteY = input signalU = output signal
Dimensions
N L 24 V a.c./ 24 V d.c.*/
* valid only for some actuators - see ordering section
4 ED.96.N6.02 Prepared by Danfoss A/S © 12/2008
Data sheet Actuator AMB 162 and AMB 182