SKC-SC controls fire curtains and smoke curtains. The system is modular and can be configured on a PC via a USB interface to provide the required functionality for a project. Activation is via a fire alarm system or its own smoke alarm and manual control points.When the alarm is raised, the system provides status messages and optical or acoustic signalling. It monitors cables for wire- break and short circuit. The control panel is designed for the safe operation of automatic smoke and fire curtains. It contains programs for intermediate positions for both drive up / drive down and ‚‘gravity fail-safe‘‘ operation, as well as for the re-opening of the curtain after it has been lowered. The control panel is designed to meet the requirements of the pr12101-9 product standard. It has a local power supply system to maintain all control functions over a period of at least 72 hours, meeting the requirements of EN 12101- 10.The control panel meets all the requirements of CE marking under the Construction Products Regulation. Its features and benefits are described overleaf. SKC-SC PRODUCT DATA SHEET | SKC-SC CONTROL DATA SHEET | CURTAIN CONTROLS

DATA SHEET | CURTAIN CONTROLS SKC-SC curtain control system.pdf · SKC-SC controls fire curtains and smoke curtains. The system is modular and can be configured on a PC via a USB

  • Upload
    others

  • View
    1

  • Download
    0

Embed Size (px)

Citation preview

Page 1: DATA SHEET | CURTAIN CONTROLS SKC-SC curtain control system.pdf · SKC-SC controls fire curtains and smoke curtains. The system is modular and can be configured on a PC via a USB

SKC-SC controls fire curtains and smoke curtains. The system is modular and can be configured ona PC via a USB interface to provide the requiredfunctionality for a project. Activation is via afire alarm system or its own smoke alarm andmanual control points. When the alarm is raised, the system provides status messages and opticalor acoustic signalling. It monitors cables for wire-break and short circuit.

The control panel is designed for the safeoperation of automatic smoke and fire curtains. Itcontains programs for intermediate positions forboth drive up / drive down and ‚‘gravity fail-safe‘‘operation, as well as for the re-opening of thecurtain after it has been lowered.

The control panel is designed to meet therequirements of the pr12101-9 product standard. It has a local power supply system to maintainall control functions over a period of at least 72hours, meeting the requirements of EN 12101-10. The control panel meets all the requirementsof CE marking under the Construction ProductsRegulation.

Its features and benefits are described overleaf.

SKC-SC

PRODUCT DATA SHEET | SKC-SC CONTROL

DATA SHEET | CURTAIN CONTROLS

360°

360°

360°

360°

360°

Page 2: DATA SHEET | CURTAIN CONTROLS SKC-SC curtain control system.pdf · SKC-SC controls fire curtains and smoke curtains. The system is modular and can be configured on a PC via a USB

KL monitoring

Safety bottom bar

Attached to the bottom bar

LS monitoring

Obstruction warning system

Installed in the wall opening

WN Function

Emergency opening by people escaping

Button adjacent tocurtain

WF Function

Emergency opening by fire-fighters

Manual release

Break glass push button

Button adjacent tocurtain

Auto release

Smoke or heat detector

In front of or behind the curtain

S Signals

Multi-tone siren / strobe light

Installed in the immediate vicinity of

the curtain

S Signals

Multi-tone siren / strobe light / voice

warning system

Installed in the immediate vicinity of

the curtain

SKC-SCCONTROLS

Modular design for

your safetyEV

Supply modulewith backup

AMConnection

module

BMHeart modulewith processor

and USB

ZMAuxiliary module

for addedfunctions

WRe-transmission

module

SSignallingmodule

rest position rest position rest position

hold t2 HWD hold t2 HWD-1 hold t2 HWD +2,0 m

hold t4 HWD-2

FFL curtain dropped FFL curtain dropped FFL curtain dropped

sketch 1 sketch 2 sketch 3

way

t1

way

t1

way

t3

way

t1

HWD (half way down) program

SOME FEATURES OF THE SKC-SC CON-TROL SYSTEM

Processor controls:A wide range of modesModular designUSB interfaceConfiguration via a PC72 hours local power supplyMonitoring of cablesIntermediate drop position option

Developed for automatic smoke and fire curtainsOperation with ASB types 1 to 4

Designed and tested in accordance with prEN 12101-9, EN 12101-10 and BS 8524. Certification being prepared.

Can control up to four groups of curtains, if necessary each with different functions.

PRODUCT DATA SHEET | SKC-SC CONTROL

SKC-SC controls fire curtains and smokecurtains. It has been tested in accordancewith prEN 12101-9 and BS 8524. Ithas a power supply to maintain thecontrol functions for at least 72 hours inaccordance with EN 12101-10.

It provides the following functions:• Maintains the curtains in the raised position in the event of a temporary interruption to the power supply assuming the optional uninterruptible power supply (UPS) has been supplied and connected.• Automatically lowers the curtain in case of alarm.• Intermediate stop for curtains before they descend completely to the floor (HWD-1 + 2).• Emergency opening button to enable personnel leaving an area to be able to open the curtain once it has been lowered.• Fire-fighter’s override button.• Safety bottom bar to stop the curtain if there is an obstruction.• Beam detector to monitor the opening for obstructions.• Combination multi-tone siren and strobe light with the option of a voice warning system.• Manual operation• Status reports to building management. The system is modular and can beconfigured on a PC via a USB interfaceto provide the required functionality fora project.

The history relating to the system statusand fault events is stored within theinternal memory.

The panel has a switch for service andmaintenance purposes.

“People feel better in Colt conditions.” | Version 08-2016© Colt International Licensing Limited 2016www.coltgroup.com

rest position rest position rest position

hold t2 HWD hold t2 HWD-1 hold t2 HWD +2,0 m

hold t4 HWD-2

FFL curtain dropped FFL curtain dropped FFL curtain dropped

sketch 1 sketch 2 sketch 3

way

t1

way

t1

way

t3

way

t1

Emergency opening program

ASB types 2 and 4Without fail-safe

function

ASB types 1 and 3With fail-safe func-

tion

Parameters entered by use of the ''SmokiControl'' program

t1 t

rave

lt3

tra

vel

Curtain up

HWD-1

HWD-2

Curtain downFloor level

Stop t2

Stop t4

Curtain up

HWD-2.0m

Curtain downFloor level

Stop t2

t1 t

rave

l