Main dimensions
Flue Gas Flange
Dimensions in accordance with Part 4 of the DIN 24154 Standard
Project number: 147083/2.74 DA078
Offer No.: 1168947643-74 Printing date: 19.06.2012
Page 1 of 1
nominal diameter Dimension(s) Quantity wall thickness weight
[DN] 1)
D 1 D 2 D 3 D 4 Bores
[mm] [mm] [mm] [mm] [mm] [ ° ] [ ° ] [ - ] [mm] [kg]
400 484 448 392 11,5 15 30 12 8 3,8
The bores are evenly distributed along the periphery.
Dimensions with ± 1 % tolerance; transport weight indication with ± 4 % tolerance and operating weight indication with ± 2 %
tolerance
The exhaust pipe is not pushed through and welded, as in DIN 24154 R4, but rather butted onto the flange and welded!
Load securing device
LOGANO SHD815
in three-pass flame-tube smoke-tube technology
Project number: 147083/2.74 DA368
Offer No.: 1168947643-74 Printing date: 19.06.2012
Page 1 of 1
Explanation of symbols
Lifting equipment to be fastened here, only
centre of gravity
Lashing equipment
LOGANO SHD815 Anhängelast
Nominal output Mean working gauge pressure Transportation weight A 1 A 2
[kg/h] [bar] [kg] [kg] [kg]
3500 8 9521 4899 4622
Dimension(s)
L 1 L 3 L 6 L 8 L 9 B 1 H1 1)
[mm] [mm] [mm] [mm] [mm] [mm] [mm]
6217 3030 735 100 50 2165 2510
Base frame centre of gravity Lashing point requirements
L 2 L 7 B 2 wide flange beam L 4 B 3 H 2 L 5 B 4
[mm] [mm] [mm] [IPB - HEB - DIN1025] [mm] [mm] [mm] [mm] [mm]
3750 425 1655 180 1781 815 1143 1000 1655
The scope of delivery is defined in the order confirmation.
Transport the boiler on anti-slip mats (positioned below the boiler feet) with a coefficient of sliding friction of µ >= 0.6.
The entire surface of the base frame must rest on the loading platform. 1)
Height to top edge Transportation lugs
Main dimensions
LOGANO SHD815
in three-pass flame-tube smoke-tube technology
Project number: 147083/2.74 DA011
Offer No.: 1168947643-74 Printing date: 19.06.2012
Page 1 of 2
51.004 terminal box D12.002 Quick shut-off blow down valve
A01.000 Burner D12.503 Connection for drainage flue gas condensate
D03.000 Flue gas connection socket D13.001 Feed water shut-off valve
D03.002 Flue gas chamber D13.002 Feed water non-return valve
D04.007 Reversing chamber door D14.001 Pressure indicator (with test unit)
D05.000 Inspection opening steam-side D14.002 Pressure limiter
D05.001 Inspection opening water side D14.005 Shut-off valve
D05.002 Inspection opening flue gas side D14.013 Pressure transducer
D05.005 Sight hole D15.001 Level indicator 1
D06.000 Base frame Level indicator 2 option
D06.002 Lifting lug D15.003 Level transducer
D07.000 Operating platform option D15.006 Level limiter
D08.000 Pressure safeguard valve 1 D16.002 Desalting shut-off valve
D08.100 Pressure safeguard valve 2 D16.005 Desalting control valve
D09.000 Steam shut-off valve D16.006 Conductivity transducer option
D12.001 Drain shut-off valve D19.001 vent shut-off valve option
Explanation of symbols
Warning: dangerous electrical voltage
Lifting equipment to be fastened here, only
Warning: hot surface, e. g. uninsu-lated fitting
Main dimensions
LOGANO SHD815
in three-pass flame-tube smoke-tube technology
Project number: 147083/2.74 DA011
Offer No.: 1168947643-74 Printing date: 19.06.2012
Page 2 of 2
LOGANO SHD815
Nominal
output
Mean working gauge pres-
sure
Transportation
weight
Operating
weight
Maximum weight
3)
Connected load (electri-
cal)
[kg/h] [bar] [kg] [kg] [kg] [kW]
3500 8 9521 15269 17359 9,5
Dimension(s) Flue gas connection
L 1 L 2 1)
L 3 B 1 B 2 1)
H 1 H 2 1) 4)
B 4 H 3
[mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm]
6217 5050 4600 2439 2165 2947 2510 358 623
Base frame
L 4 L 5 L 6 L 7 L 8 L 9 2)
B 3 wide flange beam
[mm] [mm] [mm] [mm] [mm] [mm] [mm] [IPB - HEB - DIN1025]
3750 3400 600 425 175 225 1655 180
References and defaults to Requirements for the boiler installation room see technical information TI024.
Missing dimensions are not contained in scope of delivery.
Dimensions with ± 1 % tolerance; transport weight indication with ± 4 % tolerance and operating weight indication with ± 2 %
tolerance
The indicated transport weight already includes the surcharges for normal sheet metal thickness tolerances, hence difference
downwards is possible.
Dimensioning insertion opening:
Positioning height: addition of at least 100 mm to dimension H1 resp. dimension H2
(mounted / not mounted fittings)
Positioning width: addition of at least 200 mm to dimension B1 resp. dimension B2
(mounted / not mounted fittings) 1)
Smallest transport dimensions once fittings, burner and terminal box have been removed (without cable ducting; with cable ducting
+ 75 mm on right). 2)
The boiler operating weight must be absorbed by the foundation in the area of the front and rear supports. 3)
Maximum weight incl. 100 % filled with water 4)
Height to top edge Transportation lugs
Individual dimensions
LOGANO SHD815
in three-pass flame-tube smoke-tube technology
Project number: 147083/2.74 DA012
Offer No.: 1168947643-74 Printing date: 19.06.2012
Page 1 of 2
D03.000 Flue gas connection socket D12.503 Connection for drainage flue gas condensate
D05.000 Inspection opening steam-side D13.501 Connection for Feed water shut-off valve
D05.001 Inspection opening water side D14.500 Connection for manostat pipe
D05.002 Inspection opening flue gas side D15.501 Connection for Level indicator 1
D08.500 Connection for Pressure safeguard valve 1 Connection for Level indicator 2 option
D08.600 Connection for Pressure safeguard valve 2 D16.501 Connection for Desalting shut-off valve
D09.500 Connection for Steam shut-off valve D19.501 Connection for vent shut-off valve option
D12.500 Connection for drain
Individual dimensions
LOGANO SHD815
in three-pass flame-tube smoke-tube technology
Project number: 147083/2.74 DA012
Offer No.: 1168947643-74 Printing date: 19.06.2012
Page 2 of 2
LOGANO SHD815 Dimension(s)
Nominal output L 1 B 1 H 1 4)
[kg/h] [mm] [mm] [mm]
3500 5050 2165 2510
Nozzle position
L 3 L 4 L 5 L 6 L 7 L 8 L 9 L 10
[mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm]
2250 2550 1850 1500 1150 800
Nozzle position
L 12 L 13 B 3 H 2 H 3 H 4 H 5 H 8
[mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm]
420 950 2415 1740 1700 1215 340
Flue gas connection Base frame
B 4 H 6 L 2 L 11 B 2 H 7 wide flange beam
[mm] [mm] [mm] [mm] [mm] [mm] [IPB - HEB - DIN1025]
358 623 3750 425 1655 190 180
Connection D03.000 1)
D08.500 / D08.600 2)
D09.500 2)
D12.500 2) D12.503
3)
DN [mm] 400 40 100 40 3/4“
PN [bar/120°C] 0,1 40 16 40 0,1
Connection D13.501 2) D14.500
2) D15.501
2) D16.501
2) D19.501
2)
DN [mm] 40 20 25 25
PN [bar/120°C] 40 40 40 40
References and defaults to Requirements for the boiler installation room see technical information TI024.
Missing dimensions are not contained in scope of delivery.
Dimensions with ± 1 % tolerance 1)
Nominal diameter for pipe connection according to DIN 24154 part 4 2)
Nominal diameter for flanges according to DIN 2633 / 2634 / 2635 3)
Pipe thread according to DIN 2999 4)
Height to top edge Transportation lugs
Piping diagram
LOGANO SHD615 , LOGANO SHD815
Project number: 147083/2.74 DA021
Offer No.: 1168947643-74 Printing date: 19.06.2012
Page 1 of 2
Position Designation Position Designation
D08.000 Pressure safeguard valve D15.001 Level indicator
D08.100 Pressure safeguard valve D15.003 Level controller
D09.000 Steam extraction shut-off valve D15.006 Level limiter
D12.001 Drain shut-off valve D15.007 Level limiter
D12.002 Quick shut-off blow down valve D15.008 level switch
D12.005 three-way regulator valve (magnetic) D15.009 Shut-off valve
D12.006 Filter valve D15.101 Level indicator option
D12.007 Shut-off valve D15.109 Shut-off valve option
D13.001 Feed water shut-off valve D16.002 Desalting shut-off valve
D13.002 Feed water non-return valve D16.003 conductivity controller 1)
D14.001 Pressure indicator (with test unit) D16.004 flow rate indicator
D14.002 Pressure limiter D16.005 Desalting control valve (motorized)
D14.004 pressure regulator D16.007 Shut-off valve
D14.005 Shut-off valve D16.010 Non-return valve
Piping diagram
LOGANO SHD615 , LOGANO SHD815
Project number: 147083/2.74 DA021
Offer No.: 1168947643-74 Printing date: 19.06.2012
Page 2 of 2
Position Piping Position Piping
08.001 Pressure safeguard blowoff line 12.004 Discharge line flue gas condensate
08.002 Pressure safeguard drainage line 15.001 water level blowoff pipe
08.101 Pressure safeguard blowoff line 16.001 boiler water desalting line
09.001 Steam pipe 16.002 Water sample extraction pipe
12.001 Drain pipe 23.001 Flue gas line
12.002 control line control medium 40.002 Feed water pressure line
Depicted equipment is on the basis of EN12953 Part 6
References and defaults to Requirements for the boiler installation room see technical information TI024.
The scope of delivery is defined in the order confirmation. 1)
The conductivity measuring transducer with shut-off at the limit value is a minimum requirement of EN12953 Part 6.
Main and individual dimensions
Feed pump unit SG
Project number: 147083/2.74 DA004
Offer No.: 1168947643-74 Printing date: 19.06.2012
Page 1 of 1
A37.001 Shut-off valve (throttle cone) A37.009 Pump engine
A37.002 Non-return valve A37.011 bracket
A37.003 Pressure indicator A37.019 pressure monitor (minimum pressure)
A37.004 Shut-off valve A37.501 Connection for suction side
A37.005 Filter valve A37.502 Connection for pressure side
A37.008 Pump
Feed pump
unit
discharge
pressure
Min. required positive suction
head
Transportation
weight
Operating
weight
Connected load
(electrical)
Discharge flow
[kg/h] [bar] [mm] [kg] [kg] [kW]
3783 10 1000 132 140 3
Dimension(s)
L 1 L 2 L 3 B 1 B 3 B 4 H 1 H 2 H 3 H4
[mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm]
1044 732 662 240 110 178 1232 540 235 160
Bearing area Connection for
L 4 B 2 Surface area A37.501 1) A37.502
1)
[mm] [mm] [cm²] DN PN DN PN
600 60 720 65 16 32 40
References and defaults to Requirements for the boiler installation room see technical information TI024.
During assembly, please note the specified flow direction
Install the consoles onto anti-vibration supports
Missing dimensions are not contained in scope of delivery.
Dimensions with ± 1 % tolerance; transport weight indication with ± 4 % tolerance and operating weight indication with ± 2 %
tolerance 1)
Nominal diameter for flanges according to DIN 2633 / 2634 / 2635
Piping diagram
Feed water supply steam boiler
Boiler level control via two-step control
Project number: 147083/2.74 DA388
Offer No.: 1168947643-74 Printing date: 19.06.2012
Page 1 of 2
Depiction of the feed water supply from the tank to the boiler
depiction with 2 feed pumps per boiler
Hinweis: Nur eine Speisepumpe im Lieferumfang!
Piping diagram
Feed water supply steam boiler
Boiler level control via two-step control
Project number: 147083/2.74 DA388
Offer No.: 1168947643-74 Printing date: 19.06.2012
Page 2 of 2
Position Designation Position Designation
A37.001 Shut-off valve (throttle cone) A37.008 Feed pump
A37.002 Non-return valve A37.019 pressure monitor option
A37.003 Pressure indicator B30.000 Feed water tank
A37.004 Shut-off valve D01 steam boiler
A37.005 Filter valve
Position Piping Position Piping
30.001 Feed water suction piping 40.002 Feed water pressure line
30.010 Feed water suction piping
The scope of delivery is defined in the order confirmation.
Individual dimensions
LOGANO SHD815
in three-pass flame-tube smoke-tube technology
Project number: 147083/2.74 DA012
Offer No.: 1168947643-74 Printing date: 19.06.2012
Page 1 of 2
D03.000 Flue gas connection socket D12.503 Connection for drainage flue gas condensate
D05.000 Inspection opening steam-side D13.501 Connection for Feed water shut-off valve
D05.001 Inspection opening water side D14.500 Connection for manostat pipe
D05.002 Inspection opening flue gas side D15.501 Connection for Level indicator 1
D08.500 Connection for Pressure safeguard valve 1 Connection for Level indicator 2 option
D08.600 Connection for Pressure safeguard valve 2 D16.501 Connection for Desalting shut-off valve
D09.500 Connection for Steam shut-off valve D19.501 Connection for vent shut-off valve option
D12.500 Connection for drain
Individual dimensions
LOGANO SHD815
in three-pass flame-tube smoke-tube technology
Project number: 147083/2.74 DA012
Offer No.: 1168947643-74 Printing date: 19.06.2012
Page 2 of 2
LOGANO SHD815 Dimension(s)
Nominal output L 1 B 1 H 1 4)
[kg/h] [mm] [mm] [mm]
3500 5050 2165 2510
Nozzle position
L 3 L 4 L 5 L 6 L 7 L 8 L 9 L 10
[mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm]
2250 2550 1850 1500 1150 800
Nozzle position
L 12 L 13 B 3 H 2 H 3 H 4 H 5 H 8
[mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm]
420 950 2415 1740 1700 1215 340
Flue gas connection Base frame
B 4 H 6 L 2 L 11 B 2 H 7 wide flange beam
[mm] [mm] [mm] [mm] [mm] [mm] [IPB - HEB - DIN1025]
358 623 3750 425 1655 190 180
Connection D03.000 1)
D08.500 / D08.600 2)
D09.500 2)
D12.500 2) D12.503
3)
DN [mm] 400 40 100 40 3/4“
PN [bar/120°C] 0,1 40 16 40 0,1
Connection D13.501 2) D14.500
2) D15.501
2) D16.501
2) D19.501
2)
DN [mm] 40 20 25 25
PN [bar/120°C] 40 40 40 40
References and defaults to Requirements for the boiler installation room see technical information TI024.
Missing dimensions are not contained in scope of delivery.
Dimensions with ± 1 % tolerance 1)
Nominal diameter for pipe connection according to DIN 24154 part 4 2)
Nominal diameter for flanges according to DIN 2633 / 2634 / 2635 3)
Pipe thread according to DIN 2999 4)
Height to top edge Transportation lugs
Main dimensions
Flue Gas Flange
Dimensions in accordance with Part 4 of the DIN 24154 Standard
Project number: 147083/2.74 DA078
Offer No.: 1168947643-74 Printing date: 19.06.2012
Page 1 of 1
nominal diameter Dimension(s) Quantity wall thickness weight
[DN] 1)
D 1 D 2 D 3 D 4 Bores
[mm] [mm] [mm] [mm] [mm] [ ° ] [ ° ] [ - ] [mm] [kg]
500 587 551 495 11,5 15 30 12 8 4,3
The bores are evenly distributed along the periphery.
Dimensions with ± 1 % tolerance; transport weight indication with ± 4 % tolerance and operating weight indication with ± 2 %
tolerance
The exhaust pipe is not pushed through and welded, as in DIN 24154 R4, but rather butted onto the flange and welded!
Main dimensions
LOGANO S825L
Project number: 147083/2.74 DA160
Offer No.: 1168947643-74 Printing date: 19.06.2012
Page 1 of 2
51.002 Instrument box option D07.000 Operating platform option
51.004 terminal box option D08.000 Pressure safeguard valve 1
A01.000 Burner D08.100 Pressure safeguard valve 2
D03.000 Flue gas connection socket D10.000 Supply flow
D04.000 Boiler front door D10.002 Supply flow adapter piece
D05.002 Inspection opening flue gas side D11.000 Return flow
D05.005 Sight hole D12.001 Drain shut-off valve option
D06.000 Base frame D12.503 Connection for drainage flue gas condensate
D06.002 Lifting lug
Explanation of symbols
Warning: dangerous electrical voltage
Lifting equipment to be fastened here, only
Warning: hot surface, e. g. uninsulated fitting
Main dimensions
LOGANO S825L
Project number: 147083/2.74 DA160
Offer No.: 1168947643-74 Printing date: 19.06.2012
Page 2 of 2
LOGANO S825L
Type Mean working gauge pressure Transportation weight Maximum weight 2)
Connected load (electrical)
[bar] [kg] [kg] [kW]
3700 5,16 5800 8500
Dimension(s)
L 1
L 2 1)
L 3 B 1 1)
H 1 H 2 1)
H 3
[mm] [mm] [mm] [mm] [mm] [mm] [mm]
5266 4075 3820 1724 2717 2100 2010
Flue gas connection Base frame
H 4 L 4 B 2 H 5
[mm] [mm] [mm] [mm]
1490 3410 1150 200
References and defaults to Requirements for the boiler installation room see technical information TI024.
Missing dimensions are not contained in scope of delivery.
Dimensions with ± 1 % tolerance; transport weight indication with ± 4 % tolerance and operating weight indication with ± 2 %
tolerance
The indicated transport weight already includes the surcharges for normal sheet metal thickness tolerances, hence difference
downwards is possible.
Dimensioning insertion opening:
Positioning height: addition of at least 100 mm to dimension H1 resp. dimension H2
(mounted / not mounted fittings)
Positioning width: addition of at least 200 mm to dimension B1
(mounted / not mounted fittings) 1)
Smallest transport dimensions once fittings, burner and terminal box have been removed (without cable ducting; with cable
ducting + 75 mm on right). 2)
Maximum weight incl. 100 % filled with water
Individual dimensions
LOGANO S825L
Project number: 147083/2.74 DA162
Offer No.: 1168947643-74 Printing date: 19.06.2012
Page 1 of 1
D03.000 Flue gas connection socket D10.500 Connection for Supply flow
D05.002 Inspection opening flue gas side D11.500 Connection for Return flow
D08.500 Connection for Pressure safeguard valve 1 D12.500 Connection for drain
D08.600 Connection for Pressure safeguard valve 2 D12.503 Connection for drainage flue gas condensate
LOGANO S825L Nozzle position Base frame
L 2 L 3 L 4 L 5 H 1 H 2 D 1 L 1 B 1 U-Profil
Type [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [U-DIN 1026]
3700 2490 600 800 300 2000 1490 1700 3410 1150 200
Connection for D03.000 1) D08.500 / D08.600
2) D10.500
2) D11.500
2) D12.500
2) D12.503
3)
DN [mm] 500 65 200 200 32 3/4“
PN [ bar / 120°C ] 0,1 16 16 16 40 0,1
References and defaults to Requirements for the boiler installation room see technical information TI024.
Missing dimensions are not contained in scope of delivery.
Dimensions with ± 1 % tolerance 1)
Nominal diameter for pipe connection according to DIN 24154 part 4 2)
Nominal diameter for flanges according to DIN 2633 / 2634 / 2635 3)
Pipe thread according to DIN 2999
Piping diagram
LOGANO S825L
Project number: 147083/2.74 DA111
Offer No.: 1168947643-74 Printing date: 19.06.2012
Page 1 of 2
Position Designation Position Designation
D08.000 Pressure safeguard valve D12.001 Drain shut-off valve
D08.100 Pressure safeguard valve D12.002 Quick shut-off blow down valve
D10.003 temperature indicator D14.001 Pressure indicator (with test unit)
D10.004 Temperature limiter D14.002 Pressure limiter
D10.013 flow limiter option D14.005 Shut-off valve
D10.014 temperature controller D15.004 temperature indicator
D11.003 temperature indicator D15.006 Level limiter
D11.004 temperature monitor
Piping diagram
LOGANO S825L
Project number: 147083/2.74 DA111
Offer No.: 1168947643-74 Printing date: 19.06.2012
Page 2 of 2
Position Piping Position Piping
08.001 Pressure safeguard blowoff line 10.001 hot water supply flow line
08.002 Pressure safeguard drainage line 11.001 hot water return flow line
08.003 pressure safeguard vapour line 12.001 Drain pipe
08.101 Pressure safeguard blowoff line 12.004 Discharge line flue gas condensate
08.102 Pressure safeguard drainage line 23.001 Flue gas line
08.103 pressure safeguard vapour line
References and defaults to Requirements for the boiler installation room see technical information TI024.
The scope of delivery is defined in the order confirmation.
Main and individual dimensions
Supply flow adapter piece
for LOGANO S825L
Project number: 147083/2.74 DA131
Offer No.: 1168947643-74 Printing date: 19.06.2012
Page 1 of 1
BAR
~510 L 1B 1 B 2
700
D15.006D10.500D10.004
D10.500
D14.006 D14.005D14.002D14.001 D10.014
D10.013
D10.004 Temperature limiter option
D10.013 flow limiter option D14.002 Pressure limiter
D10.014 temperature controller D14.005 manostat tube - Shut-off valve DN20
D10.500 Connection for Supply flow D14.006 Pressure limiter
D14.001 Pressure indicator (with test unit) D15.006 Level limiter option
Supply flow adapter piece Transportation weight Maximum weight Dimension(s) nominal diameter
L 1 B 1 B 2 D10.500
Type [kg] [kg] [mm] [mm] [mm] DN 1) PN
1)
VZ 200 49 71 305 515 290 200 16
Dimensions with ± 1 % tolerance; transport weight indication with ± 4 % tolerance and operating weight indication with ± 2 %
tolerance 1)
Nominal diameter for flanges according to DIN 2633 / 2634 / 2635 2)
Maximum weight incl. 100 % filled with water
System diagram
Single boiler system with Logamatic boiler control unit with hydraulic decoupling
for hot water generator
Project number: 147083/2.74 DA201
Offer No.: 1168947643-74 Printing date: 19.06.2012
Page 1 of 1
hot water boiler without flue gas heat exchanger hot water boiler with a flue gas heat exchanger integrated into the boiler
circuit
FK boiler water - temperature sensor (inserted in low-loss header)
RWT Return flow flue gas heat exchanger
FZ auxiliary sensor for the return flow temperature SR control element for return flow temperature boosting
PK boiler circuit pump V Supply flow
R Return flow VK boiler supply flow
RG control device Logamatic VWT Supply flow flue gas heat exchanger
RK boiler return flow WH Hydraulic compensation line (low-loss header)
brief description of the system:
Control of the minimum return flow temperature via a separate control element (SR) in the boiler circuit and a boiler circuit pump as
primary circuit pump.
function description of the system:
The return flow temperature is controlled by actuating the three-way valve (SR). The return flow temperature sensor (FZ) measures the
boiler return flow temperature. If it falls below the setpoint, the volumetric flow of heating water to the boiler return is continuously
throttled by actuating the three-way valve (SR). When the return flow temperature rises above the setpoint, the three-way valve (SR)
reopens and the volumetric flow to the heating circuit increases.
Special planning notes:
A low-loss header or alternatively a flow header with bypass and non-return valve must be included when planning.
The boiler circuit pump must be switched to continuous operation or with an overrun of 60 minutes.
The accompanying temperature sensor built into the boiler supply flow connection socket must not be used for boiler temperature
control. For temperature control, use the temperature sensor supplied separately which must be built into the low-loss header.
The diagrams show only the control elements necessary for control. The boiler equipment required can be found in the
corresponding piping diagrams.
The scope of delivery is defined in the order confirmation.
The system diagram provides a general guide to the possible configuration without obligation or claims as to its completeness. The
practical implementation is subject to currently applicable technical rules. Safety equipment must be installed in accordance with
local regulations.