Main dimensions Flue Gas Flange Dimensions in accordance with Part 4 of the DIN 24154 Standard Project number: 147083/2.74 DA078 Offer No.: 1168947643-74 Printing date: 19.06.2012 Page 1 of 1 nominal diameter Dimension(s) Quantity wall thickness weight [DN] 1) D 1 D 2 D 3 D 4 Bores [mm] [mm] [mm] [mm] [mm] [ ° ] [ ° ] [ - ] [mm] [kg] 400 484 448 392 11,5 15 30 12 8 3,8 The bores are evenly distributed along the periphery. Dimensions with ± 1 % tolerance; transport weight indication with ± 4 % tolerance and operating weight indication with ± 2 % tolerance The exhaust pipe is not pushed through and welded, as in DIN 24154 R4, but rather butted onto the flange and welded!

Data Sheet

  • Upload
    svoicum

  • View
    113

  • Download
    1

Embed Size (px)

Citation preview

Page 1: Data Sheet

Main dimensions

Flue Gas Flange

Dimensions in accordance with Part 4 of the DIN 24154 Standard

Project number: 147083/2.74 DA078

Offer No.: 1168947643-74 Printing date: 19.06.2012

Page 1 of 1

nominal diameter Dimension(s) Quantity wall thickness weight

[DN] 1)

D 1 D 2 D 3 D 4 Bores

[mm] [mm] [mm] [mm] [mm] [ ° ] [ ° ] [ - ] [mm] [kg]

400 484 448 392 11,5 15 30 12 8 3,8

The bores are evenly distributed along the periphery.

Dimensions with ± 1 % tolerance; transport weight indication with ± 4 % tolerance and operating weight indication with ± 2 %

tolerance

The exhaust pipe is not pushed through and welded, as in DIN 24154 R4, but rather butted onto the flange and welded!

Page 2: Data Sheet

Load securing device

LOGANO SHD815

in three-pass flame-tube smoke-tube technology

Project number: 147083/2.74 DA368

Offer No.: 1168947643-74 Printing date: 19.06.2012

Page 1 of 1

Explanation of symbols

Lifting equipment to be fastened here, only

centre of gravity

Lashing equipment

LOGANO SHD815 Anhängelast

Nominal output Mean working gauge pressure Transportation weight A 1 A 2

[kg/h] [bar] [kg] [kg] [kg]

3500 8 9521 4899 4622

Dimension(s)

L 1 L 3 L 6 L 8 L 9 B 1 H1 1)

[mm] [mm] [mm] [mm] [mm] [mm] [mm]

6217 3030 735 100 50 2165 2510

Base frame centre of gravity Lashing point requirements

L 2 L 7 B 2 wide flange beam L 4 B 3 H 2 L 5 B 4

[mm] [mm] [mm] [IPB - HEB - DIN1025] [mm] [mm] [mm] [mm] [mm]

3750 425 1655 180 1781 815 1143 1000 1655

The scope of delivery is defined in the order confirmation.

Transport the boiler on anti-slip mats (positioned below the boiler feet) with a coefficient of sliding friction of µ >= 0.6.

The entire surface of the base frame must rest on the loading platform. 1)

Height to top edge Transportation lugs

Page 3: Data Sheet

Main dimensions

LOGANO SHD815

in three-pass flame-tube smoke-tube technology

Project number: 147083/2.74 DA011

Offer No.: 1168947643-74 Printing date: 19.06.2012

Page 1 of 2

51.004 terminal box D12.002 Quick shut-off blow down valve

A01.000 Burner D12.503 Connection for drainage flue gas condensate

D03.000 Flue gas connection socket D13.001 Feed water shut-off valve

D03.002 Flue gas chamber D13.002 Feed water non-return valve

D04.007 Reversing chamber door D14.001 Pressure indicator (with test unit)

D05.000 Inspection opening steam-side D14.002 Pressure limiter

D05.001 Inspection opening water side D14.005 Shut-off valve

D05.002 Inspection opening flue gas side D14.013 Pressure transducer

D05.005 Sight hole D15.001 Level indicator 1

D06.000 Base frame Level indicator 2 option

D06.002 Lifting lug D15.003 Level transducer

D07.000 Operating platform option D15.006 Level limiter

D08.000 Pressure safeguard valve 1 D16.002 Desalting shut-off valve

D08.100 Pressure safeguard valve 2 D16.005 Desalting control valve

D09.000 Steam shut-off valve D16.006 Conductivity transducer option

D12.001 Drain shut-off valve D19.001 vent shut-off valve option

Explanation of symbols

Warning: dangerous electrical voltage

Lifting equipment to be fastened here, only

Warning: hot surface, e. g. uninsu-lated fitting

Page 4: Data Sheet

Main dimensions

LOGANO SHD815

in three-pass flame-tube smoke-tube technology

Project number: 147083/2.74 DA011

Offer No.: 1168947643-74 Printing date: 19.06.2012

Page 2 of 2

LOGANO SHD815

Nominal

output

Mean working gauge pres-

sure

Transportation

weight

Operating

weight

Maximum weight

3)

Connected load (electri-

cal)

[kg/h] [bar] [kg] [kg] [kg] [kW]

3500 8 9521 15269 17359 9,5

Dimension(s) Flue gas connection

L 1 L 2 1)

L 3 B 1 B 2 1)

H 1 H 2 1) 4)

B 4 H 3

[mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm]

6217 5050 4600 2439 2165 2947 2510 358 623

Base frame

L 4 L 5 L 6 L 7 L 8 L 9 2)

B 3 wide flange beam

[mm] [mm] [mm] [mm] [mm] [mm] [mm] [IPB - HEB - DIN1025]

3750 3400 600 425 175 225 1655 180

References and defaults to Requirements for the boiler installation room see technical information TI024.

Missing dimensions are not contained in scope of delivery.

Dimensions with ± 1 % tolerance; transport weight indication with ± 4 % tolerance and operating weight indication with ± 2 %

tolerance

The indicated transport weight already includes the surcharges for normal sheet metal thickness tolerances, hence difference

downwards is possible.

Dimensioning insertion opening:

Positioning height: addition of at least 100 mm to dimension H1 resp. dimension H2

(mounted / not mounted fittings)

Positioning width: addition of at least 200 mm to dimension B1 resp. dimension B2

(mounted / not mounted fittings) 1)

Smallest transport dimensions once fittings, burner and terminal box have been removed (without cable ducting; with cable ducting

+ 75 mm on right). 2)

The boiler operating weight must be absorbed by the foundation in the area of the front and rear supports. 3)

Maximum weight incl. 100 % filled with water 4)

Height to top edge Transportation lugs

Page 5: Data Sheet

Individual dimensions

LOGANO SHD815

in three-pass flame-tube smoke-tube technology

Project number: 147083/2.74 DA012

Offer No.: 1168947643-74 Printing date: 19.06.2012

Page 1 of 2

D03.000 Flue gas connection socket D12.503 Connection for drainage flue gas condensate

D05.000 Inspection opening steam-side D13.501 Connection for Feed water shut-off valve

D05.001 Inspection opening water side D14.500 Connection for manostat pipe

D05.002 Inspection opening flue gas side D15.501 Connection for Level indicator 1

D08.500 Connection for Pressure safeguard valve 1 Connection for Level indicator 2 option

D08.600 Connection for Pressure safeguard valve 2 D16.501 Connection for Desalting shut-off valve

D09.500 Connection for Steam shut-off valve D19.501 Connection for vent shut-off valve option

D12.500 Connection for drain

Page 6: Data Sheet

Individual dimensions

LOGANO SHD815

in three-pass flame-tube smoke-tube technology

Project number: 147083/2.74 DA012

Offer No.: 1168947643-74 Printing date: 19.06.2012

Page 2 of 2

LOGANO SHD815 Dimension(s)

Nominal output L 1 B 1 H 1 4)

[kg/h] [mm] [mm] [mm]

3500 5050 2165 2510

Nozzle position

L 3 L 4 L 5 L 6 L 7 L 8 L 9 L 10

[mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm]

2250 2550 1850 1500 1150 800

Nozzle position

L 12 L 13 B 3 H 2 H 3 H 4 H 5 H 8

[mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm]

420 950 2415 1740 1700 1215 340

Flue gas connection Base frame

B 4 H 6 L 2 L 11 B 2 H 7 wide flange beam

[mm] [mm] [mm] [mm] [mm] [mm] [IPB - HEB - DIN1025]

358 623 3750 425 1655 190 180

Connection D03.000 1)

D08.500 / D08.600 2)

D09.500 2)

D12.500 2) D12.503

3)

DN [mm] 400 40 100 40 3/4“

PN [bar/120°C] 0,1 40 16 40 0,1

Connection D13.501 2) D14.500

2) D15.501

2) D16.501

2) D19.501

2)

DN [mm] 40 20 25 25

PN [bar/120°C] 40 40 40 40

References and defaults to Requirements for the boiler installation room see technical information TI024.

Missing dimensions are not contained in scope of delivery.

Dimensions with ± 1 % tolerance 1)

Nominal diameter for pipe connection according to DIN 24154 part 4 2)

Nominal diameter for flanges according to DIN 2633 / 2634 / 2635 3)

Pipe thread according to DIN 2999 4)

Height to top edge Transportation lugs

Page 7: Data Sheet

Piping diagram

LOGANO SHD615 , LOGANO SHD815

Project number: 147083/2.74 DA021

Offer No.: 1168947643-74 Printing date: 19.06.2012

Page 1 of 2

Position Designation Position Designation

D08.000 Pressure safeguard valve D15.001 Level indicator

D08.100 Pressure safeguard valve D15.003 Level controller

D09.000 Steam extraction shut-off valve D15.006 Level limiter

D12.001 Drain shut-off valve D15.007 Level limiter

D12.002 Quick shut-off blow down valve D15.008 level switch

D12.005 three-way regulator valve (magnetic) D15.009 Shut-off valve

D12.006 Filter valve D15.101 Level indicator option

D12.007 Shut-off valve D15.109 Shut-off valve option

D13.001 Feed water shut-off valve D16.002 Desalting shut-off valve

D13.002 Feed water non-return valve D16.003 conductivity controller 1)

D14.001 Pressure indicator (with test unit) D16.004 flow rate indicator

D14.002 Pressure limiter D16.005 Desalting control valve (motorized)

D14.004 pressure regulator D16.007 Shut-off valve

D14.005 Shut-off valve D16.010 Non-return valve

Page 8: Data Sheet

Piping diagram

LOGANO SHD615 , LOGANO SHD815

Project number: 147083/2.74 DA021

Offer No.: 1168947643-74 Printing date: 19.06.2012

Page 2 of 2

Position Piping Position Piping

08.001 Pressure safeguard blowoff line 12.004 Discharge line flue gas condensate

08.002 Pressure safeguard drainage line 15.001 water level blowoff pipe

08.101 Pressure safeguard blowoff line 16.001 boiler water desalting line

09.001 Steam pipe 16.002 Water sample extraction pipe

12.001 Drain pipe 23.001 Flue gas line

12.002 control line control medium 40.002 Feed water pressure line

Depicted equipment is on the basis of EN12953 Part 6

References and defaults to Requirements for the boiler installation room see technical information TI024.

The scope of delivery is defined in the order confirmation. 1)

The conductivity measuring transducer with shut-off at the limit value is a minimum requirement of EN12953 Part 6.

Page 9: Data Sheet

Main and individual dimensions

Feed pump unit SG

Project number: 147083/2.74 DA004

Offer No.: 1168947643-74 Printing date: 19.06.2012

Page 1 of 1

A37.001 Shut-off valve (throttle cone) A37.009 Pump engine

A37.002 Non-return valve A37.011 bracket

A37.003 Pressure indicator A37.019 pressure monitor (minimum pressure)

A37.004 Shut-off valve A37.501 Connection for suction side

A37.005 Filter valve A37.502 Connection for pressure side

A37.008 Pump

Feed pump

unit

discharge

pressure

Min. required positive suction

head

Transportation

weight

Operating

weight

Connected load

(electrical)

Discharge flow

[kg/h] [bar] [mm] [kg] [kg] [kW]

3783 10 1000 132 140 3

Dimension(s)

L 1 L 2 L 3 B 1 B 3 B 4 H 1 H 2 H 3 H4

[mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm]

1044 732 662 240 110 178 1232 540 235 160

Bearing area Connection for

L 4 B 2 Surface area A37.501 1) A37.502

1)

[mm] [mm] [cm²] DN PN DN PN

600 60 720 65 16 32 40

References and defaults to Requirements for the boiler installation room see technical information TI024.

During assembly, please note the specified flow direction

Install the consoles onto anti-vibration supports

Missing dimensions are not contained in scope of delivery.

Dimensions with ± 1 % tolerance; transport weight indication with ± 4 % tolerance and operating weight indication with ± 2 %

tolerance 1)

Nominal diameter for flanges according to DIN 2633 / 2634 / 2635

Page 10: Data Sheet

Piping diagram

Feed water supply steam boiler

Boiler level control via two-step control

Project number: 147083/2.74 DA388

Offer No.: 1168947643-74 Printing date: 19.06.2012

Page 1 of 2

Depiction of the feed water supply from the tank to the boiler

depiction with 2 feed pumps per boiler

Hinweis: Nur eine Speisepumpe im Lieferumfang!

Page 11: Data Sheet

Piping diagram

Feed water supply steam boiler

Boiler level control via two-step control

Project number: 147083/2.74 DA388

Offer No.: 1168947643-74 Printing date: 19.06.2012

Page 2 of 2

Position Designation Position Designation

A37.001 Shut-off valve (throttle cone) A37.008 Feed pump

A37.002 Non-return valve A37.019 pressure monitor option

A37.003 Pressure indicator B30.000 Feed water tank

A37.004 Shut-off valve D01 steam boiler

A37.005 Filter valve

Position Piping Position Piping

30.001 Feed water suction piping 40.002 Feed water pressure line

30.010 Feed water suction piping

The scope of delivery is defined in the order confirmation.

Page 12: Data Sheet

Individual dimensions

LOGANO SHD815

in three-pass flame-tube smoke-tube technology

Project number: 147083/2.74 DA012

Offer No.: 1168947643-74 Printing date: 19.06.2012

Page 1 of 2

D03.000 Flue gas connection socket D12.503 Connection for drainage flue gas condensate

D05.000 Inspection opening steam-side D13.501 Connection for Feed water shut-off valve

D05.001 Inspection opening water side D14.500 Connection for manostat pipe

D05.002 Inspection opening flue gas side D15.501 Connection for Level indicator 1

D08.500 Connection for Pressure safeguard valve 1 Connection for Level indicator 2 option

D08.600 Connection for Pressure safeguard valve 2 D16.501 Connection for Desalting shut-off valve

D09.500 Connection for Steam shut-off valve D19.501 Connection for vent shut-off valve option

D12.500 Connection for drain

Page 13: Data Sheet

Individual dimensions

LOGANO SHD815

in three-pass flame-tube smoke-tube technology

Project number: 147083/2.74 DA012

Offer No.: 1168947643-74 Printing date: 19.06.2012

Page 2 of 2

LOGANO SHD815 Dimension(s)

Nominal output L 1 B 1 H 1 4)

[kg/h] [mm] [mm] [mm]

3500 5050 2165 2510

Nozzle position

L 3 L 4 L 5 L 6 L 7 L 8 L 9 L 10

[mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm]

2250 2550 1850 1500 1150 800

Nozzle position

L 12 L 13 B 3 H 2 H 3 H 4 H 5 H 8

[mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm]

420 950 2415 1740 1700 1215 340

Flue gas connection Base frame

B 4 H 6 L 2 L 11 B 2 H 7 wide flange beam

[mm] [mm] [mm] [mm] [mm] [mm] [IPB - HEB - DIN1025]

358 623 3750 425 1655 190 180

Connection D03.000 1)

D08.500 / D08.600 2)

D09.500 2)

D12.500 2) D12.503

3)

DN [mm] 400 40 100 40 3/4“

PN [bar/120°C] 0,1 40 16 40 0,1

Connection D13.501 2) D14.500

2) D15.501

2) D16.501

2) D19.501

2)

DN [mm] 40 20 25 25

PN [bar/120°C] 40 40 40 40

References and defaults to Requirements for the boiler installation room see technical information TI024.

Missing dimensions are not contained in scope of delivery.

Dimensions with ± 1 % tolerance 1)

Nominal diameter for pipe connection according to DIN 24154 part 4 2)

Nominal diameter for flanges according to DIN 2633 / 2634 / 2635 3)

Pipe thread according to DIN 2999 4)

Height to top edge Transportation lugs

Page 14: Data Sheet

Main dimensions

Flue Gas Flange

Dimensions in accordance with Part 4 of the DIN 24154 Standard

Project number: 147083/2.74 DA078

Offer No.: 1168947643-74 Printing date: 19.06.2012

Page 1 of 1

nominal diameter Dimension(s) Quantity wall thickness weight

[DN] 1)

D 1 D 2 D 3 D 4 Bores

[mm] [mm] [mm] [mm] [mm] [ ° ] [ ° ] [ - ] [mm] [kg]

500 587 551 495 11,5 15 30 12 8 4,3

The bores are evenly distributed along the periphery.

Dimensions with ± 1 % tolerance; transport weight indication with ± 4 % tolerance and operating weight indication with ± 2 %

tolerance

The exhaust pipe is not pushed through and welded, as in DIN 24154 R4, but rather butted onto the flange and welded!

Page 15: Data Sheet

Main dimensions

LOGANO S825L

Project number: 147083/2.74 DA160

Offer No.: 1168947643-74 Printing date: 19.06.2012

Page 1 of 2

51.002 Instrument box option D07.000 Operating platform option

51.004 terminal box option D08.000 Pressure safeguard valve 1

A01.000 Burner D08.100 Pressure safeguard valve 2

D03.000 Flue gas connection socket D10.000 Supply flow

D04.000 Boiler front door D10.002 Supply flow adapter piece

D05.002 Inspection opening flue gas side D11.000 Return flow

D05.005 Sight hole D12.001 Drain shut-off valve option

D06.000 Base frame D12.503 Connection for drainage flue gas condensate

D06.002 Lifting lug

Explanation of symbols

Warning: dangerous electrical voltage

Lifting equipment to be fastened here, only

Warning: hot surface, e. g. uninsulated fitting

Page 16: Data Sheet

Main dimensions

LOGANO S825L

Project number: 147083/2.74 DA160

Offer No.: 1168947643-74 Printing date: 19.06.2012

Page 2 of 2

LOGANO S825L

Type Mean working gauge pressure Transportation weight Maximum weight 2)

Connected load (electrical)

[bar] [kg] [kg] [kW]

3700 5,16 5800 8500

Dimension(s)

L 1

L 2 1)

L 3 B 1 1)

H 1 H 2 1)

H 3

[mm] [mm] [mm] [mm] [mm] [mm] [mm]

5266 4075 3820 1724 2717 2100 2010

Flue gas connection Base frame

H 4 L 4 B 2 H 5

[mm] [mm] [mm] [mm]

1490 3410 1150 200

References and defaults to Requirements for the boiler installation room see technical information TI024.

Missing dimensions are not contained in scope of delivery.

Dimensions with ± 1 % tolerance; transport weight indication with ± 4 % tolerance and operating weight indication with ± 2 %

tolerance

The indicated transport weight already includes the surcharges for normal sheet metal thickness tolerances, hence difference

downwards is possible.

Dimensioning insertion opening:

Positioning height: addition of at least 100 mm to dimension H1 resp. dimension H2

(mounted / not mounted fittings)

Positioning width: addition of at least 200 mm to dimension B1

(mounted / not mounted fittings) 1)

Smallest transport dimensions once fittings, burner and terminal box have been removed (without cable ducting; with cable

ducting + 75 mm on right). 2)

Maximum weight incl. 100 % filled with water

Page 17: Data Sheet

Individual dimensions

LOGANO S825L

Project number: 147083/2.74 DA162

Offer No.: 1168947643-74 Printing date: 19.06.2012

Page 1 of 1

D03.000 Flue gas connection socket D10.500 Connection for Supply flow

D05.002 Inspection opening flue gas side D11.500 Connection for Return flow

D08.500 Connection for Pressure safeguard valve 1 D12.500 Connection for drain

D08.600 Connection for Pressure safeguard valve 2 D12.503 Connection for drainage flue gas condensate

LOGANO S825L Nozzle position Base frame

L 2 L 3 L 4 L 5 H 1 H 2 D 1 L 1 B 1 U-Profil

Type [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [U-DIN 1026]

3700 2490 600 800 300 2000 1490 1700 3410 1150 200

Connection for D03.000 1) D08.500 / D08.600

2) D10.500

2) D11.500

2) D12.500

2) D12.503

3)

DN [mm] 500 65 200 200 32 3/4“

PN [ bar / 120°C ] 0,1 16 16 16 40 0,1

References and defaults to Requirements for the boiler installation room see technical information TI024.

Missing dimensions are not contained in scope of delivery.

Dimensions with ± 1 % tolerance 1)

Nominal diameter for pipe connection according to DIN 24154 part 4 2)

Nominal diameter for flanges according to DIN 2633 / 2634 / 2635 3)

Pipe thread according to DIN 2999

Page 18: Data Sheet

Piping diagram

LOGANO S825L

Project number: 147083/2.74 DA111

Offer No.: 1168947643-74 Printing date: 19.06.2012

Page 1 of 2

Position Designation Position Designation

D08.000 Pressure safeguard valve D12.001 Drain shut-off valve

D08.100 Pressure safeguard valve D12.002 Quick shut-off blow down valve

D10.003 temperature indicator D14.001 Pressure indicator (with test unit)

D10.004 Temperature limiter D14.002 Pressure limiter

D10.013 flow limiter option D14.005 Shut-off valve

D10.014 temperature controller D15.004 temperature indicator

D11.003 temperature indicator D15.006 Level limiter

D11.004 temperature monitor

Page 19: Data Sheet

Piping diagram

LOGANO S825L

Project number: 147083/2.74 DA111

Offer No.: 1168947643-74 Printing date: 19.06.2012

Page 2 of 2

Position Piping Position Piping

08.001 Pressure safeguard blowoff line 10.001 hot water supply flow line

08.002 Pressure safeguard drainage line 11.001 hot water return flow line

08.003 pressure safeguard vapour line 12.001 Drain pipe

08.101 Pressure safeguard blowoff line 12.004 Discharge line flue gas condensate

08.102 Pressure safeguard drainage line 23.001 Flue gas line

08.103 pressure safeguard vapour line

References and defaults to Requirements for the boiler installation room see technical information TI024.

The scope of delivery is defined in the order confirmation.

Page 20: Data Sheet

Main and individual dimensions

Supply flow adapter piece

for LOGANO S825L

Project number: 147083/2.74 DA131

Offer No.: 1168947643-74 Printing date: 19.06.2012

Page 1 of 1

BAR

~510 L 1B 1 B 2

700

D15.006D10.500D10.004

D10.500

D14.006 D14.005D14.002D14.001 D10.014

D10.013

D10.004 Temperature limiter option

D10.013 flow limiter option D14.002 Pressure limiter

D10.014 temperature controller D14.005 manostat tube - Shut-off valve DN20

D10.500 Connection for Supply flow D14.006 Pressure limiter

D14.001 Pressure indicator (with test unit) D15.006 Level limiter option

Supply flow adapter piece Transportation weight Maximum weight Dimension(s) nominal diameter

L 1 B 1 B 2 D10.500

Type [kg] [kg] [mm] [mm] [mm] DN 1) PN

1)

VZ 200 49 71 305 515 290 200 16

Dimensions with ± 1 % tolerance; transport weight indication with ± 4 % tolerance and operating weight indication with ± 2 %

tolerance 1)

Nominal diameter for flanges according to DIN 2633 / 2634 / 2635 2)

Maximum weight incl. 100 % filled with water

Page 21: Data Sheet

System diagram

Single boiler system with Logamatic boiler control unit with hydraulic decoupling

for hot water generator

Project number: 147083/2.74 DA201

Offer No.: 1168947643-74 Printing date: 19.06.2012

Page 1 of 1

hot water boiler without flue gas heat exchanger hot water boiler with a flue gas heat exchanger integrated into the boiler

circuit

FK boiler water - temperature sensor (inserted in low-loss header)

RWT Return flow flue gas heat exchanger

FZ auxiliary sensor for the return flow temperature SR control element for return flow temperature boosting

PK boiler circuit pump V Supply flow

R Return flow VK boiler supply flow

RG control device Logamatic VWT Supply flow flue gas heat exchanger

RK boiler return flow WH Hydraulic compensation line (low-loss header)

brief description of the system:

Control of the minimum return flow temperature via a separate control element (SR) in the boiler circuit and a boiler circuit pump as

primary circuit pump.

function description of the system:

The return flow temperature is controlled by actuating the three-way valve (SR). The return flow temperature sensor (FZ) measures the

boiler return flow temperature. If it falls below the setpoint, the volumetric flow of heating water to the boiler return is continuously

throttled by actuating the three-way valve (SR). When the return flow temperature rises above the setpoint, the three-way valve (SR)

reopens and the volumetric flow to the heating circuit increases.

Special planning notes:

A low-loss header or alternatively a flow header with bypass and non-return valve must be included when planning.

The boiler circuit pump must be switched to continuous operation or with an overrun of 60 minutes.

The accompanying temperature sensor built into the boiler supply flow connection socket must not be used for boiler temperature

control. For temperature control, use the temperature sensor supplied separately which must be built into the low-loss header.

The diagrams show only the control elements necessary for control. The boiler equipment required can be found in the

corresponding piping diagrams.

The scope of delivery is defined in the order confirmation.

The system diagram provides a general guide to the possible configuration without obligation or claims as to its completeness. The

practical implementation is subject to currently applicable technical rules. Safety equipment must be installed in accordance with

local regulations.