Data Centers Presented on the Momentum Savings Monthly Call

May 3rd & June 7th

Page 2: Data Centers - Bonneville Power Administration...Data Centers in the PNW PNW Population Avg. IT Load kW** aMW Enterprise ??? ????? ????? Mid-Tier 500 122 61 Localized 700 16 11 Server

Why should we

CARE?

Page 3: Data Centers - Bonneville Power Administration...Data Centers in the PNW PNW Population Avg. IT Load kW** aMW Enterprise ??? ????? ????? Mid-Tier 500 122 61 Localized 700 16 11 Server

350-450 aMW 7th Plan

Embedded Data Center Load

Page 4: Data Centers - Bonneville Power Administration...Data Centers in the PNW PNW Population Avg. IT Load kW** aMW Enterprise ??? ????? ????? Mid-Tier 500 122 61 Localized 700 16 11 Server

55aMW Savings Potential

With no program in place to capture it

7th Plan Potential, 2016-2021

Page 5: Data Centers - Bonneville Power Administration...Data Centers in the PNW PNW Population Avg. IT Load kW** aMW Enterprise ??? ????? ????? Mid-Tier 500 122 61 Localized 700 16 11 Server

So what is a data center?

Page 6: Data Centers - Bonneville Power Administration...Data Centers in the PNW PNW Population Avg. IT Load kW** aMW Enterprise ??? ????? ????? Mid-Tier 500 122 61 Localized 700 16 11 Server

Closets

Page 7: Data Centers - Bonneville Power Administration...Data Centers in the PNW PNW Population Avg. IT Load kW** aMW Enterprise ??? ????? ????? Mid-Tier 500 122 61 Localized 700 16 11 Server

Server Room

Page 8: Data Centers - Bonneville Power Administration...Data Centers in the PNW PNW Population Avg. IT Load kW** aMW Enterprise ??? ????? ????? Mid-Tier 500 122 61 Localized 700 16 11 Server

Localized Data Centers

Page 9: Data Centers - Bonneville Power Administration...Data Centers in the PNW PNW Population Avg. IT Load kW** aMW Enterprise ??? ????? ????? Mid-Tier 500 122 61 Localized 700 16 11 Server

Mid-Tier Data Centers

Page 10: Data Centers - Bonneville Power Administration...Data Centers in the PNW PNW Population Avg. IT Load kW** aMW Enterprise ??? ????? ????? Mid-Tier 500 122 61 Localized 700 16 11 Server

Co-Location, ‘Colos’

Page 11: Data Centers - Bonneville Power Administration...Data Centers in the PNW PNW Population Avg. IT Load kW** aMW Enterprise ??? ????? ????? Mid-Tier 500 122 61 Localized 700 16 11 Server

Enterprise

Page 12: Data Centers - Bonneville Power Administration...Data Centers in the PNW PNW Population Avg. IT Load kW** aMW Enterprise ??? ????? ????? Mid-Tier 500 122 61 Localized 700 16 11 Server
Page 13: Data Centers - Bonneville Power Administration...Data Centers in the PNW PNW Population Avg. IT Load kW** aMW Enterprise ??? ????? ????? Mid-Tier 500 122 61 Localized 700 16 11 Server
Page 14: Data Centers - Bonneville Power Administration...Data Centers in the PNW PNW Population Avg. IT Load kW** aMW Enterprise ??? ????? ????? Mid-Tier 500 122 61 Localized 700 16 11 Server

What they all have in common

Page 15: Data Centers - Bonneville Power Administration...Data Centers in the PNW PNW Population Avg. IT Load kW** aMW Enterprise ??? ????? ????? Mid-Tier 500 122 61 Localized 700 16 11 Server

Priorities

Security

Reliability thereafter, efficiency

Page 16: Data Centers - Bonneville Power Administration...Data Centers in the PNW PNW Population Avg. IT Load kW** aMW Enterprise ??? ????? ????? Mid-Tier 500 122 61 Localized 700 16 11 Server

IT Equipment

– Servers

– Storage

– Networking (communications)

HVAC and Infrastructure

– Cooling

– Power management

Page 17: Data Centers - Bonneville Power Administration...Data Centers in the PNW PNW Population Avg. IT Load kW** aMW Enterprise ??? ????? ????? Mid-Tier 500 122 61 Localized 700 16 11 Server

IT Equipment

– Servers

– Storage

– Networking (communications)

HVAC and Infrastructure

– Cooling

– Power management

Computer Wattage BTUs

Page 18: Data Centers - Bonneville Power Administration...Data Centers in the PNW PNW Population Avg. IT Load kW** aMW Enterprise ??? ????? ????? Mid-Tier 500 122 61 Localized 700 16 11 Server

IT Equipment

– Servers

– Storage

– Networking (communications)

HVAC and Infrastructure

– Cooling

– Power management

Computer Wattage BTUs

Page 19: Data Centers - Bonneville Power Administration...Data Centers in the PNW PNW Population Avg. IT Load kW** aMW Enterprise ??? ????? ????? Mid-Tier 500 122 61 Localized 700 16 11 Server

IT Equipment

– Servers

– Storage

– Networking (communications)

HVAC and Infrastructure

– Cooling

– Power management

Computer Wattage BTUs

Page 20: Data Centers - Bonneville Power Administration...Data Centers in the PNW PNW Population Avg. IT Load kW** aMW Enterprise ??? ????? ????? Mid-Tier 500 122 61 Localized 700 16 11 Server

IT and Infrastructure

Page 21: Data Centers - Bonneville Power Administration...Data Centers in the PNW PNW Population Avg. IT Load kW** aMW Enterprise ??? ????? ????? Mid-Tier 500 122 61 Localized 700 16 11 Server

Consumption Nationally

Berkeley National Lab

Page 22: Data Centers - Bonneville Power Administration...Data Centers in the PNW PNW Population Avg. IT Load kW** aMW Enterprise ??? ????? ????? Mid-Tier 500 122 61 Localized 700 16 11 Server

Data Centers in the PNW

Enterprise ???

Mid-Tier 500

Localized 700

Server Rooms 20,000

Server Closet 16,233

CBSA

Page 23: Data Centers - Bonneville Power Administration...Data Centers in the PNW PNW Population Avg. IT Load kW** aMW Enterprise ??? ????? ????? Mid-Tier 500 122 61 Localized 700 16 11 Server

Trend to Enterprise DCs

Berkeley National Lab

Page 24: Data Centers - Bonneville Power Administration...Data Centers in the PNW PNW Population Avg. IT Load kW** aMW Enterprise ??? ????? ????? Mid-Tier 500 122 61 Localized 700 16 11 Server

Getting EE into the DC

Page 25: Data Centers - Bonneville Power Administration...Data Centers in the PNW PNW Population Avg. IT Load kW** aMW Enterprise ??? ????? ????? Mid-Tier 500 122 61 Localized 700 16 11 Server

EE savings from embedded

DCs only

– Assumption: enterprise

DCs high-efficient facilities

Criticism for being overly

optimistic/aggressive

– Input from Cadmus study

and CBSA

7th Plan Scope

Page 26: Data Centers - Bonneville Power Administration...Data Centers in the PNW PNW Population Avg. IT Load kW** aMW Enterprise ??? ????? ????? Mid-Tier 500 122 61 Localized 700 16 11 Server

Savings Potential

– 55 aMW 5-year potential

– 750 aMW 20-year potential

Load Forecast

– 405 aMW in 2017

– 637 aMW in 2030

Avg. 2.7% annual growth

7th Plan Scope

Page 27: Data Centers - Bonneville Power Administration...Data Centers in the PNW PNW Population Avg. IT Load kW** aMW Enterprise ??? ????? ????? Mid-Tier 500 122 61 Localized 700 16 11 Server

0

100

200

300

400

500

600

700

2016 2021 2026 2031

Load Forecast

Savings Potential

LF - Savings

aMW

Page 28: Data Centers - Bonneville Power Administration...Data Centers in the PNW PNW Population Avg. IT Load kW** aMW Enterprise ??? ????? ????? Mid-Tier 500 122 61 Localized 700 16 11 Server

0

10

20

30

40

50

60

70

2016 2021 2026 2031

Savings Potential

aMW

Page 29: Data Centers - Bonneville Power Administration...Data Centers in the PNW PNW Population Avg. IT Load kW** aMW Enterprise ??? ????? ????? Mid-Tier 500 122 61 Localized 700 16 11 Server

Practices v. Widgets

Page 30: Data Centers - Bonneville Power Administration...Data Centers in the PNW PNW Population Avg. IT Load kW** aMW Enterprise ??? ????? ????? Mid-Tier 500 122 61 Localized 700 16 11 Server

Practices

Virtualization (43%*)

– Running the workload of multiple

servers on one physical host

server – creates “virtual”

servers

Decommissioning servers

(9.5%*)

ASHRAE HVAC guidelines

And the cloud… more later

* 7th Plan Potential

Page 31: Data Centers - Bonneville Power Administration...Data Centers in the PNW PNW Population Avg. IT Load kW** aMW Enterprise ??? ????? ????? Mid-Tier 500 122 61 Localized 700 16 11 Server

Widgets

Efficient servers (11%*) – An ENERGY STAR qualified server uses 30% less energy

than a conventional server

– Most energy intensive component

Efficient storage (10%*) – Far second in energy intensiveness

Efficient network equipment (3.6%*) – Distant 3rd in energy intensiveness

Efficient UPS (6%*) – Uninterruptible Power Supply

* 7th Plan Potential

Page 32: Data Centers - Bonneville Power Administration...Data Centers in the PNW PNW Population Avg. IT Load kW** aMW Enterprise ??? ????? ????? Mid-Tier 500 122 61 Localized 700 16 11 Server

% ENERGY STAR Servers % Virtualization

Enterprise ??? ???

Mid-Tier 71% 33%

Localized 44% 27%

Server Rooms 31% 30%

Server Closet 38% 8%

CBSA *CBSA pop. ¼ of national estimates

**does not include HVAC

Top Practice & Widget in Use

Page 33: Data Centers - Bonneville Power Administration...Data Centers in the PNW PNW Population Avg. IT Load kW** aMW Enterprise ??? ????? ????? Mid-Tier 500 122 61 Localized 700 16 11 Server

Market Analysis

Page 34: Data Centers - Bonneville Power Administration...Data Centers in the PNW PNW Population Avg. IT Load kW** aMW Enterprise ??? ????? ????? Mid-Tier 500 122 61 Localized 700 16 11 Server

Market Analysis

DCs in our region

Supply Chain

Market Actors

Page 35: Data Centers - Bonneville Power Administration...Data Centers in the PNW PNW Population Avg. IT Load kW** aMW Enterprise ??? ????? ????? Mid-Tier 500 122 61 Localized 700 16 11 Server

PNW Population Avg. IT Load kW**

Enterprise ??? ?????

Mid-Tier 500 122

Localized 700 16

Server Rooms 20,000 5

Server Closet 16,233 1.3

CBSA **does not include HVAC

Data Centers in the PNW

Page 36: Data Centers - Bonneville Power Administration...Data Centers in the PNW PNW Population Avg. IT Load kW** aMW Enterprise ??? ????? ????? Mid-Tier 500 122 61 Localized 700 16 11 Server

PNW Population Avg. IT Load kW** aMW

Enterprise ??? ????? ??????

Mid-Tier 500 122 61

Localized 700 16 11

Server Rooms 20,000 5 100

Server Closet 16,233 1.3 21

CBSA **does not include HVAC

Data Centers in the PNW

Page 37: Data Centers - Bonneville Power Administration...Data Centers in the PNW PNW Population Avg. IT Load kW** aMW Enterprise ??? ????? ????? Mid-Tier 500 122 61 Localized 700 16 11 Server

Not in the 7th Plan, CBSA – assumed highly efficient

Irony

– All over the news

– Yet, next to no details about what is inside them

Moving to our region

– Cheap energy/temperate climates

– Trans-Pacific telecommunications hub

– Cloud migration

Enterprise Data Centers

Page 38: Data Centers - Bonneville Power Administration...Data Centers in the PNW PNW Population Avg. IT Load kW** aMW Enterprise ??? ????? ????? Mid-Tier 500 122 61 Localized 700 16 11 Server

… just means using someone else’s computer

Page 39: Data Centers - Bonneville Power Administration...Data Centers in the PNW PNW Population Avg. IT Load kW** aMW Enterprise ??? ????? ????? Mid-Tier 500 122 61 Localized 700 16 11 Server

Supply Chain Our understanding of the supply chain is very basic

Page 40: Data Centers - Bonneville Power Administration...Data Centers in the PNW PNW Population Avg. IT Load kW** aMW Enterprise ??? ????? ????? Mid-Tier 500 122 61 Localized 700 16 11 Server

…But that’s about it

– Are there other channels?

• Physical v. Financial

–What are the estimate sizes of each channel?

–What is the difference between branded/unbranded

equipment?

–Where is the influence?

Supply Chain

Page 41: Data Centers - Bonneville Power Administration...Data Centers in the PNW PNW Population Avg. IT Load kW** aMW Enterprise ??? ????? ????? Mid-Tier 500 122 61 Localized 700 16 11 Server

Supply Chain Market Actors

– Manufacturers, VARs (Value Added Reseller), IT service

providers, System integrators

Data Center Actors

– Facilities Manager

– IT Manager

– CFO

– Good information on decision-making process at DC

Market Actors

Page 42: Data Centers - Bonneville Power Administration...Data Centers in the PNW PNW Population Avg. IT Load kW** aMW Enterprise ??? ????? ????? Mid-Tier 500 122 61 Localized 700 16 11 Server

Need a lot more information – especially on supply chain

– Most information is technology focused

– Who are they? We have a sense of types of actors, but not much

info on specific market actor profiles

– What is the difference between them?

– What value-add do they contribute?

– What existing relationships does our industry have with these

market actors, if any, that might be leveraged?

Market Actors

Page 43: Data Centers - Bonneville Power Administration...Data Centers in the PNW PNW Population Avg. IT Load kW** aMW Enterprise ??? ????? ????? Mid-Tier 500 122 61 Localized 700 16 11 Server

Momentum Savings?

Modeling a data center

We have one model for DC energy

consumption, what are its weaknesses

and strengths?

Sales Data Availability

It appears one source of sales data may

exist (IDC), but do any other possibilities

exist out there?

Page 44: Data Centers - Bonneville Power Administration...Data Centers in the PNW PNW Population Avg. IT Load kW** aMW Enterprise ??? ????? ????? Mid-Tier 500 122 61 Localized 700 16 11 Server

Risks and Barriers Ethan’s Gut Feeling

Collecting sales data could be difficult – if we do that

No EE program – Incentives, relationships, etc.

Broadly speaking, little interest in EE

Secretive market – Market actors, especially large ones (enterprise DCs) may not be open to

sharing market intelligence, qualitatively or quantitatively.

Double counting

– End Use types not unique to DCs, e.g. HVAC

Page 45: Data Centers - Bonneville Power Administration...Data Centers in the PNW PNW Population Avg. IT Load kW** aMW Enterprise ??? ????? ????? Mid-Tier 500 122 61 Localized 700 16 11 Server

Where next?

Need an ‘IT meets EE’ expert

– Help us understand the market

There’s a lot of niche topics

here – what is noise and what

is substance?

– We only have the 7th Plan to

guide us and it doesn’t seem to

be a very robust analysis

Dig deeper into what we have

– CBSA especially

Get a grasp on enterprise DCs

– How many are there, are they

really super efficient?

– Can we get much info on them?

Or are they black boxes?

Page 46: Data Centers - Bonneville Power Administration...Data Centers in the PNW PNW Population Avg. IT Load kW** aMW Enterprise ??? ????? ????? Mid-Tier 500 122 61 Localized 700 16 11 Server

Where next?

Need an ‘IT meets EE’ expert perspective

There’s a lot of niche topics here – what is noise and what is substance?

– We only have the 7th Plan to guide us and it doesn’t seem to be a very robust analysis

Dig deeper into what we have – CBSA especially

– Utility Programs

Get a grasp on enterprise DCs – How many are there? Are they

really super efficient?

– Can we get much info on them? Or are they black boxes?

– Should we ignore them?

Page 47: Data Centers - Bonneville Power Administration...Data Centers in the PNW PNW Population Avg. IT Load kW** aMW Enterprise ??? ????? ????? Mid-Tier 500 122 61 Localized 700 16 11 Server

Where next?

Figure out the

technology/efficiency options

– With lighting, we think:

Incandescent, CFL, LED…

What is the equivalent for data

centers?

End Use v. Building Type

– Is this a study of data centers, or

is it a study of IT equipment?

Page 48: Data Centers - Bonneville Power Administration...Data Centers in the PNW PNW Population Avg. IT Load kW** aMW Enterprise ??? ????? ????? Mid-Tier 500 122 61 Localized 700 16 11 Server

Sources Cadmus Study

Has worked with PG&E on a couple large DC studies PG&E

Multiple DC studies Berkeley National Laboratory

The lab where data center research is focused – multiple sources Power Council

Workbooks CBSA

Surveyed small to medium DCs NEEA

Embedded DC market actor survey ACEEE

Based on NEEA work, embedded data center

Page 49: Data Centers - Bonneville Power Administration...Data Centers in the PNW PNW Population Avg. IT Load kW** aMW Enterprise ??? ????? ????? Mid-Tier 500 122 61 Localized 700 16 11 Server

Questions?