Upload
others
View
0
Download
0
Embed Size (px)
Citation preview
©2014 Lennox Industries Inc.Dallas, Texas, USA
RETAIN THESE INSTRUCTIONSFOR FUTURE REFERENCE
These instructions are intended as a general guide and donot supersede local codes in any way. Consult authoritieshaving jurisdiction before installation.
WARNINGImproper installation, adjustment, alteration, service ormaintenance can cause personal injury, loss of life, ordamage to property.
Installation and service must be performed by a licensedprofessional installer (or equivalent) or a service agency.
IMPORTANTThe Clean Air Act of 1990 bans the intentional venting ofrefrigerant (CFCs, HCFCs AND HFCs) as of July 1,1992. Approved methods of recovery, recycling orreclaiming must be followed. Fines and/or incarcerationmay be levied for noncompliance.
IMPORTANTThis unit must be matched with an indoor coil as specified in Lennox Engineering Handbook. Coils previously charged with HCFC-22 must be flushed.
NOTICE TO INSTALLERUNIT PLACEMENT
It is critical for proper unit operation to place outdoor unit on anelevated surface as described in Unit Placement section on page 6.
BRAZING LINE SET TO SERVICE VALVES
It is imperative to follow the brazing technique illustrated starting onpage 9 to avoid damaging the service valve's internal seals.
INSTALLATIONINSTRUCTIONS
T-Class� TSA*S4 UnitsM and T Voltages
AIR CONDITIONER506663-01 8/2014Supersedes 11/2010
TABLE OF CONTENTS
Shipping and Packing List 1. . . . . . . . . . . . . . . . . . . . . . . .
Outdoor Unit 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Unit Dimensions 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Typical Unit Parts Arrangement 2. . . . . . . . . . . . . . . . . . .
Model Number Identification 3. . . . . . . . . . . . . . . . . . . . . .
General Information 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Operating Gauge Set and Service Valves 3. . . . . . . . . . .
Recovering Refrigerant from Existing System 5. . . . . . .
New Outdoor Unit Placement 6. . . . . . . . . . . . . . . . . . . . .
New or Replacement Line Set 7. . . . . . . . . . . . . . . . . . . . .
Brazing Connections 9. . . . . . . . . . . . . . . . . . . . . . . . . . .
Flushing Line Set and Indoor Coil 12. . . . . . . . . . . . . . . .
Installing Indoor Metering Device 13. . . . . . . . . . . . . . . .
Leak Test Line Set and Indoor Coil 14. . . . . . . . . . . . . . .
Evacuating Line Set and Indoor Coil 15. . . . . . . . . . . . .
Electrical Connections 16. . . . . . . . . . . . . . . . . . . . . . . . . .
Servicing Unit Delivered Void of Charge 20. . . . . . . . . . .
Unit Start-Up 20. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
System Refrigerant 20. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
System Operation 25. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Maintenance 25. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Start-Up and Performance Checklist 27. . . . . . . . . . . . . .
Shipping and Packing List
Check the unit for shipping damage and listed times beloware intact. If damaged, or if parts are missing, immediatelycontact the last shipping carrier.
1 — Assembled outdoor unit
1 — Liquid line filter drier
Outdoor Unit
This outdoor unit is designed for use with HFC-410Arefrigerant only. This unit must be installed with anapproved indoor air handler or coil. See the LennoxTSA*S4 Engineering Handbook for approved indoorcomponent matchups.
This outdoor unit is designed for use in thermal expansionvalve (TXV) systems only.
Litho U.S.A.
Page 2
506663-01 11/10
Unit Dimensions - Inches (mm)
SUCTION AND LIQUID LINECONNECTIONS
SIDE VIEW
OUTDOOR COIL FAN
A
B
A
OPTIONAL UNIT STAND‐OFF KIT(4) (FIELD-INSTALLED)
Discharge Air
SIDE VIEW
COMPRESSOR
Model Number A B
TSA024S4N41T 24-1/4 (616) 25-1/4 (641)
TSA030S4N41T 24-1/4 (616) 29-1/4 (743)
TSA036S4N41M 24-1/4 (616) 29-1/4 (743)
TSA036S4N41T 28-1/4 (718) 29-1/4 (743)
TSA048S4N41T and M 28-1/4 (718) 37-1/4 (946)
TSA060S4N41T and M 28-1/4 (718) 33-1/4 (845)
Typical Unit Parts Arrangement
GROUND LUG
CONTROL
CUTOUT FOR HIGHVOLTAGE CONDUIT
OR
CONTACTOR (K1)LOCATION
LIQUID LINESERVICE VALVE
SUCTION LINESERVICE VALVE
HIGH PRESSURESWITCH (S4)
NOTE: PLUMBING LAYOUT MAYVARY SLIGHTLY BETWEEN
MODEL SIZES.
CRANKCASE HEATERTHERMOSTAT (S40)
DUAL RUN CAPACITOR(C12) (T-VOLTAGE)
SINGLE RUN CAPACITOR(C12) (M-VOLTAGE)
ONE POLE(T-VOLTAGE)
TWO-POLE(M-VOLTAGE)
Figure 1. Typical Unit Parts Arrangement
Page 3
TSA*S4 SERIES
Model Number Identification
T S A M1036 S 44 N
Major Design SequenceA = 1st Generation
B = 2nd Generation
Brand/FamilyT = T-Class� Product Line
Unit TypeS = Split-System Air Conditioner
024 = 2 Tons030 = 2.5 Tons0036 = 3 Tons
048 = 4 Tons060 = 5Tons
Cooling EfficiencyS = Standard Efficiency
Minor Design Sequence
1 = 1st Revision2 = 2nd Revision3 = 3rd Revision
VoltageM = 380/420V-3 phase 50hzT = 220/240V-1 phase 50hz
Refrigerant Type4 = R-410A
Part Load CapabilityN = No part load, single stage compressor
Coil Type4 = Four-sided
IMPORTANTThis model is designed for use in expansion valvesystems only. An indoor expansion valve approved foruse with HFC-410A refrigerant must be orderedseparately, and installed prior to operating the system.
CAUTIONPhysical contact with metal edges and corners whileapplying excessive force or rapid motion can result inpersonal injury. Be aware of, and use caution whenworking near these areas during installation or whileservicing this equipment.
General Information
These instructions are intended as a general guide and donot supersede local codes in any way. Consult authorities
who have jurisdiction before installation.
Operating Gauge Set and Service Valves
These instructions are intended as a general guide and donot supersede local codes in any way. Consult authoritieswho have jurisdiction before installation.
TORQUE REQUIREMENTS
When servicing or repairing heating, ventilating, and airconditioning components, ensure the fasteners areappropriately tightened. Table 1 lists torque values forfasteners.
IMPORTANTOnly use Allen wrenches of sufficient hardness (50Rc -Rockwell Harness Scale minimum). Fully insert thewrench into the valve stem recess.
Service valve stems are factory-torqued (from 9 ft-lbs forsmall valves, to 25 ft-lbs for large valves) to preventrefrigerant loss during shipping and handling. Using anAllen wrench rated at less than 50Rc risks rounding orbreaking off the wrench, or stripping the valve stemrecess.
See the Lennox Service and Application Notes #C-08-1for further details and information.
IMPORTANTTo prevent stripping of the various caps used, theappropriately sized wrench should be used and fittedsnugly over the cap before tightening.
When servicing or repairing HVAC components, ensurethe fasteners are appropriately tightened. Table 1 providestorque values for fasteners.
Table 1. Torque Requirements
Parts Recommended Torque
Service valve cap 8 ft.- lb. 11 NM
Sheet metal screws 16 in.- lb. 2 NM
Machine screws #10 28 in.- lb. 3 NM
Compressor bolts 90 in.- lb. 10 NM
Gauge port seal cap 8 ft.- lb. 11 NM
USING MANIFOLD GAUGE SET
When checking the system charge, only use a manifoldgauge set that features low loss anti-blow back fittings.
Page 4
506663-01 11/10
Manifold gauge set used with HFC-410A refrigerantsystems must be capable of handling the higher systemoperating pressures. The gauges should be rated for usewith pressures of 0 - 800 psig on the high side and a lowside of 30” vacuum to 250 psig with dampened speed to500 psi. Gauge hoses must be rated for use at up to 800psig of pressure with a 4000 psig burst rating.
OPERATING SERVICE VALVESThe liquid and vapor line service valves are used forremoving refrigerant, flushing, leak testing, evacuating,checking charge and charging.
Each valve is equipped with a service port which has afactory-installed valve stem. Figure 2 provides informationon how to access and operating both angle and ball servicevalves.
(VALVE STEM SHOWNCLOSED) INSERT HEXWRENCH HERE
SERVICE PORT CORE
SERVICE PORT CAP
ANGLE-TYPE SERVICE VALVE(FRONT-SEATED CLOSED)
SERVICE PORTCORE
TO OUTDOOR UNIT
STEM CAP
(VALVE STEM SHOWN OPEN)INSERT HEX WRENCH HERE
TO INDOORUNIT
ANGLE-TYPE SERVICE VALVE(BACK-SEATED OPENED)
BALL (SHOWNCLOSED)
SERVICE PORTCORE
TO INDOOR UNIT
TO OUTDOORUNIT
TO OPEN ROTATE STEMCOUNTERCLOCKWISE 90°.
TO CLOSE ROTATE STEMCLOCKWISE 90°.
SERVICE PORT
SERVICE PORTCAP
STEM CAP
VALVESTEM
Operating Angle Type Service Valve:
1. Remove stem cap with an appropriately sized wrench.
2. Use a service wrench with a hex-head extension (3/16” for liquid line valve sizes and 5/16” for vapor line valve sizes) to backthe stem out counterclockwise as far as it will go.
Operating Ball Type Service Valve:
1. Remove stem cap with an appropriately sized wrench.
2. Use an appropriately sized wrenched to open. To open valve,rotate stem counterclockwise 90°. To close rotate stemclockwise 90°.
123
4567
8910
11 12
1/12 TURN
To Access Service Port:
A service port cap protects the service port core from contamination andserves as the primary leak seal.
1. Remove service port cap with an appropriately sized wrench.
2. Connect gauge set to service port.
3. When testing is completed, replace service port cap and tighten asfollows:
� With torque wrench: Finger tighten andtorque cap per table 1.
� Without torque wrench: Finger tighten anduse an appropriately sized wrench to turnan additional 1/6 turn clockwise.
123
4567
8910
11 12
1/6 TURN
WHEN SERVICE VALVE IS CLOSED, THE SERVICE PORT IS OPENTO THE LINE SET AND INDOOR UNIT.
When service valve is OPEN, the service port isopen to linE set, indoor and outdoor unit.
Reinstall Stem Cap:
Stem cap protects the valve stem from damage and serves as theprimary seal. Replace the stem cap and tighten as follows:
� With Torque Wrench: Finger tighten andthen torque cap per table 1.
� Without Torque Wrench: Finger tighten and use an appropriately sizedwrench to turn an additional 1/12 turnclockwise.
NOTE — A label with specific torque requirements may be affixed to the stem cap. If the label is present, use the specified torque.
Figure 2. Angle and Ball Service Valves
Page 5
TSA*S4 SERIES
Recovering Refrigerant from Existing System
SERVICEDISCONNECT
SWITCH
Disconnect all power to the existing outdoor unit at the servicedisconnect switch or main fuse box/breaker panel.
DISCONNECT POWER CONNECT MANIFOLD GAUGE SET
MANIFOLD GAUGES
RECOVERY MACHINE
CLEAN RECOVERYCYLINDER
OUTDOOR UNIT
HIGHLOW
Connect a gauge set, clean recovery cylinder and a recoverymachine to the service ports of the existing unit. Use theinstructions provided with the recovery machine to make theconnections.
METHOD 1:Us this method if the existing outdoor unit is not equipped with shut-off valves, or if the unit is not operational and you plan to use the existing toflush the system.
Remove all refrigerant from the existing system. Check gauges after shutdown to confirm that the entire system is completely void of refrigerant.
METHOD 2:Use this method if the existing outdoor unit is equipped with manual shut-off valves, and you plan to use new refrigerant to flush the system.
The following devices could prevent full system charge recovery into the outdoor unit:
� Outdoor unit's high or low-pressure switches (if applicable) when tripped can cycle the compressor OFF.
� Compressor can stop pumping due to tripped internal pressure relief valve.
� Compressor has internal vacuum protection that is designed to unload the scrolls (compressor stops pumping) when the pressure ratio meetsa certain value or when the suction pressure is as high as 20 psig. (Compressor suction pressures should never be allowed to go into a vacuum.Prolonged operation at low suction pressures will result in overheating of the scrolls and permanent damage to the scroll tips, drive bearings andinternal seals.)
Once the compressor can not pump down to a lower pressure due to one of the above system conditions, shut off the vapor valve. Turn OFF the
main power to unit and use a recovery machine to recover any refrigerant left in the indoor coil and line set.
Perform the following task:
A Start the existing system in the cooling mode and close the liquid line valve.
B Use the compressor to pump as much of the existing HCFC-22 refrigerant into the outdoor unit until the outdoor system is full. Turn the outdoor unitmain power OFF and use a recovery machine to remove the remaining refrigerant from the system.
NOTE — It may be necessary to bypass the low pressure switches (if equipped) to ensure complete refrigerant evacuation.
C When the low side system pressures reach 0 psig, close the vapor line valve.
D Check gauges after shutdown to confirm that the valves are not allowing refrigerant to flow back into the low side of the system.
RECOVERINGREFRIGERANT FROM SYSTEM
Remove existing refrigerant using one of the following procedures:
RECOVERING REFRIGERANT
IMPORTANT — Some system configurations may contain higher than normal refrigerant charge due to either large internal coil volumes,and/or long line sets.
1 2
3
Figure 3. Refrigerant Recovery
Page 6
506663-01 11/10
6 (152)
36 (914)
12 (305)30 (762)
LINE SETCONNECTIONS
24 (610)
48 (1219)
MINIMUM CLEARANCE BETWEENTWO UNITS
CLEARANCE ON ALL SIDES — INCHES (MILLIMETERS)
ACCESS PANEL
MINIMUM CLEARANCEABOVE UNIT
NOTES:
� Clearance to one of the other threesides must be 36 inches (914mm).
� Clearance to one of the remainingtwo sides may be 12 inches(305mm) and the final side may be6 inches (152mm).
Figure 4. Installation Clearances
Install unit level or, if on a slope, maintain slope tolerance of 2 degrees(or 2 inches per 5 feet [50 mm per 1.5 m]) away from buildingstructure.
DETAIL A DETAIL B
DISCHARGE AIR
MOUNTING SLAB MUST SLOPEAWAY FROM BUILDING.
GROUND LEVEL
STRUCTUREInstall unit awayfrom windows .
Two 90° elbows installed in line set willreduce line set vibration.
Figure 5. Placement, and Slab Mounting
New Outdoor Unit Placement
See Unit Dimensions on page 2 for sizing mounting slab,platforms or supports. Refer to figure 4 for mandatoryinstallation clearance requirements.
POSITIONING CONSIDERATIONS
CAUTIONIn order to avoid injury, take proper precaution when lifting heavy objects.
Consider the following when positioning the unit:
� Some localities are adopting sound ordinances basedon the unit's sound level registered from the adjacent
property, not from the installation property. Install theunit as far as possible from the property line.
� When possible, do not install the unit directly outsidea window. Glass has a very high level of sound
transmission. For proper placement of unit in relationto a window see the provided illustration in figure 5.
Page 7
TSA*S4 SERIES
PLACING OUTDOOR UNIT ON SLAB
When installing a unit at grade level, the top of the slabshould be high enough above the grade so that water fromhigher ground would not collect around the unit asillustrated in figure 5.
Slab may be level or have a slope tolerance away from thebuilding of not more than two degrees, or 2 inches per 5feet (51 mm per 1524 mm) as illustrated in figure 5.
Slab may be level or have a slope tolerance away from thebuilding of not more than two degrees, or 2 inches per 5feet (51 mm per 1524 mm) as illustrated in figure 5.
INSTALLING OUTDOOR UNIT ON ROOF
Install the unit at a minimum of 4 inches (102 mm) abovethe surface of the roof. Ensure the weight of the unit isproperly distributed over roof joists and rafters. Redwoodor steel supports are recommended.
New or Replacement Line Set
This section provides information on new installation or
replacement of existing line set. If a new or replacementline set is not required, then proceed to BrazingConnections on page 9.
If refrigerant lines are routed through a wall, seal andisolate the opening so vibration is not transmitted to thebuilding. Pay close attention to line set isolation during
installation of any HVAC system. When properly isolatedfrom building structures (walls, ceilings. floors), therefrigerant lines will not create unnecessary vibration andsubsequent sounds.
Also, consider the following when placing and installing ahigh-efficiency air conditioner:
REFRIGERANT LINE SET
Field refrigerant piping consists of liquid and suction lines
from the outdoor unit (braze connections) to the indoor unitcoil (flare or braze connections). Use Lennox L15 (braze,non-flare) series line set, or use field-fabricated refrigerantlines as listed in table 2.
NOTE - When installing refrigerant lines longer than 50
feet, contact Lennox Technical Support Product
Applications for assistance or Lennox piping manual. To
obtain the correct information from Lennox, be sure to
communicate the following points:
� Model (TSA*S4) and size of unit (e.g. -060).
� Line set diameters for the unit being installed as listedin table 2 and total length of installation.
� Number of elbows and if there is a rise or drop of thepiping.
IMPORTANTMineral oils are not compatible with HFC-410A. If oilmust be added, it must be a Polyol ester oil.
The compressor is charged with sufficient Polyol ester oilfor line set lengths up to 50 feet. Recommend adding oil tosystem based on the amount of refrigerant charge in thesystem. No need to add oil in system with 20 pounds ofrefrigerant or less. For systems over 20 pounds - add oneounce of every five pounds of refrigerant.
Recommended topping-off POE oils are Mobil EALARCTIC 22 CC or ICI EMKARATE� RL32CF.
MATCHING WITH NEW OR EXISTING INDOOR COILAND LINE SET
The RFC1-metering line consisted of a small bore copperline that ran from condenser to evaporator coil. Refrigerantwas metered into the evaporator by utilizingtemperature/pressure evaporation effects on refrigerant inthe small RFC line. The length and bore of the RFC linecorresponded to the size of cooling unit.
If the TSA*S4 is being used with either a new or existingindoor coil which is equipped with a liquid line which servedas a metering device (RFCI), the liquid line must bereplaced prior to the installation of the TSA*S4 unit.Typically a liquid line used to meter flow is 1/4” in diameterand copper.
LIQUID LINE FILTER DRIER INSTALLATION
The filter drier (one is shipped with each TSA*S4 unit) mustbe field installed in the liquid line between the outdoor unit'sliquid line service valve and the indoor coil's meteringdevice (fixed orifice or TXV) as illustrated in figure 6. Thisfilter drier must be installed to ensure a clean,moisture-free system. Failure to install the filter drier willvoid the warranty. A replacement filter drier is availablefrom Lennox. See Brazing Connections on page 9 forspecial procedures on brazing filter drier connections tothe liquid line.
OUTDOORUNIT
LIQUID LINESERVICE VALVE
LIQUID LINEFILTER DRIER
LINELIQUIDLINE
BRAZE CONNECTION POINTS
Figure 6. Typical Liquid Line Filter Drier Installation
Page 8
506663-01 11/10
Table 2. Refrigerant Line Set — Inches (mm)
ModelField Connections Recommended Line Set
Liquid Line Vapor Line Liquid Line Vapor Line L15 Line Sets
TSA024S4N4 3/8 in. (10 mm) 3/4 in. (19 mm) 3/8 in. (10 mm) 3/4 in. (19 mm) L15-41 — 15 ft. - 50 ft. (4.6 m - 15 m)
TSA036S4N43/8 in. (10 mm) 7/8 in. (22 mm) 3/8 in. (10 mm) 7/8 in. (22 mm) L15-65 — 15 ft. - 50 ft. (4.6 m - 15 m)
TSA048S4N4
TSA060S4N4 3/8 in. (10 mm) 1-1/8 in. (29 mm) 3/8 in. (10 mm) 1-1/8 in. (29 mm) Field Fabricated
NOTE — Some applications may required a field provided 7/8” to 1-1/8” adapter
ANCHORED HEAVY NYLONWIRE TIE OR AUTOMOTIVE
MUFFLER‐TYPE HANGER
STRAP LIQUID LINE TOVAPOR LINE
WALLSTUD
LIQUID LINE
NON-CORROSIVEMETAL SLEEVE
VAPOR LINE - WRAPPEDIN ARMAFLEX
AUTOMOTIVEMUFFLER‐TYPE HANGER
REFRIGERANT LINE SET — TRANSITIONFROM VERTICAL TO HORIZONTAL
Line Set Isolation — The following illustrations areexamples of proper refrigerant line set isolation:
STRAPPINGMATERIAL (AROUND
VAPOR LINE ONLY)
TAPE ORWIRE TIE
WIRE TIE (AROUNDVAPOR LINE ONLY)
FLOOR JOIST ORROOF RAFTER
TAPE ORWIRE TIE
To hang line set from joist or rafter, use either metal strapping materialor anchored heavy nylon wire ties.
8 FEET (2.43 METERS)
STRAP THE VAPOR LINE TO THE JOISTOR RAFTER AT 8 FEET (2.43 METERS)INTERVALS THEN STRAP THE LIQUIDLINE TO THE VAPOR LINE.
FLOOR JOIST OR
ROOF RAFTER
REFRIGERANT LINE SET — INSTALLING HORIZONTAL RUNS
NOTE — Similar installation practices should be used if line set isto be installed on exterior of outside wall.
PVCPIPE
FIBERGLASSINSULATION
CAULK
OUTSIDEWALL
VAPOR LINE WRAPPEDWITH ARMAFLEX
LIQUIDLINE
OUTSIDE WALL LIQUID LINEVAPOR LINE
WOOD BLOCKBETWEEN STUDS
STRAP
WOOD BLOCK
STRAP
SLEEVE
WIRE TIE
WIRE TIE
WIRE TIE
INSIDE WALL
REFRIGERANT LINE SET — INSTALLINGVERTICAL RUNS (NEW CONSTRUCTION SHOWN)
INSTALLATION
NOTE — Insulate liquid line when it is routed through areas where thesurrounding ambient temperature could become higher than thetemperature of the liquid line or when pressure drop is equal to or greaterthan 20 psig.
NON-CORROSIVEMETAL SLEEVE
IMPORTANT — Refrigerant lines must not contact structure.
NON-CORROSIVEMETAL SLEEVE
8 FEET (2.43 METERS)
IMPORTANT — Refrigerant lines must not contact wall
Figure 7. Line Set Installation
Page 9
TSA*S4 SERIES
IMPORTANTIf this unit is being matched with an approved line setor indoor unit coil which was previously charged withmineral oil, or if it is being matched with a coil whichwas manufactured before January of 1999, the coiland line set must be flushed prior to installation. Takecare to empty all existing traps. Polyol ester (POE) oilsare used in Lennox units charged with HFC-410Arefrigerant. Residual mineral oil can act as aninsulator, preventing proper heat transfer. It can alsoclog the expansion device, and reduce the systemperformance and capacity.Failure to properly flush the system per theinstructions below will void the warranty.
Brazing Connections
Use the procedures outline in figures 8 and 9 for brazingline set connections to service valves.
IMPORTANTPolyol ester (POE) oils used with HFC-410Arefrigerant absorb moisture very quickly. It is veryimportant that the refrigerant system be kept closedas much as possible. DO NOT remove line set capsor service valve stub caps until you are ready to makeconnections.
WARNINGDanger of fire. Bleeding the refrigerantcharge from only the high side may resultin pressurization of the low side shell andsuction tubing. Application of a brazingtorch to a pressurized system may resultin ignition of the refrigerant and oilmixture - Check the high and lowpressures before applying heat.
WARNINGWhen using a high pressure gas such asdry nitrogen to pressurize a refrigerationor air conditioning system, use aregulator that can control the pressuredown to 1 or 2 psig (6.9 to 13.8 kPa).
CAUTIONBrazing alloys and flux contain materials which arehazardous to your health.
Avoid breathing vapors or fumes from brazingoperations. Perform operations only in well-ventilatedareas.
Wear gloves and protective goggles or face shield toprotect against burns.
Wash hands with soap and water after handling brazingalloys and flux.
IMPORTANTConnect gauge set low pressure side to vapor lineservice valve and repeat procedure starting atparagraph 4 for brazing the liquid line to service portvalve.
IMPORTANTAllow braze joint to cool before removing the wet ragfrom the service valve. Temperatures above 250ºF candamage valve seals.
IMPORTANTUse silver alloy brazing rods with 5% minimum silveralloy for copper-to-copper brazing. Use 45% minimumalloy for copper-to-brass and copper-to-steel brazing.
WARNINGFire, Explosion and Personal SafetyHazard.
Failure to follow this warning couldresult in damage, personal injury ordeath.
Never use oxygen to pressurize orpurge refrigeration lines. Oxygen,when exposed to a spark or openflame, can cause fire and/or an explosion, that could result in propertydamage, personal injury or death.
Page 10
506663-01 11/10
ATTACH THE MANIFOLD GAUGE SET FOR BRAZING LIQUID AND SUCTION / VAPOR LINE SERVICEVALVES
OUTDOORUNIT
LIQUID LINE
VAPOR LINE
LIQUID LINE SERVICEVALVE
SUCTION /VAPOR LINE
SERVICEVALVE
ATTACHGAUGES
INDOORUNIT
SUCTION / VAPOR SERVICE PORT MUST BEOPEN TO ALLOW EXIT POINT FOR NITROGEN
A Connect gauge set low pressure side toliquid line service valve (service port).
B Connect gauge set center port to bottle ofnitrogen with regulator.
C Remove Schrader valve in suction / vaporline service port to allow nitrogen to escape.
NITROGEN
HIGHLOWUSE REGULATOR TO FLOWNITROGEN AT 1 TO 2 PSIG.
B
A
C
WHEN BRAZING LINE SET TOSERVICE VALVES, POINT FLAME
AWAY FROM SERVICE VALVE.
Flow regulated nitrogen (at 1 to 2 psig) through the low-side refrigeration gauge set into the liquid line service port valve, and out of the suction /vapor line service port valve.
CUT AND DEBUR CAP AND CORE REMOVAL
Cut ends of the refrigerant lines square (free from nicks or dents)and debur the ends. The pipe must remain round. Do not crimp endof the line.
Remove service cap and core from both thevapor and liquid line service ports.1 2
LIQUID LINE SERVICEVALVE
SERVICEPORTCORE
SERVICE PORTCAP
SERVICEPORTCORE
SERVICEPORT CAP
CUT AND DEBUR
LINE SET SIZE MATCHESSERVICE VALVE CONNECTION
COPPER TUBESTUB
SERVICE VALVECONNECTION
REFRIGERANT LINE
DO NOT CRIMP SERVICE VALVECONNECTOR WHEN PIPE IS
SMALLER THAN CONNECTION
REDUCER
3
SUCTION / VAPOR LINESERVICE VALVE
LINE SET SIZE IS SMALLERTHAN CONNECTION
Figure 8. Brazing Procedures
Page 11
TSA*S4 SERIES
WHEN BRAZING LINE SET TOSERVICE VALVES, POINT FLAME
AWAY FROM SERVICE VALVE.
LIQUID LINE SERVICE VALVE
LIQUID LINE
BRAZE LINE SET
Wrap both service valves with a saturated cloth as illustrated here before brazing to line set.
SATURATED CLOTH
IMPORTANT — Allow braze joint to cool. Applyadditional saturated cloths to help cool brazed joint.Do not remove wet rag until piping has cooled.Temperatures above 250ºF will damage valve seals.
6
SUCTION / VAPOR LINE
SATURATED CLOTH
SUCTION / VAPOR LINESERVICE VALVE
After all connections have been brazed, disconnect manifold gauge set from service ports. Apply saturated rags to both services valves to coolpiping. Once piping is cool, remove all wet cloths. Refer to the unit installation instructions for the next step in preparing the unit.
WHEN BRAZING LINE SET TOSERVICE VALVES, POINT FLAME
AWAY FROM SERVICE VALVE.
PREPARATION FOR NEXT STEP7
WARNING
1. FIRE, PERSONAL INJURY, OR PROPERTYDAMAGE will result if you do not wrap a wet clotharound both liquid and suction line service valvebodies and copper tube stub while brazing in the lineset! The braze, when complete, must be quenchedwith water to absorb any residual heat.
2. Do not open service valves until refrigerant lines andindoor coil have been leak-tested and evacuated.Refer to procedures provided in this supplement.
WRAP SERVICE VALVES
To help protect service valve seals during brazing, wrap a saturated cloth around service valve bodies and copper tube stub. Use anothersaturated cloth underneath the valve body to protect the base paint.
4FLOW NITROGEN
Flow regulated nitrogen (at 1 to 2 psig) through the refrigeration gauge set into the valve stem port connection on the liquid service valve andout of the suction / vapor valve stem port. See steps 3A, 3B and 3C on manifold gauge set connections
5
Figure 9. Brazing Procedures (continued)
Page 12
506663-01 11/10
Flushing Line Set and Indoor Coil
Flushing is only required if existing indoor coil and line set are to be used. Otherwise proceed to Installing Indoor MeteringDevice on page 13.
SENSINGLINE
TEFLON® RING
FIXED ORIFICE
BRASS NUT
LIQUID LINE ASSEMBLY(INCLUDES STRAINER)
LIQUID LINE ORIFICE HOUSING
DISTRIBUTOR TUBES
DISTRIBUTORASSEMBLY
REMOVE AND DISCARD
WHITE TEFLON® SEAL(IF PRESENT)
A On fully cased coils, remove the coil access and plumbing panels.
B Remove any shipping clamps holding the liquid line and distributor assembly.
C Using two wrenches, disconnect liquid line from liquid line orifice housing. Take care not to twist or damage distributor tubes during this process.
D Remove and discard fixed orifice, valve stem assembly if present andTeflon® washer as illustrated above.
E Use a field-provided fitting to temporary reconnect the liquid line to theindoor unit's liquid line orifice housing.
TYPICAL EXISTING FIXED ORIFICEREMOVAL PROCEDURE(UNCASED COIL SHOWN)
TYPICAL EXISTING EXPANSION VALVEREMOVAL PROCEDURE (UNCASED COILSHOWN)
TWO PIECE PATCH PLATE(UNCASED COIL ONLY)
VAPORLINE
DISTRIBUTORASSEMBLY
DISTRIBUTORTUBES
LIQUIDLINE
MALE EQUALIZERLINE FITTING
EQUALIZERLINE
CHECKEXPANSION
VALVE
TEFLON®
RING
STUB END
TEFLON®
RING
SENSING BULB
LIQUID LINEORIFICE
HOUSING
LIQUID LINEASSEMBLY WITH
BRASS NUT
A On fully cased coils, remove the coil access and plumbing panels.
B Remove any shipping clamps holding the liquid line and distributorassembly.
C Disconnect the equalizer line from the check expansion valveequalizer line fitting on the vapor line.
D Remove the vapor line sensing bulb.
E Disconnect the liquid line from the check expansion valve at the liquidline assembly.
F Disconnect the check expansion valve from the liquid line orificehousing. Take care not to twist or damage distributor tubes during thisprocess.
G Remove and discard check expansion valve and the two Teflon® rings.
H Use a field-provided fitting to temporary reconnect the liquid line to theindoor unit's liquid line orifice housing.
LOW HIGH
EXISTINGINDOOR
UNIT
GAUGEMANIFOLD
INVERTED CYLINDERCONTAINS CLEAN TOBE USED FORFLUSHING.
LIQUID LINE SERVICEVALVE
INLET
DISCHARGE
TANKRETURN
CLOSEDOPENED
RECOVERYCYLINDER
RECOVERY MACHINE
NEWOUTDOOR
UNIT
VAPOR LINESERVICE VALVE
VA
PO
R
LIQ
UID
1
A Inverted cylinder with clean refrigerant to the vapor service valve.
B gauge set (low side) to the liquid line valve.
C gauge set center port to inlet on the recovery machine with an emptyrecovery tank to the gauge set.
D Connect recovery tank to recovery machines per machine instructions.
CONNECT GAUGES AND EQUIPMENT FORFLUSHING PROCEDURE
A
B
CD
B
OR
FLUSHING LINE SET
A Set the recovery machine for liquid recovery and start therecovery machine. Open the gauge set valves to allow therecovery machine to pull a vacuum on the existing system lineset and indoor unit coil.
B Invert the cylinder of clean and open its valve to allow liquidrefrigerant to flow into the system through the vapor line valve.Allow the refrigerant to pass from the cylinder and through theline set and the indoor unit coil before it enters the recoverymachine.
C After all of the liquid refrigerant has been recovered, switch therecovery machine to vapor recovery so that all of the vapor isrecovered. Allow the recovery machine to pull down to 0 thesystem.
D Close the valve on the inverted drum and the gauge set valves.Pump the remaining refrigerant out of the recovery machine andturn the machine off.
The line set and indoor unit coil must be flushed with at least thesame amount of clean refrigerant that previously charged thesystem. Check the charge in the flushing cylinder beforeproceeding.
1A
2
3
1B
Figure 10. Removing Metering Device and Flushing
Page 13
TSA*S4 SERIES
Installing Indoor Metering Device
This outdoor unit is designed for use in systems that useeither an fixed orifice (RFC) (included with outdoor unit), orexpansion valve metering device (purchased separately)at the indoor coil.
See the Lennox TSA*S4 Engineering Handbook forapproved expansion valve kit match ups. The expansionvalve unit can be installed internal or external to the indoor
coil. In applications where an uncased coil is beinginstalled in a field-provided plenum, install the expansionvalve in a manner that will provide access for field servicingof the expansion valve. Refer to below illustration forreference during installation of expansion valve unit. .
After installation of the indoor coil metering device,proceed to Leak Test Line Set and Indoor Coil on page 14.
A Attach the vapor line sensing bulb in the properorientation as illustrated to the right using the clamp andscrews provided.
NOTE — Confirm proper thermal contact between vapor lineand expansion bulb before insulating the sensing bulb onceinstalled.
B Connect the equalizer line from the expansion valve tothe equalizer vapor port on the vapor line. Finger tightenthe flare nut plus 1/8 turn (7 ft-lbs) as illustrated below.
TWO PIECEPATCH PLATE
(UNCASEDCOIL ONLY)
VAPORLINE
LIQUID LINEORIFICE
HOUSINGDISTRIBUTOR
TUBES
LIQUID LINE
MALE EQUALIZER LINEFITTING (SEE
EQUALIZER LINEINSTALLATION FORFURTHER DETAILS)
SENSINGLINE
EQUALIZERLINE
EXPANSIONVALVE
TEFLON®
RING
(Uncased Coil Shown)
Sensing bulb insulation is required ifmounted external to the coil casing. sensingbulb installation for bulb positioning.
STUBEND
TEFLON®
RING
LIQUID LINEASSEMBLY WITH
BRASS NUT
DISTRIBUTORASSEMBLY
A Remove the field-provided fitting that temporaryreconnected the liquid line to the indoor unit's distributorassembly.
B Install one of the provided Teflon® rings around thestubbed end of the expansion valve and lightly lubricatethe connector threads and expose surface of the Teflon®
ring with refrigerant oil.
C Attach the stubbed end of the expansion valve to theliquid line orifice housing. Finger tighten and use anappropriately sized wrench to turn an additional 1/2 turnclockwise as illustrated in the figure above, or 20 ft-lb.
D Place the remaining Teflon® washer around the otherend of the expansion valve. Lightly lubricate connectorthreads and expose surface of the Teflon® ring withrefrigerant oil.
E Attach the liquid line assembly to the expansion valve.Finger tighten and use an appropriately sized wrench toturn an additional 1/2 turn clockwise as illustrated in thefigure above or 20 ft-lb.
ON 7/8” AND LARGER LINES,MOUNT SENSING BULB ATEITHER THE 4 OR 8 O'CLOCKPOSITION. NEVER MOUNT ONBOTTOM OF LINE.
12
ON LINES SMALLER THAN7/8”, MOUNT SENSINGBULB AT EITHER THE 3 OR9 O'CLOCK POSITION.
12
BULB
VAPOR LINE
VAPOR LINE
NOTE — NEVER MOUNT ON BOTTOM OF LINE.
BULB
BULBBULB
VAPOR LINE
FLARE NUT
COPPER FLARESEAL BONNET
MALE BRASS EQUALIZERLINE FITTING
FLARE SEAL CAP
OR
123
4567
8910
11 12
1/2 Turn
SENSING BULB INSTALLATION
EQUALIZER LINE INSTALLATION
123
4567
8910
11 12
1/8 Turn
A Remove and discard either the flare seal cap or flare nutwith copper flare seal bonnet from the equalizer line porton the vapor line as illustrated in the figure to the right.
B Remove and discard either the flare seal cap or flare nutwith copper flare seal bonnet from the equalizer line port onthe vapor line as illustrated in the figure to the right.
INDOOR EXPANSION VALVE INSTALLATION
Figure 11. Installing Indoor Expansion Valve
Page 14
506663-01 11/10
IMPORTANTThe Environmental Protection Agency (EPA) prohibitsthe intentional venting of HFC refrigerants duringmaintenance, service, repair and disposal of appliance.Approved methods of recovery, recycling or reclaimingmust be followed.
IMPORTANTIf this unit is being matched with an approved line setor indoor unit coil which was previously charged withmineral oil, or if it is being matched with a coil whichwas manufactured before January of 1999, the coiland line set must be flushed prior to installation. Takecare to empty all existing traps. Polyol ester (POE) oilsare used in Lennox units charged with HFC-410Arefrigerant. Residual mineral oil can act as aninsulator, preventing proper heat transfer. It can alsoclog the expansion device, and reduce the systemperformance and capacity.Failure to properly flush the system per theinstructions below will void the warranty.
Leak Test Line Set and Indoor Coil
IMPORTANTLeak detector must be capable of sensing HFCrefrigerant.
After completing the leak testing the line set and indoor coilas outlined in figure 12, proceed to Evacuating Line Setand Indoor Coil on page 15.
WARNINGWhen using a high pressure gas such asdry nitrogen to pressurize a refrigerationor air conditioning system, use aregulator that can control the pressuredown to 1 or 2 psig (6.9 to 13.8 kPa).
WARNINGRefrigerant can be harmful if it is inhaled. Refrigerantmust be used and recovered responsibly.
Failure to follow this warning may result in personal injuryor death.
TO VAPORSERVICE VALVE
HFC-410A
MANIFOLD GAUGE SET
OUTDOOR UNIT
HIGHLOW
NITROGEN
A With both manifold valves closed, connect the cylinder of HFC-410A refrigerant to the center port of the manifold gauge set. Open the valveon the HFC-410A cylinder (vapor only).
B Open the high pressure side of the manifold to allow HFC-410A into the line set and indoor unit. Weigh in a trace amount of HFC-410A. [Atrace amount is a maximum of two ounces (57 g) refrigerant or three pounds (31 kPa) pressure]. Close the valve on the HFC-410A cylinderand the valve on the high pressure side of the manifold gauge set. Disconnect the HFC-410A cylinder.
C Connect a cylinder of dry nitrogen with a pressure regulating valve to the center port of the manifold gauge set.
D Adjust dry nitrogen pressure to 150 psig (1034 kPa). Open the valve on the high side of the manifold gauge set in order to pressurize the line setand the indoor unit.
E After a few minutes, open one of the service valve ports and verify that the refrigerant added to the system earlier is measurable with a leakdetector.
F After leak testing disconnect gauges from service ports.
After the line set has been connected to the indoor and outdoor units, check the line set connections and indoor unit for leaks. Use thefollowing procedure to test for leaks:
A Connect an HFC-410A manifold gauge set high pressurehose to the vapor valve service port.
NOTE — Normally, the high pressure hose is connected tothe liquid line port. However, connecting it to the vapor portbetter protects the manifold gauge set from high pressuredamage.
B With both manifold valves closed, connect the cylinder ofHFC-410A refrigerant to the center port of the manifold gaugeset.
NOTE — Later in the procedure,the HFC-410A container will bereplaced by the nitrogencontainer.
1CONNECT GAUGESET
2 TEST FOR LEAKS
AB
Figure 12. Leak Test
Page 15
TSA*S4 SERIES
Evacuating Line Set and Indoor Coil
A Open both manifold valves and start the vacuum pump.
B Evacuate the line set and indoor unit to an absolute pressure of 23,000 microns (29.01 inches of mercury).
NOTE — During the early stages of evacuation, it is desirable to close the manifold gauge valve at least once. A rapid rise in pressure
indicates a relatively large leak. If this occurs, repeat the leak testing procedure.
NOTE — The term absolute pressure means the total actual pressure within a given volume or system, above the absolute zero ofpressure. Absolute pressure in a vacuum is equal to atmospheric pressure minus vacuum pressure.
C When the absolute pressure reaches 23,000 microns (29.01 inches of mercury), perform the following:
� Close manifold gauge valves
� Close valve on vacuum pump
� Turn off vacuum pump
� Disconnect manifold gauge center port hose from vacuum pump
� Attach manifold center port hose to a dry nitrogen cylinder with pressure regulator set to 150 psig (1034 kPa) and purge the hose.
� Open manifold gauge valves to break the vacuum in the line set and indoor unit.
� Close manifold gauge valves.D Shut off the dry nitrogen cylinder and remove the manifold gauge hose from the cylinder. Open the manifold gauge valves to release the
dry nitrogen from the line set and indoor unit.
E Reconnect the manifold gauge to the vacuum pump, turn the pump on, and continue to evacuate the line set and indoor unit until theabsolute pressure does not rise above 500 microns (29.9 inches of mercury) within a 20-minute period after shutting off the vacuum pumpand closing the manifold gauge valves.
F When the absolute pressure requirement above has been met, disconnect the manifold hose from the vacuum pump and connect it to anupright cylinder of HFC-410A refrigerant. Open the manifold gauge valve 1 to 2 psig in order to release the vacuum in the line set andindoor unit.
G Perform the following:
OUTDOOR
UNIT
TO VAPORSERVICE VALVE
TO LIQUID LINESERVICE VALVE
MICRONGAUGE
VACUUM PUMP
A34000 1/4 SAE TEE WITHSWIVEL COUPLER
500
MANIFOLDGAUGE SET
HFC-410A
RECOMMENDMINIMUM 3/8” HOSE
A Connect low side of manifold gauge setwith 1/4 SAE in-line tee to vapor lineservice valve
B Connect high side of manifold gaugeset to liquid line service valve
C Connect micron gauge availableconnector on the 1/4 SAE in-line tee.
D Connect the vacuum pump (withvacuum gauge) to the center port of themanifold gauge set. The center portline will be used later for both theHFC-410A and nitrogen containers.
HIGHLOW
12
34
56
78
910
11 12
1/6 TURN
NITROGEN
1CONNECT GAUGE SET
A
B
C
D
2EVACUATE THE SYSTEM
NOTE — Remove cores from service valves (if not already done).
� Close manifold gauge valves.
� Shut off HFC-410A cylinder.
� Reinstall service valve cores by removing manifold hose from service valve. Quickly install cores with coretool while maintaining a positive system pressure.
� Replace stem caps and secure finger tight, then tighten an additional one-sixth (1/6) of a turn as illustrated.
Figure 13. Evacuating System
Page 16
506663-01 11/10
Electrical
In the U.S.A., wiring must conform with current local codesand the current National Electric Code (NEC). In Canada,wiring must conform with current local codes and the currentCanadian Electrical Code (CEC).
Refer to the furnace or air handler installation instructions
for additional wiring application diagrams and refer to unitnameplate for minimum circuit ampacity and maximumovercurrent protection size.
24VAC TRANSFORMER
Use the transformer provided with the furnace or airhandler for low‐voltage control power (24VAC - 40 VAminimum)
SERVICEDISCONNECT
SWITCH
MAIN FUSE BOX/BREAKER PANEL
Refer to the unit nameplate for minimum circuit ampacity, and maximumfuse or circuit breaker (HACR per NEC). Install power wiring and properlysized disconnect switch.
NOTE — Units are approved for use only with copper conductors.Ground unit at disconnect switch or to an earth ground.
SIZE CIRCUIT AND INSTALL DISCONNECT SWITCH
NOTE — 24VAC, Class II circuit connections are made in the controlpanel.
Install room thermostat (ordered separately) on an inside wallapproximately in the center of the conditioned area and 5 feet (1.5m) fromthe floor. It should not be installed on an outside wall or where it can beaffected by sunlight or drafts.
THERMOSTAT
5 FEET(1.5M)
INSTALL THERMOSTAT
WARNINGElectric Shock Hazard. Can cause injury or death. Unit must be grounded in accordance with national andlocal codes.
Line voltage is present at all components when unit is not in operation on units with single‐pole contactors.Disconnect all remote electric power supplies before opening access panel. Unit may have multiple powersupplies.
Page 17
TSA*S4 SERIES
Any excess high voltage field wiring should be trimmed and secured away from any low voltage field wiring. To facilitate a conduit, a cutout is locatedin the bottom of the control panel. Connect conduit to the control panel using a proper conduit fitting.
ROUTING HIGH VOLTAGE/ GROUND AND CONTROL WIRING
CONTROL
WIRING
HIGH VOLTAGEFIELD WIRING
LOW VOLTAGEFIELD WIRING
FACTORYWIRING
GROMMET ANDWIRE TIE
WIRE RUN LENGTH AWG# INSULATION TYPE
LESS THAN 100' (30 METERS) 18 TEMPERATURE RATING
MORE THAN 100' (30 METERS) 16 35ºC MINIMUM.
Install low voltage wiring from outdoor to indoor unitand from thermostat to indoor unit as illustrated.
HIGH VOLTAGE / GROUND WIRES
CONTROL WIRING
A Run 24VAC control wires through hole with grommetand secure with provided wire tie.
B Make 24VAC thermostat wire connections. Locate thetwo wires from the contactor and make connectionusing field provided wire nuts:
� Yellow to Y1
� Black to C (common)
NOTE — For proper voltages, select thermostat wire (control wires)gauge per table below.
NOTE — Wire tie provides low voltage control wire strainrelief and to maintain separation of field installed low andhigh voltage circuits.
A
W1
Y
G
C
R
Y
G
C
THERMOSTAT INDOOR UNIT
POWER
HEAT
COOLING
INDOORBLOWER
COMMON
OUTDOORUNIT
Y1
C
W
R
TYPICAL LOW VOLTAGE FIELDWIRING
HIGH VOLTAGE FLEXIBLECONDUIT
THREE PHASE
SINGLE PHASE
NOTE — Do not bundle any excess 24VAC control wiresinside control panel.
CONTROLWIRING
GROUND
HIGH VOLTAGE
CONNECTIONS
(CONTACTOR)
HIGH VOLTAGECONNECTIONS(CONTACTOR)
GROUND
GROMMET ANDWIRE TIE
HIGH VOLTAGEFLEXIBLE CONDUIT
B
A
B
Page 18
506663-01 11/10
Figure 14. Typical Field Wiring Diagram — M Voltage — 380/420v (3PH) 50Hz
Page 19
TSA*S4 SERIES
Figure 15. Typical Field Wiring Diagram — T Voltage — 220/240v (1PH) 50Hz
Page 20
506663-01 11/10
Figure 16. Typical Factory Wiring Diagram
Servicing Units Delivered Void of Charge
If the outdoor unit is void of refrigerant, clean the systemusing the procedure described below.
1. Leak check system using procedure outlined in thisinstallation instruction.
2. Evacuate the system using procedure outlined in thisinstallation instruction.
3. Use nitrogen to break the vacuum and install a newfilter drier in the system.
4. Evacuate the system again using procedure outlinedin this installation instruction.
5. Weigh in refrigerant using procedure outlined in figure20.
Unit Start-Up
IMPORTANTIf unit is equipped with a crankcase heater, it should beenergized 24 hours before unit start-up to preventcompressor damage as a result of slugging.
1. Check that fan rotates freely.
2. Inspect all factory- and field-installed wiring for looseconnections.
3. After evacuation is complete, open the liquid line andsuction line service valves to release the refrigerantcharge (contained in outdoor unit) into the system.
4. Replace the stem caps and tighten as specified inOperating Service Valves on page 3.
5. Check voltage supply at the disconnect switch. Thevoltage must be within the range listed on the unit'snameplate. If not, do not start the equipment until youhave consulted with the power company and thevoltage condition has been corrected.
6. Set the thermostat for a cooling demand. Turn onpower to the indoor indoor unit and close the outdoorunit disconnect switch to start the unit.
7. Recheck voltage while the unit is running. Power mustbe within range shown on the nameplate.
8. Check system for sufficient refrigerate by using theprocedures listed under Start-Up and ChargingProcedures.
System Refrigerant
This section outlines procedures for:
1. Connecting gauge set for testing and charging;
2. Checking and adjusting indoor airflow;
3. Adding or removing refrigerant.
Page 21
TSA*S4 SERIES
TO LIQUIDLINE SERVICE
VALVETEMPERATURE
SENSOR
DIGITAL SCALE
REFRIGERANT TANK
TEMPERATURE SENSOR(LIQUID LINE)
MANIFOLD GAUGE SET
AClose manifold gauge set valves andconnect the center hose to a cylinder ofHFC-410A. Set for liquid phasecharging.
BConnect the manifold gauge set's lowpressure side to the suction line serviceport.
CConnect the manifold gauge set's highpressure side to the liquid line serviceport.
DPosition temperature sensor on liquid linenear liquid line service port.
OUTDOOR UNIT
CHARGE INLIQUID PHASE
CONNECTIONS FOR TESTING AND CHARGING
GAUGE SET
A
C
D
LOW HIGH
B SUCTION LINESERVICE PORTCONNECTION
Figure 17. Gauge Set Setup and Connections
WHEN TO CHARGE?
� Warm weather best� Can charge in colder weatherCHARGE METHOD? Determine by:
� Metering device type� Outdoor ambient temperatureREQUIREMENTS:
� Sufficient heat load in structure� Indoor temperature between 70‐80ºF (21-26ºC)� Manifold gauge set connected to unit� Thermometers:
- to measure outdoor ambient temperature- to measure liquid line temperature- to measure suction line temperature SUBCOOLING WEIGH‐IN
64ºF (17.7ºC)AND BELOW
65ºF (18.3ºC)AND ABOVE
START: Determine how refrigerant is metered
TXV
Figure 18. Determining Charge Method
OUTDOOR AMBIENT
TEMPERATURE
Page 22
506663-01 11/10
CHECKING AIR FLOW AT INDOOR COIL
Check airflow using the Delta-T (DT) process using the illustration in figure 19.
1. Determine the desired DT—Measure entering air temperature using dry bulb (A) and wet bulb (B). DT is the intersecting value of A and B in the table (see triangle).
2. Find temperature drop across coil—Measure the coil's drybulb entering and leaving air temperatures (A and C). Temperature Drop Formula: (TDrop) = A minus C.
3. Determine if fan needs adjustment—If the difference betweenthe measured TDrop and the desired DT (TDrop–DT) is within+3º, no adjustment is needed. See examples: Assume DT =15 and A temp. = 72º, these C temperatures would necessitate stated actions:
Cº TDrop – DT = ºF ACTION
53º 19 – 15 = 4 Increase the airflow58º 14 – 15 = -1 (within +3º range) no change62º 10 – 15 = -5 Decrease the airflow
4. Adjust the fan speed—See indoor unit instructions to increase/decrease fan speed.
Changing air flow affects all temperatures; recheck temperatures to confirm that the temperature drop and DT are within+3º.
DT80 24 24 24 23 23 22 22 22 20 19 18 17 16 15
78 23 23 23 22 22 21 21 20 19 18 17 16 15 14
76 22 22 22 21 21 20 19 19 18 17 16 15 14 13
74 21 21 21 20 19 19 18 17 16 16 15 14 13 12
72 20 20 19 18 17 17 16 15 15 14 13 12 11 10
70 19 19 18 18 17 17 16 15 15 14 13 12 11 10
57 58 59 60 61 62 63 64 65 66 67 68 69 70
Temp.of airenteringindoorcoil ºF
INDOORCOIL
DRYBULB
DRYBULB
WETBULB
B
TDrop
19º
A
Dry
-bu
lb
Wet-bulb ºF
A
72º
B
64º
C
53º
air flowair flow
All temperatures areexpressed in ºF
Figure 19. Checking Indoor Airflow over Evaporator Coil using Delta-T Chart
START: Measure outdoor ambient temperature 64ºF
(17.7ºC) and
BELOW
1. Check Liquid and suction line pressures
2. Compare unit pressures with table 5 or 6.
3. Conduct leak check; evacuate aspreviously outlined.
4. Weigh in the unit nameplate charge plusany charge required for line set differencesover feet.
Liquid Line
Set Diameter
g per 1.5 m) adjust from 4.6 m lineset*
9.5 mm 85 g per 1.5 m)
NOTE - *If line length is greater than 4.6 m, add this amount. Ifline length is less than 4.6 m, subtract this amount.
Refrigerant Charge per Line Set Length
USE SUBCOOLINGMETHOD
This nameplate is for illustration purposes
only. Go to actual nameplate on outdoor
unit for charge information.
ABOVE orBELOW
Figure 20. HFC-410A Weigh In
65ºF
(18.3ºC)
and
ABOVE
Page 23
TSA*S4 SERIES
DO NOT CHARGE UNIT
(Results of charging at lowtemperatures not reliable)
START: Measure outdoor ambient temperature
USE WEIGH‐IN METHOD
Weigh‐in or remove refrigerantbased upon line set length
BLOCK OUTDOOR COIL: [sometimes necessary with lower temperatures]Use cardboard or plastic sheet to restrict the airflow through the outdoor coilto achieve pressures from 325-375 psig (2240-2585 kPa). Higher pressuresare needed to check charge. Block equal sections of air intake panels andmove coverings sideways until the liquid pressure is in the above notedranges.
If value is MORE
than shown, remove
refrigerant.
1. Confirm proper airflow across coil using figure19.
2. Compare unit pressures with table 5 or 6.
3. Set thermostat to call for heat (must have acooling load between 70‐80ºF (21-26ºC)
4. Connect gauge set
5. Measure outdoor ambient temperature
6. When heat demand is satisfied, set thermostat tocall for cooling
7. Allow temperatures and pressures to stabilize.
NOTE - If necessary, block outdoor coil to
maintain 325 - 375 psig.
8. Record liquid line temperature:
LIQº = ______
9. Measure liquid line pressure and use the value todetermine saturation temperature (see table 7):
SATº = ______
10. Subtract to determine subcooling (SCº):
SATº_____ - LIQº _____ = SCº _____
11. Compare results with tables 3 or 4 .
Figure 21. HFC-410A Subcooling Charge
MORE orLESS
If value is LESS
than shown, add
refrigerant.
ABOVE orBELOW
65ºF
(18.3ºC)
and
ABOVE
64ºF
(17.7ºC) and
BELOW
Table 3. Subcooling (SC) Values —TXV System - ºF(ºC) +1ºF (0.5ºC) (1-PHASE)
TSA*S4 50Hz International (1-Phase)
F(5C) -024 -030 -036 -048 -060
65 (18) 10 6 5 2 4
70 (21) 10 6 5 2 4
75 (24) 11 6 6 3 4
80 (27) 11 7 6 3 5
85 (29) 11 7 6 3 5
90 (32) 11 7 7 4 5
95 (35) 11 7 7 4 5
100 (38) 11 7 7 5 5
105 (41) 11 7 7 5 5
110 (43) 11 8 7 5 5
115 (45) 11 8 8 6 5
Table 4. Subcooling (SC) Values — TXV System - ºF(ºC) +1ºF (0.5ºC) (3-PHASE)
TSA*S4 50Hz International (3-Phase)
F(5C) -036 -048 -060
65 (18) 8 2 2
70 (21) 8 2 3
75 (24) 9 3 3
80 (27) 9 3 3
85 (29) 9 4 4
90 (32) 10 4 4
95 (35) 10 4 4
100 (38) 10 5 4
105 (41) 10 5 4
110 (43) 10 5 4
115 (45) 10 6 4
Page 24
506663-01 11/10
IMPORTANTUse this table to perform maintenance checks; it is not a procedure for charging thesystem. Minor variations in these pressures may be due to differences in installations.Significant deviations could mean that the system is not properly charged or that aproblem exists with some component in the system.
Table 5. HFC-410A Normal Operating Pressures — Liquid +10 and Suction +5 Psig (1-Phase)TSA*S4 50Hz International (1-Phase)
TSA*S4 -024 -030 -036 -048 -060
F(5C)* Liquid / Suction Liquid / Suction Liquid / Suction Liquid / Suction Liquid / Suction
65 (18) 260 / 137 255 / 132 246 / 133 248 / 133 259 / 143
70 (21) 280 / 138 274 / 134 265 / 134 269 / 134 279 / 144
75 (24) 301 / 139 295 / 135 286 / 136 290 / 136 299 / 146
80 (27) 323 / 141 317 / 136 307 / 137 313 / 137 320 / 147
85 (29) 346 / 142 339 / 137 330 / 138 335 / 138 342 / 148
90 (32) 370 / 144 363 / 139 354 / 140 360 / 140 364 / 150
95 (35) 395 / 145 387 / 140 378 / 141 386 / 142 387 / 151
100 (38) 421 / 147 413 / 142 404 / 143 412 / 143 411 / 153
105 (41) 449 / 149 439 / 143 430 / 145 440 / 145 437 / 154
110 (43) 478 / 151 468 / 145 458 / 146 468 / 147 464 / 156
115 (45) 507 / 152 497 / 147 487 / 148 498 / 149 492 / 157
*Temperature of the air entering the outside coil.
Table 6. HFC-410A Normal Operating Pressures — Liquid +10 and Suction +5 Psig (3-Phase)
TSA*S4 50Hz International (3-Phase)
TSA*S4 -036 -048 -060
F( 5C)* Liquid / Suction Liquid / Suction Liquid / Suction
65 (18) 269 / 135 247 / 132 269 / 136
70 (21) 290 / 136 269 / 134 289 / 137
75 (24) 311 / 137 290 / 136 310 / 139
80 (27) 334 / 138 312 / 138 332 / 140
85 (29) 357 / 139 335 / 139 355 / 142
90 (32) 382 / 141 360 / 140 377 / 143
95 (35) 407 / 142 385 / 142 400 / 144
100 (38) 433 / 143 412 / 144 423 / 146
105 (41) 460 / 145 439 / 145 449 / 148
110 (43) 490 / 146 468 / 147 476 / 149
115 (45) 520 / 148 498 / 149 504 / 151
*Temperature of the air entering the outside coil.
Table 7. HFC-410A Temperature (°F) - Pressure (Psig)
°F °C Psig °F °C Psig
-40 -40.0 11.6 60 15.6 170
-35 -37.2 14.9 65 18.3 185
-30 -34.4 18.5 70 21.1 201
-25 -31.7 22.5 75 23.9 217
-20 -28.9 26.9 80 26.7 235
-15 -26.1 31.7 85 29.4 254
-10 -23.3 36.8 90 32.2 274
-5 -20.6 42.5 95 35.0 295
0 -17.8 48.6 100 37.8 317
5 -15.0 55.2 105 40.6 340
10 -12.2 62.3 110 43.3 365
15 -9.4 70.0 115 46.1 391
20 -6.7 78.3 120 48.9 418
25 -3.9 87.3 125 51.7 446
30 -1.1 96.8 130 54.4 476
35 1.7 107 135 57.2 507
40 4.4 118 140 60.0 539
45 7.2 130 145 62.8 573
50 10.0 142 150 65.6 608
55 12.8 155
Page 25
TSA*S4 SERIES
System Operation
IMPORTANTSome scroll compressor have internal vacuum protectorthat will unload scrolls when suction pressure goesbelow 20 psig. A hissing sound will be heard when thecompressor is running unloaded. Protector will resetwhen low pressure in system is raised above 40 psig. DONOT REPLACE COMPRESSOR.
The outdoor unit and indoor blower cycle on demand from
the room thermostat. When the thermostat blower switchis in the ON position, the indoor blower operatescontinuously.
HIGH PRESSURE SWITCH (S4)
TSA*S4 units are equipped with a high‐pressure switchthat is located in the liquid line of the compressor asillustrated in figure 1 on page 2.
MANUAL RESETBUTTON
Figure 22. High Pressure Switch (S4) Manual Reset
The switch is a Single Pole, Single Throw (SPST),manual-reset switch which is normally closed andremoves power from the compressor when dischargepressure rises above factory setting at 590 + 10 psi. The
manual-reset button can be identified by a red cap that ispress to preform the reset function.
Crankcase Heater (HR1)
Crankcase heater HR1 prevents liquid from accumulatingin the compressor. The heater is always on when thecompressor is off. An optional crankcase heaterthermostat (S40) is available.
Table 8. Crankcase Heaters
Parts Watts Voltage
M Voltage 40 480
T Voltage 40 240
Maintenance
DEALER
Maintenance and service must be performed by a qualifiedinstaller or service agency. At the beginning of eachcooling season, the system should be checked as follows:
WARNINGElectric shock hazard. Can cause injuryor death. Before attempting to performany service or maintenance, turn theelectrical power to unit OFF at disconnectswitch(es). Unit may have multiple powersupplies.
WARNINGImproper installation, adjustment, alteration, service ormaintenance can cause personal injury, loss of life, ordamage to property.
Installation and service must be performed by a licensedprofessional installer (or equivalent) or a service agency.
Outdoor Unit
1. Outdoor unit fan motor is pre-lubricated and sealed.No further lubrication is needed.
2. Visually inspect all connecting lines, joints and coils forevidence of oil leaks.
3. Check all wiring for loose connections.
4. Check for correct voltage at unit (unit operating).
5. Check amp draw on outdoor fan motor.
Motor Nameplate:_________ Actual:__________.
6. Inspect drain holes in coil compartment base andclean if necessary.
NOTE ‐ If insufficient cooling occurs, the unit should begauged and refrigerant charge should be checked.
Outdoor Coil
Clean and inspect outdoor coil (may be flushed with awater hose). Ensure power is off before cleaning.
NOTE — It may be necessary to flush the outdoor coilmore frequently if it is exposed to substances which arecorrosive or which block airflow across the coil (e.g., peturine, cottonwood seeds, fertilizers, fluids that maycontain high levels of corrosive chemicals such as salts)
Sea Coast — Moist air in ocean locations can carry salt,which is corrosive to most metal. Units that are locatednear the ocean require frequent inspections andmaintenance. These inspections will determine thenecessary need to wash the unit including the outdoor coil.Consult your installing contractor for properintervals/procedures for your geographic area or servicecontract.
Indoor Unit
1. Clean or change filters.
2. Lennox blower motors are prelubricated andpermanently sealed. No more lubrication is needed.
Page 26
506663-01 11/10
3. Adjust blower speed for cooling. Measure the pressuredrop over the coil to determine the correct blower CFM.Refer to the unit information service manual for pressuredrop tables and procedure.
4. Belt Drive Blowers - Check belt for wear and propertension.
5. Check all wiring for loose connections.
6. Check for correct voltage at unit. (blower operating)
7. Check amp draw on blower motor.
Motor Nameplate:_________ Actual:__________.
Indoor Coil
1. Clean coil if necessary.
2. Check connecting lines, joints and coil for evidence ofoil leaks.
3. Check condensate line and clean if necessary.
OWNER
Cleaning of the outdoor unit's coil should be performed bya trained service technician. Contact your dealer and setup a schedule (preferably twice a year, but at least once ayear) to inspect and service your outdoor unit. Thefollowing maintenance may be performed by thehomeowner.
NOTE - A white residue may appear on the coil guards andgrilles on outdoor units. The residue is a non-toxicbyproduct of manufacturing the flexible coating. It can beremoved by wiping the coil guard with a cloth.
CAUTIONPhysical contact with metal edges and corners whileapplying excessive force or rapid motion can result inpersonal injury. Be aware of, and use caution whenworking near these areas during installation or whileservicing this equipment.
IMPORTANTSprinklers and soaker hoses should not be installedwhere they could cause prolonged exposure to theoutdoor unit by treated water. Prolonged exposure of theunit to treated water (i.e., sprinkler systems, soakers,waste water, etc.) will corrode the surface of steel andaluminum parts and diminish performance and longevityof the unit.
Outdoor Coil
1. Make sure power is off before cleaning. Clean andinspect outdoor coil. The coil may be flushed with awater hose.
2. The outdoor coil is protected by an inner mesh screenand a wire cage (see figure 23). If debris has collectedbetween the mesh screen and the coil and cannot bedislodged by spraying unpressurized water frominside coil surface to the outside, the mesh may beremoved by first removing the top of the unit which willallow for removal of the wire cage.
3. Then, using pliers to grip the head of the push pins, pullstraight out to extract the push pins along one side ofthe coil. If necessary, remove the push pins along theback of the unit; it is usually unnecessary to fullyremove the inner mesh screen.
4. Drape the mesh screen back and wash the coil. Whenall the debris has been removed from the coil, reinstallthe mesh screen by positioning it in its original positionand reinserting the push pin. No tool is required topush the pin back into the same slot in the fins.
5. If the push pin is loose and tends not to stay in place,brush the fins with a fin brush (22 fins/in). Line up thepush pin a couple fins to the right or left of the originalhole and re-insert the pin.
9 PINS USED ON -048AND -060; 6 PINS ALLOTHERS
MESH SCREEN
ÂÂÂÂÂÂÂÂÂÂÂÂÂÂÂÂÂÂÂÂÂÂÂÂÂÂÂÂÂÂÂÂÂÂÂÂÂÂÂÂÂÂÂÂÂÂÂÂÂÂÂÂÂÂÂÂÂÂÂÂÂÂÂÂÂÂ
Figure 23. Cleaning Debris from Mesh
PUSH PIN
NOTE — It may be necessary to flush the outdoor coil
more frequently if it is exposed to substances which are
corrosive or which block airflow across the coil (e.g., pet
urine, cottonwood seeds, fertilizers, fluids that may
contain high levels of corrosive chemicals such as salts)
Routine Maintenance
In order to ensure peak performance, your system must beproperly maintained. Clogged filters and blocked airflowprevent your unit from operating at its most efficient level.
1. Air Filter — Ask your Lennox dealer to show youwhere your indoor unit's filter is located. It will be eitherat the indoor unit (installed internal or external to thecabinet) or behind a return air grille in the wall orceiling. Check the filter monthly and clean or replaceit as needed.
2. Disposable Filter — Disposable filters should bereplaced with a filter of the same type and size.
NOTE — If you are unsure about the filter required for yoursystem, call your Lennox dealer for assistance.
3. Reusable Filter — Many indoor units are equippedwith reusable foam filters. Clean foam filters with amild soap and water solution; rinse thoroughly; allowfilter to dry completely before returning it to the unit orgrille.
Page 27
TSA*S4 SERIES
NOTE — The filter and all access panels must be in placeany time the unit is in operation.
4. Lennox Branded Air Filters — are designed toremove airborne particles from the air passing throughthe filter.
5. Indoor Unit — The indoor unit's evaporator coil isequipped with a drain pan to collect condensateformed as your system removes humidity from theinside air. Have your dealer show you the location ofthe drain line and how to check for obstructions. (Thiswould also apply to an auxiliary drain, if installed.)
Thermostat Operation
See the thermostat homeowner manual for instructions onhow to operate your thermostat.
Preservice CheckIf your system fails to operate, check the following beforecalling for service:
� Verify room thermostat settings are correct.
� Verify that all electrical disconnect switches are ON.
� Check for any blown fuses or tripped circuit breakers.
� Verify unit access panels are in place.
� Verify air filter is clean.
� If service is needed, locate and write down the unitmodel number and have it handy before calling.
AccessoriesFor update-to-date information, see any of the followingpublications:
� Lennox TSA*S4 Engineering Handbook
� Lennox Commercial Price Book
Start-Up and Performance Checklist
Job Name Job no. Date
Job Location City State
Installer City State
Unit Model No. Serial No. Service Technician
Nameplate Voltage
Rated Load Ampacity Compressor Outdoor Fan
Maximum Fuse or Circuit Breaker
Electrical Connections Tight? � Indoor Filter clean? � Supply Voltage (Unit Off)
Indoor Blower RPM S.P. Drop Over Indoor (Dry) Outdoor Coil Entering Air Temp.
Discharge Pressure Suction Pressure Refrigerant Charge Checked? �
Refrigerant Lines: Leak Checked? � Properly Insulated? � Outdoor Fan Checked? �
Service Valves: Fully Opened? � Caps Tight? � Thermostat
Voltage With Compressor Operating Calibrated? � Properly Set? � Level? �
07/11 506294−01
�������� ����������Page 1
�2011 Lennox Industries Inc.Dallas, Texas, USA
RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE
WARNINGImproper installation, adjustment, alteration, service ormaintenance can cause personal injury, loss of life, ordamage to property.
Installation and service must be performed by a licensedprofessional installer (or equivalent) or a service agency.
CAUTIONPhysical contact with metal edges and corners whileapplying excessive force or rapid motion can result inpersonal injury. Be aware of, and use caution whenworking near these areas during installation or whileservicing this equipment.
IMPORTANTThe Clean Air Act of 1990 bans the intentional venting ofrefrigerant (CFCs, HCFCs and HFCs) as of July 1, 1992.Approved methods of recovery, recycling or reclaimingmust be followed. Fines and/or incarceration may belevied for noncompliance.
INSTALLATIONINSTRUCTIONS
Elite® Series CBX27UHUnits
MULTI−POSITION AIR HANDLERS506294−0107/11Supersedes 05/11
Table of Contents
CBX27UH Up−flow/Down−flow Unit Dimensions 2. . .
CBX27UH Horizontal LH/RH Unit Dimensions 3. . . .
General Information 4. . . . . . . . . . . . . . . . . . . . . . . . . . .
Shipping and Packing List 4. . . . . . . . . . . . . . . . . . . . . .
Requirements 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Installing the Unit 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Brazing Connections 6. . . . . . . . . . . . . . . . . . . . . . . . . . .
Installing the Condensate Drain 7. . . . . . . . . . . . . . . . .
Inspecting and Replacing Filters 8. . . . . . . . . . . . . . . . .
Sealing the Unit 9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Measuring Static Pressure 9. . . . . . . . . . . . . . . . . . . . .
Adjusting the Blower Speed 9. . . . . . . . . . . . . . . . . . . .
Making Electrical Connections 11. . . . . . . . . . . . . . . . . .
Repairing or Replacing Cabinet Insulation 15. . . . . . . . .
TOP CAP SHIPPINGBRACKET (REPLACE
SCREWS IN TOP CAPAFTER REMOVAL)
HORIZONTAL DRAIN PAN (SEE PAGES 4AND 6)
BLOWER HOUSINGSUPPORT PAD
IMPORTANT INFORMATION TO INSTALLERCHECK FOR AND REMOVE THE FOLLOWING ITEMS BEFORE OPERATING UNIT.
REFRIGERANT LINE PLUGS(SEE PAGE 6)
DRIP SHIELD FOR −060 UNITS ONLYHORIZONTAL APPLICATIONS (SEEPAGE 5).
D
D
Litho U.S.A.
Page 2
506294−01
CBX27UH Up−flow and Down−flow Unit Dimensions − Inches (mm)
OPTIONALELECTRIC HEAT
(FIELD−INSTALLED)
AIRFLOW
LIQUIDLINE
SUCTIONLINE
SUPPLY AIROPENING
RETURN AIRFILTER
LOW VOLTAGEINLETS (TOP AND
RIGHT SIDE)
RETURN AIR
TOP VIEW
FRONT VIEWSIDE VIEW
BLOWER
PIPING PLATE DETAIL(FOR UP−FLOW AND DOWN−FLOW POSITIONS)
A
B C
11-1/16 (281)
D
F E
LIQUID LINE
SUCTION LINE
CONDENSATE DRAINS(2) (HORIZONTAL)
COIL
3/4 (19)
3/4 (19)
5/8 (16)5/8 (16) 1 (25)
5/8 (16)
1-3/4 (44)
2(51)
1-1/8 (29) 4-3/8 (111)
2-3/4(70)
5-3/8(137)
3-1/2 (89)
OPTIONALELECTRIC HEAT
(FIELD−INSTALLED) AIR FLOW
LIQUIDLINE
SUCTIONLINE
ReturnAir Opening
SUPPLYAIR
FILTER
SUPPLY AIR
TOP VIEW
FRONT VIEWSIDE VIEW
BLOWER
A
BC
11-1/16 (281)
F
D
E
COIL
5/8 (16)5/8 (16)
5/8 (16)
5/8 (16)
5/8 (16)
LOW VOLTAGE(RIGHT SIDE)
LINE VOLTAGE(LEFT SIDE)
DOWN−FLOW POSITION
1 (25)
UP−FLOW POSITION
CONDENSATE DRAINS(2) (UP−FLOW ANDDOWN−FLOW)
FILTER ACCESS
FILTER ACCESS
H
G
H
G
LINE VOLTAGEINLETS (TOP
AND LEFT SIDE)
5/8 (16)
5/8 (16)
CBX27UH Common Dimensions − Inches (mm)
Dim. −018/−024 −030/−036 −042/−048 −060
A 49−1/4 (1251) 51 (1295) 58−1/2 (1486) 62-1/2 (1588)
B 21−1/4 (540) 21−1/4 (540) 21-1/4 (540) 21-1/4 (540)
C 20−5/8 (524) 22-5/8 (575) 24−5/8 (625) 24−5/8 (625)
D 19−3/4 (502) 19−3/4 (502) 19-3/4 (502) 19-3/4 (502)
E 19 (483) 21 (533) 23 (584) 23 (584)
F 20 (508) 20 (508) 20 (508) 20 (508)
G 24−5/8 (625) 26-3/8 (670) 27-7/8 (708) 27-7/8 (708)
H 24−5/8 (625) 24−5/8 (625) 30−5/8 (778) 34-5/8 (879)
Page 3
CBX27UH SERIES
CBX27UH Horizontal Left− and Right−Hand Unit Dimensions − Inches (mm)
LIQUIDLINE
SUCTIONLINE
SupplyAir
Opening
FILTER
LOW VOLTAGEINLETS (BOTTOM
AND RIGHTSIDE)
TOP VIEW
FRONT VIEW
BLOWER
H
B
C
D
LIQUIDLINE
SUCTIONLINE
CONDENSATEDRAINS (2)(UP−FLOW
ANDDOWN−FLOW)
CONDENSATEDRAINS (2)
(HORIZONTAL)
Coil
3/4 (19)
3/4 (19)
1-1/2(38)
1-3/4(44)
5-3/4(46)
2(51)
1-1/8(29)
RETURN AIROPENINGF
E
5/8 (16)
5/8 (16)
5/8 (16)
END VIEW
AIRFLOW
OPTIONAL ELECTRICHEAT (FIELD−INSTALLED)
11-1/16(281)
LINE VOLTAGEINLETS (TOP
AND RIGHTSIDE)
5-3/8(137)
4-3/8(111)
LIQUIDLINE
SUCTIONLINE
SupplyAir Opening
FILTER
LOW VOLTAGEINLETS (TOP AND
LEFT SIDE)
END VIEW
BLOWER
B
C
D
Coil
3/4 (19)
3/4 (19)
3/4 (19)
ReturnAir Opening
F
E
5/8 (16)
5/8 (16)
5/8 (16)
END VIEW
Air Flow
OPTIONAL ELECTRICHEAT (FIELD INSTALLED)
LINE VOLTAGE INLETS(BOTTOM AND LEFT SIDE)
Horizontal Position(Right-Hand Air
Discharge)
FILTER ACCESS
FILTER ACCESS
5-3/4(146)
1-1/2 (38)
1-3/4(44)
CONDENSATE DRAINS (2)(HORIZONTAL)
A5/8 (16)G
H
A5/8 (16)
G
1 (25)
1 (25)
11-1/16(281)
PIPING PLATEDETAIL
LIQUIDLINE
SUCTION LINE
2(51)
1-1/8(29)
5-3/8(137)
4-3/8(111)
PIPING PLATEDETAIL
Horizontal Position(Left-Hand Air
Discharge)
TOP VIEW
FRONT VIEW
3/4 (19)
END VIEW
FOR DIMENSIONS �A" THROUGH�H", SEE CHART ON PAGE 2.
WARNINGThis product and/or the indoor unit it is matched with may contain fiberglass wool.
Disturbing the insulation during installation, maintenance, or repair will expose you to fiberglass wool dust. Breathing thismay cause lung cancer. (Fiberglass wool is known to the State of California to cause cancer.)
Fiberglass wool may also cause respiratory, skin, and eye irritation.
To reduce exposure to this substance or for further information, consult material safety data sheets available from addressshown below, or contact your supervisor.
Lennox Industries Inc.P.O. Box 799900Dallas, TX 75379−9900
Page 4
506294−01
General Information
The Elite® CBX27UH series air handler is designed forinstallation with optional field−installed electric heat and amatching HFC−410A outdoor unit
This instruction is intended as a general guide and doesnot supersede local or national codes in any way. Consultauthorities having jurisdiction before installation. Checkequipment for shipping damage; if found, immediatelyreport damage to the last carrier.
Shipping and Packing List
Package 1 of 1 contains the following:
1�Assembled air handler unit
1�Horizontal drip shield (CBX27UH−60 only)
NOTE − For down−flow applications, order kit number
83M57.
Requirements
IMPORTANTThis unit must be matched with an indoor coil as speci-fied in Lennox Engineering Handbook. Coils previous-ly charged with HCFC−22 must be flushed.
In addition to conforming to manufacturer’s installationinstructions and local municipal building codes, installationof Lennox air handler units (with or without optional electricheat), shall conform with the following National FireProtection Association (NFPA) standards:
� NFPA No. 90A − Standard for Installation of Air
Conditioning and Ventilation Systems
� NFPA No. 90B − Standard for Installation of Residence
Type Warm Air Heating and Air Conditioning Systems
This unit is approved for installation clearance tocombustible material as stated on the unit rating plate.Accessibility and service clearances must takeprecedence over combustible material clearances.
Installing the Unit
These units are factory−configured for up−flow andhorizontal right−hand discharge installation. For down−flowor horizontal left−hand discharge, certain fieldmodifications are required.
DISASSEMBLE/REASSEMBLE AIR HANDLER UNITS
The air handler units consists of two factory-assembledsections. It may be necessary to disassemble the sectionswhen positioning the unit for installation.
To disassemble:
1. Remove access panels.
2. Remove both blower and coil assemblies. This willlighten the cabinet for lifting.
3. Remove one screw from the left and right posts insidethe unit. Remove one screw from each side on theback of the unit. Unit sections will now separate.
To reassemble:
1. Align cabinet sections together.
2. Reinstall screws.
3. Replace blower and coil assemblies.
4. Replace access panel.
UP−FLOW APPLICATIONUse the following procedures to configure the unit forup−flow operations:
1. Remove access panels.
2. Remove and discard the horizontal drip shield (−060model, used only on horizontal applications) and thecorrugated padding between the blower and coilassembly.
3. The horizontal drain pan must be removed when thecoil blower is installed in the up−flow position.Removing horizontal drain pain will allow properairflow and increase efficiency.
4. After removing horizontal drain pan, place the unit indesired location. Set unit so that it is level. Connectreturn and supply air plenums as required using sheetmetal screws as illustrated in figure 1.
5. Install units that have no return air plenum on a standthat is at least 14" from the floor to allow for proper airreturn. Lennox offers an optional up−flow unit stand aslisted in table 1.
HORIZONTAL DRAIN PAN(MUST BE REMOVED)
UP−FLOW/DOWN−FLOWDRAIN PAN
Figure 1. Up−flow Configuration
Table 1. Optional Unit Side Stand (Up−Flow Only)
Model Kit Number
−21, −26, and −31 45K31
−41 through −65. 45K32
HORIZONTAL RIGHT−HAND DISCHARGEAPPLICATION
Use the following procedures to configure the unit forhorizontal right−hand discharge operations:
NOTE − For horizontal applications, a secondary drain pan
is recommended. Refer to local codes.
Page 5
CBX27UH SERIES
1. Before operating the unit, remove access panels andthe horizontal drip shield (−060 model) and thecorrugated padding between the blower and coilassembly. Discard the corrugated padding.
2. Install the horizontal shield on the front edge of thehorizontal drain pan as illustrated in figure 2.
3. No further adjustment is necessary. Set unit so that it issloped 1/4" towards the drain pan end of the unit.
4. If the unit is suspended, the entire length of the cabinetmust be supported. If you use a chain or strap, use apiece of angle iron or sheet metal attached to the unit(either above or below) to support the length of thecabinet. Use securing screws no longer than 1/2" toavoid damaging the coil or filter as illustrated in figure3. Use sheet metal screws to connect the return andsupply air plenums as required.
No Adjustment Is Necessary
HORIZONTAL DRIP SHIELD (−060 MODELS)
UPLOAD / DOWN−FLOWDRAIN PAN
HORIZONTAL DRAINPAN
DOWN−FLOW RAIL
Figure 2. Right−Hand Discharge Configuration
HORIZONTAL RIGHT−HAND DISCHARGE APPLICATION IN HIGH HUMIDITY AREAS
For horizontal applications in high humidity areas removethe down−flow rail closest to the drain pan.
To remove rail:
1. Remove the screws from the rail at the back of unit andat the cabinet support rail.
2. Remove the down−flow rail then replace screws.
3. Seal around the exiting drain pipe, liquid line, andsuction line to prevent humid air from infiltrating intothe unit.
FRONT VIEW END VIEW
ANGLE IRON ORSHEET METAL
electrical inlet clearance 4 in.(102 mm)
1/2 in. Screws Maximum
Figure 3. Suspending Horizontal Unit
IMPORTANTWhen removing the coil, there is possible danger ofequipment damage and personal injury. Be careful whenremoving the coil assembly from a unit installed in right−or left−hand applications. The coil may tip into the drainpan once it is clear of the cabinet. Support the coil whenremoving it.
HORIZONTAL LEFT−HAND DISCHARGE APPLICATION
NOTE − For horizontal applications, a secondary drain pan
is recommended. Refer to local codes.
90ºBEND
CABINETSUPPORT
Coil shown in upload position for easy conversion
TOP CAP SCREWS
DRAIN PANreinstalled here
DRIPSHIELD
DRAIN PANSHIPPINGLOCATION
TOP CAP ROTATED TOCORRECT POSITION
���� DRAIN plugs ����reinstalled here removed from here
back coil endseal
TOPCAP
90ºBEND
Align holeswith holes in
coil end plate.
Figure 4. Field Modification for Left−Hand Discharge
Use the following procedures to configure the unit forhorizontal left−hand discharge operations:
1. Before operating the unit, remove access panels andthe horizontal drip shield (−060 model) and thecorrugated padding between the blower and coilassembly. Discard the corrugated padding.
2. Pull the coil assembly from unit. Pull off the horizontaldrain pan.
3. Remove the drain plugs from back drain holes onhorizontal drain pan and reinstall them on front holes.
IMPORTANTAfter removal of drain pan plug(s), check drain hole(s) toverify that drain opening is fully open and free of anydebris. Also check to make sure that no debris has falleninto the drain pan during installation that may plug up thedrain opening.
Page 6
506294−01
4. Rotate drain pan 180º front-to-back and install it on theopposite side of the coil.
5. Remove screws from top cap. Remove horizontal dripshield screw located in the center of the back coil endseal as illustrated in figure 4 on page 5.
6. Rotate horizontal drip shield 180º front to back.
7. Remove plastic plug from left hole on coil front endseal and reinstall plug in back hole. Reinstall horizontaldrip shield screw in front coil end seal. Drip shieldshould drain downward into horizontal drain pan insidecoil.
HORIZONTAL DRIP SHIELD (−060 MODEL)
DOWN−FLOWRAIL
FRONT EDGE OF HORIZONTALDRAIN PAN
Figure 5. Left−Hand Discharge Configuration
8. Rotate top cap 180º front-to-back and align withunused screw holes. Holes must align with front andback coil end plates. The top cap has a 45º bend onone side and a 90º bend on the other. The 90º bendmust be on the same side as the horizontal drainpan as illustrated in figure 4 on page 5.
NOTE − Be very careful when you reinstall the screws into
coil end plate engaging holes. Misaligned screws may
damage the coil.
9. From the up−flow position, flip cabinet 90º to the leftand set into place. Replace blower assembly. Securecoil in place by bending down the tab on the cabinetsupport rail as illustrated in figures 4 and 5.
10. Install the horizontal shield (−060 model) on the frontedge of the horizontal drain pan as illustrated in figure5 on page 6.
NOTE − For horizontal applications in high humidity
areas, remove the down−flow rail closest to the drain pan.
To remove rail, remove screw from rail at back of unit and
at cabinet support rail. Remove down−flow rail then replace
screws. Also, seal around the exiting drain pipe, liquid and
suction lines to prevent infiltration of humid air.
11. Knock out drain seal plate from access door. Secureplate to cabinet front flange with screw provided.
12. Flip access door and replace it on the unit.
13. Set unit so that it is sloped 1/4" toward the drain panend of the unit. Connect return and supply air plenumsas required using sheet metal screws.
14. If suspending the unit, it must be supported along theentire length of the cabinet. If using chain or strap, usea piece of angle iron or sheet metal attached to the unit(either above or below) so that the full length of thecabinet is supported. Use securing screws no longerthan 1/2" to avoid damage to coil or filter. as illustratedin figure 3 on page 5. Connect return and supply airplenums as required using sheet metal screws.
DOWN−FLOW APPLICATION
NOTE − If down−flow application is required, separately
order kit number 83M57 and install per kit’s instructions.
Also use metal or class I supply and return air plenums.
Use the installation instruction provided with the downflowkit.
IMPORTANTIf electric heat section with circuit breakers(ECB29/ECB31) is applied to down−flow and CBX27UHunits, the circuit breakers must be rotated 180° to the UPposition. See ECB29/ECB31 installation instructions formore details.
Brazing Connections
IMPORTANTTo prevent the build up of high levels of nitrogen whenpurging, be sure it is done in a well ventilated area. Purgelow pressure nitrogen (1 to 2 psig) through the refrigerantpiping during brazi