7
D. B. Raut & A. Bhattrai: Performance Analysis of Grid Connected Solar PV System Using Matlab/Simulink Rentech Symposium Compendium, Volume 3, September 2013 48 Performance Analysis of Grid Connected Solar PV System Using Matlab/Simulink Debendra Bahadur Raut* 1 and Ajay Bhattrai 2 1 Peaksun Engineering Solutions (PES) Pvt. Ltd., Kathmandu, Nepal 2 Institute of Engineering (IOE), Pulchowk Campus, Nepal AbstractSolar PV energy is one of the most promising renewable resources that use the abundant and free energy from the sun having clean, inexhaustible and environmentfriendly cyclic operations. However, the intermittent nature of the output power of PV systems reduces their reliability in providing continuous power to customers. Solar PV energy can be used mainly in standalone (off-grid) and grid connected system. A stand alone solar PV cannot provide a continuous supply of energy due to seasonal and periodic variations. Therefore, in order to satisfy consumer load demand, grid connected PV energy systems that combine solar energy and other conventional conversion units are becoming more popular in recent years. But, the fluctuations in the PV output power with climatic conditions might lead to undesirable performance of the electric network in grid connected system. The objective of this work to study the performance analysis of grid connected solar PV system. To accomplish this, the mathematical modeling of 1kWp grid connected system is carried out and the power profile is estimated using historical environmental data collected over a number of years at Kathmandu. Identified the possible operational problems that might arise in grid connected PV system and different strategies that can mitigate these problems are studied. In addition, the performance of the system is evaluated. 1 Index TermsStandalone, off-grid, grid penetration, performance ratio, Maximum Power Point Tracking (MPPT), Total Harmonic Distortion (THD), power factor (Pf). I. INTRODUCTION In gird connected PV system, the output from the PV system is connected to utility grid by means of PV grid tied inverter. Unlike off grid system, there is no need of batteries and charge controllers but the grid tied inverter should have special functioning capability such as anti-islanding, grid synchronization etc. Out of 67GWp PV installed globally, 80% is of the grid connection type. In Nepal, 680 kWp PV system delivering energy of 560kWh/day for water pumping and 1736kWh/day is injected to NEA grid is the first grid connection project in country. 1kWp grid connected PV system has been installed at CES/IOE to study the performance analysis of it and its effect on utility system. The fluctuating behavior of PV output with environmental condition may degrade the power quality of inverter output which may cause to degrade the performance of utility and the consumer electrical appliances? So, to study the performance of PV grid connected system, 1kWp PV system is modeled using MATLAB/Simulink and detail study has been carried out in this work. * Corresponding author: [email protected] II. SYSTEM DESIGN A. Modeling of solar cell and module The short-circuit current (I sc ) from a cell is nearly proportional to the illumination, while the open-circuit voltage (V oc ) may drop only 10%with an 80% drop in illumination [1]. The important result of these two effects is that the power of a PV cell decreases when light intensity decreases and/or temperature increases. The amount of power generated by a PV cell depends on the operating voltage of the PV cell array. It’s V-I and V-P characteristic curves specify a unique operating point at which maximum possible power is delivered. The point at which the PV operates at highest efficiency is called the maximum power point (MPP). The light generated current (I pv .) is the function of solar irradiance and environmental temperature. The little impact has also been shown by the wind speed. Irradiance has direct relation while working temperature has inverse relation to the I pv . Fig. 1: Single-diode model of the theoretical PV cell and equivalent circuit of a practical PV cell Practical PV device is composed of several connected PV cells and the observation of the characteristics at the terminals of the PV array requires the inclusion of additional parameters to the basic equations given by Eq.1 [2] Where, I pv and I 0 are the PV and saturation currents of module, V t = N s kT/q is the thermal voltage of the array with N s cells connected in series, R s = equivalent series resistance and R p = equivalent parallel resistance of the array of N s cells in series. The value of the diode constant ‘a’ may be arbitrarily chosen usually 1a 1.5[3]. If the array is composed of N p parallel connections of cells then the saturation currents is given by I 0 =I 0 , cell *N p . and module current is modified to I pv =I pv , cell *N p .

D. B. Raut & A. Bhattrai: Performance Analysis of Grid ... · D. B. Raut & A. Bhattrai: Performance Analysis of Grid Connected Solar PV System Using Matlab/Simulink Rentech Symposium

  • Upload
    trannga

  • View
    242

  • Download
    1

Embed Size (px)

Citation preview

D. B. Raut & A. Bhattrai: Performance Analysis of Grid Connected Solar PV System Using Matlab/Simulink

Rentech Symposium Compendium, Volume 3, September 2013 48

Performance Analysis of Grid Connected Solar PV System

Using Matlab/Simulink Debendra Bahadur Raut*

1 and Ajay Bhattrai

2

1Peaksun Engineering Solutions (PES) Pvt. Ltd., Kathmandu, Nepal

2Institute of Engineering (IOE), Pulchowk Campus, Nepal

Abstract— Solar PV energy is one of the most promising

renewable resources that use the abundant and free energy

from the sun having clean, inexhaustible and

environmentfriendly cyclic operations. However, the

intermittent nature of the output power of PV systems reduces

their reliability in providing continuous power to customers.

Solar PV energy can be used mainly in standalone (off-grid)

and grid connected system. A stand alone solar PV cannot

provide a continuous supply of energy due to seasonal and

periodic variations. Therefore, in order to satisfy consumer

load demand, grid connected PV energy systems that combine

solar energy and other conventional conversion units are

becoming more popular in recent years. But, the fluctuations in

the PV output power with climatic conditions might lead to

undesirable performance of the electric network in grid

connected system.

The objective of this work to study the performance

analysis of grid connected solar PV system. To accomplish this,

the mathematical modeling of 1kWp grid connected system is

carried out and the power profile is estimated using historical

environmental data collected over a number of years at

Kathmandu. Identified the possible operational problems that

might arise in grid connected PV system and different

strategies that can mitigate these problems are studied. In

addition, the performance of the system is evaluated.1

Index Terms— Standalone, off-grid, grid penetration,

performance ratio, Maximum Power Point Tracking (MPPT),

Total Harmonic Distortion (THD), power factor (Pf).

I. INTRODUCTION

In gird connected PV system, the output from the PV

system is connected to utility grid by means of PV grid tied

inverter. Unlike off grid system, there is no need of batteries

and charge controllers but the grid tied inverter should have

special functioning capability such as anti-islanding, grid

synchronization etc. Out of 67GWp PV installed globally,

80% is of the grid connection type. In Nepal, 680 kWp PV

system delivering energy of 560kWh/day for water pumping

and 1736kWh/day is injected to NEA grid is the first grid

connection project in country. 1kWp grid connected PV

system has been installed at CES/IOE to study the

performance analysis of it and its effect on utility system.

The fluctuating behavior of PV output with

environmental condition may degrade the power quality of

inverter output which may cause to degrade the performance

of utility and the consumer electrical appliances? So, to

study the performance of PV grid connected system, 1kWp

PV system is modeled using MATLAB/Simulink and detail

study has been carried out in this work.

* Corresponding author: [email protected]

II. SYSTEM DESIGN

A. Modeling of solar cell and module

The short-circuit current (Isc) from a cell is nearly

proportional to the illumination, while the open-circuit

voltage (Voc) may drop only 10%with an 80% drop in

illumination [1]. The important result of these two effects is

that the power of a PV cell decreases when light intensity

decreases and/or temperature increases. The amount of

power generated by a PV cell depends on the operating

voltage of the PV cell array. It’s V-I and V-P characteristic

curves specify a unique operating point at which maximum

possible power is delivered. The point at which the PV

operates at highest efficiency is called the maximum power

point (MPP). The light generated current (Ipv.) is the

function of solar irradiance and environmental temperature.

The little impact has also been shown by the wind speed.

Irradiance has direct relation while working temperature has

inverse relation to the Ipv.

Fig. 1: Single-diode model of the theoretical PV cell and

equivalent circuit of a practical PV cell

Practical PV device is composed of several connected

PV cells and the observation of the characteristics at the

terminals of the PV array requires the inclusion of additional

parameters to the basic equations given by Eq.1 [2]

Where,

Ipv and I0 are the PV and saturation currents of module,

Vt = NskT/q is the thermal voltage of the array with Ns

cells connected in series,

Rs = equivalent series resistance and

Rp= equivalent parallel resistance of the array of Ns cells

in series.

The value of the diode constant ‘a’ may be arbitrarily

chosen usually 1≤a ≤1.5[3]. If the array is composed of Np

parallel connections of cells then the saturation currents is

given by I0=I0,cell*Np. and module current is modified to

Ipv=Ipv,cell*Np.

D. B. Raut & A. Bhattrai: Performance Analysis of Grid Connected Solar PV System Using Matlab/Simulink

Rentech Symposium Compendium, Volume 3, September 2013 49

Fig. 2: Mathematical modeling of solar cell in Matlab/Simulink

The effect of solar irradiance and cell temperature on

light generated current of solar PV is given by the Eq. 2 as

follows [4]:

Where,

Ipv,n[A] = Light-generated current at the nominal

condition, Ampere

∆T [K] = T–Tn (T and Tn the actual and nominal

temperatures respectively), Kelvin

G [W/m2] = Irradiation on the device surface, and

Gn[W/m2]= Nominal irradiation.

Ki = Temperature coefficient of cell for the short circuit

current

And diode saturation current I0 also depends on nominal

open circuit voltage (Vocn) and temperature coefficient of

cell for the open circuit voltage (Kv) given by equation

below [5]:

This modification aims to match the open-circuit

voltages of the model with the experimental data for a very

large range of temperatures. The ambient temperature sets

the base temperature of the module and the irradiance

predominantly sets the temperature raise of the module,

which is about 0.028oC per W/m2. The research work

reported in [6] says that wind speed and ambient humidity

slightly influence the module temperature whereas the wind

direction influence is negligibly small. The mathematical

equation determined by the reduction and analysis work

performed on a long-term collected data and regression

analysis:

Eq.4 is used to analyze the effect of ambient temperature

and wind speed on the PV output. Also, the report says that

humidity coefficients for the modules range from 0.089oC to

D. B. Raut & A. Bhattrai: Performance Analysis of Grid Connected Solar PV System Using Matlab/Simulink

Rentech Symposium Compendium, Volume 3, September 2013 50

0.181oC per RH% and it has little or no influence on the

temperature of the modules [6]. The mathematical modeling

of PV cell has shown in Fig. 2.

Simulink model for cell temperature

Simulink model for module

Fig. 3: Mathematical modeling of solar PV in Matlab/Simulink

B. Modeling of MPPT system algorithms

Maximum Power Point Tracker (MPPT) is used to

operate the module at the peak power point so that the

maximum power can be delivered to the load under varying

temperature and irradiance conditions. A DC to DC

converter serves the purpose of transferring maximum

power from the solar PV module to the load by changing the

duty cycle of it and load impedance as seen by the source is

varied and matched at the point of the peak power with the

source so as to transfer the maximum power.

Among various algorithms, Perturb and Observe (P&O)

algorithm is used in this work for the MPP tracking. A slight

perturbation is introduced to the system, due to this

perturbation, the power of the module changes. If the power

increases due to the perturbation then the perturbation is

continued in that direction. After the peak power is reached

the power at the next instant decreases and hence after that

the perturbation reverses [7][8]. The Matlab/Simulink model

has shown in Fig. 4.

Fig. 4(b): Model for MPPT: Simulink model for PWM wave

generation

Fig. 4(a): Model for MPPT: Simulink model for P&O algorithm

D. B. Raut & A. Bhattrai: Performance Analysis of Grid Connected Solar PV System Using Matlab/Simulink

Rentech Symposium Compendium, Volume 3, September 2013 51

Fig. 5: Simulation of grid connected PV array with BOS (185Wp * 6 PV modules connected in series)

C. Requirements of grid connection system

Power quality, protection coordination and grid

synchronization are the major issues to be concern over the

grid connection of solar PV system. Harmonics, voltage

regulation, power factor, EMI and DC current injection are

the main power quality issues that may cause adverse effects

like additional heating, reduction of transmission system

efficiency, overheating of distribution transformers,

malfunctioning of electronic equipment etc. in gird

connected system if not properly addressed. According to

IEEE1547 standard, allowable current THD is 5% (Even

harmonics are limited to 25% of the odd harmonic limits), 2

% for voltage THD and 1% for individual voltage harmonics

in Distributive Resource (DR) connected to area Electric

Power System (EPS). DC current injection shall not be

greater than 0.5% of the full rated output current at the point

of DR connection as per IEEE standards.

The complete model for gird connection of 1kWp PV

system has shown in figure 5.

III. DATA COLLECTION

The historical data of inclined irradiance (W/m2)

collected over two years, in the interval of every five

minutes, reported by SWERA, are used to estimate the

profile of the output power of the PV system. The two year

average temperature reported by weather station Kathmandu

airport has been collected and calculated the average day

temperature to analyze the effect of temperature on solar PV

output. Also, the effect of wind speed on soar PV output has

been analyzed by using the historical value of ten year

average wind at speed above 50 meter from the surface of

ground at Kathmandu, reported by NASA data.

IV. SIMULATION RESULTS

A. Output from array

The IV and PV curve from array has shown in Fig. 7

under the time varying input of irradiance and ambient

temperature. The open circuit voltage of array was about

250V and short circuit current was 3.9A. It has found that

increase in irradiance caused array current to increase while

small reduction of array voltage but ambient temperature has

reverse relation unlike irradiance. At very low irradiance,

array voltage has dropped below the threshold voltage level

for the inverter resulting highly distorted waveform and it

needs to use undervoltage protection circuit for such cases.

Fig. 6: Meteorological data at Kathmandu valley

Fig. 7: IV and PV curve of array with RL load and time varying

input

It has found that the use of P&O MPPT algorithm

increased the array power output by 23%. Especially at low

irradiance, the MPPT system was more effective. As shown

in Fig. 9, initially it took few seconds to maintain the

operating point and the ripple voltage appeared due to the

D. B. Raut & A. Bhattrai: Performance Analysis of Grid Connected Solar PV System Using Matlab/Simulink

Rentech Symposium Compendium, Volume 3, September 2013 52

perturbance of the algorithms. Upon the use of small

perturbance, ripple was reduced but it took more time to

track the operating point.

B. Power quality

It has found that current THD is 21.35% and

fundamental or 1st harmonic component (50Hz) is

4.124Apeak (2.91Arms). The even harmonics are much less

than the odd harmonics and they have severe impacts on

power quality. Similarly, voltage signal contained 5.01% of

THD with fundamental components of 312.8 Vpeak

(221.18Vrms). The details of even and odd harmonics are

shown in Table I. Since the harmonics present in the inverter

output are higher than the IEEE 159 standard (below 5%),

harmonic filter is used for suppression of harmonics. In this

work, a passive LCL harmonic filter is used for the

harmonics compensation techniques.

Output current, voltage and power from PV array without MPPT

Output current, voltage and power from PV array without MPPT

Fig. 8: Array output profile with time

Fig. 9: Voltage output from boost converter with time

Fig. 10: Current and Voltage THD at inverter before LCL filtering

After employing harmonic compensation techniques, the

current THD is maintained at 4.98% with the fundamental

output of 4.048Apeak (2.86rms). The voltage THD is 0.12%

with fundamental component of 312.8Vpeak. The orders of

filtered harmonics are presented in Table I and II.

TABLE I

HARMONIC ORDERS AND MAGNITUDES AT INVERTER CURRENT

Even

harmonics %

h2 h4 h6 h8 h10 h12 h14 h16 h18 h20 DC

component 0.35 0.42 0.28 0.71 0.30 0.45 0.20 0.28 0.06 0.33

Odd

harmonics %

h3 h5 h7 h9 h11 h13 h15 h17 h19 h21 0.13%

8.14 11.42 5.05 3.96 1.35 1.37 0.99 0.71 0.93 0.36

TABLE II

HARMONIC ORDERS AND MAGNITUDES OF FILTERED CURRENT

Even

harmonics %

h2 h4 h6 h8 h10 h12 h14 h16 h18 h20 DC

component 0.22 0.02 0.06 0.04 0.01 0.02 0.01 0.00 0.02 0.02

Odd

harmonics %

h3 h5 h7 h9 h11 h13 h15 h17 h19 h21 0.13% 3.07 1.17 0.12 0.15 0.09 0.04 0.02 0.04 0.02 0.01

D. B. Raut & A. Bhattrai: Performance Analysis of Grid Connected Solar PV System Using Matlab/Simulink

Rentech Symposium Compendium, Volume 3, September 2013 53

Pf fluctuation at high solar irradiance

Pf fluctuation at intermediate solar irradiance

Fig. 11: Variation of power factor with irradiance

Ideally, the reactive power generated by the inverter

should be zero i.e. the power factor is unity. But, because of

the inductive and capacitive components used in the energy

conversion and transmission system power factor is

changed. Results show that the reactive power generated by

the inverter is increased with the decrease in irradiance i.e.

power factor decreased with decrease in irradiance.

C. Power outputs from the array and system efficiency

The system is simulated individually for the inputs of

meteorological data collected over 12 month. The array

energy was 1886.1 kWh/Year at STC but the array actually

produced 1699.62kWh/year out of which 1523.69 kWh/year

is injected to the grid and the performance ratio is 80.76%.

The least energy is generated in January and August

(4.09kWh/day) and total energy in this month is

126.66kWh/month. The highest energy is produced in

October with 5.68kWh/day and total of 176.2kWh/month.

The average inverter efficiency throughout the year ranged

from 87% to 93%. The average gird penetration throughout

the year varied from 95%, in June, to 99%, in February.

Similarly, the overall performance ratio is 78% to 84 %. A

thesis work done by A. Bhattrai 2012 shows that average

final yield is 2.31kWh/day; array yield is 2.64 kWh/day

under the average 4 hours of load shedding during day time

at Kathmandu. Grid penetration is the ratio of energy

injected to the grid to the energy available at inverter output

and performance ratio is the power at inverter output to the

energy fall to the PV array.

Fig. 12: Monthly energy generation from 1kWp PV system

throughout the year

Variation of current THD and power factor with irradiance

Variation of voltage THD with irradiance

Fig. 13: Effect of irradiance on power quality on inverter output

Inductive load decreased the power factor and to

compensate it, capacitive load should be added. But, the

power factor also varied with the irradiance in grid

connected solar PV. The variation of power factor with time

D. B. Raut & A. Bhattrai: Performance Analysis of Grid Connected Solar PV System Using Matlab/Simulink

Rentech Symposium Compendium, Volume 3, September 2013 54

at constant load and it has found that for most fraction of

day, the power factor is acceptable. Also, the current THD

became lowest at peak day but voltage THD is highest and it

slowly decreased on either side.

Active and reactive power variation at inverter output

Performance of PV system with irradiance

Fig. 14: Active and Reactive power vs. Irrad; PV performance vs.

Irrad.

V. CONCLUSION

Grid tied inverters convert DC power to AC power with

an efficiency of 90% or more most of the time. Inverters can

even work to some extent when irradiance levels up to

200W/m2, but performance starts to drop off dramatically

when irradiance levels falls below it.

The use of MPPT system is of great value to the array

output as it (P&O algorithm) optimizes the PV power output

by 23% than without the use of MPPT system. The

nonlinear devices used in the converter circuits are the great

source of harmonics in the PV grid connected system. The

harmonics generated in the PV power converting systems

greatly vary with the solar irradiance. The odd harmonics

have greater impacts on power quality than even harmonics

as they have higher magnitude. The current THD is more

sensitive on the fluctuation of solar irradiance than the

respective voltage THD. Current THD greatly decreases

with the increase in the solar irradiance while voltage THD

slightly increases with increase in solar irradiance. Power

factor varies linearly for values of solar irradiance lower

than 200 W/m2 and remains close to unity for higher solar

irradiance values. In addition, reactive power injection

increases at low irradiance.

ACKNOWLEDGEMENT

In the first place, I owe my deepest gratitude to my thesis

supervisor Prof. Jagan Nath Shrestha, PhD, IOE Pulchowk

Campus, for his continuous supervision, advice, and

guidance for this thesis work. The authors gratefully

acknowledge the contributions of everyone involved during

the planning and organizing the background for this project.

REFERENCES

[1] G. E. Ahmad, H. M. S. Hussein, and H. H. El-Ghetany, 2003,

“Theoretical analysis and experimental verification of PV modules”,

”Renewable Energy”, 28(8):1159–1168.

[2] H. S. Rauschenbach, Solar cell array design handbook, Van Nostrand

Reinhold, 1980.

[3] C. Carrero, J. Amador, and S. Arnaltes, 2007, “A single procedure for

helping PV designers to select silicon PV module and evaluate the

loss resistances”, Renewable Energy.

[4] E. I. Ortiz-Rivera and F. Z. Peng, 2005, “Analytical model for a PV

module using the electrical characteristics provided by the

manufacturer data sheet”, “In Proc. IEEE 36th Power Electronics

Specialists Conference, PESC”, p. 2087–2091, 2005.

[5] D. Sera, R. Teodorescu, and P. Rodriguez, 2007, “PV panel model

based on datasheet values”. “In Proc. IEEE International Symposium

on Industrial Electronics, ISIE”, p. 2392–2396.

[6] G.T. Mani, Liang Ji, Yingtang Tang, 2006, “Long –Term Monitoring

and Model Development for Energy Rating”, “Renewable Energy

Laboratory. NCPV and Solar Program Review Meeting“ NREL/CD-

520-33586 Pg. 936.

[7] Hua, Chihchiang, Jongrong Lin & Chihming Shen, 1998,

“Implementation of a DSP Controlled PV System with Peak Power

Tracking”, “IEEE Transactions on Industrial Electronics”, Vol. 45,

No. 1, page 99-107.

[8] Xuejun Liu and A.C.Lopes, 2004,“An Improved Perturbation and

Observe Maximum Power Point Tracking Algorithm for PV Arrays”,

“ IEEE PESC “, pp.2005-2010

BIOGRAPHIES

Mr. Debendra Bahadur Raut is the postgraduate

of Renewable Energy Engineering form Institute of

Engineering (IOE) Pulchowk Campus, Nepal after

graduated from Electronics and Communication

Engineering. He is the Managing Director of

Peaksun Engineering Solutions Pvt. Ltd. Kathmandu

Nepal. He is also involving in academics as Lecturer

at Acme Engineering College, Kathmandu Nepal.

Mr. Ajay Bhattarai has completed master’s degree

in Renewable Energy Engineering form Institute of

Engineering (IOE) Pulchowk Campus, Nepal after

graduated from Electronics and Communication

Engineering. He is currently involved as part time

Lecturer at Pulchowk Campus.