CVT-765

Capacitor Voltage Transformer Ratio Tester

USER’S MANUAL

Vanguard Instruments Company, Inc. 1520 S. Hellman Ave. Ontario, California 91761, USA

TEL: (909) 923-9390 FAX: (909) 923-9391

March 2017 Revision 1

Page 2: CVT-765 User's Manual Revision 1.3 - Welcome | Vanguard ... · PDF fileCVT-765 Capacitor Voltage Transformer Ratio Tester USER’S MANUAL Vanguard Instruments Company, Inc. 1520 S

CVT-765 USER’S MANUAL REV 1

i

SAFETY SUMMARY

FOLLOW EXACT OPERATING PROCEDURES Any deviation from procedures described in this User’s Manual may create one or more safety hazards, damage the CVT-765, damage the test transformer, or cause errors in the test results. Vanguard Instruments Company, Inc. assumes no liability for unsafe or improper use of the CVT-765.

SAFETY WARNINGS AND CAUTIONS The CVT-765 shall be used only by trained operators. All transformers under test shall be off-line and fully isolated. Always ground the CVT-765 to a substation ground before connecting the test cables to a transformer. Do not perform test procedures or service unless another person is also present who is capable of rendering aid and resuscitation.

DO NOT MODIFY TEST EQUIPMENT To avoid the risk of introducing additional or unknown hazards, do not install substitute parts or perform any unauthorized modification to any CVT-765 test unit. To ensure that all designed safety features are maintained, it is highly recommended that repairs be performed only by Vanguard Instruments Company factory personnel or by an authorized repair service provider. Unauthorized modifications can cause safety hazards and will void the manufacturer’s warranty.

WARNING Do not remove test leads during a test. Failure to heed this warning can result in electrical shock to personnel and damage to the equipment.

Always check the voltage setting of the unit before plugging in to power. Failure to heed this warning may damage the device.

Page 3: CVT-765 User's Manual Revision 1.3 - Welcome | Vanguard ... · PDF fileCVT-765 Capacitor Voltage Transformer Ratio Tester USER’S MANUAL Vanguard Instruments Company, Inc. 1520 S

REV 1 CVT-765 USER’S MANUAL

ii

TABLE OF CONTENTS CONVENTIONS USED IN THIS DOCUMENT ....................................................................... 1 1.0 INTRODUCTION .................................................................................................................... 2

1.1 General Description and Features ................................................................................... 2 1.2 Technical Specifications ................................................................................................... 3 1.3 Controls and Indicators .................................................................................................... 4

2.0 PRE-TEST SETUP ................................................................................................................... 6 2.1 Operating Voltages .......................................................................................................... 6 2.2 LCD Screen Contrast Control ............................................................................................ 6

3.0 OPERATING PROCEDURES ................................................................................................... 7 3.1 Connection Diagram ........................................................................................................ 7 3.2 Setting the Date and Time ............................................................................................... 8 3.3 Setting the Interface Language ........................................................................................ 9 3.4 Setting the Frequency (50 or 60 Hz) .............................................................................. 10 3.5 Performing Tests ............................................................................................................ 11

3.5.1. Entering Test Record Header Information ............................................................. 11 3.5.2. Performing a Transformer Test .............................................................................. 15

3.6 Working With Test Records ........................................................................................... 20 3.6.1. Viewing the Contents of the Working Memory ..................................................... 20 3.6.2. Saving Test Results to a Test Record ...................................................................... 21 3.6.3. Restoring a Test Record From Flash EEPROM ........................................................ 24 3.6.4. Restoring a Test Record From a USB Flash Drive ................................................... 28 3.6.5. Copying Test Records to a USB Flash Drive ............................................................ 31 3.6.6. Viewing the Test Record Directory ......................................................................... 34 3.6.7. Erasing Test Records from the Flash EEPROM ....................................................... 36 3.6.8. Erasing Test Records from a USB Flash Drive ......................................................... 40

LIST OF TABLES Table 1. CVT-765 Technical Specifications ...................................................................................... 3 Table 2. Functional Descriptions of CVT-765 Controls and Indicators ........................................... 5

LIST OF FIGURES Figure 1. CVT-765 Controls and Indicators ..................................................................................... 4 Figure 2. Typical CVT-765 Cable Connections ................................................................................. 7

Page 4: CVT-765 User's Manual Revision 1.3 - Welcome | Vanguard ... · PDF fileCVT-765 Capacitor Voltage Transformer Ratio Tester USER’S MANUAL Vanguard Instruments Company, Inc. 1520 S

This docu

• A key

• Menu

• CVT-7

• Whenrecta

• Warn

WA

• Impo

N

1. 2. 3. 4. 5.

1. 2. 3. 4. 5.

C

ument uses

y, switch, or

u names are

765 LCD scre

n instructionngle as show

ning message

ARNING

Wa

ortant notes

OTE

No

OPTION 1

OPTION 2

OPTION 3

OPTION 4

OPTION 5

OPTION 1

OPTION 2

OPTION 3

OPTION 4

OPTION 5

CONVENT

the followin

knob on the

e referenced

een output i

ns are providwn below (o

es are indica

arning mess

are indicate

te details

2

3

4

5

2

3

4

5

TIONS US

ng conventio

e CVT-765 is

as “MENU N

s shown as:

ded, the menption 3 shou

ated as:

sage

ed as:

SED IN TH

ons:

indicated as

NAME”

nu item thatuld be select

CVT-7

HIS DOCU

s [KEY], [S

t should be sted):

65 USER’S M

UMENT

SWITCH], [

selected is o

MANUAL R

[KNOB].

outlined with

REV 1

1

h a

Page 5: CVT-765 User's Manual Revision 1.3 - Welcome | Vanguard ... · PDF fileCVT-765 Capacitor Voltage Transformer Ratio Tester USER’S MANUAL Vanguard Instruments Company, Inc. 1520 S

REV 1 CVT-765 USER’S MANUAL

2

1.0 INTRODUCTION 1.1 General Description and Features The Vanguard CVT-765 is a microprocessor-based, single phase, automatic, transformer turns-ratio tester. This portable test unit is specifically designed to measure the turns-ratios of Capacitor Voltage Transformers (CVT’s).

The CVT-765 determines the transformer turns-ratio using the IEEE C57.12.90 measuring method. It uses a 7500Vac excitation voltage source to accurately measure the turns-ratio of Capacitor Voltage Transformers with a rating of up to 765KV. The transformer turns-ratio is determined by precisely measuring the voltages across the unloaded transformer windings.

The CVT-765 can measure the turns-ratios of Capacitor Voltage Transformers ranging from 75 to 15,000. The measured turns-ratio, winding polarity, and winding phase angle are displayed on the unit’s LCD screen.

A transformer’s nameplate voltages can also be entered, and the CVT-765 will display the turns-ratio percentage error by comparing the test results with the nameplate voltage values. This convenient feature eliminates any user-calculation errors when testing transformers.

User Interface The CVT-765 features a back-lit LCD screen (128 x 64 pixels) that is viewable in bright sunlight and low-light conditions. A rugged 16-key membrane keypad is used to enter test information and to operate the unit.

Test Record Storage The CVT-765 can store 128 records of 33 readings internally, and up to 999 test records on an external USB Flash drive. Test records can be recalled using the included Transformer Analysis PC Software.

Computer Interface A Windows® based (XP/Vista/7) Transformer Analysis Software is provided with each unit. Using this software, the user can retrieve test records (from the CVT-765’s memory or a USB Flash drive), analyze test results, and print test results on a desktop printer. Test results are automatically exported to PDF, EXCEL, and XML formats.

Operating Voltage The CVT-765 can be operated from 100-120Vac or 220-240Vac. The proper voltage can be set using the voltage selection switch on the front panel.

Page 6: CVT-765 User's Manual Revision 1.3 - Welcome | Vanguard ... · PDF fileCVT-765 Capacitor Voltage Transformer Ratio Tester USER’S MANUAL Vanguard Instruments Company, Inc. 1520 S

1.2 T

PHYS

MERATTUR

P

C

IN

EX

NO

Technical S

SICAL SPECIF

INPUEASUREMENT

TIO MEASURINRNS-RATIO AHASE ANGLE

TEST

COMPUTER INPC S

TERNAL TEST

XTERNAL TEST

ENVI

HUMIDALTITU

W

TE

The atemp

SpecificatioTable

TYPE PFICATIONS D

WUT POWER 1T METHOD ANG RANGE 7CCURACY 7

E READING 0POLARITY I

T VOLTAGE 7DISPLAY B

NTERFACE ROFTWARE WT RECORD STORAGE

1

T RECORD STORAGE

U

SAFETY DS

IRONMENT OS

DITY (MAX) 9UDE (MAX) 2

CABLES Oc

WARRANTY O

above specifperature of 2

ons e 1. CVT-765

Portable, automDimensions: 19Weight: 55 lbs. 100-120 Vac orANSI/IEEE C5775 - 15,000 (5 d75 - 5,000: ±0.20-360 degrees,n-Phase or Ou

7440Vac @ 50Back-lit LCD (1RS-232C Windows XP/V128 test record

Up to 999 test r

Designed to meStandards Operating: -10˚Storage: -30˚ C90% RH @ 40˚2000m (6562 ftOne 50 ft. H cacable One year on pa

ications are 25°C (77°F).

5 Technical S

matic, CVT, VT9.5" x 12" x 17"

(24.9 Kg) r 220-240 Vac 7.12.90 digit resolution)25%, 5,001 - 1 ±0.1 degree a

ut-of-Phase indma 28 x 64 pixels)

ista/7 Transfors. Each record

records on exte

eet IEC 61010A

to 50˚ C (15˚ tC to 70˚ C (-22˚

C (104˚ F) not) to fully safetyable, one 15 ft.

arts and labor

valid at nomSpecification

CVT-7

Specification

, PT turns-ratio" D (49.5 cm x

(selectable), 5

) 10,000: ±0.35%accuracy ication

), viewable in d

mer Analysis Sd contains 33 re

ernal USB Flas

A-1 and CAN/C

to +122˚ F); to +158˚ F) n-condensing

y specificationsX cable, one p

minal operatns may chan

65 USER’S M

s

o tester 30.5 cm x 43.2

0/60 hz

%, 10,001 - 15,0

direct sunlight a

Software (includeadings.

sh drive.

CSA C22.2 No.

s power cable, on

ting voltage ange without

MANUAL R

2 cm)

000: ±0.5%

and low light lev

ded with purch

. 1010.1-92

ne safety groun

and at a prior notice

REV 1

3

vels

ase)

nd

.

Page 7: CVT-765 User's Manual Revision 1.3 - Welcome | Vanguard ... · PDF fileCVT-765 Capacitor Voltage Transformer Ratio Tester USER’S MANUAL Vanguard Instruments Company, Inc. 1520 S

REV 1 CVT-765 USER’S MANUAL

4

1.3 Controls and Indicators The CVT-765 controls and indicators are shown in Figure 1. A leader line with an index number points to each control and indicator, which is cross-referenced to a functional description in the corresponding table. The purpose of the controls and indicators may seem obvious, but users should familiarize themselves with them before using the CVT-765. Accidental misuse of the controls will usually cause no serious harm. Users should also familiarize themselves with the safety summary information found on the front page of this User’s Manual.

Figure 1. CVT-765 Controls and Indicators

Page 8: CVT-765 User's Manual Revision 1.3 - Welcome | Vanguard ... · PDF fileCVT-765 Capacitor Voltage Transformer Ratio Tester USER’S MANUAL Vanguard Instruments Company, Inc. 1520 S

CVT-765 USER’S MANUAL REV 1

5

Table 2. Functional Descriptions of CVT-765 Controls and Indicators

Item Number Panel Markings Functional Description

1 GROUND Ground stud for connecting to sub-station ground 2 X X voltage connector 3 USB MEM USB Flash drive interface port 4 RS-232C RS-232C computer interface port

5 Back-lit LCD screen (128 x 64 pixels), viewable in direct light and low light conditions

6 VOLTAGE SELECTOR

Voltage selection switch

7 120/240 Vac, 4A, 50-60 Hz Fuse: 250Vac, 5A Fast Blow

Input power connector and fused power switch with third-wire safety ground

8 Rugged alpha-numeric keypad

9 7500VAC PRESENT

7500VAC hazard warning LED. This LED will be lit when a test is being performed to remind the user that 7500VAC is present.

10 H2 H2 voltage connector 11 H1 H1 voltage connector

12 “PUSH”

TO ARM

Spring-loaded push button switch. Press and hold to initiate a test.

Page 9: CVT-765 User's Manual Revision 1.3 - Welcome | Vanguard ... · PDF fileCVT-765 Capacitor Voltage Transformer Ratio Tester USER’S MANUAL Vanguard Instruments Company, Inc. 1520 S

REV 1 CVT-765 USER’S MANUAL

6

2.0 PRE-TEST SETUP 2.1 Operating Voltages The CVT-765 can be operated from 100-120 Vac or 220-240 Vac. The proper voltage can be set using the voltage selection switch on the front panel (see Figure 1).

2.2 LCD Screen Contrast Control To increase the LCD screen contrast, press and hold the [Contrast ∧] key for two seconds. Release the button when the desired contrast level has been reached.

To decrease the LCD screen contrast, press and hold the [Contrast ∨] key for two seconds. Release the button when the desired contrast level has been reached.

Page 10: CVT-765 User's Manual Revision 1.3 - Welcome | Vanguard ... · PDF fileCVT-765 Capacitor Voltage Transformer Ratio Tester USER’S MANUAL Vanguard Instruments Company, Inc. 1520 S

CVT-765 USER’S MANUAL REV 1

7

3.0 OPERATING PROCEDURES The CVT-765 should always be grounded with the provided ground cable before connecting H and X cables. The transformer bushings should also be grounded before connecting test leads to the transformer. This will prevent inducing any voltages into the CVT-765. All transformer bus connections must be removed, and the transformer must be isolated before performing any tests.

3.1 Connection Diagram

Figure 2. Typical CVT-765 Cable Connections

Page 11: CVT-765 User's Manual Revision 1.3 - Welcome | Vanguard ... · PDF fileCVT-765 Capacitor Voltage Transformer Ratio Tester USER’S MANUAL Vanguard Instruments Company, Inc. 1520 S

REV 1 CVT-765 USER’S MANUAL

8

3.2 Setting the Date and Time To set the date and time:

a. Start from the “START-UP” menu:

Press the [2] key (SETUP).

b. The following screen will be displayed:

Press the [5] key (SET TIME).

c. The following screen will be displayed:

Enter the date using the alpha-numeric keypad.

d. The following screen will be displayed:

Enter the current time using the alpha-numeric keypad. When the complete time has been entered, you will be immediately returned to the “START-UP” menu.

ENTER TIME

HH:MM:SS

ENTER DATE

MM-DD-YY

1. RECORD ID 2. SET 50/60 HZ 3. DISPLAY RECORD 4. SAVE/RESTORE RECORD 5. SET TIME 6. set language

1. TEST TRANSFORMER 2. SETUP

TIME: 15:16:17

DATE: 05/17/11

Page 12: CVT-765 User's Manual Revision 1.3 - Welcome | Vanguard ... · PDF fileCVT-765 Capacitor Voltage Transformer Ratio Tester USER’S MANUAL Vanguard Instruments Company, Inc. 1520 S

CVT-765 USER’S MANUAL REV 1

9

3.3 Setting the Interface Language Follow the steps below to set the interface language (English, Spanish, or Turkish):

a. Start from the “START-UP” menu:

Press the [2] key (SETUP)

b. The following screen will be displayed:

Press the [6] key (SET LANGUAGE)

c. The following screen will be displayed:

Select the preferred interface language by pressing the corresponding key on the keypad ([1], [2], or [3]). The interface language will be set and a confirmation screen will be displayed as shown below:

Press any key to return to the “START-UP” menu.

ENGLISH SET

1. ENGLISH 2. TURKISH 3. SPANISH

1. RECORD ID 2. SET 50/60 HZ 3. DISPLAY RECORD 4. SAVE/RESTORE RECORD 5. SET TIME 6. set language

1. TEST TRANSFORMER 2. SETUP

TIME: 15:16:17

DATE: 05/17/11

Page 13: CVT-765 User's Manual Revision 1.3 - Welcome | Vanguard ... · PDF fileCVT-765 Capacitor Voltage Transformer Ratio Tester USER’S MANUAL Vanguard Instruments Company, Inc. 1520 S

REV 1 CVT-765 USER’S MANUAL

10

3.4 Setting the Frequency (50 or 60 Hz) Follow the steps below to set the preferred frequency:

a. Start from the “START-UP” menu:

Press the [2] key (SETUP).

b. The following screen will be displayed:

Press the [2] key (SET 50/60 HZ).

c. The following screen will be displayed:

Select the preferred frequency by pressing the corresponding key on the keypad ([1] or [2]). The frequency will be set and a confirmation screen will be displayed as shown below:

Press any key to return to the “START-UP” menu.

60 hz set

1. 60 Hz 2. 50 hz

1. RECORD ID 2. SET 50/60 HZ 3. DISPLAY RECORD 4. SAVE/RESTORE RECORD 5. SET TIME 6. set language

1. TEST TRANSFORMER 2. SETUP

TIME: 15:16:17

DATE: 05/17/11

Page 14: CVT-765 User's Manual Revision 1.3 - Welcome | Vanguard ... · PDF fileCVT-765 Capacitor Voltage Transformer Ratio Tester USER’S MANUAL Vanguard Instruments Company, Inc. 1520 S

CVT-765 USER’S MANUAL REV 1

11

3.5 Performing Tests 3.5.1. Entering Test Record Header Information You can enter the test record header information before performing tests. The record header includes identifying information such as the company, station, circuit, manufacturer, etc. Once the header information has been set, it will apply to all subsequent test records. To enter the header information:

a. Start from the “START-UP” menu:

Press the [2] key (SETUP).

b. The following screen will be displayed:

Press the [1] key (RECORD ID).

c. The following screen will be displayed:

Type the company name using the alpha-numeric keypad.

When pressing a key, the corresponding number on the key will be displayed first. Pressing the key again will display the first letter on the key. Pressing the key again will display the second letter on the key. For example, to type the letter “A”, you must press the [2] key twice. To erase the character at the cursor position, press the [CLEAR] key. Press the [Contrast ∧] key to move to the next character. Press the [Contrast ∨]

COMPANY:

_

↑/↓ TO POSITION "ENTER" TO ACCEPT

1. RECORD ID 2. SET 50/60 HZ 3. DISPLAY RECORD 4. SAVE/RESTORE RECORD 5. SET TIME 6. set language

1. TEST TRANSFORMER 2. SETUP

TIME: 15:16:17

DATE: 05/17/11

Page 15: CVT-765 User's Manual Revision 1.3 - Welcome | Vanguard ... · PDF fileCVT-765 Capacitor Voltage Transformer Ratio Tester USER’S MANUAL Vanguard Instruments Company, Inc. 1520 S

REV 1 CVT-765 USER’S MANUAL

12

key to move to the previous character. Press the [ENTER] key when you are done typing the company name.

d. The following screen will be displayed:

Type the station name using the alpha-numeric keypad and then press the [ENTER] key.

e. The following screen will be displayed:

Type the circuit information using the alpha-numeric keypad and then press the [ENTER] key.

f. The following screen will be displayed:

Type the manufacturer name using the alpha-numeric keypad and then press the [ENTER] key.

MANUFACTURER:

_

↑/↓ TO POSITION "ENTER" TO ACCEPT

CIRCUIT:

_

↑/↓ TO POSITION "ENTER" TO ACCEPT

STATION:

_

↑/↓ TO POSITION "ENTER" TO ACCEPT

Page 16: CVT-765 User's Manual Revision 1.3 - Welcome | Vanguard ... · PDF fileCVT-765 Capacitor Voltage Transformer Ratio Tester USER’S MANUAL Vanguard Instruments Company, Inc. 1520 S

CVT-765 USER’S MANUAL REV 1

13

g. The following screen will be displayed:

Type the transformer’s model information using the alpha-numeric keypad and then press the [ENTER] key.

h. The following screen will be displayed:

Type the transformer’s serial number using the alpha-numeric keypad and then press the [ENTER] key.

i. The following screen will be displayed:

Type the transformer’s KVA rating using the alpha-numeric keypad and then press the [ENTER] key.

KVA RATING:

_

↑/↓ TO POSITION "ENTER" TO ACCEPT

SERIAL NUMBER:

_

↑/↓ TO POSITION "ENTER" TO ACCEPT

MODEL:

_

↑/↓ TO POSITION "ENTER" TO ACCEPT

Page 17: CVT-765 User's Manual Revision 1.3 - Welcome | Vanguard ... · PDF fileCVT-765 Capacitor Voltage Transformer Ratio Tester USER’S MANUAL Vanguard Instruments Company, Inc. 1520 S

REV 1 CVT-765 USER’S MANUAL

14

j. The following screen will be displayed:

Type the operator’s name using the alpha-numeric keypad and then press the [ENTER] key. All header information will be saved, and you will be returned to the “START-UP” menu.

OPERATOR:

_

↑/↓ TO POSITION "ENTER" TO ACCEPT

Page 18: CVT-765 User's Manual Revision 1.3 - Welcome | Vanguard ... · PDF fileCVT-765 Capacitor Voltage Transformer Ratio Tester USER’S MANUAL Vanguard Instruments Company, Inc. 1520 S

3.5.2. PFollow th

a. St

P

b. T

Se

c. T

Performinghe steps belo

tart from th

ress the [1]

he following

elect the win

he following

NOTE

If yoscre

Prethe

N

1

2

3

NAME PLA

1. YES 2. NO

TEST

1.X1-X3

3.Y1-Y3

5.Z1-Z3

1. TEST T2. SETUP

TIME: 1

DATE: 0

a Transfoow to test a

e “START-UP

key (TEST T

g screen will

nding by pre

g screen will

ou had enteeen will be d

ss the [3] ke previous te

AME PLATE

. YES

. NO

. USE PRE

ATE VOLTAG

T WINDING

2.X2-X

4.Y2-Y

6.Z2-Z

TRANSFORM

5:16:17

05/17/11

ormer Test transformer

P” menu:

TRANSFORM

be displaye

essing the co

be displaye

red name pdisplayed ins

ey if you woest performe

E VOLTAGE

EV DATA

GE?

G:

X3

Y3

Z3

MER

r:

ER).

d:

orresponding

d:

late voltagesstead of the

uld like to u

ed. Continue

E?

CVT-7

g numeric ke

s for a previoabove scree

se the namee to step c.

65 USER’S M

ey on the ke

ous test, theen:

e plate volta

MANUAL R

eypad.

e following

ge values fro

REV 1

15

om

Page 19: CVT-765 User's Manual Revision 1.3 - Welcome | Vanguard ... · PDF fileCVT-765 Capacitor Voltage Transformer Ratio Tester USER’S MANUAL Vanguard Instruments Company, Inc. 1520 S

REV 1 CVT-765 USER’S MANUAL

16

1. YES

Press the [1] key (YES) if you would like to enter the transformer name plate voltage values. The following screen will be displayed.

Type the H winding name plate voltage value using the numeric keypad. The screen will be updated as shown below:

Press the [ENTER] key. The screen will be updated as shown below:

Type the X winding name plate voltage value using the numeric keypad. The screen will be updated as shown below:

Press the [ENTER] key. Continue to step c.

2. NO

Press the [2] key (NO) if you do not want to enter the transformer name plate voltage values. Continue to step c.

NAME PLATE VOLTAGE:

H : X

2,400 : 240

NAME PLATE VOLTAGE:

H : X

2,400 : 0

NAME PLATE VOLTAGE:

H : X

2,400 :

NAME PLATE VOLTAGE:

H : X

0 :

Page 20: CVT-765 User's Manual Revision 1.3 - Welcome | Vanguard ... · PDF fileCVT-765 Capacitor Voltage Transformer Ratio Tester USER’S MANUAL Vanguard Instruments Company, Inc. 1520 S

d. T

P

e. T

Cb

Y

T“o

P

he following

ress and hol

he following

ontinue to he displayed

ou can now

The polarity out-of-phase

NOTE

The[(C

ress any key

RATIO

+10.004

PHASE =

test i

please

PRESS

SWIT

"STOP

g screen will

ld the [ARM

g screen will

hold down thon the LCD s

release the

is displayed e”. The value

e percentagealculated Ra

y to continue

O %

= 0.02°

n progres

e wait...

AND HOLD

CH TO TES

OR

P" TO ABO

be displaye

M] switch to

be displaye

he [ARM] swscreen when

[ARM] swit

as either a pe listed unde

e error (% Datio – Measu

e.

%DIFF

0.04

ss

ARM

ST

ORT

d:

initiate the

d while the

witch. Testinn testing has

tch.

plus sign (+) er “% DIFF”

IFF) is calculured Ratio) /

CVT-7

test.

test is being

ng will contis finished:

for “in-phasis the perce

lated as the / Calculated

65 USER’S M

g performed

nue, and the

se” or a minntage error.

absolute vaRatio)] x 100

MANUAL R

:

e test results

us sign (-) fo

lue of: 0

REV 1

17

s will

or

Page 21: CVT-765 User's Manual Revision 1.3 - Welcome | Vanguard ... · PDF fileCVT-765 Capacitor Voltage Transformer Ratio Tester USER’S MANUAL Vanguard Instruments Company, Inc. 1520 S

REV 1 C

18

f. T

P

g. T

P

CVT-765 US

he following

ress the [1]

he following

ress any key

NOTE

Themeresbe

PrewoDAtheThe

Pre

P

1

2

TE

KEEP THI

1. YES

2. NO

ER’S MANUA

g screen will

key (YES) to

g screen will

y to continue

e above screemory bufferstored from displayed in

ess the [1] korking memo

TA) to clear e current tese following s

ess any key t

TEST

PREVIOUS

1. APPEND

2. CLEAR

ST SAVED

S READING

AL

be displaye

o save the re

be displaye

e.

een will be dr. If a test waFlash EEPRO

nstead:

ey (APPENDory to the cu

any previoust results. screen will th

to continue.

T SAVED

DATA IN B

PREV. DA

PREV. DAT

G?

d:

eading.

d:

isplayed if tas previously

OM or from a

D PREV. DATA

rrent test reus data from

hen be displ

BUF

ATA

TA

here is currey performeda Flash drive

A) to appendesults, or pre the unit’s m

ayed:

ently no datad or a test ree, the follow

d the data iness the [2] kmemory buff

a in the unitecord was ing screen w

n the unit’s key (CLEAR Pfer and only

’s

will

PREV. save

Page 22: CVT-765 User's Manual Revision 1.3 - Welcome | Vanguard ... · PDF fileCVT-765 Capacitor Voltage Transformer Ratio Tester USER’S MANUAL Vanguard Instruments Company, Inc. 1520 S

h. T

P

i. T

P

j. T

T

P

he following

ress the [2]

he following

ress the [1]

he following

he following

NOTE

Theexi

ress any key

RECORD

HAS BEE

SAVING R

PLEASE W

SAVE THI

1. YES

2. NO

RUN ANOT

1. YES

2. NO

3. REPEA

g screen will

key (NO).

g screen will

key (YES) to

g screen will

g confirmatio

e unit will austing test re

y to return to

NUMBER 1

EN SAVED!

RECORD...

WAIT...

S RECORD?

THER TEST?

AT PREV. T

be displaye

be displaye

o save the te

be displaye

on screen w

utomaticallycords.

o the “START

?

?

TEST

d:

d:

est record to

d momenta

ill then be d

assign the r

T-UP” menu

CVT-7

o the unit’s F

rily:

isplayed:

record numb

u.

65 USER’S M

Flash EEPROM

ber and will

MANUAL R

M.

not over-wr

REV 1

19

rite

Page 23: CVT-765 User's Manual Revision 1.3 - Welcome | Vanguard ... · PDF fileCVT-765 Capacitor Voltage Transformer Ratio Tester USER’S MANUAL Vanguard Instruments Company, Inc. 1520 S

REV 1 CVT-765 USER’S MANUAL

20

3.6 Working With Test Records 3.6.1. Viewing the Contents of the Working Memory Whenever a test is performed or a test record is retrieved, the data is stored in the CVT-765’s working memory. You can view the test data using the steps below:

a. Start from the “START-UP” menu:

Press the [2] key (SETUP).

b. The following screen will be displayed:

Press the [3] key (DISPLAY RECORD).

c. The basic test record information will be displayed as shown:

d. Press the [Contrast ∨] key. The test record details will be displayed as shown below:

Press the [STOP] key to return to the “START-UP” menu.

1 SINGLE PHASE

7440 volts

RATIO %DIFF

10.004 0.04

SINGLE PHASE

Num Tests: 1

04/15/11 09:52:50

1. RECORD ID 2. SET 50/60 HZ 3. DISPLAY RECORD 4. SAVE/RESTORE RECORD 5. SET TIME 6. set language

1. TEST TRANSFORMER 2. SETUP

TIME: 15:16:17

DATE: 05/17/11

Page 24: CVT-765 User's Manual Revision 1.3 - Welcome | Vanguard ... · PDF fileCVT-765 Capacitor Voltage Transformer Ratio Tester USER’S MANUAL Vanguard Instruments Company, Inc. 1520 S

CVT-765 USER’S MANUAL REV 1

21

3.6.2. Saving Test Results to a Test Record After performing a test, the user is presented the option to save the test results to the unit’s Flash EEPROM or to a USB Flash Drive. If the test results are not saved immediately after performing a test, they will still remain in the working memory and can be saved later, as long as a new test has not been performed and the unit has not been turned off. Follow the steps below to save the test results from the working memory to a test record (the following procedure can also be used to re-save a restored test record to a new memory location or to a USB Flash Drive):

a. Perform a test or restore a test record to the working memory (see section 3.6.3 and 3.6.4), and then start from the “START-UP” menu:

Press the [2] key (SETUP).

b. The following screen will be displayed:

Press the [4] key (SAVE/RESTORE RECORD).

1. RECORD ID 2. SET 50/60 HZ 3. DISPLAY RECORD 4. SAVE/RESTORE RECORD 5. SET TIME 6. set language

1. TEST TRANSFORMER 2. SETUP

TIME: 15:16:17

DATE: 05/17/11

Page 25: CVT-765 User's Manual Revision 1.3 - Welcome | Vanguard ... · PDF fileCVT-765 Capacitor Voltage Transformer Ratio Tester USER’S MANUAL Vanguard Instruments Company, Inc. 1520 S

REV 1 C

22

c. T

P

IfIf

d. T

CVT-765 US

he following

NOTE

Opcon

ress the [2]

f a USB Flashf a USB Flashhe following

1. SAVE

Press EEPRO

2. SAVE

Press conne

Press

REC

THU

1. SAVE I2. SAVE T

1. RESTOR2. SAVE R3. RECORD4. ERASE 5. COPY t

ER’S MANUA

g screen will

tion 5 (COPYnnected to t

key (SAVE R

h drive is conh drive is NOg screen will

INTERNALLY

the [1] key OM. ContinuTO THUMB

the [2] key ected USB Fl

any key to r

C_001 SAVE

UMB DRIVE

INTERNALL

TO THUMB

RE RECORD

RECORD

D DIRECTO

RECORD

to THUMB

AL

be displaye

Y TO THUMBhe CVT-765.

RECORD).

nnected to tOT connecte

be displaye

Y

(SAVE INTERue to step e.DRIVE

(SAVE TO THash drive. Th

return to the

ED TO

.

LY

DRIVE

D

ORY

DRIVE

d:

B DRIVE) will.

the unit, coned to the uni

d:

RNALLY) to s.

HUMB DRIVEhe following

e “START-UP

l be listed on

ntinue to steit, continue

save the test

E) to save thg screen will

P” menu.

nly if a USB F

ep d. to step e.

t record to t

he test recorbe displayed

Flash drive is

he unit’s Fla

rd to the d:

s

ash

Page 26: CVT-765 User's Manual Revision 1.3 - Welcome | Vanguard ... · PDF fileCVT-765 Capacitor Voltage Transformer Ratio Tester USER’S MANUAL Vanguard Instruments Company, Inc. 1520 S

CVT-765 USER’S MANUAL REV 1

23

e. The following screen will be displayed:

Press any key to return to the “START-UP” menu.

RECORD NUMBER 5

HAS BEEN SAVED!

Page 27: CVT-765 User's Manual Revision 1.3 - Welcome | Vanguard ... · PDF fileCVT-765 Capacitor Voltage Transformer Ratio Tester USER’S MANUAL Vanguard Instruments Company, Inc. 1520 S

REV 1 C

24

3.6.3. RUse the smemory:

a. St

P

b. T

P

c. T

P

CVT-765 US

Restoring asteps below :

tart from th

ress the [2]

he following

ress the [4]

he following

NOTE

Opcon

ress the [1]

1. RESTOR2. SAVE R3. RECORD4. ERASE 5. COPY t

1. RECORD2. SET 503. DISPLA4. SAVE/R5. SET TI6. set la

1. TEST T2. SETUP

TIME: 1

DATE: 0

ER’S MANUA

a Test Recoto restore a

e “START-UP

key (SETUP

g screen will

key (SAVE/R

g screen will

tion 5 (COPYnnected to t

key (RESTO

RE RECORD

RECORD

D DIRECTO

RECORD

to THUMB

D ID

0/60 HZ

AY RECORD

RESTORE R

IME

anguage

TRANSFORM

5:16:17

05/17/11

AL

ord From Fa test record

P” menu:

).

be displaye

RESTORE RE

be displaye

Y TO THUMBhe CVT-765.

RE RECORD)

D

ORY

DRIVE

D

RECORD

MER

Flash EEPR from the CV

d:

ECORD).

d:

B DRIVE) will.

).

ROM VT-765’s Flas

l be listed on

sh EEPROM

nly if a USB F

to the work

Flash drive is

king

s

Page 28: CVT-765 User's Manual Revision 1.3 - Welcome | Vanguard ... · PDF fileCVT-765 Capacitor Voltage Transformer Ratio Tester USER’S MANUAL Vanguard Instruments Company, Inc. 1520 S

d. The following

NOTE

If yfoll

PreThe

Con

1. ENTER

Press you w

1.1.

1

2

1

2

REST

1.ENTER

2.SCROLL

g screen will

you have a Ulowing scree

ess the [1] ke following s

ntinue with

R RECORD N

the [1] key would like to

The followi

Type the rethe [ENTE

RESTO

NUM

RESTOR

1.ENTER RE

2.SCROLL

1.INTERNAL

2.THUMB D

ORE RECOR

RECORD NU

L TO SELEC

be displaye

USB Flash driven will be dis

ey (INTERNAscreen will b

the steps be

NUMBER

(ENTER RECrestore.

ng screen w

ecord numbeER] key.

ORE RECOR

MBER:

RE RECORD

ECORD NUM

TO SELECT

L STORAGE

RIVE

RD

UMBER

CT

d:

ve inserted splayed inste

AL STORAGE

be displayed:

elow.

CORD NUMB

will be display

er using the

RD

D

MBER

T

E

CVT-7

in the CVT-7ead of the a

E). :

ER) if you kn

yed:

alpha-nume

65 USER’S M

765’s “USB Mbove screen

now the reco

eric keypad a

MANUAL R

MEM” port, tn:

ord number

and then pre

REV 1

25

the

that

ess

Page 29: CVT-765 User's Manual Revision 1.3 - Welcome | Vanguard ... · PDF fileCVT-765 Capacitor Voltage Transformer Ratio Tester USER’S MANUAL Vanguard Instruments Company, Inc. 1520 S

REV 1 CVT-765 USER’S MANUAL

26

1.2. The following screen will be displayed:

Press the [1] key (YES) to display the test record.

1.3. The basic information about the restored test record will be displayed as shown:

Press the [Contrast ∨] key. The test record details will be displayed as shown:

Press the [STOP] key to return to the “START-UP” menu. The restored test record will remain loaded in the working memory.

2. SCROLL TO SELECT

Press the [2] key (SCROLL TO SELECT) to scroll through a directory of the stored test records.

2.1. The following screen will be displayed:

RECORDS DIRECTORY

"UP" TO SCROLL FWD

"DWN" TO SCROLL RVS

1 SINGLE PHASE

7440 volts

RATIO %DIFF

10.004 0.04

SINGLE PHASE

Num Tests: 1

04/15/11 09:52:50

RECORD RESTORED!

DISPLAY RECORD?

1.YES

2.NO

Page 30: CVT-765 User's Manual Revision 1.3 - Welcome | Vanguard ... · PDF fileCVT-765 Capacitor Voltage Transformer Ratio Tester USER’S MANUAL Vanguard Instruments Company, Inc. 1520 S

CVT-765 USER’S MANUAL REV 1

27

Press the [Contrast ∧] button or the [Contrast ∨] key to display the next or previous test record, respectively.

The basic test record information will be displayed as shown:

When you have located the test record that you would like to restored, press the [ENTER] key. Continue to step 1.2 on page 26.

#1 04/15/11 09:52

SINGLE PHASE

1 TESTS

Page 31: CVT-765 User's Manual Revision 1.3 - Welcome | Vanguard ... · PDF fileCVT-765 Capacitor Voltage Transformer Ratio Tester USER’S MANUAL Vanguard Instruments Company, Inc. 1520 S

REV 1 CVT-765 USER’S MANUAL

28

3.6.4. Restoring a Test Record From a USB Flash Drive Use the steps below to restore a test record from a USB Flash drive to the CVT-765’s working memory:

a. Make sure the USB Flash drive containing the test record(s) is inserted in the CVT-765’s USB Flash drive port (“USB MEM” port). Then start from the “START-UP” menu:

Press the [2] key (SETUP).

b. The following screen will be displayed:

Press the [4] key (SAVE/RESTORE RECORD).

c. The following screen will be displayed:

Press the [1] key (RESTORE RECORD).

1. RESTORE RECORD 2. SAVE RECORD 3. RECORD DIRECTORY 4. ERASE RECORD 5. COPY TO THUMB DRIVE

1. RECORD ID 2. SET 50/60 HZ 3. DISPLAY RECORD 4. SAVE/RESTORE RECORD 5. SET TIME 6. set language

1. TEST TRANSFORMER 2. SETUP

TIME: 15:16:17

DATE: 05/17/11

Page 32: CVT-765 User's Manual Revision 1.3 - Welcome | Vanguard ... · PDF fileCVT-765 Capacitor Voltage Transformer Ratio Tester USER’S MANUAL Vanguard Instruments Company, Inc. 1520 S

CVT-765 USER’S MANUAL REV 1

29

d. The following screen will be displayed:

Press the [2] key (THUMB DRIVE).

e. The following screen will be displayed:

Type the record number that you would like to restore using the alpha-numeric keypad and then press the [ENTER] key.

f. The test record will be restored to the unit’s working memory and the following screen will be displayed:

Press the [1] key (YES) to display the restored test record.

g. The basic information about the restored test record will be displayed as shown below:

SINGLE PHASE

Num Tests: 1

04/15/11 09:52:50

REC_000 restored!

DISPLAY RECORD?

1.YES

2.NO

RESTORE THUMB DRIVE

REC_

1.INTERNAL STORAGE

2.THUMB DRIVE

Page 33: CVT-765 User's Manual Revision 1.3 - Welcome | Vanguard ... · PDF fileCVT-765 Capacitor Voltage Transformer Ratio Tester USER’S MANUAL Vanguard Instruments Company, Inc. 1520 S

REV 1 CVT-765 USER’S MANUAL

30

Press the [Contrast ∨] key. The test record details will be displayed as shown below:

Press the [STOP] key to return to the “START-UP” menu. The restored test record will remain loaded in the working memory.

1 SINGLE PHASE

7440 volts

RATIO %DIFF

10.004 0.04

Page 34: CVT-765 User's Manual Revision 1.3 - Welcome | Vanguard ... · PDF fileCVT-765 Capacitor Voltage Transformer Ratio Tester USER’S MANUAL Vanguard Instruments Company, Inc. 1520 S

CVT-765 USER’S MANUAL REV 1

31

3.6.5. Copying Test Records to a USB Flash Drive Use the steps below to copy one or all test records from the unit’s Flash EEPROM to a connected USB Flash drive:

a. Make sure a USB Flash drive is connected to the unit’s “USB MEM” port, and then start from the “START-UP” menu:

Press the [2] key (SETUP).

b. The following screen will be displayed:

Press the [4] key (SAVE/RESTORE RECORD).

c. The following screen will be displayed:

Press the [5] key (COPY TO THUMB DRIVE).

1. RESTORE RECORD 2. SAVE RECORD 3. RECORD DIRECTORY 4. ERASE RECORD 5. COPY TO THUMB DRIVE

1. RECORD ID 2. SET 50/60 HZ 3. DISPLAY RECORD 4. SAVE/RESTORE RECORD 5. SET TIME 6. set language

1. TEST TRANSFORMER 2. SETUP

TIME: 15:16:17

DATE: 05/17/11

Page 35: CVT-765 User's Manual Revision 1.3 - Welcome | Vanguard ... · PDF fileCVT-765 Capacitor Voltage Transformer Ratio Tester USER’S MANUAL Vanguard Instruments Company, Inc. 1520 S

REV 1 CVT-765 USER’S MANUAL

32

d. The following screen will be displayed:

1. COPY SINGLE RECORD

Press the [1] key (COPY SINGLE RECORD) to copy a single test record from the CVT-765’s Flash EEPROM to the connected USB Flash drive. The following screen will be displayed:

Type the record number using the alpha-numeric keypad and then press the [ENTER] key. The test record will be copied to the USB Flash drive and the following screen will be displayed:

Press any key to return to the “START-UP” menu.

2. COPY ALL RECORDS

Press the [2] key (COPY ALL RECORDS) to copy all test records from the CVT-765’s Flash EEPROM to the connected USB Flash drive. All test records will be copied from the unit to the connected USB Flash drive. The following screen will be displayed when the process is finished:

REC_000 SAVED TO THUMB DRIVE

ENTER RECORD NUMBER

TO COPY TO FLASH DRV

NUMBER:

COPY REC TO THUMB DRV

1.COPY SINGLE RECORD

2.COPY ALL RECORDS

Page 36: CVT-765 User's Manual Revision 1.3 - Welcome | Vanguard ... · PDF fileCVT-765 Capacitor Voltage Transformer Ratio Tester USER’S MANUAL Vanguard Instruments Company, Inc. 1520 S

CVT-765 USER’S MANUAL REV 1

33

Press any key to return to the “START-UP” menu.

ALL RECORDS HAVE BEEN

TRANSFERRED TO THUMB

DRIVE!

Page 37: CVT-765 User's Manual Revision 1.3 - Welcome | Vanguard ... · PDF fileCVT-765 Capacitor Voltage Transformer Ratio Tester USER’S MANUAL Vanguard Instruments Company, Inc. 1520 S

REV 1 C

34

3.6.6. VUse the sFlash EEP

a. St

P

b. T

P

c. T

P

CVT-765 US

Viewing thesteps below PROM memo

tart from th

ress the [2]

he following

ress the [4]

he following

NOTE

Opcon

ress the [3]

1. RESTOR2. SAVE R3. RECORD4. ERASE 5. COPY T

1. RECORD2. SET 503. DISPLA4. SAVE/R5. SET TI6. set la

1. TEST T2. SETUP

TIME: 1

DATE: 0

ER’S MANUA

e Test Recoto browse t

ory:

e “START-UP

key (SETUP

g screen will

key (SAVE/R

g screen will

tion 5 (COPYnnected to t

key (RECOR

RE RECORD

RECORD

D DIRECTO

RECORD

TO THUMB

D ID

0/60 HZ

AY RECORD

RESTORE R

IME

anguage

TRANSFORM

5:16:17

05/17/11

AL

ord Directohrough a dir

P” menu:

)

be displaye

RESTORE RE

be displaye

Y TO THUMBhe unit.

RD DIRECTOR

D

ORY

DRIVE

D

RECORD

MER

ory rectory of th

d:

ECORD).

d:

B DRIVE) is li

RY)

he test recor

sted only if

rds stored in

a USB Flash

the CVT-76

drive is

5’s

Page 38: CVT-765 User's Manual Revision 1.3 - Welcome | Vanguard ... · PDF fileCVT-765 Capacitor Voltage Transformer Ratio Tester USER’S MANUAL Vanguard Instruments Company, Inc. 1520 S

CVT-765 USER’S MANUAL REV 1

35

d. The following screen will be displayed:

Press the [Contrast ∧] or [Contrast ∨] key to scroll through the test record directory. The test record header will be displayed as shown:

You can continue to scroll through the record directory by pressing the [Contrast ∧] and [Contrast ∨] keys. Press the [STOP] key to return to the “START-UP” menu.

SINGLE PHASE

Num Tests: 1

04/15/11 09:52:50

RECORDS DIRECTORY

"UP" TO SCROLL FWD

"DWN" TO SCROLL RVS

Page 39: CVT-765 User's Manual Revision 1.3 - Welcome | Vanguard ... · PDF fileCVT-765 Capacitor Voltage Transformer Ratio Tester USER’S MANUAL Vanguard Instruments Company, Inc. 1520 S

REV 1 CVT-765 USER’S MANUAL

36

3.6.7. Erasing Test Records from the Flash EEPROM Follow the steps below to erase test records from the Flash EEPROM:

a. Start from the “START-UP” menu:

Press the [2] key (SETUP).

b. The following screen will be displayed:

Press the [4] key (SAVE/RESTORE RECORD).

c. The following screen will be displayed:

Press the [4] key (ERASE RECORD).

1. RESTORE RECORD 2. SAVE RECORD 3. RECORD DIRECTORY 4. ERASE RECORD 5. COPY TO THUMB DRIVE

1. RECORD ID 2. SET 50/60 HZ 3. DISPLAY RECORD 4. SAVE/RESTORE RECORD 5. SET TIME 6. set language

1. TEST TRANSFORMER 2. SETUP

TIME: 15:16:17

DATE: 05/17/11

Page 40: CVT-765 User's Manual Revision 1.3 - Welcome | Vanguard ... · PDF fileCVT-765 Capacitor Voltage Transformer Ratio Tester USER’S MANUAL Vanguard Instruments Company, Inc. 1520 S

d. T

1

he following

NOTE

If yfoll

PreThe

Con

. ERASE SIN

Press the internal F

NOTE

Yt

ERA

NUM

1

2

1

2

ERA

1.ERASE

2.ERASE

"STO

g screen will

you have a Ulowing scree

ess the [1] ke following s

ntinue with

NGLE REC.

[1] key (ERAFlash EEPROM

You can cancthe [STOP]

ASE RECOR

MBER:

ERASE

1.ERASE S

2.ERASE A

"STOP

1.ERASE IN

2.ERASE T

SE RECORD

SINGLE RE

ALL RECOR

P" TO EXI

be displaye

USB Flash driven will be dis

ey (ERASE INscreen will b

the steps be

ASE SINGLE M. The follow

cel the proce] key.

RD

E RECORD

INGLE REC

LL RECORD

" TO EXIT

NTERNAL R

HUMB DRV

D

EC.

RDS

IT

d:

ve inserted splayed inste

NTERNAL REbe displayed:

elow.

REC.) to erawing screen

ess and retu

C.

DS

T

REC

REC

CVT-7

in the CVT-7ead of the a

EC). :

se a single te will be disp

urn to the “S

65 USER’S M

765’s “USB Mbove screen

est record frplayed:

TART-UP” m

MANUAL R

MEM” port, tn:

rom the unit

menu by pres

REV 1

37

the

t’s

ssing

Page 41: CVT-765 User's Manual Revision 1.3 - Welcome | Vanguard ... · PDF fileCVT-765 Capacitor Voltage Transformer Ratio Tester USER’S MANUAL Vanguard Instruments Company, Inc. 1520 S

REV 1 CVT-765 USER’S MANUAL

38

Type the record number that you would like to erase using the alpha-numeric keypad and then press the [ENTER] key. If you do not know the test record number, you can first view the test record directory using the instructions in section 3.6.6.

The following screen will be displayed while the record is being erased:

The following screen will be displayed when the test record has been completely erased:

Press any key to continue. You will be returned to the beginning of step d.

2. ERASE ALL RECORDS

Press the [2] key (ERASE ALL RECORDS) to erase all the test records from the unit’s internal Flash EEPROM. The following warning screen will be displayed:

You can press the [STOP] key to cancel the process and return to the “START-UP” menu.

Press the [ENTER] key to proceed with deleting all the test records from the unit’s Flash EEPROM. The following screen will be displayed during the erasure process:

ERASE ALL RECORDS!

ARE YOU SURE?

"ENTER" To CONTINUE.

RECORD NUMBER 8

ERASED!

ERASing record

PLEASE WAIT...

Page 42: CVT-765 User's Manual Revision 1.3 - Welcome | Vanguard ... · PDF fileCVT-765 Capacitor Voltage Transformer Ratio Tester USER’S MANUAL Vanguard Instruments Company, Inc. 1520 S

CVT-765 USER’S MANUAL REV 1

39

The following screen will be displayed when all test records have been completely erased:

Press any key to return to the “START-UP” menu.

RECORDS ERASED!

ERASing recordS

PLEASE WAIT...

Page 43: CVT-765 User's Manual Revision 1.3 - Welcome | Vanguard ... · PDF fileCVT-765 Capacitor Voltage Transformer Ratio Tester USER’S MANUAL Vanguard Instruments Company, Inc. 1520 S

REV 1 CVT-765 USER’S MANUAL

40

3.6.8. Erasing Test Records from a USB Flash Drive Follow the steps below to erase test records from a USB Flash drive:

a. Make sure a USB Flash drive is connected to the unit’s “USB MEM” port, and then start from the “START-UP” menu:

Press the [2] key (SETUP).

b. The following screen will be displayed:

Press the [4] key (SAVE/RESTORE RECORD).

c. The following screen will be displayed:

Press the [4] key (ERASE RECORD).

1. RESTORE RECORD 2. SAVE RECORD 3. RECORD DIRECTORY 4. ERASE RECORD 5. COPY TO THUMB DRIVE

1. RECORD ID 2. SET 50/60 HZ 3. DISPLAY RECORD 4. SAVE/RESTORE RECORD 5. SET TIME 6. set language

1. TEST TRANSFORMER 2. SETUP

TIME: 15:16:17

DATE: 05/17/11

Page 44: CVT-765 User's Manual Revision 1.3 - Welcome | Vanguard ... · PDF fileCVT-765 Capacitor Voltage Transformer Ratio Tester USER’S MANUAL Vanguard Instruments Company, Inc. 1520 S

CVT-765 USER’S MANUAL REV 1

41

d. The following screen will be displayed:

Press the [2] key (ERASE THUMB DRV REC).

e. The following screen will be displayed:

1. ERASE SINGLE REC.

Press the [1] key (ERASE SINGLE REC.) to erase a single test record from the connected USB Flash drive. The following screen will be displayed:

Type the record number that you would like to erase using the alpha-numeric keypad and then press the [ENTER] key. The test record will be erased from the USB Flash drive and the following screen will be displayed:

Press any key to continue. You will be returned to the beginning of step e. Press the [STOP] key to return to the “START-UP” menu.

THUMB DRIVE RE000

ERASED!

ERASE THUMB DRIVE

REC_

ERASE RECORD

1.ERASE SINGLE REC.

2.ERASE ALL RECORDS

"STOP" TO EXIT

1.ERASE INTERNAL REC

2.ERASE THUMB DRV REC

Page 45: CVT-765 User's Manual Revision 1.3 - Welcome | Vanguard ... · PDF fileCVT-765 Capacitor Voltage Transformer Ratio Tester USER’S MANUAL Vanguard Instruments Company, Inc. 1520 S

REV 1 CVT-765 USER’S MANUAL

42

2. ERASE ALL RECORDS

Press the [2] key (ERASE ALL RECORDS) to delete all test records from the connected USB Flash drive. The following warning screen will be displayed:

Press the [STOP] key if you do not want to erase all the test records. You will be returned to the “START-UP” menu.

Press the [ENTER] key to proceed with deleting all the test records from the connected USB Flash drive. The following screen will be displayed when all the records have been erased:

Press any key to return to the “START-UP” menu.

all thumb drive

records erased!

ERASE ALL THUMB DRIVE

RECORDS!

ARE YOU SURE?

"ENTER" TO CONTINUE.

Page 46: CVT-765 User's Manual Revision 1.3 - Welcome | Vanguard ... · PDF fileCVT-765 Capacitor Voltage Transformer Ratio Tester USER’S MANUAL Vanguard Instruments Company, Inc. 1520 S

1520 S. Hellman Ave • Ontario, CA 91761 • USA

Phone: 909-923-9390 • Fax: 909-923-9391 www.vanguard-instruments.com

Copyright © 2017 by Vanguard Instruments Company, Inc.

CVT-765 User’s Manual • Revision 1.3 • March 31, 2017 • TA