October 1998
CAT.73.01.T.E
Cutler-Hammer B-1Type CH LoadcentersIndex
Selection Chart . . . . . . . . . . . . . . . . . . .B-2
Catalog Numbering System. . . . . . . . .B-4
Applications and Warranties . . . . . . . .B-5
1-Phase Main Circuit Breakers Loadcenters . . . . . . . . . . . . . . . . . . . .B-6
1-Phase High Interrupting Rated MainCircuit Breaker Loadcenters . . . . . . .B-7
1-Phase Main Lug . . . . . . . . . . . . B-8 – B-9
3-Phase Main Circuit Breaker Loadcenters . . . . . . . . . . . . . . . . . . .B-10
3-Phase Main Lug . . . . . . . . . . . . . . . .B-11
Convertible, Base Unit and Main Devices . . . . . . . . . . . . . . . . . .B-12
1- and 3-Phase Circuit Breaker Unit Enclosure . . . . . . . . . . . . . . . . .B-13
Type CH Power Centers . . . . . . . . . . .B-14
Accessories . . . . . . . . . . . . . . . B-15 – B-16
Decorator Cover Accessory . . . . . . . .B-17
Surge Protection . . . . . . . . . . . . . . . . .B-18
Plug-On Circuit Breakers . . . . B-19 – B-20
Plug-On Ground Fault Circuit Breakers . . . . . . . . . . . . . . . . . . . . . .B-21
Plug-On Circuit Breakers . . . . . . . . . .B-22
Special Applications Plug-On Circuit Breakers . . . . . . . . . . . . . . . .B-23
Special Application Plug-On CHPCircuit Breakers . . . . . . . . . . B-24 – B-25
Replacement for Square D Type QO Breakers . . . . . . . . . . . . . .B-26
Circuit Breakers Accessories . . . . . . .B-27
Box Sizes . . . . . . . . . . . . . . . . . . . . . . .B-28
Knockouts . . . . . . . . . . . . . . . . B-29 – B-30
Typical Specifications. . . . . . . B-31 – B-32
Page Page
CAT.73.01.T.E
Cutler-HammerB-2October 1998
Type CH LoadcentersSelection Chart
Loadcenter Selection Chart
Service ■ Single-phase, three-wire, 120/240V AC.■ Three-phase, three-wire, 240V corner grounded
delta (see accessories).
■ Three-phase, four-wire, 208Y/120V AC.■ Three-phase, three-wire, 240V AC delta.
Short Circuit Current Rating ■ 10,000 AIC: All single- and three-phase loadcenters 40 through 400 amperes 2 to 42 circuits, except when series ratings are applied.
■ 25,000 AIC: All convertible and factory installed single-phase loadcenters rated 150 through 225 amperes using type CSR main breakers.
■ 42,000 and 100,000 are available on some styles: single-phase and three-phase.
Main Breaker/Main LugLoadcenters
Single-Phase
■ Main Breaker: 100, 125, 150, 200, 225, 400 amperes.■ Main Lugs: 40, 70, 125, 150, 200, 225, 400 amperes.
Three-Phase
■ Main Breaker: 150, 200, 225, 300, 400 amperes.■ Main Lugs: 125, 150, 200, 225, 400 amperes.
Convertible Loadcenters ■ Main Breaker or Main Lugs: single-phase up to 225 amperes.
Branch Breakers ■ Type CH: 10 to 150 amperes.One-, two- and three-pole. Two-position tripbreakers. Selected amperages available in,shunt trip, HACR and switching duty.
■ Type CH-HID: 15 to 30 amperes.One-, two- and three-poles.
■ Type CH-PSD: Remotely controlled circuit breaker.Available one-, one and a half-, two-pole.15 to 40 amperes.
■ Type CH-AFCI arc fault circuit interrupter.■ Type CHP: 10 to 125 amperes.
One-, two- and three-pole. Three-positioncommercial trip. Selected amperages available in HACR switching duty.
■ Type CHP-HID: 15-30 amperes.One-, two- and three-pole.
■ Type CH-GFCI: 15-60 amperes.One- and two-pole ground fault breakers
■ Type CHP GFCI: 15-30 amperes.One-pole ground fault breakers.
Enclosures ■ NEMA Type 1 indoor.■ NEMA Type 3R outdoor.
Meets or exceeds UL requirements for indoor oroutdoor applications.
Loadcenter and Breaker Accessories ■ Branch Circuit BreakerAuxiliary components.Hold down kits.Handle ties.Lockoffs.Lockdogs.
■ Complete Line of Ground Bar Kits5, 10, 14, and 21 circuit, some with additional #2/0 lugs. Each terminal will accommodate: (3) #14-#10 Cu/Al or (1) #14-#4 Cu/Al
■ Sub-feed Lugs125, 150 amperes – two- and three-pole.
■ Shunt Trips
■ Surge ProtectionSingle-phase whole home surge protector.Single-phase plug-on surge protector.Single-phase bottle type surge protector.Three-phase bottle type surge protector.Universal Rainproof Conduit Hubs
■ Group One: 3/4, 1, 1-1/4, 1-1/2, 2 inches(19.6, 25.4, 31.8, 38.1, 50.8 mm)
■ Group Two: 2, 2-1/2, 3 inches(50.8, 63.5, 76.2 mm)
■ Adapter plate.
Bussing Copper Bus is a standard feature with tin-plated copper branch fingers.
October 1998
CAT.73.01.T.E
Cutler-Hammer B-3Type CH LoadcentersProduct Styles
Single-Phase Main Circuit Breaker –NEMA 1 Enclosure
Three-Phase Main Circuit Breaker –NEMA 3R Enclosure
Single-Phase Main Circuit Breaker – Bottom Feed – NEMA 1 Enclosure
Cutler-Hammer Type CH Convertible Family Advanced Power Center Separately Packaged Covers
Cutler-Hammer Type CH Breaker Family
CAT.73.01.T.E
Cutler-HammerB-4October 1998
Type CH LoadcentersLoadcenter Features – Catalog Numbering System
Extra 1.5-inch Knockoutfor Bundling
Provides for easier installation,less installation time.Top or Bottom Feed
■ Straight-in wiring saves labor and material.
■ Only one panel for eitherapplication – no modifications necessary.
Commercial Grade Main Breaker
■ 25 kAIC series rated main breaker in 150 and 200ampere loadcenters.
■ 42 and 100 kAIC series ratingsavailable.
Steel Backpan
■ Provides positive, reliable breaker mounting.
■ One-piece designed for stability.
Copper Bus
Provides superior conductivitythroughout the entire product line.
Copper Bus Fingers
Tin-plated for longer servicelife, the best in the industry.
Dry Wall Markingon Enclosure
Indicates proper mountingdepth for flush applications.
Single Keyhole Mounting
Just one keyhole at top andbottom for easier mounting and leveling.
Unique Sandalwood Finish
Immediately recognizable,esthetically appealing, scratch resistant powder coating.
Flexible Neutral Design (For styles as indicated)
■ Factory bonded for service entrance applications provid-ing a split neutral.
■ Bonding strap is easily removable for sub-panel applications providing a ground and neutral.
■ Ample additional 2/0 lugs provided; no kits necessary.
Separately Packaged Covers
■ Full line of “true” surface and combination covers.
■ Built-in flush leveling feature■ Choice of circuit identification
by breakers or circuit directory
Improved Endwall Knockouts
Larger KOs are balanced to enhance installed appearance and to ease use of existingwiring.
New Convertible StylesAvailable
■ Uses field installable main breaker or main lug kits.
■ Flexible inventory – same breaker is used in loadcenter and circuit breaker enclosures.
C H 1 4 __ __ L 3 1 0 0 B F
Type CH3/4 inchBranchCircuitBreakers
Blank= Single-Phase
3 = Three-Phase
100 Amp125150200225 B
CDEGJKLR = Outdoor
(No Cover)
F = SubfeedLugsIncluded
Blank = NoSubfeedLugs
LC TypeNumberof Circuits
MainDevice
BusAmps
BoxSize OptionsPhases
Selection 8 Circuits1214161820222428303242
F = CombinationFlush/Surface
S = Surface
C H 8 B F
TypeCH
LoadcenterCover Series
Box Size(Indicated in LoadcenterCatalog Number)
Catalog Numbering System
(Loadcenters 100-225 amperes and 12-42 circuits)
Catalog Numbering System
(Indoor covers to be ordered separately)
L = Main Lug OnlyB = Main BreakerN = ConvertibleH = High AIC Main Breaker
Note: All combinations are not valid,refer to the catalog section.
Twins14/2016/2418/2432/42
October 1998
CAT.73.01.T.E
Cutler-Hammer B-5Type CH LoadcentersApplications and Warranties
Application Information
Loadcenter Construction
CH loadcenters feature solid copperbus and branch fingers in all interiors.Fingers are tin-plated and rated 140 amperes throughout the CH line. There-fore, the sum of the handle ratings con-nected to any one stab is limited to 140 amperes maximum. NEMA 1 boxes are manufactured from cold rolled 16 gauge sheet steel. Raintight boxes are manu-factured from G60 galvanized steel.All boxes and trims are finished usingan electrostatic powder coat, bakedurethane paint process.
UL Listings
All Cutler-Hammer-type CH loadcenters are listed under UL file E8741.
Neutrals
Cutler-Hammer-type CH loadcentersfeature two types of neutrals:
Factory Bonded Split Neutrals –feature a twin neutral (mounted on both sides of the interior assembly) with a cross bus connecting them that is bonded at the factory. For sub-feed applications, the bonding strap can be removed, providing a separate neutral and ground bar. In a service entranceapplication, where the neutral is bonded, unused neutral connections may be used for the termination of equipment grounds.
Insulated/Bondable Single Neutral – When a panel is supplied with a single neutral, it arrives from the factory in an “unbonded” state. All that is required to bond the neutral is to loosen the bond-ing screw and the neutral screw directly beside it, insert the bonding strap into the neutral bar, and re-tighten bothconnections. The single neutral can be moved by the contractor to the other side of the panel, if desired. In a service entrance application, where the neutral is bonded, unused neutral connections may be used for the termination of equipment grounds.
Grounds
Factory Bonded Split NeutralPanels – For service entrance applica-tions, the split neutral doubles as botha neutral and ground. When using the panel as a sub-feed, the bonding strap should be removed, and the bonding screw should be reinstalled, therefore providing a bonded ground and an iso-lated neutral.
Insulated/Bondable Single NeutralPanels – Main lug panels (12 circuit and above) are supplied with a separateneutral and ground bar. Main breaker panels, convertible outdoor panels and panels under 12 circuit are supplied with a neutral bar only. The ground bar must be ordered separately.
Neutral and Ground Terminals
The standard terminals on groundsand neutrals are rated to accept(3) – #14-#10 Cu/Al or (1) – #14-4 wires. For larger cables, add-on neutral lugs may be ordered from the accessories on page B-12.
Bottom-Fed Loadcenters
When the power cable is brought into the loadcenter from below the panel; then the main lug panels, and single-phase, 225 ampere and below, load-centers can be rotated 180 degrees to allow straight-in wiring of power cables to the main terminals. Because the CSR main circuit breaker handle operates horizontally, the orientation of the main circuit breaker handle is consistent with the requirements of NEC Article 240-81.
Gutter Splicing
Loadcenters are not UL listed as wiring troughs. Therefore, gutter splicing of riser cables to tap off to the main device is not permitted.
Fire Rating
Due to the numerous openings in both loadcenter boxes and trims, they should not be mounted in firewalls. There isno approval method for sealing the enclosures for this application.
➀ See Cutler-Hammer Publication Number SA-365 for complete details.
Application Notes and Extended Warranty Highlights
Date Code
The date of manufacture of each load-center is printed on the outside of the carton as well as inside the loadcenter. On the carton, the date code is printed on the end carton label. In the load-center, the date code is located on the small white label located on the right side wall (with the main device on top).
The date code is in the following for-mat: F # # # =. The “F” is the numeric code for the Lincoln, IL plant, and the three numbers are the year and week of manufacture e.g., 823. The “=” sign at the end signifies the decade of the 1990s. Therefore, the date code F823= would indicate that the product was manufac-tured in the 23rd week of 1998. The 1980s are represented by a “+” sign at the end of the code.
Surge Protectors
CHSA – the CHSA is a plug-on surgeprotector that provides protection for the AC power lines only. This device uses indicating lights to signal the need for replacement.
CHSA01 (single-phase) and CHSA03 (three-phase) – these two surge protectors are hard wired to a 15 ampere circuit breaker and provides protection for the AC power lines only. These devices will trip the circuit breaker tosignal the need for replacement.
CHSPCH – the CHSPCH is hard wired to a 2-pole 15 ampere circuit breaker and with proper telephone and coaxial cable connection provides protection for the AC power, telephone and coaxial cable lines. This device uses indicating lights to indicate the need for replacement.
Extended Residential WarrantyHighlights➀
■ Lifetime feeder breaker warranty■ 15-year loadcenter warranty■ Upgradable to 20 years if a Cutler-
Hammer surge protector is installedin the loadcenter.
■ $100,000 limited warranty on Cutler-Hammer high AIC ratedloadcenter.
CAT.73.01.T.E
Cutler-HammerB-6October 1998
MainBreakerType
MainAmpereRating
MaximumNumber3/4-inch (25.4 mm)
EnclosureType
Commercial➀➂LoadcenterCatalog Number
List Price Loadcenter CoverCatalog Number
List Price BoxSize➃
Wire Size RangeCu/Al60°C or 75°Cfor Main Breaker
Space Poles Flush Surface
LD10 kAIC
300 42 42 Indoor CH42PM300 $3495.00 CH7PMF➉ CH7PMS $387.00 PM (2) 400-500 kcmil
400 42 42 Indoor CH42PM400 3495.00 CH7PMF➉ CH7PMS 387.00 PM (2) 400-500 kcmil
1-Phase 3-Wire – 120/240V AC – Factory Bonded Split Neutral
MainBreakerType
MainAmpereRating
MaximumNumber3/4-inch (25.4 mm)
EnclosureType
Loadcenter➀➁Catalog Number
List Price Loadcenter CoverCatalog Number
List Price BoxSize➃
Wire Size RangeCu/Al60°C or 75°Cfor Main Breaker
Space Poles Combination➈ Surface
CH10 kAIC
100 22 22 Indoor CH22B100C➄ $261.00 CH8CF CH8CS $33.50 C #6 - 1/0
125 22 22 Indoor CH22B125C➄ 403.00 CH8CF CH8CS 33.50 C
CSR25 kAIC�
150 32 32 Indoor CH32B150J➄ 483.00 CH8JF CH8JS 72.00 J #2 - 300 kcmil
200 3242
3242
IndoorIndoor
CH32B200J➄CH42B200K➄
497.00580.00
CH8JFCH8KF
CH8JSCH8KS
72.0098.00
JK
Type CH Loadcenters1-Phase with Main Circuit Breakers
➀ All main circuit breaker loadcenters arelisted for use as service entrance equipment.
➁ Loadcenters are factory bonded for service entrance applications. Remove bonding strap for separate neutral and ground bars for sub-feed applications.
➂ Ground bar kits priced separately.See page B-15.
➃ Refer to page B-28 for dimensions.
1-Phase 3-Wire – 120/240V AC – Insulated/Bondable Neutral
MainBreakerType
MainAmpereRating
MaximumNumber3/4-inch (25.4 mm)
EnclosureType
Loadcenter➀➂Catalog Number
List Price Loadcenter CoverCatalog Number
List Price BoxSize➃
Wire Size RangeCu/Al60°C or 75°Cfor Main Breaker
Space Poles Combination➈ Surface
CH10 kAIC
100 1414141418181818223030
141420➇20➇181824➇24➇223030
IndoorOutdoorIndoor
OutdoorIndoor
OutdoorIndoor
OutdoorOutdoorIndoor
Outdoor
CH14B100B➄CH14B100R➅CH1420B100B➄CH1420B100R➅CH18B100C➄CH18B100R➅CH1824B100C➄CH1824B100R➅CH22B100R➅CH30B100D➄CH30B100R➅
$200.00310.00206.00316.00250.00337.00252.00331.00342.00274.00401.00
CH8BF—CH8BF—CH8CF—CH8CF——CH8DF—
CH8BS—CH8BS—CH8CS—CH8CS——CH8DS—
$ 33.50—
33.50—
33.50—
33.50——
62.00—
BBBBCCCCCDD
#6 - 1/0
125 223030
223030
OutdoorIndoor
Outdoor
CH22B125R➅CH30B125D➄CH30B125R➅
635.00464.00685.00
—CH8DF—
—CH8DS—
—62.00
—
CDD
#6 - 1/0
CSR25 kAIC�
150 8242432
8242432
OutdoorIndoor
OutdoorOutdoor
CH8B150RF➅➆CH24B150E➄CH24B150R➅CH32B150R➅
510.00433.00650.00700.00
—CH8EF——
—CH8ES——
—72.00
——
EEEJ
#2-300 kcmil
200 8242432323242
824243242➇42➇42
OutdoorIndoor
OutdoorOutdoorIndoor
OutdoorOutdoor
CH8B200RF➅➆CH24B200E➄CH24B200R➅CH32B200R➅CH3242B200J➄CH3242B200R➅CH42B200R➅
510.00452.00650.00720.00560.00740.00820.00
—CH8EF——CH8JF——
—CH8ES——CH8JS——
—72.00
——
72.00——
EEEJJJK
#2-300 kcmil
225 32324242
32323232
IndoorOutdoorIndoor
Outdoor
CH32B225J➄CH32B225R➅CH42B225K➄CH42B225R➅
605.00940.00650.00980.00
CH8JF—CH8KF—
CH8JS—CH8KS—
72.00—
98.00—
JJKK
#2-300 kcmil
➄ Indoor loadcenters can be top or bottom fed by rotating the enclosure and trim – 180 degrees.
➅ Rainproof panels are furnished with hubclosure plates. For rainproof hubs,refer to page B-15.
➆ Panel includes #4-300 kcmil feed-through lugs.
➇ Requires the use of CHT breakers.
➈ Combination style covers may be used in surface or flush applications.
➉ This cover is for flush applications only.(not combination)
� 25,000 AIC series combination rating is obtained when types CH, CHT, and CHP branch breakers are used with CSR main.
Discount Symbol 22CD
1-Phase – Main Circuit Breaker Loadcenters10,000/22,000/25,000 Amperes Interrupting Capacity
October 1998
CAT.73.01.T.E
Cutler-Hammer B-7
1-Phase 3-Wire – 120/240V AC – Insulated/Bondable Neutral
MainBreakerType
MainAmpereRating
Maximum Number3/4-inch (25.4 mm)
EnclosureType
Loadcenter➀➁Catalog Number
List Price Loadcenter CoverCatalog Number
List Price BoxSize➂
Wire Size RangeCu/Al60°C or 75°Cfor Main Breaker
Space Poles Combination➇ Surface
CHB442 kAIC➅
100 20202828
20202828
IndoorOutdoorIndoor
Outdoor
CH20H100C➄CH20H100R➃CH28H100D➄CH28H100R➃
$ 365.00444.00464.00545.00
CH8CF—CH8DF—
CH8CS—CH8DS—
$ 33.50—
62.00—
CCDD
#6-1/0
125 2828
2828
IndoorOutdoor
CH28H125D➄CH28H125R➃
600.00745.00
CH8DF—
CH8DS—
62.00—
DD
#6-1/0
CHH100 kAIC➆
150 3232
3232
IndoorOutdoor
CH32H150LCH32H150R➃
915.001165.00
CH8LF—
CH8LS—
126.00—
LL
#2/0-300 kcmil
200 32324242
32324242
IndoorOutdoorIndoor
Outdoor
CH32H200LCH32H200R➃CH42H200LCH42H200R➃
915.001165.00990.00
1275.00
CH8LF—CH8LF—
CH8LS—CH8LS—
126.00—
126.00—
LLLL
#2/0-300 kcmil
225 4242
4242
IndoorOutdoor
CH42H225LCH42H225R➃
1080.001310.00
CH8LF—
CH8LS—
126.00—
LL
#2/0-300 kcmil
Type CH Loadcenters1-Phase with High Interrupting Rated Main Circuit Breakers
➀ All main circuit breaker loadcenters arelisted for use as service entrance equipment.
➁ Ground bar kits priced separately.See page B-15.
➂ Refer to page B-28 for dimensions.➃ Rainproof panels are furnished with hub
closure plates. For rainproof hubs,refer to page B-15.
Discount Symbol 22CD
1-Phase – Main Circuit Breaker Loadcenters42,000/100,000 Amperes Interrupting Capacity
➄ Indoor loadcenters can be top or bottom fed by rotating the enclosure and trim – 180 degrees.
➅ Series rated for 42,000 AIC with all CH, CHT, and CHP breakers.
➆ Series rated for 100,000 AIC with all CH, CHT, and CHP breakers.
➇ Combination style covers may be used in surface or flush applications.
CAT.73.01.T.E
Cutler-HammerB-8October 1998
1-Phase – Main Lug Loadcenters
1-Phase 3-Wire – 120/240V AC – Insulated/Bondable Neutral
MainAmpereRating
Maximum Number3/4-inch (25.4 mm)
EnclosureType
Type of Trim(Included)
LoadcenterCatalog Number
List Price BoxSize➁
Wire Size RangeCu/Al60°C or 75°Cfor Main Lugs
Space Poles
40 222
4➂4➂4➂
IndoorOutdoorIndoor
Surface no Door—
Flush no Door
CH2L40SP➃➀CH2L40RP➃➆➀CH2L40FP➃➀
$ 31.2584.0036.75
55R5
#14-6
70 222
4➂4➂4➂
IndoorOutdoorIndoor
Surface no Door—
Flush no Door
CH2L70SP➃➀CH2L70RP➃➆➀CH2L70FP➃➀
46.5086.5048.50
55R5
#14-2
125 222
4➂4➂4➂
IndoorOutdoorIndoor
Surface no Door—
Flush no Door
CH2L125SP➃➀CH2L125RP➃➆➀CH2L125FP➃➀
56.00101.0070.50
66R6
#14-1/0
444
8➂8➂8➂
IndoorOutdoorIndoor
Surface no Door—
Flush no Door
CH4L125SP➄➀CH4L125RP➄➆➀CH4L125FP➄➀
56.50101.0056.50
77R7
#14-1/0
888
16➂16➂16➂
IndoorOutdoorIndoor
Surface no Door—
Flush no Door
CH8L125SP➅➀CH8L125RP➅➆➀CH8L125FP➅➀
73.00129.0074.00
77R7
#6-1/0
Type CH Loadcenters1-Phase with Main Lugs
➀ Ground bar kits priced separately,see page B-5.– For 2/4 circuit loadcenters use
GBKS or GBK520 ground bar– For 4/8 and 8/16 circuit loadcenters use
GBK10 ground bar– Ground bars mount to the left side wall of
the enclosure for the 4/8 and 8/16 circuitloadcenters.
➁ Refer to page B-28 for dimensions.➂ Requires the use of CHNT breakers.
➃ Suitable for use as service equipment when not more than two service disconnecting mains are provided or when not used as a lighting and appliance panelboard(see Article 384-14 of the NEC).
➄ Suitable for use as service equipment when not more than two service disconnecting mains are provided or when not more than six service disconnecting mains are pro-vided and when not used as a lighting and appliance panelboard (see Article 384-14 of the NEC).
➅ Suitable for use as service equipmentwhen a main breaker is used or when not more than six service disconnecting mains are provided and when not used as a light-ing and appliance panelboard (see Article 384-14 of the NEC).
➆ Rainproof panels are furnished with hubclosure plates. For rainproof hubs refer to page B-15.
Discount Symbol 22CD
2 Circuits 40 and 70 Amperes 2 Circuits 125 Amperes4 and 8 Circuits 125 Amperes
Surface
Outdoor
Flush Surface FlushSurface no Door Flush no Door
OutdoorOutdoor
October 1998
CAT.73.01.T.E
Cutler-Hammer B-9
MainAmpereRating
Maximum Number3/4-inch (25.4 mm)
EnclosureType
CommercialLoadcenterCatalog Number
List Price Loadcenter CoverCatalog Number
List Price BoxSize➁
Wire Size RangeCu/Al60°C or 75°C
Space Poles Flush Surface
400 42 42 Indoor CH42PL400➈➉ $950.00 CH7PF� CH7PS $366.00 P (2) 1/0 - 300 kcmil(1) 750 kcmil
Type CH Loadcenters1-Phase with Main Lugs
1-Phase – Main Lug Loadcenters, Continued
1-Phase 3-Wire – 120/240V AC – Insulated/Bondable Neutral
MainAmpereRating
Maximum Number3/4-inch (25.4 mm)
EnclosureType
LoadcenterCatalog Number➀
List Price Loadcenter CoverCatalog Number
ListPrice➃
BoxSize➁
Wire Size RangeCu/Al60°C or 75°Cfor Main Lugs
Space Poles Combination Surface
125 12121616161620202424
1212161624➂2420202424
IndoorOutdoorIndoor
OutdoorIndoor
OutdoorIndoor
OutdoorIndoor
Outdoor
CH12L125B➃➅CH12L125R➃➅➇CH16L125B➃➅CH16L125R➃➅➇CH1624L125B➃➅CH1624L125R➃➅➇CH20L125C➃➅CH20L125R➃➅➇CH24L125C➃➅CH24L125R➃➅➇
$ 76.50203.00125.00254.00195.00315.00175.00286.00225.00320.00
CH8BF—CH8BF—CH8BF—CH8CF—CH8CF—
CH8BS—CH8BS—CH8BS—CH8CS—CH8CS—
$33.50—
33.50—
33.50—
33.50—
33.50—
BBBBBBCCCC
#6 - 2/0
150 24243232
24243232
IndoorOutdoorIndoor
Outdoor
CH24L150D➃➅CH24L150R➃➆➇CH32L150D➃➅CH32L150R➃➆➇
205.00387.00216.00399.00
CH8DF—CH8DF—
CH8DS—CH8DS—
62.00—
62.00—
DDDD
#4-300 kcmil
200 12121616
12121616
IndoorOutdoorIndoor
Outdoor
CH12L200D➃➅CH12L200R➃➆➇CH16L200D➃➅CH16L200R➃➆➇
203.00341.00288.00419.00
CH8DF—CH8DF—
CH8DS—CH8DS—
62.00—
62.00—
DDDD
#4-300 kcmil
225 2424323232324242
2424323242➂424242
IndoorOutdoorIndoor
OutdoorIndoor
OutdoorIndoor
Outdoor
CH24L225D➃➅CH24L225R➃➆➇CH32L225D➃➅CH32L225R➃➆➇CH3242L225D➄➅CH3242L225R➄➆➇CH42L225G➄➆CH42L225R➄➆➇
253.00439.00250.00447.00397.00575.00418.00590.00
CH8DF—CH8DF—CH8DF—CH8GF—
CH8DS—CH8DS—CH8DS—CH8GS—
62.00—
62.00—
62.00—
80.00—
DDDDDDGG
#4-300 kcmil
➀ Includes factory installed ground bar.➁ Refer to B-28 for dimensions.➂ Requires the use of CHT breakers.➃ Ground bar GBK14 is installed.➄ Ground bar GBK21 is installed.➅ Suitable for use as service equipment when
a circuit breaker is used as a main breaker. The main breaker is backfed and requires hold-down bracket kit catalog number CH125RB. Suitable for use as service equip-ment when not more than six disconnecting
➈ Suitable for use as service equipment when a circuit breaker is used as a main breaker. The main breaker is backfed and must be a type CHB. The breaker cannot be a type CH.
➉ Ground bar kit priced separately,see page B-15.
� This cover is for flush application only (not combination).
means are provided and when not usedas a lighting and appliance panelboard(see Article 384-14 of the NEC).
➆ Suitable for use as service equipment when a circuit breaker is used as a main breaker. The main breaker is backfed and requires hold-down bracket kit catalog number CH125RB.
➇ Rainproof panels are furnished with hubclosure plates. For rainproof hubs refer to page B-15.
CAT.73.01.T.E
Cutler-HammerB-10October 1998
MainBreakerType
MainAmpereRating
Maximum Number3/4 inch (25.4 mm)
EnclosureType
Loadcenter➀➁Catalog Number
List Price Loadcenter CoverCatalog Numbers
List Price BoxSize➂
Wire Size RangeCu/Al60°C or 75°Cfor Main Breaker
Space Poles Combination Surface
CHH100 kAIC➅
200 30304242
30304242
IndoorOutdoorIndoor
Outdoor
CH30H3200LCH30H3200R➃CH42H3200LCH42H3200R➃
$1715.002115.001815.002535.00
CH8LF—CH8LF—
CH8LS—CH8LS—
$126.00—
126.00—
LLLL
#2/0-300 kcmil
225 4242
4242
IndoorOutdoor
CH42H3225LCH42H3225R➃
1960.002745.00
CH8LF—
CH8LS—
126.00—
LL
MainBreakerType
MainAmpereRating
Maximum Number3/4 inch (25.4 mm)
EnclosureType
CommercialLoadcenter➀➁Catalog Number
List Price Loadcenter CoverCatalog Numbers
List Price BoxSize➂
Wire Size RangeCu/Al60°C or 75°Cfor Main Breaker
Space Poles Flush Surface
LD10 kAIC
300 42 42 Indoor CH424PM300 $4265.00 CH7PMF➄ CH7PMS $387.00 PM (2) 3/0-350 kcmil
400 42 42 Indoor CH424PM400 4010.00 CH7PMF➄ CH7PMS 387.00 PM (2) 3/0-350 kcmil
3-Phase 4-Wire – 208Y/120V AC or 240V AC Insulated/Bondable Neutral
MainBreakerType
MainAmpereRating
Maximum Number3/4 inch (25.4 mm)
EnclosureType
Loadcenter➀➁Catalog Number
List Price Loadcenter CoverCatalog Numbers
List Price BoxSize➂
Wire Size RangeCu/Al60°C or 75°Cfor Main Breaker
Space Poles Combination Surface
CC10 kAIC
150 3030
3030
IndoorOutdoor
CH30B3150LCH30B3150R➃
$1135.001480.00
CH8LF—
CH8LS—
$126.00—
LL
#1-4/0
200 30304242
30304242
IndoorOutdoorIndoor
Outdoor
CH30B3200LCH30B3200R➃CH42B3200LCH42B3200R➃
1135.001480.001195.001695.00
CH8LF—CH8LF—
CH8LS—CH8LS—
126.00—
126.00—
LLLL
#2/0-300 kcmil
225 30304242
30304242
IndoorOutdoorIndoor
Outdoor
CH30B3225LCH30B3225R➃CH42B3225LCH42B3225R➃
1235.001605.001285.001820.00
CH8LF—CH8LF—
CH8LS—CH8LS—
126.00—
126.00—
LLLL
Type CH Loadcenters3-Phase with Main Circuit Breaker
➀ All main circuit breaker loadcenters are listed for use as service entrance equipment.
➁ Ground bar kits priced separately.See page B-15.
➂ Refer to page B-28 for dimensions. Discount Symbol 22CD
3-Phase – Main Circuit Breaker Loadcenters10,000/100,000 Amperes Interrupting Capacity
➃ Rainproof loadcenters are furnished with hub closure plates. For rainproof hubs refer to page B-15.
➄ This cover for flush application only.(not combination)
➅ 100,000 AIC series combination rating is obtained when types CH and CHP branch breakers are used with CHH main.
October 1998
CAT.73.01.T.E
Cutler-Hammer B-11
MainAmpereRating
Maximum Number3/4-inch (25.4 mm)
EnclosureType
CommercialLoadcenterCatalog Number
List Price Loadcenter CoverCatalog Numbers
List Price BoxSize➁
Wire Size RangeCu/Al60°C or 75°Cfor Main Lugs
Space Poles Flush Surface
400 42 42 Indoor CH424PL400➈� $1090.00 CH7PF� CH7PS $366.00 P (2) 1/0-300 kcmil(1) 750 kcmil
MainAmpereRating
Maximum Number3/4-inch (25.4 mm)
EnclosureType
LoadcenterCatalog Number
List Price Loadcenter CoverCatalog Numbers
List Price BoxSize➁
Wire Size RangeCu/Al60°C or 75°Cfor Main Lugs
Space Poles Combination Surface
125 121218182424
121218182424
IndoorOutdoorIndoor
OutdoorIndoor
Outdoor
CH12L3125B➃➆CH12L3125R➃➆➉CH18L3125C➃➆CH18L3125R➃➆➉CH24L3125C➃➆CH24L3125R➃➆➉
$188.00304.00270.00386.00283.00422.00
CH8BF—CH8CF—CH8CF—
CH8BS—CH8CS—CH8CS—
$ 33.50—
33.50—
33.50—
BBCCCC
#14-1/0
150 3030
3030
IndoorOutdoor
CH30L3150D➃➆CH30L3150R➃➇➉
330.00515.00
CH8DF—
CH8DS—
62.00—
D #4-300 kcmil
225 242430304242
242430304242
IndoorOutdoorIndoor
OutdoorIndoor
Outdoor
CH24L3225D➃➆CH24L3225R➃➇➉CH30L3225D➃➆CH30L3225R➃➇➉CH42L3225G➄➇CH42L3225R➄➇➉
359.00535.00366.00600.00515.00980.00
CH8DF—CH8DF—CH8GF—
CH8DS—CH8DS—CH8GS—
62.00—
62.00—
80.00—
DDDDGG
#4-300 kcmil
3-Phase – Main Lug Loadcenters
3-Phase 4-Wire – 208Y/120V AC or 240V AC Insulated/Bondable Neutral
MainAmpereRating
Maximum Number3/4-inch (25.4 Mm)
EnclosureType
Type of TrimIncluded
LoadcenterCatalog Number
List Price BoxSize➁
Wire Size RangeCu/Al60°C or 75°Cfor Main Lugs
Space Poles
125 666
12➂12➂12➂
IndoorOutdoorIndoor
Surface No Door—
Flush No Door
CH6L3125SP➅➀CH6L3125RP➅➉➀CH6L3125FP➅➀
$131.00171.00131.00
77R7
#14-1/0
Type CH Loadcenters3-Phase with Main Lugs
Discount Symbol 22CD
➀ Ground bar kits priced separately,see page B-15.– Use GBK10 ground bar– Ground bars mount to the left side wall of
the enclosure.➁ Refer to page B-28 for dimensions.➂ Requires the use of CHNT breakers.➃ Ground bar GBK14 is installed.➄ Ground bar GBK21 is installed.➅ Suitable for use as service equipment when
not more than two service disconnecting means are provided or when not morethan six service disconnecting means are provided and when not used as a lighting and appliance panelboard (see Article 384-14 of the NEC).
➆ Suitable for use as service equipmentwhen a circuit breaker is used as a main breaker. The main breaker is backfed and requires hold-down bracket kit catalognumber CH125RB. Suitable for use as service equipment when not more than six service disconnecting means are provided and when not used as a lighting and appliancepanelboard (see Article 384-14 of the NEC).
➇ Suitable for use as service equipmentwhen a circuit breaker is used as a main breaker. The main breaker is backfed and requires hold-down kit catalog number CH125RB.
➈ Suitable for use as service equipment when a circuit breaker is used as a main breaker. The main breaker is backfed and must be a type CHB. The breaker cannot be a type CH.
➉ Rainproof panels are furnished with hubclosure plates. For rainproof hubs refer to page B-15.
� Ground bar kit priced separately,see page B-15.
� This cover is for flush application only (not combination).
CAT.73.01.T.E
Cutler-HammerB-12October 1998
Outdoor – Single-Phase – 3-Wire – 120/240V – Insulated/Bondable Neutral
MaximumMainAmpereRating
MaximumNumber ofSinglePoles
BoxSize➁
Loadcenter Boxand Panel
Main Lug Kit Main Breaker Kit
CatalogNumber➂
ListPrice
CatalogNumber
ListPrice
WireSize
CatalogNumber
ListPrice
AICRating
WireSize
200 8 E CH8N200RF➆➇ $261.00 CHL225N $151.00 #4-300 kcmil CSR2125NCSR2150NCSR2175NCSR2200N
$295.00 25K #2-300 kcmil
125 22 C CH22N125R➆ 206.00 CHL125N 77.00 #10-1/0 CH2100NCH2125
141.00267.00
10K #10-1/0
200 32 J CH32N200R➆ 290.00 CHL225N 151.00 #4-300 kcmil CSR2125N➄➅CSR2150N➄➅CSR2175N➄➅CSR2200N➄➅
295.00 25K #2-300 kcmil
225 42 K CH42N225R➆ 419.00 CHL225N 151.00 #4-300 kcmil CSR2125N➄➅CSR2150N➄➅CSR2175N➄➅CSR2200N➄➅CSR2225N➄➅
295.00 25K #2-300 kcmil
Indoor – Single-Phase – 3-Wire – 120/240V – Factory Bonded Split Neutral – Top or Bottom Feed
Maximum
Main
Ampere
Rating
Maximum
Number of
Single
Poles
Box
Size➁Loadcenter Box
and Panel
Loadcenter Cover
Catalog Numbers
Main
Lug Kit
Main
Breaker Kit
Catalog
Number➂➃List
Price
Combination Surface List
Price
Catalog
Number
List
Price
Wire
Size
Catalog
Number
List
Price
AIC
Rating
Wire
Size
125 22 C CH22N125C $153.00 CH8CF CH8CS $33.50 CHL125N $ 77.00 #10-1/0 CH2100N
CH2125N
$141.00
272.00
10K #10-1/0
200 32 J CH32N200J 217.00 CH8JF CH8JS 72.00 CHL225N 151.00 #4-300 kcmil CSR2125N➄➅CSR2150N➄➅CSR2175N➄➅CSR2200N➄➅
295.00 25K #2-300 kcmil
225 42 K CH42N225K 292.00 CH8KF CH8KS 98.00 CHL225N 151.00 #4-300 kcmil CSR2125N➄➅CSR2150N➄➅CSR2175N➄➅CSR2200N➄➅CSR2225N➄➅
295.00 25K #2-300 kcmil
Type CH LoadcentersConvertible, Base Units and Main Devices
Convertible Loadcenters MCB or MLO – Base Units and Main Devices10,000/25,000 Amperes Interrupting Capacity➀
Complete assembly consists of: Loadcenter, Cover, and either Main Breaker Kit or Main Lug Kit.
➀ Interrupting rating depends on main circuit breaker selected.
➁ Refer to page B-28 for enclosure dimensions.➂ Panel does not include main. Order main
breaker or main lug kit separately.➃ Loadcenters are factory bonded for service
entrance applications. Remove bonding strap for separate neutral and ground bars for sub-feed applications. Discount Symbol 22CD
➄ 25,000 AIC series combination rating is obtained when types CH, CHT, and CHP branch breakers are used with CSR main.
➅ CSR breakers include line lugs onlyas standard.
➆ Rainproof panels are furnished with hubclosure plates. For rainproof hubs refer to page B-15.
➇ Includes feed-through lugs for both phase and neutral conductors.
October 1998
CAT.73.01.T.E
Cutler-Hammer B-13
CSR Lug Tree Kit For Replacement Purposes OnlyFor Use in Type ECB Unit Enclosures
AmpereRating
Description CatalogNumber
ListPrice
Wire Size RangeCu/Al60°C or 75°C forLine Terminals
225 For use on125, 150, 175, 200and 225 Ampere
CSR Breakers
MCBK225 $84.00 #2-300 kcmil
Type CC Circuit Breakers 240V AC – 10,000 AICFor Use in Type ECC Unit Enclosures
AmpereRating
Type CC10,000 AIC
Type CC Hi Mag10,000 AIC
Wire Size RangeCu/Al60°C or 75°C forLine Terminals
CatalogNumber
ListPrice
CatalogNumber
ListPrice
2-Pole
100125150
CC2100CC2125CC2150
$295.00295.00295.00
CC2100HMCC2125HMCC2150HM
$365.00365.00365.00
#4-4/0
175200225
CC2175CC2200CC2225
295.00295.00295.00
CC2175HMCC2200HMCC2225HM
365.00365.00365.00
#2/0 - 300 kcmil
3-Pole
100125150
CC3100CC3125CC3150
430.00790.00790.00
CC3100HMCC3125HMCC3150HM
505.00855.00855.00
#4-4/0
175200225
CC3175CC3200CC3225
790.00790.00790.00
CC3175HMCC3200HMCC3225HM
855.00855.00855.00
#2/0 - 300 kcmil
Type CSR Circuit Breakers 120/240V AC – 25,000 AICFor Use in Type ECB Unit Enclosures
AmpereRating
2-Pole Breakers Wire Size RangeCu/Al60°C or 75°C forLine Terminals
25,000 AIC
CatalogNumber
ListPrice
125150175200225
CSR2125NCSR2150NCSR2175NCSR2200NCSR2225N
$295.00295.00295.00295.00295.00
#2-300 kcmil
Type CH Loadcenters1- and 3-Phase Circuit Breaker Unit Enclosure
MainAmpereRating
Unit Enclosure Catalog Number Unit Enclosure Catalog Number Type ofCircuitBreaker
Wire Size RangeCu/Al60°C or 75°C
EnclosureType
FlushCover➁
SurfaceCover➁
ListPrice
EnclosureType
RainproofNEMA Type 3R➁
ListPrice
Type ECB Circuit Breaker Unit Enclosures – Order Type CSR Circuit Breaker SeparatelyUnit Enclosure Includes Lug Tree Kit1-Phase 3-Wire – 240V AC Maximum
225 Indoor ECB225F➀➅ ECB225S➀➅ $141.00 Outdoor ECB225R➀➄➅ $270.00 CSR25 kAIC
➆
Type ECB Circuit Breaker Unit Enclosures – Includes Factory Installed CSR Circuit Breaker1-Phase 3-Wire – 240V AC Maximum
150 — — — — Outdoor ECB150RB➂➄➅ 625.00 CSR2150N25 kAIC
➆
200 — — — — Outdoor ECB200RB➃➄➅ 625.00 CSR2200N25 kAIC
Type ECC Circuit Breaker Unit Enclosures – Order Type CC Circuit Breakers Separately1-Phase 3-Wire/3-Phase 4-Wire – 240V AC Maximum
225 Indoor ECC225F➀➅ ECC225S➀➅ 141.00 Outdoor ECC225R➀➄➅ 270.00 CC10 kAIC
➆
1-Phase and 3-PhaseCircuit Breaker Unit Enclosures10,000/25,000 Amperes Interrupting Capacity
➀ Order circuit breaker separately.➁ Dimensions see page B-28.➂ CSR2150N factory installed circuit breaker.➃ CSR2200N factory installed circuit breaker.➄ Rainproof panels are furnished with hub
closures plates. For rainproof hubs refer to page B-15.
➅ One ground lug accepting (1) #14-#2 is factory installed. Also, there are pre-drilled holes to accept a GBK5 ground bar.
➆ Wire size is determined by the circuit breaker installed in enclosure. Maximum wire size and ampere rating is determined by table to the right.
CSR2200N
Wire/Application Maximum
Wire Size
Maximum
Ampere Rating
Aluminum – Standard
250 kcmil 200
Aluminum –Service Entrance
250 kcmil 225
Copper –Standard andService Entrance
250 kcmil 225
Discount Symbol 22CD
Circuit BreakerUnit Enclosures
CAT.73.01.T.E
Cutler-HammerB-14October 1998
Power Center
A special style loadcenter with provisions for installing a Power Manager ™.
Whole Home Power Sensors™Monitor energy consumptionat the incoming line.
Type CH Branch Circuit Breakers1-, and 2-pole, 120/240V AC. 15-60 A, 10 kAIC.
Arc Fault CircuitInterruptersEnhancedprotection from the risk of electrical fires.
Type CH Ground Fault Circuit Breakers1- and 2-pole, 120/240V AC. 15-60 A, up to 22 kAIC.
Type CH Power Centers
Protecting and Controlling Your Home Today and TomorrowThe unique Advanced Power Centersystem provides an easy, reliable, and economical way to monitor and control energy usage in your home.
Cutler-Hammer’s Advanced PowerCenter system makes home controlsolutions an economical reality. This highly reliable system is easy-to-operate, yet inexpensive and easy-to-install…because it uses the equipment found in every home – the loadcenter and existing wiring.
Advanced Power Center SystemConsists of:
■ Power CentersFor installation in new homes or any renovation where a loadcenter is required. Home control capabilities can be easily and inexpensively added whenever the homeowner wants. Power Centers futureproof the home with a minimum investment, and are installed like a standard loadcenter.
■ Power ManagerInstalled by the systems integrator that is installing the integrated home control system. The Power Manager supports industry-standard communi-cations such as X-10®, CEBus®, and INCOM… providing flexibility tointerface with most manufacturers’ home control systems.
■ Power SensorsAdd monitoring capability to any indi-vidual circuit or the incoming service.
■ Power Circuit InterruptersAdd remote control capability ofindividual circuits.
■ Monitor Energy UsageThe homeowner can determine where electrical energy is being used to take advantage of incentives provided by the energy supplier. Major appliances can be monitored to provide early indications of potential failures.
■ Safety and SecurityThe homeowner can also take advan-tage of several capabilities such as:– In event of a fire alarm, turn off the
furnace or air conditioner to pre-vent smoke from spreading, turn off major appliances, and turn on lights so home can be safely exited.
– Turning on outdoor and other lights to provide safe entry on arrival home, or to startle intruders.
– Increased protection from fire haz-ards and electrical shocks is pro-vided when ground fault and arc fault circuit interrupter breakers are installed.
■ Energy SavingsCapabilities to reduce energy costs include turning off nonessential light-ing and appliances when not at home…taking advantage of utility rate-saving structures by controlling appliances to run during the least expensive time-of-day…and taking advantage of billing options and pro-grams offered by energy providers due to deregulation.
■ Enhanced Comfort andConvenienceThe homeowner has control of light-ing, sprinkler systems, heating cables, and appliances.
■ The Advanced Power Center makes home protection and control an affordable reality for just abouteveryone.
■ For more information on the Advanced Power Center� system refer to section A.
Clipper Home Surge ProtectorProtects electronic equipment from spikes and surges.
Power Circuit Interrupters ™Remote controlled branch circuit breakers.
Branch Circuit Power Sensors™Monitor energy consumption on selected branchcircuits.
The Power Manager™Electronic module that provides the communication, monitoring, and control capabilities.
Your Choice of Integrated Home Control Solu-tions
SecuritySystem
Television SmartThermostat
Smart Phone Personal Computer
Programming…Control…Management Right at Your Fingertips!
October 1998
CAT.73.01.T.E
Cutler-Hammer B-15
Ground Bar Kits
Description
(See Legend)
Length Catalog
Number
List Price
Each
Ordering
Quantity➀Inches mm
�������
��������
������������
�������������
���������������
����������������
�����������������
�����������������������
������������������������
�����������������������
2.543.594.295.344.615.696.748.149.197.94
(64.5)(91.9)(109.0)(135.6)(117.1)(144.5)(171.2)(206.8)(233.4)(252.5)
GBK5➁GBK520➁GBK10➁GBK1020➁GBK13➁GBK14➁GBK1420➁GBK21➁GBK2120➁CH9GP21➂➃
$10.20
12.10
11.60
14.50
12.70
13.60
16.80
18.40
19.50
21.70
1111111111
� � � � � � � � � � � � � � �
Field Installation Rainproof Conduit Hubs
Description Conduit Size Catalog
Number
List Price
Each
Ordering
Quantity
➀Inches mm
Group 1 – For use with 70, 100 and 125 AmpereMLO and MCB Loadcenters and Circuit BreakerEnclosures
3/41
1-1/41-1/2
2
19.125.431.838.150.8
DS075H1
DS100H1
DS125H1
DS150H1
DS200H1
$23.60
23.60
23.60
23.60
38.50
11111
Group 2 – For use with 150, 200 and 225 AmpereMLO and MCB Loadcenters and Circuit BreakerEnclosure
22-1/2
3
50.863.576.2
DS200H2
DS250H2
DS300H2
38.50
68.50
80.50
111
Adapter Kit – Allows Installing a Group 1 Hub onDevices Arranged for Group 2 HubsGroup 1 – Small Blank Hub Closure PlateGroup 2 – Large Blank Hub Closure Plate
———
———
DS900AP
CS900CP1
CS900CP2
11.10
1.70
3.30
111
Type CH LoadcentersAccessories
Loadcenter Accessories
Field Installation Kits and Parts
Number
of Poles
Ampere
Rating
Number of
1-inch (25.4 mm)
Spaces Needed
Wire Size
Range Cu/Al
60°C or 75°C
Catalog
Number
List Price
Each
Ordering
Quantity
➀
Sub-Feed Lug Blocks
23
125125
23
#1/0 Maximum#1/0 Maximum
CHSF2125
CHSF3125
$54.50
80.00
1
Neutral/Ground LugAdd-on Neutral or Ground Lug
#2/0 Maximum#3/0 Maximum
300 kcmil Maximum
NL20
NL30
NL300
12.00
14.70
27.25
1
Filler Plates
3/4-inch Space (???) Circuit Breaker SpaceCHFP 2.70 25
Door Lock – 12 through 42 Circuits, and 100 through 225 Amperes TDL 52.00 1
Sandlewood Spray Paint SPCSW 33.25 1
ANSI-61 Light Gray Touchup Paint for Outdoor Loadcenters SPCSW 33.25 1
Isolated Neutral Assembly (Computer Circuits) BINA 7.85 1
Circuit Directory – Adhesive Backed TCD 1.35 10
Cover Screws LCCS .76 25
Cover Replacement Latch 14-5/16 inch (363.55 mm) wide Loadcenters Only CHRLS 7.00 1
Circuit Marking Strip (next to breakers) CHMS 2.30 10
Circuit Identification Label (preprinted breaker labels) CHBL 2.30 25
Series Rated Caution Label SRL 1.45 25
Branch Circuit Numbering Strip CHNS 2.10 20
CHRLS
CHSF2125
TDL
CHFP
CHSF3125
➀ Must be purchased in multiples of ordering quantities indicated.
➁ Distance between mounting holes is 1-3/4 inches (44.5mm). Discount Symbol 22CD
Ground Bar Legend
�(3) #14 - #10 Cu/Al or (1) #14 - #4 Cu/Al�(1) #6 - 2/0 Cu/Al�(1) #14 - #6 Cu/Al or (2) #14 - #12 Cu/Al�(1) 1/8 - 14 or (3) #10 - 12 Cu/Al�(1) #14 - 1/0 Cu/Al or (3) #14 - #10 Cu/Al�(1) #6 - 14 or (2) #10 - 14 Cu/Al�Mounting Hole
� �
➂ For 1- and 3-phase 400 ampere loadcenters.➃ Distance between mounting holes is
2-13/32 inches.
CAT.73.01.T.E
Cutler-HammerB-16October 1998
Grounded ”B“ Phase Adapters
Maximum
Amperes
3-Phase Loadcenter
Types of Panels
Kit Catalog
Number➁List
Price
125 125 Ampere 12-32 CircuitLug Main
CHGRD1 $199.90
225 225 Ampere Main Lugand CHH Main Breaker Panels
CHGRD2 179.00
225 Ampere CC MainCB Panels
CHGRD3 400.00
Type CH LoadcentersAccessories, Continued
Mechanism interlocks two breakers in side-by-side position at the top of the panel. Used to switch normal power to emergency power or alternate branch feeds. UL listed for application with1-, 2- and 3-pole breakers through 100A.
Fits Loadcenter
Numbers
Mechanical Interlock Panel Cover
Catalog Number List Price
Flush Surface
CH12L125B, CH16L125BCH12L3125B, CH14B100B
CH8BFM CH8BSM $187.00
CH20L125C, CH24L125C, CH18L3125C,CH24L3125C, CH22B100C, CH22N100C
CH8CFM CH8CSM 187.00
CH24L150D, CH32L150D,CH24L3225D, CH30L3150D
CH8DFM CH8DSM 229.00
CH42L225G, CH42L3225G CH8GFM CH8GSM 229.00
Inner Cover of Box B RaintightInner Cover of Box C Raintight
—
—
CH8BRM
CH8CRM
156.00
➀ These covers do not meet UL1008 fortransfer switches.
➁ Can not be used in Safety Breaker Panels, only in Classic Plus Panels.
CH8BRM
Discount Symbol 22CD
Cover with Mechanical Interlock➀
October 1998
CAT.73.01.T.E
Cutler-Hammer B-17Type CH LoadcentersDecorator Cover Accessory
■ For easy use with CH Loadcenters mounted in living space.■ Easily wallpapered or painted to match any decor.■ Patented Loadcenter accessory – exclusively from Cutler-Hammer.
Now you see it. Now you don’t.
Decorator Cover
Catalog Number
For Use with
CH Loadcenter Cover
Catalog Number
List
Price
CH8KDNB
CH8KDNC
CH8KDND
CH8KDNJ
CH8KDNK
CH8BF
CH8CF
CH8DF/EF
CH8GF/JF
CH8KF
$192.00
205.00
226.00
250.00
260.00
Discount Symbol 22CD
CAT.73.01.T.E
Cutler-HammerB-18October 1998
Description CatalogNumber
ListPrice
Discharge Voltage, V AC Lead LengthInches (mm)1.5 kA 3 kA 5 kA 10 kA
Surge Protector Plug-On Type CH,Single-Phase, 120/240V AC
CHSA $85.00 345 370 500 545 8 (203.2)
Surge Protector, 2-PoleSingle-Phase, 3-Wire, 120/240V AC
CHSA01 49.50 490 640 980 1410 15 (381.0)
Surge Protector, 3-PoleThree-Phase, 4-Wire, 600V AC
CHSA03 100.00 1700 2100 2510 3800 15 (381.0)
Type CH LoadcentersSurge Protection
CHSA SurgeProtector
Surge Protector
CHSA – For use on single-phase, 120/240V AC systems. This easily plugs into a single-phase Type CH loadcenter and occupies two 3/4-inch pole spaces similar to a 2-pole Type CH breaker. When plugged into the first two stabs at the top of the loadcenter just below the main breaker or main lug, it provides surge protection for the entire load-center. If internal components are dam-aged, the CHSA LED visual indicators will signal the need for replacement. This device is suitable for service entry loca-tions installed in accordance with NEC Article 280. The CHSA is ideal for protect-ing sensitive appliances and electronics, such as refrigerators, microwave ovens, and home computers.
Surge Protector
CHSA01 – For use on single-phase, 120/240V AC systems. This surge protector can be easily installed in the enclosure of indoor or outdoor loadcenters by using the 1/2-inch (12.7 mm) threaded nipple. It is ideal for protecting outdoor lighting, garages, sump and irrigation pumps, etc.
Surge Protector
CHSA03 – For use on three-phase, 600V AC systems. This surge protector is installed in the enclosure of indoor and outdoor loadcenters by using the 1/2-inch (12.7 mm) threaded nipple. It pro-vides protection for commercial electri-cal services especially those using electric motors.
CHSA01Surge
Protector
CHSA03Surge
Protector
➀ Refer to Cutler-Hammer CHSP warranty for complete details. Discount Symbol 22CD
CHSP (Clipper Home Surge Protector)
Surge Protectors
Clipper Home Surge Protector
CHSP – This surge protector is an exter-nally mounted TVSS unit that provides industrial level surge protection in aresidential design. It is available in two versions, available in both indoor and outdoor enclosures. The first provides AC power line protection only. The sec-ond provides complete surge protection for your electrical, telephone, and coax-ial cable lines in one convenient unit. Both CHSP models are UL1449 (2ndedition) and 497A listed.
The CHSP is backed by a 5-year product warranty and provides a $10,000 warranty for properly connected equipment.➀
Protection Specifications
AC Power Protection
■ 120/240V (3-wire + ground) ■ 39 kA surge current per phase■ All modes protected ■ Nanosecond response time ■ 24-inch (609.6 mm) leads included for
installation■ Two status indicator lights
Telephone Protection
■ Two incoming lines■ 10 kA per pair surge protection■ PTC polyswitch resetting fuses■ 230V DC gas tube protection
Coaxial Cable Protection
■ Two Cable Type F connectors (input and output)
■ Line-to-shield (ground) protection■ 90V DC gas tube protection
Construction/Safety Specifications
■ UL1449 listed (2nd Edition) UL497A, 400V Rating, CSACertified
■ Tested to ANSI/IEEE Category B3 and C3 levels
■ Unique Surge Plane™ design■ -25°C to +50°C■ Steel enclosure■ 5-year limited warranty
Clipper Home Surge Protector CatalogNumbering System
CHSPCH A R B
ProtectionPosition 1
A = ACProtectionOnly
S = AC,Telephoneand Cable
EnclosurePosition 2
R = Surface/Flush
O = OutdoorEnclosure
PackagingPosition 3
B = Box
P = BlisterPack
CatalogNumber
ListPrice
CHSPCHARBCHSPCHARPCHSPCHAOBCHSPCHAOP
$335.00325.00410.00395.00
CHSPCHSRBCHSPCHSRPCHSPCHSOBCHSPCHSOP
410.00400.00485.00470.00
October 1998
CAT.73.01.T.E
Cutler-Hammer B-19Type CH LoadcentersPlug-On Circuit Breakers
Plug-On Type CH BreakerDescription
Quick-make, quick-break switch mecha-nism combined with inverse time ele-ment tripping operation and trip-free handle design. The thermal-magnetic trip curve avoids nuisance tripping on mild overloads while reacting almost instantaneously to severe short circuit conditions. Multipole breakers have internal common trip connection to oper-ate all poles simultaneously. Handles are marked with ON-OFF indication and ampere rating of the breaker. Type CH breakers meet UL Standard 489, NEMA standards, and Federal Spec Classifica-tion W-C 375 b/Gen. They are UL listed under file number E11713, E8741, E3624 and E51287: and CSA certified file num-ber LR87196, except Type CHT breakers.
Type CH Circuit Breaker Ratings
Single- and double-pole CH breakers rated 15 and 20 ampere have low instan-taneous magnetic trip levels. The 15 and 20 ampere breakers with “HM” suffix have high magnetic trip settings recom-mended for circuits with inherently high inrush currents. All type CH breakers are marked for heating, air conditioning and refrigeration (HACR) equipment applica-tion. Single-pole 15-20 ampere breakers are also suitable for switching duty (SWD). Shunt trip coils operate on 120V AC and require one additional pole space per breaker.
Type CH Circuit Breaker Wire Size Rating
Standard 10,000 AIC branch breakers with and without shunt trip and 10,000 AIC CH breakers with HM or HD suffix.
High Fault Current Application
Types CH and CHT breakers with 10,000 AIC rating can be used in series combi-nation with Cutler-Hammer types CSR, CHH, CHB4 and CHB2 main breakers. The UL listed combination rating will be suitable for applications up to 100,000 ampere of available fault current depend-ing upon the AIC rating of the main.
LatchLever
LatchSpring
LineContactClip
ContactClipSpring Contact
Over-CenterToggle Spring
MagneticPole Piece
Load Terminal
Calibration Screw(under UL label)
CurrentBi-Metal
MagneticArmature
Type CH Circuit Breakers – 10,000 AIC
Two-position trip breakers for ON-OFF operation to eliminate nuisance callbacks.
CAT.73.01.T.E
Cutler-HammerB-20October 1998
Type CH Breakers, 3/4-inch (19.05 mm) per Pole 120, 120/240 or 240 V AC, 10,000 AIC➀
Ampere
Rating
1-Pole 120V AC
Requires One 3/4-inch Space
2-Pole 120/240V AC
Common Trip
Requires Two 3/4-inch Spaces
3-Pole 240V AC
Common Trip
Requires Three 3/4-inch Spaces
Wire Size
Range
Cu/Al
60ºC or 75°10 per Shelf Carton 5 per Shelf Carton 5 per Shelf Carton
10 kAIC 10 kAIC 10 kAIC
Catalog Number List Price Catalog Number List Price Catalog Number List Price
1015202530
CH110
CH115➁➂➃CH120➁➂➃CH125➃CH130➃
$18.70
18.70
18.70
18.70
18.70
—
CH215➁➃CH220➁➃CH225➃CH230➃
—
$ 43.75
43.75
43.75
43.75
—
CH315➃CH320➃CH325➃CH330➃
—
$153.00
153.00
153.00
153.00
(1) #14-8➅(2) #14-10➅➆
(1)#14-6➇
35 CH135➃ 18.70 CH235➃ 43.75 CH335 153.00 #14-2➅#14-6➇
40455060708090
100110125150
CH140➃CH145➃CH150➃CH160➃CH170
—
—
—
—
—
—
18.70
18.70
18.70
18.70
43.75
—
—
—
—
—
—
CH240➃CH245➃CH250➃CH260➃CH270
CH280
CH290
CH2100
CH2110
CH2125
CH2150➄
43.75
43.75
43.75
43.75
91.00
126.00
126.00
126.00
267.00
267.00
348.00
CH340➃CH345➃CH350➃CH360➃CH370
CH380
CH390
CH3100
—
—
—
153.00
153.00
153.00
153.00
200.00
193.00
193.00
625.00
—
—
—
#10-1/0➉#14-2➈#3/0�
Type CH LoadcentersPlug-On Circuit Breakers
The NEC will mandate the use of AFCI protection for 15 and 20 ampere bed-room outlet circuits in the year 2002. Information will be published in the 1999 National Electrical Code.
Plug-On Arc Fault Circuit Breakers, Type CH10,000 Amperes Interrupting Capacity120V AC and 120/240V AC
Type CH Arc Fault Circuit Breakers3/4-inch (19.05 mm) per Pole 120V AC or 120/240V AC
AFCI technology recognizes the unique characteristics of an arcing fault to trip the breaker and interrupt the circuit.
Ampere
Rating
1-Pole
120V AC
Requires One 3/4-inch Space
2-Pole�
120/240V AC
Common Trip
Requires Two 3/4-inch Spaces
Wire Size
Range
Cu/Al
60ºC or 75°
1 per Shelf Carton 1 per Shelf Carton
10,000 AIC 10,000 AIC
Configuration Catalog Number List Price Configuration Catalog Number List Price
15 AFCIAFCI w/GFCI
CH115AF
CH115GFAF
$146.00� AFCIAFCI w/GFCI
CH215AF
CH215GFAF
�
�(1)#14-8
20 AFCIAFCI w/GFCI
CH120AF
CH120GFAF
$146.00� AFCIAFCI w/GFCI
CH220AF
CH220GFAF
�
�
(2)#14-10➆
Type CH 1- and 2-PoleAFCI Circuit Breakers
➀ For factory installed options and pricing, refer to page B-27.
➁ For high magnetic settings, add suffix HM and obtain pricing from page B-27.
➂ Switching duty rated.➃ HACR rated.➄ CH2150 requires 4-pole spaces and is not
suitable for use on 3-phase panels, not CSA certified.
➅ For 1- and 2-pole breakers.➆ Solid and stranded wire can be used together.➇ For 3-pole breakers.➈ 1-pole 40-50 amperes, 2-pole 40-70 amperes.➉ 1-pole 60-70 amperes, 2-pole 80-125 amperes,
3-pole 40-100 amperes.� 2-pole 150 amperes.
Discount Symbol 22CD
Plug-On Circuit Breakers, Type CH10,000 Amperes Interrupting Capacity120V AC, 120/240V AC and 240V AC
� Two-pole AFCI breakers are designed for use in 3-wire, 120/240V AC circuits, 120V AC multiwire circuits utilizing a shared neutral (often referred to as a “home run” circuit), and 240V AC circuits obtained from 120/240V AC source.
� Availability to be announced.
October 1998
CAT.73.01.T.E
Cutler-Hammer B-21
Type CH Ground Fault Circuit Breakers (5 Milliampere)3/4-inch (19.05 mm) per Pole 120V AC or 120/240V AC,10,000 AIC
Ampere
Rating
1-Pole
120V AC
Requires One 3/4-inch Space
2-Pole
120/240V AC
Common Trip
Requires Two 3/4-inch Spaces
Wire
Size
Range
Cu/Al
60ºC or
75°C1 per Shelf Carton 1 per Shelf Carton
10,000 AIC 10,000 AIC
Catalog Number List Price Catalog Number List Price
152025303540455060
CH115GF
CH120GF
—
CH130GF
—
—
—
—
—
$150.00
150.00
—
150.00
—
—
—
—
—
CH215GF
CH220GF
CH225GF
CH230GF
CH235GF
CH240GF
CH245GF
CH250GF
CH260GF
$267.00
267.00
267.00
267.00
267.00
267.00
267.00
267.00
267.00
#14-6
Plug-On Ground Fault Circuit Breakers, Type CH10,000 Amperes Interrupting Capacity120V AC and 120/240V AC
Type CH LoadcentersPlug-On Ground Fault Circuit Breakers
Type CH 1-Pole Type CH 2-Pole
Type CH Ground Fault Equipment Protectors (30 Milliampere)3/4-inch (19.05 mm) per Pole 120V AC or 120/240V AC,10,000 AIC
Ampere
Rating
1-Pole
120V AC
Requires One 3/4-inch Space
2-Pole
120/240V AC
Common Trip
Requires Two 3/4-inch Spaces
WireSizeRangeCu/Al60ºC or75°C1 per Shelf Carton 1 per Shelf Carton
10,000 AIC 10,000 AIC
Catalog Number List Price Catalog Number List Price
152030405060
CH115EPD
CH120EPD
CH130EPD
—
—
—
$239.00
239.00
239.00
—
—
—
CH215EPD
CH220EPD
CH230EPD
CH240EPD
CH250EPD
CH260EPD
$403.00
403.00
403.00
403.00
403.00
403.00
#14-6
Ground Fault Application Notes
Single-pole Type CHGFIs are designed for use in 2-wire, 120V AC circuits. Figure 1 shows a typical wiring configuration.
Two-pole Type CHGFIs are designed for use in 3-wire, 120/240V AC circuits, 120V AC multi-wire circuits employing common, neutral and 2-wire, 240V AC circuits obtained from a120/240V AC source.
Figures 2 and 3 illustrate typical wiring config-urations for a 120/240V AC multiwire circuits.
Figure 4 depicts a 240V AC, 2-wire circuit. Note the “panel neutral” conductor connects to the neutral bar, even though the neutral is not included in the load circuit. This connection is necessary to supply a 120V AC power source to the ground fault sensing circuit.
The figures are shown with a 120/240V AC,single-phase, 3-wire power source, but are also applicable to a 120/208V AC, 3-phase, 4-wire power supply. For all figures the electrical operation of the Type CHGFI is not affectedby the equipment ground.
Figure 11-Pole
Figure 32-Pole
Figure 22-Pole
Figure 42-Pole
Discount Symbol 22CD
CAT.73.01.T.E
Cutler-HammerB-22October 1998
Type CH LoadcentersPlug-On Circuit Breakers – CTL and Non-CTL Twins
CTL Plug-On Circuit Breakers, Type CHT Twin10,000 Amperes Interrupting Capacity120/240V AC
Type CHT Twin (CTL)3/4-inch (19.05 mm) per Pole 120V AC
Class CTL 10,000 AIC – All circuitbreakers have rejection feature. Use only with loadcenters marked for use with CHT breakers.
Ampere
Rating
1-Pole
Requires One 3/4-inch Space
Wire
Size
Range
Cu/Al
60ºC or
75°C
10 per Shelf Carton
10,000 AIC
Catalog Number List Price
15-1515-2020-20
CHT1515➀➁CHT1520➀➁CHT2020➀➁
$44.75
44.75
44.75
#14-8
➀ Switch duty rated.➁ HACR rated.
Non-CTL Plug-On Replacement Circuit Breakers, Type CHNT10,000 Amperes Interrupting Capacity120/240V AC
Type CHNT3/4-inch (19.05 mm) per Pole 120V AC
Non-CTL 10,000 AIC – For use as replace-ment in loadcenters built prior to 1968 and within the current style 2-8 circuit loadcenters as indicated in the load-center section.
Ampere
Rating
1-Pole
Requires One 3/4-inch Space
Wire
Size
Range
Cu/Al
60ºC or
75°C
10 per Shelf Carton
10,000 AIC
Catalog Number List Price
15-1515-2020-20
CHNT1515➀➁CHNT1520➀➁CHNT2020➀➁
$47.25
47.25
47.25
#14-8
120V AC120V AC
120V AC120V AC
Discount Symbol 22CD
October 1998
CAT.73.01.T.E
Cutler-Hammer B-23
Type CH Neutral Switching Breakers,3/4-inch (19.05 mm) per Pole 120/240 or 240 V AC, 10,000 AIC
Used to open the neutral along power line(s) for applications of gas pumps.
Ampere
Rating
2-Pole
120V AC
Common Trip
Requires Two 3/4-inch Spaces
3-Pole
120/240V AC
Common Trip
Requires Three 3/4-inch Spaces
Wire
Size
Range
Cu/Al
60ºC or
75°C1 per Individual Carton 1 per Individual Carton
10,000 AIC 10,000 AIC
Catalog Number List Price Catalog Number List Price
1520304050
CH215SW➀CH220SW➀CH230SW➀CH240SW➀CH250SW➀
$68.00
68.00
68.00
68.00
68.00
CH315SW➀CH320SW➀CH330SW➀CH340SW➀CH350SW➀
$98.00
98.00
98.00
98.00
98.00
#14-8
Type CH LoadcentersSpecial Applications Plug-On Circuit Breakers
CH Neutral Switching Breakers10,000 Amperes Interrupting Capacity120V AC and 120/240V AC
CH220SW
CH-HID Circuit Breakers10,000 Amperes Interrupting Capacity120V AC, 120/240V AC and 240V AC
Type CH-HID Circuit Breakers, 3/4-inch (19.05 mm) per Pole 120V AC,120/240 and 240 V AC, 10,000 AIC
Suitable for use in circuits for fluorescent and High Intensity Discharge lighting.Also suitable for HACR applications.
Ampere
Rating
1-Pole
120V AC
Requires One 3/4-inch Space
2-Pole
120/240V AC
Common Trip
Requires Two 3/4-inch Spaces
3-Pole
240V AC
Common Trip
Requires Three 3/4-inch Spaces
Wire
Size
Range
Cu/Al
60ºC or
75°10 per Shelf Carton 5 per Shelf Carton 5 per Shelf Carton
10,000 AIC 10,000 AIC 10,000 AIC
Catalog Number List Price Catalog Number List Price Catalog Number List Price
152030
CH115HID
CH120HID
CH130HID
$38.25
38.25
38.25
CH215HID
CH220HID
CH230HID
$84.00
84.00
84.00
CH315HID
CH320HID
CH330HID
$223.00
223.00
223.00
#14-8
➀ For circuit breakers with shunt trip, add ST suffix. Shunt trip requires one additional pole space. Obtain pricing from page B-27.
Neutral InNeutral OutPhasePhase
Neutral InNeutral Out(Hot leg)
Discount Symbol 22CD
CAT.73.01.T.E
Cutler-HammerB-24October 1998
Type CHP-GFCI➀ Breakers (5 Milliampere) 3/4-inch (19.05 mm) per Pole 120 V ACand 120/240, 10,000 AIC
Ampere
Rating
1-Pole
120V AC
Requires One 3/4-inch Space
Wire Size
Range
Cu/Al 60ºC
or 75°C
1 per Individual Carton
10,000 AIC
Catalog Number List Price
152030405060
CHP115GF
CHP120GF
CHP130GF
—
—
—
$210.00
210.00
210.00
—
—
—
#14-6
Type CH LoadcentersSpecial Application Plug-On CHP Circuit Breakers
CHP➀ Commercial Breakers10,000 Amperes Interrupting Capacity120V AC, 120/240V AC and 240V AC
Type CHP➀ Breakers, 3/4-inch (19.05 mm) per Pole 120, 120/240 or 240 V AC, 10,000 AIC
Ampere
Rating
1-Pole
120V AC
Requires One
3/4-inch Space
2-Pole
120/240V AC
Common Trip
Requires Two
3/4-inch Spaces
3-Pole
240V AC
Common Trip
Requires Three
3/4-inch Spaces
Wire
Size
Range
Cu/Al
60ºC or
75°C10 per Shelf Carton 5 per Shelf Carton 5 per Shelf Carton
10,000 AIC 10,000 AIC 10,000 AIC
Catalog Number List Price Catalog Number List Price Catalog Number List Price
1015202530
CHP110
CHP115➁➂➃CHP120➁➂➃CHP125➃CHP130➃
$27.50
27.50
27.50
26.30
26.30
CHP210
CHP215➁➃CHP220➁➃CHP225➃CHP230➃
$55.00
57.50
57.50
55.00
57.50
CHP310
CHP315➃CHP320➃CHP325➃CHP330➃
$210.00
210.00
219.00
210.00
219.00
(1) #14-8➄(2) #14-10➄➅
(1)#14-6➆
35 CHP135➃ 26.30 CHP235➃ 55.00 CHP335➃ 210.00 #14-2➄#14-6➆
40455060708090
100110125
CHP140➃CHP145➃CHP150➃CHP160➃CHP170
—
—
—
—
—
26.30
26.30
26.30
26.30
48.30
—
—
—
—
—
CHP240➃CHP245➃CHP250➃CHP260➃CHP270
CHP280
CHP290
CHP2100
CHP2110
CHP2125
57.50
55.00
57.50
55.00
106.00
160.00
160.00
160.00
305.00
305.00
CHP340➃CHP345➃CHP350➃CHP360➃CHP370
—
—
CHP3100
—
—
210.00
210.00
210.00
210.00
262.00
—
—
273.00
—
—
#10-1/0➈#14-2➇
CHP-GFCI➀ Circuit Breakers10,000 Amperes Interrupting Capacity120V AC and 120/240V AC
➀ CHP Breakers offer on-off and trip positions for commercial applications.
➁ For high magnetic settings, add suffix HM and obtain pricing from page B-27.
➂ Switching duty rated.
Ground Fault Application Notes
Single-pole Type CHPGFIs are designed for use in 2-wire, 120V AC circuits. Figure 1 shows a typical wiring configuration.
The figure is shown with a 120/240V AC,single-phase, 3-wire power source, but are also applicable to a 120/208V AC, 3-phase, 4-wire power supply. For all figures the electrical operation of the Type CHPGFI is not affected by the equipment ground.
Figure 11-Pole
➃ HACR rated.➄ For 1- and 2-pole breakers.➅ Solid and stranded wire can be used together.➆ For 3-pole breakers.➇ 1-pole 40-50 amperes, 2-pole 40-70 amperes. Discount Symbol 22CD
➈ 1-pole 60-70 amperes, 2-pole 80-125 amperes, 3-pole 40-100 amperes.
October 1998
CAT.73.01.T.E
Cutler-Hammer B-25
Type CHP-HID Circuit Breakers, 3/4-inch (19.05 mm) per Pole120V AC, 120/240 and 240 V AC, 10,000 AIC
Suitable for use in circuits for fluorescent and High Intensity Discharge lighting.Also suitable for HACR applications.
Ampere
Rating
1-Pole
120V AC
Requires One
3/4-inch Space
2-Pole
120/240V AC
Common Trip
Requires Two
3/4-inch Spaces
3-Pole
240V AC
Common Trip
Requires Three
3/4-inch Spaces
Wire
Size
Range
Cu/Al
60ºC or
75°C10 per Shelf Carton 5 per Shelf Carton 5 per Shelf Carton
10,000 AIC 10,000 AIC 10,000 AIC
Catalog Number List Price Catalog Number List Price Catalog Number List Price
152030
CHP115HID
CHP120HID
CHP130HID
$41.00
41.00
41.00
CHP215HID
CHP220HID
CHP230HID
$92.50
92.50
92.50
CHP315HID
CHP320HID
CHP330HID
$260.00
260.00
260.00
#14-6
Type CHP Neutral Switching Breakers, 3/4-inch (19.05 mm) per Pole120/240 or 240 V AC, 10,000 AIC
Used to open the neutral along power line(s) for applications of gas pumps.
Ampere
Rating
2-Pole
120/240V AC
Common Trip
Requires Two 3/4-inch Spaces
3-Pole
240V AC
Common Trip
Requires Three 3/4-inch Spaces
Wire
Size
Range
Cu/Al
60ºC or
75°C1 per Shelf Carton 1 per Shelf Carton
10,000 AIC 10,000 AIC
Catalog Number List Price Catalog Number List Price
1520304050
CHP215SW➀CHP220SW➀—
—
—
$78.00
81.00
—
—
—
CHP315SW➀CHP320SW➀—
—
—
$136.00
136.00
—
—
—
#14-8
Type CH LoadcentersSpecial Application Plug-On CHP Circuit Breakers
➀ For circuit breakers with shunt trip, add ST suffix. Shunt trip requires one additional pole space, obtain pricing from B-27.
CHP-HID Circuit Breakers10,000 Amperes Interrupting Capacity120V AC, 120/240V AC and 240V AC
Discount Symbol 22CD
CHP Neutral Switching Breakers10,000 Amperes Interrupting Capacity120V AC and 120/240V AC
CAT.73.01.T.E
Cutler-HammerB-26October 1998
CHQ Breaker Accessories
Description Catalog
Number
List
Price
Breaker Padlocking DeviceBreaker Handle LockGround Fault Padlocking Device
CHQPL
CHLO
CHQPLGF
$4.50
2.10
6.00
Type CHQ Surge Arrester
Catalog Number List Price
CHQSA $103.00
Type CH LoadcentersReplacement for Square D® Type QO® Breakers
Type CHQ Classified Breakers 3/4-inch (19.05 mm) per Pole 120/240 or 240 V AC, 10,000 AIC
Ampere
Rating
1-Pole
120V AC
Requires One 3/4-inch Space
2-Pole
120/240V AC Common Trip
Requires Two 3/4-inch Spaces
Wire Size
Range
Cu/Al
60ºC or
75°C10 per Shelf Carton 5 per Shelf Carton
10,000 AIC 10,000 AIC
Catalog Number List Price Catalog Number List Price
1520253035404550
CHQ115
CHQ120
CHQ125
CHQ130
CHQ135
CHQ140
CHQ145
CHQ150
$16.90
16.90
16.90
16.90
16.90
16.90
16.90
16.90
CHQ215
CHQ220
CHQ225
CHQ230
CHQ235
CHQ240
CHQ245
CHQ250
$39.25
39.25
39.25
39.25
39.25
39.25
39.25
39.25
(1) #14-8(2) #14-10
Type CHQ Classified Breakers10,000 Amperes Interrupting Capacity120V AC and 120/240V AC
CHQ120
Type CHQ Ground Fault 10,000 Amperes Interrupting Capacity120V AC and 120/240V AC
CHQ115GF
Type CHQ Ground Fault (5 Milliampere) 3/4-inch (19.05 mm) per Pole 120/240 or 240 V AC, 10,000 AIC
Ampere
Rating
1-Pole
120V AC
Requires One 3/4-inch Space
2-Pole
120/240V AC Common Trip
Requires Two 3/4-inch Spaces
Wire
Size
Range
Cu/Al
60ºC or
75°C10 per Shelf Carton 5 per Shelf Carton
10,000 AIC 10,000 AIC
Catalog Number List Price Catalog Number List Price
1520304050
CHQ115GF
CHQ120GF
CHQ130GF
—
—
$150.00
150.00
150.00
CHQ215GF
CHQ220GF
CHQ230GF
CHQ240GF
CHQ250GF
$266.00
266.00
266.00
266.00
266.00
(1) #14-8(2) #14-10
Ground Fault Application Notes
Single-pole Type CHQGFIs are designed for use in 2-wire, 120V AC circuits. Figure 1 shows a typical wiring configuration.
Two-pole Type CHQGFIs are designed for use in 3-wire, 120/240V AC circuits, 120V AC multi-wire circuits employing common, neutral and 2-wire, 240V AC circuits obtained from a 120/240V AC source.
Figures 2 and 3 illustrate typical wiring config-urations for a 120/240V AC multiwire circuits.
Figure 4 depicts a 240V AC, 2-wire circuit. Note the “panel neutral” conductor connects to the neutral bar, even though the neutral is not included in the load circuit. This connection is necessary to supply a 120V AC power source to the ground fault sensing circuit.
The figures are shown with a 120/240V AC, sin-gle-phase, 3-wire power source, but are also applicable to a 120/208V AC, 3-phase, 4-wire power supply. For all figures the electrical operation of the Type CHQGFI is not affected by the equipment ground.
Warranty Information
15-year warranty on the replacementcircuit breaker and Square D� QO� load-center. See publication SA-103 for full details.
Square D� and QO� are registered trade-marks of The Square D Company.
Figure 11-Pole
Figure 32-Pole
Figure 22-Pole
Figure 42-Pole
Discount Symbol 22CDCHQSA
October 1998
CAT.73.01.T.E
Cutler-Hammer B-27
Shunt Trips, Auxiliary, Alarm Contacts and High Magnetic Options
Description Catalog
Number➈List Price
Adder Each
Shunt Trip for
Type CSR– 12 Volt– 24 Volt– 120 Volt
Type CH– 120 Volt
Add Suffix:
SR12
SR24
SR01
ST➉
$392.00
392.00
392.00
121.60
Auxiliary Contact for
Type CSR– (1) N.O. and (1) N.C.– (2) N.O. and (2) N.C.
AL1
AL2
170.00
334.00
Alarm Contact for
Type CSR CR1 170.00
High Magnetics
Type CH HM 2.60
Type CH LoadcentersCircuit Breaker Accessories
� Handle Position Changeability Chart
Handle Lockoff
and Lockdog
Types
To Change Handle Position from
“On to “Off,” or “Off” to “On”
You Must...
Remove
Padlock
Remove
Device
Remove
Load-
center
Deadfront
LockoffEscutcheonMounted
Remove — —
Lockoff ScrewMounted
Remove — —
Lockdog HandleMounted
N/A Remove —
➀ Handle Ties: Typically used to join two simi-lar independent single-pole breakers to form a 2-pole noncommon trip breaker.
➁ Handle Lockoffs: Devices that use a padlock to lock the circuit breaker’s handle in the “On” or “Off” position.
➂ Handle Lockdogs: Devices that are used to secure a circuit breaker’s handle in the “On” or “Off” position. Handle Lockdogs are not padlockable devices.
➃ Hold-Down Kits: Devices used to secure the circuit breaker to the loadcenter for back-feed main application. See NEC Article 384-16(f).
Discount Symbol 22-CD
➄ Escutcheon Mounted: Device mounted semi-permanently to the face of the circuit breaker and secured by the loadcenter deadfront.
➅ Handle Mounted: Device mounted above or below handle using spring pressure.
➆ Screw Mounted: Device permanently mounted to the face of the circuit breaker by the use of a non-removable screw.
➇ Must be purchased in multiples of ordering quantities indicated.
➈ Add suffix indicated to end of breaker catalog number.
➉ Requires one additional pole space.
CHHT
MCBPL (Installed)
CH125RB
Circuit Breaker Accessories
Field Installation Kits and Parts
Description Catalog
Number
List Price
Each
Ordering
Quantity➇
Handle Ties➀Handle tie bar for physically joining the handles of twoadjacent 1-pole Type CH Circuit Breakers. (Molded PlasticHandle Cover) CHHT $ .96 25
Handle Lockoffs➁➉Padlockable device for locking the handle of 1-, 2-, or 3-poleType CH Circuit Breakers (Escutcheon Mounted)➄ CHPL 6.35 1
Padlockable device for locking the handle of a 1-, 2- or3-pole Type CHGFI Circuit Breaker. (Escutcheon Mounted)➄ CHPLGF 6.25 1
Padlockable device for locking the handle of main circuitbreaker Types CC and CCH into the “On” or “Off” position.(Screw Mounted)➆ CCPL 21.60 1
Padlockable device for locking the handle of main breakerTypes CCH and CSR into the “On” or “Off” position.(Escutcheon Mounted)➄ MCBPL 25.25 1
Handle Lockdogs➂➉Device used to secure handle in “On” or “Off” position for1-pole Type CH Circuit Breakers. (Handle Mounted)➅ CHL0 2.30 10
Hold-Down Kits➃Hold-down retainer kit for 1-,2-, 3-Pole Type CH Circuit Break-ers. For 6-24 circuit 125 ampere single and 3-phase, 12-42circuit single-phase 225 ampere and 24-42 circuit 3-phase225 ampere MLO Type CH Loadcenters.
CH125RB 3.95 1
Hold-Down Kits➃Hold-down retainer kit for 1-,2-, 3-Pole Type CH Circuit Breakers for 2 through 4 circuit MLO CH Loadcenters.
CH125RB24 9.60 1
Mounting Bases
Mounting base for 2-Pole Type CH Circuit Breaker –70 ampere maximum CH9MB270 18.40 1
Main Breaker Lug Kits
Types CC and CCH Main Breaker Lug Kit (2) 300 kcmil.Type CSR Main Breaker Lug Kit (2) 300 kcmil.
CCL300
MCBL300
41.50
43.50
11
CHPL
CHLO MCBPL
CHPLGF
CH9MB270
CAT.73.01.T.E
Cutler-HammerB-28October 1998
Types ECB and ECC Unit EnclosuresNEMA Type 3R Outdoor
Dimensions in Inches Dimensions in mm
Height Width Depth Height Width Depth
23-11/16 9-5/16 5-7/16 601.4 236.5 138.1
Types ECB and ECC Unit EnclosuresNEMA Type 1 Indoor
Dimensions in Inches Dimensions in mm
Height Width Depth Height Width Depth
23-1/4 8-7/8 4-1/2 590.3 255.3 114.3
Type CH LoadcentersBox Sizes
Residential LoadcentersNEMA Type 3R Outdoor
BoxSize
Dimensions in Inches Dimensions in mm
Height Width Depth Height Width Depth
5R6R7RBCDEGJKL
9-1/211-1/2
1316-3/4
2129-1/829-1/834-1/834-1/8
3739
4-1/26-1/8
1114-5/1614-5/1614-5/1614-5/1614-5/1614-5/1614-5/1614-5/16
3-1/84-15/323-11/165-3/165-3/165-3/165-3/165-3/165-3/165-3/165-3/16
241.3292.1330.1425533740740867867940991
114.3155.6279.3364364364364364364364364
79.4114.390.5131.8131.8131.8131.8131.8131.8131.8131.8
Commercial LoadcentersNEMA Type 1 Indoor
BoxSize
Dimensions in Inches Dimensions in mm
Height Width Depth Height Width Depth
PPM
54-3/862-5/8
2121
66
13811591
533533
152152
Residential LoadcentersNEMA Type 1 Indoor
BoxSize
Dimensions in Inches Dimensions in mm
Height Width Depth Height Width Depth
567BCDEGJKL
9-1/211-3/8
1316-3/4
2129-1/829-1/834-1/834-1/8
3739
4-1/26-7/8
1114-5/1614-5/1614-5/1614-5/1614-5/1614-5/1614-5/1614-5/16
3-1/83-25/643-11/163-7/83-7/83-7/83-7/83-7/83-7/83-7/83-7/8
241.3288.9330.1425533740740867867940991
114.3174.6279.3364364364364364364364364
7986939898989898989898
Residential/Commercial/Unit Enclosure – Box Sizes➀
➀ Box sizes do not include covers/fronts.
October 1998
CAT.73.01.T.E
Cutler-Hammer B-29
Knockouts for Box Sizes 5, 6, 7, 5R, 6R, 7R
Code Diameter in Inches Diameter in mm
A 1/2 — — — 12.7 — — —
B 1/2 3/4 — — 12.7 19.0 — —
C 1/2 3/4 1 — 12.7 19.0 25.4 —
D 1/2 3/4 1 1-1/4 12.7 19.0 25.4 31.7
E 3/4 1 1-1/4 — 19.0 25.4 31.7 —
F 3/4 1 1-1/4 1-1/2 19.0 25.4 31.7 38.1
G 1 1-1/4 1-1/2 – 25.4 31.7 38.1 —
H 1 1-1/4 1-1/2 2 25.4 31.7 38.1 50.8
I 1-1/4 1-1/2 2 — 31.7 38.1 50.8 —
Type CH LoadcentersKnockouts
Residential Loadcenter Knockouts Dimensions in Inches (mm)
Residential NEMA Type 1 Indoor and NEMA Type 3R Outdoor Enclosures
Box 6R Box 7 Box 7R
Box 5 Box 5R Box 6
A
A
A
A
A
A
D D D
D
F
F
A
A
D D D
F
Hub
A
A
BA
B
B
C
C
F F
FF
AB
F
F
H
A
B
A
BH
F
B B
B
H
Hub
D D
A
A
AA
A
AAA
AAA AAA
B B B
A B B
B
BB
B
C CC
C
C
B C
G
G
GG
G GF
AAA AAA
A B BB C
C
G
G GF
Hub
CAT.73.01.T.E
Cutler-HammerB-30October 1998
NEMA Type 3R Outdoor
A 1/2 – – – – 12.7 – – – –
B 1-1/4 1-1/2 1-3/4 2 2-1/2 31.7 38.1 44.5 50.8 63.5
Type CH LoadcentersKnockouts
Code Diameter in Inches Diameter in mm
a 3/4 — — — — 12.7 — — — —
b 1/2 3/4 — — — 12.7 19.0 — — —
c 1/2 — — — — 12.7 — — — —
d 1 1-1/4 1-1/2 2 2-1/2 25.4 31.7 38.1 50.8 63.5
e 1-1/4 1-1/2 2 2-1/2 — 31.7 38.1 50.8 63.5 —
f 3/4 1-1/4 1-1/2 2 — 25.4 31.7 38.1 50.8 —
g 1/2 3/4 1 — — 12.7 19.0 25.4 — —
h 1-1/2 2 2-1/2 — — 38.1 50.8 63.5 — —
i 1/2 3/4 1 1-1/4 1-1/2 12.7 19.0 25.4 31.7 38.1
j 1 1-1/4 1-1/2 — — 25.4 31.7 38.1 — —
k 1-1/4 1-1/2 2 — — 31.7 38.1 50.8 — —
m 3/4 1 1-1/4 1-1/2 2 19.0 25.4 31.7 38.1 50.8
n 3/4 1 1-1/4 1-1/2 — 19.0 25.4 31.7 — —
p 2 2-1/2 — — — 50.8 63.5 — — —
Residential and Commercial Loadcenter Knockouts Dimensions in Inches (mm)
Residential NEMA Type 1 Indoor and NEMA Type 3R Outdoor Enclosures
e e e e
dcc
cc c
b
bi
ccc
c c
bg
bc
b
e
g
b
b
cc
c
g
e
b
e
g
b
b
cc
c
g
e
e e
ee
g g
dc c
ccc
b
bi
c cc
cc
b
g
bc
dcc
cc c
b
bi
ccc
c c
b
g
b
c
b
e
g
b
b
cc
g
e
e e
ee
g g
b
cc
b
e
g
b
b
cc
c
g
e
bc
dc c
ccc
b
bi
c cc
cc
b
g
bc
dcc
cc c
b
bi
ccc
c c
b
g
b
c
j
k
m
g
a
ac
c
f
f
b b b
bbb
p n
ac
cc
a
c
m
cc
c
cg
g
m
k
j
g g g
c
FlushTrim
3/4
c
h
b
Box 8R (CH8R, CH64R)Box 8 (CH8, CH64)
Box P, PMOutdoor Boxes12-42 CKT 225A Max.
Box B Box C, D, E, G, J, K, L
.450 Dia..450 Dia.
.450 Dia..450 Dia.
.450 Dia..450 Dia.
.450 Dia..450 Dia..450 Dia..450 Dia.
Unit Enclosures Knockouts, Type Knockouts
NEMA Type 1 Indoor (Flush and Surface Trims)
Code Diameter in Inches Diameter in mm
A 1/2 – – – – 12.7 – – – –
B 1-1/4 1-1/2 1-3/4 2 2-1/2 31.7 38.1 44.5 50.8 63.5
B
B
B
B
A
A
B
B
B
B B
B A
B B
HUB
NEMA Type 1 – Indoor NEMA Type 3R – Outdoor
October 1998
CAT.73.01.T.E
Cutler-Hammer B-31Type CH LoadcentersTypical Specifications
General
A. The Contractor shall furnish and install loadcenters incorporating circuit breakers of the number, rating and type as specified herein and as shown on the contract drawings.
B. The loadcenter and all components shall be designed, manufactured and tested in accordance with the latest applicable standards of UL and NEMA including:
1. UL 67 – Standards for Panelboards
2. UL 50 – Standards for Cabinetsand Boxes
3. UL 489 – Standards for Molded Case Circuit Breakers
4. Federal Spec ClassificationW-C 375
Qualifications
A. The manufacturer of the load center shall be the manufacturer of the circuit breaker within the load center. All breakers shall be full size.
B. For the equipment specified herein, the manufacturer shall be ISO 9000 certified.
C. The manufacturer of this equipment shall have produced similar electrical equipment for a minimum period of seven (7) years.
Manufacturers
A. Cutler-Hammer
Ratings
A. Loadcenters shall be rated for 240V AC and shall have short circuit ratings as shown on the drawings or as herein scheduled, but not less than 10,000 amperes RMS symmetrical.
B. Breakers shall be full size and a mini-mum of 125 ampere frame. Breakers 10 through 125 ampere trip size shall take up the same pole spacing.
C. Loadcenters shall be labeled witha UL short circuit rating. When series ratings are applied with integral or remote devices, a label shall be pro-vided. Series ratings shall cover all trip ratings of installed frames. It shall state the conditions of the UL series ratings including:
1. Size and type of upstream device.
2. Branch devices that can be used.
3. UL series short circuit rating.
Construction
A. All interiors, with the exception of the branch circuit breakers shall be com-pletely factory assembled with main breakers, main lugs or no main device.
B. Interiors shall be so designed that cir-cuit breakers can be replaced without disturbing adjacent units and without removing the main bus connectors and shall be so designed that circuits may be changed without machining,drilling, or tapping.
C. Physical means must be provided to prevent the installation of more over-current devices than that number for which the enclosure was designed. Full size breakers are required.
Bus
A. Bus bars for the main and cross con-nectors shall be of copper construc-tion in accordance with Underwriters Laboratories, Inc. standards. Bussing shall be braced to 65 kAIC. All connec-tion points shall be tin-plated copper.
B. Neutral bussing shall have a suitable lug for each outgoing feeder requiring a neutral connection of same ampacity as branch.
Wiring/Termination
A. All wire connectors and terminals shall be of the anti-turn solderless type and suitable for copper or aluminum wire of the sizes indicated. All connec-tors shall meet the “Requirements for Wire Connectors and Soldering Lugs” UL486B.
B. All loadcenters where marked shall be suitable for use with 60/75°C rated wire.
Circuit Breakers
A. Circuit breakers shall be molded case type, 3/4-inch wide per pole. Multi-pole circuit breakers shall be of a stack pole design to provide electrical phase isolation and have an internal com-mon trip.
B. Each pole of the circuit breaker will have inverse time delay overload and instantaneous short circuit protection by means of both thermal and mag-netic sensors. Circuit breakers shall be quick-make/quick-break.
C. The circuit breaker calibration shall not be affected by environmental changes in relative humidity. Breakers shall be calibrated after assembly.
D. All circuit breakers shall be operated by a toggle-type handle and multi-pole circuit breakers shall have an internal common trip mechanism. The circuit breakers shall incorporate trip mecha-nisms that are mechanically trip-free from the handle. The handle position shall provide good visual trip indica-tion.
E. Contacts shall be of non-weldingsilver alloy.
F. All branch breaker handles shall beof a different color than the case ofthe breaker.
G. All terminals shall be listed for use with copper or aluminum conductors. Terminals shall be of the box lug design. The terminals shall meet UL 486B requirements and shall besuitable for use with either 60° or75°C wire.
H. Breakers shall be SWD rated and/or HACR rated as required.
I. Arc Fault Interrupting circuit breakers, (AFI), shall be provided on all 15 and 20 ampere single phase 120/240V AC circuits except those indicated as remote controlled breakers. AFI break-ers shall be “Classified for mitigating the effects of arcing faults,” orconforming to UL Standard 1699 and as defined by per article 210-12Section A of the 1999 NEC Code.
Typical Specifications
CAT.73.01.T.E
Cutler-HammerB-32October 1998
Type CH LoadcentersTypical Specifications
Surge Protection Devices
All 120/240V AC single-phase loadcenters shall have surge protection provided by a [Clipper Home Surge Protector device] [plug in surge protection device]
A. The Clipper Home Surge Protector shall be supplied in its own rugged steel enclosure and must be suitable for flush or surface mounting external of the loadcenter. The device shallprovide surge protection for the load-center as well as protection for:two incoming telephone lines and one incoming coaxial cable. The surge pro-tector shall be installed in accordance to NEC Article 280 and be listed under UL1449, (2nd Edition), and UL497A. The units shall be CSA certified and be tested to meet ANIS/IEEE Category B3 and C3 levels. The surge protector shall incorporate a surge plane design to facilitate a common point of grounding for all connected, power, telephone and coaxial incoming con-ductors. The device shall provide, as a minimum, the following protection:
– Up to 39 kA surge current protec-tion per phase for transients on the incoming AC line
– Up to 10 kA surge protection per pair for telephone lines
– Up to 5 kA line to shield (ground) protection for coaxial conductors
OR
A. The surge protection device becapable of plugging onto a maximum of two adjacent spaces in single-phase loadcenter. The device shall provide, as a minimum, up to 10 kA surgecurrent protection per phase fortransients on the incoming AC line.
B. Surge protection devices must be equipped with LEDs to indicate proper functioning of the internal electronics.
Enclosures
A. Loadcenters shall have NEMA 1general purpose or NEMA 3R rain-proof enclosures as indicated on the drawings and shall be surface or flush mounted except where noted.
B. For indoor applications, enclosures shall be rated NEMA 1. Enclosures shall be manufactured from cold rolled code gauge sheet steel having multiple knockouts and painted per paint specification. For outdoor appli-cations, enclosures shall be rated NEMA 3R. Enclosures shall be manu-factured from galvanized steel which shall be painted per the painted as specified. Enclosures shall be of suffi-cient size to meet or exceed NEC wire bending space.
C. The cover shall have an easy adjust-ment feature for flush applications.
D. Boxes shall be factory assembled into a single rigid structure.
E. Provide circuit breaker marking labels and directories.
Finish
F. Boxes and trims shall be finished with a high scratch-resistant aesthetically pleasing finish. The finish shall poly-urethane coating electrostatically applied to a thickness of 1.8 to 2 mils.
G. All loadcenters shall be provided with provisions for accepting a paintableor wall paperable decorator accessory cover. Where loadcenters are installed in living areas, provide manufacturer designed and tested decoratorcover kits.
Warranty
The minimum warranty for Residential loadcenters, breakers and surge protec-tion devices shall be as follows:
– 15 Years on loadcenter, (20 years if provided with loadcenter manufac-turer’s surge protection device).
– Lifetime warranty on all thermal magnetic and GFCI branch circuit breakers.
– 5 year warranty on all Arc Fault Interrupting Circuit Breakers.
– 5 year warranty on Clipper Home Surge Protector with a 2 year $10K maximum coverage for damaged electrical appliances resulting from a surge.
– 1 year warranty on plug-in surge protection device.