6
UNIT NO. RUNTAL RADIATION SCHEDULE CAPACITY DESIGN BASIS NOTES LOCATION DIMENSIONS LENGTH HEIGHT E.W.T. (degrees F) L.W.T. (degrees F) BTUH PER LINEAR FT FTR-1 FTR-2 FTR-3 SEE PLANS SEE PLANS SEE PLANS 180 150 180 150 180 150 950 11.5" SEE PLANS RUNTAL - RF-5 800 SEE PLANS 500 SEE PLANS 11.5" 6" RUNTAL - UFLT-4 RUNTAL - UFLT-2 MV T HVAC LEGEND AD ACCESS DOOR AFF ABOVE FINISH FLOOR BTUH BRITISH THERMAL UNITS PER HOUR LWT DIA, ø DIAMETER DN DOWN (E) EXISTING EWT ENTERING WATER TEMPERATURE (°F) °F DEGREES FAHRENHEIT HWR HOT WATER RETURN HWS HOT WATER SUPPLY NTS NOT TO SCALE DESCRIPTION PIPING SYMBOL 2-WAY CONTROL VALVE DESCRIPTION PIPING RISE BOTTOM PIPE CONNECTION TOP PIPE CONNECTION PIPING DROP PIPING SYMBOL STRAINER BALANCE VALVE PIPE CAP PIPING REDUCER - CONCENTRIC THERMOSTAT RUNTAL RADIATION WITH ENCLOSURE MANUAL AIR VENT BALL VALVE - OPEN GPM GALLONS PER MINUTE LEAVING WATER TEMPERATURE (°F) HWR M HEATING VALVE (24v CONTROL WIRE ) ALL RUNTAL RADIATORS HWS T ZONE SENSOR RUNTAL RADIATION CONTROL A. RUN CONDITIONS - CONTINUOUS: THE UNIT SHALL RUN CONTINUOUSLY AND SHALL MAINTAIN A HEATINGB SETPOINT OF 70 DEGREE F (ADJ.). B. HEATING VALVE CONTROLLER SHALL MEASURE THE ZONE TEMPERATURE AND MODULATE THE HEATING COIL VALVE TO MAINTAIN ITS HEATING SETPOINT. BALL VALVE STRAINER 2-WAY CONTROL VALVE BALL VALVE BALANCE VALVE AIR VENT RUNTAL RADIATOR. CONTRACTOR RESPONSIBLE FOR PROPER HOT WATER SUPPLY & RETURN CONNECTION TYPES ALL VALVING & CONTROLS TO BE IN CEILING SPACE HOT WATER SUPPLY HOT WATER RETURN REVISIONS DESCRIPTION: ISSUED: SHEET: CONNOR ARCHITECTURE ACCEPTS NO RESPONSIBILITY FOR UNAUTHORIZED REPRODUCTION OR UNAUTHORIZED USE OF THIS DOCUMENT. DRAWINGS ARE FOR GENERAL PURPOSES ONLY. NO MEASUREMENTS SHALL BE SCALED OFF DRAWINGS. ALL MEASUREMENTS SHALL BE VERIFIED IN FIELD. ENGINEER: DRAWN BY: CHECKED BY: 1656 Massachusetts Ave. | Lexington, MA 02420 Tel: 781-652-0114 | connorarchitecture.com ARCHITECT: 49 Court Street | P.O. Box 1980 | Binghamton, NY 13902 Tel: 607-723-9421 | mjinc.com NJDCA ELECTRONIC SUBMITTAL STAMP: SEALED: 3/2 3/2016 3:20: 15 PM M-000 SCHEDULES, DETAILS & CONTROLS 3.24.2016 BID DOCUMENTS RAMAPO COLLEGE OF NEW JERSEY 505 RAMAPO VALLE Y RD. MAHWAH, NJ 07430 18 031.00 CJZ PP RCNJ No.201437.01C ALTERATIONS SCALE - NONE RUNTAL RADIATION CONTROL 2 SCALE - NONE RUNTAL RADIATION DETAIL 1

C:UsersANGELA - DESKTOPDocumentsRamapoCollegePhase2 … · supply 250 12x12 - 12 0.3 ceiling titus spectrum 1 1. neck to be existing branch duct size. titus 300rs 1 d-e supply 1000

  • Upload
    others

  • View
    1

  • Download
    0

Embed Size (px)

Citation preview

UNIT NO.

RUNTAL RADIATION SCHEDULECAPACITY DESIGN BASIS NOTESLOCATION DIMENSIONS

LENGTH HEIGHTE.W.T.

(degrees F)

L.W.T.

(degrees F)

BTUH PERLINEAR FT

FTR-1

FTR-2

FTR-3

SEE PLANS

SEE PLANS

SEE PLANS

180 150

180 150

180 150

950 11.5"SEE PLANS RUNTAL - RF-5

800 SEE PLANS

500 SEE PLANS

11.5"

6"

RUNTAL - UFLT-4

RUNTAL - UFLT-2

MV

T

HVAC LEGEND

AD ACCESS DOOR

AFF ABOVE FINISH FLOOR

BTUH BRITISH THERMAL UNITS PER HOUR

LWT

DIA, ø DIAMETER

DN DOWN

(E) EXISTING

EWT ENTERING WATER TEMPERATURE (°F)

° F DEGREES FAHRENHEIT

HWR HOT WATER RETURN

HWS HOT WATER SUPPLY

NTS NOT TO SCALE

DESCRIPTIONPIPING SYMBOL

2-WAY CONTROL VALVE

DESCRIPTION

PIPING RISE

BOTTOM PIPE CONNECTION

TOP PIPE CONNECTION

PIPING DROP

PIPING SYMBOL

STRAINER

BALANCE VALVE

PIPE CAP

PIPING REDUCER - CONCENTRIC

THERMOSTAT

RUNTAL RADIATION WITH ENCLOSURE

MANUAL AIR VENT

BALL VALVE - OPEN

GPM GALLONS PER MINUTE

LEAVING WATER TEMPERATURE (°F)

HWR

M

HEATING VALVE (24v CONTROL WIRE )

ALL RUNTAL RADIATORS

HWST

ZONE SENSOR RUNTAL RADIATION CONTROL

A. RUN CONDITIONS - CONTINUOUS: THE UNIT SHALL RUN CONTINUOUSLY AND SHALL MAINTAIN AHEATINGB SETPOINT OF 70 DEGREE F (ADJ.).

B. HEATING VALVE CONTROLLER SHALL MEASURE THE ZONE TEMPERATURE AND MODULATE THEHEATING COIL VALVE TO MAINTAIN ITS HEATING SETPOINT.

BALL VALVE

STRAINER

2-WAY CONTROL VALVE

BALL VALVE

BALANCE VALVE

AIR VENT

RUNTAL RADIATOR.CONTRACTOR RESPONSIBLE

FOR PROPER HOT WATER SUPPLY & RETURN CONNECTION TYPES

ALL VALVING & CONTROLSTO BE IN CEILING SPACE

HOT WATER SUPPLY

HOT WATER RETURN

REVISIONS

DESCRIPTION:

ISSUED:

SHEET:

CONNOR ARCHITECTURE ACCEPTS NO RESPONSIBILITY FOR UNAUTHORIZED REPRODUCTION ORUNAUTHORIZED USE OF THIS DOCUMENT.

DRAWINGS ARE FOR GENERAL PURPOSES ONLY. NO MEASUREMENTS SHALL BE SCALED OFF DRAWINGS.ALL MEASUREMENTS SHALL BE VERIFIED IN FIELD.

ENGINEER:

DRAWN BY:

CHECKED BY:

1656 Massachusetts Ave. | Lexington, MA 02420Tel: 781-652-0114 | connorarchitecture.com

ARCHITECT:

49 Court Street | P.O. Box 1980 | Binghamton, NY 13902Tel: 607-723-9421 | mjinc.com

NJDCA ELECTRONIC SUBMITTAL STAMP:

SEALED:

3/2

3/2

01

6 3

:20

: 15 P

M

M-000

SC

HED

ULE

S, D

ET A

ILS &

CO

NTR

OLS

3.24.2016

BID DOCUMENTS

RA

MA

PO

CO

LLEG

E

OF N

EW

JER

SEY

50

5 R

AM

AP

O V

ALL

EY

RD

.M

AH

WA

H, N

J 0

74

30

18

03

1.0

0

CJZ

PP

RC

NJ

No

.201437.0

1C

ALT

ER

ATI

ON

S

SCALE - NONE

RUNTAL RADIATION CONTROL2SCALE - NONE

RUNTAL RADIATION DETAIL1

UNIT

DIFFUSER & REGISTER SCHEDULE

SERVICE MAX. NCFACE

SIZE SIZE

NECK DESIGN

BASIS

NOTESMAX. S.P.

(in. wc.)

ARRANGEMENT

D-A

D-C

18x8 - 15 0.07 DUCT MOUNTEDTITUS SPIRAL S301FL

DOUBLE DEFLECTION

D-D

SUPPLYD-B

0.3 CEILING TITUS SPECTRUMSUPPLY 12x12 10" 12

MAX CFM

300

250

R-A

14x6 CUSTOM 12 0.03 WALLSUPPLY 200 TITUS 300RS

24x24 - 10 0.03 CEILINGEXHAUST 450

0.3 CEILINGSUPPLY 12x12 - 12250 TITUS SPECTRUM

1

1. NECK TO BE EXISTING BRANCH DUCT SIZE.

TITUS 300RS

1

D-E 0.3 WALLSUPPLY 36x12 - 151000 TITUS 300RS 1, 2

2. D-E TO BE FACTORY PAINTED BLACK.

D-E 0.5 CEILINGSUPPLY 48x6 8" PLENUM 20350TITUS FLOW BAR FL15

1.5" SLOT JET3

3. DIFFUSER TO COME WITH CORRESPONDING FACTORY PLENUM & FACE ADJUSTABLE VOLUME DAMPER. CONNECTION FOR GYPSUM BOARD.

ELECTRIC CABINET UNIT HEATER SCHEDULEDESIGN BASISUNIT NO. NOTESLOCATION DIMENSIONS

VOLTS/PHASE

ELECTRICAL

CAPACITY (KW)CAPACITY (BTUH)

CUH-1 MAIN VESTIBULE 36 10,236 3KW 208/1 TRANE - FCEB030

CFM

300 30 10

LENGTH WIDTH HEIGHT HP

1/4

DUCT UP - POSITIVE PRESSURE

DUCT UP - NEGATIVE PRESSURE

DUCT DN - POSITIVE PRESSURE

DUCT DN - NEGATIVE PRESSURE

DUCT BALANCE OR VOLUME DAMPER

RECTANGULAR DUCT WITH TURNING VANES

RADIUS ELBOW (MIN. R/W = 1.5)

EXHAUST REGISTER

SUPPLY DIFFUSER

AIR FLOW

NEW EQUIPMENT

DEMOLITION EQUIPMENT

EXISTING EQUIPMENT TO REMAIN

DUCT SYMBOL DESCRIPTION LINE TYPE SYMBOL DESCRIPTION ABBREVIATION DESCRIPTION

BTU BRITISH THERMAL UNIT

BTUH BRITISH THERMAL UNIT PER HOUR

CFM CUBIC FEET PER MINUTE

CUH CABINET UNIT HEATER

D DIFFUSER

DIA DIAMETER

DN DOWN

DWG DRAWING

(E) EXISTING

EA EXHAUST AIR

EF EXHAUST FAN

HP HORSE POWER

KW KILOWATTS

MBH THOUSAND BTUH

MCA MINIMUM CIRCUIT AMPACITY

MOP MAXIMUM OVER-CURRENT PROTECTION

NTS NOT TO SCALE

R REGISTER

HVAC LEGEND

INSULATED,

FLEXIBLE

DUCT

SUPPLY AIR

DIFFUSER

(TYP.)

1X DUCT DIA. OFFSET (MAX.)

PANDUIT STRAP (TYP.)

DUCT MAIN

SQUARE TO

ROUND

45° BOOT

TAKE-OFF

(TYP.) HARD DUCT ELBOW.MANUAL VOLUME DAMPER

(TYP.)

(TYP.)

CEILING

48" MAX

V.D.

PAINT INSIDE FLAT BLACK

V.D.

DUCT MAIN

BRANCH

SHEET METAL

"PLENUM" BOX

(TYP.) MIN. 6" HIGHER THAN

BRANCH DUCT DEPTH

DUCT MAIN

V.D.

DUCT MAIN

30 DEGREE ANGLE

TOWARDS FLOOR,

AVOID NEW ARCHITECTURAL

CEILING CLOUD.

CAP DUCT END

SUPPLY CEILING DIFFUSER EXHAUST & SUPPLY REGISTER - WALL/CEILING SUPPLY - ROUND DUCT MOUNTED DIFFUSER

DAMPER/REGISTER

CABINET UNIT HEATER CONTROL

A. RUN CONDITIONS - CONTINUOUS: THE UNIT SHALL RUN CONTINUOUSLY AND SHALL MAINTAIN A HEATING SETPOINT OF 70 DEG. F (ADJ.).

B. FAN: THE FAN SHALL RUN ANYTIME THE ZONE TEMPERATURE IS BELOW THE HEATING SETPOINT, UNLESS SHUTDOWN ON SAFETIES.

C. THE HEATING SHALL BE ENABLED WHENEVER:

1. OUTSIDE AIR TEMPERATURE IS LESS THAN 60 DEG. F (ADJ.)

2. ZONE TEMPERATURE IS BELOW HEATING SETPOINT.

D. THE CONTROLLER SHALL MONITOR THE FAN STATUS.

E. ALARMS SHALL BE PROVIDED AS FOLLOWS:

1. FAN FAILURE: COMMAND ON, BUT THE STATUS IS OFF.

2. FAN IN HAND: COMMAND OFF, BUT THE STATUS IS ON.

3. LOW ZONE TEMP.: ID THE ZONE TEMPERATURE IS LESS THAN THE HEATING SETPOINT BY A USER DEFINABLE AMOUNT OF TIME (ADJ.).

TEMPERATURE SENSOR IN

RETURN AIR

ELEC.

CO

IL

CT

M

FAN STATUS

FAN START/STOP

VOLTS/PHASE

FAN SCHEDULE

UNIT NO. AREA SERVED

HP

TYPE DESIGN BASISDRIVE NOTESLOCATION

CONN. POINTS

ELECTRICAL

LENGTH

ROOF OPG. ROOF OPG.

WIDTH

PHYSICAL PROPERTIES

LENGTH" WIDTH" HEIGHT"

SONESFAN SPEEDTOTALC.F.M.

RPMS.P.

PERFORMANCE

WEIGHT LBS.

EF-1 ROOF EXISTING WOK HOOD 2400 3.0 2655 27 460/3 5 1 UTILITY - KITCHEN EXHAUST BELT - - 40 28 32 280 GREENHECK-13-CSW-BI-21-10-I-50 1

NOTES: FAN TO BE CONTROLLED THROUGH EXISTING EXHAUST HOOD CONTROLS. COORDINATE WITH OWNER PRIOR TO EXHAUST FAN REMOVEL.

THIRD LAYER FIRE RATED DUCT WRAP 2", 1" OVERLAP

WING NUTS

ALL THREAD RODS

ACCESS DOOR OPENING

INSULATION PINS - WELDED TO COVER

SPEED CLIPS/WASHERS

SECOND LAYER FIRE RATED DUCT WRAP 2", 1" OVERLAP

CUT EDGES SEALED WITH ALUMINUM FOIL TAPE

FIRST LAYER FIRE RATED DUCT WRAP 2"

9

8

6

7

5

4

3

LEGEND:

2

1

WASHERS10

INSULATION PLATE11

1

2

7

8

9

10

3

4 5 6

11

12

12

13

13

2 LAYERS FIRE RATED DUCT WRAP

PRE-FABRICATED ACCESS DOOR

EXISTING EXHAUST DUCT

FROM KITCHEN HOOD

EXHAUST FAN

DISCHARGE EXTENSION

MINIMUM 80"

DISCHARGE HEIGHT

FLEX CONNECTION

ROOF LINE

EXHAUST FAN

MOTOR COVER ACCESS DOOR

BIRD SCREEN AND RAIN COVER

MODIFY EXISTING

EXHAUST FAN SUPPORTS

AS REQUIRED FOR

NEW EXHAUST FAN

REVISIONS

DESCRIPTION:

ISSUED:

SHEET:

CONNOR ARCHITECTURE ACCEPTS NO RESPONSIBILITY FOR UNAUTHORIZED REPRODUCTION ORUNAUTHORIZED USE OF THIS DOCUMENT.

DRAWINGS ARE FOR GENERAL PURPOSES ONLY. NO MEASUREMENTS SHALL BE SCALED OFF DRAWINGS.ALL MEASUREMENTS SHALL BE VERIFIED IN FIELD.

ENGINEER:

DRAWN BY:

CHECKED BY:

1656 Massachusetts Ave. | Lexington, MA 02420Tel: 781-652-0114 | connorarchitecture.com

ARCHITECT:

49 Court Street | P.O. Box 1980 | Binghamton, NY 13902Tel: 607-723-9421 | mjinc.com

NJDCA ELECTRONIC SUBMITTAL STAMP:

SEALED:

3/2

3/2

01

6 3

:23

: 21 P

M

M-001

MEC

HA

NI C

AL

LEG

EN

DSC

HED

UL E

S D

ET A

ILS &

CO

NTR

OLS

3.24.2016

BID DOCUMENTS

RA

MA

PO

CO

LLEG

E

OF N

EW

JER

SEY

50

5 R

AM

AP

O V

ALL

EY

RD

.M

AH

WA

H, N

J 0

74

30

18

03

1.0

0

CJZ

PP

RC

NJ

No

.201437.0

1C

ALT

ER

ATI

ON

S

SCALE - NONE

DIFFUSERS & REGISTERS DETAIL1

SCALE - NONE

CABINET UNIT HEATER CONTROL4SCALE - NONE

FIRE RATED DUCT ACCESS DOOR DETAIL3SCALE - NONE

EXISTING EXHAUST FAN5

3" = 1'-0"

EXHAUST FAN DETAIL2

1

3

2

1

1

1 1

1

1

1

1

1 1/2"

HWS/R

1"

HWS/R

3/4"

HWS/R

3/4"

HWS/R

5

6

1 1/4"

HWS/R

3/4"

HWS/R

1 1/4"

HWS/R1" HWS/R

3/4"

HWS/R

1"

HWS/R

1"

HWS/R

3/4"

HWS/R

3/4"

HWS/R

7

3/4"

HWS/R

3/4"

HWS/R

8

3/4"

HWS/R

4

4

REMOVE INSULATION

OFF EXISTING SUPPLY

DUCT THAT IS TO BE EXPOSED

68"x14"

40"x14"

20"x14"

26"x14"

16"x12"

16"x12"

12"ø

12"ø

12"ø

12"ø

2

2

DUCTWORK, PIPING & EQUIPMENT TO BE REMOVED

POINT OF DISCONNECTION

EXISTING DUCTWORK, PIPING & EQUIPMENT TO REMAIN

DEMOLITION WORK LEGEND

8

8

7

4

4

EXISTING

HIGH WINDOW

FIN TUBE, VALVES & CONTROLS

TO REMAIN AND REUSED.

MODIFY AS REQUIRED.

EXISTING

HIGH WINDOW

FIN TUBE, VALVES & CONTROLS

TO REMAIN AND REUSED.

MODIFY AS REQUIRED.

7

GENERAL NOTES

DEMOLITION

KEYED NOTES

1. IDENTIFICATION AND/OR ABATEMENT OFHAZARDOUS MATERIALS IS NOT PART OF THIS SCOPEOF WORK. IF ASBESTOS OR OTHER HAZARDOUS

MATERIALS ARE ENCOUNTERED, THE CONTRACTORSHALL NOTIFY THE OWNER IMMEDIATELY.

2. REFER TO SPECIFICATIONS FOR RECYCLING,

CONSTRUCTION WASTE MANAGEMENT ANDDISPOSAL REQUIREMENTS.

3. OPENING IN THE EXISTING STRUCTURE SMALLER THAN12" IN ANY DIRECTION ARE NOT IDENTIFIED ON THESEDRAWINGS. SUBCONTRACTORS SHALL BE

RESPONSIBLE FOR PROVIDING OPENINGS SMALLERTHAN 12" AS REQUIRED FOR INSTALLATION OF THEIR

WORK.4. OPENINGS IN THE EXISTING STRUCTURE SHALL NOT BE

MADE WITHOUT PRIOR APPROVAL OF THE

STRUCTURAL ENGINEER.5. DO NOT REMOVE ITEMS WHICH JEOPARDIZE THE

STRUCTURAL INTEGRITY OF THE BUILDING. IF HIDDENELEMENTS OR DETERIORATED ELEMENTS AREENCOUNTERED, NOTIFY THE ARCHITECT IMMEDIATELY.

6. PROTECT ADJACENT AREAS AND ITEMS "TO REMAIN"DURING DEMOLITION/CONSTRUCTION.

REPAIR/REPLACE ITEMS DAMAGED DURINGCONSTRUCTION.

7. IF UNANTICIPATED HIDDEN ELEMENTS OR

DETERIORATED ELEMENTS ARE ENCOUNTERED, NOTIFYTHE OWNERS REPRESENTATIVE IMMEDIATELY.

REFER TO CONSULTANT DRAWINGS FOR ADDITIONALDEMOLITION WORK.

8. REVIEW w/ OWNER TO DETERMINE WHAT, IF

ANYTHING, WILL BE REMOVED BY OWNER AND WHAT,IF ANYTHING, IS TO BE SALVAGED & TURNED OVERTO OWNER.

D1. REMOVE ALL EXISTING FIN TUBE RADIATION, VALVES ANDCONTROLS.

D2. REMOVE SUPPLY DUCTWORK.

D3. REMOVE EXISTING SUPPLY GRILLE.

D4. EXISTING HWS/R PIPING IN CHASE TO BE REUSED.

D5. EXISTING CABINET UNIT HEATER TO BE REMOVED ANDREUSED. EXISTING HWS/R PIPING, VALVES AND CONTROLS TO

BE REUSED.

D6. REMOVE EXISTING SUPPLY DIFFUSER AND PORTION OFBRANCH DUCT.

D7. EXISTING HWS/R PIPING, VALVES AND CONTROLSSERVING HIGH WINDOW FIN TUBE RADIATION TO REMAIN,

MODIFY AS REQUIRED.

D8. REMOVE SUPPLY DIFFUSER AND BRANCH DUCT BACK TO

MAIN.

REVISIONS

DESCRIPTION:

ISSUED:

SHEET:

CONNOR ARCHITECTURE ACCEPTS NO RESPONSIBILITY FOR UNAUTHORIZED REPRODUCTION ORUNAUTHORIZED USE OF THIS DOCUMENT.

DRAWINGS ARE FOR GENERAL PURPOSES ONLY. NO MEASUREMENTS SHALL BE SCALED OFF DRAWINGS.ALL MEASUREMENTS SHALL BE VERIFIED IN FIELD.

ENGINEER:

DRAWN BY:

CHECKED BY:

1656 Massachusetts Ave. | Lexington, MA 02420Tel: 781-652-0114 | connorarchitecture.com

ARCHITECT:

49 Court Street | P.O. Box 1980 | Binghamton, NY 13902Tel: 607-723-9421 | mjinc.com

NJDCA ELECTRONIC SUBMITTAL STAMP:

SEALED:

3/2

3/2

01

6 3

:28

: 11 P

M

MD-100

DEM

OLI

T IO

N F

IRST

FL O

OR

3.24.2016

BID DOCUMENTS

RA

MA

PO

CO

LLEG

E

OF N

EW

JER

SEY

50

5 R

AM

AP

O V

ALL

EY

RD

.M

AH

WA

H, N

J 0

74

30

18

03

1.0

0

CJZ

PP

RC

NJ

No

.201437.0

1C

ALT

ER

ATI

ON

S

1/8" = 1'-0"

FIRST FLOOR DEMOLITION10 16 248

NORTH

VAV-4 (E)

VAV-5 (E)VAV-3 (E)

VAV-1 (E)

T 1(E)

T2(E)

T3(E)

T4(E)

T5(E)

VAV-2 (E)

VAV-6 (E)

VAV-7 (E)

VAV-10 (E)

VAV-8 (E)

VAV-9 (E)

T 6(E)

T 7(E)

T

8(E)

T 9(E)

T

10(E)

1 1/2"

HWS/R

1 1/2"

HWS/R

(E)

1 1/2"

HWS/R

(E)

T

TT

T

T

T

T

E

E

TE

E

E

E

E

E

1

1

2

2

7

18"x10"

24"x10"

24"x10"

12x10

POINT OF DISCONNECTION

EQUIPMENT TO BE REMOVED

DEMOLITION WORK LEGEND

EQUIPMENT TO REMAIN

3

GENERAL NOTES

DEMOLITION

KEYED NOTES

1. IDENTIFICATION AND/OR ABATEMENT OFHAZARDOUS MATERIALS IS NOT PART OF THIS SCOPEOF WORK. IF ASBESTOS OR OTHER HAZARDOUS

MATERIALS ARE ENCOUNTERED, THE CONTRACTORSHALL NOTIFY THE OWNER IMMEDIATELY.

2. REFER TO SPECIFICATIONS FOR RECYCLING,

CONSTRUCTION WASTE MANAGEMENT ANDDISPOSAL REQUIREMENTS.

3. OPENING IN THE EXISTING STRUCTURE SMALLER THAN12" IN ANY DIRECTION ARE NOT IDENTIFIED ON THESEDRAWINGS. SUBCONTRACTORS SHALL BE

RESPONSIBLE FOR PROVIDING OPENINGS SMALLERTHAN 12" AS REQUIRED FOR INSTALLATION OF THEIR

WORK.4. OPENINGS IN THE EXISTING STRUCTURE SHALL NOT BE

MADE WITHOUT PRIOR APPROVAL OF THE

STRUCTURAL ENGINEER.5. DO NOT REMOVE ITEMS WHICH JEOPARDIZE THE

STRUCTURAL INTEGRITY OF THE BUILDING. IF HIDDENELEMENTS OR DETERIORATED ELEMENTS AREENCOUNTERED, NOTIFY THE ARCHITECT IMMEDIATELY.

6. PROTECT ADJACENT AREAS AND ITEMS "TO REMAIN"DURING DEMOLITION/CONSTRUCTION.

REPAIR/REPLACE ITEMS DAMAGED DURINGCONSTRUCTION.

7. IF UNANTICIPATED HIDDEN ELEMENTS OR

DETERIORATED ELEMENTS ARE ENCOUNTERED, NOTIFYTHE OWNERS REPRESENTATIVE IMMEDIATELY.

REFER TO CONSULTANT DRAWINGS FOR ADDITIONALDEMOLITION WORK.

8. REVIEW w/ OWNER TO DETERMINE WHAT, IF

ANYTHING, WILL BE REMOVED BY OWNER AND WHAT,IF ANYTHING, IS TO BE SALVAGED & TURNED OVERTO OWNER.

D1. REMOVE EXISTING EXHAUST GRILLE AND 2'-0" PORTIONOF EXISTING EXHAUST BRANCH DUCT. PER BASE BID.

D2. REMOVE EXISTING SUPPLY DIFFUSER AND ASSOCIATEDFLEX DUCT. PER BASE BID.

D3. EXISTING CABINET UNIT HEATER TO BE TEMPORARILYDISCONNECTED FROM EXISTING HWS/R PIPING, CONTROLS

AND POWER. EXISTING CABINET UNIT HEATER TO BERELOCATED. MODIFY EXISTING HWS/R PIPING, VALVES &CONTROLS AS REQUIRED AND REUSE.

D4. REMOVE EXISTING 12x10 GREASE EXHAUST DUCT FROM

EXISTING HOOD BACK TO EXTERIOR WALL PENETRATION.PER ADD ALTERNATE-1.

D5. REMOVE EXISTING SUPPLY GRILLE, INSULATE ANDPATCH EXISTING SUPPLY DUCT. PAINT TO MATCH

EXISTING DUCT COLOR. PER ADD ALTERNATE -1.

D6. REMOVE EXISTING GREASE EXHAUST HOOD FAN.

EXISTING CONTROLS AND ROOF SUPPORTS TO REMAINAND BE REUSED. PER ADD ALTERNATE -1.

D7. REMOVE EXISTING SUPPLY GRILLE. PER BASE BID.

18"x10"

24"x10"

24"x10"

12x10

EXISTING HOOD

TO REMAIN

4

5

5

REVISIONS

DESCRIPTION:

ISSUED:

SHEET:

CONNOR ARCHITECTURE ACCEPTS NO RESPONSIBILITY FOR UNAUTHORIZED REPRODUCTION ORUNAUTHORIZED USE OF THIS DOCUMENT.

DRAWINGS ARE FOR GENERAL PURPOSES ONLY. NO MEASUREMENTS SHALL BE SCALED OFF DRAWINGS.ALL MEASUREMENTS SHALL BE VERIFIED IN FIELD.

ENGINEER:

DRAWN BY:

CHECKED BY:

1656 Massachusetts Ave. | Lexington, MA 02420Tel: 781-652-0114 | connorarchitecture.com

ARCHITECT:

49 Court Street | P.O. Box 1980 | Binghamton, NY 13902Tel: 607-723-9421 | mjinc.com

NJDCA ELECTRONIC SUBMITTAL STAMP:

SEALED:

3/2

3/2

01

6 4

:03

: 34 P

M

MD-110

MEC

HA

NI C

AL

DEM

OL I

TIO

N -

FI R

ST

FLO

OR

3.24.2016

BID DOCUMENTS

RA

MA

PO

CO

LLEG

E

OF N

EW

JER

SEY

50

5 R

AM

AP

O V

ALL

EY

RD

.M

AH

WA

H, N

J 0

74

30

18

03

1.0

0

CJZ

PP

RC

NJ

No

.201437.0

1C

ALT

ER

ATI

ON

S

1/8" = 1'-0"

FIRST FLOOR DEMOLITION - BASE BID3

1/8" = 1'-0"

FIRST FLOOR DEMOLITION - ADD ALTERNATE-11

1/8" = 1'-0"

ROOF PLAN DEMOLITION - ADD ALTERNATE-12

6

NORTH

0 16 248

VAV-4 (E)

VAV-5 (E)VAV-3 (E)

VAV-1 (E)

T 1(E)

T2(E)

T3(E)

T4(E)

T5(E)

VAV-2 (E)

VAV-6 (E)

VAV-7 (E)

VAV-10 (E)

VAV-8 (E)

VAV-9 (E)

T 6(E)

T 7(E)

T

8(E)

T 9(E)

T

10(E)

1 1/2"

HWS/R

1 1/4"

HWS/R

3/4"

HWS/R (E)

3/4"

HWS/R (E)

1.5 GPM

3/4"

HWR (E)

UP

1 1/2"

HWS/R

(E)

1 1/2"

HWS/R

(E)

1" HWS/R

DN IN WALL

SERVING FTR-1 & 2

1" HWS/R

DN IN WALL

3.5

FTR-1 (RF-5)

CURVED RUNTAL

WALL HUNG

FTR-1 (RF-5)

CURVED RUNTAL

WALL HUNG (TYP. 3 SECTIONS)

RUN PIPING

BEHIND COLUMN

IN WALL RUN PIPING

BEHIND COLUMN

IN WALL

FTR-3

FTR-3

FTR-2

FTR-3

FTR-3 FTR-3

FTR-3

FTR-3

UFLT-2

UFLT-4 UFLT-4

UFLT-4

UFLT-4

UFLT-4

3/4"

HWR DN

PROVIDE

PIPE CHASE

TO MATCH

ADJACENT WALL

INSTALL 3/4" HWS/R

HIGH AND TIGHT TO

CEILING ALONG WALL

INSTALL 3/4" HWS/R

DN ALONG COLUMN

IN ENCLOSURE

CONNECT NEW FTR-3

TO EXISTING HWS/R DN

IN EXISTING CHASE

CONNECT NEW FTR-3

TO EXISTING HWS/R DN

IN EXISTING CHASE

T

T

T FTR-3

T

T

T

2.5 GPM

2.5 GPM

1 1/4"

HWS/R

S

S

TS

S

S

S

S

T

S

EXISTING HOOD EXHAUST

UP TO EXISTING FANS (TYP. 4)

EXISTING DUCT UP TO

EXISTING MAKE-UP AIR UNIT

PAINT ALL EXISTING

AND NEW EXPOSED DUCT.

COLOR SELECTION

BY ARCHITECT.

1 1/2"

HWS/R

1 1/4"

HWS/R

1" HWS/R

18"x10"

24"x10"

24"x10"

12"x10"

30"x12"

30"x12"30"x22"

30"x14"

26"x14"

26"x14"

40"x14"

68"x20"

14"x8"

300 CFM

300 CFM

300 CFM

300 CFM

EXISTING

HIGH WINDOW

FIN TUBE, VALVES & CONTROLS

TO REMAIN AND REUSED.

MODIFY AS REQUIRED.

EXISTING

HIGH WINDOW

FIN TUBE, VALVES & CONTROLS

TO REMAIN AND REUSED.

MODIFY AS REQUIRED.

3/4"

HWS (E)

UP

1 1/4"

HWS/R

3/4"

HWS/R

1"HWS/R 3/4"

HWS/R

GENERAL NOTES

ADDITION/ALTERATION

KEYED NOTES

1. IDENTIFICATION AND/OR ABATEMENT OFHAZARDOUS MATERIALS IS NOT PART OF THIS SCOPEOF WORK. IF ASBESTOS OR OTHER HAZARDOUS

MATERIALS ARE ENCOUNTERED, THE CONTRACTORSHALL NOTIFY THE OWNER IMMEDIATELY.

2. REFER TO SPECIFICATIONS FOR RECYCLING,

CONSTRUCTION WASTE MANAGEMENT ANDDISPOSAL REQUIREMENTS.

3. OPENING IN THE EXISTING STRUCTURE SMALLER THAN12" IN ANY DIRECTION ARE NOT IDENTIFIED ON THESEDRAWINGS. SUBCONTRACTORS SHALL BE

RESPONSIBLE FOR PROVIDING OPENINGS SMALLERTHAN 12" AS REQUIRED FOR INSTALLATION OF THEIR

WORK.4. OPENINGS IN THE EXISTING STRUCTURE SHALL NOT BE

MADE WITHOUT PRIOR APPROVAL OF THE

STRUCTURAL ENGINEER.5. DO NOT REMOVE ITEMS WHICH JEOPARDIZE THE

STRUCTURAL INTEGRITY OF THE BUILDING. IF HIDDENELEMENTS OR DETERIORATED ELEMENTS AREENCOUNTERED, NOTIFY THE ARCHITECT IMMEDIATELY.

6. PROTECT ADJACENT AREAS AND ITEMS "TO REMAIN"DURING DEMOLITION/CONSTRUCTION.

REPAIR/REPLACE ITEMS DAMAGED DURINGCONSTRUCTION.

7. IF UNANTICIPATED HIDDEN ELEMENTS OR

DETERIORATED ELEMENTS ARE ENCOUNTERED, NOTIFYTHE OWNERS REPRESENTATIVE IMMEDIATELY.

REFER TO CONSULTANT DRAWINGS FOR ADDITIONALDEMOLITION WORK.

8. REVIEW w/ OWNER TO DETERMINE WHAT, IF

ANYTHING, WILL BE REMOVED BY OWNER AND WHAT,IF ANYTHING, IS TO BE SALVAGED & TURNED OVERTO OWNER.

REVISIONS

DESCRIPTION:

ISSUED:

SHEET:

CONNOR ARCHITECTURE ACCEPTS NO RESPONSIBILITY FOR UNAUTHORIZED REPRODUCTION ORUNAUTHORIZED USE OF THIS DOCUMENT.

DRAWINGS ARE FOR GENERAL PURPOSES ONLY. NO MEASUREMENTS SHALL BE SCALED OFF DRAWINGS.ALL MEASUREMENTS SHALL BE VERIFIED IN FIELD.

ENGINEER:

DRAWN BY:

CHECKED BY:

1656 Massachusetts Ave. | Lexington, MA 02420Tel: 781-652-0114 | connorarchitecture.com

ARCHITECT:

49 Court Street | P.O. Box 1980 | Binghamton, NY 13902Tel: 607-723-9421 | mjinc.com

NJDCA ELECTRONIC SUBMITTAL STAMP:

SEALED:

3/2

3/2

01

6 3

:38

: 15 P

M

M-100

FIR

ST

FLO

OR

-A

LTER

ATI

ON

/ AD

DIT

ION

3.24.2016

BID DOCUMENTS

RA

MA

PO

CO

LLEG

E

OF N

EW

JER

SEY

50

5 R

AM

AP

O V

ALL

EY

RD

.M

AH

WA

H, N

J 0

74

30

18

03

1.0

0

CJZ

PP

RC

NJ

No

.201437.0

1C

ALT

ER

ATI

ON

S

1/8" = 1'-0"

FIRST FLOOR - RENOVATION1 0 16 248

NORTH

VAV-4 (E)1.5 gpm

VAV-5 (E)1.5 gpm

VAV-3 (E)1.5 gpm

VAV-1 (E).5 gpm

T 1(E)T

2(E)

T3(E)

T4(E)

T5(E)

VAV-2 (E).5 gpm

VAV-6 (E)1.5 gpm

VAV-7 (E)1 gpm

VAV-10 (E)1 gpm

VAV-8 (E)1 gpm

VAV-9 (E)1.5 gpm

T 6(E)

T 7(E)

T

8(E)

T 9(E)

T

10(E)

1 1/2"HWS/R28 GPM

16"ø

18"ø

D-B300 CFMDUCT MOUNTED(TYP. 16)

D-A250 CFM(TYP. 6)

D-B200 CFM

DUCT MOUNTED(TYP. 4)T

T

T

T

T

T

POINT OF CONNECTION

NEW DUCTWORK & EQUIPMENT

RENOVATION WORK LEGEND

E

TE

E

E

E

E

E

68"x20"

D-E1000 CFM

18"ø

INSTALL DUCTTIGHT TO BEAM

PAINT ALL EXISTINGAND NEW EXPOSED DUCT.COLOR SELECTIONBY ARCHITECT.

CENTER NEW DUCT MAINOVER NEW CEILING

D-C200 CFMWALL MOUNTED

EXISTING GRILLE400 CFM(TYP. 5)

10" DIA.(TYP. 6)

D-D200 CFM(TYP. 2)

R-A300 CFM

R-A450 CFM

CUH-1

PAINT ALL NEW EXPOSED DUCT.COLOR SELECTIONBY ARCHITECT.

PAINT ALL NEW EXPOSED DUCT.COLOR SELECTION

BY ARCHITECT.

EXISTING DUCTWORK & EQUIPMENT

BALANCE DAMPER

EXISTING HOOD EXHAUSTUP TO EXISTING FANS (TYP. 4)

EXISTING DUCT UP TOEXISTING MAKE-UP AIR UNIT

24"x10"

24"x10"

18"x10"

30"x22"

30"x14"

30"x12"

30"x12"

40"x14"

26"x14"

26"x14"

VOLUMEDAMPER

1

2

TE

3

3

4

4

1.5 gpm

1 1/4" HWS/R8 GPM

1 1/4" HWS/R

1.5 gpm

1"HWS/R4.5 GPM

68"x20"

D-E1000 CFM

300 CFM

300 CFM

300 CFM

300 CFM

400 CFM400 CFM

400 CFM400 CFM

400 CFM

350 CFM

350 CFM

3/4" HWS/RDN ALONG COLUMN

36"x8"

36"x18"

VOLUMEDAMPER

VOLUMEDAMPER

VOLUMEDAMPER

GENERAL NOTES

ADDITION/ALTERATION

KEYED NOTES

M1. CABINET UNIT HEATER (CUH-1) TO BE HUNG FROM ROOFSTRUCTURE, FLUSH WITH CEILING. PROVIDE TEMPERATURESENSOR IN RETURN AIR GRILLE PORTION OF CEILING MOUNTED

CABINET UNIT HEATER, COORDINATE WITH LIGHTING ANDSPRINKLER PIPING. INTEGRATE INTO EXISTING BUILDINGMANAGEMENT SYSTEM. PER BASE BID.

M2. EXISTING CABINET UNIT HEATER TO BE TEMPORARILY

DISCONNECTED FROM EXISTING HWS/R, CONTROLS & POWER.EXISTING CABINET UNIT HEATER TO RELOCATED. MODIFY EXISTINGHWS/R PIPING AND CONTROLS AS REQUIRED AND REUSE. PER

BASE BID.

M3. PROVIDE NEW EXHAUST GRILLE (R-A). PROVIDE NEW BRANCHDUCTWORK AS REQUIRED FOR GRILLE TO FIT IN NEW CEILINGGRID. NEW EXHAUST DUCT TO BE SAME SIZE AS EXISTING BRANCH

DUCT. PER BASE BID.

M4. PROVIDE NEW SUPPLY DIFFUSER (D-D). PROVIDE NEWBRANCH DUCTWORK AS REQUIRED FOR DIFFUSER TO FIT IN NEWCEILING GRID. NEW SUPPLY DUCT TO BE SAME SIZE AS EXISTING

BRANCH DUCT. PER BASE BID.

M5. PROVIDE 20x12 GREASE EXHAUST DUCT AND ASSOCIATED FIRERATED DUCT ACCESS DOORS. CONNECT NEW 20x12 DUCT TOEXISTING GREASE EXHAUST HOOD AND EXISTING EXTERIOR 20x12

GREASE EXHAUST DUCT.PER ADD ALTERNATE - 1.

M6. PROVIDE EXHAUST FAN (EF-1). MODIFY EXISTING FANSUPPORT BASE AS REQUIRED TO MOUNT EXHAUST FAN (EF-1)

MAINTAIN ROOF INTEGRITY TO BE WEATHER TIGHT. CONNECTEXISTING WOK EXHAUST HOOD CONTROLS TO NEW EXHAUST FAN(EF-1). PER ADD ALTERNATE-1.

1. IDENTIFICATION AND/OR ABATEMENT OFHAZARDOUS MATERIALS IS NOT PART OF THIS SCOPEOF WORK. IF ASBESTOS OR OTHER HAZARDOUS

MATERIALS ARE ENCOUNTERED, THE CONTRACTORSHALL NOTIFY THE OWNER IMMEDIATELY.

2. REFER TO SPECIFICATIONS FOR RECYCLING,

CONSTRUCTION WASTE MANAGEMENT ANDDISPOSAL REQUIREMENTS.

3. OPENING IN THE EXISTING STRUCTURE SMALLER THAN12" IN ANY DIRECTION ARE NOT IDENTIFIED ON THESEDRAWINGS. SUBCONTRACTORS SHALL BE

RESPONSIBLE FOR PROVIDING OPENINGS SMALLERTHAN 12" AS REQUIRED FOR INSTALLATION OF THEIR

WORK.4. OPENINGS IN THE EXISTING STRUCTURE SHALL NOT BE

MADE WITHOUT PRIOR APPROVAL OF THE

STRUCTURAL ENGINEER.5. DO NOT REMOVE ITEMS WHICH JEOPARDIZE THE

STRUCTURAL INTEGRITY OF THE BUILDING. IF HIDDENELEMENTS OR DETERIORATED ELEMENTS AREENCOUNTERED, NOTIFY THE ARCHITECT IMMEDIATELY.

6. PROTECT ADJACENT AREAS AND ITEMS "TO REMAIN"DURING DEMOLITION/CONSTRUCTION.

REPAIR/REPLACE ITEMS DAMAGED DURINGCONSTRUCTION.

7. IF UNANTICIPATED HIDDEN ELEMENTS OR

DETERIORATED ELEMENTS ARE ENCOUNTERED, NOTIFYTHE OWNERS REPRESENTATIVE IMMEDIATELY.

REFER TO CONSULTANT DRAWINGS FOR ADDITIONALDEMOLITION WORK.

8. REVIEW w/ OWNER TO DETERMINE WHAT, IF

ANYTHING, WILL BE REMOVED BY OWNER AND WHAT,IF ANYTHING, IS TO BE SALVAGED & TURNED OVERTO OWNER.

EXISTING HOOD EXHAUSTUP TO EXISTING FANS (TYP. 4)

24"x10"

24"x10"

18"x10"

30"x12"

20"x12" 5

8"ø8"ø

14"x8"

D-F330 CFM(TYP. 2)

6

REVISIONS

DESCRIPTION:

ISSUED:

SHEET:

CONNOR ARCHITECTURE ACCEPTS NO RESPONSIBILITY FOR UNAUTHORIZED REPRODUCTION ORUNAUTHORIZED USE OF THIS DOCUMENT.

DRAWINGS ARE FOR GENERAL PURPOSES ONLY. NO MEASUREMENTS SHALL BE SCALED OFF DRAWINGS.ALL MEASUREMENTS SHALL BE VERIFIED IN FIELD.

ENGINEER:

DRAWN BY:

CHECKED BY:

1656 Massachusetts Ave. | Lexington, MA 02420Tel: 781-652-0114 | connorarchitecture.com

ARCHITECT:

49 Court Street | P.O. Box 1980 | Binghamton, NY 13902Tel: 607-723-9421 | mjinc.com

NJDCA ELECTRONIC SUBMITTAL STAMP:

SEALED:

3/2

3/2

01

6 4

:09

: 10 P

M

M-110

MEC

HA

NIC

AL

ALT

ER

AT I

ON

S -

FI R

ST

FLO

OR

3.24.2016

BID DOCUMENTS

RA

MA

PO

CO

LLEG

E

OF N

EW

JER

SEY

50

5 R

AM

AP

O V

ALL

EY

RD

.M

AH

WA

H, N

J 0

74

30

18

03

1.0

0

CJZ

PP

RC

NJ

No

.201437.0

1C

ALT

ER

ATI

ON

S

1/8" = 1'-0"

FIRST FLOOR ALTERATION - BASE BID3

1/8" = 1'-0"

FIRST FLOOR ALTERATION - ADD ALTERNATE-11

1/8" = 1'-0"

ROOF PLAN ALTERATION - ADD ALTERNATE-12

NORTH

0 16 248