15
Building Code 2012 International Building Code Building Use Business Risk Category II Vertical Loads Dead Loads at Roof Single Ply membrane and insulation 2 psf Steel Framing 4 psf Collateral 8 psf Dead Loads at Floor 5" Concrete Slab with Deck 50 psf Steel Framing 8 psf Collateral 8 psf Live Loads at Roof Occupancy (Reducible of Area, Slope) 20 psf Live Loads at Floor Offices 50 psf Corridors (first floor) 100 psf Corridors (above first floor) 80 psf Snow Loads Ground Snow Load 10 psf Importance Factor 1.0 Rain on Snow Surcharge 5 psf Design Snow Load (No surcharge) 8.0 psf LATERAL LOADS Wind Loads Velocity (Ultimate Wind Design Speed) 115 mph Exposure B Enclosed Building Internal Pressure Coefficient +/-0.18 Components and Cladding Wall Interior Zones (ht, areas, pressures) 30', 10 sf, 18 psf, -19 psf 30', 100 sf, 15 psf, -17 psf Wall Corner Zones (7'-0" from exterior corners) 30', 10 sf, 18 psf, -24 psf 30', 100 sf, 15 psf, -18 psf Roof Components Loads (6'-0" band) 30', 10 sf, -19 psf (Zone 1), - 33 psf (Zone2), -47 psf (Zone 3) Seismic Loads Importance Factor 1.25 Ss, Short Term Spectral Response 0.28 S1, 1 second Spectral Response 0.11 Site Class (Confirmed) D Response Modification Coefficient (Steel Systems not specifically detailed for Seismic Reinforcing) 3 Spectral Response, Sds 0.29 Spectral Response, Sd1 0.17 Design Category C Analysis Type ELF 03000 FOUNDATIONS: 1. The Contractor shall notify the Structural Engineer of Record (EOR) of any below grade structure which may affect the foundation performance. 2. Foundations shall bear on residual soils or engineered fill capable of supporting an allowable pressure of 3000 psf for column footings. Soils shall be stable, and any expansive, compressible, or shifting material shall be removed to ensure a stable moisture content. 3. Slabs on grade are designed for a modulus of subgrade reaction of 175 pci using a K = 30. 4. Refer to the project Geotechnical Report from Bunnell-Lammons Engineering, Inc. dated Sept. 12, 2014 for fill placement and compaction requirements required to obtain the above listed design parameters. 03300 CAST-IN-PLACE CONCRETE: 1. All concrete work and materials shall be in accordance with ACI 318 2008 and ACI 301. 2. Minimum Material Specifications: a. Portland Cement: ASTM C150, Type 1 b. Fly Ash: ASTM C 618, Type F (limit to 20% of cementitious content) c. Maximum water/cementitious material ratio: 0.5. d. Course Aggregate: ASTM C33. Maximum Aggregate size to be 1" (#57). e. Water: Potable i. No water may be added at the site without consent of the engineer. f. Synthetic Micro fiber: Polypropylene microfiber such as Fiberstrand 100 by Euclid Chemical Company applied at a rate of one pound per cubic yard. Mix for a minimum of three minutes at maximum mixing speed to ensure proper distribution. g. Admixtures: Air-entraining, water-reducing, plasticizing, retarding, and other admixtures will be reviewed for consideration by the contractor. 3. Reinforcing Material Specifications: a. Reinforcing Bars: New billet bars; ASTM A615 Grade 60; deformed. b. Steel Wire: ASTM A82, plain c. Welded Wire Fabric: ASTM A182 Sheet stock only. 4. Related Material Specifications: a. Non-shrink grout for equipment foundations and column bases (as needed) at the Faraday Building. i. ASTM C 1107. ii. Compressive strength of 7000 psi at 28 days. b. Non-shrink grout for precast panel and column baseplate grouting: i. ASTM C 1107. ii. Compressive strength of 5000 psi at 28 days. c. Waterstops: premolded, bentonite type waterstop with 1inch by 3/4 inch profile such as Volclay Waterstop RX by Colloid Environmental Technologies, Inc. 5. Foundations: a. Foundations shall have a 28 day compressive strength of 3000 psi. 6. Foundation Walls. a. Foundation walls shall have a 28 day compressive strength of 4000 psi and shall have an air entraining admixture. b. Walls and slab edges, where permanently exposed to view, shall be free of honeycombing and shall be rubbed with a mixture of sand and cement to provide a uniform appearance in color and texture. 7. Slabs-on-grade: a. Interior slabs-on-grade shall have a 28 day compressive strength of 3000 psi and shall be fiber reinforced. b. Interior slabs to receive a hard steel trowel finish with overall Ff =35 and FL=25, and minimum local values of Ff = 24 and Fl = 17. c. Exterior slabs (under roof or floor) shall have air entraining admixture to provide 6% entrained air. Chamfer all exposed slab edge corners (3/4”). d. Slabs shall be wet cured for a period of seven days. Maintain moisture by ponding, fogging, or by overlaying with polyethylene coated burlap, wetting as needed. e. Vapor barrier under slab shall be a zero permeability barrier, sealing all seams as directed by the manufacturer. f. Provide sawcut control joints or construction joints at 12’-0” (maximum) square pattern (see slab plan for other requirements). Cut 1” joints as soon as possible after finishing (within 8 hours of placement). Construction joints shall be formed by thickening the slab to 8” within 18” of the joint and installing a continuous key or ¾” dowels at 18” o.c. Joint filler specification to be by owner or architect. g. Provide isolation joints at column boxouts, walls, and penetrations. h. Reinforce at all re-entrant corners with no control joints with (2) #3 x 4’-0” long centered on the corner, located in the top of the slab. Reinforce around all pipe or box penetrations greater than 3” with (4) #3 in diamond pattern. i. Specification of exterior concrete paving or sidewalks is by the Civil Engineer. j. Concrete splatter on walls or adjacent slabs shall be removed. 8. Reinforcing Steel: a. All detailing, fabrication, and placing shall be in accordance with ACI 315. b. Reinforcing steel shall be new billet bars conforming to ASTM A615, grade 60. c. Provide 3” concrete cover for all concrete cast against earth. 9. Post-Installed Anchors a. Expansion Anchors to be Hilti Kwik Bolt 3, ITW Redhead Trubolt, or approved equal. Sleeve anchors to be Hilti HLC Sleeve Anchor or ITW Redhead Dynabolt. b. Epoxy or chemical adhesive shall be Ramset Epcon A7 or C6; Hilti HY 150; or Simpson SET Epoxy-TIE. c. Anchors labeled as LDT anchors are to be hot-dip galvanized anchors with cutting threads such as Ramset/Redhead LDT; Simpson Titen HD; or Powers Wedge. 05120 STRUCTURAL STEEL: 1. Design, fabrication and erection of all structural steel shall be in accordance with the AISC Manual of Steel Construction, ASD, Thirteenth Edition. 2. Minimum material specifications: a. W-Structural Steel Shapes: ASTM A992 b. Rolled Steel Floor Plates: ASTM A786 Commercial Grade c. Steel Pipe: ASTM A53 gr. B d. Hollow Structural Sections: ASTM A500 gr. B e. M, S, C, MC, HP Shapes: ASTM A36 f. Plates: ASTM A36 g. Angles: ASTM A36 h. Anchor Rods: ASTM F1554 gr. 36 i. Bolts: ASTM A325N j. Weld Electrodes: AWS E70xx k. Shear Connectors ASTM A108, grades 1015 through 1020, headed stud type l. Non-shrink grout: ASTM C 1107, non metallic – 5000 psi 3. Product Submittals: a. Typical shop fabrication and field erection drawings. i. The field erection drawings should clearly state length and size of field welds of diagonal braces to gussets b. Calculations for braced frames to include weld, gusset, and localized column and beam checks. 4. Provide 2 mils DFT of rust inhibitive primer after power tool cleaning. Provide coating for columns or any other steel below slab such as Sherwin Williams Tar Guard B69B60. 5. Field connections shall be bolted unless shown otherwise on the drawings. Bolted connections shall be made with A325N bolts. Snug-tight connections shall be designed per the fabricator's engineer to resist half of the uniform load given in Table 3-6 in the 13th Edition of AISC "Manual of Steel Construction". 6. Any steel permanently exposed to view such as the canopy frames shall be considered AESS. a. Piece Marks, erection aides, or similar components shall be removed. b. Steel shall be commercial blast cleaned prior to shop priming and one coat of shop paint at the direction of the architect. 7. Post-Installed Anchors a. Expansion Anchors to be Hilti Kwik Bolt 3, ITW Redhead Trubolt, or approved equal. Sleeve anchors to be Hilti HLC Sleeve Anchor or ITW Redhead Dynabolt. b. Epoxy or chemical adhesive shall be Ramset Epcon A7 or C6; Hilti HY 150; or Simpson SET Epoxy-TIE. 8. The fabricator and erector shall include a minimum of 1.5 tons of field weldedmiscellaneous angles, etc. for deck support, openings, etc. which may be added during the course of the project. 05210 STEEL JOISTS: 1. Design, fabrication and erection of all steel joists shall be in accordance with the Steel Joist Institute (SJI). 2. Use special joists at roof top units using the unit layout and weights shown on the structural drawings or on the mechanical drawings. Add unit weights to the K joist design values. 3. Bridging is to be designed and installed per SJI requirements. Anchor by welding to steel beam (per SJI). 4. Joists to be designed for a net uplift of 15 psf at a perimeter band of 20’-0” and 12 psf elsewhere. Provide joist bridging as required and note on erection drawings. 5. Joists shall receive a shop-coat of rust-inhibitive primer (1 mil DFT minimum). 6. Do not weld bottom chord struts or girders or joist bottom chord extensions to stabilizer plates unless noted on the drawings. 7. Hang piping, lights, ceiling, etc. from joists only at panel points. Any point load greater than 100 pounds located between panel points must be accompanied by a chord strengthening detail per the joist shop drawings. 8. Joist vendor to coordinate sprinkler piping from sprinkler contractor’s drawing. 05300 STEEL DECK: 1. Design, fabrication and erection of all steel deck shall be in accordance with the Steel Deck Institute. All welds shall be made following AWS D1.3 specifications by qualified welding operators. 2. Deck Sheet Steel shall conform with ASTM A611 and shall have FM Label attached. 3. Deck Vendor shall supply closures, ridge plates, valley plates, sump pans, etc. necessary to provide a finished roof surface. Deck Vendor shall supply pour stops, closures, and accessories required to provide a finished floor deck surface prior to placing concrete. 4. Deck Sheet shall extend over a minimum of (3) spans of structural steel. 5. Roof deck shall be, 1-1/2" deep, 22 gage, type B, painted, (I) minimum = 0.16 in4/ft., 33 ksi. As a minimum, deck attachment to supports supports shall be made with a 36/4 (12" o.c.) pattern using 5/8" puddle welds. As a minimum, install (2) #10 sidelap screws between all supports. End laps of sheets shall be a minimum of 4” and shall occur over supports. 6. Floor deck shall be 2", 20 gage, factory primed steel deck. Attach to supports at 12" o.c. using 5/8" puddle welds. Sidelap connections shall be (1) #10 screw placed between each support. 01000 GENERAL 1. The structure reflected on the drawings is structurally sound in its completed condition only. The design of any and all temporary shoring and bracing prior to the completed condition shall be the contractor's responsibility. The Structural Engineer of Record (EOR) shall not be responsible for the means, methods, techniques, sequences, procedures nor safety programs which are empolyed by the contractor to build the completed structure. Any deviations from the completed structure represented in the drawings must be submitted to the EOR for approval in writing. 2. The Contractor shall verify all conditions including exsisting structures (above and below grade) and shall notify of the EOR of any discrepancies. The Contractor shall perform all required field measurements. 3. The Sections and Details shown shall be considered to be typical for all similar conditions. The Contractor shall submit written Requests for Information for areas in question. 4. The Contractor shall submit shop drawings for each of the structural components shown on the drawings. Four copies of the shop drawings shall be submitted to the Architect for distribution. 2012 IBC CHAPTER 17 –STRUCTURAL TESTS AND SPECIAL INSPECTIONS The Owner shall engage a special inspection coordinator. Below represents the inspections required for structural elements by Chapter 17 and additional testing needed to assist in Quality Assurance and shall be considered the project's Statement of Special Inspections. STATEMENT OF SPECIAL INSPECTIONS STATEMENT OF SPECIAL INSPECTIONS STATEMENT OF SPECIAL INSPECTIONS STATEMENT OF SPECIAL INSPECTIONS 1. Section 1704 – Special Inspections a. 1704.1.2 Report Requirements i. Special Inspection Reports shall be emailed to the Contractor within one week of performing Tests and/or Inspections. ii. Non-conforming items shall be immediately brought to the attention of the contractor for correction. iii. If non-conforming items are not corrected, the items shall be brought to the attention of the building official and the Design Professional in Responsible Charge prior to completion of that portion of the work and prior to that work being covered. iv. All Inspection Reports shall be compiled by the Contractor and submitted to the Design Professional in Responsible Charge. v. At the Project's completion, the Special Inspection's Coordinator shall issue a final report documenting special inspections were performed per this Statement of Special Inspections and Deficiencies were corrected. a. 1704.2 – Inspection of Fabricators i. Precast Concrete Fabricator shall provide quality control procedures to the special inspector or the fabricator must be certified by the National Precast Concrete Association. b. 1705.2 – Steel Construction i. Welding. 1) Review field welds to ensure welds conform with AWS D1.1. 2) Visually inspect floor and roof deck welds. 3) Test 10% of the field welded connections. ii. Details. 1) Inspect anchor rods for all columns to ensure proper washer and nut installation. 2) Inspect all horizontal and vertical rod bracing to ensure proper tension and nut/bolt installation. 3) Inspect all purlin and girt bolted connections to ensure snug tight condition. iii. High-Strength bolts. 1) Test 10% of high strength bolted connections. 2) Obtain Certificate of Compliance for bolts, nuts, and washers for all types used. c. 1705.3 – Concrete Construction i. The Testing Agency shall inspect foundation reinforcing (size, spacing, and laps) for each set of foundations placed. ii. Obtain mix designs, and ensure each concrete placement uses the approved mix design. iii. The Testing agency shall field sample concrete. The following tests should be performed for each day’s first load and each 100 cubic yards: 1. Weight of concrete, ASTM C 138. 2. Slump, ASTM C 143, 3. If required, Air content of freshly mixed concrete by pressure method, ASTM C 231 or volumetric method, ASTM C 173. 4. Concrete temperature at placement time. 5. Air temperature and weather (windy, cloudy, etc) at placement time. 6. Strength determined in accordance with ASTM C 39. iv. The Testing Agency shall observed curing of slabs, noting weather, techniques, and time of sawcutting slab control joints. e. 1704.7 – Soils i. See geotechnical engineer’s requirements for testing of fill and stone base. CHECKED BY: DRAWN BY: DATE: PROJECT: REVISIONS: MEMBERS OF THE AMERICAN INSTITUTE OF ARCHITECTS 1 A 2 3 4 5 6 B C D E COPYRIGHT 2014 ALL RIGHTS RESERVED PRINTED OR ELECTRONIC DRAWINGS AND DOCUMENTATION MAY NOT BE REPRODUCED IN ANY FORM WITHOUT WRITTEN PERMISSION FROM LS3P ASSOCIATES LTD. TEL. 864.235.0405 FAX 864.233.4027 GREENVILLE, SOUTH CAROLINA 29601 110 WEST NORTH STREET SUITE 300 ISSUE FOR FOUNDATION PERMIT 12.9.14 12/10/2014 1:29:08 PM \\Aa-sbs11\Data\AA\Projects\LS3P\12-LS3P-17-Collab I\Buzzsaw\_Struct Sync Folder\CU-ICAR Research One_Struct_2014.rvt 12-LS3P-17 11.05.2014 WHB AJA GENERAL NOTES & DESIGN CRITERIA S-100 CU-ICAR RESEARCH ONE 12.9.2014 Owner 864.232.7855 (f) 864.233.9383 (t) Greenville, SC 29607 412-B Pettigru Street Arrowood & Arrowood, PC A&A PROJECT #12-LS3P-17 a r r o w o o d a r r o w o o d No. Description Date

C:UsersallanDocumentsCU-ICAR Research One Struct 2014

  • Upload
    others

  • View
    2

  • Download
    0

Embed Size (px)

Citation preview

Building Code2012 International Building Code

Building UseBusiness

Risk Category II

Vertical Loads

Dead Loads at RoofSingle Ply membrane and insulation 2 psfSteel Framing 4 psfCollateral 8 psf

Dead Loads at Floor5" Concrete Slab with Deck 50 psfSteel Framing 8 psfCollateral 8 psf

Live Loads at RoofOccupancy (Reducible of Area, Slope) 20 psf

Live Loads at FloorOffices 50 psfCorridors (first floor) 100 psfCorridors (above first floor) 80 psf

Snow LoadsGround Snow Load 10 psfImportance Factor 1.0Rain on Snow Surcharge 5 psfDesign Snow Load (No surcharge) 8.0 psf

LATERAL LOADS

Wind LoadsVelocity (Ultimate Wind Design Speed) 115 mphExposure BEnclosed BuildingInternal Pressure Coefficient +/-0.18

Components and CladdingWall Interior Zones (ht, areas, pressures)30', 10 sf, 18 psf, -19 psf30', 100 sf, 15 psf, -17 psf

Wall Corner Zones (7'-0" from exterior corners)30', 10 sf, 18 psf, -24 psf30', 100 sf, 15 psf, -18 psf

Roof Components Loads (6'-0" band)30', 10 sf, -19 psf (Zone 1), - 33 psf (Zone2),-47 psf (Zone 3)

Seismic LoadsImportance Factor 1.25Ss, Short Term Spectral Response 0.28S1, 1 second Spectral Response 0.11Site Class (Confirmed) DResponse Modification Coefficient

(Steel Systems not specificallydetailed for Seismic Reinforcing) 3

Spectral Response, Sds 0.29Spectral Response, Sd1 0.17Design Category CAnalysis Type ELF

03000 FOUNDATIONS:

1. The Contractor shall notify the Structural Engineer of Record (EOR) of any below grade structure which may affect the foundation performance.2. Foundations shall bear on residual soils or engineered fill capable of supporting an allowable pressure of 3000 psf for column footings.

Soils shall be stable, and any expansive, compressible, or shifting material shall be removed to ensure a stable moisture content.3. Slabs on grade are designed for a modulus of subgrade reaction of 175 pci using a K = 30.4. Refer to the project Geotechnical Report from Bunnell-Lammons Engineering, Inc. dated Sept. 12, 2014 for fill placement and compaction requirements required to obtain the above listed design parameters.

03300 CAST-IN-PLACE CONCRETE:

1. All concrete work and materials shall be in accordance with ACI 318 2008 and ACI 301.2. Minimum Material Specifications:

a. Portland Cement: ASTM C150, Type 1b. Fly Ash: ASTM C 618, Type F (limit to 20% of cementitious content)c. Maximum water/cementitious material ratio: 0.5.d. Course Aggregate: ASTM C33. Maximum Aggregate size to be 1" (#57).e. Water: Potable

i. No water may be added at the site without consent of the engineer.f. Synthetic Micro fiber: Polypropylene microfiber such as Fiberstrand 100 by Euclid Chemical Company applied at a rate of one pound per cubic yard. Mix for a minimum of three minutes at maximum mixing speed to ensure proper distribution.g. Admixtures: Air-entraining, water-reducing, plasticizing, retarding, and other admixtures will be reviewed for consideration by the

contractor.3. Reinforcing Material Specifications:

a. Reinforcing Bars: New billet bars; ASTM A615 Grade 60; deformed.b. Steel Wire: ASTM A82, plainc. Welded Wire Fabric: ASTM A182 Sheet stock only.

4. Related Material Specifications:a. Non-shrink grout for equipment foundations and column bases (as needed) at the Faraday Building.

i. ASTM C 1107.ii. Compressive strength of 7000 psi at 28 days.

b. Non-shrink grout for precast panel and column baseplate grouting:i. ASTM C 1107.ii. Compressive strength of 5000 psi at 28 days.

c. Waterstops: premolded, bentonite type waterstop with 1inch by 3/4 inch profile such as Volclay Waterstop RX by Colloid Environmental Technologies, Inc.5. Foundations:

a. Foundations shall have a 28 day compressive strength of 3000 psi.6. Foundation Walls.

a. Foundation walls shall have a 28 day compressive strength of 4000 psi and shall have an air entraining admixture.b. Walls and slab edges, where permanently exposed to view, shall be free of honeycombing and shall be rubbed with a mixture of sand and cement to provide a uniform appearance in color and texture.

7. Slabs-on-grade:a. Interior slabs-on-grade shall have a 28 day compressive strength of 3000 psi and shall be fiber reinforced.b. Interior slabs to receive a hard steel trowel finish with overall Ff =35 and FL=25, and minimum local values of Ff = 24 and Fl = 17.c. Exterior slabs (under roof or floor) shall have air entraining admixture to provide 6% entrained air. Chamfer all exposed slab edge corners (3/4”).d. Slabs shall be wet cured for a period of seven days. Maintain moisture by ponding, fogging, or by overlaying with polyethylene coated burlap, wetting as needed.e. Vapor barrier under slab shall be a zero permeability barrier, sealing all seams as directed by the manufacturer.f. Provide sawcut control joints or construction joints at 12’-0” (maximum) square pattern (see slab plan for other requirements). Cut 1” joints as soon as possible after finishing (within 8 hours of placement). Construction joints shall be formed by thickening the slab to 8” within 18” of the joint and installing a continuous key or ¾” dowels at 18” o.c. Joint filler specification to be by owner or architect.g. Provide isolation joints at column boxouts, walls, and penetrations.h. Reinforce at all re-entrant corners with no control joints with (2) #3 x 4’-0” long centered on the corner, located in the top of the slab. Reinforce around all pipe or box penetrations greater than 3” with (4) #3 in diamond pattern.i. Specification of exterior concrete paving or sidewalks is by the Civil Engineer.j. Concrete splatter on walls or adjacent slabs shall be removed.

8. Reinforcing Steel:a. All detailing, fabrication, and placing shall be in accordance with ACI 315.b. Reinforcing steel shall be new billet bars conforming to ASTM A615, grade 60.c. Provide 3” concrete cover for all concrete cast against earth.

9. Post-Installed Anchorsa. Expansion Anchors to be Hilti Kwik Bolt 3, ITW Redhead Trubolt, or approved equal. Sleeve anchors to be Hilti HLC Sleeve Anchor or ITW Redhead Dynabolt.b. Epoxy or chemical adhesive shall be Ramset Epcon A7 or C6; Hilti HY 150; or Simpson SET Epoxy-TIE.c. Anchors labeled as LDT anchors are to be hot-dip galvanized anchors with cutting threads such as Ramset/Redhead LDT; Simpson Titen HD; or Powers Wedge.

05120 STRUCTURAL STEEL:

1. Design, fabrication and erection of all structural steel shall be in accordance with the AISC Manual of Steel Construction, ASD, Thirteenth Edition.2. Minimum material specifications:

a. W-Structural Steel Shapes: ASTM A992b. Rolled Steel Floor Plates: ASTM A786 Commercial Gradec. Steel Pipe: ASTM A53 gr. Bd. Hollow Structural Sections: ASTM A500 gr. Be. M, S, C, MC, HP Shapes: ASTM A36f. Plates: ASTM A36g. Angles: ASTM A36h. Anchor Rods: ASTM F1554 gr. 36i. Bolts: ASTM A325Nj. Weld Electrodes: AWS E70xxk. Shear Connectors ASTM A108, grades 1015 through 1020, headed stud typel. Non-shrink grout: ASTM C 1107, non metallic – 5000 psi

3. Product Submittals:a. Typical shop fabrication and field erection drawings.

i. The field erection drawings should clearly state length and size of field welds of diagonal braces to gussetsb. Calculations for braced frames to include weld, gusset, and localized column and beam checks.

4. Provide 2 mils DFT of rust inhibitive primer after power tool cleaning. Provide coating for columns or any other steel below slab such as Sherwin Williams Tar Guard B69B60.5. Field connections shall be bolted unless shown otherwise on the drawings. Bolted connections shall be made with A325N bolts. Snug-tight connections shall be designed per the fabricator's engineer to resist half of the uniform load given in Table 3-6 in the 13th Edition of AISC "Manual of Steel Construction".6. Any steel permanently exposed to view such as the canopy frames shall be considered AESS.

a. Piece Marks, erection aides, or similar components shall be removed.b. Steel shall be commercial blast cleaned prior to shop priming and one coat of shop paint at the direction of the architect.

7. Post-Installed Anchorsa. Expansion Anchors to be Hilti Kwik Bolt 3, ITW Redhead Trubolt, or approved equal. Sleeve anchors to be Hilti HLC Sleeve Anchor or ITW Redhead Dynabolt.b. Epoxy or chemical adhesive shall be Ramset Epcon A7 or C6; Hilti HY 150; or Simpson SET Epoxy-TIE.

8. The fabricator and erector shall include a minimum of 1.5 tons of field weldedmiscellaneous angles, etc. for deck support, openings, etc. which may be added during the course of the project.

05210 STEEL JOISTS:

1. Design, fabrication and erection of all steel joists shall be in accordance with the Steel Joist Institute (SJI).2. Use special joists at roof top units using the unit layout and weights shown on the structural drawings or on the mechanical drawings. Add unit weights to the K joist design values.3. Bridging is to be designed and installed per SJI requirements. Anchor by welding to steel beam (per SJI).4. Joists to be designed for a net uplift of 15 psf at a perimeter band of 20’-0” and 12 psf elsewhere. Provide joist bridging as required and note on erection drawings.5. Joists shall receive a shop-coat of rust-inhibitive primer (1 mil DFT minimum).6. Do not weld bottom chord struts or girders or joist bottom chord extensions to stabilizer plates unless noted on the drawings.7. Hang piping, lights, ceiling, etc. from joists only at panel points. Any point load greater than 100 pounds located between panel points must be accompanied by a chord strengthening detail per the joist shop drawings.8. Joist vendor to coordinate sprinkler piping from sprinkler contractor’s drawing.

05300 STEEL DECK:

1. Design, fabrication and erection of all steel deck shall be in accordance with the Steel Deck Institute. All welds shall be made following AWS D1.3 specifications by qualified welding operators.2. Deck Sheet Steel shall conform with ASTM A611 and shall have FM Label attached.3. Deck Vendor shall supply closures, ridge plates, valley plates, sump pans, etc. necessary to provide a finished roof surface. Deck Vendor shall supply pour stops, closures, and accessories required to provide a finished floor deck surface prior to placing concrete.4. Deck Sheet shall extend over a minimum of (3) spans of structural steel.5. Roof deck shall be, 1-1/2" deep, 22 gage, type B, painted, (I) minimum = 0.16 in4/ft., 33 ksi. As a minimum, deck attachment to supports supports shall be made with a 36/4 (12" o.c.) pattern using 5/8" puddle welds. As a minimum, install (2) #10 sidelap screws between all supports. End laps of sheets shall be a minimum of 4” and shall occur over supports.6. Floor deck shall be 2", 20 gage, factory primed steel deck. Attach to supports at 12" o.c. using 5/8" puddle welds. Sidelap connections shall be (1) #10 screw placed between each support.

01000 GENERAL

1. The structure reflected on the drawings is structurally sound in its completed condition only. The design of any and all temporary shoring and bracing prior to the completed condition shall be the contractor's responsibility. The Structural Engineer of Record (EOR) shall not be responsible for the means, methods, techniques, sequences, procedures nor safety programs which are empolyed by the contractor to build the completed structure. Any deviations from the completed structure represented in the drawings must be submitted to the EOR for approval in writing.2. The Contractor shall verify all conditions including exsisting structures (above and below grade) and shall notify of the EOR of any discrepancies. The Contractor shall perform all required field measurements.3. The Sections and Details shown shall be considered to be typical for all similar conditions. The Contractor shall submit written Requests for Information for areas in question.4. The Contractor shall submit shop drawings for each of the structural components shown on the drawings. Four copies of the shop drawings shall be submitted to the Architect for distribution.

2012 IBC CHAPTER 17 –STRUCTURAL TESTS AND SPECIAL INSPECTIONS

The Owner shall engage a special inspection coordinator. Below represents the inspections required for structural elements by Chapter 17 and additional testing needed toassist in Quality Assurance and shall be considered the project's Statement of Special Inspections.

STATEMENT OF SPECIAL INSPECTIONSSTATEMENT OF SPECIAL INSPECTIONSSTATEMENT OF SPECIAL INSPECTIONSSTATEMENT OF SPECIAL INSPECTIONS

1. Section 1704 – Special Inspectionsa. 1704.1.2 Report Requirements

i. Special Inspection Reports shall be emailed to the Contractor within one week of performing Tests and/or Inspections.ii. Non-conforming items shall be immediately brought to the attention of the contractor for correction.iii. If non-conforming items are not corrected, the items shall be brought to the attention of the building official and the Design Professional in Responsible Charge prior to completion of that portion of the work and prior to that work being covered.iv. All Inspection Reports shall be compiled by the Contractor and submitted to the Design Professional in Responsible Charge.v. At the Project's completion, the Special Inspection's Coordinator shall issue a final report documenting special inspections were performed per this Statement of Special Inspections and Deficiencies were corrected.

a. 1704.2 – Inspection of Fabricatorsi. Precast Concrete Fabricator shall provide quality control procedures to the special inspector or the fabricator must be certified by the National Precast Concrete Association.

b. 1705.2 – Steel Constructioni. Welding.

1) Review field welds to ensure welds conform with AWS D1.1.2) Visually inspect floor and roof deck welds.3) Test 10% of the field welded connections.

ii. Details.1) Inspect anchor rods for all columns to ensure proper washer and nut installation.2) Inspect all horizontal and vertical rod bracing to ensure proper tension and nut/bolt installation.3) Inspect all purlin and girt bolted connections to ensure snug tight condition.

iii. High-Strength bolts.1) Test 10% of high strength bolted connections.2) Obtain Certificate of Compliance for bolts, nuts, and washers for all types used.

c. 1705.3 – Concrete Constructioni. The Testing Agency shall inspect foundation reinforcing (size, spacing, and laps) for each set of foundations placed.ii. Obtain mix designs, and ensure each concrete placement uses the approved mix design.iii. The Testing agency shall field sample concrete. The following tests should be performed for each day’s first load and each 100 cubic yards:

1. Weight of concrete, ASTM C 138.2. Slump, ASTM C 143,3. If required, Air content of freshly mixed concrete by pressure method, ASTM C 231 or volumetric method, ASTM C 173.4. Concrete temperature at placement time.5. Air temperature and weather (windy, cloudy, etc) at placement time.6. Strength determined in accordance with ASTM C 39.

iv. The Testing Agency shall observed curing of slabs, noting weather, techniques, and time of sawcutting slab control joints.e. 1704.7 – Soils

i. See geotechnical engineer’s requirements for testing of fill and stone base.

CHECKED BY:

DRAWN BY:

DATE:

PROJECT:

REVISIONS:

MEMBERS OF THE AMERICAN INSTITUTE OF ARCHITECTS

1

A

2 3 4 5 6

B

C

D

E

COPYRIGHT 2014 ALL RIGHTS RESERVEDPRINTED OR ELECTRONIC DRAWINGS ANDDOCUMENTATION MAY NOT BE REPRODUCEDIN ANY FORM WITHOUT WRITTEN PERMISSIONFROM LS3P ASSOCIATES LTD.

TEL. 864.235.0405 FAX 864.233.4027

GREENVILLE, SOUTH CAROLINA 29601

110 WEST NORTH STREET SUITE 300

ISS

UE

FO

R F

OU

ND

AT

ION

PE

RM

IT 1

2.9

.14

12/1

0/2

014 1

:29:0

8 P

M

\\A

a-s

bs11\D

ata

\AA

\Pro

jects

\LS

3P

\12-L

S3P

-17-C

ollab

I\B

uzzsaw

\_S

tru

ct

Syn

c F

old

er\

CU

-IC

AR

Researc

h O

ne_S

tru

ct_

2014.r

vt

12-LS3P-17

11.05.2014

WHB

AJA

GENERALNOTES &DESIGNCRITERIA

S-100

CU-ICARRESEARCH ONE

12.9.2014

Owner

864.232.7855 (f)864.233.9383 (t)

Greenville, SC 29607412-B Pettigru Street

Arrowood & Arrowood, PC

A&A PROJECT #12-LS3P-17

a r r o w o o d

a r r o w o o d

No. Description Date

1

1

2

2

3

3

4

4

5

5

6

6

7

7

8

8

9

9

10

10

11

11

A A

BB

C C

C.9 C.9

D D

C7F10 (-2'-0")

F2 (-2'-0")

F2 (

-2'-0")

F2 (

-2'-0")

F2 (-2'-0")

1'-4" THICK ELEVATOR MAT FOUNDATIONREINFORCED WITH #5 AT 12" EW; T&B.8" REINFORCED ELEVATOR PIT WALLS.T/MAT = -4'-0"

A.5

F2 (-2'-0")

C6F10 (-2'-0")

C7F10 (-2'-0")

C1F6 (-2'-0")

C7

C7

C7F12 (-4'-0")PIER(T/PIER = -1'-0")

C7PIER (T/PIER = -2'-0")(6/S-201)

C9

C7PIER (T/PIER = -2'-0")(6/S-201)

C10

C1F6 (-3'-0")PIER (T/PIER= -2'-0")(6/S-201)

C6

C3F9 (-2'-0")

C3F8 (-2'-0")

C3F8 (-2'-0")

C6

C3F8 (-2'-0")

C3F8 (-2'-0")

C6F11 (-2'-0")

C6F10 (-2'-0")

C2F8 (-2'-0")

C6F11 (-2'-0")

C6F11 (-2'-0")

F2 (

-2'-0")

C4F9 (-2'-0")

C2

C6F11 (-2'-0")

SHAFT

ELEVATOR

EL

EV

AT

OR

DO

OR

S

VB

F 1

VB

F 2

VB

F 3

A.2 A.2

C.8

9.1

9.1

2.9

2.9

A'

VB

F 4

C6

C6 F8C (-2'-0")

2'-0" SQUARE BY2'-0" DEEP SUMP

4", 3000 PSI CONCRETE SLAB ON ZEROPERMEABILITY VAPOR BARRIER ON 4"WASHED STONE. REINFORCE WITHWWF6x6-W2.1xW2.1

THICKEN SLAB EDGEAT STOREFRONT

CONCRETE CURBEXTENDING TO +1'-0"

6", 4000 PSI CONCRETE SLABON ZERO PERMEABILITYVAPOR BARRIER ON 4"WASHED STONE. REINFORCEWITH WWF6x6-W2.1xW2.1

HSS6x4x3/8SPREADERBAR

4'-0" WIDE BAND OF CONCRETE

6" THICK, 3000 psiCONCRETE BANDAROUND PERIMETER

15 MIL VAPOR BARRIERON 4" WASHED STONEBASE (T/BASE = -0'-6")

6" THICK, 3000 psiCONCRETE BANDAROUND PERIMETER

3' -

8"

7' -

4"

10' -

0"

18' -

6"

22' -

4"

22' -

3"

13' -

7"

3' -

8"

5' -

0"

1' -

0"

25' - 0" 23' - 5 1/8" 1' - 6 7/8" 25' - 0" 25' - 0" 25' - 0" 25' - 0" 25' - 0" 25' - 0" 1' - 5 3/4" 18' - 6 1/4" 5' - 0" 9' - 1"

25' - 0" 11' - 3" 12' - 2 1/8" 1' - 6 7/8" 25' - 0" 25' - 0" 25' - 0" 25' - 0" 25' - 0" 25' - 0" 1' - 5 3/4" 18' - 6 1/4" 5' - 0" 5' - 7"

3' -

6"

7' -

4 1

/2"

11' -

0"

28' -

6"

22' -

4"

31' -

10 1

/8"

3' -

11 7

/8"

3' -

8"

D.1

2.6

C.5

C2F6 (-2'-0")

F2 (

-2'-0")

F2 (-2'-0")

1' -

6"

D.3

C4F9 (-2'-0")

C4F9 (-2'-0")

C4F9 (-2'-0")

EXISITING RETAINING WALL

C4F8 (-2'-0")

CONCRETE CURB

C4F8 (-2'-0")

12

13

C1F6 (-2'-0")

C4F9 (-2'-0")

10' - 0"

10' -

0"

C2F9 (-2'-0")

C7F12 (-2'-0")

C7F12 (-3'-0")PIER (T/PIER = -2'-0")(6/S-201)

VB

F 5

8' -

0"

8' -

0"

10' - 0" 10' - 0"

8' -

0"

8' -

0"

8' - 0"

7' -

0"

7' -

0"

C5

C5

C2F6 (-2'-0")

C7F12 (-4'-0")PIER(T/PIER = -1'-0")

1' -

8"

TOP OF SLAB REFERENCE ELEVATION = 0'-0"= 901.5' MSL

30" THICK FOUNDATIONT/FOUNDATION = (-2'-0")REINFORCE WITH #7 @ 9" O.C.EACH WAY, TOP AND BOTTOM

30" THICK FOUNDATIONT/FOUNDATION = (-3'-0")REINFORCE WITH #7 @ 9" O.C.EACH WAY, TOP AND BOTTOMPIER (T/PIER = -2'-0") (6/S-201)

30" THICK FOUNDATIONT/FOUNDATION = (-3'-0")REINFORCE WITH #7 @ 9" O.C.EACH WAY, TOP AND BOTTOMPIER (T/PIER = -2'-0") (6/S-201)

30" THICK FOUNDATIONT/FOUNDATION = (-2'-0")REINFORCE WITH #7 @ 9" O.C.EACH WAY, TOP AND BOTTOM

C8F6 (-2'-0")

7

S-200

PRECAST WAINSCOT PRECAST WAINSCOT

F2 (-2'-0")

F2 (-2'-0")F2 (-2'-0")

1' -

4 1

/2"

CU

T S

HE

ET

S

CO

NF

IRM

WIT

H E

LE

VA

TO

R1' -

4"

6' - 11"

THICKEN SLAB UNDER STAIRSTRINGER BEARING TO 10"FOR 2'-0" WIDTH (TYPICAL)

L2x2x1/4 w/ 1/2x6" HEADEDSTUDS @ 12" O.C. (ALLH.D.G.) AT ROLLUP DOORS.

L2x2x1/4 w/ 1/2x6" HEADEDSTUDS @ 12" O.C. (ALLH.D.G.) AT ROLLUP DOORS.

S

S

PRECAST WAINSCOT

POUR CURB AROUND COLUMN, PLACINGVOID FORM OR OTHER ISOLATION MATERIALAROUND COLUMN TO CREATE 1/2" OPENSPACE BETWEEN COLUMN AND CONCRETE.

S-200

8

S-200

8

F2 (-2'-0")

3

S-200

3

S-200

2

S-200

2

S-200

2

S-200

2

S-200

2

S-200

2

S-200

2

S-200

2

S-200

2

S-200

3

S-200

3

S-200

2

S-200

4

S-200

4

S-200

A''

6", 4000 PSI POLISHED CONCRETEWITH WWF6x6-W2.1xW2.1

3

S-200

3

S-200

SIM

SIM

3

S-200

SIM

C.J. C.J.C.J. C.J. C.J. C.J. C.J. C.J. C.J.

C.J.

C.J. C.J. C.J.

C.J.C.J.C.J.

C.J. C.J. C.J.C.J.C.J.C.J.C.J.

6

S-200

9

S-200

VBF 6 VBF 7

VBF 9VBF 8

F8C (-2'-0")

-

---

A.1 A.1

-

---

HSS8x4x1/4 WIND POST HOLD

-

---

-

---

5

S-200

5

S-200

O.H. 5' -

0"

21' -

0"

7 1

/2"

12' - 0" 6"

6"

8"

6"

8"

-

---

7"

2' -

2"

1' - 6" 1' - 6"

1' -

3 1

/2"

5' -

9 1

/2"

6' -

0"

3' -

1"

1' - 0"

1' -

3 1

/2"

7"

1' -

2"

5' - 5"

7"

5"

9' - 6" 5"

1' -

2"

7"

1' -

3 1

/2"1' - 0"

2' -

4 1

/2"

8' -

4 1

/4"

23' - 6" 2' - 7 1/2"

1' - 6" 1' - 6"

10' -

4 1

/2"

5' -

0"

8"

8"

8"

8"

10 7/8"

C.J. C.J. C.J. C.J. C.J. C.J. C.J. C.J. C.J. C.J. C.J. C.J. C.J. C.J.C.J. C.J. C.J.

CONTROL JOINTS TO BESPACED @ 6"-3" O.C. +/- INPERIMETER CONCRETE BAND(TYPCIAL)

C.J. C.J. C.J. C.J. C.J. C.J.

C.J.C.J.C.J.C.J.C.J. C.J. C.J. C.J. C.J.

C.J. C.J.

C.J.

F2

TYPE

FOUNDATION SCHEDULEWIDTH xLENGTH

THICK. REINFORCING

2'-0" x CONTINUOUS 12" (2) #5 CONT.w/#5@32" SW *

F8C 8'-0" x CONTINUOUS 21" #6 @ 9"EACH WAY; TOP & BOTTOM

F10 10'-0" x 10'-0" 24" (12) #8 EACH WAY; TOP & BOTTOM

F11 11'-0" x 11'-0" 30" (16) #8 EACH WAY; TOP & BOTTOM

F1210 12'-0" x 10'-0" 28" (18) #8 EACH WAY; TOP & BOTTOM

F8 8'-0" x 8'-0" 18" (9) #6 EACH WAY; TOP & BOTTOM

F9 9'-0" x 9'-0" 18" (9) #6 EACH WAY; TOP & BOTTOM

F6 6'-0" x 6'-0" 16" (12) #8 EACH WAY; TOP & BOTTOM

F4 4'-0" x 4'-0" 16" (9) #6 EACH WAY; TOP & BOTTOM

F12 12'-0" x 12'-0" 24" (12) #8 EACH WAY; TOP & BOTTOM

F13 13'-0" x 13'-0" 30" (16) #8 EACH WAY; TOP & BOTTOM

1410 14'-0" x 10-0" 28" (18) #8 EACH WAY; TOP & BOTTOM

15 15'-0" x 15'-0" 30" (18) #8 EACH WAY; TOP & BOTTOM

TYPE

COLUMN SCHEDULE

SIZE

NOTES:

1. SEE S-201 FOR ANCHOR ROD DETAILS

C1 W10x33

C2 W10x49

C3 W10x54

C4 W10x60

C5 W12x58

C6 W12x65

C7 W12x72

C8 HSS5x5x3/8

C9 W12x79

C10 W12x87

LEGEND

CX = COLUMN TYPE "X". SEE SCHEDULE

FX(-X-X") =

= FOOTING ELEVATION STEP. SEE A/S-200S

VBF = VERTICAL BRACE FRAME, SEE S-205

FOOTING TYPE "X" WITH TOP OF FOOTINGREFERENCING TOP OF 1ST FLOOR ELEVATION

C.J. = 1 1/2" SAWCUT CONTROL JOINT

CHECKED BY:

DRAWN BY:

DATE:

PROJECT:

REVISIONS:

MEMBERS OF THE AMERICAN INSTITUTE OF ARCHITECTS

1

A

2 3 4 5 6

B

C

D

E

COPYRIGHT 2014 ALL RIGHTS RESERVEDPRINTED OR ELECTRONIC DRAWINGS ANDDOCUMENTATION MAY NOT BE REPRODUCEDIN ANY FORM WITHOUT WRITTEN PERMISSIONFROM LS3P ASSOCIATES LTD.

TEL. 864.235.0405 FAX 864.233.4027

GREENVILLE, SOUTH CAROLINA 29601

110 WEST NORTH STREET SUITE 300

ISS

UE

FO

R F

OU

ND

AT

ION

PE

RM

IT 1

2.9

.14

12/1

0/2

014 1

:29:1

4 P

M

\\A

a-s

bs11\D

ata

\AA

\Pro

jects

\LS

3P

\12-L

S3P

-17-C

ollab

I\B

uzzsaw

\_S

tru

ct

Syn

c F

old

er\

CU

-IC

AR

Researc

h O

ne_S

tru

ct_

2014.r

vt

12-LS3P-17

11.05.2014

AP/WB

ARROWOOD

FOUNDATION/SLABPLAN

S-101

CU-ICARRESEARCH ONE

12.9.2014

Owner

864.232.7855 (f)864.233.9383 (t)

Greenville, SC 29607412-B Pettigru Street

Arrowood & Arrowood, PC

A&A PROJECT #12-LS3P-17

a r r o w o o d

a r r o w o o d

1/8" = 1'-0"S-101

1 FOUNDATION / SLAB PLAN

..COORDINATION

1) ROOF DRAIN LEADERS

2) ELEVATOR CUT SHEETS

3) STOREFRONT / PRECAST SILL

4) DROP FOOTINGS FOR EQUIPMENT

5) TRUCK DOCK AND WALL

No. Description Date

1 Issue for ------ 00-00-0000

1

1

2

2

3

3

4

4

5

5

6

6

7

7

8

8

9

9

10

10

11

11

A A

BB

C C

C.9 C.9

D D

A.5

W18X35 c=3/4"(16) W18X35 c=3/4"(16)

25' - 0" 25' - 0" 25' - 0" 25' - 0" 25' - 0" 25' - 0" 25' - 0" 25' - 0" 20' - 0" 5' - 0"

W18X

35

c=

1 1

/4"

(30)

W18X

35

c=

1 1

/4"

(30)

W18X

35

c=

1 1

/4"

(30)

W30X

148

W24X

84

(25)

W21X

55

(25)

W18X

35

c=

1 1

/4"

(30)

W18X

35

c=

1 1

/4"

(30)

W18X

35

c=

1 1

/4"

(30)

W18X

35

c=

1 1

/4"

(30)

W18X

35

c=

1 1

/4"

(30)

W18X

35

c=

1 1

/4"

(30)

W18X

35

c=

1 1

/4"

(30)

W18X

35

c=

1 1

/4"

(30)

W18X

35

c=

1 1

/4"

(30)

W18X

35

c=

1 1

/4"

(30)

W18X

35

c=

1 1

/4"

(30)

W21X

55

(26)

W18X

35

c=

1 1

/4"

(30)

W18X

35

c=

1 1

/4"

(30)

W21X

55

(26)

W18X

35

c=

1 1

/4"

(30)

W18X

35

c=

1 1

/4"

(30)

W18X

35

c=

1 1

/4"

(30)

W18X

35

c=

1 1

/4"

(30)

W18X

35

c=

1 1

/4"

(30)

W18X

35

c=

1 1

/4"

(30)

W18X

35

c=

1 1

/4"

(30)

W24X

76

(35)

W18X35 c=3/4"(16) W18X35 c=3/4"(16) W18X35 c=3/4"(16) W18X35 c=3/4"(16) W18X40 (22) W18X35 c=3/4"(16)

W16X31

W10X

12

W10X

12

W18X35 c=3/4"(16) W18X35 c=3/4"(16)

W14X

22

(10)

W14X

22

(10)

W14X

22

(10)

W14X

22

(10)

W8X

58

c=

3/4

"(1

8)

W21X62 (48) W21X62 (48) W21X62 (49)

W21X62 (48) W21X62 (48) W21X62 (49)W21X44 (49)

W16X

26

(18)

W14X

22

(18)

W14X

22

(10)

W14X

22

(10)

W14X

22

(10)

W21X

55

(18) W

12X

14

(8)

W21X

55

(18)

W14X

22

(10)

W21X

55

(18)

W21X50 (49)

W21X44 (49) W21X44 (49)

W21X44 (49) W21X44 (49)

W14X

22

(10)

W14X

22

(10)

W14X

22

(10)

W14X

22

(10)

W14X

22

(10)

W18X

35

(8)

W21X

44

c=

1 3

/4"

(54)

W21X

44

c=

1 3

/4"

(54)

W21X

44

c=

1 3

/4"

(54)

W21X

44

c=

1 3

/4"

(54)

W21X

44

c=

1 3

/4"

(54)

W21X

44

c=

1 3

/4"

(54)

W21X

44

c=

1 3

/4"

(54)

W21X

44

c=

1 3

/4"

(54)

W21X

44

c=

1 3

/4"

(54)

W21X

44

c=

1 3

/4"

(54)

W18X

35

c=

1 1

/4"

(26)

W18X

35

c=

1 1

/4"

(26)

W27X

146

c=

1 1

/4"

(16)

W18X

35

c=

1 1

/4"

(26)

W18X

35

c=

1 1

/4"

(26)

W18X

35

c=

1"

(18)

W18X

35

c=

1"

(16)

W21X44 (30)

W18X

35

c=

1 1

/4"

(26)

W18X

35

c=

1 1

/4"

(26)

W18X

35

c=

1 1

/4"

(26)

W18X

35

c=

1 1

/4"

(26)

W21X

44

c=

1 3

/4"

(54)

W21X

44

c=

1 3

/4"

(54)

W21X

44

c=

1 3

/4"

(54)

W21X

44

c=

1 3

/4"

(54)

W10

X49(P

OST)

W10

X49(P

OST)

SHAFT

ELEVATOR

VB

F 1

VB

F 3

TOP OF SLAB ELEVATION = 18'-0"BOTTOM OF DECK ELEVATION = 17'-7"FLOOR SLAB TO BE 5" (3000 PSI) CONCRETE WITHWWF 6x6-W2.9xW2.9 WITH 2"x20 GAGE GALVANIZED(G60) COMPOSITE STEEL DECK.

A.2 A.2

C.8

9.12.9

A'

VB

F 4

W16X

26

(18)

W27X

146

c=

1"

(16)

W21X

44

(18)

(T/B

EA

M =

16

'-5")

W14X61

W14X61

W14X61

W14X61

W14X48

VB

F 2

W16X

36

W14X

22

W18X35

HS

S16X

8X

3/8

CONCRETE FILLED, STEELPAN STAIRS BY MISC.METALS FABRICATOR

CONCRETE FILLED, STEELPAN STAIRS BY MISC.METALS FABRICATOR

W12X

14

(8)

HSS6x4x3/8SPREADERBEAM

D.1

2.6

C.5

D.3

D.3

12

12

13

W21X44 (16) W21X44 (16) W21X44 (16)

(LO

W)

W18X35 c=3/4"(16) W21X44 c=1"(30)

W10

x49

POST F

RO

M W

27

CANTILEVER W27 OVER COLUMN. (2)3/4" FULL DEPTH STIFFENERS IN W27WEB OVER COLUMN (NS,FS) AND ATPOST BEARING (NS, FS)

W10

x49

POST F

RO

M W

27

W18X35

CO

LUM

N B

ELOW

W18X35 W21X50 (48)

CO

LUM

N B

ELOW

MOMENTCONECTED W18X35

MOMENTCONECTEDW18X35

W24X55 c=1"(35)

W12X50

W21X44

MOMENTCONNECTED W21

W27X

146

c=

3/4

"

W10

X49

PO

ST

COLUMN BELOW

CO

LUM

N B

ELOW

VB

F5

W12X35

W12X35

W12X35

W12X35

T/BEAM = 16'-5"BEAM TO BE BELOWCANTILEVERED W14. BEAM TOATTACHED TO THE DROPPEDW27 AND THE CANTILEVEREDEND OF THE W14.

W21X44 (49)

18' -

6"

W16X

36

A''

CO

LUM

N B

ELOW

7

S-202

5

S-204

8

S-202

3

S-204

W18X35 W21X44 (16)

VBF 7

VBF 9

HS

S16X

8X

3/8

VBF 6

VBF 8

14' - 4" 6' - 4"

3

S-205

W12X

14

7

S-202

W21X44

W18X35

MOMENTCONECTED W18X35

A.1 A.1

8

S-202

4' - 9"

9' - 1" 7' - 6"

7

S-203

7

S-203

8

S-203

9

S-203

HOLD DETAILING AROUND STAIR,ELEVATOR, AND MECHANICAL SHAFTS.

(2) 3/4" FULL DEPTH STIFFENERS INW30 WEB OVER COLUMN (NS,FS)AND AT POST BEARING (NS, FS)

9

S-202

SIM

EOS9 1/2"

8

S-203

EOS1' - 8 1/2"

9

S-202

8

S-202

4' - 8"

HSS10x4x1/4 CENTERED FROMCOLUMN. HSS3x3x1/4 KICKER TOSUPPORT EDGE ANGLE.

9

S-202EOS

1' - 3 1/2"

HSS12x6x1/4

HSS12x4x1/4

CANTILEVERW30 OVERCOLUMN

6' - 5" 4' - 7"

W12x14 4' - 6" 4' - 6 7/8" 4' - 6"

HSS12X4X1/4W12x14

5' - 2" W14X

22

EOS5' - 9"

9

S-202

6' -

0"

6' -

0"

6' -

0"

6' -

0"

5' -

6"

5' -

6"

6' -

0"

6' -

0"

6' -

0"

6' -

0"

2' -

11 1

/2"

2' -

11 1

/2"

3' -

6"

6' -

0"

6' -

0"

6' -

0"

6' -

0"

6' -

0"

6' -

0"

4' -

6"

3' -

6"

8' - 4" 8' - 4" 8' - 4"

5' -

11 1

/4"

7' -

0"

7' -

0"

7' -

0"

6' -

0"

6' -

6 3

/4"

HSS10x4x1/4 CENTERED FROMCOLUMN. HSS3x3x1/4 KICKER TOSUPPORT EDGE ANGLE.

-

---

-

---

MOMENTCONNECTED W12(T/W12 = 16'-5")

W14X22

W14 FILLER BEAM ABOVE

10

S-208

11

S-208

BeamClass

W14

End ShearReaction

25 kips

Notes

Composite Beam End Reaction Schedule

1. Fabricator to design beam shear connections for the minimumreaction listed above.

W16 30 kips

W18 35 kips

W21 45 kips

W24 60 kips

W27 85 kips

W30 130 kips

NOTES

1. FLOOR SLAB TO BE 5" (3000 PSI) CONCRETE WITH WWF 6x6-w2.9Xw2.9 WITH2"x20/20 GA GALVANIZED (G60) COMPOSITE STEEL DECK.

LEGEND

C = CAMBER IN BEAM(X) = X NUMBER OF 3/4"x5" HEADED STUDS. SEE S204

= MOMENT CONNECTION. SEE 5/S201

VBF = VERTICAL BRACED FRAME. SEE S205

XX k-ft = END MOMENT FOR MOMENT CONNECTION DESIGNS

= 1 1/2"x22 GAGE, TYPE B STEEL DECK

CHECKED BY:

DRAWN BY:

DATE:

PROJECT:

REVISIONS:

MEMBERS OF THE AMERICAN INSTITUTE OF ARCHITECTS

1

A

2 3 4 5 6

B

C

D

E

COPYRIGHT 2014 ALL RIGHTS RESERVEDPRINTED OR ELECTRONIC DRAWINGS ANDDOCUMENTATION MAY NOT BE REPRODUCEDIN ANY FORM WITHOUT WRITTEN PERMISSIONFROM LS3P ASSOCIATES LTD.

TEL. 864.235.0405 FAX 864.233.4027

GREENVILLE, SOUTH CAROLINA 29601

110 WEST NORTH STREET SUITE 300

ISS

UE

FO

R F

OU

ND

AT

ION

PE

RM

IT 1

2.9

.14

12/1

0/2

014 1

:29:1

7 P

M

\\A

a-s

bs11\D

ata

\AA

\Pro

jects

\LS

3P

\12-L

S3P

-17-C

ollab

I\B

uzzsaw

\_S

tru

ct

Syn

c F

old

er\

CU

-IC

AR

Researc

h O

ne_S

tru

ct_

2014.r

vt

12-LS3P-17

11.05.2014

AP/WB

ARROWOOD

SECONDFLOORFRAMING PLAN

S-102

CU-ICARRESEARCH ONE

12.9.2014

Owner

1/8" = 1'-0"S-102

1 SECOND FLOOR FRAMING PLAN

864.232.7855 (f)864.233.9383 (t)

Greenville, SC 29607412-B Pettigru Street

Arrowood & Arrowood, PC

A&A PROJECT #12-LS3P-17

a r r o w o o d

a r r o w o o d

.. PRICING NOTES

1) ELEVATOR STEEL - ASSUME HSS5x5x1/4 ELEVATOR GUIDERAIL BRACKET SUPPORT POSTS, (3) TOTAL. ASSUME FIELDWELDED PLATE 1"x8x1'-4" FOR CONNECTION OF BRACKET TO BE SPACED @ 12'-0" O.C. ALSO ASSUME W8x24 HOIST BEAMS.

2) EDGES - TYPICAL SLAB EDGE TO BE BENT PLATE 1/4 w/ 3/4"x8" H.S. @ 12" O.C. PROVIDE L2 KICKERS @ 4'-0" O.C. FORBENT PLATE SUPPORT.

COORDINATION

1) OPENING IN BEAMS FOR CONDUIT ROUTING

No. Description Date

1

1

2

2

3

3

4

4

5

5

6

6

7

7

8

8

9

9

10

10

11

11

A A

BB

C C

C.9C.9

D D

A.5

W18X

35

W18X

35

W18X35 c=3/4"(16) W18X35 c=3/4"(16) W18X35 c=3/4"(16)W

18X

35

c=

1 1

/4"

(30)

W18X

35

c=

1 1

/4"

(30)

W18X

35

c=

1 1

/4"

(30)

W18X

35

c=

1 1

/4"

(30)

W18X

35

c=

1 1

/4"

(30)

W18X

35

c=

1 1

/4"

(30)

W18X35 c=3/4"(16) W18X35 c=3/4"(16)

W21X44 (49)

W18X35 c=3/4"(16) W18X35 c=3/4"(16)

W21X55 (48)W21X62 (48)

W18X

35

c=

1 1

/4"

(30)

W18X

35

c=

1 1

/4"

(30)

W18X

35

c=

1 1

/4"

(30)

W18X

35

c=

1 1

/4"

(30)

W18X

35

c=

1 1

/4"

(30)

W18X

35

c=

1 1

/4"

(30)

W18X

35

c=

1 1

/4"

(30)

W18X

35

c=

1 1

/4"

(30)

W18X

35

c=

1 1

/4"

(30)

W18X

35

c=

1 1

/4"

(30)

W18X

35

c=

1 1

/4"

(30)

W21X

55

(26)

W18X

35

c=

1 1

/4"

(30)

W18X

35

c=

1 1

/4"

(30)

W21X

55

(26)

W18X

35

c=

1 1

/4"

(30)

W18X

35

c=

1 1

/4"

(30)

W18X

35

c=

1 1

/4"

(30)

W18X

35

c=

1 1

/4"

(30)

W18X40 (22) W18X35 c=3/4"(16)W18X35 c=3/4"(16)

W21X55 (49) W21X44 (49)

W21X44 (49)

W24X55 (35)

W24X

76

(35)

W18X

35

c=

1 1

/4"

(30)

W21X44 (49)

W14X

22

(10)

W14X

22

(10)

W14X

22

(10)

W14X

22

(10)

W18X

35

(10)

W16X

26

(8)

W14X

22

(10)

W14X

22

(10)

W14X

22

(10)

W14X

22

(10)

W18X

35

(10)

W21X55 (48)W21X55 (48)W21X55 (48)W21X50 (48)

W18X

35

(10)

W14X

22

(10)

W18X

35

(10)

W21X50 (48)

W14X

22

(10)

W14X

22

(10)

W14X

22

(10)

W14X

22

(10)

W14X

22

(10)

W18X

35

(10)

W21X44 (49) W21X44 (49)

W21X

44

c=

1 1

/2"

(54)

W21X

44

c=

1 1

/2"

(54)

W21X

44

c=

1 1

/2"

(54)

W21X

44

c=

1 1

/2"

(54)

W21X

44

c=

1 1

/2"

(54)

W21X

44

c=

1 1

/2"

(54)

W21X

44

c=

1 1

/2"

(54)

W21X

44

c=

1 1

/2"

(54)

W21X

44

c=

1 1

/2"

(54)

W21X

44

c=

1 1

/2"

(54)

W21X

44

c=

1 1

/2"

(54)

W21X

44

c=

1 1

/2"

(54)

W21X

44

c=

1 1

/2"

(54)

W21X

44

c=

1 1

/2"

(54)

W18X

35

c=

1 1

/4"

(26)

W18X

35

c=

1 1

/4"

(26)

W18X

35

c=

1 1

/4"

(26)

W18X

35

c=

1 1

/4"

(26)

W18X

35

c=

1 1

/4"

(26)

W18X

35

c=

1 1

/4"

(26)

W21X44 (30)

W18X

35

c=

1 1

/4"

(26)

W18X

35

c=

1 1

/4"

(26)

W18X

35

c=

1 1

/4"

(26)

W18X

35

c=

1"

(26)

W18X

35

(13)

W21X44 c=1"(30)W21X44 c=1"(30)

W16X31

W10X

12

W10X

12

SHAFT

ELEVATOR

VB

F 1

VB

F 3

TOP OF SLAB ELEVATION = 32'-0"BOTTOM OF DECK ELEVATION = 31'-7"FLOOR SLAB TO BE 5" (3000 PSI) CONCRETE WITHWWF 6x6-W2.9xW2.9 WITH 2"x20 GAGE GALVANIZED(G60) COMPOSITE STEEL DECK.

A.2 A.2

C.8

9.12.9

A'

W18X

35

(10)

W16X26

W12X

14

(8)

W18X

35

c=

3/4

"(1

3)

VB

F 4

W27X

161

c=

1"

(T/B

EA

M =

31

' - 5

")

W12X50

W14X

22

VB

F 2

CONCRETE FILLED, STEELPAN STAIRS BY MISC.METALS FABRICATOR

CONCRETE FILLED, STEELPAN STAIRS BY MISC.METALS FABRICATOR

W12X

14

(8)

HSS6x4x3/8SPREADERBEAM

D.1

2.6

C.5

D.3

12

13

W18X35

W18X35

MOMENT CONNECT W18X35

MOMENT CONNECT W18X35

W16X

26

MOMENTCONNECTED W21

MOMENTCONNECTED W12(T/W12 = 30'-5")

4' - 5" 4' - 7" 4' - 6" 7' - 8"

4' - 5"

VB

F5

W14X90

W14X74

W14X61

W14X74

W12X35

W12X50

W12X50

W12X50

T/BEAM = 30'-5"BEAM TO BE BELOWCANTILEVERED W14. BEAM TOATTACHED TO THE DROPPEDW27 AND THE CANTILEVEREDEND OF THE W14.

W14X48

W16X

36

W16X

36

A''

5

S-204

4

S-202

5

S-2024

S-202

SIM

3

S-204

W21X44 (16) W21X44 (16) W21X44 (16) W21X44 (16)

VBF 7

VBF 9

HS

S16X

8X

3/8

HS

S16X

8X

3/8

VBF 6

VBF 8

W21X44

W14X48

14' - 4" 6' - 5" 3' - 4"

W12X

14

W12X50

W18X35

A.1 A.1

4' - 1"

4

S-203

4

S-203

5

S-202

5

S-203

5

S-203

6

S-203

6

S-203

SIM

2

S-205

HOLD DETAILING AROUND STAIR,ELEVATOR, AND MECHANICAL SHAFTS.

4' - 8"

SIM

SECTION CUT APPLIS FROMCOLUMN LINE 1 TO 22'-11"EAST OF COLUMN LINE 1

W12x14HSS12x4x1/4 BAND

2' -

11 1

/2"

5' -

6"

6' -

0"

6' -

0"

6' -

0"

6' -

0"

3' -

6"

8' - 4" 8' - 4" 8' - 4"

1' -

7"

4' -

8"

6' -

10"

6' -

11"

6' -

11"

6' -

7"

6' -

0"

-

---

W14X22

W14 FILLER BEAM ABOVE

12

S-208

13

S-208

BeamClass

W14

End ShearReaction

25 kips

Notes

Composite Beam End Reaction Schedule

1. Fabricator to design beam shear connections for the minimumreaction listed above.

W16 30 kips

W18 35 kips

W21 45 kips

W24 60 kips

W27 85 kips

W30 130 kips

NOTES

1. FLOOR SLAB TO BE 5" (3000 PSI) CONCRETE WITH WWF 6x6-w2.9Xw2.9 WITH2"x20/20 GA GALVANIZED (G60) COMPOSITE STEEL DECK.

LEGEND

C = CAMBER IN BEAM(X) = X NUMBER OF 3/4"x5" HEADED STUDS. SEE S204

= MOMENT CONNECTION. SEE 5/S201

VBF = VERTICAL BRACED FRAME. SEE S205

XX k-ft = END MOMENT FOR MOMENT CONNECTION DESIGNS

= 1 1/2"x22 GAGE, TYPE B STEEL DECK

CHECKED BY:

DRAWN BY:

DATE:

PROJECT:

REVISIONS:

MEMBERS OF THE AMERICAN INSTITUTE OF ARCHITECTS

1

A

2 3 4 5 6

B

C

D

E

COPYRIGHT 2014 ALL RIGHTS RESERVEDPRINTED OR ELECTRONIC DRAWINGS ANDDOCUMENTATION MAY NOT BE REPRODUCEDIN ANY FORM WITHOUT WRITTEN PERMISSIONFROM LS3P ASSOCIATES LTD.

TEL. 864.235.0405 FAX 864.233.4027

GREENVILLE, SOUTH CAROLINA 29601

110 WEST NORTH STREET SUITE 300

ISS

UE

FO

R F

OU

ND

AT

ION

PE

RM

IT 1

2.9

.14

12/1

0/2

014 1

:29:1

9 P

M

\\A

a-s

bs11\D

ata

\AA

\Pro

jects

\LS

3P

\12-L

S3P

-17-C

ollab

I\B

uzzsaw

\_S

tru

ct

Syn

c F

old

er\

CU

-IC

AR

Researc

h O

ne_S

tru

ct_

2014.r

vt

12-LS3P-17

11.05.2014

AP/WB

ARROWOOD

THIRD FLOORFRAMING PLAN

S-103

CU-ICARRESEARCH ONE

12.9.2014

Owner

864.232.7855 (f)864.233.9383 (t)

Greenville, SC 29607412-B Pettigru Street

Arrowood & Arrowood, PC

A&A PROJECT #12-LS3P-17

a r r o w o o d

a r r o w o o d

1/8" = 1'-0"S-103

1 THIRD FLOOR FRAMING PLAN

PRICING NOTES

1) ELEVATOR STEEL - ASSUME HSS5x5x1/4 ELEVATOR GUIDERAIL BRACKET SUPPORT POSTS, (3) TOTAL. ASSUME FIELDWELDED PLATE 1"x8x1'-4" FOR CONNECTION OF BRACKET TO BE SPACED @ 12'-0" O.C. ALSO ASSUME W8x24 HOISTBEAMS.

No. Description Date

1

1

2

2

3

3

4

4

5

5

6

6

7

7

8

8

9

9

10

10

11

11

A A

B B

C C

C.9 C.9

D D

A.5

W18X35

W18X

35

c=

3/4

"

W18X

35

c=

3/4

"

W18X

35

c=

3/4

"

W18X

35

c=

3/4

"

W18X

35

c=

3/4

"

W18X35

W18X35 W18X35

W18X

35

W18X

35

W14X22 W14X22 W14X22

W21X44 (25) W21X62 (25) W21X44 (25)

W14X22

W21X55 (49)

W18X40

W18X35 (20) W24X55 (35)

W18X

35

c=

1 1

/4"

(26)

W18X

35

c=

1 1

/4"

(26)

W18X

35

c=

1 1

/4"

(26)

W18X

35

c=

1"

(16)

W18X

35

c=

1"

(16)

W21X44 (49) W21X44 (25) W24X55 (30)W

14X

30

W18X

35

(10)

W14X

22

(10)

W14X

22

(10)

W21X44 (25)

W16X

26

(10)

W16X

31

(10)

W18X

35

(10)

W14X

22

(10)

W14X

22

(10)

W14X

22

(10)

W14X

22

(10)

W18X

35

(10)

W14X

22

(10)

W16X

31

(10)

W14X

22

(10)

W14X

22

(10)

W18X

35

(10)

W14X

22

(10)

W14X

22

(10)

W21X44 (25) W24X55 (30)W21X44 (25)

W16X

26

(8)

W18X

35

c=

1"

(16)

W18X

35

c=

1 1

/4"

(26)

W18X

35

c=

1 1

/4"

(26)

W18X

35

c=

1 1

/4"

(26)

W24X

131

c=

1"

W27X

146

c=

1"

W24X

131

c=

1"

W27X

146

c=

1"

W27X

146

c=

1 1

/4"

W27X

146

c=

1 1

/4"

W24X

55

c=

1 1

/2"

W27X

146

c=

1"

HANGER AND KICKERFOR SUPPORT OF HSS8

SHAFT

ELEVATOR

VB

F 1

VB

F 3

W21X55 (25) W21X44 (25) W21X50 (25)

TOP OF SLAB ELEVATION = 46'-10"BOTTOM OF DECK ELEVATION = 46'-5"TOP OF DROPPED BEAMS = 44'-11" U.N.O.FLOOR SLAB TO BE 5" (3000 PSI) CONCRETE WITHWWF 6x6-W2.9xW2.9 WITH 2"x20 GAGE GALVANIZED(G60) COMPOSITE STEEL DECK.

A.2 A.2

C.8

9.12.9

A'

W18X

35

c=

1"

(26)

W16X

26

(10)W

18X

35

(10)

W12X

14

W18X35

VB

F 4

VB

F 2

HSS8X4X1/4

(43'-7")

CONCRETE FILLED, STEELPAN STAIRS BY MISC.METALS FABRICATOR

CONCRETE FILLED, STEELPAN STAIRS BY MISC.METALS FABRICATOR

DROPPED DROPPED DROPPED DROPPED DROPPED DROPPED DROPPED DROPPED

DR

OP

PE

D

DR

OP

PE

D

DR

OP

PE

D

DR

OP

PE

D

DR

OP

PE

D

DROPPED

DR

OP

PE

D

DR

OP

PE

D

DR

OP

PE

D

DROPPED

DR

OP

PE

D

DR

OP

PE

D

DR

OP

PE

D

DR

OP

PE

D

DR

OP

PE

D

DROPPED W24X55 (30)DROPPED

DROPPED

DROPPED

DR

OP

PE

DD

RO

PP

ED

DR

OP

PE

D

DROPPED DROPPED

DR

OP

PE

D

DR

OP

PE

D

DR

OP

PE

D

DR

OP

PE

D

DR

OP

PE

D

BE

LO

W W

10

X1

2

DROPPED W14X22

W14X22DROPPED

DECK SUPPORTANGLE IN WEB ALONGCOLUMN LINE 3

DECK SUPPORTANGLE IN WEB ALONGCOLUMN LINE 9

W16X

36

W16X

36

W16X

36

W16X

36

DR

OP

PE

D

DR

OP

PE

D

DROPPED

W18X35 (20)

DR

OP

PE

D

DR

OP

PE

D

DR

OP

PE

D

DR

OP

PE

D

DR

OP

PE

D

DR

OP

PE

D

DR

OP

PE

D

W12X

14

HSS6x4x3/8SPREADERBEAM

D.1

2.6

C.5

D.3

12

13

MOMENT CONNECTED W18X35

MOMENT CONNECTED W18X35

MOMENT CONNECTED W18X35

MOMENT CONNECTED W18X35

VB

F5

W18X35

W14X22

W14X22

W14X22W14X22

W14X22

W14X22

W18X35

W14X22

W14X22

W14X22

W18X35

W14X22

W14X22

W14X22

W18X35

W14X22

W14X22

W14X22

W18X35

W14X22

W14X22

W14X22

W18X35

W24X

131

c=

1"

W24X

131

c=

1"

W24X

131

c=

1"

W24X

131

c=

1 1

/4"

W24X

131

c=

1 1

/4"

W24X

131

c=

1"

DR

OP

PE

D

DR

OP

PE

D

DR

OP

PE

D

DR

OP

PE

D

DR

OP

PE

D

DR

OP

PE

D

W18X35

W14X22

W14X22

W14X22W14X22

W14X22

W14X22

W16X50 (20)

W14X22

W14X22

W14X22

W18X35

W14X22

W14X22

W14X22

W18X35

W14X22

W14X22

W14X22

W18X35

W14X22

W14X22

W14X22 (20)

W18X35

A''

W14X22W14X22 W14X22 W14X22 W14X22 W14X22 (10)DROPPEDDROPPEDDROPPED DROPPED DROPPED

POST

UP

POST

UP

POST

UP

POST

UP

POST

UP

POST

UP

HSS6x

6x1/

4

POST

UP

POST

UP

HSS6x

6x1/

4

POST

UP

POST

UP

POST

UP

POST

UP

POST

UP

HSS6x

6x3/

8

POST

UP

1

S-202

2

S-2023

S-202

6

S-202

ROOF DECK FLOOR DECK

6

S-208

1

S-208

2

S-208

3

S-208

4

S-208

5

S-208

1

S-204

HSS6x

6x1/

4

HSS6x

6x1/

4

HSS6x

6x1/

4

HSS6x

6x1/

4

HSS6x

6x1/

4

HSS6x

6x1/

4

HSS6x

6x1/

4

HSS6x

6x1/

4

HSS6x

6x1/

4

HSS6x

6x1/

4

45' -

6"

W10X12DROPPED

W10X12DROPPED

W10X12DROPPED

W10X12DROPPED

W10X12DROPPED

W10X12DROPPED

W10X12DROPPED

W16X26 W16X26 W16X26 W16X26 W14X

22

W14X22

W14X22

DROPPED

DROPPED

W14X22

W14X22

DROPPED

DROPPED

W14X22

W14X22

DROPPED

DROPPED

W14X22

W14X22

DROPPED

VBF 7

VBF 9

DROPPED W18X35 (20)

ROOF DECK FLOOR DECK

W14X22 (10)DROPPED

W18X35

DR

OP

PE

D

DR

OP

PE

D

7' -

4 1

/2"

8' -

7 1

5/1

6"

DROPPED

7' - 8 13/16" 7' - 8 13/16" 7' - 8 7/8"

HS

S16X

8X

3/8

DROPPEDDROPPEDDROPPED

DROPPED W16X26

VBF 6

VBF 8

HSS8x8x1/4HSS8x8x1/4HSS8x8x1/4HSS8x8x1/4HSS8x8x1/4HSS8x8x1/4

A.1 A.1

4' - 3"

3' - 2 1/2"

1

S-203

1

S-202

2

S-202

2

S-203

3

S-203

W18X

35

1

S-205

HOLD DETAILING AROUND STAIR,ELEVATOR, AND MECHANICAL SHAFTS.

W12X14

3' - 2 1/2"

1' - 2 1/2"

4' - 7"

HSS12x4x1/4CANTILEVEREDOFF COLUMN

HSS12x4x1/4WHERE SHOWN

W12x14

6' - 0"

W12x14 @ 6'-0" O.C. (TYPICAL)

6' - 10"

HSS12x4x1/4 FROM COLUMNLINE 11 TO EAST EXTENTS

HSS12x4x1/4

2' -

11 1

/2"

6' - 0" 6' - 0" 6' - 0" 6' - 0" 6' - 0" 6' - 0" 6' - 0" 6' - 0" 6' - 0" 6' - 0" 6' - 0" 6' - 0" 6' - 0" 6' - 0" 6' - 0" 6' - 0" 6' - 0" 6' - 0" 6' - 0" 6' - 0" 6' - 0" 6' - 0" 6' - 0" 6' - 0" 6' - 0" 6' - 0"

2' -

11 1

/2"

4' - 7" 4' - 6" 6' - 10"

4' -

6"

3' -

6"

7

S-208

1

S-203

SIM

8

S-208

CHANGE IN DECK DIRECTION

2' - 7"

2' - 11"

6' -

0"

6' -

0"

6' -

0"

6' -

0"

6' -

0"

6' -

0"

3' -

6"

9"

HSS12X6X1/4

3' - 2 1/2"

W12X

22

W12X

22

W12X

22

W12X

22

W12X

22

W12X

22

6' - 0" 6' - 0" 6' - 0" 6' - 0" 6' - 0" 6' - 0" 6' - 0"

5' -

2 1

/2"

6' -

0"

6' -

0"

6' -

0"

6' -

0"

-

---

-

---

9

S-208

BeamClass

W14

End ShearReaction

25 kips

Notes

Composite Beam End Reaction Schedule

1. Fabricator to design beam shear connections for the minimumreaction listed above.

W16 30 kips

W18 35 kips

W21 45 kips

W24 60 kips

W27 85 kips

W30 130 kips

NOTES

1. FLOOR SLAB TO BE 5" (3000 PSI) CONCRETE WITH WWF 6x6-w2.9Xw2.9 WITH2"x20/20 GA GALVANIZED (G60) COMPOSITE STEEL DECK.

LEGEND

C = CAMBER IN BEAM(X) = X NUMBER OF 3/4"x5" HEADED STUDS. SEE S204

= MOMENT CONNECTION. SEE 5/S201

VBF = VERTICAL BRACED FRAME. SEE S205

XX k-ft = END MOMENT FOR MOMENT CONNECTION DESIGNS

= 1 1/2"x22 GAGE, TYPE B STEEL DECK

CHECKED BY:

DRAWN BY:

DATE:

PROJECT:

REVISIONS:

MEMBERS OF THE AMERICAN INSTITUTE OF ARCHITECTS

1

A

2 3 4 5 6

B

C

D

E

COPYRIGHT 2014 ALL RIGHTS RESERVEDPRINTED OR ELECTRONIC DRAWINGS ANDDOCUMENTATION MAY NOT BE REPRODUCEDIN ANY FORM WITHOUT WRITTEN PERMISSIONFROM LS3P ASSOCIATES LTD.

TEL. 864.235.0405 FAX 864.233.4027

GREENVILLE, SOUTH CAROLINA 29601

110 WEST NORTH STREET SUITE 300

ISS

UE

FO

R F

OU

ND

AT

ION

PE

RM

IT 1

2.9

.14

12/1

0/2

014 1

:29:2

3 P

M

\\A

a-s

bs11\D

ata

\AA

\Pro

jects

\LS

3P

\12-L

S3P

-17-C

ollab

I\B

uzzsaw

\_S

tru

ct

Syn

c F

old

er\

CU

-IC

AR

Researc

h O

ne_S

tru

ct_

2014.r

vt

12-LS3P-17

11.05.2014

AP/WB

ARROWOOD

FOURTHFLOORFRAMING PLAN

S-104

CU-ICARRESEARCH ONE

12.9.2014

Owner

864.232.7855 (f)864.233.9383 (t)

Greenville, SC 29607412-B Pettigru Street

Arrowood & Arrowood, PC

A&A PROJECT #12-LS3P-17

a r r o w o o d

a r r o w o o d

1/8" = 1'-0"S-104

1 FOURTH FLOOR FRAMING PLAN

PRICING NOTES

1) ELEVATOR STEEL - ASSUME HSS5x5x1/4 ELEVATOR GUIDERAIL BRACKET SUPPORT POSTS, (3) TOTAL. ASSUME FIELDWELDED PLATE 1"x8x1'-4" FOR CONNECTION OF BRACKET TO BE SPACED @ 12'-0" O.C. ALSO ASSUME W8x24 HOIST BEAMS.

2) EDGES - TYPICAL SLAB EDGE TO BE BENT PLATE 1/4 w/ 3/4"x8" H.S. @ 12" O.C. PROVIDE L2 KICKERS @ 4'-0" O.C. FORBENT PLATE SUPPORT.

Coordinate openings in beams for utilities....

No. Description Date

3

3

4

4

5

5

6

6

7

7

8

8

9

9

A A

B B

C C

W16X31 W18X50 W18X50 W16X26W18X50

W16X26

W18X50

W18X50 W18X50

W12X

26

W16X

26

W16X

26

W16X

26

W16X

26

VB

F 1

VB

F 3

A.2 A.2

C.8 C.8

9.1

9.1

2.9

2.9

HSS10x4x3/8 BAND

HSS10x4x3/8 BAND

HSS8x6 CANTILEVERING OFF OFCOLUMNS FOR 4'-0" OVERHANG(TYPICAL)

BEAMS TAPER TO 10". (TYPICAL)

W16X

26

W16X31

W16X

50

W16X

50

W16X

26

W16X

50

W16X

26

W16X26

W16X26 W16X26 W16X26 W16X26

W16X26

W16X

26

16K

5

W16X

26

16K

5

W16X

50

16K

5

W16X

26

16K

5

W16X26 W16X26 W16X26 W16X26

W16X

26

W16X

26

A'

W16X

26

W16X

26

W16X31

W8X15

W16X26

W16X26

W16X26

W16X26

W8X15

W8X15

HS

S8X

8X

3/8

HS

S8X

8X

3/8

37' -

5"

22' -

4"

33' -

11"

W8X15

W16X

26

W16X

26

W16X

26

16K

5

16K

5

16K

5

16K

5

16K

5

16K

5

16K

5

16K

5

16K

5

16K

5

16K

5

16K

5

16K

5

16K

5

16K

5

16K

5

W16

X67

16K

5

16K

5

16K

5

16K

5

16K

5

16K

5

16K

5

16K

5

16K

5

16K

5

16K

5

16K

5

16K

5

16K

5

16K

5

16K

5

W16X67

14K

4

14K

4

14K

4

14K

4

14K

4

14K

4

14K

4

14K

4

14K

4

14K

4

14K

4

14K

4

14K

4

14K

4

14K

4

4' - 8 3/4" 5' - 2" 5' - 2" 5' - 2" 4' - 9 1/4" 5' - 10 1/2" 5' - 10 1/2" 5' - 5"

5' -

6 7

/8"

B.O.D. = 60'-2"

B.O.D. = 60'-2"

B.O.D. = 59'-1 1/2"

B.O.D. = 60'-2"

B.O.D. = 60'-2"

B.O.D. = 59'-1 1/2"

B.O.D. = 59'-1 1/2"

B.O.D. = 59'-1 1/2"

HSS5X5X3/8

HSS5X5X3/8

HSS5X5X3/8 HSS5X5X3/8

POST UP

POST UP

POST UP

POST UP

W16X26

W16X

26

W16X

26

W10X

33

W16X26

HO

IST

BE

AM

(6

1'-9

")

(58

'-11

", 6

2'-0

")

(58

'-11

", 6

1'-1

0")

2.6

C.5

D.3

12

13

W16X31

A''

2

S-204

VBF 7

VBF 9

W16X

26

W16X31W

16X

50

W16X

26

W16X

26

W16X26

W16X26

W16X

26

W16X

26

W16X26

W16X26

W16X26

W16X26

W16X26

W16X26

W16X26

W16X26

W16X

26

W16X

26

W16X

26

W16X67

W16

X67

W16X

50

W16X

50

W16X31

VB

F 2

T/BEAM = 53'-10"

T/COLUMN = 53'-10"

T/BEAM = 53'-10"

T/COLUMN = 53'-2"

VBF 6

VBF 8

BEAM TO CANTILEVERACROSS TOP OF COLUMN

HS

S8X

6X

1/4

HS

S8X

6X

1/4

HS

S8X

6X

1/4

HS

S8X

6X

1/4

HS

S8X

6X

1/4

HS

S8X

6X

1/4

HS

S8X

6X

1/4

HS

S8X

6X

1/4

HS

S8X

6X

1/4

HS

S8X

6X

1/4

8" DEEP JOISTEXTENSIONS (TYPICAL)

8" DEEP JOISTEXTENSIONS (TYPICAL)A.1 A.1

2

S-204

BEAMS TAPER TO 10". (TYPICAL)

5' -

9"

8' - 3"

1' - 4 1/16"

(DR

OP

PE

D)

(DR

OP

PE

D)

(DR

OP

PE

D)

(DR

OP

PE

D)

45.0

45.0

45.0

45.0

(DR

OP

PE

D)

(DR

OP

PE

D)

W16X26

4' - 3" 4' - 0" 5' - 7" 5' - 7" 5' - 7" 5' - 10 1/2" 5' - 10 1/2" 5' - 5"

W16X31

4' - 8 3/4"

W8X

15

W8X15

W8X

15

W8X

15

W8X

15

W16X

26

W8X

15

W8X

15

W8X

15

W8X

15

HS

S8X

6X

1/4

W8X

15

W8X

15

HS

S8X

6X

1/4

W8X

15

W8X

15

W8X

15

W8X

15

(HI)

W16X

26

(HI)

5' -

8 3

/8"

5' -

8 3

/8"

5' -

8 3

/8"

5' -

8 3

/8"

5' -

8 3

/8"

5' -

7"

5' -

7"

5' -

7"

5' -

7"

5' -

2 1

/8"

5' -

4"

5' -

4"

5' -

4"

5' -

4"

5' -

4"

HS

S8X

6X

1/4

W8X

15

W8X

15

W8X

15

W8X

15

W8X15

W8X

15

W8X

15

W8X

15

W8X

15

W8X

15

W8X15

W8X

15

HS

S8X

6X

1/4

1' - 4 1/16"

5' - 6 7/8" 4' - 8" 4' - 4" 5' - 2" 5' - 2" 5' - 4" 5' - 0"

5' -

6 7

/8"

5' -

4"

5' -

4"

5' -

4"

5' -

4"

10' -

6 1

/8"

5' -

7"

5' -

7"

5' -

7"

5' -

7"

5' -

8 3

/8"

5' -

8 3

/8"

5' -

8 3

/8"

5' -

8 3

/8"

5' -

8 3

/8"

5' -

5"

5' - 5" 4' - 10 1/8"

1' - 8 1/4"

5' - 8 1/2" 5' - 11" 5' - 8" 6' - 0"

HS

S10X

4X

3/8

HS

S10X

4X

3/8

HS

S10X

4X

3/8

HS

S10X

4X

3/8

HS

S10X

4X

3/8

HS

S10X

4X

3/8

W16X31

W16X31

W16X26W16X26

W16X31

B.O

.D. =

60

'-2"

B.O

.D. =

60

'-2"

W8X15

2' -

2 1

/8"

-

---

1' -

0"

20' -

4"

1' -

0"

7' - 7" 10"

LEGEND

C = CAMBER IN BEAM

= MOMENT CONNECTION. SEE 5/S-201

VBF = VERTICAL BRACED FRAME. SEE S-205

FRAMING NOTES

1. DECK TO BE 1 1/2"x22GAGE, TYPE B STEEL ROOF DECK.

CHECKED BY:

DRAWN BY:

DATE:

PROJECT:

REVISIONS:

MEMBERS OF THE AMERICAN INSTITUTE OF ARCHITECTS

1

A

2 3 4 5 6

B

C

D

E

COPYRIGHT 2014 ALL RIGHTS RESERVEDPRINTED OR ELECTRONIC DRAWINGS ANDDOCUMENTATION MAY NOT BE REPRODUCEDIN ANY FORM WITHOUT WRITTEN PERMISSIONFROM LS3P ASSOCIATES LTD.

TEL. 864.235.0405 FAX 864.233.4027

GREENVILLE, SOUTH CAROLINA 29601

110 WEST NORTH STREET SUITE 300

ISS

UE

FO

R F

OU

ND

AT

ION

PE

RM

IT 1

2.9

.14

12/1

0/2

014 1

:29:2

6 P

M

\\A

a-s

bs11\D

ata

\AA

\Pro

jects

\LS

3P

\12-L

S3P

-17-C

ollab

I\B

uzzsaw

\_S

tru

ct

Syn

c F

old

er\

CU

-IC

AR

Researc

h O

ne_S

tru

ct_

2014.r

vt

12-LS3P-17

11.05.2014

AP/WB

ARROWOOD

ROOFFRAMING PLAN

S-105

CU-ICARRESEARCH ONE

12.9.2014

Owner

864.232.7855 (f)864.233.9383 (t)

Greenville, SC 29607412-B Pettigru Street

Arrowood & Arrowood, PC

A&A PROJECT #12-LS3P-17

a r r o w o o d

a r r o w o o d

1/8" = 1'-0"S-105

1 ROOF FRAMING PLAN

PRICING NOTES

1) ASSUME (5) L4 FRAMES FOR EXHAUST & OTHER PENETRATIONS.

No. Description Date

(CO

NF

IRM

DE

PT

H W

ITH

ELE

VA

TO

R C

UT

SH

EE

TS

)

4' -

0"

8" 4" MIN.

#5 @ 12"

#5 @ 12" O,C,;EACH WAY, TOP & BOTTOM

2"

1' -

4"

48" LEG

2"

CLR

.

2

1

2x4 KEY

SEE ARCH. DRAWINGSFOR WATERPROOFING

2x4 KEY w/PREMOLDED TYPEWATERSTOP2'-0" DEEP SUMP PIT

2' - 0" SQUARE x

1

1

SEE ARCH. DRAWINGSFOR WATERPROOFING

2"#5 @ 12"

1' -

0"

#4x48" @ 45º TO CORNER,PLACE IN TOP OF SLAB

FINISH FLOOR

ELEV. 0'-0"

TOP OF FOOTING

ELEV. (SEE PLAN)

CLR.

3"

CL COLUMN & FOOTING

ANCHOR RODS, SEEDETAILS ON S-201

EXPANSION JOINTMATERIAL (TYP.)

FUTURE ISOLATION POCKET.FILL w/CONCRETE AFTERSLAB JOINTS ARE CUT

CONCRETE COLUMNFOOTING, SEEPLAN & SCHEDULEFOR SIZE &REINFORCING

CLR

.

3"

CL COLUMN & FOOTING

FUTURE SLAB

2

1

#5 @ 9" o.c.

Z-BAR SIZE TO MATCHLONGITUDINAL REINFORCINGIN FOOTING

SEE PLAN &FOOTING SCHEDULE

( 4'-0"

MA

X. )

1' - 0"

3"

FINISH FLOOR

ELEV. 0'-0"

TOP OF FOOTING

ELEV. (SEE PLAN)

CLR.

3"

COLUMN &FOOTING

ANCHOR RODS, SEES-201

1/2" ISOLATION JOINTMATERIAL (TYP.).

CONCRETE COLUMN FOOTING, SEEPLAN & SCHEDULE FOR SIZE &REINFORCING

CLR

.

3"

TOP OF PIER

ELEV. (-1'-0")

PER FOOTING SCHEDULE

PE

R F

OO

TIN

G S

CH

D.

ISOLATION POCKETAROUND COLUMN

2' -

8"

3' - 8"

(20) #8

2" COVER

#4 CLOSED TIE @ 6"

1' -

0"

ELEVATOR PIT WALLS TO BETIED INTO PIER.T/ELEVATOR WALL = -1'-0"

2' - 0" 1' - 8"

10"

0'-0"

SC

HE

DU

LE

SE

E F

OO

TIN

G

SEE FOOTING SCHEDULE

SEE FOOTINGSCHEDULE FORREINFORCING DETAILS

COLUMN

1/2" ISOLATION JOINT

FILL ISOLATION

SEE S-201 FORBASEPLATE ANDANCHOR ROD DETAILS

TOP OF FOOTING

PE

R S

CH

ED

ULE

TH

ICK

NE

SS

WIDTH PER SCHEDULE

PRECAST WAINSCOT PANEL

0'-0"

2x4 KEY

4" STONE BASE

VAPOR BARRIER

3' - 0"

CONNECTION BYPRECAST SUPPLIER

-2'-0"

PE

R S

CH

ED

ULE

TH

ICK

NE

SS

WIDTH PER SCHEDULE

SEE PLAN FORSLAB INFO.

#4 @ 24" O.C. w/ 42" HORIZONTALLEG. (4) #5xCONT.

0'-0"2"

CLR

.

1' - 0"

MIN6"

4' - 0"

2x4 KEY

#5 @ 24" O.C.

4" STONE BASE

VAPOR BARRIER

SEE PLAN FORSLAB INFO.

#4 @ 24" O.C. w/ 40" HORIZONTALLEG. (2) #5xCONT.

2"

CLR

.

MIN6"

4" STONE BASE

VAPOR BARRIER

1' - 4"

1' -

6"

4" STONE BASE

VAPOR BARRIER

1' - 6"

8"

2x4 KEY

4"

ARCH. DRAWINGS

COORDINATE WITH3/4" CHAMFER

1'-0"

COVER2"

#4 @ 24" O.C. (EACH FACE)

(4) #4 (EACH FACE)

CHECKED BY:

DRAWN BY:

DATE:

PROJECT:

REVISIONS:

MEMBERS OF THE AMERICAN INSTITUTE OF ARCHITECTS

1

A

2 3 4 5 6

B

C

D

E

COPYRIGHT 2014 ALL RIGHTS RESERVEDPRINTED OR ELECTRONIC DRAWINGS ANDDOCUMENTATION MAY NOT BE REPRODUCEDIN ANY FORM WITHOUT WRITTEN PERMISSIONFROM LS3P ASSOCIATES LTD.

TEL. 864.235.0405 FAX 864.233.4027

GREENVILLE, SOUTH CAROLINA 29601

110 WEST NORTH STREET SUITE 300

ISS

UE

FO

R F

OU

ND

AT

ION

PE

RM

IT 1

2.9

.14

12/1

0/2

014 1

:29:2

8 P

M

\\A

a-s

bs11\D

ata

\AA

\Pro

jects

\LS

3P

\12-L

S3P

-17-C

ollab

I\B

uzzsaw

\_S

tru

ct

Syn

c F

old

er\

CU

-IC

AR

Researc

h O

ne_S

tru

ct_

2014.r

vt

12-LS3P-17

11.05.2014

AP/WB

ARROWOOD

SECTIONS &DETAILS

S-200

CU-ICARRESEARCH ONE

12.9.2014

Owner

1" = 1'-0"S-200

7 ELEVATOR PIT SECTION

1" = 1'-0"S-200

B Corner Reinforcing Detail

1" = 1'-0"S-200

6 Interior Column Footing

1" = 1'-0"S-200

A Step Footing Detail

1" = 1'-0"S-200

8 Pier And Footing Detail

1" = 1'-0"S-200

1 Section 1" = 1'-0"S-200

2 Footing @ Precast Panel 1" = 1'-0"S-200

3 Thickened Edge Slab 1" = 1'-0"S-200

4 Turn Down Slab 1" = 1'-0"S-200

5 Section

1" = 1'-0"S-200

9 Curb Section

864.232.7855 (f)864.233.9383 (t)

Greenville, SC 29607412-B Pettigru Street

Arrowood & Arrowood, PC

A&A PROJECT #12-LS3P-17

a r r o w o o d

a r r o w o o d

No. Description Date

8" 8"2" 2"

2"

8"

8"

2"

1" HEADED ANCHOR ROD w/HEAVY HEX NUT & LEVELING NUT

5/16

W12 COLUMN

3 1

/2"

PR

OJ

2 1

/2"

EM

BE

DM

EN

T

1' -

2"

PL 1/2x4x4 w/NUT

2"

GR

OU

T

1 1

/2"

B P

L

1' - 8"

1' -

8"

4"

2 1/2" 2 1/2"

4"

1" HEADED ANCHOR ROD w/ HEAVYHEX NUT & LEVELING NUT

5/16

W10 COLUMN

EM

BE

DM

EN

T

1' -

0"

3 1

/2"

2"

PL 3/8x3x3 w/NUT

2"

GR

OU

T

1 1

/2"

B P

L

3"

3 1

/2"

3 1

/2"

3"

1' -

1"

PLATE WASHER

5" 3"9"9"GUSSET LENGTHAS REQUIRED FOR

5"

1 1/2" ANCHOR ROD w/ HEAVYHEX NUT & LEVELING NUT

5/16

W12 COLUMN

4 1

/2"

PR

OJ

3"

EM

BE

DM

EN

T

2' -

0"

PL 1/2x4x4 w/NUT

2"

GR

OU

T

2"

B P

L

4"

3 1

/2"

3 1

/2"

4"

1' -

3"

GUSSET (ASREQUIRED FORBRACE)

3"9"9"GUSSET LENGTHAS REQUIRED FOR

5"

1 1/2" ANCHOR ROD w/ HEAVYHEX NUT & LEVELING NUT

5/16

W12 COLUMN

PL 1/2x4x4 w/NUT

2"

GR

OU

T

2"

B P

L

4"

3 1

/2"

3 1

/2"

7"

GU

SS

ET

LE

NG

TH

AS

RE

QU

IRE

D F

OR

GUSSET (ASREQUIRED FORBRACE)

EM

BE

DM

EN

T

2' -

0"

4"

PR

OJ.

3 1

/2"

8" 8"3" 3"

3"

8"

8"

3"

1 1/2" HEADED ANCHOR ROD w/HEAVY HEX NUT & LEVELING NUT

5/16

W12 COLUMN

PL 1/2x4x4 w/NUT

2"

GR

OU

T

2"

B P

L

1' - 10"

1' -

10"

2' -

0"

4"

3 1

/2"

FINISH FLOOR

ELEV. 0'-0"

TOP OF FOOTING

ELEV. (SEE PLAN)

CLR.

3"

COLUMN &FOOTING

ANCHOR RODS, SEES-201

1/2" ISOLATION JOINTMATERIAL (TYP.).

CONCRETE COLUMN FOOTING, SEEPLAN & SCHEDULE FOR SIZE &REINFORCING

CLR

.

3"

TOP OF PIER

ELEV. (-2'-0")

PER FOOTING SCHEDULE

PE

R F

OO

TIN

G S

CH

D.

ISOLATION POCKETAROUND COLUMN

2' -

4"

3' - 6"

(20) #8

2" COVER

#4 CLOSED TIE @ 6"

1' - 9" 1' - 9"

2' -

4"

2' - 4"

(16) #8

2" COVER

#4 CLOSED TIE @ 6"

2' -

10"

3' - 4"

(20) #8

2" COVER

#4 CLOSED TIE @ 6"

#4 TIE TOPAND BOTTOM

#4 TIE TOPAND BOTTOM#4 TIE TOP

AND BOTTOM

PIER AT BASEPLATE WITH (1) GUSSET PIER AT BASEPLATE WITH (2) GUSSETS PIER AT BASEPLATE WITHOUT GUSSETS

CHECKED BY:

DRAWN BY:

DATE:

PROJECT:

REVISIONS:

MEMBERS OF THE AMERICAN INSTITUTE OF ARCHITECTS

1

A

2 3 4 5 6

B

C

D

E

COPYRIGHT 2014 ALL RIGHTS RESERVEDPRINTED OR ELECTRONIC DRAWINGS ANDDOCUMENTATION MAY NOT BE REPRODUCEDIN ANY FORM WITHOUT WRITTEN PERMISSIONFROM LS3P ASSOCIATES LTD.

TEL. 864.235.0405 FAX 864.233.4027

GREENVILLE, SOUTH CAROLINA 29601

110 WEST NORTH STREET SUITE 300

ISS

UE

FO

R F

OU

ND

AT

ION

PE

RM

IT 1

2.9

.14

12/1

0/2

014 1

:29:2

9 P

M

\\A

a-s

bs11\D

ata

\AA

\Pro

jects

\LS

3P

\12-L

S3P

-17-C

ollab

I\B

uzzsaw

\_S

tru

ct

Syn

c F

old

er\

CU

-IC

AR

Researc

h O

ne_S

tru

ct_

2014.r

vt

12-LS3P-17

11.05.2014

Author

Checker

SECTIONS &DETAILS

S-201

CU-ICARRESEARCH ONE

12.9.2014

Owner

1 1/2" = 1'-0"S-201

2 Typical W12 Baseplate

864.232.7855 (f)864.233.9383 (t)

Greenville, SC 29607412-B Pettigru Street

Arrowood & Arrowood, PC

A&A PROJECT #12-LS3P-17

a r r o w o o d

a r r o w o o d

1 1/2" = 1'-0"S-201

1 Typical W10 Baseplate 1 1/2" = 1'-0"S-201

4 VBF Baseplate with (1) Gusset

1 1/2" = 1'-0"S-201

5 VBF Baseplate with (2) Gussets

1 1/2" = 1'-0"S-201

3 Typical VBF Column Baseplate (Not At Gusset)

No. Description Date

1" = 1'-0"S-201

6 Pier and Footing Detail At VBF Columns

A

3/4

" C

OV

ER

SEE PLAN FORSLAB INFO

2" STEEL DECK,SEE PLAN

EDGE OF SLAB

1' - 1"

BENT PLATE 5/16x5x1'-2" LLHw/ 3/4x8" H.S. @ 16" O.C.

GIRDER

SHEAR STUD(SEE S-206)

WWF, SEE PLAN

5' -

0"

STRAP PLATE 1/8x1"@ 32" O.C.

LATERAL AND VERTICALSUPPORT FOR C.W. BYC.W. SUPPLIER

2" ACM PANEL

T/HSS6 IS AT

B/CURTAIN WALL

HSS8x4x1/4xCONT.

EXTEND C.W. MULLIONSTO HSS8

A.11' - 2"

1' - 3 3/4"

PLATE 1/2" @ 2'-8" O.C.

8"

EOD

8"

A

3/4

" C

OV

ER

SEE PLAN FOR SLAB INFO

2" STEEL DECK, SEE PLAN

EDGE OF SLAB

1' - 1"

GIRDER

SHEAR STUD(SEE S-206)

WWF, SEE PLAN

A.1

BENT PLATE 5/16x5x1'-2" LLHw/ 3/4x8" H.S. @ 16" O.C.

STRAP PLATE 1/8x1"@ 32" O.C.

PLATE 1/2" @ 2'-8" O.C.

EOD

8"

A

3/4

" C

OV

ER

SEE PLAN FOR SLAB INFO

2" STEEL DECK, SEE PLAN

#4 x 4'-0" AT 16" SHEAR STUD(SEE S-206)

WWF, SEE PLAN

COLUMN (BEYOND)

6" STEEL MEMBERBY OTHERS

HSS8x8x1/4

W12x14

L3x3x1/4 KICKER @ 12'-6"

#5 @ 12" O.C.

(4) #5xCONT.46' - 10"

3' - 1 1/2"

3/4" CHAMFER8"

L3x3x1/4 @ 12'-6"

L6x6x3/8 w/ 3/4x8"H.S. @ 12" O.C.

ANGLE BETWEEN TUBESBY OTHERS

6" STEEL MEMBERBY OTHERS

42' - 0"

A.1

3' - 0" EOD

HSS8x8x1/4 @ COLUMNSFOR SUPPORT OFCONTINUOUS HSS8x8x1/4

GIRDER

A

3/4

" C

OV

ER

SEE PLAN FOR SLAB INFO

2" STEEL DECK, SEE PLAN

#4 x 4'-0" AT 16"

STEEL BY OTHERS

GIRDER

W12x14

SHEAR STUD(SEE S-206)

WWF, SEE PLAN

W12 TO BE MOMENTCONNECTED TO BEAM

L6x6x3/8 w/ 3/4x8"H.S. @ 12" O.C.

ANGLE BETWEEN TUBESBY OTHERS

STEEL BY OTHERSHSS8x4x1/4xCONT.

EXTEND C.W. MULLIONSTO HSS8

LIGHT GAGE FRAMING

A.1

HSS12x4

3' - 1 1/2"

3' - 0" EOD

1' - 3 3/4"

A

3/4

" C

OV

ER

SEE PLAN FOR SLAB INFO

2" STEEL DECK, SEE PLAN

#4 x 4'-0" AT 16"

GIRDER

HSS6x6x3/8 w/ 3/4"H.S. @ 12" O.C.

STEEL BY STEEL CLAD

STIFFENER 1/4"ON EACH SIDEOF VERTICAL

SHEAR STUD(SEE S-206)

WWF, SEE PLAN

C10 TO BE MOMENT CONNECTED

HSS12x4

3' - 1 1/2"

W12x14

1"

3' - 0" EOD

ANGLE BETWEEN TUBESBY OTHERS

A

3/4

" C

OV

ER SHEAR STUD

(SEE S-206)

WWF, SEE PLANSEE PLAN FOR SLAB INFO

2" STEEL DECK,SEE PLAN

#4 x 4'-0" AT 16"

GIRDER

STEEL BY OTHERS

3' - 1 1/2"

W8 TO BE MOMENT CONNECTED

W12x14

HSS6x6x3/8 w/ 3/4"H.S. @ 12" O.C.

STIFFENER 1/4"ON EACH SIDEOF VERTICAL

HSS12x4

W12x14

ANGLE BETWEEN TUBESBY OTHERS

3' - 0" EOD

1"

A

1 1/2" STEEL ROOFDECK, SEE PLAN

3' - 7 1/2"

STEEL BYOTHERS

HSS8x8x1/4

L4x4x1/4xCONT.

L3x3x1/4 @ 12'-6" O.C.

W12x14

2' - 9" E.O.D.

L3x3x1/4 KICKER @ 6'-3"

A.1

HSS8x8x1/4 @ COLUMNSFOR SUPPORT OFCONTINUOUS HSS8x8x1/4

COLUMN (BEYOND)

42' - 0"

L3x3x1/4 KICKER @ 12'-6"

HSS6x3x1/4 w/ L3x3x1/4

A

3' - 7 1/2"

GIRDER

L5x5x1/4 FORMETAL SCREEN(SEE ARCHDWGS FOREXTENT)

HSS8x8x1/4

STEEL BYOTHERS

SEE PLAN FOR SLAB INFO

2" STEEL DECK, SEE PLAN

COLUMN (BEYOND)

W12x14

L3x3x1/4 KICKER @ 12'-6"

L3x3x1/4 @ 12'-6"

L6x6x3/8 w/ 3/4x8"H.S. @ 12" O.C.

HSS8x8x1/4 @ COLUMNSFOR SUPPORT OFCONTINUOUS HSS8x8x1/4

3' - 0" EOD

BENT PLATE 5/16" (HOLDVERTICAL LEG DOWN 1/4" TOALLOW FOR FILLET WELD OFL2 TO BENT PLATE)

WWF, SEE PLAN

L2 1/2x2 1/2x3/16KICKER @ 6'-0" O.C.

(2) 1/2"x6" H.S. @ 12" O.C.

EOD @ BEAM

SEE PLAN

1/8x1" STRAP PLATE

L2x2x1/4xCONT

3-12

3-12

CHECKED BY:

DRAWN BY:

DATE:

PROJECT:

REVISIONS:

MEMBERS OF THE AMERICAN INSTITUTE OF ARCHITECTS

1

A

2 3 4 5 6

B

C

D

E

COPYRIGHT 2014 ALL RIGHTS RESERVEDPRINTED OR ELECTRONIC DRAWINGS ANDDOCUMENTATION MAY NOT BE REPRODUCEDIN ANY FORM WITHOUT WRITTEN PERMISSIONFROM LS3P ASSOCIATES LTD.

TEL. 864.235.0405 FAX 864.233.4027

GREENVILLE, SOUTH CAROLINA 29601

110 WEST NORTH STREET SUITE 300

ISS

UE

FO

R F

OU

ND

AT

ION

PE

RM

IT 1

2.9

.14

12/1

0/2

014 1

:29:3

0 P

M

\\A

a-s

bs11\D

ata

\AA

\Pro

jects

\LS

3P

\12-L

S3P

-17-C

ollab

I\B

uzzsaw

\_S

tru

ct

Syn

c F

old

er\

CU

-IC

AR

Researc

h O

ne_S

tru

ct_

2014.r

vt

12-LS3P-17

11.05.2014

AP/WB

AJA

SECTIONS &DETAILS

S-202

CU-ICARRESEARCH ONE

12.9.2014

Owner

1" = 1'-0"S-202

7 Second Floor Slab Edge Store Front (North)

1" = 1'-0"S-202

4 Third Floor Slab Edge Store Front (North)

1" = 1'-0"S-202

1 Fourth Floor Slab Edge Store Front (North)

1" = 1'-0"S-202

8 Second Floor Slab Edge Metal Panel (North)

1" = 1'-0"S-202

5 Third Floor Slab Edge Metal Panel (North)

1" = 1'-0"S-202

2 Fourth Floor Slab Edge Metal Panel (North) 1" = 1'-0"S-202

3 Fourth Floor Slab Edge Store Front Center (North)

1" = 1'-0"S-202

6 Fourth Floor Slab Edge Metal Panel (NorthWest)

1" = 1'-0"S-202

9 Second Floor Typical Slab Edge

No. Description Date

Level 218' - 0"

2ND TOS17' - 7"

D.3

W12x14 @ 6'-3" O.C.

HSS6x6x1/4

L3x3x1/4 HANGER@ 6'-3" O.C.

L2 1/2x2 1/2 x3/16KICKER @ 6'-3" O.C.

L5x5x1/4xCONT.18' - 0"

4' -

0"

3' - 1 1/2"

HSS6x6x3/8 w/ 3/4"H.S. @ 16" O.C.

1' - 9 1/2"

1' - 8" EOD

Level 446' - 0"

4TH TOS46' - 5"

D.3

HSS8x2x1/4xCONT. (LSH)

HSS12x6x1/4xCONT.

EXTEND C.W. MULLION

W12x22 @ EACH COLUMN

PLATE w/ HOLEFOR SCREENATTACHMENT

3' - 1 1/2" EOD

1' -

0 5

/8"

L2 1/2x2 1/2x3/16"

1 1/2" ROOF DECK

COLUMN

1' - 2"

Level 332' - 0"

3RD TOS31' - 7"

D.3

BENT PLATE 1/4 w3/4"x8" H.S. @ 16" O.C.

1/2x8" PLATE @ 2'-8" O.C.

1' - 2"

1' - 1" EOD

Level 218' - 0"

1

2ND TOS17' - 7"

W12x14 @ 6'-0" O.C. +/-

L6x6x3/8 w/ 3/4"x8" H.S. @ 16" O.C.

L2 1/2x2 1/2x3/16 @ 6'-0" O.C.

VERTICALLY SLOTTEDCONNECTION BY PRECASTER

2' - 9 1/2"

2' - 8" EOD

Level 332' - 0"

1

3RD TOS31' - 7"

W12x14 @ 6'-0" O.C. +/-

L6x6x3/8 w/ 3/4"x8" H.S. @ 16" O.C.

L2 1/2x2 1/2x5/16 @ 6'-0" O.C.

2' - 9 1/2"

2' - 8" EOD

Level 446' - 0"

1

4TH TOS46' - 5"

4TH DROPPED44' - 11"

W12x14 @ 6'-0" O.C. +/-

L6x6x3/8 w/ 3/4"x8" H.S. @ 16" O.C.

L2x2x1/4 @ 6'-0" O.C.

2' - 9 1/2"

2' - 8" EOD

Level 218' - 0"

3

2ND TOS17' - 7"

2.9

W18 (BEYOND)

L2 1/2x2 1/2x3/16 @ 6'-0" O.C.

L5x5x3/8 w/ 3/4x8"H.S. @ 16" O.C.

W12x6x5/16 (COL TO COL)

Level 332' - 0"

3

3RD TOS31' - 7"

2.9

L5x5x3/8 w/ 3/4x8"H.S. @ 16" O.C.

6' - 6"

6' - 5" EOD

6' - 2 7/8"

L2 1/2x2 1/2x3/16 @ 6'-0" O.C.

Level 446' - 0"

3

4TH TOS46' - 5"

2.9

4TH DROPPED44' - 11"

L3x3x1/4xCONT

L5x5x1/4xCONT.

6' - 1 7/8"

6' - 6"

6' - 5" EOD

1/2" EOD

CHECKED BY:

DRAWN BY:

DATE:

PROJECT:

REVISIONS:

MEMBERS OF THE AMERICAN INSTITUTE OF ARCHITECTS

1

A

2 3 4 5 6

B

C

D

E

COPYRIGHT 2014 ALL RIGHTS RESERVEDPRINTED OR ELECTRONIC DRAWINGS ANDDOCUMENTATION MAY NOT BE REPRODUCEDIN ANY FORM WITHOUT WRITTEN PERMISSIONFROM LS3P ASSOCIATES LTD.

TEL. 864.235.0405 FAX 864.233.4027

GREENVILLE, SOUTH CAROLINA 29601

110 WEST NORTH STREET SUITE 300

ISS

UE

FO

R F

OU

ND

AT

ION

PE

RM

IT 1

2.9

.14

12/1

0/2

014 1

:29:3

1 P

M

\\A

a-s

bs11\D

ata

\AA

\Pro

jects

\LS

3P

\12-L

S3P

-17-C

ollab

I\B

uzzsaw

\_S

tru

ct

Syn

c F

old

er\

CU

-IC

AR

Researc

h O

ne_S

tru

ct_

2014.r

vt

12-LS3P-17

11.05.2014

AP/WB

AJA

SECTIONS &DETAILS

S-203

CU-ICARRESEARCH ONE

12.9.2014

Owner

1" = 1'-0"S-203

7 Section

1" = 1'-0"S-203

1 Section

1" = 1'-0"S-203

4 Section

1" = 1'-0"S-203

8 Section

1" = 1'-0"S-203

5 Section

1" = 1'-0"S-203

2 Section

1" = 1'-0"S-203

9 Section

1" = 1'-0"S-203

6 Section

1" = 1'-0"S-203

3 Section

No. Description Date

C.9 DC.8

W18x35

W24

1 1/2" STEEL DECK

2" STEEL DECK, SEEPLAN

HSS3x3x1/4 @ 8'-0" O.C.

HSS6x6 POST UP TOROOF ABOVE

HSS8x2x1/4xCONT.

L5x5x5/16

WEB STIFFENER (1/2")BELOW HSS6 POST(NS, FS)

1' - 2"

1/4" PLATE 50' - 2"

1/2" EOD

1' - 4 7/8"

1' - 3" EOD

C.9

ROOF TOS58' - 7"

C.8

5' - 8 7/8"

3/8"x5" PLATE @ 2'-8" O.C.

1/4"x1'-6"xCONT. PLATE

HSS8x4x1/4xCONT.

8" DEEP JOIST EXTENSION

1' - 4"

57' - 10"

B

1' - 6"

PRECAST PANEL

VERTICALLY SLOTTEDCONNECTION BY PRECASTER

L2x2X1/4

BENT PLATE 5/16" (HOLD VERTICALLEG DOWN 1/4" FOR WELDING OF L2)

EXTEND PRECAST PANEL

PLATE 1/2x8 @ 32" O.C.

L5x5x3/8 w/ 3/4x8"H.S. @ 16" O.C.

10"

9" EOD

H.S. 3/4"x8" @ 16" O.C.

PLATE 1/2x8 @ 2'-8" O.C.

1' - 3"

EOD @ BEAM CENTERLINE

12

CURTAIN WALL

L5x5x1/4 w/ 3/4x8"H.S. @ 16" O.C.

LATERAL SUPPORTBY C.W. SUPPLIER

W18

W27

1' - 3"

HSS5x5x3/16@ 6'-3" O.C.

STEEL BYOTHERS

1/4" PLATE

3/8"x8" PLATE @ 2'-8" O.C.

L5x5x3/8xCONT. w/ 3/4"x8" H.S.

L3x3x1/4xCONT

18' - 0"

3' -

0"

W12x14 @ 6'-0" O.C.

4' - 11" EOD

4' - 4" EOD

4' - 5"

5' - 0 1/2"

6' - 4 1/2"

CHECKED BY:

DRAWN BY:

DATE:

PROJECT:

REVISIONS:

MEMBERS OF THE AMERICAN INSTITUTE OF ARCHITECTS

1

A

2 3 4 5 6

B

C

D

E

COPYRIGHT 2014 ALL RIGHTS RESERVEDPRINTED OR ELECTRONIC DRAWINGS ANDDOCUMENTATION MAY NOT BE REPRODUCEDIN ANY FORM WITHOUT WRITTEN PERMISSIONFROM LS3P ASSOCIATES LTD.

TEL. 864.235.0405 FAX 864.233.4027

GREENVILLE, SOUTH CAROLINA 29601

110 WEST NORTH STREET SUITE 300

ISS

UE

FO

R F

OU

ND

AT

ION

PE

RM

IT 1

2.9

.14

12/1

0/2

014 1

:29:3

3 P

M

\\A

a-s

bs11\D

ata

\AA

\Pro

jects

\LS

3P

\12-L

S3P

-17-C

ollab

I\B

uzzsaw

\_S

tru

ct

Syn

c F

old

er\

CU

-IC

AR

Researc

h O

ne_S

tru

ct_

2014.r

vt

12-LS3P-17

11.05.2014

Author

Checker

SECTIONS &DETAILS

S-204

CU-ICARRESEARCH ONE

12.9.2014

Owner

1" = 1'-0"S-204

1 Section

1" = 1'-0"S-204

2 Section 1" = 1'-0"S-204

3 Section 1" = 1'-0"S-204

5 Section

No. Description Date

Level 218' - 0"

11

2ND TOS17' - 7"

13

HSS6x6x3/16 (HDG) CAP ENDS

W12X35

W14X61

W27

W12x14

STIFFENER PLATE (NS, FS)

EXTEND CURTAINWALL MULLION TOHSS6x4

HSS8x4x1/4xCONT

1/4" BENT PLATE OR TWO SEPARATE PLATES

STIFFENER PLATE 1/2" (NS, FS)

1' - 3"

5' - 3"

CONTRACTOR TO FORM EDGE

L5x5x1/4xCONT

12' - 7"

11' - 9" EOS

11' - 7" EOD @ BEAM CENTERLINE

Level 332' - 0"

11

3RD TOS31' - 7"

13

L5x5x1/4 w/ H.S.

W12x14

W14X61

W27

STIFFENER PLATE (NS, FS)

W12X35

1/4" BENT PLATE OR TWO SEPARATE PLATES

12' - 0"

11' - 8"

5' - 11"

5' - 3"

Level 446' - 0"

4TH TOS46' - 5"

4TH DROPPED44' - 11"

13 HSS6x6x3/16 (HDG) CAP ENDS

STEEL BY STEEL CLAD

BENT PLATE w/ H.S.ANDKICKER @ 4'-0" O.C.

10' - 1 1/8"

5' - 11"

5' - 8" EOS

5' - 7" EOD

4' - 3"

-

---

CHECKED BY:

DRAWN BY:

DATE:

PROJECT:

REVISIONS:

MEMBERS OF THE AMERICAN INSTITUTE OF ARCHITECTS

1

A

2 3 4 5 6

B

C

D

E

COPYRIGHT 2014 ALL RIGHTS RESERVEDPRINTED OR ELECTRONIC DRAWINGS ANDDOCUMENTATION MAY NOT BE REPRODUCEDIN ANY FORM WITHOUT WRITTEN PERMISSIONFROM LS3P ASSOCIATES LTD.

TEL. 864.235.0405 FAX 864.233.4027

GREENVILLE, SOUTH CAROLINA 29601

110 WEST NORTH STREET SUITE 300

ISS

UE

FO

R F

OU

ND

AT

ION

PE

RM

IT 1

2.9

.14

12/1

0/2

014 1

:29:3

4 P

M

\\A

a-s

bs11\D

ata

\AA

\Pro

jects

\LS

3P

\12-L

S3P

-17-C

ollab

I\B

uzzsaw

\_S

tru

ct

Syn

c F

old

er\

CU

-IC

AR

Researc

h O

ne_S

tru

ct_

2014.r

vt

12-LS3P-17

11.05.2014

Author

Checker

SECTIONS &DETAILS

S-205

CU-ICARRESEARCH ONE

12.9.2014

Owner

1" = 1'-0"S-205

3 Section

1" = 1'-0"S-205

2 Section

1" = 1'-0"S-205

1 Section

No. Description Date

MIN. 2" DECK BEARINGINTERIOR OPENING

SEE PLAN FOR

BEAM AT FLOOR OPENINGSFLOOR BEAM

3/4

" C

OV

ER

SHEAR STUD(SEE _____)

WWF, SEE PLAN

SEE PLAN FOR SLAB INFO

CONTINUOUS HIGHCHAIRAT 4'-0" O.C. (EACH WAY)

2" STEEL DECK, SEE PLAN

SE

E P

LA

N

FO

R T

HIC

KN

ES

S

SHEET METAL CLOSURE,ANGLE OR BENT PLATE

CLOSURE

FLOOR GIRDER

3/4

" C

OV

ER

SHEAR STUD(SEE _____)

WWF, SEE PLAN

SEE PLAN FOR SLAB INFO

CONTINUOUS HIGHCHAIRAT 4'-0" O.C. (EACH WAY)

2" STEEL DECK, SEE PLAN

SE

E P

LA

N

FO

R T

HIC

KN

ES

S

#4 x 4'-0" AT 16"

GIRDER

NOTES:

1. SEE SPECIFICATIONS SHEET FOR DECK ATTACHMENT AND SIDELAP SIZE AND SPACING.2. DECKING IS NOT TO BE SHORED.

ONE OR TWOROWS ASREQUIRED

NOTE:

1. BEGIN PLACEMENT BY WELDING SHEAR STUDS AT EVERY OTHER RIB,STARTING AT EACH END. WORKING TOWARD CENTERLINE. THEN PLACEREMAINING STUDS IN EACH RIB THAT DOES NOT HAVE STUD, AGAINWORKING FROM ENDS TO CENTERLINE.

NOTE:

** IF SPACING WOULD BE LESS THAN 6",PLACE STUDS IN TWO ROWS.

DECK PERPENDICULARDECK PARALLEL

TO BEAM SPANTO BEAM SPAN

BEAM

BEAM / SLAB

X X

2X 2X

X X X X

2X 2X

. .

UNIFORM SPACING ALONGLENGTH OF BEAM(GREATER THAN 6" **)

L3x3x1/4 DECK SUPPORT

SHEET METAL WEB CLOSURE

BEAM

BENT PLATE OR POUR STOP

CHASE TYPE OPENING

USE HOOK WHERE FULL BARLENGTH CANNOT BE PROVIDED

(2) #4 TOP AND BOTTOM

BLOCK OUT HOLE FOR CONCRETEPOUR. CUT OUT METAL DECK AFTERSURROUNDING CONCRETE HASCURED FOR 7 DAYS

MIN

. 2

' - 0

" (

TY

P.)

1'-0" TO 2' - 6" (EACH WAY)

NO REINFORCING REQUIRED

OPENING BETWEEN FLUTES

TYPICAL METAL DECK DETAILS

OPENING THROUGH ONE FLUTE

NOTE:1. SEE MECHANICAL DRAWINGS FOR PENETRATION SIZES AND LOCATIONS.

2' - 0" 1' - 11 15/16"

#5 EACH SIDE

1 1

/2"

TO REMAIN BETWEEN PENETRATIONS

MINIMUM OF TWO FLUTES

GANGED OPENINGS

(2) #5 EACH SIDE (IN TOP)

1 1

/2"

(2) #5 IN BOTTOM

(2) #5 IN BOTTOM

2' - 0" 2' - 0"2'-6" (MAX.)

1' -

6"

L4x4x3/8 (TYP)

JO

IST

1/4

1/4

PROVIDE L4 UNDER ALL EDGES OF RTUAND AROUND DUCT PENETRATIONS. PLACEVERTICAL LEG OF L4 AT THE INSIDE EDGE OFRTU CURB. LOCATE USING HVAC CUT SHEETS.

L6x6x3/8x8" LONG

JO

IST

LOAD AND BOTTOM CHORD PANELWELDED TO JOIST TO TOP CHORDL2x2x1/4 (EA SIDE OF JOIST)

POINT

PROVIDE L2 WHERE A POINT LOAD GREATERTHAN 100# WILL BE IN PLACE 6" AWAY FROMPANEL POINT

CHECKED BY:

DRAWN BY:

DATE:

PROJECT:

REVISIONS:

MEMBERS OF THE AMERICAN INSTITUTE OF ARCHITECTS

1

A

2 3 4 5 6

B

C

D

E

COPYRIGHT 2014 ALL RIGHTS RESERVEDPRINTED OR ELECTRONIC DRAWINGS ANDDOCUMENTATION MAY NOT BE REPRODUCEDIN ANY FORM WITHOUT WRITTEN PERMISSIONFROM LS3P ASSOCIATES LTD.

TEL. 864.235.0405 FAX 864.233.4027

GREENVILLE, SOUTH CAROLINA 29601

110 WEST NORTH STREET SUITE 300

ISS

UE

FO

R F

OU

ND

AT

ION

PE

RM

IT 1

2.9

.14

12/1

0/2

014 1

:29:3

5 P

M

\\A

a-s

bs11\D

ata

\AA

\Pro

jects

\LS

3P

\12-L

S3P

-17-C

ollab

I\B

uzzsaw

\_S

tru

ct

Syn

c F

old

er\

CU

-IC

AR

Researc

h O

ne_S

tru

ct_

2014.r

vt

12-LS3P-17

11.05.2014

AP/WB

ARROWOOD

SECTIONS &DETAILS

S-206

CU-ICARRESEARCH ONE

12.9.2014

Owner

1" = 1'-0"S-206

1 TYPICAL ELEVATED FLOOR SLAB DETAILS

1" = 1'-0"S-206

2 SHEAR STUD PLACEMENT DETAIL

1" = 1'-0"S-206

3 DECK SUPPORT AT COLUMN

1" = 1'-0"S-206

4 TYPICAL PENETRATION IN STEEL DECK

1" = 1'-0"S-206

5 ROOF OPENING FRAME DETAIL

864.232.7855 (f)864.233.9383 (t)

Greenville, SC 29607412-B Pettigru Street

Arrowood & Arrowood, PC

A&A PROJECT #12-LS3P-17

a r r o w o o d

a r r o w o o d

No. Description Date

Level 10"

B C

TOP OF FOOTING-2' - 0"

2ND TOS17' - 7"

3RD TOS31' - 7"

4TH TOS46' - 5"

ROOF TOS58' - 7"

W12X26

W16X26 (10)

W18X35 (10)

W8X58 c=3/4"(18)

HSS10X10

X3/8

HSS10X10X3/8

HSS8X8X5/8

HSS6X6X1/4

AXIAL

LOAD =

200

k

AXIAL LOAD = 175k

AXIAL LOAD = 160k

AXIAL LOAD = 30k

Level 10"

B C

TOP OF FOOTING-2' - 0"

2ND TOS17' - 7"

3RD TOS31' - 7"

4TH TOS46' - 5"

ROOF TOS58' - 7"

W16X26

W16X31 (10)

W18X35 (10)

W21X55 (18)

HSS10X10X3/8

HSS8X8X3/8

HSS8X8X3/8

HSS6X6X1/4

AXIAL LOAD =

175k

AXIAL LOAD = 155k

AXIAL LOAD = 95k

AXIAL LOAD = 20k

Level 10"

Level 218' - 0"

B C

TOP OF FOOTING-2' - 0"

2ND TOS17' - 7"

3RD TOS31' - 7"

4TH TOS46' - 5"

ROOF TOS58' - 7"

W16X26

HSS6X6X1/4

W16X31 (10)

HSS8X8X1/4

W18X35 (10)

HSS8X8X3/8

W21X55 (18)

HSS10X10X3/8

AXIAL LOAD =

170k

AXIAL LOAD = 135k

AXIAL LOAD = 105k

AXIAL LOAD = 35k

Level 10"

A

TOP OF FOOTING-2' - 0"

2ND TOS17' - 7"

3RD TOS31' - 7"

A.5

W18X35

HSS6X6X1/4

W18X35

HSS8X8X1/4

W24X84 (25)

HSS8X

8X1/

2

W1

0X

49

4TH DROPPED44' - 11"

AXIAL LOAD = 33k

AXIAL LOAD = 92k

AXIAL

LOAD

= 1

68k

A.1

8

S-203

5

S-203

2

S-203

Level 10"

B C

TOP OF FOOTING-2' - 0"

2ND TOS17' - 7"

3RD TOS31' - 7"

4TH TOS46' - 5"

HSS6X

6X1/4

HSS8X

8X3/8

HSS8X

8X3/

8

HSS

10X

10X

3/8 H

SS

10X10X

3/8

W18X35 (8)

W18X35 (10)

W16X26 (8)

HSS6X

6X1/

4A

XIA

L LO

AD

= 2

50k

AXIAL LO

AD =

140k

AXI

AL

LOAD

= 8

0k

AXIA

L LO

AD =

140

k

AXIAL LO

AD =

80k

AXIA

L LOA

D =

250k

-

---

Level 10"

456

TOP OF FOOTING-2' - 0"

2ND TOS17' - 7"

3RD TOS31' - 7"

4TH TOS46' - 5"

ROOF TOS58' - 7"

HSS10X10X1/2

AXIAL LOAD =

210k

HSS10X10X3/8

AXIAL LOAD = 150k

HSS8X8X3/8

AXIAL LOAD = 90k

HSS6X6X3/8

AXIAL LOAD = 35k

W21X62 (48) W21X62 (48)

W21X62 (48)

W21X62 (25)

W18X50

Level 10"

67

TOP OF FOOTING-2' - 0"

2ND TOS17' - 7"

3RD TOS31' - 7"

4TH TOS46' - 5"

ROOF TOS58' - 7"

HSS6X6X3/8

HSS8X8X1/4

HSS8X8X1/2

HSS10X10X3/8

AXIAL LOAD = 75k

AXIAL LOAD = 125k

AXIAL LOAD =

150k

AXIAL LOAD = 35k

W21X62 (49)

W21X55 (49)

W21X55 (49)

W18X50

Level 10"

4 5 6

TOP OF FOOTING-2' - 0"

2ND TOS17' - 7"

3RD TOS31' - 7"

4TH TOS46' - 5"

ROOF TOS58' - 7"

HSS8X8X1/2

HSS10X10X3/8

AXIAL LOAD = 130k

AXIAL LOAD = 165k

HSS8X8X3/8AXIAL LOAD = 100k

HSS6X6X1/4AXIAL LOAD = 30k

W21X55 (25)

W21X55 (48)

W21X62 (48) W21X62 (48)

W18X50

Level 10"

6 7

TOP OF FOOTING-2' - 0"

2ND TOS17' - 7"

3RD TOS31' - 7"

4TH TOS46' - 5"

ROOF TOS58' - 7"

HSS6X6X1/4

HSS8X8X1/4

HSS8X8X3/8

HSS8X8X1/2

AXIAL LOAD = 30k

AXIAL LOAD = 105k

AXIAL LOAD = 120k

AXIAL LOAD = 80k

W18X50

W21X50 (25)

W21X55 (48)

W21X62 (49)

CHECKED BY:

DRAWN BY:

DATE:

PROJECT:

REVISIONS:

MEMBERS OF THE AMERICAN INSTITUTE OF ARCHITECTS

1

A

2 3 4 5 6

B

C

D

E

COPYRIGHT 2014 ALL RIGHTS RESERVEDPRINTED OR ELECTRONIC DRAWINGS ANDDOCUMENTATION MAY NOT BE REPRODUCEDIN ANY FORM WITHOUT WRITTEN PERMISSIONFROM LS3P ASSOCIATES LTD.

TEL. 864.235.0405 FAX 864.233.4027

GREENVILLE, SOUTH CAROLINA 29601

110 WEST NORTH STREET SUITE 300

ISS

UE

FO

R F

OU

ND

AT

ION

PE

RM

IT 1

2.9

.14

12/1

0/2

014 1

:29:3

8 P

M

\\A

a-s

bs11\D

ata

\AA

\Pro

jects

\LS

3P

\12-L

S3P

-17-C

ollab

I\B

uzzsaw

\_S

tru

ct

Syn

c F

old

er\

CU

-IC

AR

Researc

h O

ne_S

tru

ct_

2014.r

vt

12-LS3P-17

11.05.2014

AP/WB

ARROWOOD

VERTICALBRACEDFRAMES

S-207

CU-ICARRESEARCH ONE

12.9.2014

Owner

1/8" = 1'-0"S-207

1 VBF 1 ELEVATION ALONG 4 1/8" = 1'-0"S-207

2 VBF 2 ELEVATION ALONG 6 1/8" = 1'-0"S-207

3 VBF 3 ELEVATION ALONG 8 1/8" = 1'-0"S-207

4 VBF 4 ELEVATION ALONG 1 1/8" = 1'-0"S-207

5 VBF 5 ELEVATION ALONG 11

864.232.7855 (f)864.233.9383 (t)

Greenville, SC 29607412-B Pettigru Street

Arrowood & Arrowood, PC

A&A PROJECT #12-LS3P-17

a r r o w o o d

a r r o w o o d

1/8" = 1'-0"S-207

6 VBF 6 ELEVATION ALONG B 1/8" = 1'-0"S-207

7 VBF 7 ELEVATION ALONG B 1/8" = 1'-0"S-207

8 VBF 8 ELEVATION ALONG C 1/8" = 1'-0"S-207

9 VBF 9 ELEVATION ALONG C

No. Description Date

D

2' - 10 1/2" EOS

2' - 9" EOD

W12x14 @ 6'-0" O.C.

L6x6x3/8 w/ 3/4x8"H.S. @ 12" O.C.

STEEL BY OTHERS

CURTAIN WALL TOEXTEND VERTICALLYTO BOTTOM OF W12

12

6' - 7 1/4"

W12x14 @6'-0" O.C.

L6x6x3/8 w/ 3/4x8"H.S. @ 12" O.C.

STEEL BY OTHERS

CURTAIN WALL TOEXTEND VERTICALLYTO BOTTOM OF W12

6' - 1 1/4" EOS

6' - 0" EOD

3' - 2 1/2"

11

4" EOS

3" EOD

L5x5x5/16 w/ 3/4x8"H.S. @ 12" O.C.

C

1' - 0" EOS

BENT PLATE 5/16x5x1'-2" LLHw/ 3/4x8" H.S. @ 16" O.C.

STRAP PLATE 1/8x1"@ 32" O.C.

PLATE 1/2" @ 2'-8" O.C.

11" EOD

STEEL BY OTHERS

B

2' - 6 1/2" EOS

W12x14 @ 6'-0" O.C.

L6x6x3/8 w/ 3/4x8"H.S. @ 12" O.C.

STEEL BY OTHERS

CURTAIN WALL TOEXTEND VERTICALLYTO BOTTOM OF W12

2' - 5" EOD

B

3' - 3 1/2"

W12x14 @ 6'-0" O.C.

L6x6x3/8 w/ 3/4x8"H.S. @ 12" O.C.

STEEL BY OTHERS

CURTAIN WALL TOEXTEND VERTICALLYTO BOTTOM OF W12

Level 446' - 0"

4TH TOS46' - 5"

2.6

STEEL BYOTHERS

L4x4x1/4xCONT.

CANTILEVERED W10x12

HSS6x3x1/4 w/ L3x3x1/4

L3x3x1/4 KICKER @ 6'-0" O.C.

C.9D

W12x14 @ 6'-0" O.C.

L6x6x3/8 w/ 3/4x8"H.S. @ 12" O.C.

STEEL BY OTHERS

CURTAIN WALL TOEXTEND VERTICALLYTO BOTTOM OF W12

3' - 4 1/2"

2' - 10 1/2" EOS

2' - 9" EOD 6' - 5" EOD

Level 446' - 0"

4TH TOS46' - 5"

A.2

4TH DROPPED44' - 11"

W18x35

2" STEEL DECK, SEEPLAN

HSS6x6 POST UP TOROOF ABOVE

L5x5x5/16

WEB STIFFENER (1/2")BELOW HSS6 POST(NS, FS)

6 1/8"

9 1/8" EOS

7" EOD

C

STEEL BY OTHERS

BENT PLATE 1/4 w 3/4"x8"H.S. @ 16" O.C.

1/2x8" PLATE @ 2'-8" O.C.

1' - 0" EOS

10" EOD

Level 218' - 0"

B

2ND TOS17' - 7"

BENT PLATE 1/4 w 3/4"x8"H.S. @ 16" O.C.

10" EOS

8" EOD

B

BENT PLATE 1/4 w 3/4"x8"H.S. @ 16" O.C.

10" EOS

8" EOD

Level 332' - 0"

C

3RD TOS31' - 7"

STEEL BY OTHERS

BENT PLATE 1/4 w 3/4"x8"H.S. @ 16" O.C.

1/2x8" PLATE @ 2'-8" O.C.

1' - 0" EOS

10" EOD

CHECKED BY:

DRAWN BY:

DATE:

PROJECT:

REVISIONS:

MEMBERS OF THE AMERICAN INSTITUTE OF ARCHITECTS

1

A

2 3 4 5 6

B

C

D

E

COPYRIGHT 2014 ALL RIGHTS RESERVEDPRINTED OR ELECTRONIC DRAWINGS ANDDOCUMENTATION MAY NOT BE REPRODUCEDIN ANY FORM WITHOUT WRITTEN PERMISSIONFROM LS3P ASSOCIATES LTD.

TEL. 864.235.0405 FAX 864.233.4027

GREENVILLE, SOUTH CAROLINA 29601

110 WEST NORTH STREET SUITE 300

ISS

UE

FO

R F

OU

ND

AT

ION

PE

RM

IT 1

2.9

.14

12/1

0/2

014 1

:29:4

0 P

M

\\A

a-s

bs11\D

ata

\AA

\Pro

jects

\LS

3P

\12-L

S3P

-17-C

ollab

I\B

uzzsaw

\_S

tru

ct

Syn

c F

old

er\

CU

-IC

AR

Researc

h O

ne_S

tru

ct_

2014.r

vt

12-LS3P-17

11.05.2014

Author

Checker

SECTIONS &DETAILS

S-208

CU-ICARRESEARCH ONE

12.9.2014

Owner

1" = 1'-0"S-208

1 Section 1" = 1'-0"S-208

2 Section 1" = 1'-0"S-208

3 Section 1" = 1'-0"S-208

4 Section

1" = 1'-0"S-208

5 Section 1" = 1'-0"S-208

6 Section 1" = 1'-0"S-208

7 Section 1" = 1'-0"S-208

8 Section

1" = 1'-0"S-208

9 Section

1" = 1'-0"S-208

10 Section 1" = 1'-0"S-208

11 Section 1" = 1'-0"S-208

12 Section 1" = 1'-0"S-208

13 Section

No. Description Date