    Appendix 1 FTA for Impluse Fai lure Decision 1 = not cause2 = possible cause

    3 =most possible cause

    Event No. Evaluation Decision Countermeasure

    (*) : Corrective action only

    1

    1

    ------------

    ------------

    No Load Test Showing similar

    result before and after impulse

    failure

    1 ------------3

    Not sufficent Clearance

    Defect Insulation

    1Clearancse are sufficient as per

    drawing & standard

    Visual Inspection did not found

    any defect2

    Factors

    Impulse

    Failure Lead

    Winding Defect Insulation (Interturn)

    Area of non live part too small

    (limited safety) (Big Bushing)4 2

    if using Big Bushing, live

    area space will be added

    5

    Did not consider the length of

    CT wire and understanding of

    live are inside transformer

    3

    1. Training & Path of CT

    Cables will be provided bu

    Design

    2. Make new Procedure for

    CT Installation

    MaterialCT secondary wire

    insulation7

    CT secondary Wire Design

    Manufacuring

    Inspection 6

    CT secondary insulation is

    designed only 3kV impulserated, and must be located in

    non live area. In this event, CT

    secondary wire is accidentaly

    located in live area which cause

    impulse failure

    1

    During corrective action, CTsecondary insulation is

    repaired and added, due to

    its insulation was little bit

    burned (*)

    Secondary Wire too

    long

    Inspection not done

    after installing the

    CT Wire

    No specific Inspection/Check

    List for CT Wire3

    Add Specific Inspection

    Cheklist for CT wire after

    connection to terminal Box