Appendix 1 FTA for Impluse Fai lure Decision 1 = not cause2 = possible cause
3 =most possible cause
Event No. Evaluation Decision Countermeasure
(*) : Corrective action only
1
1
------------
------------
No Load Test Showing similar
result before and after impulse
failure
1 ------------3
Not sufficent Clearance
Defect Insulation
1Clearancse are sufficient as per
drawing & standard
Visual Inspection did not found
any defect2
Factors
Impulse
Failure Lead
Winding Defect Insulation (Interturn)
Area of non live part too small
(limited safety) (Big Bushing)4 2
if using Big Bushing, live
area space will be added
5
Did not consider the length of
CT wire and understanding of
live are inside transformer
3
1. Training & Path of CT
Cables will be provided bu
Design
2. Make new Procedure for
CT Installation
MaterialCT secondary wire
insulation7
CT secondary Wire Design
Manufacuring
Inspection 6
CT secondary insulation is
designed only 3kV impulserated, and must be located in
non live area. In this event, CT
secondary wire is accidentaly
located in live area which cause
impulse failure
1
During corrective action, CTsecondary insulation is
repaired and added, due to
its insulation was little bit
burned (*)
Secondary Wire too
long
Inspection not done
after installing the
CT Wire
No specific Inspection/Check
List for CT Wire3
Add Specific Inspection
Cheklist for CT wire after
connection to terminal Box