CT Calculation which is useful to electrical engineers whose are looking opportunity in design field
Citation preview
HV side CTTransformer primary 33 KV Rct 1Transformer secondary 0.34 Kv Rr 0.15Transformer rating 1250 KVA Rl 0.32Transformer impedance 0.06 x/% Total 1.47CT ratio HV side 30CT ratio LV side 2500
Primary side CT Sec Side CTTransformer HV current 21.86996990692 A 0.7289989969 ATransformer LV current 2122.673549789 A 0.8490694199 A
Transformer HT fault current 364.4994984487 A 12.149983282 ATransformer LT fault current 35377.89249649 A 14.151156999 A
I(ft) secondary HV side 12.14998328162 AI(ft) secondary LV side 14.1511569986 A
K x I(ft) of HV side 24.29996656325 K is 2K x I(ft) of LV side 28.30231399719 Kis 2
Rct + Rb for HV side 1.47Rct + Rb for LV side 2.24639
V(K) HV CT k x I(ft) x (Rct + Rb) 35.72095084797V(K) LV CT k x I(ft) x (Rct + Rb) 63.57803514015
LV side CT NCTRct 2Rr 0.15Rl 0.09639
2.24639
HV side CTTransformer primary 33 KV Rct 1Transformer secondary 0.34 Kv Rr 0.15Transformer rating 1250 KVA Rl 0.32Transformer impedance 0.06 x/% Total 1.47CT ratio HV side 30CT ratio LV side 2500
Primary side CT Sec Side CTTransformer HV current 21.86996990692 A 0.7289989969 ATransformer LV current 2122.673549789 A 0.8490694199 A
Transformer HT fault current 364.4994984487 A 12.149983282 ATransformer LT fault current 35377.89249649 A 14.151156999 A
I(ft) secondary HV side 12.14998328162 AI(ft) secondary LV side 14.1511569986 A
K x I(ft) of HV side 24.29996656325 K is 2K x I(ft) of LV side 28.30231399719 Kis 2
Rct + Rb for HV side 1.47Rct + Rb for LV side 10.24639
V(K) HV CT k x I(ft) x (Rct + Rb) 35.72095084797V(K) LV CT k x I(ft) x (Rct + Rb) 289.9965471177
LV side CT NCTRct 10 Rct 4Rr 0.15 Rr 0.15Rl 0.09639 Rl 0.09639
10.24639 4.24639