10
1 of 4 pricecritical controls.com | 678.578.7495 | 2013-10-08 FUME HOOD CONTROLLER (FHC) The FHC is designed to control face velocity on variable volume fume hoods with audible and visual indicating alarms. The Fume Hood Controller can ensure a safe working environment by constantly monitoring and adjusting the exhaust to maintain a correct face velocity. The controller supports multiple air control devices including Venturi valves, LDV exhaust valves and Variable frequency drives. The controller comes standard with the both sidewall and sash position sensor inputs and both can be used together. The FHC is valve mounted and includes an analog input for monitoring the static pressure across the valve, alarming if minimum static pressures are met and can be used during test and balance to set up the system. The FHC integrates with the Price Laboratory space controller when airflow control calls for maintaining a volumetric offset between supply, general exhaust and fume hood exhaust flows. The FHC comes standard as a BTL – certified native BACnet device for simple integration with building management systems. CRITICAL CONTROLS - PRODUCT OVERVIEW Product Features Fume Hood Controller (FHC): • High speed flash base microprocessor • Multi-stage surge protection against voltage spikes on 24 VAC input • Simple connections to sidewall sensors (SWS) using RJ-12 jacks • 3 Sash position sensor inputs (10kΩ) • Pluggable terminal blocks • Mnet high-speed fume hood network port • Pressure port input, 0”- 5” w.c. (For measuring DP across Price Venturi Valve) • LED’s for Lnet data TX/RX, Lnet wiring fault, and RS-485 termination Fume Hood Interface (FHI) • Designed with audible and visual alarms • FHI Backlot LCD screen with LED sidebars • Password protected menu • Easy to use MENU system for fast and simple setup of system • Service port on back for use with Price LINKER2 setup software • Included RJ45 plenum rated cable for fast, error free hookup • Setup Wizard – walk through setup of PFHC when first powered up Sidewall Sensor (SWS) Features • Ultra Low flow digital temperature compensated pressure transducer • 25 ft. sensor cable with quick-connect installation • Sidewall assembly with easy-to-mount hardware Sash Position Sensor (SPS) Features • Ultra long life potentiometer (over 250,000 cycles) • Stainless steel cable for chemical resistance and strength • Metal mounting grommet for stable installation and reliability • Robust plastic cover for protection against airborne chemical agents

CRITICAL CONTROLS - PRODUCT OVERVIEW

  • Upload
    others

  • View
    4

  • Download
    0

Embed Size (px)

Citation preview

Page 1: CRITICAL CONTROLS - PRODUCT OVERVIEW

1 of 4pricecriticalcontrols.com | 678.578.7495 | 2013-10-08

FUME HOOD CONTROLLER (FHC)The FHC is designed to control face velocity on variable volume fume hoods

with audible and visual indicating alarms. The Fume Hood Controller can

ensure a safe working environment by constantly monitoring and adjusting the

exhaust to maintain a correct face velocity. The controller supports multiple

air control devices including Venturi valves, LDV exhaust valves and Variable

frequency drives.

The controller comes standard with the both sidewall and sash position

sensor inputs and both can be used together.

The FHC is valve mounted and includes an analog input for monitoring the

static pressure across the valve, alarming if minimum static pressures are met

and can be used during test and balance to set up the system.

The FHC integrates with the Price Laboratory space controller when airflow control calls for maintaining a volumetric offset

between supply, general exhaust and fume hood exhaust flows.

The FHC comes standard as a BTL – certified native BACnet device for simple integration with building management systems.

CRITICAL CONTROLS - PRODUCT OVERVIEW

Product FeaturesFume Hood Controller (FHC):

• High speed flash base microprocessor

• Multi-stage surge protection against voltage spikes on 24 VAC input

• Simple connections to sidewall sensors (SWS) using RJ-12 jacks

• 3 Sash position sensor inputs (10kΩ)

• Pluggable terminal blocks

• Mnet high-speed fume hood network port

• Pressure port input, 0”- 5” w.c. (For measuring DP across Price Venturi Valve)

• LED’s for Lnet data TX/RX, Lnet wiring

fault, and RS-485 termination

Fume Hood Interface (FHI)

• Designed with audible and visual alarms

• FHI Backlot LCD screen with LED sidebars

• Password protected menu

• Easy to use MENU system for fast and simple setup of system

• Service port on back for use with Price LINKER2 setup software

• Included RJ45 plenum rated cable for fast, error free hookup

• Setup Wizard – walk through setup of PFHC when first powered up

Sidewall Sensor (SWS) Features

• Ultra Low flow digital temperature compensated pressure transducer

• 25 ft. sensor cable with quick-connect installation

• Sidewall assembly with easy-to-mount hardware

Sash Position Sensor (SPS) Features

• Ultra long life potentiometer (over 250,000 cycles)

• Stainless steel cable for chemical resistance and strength

• Metal mounting grommet for stable installation and reliability

• Robust plastic cover for protection against airborne chemical agents

Page 2: CRITICAL CONTROLS - PRODUCT OVERVIEW

2 of 4pricecriticalcontrols.com | 678.578.7495 | 2013-10-08

SPECIFICATIONS

24 VAC, 50/60 Hz, 15VA (plus external loads), Class 2

10 C to 50 C (50 F to 122 F), 0% to 95% R.H. (non-condensing)

-30 C to 50 C (-22 F to 122 F), 0% to 95% R.H. (non-condensing)

2 Binary inputs: (Configurable for duct pressure status from LMX), 2 Analog inputs: 0-10 VDC inputs (configurable for sash sensor, sidewall sensor, flow measuring station, or duct pressure from LMX)

Accuracy better than 0.2% FS near zero, temperature compensated

2 dry binary outputs rated at 0.2 amps each (maximum 24 VAC/VDC), protected with thermal fuse, 2 analog outputs: (10mA maximum, 0-10 VDC), configurable for pressure and alarm outputs

RGB LEDs on Monitor side indicator bars and LCD screen

Status LEDs on all I/O

RJ45, RJ-12, Removable terminal blocks.

Fume hood communication port, RJ-45 connection

Optional Native BACnet MS/TP (BTL Listed)

Specifications subject to change without notice

Input Power (PRPM):

Environmental (operating):

Environmental (storage):

Inputs:

Sidewall pressure sensor:

Outputs:

Indicators:

Connections:

Communication:

FHI Display: 5 1/8”H x 3 1/4” W x 1 3/16” D - Fire Retardant Anti-Microbial Plastic

FHI Wall Plate: 4.5” H x 4.6” W x 2” D Stainless Steel with Fire Retardant Plastic Sensor Cover

5 1/8” H

3 1/4” W 1 3/16” D 3.5” clearance from wall for bend radius of cable

4.6” W

4.5” H

2” D

Page 3: CRITICAL CONTROLS - PRODUCT OVERVIEW

3 of 4pricecriticalcontrols.com | 678.578.7495 | 2013-10-08

TYPICAL WIRING

SELECTION CHART

FHMFUME HOOD

MONITOR

FHCFUME HOOD

CONTROLLER

LSCLABORATORY SPACE

CONTROLLER

Side wall Sensor Face Velocity Monitoring x x

Side wall Sensor Face Velocity Control x

Sash Position Sensor Face Velocity Control x

Combination Sidewall/Sash Position Face Velocity Control x

Analog Valve Pressure Output x x

Volumetric Offset Control x

Temperature Control x

Humidity Control x

Room Pressure Monitor x

Native BACnet x

Page 4: CRITICAL CONTROLS - PRODUCT OVERVIEW

4 of 4pricecriticalcontrols.com | 678.578.7495 | 2013-10-08

PRODUCT CODE

FHC-FHIKP-SWS-SPS1-OCC-PLSC

Model Hood Interface Sidewall Pressure Sensor Sash Position Sensor Occupancy Sensor Network Connectivity

FHC - Fume Hood Controller FHI-KP - Standard Keypad

Interface with 2 Line Display

SWS - 1 Sidewall Face

Velocity Sensor

SWS2 - 2 Sidewall Face

Velocity Sensors

SPS1,SPS2, SPS3 - Sash

Position Sensor

OCC - Infrared Fume Hood

Occupancy Sensor

Blank - None

PLSC - Network connection

to PLSC

BAC - Native BACnet MS/TP

interface

Page 5: CRITICAL CONTROLS - PRODUCT OVERVIEW

1 of 2pricecriticalcontrols.com | 678.578.7495 | 2013-10-08

Product FeaturesFHM:

• Measuresairflowusingaflowmeasuring

stationorsidewallsensor

• Highspeedflashbasedmicroprocessor

• Multi-stagesurgeprotectionagainst

voltagespikeson24VACinput

• NativeBACnetMS/TPConnection

• LED’sforBACnetdataTX/RX,BACnet

wiringfault,andMS/TPtermination

• Pluggableterminalblocks

• Electricalenclosurewith24VACtransformer

Interface Features:

• Designedwithaudibleandvisualalarms

• BacklitLCDScreenwithLEDsidebarsthatoffer

180degreeviewingofcurrentroomstatus

• Passwordprotectedmenus

• Easytousemenusystemforfast

andsimplesetupofsystem

• ServiceportonbackforusewithPrice

LINKER2setupsoftware

• IncludedRJ45plenumratedcable

forfast,errorfreehookup

• SetupWizard–walkthroughsetupof

FHMwhenfirstpoweredup

CRITICAL CONTROLS - PRODUCT OVERVIEW

FUME HOOD MONITOR (FHM)TheFumeHoodMonitor(FHM)isdesignedtoprovideintelligent

monitoringoffumehoodswithnativeBACnetcommunication.Using

thelatestinmicrocontrollerandsensortechnologiestheFHMcan

measureairflowusingacrossflowsensorintheductand,usingasash

positionsensor,displaythefacevelocityonthelocalLCDdisplay.

Themonitorfeaturesvisualandaudiblealarmssignalingunsafe

conditionswithilluminatingsidebarsprovide180degreevisualstatus.

Thecommissioningsoftwareallowsquickandthoroughsetupof

theFHMsystemwiththeabilitytogenerateaprintabletestreport.

Page 6: CRITICAL CONTROLS - PRODUCT OVERVIEW

2 of 2pricecriticalcontrols.com | 678.578.7495 | 2013-10-08

SPECIFICATIONS

120VACto24VAC,50/60Hz,50VAClass2

24VAC,50/60Hz,10VA(plusexternalloads),Class2

10Cto50C(50Fto122F),0%to95%R.H.(non-condensing)

-30Cto50C(-22Fto122F),0%to95%R.H.(non-condensing)

2Binaryinputs:(ConfigurableforductpressurestatusfromLMX)

2Analoginputs:0-10VDCinputs(configurableforsashsensor,sidewallsensor,flowmeasuringstation,orductpressurefromLMX)

±25Pa(0.1in.wg),accuracybetterthan 0.2%FSnearzero,temperaturecompensated

2drybinaryoutputsratedat0.2ampseach (maximum24VAC/VDC),protectedwiththermalfuse

2analogoutputs:(10mAmaximum,0-10VDC),configurableforpressureandalarmoutputs

RGBLEDsonMonitorsideindicatorbarsandLCDscreen

StatusLEDsonallI/O

RJ45,RJ-12,Removableterminalblocks.

Specifications subject to change without notice

Integrated Transformer:

Input Power (PRPM):

Environmental (operating):

Environmental (storage):

Inputs:

Sidewall pressure sensor:

Outputs:

Indicators:

Connections:

Page 7: CRITICAL CONTROLS - PRODUCT OVERVIEW

1 of 4pricecriticalcontrols.com | 678.578.7495 | 2013-10-08

LABORATORY SPACE CONTROLLER (LSC)The LSC is designed for laboratory applications that require airflow and

temperature control using a dedicated system that ties into the fume hoods

within the space. The digital controller maintains a constant volumetric offset

between the supply, general exhaust and fume hood air valves in the VAV system

to ensure accurate control of directional airflow. Fume hood controllers are daisy

chain wired to the controller and the local network uses Price M-Net for a less

than 1 second speed of response between the controllers.

The LSC can tie in a room pressure sensor to monitor the pressure in the space

with a local visual and audible alarm option available.

Room temperature and humidity are measured using a Price thermostat mounted

in the occupied space. Simple connection to thermostat is provided with plug and play RJ45 cables. Outputs for the LSC for

reheat and humidity include binary (24VAC), staged, and analog (0-10VDC).

With Native BACnet MS/TP communication, the LSC can tie into building management systems (BMS). When connected to

the network both the space and attached fume hood variables are available for monitoring and control.

Commissioning software allows quick and thorough setup of the LSC system with the ability to generate a printable test

report.

PRODUCT OVERVIEW

Product FeaturesLaboratory Space Controller (LSC):

• Volumetric control up to 8 supply or general exhaust valves

• System control of up to 16 fumehoods

• Temperature and humidity controls

• High speed flash based microprocessor

• Multi-stage surge protection against

voltage transients on 24 VAC input

• Pluggable terminal blocks

• Panel Enclosure or Valve mount options

• Two level password protected menus

• Service port on Thermostat or RPI for

use with Linker2 setup software

• Setup Wizard – walk through setup of

the PLSC when first powered up

• Simple plug and play RJ45 connections to the fume

hood controllers, thermostats, and pressure monitors.

Page 8: CRITICAL CONTROLS - PRODUCT OVERVIEW

2 of 4pricecriticalcontrols.com | 678.578.7495 | 2013-10-08

SPECIFICATIONS

24 VAC, 50/60 Hz, 15 VA (plus external loads), Class 2

10 C to 50 C (50 F to 122 F), 0% to 95% R.H. (non-condensing)

-30 C to 50 C (-22 F to 122 F), 0% to 95% R.H. (non-condensing)

2-6 Binary inputs: (Configurable for duct pressure status from LMX), 8-10 Analog inputs: 0-10 VDC inputs (configurable for valve, terminal airflow, or duct pressure from LMX), 1 temperature input: 10k type J analog thermistor RJ45 jack - Thermostat

±25 Pa (0.1 in. wg), accuracy better than 0.2% FS near zero, temperature compensated

2 dry binary outputs rated at 0.2 amps each (maximum 24 VAC/VDC), protected with thermal fuse

3 24 VAC binary outputs rated at 0.2 amps each (maximum 24 VAC/VDC), protected with thermal fuse

6 analog outputs: (10mA maximum, 0-10 VDC), configurable for pressure and alarm outputs, actuator (Venturi valve), reheat and humidifier

Status LEDs on all I/O

RJ45, RJ-12, Removable terminal blocks.

Fume hood communication port, RJ-45 connection

Optional Native BACnet MS/TP (BTL Listed)

Specifications subject to change without notice

Input Power:

Environmental (operating):

Environmental (storage):

Inputs:

Optional pressure sensor:

Outputs:

Indicators:

Connections:

Communication:

Page 9: CRITICAL CONTROLS - PRODUCT OVERVIEW

3 of 4pricecriticalcontrols.com | 678.578.7495 | 2013-10-08

TYPICAL WIRING

Page 10: CRITICAL CONTROLS - PRODUCT OVERVIEW

4 of 4pricecriticalcontrols.com | 678.578.7495 | 2013-10-08

DIMENSIONAL DATA

Electrical Enclosure: 8”W x 16”L x 3”D Powder Coat White Paint Finish

Top view

16” L 8” WSide view

8” W 3” D

PRODUCT CODE

SELECTION CHART

FHMFUME HOOD

MONITOR

FHCFUME HOOD

CONTROLLER

LSCLABORATORY SPACE

CONTROLLER

Side wall Sensor Face Velocity Monitoring x x

Side wall Sensor Face Velocity Control x

Sash Position Sensor Face Velocity Control x

Combination Sidewall/Sash Position Face Velocity Control x

Analog Valve Pressure Output x x

Volumetric Offset Control x

Temperature Control x

Humidity Control x

Room Pressure Monitor x

Native BACnet x

LSC-RPI-RPS1-BAC-SENS

Product Interface Type # of Pressure Sensors Network Type Thermostat Type

LSC - Laboratory Space Controller RPI - LCD Room Pressure Interface

RPS1 - One Room Pressure Sensor RPS2 - Two Room Pressure Sensors

BAC - Native BACnet MS/TP Network SENS- T-Stat with Blank FaceDIAL- T-Stat with Dial SetpointLCD- T-Stat with LCD ScreenLCDH - T-Stat with LCD Screen and Integrated Humidity SensorMOT- T-Stat with LCD Screen and Motion SensorC02H- T-Stat with LCD Screen and Integrated CO2 and Humidity Sensors