    P ower Genera to r S iz ing08/05/2010 12:20 PM

    Hi everybody, I am trying to size one diesel power generator to feed the 01 cooling water pumps. Its capacity is 160kW by Soft starter.

    Another 03 ones are also water pumps with 30kW each and star/delta starters.

    Question is that what I should keep my eyes on during the calculation. Since I have many references that give me different methods. One saidwe just add up the total load then give some percent to compensate for the efficiency of the generator, one said I need to consider the

    starting current of these pumps, one said I need to consider the starting capacity of the pumps and if the generator can delivery enough power

    for starting. It might be OK. I am considering about the starting current of motors that use soft starter. It starting current may increase up to

    3 or 4 percent of the nominal current. So, we will need to consider that or we just can ignore it because the starting time is quite short?

    I might have something in the mind already but I want to post it here to get your advices from experienced people.

    Tks,

    Hien

    __________________Anything that can go wrong, will go wrong

    Interested in this topic? By joining CR4 you can "subscribe" tothis discussion and receive notification when new comments are added.

    Join CR4, The Engineer's Place for News and Discussion!

    C omm ents ra ted to be Good Answ ers :These comments received enough positive ratings to make them "good answers".

    #2 "Re: Power Generator Sizing" by msamad on 08/05/2010 6:42 PM (score 3)

    #5 "Re: Power Generator Sizing" by msamad on 08/25/2010 7:17 PM (score 2)

    C omm ents ra ted to be "a lmos t " Good Answ ers :

    Check out these comments that don't yet have enough votes to be "official" good answers and, if you agree with them, rate them!

    #7 "Re: Power Generator Sizing" by msamad on 08/27/2010 7:30 PM (score 1)

    UnredundantGuru Re: Power Genera to r Siz ing

    08/05/2010 12:36 PM

    Some generators voltage regulators are negatively affected by soft starters and VFDs. I would suggest contacting the generator manufacturer

    Got Someth ing to Say?

    Search th is Forum

    Electrical Engineering:

    Search all of CR4

    CR4 Sect ions

    Aerospace

    BioMech & BioMed

    Chemical & Material

    Science

    Civil Engineering

    Communications &

    Electronics

    Education and

    Engineering Careers

    Electrical Engineering

    General

    Instrumentation

    Manufacturing

    MechanicalEngineering

    New Technologies &

    Research

    Software &

    Programming

    Sustainable

    Engineering

    Transportation

    Ask a Question

    Start a Discussion

    The Engineer's Place for News and Discussion Log in |Register

    https://twitter.com/intent/tweet?original_referer=http%3A%2F%2Fcr4.globalspec.com%2Fthread%2F58246%2FPower-Generator-Sizing&text=CR4%20-%20Thread%3A%20Power%20Generator%20Sizing%3A&tw_p=tweetbutton&url=http%3A%2F%2Fcr4.globalspec.com%2Fthread%2F58246%2FPower-Generator-Sizing%23.UVEqGfVkeU8.twitterhttp://twitter.com/search?q=http%3A%2F%2Fcr4.globalspec.com%2Fthread%2F58246%2FPower-Generator-Sizinghttp://cr4.globalspec.com/user/registerhttp://cr4.globalspec.com/comment/606941/Re-Power-Generator-Sizinghttp://void%280%29/http://void%280%29/http://cr4.globalspec.com/http://cr4.globalspec.com/section/electrical-engineeringhttp://cr4.globalspec.com/forum/electrical-engineeringhttp://cr4.globalspec.com/thread/58239/Calculating-Water-Heater-Capacity-for-a-Standard-Olympic-Size-Swimming-Poolhttp://cr4.globalspec.com/thread/58248/DG-Neutral-Earthinghttp://cr4.globalspec.com/edit/discussionsubscribe?objecttype=THREAD&objectid=58246http://cr4.globalspec.com/edit/addratingvote?objecttype=THREAD&objectid=58246http://cr4.globalspec.com/thread/58246/Power-Generator-Sizing?sort=linear&order=aschttp://cr4.globalspec.com/member/30399/hien-nguyenquochttp://cr4.globalspec.com/user/registerhttp://cr4.globalspec.com/member/13928/Unredundanthttp://cr4.globalspec.com/section/aerospacehttp://cr4.globalspec.com/section/biomed-biomechhttp://cr4.globalspec.com/section/chemical-material-sciencehttp://cr4.globalspec.com/section/chemical-material-sciencehttp://cr4.globalspec.com/section/civil-engineeringhttp://cr4.globalspec.com/section/communications-electronicshttp://cr4.globalspec.com/section/communications-electronicshttp://cr4.globalspec.com/section/engineering-careershttp://cr4.globalspec.com/section/engineering-careershttp://cr4.globalspec.com/section/electrical-engineeringhttp://cr4.globalspec.com/section/generalhttp://cr4.globalspec.com/section/instrumentationhttp://cr4.globalspec.com/section/manufacturinghttp://cr4.globalspec.com/section/mechanical-engineeringhttp://cr4.globalspec.com/section/mechanical-engineeringhttp://cr4.globalspec.com/section/new-technologieshttp://cr4.globalspec.com/section/new-technologieshttp://cr4.globalspec.com/section/software-programminghttp://cr4.globalspec.com/section/software-programminghttp://cr4.globalspec.com/section/sustainable-engineeringhttp://cr4.globalspec.com/section/sustainable-engineeringhttp://cr4.globalspec.com/section/automotivehttp://cr4.globalspec.com/edit/newthread?pt=1http://cr4.globalspec.com/edit/newthread?pt=2http://cr4.globalspec.com/user/loginhttp://cr4.globalspec.com/user/registerhttp://cr4.globalspec.com/user/registerhttp://cr4.globalspec.com/user/loginhttp://cr4.globalspec.com/http://cr4.globalspec.com/edit/newthread?pt=2http://cr4.globalspec.com/edit/newthread?pt=2http://cr4.globalspec.com/edit/newthread?pt=1http://cr4.globalspec.com/edit/newthread?pt=1http://cr4.globalspec.com/section/automotivehttp://cr4.globalspec.com/section/automotivehttp://cr4.globalspec.com/section/sustainable-engineeringhttp://cr4.globalspec.com/section/sustainable-engineeringhttp://cr4.globalspec.com/section/sustainable-engineeringhttp://cr4.globalspec.com/section/software-programminghttp://cr4.globalspec.com/section/software-programminghttp://cr4.globalspec.com/section/software-programminghttp://cr4.globalspec.com/section/new-technologieshttp://cr4.globalspec.com/section/new-technologieshttp://cr4.globalspec.com/section/new-technologieshttp://cr4.globalspec.com/section/mechanical-engineeringhttp://cr4.globalspec.com/section/mechanical-engineeringhttp://cr4.globalspec.com/section/mechanical-engineeringhttp://cr4.globalspec.com/section/manufacturinghttp://cr4.globalspec.com/section/manufacturinghttp://cr4.globalspec.com/section/instrumentationhttp://cr4.globalspec.com/section/instrumentationhttp://cr4.globalspec.com/section/generalhttp://cr4.globalspec.com/section/generalhttp://cr4.globalspec.com/section/electrical-engineeringhttp://cr4.globalspec.com/section/electrical-engineeringhttp://cr4.globalspec.com/section/engineering-careershttp://cr4.globalspec.com/section/engineering-careershttp://cr4.globalspec.com/section/engineering-careershttp://cr4.globalspec.com/section/communications-electronicshttp://cr4.globalspec.com/section/communications-electronicshttp://cr4.globalspec.com/section/communications-electronicshttp://cr4.globalspec.com/section/civil-engineeringhttp://cr4.globalspec.com/section/civil-engineeringhttp://cr4.globalspec.com/section/chemical-material-sciencehttp://cr4.globalspec.com/section/chemical-material-sciencehttp://cr4.globalspec.com/section/chemical-material-sciencehttp://cr4.globalspec.com/section/biomed-biomechhttp://cr4.globalspec.com/section/biomed-biomechhttp://cr4.globalspec.com/section/aerospacehttp://cr4.globalspec.com/section/aerospacehttp://cr4.globalspec.com/member/13928/Unredundanthttp://cr4.globalspec.com/user/registerhttp://cr4.globalspec.com/group/member/1815http://cr4.globalspec.com/group/member/1633http://cr4.globalspec.com/group/member/1632http://cr4.globalspec.com/member/30399/hien-nguyenquochttp://cr4.globalspec.com/member/30399/hien-nguyenquochttp://cr4.globalspec.com/thread/58246/Power-Generator-Sizing?sort=linear&order=aschttp://cr4.globalspec.com/edit/addratingvote?objecttype=THREAD&objectid=58246http://cr4.globalspec.com/edit/addratingvote?objecttype=THREAD&objectid=58246http://cr4.globalspec.com/edit/discussionsubscribe?objecttype=THREAD&objectid=58246http://cr4.globalspec.com/thread/58248/DG-Neutral-Earthinghttp://cr4.globalspec.com/thread/58239/Calculating-Water-Heater-Capacity-for-a-Standard-Olympic-Size-Swimming-Poolhttp://cr4.globalspec.com/forum/electrical-engineeringhttp://cr4.globalspec.com/section/electrical-engineeringhttp://cr4.globalspec.com/http://void%280%29/http://void%280%29/http://void%280%29/http://void%280%29/http://cr4.globalspec.com/comment/606941/Re-Power-Generator-Sizinghttp://cr4.globalspec.com/user/registerhttp://twitter.com/search?q=http%3A%2F%2Fcr4.globalspec.com%2Fthread%2F58246%2FPower-Generator-Sizinghttps://twitter.com/intent/tweet?original_referer=http%3A%2F%2Fcr4.globalspec.com%2Fthread%2F58246%2FPower-Generator-Sizing&text=CR4%20-%20Thread%3A%20Power%20Generator%20Sizing%3A&tw_p=tweetbutton&url=http%3A%2F%2Fcr4.globalspec.com%2Fthread%2F58246%2FPower-Generator-Sizing%23.UVEqGfVkeU8.twitterhttps://twitter.com/intent/tweet?original_referer=http%3A%2F%2Fcr4.globalspec.com%2Fthread%2F58246%2FPower-Generator-Sizing&text=CR4%20-%20Thread%3A%20Power%20Generator%20Sizing%3A&tw_p=tweetbutton&url=http%3A%2F%2Fcr4.globalspec.com%2Fthread%2F58246%2FPower-Generator-Sizing%23.UVEqGfVkeU8.twitterhttps://twitter.com/intent/tweet?original_referer=http%3A%2F%2Fcr4.globalspec.com%2Fthread%2F58246%2FPower-Generator-Sizing&text=CR4%20-%20Thread%3A%20Power%20Generator%20Sizing%3A&tw_p=tweetbutton&url=http%3A%2F%2Fcr4.globalspec.com%2Fthread%2F58246%2FPower-Generator-Sizing%23.UVEqGfVkeU8.twitter
  • 7/29/2019 CR4 - Thread_ Power Generator Sizing

    2/6

    CR4 - Thread: Power Generator Sizing

    http://cr4.globalspec.com/thread/58246/Power-Generator-Sizing[3/26/2013 10:27:09 AM]

    Register to Reply

    #2In reply to #1

    Register to Reply

    #3In reply to #2

    Register to Reply

    Join Date: Feb 2008Location: The "Sunny sideof the street".Posts: 1309Good Answers: 42

    concerning these issues.

    __________________

    No matter how much you push the envelope, it'll still be stationery.

    msamadGuru

    Join Date: Feb 2009Location: Houston, USAPosts: 956Good Answers: 236

    Re: Power Genera to r Siz ing08/05/2010 6:42 PM

    I would like to ask you to see this thread first: http://cr4.globalspec.com/thread/45119

    Now, come to your point:

    You have total load 160 KW + 3 x 30 KW = 250 KW

    I am assuming all are continuous. So, in terms of capacity, you at least need a generator of the capacity 250 KW.

    Now consider these two possible worse starting scenarios:

    (1) All of the 30 KW motor running and you will be starting the 160 KW motor (soft starter)

    (2) 2 of the 30 KW motor and the 160 KW motor running and you will be starting the third 30 KW motors (start delta starter)

    In the scenario (1), you need 2 to 3 (average 2.5) times capacity of generator to start it. So, the generator capacity required is 30 x 3 + 2.5 x160 = 490 KW

    In scenario (2), you need almost 4 times (worst case like DOL starting), capacity to start it. So, the generator capacity required is 160 + 2 x 30

    + 4 x 30 = 340 KW.

    The scenario (1) is the worst case starting scenario. So, based on this scenario, the capacity required is 490 KW. You can select 500 KW

    generator.

    However, if the system allows you to start 160 KW motor every time keeping all other 3 motor stopped. Then you can select 160 x 2.5 = 400

    KW generator.

    You also need to consider the future load and add it on top of this required capacity.

    - MS

    __________________"All my technical advices in this forum must be consulted with and approved by a local registered professional engineer before implementation" -

    Mohammed Samad (Linkedin Profile: http://www.linkedin.com/in/msamad)

    Good Answer (Sco re 3 )

    Go to Next Good Answer

    hien.nguyenquocPower-User

    Join Date: Sep 2009Location: BH, VietnamPosts: 438Good Answers: 1

    Re: Power Genera to r Siz ing08/06/2010 9:27 AM

    MS, tks for youe reply,

    Hien

    __________________

    Anything that can go wrong, will go wrong

    Site D irecto r ies

    Forum Directory

    Blog Directory

    User Group Directory

    RSS Feeds

    CR4 Store

    CR4 Rules of Conduct

    CR4 FAQ

    Site Glossary

    Who's Online(173 right now)

    Show Members

    3

    http://cr4.globalspec.com/user/registerhttp://cr4.globalspec.com/comment/607136/Re-Power-Generator-Sizinghttp://cr4.globalspec.com/user/registerhttp://cr4.globalspec.com/comment/607460/Re-Power-Generator-Sizinghttp://cr4.globalspec.com/user/registerhttp://cr4.globalspec.com/member/23650/msamadhttp://cr4.globalspec.com/thread/45119http://cr4.globalspec.com/member/30399/hien-nguyenquochttp://cr4.globalspec.com/browse/allforumshttp://cr4.globalspec.com/browse/allblogshttp://cr4.globalspec.com/browse/allgroupshttp://cr4.globalspec.com/rss/rss_indexhttp://www.zazzle.com/cr4_merchhttp://cr4.globalspec.com/faq/cr4ruleshttp://cr4.globalspec.com/faqhttp://cr4.globalspec.com/faq/glossaryhttp://cr4.globalspec.com/search/onlinehttp://cr4.globalspec.com/browse/membershttp://googleads.g.doubleclick.net/aclk?sa=L&ai=B9BjzGipRUc6lJenCigfF-YCQCv-G048DAAAAEAEgADgAUMKxhb8GWJfsy6BFYOXS5IOoDoIBF2NhLXB1Yi02MDM1NTEzODUzMTA4OTc5sgESY3I0Lmdsb2JhbHNwZWMuY29tugEJZ2ZwX2ltYWdlyAED2gGMAWh0dHA6Ly9jcjQuZ2xvYmFsc3BlYy5jb20vYWQvc2hvd2FkP3pvbmU9Q1I0X0VsZWN0cmljYWxFbmdpbmVlcmluZyZzaXplPTE2MHg2MDAmb3JkPTU5NDc0NDQzJnBhZ2U9JTJGdGhyZWFkJTJGNTgyNDYlMkZQb3dlci1HZW5lcmF0b3ItU2l6aW5nwAIC4AIA6gIlNDI1MC9DUjQuR1MvQ1I0X0VsZWN0cmljYWxFbmdpbmVlcmluZ_gC9dEekAOaCJgD4AOoAwHQBJBO4AQBoAYU&num=0&sig=AOD64_0gsYlf35K19gYigzFe3XgVQ5aI1g&client=ca-pub-6035513853108979&adurl=http://www.deltron.com/http://cr4.globalspec.com/browse/membershttp://cr4.globalspec.com/search/onlinehttp://cr4.globalspec.com/faq/glossaryhttp://cr4.globalspec.com/faqhttp://cr4.globalspec.com/faq/cr4ruleshttp://www.zazzle.com/cr4_merchhttp://cr4.globalspec.com/rss/rss_indexhttp://cr4.globalspec.com/browse/allgroupshttp://cr4.globalspec.com/browse/allblogshttp://cr4.globalspec.com/browse/allforumshttp://cr4.globalspec.com/group/member/1815http://cr4.globalspec.com/group/member/1633http://cr4.globalspec.com/group/member/1632http://cr4.globalspec.com/member/30399/hien-nguyenquochttp://cr4.globalspec.com/member/30399/hien-nguyenquochttp://cr4.globalspec.com/thread/45119http://cr4.globalspec.com/member/23650/msamadhttp://cr4.globalspec.com/member/23650/msamadhttp://cr4.globalspec.com/member/13928/Unredundanthttp://cr4.globalspec.com/user/registerhttp://cr4.globalspec.com/comment/607460/Re-Power-Generator-Sizinghttp://cr4.globalspec.com/user/registerhttp://cr4.globalspec.com/comment/607136/Re-Power-Generator-Sizinghttp://cr4.globalspec.com/user/register
  • 7/29/2019 CR4 - Thread_ Power Generator Sizing

    3/6

    CR4 - Thread: Power Generator Sizing

    http://cr4.globalspec.com/thread/58246/Power-Generator-Sizing[3/26/2013 10:27:09 AM]

    #4In reply to #2

    Register to Reply

    #5In reply to #4

    hien.nguyenquocPower-User

    Join Date: Sep 2009Location: BH, VietnamPosts: 438Good Answers: 1

    Re: Power Genera to r Siz ing08/24/2010 12:44 AM

    Ms, it is me again for the question.

    As I referred to ABB soft starter handbook, it is implied that normally the sort starter's stating current is around 3 t o 4 t i m e s FLC. Since

    the motors are rather big so could you explain it again?

    Nevertheless, I referred to some other manual provided by CAT - generator supplier. They recommended one calculation method based on

    NEMA std and i t i s so comp l i ca ted . To do do this, I must gather many information such as SkVA/hp, RLC, Motor code... But these things

    are just applied within the US and we are not. In fact, do we need to follow this procedure? I took my looks over some suppliers like CAT,

    Siemens... they also recommended the same procedure. To be concluded, I found that whatever the method they are using, the original is

    to based on the starting capacity of the motor.

    I have been struggling on how to grasp one good and simple method of generator sizing. I dont want to design by myself and I want to

    follow some standardized procedures but it seems impossible.

    Hien

    __________________

    Anything that can go wrong, will go wrong

    msamadGuru

    Join Date: Feb 2009Location: Houston, USAPosts: 956Good Answers: 236

    Re: Power Genera to r Siz ing08/25/2010 7:17 PM

    The calculation that I posted in comment # 2 is a type of short-cut method. Here is more detail calculation for the generator capacity

    (though the final result is same):

    Loads:

    Water Pump 1 motor: 30 KW, 0.8 p.f, 380V, 57A

    Water Pump 2 motor: 30 KW, 0.8 p.f, 380V, 57A

    Water Pump 2 motor: 30 KW, 0.8 p.f, 380V, 57A

    Cooling Water Pump motor: 160 KW, 0.8 p.f, 380V, 304A, (assumed starting p.f = 0.25, DOL stating current is 6 times of FLA)

    (The p.f and voltage are assumed 0.8 and 380V respectively)

    Befo re the s ta r t i ng o f the Coo l i ng Wate r pum p:

    Total running load (rKW): 90 KW

    Total running KVA (rKVA): 90/0.8 = 112 KVA

    D ur ing s ta r t i ng o f the C oo l i ng Wate r pump:

    DOL Starting Cooling Water KVA (sKVA) = (1.732 x 380 x 6 x 304 x 1.2)/1000 = 1440 KVA

    Soft Starter Starting Cooling Water KVA (sKVA) = 1440 x 0.6 = 864 KVA

    Starting Cooling Water KW = 1440 x 0.25 = 360 KW

    Soft Starter Starting Cooling Water KW = 864 x 0.25 = 216 KW

    (The multiplier 1.2 is for 20% contingency and 0.6 for soft starter starting, it is assumed that the soft starter reduces 40% of starting

    current, starting current 4 times of FLA)

    Total KVA during starting (sKVA) = 864 + 112 = 976 KVA

    Total KW during starting (sKW) = 216 + 90 = 3 0 6 K W

    (The starting time of the motor is considered 15 seconds)

    2

    http://cr4.globalspec.com/comment/615790/Re-Power-Generator-Sizinghttp://cr4.globalspec.com/user/registerhttp://cr4.globalspec.com/comment/616906/Re-Power-Generator-Sizinghttp://cr4.globalspec.com/member/30399/hien-nguyenquochttp://cr4.globalspec.com/member/23650/msamadhttp://cr4.globalspec.com/member/23650/msamadhttp://cr4.globalspec.com/member/23650/msamadhttp://cr4.globalspec.com/group/member/1815http://cr4.globalspec.com/group/member/1633http://cr4.globalspec.com/group/member/1632http://cr4.globalspec.com/member/30399/hien-nguyenquochttp://cr4.globalspec.com/member/30399/hien-nguyenquochttp://cr4.globalspec.com/comment/616906/Re-Power-Generator-Sizinghttp://cr4.globalspec.com/user/registerhttp://cr4.globalspec.com/comment/615790/Re-Power-Generator-Sizing
  • 7/29/2019 CR4 - Thread_ Power Generator Sizing

    4/6

    CR4 - Thread: Power Generator Sizing

    http://cr4.globalspec.com/thread/58246/Power-Generator-Sizing[3/26/2013 10:27:09 AM]

    Register to Reply

    #6In reply to #5

    Register to Reply

    #7In reply to #6

    Af te r the s ta r t i ng o f the C oo l ing Wate r pum p:

    Total running load (rKW): 90 + 160 = 2 5 0 K W

    Total running KVA (rKVA): 250/0.8 = 312 KVA

    Now, you have to select a generator whose continuous capacity is 312 KVA and momentary capacity (for 15 seconds) is at least 976 KVA.

    Also select the engine whose continuous capacity is 250 KW and momentary capacity (for 15 seconds) is at least 306 KW.

    If you select a 500 KW generator (p.f 0.8), the KVA rating of the generator is 500/0.8 = 625 KVA. Every generator has some overload

    capacity for short time duration. The NEMA standard generators can withstand 50% load for at least 30 sec. Considering the overload

    capacity, the generator has the capability to supply 625 x 1.5 = 937 KVA for at least 30 seconds (and more than 976 KVA for 15 seconds

    for sure). So, 500 KW generator should work fine for these loads.

    Voltage dip is also one factor that requires selecting the generator reactances but in this type of load, it is not so important.

    I also would suggest you to consult with the generator manufacturer for final selection.

    N ote fo r H ien : I sent you the Caterpillar work sheet (that you emailed me yesterday) with filling out the information of you loads including

    my comments. Please check your email.

    - MS

    __________________

    "All my technical advices in this forum must be consulted with and approved by a local registered professional engineer before

    implementation" - Mohammed Samad (Linkedin Profile: http://www.linkedin.com/in/msamad)

    Good Answer (Sco re 2 )

    No more Good Answers. Go to first "Almost" Good Answer

    hien.nguyenquocPower-User

    Join Date: Sep 2009Location: BH, VietnamPosts: 438Good Answers: 1

    Re: Power Genera to r Siz ing08/26/2010 10:32 PM

    MS, I suggest to close the topic here since your answer said it all. It is very useful and I think I have got what I have been looking for.

    Hope you will be always fine. Please contribute more for this forum. Thank you,

    Hien

    __________________

    Anything that can go wrong, will go wrong

    msamadGuru

    Join Date: Feb 2009Location: Houston, USAPosts: 956Good Answers: 236

    Re: Power Genera to r Siz ing

    08/27/2010 7:30 PM

    I have p rov ided answ ers t o some H ien ' s ques t i ons by ema i l . Fo r fu r the r re fe rence , I pas ted th em here so tha t o the r eng ineers

    can be bene f i ted i n fu tu re :

    1. At this case, we can start the biggest cooling pump first, then we go for the rest pumps. The generator capacity would be much

    reduced. Right? '

    Yes, it will reduce to at least 50 KW to 100 KW

    2. What does "voltage dip" mean? And 10, 20 or 30% are our requirement? It means if I am the customer, I will request the supplier for

    this?

    Voltage dip is the momentary voltage drop within the generator during first few cycles of the motor starting. It is due to the synchronous

    reactance of the generator. The higher the generator capacity, the lower the reactance value, the lower is the voltage dip. See this link:

    http://www.re-volt.us/pdf/CPS_info_sheet_38_Voltage_Dip.pdf. This curve is almost same as NEMA 32.18.2 (definition of voltage dip).

    3. Is that Ok with 30% voltage dip? Does it affect to the controller e.g the contactor coils will be unable to hold closing? In the case thisgenerator will have to provide power for the lighting system, will 30% voltage dip be accepted?

    Unless the system has very voltage sensitive loads (sensitive relay, contactor), 30% voltage dip is ok.

    http://cr4.globalspec.com/user/registerhttp://cr4.globalspec.com/comment/617584/Re-Power-Generator-Sizinghttp://cr4.globalspec.com/user/registerhttp://cr4.globalspec.com/comment/618060/Re-Power-Generator-Sizinghttp://cr4.globalspec.com/member/30399/hien-nguyenquochttp://cr4.globalspec.com/member/23650/msamadhttp://www.re-volt.us/pdf/CPS_info_sheet_38_Voltage_Dip.pdfhttp://www.re-volt.us/pdf/CPS_info_sheet_38_Voltage_Dip.pdfhttp://www.re-volt.us/pdf/CPS_info_sheet_38_Voltage_Dip.pdfhttp://cr4.globalspec.com/member/23650/msamadhttp://cr4.globalspec.com/member/23650/msamadhttp://cr4.globalspec.com/group/member/1815http://cr4.globalspec.com/group/member/1633http://cr4.globalspec.com/group/member/1632http://cr4.globalspec.com/member/30399/hien-nguyenquochttp://cr4.globalspec.com/member/30399/hien-nguyenquochttp://cr4.globalspec.com/comment/618060/Re-Power-Generator-Sizinghttp://cr4.globalspec.com/user/registerhttp://cr4.globalspec.com/comment/617584/Re-Power-Generator-Sizinghttp://cr4.globalspec.com/user/register
  • 7/29/2019 CR4 - Thread_ Power Generator Sizing

    5/6

    CR4 - Thread: Power Generator Sizing

    http://cr4.globalspec.com/thread/58246/Power-Generator-Sizing[3/26/2013 10:27:09 AM]

    Register to Reply

    #8In reply to #7

    Register to Reply

    4. Is voltage dip different from voltage drop and how it is different? Normally, we need the voltage drop during motor starting to be kept

    within 10%. I don't understand why they have three kinds of voltage dip?

    Yes. As already mentioned, the voltage dip is the momentary (few cycles) voltage drop within the generator, voltage drop is the withinthe cable and transformers.

    5 . If some educational books say that we just need to gather all of starting current of the motors. Then choose the generator whose

    running current is equal of higher than these total starting currents. Is that not clear and incorrect?

    This is correct if all of motors are started same time. However, it is even not 100% correct.

    6. I have contacted some local suppliers and they obviously don't understand about the sKVA that the generator can provide during motor

    starting.

    These are so technical terms; generally local suppliers don't have this level of knowledge. They generally use some short-cut calculation.

    7. If all these things have been go through, do I need to double check by recalculate the "voltage drop" in the cable during motor

    starting. We need it within 10%.

    Yes, it is correct. You can go up to 20% for total voltage drop during starting (for NEMA motor). After starting is over, it should be not

    more than 5%.

    See more information in these sites:

    http://ecmweb.com/training/electrical_basics/electric_sizing_gensets_large

    http://www.buyerzone.com/facilities/generators/rbic-power-quality-08.html

    http://www.myemergencygenerator.com/site/1324593/page/555882

    http://www.gregorypoole.com/products/electricpowergenerator/Documents/LEBE5294-02%20Electric%

    20Power%20Application%20Sizing.pdf

    http://www.dieselduck.ca/machine/03%20electricity/alternator.htm

    http://www.cashmanequipment.com/UserFiles/Uploaded/cms/motor-start-concerns.pdf

    http://www.gillettegenerators.com/sizing/sizing03.html

    http://forums.mikeholt.com/showthread.php?p=1161144

    http://www.buyerzone.com/facilities/generators/rbic-power-quality-01.html

    http://www.kwietpower.com/_docs/motor_starting/sizing_inst.pdf

    http://www.kohlerpower.com/common/pdfs/83474_GensetMotorStarting_Final.pdf

    - MS

    __________________

    "All my technical advices in this forum must be consulted with and approved by a local registered professional engineer before

    implementation" - Mohammed Samad (Linkedin Profile: http://www.linkedin.com/in/msamad)

    Score 1 fo r Good Answer

    No more "Almost" Good Answers.

    JRaefGuru

    Join Date: Sep 2006Location: California, USA,where the Godless livenext door to God.Posts: 3368Good Answers: 447

    Re: Power Genera to r Siz ing08/27/2010 8:17 PM

    Nice work.

    __________________

    ** All I every really wanted to be, was... A LUMBERJACK!.**

    http://cr4.globalspec.com/user/registerhttp://cr4.globalspec.com/comment/618064/Re-Power-Generator-Sizinghttp://cr4.globalspec.com/user/registerhttp://ecmweb.com/training/electrical_basics/electric_sizing_gensets_largehttp://www.buyerzone.com/facilities/generators/rbic-power-quality-08.htmlhttp://www.myemergencygenerator.com/site/1324593/page/555882http://www.gregorypoole.com/products/electricpowergenerator/Documents/LEBE5294-02%20Electric%20Power%20Application%20Sizing.pdfhttp://www.gregorypoole.com/products/electricpowergenerator/Documents/LEBE5294-02%20Electric%20Power%20Application%20Sizing.pdfhttp://www.dieselduck.ca/machine/03%20electricity/alternator.htmhttp://www.cashmanequipment.com/UserFiles/Uploaded/cms/motor-start-concerns.pdfhttp://www.gillettegenerators.com/sizing/sizing03.htmlhttp://forums.mikeholt.com/showthread.php?p=1161144http://www.buyerzone.com/facilities/generators/rbic-power-quality-01.htmlhttp://www.kwietpower.com/_docs/motor_starting/sizing_inst.pdfhttp://www.kohlerpower.com/common/pdfs/83474_GensetMotorStarting_Final.pdfhttp://cr4.globalspec.com/member/2294/JRaefhttp://cr4.globalspec.com/group/member/1389http://cr4.globalspec.com/group/member/1388http://cr4.globalspec.com/member/2294/JRaefhttp://cr4.globalspec.com/member/2294/JRaefhttp://www.kohlerpower.com/common/pdfs/83474_GensetMotorStarting_Final.pdfhttp://www.kohlerpower.com/common/pdfs/83474_GensetMotorStarting_Final.pdfhttp://www.kwietpower.com/_docs/motor_starting/sizing_inst.pdfhttp://www.kwietpower.com/_docs/motor_starting/sizing_inst.pdfhttp://www.buyerzone.com/facilities/generators/rbic-power-quality-01.htmlhttp://www.buyerzone.com/facilities/generators/rbic-power-quality-01.htmlhttp://forums.mikeholt.com/showthread.php?p=1161144http://forums.mikeholt.com/showthread.php?p=1161144http://www.gillettegenerators.com/sizing/sizing03.htmlhttp://www.gillettegenerators.com/sizing/sizing03.htmlhttp://www.cashmanequipment.com/UserFiles/Uploaded/cms/motor-start-concerns.pdfhttp://www.cashmanequipment.com/UserFiles/Uploaded/cms/motor-start-concerns.pdfhttp://www.dieselduck.ca/machine/03%20electricity/alternator.htmhttp://www.dieselduck.ca/machine/03%20electricity/alternator.htmhttp://www.gregorypoole.com/products/electricpowergenerator/Documents/LEBE5294-02%20Electric%20Power%20Application%20Sizing.pdfhttp://www.gregorypoole.com/products/electricpowergenerator/Documents/LEBE5294-02%20Electric%20Power%20Application%20Sizing.pdfhttp://www.gregorypoole.com/products/electricpowergenerator/Documents/LEBE5294-02%20Electric%20Power%20Application%20Sizing.pdfhttp://www.myemergencygenerator.com/site/1324593/page/555882http://www.myemergencygenerator.com/site/1324593/page/555882http://www.buyerzone.com/facilities/generators/rbic-power-quality-08.htmlhttp://www.buyerzone.com/facilities/generators/rbic-power-quality-08.htmlhttp://ecmweb.com/training/electrical_basics/electric_sizing_gensets_largehttp://ecmweb.com/training/electrical_basics/electric_sizing_gensets_largehttp://cr4.globalspec.com/user/registerhttp://cr4.globalspec.com/comment/618064/Re-Power-Generator-Sizinghttp://cr4.globalspec.com/user/register
  • 7/29/2019 CR4 - Thread_ Power Generator Sizing

    6/6

    CR4 - Thread: Power Generator Sizing

    http://cr4.globalspec.com/thread/58246/Power-Generator-Sizing[3/26/2013 10:27:09 AM]

    #9In reply to #2

    Register to Reply

    Copy to Clipboard

    gkkumarAssociate

    Join Date: Sep 2010Posts: 47

    Re: Power Genera to r Siz ing09/19/2010 10:57 AM

    if we using VVVFD or VFD what will be the capacity of generator for 250 KW motor

    Register to Reply 9 comments

    Back to top

    Interested in this topic? By joining CR4 you can "subscribe" tothis discussion and receive notification when new comments are added.

    Join CR4, The Engineer's Place for News and Discussion!

    C omm ents ra ted to be Good Answ ers :

    These comments received enough positive ratings to make them "good answers".

    #2 "Re: Power Generator Sizing" by msamad on 08/05/2010 6:42 PM (score 3)

    #5 "Re: Power Generator Sizing" by msamad on 08/25/2010 7:17 PM (score 2)

    C omm ents ra ted to be "a lmos t " Good Answ ers :Check out these comments that don't yet have enough votes to be "official" good answers and, if you agree with them, rate them!

    #7 "Re: Power Generator Sizing" by msamad on 08/27/2010 7:30 PM (score 1)

    Users who posted comments:

    gkkumar (1); hien.nguyenquoc (3); JRaef(1); msamad (3); Unredundant (1)

    Previous in Forum: Calculating Water Heater Capacity for a Standard Olympic Size Swimming Pool Next in Forum: DG Neutral Earthing

    You might be interested in: Hand Pumps and Foot Pumps, Piston Pumps and Plunger Pumps, DC Powered Pumps

    "Dil igence is the m other of good fortune." - - Miguel de Cervantes

    All times are displayed in US/Eastern (EDT) (Register to change time zone)

    2013 IHS.GlobalSpec, the GlobalSpec logo, SpecSearch, the Engineering Web,

    the Engineering Search Engine, CR4 and Conference Room 4 are registered trademarks of IHS.All other company and product names may be trademarks of their respective owners. No portion

    of this site may be copied, retransmitted, reposted, duplicated or otherwise used without theexpress written permission of IHS GlobalSpec, 30 Tech Valley Dr. Suite 102, East Greenbush, NY, 12061

    http://cr4.globalspec.com/comment/629062/Re-Power-Generator-Sizinghttp://cr4.globalspec.com/user/registerhttp://cr4.globalspec.com/member/41577/gkkumarhttp://cr4.globalspec.com/user/registerhttp://cr4.globalspec.com/user/registerhttp://cr4.globalspec.com/member/41577/gkkumarhttp://cr4.globalspec.com/member/30399/hien-nguyenquochttp://cr4.globalspec.com/member/2294/JRaefhttp://cr4.globalspec.com/member/23650/msamadhttp://cr4.globalspec.com/member/13928/Unredundanthttp://cr4.globalspec.com/thread/58239/Calculating-Water-Heater-Capacity-for-a-Standard-Olympic-Size-Swimming-Poolhttp://cr4.globalspec.com/thread/58248/DG-Neutral-Earthinghttp://www.globalspec.com/SpecSearch/Suppliers/Flow_Transfer_Control/Pumps/Hand_Pumpshttp://www.globalspec.com/SpecSearch/Suppliers/Flow_Transfer_Control/Pumps/Piston_Plunger_Pumpshttp://www.globalspec.com/SpecSearch/Suppliers/Flow_Control_Flow_Transfer/Pumps/DC_Pumpshttp://cr4.globalspec.com/user/registerhttp://cr4.globalspec.com/user/registerhttp://googleads.g.doubleclick.net/aclk?sa=L&ai=Bs5YKGipRUdftJYW6igfypoFwr8e_gAMAAAAQASAAOABQw6js_wJYp_Pd30Vg5dLkg6gOggEXY2EtcHViLTYwMzU1MTM4NTMxMDg5NzmyARJjcjQuZ2xvYmFsc3BlYy5jb226AQlnZnBfaW1hZ2XIAQPaAYsBaHR0cDovL2NyNC5nbG9iYWxzcGVjLmNvbS9hZC9zaG93YWQ_em9uZT1DUjRfRWxlY3RyaWNhbEVuZ2luZWVyaW5nJnNpemU9NzI4eDkwJm9yZD01OTQ3NDQ0MyZwYWdlPSUyRnRocmVhZCUyRjU4MjQ2JTJGUG93ZXItR2VuZXJhdG9yLVNpemluZ8ACAuACAOoCJTQyNTAvQ1I0LkdTL0NSNF9FbGVjdHJpY2FsRW5naW5lZXJpbmf4AvXRHpADmgiYA-ADqAMB0ASQTuAEAaAGFA&num=0&sig=AOD64_0Fbcb9H11KEWucrB1Op1BVDJ3-mg&client=ca-pub-6035513853108979&adurl=http://WWW.solarinstitute.bizhttp://cr4.globalspec.com/rss/rss_use?feedUrl=%2Fforum%2Frss%2Felectrical%2Dengineeringhttp://www.globalspec.com/SpecSearch/Suppliers/Flow_Control_Flow_Transfer/Pumps/DC_Pumpshttp://www.globalspec.com/SpecSearch/Suppliers/Flow_Transfer_Control/Pumps/Piston_Plunger_Pumpshttp://www.globalspec.com/SpecSearch/Suppliers/Flow_Transfer_Control/Pumps/Hand_Pumpshttp://cr4.globalspec.com/thread/58248/DG-Neutral-Earthinghttp://cr4.globalspec.com/thread/58239/Calculating-Water-Heater-Capacity-for-a-Standard-Olympic-Size-Swimming-Poolhttp://cr4.globalspec.com/member/13928/Unredundanthttp://cr4.globalspec.com/member/23650/msamadhttp://cr4.globalspec.com/member/2294/JRaefhttp://cr4.globalspec.com/member/30399/hien-nguyenquochttp://cr4.globalspec.com/member/41577/gkkumarhttp://cr4.globalspec.com/user/registerhttp://cr4.globalspec.com/user/registerhttp://cr4.globalspec.com/member/41577/gkkumarhttp://cr4.globalspec.com/user/registerhttp://cr4.globalspec.com/comment/629062/Re-Power-Generator-Sizing