Upload
usama-awad
View
217
Download
0
Embed Size (px)
Citation preview
8/11/2019 Corrosion Protection Evaluation of Some Organic Coatings Incorrosion Protection Evaluation
1/61
CORROSION PROTECTION EVALUATION
OF SOME ORGANIC COATINGS IN
WATER TRANSMISSION LINES1
Anees U. Malik, Shahreer Ahmad, Ismail Andijani
Fahad Al-Muaili, T.L. Prakash and John OHara
Research & Development Center,
Saline Water Conversion Corporation
P.O. Box # 8328, Al-Jubail 31951, Kingdom of Saudi Arabia
SUMMARY
As an alternative to cementitious materials, organic polymeric materials have long been
considered for pipe coatings. This is due to their good corrosion resistance, imperviousity to
water/air, resistant to salinity, immunity to large variations in pH and chemical and physical
stabilities at moderately high temperatures. Keeping in view the viability of organic coatings
as promising area of water research, a project proposal entitled Corrosion Protection
Evaluation of Some Organic Coatings in Water Transmission Lines was formulated by the
Corrosion Department of R&D Center, Al-Jubail which was subsequently sponsored and
funded by King Abdul Aziz City for Science and Technology (KACST) as a one year short
project.
The project encompasses short and long terms testing of three types of organic coatings, viz.,
polyethylene (PE), polyurethane (PU) and fusion bonded epoxy (FBE) on steel in order to
determine the corrosion behavior in aqueous environment with special reference to product
water. The work of the project was divided into seven tasks, namely, Task-I: litera ture survey,
Task-2 : establishment of facilities, Task-3: mechanical testing, Task-4 : wet tests, Task-5:
impedance studies, and task-6: data analysis and report preparation. Coating materials,
namely, FBE-Scotchkote-206N, PUAqualine-600A, PU-Irathane-155 and 3 layer PE were
used for the studies. Wet tests consisting of salt fog, autoclave and close circuit corrosion
loop were carried out to study the corrosion behavior of coating, water uptake or permeation
1
Issued as Technical Report No. TR 3804/APP 95009 in November 1999.
1966
8/11/2019 Corrosion Protection Evaluation of Some Organic Coatings Incorrosion Protection Evaluation
2/61
and stability of coating under high temperature and pressure. The mechanical testing
consisted of adhesion, bending and cathodic disbonding tests provided information about the
adhesivity or bonding of the coating to the substrate, resistance to cracking, disbonding,
delamination or other mechanical damage as a result of bending. Cathodic disbondment testprovides adhesion assessment and determines resistance of the coating to C.P and current
flow. AC impedance measurements evaluate quantitatively the water uptake by the coatings
and non-destructive determination of cathodic disbondment.
The results of accelerated tests (salt fog tests) showed that in the scribed-coated samples, the
creepage increases with increasing exposure time. FBE, 3 layer PE and Irathane-155 (PU)
show no blistering after 100 days exposure in salt spray cabinet but Aqualine-600A (PU)show blistering on scribed and unscribed surfaces. Autoclave tests were carried out to
determine the behavior of coatings under high temperature and pressure. The results of the
tests indicate that FBE, Aqualine-600A and 3 layer PE coatings are quite resistant to waters
at 40oC and 1500 psi but Irathane155 shows decrease in thickness in liquid as well as vapor
phases and also exhibits slight decoloration, swelling and texture appearance in both phases.
This is an indication of degradation of Irathane-155 in water under high temperature and
pressure. Close circuit loop test results of 4 weeks exposure in water indicate no markedchange in the color and texture of the coating. There was no perceptible change in weight
during 1 month exposure to water at 25oC.
The results of adhesion tests on coatings showed that the binding between the metal substrate
and the coating was more than the coating and the dolly. The pull off adhesion tests carried
out on coated samples after autoclave tests showed that adhesive strength of all the coating is
greater than 500 psi. The flexibility (bending) tests carried out on coatings show no defect orpresence of holidays at the bending site. On the basis of radial disbondment measurements
from cathodic disbondment tests, the decreasing performance of the coatings can be
represented as :
FBE > 3 layer PE > Aqualine 600 > Irathane 155
It is important to note that during cathodic disbondment tests at 25C and 40C, Aqualine 600
and Irathane 155 were found swelled and sticky.
1967
8/11/2019 Corrosion Protection Evaluation of Some Organic Coatings Incorrosion Protection Evaluation
3/61
The results of AC impedance tests carried out on all the coatings in 3% NaCl indicate no
water uptake by the coatings even after 6 months of exposure.
A detailed analysis of the results from immersion, electrochemical and mechanical studies
carried out on four organic coatings indicates that only FBE appears to have right
combination of properties which make it viable for consideration as an internal coating for
pipes. The results of cathodic disbondment tests show that as external coatings both FBE and
PE can be employed under cathodic protection conditions.
1. INTRODUCTION
In recent years, there are several cases of pipe failures in the form of leakages, bursting or
cracking of the pipelines [1-4]. In majority of cases the failures have been attributed mainly to
rebar corrosion, which is caused by permeability of chloride from low resistivity soil. The
problem is acute in areas where the soil, besides having high chloride contents, has
intermittent dry and wet spells. As a possible alternative to cementitious materials, in recent
years, a number of olefin, vinyl and epoxy based polymer coating have appeared in the market.
Epoxy based paints or coatings have been employed as internal linings as well as external
coatings in considerable number of pipelines in the Kingdom. The epoxy paints are quite
impervious to water/air and are resistant to salinity; large variations in pH and temperatures
but surprisingly their performance record have not been consistently satisfactory [1]. Fiber
reinforced plastics (FRP) have been used on limited scale in desalination plants for distillate
transmission and in seawater intake [5]. However, FRP pipelines have never been used in
large diameter long distance water transmission system perhaps due to their fabrication
limitation and strength factors. Fusion bonded epoxy (FBE) and fusion bonded polyurethane
(FBU) based coatings have been used for internal and external applications for transmitting
potable water though on limited scale [6]. Polyethylene coatings have been used as external
coatings but constitute one of the 3 layers of olefin based internal linings [7-8]. These coatings
appear to have characteristic properties required for application in water transmission system
but performance data about these coatings are sketchy and therefore, a detailed and systematic
performance evaluation is essential.
1968
8/11/2019 Corrosion Protection Evaluation of Some Organic Coatings Incorrosion Protection Evaluation
4/61
Keeping in view this background, a project proposal entitled Corrosion Protection Evaluation
of Some Organic Coatings in Water Transmission Line had been formulated and which was
subsequently sponsored by King Abdul Aziz City for Science and Technology (KACST) as a
one-year short project. The proposed studies encompass accelerated and short term testing ofsome polymer coatings (polyethylene, polyurethane and fusion bonded epoxy) on steel in
order to determine the corrosion behavior in aqueous environment with special reference to
product water. There is paucity of data regarding the behavior of these coatings in product
water and the results of the studies are likely to provide data, which would be useful in
selection of pipe coating materials for water transmission system.
1.1 Organic Coatings
Organic coatings, applied on properly pretreated surfaces, are the most common and most
effective mode of corrosion protection for metallic objects and structures. The exterior
surfaces of corrodible metals such as iron and steel are effectively protected from their
environment by a coating system. Organic coatings have also been used for protection of
porous refractory surfaces such as cement mortar or concrete structures, which are pervious to
moisture or gases.
Despite the fact that the pipeline coating represents only about 5% of the total cost, the choice
of the most effective coating is a key point to guarantee the life of the installed pipelines. A
recent survey [9] of the failures of the protective coatings on pipeline indicates that 48.8%
failures are attributed to delamination, 26.8% to blisters; loss of gloss, solvent entrapment and
pinholes account 9.7% each (the total exceeds 100% because some of the cases show
combined multiple failure phenomena). For failure avoidance, considerations ofenvironmental factors and nature of flow medium are most important issues for selection of
suitable coating materials.
A large variety of organic polymeric materials belonging to different functional groups have
been used as external coatings for open air or buried pipelines. Asphalt mastic and asphalt
enamel, coal tar epoxy, extruded polyethylene, fusion bonded epoxy, multilayer polyolefin
coating systems including polyethylene or polypropylene and polyurethane are some of themost widely used organic pipe coatings for external applications. Polyethylene coatings
1969
8/11/2019 Corrosion Protection Evaluation of Some Organic Coatings Incorrosion Protection Evaluation
5/61
having an FBE primer and a 2-layer polyethylene based material extruded over it has been
used extensively through out the world in recent years [10, 11]. In such coatings, the epoxy
provides good adhesion to steel and good cathodic disbonding characteristics, which are
combined with water barrier and good mechanical properties of polyethylene. Thecombination has better adhesion, cathodic disbonding resistance, hydrolytic stability and
impact strength than either coating used by it self. For internal coatings, fusion-bonded epoxy
(FBE) and fusion bonded polyurethane (FBU) based coatings are promising materials as
internal coatings and have been used for transmitting water though on limited scale.
1.2 FBE as I nternal Coatings for Water Transmission
Cement concrete and fusion-bonded epoxy (FBE) is the two major types of internal lining
used in steel pipes for potable water transmission purposes. The literature is abounded with
references on the technology and application of cement concrete pipes. The cement concrete
internal lined pipes appear to have best performance under positive Langelier index conditions
when protective carbonate scales are formed on the lining. FBE has many advantages over
cement concrete, which include:
(i) Saving in pipe thickness (or material).
(ii) Chemical inertness over a broad range of pH.
(iii) Presence of smooth and chemically inert surface.
(iv) High friction resistance surface.
(v) Ease in coating of complex shapes.
(vi) Ease in field welding.
(vii) Ease in transportation of large size pipes and consequent saving in cost.
FBE linings have been extensively used by SAUDI ARAMCO in their water injection systems
and appear to be performing satisfactorily [12]. FBE internally lined pipes have been used for
water transmission purpose in U.K., U.S.A and other parts of the world for the last several
years [12]. For example, Scotch 206N (FBE) internal lined pipes have been used since 1978
in U.K for drinking water pipelines and no failure has been reported so far [13]. In U.S.A.
East Bay Municipal Utility has been using Scotckote fusion epoxy 134, 203 and 206N as
external and internal coatings in their potable water system for more than 20 years [14].
1970
8/11/2019 Corrosion Protection Evaluation of Some Organic Coatings Incorrosion Protection Evaluation
6/61
1.3 Ef fect of Chlori de Contamination on FBE Coating Perf ormance
Soluble salt contamination can cause premature failure on virtually all types of coatings.
Amongst the anions, chloride is the single most damaging anion because it migrates under
coating film. Chloride containing solution has a high osmotic pressure contributing to
moisture penetration, loss of adhesion and blistering. The source of chloride contamination
could be from environment around metallic surface, corrosion products and pits. Alblas and
Londen [15] reviewed the literature concerning the effect of chloride contamination on the
corrosion of coated steel surfaces. Appleman [16], Helvig [17], Weldon [18] and Flores [19]
showed various correlations between level of chloride and premature coating failures. These
investigators apply the contaminant (chloride) in known quantities to the steel surface and
apply the coating shortly thereafter. Niel and Whitehurst [20] used chloride contaminations
that remained in the micropits after sand blasting of steel surface for studying FBE coating
performance. They found that in presence of pitted surface, chloride contamination could
cause serious loss of performance in FBE coatings in hot cathodic disbonding and hot water
tests. For underground coatings and other immersion coatings in critical applications, a
maximum chloride level of 2 g/cm2was suggested [21].
1.4 Polyurethane as I nternal Coating for Water Transmission
Moisture curing polyurethane based coatings has long been used for construction and
rehabilitation of steel structures providing economical reliable protection. These coatings with
proven, long-term field applications can be applied over both abrasive- blasted and power tool
cleaned steel. They are quick to dry and cure, provide good adhesion and endurance, they do
not embrittle with age and retain their color and gloss. Polyurethane has a long chain polymer
structure with a number of building blocks including a backbone resin or polyol (A) a di-
isocyanate (B) and a curing agent, usually a diol or diamine. The polyol component usually
contains pigments. A coating is formed when the two components are combined; a rapid and
exothermic chemical polymerization reaction takes place.
1971
8/11/2019 Corrosion Protection Evaluation of Some Organic Coatings Incorrosion Protection Evaluation
7/61
O
R-NCO + R-OH = R- N- C - OR
HB A
Isocyanate Polyol Urethane
The exothermic nature of this chemical reaction enables the coatings to be applied at almost
any ambient temperature. The chemical resistance of such coatings is directly related to the
degree of cross-linking of polymer. A highly cross-linked system generally results in good
chemical and corrosion resistance. The desirable attributes for internal lining is that the
material should be solvent free with good mechanical properties, e.g., abrasion resistance,
tensile strength, elasticity and adhesion and good resistance to water. Polyurethane polymers
based on different resins, e.g., polyester, polyether, etc. generally fulfil the requirements
although the selection of appropriate polymer depends upon particular service environment.
For example, a polyester based polyurethane will generally not offer as good a long term
performance in water as a polyether based material. Polyurethane coating material Aqualine-
600A has been used for internal coating applications [22]. It meets the British regulations for
use with cold potable water and for hot water (60 oC). During long-term contact with water, it
is imperative for polyurethane coating to undergo hydrolysis causing thickening and even
gelation of the material. Water is normally miscible with polyols and there is no apparent
reaction of water with polyol component while the water is absorbed. When the water
contaminated polyol component meets with the Isocyanate component, the following reaction
occurs:
O
2 ( R NCO) + H2O = > R-HN C HN R + CO2
Isocyanate Urea
1972
8/11/2019 Corrosion Protection Evaluation of Some Organic Coatings Incorrosion Protection Evaluation
8/61
CO2 is evolved from the reaction generating bubbles in the coating during cure. If there is
significant bubbling then the physical and chemical properties will be diminished.
Solvent free polyurethane sometimes called multicomponent liquid urethane or high buildelastomeric urethanes have been commercially available for more than 30 years. These
coatings have gained wide acceptance for at least 15 years for their resistance to corrosion,
impact, and abrasion, and for their thermal insulation properties. In general, solvent free
polyurethanes offers the advantages of speed of application under almost all environmental
conditions, rapid cure and return to service time, long-life maintenance free periods and a
reasonable life-cycle cost per liter [23]. Solvent free polyurethanes have proven performance
on pipelines, structural steel work and steel structures.
In recent years, a new generation of solvent free polyurethane materials have been developed
which offer high strength and have elongation at breaking points [24]. This combination of
properties allows the materials to stretch over a crack without rupturing. The results of
immersion tests on solvent free polyurethane at ambient and high temperatures indicate a 20
years life expectancy at ambient temperature and a reduction in tensile strength of only about
30% over a two years period. The solvent free polyurethane confirms to the most stringentpotable water regulation 25 section (1) paragraph (a) administered by the Drinking Water
Incorporate of the U.K. Department of the Environment [22].
1.5 Electrochemical Impedance Spectroscopy (EI S) As Appl ied to Coatings
The most common methods used to analyze the degradation of coated metal surface are
potential/time, DC resistance, polarization curve, polarization resistance, galvanic current,dynamic relaxation and AC impedance at fixed and wide range frequency. Several reviews
are published on electrochemical methods for coated metal evaluation [25-27]. The
potential/time method is time consuming while in other DC methods some DC potential has to
be applied which can disturb the equilibrium at the coating/metal interface. While using these
methods, the highly resistive nature of the coating and ohmic drop can cause severe distortions
on polarization curves resulting in the underestimation of corrosion rates. However, in AC
impedance tests, a small AC signal is applied which may not cause disturbance to the system(5-10 mv peak to peak). A corroding system can be expressed in terms of an electric circuit
1973
8/11/2019 Corrosion Protection Evaluation of Some Organic Coatings Incorrosion Protection Evaluation
9/61
network consisting of various elements like resistors, capacitors and inductors, which can be
determined by analyzing the response received upon applying the AC signal. Thus AC
impedance technique becomes a basic tool for characterization/evaluation of coated metal
surfaces, inhibitors and any corroding system.
Electrochemical Impedance Spectroscopy (EIS) has found widespread application in coating
technology. The availability of modern instrumentation to obtain impedance data as well as
computer program to interpret the results has made the technique popular [28]. EIS is very
suited to the study of polymeric coated metals. From experimental data it is possible to
establish relationship of different physico-chemical parameters with the values of the
corresponding components of the equivalent electric circuit and obtain trend towardsdegradation, water absorption, porosity and corrosion rate. The latter can be evaluated as a
function of natural or artificial degradation phenomenon including mechanical deformation
[29]. Considering the determination of water absorption in coating, EIS measures the flow of
electric current through a coating film. A good barrier allows very little current flow, heavy
current flow, on the other hand, indicates a poor barrier, which means salt and water
permeated the coating and set up conditions for corrosion. In a study [30] concerning with
behavior of polyurethane coating in a 3% NaCl aqueous solution, the data analysis was carriedout using a simple Ru(RcCc) equivalent circuit, where Ru, Rc and Ccare electrolyte resistance,
ohmic resistance and capacitance of the coating, respectively. The coating capacitance, Cc,
which would be accurately determined by EIS, was used for the evaluation of the barrier
properties of the coatings. Analysis of the results shows that Cc values, which depend on
coating formation and thickness increase with exposure time indicating progressive absorption
of water by the coating. Generally, the primer/intermediate/top coat systems were found to be
particularly effective barrier against water and ion penetration as indicated by their lowcapacitance variation after prolonged exposure to the test solution. Epoxy model coatings [31]
were investigated while immersed in a 3% NaCl solution using EIS during first stage of the
exposure where water uptake is the main process and long-term exposure when the corrosion
starts. The results of the impedance measurement on the water uptake of the coatings showed
that the entering water not only affects the dielectric properties but also yields swelling of the
coating polymer. Impedance measurement during the long-term immersion showed that the
start of the corrosion process under high impedance barrier type coatings can be detected bythe changes of the dielectric properties of the coating. Kellner [32] carried out EIS studies on
1974
8/11/2019 Corrosion Protection Evaluation of Some Organic Coatings Incorrosion Protection Evaluation
10/61
polyethylene, coal tar enamel and fusion bonded epoxy (FBE) to compare the extent of water
penetration into these coatings. Mansfield et al. [33] performed EIS tests for coated sheet
(polybutadiene) and aluminum alloys in 0.5 N NaCl solution with different pretreatment
procedures. Based upon this analysis, ranking of different pretreatment procedures was carriedout. During the degradation of marine paints on steel, the primary controlling factor in the life
of the paint was the amount of water uptake while ionic concentration was a secondary
controlling factor [34]. For the optimization of automotive electro-deposited coatings,
container interior coatings and industrial maintenance coating, EIS data were used to predict
corrosion protection, film porosity, solution absorption into the coatings and film
delamination properties [35]. Variables such as resin contents, cross link densities, cure
temperatures and solvent types and contents were evaluated for the various types of coating. Ingeneral, EIS data correlated well with conventional exposure test results such as salt fog, cycle
scale corrosion and delamination test. The impedance spectra permits a rather rapid (15-75
min per sample) assessment of coating film characteristic even when no visually observable
changes have occurred. EIS provides a technique to optimize coatings while reducing the time
of coating evaluation and gives insight into chemical and physical properties of the coatings.
Titz et al. [36] characterized the protection of coatings through EIS and determinedquantitatively the local defects within the coating and delamination effects at the substrate
coating interface. EIS method has been applied successfully to evaluate the degradation of
organic coating on stainless steel (SS) with a macroscopic line defect [37]. The delamination
propagated in the direction normal to the macroscopic defect during the corrosion test, and a
thin electrolyte layer was formed under the delaminated coatings. EIS data are interpreted in
terms of a model in which the equivalent circuit of SS/coating/solution interfaces are
composed of a parallel of the circuits for a macroscopic defective part and for a delaminationpart. The detection and mapping of chemical heterogeneities or physical defects in organic
coatings [38] have been carried out using local electrochemical impedance spectroscopy
method (LEIS). Coating failure initiates as a local event at defects which can result from
chemical heterogeneities in the resin or physical defects such as bubbles, under film deposits
or pin holes. The study helped in identifying the source of failure (i.e. coating chemistry,
methods of application and cure schedule) and providing an insight into the mechanism of
degradation.
1975
8/11/2019 Corrosion Protection Evaluation of Some Organic Coatings Incorrosion Protection Evaluation
11/61
While considering the selection of organic coating for pipelines some common defects which
are characteristic of these types of coating are to be taken into account. These defects include
blistering, early rusting, anodic undermining, filiform corrosion, cathodic delamination and
loss of adhesion.
1.6 Blistering
Blistering is one of the first signs of the breakdown in the protective nature of the coating. The
blisters are local regions where the coating has lost adherence from the substrate and where
water may accumulate and corrosion may begin. Under different circumstances, blister
formation can follow different mechanism [39].
Sometimes water absorption leads to swelling of the coating and when this occurs locally for
any reason, blisters may form and water may accumulate at the interface [40]. Potential
gradients developed due to galvanic coupling may cause electroendosmosis, leading to a
blister. There are reported cases of blistering of internal epoxy coating in product water
transmission lines [1].
The osmotic mechanism is probably the most common mechanism by which blisters form
[41]. The driving force for osmotic blistering is the presence of soluble salt at the
coating/substrate interface. As water penetrates the coating to the interface, a concentrated
solution is developed with sufficient osmotic force to drive water from the coating surface to
the interface and a blister is formed.
1.7 Ear ly Rusting
This term is applied to a measles-like rusting that occurs after the coating has dried to the
touch. It only occurs after the coated metal is exposed to high moisture conditions [42]. The
three conditions, which lead to early rusting, are: (i) a thin latex coating (< 40 m), (ii) a cool
substrate temperature, and (iii) high moisture conditions. Thus, early rusting is a consequence
of moist conditions occurring before the latex coating has dried sufficiently.
1.8 Anodic Undermin ing
Anodic undermining represents that class of corrosion reactions underneath an organic coating
in which the major separation process is the anodic corrosion reaction. An outstanding
1976
8/11/2019 Corrosion Protection Evaluation of Some Organic Coatings Incorrosion Protection Evaluation
12/61
example is the dissolution of the thin coating between the organic coating and the steel
substrate in a food container. In each case, the cathodic reaction may involve a component in
the foodstuff or a defect in the tin coating, exposing iron, which then serves as the cathode.
The tin is selectively dissolved and the coating separates from the metal and loses itsprotective character. Aluminum is particularly susceptible to anodic undermining [43].
1.9 F il if orm Corr osion
Filiform corrosion is a type of attack in which the corrosion process manifests itself as thread
like filaments. It represents a specialized form of anodic undermining. It generally occurs in
humid environments and is most common under organic coatings on steel, aluminum,
magnesium and zinc. In some cases, filiform corrosion will develop on uncoated steels onwhich small amounts of contaminating salts have been accidentally deposited.
The threads which form in filiform corrosion exhibit a wide variety of appearance from
nodular shapes such as those on aluminum to the very fine, sharply-defined threads observed
on steel [44]. Corrosion products appeared in the form of thread like filaments in the inner
walls of liquid applied epoxy coated water transmission pipe lines, presumably indicate a
filiform corrosion attack [1].
1.10 Cathodic Delamination
One of the undesirable consequences of cathodic protection is that the coating adjoining the
defect may separate from the substrate metal. This loss of adhesion is known as the "Cathodic
Delamination". It is generally believed [45, 46] that the major driving force for cathodic
delamination in corrosion processes is the presence of air in the cathodic reaction.
H2O + O2+ 2e = 2OH-
When an applied potential is used, the important reaction may be:
2H+ + 2e- = H2
Studies indicate that the pH beneath the organic coating where the cathodic reaction occurs ishighly alkaline [47] as the cathodic equation indicates. The hydroxyl ions generated appear to
1977
8/11/2019 Corrosion Protection Evaluation of Some Organic Coatings Incorrosion Protection Evaluation
13/61
have major destructive influence on the organic coating/substrate bond. The strong alkaline
environment may attack the oxide at the interface or may attack the polymer. Attack of the
oxide hasbeen observed and there is clear evidence that carboxylated species are present at
the interfaceas aresult of hydroxyl ion attack of the polymer [48]. The mechanism of accessof water and oxygen is not well established. Water and oxygen reach the reaction site largely
by diffusion through the coating [49], however, it appears unlikely to eliminate completely
these constituents by diffusion through the defect zone of the coating [50]. Another
mechanism involves electron transfer to the polymer functional groups along the coating
electrolyte interface during cathodic delamination of the polymer coating [51].
2. OBJECTIVES
The following are the project objectives on which different tasks are based.
(i) To investigate the influence of chloride ion, pH, temperature and pressure on the
corrosion resistance behavior of fusion bonded epoxy (FBE), polyethylene (PE) and
polyurethane (PU) coatings in product water of desalination plants.
(ii) To investigate the mechanism of adhesion loss of coated metals in hot water test.
(iii) To study the protective behavior of above-mentioned coatings in a corrosion test loop.(iv) To determine the ability of alkali metal ions to migrate through various coatings under
a potential gradient and correlate this ability of alkali ions with the cathodic
delamination resistance of different coatings.
(v) To determine whether the cathodic delamination is due to the attack of hydroxide ion
on polymer or on metal oxide at the coating/substrate interface.
(vi) Evaluation of anti-corrosion behavior of the above mentioned coatings by computer
controlled AC impedance measurements.(vii) Comparison of performance of all three coatings and evaluation their suitability for
water transmission systems by conducting short duration or accelerated tests.
3. PROJECT DESIGN
Following are the outlines of the different tasks, which have been completed for achieving the
objectives of the project.
1978
8/11/2019 Corrosion Protection Evaluation of Some Organic Coatings Incorrosion Protection Evaluation
14/61
Task 1 - Literature Survey
Literature survey covers the important research work carried out in field of protective
behavior of organic coatings particularly FBE, PE and PU during the last 15 years.
Task 2 - Establishment of Facilities
Experimental facilities were attained to carry out the tests under different tasks. This
includes fabrication of corrosion test loop and cathodic disbondment test assembly,
acquisition of adhesion tester, holiday detector and coating thickness gauge. Some of the
tests such as autoclave tests were carried out by the outside agencies. The coating material
specimens were acquired from different coating facilities inside and outside the Kingdom.
Figures 1-9show photographs of coated panels received and the equipment used during
the testing.
Task 3 - Mechanical Testing
It comprised of the following tests:
(a) Adhesion (b) Bending (c) Cathodic Disbondment.
Task 4 - Wet Tests
It consisted of salt spray or salt fog test, close circuit loop and autoclave tests.
Task 5 - Impedance Studies
It consisted of AC impedance tests.
Task 6 - Data Analysis and Report Preparation
4. EXPERIMENTAL
4.1 Coating
Three types of organic coatings namely, Fusion Bonded Epoxy (FBE) Scotchkote-206N,
Polyurethane (PU) Aqualine-600A, PU-Irathane-155 and 3-Layer Polyethylene (PE) were
employed for the studies(Figure1).
4.1.1 Fusion Bonded Epoxy (FBE)
FBE coated panels specimens of Scotchkote-206 N were obtained from Al-Qahtani Pipe
Terminal (AQPT) of Dammam of the following specifications:
1979
8/11/2019 Corrosion Protection Evaluation of Some Organic Coatings Incorrosion Protection Evaluation
15/61
8/11/2019 Corrosion Protection Evaluation of Some Organic Coatings Incorrosion Protection Evaluation
16/61
4.1.3.1 Aqualine-600A
Color: Gray
Thickness & coupon size: Size Coating Thickness Quantity
(mm) (mils) (Nos.)
100x 50 ~35-40 50
200x 200 ~40-55 50
200x 25 ~20-30 25
Pipes: Two internally coated pipes of 68 mm diameter and
500 mm long.
4.1.3.2 Irathane-155
Type: Polyurethane (PU)
Name: Irathane 155 with Primer
Color: Yellow
Thickness & coupon size:
Size Coating Thickness Quantity
(mm) (mils) (Nos.)
100x 50 ~35-40 50
200x 200 ~30-50 50
200x 25 ~40-50 25
Pipes : Two internally coated pipes of 68 mm diameter and
500 mm long.
4.2 Equipment
Following instruments have been used for carrying out the experimental work for this project.
(i) Salt spray cabinet
(ii) Holiday Detector; with Calibration Meter- model AP-W, Tinker and Rasor.
(iii) Coating Thickness Meter, Elcometer Model 345 and Posi Tector-2000.
(iv) Adhesion Meter from DYNA Proceq, Zurich, Switzerland.
(v) Cathodic Disbondment Testing Assembly It was fabricated in the Corrosion
Research Lab. from the parts acquired through Thyseer Al-Sheikh Corp.. Al-Khobar.
1981
8/11/2019 Corrosion Protection Evaluation of Some Organic Coatings Incorrosion Protection Evaluation
17/61
(vi) A.C Impedance Unit Solarton 1250B Frequency Response Analyzer with blank
front panel and 1287 Electrochemical interface.
(vii) Close circuit corrosion test loop.
5. EXPERIMENTAL METHODOLOGY
The work on the project was started with effect from November 15, 1998. In the following
sections the salient information regarding the experimental work carried out under different
tasks.
5.1 Mechanical Testing
5.1.1 Adhesion Test
Adhesion tests on coated steel samples were carried out under the following conditions:
Sample : Coated with FBE, Irathane-155 and Aqualine-600A
Temperature : Room temperature (25C)
Technique : ASTM D4541 85 (Re-approved 1989)
Pull-Off adhesion test and/or crosscut methods were employed to determine the adhesive
strength of the coatings. Adhesion tester consists of dollies made of aluminum, which were
glued perpendicular onto the coated surface of the samples. After the curing of adhesive (glue)
testing apparatus (Section 5.2) was attached to the loading fixture(Figures 2-3)and aligned to
apply the tension normal to the test surface. The force applied to the loading fixture is then
gradually increased and monitored until either plug of coating material is detached or a
specified value is reached. The relative stress applied to each coating can be calculated as
follows:
where
X : Greatest mean pull-off stress applied during the pull off strength achieved at failure (psi)
F : Highest force applied to the test surface (pounds)
d : Equivalent diameter of the original surface area stressed (inches)
2
d
F4X
=
1982
8/11/2019 Corrosion Protection Evaluation of Some Organic Coatings Incorrosion Protection Evaluation
18/61
In crosscut adhesion test, a crosscut was made with the help of a utility knife on the coated
surface deep to the metal substrate. At the crosscut the blade of the knife was inserted under
the coating and with a levering action force was applied to chip off the coating. The chipped
off area was observed under microscope (magnification. x 40) to see the extent of removal ofthe coating from the substrate.
5.1.2 Flexibility Test
Flexibility or bending test provides information on the ability of coatings applied to pipe to
resist cracking, disbonding, or other mechanical damage as a result of bending. This test has
also been application as a quality control method when variations in coating application or
material formulation would affect bending performance.
Mandrel Bend Machine (Figure 4) was used to test the steel specimens coated with FBE,
Irathane-155 and Aqualine-600A at room temperature. The main objective of the bending test
is to determine the strength of the coating under bending condition. Prior to bending, the
specimens were inspected visually for any visible defect followed by holiday test. The FBE
coated samples were tested by pulse type detector set at 2500 50 Volts while Irathane-155
and Aqualine-600A were tested using a wet sponge set at 67.5 Volts. The thickness of the
specimens was also measured before the test. The specimens were then clamped in the holder
and bent flat-wise at 60oC over a thick shoe, bending was accomplished in approx. 30
seconds. The specimens were again inspected by holiday detector to confirm any cracking in
the coating after bending.
The Mandrel Ben Machine was programmed to carry out the flexibility test by increasing the
mandrel radius step by step until the coating stops failing. The smallest available mandrel shoe
was of 87 mm radius. The percent strain was calculated as given below:
Where:
t = Effective thickness of the specimens (DFT + Metal)
r = Radius of the mandrel shoe.
DFT = Dry Film Thickness
%( )
Straint
r t=
+100
2
1983
8/11/2019 Corrosion Protection Evaluation of Some Organic Coatings Incorrosion Protection Evaluation
19/61
The percent strain is directly proportional to the effective thickness t of the specimen.
5.1.3 Cathodic Disbondment Test
This test provides accelerated adhesion assessment and determines resistance of the coating to
cathodic potential and current flow. Coated steel samples of dimension 200 x 200 mm were
used for the tests. In the middle of the coated specimen a hole of 6 mm dia. (PE) or 3.2 mm
dia. (FBE and PU) was drilled through the coating to expose the substrate. A 200 mm long
plastic pipe of 100 mm diameter was glued on to the specimen with the holiday at the center
of the tubing. A cathodic disbondment test cell was assembled with a DC power supply,
platinum wire as anode, high resistance volt/amp meter and a calomel reference electrode as
shown inFigure 5. The DC power supply was designed and fabricated at the research and
development center by the instrumentation section. The advantage in using this power supply
was that it keeps the applied potential constant irrespective of current flowing through the cell.
All the four test specimens glued with the plastic pipe were kept on a hot plate and 900 ml
solution of 3% NaCl was poured in each plastic pipe(Figure 5).The temperature of the hot
plate was raised to maintain the temperature of the NaCl solution at 40oC.
The negative lead of the power supply was connected to the coated plate and positive lead to
platinum anode. After 7 days, the electrolyte was drained out and the test cell was immediately
dismantled. Coated plate was cooled down to room temperature. The blade of a hard utility
knife was inserted under the coating near the holiday edge and using a levering action, coating
was chipped off. This action was continued till it became impossible to flake off the coating.
Radius of the disbonded area from the holiday edge was measured along seven angles and
average was obtained.
The disbondment tests were carried out under the following conditions:
Samples : FBE (Green), 3-Layer PE (Black), Irathane-155 (Yellow) and Aqualine-
600A (Gray)
Temp. : (a) Room temperature (25C). (b) 40oC
Duration : 7 days at 40o
C and 4 weeks at 25C.
1984
8/11/2019 Corrosion Protection Evaluation of Some Organic Coatings Incorrosion Protection Evaluation
20/61
Test Method : CAN/CSA-2245.20 M92 Canadian.
5.2 Wet Test
5.2.1 Salt Spray Test
Salt spray tests were carried out in a salt spray fog chamber following ASTM B117 90. A
photograph of the equipment is shown in Figure 6. The coupons were exposed for time
periods varying from 25 to 100 days.
During salt spray tests, the development of corrosion on some abraded area was studied. In
one set of samples, scratch lines (scribes) were made through one corner of the samples to the
diagonally opposite corner of the sample, i.e. X shaped. One side of the coupons wasscribed while the other side was left unscribed. The specimens, without the scribe mark, were
weighed before starting the salt spray test.
In the salt spray chamber the specimens were placed meeting the following conditions:
(i) All the specimens were supported parallel to the principal direction of horizontal flow
of fog.
(ii) Specimen holder was made of plastic and, therefore, specimens were not in contact
with each other or worth any metallic material.
(iii) A 5% solution of sodium chloride was atomized by compressed air in the chamber.
(iv) The temperature of the chamber was kept at 38oC (100oF).
Specimens were exposed under above-mentioned conditions for 25, 50, 75 and 100 days,
respectively. After the required exposure period, the samples were examined as per ASTM
D1645-71a (Re-approved 1984). This method provides a means of evaluating and comparing
basic corrosion performance of substrate, pretreatment, or coating system, or combination
thereof, after exposure to corrosive environment. The specimens were carefully removed from
the holder and gently washed in clean running water, to remove salt deposits from their
surfaces, and then immediately dried. Exposed surface at the scribes was cleaned with brush to
remove all the rust. Mean creepage from the scribe and failed area was measured and rated as
per ASTM D1654-71a (Table 5). Similarly, measurements were also carried out for the
blisters appeared on scribed and unscribed sides.
1985
8/11/2019 Corrosion Protection Evaluation of Some Organic Coatings Incorrosion Protection Evaluation
21/61
5.2.2 Close Circuit Loop Test
The close circuit loop was fabricated in the corrosion laboratory. It has a reservoir of 200
liters water capacity for internal circulation, plastic (HDPE) pipes (60 mm diam) witharrangement of fixing coupons internally in preinstalled coupon holders. It has provisions of
adjusting pressure, flow rate and temperature.
Specimens of FBE, Aqualine-600A and Irathane-155 were fixed in coupon holders and
installed in an indigenously designed and fabricated close circuit loop (Figure 7). The
experiments were carried out under the following conditions.
Temperature : 40oC
Medium : Distilled water
pH : 7.3
Duration : 4 Weeks
Flow Rate : 60 GPM
5.2. 3 Autoclave Test
The autoclave test was carried out at Al-Qahtani Pipe Coating Terminal (AQPCT), Al-
Dammam under the supervision of SWCC-RDC staff (Figure 8).The test was carried out on
an AQPCT autoclave at 1500 psi, 40C in distilled water for 48 hours. The specimens were
half immersed in the test solution during the test. The thickness of coating was measured
before and after each test using a electromagnetic thickness gauge Posi-Tector 2000 at 6
different places (3 in aqueous and 3 in vapor phase) on the specimen. After completion of the
test the samples were assessed visually for swelling and blistering. The pull-off adhesion test
was also carried out on each phase i.e. vapor and aqueous.
The test were conducted on samples a, b, c under following conditions:
i. Samples
(a) Scotchkote-206N (Green) 3 No.
(b) Irathane-155 (Yellow) 3 No.
(c) Aqualine-600A (Gray) 3 No.
ii. Test conditions
Sample size: 100 x 25 mm
Pressure: 1500 psi
Temperature: 40o
CAtmosphere: Nitrogen gas
1986
8/11/2019 Corrosion Protection Evaluation of Some Organic Coatings Incorrosion Protection Evaluation
22/61
Test medium: Distilled water
pH: ~7.3
Duration: 48 hours
5.3 Impedance Studies
The AC Impedance tests were carried out on FBE, Polyethylene, Irathane-155 and Aqualine-
600A coated specimens. The main objectives of the AC Impedance Measurements were to
evaluate quantitatively the water uptake by the coatings and non-destructive determination of
cathodic disbondment. On the basis of this information the performance of coating was
evaluated. The measurements were carried out on Solarton AC Impedance System, which is
consisted of 1250B frequency response analyzer with blank front panel and 1287
electrochemical interface unit(Figure 9). The samples and test conditions for AC Impedance
studies were:
Sample : Steel coated with FBE, polyethylene, Irathane-155 and Aqualine-600A
Medium : 3% NaCl
Temperature : Room temperature (25C)
Duration : 6 months.
6. RESULTS AND DISCUSSION
Coated panels of four different type coatings(Figure 1)were obtained from different supplies.
The details about the supplies and samples are given in section 5.1. It is to be noted that,
before carrying out any test, all the samples were checked visually and by holiday detector
including coating thickness measurements. The holiday detection method has been discussed
in detail in section 5.1.2.
6.1 Adhesion Test
Adhesion test was performed on FBE, PUAqualine-600A and PU-Irathane-155 as mentioned
in section 6.1.1. In all the tests the dolly was detached at the coating/dolly interface. This
confirms that the bonding between the metal substrate and coating was more than the coating
and dolly (Figures 10-12). The adhesion test results obtained are shown in Table 3. The
1987
8/11/2019 Corrosion Protection Evaluation of Some Organic Coatings Incorrosion Protection Evaluation
23/61
results were not consistent i.e. a large difference among the data was observed. The maximum
adhesion strength between coating and dolly for FBE, Aqualine-600A and Irathane-155 was
345, 451 and 270 psi, respectively. The lower adhesion strength value of 270 psi for Irathane-
155 shows that the bonding strength of adhesive was lowest and highest with Aqualine-600A.Adhesion test was also carried out on samples used for autoclave test at AQPC facility. Here
again the strength of glue and coating was not enough to pull-off the coatings. Maximum
adhesion strength of glue used to fix the dollies to coatings was around 500 psi.
6.2 F lexibil ity Test
The samples of FBE, PU Aqualine-600A and Irathane-155 were tested as explained in
section 6.1.2. After bending the samples were examined visually followed by holiday test at
the bend site. No defect was found either visually or by holiday tester on any of the samples
tested(Figures 13-15).This confirms that FBE, 600A and 155 can sustain up to 2.41, 3.06 and
3.33 percent strain respectively (Table 2).
6.3 Cathodic Di sbondment Tests (CDT)
CDT test was carried out on all the four types of coatings i.e. FBE, PE, PU Aqualine-600A
and Irathane-155 at 232 C and 402 C. The details about the CDT test has been explained
earlier in section 6.1.3. An increase in pH value from 4.5 at the start of the test to 8.5-9.0 at
the end of all tests was recorded. Radial Disbondment (RD) results obtained from the CDT at
40C are given in Table 3. The fusion bonded epoxy coated samples showed the lowest
average RD value of 2.0 mm. While the PU coated 600A and 155 have the high average RD
values of 17.0 and 14.9 mm, respectively (Figures 16-19).The 3 layer PE coating has slightly
higher average RD value than FBE (3.16). On the basis of average RD results at 40C, the
four types of coatings can be arranged in the following ascending order:
FBE > 3-Layer PE > Irathane 155 > Aqualine-600A
At room temperature (25C), FBE, 3-Layer PE and Aqualine-600A showed almost negligible
average RD(Table 4).However, the Irathane-155 has very high RD value of 30 mm (Figures
1988
8/11/2019 Corrosion Protection Evaluation of Some Organic Coatings Incorrosion Protection Evaluation
24/61
20-22). The performance of these coatings at 25C can be arranged in the following
descending order:
FBE 3-Layer PE Aqualine-600A > Irathane 155
Under both the test conditions no deposits on or underneath the coated surface were found.
However, the coated area exposed during the CDT test for Aqualine-600A and Irathane-155
were swelled and sticky. This shows that due to increase in pH these coating react with salt
and/ or absorb water from the test solution. A change in color on the area exposed for CDT of
Aqualine-600A and Irathane-155 samples can be seen in Figures 18-19 and 21-22,
respectively.
6.4 Salt Spray Tests
Specimens with and without scribe exposed to the salt fog were evaluated with respect to
mean creepage (from scribe) and blistering.Figures 23-30show photographs of the coating
after 25, 50, 75 and 100 days exposures to salt spray. Table 6 summarizes the salt spray
results for FBE, Aqualine-600A, Irathane-155 and 3-Layer PE coatings.
FBE coating (green) shows little creepage (0.09 mm) after 25 days of exposure but it is
increased considerably (2.06 mm) after 100 days exposure although no blistering in the
coating was found. Irathane-155 shows high creepage of 0.48, 1.51, 1.92 and 2.12 mm after
25, 50, 75 and 100 days of exposure, respectively but no blistering was observed even after
100 days of exposure. Surprisingly, Aqualine-600A has relatively low creepage (0.13 after 25
days and 1.53 after 100 days) but invariably shows blistering on scribed and unscribed sides
after 50, 75 and 100 days of exposure(Tables 7 and 8).The failure rating at the scribe and for
FBE and Irathane-155 was 6 while for 3-Layer PE and Aqualine-600A is 7 (Table 6).This
shows that, the Aqualine-600A and 3-Layer PE have better performance than FBE and
Irathane-155 at the scribe after 100 days of exposure in salt spray test. The mean creepage
value for Aqualine-600A and 3-Layer PE coatings is almost similar. Figure 25 shows
Aqualine-600A samples exposed for 50 days in the salt spray chamber with scribe (Left) and
without scribe (Right). The scribed samples show a number of blisters where as unscribed
samples are devoid of any blister. It is interesting to note that, a decrease in number of pits
was found from 50 to 100 days of exposure in salt spray chamber (Tables 7 and 8). The
1989
8/11/2019 Corrosion Protection Evaluation of Some Organic Coatings Incorrosion Protection Evaluation
25/61
maximum number of blisters was found on the scribed side (Figures 27-30). 3-layer
polyethylene shows 0.08 and 1.66 mm creepage after 25 and 100 days of exposure
respectively in salt spray chamber but no blistering was observed.
6.5 Close Cir cui t Loop Test
Coupons of FBE, Aqualine-600A and Irathane-155 were exposed to distilled water in the
close circuit loop at 40C for 1 month under flowing condition (Flow rate 60 GPM). All the
samples were intact and no remarkable change in the physical condition of the coating was
observed.
6.6 Au toclave Test
The autoclave tests were carried out in order to know the behavior of coatings under high
pressure and temperature. The test duration was 48 hours and the temperature was fixed to
40C. The pressure of the test vessel was kept at 1500 psi. After the test samples were
examined for color, blistering, loss in adhesion strength and thickness. These tests were
carried out at AQPCT, Dammam. Figures 31-33 show the samples after autoclave test.
Tables 9 and 10 present the thickness of Scotchkote-206N (FBE) coating in vapor and
aqueous phases respectively. A slight increase in thickness can be seen in both phases.
Similarly Aqualine-600A coating shows an average increase of 1-2 mil in coating thickness in
aqueous phase. While a slight decrease in thickness in vapor phase was observed (Tables 11
and 12). Contrary to Aqualine-600A, the Irathane-155 coating which showed a reverse
behavior. An increase in the average coating thickness in vapor phase and a decrease in
aqueous phase (Tables 13and 14). This shows that coating has absorbed moisture from the
vapors and resulted in increase in coating thickness. While a decrease in coating thickness and
appearance of texture on the coating surface exposed to aqueous phase confirms the
dissolution of coating in the test solution. Aqualine-600A and FBE coatings do not show any
loss of color in autoclave test. While carrying out Pull-Off adhesion test on the panels of FBE
and Aqualine-600A after the autoclave test, again failure (at 500 psi) of dolly and coating was
observed (Tables 15 and 16).A slight discoloration and texture appearance in both the phases
was found on the Irathane-155 panels(Figure 34).Appearance of textured surface can be seen
in Figure 35. The dolly could not be fixed properly for adhesion test on either vapor or
aqueous phases exposed part of the panel.
1990
8/11/2019 Corrosion Protection Evaluation of Some Organic Coatings Incorrosion Protection Evaluation
26/61
On coating stability consideration, the results of autoclave tests show opposite behavior of two
urethane coatings viz. Irathane 155 and Aqualine 600 A. Irethane shows an increase in the
average coating thickness in the vapor phase and a decrease in aqueous phase (both at 40oC
and 1500 psi) whereas a reverse behavior has been observed in Aqualine 600A and FBE
coatings. The peculiar behavior of Irethane could be attributed to an exothermic disbondment
reaction, which is not favorable in the vapor phase because of the enormous amount of heat
energy required to generate and sustain water vapors in the vapor phase at a high pressure of
1500 psi and a relatively low temperature of 40oC. The heat content of vapor phase might be
further enhanced by inevitable condensation of some of the vapors. In contrast, the heat
contents of aqueous phase are expected to be lower and more favorable in energy content to an
highly exothermic disbonding reaction. This peculiar behavior of Irathane 155 is in
conformity with the results of the cathodic disbondment studies of the two-urathane coatings.
The results indicate that Irathane deteriorated more severely at room temperature (25OC) than
at higher temperature (40OC). This curious behavior points out to an exothermic reaction,
which is suppressed at higher temperature, yet favored at low temperature. In Aqualine 600 A
and FBE coatings, the disbonding reaction in the coating seems to be endothermic reaction
thereby showing the stability of the coatings in aqueous solution.
On practical considerations pertinent to the application of organic materials as internal
coatings in water transmission lines, it must be emphasized that vapor forming conditions do
not exist in flowing water under high pressure (60 bar). The results of vapor phase are,
therefore, only relevant to shut down conditions or to external coatings.
6.7 A.C Impedance Test
Bode plots for FBE, Aqualine-600A, Irathane-155 and 3-Layer PE samples exposed to 3%
NaCl solution at room temperature (25C) after 6 months of exposure are shown inFigures
36-39. In fact after 6 months of exposure, only slight change in impedance value was found.
This could be due to surface adsorption of moisture. In Nyquist plots a straight line was
observed instead of a semicircle. This confirms that no corrosion process was started even
after 6 months of exposure.
1991
8/11/2019 Corrosion Protection Evaluation of Some Organic Coatings Incorrosion Protection Evaluation
27/61
1. The results of adhesion tests carried out on FBE, PU 600 A and 155 show that the
bonding between the metal substrate and the coating was more than the coating and
dolly. The maximum adhesive strength was for Aqualine-600 A and minimum for
Irathane-155.
2. The flexibility test (bending test) carried out on FBE and PU 600 A and 155 shows no
defect or presence of holidays at the bending site. Irathane-155 coating can sustain up
to 3.33% strain.
3. On the basis of radial disbondment measurements from cathodic disbondment tests,
the decreasing performance of the coatings can be represented as:
FBE > 3-Layer PE > Aqualine-600 > Irathane-155
4. During cathodic disbondment tests, Aqualine 600 and Irathane-155 were found
swelled and sticky.
5. The results from salt fog tests show following behavior for different coatings.
(a) In scribed samples, the creepage increases with increasing exposure time:
25 days test : from 0.09 mm (FBE) to 0.48 mm (Irathane 155).100 days tests : from 1.53 mm (Aqualine 600 A) to 2.12 mm (Irathane 155).
(b) Whilst FBE, Irathane-155 and 3-Layer PE show no blistering after 100 days,
Aqualine-600 shows blistering on scribed and unscribed surfaces.
6. The pull off adhesion tests carried out on coated samples after autoclave tests show
that the adhesive strength of FBE, 3-Layer PE and PU 600-A and 155 coatings is
greater than 500 psi.
7. The results of the autoclave tests indicate that FBE and Aqualine-600A coatings show
very small variations in thickness in vapor phase and a definite increase in aqueous
phase. However, Irathane-155 shows a clear increase in thickness in vapor phase and a
decrease in thickness in aqueous phase indicating the dissolution of coating in test
solution.
8. Aqualine-600A and FBE coatings do not show any loss of color in autoclave tests.
7. CONCLUSIONS
1992
8/11/2019 Corrosion Protection Evaluation of Some Organic Coatings Incorrosion Protection Evaluation
28/61
9. AC impedance tests carried out on all three coatings in 3% NaCl at room temperature
(25oC) show only slight change in impedance due to surface adsorption of moisture.
However, no corrosion process appears to be initiated after 6 months of exposure.
10. Close circuit loop tests results of 1-month exposure in distilled water indicate no
marked change in the color and texture of the coating. There was no perceptible
change in weight.
8. RECOMMENDATIONS
1. Out of the 4 organic coatings, viz. Scotchkote-206 N (FBE); Aqualine-600A (PU),
Irathane-155 (PU) and 3-Layer PE tested, only FBE coating appears to have
formidable properties. FBE has good mechanical properties, low water permeation, no
chemical degradation and good corrosion resistance. Moreover, FBE shows small
increase in radial disbondment under applied potential (1.5 volts Vs SCE) thus
indicating its stability towards cathodic disbondment. This combination of properties
provide FBE as a suitable choice for internal and external lining material for steel
pipes in water transmission systems.
2. Considering the application of FBE as internal coating in water transmission system,
the effect of chlorinated water on FBE is not well documented. It is therefore,
recommended to carry out studies related to the influence of chlorinated water on FBE
coatings.
3. Polyurethane 600A and 155 have reasonably good mechanical properties though, but
show degradation during cathodic disbondment and poor performance in autoclave
tests and therefore, do not appear to be suitable for internal lining. However, new
generation of solvent free polyurethane which showed promising properties as internal
coating can be considered for detailed studies in future research projects.
4. 3-Layer polyethylene showed good resistance to water and chloride permeation. Such
a material can be considered for external coating on steel pipes exposed to marine
atmosphere and/or in contact with high chloride low resistivity soil (Subkha).
1993
8/11/2019 Corrosion Protection Evaluation of Some Organic Coatings Incorrosion Protection Evaluation
29/61
Table 1. Pull-off adhesion test results measured by DYNA adhesion tester with 50
mm dolly
Adhesive Strength (psi)S. No. Coating Type
#1 #2 #3 Average*
1. Scotchkote-206N
(FBE) Green
150 210 345 277
2. Aqualine-600A Gray 375 120 451 413
3. Irathane-155 Yellow 225 75 270 247
* Average of two comparable values
Table 2. Calculated Average Percent Strain of the specimens under test
S.No. Coating Type Thickness t (mm) % Strain
1. Scotchkote-206N (FBE)
Green
4.3 2.41
2. Aqualine 600A PU
Gray
5.5 3.06
3. Irathane-155 PU
Yellow
6.0 3.33
Thickness t: DFT + MetalPU: Polyurethane
DFT: Dry Film Thickness
1994
8/11/2019 Corrosion Protection Evaluation of Some Organic Coatings Incorrosion Protection Evaluation
30/61
Table 3. Measured radial disbandment after the Cathodic Disbondment test carried out
at 40C in 3% NaCl solution for seven days. The applied voltage was 1.5against Saturated Calomel Electrode (SCE).
S.No. Coating Type Sample # Average
DFT(mils)
Radial
Disbondment(mm)
Average
Disbondment(mm)
1. Scotchkote-206N Green A
B
C
23.0
24.4
27.7
1.7
2.2
2.0
2.0
2. Aqualine-600A Gray A
B
C
54.4
35.1
36.9
13.5
16.5
21.0
17.0
3. Irathane-155 Yellow A
B
C
33.7
49.9
28.4
15.0
12.7
16.9
14.9
4. 3-Layer PE Black A
B
C
4.5
4.5
4.5
2.5
4.0
3.0
3.2
DFT : Dry Film Thickness
Table 4. Measured radial disbondment after the Cathodic Disbondment test carried out
at 25C in 3% NaCl solution for 4 weeks. The applied voltage was 1.5 againstSaturated Calomel Electrode (SCE).
S.No. Coating Type Radial Disbondment (mm)
1. Scotchkote-206N Green Negligible
2. Aqualine-600A Gray Negligible
3. Irathane-155 Yellow 30.00
4. Polyethylene 3 Layer- Black Negligible
1995
8/11/2019 Corrosion Protection Evaluation of Some Organic Coatings Incorrosion Protection Evaluation
31/61
Table 5. Rating of failure at scribed and unscribed area [ASTM D1654 71a]
Mean Creepage from scribe (mm) UnscribedS.No.
Millimeters Rating Number % Area Failed Rating Number
1. Over 0 10 No Failure 10
2. Over 0.0 0.5 9 0 1 9
3. Over 0.5 1.0 8 2 3 8
4. Over 1.0 2.0 7 4 6 7
5. Over 2.0 3.0 6 7 10 6
6. Over 3.0 5.0 5 11 20 5
7. Over 5.0 7.0 4 21 30 4
8. Over 7.0 10.0 3 31 40 3
9. Over 10.0 13.0 2 41 55 2
10. Over 13.0 16.0 1 56 - 75 1
11. Over 16.0 0 Above 75 0
Table 6. Salt Spray Test Results: Mean Creepage from Scribe (mm)
Coating Exposure (days) Rating Visual Examination
Remarks
25 50 75 100
Scotchkote-206N
(Green)
0.09 1.27 1.57 2.06 6 No blistering
Aqualine 600 A(Gray)
0.13 0.21 1.13 1.53 7 Blistering observedafter 50 days.
Irathane 155
(Yellow)
0.48 1.51 1.92 2.12 6 No blistering
Polyethylene
(Black)
0.08 0.23 1.27 1.66 7 No blistering
1996
8/11/2019 Corrosion Protection Evaluation of Some Organic Coatings Incorrosion Protection Evaluation
32/61
8/11/2019 Corrosion Protection Evaluation of Some Organic Coatings Incorrosion Protection Evaluation
33/61
Table 9. Thickness (mils) of Scotchkote-206N (FBE) - Green color coatings measured at
3 different locations on 3 specimens exposed to vapor phase in autoclave test
carried out at 1500 psi at 40C for 48 hours in distilled water.
S.No. Sample # Location Before Test After Test Remarks
1. 1
Average
1
2
3
21.1
20.9
20.5
20.83
20.9
20.1
20.4
20.46
- 0.36
2. 2
Average
1
2
3
20.3
20.2
20.3
20.26
20.9
21.6
20.3
20.93
+ 0.67
3. 3
Average
1
2
3
20.8
21.4
21.6
21.26
21.4
21.9
21.7
21.66
+ 0.39
Table 10. Thickness (mils) of Scotchkote-206N (FBE) - Green color coatings measured at
3 different locations on 3 specimens exposed to aqueous phase in autoclave test
carried out at 1500 psi at 40C for 48 hours in distilled water.
S.No. Sample # Location Before Test After Test Remarks
1. 1
Average
1
2
3
20.9
20.3
20.5
20.56
21.3
22.6
21.9
21.93
+ 1.36
2. 2
Average
1
2
3
21.0
21.7
21.521.40
21.0
20.5
21.220.9
+ 0.50
3. 3
Average
1
2
3
21.5
21.8
20.9
21.40
21.7
21.8
21.5
21.66
+ 0.26
1998
8/11/2019 Corrosion Protection Evaluation of Some Organic Coatings Incorrosion Protection Evaluation
34/61
Table 11. Thickness (mils) of Polyurethane Aqualine-600A - Gray color coatings measured
at 3 different locations on 3 specimens in vapor phase in autoclave test carried
out at 1500 psi at 40C for 48 hours in distilled water.
S.No. Sample # Location Before Test After Test Remarks
1. 1
Average
1
2
3
28.6
24.9
26.2
26.56
29.4
28.7
29.6
29.23
+ 2.67
2. 2
Average
1
2
3
23.0
22.2
18.5
21.23
21.9
23.2
17.0
20.70
- 0.53
3. 3
Average
1
2
3
18.8
21.2
25.2
21.73
18.5
20.4
25.8
21.56
- 0.16
Table 12. Thickness (mils) of Polyurethane Aqualine-600A - Gray color coatings measured
at 3 different locations on 3 specimens exposed to aqueous phase in autoclave
test carried out at 1500 psi at 40C for 48 hours in distilled water.
S.No. Sample # Location Before Test After Test Remarks
1. 1
Average
1
2
3
24.48
33.5
30.6
29.63
33.3
35.2
30.8
33.10
+ 3.46
2 2
Average
1
2
3
13.6
13.2
18.3
15.03
13.7
13.9
20.5
16.03
+ 1.00
3. 3
Average
1
2
3
22.9
27.8
26.1
25.60
24.6
28.8
27.2
26.86
+ 1.26
1999
8/11/2019 Corrosion Protection Evaluation of Some Organic Coatings Incorrosion Protection Evaluation
35/61
Table 13. Thickness (mils) of Polyurethane Irathane155 - Yellow color coatings measured
at 3 different locations on 3 specimens in vapor phase in autoclave test carried
out at 1500 psi at 40C for 48 hours in distilled water.
S.No. Sample # Location Before Test After Test Remarks
1. 1
Average
1
2
3
51.9
46.5
44.6
47.66
60.2
59.3
54.6
58.03
+ 10.36
2. 2
Average
1
2
3
48.3
45.0
42.3
45.20
62.5
57.6
55.3
58.46
+ 13.26
3. 3
Average
1
2
3
39.2
38.8
41.1
39.70
48.3
48.7
48.3
48.43
+ 8.73
Table 14. Thickness (mils) of Polyurethane Irathane155 - Yellow color coatings measured
at 3 different locations on 3 specimens exposed to Aqueous Phase in autoclave
test carried out at 1500 psi at 40C for 48 hours in distilled water.
S.No. Sample # Location Before Test After Test Remarks
1. 1
Average
1
2
3
43.2
41.5
41.6
42.10
41.2
41.0
38.9
40.36
- 1.73
2. 2
Average
1
2
3
41.3
42.8
41.7
41.93
40.8
40.3
39.7
40.26
- 1.66
3. 3
Average
1
2
3
45.1
48.7
46.3
46.70
38.3
39.0
41.8
39.70
- 7.00
2000
8/11/2019 Corrosion Protection Evaluation of Some Organic Coatings Incorrosion Protection Evaluation
36/61
Table 15. Physical appearance and adhesion test results of the Scotchkote-206N (FBE)
Green color coatings after autoclave test exposure. The maximum adhesion
strength of glue used to fix the dollies to the coatings was 500 psi
Adhesion TestS.No. Sample # Physical Appearance
Gas Phase Aqueous Phase
1. 1 No Blistering or Swelling Glue Failure Glue Failure
2. 2 No Blistering or Swelling Glue Failure Glue Failure
3. 3 No Blistering or Swelling Glue Failure Glue Failure
Table 16. Physical appearance and adhesion test results of the Polyurethane Aqualine-
600A - Gray color coatings after autoclave test exposure. The maximum
adhesion strength of glue used to fix the dollies to the coatings was 500 psi
Adhesion TestS.No. Sample # Physical Appearance
Gas Phase Aqueous Phase
1. 1 No Blistering or Swelling.A light texture in the
aqueous phase.
Glue Failure Glue Failure
2. 2 No Blistering or Swelling.
A light texture in the
aqueous phase.
Glue Failure Glue Failure
3. 3 No Blistering or Swelling.
A light texture in the
aqueous phase.
Glue Failure Glue Failure
2001
8/11/2019 Corrosion Protection Evaluation of Some Organic Coatings Incorrosion Protection Evaluation
37/61
Table 17. Physical appearance and adhesion test results of the Polyurethane Irathane155 - Yellow coatings after autoclave test exposure.
Adhesion TestSample # Physical Appearance
Gas Phase Aqueous Phase
1 Discoloration and swelling on
the gas phase. Both phases
have heavy textured
appearance
Dolly could not be
fixed due to surface
roughness. It could be
easily removed byapplying little force by
hand.
Dolly could not be
fixed due to surface
roughness. It could be
easily removed byapplying little force
by hand.
2 Discoloration and swelling on
the gas phase. Both phases
have heavy textured
appearance
Dolly could not be
fixed due to surface
roughness. It could be
easily removed by
applying little force by
hand.
Dolly could not be
fixed due to surface
roughness. It could be
easily removed by
applying little force
by hand.
3 Discoloration and swelling onthe gas phase. Both phases
have heavy textured
appearance
Dolly could not befixed due to surface
roughness. It could be
easily removed by
applying little force by
hand.
Dolly could not befixed due to surface
roughness. It could be
easily removed by
applying little force
by hand.
2002
8/11/2019 Corrosion Protection Evaluation of Some Organic Coatings Incorrosion Protection Evaluation
38/61
Figure 1. Photograph showing the coated panels received, [A] for Cathodic
Disbondment Test [B] for Autoclave and Bend (Flexibility) Test and [C]
for Salt Fog Test. Yellow: Irathane-155 (PU), Gray: Aqualine-600A (PU),
Black: 3-Layer Polyethylene (PE) and Green: Fusion Bonded Epoxy
(FBE).
Figure 2. Photograph showing the Adhesion Testing Equipment
2003
8/11/2019 Corrosion Protection Evaluation of Some Organic Coatings Incorrosion Protection Evaluation
39/61
Figure 3. Schematic of Pull-Off Adhesion Tester
Figure 4. Photograph showing Bend Test equipment used for bend test.
2004
8/11/2019 Corrosion Protection Evaluation of Some Organic Coatings Incorrosion Protection Evaluation
40/61
Figure 5. Photograph showing the Cathodic Disbondment Testing Equipment
Figure 6. Photograph showing the Salt Spray Testing Equipment
2005
8/11/2019 Corrosion Protection Evaluation of Some Organic Coatings Incorrosion Protection Evaluation
41/61
Figure 7. Photograph showing the close circuit test loop
Figure 8. Photograph showing the Autoclave used during the study
2006
8/11/2019 Corrosion Protection Evaluation of Some Organic Coatings Incorrosion Protection Evaluation
42/61
Figure 9. Photograph showing AC Impedance system used during the
study
Figure 10. Photograph showing Scotchkote-206N(FBE)
coupons used for Pull-OFF Adhesion Test
2007
8/11/2019 Corrosion Protection Evaluation of Some Organic Coatings Incorrosion Protection Evaluation
43/61
Figure 11. Photograph showing Aqualine-600A (PU) coupons used
for Pull Off Adhesion Test
Figure 12. Photographs showing Irathane-155 (PU) coupons used
for Pull Off Adhesion Test
2008
8/11/2019 Corrosion Protection Evaluation of Some Organic Coatings Incorrosion Protection Evaluation
44/61
Figure 13. Photograph showing Scotchkote-206N (FBE) panels after
flexibility test
Figure 14. Photograph showing Aqualine-600A panels after
flexibility test
Figure 15. Photograph showing Scotchkote-206N (FBE) panels after
flexibility test
2009
8/11/2019 Corrosion Protection Evaluation of Some Organic Coatings Incorrosion Protection Evaluation
45/61
Figure 16. Photograph showing the Scotchkote-206N(FBE) panel tested
Cathodic Disbondment test in 3% NaCl solution at 40oC for
7 days
Figure 17. Photograph showing the 3-Layer Polyethylene (PE) panel tested
Cathodic Disbondment test in 3% NaCl solution at 40oC for
7 days
2010
8/11/2019 Corrosion Protection Evaluation of Some Organic Coatings Incorrosion Protection Evaluation
46/61
Figure 18. Photograph showing the Aqualine 600 A panel tested
Cathodic Disbondment test in 3% NaCl solution at 40oC
for 7 days
Figure 19. Photograph showing the Irathane-155 panel tested Cathodic
Disbondment test in 3% NaCl solution at 40oC for 7 days
2011
8/11/2019 Corrosion Protection Evaluation of Some Organic Coatings Incorrosion Protection Evaluation
47/61
Figure 20. Photograph showing the Scotchkote-206N (FBE) panel tested
Cathodic Disbondment test in 3% NaCl solution at room
temperature for 4 weeks
Figure 21. Photograph showing the Aqualine-600 A panel tested Cathodic
Disbondment test in 3% NaCl solution at room temperature
for 4 weeks
2012
8/11/2019 Corrosion Protection Evaluation of Some Organic Coatings Incorrosion Protection Evaluation
48/61
Figure 22. Photograph showing the Irathane-155 panel tested Cathodic
Disbondment test in 3% NaCl solution at room temperature
for 4 weeks
Figure 23. Photograph showing coupons taken out after 25 days of
exposure in Salt Fog Chamber
2013
8/11/2019 Corrosion Protection Evaluation of Some Organic Coatings Incorrosion Protection Evaluation
49/61
Figure 24. Photograph showing coupons taken out after 50 days of exposure
in Salt Fog Chamber
Figure 25. Photograph showing Aqualine-600A coupons exposed in salt spray
chamber for 50 days. Large numbers of blisters can be seen (left)
on the scribed samples while absence of blisters on unscribed samples
(right)
2014
8/11/2019 Corrosion Protection Evaluation of Some Organic Coatings Incorrosion Protection Evaluation
50/61
Figure 26. Photograph showing coupons taken out after 75 days of exposure
in Salt Fog Chamber
Figure 27. Photograph showing Aqualine-600A coupons taken out after 75 days
exposure in Salt Fog Chamber. Some blisters marked with black
dashes can be seen.
2015
8/11/2019 Corrosion Protection Evaluation of Some Organic Coatings Incorrosion Protection Evaluation
51/61
Figure 28. Reverse side of the same as in Fig. 27. The blisters are marked
with bluish dash marks
Figure 29. Photograph showing coupons taken out after 100 days of
of exposure in Salt Fog Chamber
2016
8/11/2019 Corrosion Protection Evaluation of Some Organic Coatings Incorrosion Protection Evaluation
52/61
Figure 30. Photograph Showing Aqualine-600A coupons taken out after 100 days
of exposure in Salt Fog Chamber. Some blisters marked with red
arrows can be seen
Figure 31. Photograph showing Scotchkote-206N(FBE) panels exposed in
distilled water at 40oC for 48 hours in autoclave test
2017
8/11/2019 Corrosion Protection Evaluation of Some Organic Coatings Incorrosion Protection Evaluation
53/61
Figure 32. Photograph showing Aqualine-600A panels exposed in distilled
water at 40oC for 48 hours in autoclave test
Figure 33. Photograph showing Irathane-155 panels exposed in distilled
water at 40oC for 48 hours in autoclave test
2018
8/11/2019 Corrosion Protection Evaluation of Some Organic Coatings Incorrosion Protection Evaluation
54/61
Vapor Side
Aqueous Side
Figure 34. Close-up views of the each coated panel after autoclave
test exposure showing both vapor and aqueous phases
Vapor Side Aqueous Side
Figure 35. Close-up views of Irathane-155 panel after autoclave test
exposure showing both vapor and aqueous phases. Loss in
surface texture in the aqueous phase can be seen
2019
8/11/2019 Corrosion Protection Evaluation of Some Organic Coatings Incorrosion Protection Evaluation
55/61
2020
8/11/2019 Corrosion Protection Evaluation of Some Organic Coatings Incorrosion Protection Evaluation
56/61
2021
8/11/2019 Corrosion Protection Evaluation of Some Organic Coatings Incorrosion Protection Evaluation
57/61
2022
8/11/2019 Corrosion Protection Evaluation of Some Organic Coatings Incorrosion Protection Evaluation
58/61
Figure 39A. Nyquist plots for 3-Layer Polyethylene (Black) exposed in
3% NaCl solution for 6 months
Figure 39B. Bode plots for 3-Layer Polyethylene (black) exposed in 3%
NaCl solution for 6 months
2023
8/11/2019 Corrosion Protection Evaluation of Some Organic Coatings Incorrosion Protection Evaluation
59/61
REFERENCES
1. Malik, A.U., (1991), Case History on the Failure of Pipelines in Desalination Plants,
presented in IDA World Conference on Desalination and Water Reuse, August 25-29,
Washington, D.C.
2. Malik, A.U., Kutty, M. and Andijani, I.N., (1992), Reinforced Cement Concrete
Pipelines for Desalination Water Transmission A Critical Review and Some Failure
Analysis, First Gulf Water Conference, Dubai.
3. Novokshchenov, V., (1995), Corrosion of Reinforced Concrete in Persian Gulf
Region Materials Performance, 34,(1), 51.
4. Saricimen, H., Ashiru, O.A., Jarrah, N.R., Quddus, A. and Shameem, M., (1998),
Effect of Inhibitors and Coatings on Rebar Corrosion, Materials Performance, 54,(5),
32.
5. Malik, A.U., Kutty, M., Andijani, I. and Fauzan, S., (1994), Materials Performance
and Failure Evaluation in SWCC MSF Plants, Desalination,97, 171.
6. Mills, G., The Development Application and Evaluation of FBE Internal Coating,
NACE Corrosion, 88 St. Louis, Missouri, USA.
7. Roche, M. and Samaran, J.P., (1987), Pipe Line Coating Performance Field
Experience of a Operating Petroleum Co., Materials Performance, 26(11), 28.
8. Blome, R. and Freberg, G., (1991), Multilayer Coating Systems for Buried Pipelines,Materials Performance, 30, (3), 20-24.
9. Vincent, L.D., (1999), Failure Modes of Protective Coating Who is at Fault
Materials Performance, 38, (4), 38.
10. Kellner, J.D., Doheny, A.J. and Patil, B.B., (1998), A-3 Layer Polyethylene Coating
for Plant Applications, Materials Performance, 54,(6), 28-32.
11. Alexander, M., (1998), 3 Layer Epoxy/Polyethylene. Extruded Coatings for High
Temperature Application, Proc. Int. Pipeline Conference Part-2(2), ASME, FairfieldNJ, USA, 645-652.
12. Information from Al-Qahtani Coating Terminal to H.E. Deputy Governor, (1991),
SWCC letter dated December 8.
13. Application of Scolchkote 206N to Internal Lining of Drinking Water Pipe Line
Information Bulletin from Sclockote 3M.
14. Letter from James A. Srider of East Bay Municipal Utility District through R.F.
Strobel, (1994), 3M Export St. Paul Mn to Al-Qahtani Pipe Coating Terminal, dated
Jan. 14.15. Alblas, B.P. and London, A.M. Van, (1997), Protective Coating Europe, Feb., 16-25.
2024
8/11/2019 Corrosion Protection Evaluation of Some Organic Coatings Incorrosion Protection Evaluation
60/61
16. Appleman, B.R., (1997), JPCL, October, 68.
17. Helvig , V.E., (1980), Metal Finishing, July, 41.
18. Weldon, D.G., Bochan, A. , Schleiden, M., (1987), JPCL, June, 46.
19. Flores, S. and Starr, T.L., (1994), JPCL, March, 76.
20. Neal, D. and Whitehurst, T., (1995), Chloride Contamination of Line Pipe, Materials
Performance, 34,(2), 47.
21. Paul Jeffs, (1996), Inspecting and Repairing Concrete Before Lining PCE, January 16.
22. Water Byelaws Scheme Tests of Effect on Water Quality, (1998), Aqualine 66, ITW
Irethane International Report July.
23. Ray Sams, (1999), A Universal Approach to Steel and Concrete Protection withSolvent Free Polyurethanes, PCE., April, 30-35.
24. Richard and Peter, (1999), Fully Elastomeric Linings for Water Retaining Concrete
Structure, Drinking Water, PCE, March, pp. 24-30.
25. Walter, G.W., (1986), Corrosion Science, 26, 39.
26. Walter, G.W,. (1986), Corrosion Science, 26, 681.
27. Mansfiled, F., (1988), Corrosion, 44, 856.
28. Amiruddin, A. and Thierry, D., (1995), Application of Electrochemical Impedance
Spectroscopy (EIS) to Study the Degradation of Polymer-coated Metals, Progress in
Organic Coatings, 26,(1), 1-28.
29. Bonora, P.O., Deflorian, F. and Fedrizzi, L., (1995), MaterialsScience Forum,192-
194 N., 267-276.
30. Delucchi, M., Miglio, E. and Cerisola, G., (1999), Laboratory Testing of Surface
Tolerant Coatings for Protective Maintenance of Steel Structures, PCE, 40-44.
31. Van Westing, E.P.M., Ferrari, G.M., (1994), J.H.W. DeWit Electrochimica Acta, 39,
(7), 899-910.
32. Kellner, J.D., (1986), Electrochem. Techniques for Corrosion Engg, Ed. R. Baboin,
NACE, Houston, 161-165.
33. Mansfield, F.W., Kendig, M.W. and Tsai, S., (1987), Corrosion, 38, 478.
34. Walter, G.W., (1991), Corrosion Science, 32, 681.
35. John, I, Intyre, M. C. and H. Pham, (1996), Electrochemical Impedance Spectroscopy :
A tool for Organic Coatings Optimization, Progress in Organic Coatings27,(1-4), 201-207.
2025
8/11/2019 Corrosion Protection Evaluation of Some Organic Coatings Incorrosion Protection Evaluation
61/61
36. Titz. J., (1990), Corrosion, 46, 331.
37. Katayama, H., Yagi, K., Nishikata, A and Tsuru, T., (1996), Electrochimica Acta, 14,
(7-8), 1093-1097.
38. Taylor, S.R. Taylor and Wittman, M.W., (1996), Detection and Mapping of Defects in
Organic Coatings Using Local Electrochemical Impedance Methods, Proc. Materials
Research Society Symposium, Pittsburg, U.S.A.,411, 31.
39. Funke, W., (1981), Prog. Organic Coatings,9, 29.
40. Brunt, N.A., (1964), J. Oil colour Chem. Assoc., 47, 31.
41. Vander Meer Lerk, L.A. and Heertjes, P.M., (1979), J. Oil Color Chem. Assoc., 62,
256.
42. Grouke, M.J., (1977), J. Coating Technol, 49, (632) 69.
43. Kochler, E.L., (1974), Localized Corrosion, R. W. Stachle Editor, NACE, Houston,
117.
44. Bautista, A., (1996), Filiform Corrosion in Polymer Coated Metals, Progress in
Organic Coatings, 28,(11), 49-58.
45. Leidheiser, H. Jr. and Kendig, M.W., (1976), Corrosion, 32, 69.
46. Dickie, R.A and Smith, A.G., (1980), Chem. Tech., 1, 31.
47. Ritter, J.J., and Kruger, J., (1981), Corrosion Control by Organic Coatings, H.
Leidheiser, Jr, Editor, NACE, Houston, 28.
48. Hammond, J.S., Holubka, J.W. and Dickie, R.A., (1979), J. Coating Technol, 51,
(655), 45.
49. Leidheiser, H. Jr, Wang, W. and Iyetoft, L., (1982), Prog. Organic Coating, 117.
50. Leidheiser, H., (1982), Corrosion of Painted Metals, A Review Corrosion, 38, 374-383.