Setting Cooper Form3A Recloser Controllers
in the
Computer-Aided Protection Engineering System
(CAPE)
Prepared for
CAPE Users' Group
June 20-21, 2000
Electrocon International, Inc. Georgia Power Company
Ann Arbor, Michigan Atlanta, Georgia
This document is the sole property of Electrocon International, Inc. and is provided to theCAPE Users Group for its own use only. It may not be supplied to any third party, orcopied or reproduced in any form, without the express written permission of ElectroconInternational, Inc. All copies and reproductions shall be the property of ElectroconInternational, Inc. and must bear this ownership statement in its entirety.
Setting Cooper Form 3A Recloser 2000 Users’ Group Meeting
1
Application Notes on Setting Cooper Form 3A Recloser Controllers
I. Recloser Models
This is a summary of the data a CAPE user must provide for the Cooper Power SystemsForm 3A recloser controller.
Typical STYLE used in CAPE is as follows:
Style Properties
Form 3A#KMEB General purpose controller style for model Form 3A, suitable forall Cooper or McGraw-Edison reclosers designed to be used withan electronic controller.
For details of the recloser, refer to the description in the Cooper Publication 280-75.
II. Recloser Elements
The recloser contains phase and ground overcurrent elements, with separate settingspossible for quick and delayed trip.
Element Description
Ground TCC1 Ground operation – quick trip
Ground TCC2 Ground operation – delayed trip
Phase TCC1 Phase operation – quick trip
Phase TCC2 Phase operation – delayed trip
III. Overcurrent Timing Curves
There are a number of timing curves available, all of which are included in the text tapranges named “ME Curves (GR)” and “ME Curves (PH)”. The following table lists thecurves included:
Setting Cooper Form 3A Recloser 2000 Users’ Group Meeting
2
CurveID Description
CurveID Description
1 ME Curves (GR) A ME Curves (PH)
2 ME Curves (GR) B ME Curves (PH)
3 ME Curves (GR) C ME Curves (PH)
4 ME Curves (GR) D ME Curves (PH)
5 ME Curves (GR) E ME Curves (PH)
6 ME Curves (GR) KP ME Curves (PH)
7 ME Curves (GR) L ME Curves (PH)
8* ME Curves (GR) M ME Curves (PH)
8 ME Curves (GR) N ME Curves (PH)
9 ME Curves (GR) P ME Curves (PH)
11 ME Curves (GR) R ME Curves (PH)
13 ME Curves (GR) T ME Curves (PH)
14 ME Curves (GR) V ME Curves (PH)
15 ME Curves (GR) W ME Curves (PH)
16 ME Curves (GR) Y ME Curves (PH)
18 ME Curves (GR) Z ME Curves (PH)
IV. Recloser Taps
When placing a recloser, set the following taps. Only the settings with Internal Nameshown in bold are actually used in the Program Model for this recloser.
Tap Name Internal Name Tap DescriptionsReclosing Interval 1 RECL_INTERVAL_1 1 – 60, INST
Reclosing Interval 2 RECL_INTERVAL_2 1 – 60, INST
Reclosing Interval 3 RECL_INTERVAL_3 1 – 60, INST
TCC1 Curve ID - Gnd. GND_TCC1_ID ME Curves (GR)
TCC1 Operations - Gnd. GND_TCC1_OPER 0 - 4
TCC2 Curve ID - Gnd. GND_TCC2_ID ME Curves (GR)
TCC2 Operations - Gnd. GND_TCC2_OPER 0 - 4
TCC1 Curve ID - Phs. PHS_TCC1_ID ME Curves (PH)
TCC1 Operations - Phs. PHS_TCC1_OPER 0 - 4
TCC2 Curve ID - Phs. PHS_TCC2_ID ME Curves (PH)
TCC2 Operations - Phs. PHS_TCC2_OPER 0 - 4
Reset-Delay Time RESET_DELAY 10,15,...,180 sec
Setting Cooper Form 3A Recloser 2000 Users’ Group Meeting
3
Ground Minimum Trip GND_MIN_TRIP 100,120,...,1120 A
Phase Mininum Trip PHS_MIN_TRIP 25,35,...,560 A
Ground Instantaneous Multiple GND_INST_MULT 1.4,2.0,...,5.6, NONE
Ground Instantaneous Trip GND_INST_TRIP 1 - 1-2-3-4
Phase Instantaneous Multiple PHS_INST_MULT 5.6,8.0,...,22.4, NONE
Phase Instantaneous Trip PHS_INST_TRIP 1 - 1-2-3-4
Ground Instantaneous Lockout GND_INST_LO 1.4,2.0,...,5.6, NONE
Phase Instantaneous Lockout PHS_INST_LO 5.6,8.0,...,22.4, NONE
Low-Current Ground Trip LOW_CURR_GND_TRIP 5.8/10 A, NONE
Minimum Response Time MIN_RESP_TIME 0.05-0.690 sec, NONE
Reclose Block RECLOSE_BLOCK Blk. Options
Sequence Coordination SEQ_COORD ON/OFF
V. Element Settings
On the element forms, set only the necessary contact logic codes; other settings are takenfrom the common taps. You can also change the settings from CAPE CG using the forms orusing DRAG_CURVE. The new common taps are computed automatically from theelement settings.
VI. Contact Logic
Suggested contact logic codes:
Element Contact Logic CodeGround TCC1 GND_TCC1
Ground TCC2 GND_TCC2
Phase TCC1 PHS_TCC1
Phase TCC2 PHS_TCC2
If there are duplicates from other reclosers in the same LZOP, you may add the prefix"FORM3A_" , e.g. "FORM3A_GND_TCC1".
The LZOP LOGIC (e.g. FORM3A_TRIP) for all elements is
PHS_TCC1 OR PHS_TCC2 OR GND_TCC1 OR GND_TCC2
To prevent an element from tripping the logical breakers in its local zone of protection(LZOP), omit its contact-logic code from this expression. For ground elements alone, theexpression would be:
GND_TCC1 OR GND_TCC2