471~1739kW
Cooling Capacity
Model Number Nomenclature
Legend
Digits 1 to 3: liquid chiller with screw compressors
Digits 4: model series, A water cooled
Digits 5 to 8: model number based on cooling capacity in kW
Digits 10: Voltage
0:400V-3Ph-50Hz(Std)
1:415V-3Ph-50Hz
2:380V-3Ph-50Hz
Digits11: Option equipped
0:No option(Std)
1:Option equipped
Notes:
Digits 10&11 is only for order handling, not shown on ECAT, Chiller nameplate
Digit Number 1 2 3 4 5 6 7 8 9 10 11
Product Code 3 0 X W 0 4 5 2 - 0 0
Unit Operating Range
Cooling/Heating
Evaporator Minimum Maximum
Entering temperature at start-up -
Leaving temperature during operation
Entering/leaving temperature difference at full load
Condenser Minimum Maximum
Entering temperature at start-up -
Leaving temperature during operation
Entering/leaving temperature difference at full load
02
The 30XW liquid chillers are the premium solution for industrial and commercial applications where installers, consultants and building
owners require optimal performances and maximum quality.
-
Premium full load and part load performance
New twin-rotor screw compressor speci cally designed for HFC-134a equipped with a high-ef ciency motor and a variable
capacity valve that permits exact matching of the cooling capacity to the load.
Flooded multi-pipe evaporator and condenser for increased heat exchange ef ciency. The evaporator has a low pressure
drop-which results in reduced cost of water pump.
Electronic expansion device permitting operation at a lower condensing pressure and improved utilization of the evaporator
heat exchange surface (superheat control).
Economizer system with electronic expansion device for increased cooling capacity (30XW-P).
Absolute reliability
Screw compressors
- Industrial-type screw compressors with oversized bearings and motor cooled by
suction gas.
- All compressor components are easily accessible on site mini-
mizing down-time.
- Protection increased by an electronic board.
Refrigerant circuit
- Two independent refrigerant circuits (from
800 kW upwards); the second one au-
tomatically takes over, if the rst one
develops a fault, maintaining partial
cooling under all circumstances.
Evaporator
- E lec t ron ic paddle-f ree f low
switch. Auto-setting according to
cooler size and uid type.
Auto-adaptive control
- Control algorithm prevents exces-
sive compressor cycling (Carrier
patent).
- Automatic compressor unloading in
case of abnormally high condensing pres-
sure.
Exceptional endurance tests
- Partnerships with specialized laboratories and use of
limit simulation tools ( nite element calculation) for the design
of critical components.
- Transport simulation test in the laboratory on a vibrating table and then on an
endurance circuit.
Environmental care
R134a refrigerant
- Refrigerant of the HFC group with zero ozone
depletion potential.
Leak-tight refrigerant circuit
- Reduction of leaks as no capillary tubes and are
connections are used.
- Veri cation of pressure transducers and tempera-
ture sensors without transferring refrigerant charge.
- Discharge line shut-off valve and liquid line service
valve for simpli ed maintenance.
03
Easy and fast installation
Compact design
- The 30XW units are designed to offer the most compact dimensions on the market.
- With a width of approximately 1 m up to 1500 kW the units can pass through standard door openings and only require minimum oor
space in the plant room.
Simpli ed electrical connections
- Main disconnect switch with high trip capacity.
- Transformer to supply the integrated control circuit (400/24 V).
Simpli ed hydronic connections
- Victaulic connections on the evaporator and condenser.
- Practical reference marks for entering and leaving water connections.
- Possibility to reverse the heat exchanger water inlet and outlet at the factory.
Fast commissioning
- Systematic factory operation test before shipment.
- Quick-test function for step-by-step veri cation of the instruments, expansion devices and compressors.
Pro-Dialog control
Pro-Dialog combines intelligence with operating simplicity. The control con-
stantly monitors all machine parameters and precisely manages the opera-
tion of compressors, electronic expansion devices and of the evaporator
water pump for optimum energy ef ciency.
Energy management
- Internal time schedule clock: controls chiller on/off times and opera
tion at a second set-point.
- Set-point reset based on the return water temperature.
- Master/slave control of two chillers operating in parallel with operating
time equalization and automatic change-over in case of a unit fault.
Ease-of-use
- User interface with large touch screen (120 x 99 mm) for intuitive ac-
cess to the operating parameters. The information is in clear text and
can be displayed in local language (please contact your distributor).
Remote management (standard)
The 30XW is equipped with an RS485 serial port that offers multiple remote
control, monitoring and diagnostic possibilities. Carrier offers a vast choice
of control products, specially designed to control, manage and supervise the
operation of an air conditioning system. Please consult your Carrier repre-
sentative for more information.
The 30XW also communicates with other building manage-ment systems via
optional communication gateways.
A connection terminal allows remote control of the 30XW by wired cable:
- Start/stop: opening of this contact will shut down the unit.
- Dual set-point: closing of this contact activates a second set-point (ex-
ample: unoccupied mode).
- Demand limit: closing of this contact limits the maximum chiller capacity
to a prede ned value.
- Operation indication: this volt-free contact indicates that the chiller is op-
erating (cooling load) or that it is ready to operate (no cooling load).
- Alert indication: this volt-free contact indicates the necessity to carry out
a maintenance operation or the presence of a minor fault.
- Alarm indication: this volt-free contact indicates the presence of a major
fault that has led to the shut-down of one or several refrigerant circuits.
04
Model30XW
0452S 0502S 0552S 0 52S 0702S 0802S 0852S 1002S 1052S 1152S 1352S 1452S 1502S 1 2S 1702S
CapacitykW 471 521 539 3 717 773 828 1004 1045 1132 1279 1425 1500 1 40 1709
USRT 134 148 153 189 204 220 235 28 297 322 3 4 405 427 4 48
CompressorCircuit A No. 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Circuit B No. 1 1 1 1 1 1 1 1
Evaporator
Outlet tem. degC .7
Flow rate L/s 20 22 23 29 31 33 3 43 45 49 55 1 5 71 74
Water Pressure
dropKpa 31 37 40 3 41 48 50 59 3 54 5 70 77 47 51
Water connection Dg 125 125 125 150 150 150 150 150 150 200 200 200 200 200 200
Fouling factor (sqm-K)/kW 0.018
Condenser
Inlet tem. degC 29.4
Flow rate L/s 25 28 29 3 39 42 45 54 5 1 9 77 81 89 92
Water Pressure
dropKpa 40 47 50 55 3 71 37 49 53 41 59 53 58 52 5
Water connection Dg 125 125 125 150 150 150 200 200 200 200 200 200 200 200 200
Fouling factor (sqm-K)/kW 0.044
MotorPower V-Ph-Hz 380/400/415-3-50
Input power kW 8 99 99 121 130 145 150 185 195 202 221 245 2 3 281 298
Shipping weight(with refrigerant) kg 294 2983 3032 3770 3770 3778 3958 5454 5491 5781 714 7 47 7 4 8838 8853
Operation weight kg 2580 2 17 2 348 348 3493 3711 51 1 5198 5553 995 7549 75 8938 8953
Dimension
Length mm 274 274 274 305 305 305 2780 4008 4008 4008 4 95 4 95 4 95 47 0 47 0
Width mm 970 970 970 1119 1119 1119 1085 1050 1050 1050 1188 1231 1231 19 5 19 5
Height mm 1 93 1 93 1 93 1849 1849 1849 1900 184 184 189 20 4 20 4 20 4 1537 1537
Model30XW
0502P 0552P 0702P 0802P 0852P 1002P 1152P 1352P 1452P 1 02P 1752P
CapacitykW 505 572 730 784 852 1029 1147 130 1488 1 14 1739
USRT 144 1 3 207 223 242 293 32 371 423 459 495
CompressorCircuit A No. 1 1 1 1 1 1 1 1 1 1 1
Circuit B No. 1 1 1 1 1 1
Evaporator
Outlet tem. degC .7
Flow rate L/s 22 25 31 34 37 44 49 5 4 9 75
Water Pressure
dropKpa 22 28 2 29 34 38 4 30 38 44 51
Water connection Dg 150 150 200 200 200 200 200 200 250 250 250
Fouling factor (sqm-K)/kW 0.018
Condenser
Inlet tem. degC 29.4
Flow rate L/s 27 31 39 42 4 5 2 71 80 87 94
Water Pressure
dropKpa 35 43 3 41 47 30 3 3 31 37 43
Water connection Dg 150 150 200 200 200 200 200 250 250 250 250
Fouling factor (sqm-K)/kW 0.044
MotorPower V-Ph-Hz 380/400/415-3-50
Input power kW 85 9 121 134 144 173 193 213 242 2 2 283
Shipping weight(with refrigerant) kg 3275 3312 4331 4349 4379 74 749 8995 10848 10848 10848
Operation weight kg 29 3 3025 4155 4173 4204 09 84 8945 10948 10948 10948
Dimension
Length mm 3055 3055 328 328 328 4 94 4 94 4783 4809 4809 4809
Width mm 1008 1008 1135 1135 1135 1070 1070 1985 21 0 21 0 21 0
Height mm 1743 1743 1949 1949 1949 1998 1998 1531 158 158 158
. .kW
Technical Data
Dimensions
05
Note:
1. Required clearances for maintenance,
Recommended space for tube removal (clearance 2 0 and 1000 can be either on the right or the left side).
2. Pi and Pi are two group of bolts to x the chiller, either group can be selected.
3. The water pipe connector is the Victaulic coupling. The Victaulic and the pipe are supplied with the chiller, the pipe length is 120mm.
30XW0452S~30XW0552S
Model A B C D E S R
30XW0452S/0502S 272 251 320 189 1 93 Dg125 Dg125
30XW0552S 272 251 320 189 1700 Dg125 Dg125
Model P1 P2 P3 P4 P1’ P2’ P3’ P4’ PT
30XW0452S 744 809 492 535 738 815 488 539 2580
30XW0502S 852 473 758 531
30XW0552S 780 891 530 902 458 537
Weight Distribution (kg)
06
Note:
1. Required clearances for maintenance,
Recommended space for tube removal (clearance 2 0 and 1000 can be either on the right or the left side).
2. Pi and Pi are two group of bolts to x the chiller, either group can be selected.
3. The water pipe connector is the Victaulic coupling. The Victaulic and the pipe are supplied with the chiller, the pipe length is 120mm.
30XW0652S~30XW0802S
Model P1 P2 P3 P4 P1’ P2’ P3’ P4’ PT
1173 1050 597 1185 1037 590
30XW0702S 1173 1050 597 1185 1037 590
30XW0802S 1175 1052 598 1187 1039 591 3493
Weight Distribution (kg)
600
E
DC
BA
100
111
9
500
700
958
80
808
75
80
75
2501200
S
R
3056
2660
1000120
Detail A
Chiller
Pipe
Sealing
GasketVictaulic Coupling
Coupling Pipe
(Welded with the
customer pipe)
689
P1 P1’ P3 P3’
P2 P2’ P4 P4’
889 H
1119
Connection Guide
See Detail A
Water Outlet,
Cooler
Water Inlet,
Cooler
Water Outlet,
Condenser
Water Inlet,
Condenser
1
1
1
2 2
Dimensions
Model A B C D H E S R
30XW0 52S 220 304 303 284 528 1849 Dg150 Dg150
30XW0702S/0802S 220 304 303 284 582 1849 Dg150 Dg150
07
Note:
1. Required clearances for maintenance,
Recommended space for tube removal (clearance 2 0 and 1000 can be either on the right or the left side).
2. Pi and Pi are two group of bolts to x the chiller, either group can be selected.
3. The water pipe connector is the Victaulic coupling. The Victaulic and the pipe are supplied with the chiller, the pipe length is 120mm.
30XW0852S
A B C D E S R
230 340 310 284 1900 Dg150 Dg200
Model P1 P2 P3 P4 P1’ P2’ P3’ P4’ PT
30XW0852S 1097 1238 730 1089 735 3711
Weight Distribution (kg)
08
Note:
1. Required clearances for maintenance,
Recommended space for tube removal (clearance 38 0 and 1000 can be either on the right or the left side).
2. Pi and Pi are two group of bolts to x the chiller, either group can be selected.
3. The water pipe connector is the Victaulic coupling. The Victaulic and the pipe are supplied with the chiller, the pipe length is 120mm.
30XW1002S~30XW1152S
Model A B C D E S R
30XW1002S/1052S 284 311 340 230 184 Dg150 Dg200
30XW1152S 290 333 340 230 189 Dg200 Dg200
Model P1 P2 P3 P4 P1’ P2’ P3’ P4’ PT
30XW1002S 1491 1208 1102 1508 1343 1222 1088
30XW1052S 1498 1381 1207 1113 1513 1219 1100 5198
30XW1152S 1283 1221 1572 1477 1291 1213 5553
Weight Distribution (kg)
Dimensions
60
0
E
DC
BA
10
0
10
50
50
07
00
96
71
42
76
7
42
125
2502239
S
R
4008
3860
1000
689
P1 P1’ P3 P3’
P2P2’ P4P4’
846
577
1050
Connection Guide
See Detail A
Water Outlet,
Cooler
Water Inlet,
Cooler
Water Outlet,
Condenser
Water Inlet,
Condenser
1
1
1
2
2
Circuit A Circuit B
120
Detail A
Chiller
Pipe
Sealing
GasketVictaulic Coupling
Coupling Pipe
(Welded with the
customer pipe)
09
Note:
1. Required clearances for maintenance,
Recommended space for tube removal (clearance 45 0 and 1000 can be either on the right or the left side).
2. Pi and Pi are two group of bolts to x the chiller, either group can be selected.
3. The water pipe connector is the Victaulic coupling. The Victaulic and the pipe are supplied with the chiller, the pipe length is 120mm.
30XW1352S
A B C D E S R
340 359 340 255 20 4 Dg200 Dg200
Model P1 P2 P3 P4 P1’ P2’ P3’ P4’ PT
30XW1352S 2098 1980 1501 2111 1510 1407
Weight Distribution (kg)
120
Detail A
Chiller
Pipe
Sealing
GasketVictaulic Coupling
Coupling Pipe
(Welded with the
customer pipe)
60
0
E
AB
CD
10
0
1188
50
0
70
0
11
08
40
908
14
0
250125
2585
S
R
4695
4560
1000
689
P1 P1’ P3 P3’
P2 P2’ P4 P4’
1013
655
1188
Connection Guide
See Detail A
Water Outlet,
Cooler
Water Inlet,
Cooler
Water Outlet,
Condenser
Water Inlet,
Condenser
1
1
1
2 2
Circuit A Circuit B
10
Note:
1. Required clearances for maintenance,
Recommended space for tube removal (clearance 45 0 and 1000 can be either on the right or the left side).
2. Pi and Pi are two group of bolts to x the chiller, either group can be selected.
3. The water pipe connector is the Victaulic coupling. The Victaulic and the pipe are supplied with the chiller, the pipe length is 120mm.
30XW1452S~30XW1502S
Model P1 P2 P3 P4 P1’ P2’ P3’ P4’ PT
30XW1452S 1979 2243 1559 1952 2271 1537 1789 7549
30XW1502S 1983 2247 1773 2275 1541 1794
Weight Distribution (kg)
Dimensions
A B C D E S R
340 359 340 255 20 4 Dg200 Dg200
120
Detail A
Chiller
Pipe
Sealing
GasketVictaulic Coupling
Coupling Pipe
(Welded with the
customer pipe)
60
0
E
AB
CD
10
0
12
31
50
0
70
0
11
51
40
95
11
00
250
125
2585
S
R
4695
4560
1000
689
P1 P1’ P3 P3’
P2 P2’ P4 P4’
698
1231
Connection Guide
See Detail A
Water Outlet,
Cooler
Water Inlet,
Cooler
Water Outlet,
Condenser
Water Inlet,
Condenser
1
1
1
22
Circuit A Circuit B
11
Note:
1. Required clearances for maintenance,
Recommended space for tube removal (clearance 45 0 and 1000 can be either on the right or the left side).
2. Pi and Pi are two group of bolts to x the chiller, either group can be selected.
3. The water pipe connector is the Victaulic coupling. The Victaulic and the pipe are supplied with the chiller, the pipe length is 120mm.
30XW1662S~30XW1702S
A B C D E S R
340 391 350 334 1537 Dg200 Dg200
Model P1 P2 P3 P4 P1’ P2’ P3’ P4’ PT
2391 2772 1748 2027 2794 1732 2043 8938
30XW1702S 2395 2777 1751 2030 2373 2799 1735 2047 8953
Weight Distribution (kg)
120
Detail A
Chiller
Pipe
Sealing
GasketVictaulic Coupling
Coupling Pipe
(Welded with the
customer pipe)
600
E
CD
AB
100
1965
500
700
1885
40
1685
140
40
140
250
1745
SR
4760
4560
1000
689
P1 P1ʼ P3 P3ʼ
P2 P2ʼ P4 P4ʼ
1461 450 450 346
1965
629
Connection Guide
See Detail A
Water Outlet,
Cooler
Water Inlet,
Cooler
Water Outlet,
Condenser
Water Inlet,
Condenser
1
1
1
2
2
Circuit A Circuit B
12
Note:
1. Required clearances for maintenance,
Recommended space for tube removal (clearance 29 0 and 1000 can be either on the right or the left side).
2. Pi and Pi are two group of bolts to x the chiller, either group can be selected.
3. The water pipe connector is the Victaulic coupling. The Victaulic and the pipe are supplied with the chiller, the pipe length is 120mm.
30XW0502P~30XW0552P
Model P1 P2 P3 P4 P1’ P2’ P3’ P4’ PT
30XW0502P 891 885 592 892 884 591
30XW0552P 952 552 558 951 552 559 3025
Weight Distribution (kg)
Dimensions
A B C D E S R
242 299 304 222 1743 Dg150 Dg150
120
Detail A
Chiller
Pipe
Sealing
GasketVictaulic Coupling
Coupling Pipe
(Welded with the
customer pipe)
13
Note:
1. Required clearances for maintenance,
Recommended space for tube removal (clearance 31 0 and 1000 can be either on the right or the left side).
2. Pi and Pi are two group of bolts to x the chiller, either group can be selected.
3. The water pipe connector is the Victaulic coupling. The Victaulic and the pipe are supplied with the chiller, the pipe length is 120mm.
30XW0702P~30XW0852P
Model A B C D E F G S R
30XW0702P 230 340 333 290 1949 50 328 Dg200 Dg200
30XW0802P 230 340 333 290 1949 50 328 Dg200 Dg200
30XW0852P 230 340 333 290 1949 801 3288 Dg200 Dg200
Model P1 P2 P3 P4 P1’ P2’ P3’ P4’ PT
30XW0702P 1491 1758 490 1478 1771 412 494 4155
30XW0802P 1498 418 492 1484 1779 414 4173
30XW0852P 1454 1791 433 1437 1809 428 530 4204
Weight Distribution (kg)
120
Detail A
Chiller
Pipe
Sealing
GasketVictaulic Coupling
Coupling Pipe
(Welded with the
customer pipe)
600
E
DC
BA
100
11
35
500
700
1085
25
985
75
220
1600
S
R
G
3160
1000
689
P1 P1’ P3 P3’
P2 P2’ P4 P4’
F599
1135
Connection Guide
See Detail A
Water Outlet,
Cooler
Water Inlet,
Cooler
Water Outlet,
Condenser
Water Inlet,
Condenser
1
1
1
22
14
Note:
1. Required clearances for maintenance,
Recommended space for tube removal (clearance 45 0 and 1000 can be either on the right or the left side).
2. Pi and Pi are two group of bolts to x the chiller, either group can be selected.
3. The water pipe connector is the Victaulic coupling. The Victaulic and the pipe are supplied with the chiller, the pipe length is 120mm.
30XW1002P~30XW1152P
Model P1 P2 P3 P4 P1’ P2’ P3’ P4’ PT
30XW1002P 1590 1998 1339
30XW1152P 1987 1580 1381 2019 1704 1355
Weight Distribution (kg)
Dimensions
A B C D E S R
340 359 340 255 1998 Dg200 Dg200
120
Detail A
Chiller
Pipe
Sealing
GasketVictaulic Coupling
Coupling Pipe
(Welded with the
customer pipe)
15
Note:
1. Required clearances for maintenance,
Recommended space for tube removal (clearance 45 0 and 1000 can be either on the right or the left side).
2. Pi and Pi are two group of bolts to x the chiller, either group can be selected.
3. The water pipe connector is the Victaulic coupling. The Victaulic and the pipe are supplied with the chiller, the pipe length is 120mm.
30XW1352P
A B C D E S R
340 391 350 334 1531 Dg200 Dg250
Model P1 P2 P3 P4 P1’ P2’ P3’ P4’ PT
30XW1352P 2719 1758 1774 2721 1757 1775 8945
Weight Distribution (kg)
16
Note:
1. Required clearances for maintenance,
Recommended space for tube removal (clearance 45 0 and 1000 can be either on the right or the left side).
2. Pi and Pi are two group of bolts to x the chiller, either group can be selected.
3. The water pipe connector is the Victaulic coupling. The Victaulic and the pipe are supplied with the chiller, the pipe length is 120mm.
30XW1452P~30XW1752P
Dimensions
120
Detail A
Chiller
Pipe
Sealing
GasketVictaulic Coupling
Coupling Pipe
(Welded with the
customer pipe)
60
0
E
DC
BA
10
0
21
60
50
07
00
208
04
0
1880
14
0
40
14
0
2501745
SR
4809
4560
1000
689
P1 P1’ P3 P3’
P2 P2’ P4 P4’
1484
Connection Guide
See Detail A
Water Outlet,
Cooler
Water Inlet,
Cooler
Water Outlet,
Condenser
Water Inlet,
Condenser
1
1
1
22
Circuit A Circuit B 473 473 437
2160
767
Model A B C D E S R
30XW1452P 380 347 428 349 158 Dg250 Dg250
380 347 428 349 158 Dg250 Dg250
Model P1 P2 P3 P4 P1’ P2’ P3’ P4’ PT
30XW1452P 3010 2317 2445 3001 3185 2310 2452 10948
3010 2317 2445 3001 3185 2310 2452 10948
30XW1752P 3010 2317 2445 3001 3185 2310 2452 10948
Weight Distribution (kg)
17
Foundation
ModelDimension (mm)
A B C P Q R
30XW0452S 704 920 75 970
30XW0502S 704 920 75 970
30XW0552S 704 920 75 970
1200 889 958 80 1119
30XW0702S 1200 889 958 80 1119
30XW0802S 1200 889 958 75 1119
30XW0852S 1200 751 2780 1035 75 1085
30XW1002S 2239 844 4008 100 1050
30XW1052S 2239 844 4008 100 1050
30XW1152S 2239 4008 100 1050
30XW1352S 2585 1013 1108 100 1188
30XW1452S 2585 1013 1151 100 1231
30XW1502S 2585 1013 1151 100 1231
1745 100
30XW1702S 1745 100
30XW0502P 1200 889 3055 958 75 1008
30XW0552P 1200 889 3055 958 75 1008
30XW0702P 1085 75 1135
30XW0802P 1085 75 1135
30XW0852P 1085 75 1135
30XW1002P 2585 1013 990 100 1070
30XW1152P 2585 1013 990 100 1070
30XW1352P 1745 1471 4783 1905 100 1985
30XW1452P 1745 1484 4809 2080 100
1745 1484 4809 2080 100
30XW1752P 1745 1484 4809 2080 100
18
Options
Options NO Description Advantages Use
Medium Brine 5temperature
application such
as ice storage
and industrial
processes
30XW1152S
30XW0502P
30XW0552P
30XW1002P
Low Brine
temperature
application such
as ice storage
and industrial
processes
30XW1152S
30XW0502P
to compressor motor electrical characteristics
30XW0552P
30XW1002P
Single power
connection81
This option is required to allow to connect on
single power supply line to one single location
where std machine require two
Quick and easy
installation
30XW1002S-1702S
30XW1002P-1752P
Evaporator &
Condenser water 104
Reinforced evaporator & condenser for extension
of the maximum water-side service pressure to
Covers applications
with a high water
column(high
buildings)
30XW0452S-1702S
30XW0502P-1752P
Evaporator &
Condenser water
pressue 2.1MPa
Reinforced evaporator & condenser for extension
of the maximum water-side service pressure to
2.1MPa
Covers applications
with a high water
column(high
buildings)
30XW0452S-1702S
30XW0502P-1752P
Evaporator with
reversed water
connection
107E Evaporator with reversed water inlet/outletwater piping
30XW0452S-1702S
30XW0502P-1752P
Condenser with
reversed water
connection
107C Condenser with reversed water inlet/outletwater piping
30XW0452S-1702S
30XW0502P-1752P
CCN to J bus
gateway148B
Two way protocol converter board between CCN
and J-Bus for easy connection to BMS. Easy connection
by communication
bus to a building
management
system
30XW0452S-1702S
Consist of:
-Electronic board mounted in the unit electrical
cabinet 30XW0502P-1752P
CCN to BAC Net/
Modbus gateway148C
Two way protocol converter board between CCN
and BAC Net/Modbus for easy connection to
BMS.Easy connection
by communication
bus to a building
management
system
30XW0452S-1702S
Consist of:
-Electronic board mounted in the unit electrical
cabinet 30XW0502P-1752P
CCN to Lon work
gateway148D
Two way protocol converter board between CCN
and Lon walk for easy connection to BMS. Easy connection
by communication
bus to a building
management
system
30XW0452S-1702S
Consist of:
-Electronic board mounted in the unit electrical
cabinet 30XW0502P-1752P
High condensing
temperature
unit (up to
leaving
condenser water
temperature)
150
Increased condenser leaving water temperature
.Allows applications
with high
condensing
temperature(for
heat reclaim or dry
cooler applications)
30XW0452S-0552S
30XW1002S-1152S
30XW0502P-0552P
to compressor motor electrical characteristics30XW1002P-1152P
Options NO Description Advantages Use
Heat pump Max
condenser leaving 150A
Heat pump control logic to control condenser
LWT
Allows heating
applications with
max condenser
30XW0452S-0552S
30XW1002S-1152S
to compressor motor electrical characteristics30XW0502P-0552P
30XW1002P-1152P
Condenser
maxium leaving
temperature
limited to 45
150Bmaximum condenser leaving temperature
Avoids oversizing
of the protection
elements and the
power cables
30XW0452S-1702S
30XW0502P-1752P
Heat pump Max
condenser leaving
temp 50
150D
Heat pump control logic to control condenser
LWT Allows heating
applications with
max condenser
leaving temp 50
30XW0452S-1702S
30XW0502P-1752P
Condenser water
valve control
(0-10V signal)
152
Output signal (0-10V) to control the condenser
water inlet valve
Used for
applications with
cold water at the
condenser inlet
(well water). In
this case the
valve controls the
water entering
temperature to
maintain an
acceptable
condensing
pressure
30XW0452S-1702SConsist of:
- One 8DO+4AI/2AO Board
- Connector for 3 way valve
30XW0502P-1752PNote: Power supply for water valve is not
included
Energy
management
module
Remote control module. Additional contacts for
an extension of the unit control functions (without
communication bus)
Easy connection by
wired connection
to a building
management
system
30XW0452S-1702S
Consist of:
30XW0502P-1752P- Electrinoc board mounted in the unit electrical
cabniet
Evaporator
connections
314E Victaulic to Flange water connections Easy installation30XW0452S-1702S
30XW0502P-1752P
Condenser
connections
314C Victaulic to Flange water connections Easy installation30XW0452S-1702S
30XW0502P-1752P
Nitrogen charge 320 Unit nitrogen factory charged.Less weight. No
refrigerant charged
30XW0452S-1702S
30XW0502P-1752P
Australia code 312AMeets Australia government pressure vessel
code AS 1210 and AS 4343
Meets Australia
government
pressure vessel
code AS 1210 and
AS 4343
30XW0452S-1702S
30XW0502P-1752P
Multi-piece
shipment51
"Side-by-side" Units only. Unit shipped in
connections, no refrigerant charge (Nitrogen
holding charge)
Easy installation
30XW1352P-1752P
Low noise 257
Provide 2 to 4 dBA sound attenuation vs std to
meet low noise applicationLower operating
sound levels
30XW0452S-1702S
30XW0502P-1752P
19
Options NO Description Advantages Use
Super low noise 258meet super low noise application Lower operating
sound levels
30XW0452S-1702S
30XW0502P-1752P
Super low noise 258Ameet super low noise application
Lower operating
sound levels with
waterproof
30XW0452S-1702S
30XW0502P-1752P
Super low noise 258B
Provide 8 to 10 dBA sound attenuation vs std to
meet super low noise application Lower operating
sound levels
30XW0452S-1702S
30XW0502P-1752P
20
Options
Notes:
2. Compatibility: Medium brine option PT005 is not compatible with PT150/PT150A/PT312A.
3. PT150A only suitable for 30XW0452/0502/0552/1002/1052/1152/0502P/0552P/1002P/1152P
4. Condenser water valve control option is not include 3 way valve and power supply for water valve.
2.5
mm
2M
AX
.
0-1
0V
DC
24
VA
C-4
8V
DC
MA
X
20
V-M
IN
1.5
mm
2M
AX
1.5
mm
2M
AX
.
24
VA
C-3
0V
AM
AX
1.5
mm
2M
AX
.
ALARM
ALERT
READY
REMOTE ON / OFF SWITCH
SET POINT SWITCH
DEMAND LIMIT SWITCH
WATER PUMP FEEDBACK
PUMP 1 COMMAND
PUMP 2 COMMAND
CNN CONNECTOR
80mA MIN-3A MAX
80mA MIN-3A MAX
80mA MIN-3A MAX
30A
31A
30B
31B
30B
31B
32
33
5
3
4
71
72
73
74
0.5A MAX
0.5A MAX
J3CH24
+C
CH11
+C
CH12
+CCH13
+C
CH14
+C
+C
CH10
CCNJ12CN
GND
+
A1
24
VA
C,2
0m
ACH25
+C
CH2
+C
J8
J5
J2
CH18
+C
CH19
-
CH20
-
Wiring Diagram
21
General description
Factory assembled single piece water-cooled liquid chiller. Contained within the unit shall be all factory wiring,
piping, controls, refrigerant charge (HFC-134a), refrigeration circuits set, screw compressors, electronic expan-
Quality assurance
1. Unit construction shall comply with standard including the following:
A. Code of design of heating, ventilation and air conditions (GBJ 19-87, GB50019-2003)
B. GB/T 18430.1-2007, ARI Standard 550/590-2003
ISO 9001 and environmental management system ISO 14001
3. Unit shall be run tested at the factory.
4. Unit components shall be capable of withstanding 60°C storage without damage, failure, refrigerant
loss, or safety risks.
Product features
1. Compressors:
A. Unit shall have semi-hermetic twin-screw compressors with internal relief valve and check valve to avoid
reverse rotation on shut down.
B. Each compressor shall be equipped with a discharge shut-off valve.
D. Capacity control shall be provided by a variable control slide valve capable of reducing compressor capacity
down to 15% of full load. Compressor shall start in unloaded condition.
E. Motor shall be cooled by suction gas and protected by internal winding temperature sensors. Compressor
bearings shall be designed for minimum 73000 hours at maximum operating conditions.
2. Evaporator:
A. Unit shall be equipped with a single evaporator.
B. Evaporator shall be manufactured, tested and stamped in accordance with the GB150-1998.
C. The maximum refrigerant-side operating pressure will be 2100 kPa, and the maximum waterside pressure
D. The evaporator shall be mechanically cleanable, shell-and-tube type with removable heads. Tubes shall
be internally and externally grooved, seamless-copper, and shall be rolled into tube sheets. Shell shall be
insulated with 19 mm closed-cell foam with a maximum K factor of 0.28. Evaporator thermal insulation
E. The evaporator shall have a drain and vent in each head.
F. The evaporator shall incorporate an active refrigerant level control system to ensure optimum heat transfer
performance under all load conditions.
G. Design shall incorporate either 1 or 2 independent refrigerant circuits
22
H. Chiller shall have only one water inlet & outlet connection with victaulic couplings to avoid vibrations trans-
mission and accept small misalignment (water connection kit on demand).
pressure switches shall not be acceptable.
3. Condenser:
A. Unit shall be equipped with a single condenser.
B. Condenser shall be manufactured, tested and stamped in accordance with the GB150-1998.
C. The maximum refrigerant-side operating pressure will be 2100 kPa, and the maximum waterside pressure
D. The condenser shall be mechanically cleanable shell-and-tube type with removable heads.
E. Tubes shall be internally and externally grooved, seamless-copper, and shall be rolled into tube sheets.
F. Design shall incorporate either 1 or 2 independent refrigerant circuits and the oil separator.
G. The condenser shall have a drain and vent in each head.
H. Chiller shall have only one water inlet & outlet connection with victaulic couplings to avoid vibrations trans-
mission and accept small misalignment (water connection kit on demand).
4. Refrigeration circuits:
A. Refrigerant circuit components shall include, compressor, oil separator, high and low side pressure relief
indicating sight glasses, long stroke electronic expansion device, and complete operating charge of both
refrigerant HFC-134a and compressor oil.
B. To facilitate service and maintenance and avoid refrigerant charge transfers, it must be possible to isolate
-
pressor (with service valves option).
5. Controls:
A. Unit controls shall include as a minimum: microprocessor with non-volatile memory, picture guided unit/
operator interface, the LOCAL/OFF/REMOTE/CCN selector and a touch-screen display with with multiple
language capability.
B. Pressure sensors shall be installed to measure suction, discharge, and oil pressure.
C. Thermistors shall be installed to measure cooler entering and leaving temperatures (on cooler and con-
denser side).
D. Unit shall be capable of performing the following functions:
- Automatic change-over and cycling of compressors to equalize running hours and number of starts.
- EXV control, based on throttling optimizes evaporator charging, ensuring condenser superheat and sub-
cooling.
23
minute to prevent excessive demand spikes at start-up.
- Enable reset of leaving chilled water temperature according to the return water temperature or by means
of a 0-10V signal.
- Provide a dual set point for the leaving chilled water temperature activated by a remote contact closure
signal or by the built in time clock.
- Enable a 2-level demand limit control (between 0 and 100%) or a maximum current drawn limit activat
edby a remote contact closure or by the built in time clock.
- Control evaporator water pump and the condenser pump.
- Allow two time scheduling programs to enable unit start-up control, demand limit and set-point changes.
- Enable lead lag control of two chillers running in series or parallel.
6. Diagnostics:
A. Display module shall be capable of displaying set points, system status including temperatures, pressures,
current for each compressor, run time and percent loading.
B. The control system shall allow a quick test of all machine elements to verify the correct operation of every
switch, circuit breaker, contactor etc. before the chiller is started.
7. Safeties:
A. Unit shall be equipped with all necessary components, and in conjunction with the control system shall
provide the unit with protection against the following:
- Reverse rotation.
- Low chilled water temperature.
- Low oil pressure (per compressor).
- Current imbalance.
- Compressor thermal overload
- Automatic compressor unloading in case of excessive condensing temperature
- High pressure.
- Electrical overload.
- Loss of phase.
B. Control shall provide separate general alert (minor incident) and alarm (circuit down) remote indication.
8. Operating characteristics:
9. Electrical characteristics:
A. Unit shall operate on 3-phase power supply without neutral.
B. Control voltage shall be supplied by a factory-installed transformer.
C. Unit shall be supplied with factory-installed electrical disconnect/isolator switch integrating main fuses.
D. Unit shall have a factory installed star/delta starter as standard to limit electrical inrush current.