Controls and Electrical Preferred Technologies

Steve Pavis PH-DT-DI CERN

Advel Power Supplies and ABB Circuit Breakers

Gas Control System

Steve Pavis PH-DT-DI CERN

Advel Power Supplies

Steve Pavis PH-DT-DI CERN

Advel PSUsSteve Pavis PH-DT-DI CERN

Technical Requirements (extract from our specification)  

•Preference is that overall power requirements for an individual system be achieved within a single 19" rack mounting chassis. Where this is not possible, e.g. for the larger systems, then two or more 19" rack mounting chassis may be used provided their outputs can be connected together whilst still maintaining current sharing. •The bidder should state “Comply” or “Doesn’t Comply” against the following requirements for clarity in evaluating offers.  •Housing : 19” 3U, 4U or 6U high chassis for Rack mounting

•Hot Swappable/pluggable Power Supply modules with Input Voltage: 220VAC Input Frequency :50Hz, Output Voltage: 24VDC and 15VDC versions (see table), arranged in an N+1 or Dual Redundant configuration with Power Sharing.

•Efficiency : >= 80%

•Ripple & Noise (Acc. to IEC/EN 61204) : <= 50mV p-p

•Output Hold up time : 15ms

•Deviation due to dynamic load change (Transient Response) : for 60% step load increase, output voltage must not deviate by more than 3V.

•Front of Module LEDs for Power Supply Status

•Power Fail Signal: Volt free contact to be provided (via terminals on the rear of the chassis) for power fail indication of any power supply module.

•AC input terminals and DC output terminals to be provided at the rear of the chassis.

•Operating Temperature: 0 - 55 degrees Celcius

•CE Marked for compliance to EMC and Low Voltage Directives (Immunity and Emission) 

Advel PSUsSteve Pavis PH-DT-DI CERN

In addition, the bidder should indicate the following in the offer: 

 1“In rush current" when turning on the power system (for both "no load" and "full load" conditions)

2Level of power factor correction (if provided)

3MTBF for each power supply module

4Method of power sharing e.g. "Active Current Sharing" (third wire), or "Passive Current Sharing" (Droop regulation/Slope Programming).

5If current limiting is provided on the 24VDC/15VDC output, please specify and indicate the level.

6Height of the 19” rack mounting chassis which houses the power modules.

Steve Pavis PH-DT-DI CERN

Advel PSUs

Responses To Cern Specification

Steve Pavis PH-DT-DI CERN

Advel PSUs

Responses To Cern Specification continued

Steve Pavis PH-DT-DI CERN

Advel PSUs

Steve Pavis PH-DT-DI CERN

Advel PSUs

Output Voltage Adjust +/- 10% (in addition to

sense lines)

LEDs indicate correct current balancing and

temperature within good operational limits

Fan Healthy LEDs

25W

50W

150W

200W

250W

300W

350W

500W

600W

750W

1000W

2000W

Any voltage !!

Steve Pavis PH-DT-DI CERN

Advel PSUs

Steve Pavis PH-DT-DI CERN

Advel PSUs

Steve Pavis PH-DT-DI CERN

PSU Circuit Diagram

ABB Busbar Mounted Circuit Breakers

Steve Pavis PH-DT-DI CERN

AC Power Distribution Miniature Circuit Breakers Directly

Mounted On Busbars (Complete assemby can be done “on the bench”

to enable speedy installation)

Pump Variable Frequency Drive shielded from sensitive signals

Steve Pavis PH-DT-DI CERN

Rear View

Fieldbusses “Daisy Chained” down the back of the control

chassis

Steve Pavis PH-DT-DI CERN

ABB Busbar Mounted MCB Solution

Busbars rated to 200AAuxiliary

Contact Busbar

Can be clipped under live power conditions

Phase selection

Steve Pavis PH-DT-DI CERN

ABB Busbar Mounted MCB Solution

Various Motor Starters available

Current measuring modules with

LED indicators

Steve Pavis PH-DT-DI CERN

ABB Busbar Mounted MCB Solution

Steve Pavis PH-DT-DI CERN

ABB Busbar Mounted MCB Solution

Steve Pavis PH-DT-DI CERN

ABB Busbar Mounted MCB Solution