Controls and Electrical Preferred Technologies
Steve Pavis PH-DT-DI CERN
Advel Power Supplies and ABB Circuit Breakers
Advel PSUsSteve Pavis PH-DT-DI CERN
Technical Requirements (extract from our specification)
•Preference is that overall power requirements for an individual system be achieved within a single 19" rack mounting chassis. Where this is not possible, e.g. for the larger systems, then two or more 19" rack mounting chassis may be used provided their outputs can be connected together whilst still maintaining current sharing. •The bidder should state “Comply” or “Doesn’t Comply” against the following requirements for clarity in evaluating offers. •Housing : 19” 3U, 4U or 6U high chassis for Rack mounting
•Hot Swappable/pluggable Power Supply modules with Input Voltage: 220VAC Input Frequency :50Hz, Output Voltage: 24VDC and 15VDC versions (see table), arranged in an N+1 or Dual Redundant configuration with Power Sharing.
•Efficiency : >= 80%
•Ripple & Noise (Acc. to IEC/EN 61204) : <= 50mV p-p
•Output Hold up time : 15ms
•Deviation due to dynamic load change (Transient Response) : for 60% step load increase, output voltage must not deviate by more than 3V.
•Front of Module LEDs for Power Supply Status
•Power Fail Signal: Volt free contact to be provided (via terminals on the rear of the chassis) for power fail indication of any power supply module.
•AC input terminals and DC output terminals to be provided at the rear of the chassis.
•Operating Temperature: 0 - 55 degrees Celcius
•CE Marked for compliance to EMC and Low Voltage Directives (Immunity and Emission)
Advel PSUsSteve Pavis PH-DT-DI CERN
In addition, the bidder should indicate the following in the offer:
1“In rush current" when turning on the power system (for both "no load" and "full load" conditions)
2Level of power factor correction (if provided)
3MTBF for each power supply module
4Method of power sharing e.g. "Active Current Sharing" (third wire), or "Passive Current Sharing" (Droop regulation/Slope Programming).
5If current limiting is provided on the 24VDC/15VDC output, please specify and indicate the level.
6Height of the 19” rack mounting chassis which houses the power modules.
Steve Pavis PH-DT-DI CERN
Advel PSUs
Output Voltage Adjust +/- 10% (in addition to
sense lines)
LEDs indicate correct current balancing and
temperature within good operational limits
Fan Healthy LEDs
25W
50W
150W
200W
250W
300W
350W
500W
600W
750W
1000W
2000W
Any voltage !!
AC Power Distribution Miniature Circuit Breakers Directly
Mounted On Busbars (Complete assemby can be done “on the bench”
to enable speedy installation)
Pump Variable Frequency Drive shielded from sensitive signals
Steve Pavis PH-DT-DI CERN
Rear View
Fieldbusses “Daisy Chained” down the back of the control
chassis
Steve Pavis PH-DT-DI CERN
ABB Busbar Mounted MCB Solution
Touch Proof Pluggable System – load free MCBS can be snapped on and off the bus bar assemly under live conditions without risk.
Steve Pavis PH-DT-DI CERN
ABB Busbar Mounted MCB Solution
Busbars rated to 200AAuxiliary
Contact Busbar
Can be clipped under live power conditions
Phase selection
Steve Pavis PH-DT-DI CERN
ABB Busbar Mounted MCB Solution
Various Motor Starters available
Current measuring modules with
LED indicators