28
Installation Instructions ControlLogix EtherNet/IP Module Catalog Number 1756-EN2T About This Publication Use this publication as a guide to install the module. This publication describes hardware installation only. For configuration information, refer to the EtherNet/IP Modules in Logix5000 Control Systems User Manual, publication ENET-UM001 . View or download this publication at http://www.rockwellautomation.com/literature . Topic Page About This Publication 1 Before You Begin 7 Determine Module Slot Location 8 Set the Network Address 9 Install the Module 11 Connect the Module to the EtherNet/IP Network 12 Program the Module via the USB Port 14 Configure the Module 15 Apply Chassis Power 15 Check Power Supply and Module Status 16 Install or Remove the Module Under Power 17 Interpret the Status Indicators 19 Specifications 22

ControlLogix EtherNet/IP Module Installation Instructionsliterature.rockwellautomation.com/idc/groups/literature/documents/... · Installation Instructions ControlLogix EtherNet/IP

  • Upload
    leliem

  • View
    221

  • Download
    3

Embed Size (px)

Citation preview

  • Installation Instructions

    ControlLogix EtherNet/IP ModuleCatalog Number 1756-EN2T

    About This PublicationUse this publication as a guide to install the module. This publication describes hardware installation only. For configuration information, refer to the EtherNet/IP Modules in Logix5000 Control Systems User Manual, publication ENET-UM001. View or download this publication at http://www.rockwellautomation.com/literature.

    Topic Page

    About This Publication 1

    Before You Begin 7

    Determine Module Slot Location 8

    Set the Network Address 9

    Install the Module 11

    Connect the Module to the EtherNet/IP Network 12

    Program the Module via the USB Port 14

    Configure the Module 15

    Apply Chassis Power 15

    Check Power Supply and Module Status 16

    Install or Remove the Module Under Power 17

    Interpret the Status Indicators 19

    Specifications 22

    http://www.literature.rockwellautomation.com/idc/groups/literature/documents/um/enet-um001_-en-p.pdfhttp://literature.rockwellautomation.com

  • 2 ControlLogix EtherNet/IP Module

    Important User Information

    Solid-state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (Publication SGI-1.1 available from your local Rockwell Automation sales office or online at http://www.rockwellautomation.com/literature/) describes some important differences between solid-state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid-state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable.

    In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.

    The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.

    No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.

    Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited.

    Throughout this manual, when necessary, we use notes to make you aware of safety considerations.

    WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.

    ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard and recognize the consequences.

    SHOCK HAZARD: Labels may be on or inside the equipment, for example, drive or motor, to alert people that dangerous voltage may be present.

    BURN HAZARD: Labels may be on or inside the equipment, for example, drive or motor, to alert people that surfaces may reach dangerous temperatures.

    IMPORTANT Identifies information that is critical for successful application and understanding of the product.

    Rockwell Automation Publication 1756-IN603C-EN-P - April 2010

    http://literature.rockwellautomation.com/idc/groups/literature/documents/in/sgi-in001_-en-p.pdfhttp://www.rockwellautomation.com/literature/http://www.rockwellautomation.com/literature/

  • ControlLogix EtherNet/IP Module 3

    North American Hazardous Location Approval

    The following information applies when operating this equipment in hazardous locations.

    Informations sur lutilisation de cet quipement en environnements dangereux.

    Products marked CL I, DIV 2, GP A, B, C, D are suitable for use in Class I Division 2 Groups A, B, C, D, Hazardous Locations and nonhazardous locations only. Each product is supplied with markings on the rating nameplate indicating the hazardous location temperature code. When combining products within a system, the most adverse temperature code (lowest T number) may be used to help determine the overall temperature code of the system. Combinations of equipment in your system are subject to investigation by the local Authority Having Jurisdiction at the time of installation.

    Les produits marqus "CL I, DIV 2, GP A, B, C, D" ne conviennent qu' une utilisation en environnements de Classe I Division 2 Groupes A, B, C, D dangereux et non dangereux. Chaque produit est livr avec des marquages sur sa plaque d'identification qui indiquent le code de temprature pour les environnements dangereux. Lorsque plusieurs produits sont combins dans un systme, le code de temprature le plus dfavorable (code de temprature le plus faible) peut tre utilis pour dterminer le code de temprature global du systme. Les combinaisons d'quipements dans le systme sont sujettes inspection par les autorits locales qualifies au moment de l'installation.

    WARNING:Explosion Hazard -Do not disconnect equipment

    unless power has been removed or the area is known to be nonhazardous.

    Do not disconnect connections to this equipment unless power has been removed or the area is known to be nonhazardous. Secure any external connections that mate to this equipment by using screws, sliding latches, threaded connectors, or other means provided with this product.

    Substitution of components may impair suitability for Class I, Division 2.

    If this product contains batteries, they must only be changed in an area known to be nonhazardous.

    AVERTISSEMENT:Risque dExplosion Couper le courant ou s'assurer que

    l'environnement est class non dangereux avant de dbrancher l'quipement.

    Couper le courant ou s'assurer que l'environnement est class non dangereux avant de dbrancher les connecteurs. Fixer tous les connecteurs externes relis cet quipement l'aide de vis, loquets coulissants, connecteurs filets ou autres moyens fournis avec ce produit.

    La substitution de composants peut rendre cet quipement inadapt une utilisation en environnement de Classe I, Division 2.

    S'assurer que l'environnement est class non dangereux avant de changer les piles.

    Rockwell Automation Publication 1756-IN603C-EN-P - April 2010

  • 4 ControlLogix EtherNet/IP Module

    Environment and Enclosure

    ATTENTION: This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications (as defined in IEC 60664-1), at altitudes up to 2000 m (6562 ft) without derating.

    This equipment is considered Group 1, Class A industrial equipment according to IEC/CISPR 11. Without appropriate precautions, there may be difficulties with electromagnetic compatibility in residential and other environments due to conducted and radiated disturbances.

    This equipment is supplied as open-type equipment. It must be mounted within an enclosure that is suitably designed for those specific environmental conditions that will be present and appropriately designed to prevent personal injury resulting from accessibility to live parts. The enclosure must have suitable flame-retardant properties to prevent or minimize the spread of flame, complying with a flame spread rating of 5VA, V2, V1, V0 (or equivalent) if non-metallic. The interior of the enclosure must be accessible only by the use of a tool. Subsequent sections of this publication may contain additional information regarding specific enclosure type ratings that are required to comply with certain product safety certifications.

    In addition to this publication, see:

    Industrial Automation Wiring and Grounding Guidelines, Rockwell Automation publication 1770-4.1, for additional installation requirements.

    NEMA Standard 250 and IEC 60529, as applicable, for explanations of the degrees of protection provided by different types of enclosure.

    Rockwell Automation Publication 1756-IN603C-EN-P - April 2010

    http://literature.rockwellautomation.com/idc/groups/literature/documents/in/1770-in041_-en-p.pdfhttp://literature.rockwellautomation.com/idc/groups/literature/documents/in/1770-in041_-en-p.pdf

  • ControlLogix EtherNet/IP Module 5

    Prevent Electrostatic Discharge

    ATTENTION: This equipment is sensitive to electrostatic discharge, which can cause internal damage and affect normal operation. Follow these guidelines when you handle this equipment:

    Touch a grounded object to discharge potential static. Wear an approved grounding wriststrap. Do not touch connectors or pins on component boards. Do not touch circuit components inside the equipment. Use a static-safe workstation, if available. Store the equipment in appropriate static-safe packaging when

    not in use.

    Rockwell Automation Publication 1756-IN603C-EN-P - April 2010

  • 6 ControlLogix EtherNet/IP Module

    About the ModuleUse this figure to identify the external features of the module.

    Item Description Item Description

    1 Top view 6 Front of module

    2 Backplane connector 7 RJ45 cable connector (on underside of module)

    3 Side view 8 USB port

    4 MAC ID label(on opposite side of circuit board)

    9 Front panel

    5 Bottom view 10 Front view

    31587-M

    LINK NET OK

    10/100 BASE T

    EtherNet/IP TM

    4

    103

    1

    2

    2

    8

    56

    7

    9

    Rockwell Automation Publication 1756-IN603C-EN-P - April 2010

  • ControlLogix EtherNet/IP Module 7

    Before You BeginBefore you install the module, you must install and connect a ControlLogix chassis and power supply.

    To install these products, refer to these publications.

    Item Description Item Description

    1 1756-A4 chassis 2 Power supply

    Chassis Type Chassis Installation

    Power Supply Power Supply Installation

    Series B: 1756-A4, 1756-A7, 1756-A10, 1756-A13

    Publication 1756-IN080

    1756-PA72/C Publication 1756-IN0781756-PB72/B

    1756-PA75/B Publication 1756-IN5961756-PB75/B

    20805-M

    12

    Rockwell Automation Publication 1756-IN603C-EN-P - April 2010

    http://www.literature.rockwellautomation.com/idc/groups/literature/documents/in/1756-in080_-en-p.pdfhttp://www.literature.rockwellautomation.com/idc/groups/literature/documents/in/1756-in078_-en-p.pdfhttp://www.literature.rockwellautomation.com/idc/groups/literature/documents/in/1756-in078_-en-p.pdfhttp://www.literature.rockwellautomation.com/idc/groups/literature/documents/in/1756-in596_-en-p.pdf

  • 8 ControlLogix EtherNet/IP Module

    Determine Module Slot LocationInstall the module in any slot in the ControlLogix chassis. You can install multiple 1756-EN2T modules in the same chassis. The following figure shows chassis slot numbering in a four-slot chassis. Slot 0 is the first slot and is always the leftmost slot in the rack.

    Item Description Item Description

    1 Slot 0 4 Slot 3

    2 Slot 1 5 Chassis

    3 Slot 2 6 Power supply

    6

    1

    23

    4

    5

    20806

    Rockwell Automation Publication 1756-IN603C-EN-P - April 2010

  • ControlLogix EtherNet/IP Module 9

    Set the Network AddressThe module ships with the rotary switches set to 999 and BOOTP enabled. You can set the network Internet Protocol (IP) address three ways.

    Use the rotary switches on the top of the module. Use a BOOTP server or Dynamic Host Configuration Protocol

    (DHCP) server, such as Rockwell Automation BOOTP/DHCP.

    Use the Rockwell Automation RSLinx or RSLogix 5000 software.

    The module reads the rotary switches first to determine if they are set to a valid number for the last portion of the IP address. Valid numbers range from 001254. When the switches are set to a valid number, the modules IP address is 192.168.1.xxx (where xxx represents the number set on the switches). The modules subnet mask is 255.255.255.0 and the gateway address is set to 0.0.0.0. The module does not have a host name assigned, or use any Domain Name System when using the rotary switch settings.

    Item Description

    1 Top of module

    2 Rotary switches

    3 Front of module

    2

    31

    31587

    Rockwell Automation Publication 1756-IN603C-EN-P - April 2010

  • 10 ControlLogix EtherNet/IP Module

    To reset the module to its initial out-of-the-box settings, reset the switches to 888 and cycle power.

    After cycling power with the switches set to 888, remove the module and set the switches to their final value. When you set the rotary switches to a value other than 888, or to the valid IP address values 001254, the software configuration determines the IP address.

    IMPORTANT Do not use the 888 switch setting during normal module operation.

    Determining the Module IP Address

    If BOOTP/DHCP is The module

    Enabled Asks for an address from a BOOTP/DHCP server. The server also assigns other Transport Control Protocol (TCP) parameters.

    Not enabled Uses the IP address (along with other TCP configurable parameters) stored in nonvolatile memory.

    Rockwell Automation Publication 1756-IN603C-EN-P - April 2010

  • ControlLogix EtherNet/IP Module 11

    Install the ModuleFollow this procedure to install the module.

    1. Align the circuit board with top and bottom guides in the chassis.

    2. Slide the module into the chassis.

    Item Description

    1 Circuit board

    1

    Rockwell Automation Publication 1756-IN603C-EN-P - April 2010

  • 12 ControlLogix EtherNet/IP Module

    Make sure that the module backplane connector properly connects to the chassis backplane.

    Connect the Module to the EtherNet/IP Network

    1. Be sure that power is removed or the area is nonhazardous before proceeding.

    2. Attach the RJ45 connector to the Ethernet port on the bottom of the module as shown.

    TIP The module is properly installed when it is flush with the power supply or other installed modules.

    WARNING: If you connect or disconnect the communication cable with power applied to this module or any device on the network, an electrical arc can occur. This could cause an explosion in hazardous location installations.

    Rockwell Automation Publication 1756-IN603C-EN-P - April 2010

  • ControlLogix EtherNet/IP Module 13

    Item Description Item Description

    1 USB port 2 RJ45 connector (underneath module)

    IMPORTANT We recommend connecting the module to the network via a100 MB Ethernet switch, which will reduce collisions and lost packets and increase network bandwidth. For detailed EtherNet/IP connection information, see the following publications:

    EtherNet/IP Performance and Application Guide, publication ENET-AP001

    EtherNet/IP Media Planning and Installation Guide, publication ENET-IN001

    1

    2

    Rockwell Automation Publication 1756-IN603C-EN-P - April 2010

    http://literature.rockwellautomation.com/idc/groups/literature/documents/ap/enet-ap001_-en-p.pdfhttp://www.literature.rockwellautomation.com/idc/groups/literature/documents/in/enet-in001_-en-p.pdf

  • 14 ControlLogix EtherNet/IP Module

    Program the Module via the USB Port

    Be sure that power is removed or the area is nonhazardous before proceeding.

    The module has a USB device port that uses a series B receptacle. To use the USB port, you must have RSLinx software, version 2.51 or later installed on your computer. Use a USB cable to connect your computer to the USB port. The connection lets you download programs to controllers and to configure Ethernet modules directly from your computer.

    WARNING: The USB port is intended for temporary local programming purposes only and is not intended for permanent connection. If you connect or disconnect the USB cable with power applied to this module or any device on the USB network, an electrical arc can occur. This could cause an explosion in hazardous location installations.

    Be sure that power is removed or the area is nonhazardous before proceeding.

    A Samtec Inc. RSP-119350 USB cable is required to maintain hazardous location certifications.

    ATTENTION:

    The USB port is designed for a temporary connection only. The USB cable is not to exceed 3.0 m (9.84 ft) and must not

    contain hubs. To maintain product certification integrity, you must use SAMTEC

    cable, part number RSP-119350.

    Rockwell Automation Publication 1756-IN603C-EN-P - April 2010

  • ControlLogix EtherNet/IP Module 15

    Configure the ModuleFollow these steps to configure the module.

    1. In RSLogix 5000 software, from the Controller Organizer, select New Module.

    2. Select the module you want to configure.

    For more configuration information, refer to the EtherNet/IP Modules in Logix5000 Control Systems User Manual, publication ENET-UM001. View or download this publication at http://www.rockwellautomation.com/literature.

    Apply Chassis Power

    31593-M

    Rockwell Automation Publication 1756-IN603C-EN-P - April 2010

    http://www.literature.rockwellautomation.com/idc/groups/literature/documents/um/enet-um001_-en-p.pdfhttp://literature.rockwellautomation.com

  • 16 ControlLogix EtherNet/IP Module

    Check Power Supply and Module StatusCheck the status indicators and alphanumeric display to determine whether the power supply and module are operating properly.

    Item Description Item Description

    1 OK indicator is red during self-test, then green

    3 NET status indicator

    2 LINK status indicator 4 Power supply indicator is green

    31281-M

    LINK NET OK

    123

    4

    Rockwell Automation Publication 1756-IN603C-EN-P - April 2010

  • ControlLogix EtherNet/IP Module 17

    The alphanumeric display should cycle through these states:

    TEST PASS OK REV x.x

    where x.x is the modules firmware revision.

    The display then alternates between OK and the modules EtherNet/IP address.

    Install or Remove the Module Under PowerYou can install or remove this module while chassis power is applied.

    1. Push on upper and lower module tabs to disengage them.

    WARNING: When you insert or remove the module while backplane power is on, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding. Repeated electrical arcing causes excessive wear to contacts on both the module and its mating connector. Worn contacts may create electrical resistance that can affect module operation.

    Rockwell Automation Publication 1756-IN603C-EN-P - April 2010

  • 18 ControlLogix EtherNet/IP Module

    2. Slide the module out of the chassis.

    IMPORTANT If you want to replace an existing module with an identical one, and you want to resume identical system operation, you must install the new module in the same slot.

    Rockwell Automation Publication 1756-IN603C-EN-P - April 2010

  • ControlLogix EtherNet/IP Module 19

    Interpret the Status IndicatorsIf the alphanumeric display and status indicators do not sequence through the expected states, refer to these tables. The three bi-color (red/green) status indicators on the module provide diagnostic information about the module and its connections to the network.

    Item Description Item Description

    1 OK indicator is red during self-test, then green

    3 LINK status indicator

    2 NET status indicator 4 Power supply indicator is green

    31281-M

    LINK NET OK

    123

    4

    Rockwell Automation Publication 1756-IN603C-EN-P - April 2010

  • 20 ControlLogix EtherNet/IP Module

    Status Indicators

    Indicator Status Description

    NET Off The module is not powered. Verify that there is chassis power and that the module is completely inserted into the chassis and backplane.The module does not have a valid IP address. Make sure the module has been configured with a valid IP address.

    Flashing green The module has an IP address, but has no established connections.

    Green The module has an IP address and at least one established connection.

    Red The module is attempting to use an IP address already in use on the network. Assign a unique IP address to the module.

    Link Off The module is not ready to communicate. Verify that the module has power.

    Green The module is ready to communicate.

    Flashing green The module is communicating over the network.

    Rockwell Automation Publication 1756-IN603C-EN-P - April 2010

  • ControlLogix EtherNet/IP Module 21

    OK Off Verify that the module has 24V DC chassis power and that the module is completely inserted into chassis and backplane.

    Flashing green The module is not configured.

    Green The module is operating correctly.

    Flashing red The module detected a recoverable fault. A configuration error may have caused the fault. Check the module configuration. If necessary, reconfigure the module.

    Red The module detected an unrecoverable fault. Cycle power to the module. If this does not clear the fault, replace the module.

    Red and alphanumeric display scrolls 'Image Update Needed'

    Update the firmware image. Once the image is updated, cycle power. If this does not clear the fault, replace the module.

    Flashing red and green

    The module is performing a power-up self-test.

    Status Indicators

    Indicator Status Description

    Rockwell Automation Publication 1756-IN603C-EN-P - April 2010

  • 22 ControlLogix EtherNet/IP Module

    Specifications

    Technical Specifications - 1756-EN2T

    Attribute 1756-EN2T

    Enclosure type rating None (open-style)

    Module location Any slot in the ControlLogix chassis

    Backplane current 1 A at 5.1V DC

    Backplane current 3 mA at 24V DC

    Isolation voltage 30V (continuous), Basic Insulation Type, Ethernet to backplaneNo isolation between USB and backplaneType tested at 510V AC for 60 s

    Power dissipation, max. 5.1 W

    Wire size Ethernet connections:RJ45 connector according to IEC 60603-7, 2 or 4 pair Category 5e minimum cable according to TIA 568-B.1 or Category 5 cable according to ISO/IEC 24702

    Wiring category 2 - on Ethernet ports(1)

    (1) Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

    Temperature, surrounding air

    60 C (140 F)

    North American temp code Series A: T5Series B and C: T4A

    Recommended USB cable for USB port

    Samtec cable, PN RSP-119350

    USB port USB 1.1USB deviceUSB series B receptacle

    Rockwell Automation Publication 1756-IN603C-EN-P - April 2010

    http://www.literature.rockwellautomation.com/idc/groups/literature/documents/in/1770-in041_-en-p.pdf

  • ControlLogix EtherNet/IP Module 23

    Environmental Specifications - 1756-EN2T

    Attribute 1756-EN2TTemperature, operating IEC 60068-2-1 (Test Ad, Operating

    Cold) IEC 60068-2-2 (Test Bd, Operating Dry

    Heat) IEC 60068-2-14 (Test Nb, Operating

    Thermal Shock)

    060 C (32140 F)

    Temperature, nonoperating EC 60068-2-1 (Test Ab, Unpackaged

    Nonoperating Cold) IEC 60068-2-2 (Test Bb, Unpackaged

    Nonoperating Dry Heat) IEC 60068-2-14 (Test Na, Unpackaged

    Nonoperating Thermal Shock)

    4085 C (-40185 F)

    Relative humidity IEC 60068-2-30 (Test Db, Unpackaged

    Damp Heat)

    595% noncondensing

    Vibration IEC 60068-2-6 (Test Fc, Operating)

    2 g @ 10500 Hz

    Shock, operatingIEC 60068-2-27 (Test Ea, Unpackaged Shock)

    30 g

    Shock, nonoperatingIEC 60068-2-27 (Test Ea, Unpackaged Shock)

    50 g

    Emissions CISPR 11

    Group 1, Class A

    Immunity, ESD IEC 61000-4-2

    6 kV contact discharges8 kV air discharges

    Immunity, radiated RF IEC 61000-4-3

    10V/m with 1 kHz sine-wave 80%AM from 802000 MHz10V/m with 200 Hz 50% Pulse 100%AM at 900 MHz10V/m with 200 Hz 50% Pulse 100%AM at 1890 MHz3V/m with 1 kHz sine-wave 80% AM from 20002700 MHz

    Immunity, EFT/B IEC 61000-4-4

    2 kV at 5 kHz on Ethernet port

    Immunity, surge transient IEC 61000-4-5

    2 kV line-earth(CM) on Ethernet port

    Rockwell Automation Publication 1756-IN603C-EN-P - April 2010

  • 24 ControlLogix EtherNet/IP Module

    Immunity, conducted RF IEC 61000-4-6

    10V rms with 1 kHz sine-wave 80%AM from 150 kHz80 MHz

    Certifications - 1756-EN2T

    Certifications(1)

    (when product is marked)

    1756-EN2T

    c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.

    UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810.

    CSA CSA Certified Process Control Equipment. See CSA File LR54689C.

    CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.

    FM FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations

    CE European Union 2004/108/EC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

    C-Tick Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions

    EtherNet/IP ODVA conformance tested to EtherNet/IP specifications

    (1) See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

    Environmental Specifications - 1756-EN2T

    Attribute 1756-EN2T

    Rockwell Automation Publication 1756-IN603C-EN-P - April 2010

    http://www.ab.com

  • ControlLogix EtherNet/IP Module 25

    Additional ResourcesThese documents contain additional information concerning related Rockwell Automation products.

    You can view or download publications at http://www.rockwellautomation.com/literature. To order paper copies of technical documentation, contact your local Rockwell Automation distributor or sales representative.

    Resource Description

    Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1

    Provides general guidelines for installing a Rockwell Automation industrial system

    EtherNet/IP Modules in Logix5000 Control Systems User Manual, publication ENET-UM001

    Contains information about how to use EtherNet/IP modules with various Logix5000 controllers

    EtherNet/IP Performance and Application Guide, publication ENET-AP001

    Provides detailed EtherNet/IP connection information

    EtherNet/IP Media Planning and Installation Guide, publication ENET-IN001

    Provides detailed EtherNet/IP connection information

    ControlLogix Chassis Installation Instructions, publication 1756-IN080

    Contains information about how to install a ControlLogix chassis

    ControlLogix Power Supplies Installation Instructions, publication 1756-IN078

    Contains information about how to install ControlLogix power supplies

    ControlLogix Power Supplies Installation Instructions, publication 1756-IN596

    Contains information about how to install ControlLogix power supplies

    Open DeviceNet Vendor Association (ODVA) website, http://www.odva.org

    Provides information about implementing EtherNet/IP technology

    Rockwell Automation Publication 1756-IN603C-EN-P - April 2010

    http://www.literature.rockwellautomation.com/idc/groups/literature/documents/in/1756-in080_-en-p.pdfhttp://www.literature.rockwellautomation.com/idc/groups/literature/documents/in/1756-in078_-en-p.pdfhttp://www.literature.rockwellautomation.com/idc/groups/literature/documents/in/1756-in078_-en-p.pdfhttp://www.literature.rockwellautomation.com/idc/groups/literature/documents/in/1756-in596_-en-p.pdfhttp://www.literature.rockwellautomation.com/idc/groups/literature/documents/in/1770-in041_-en-p.pdfhttp://www.literature.rockwellautomation.com/idc/groups/literature/documents/in/1770-in041_-en-p.pdfhttp://www.literature.rockwellautomation.com/idc/groups/literature/documents/um/enet-um001_-en-p.pdfhttp://literature.rockwellautomation.com/idc/groups/literature/documents/ap/enet-ap001_-en-p.pdfhttp://www.literature.rockwellautomation.com/idc/groups/literature/documents/in/enet-in001_-en-p.pdfhttp://www.odva.orghttp://literature.rockwellautomation.com

  • 26 ControlLogix EtherNet/IP Module

    Notes:

    Rockwell Automation Publication 1756-IN603C-EN-P - April 2010

  • ControlLogix EtherNet/IP Module 27

    Notes:

    Rockwell Automation Publication 1756-IN603C-EN-P - April 2010

  • Rockwell Automation Support

    Rockwell Otomasyon Ticaret A.., Kar Plaza Merkezi E Blok Kat:6 34752 erenky, stanbul, Tel: +90 (216) 5698400

    Rockwell Automation provides technical information on the Web to assist you in using its products. At http://www.rockwellautomation.com/support/, you can find technical manuals, a knowledge base of FAQs, technical and application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools.

    For an additional level of technical phone support for installation, configuration, and troubleshooting, we offer TechConnect support programs. For more information, contact your local distributor or Rockwell Automation representative, or visit http://www.rockwellautomation.com/support/.

    Installation AssistanceIf you experience a problem within the first 24 hours of installation, please review the information that's contained in this manual. You can also contact a special Customer Support number for initial help in getting your product up and running.

    New Product Satisfaction ReturnRockwell Automation tests all of its products to ensure that they are fully operational when shipped from the manufacturing facility. However, if your product is not functioning and needs to be returned, follow these procedures.

    Documentation Feedback Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this document, complete this form, publication RA-DU002, available at http://www.rockwellautomation.com/literature.

    United States or Canada 1.440.646.3434

    Outside United States or Canada

    Use the Worldwide Locator at http://www.rockwellautomation.com/support/americas/phone_en.html, or contact your local Rockwell Automation representative.

    United StatesContact your distributor. You must provide a Customer Support case number (call the phone number above to obtain one) to your distributor to complete the return process.

    Outside United States Please contact your local Rockwell Automation representative for the return procedure.

    Publication 1756-IN603C-EN-P - April 2010 PN-74517

    Allen-Bradley, ControlLogix, Rockwell Software, Rockwell Automation, and TechConnect are trademarks of Rockwell Automation, Inc.

    Trademarks not belonging to Rockwell Automation are property of their respective companies.

    Supersedes Publication 1756-IN603B-EN-P - January 2009 Copyright 2010 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.

    http://www.rockwellautomation.com/support/http://www.rockwellautomation.com/support/http://www.rockwellautomation.com/support/http://www.rockwellautomation.com/support/http://www.rockwellautomation.com/locations/http://www.rockwellautomation.com/support/americas/phone_en.html

    1756-IN603C-EN-P, ControlLogix EtherNet/IP Module Installation InstructionsAbout This PublicationImportant User InformationNorth American Hazardous Location ApprovalEnvironment and EnclosurePrevent Electrostatic DischargeAbout the ModuleBefore You BeginDetermine Module Slot LocationSet the Network AddressInstall the ModuleConnect the Module to the EtherNet/IP NetworkProgram the Module via the USB PortConfigure the ModuleApply Chassis PowerCheck Power Supply and Module StatusInstall or Remove the Module Under PowerInterpret the Status IndicatorsSpecificationsAdditional ResourcesBack Cover

    /ColorImageDict > /JPEG2000ColorACSImageDict > /JPEG2000ColorImageDict > /AntiAliasGrayImages false /CropGrayImages true /GrayImageMinResolution 300 /GrayImageMinResolutionPolicy /OK /DownsampleGrayImages true /GrayImageDownsampleType /Average /GrayImageResolution 300 /GrayImageDepth 8 /GrayImageMinDownsampleDepth 2 /GrayImageDownsampleThreshold 2.00000 /EncodeGrayImages true /GrayImageFilter /FlateEncode /AutoFilterGrayImages false /GrayImageAutoFilterStrategy /JPEG /GrayACSImageDict > /GrayImageDict > /JPEG2000GrayACSImageDict > /JPEG2000GrayImageDict > /AntiAliasMonoImages false /CropMonoImages true /MonoImageMinResolution 1200 /MonoImageMinResolutionPolicy /OK /DownsampleMonoImages true /MonoImageDownsampleType /Average /MonoImageResolution 1200 /MonoImageDepth -1 /MonoImageDownsampleThreshold 1.50000 /EncodeMonoImages true /MonoImageFilter /CCITTFaxEncode /MonoImageDict > /AllowPSXObjects false /CheckCompliance [ /None ] /PDFX1aCheck false /PDFX3Check false /PDFXCompliantPDFOnly false /PDFXNoTrimBoxError true /PDFXTrimBoxToMediaBoxOffset [ 0.00000 0.00000 0.00000 0.00000 ] /PDFXSetBleedBoxToMediaBox true /PDFXBleedBoxToTrimBoxOffset [ 0.00000 0.00000 0.00000 0.00000 ] /PDFXOutputIntentProfile (None) /PDFXOutputConditionIdentifier () /PDFXOutputCondition () /PDFXRegistryName () /PDFXTrapped /False

    /Description > /Namespace [ (Adobe) (Common) (1.0) ] /OtherNamespaces [ > /FormElements false /GenerateStructure true /IncludeBookmarks false /IncludeHyperlinks false /IncludeInteractive false /IncludeLayers false /IncludeProfiles true /MultimediaHandling /UseObjectSettings /Namespace [ (Adobe) (CreativeSuite) (2.0) ] /PDFXOutputIntentProfileSelector /NA /PreserveEditing true /UntaggedCMYKHandling /LeaveUntagged /UntaggedRGBHandling /LeaveUntagged /UseDocumentBleed false >> ]>> setdistillerparams> setpagedevice

    Introduction_Catagory Types

    This tab summarizes Rockwell Automation Global Sales and Marketing preferred printing standards. It also provides guidance on whether a publication should be released as JIT (print on demand) or if it requires an RFQ for offset printing.Find your publication type in the first section below. Use the assigned Printing Category information to determine the standard print specifications for that document type. The Printing Categories are defined below the Publication Type section. Note there may be slightly different print specifications for the categories, depending on the region (EMEA or Americas).For more information on Global Sales and Marketing Printing Standards, see publication RA-CO004 in DocMan.

    Publication Type and Print Category

    Publication TypeOff Set Print Category Spec. (See table below)JIT Spec. (See table below)DescriptionOrder MinOrder MaxLife Cycle Usage / Release Option

    ADNA - PuttmanNAAdvertisement Reprint ColourNANAPresale / Internal

    APA3D2Application Solution or Customer Success Story5100Presale / External

    ARNANAArticle/Editorial/BylineNANAPresale / Internal

    /News Release (press releases should not be checked into DocMan or printed)

    ATB3, B4D5Application Techniques5100Presale / External

    BRA2 Primary, A1NABrochures5100Presale / External

    CAC2 Primary, C1NACatalogue150Presale / External

    CGNANACatalogue Guide150Presale / External

    CLNANACollection550Presale / External

    COA5, A6, A9D5Company Confidential InformationNANANA / Confidential

    CPE-onlyE-only, D5Competitive Information550NA / Confidential

    DCE-onlyE-onlyDiscount SchedulesNANAPresale / Internal

    DIA1, A3NADirect Mail5100Presale / Internal

    DMNANAProduct Demo550Presale / Internal

    DSB3D5Dimensions Sheet15Post / External

    DUB3D5Document Update15Post / External

    GRB2D6Getting Results15Post / External

    INB3D5Installation instructions15Post / External

    LMNANALaunch KitMaterials550Presale / Internal

    PCB3D5Packaging Contents

    PLE-only Primary, B3E-onlyPrice List550Presale / Internal

    PMB2D6Programming Manual15Post / External

    PPA3D1Product Profile NOTE: Application Solutions are to be assigned the AP pub type.5100Presale / External

    QRB2 Primary, B3, B5D5, D6Quick Reference15Post / External

    QSB2 Primary, B3, B5D5, D6Quick Start15Post / External

    RMB2D5, D6Reference Manual15Post / External

    RNB3D5Release Notes15Post / External

    SGB1 Primary, B4D5, D6Selection Guide Colour550Presale / External

    SGB2D5, D6Selection Guide B/W550Presale / External

    SPA1, A2, A3, A4NAService ProfileSales Promotion NOTE: Service profiles are to be assigned the PP pub type.5100Presale / Internal

    SRB2, B3D5, D6Specification Rating Sheet5100Presale / External

    TDB2 Primary B3, B4, B5D5, D6Technical Data550Presale / External

    TGB2, B3D6Troubleshooting Guide15Post / External

    UMB2 Primary, B4D6User Manual B/W15Post / External

    WDB3D5Wiring Diagrams / Dwgs15Post / Internal

    WPB3 Primary, B5D5White Paper550Presale / External

    Pre-sale / MarketingAll paper in this category is White Brightness, 85% or better. Opacity 87% or better

    CategoryColor OptionsAP, EMEA Paper RequirementsCanada, LA, US Paper Requirements

    A14 color170gsm 2pp100# gloss cover, 100# gloss text

    A24 color170gsm, folded, 4pp100# gloss cover, 80# gloss text

    A34 colorCover 170gsm with Body 120gsm, > 4pp80# gloss cover, 80# gloss text

    A42 color80# gloss cover, 80# gloss text

    170gsm Silk 120gsm Silk

    A52 color80# gloss cover, 80# matt sheet text

    170gsm Silk 120gsm Silk

    A61 color170gsm Silk 120gsm Silk80# gloss cover, 80# matt sheet text

    A74 color cover10 Point Cover C2S

    2 color textCategory being deleted50# matte sheet text

    Selection Guide

    A84 color coverCategory being deleted50# matte sheet text, self cover

    2 color text

    Selection Guide

    A92 color100gsm bond50# matte sheet text, self cover

    Selection Guide

    Post Sale / Technical Communication

    CategoryColor OptionsAP, EMEA Paper RequirementsCanada, LA, US Paper Requirements

    B14 color cover270gsm Gloss 100gsm bond10 Point Cover C2S

    2 color text50# matte sheet text

    B21 color60# Cover

    160gsm Colortech & 100gsm Bond50# matte sheet text

    B31 color50# matte sheet text, self cover

    100gsm bond

    B42 color60# Cover

    160gsm Colortech & 100gsm Bond50# matte sheet text

    B52 color50# matte sheet text, self cover

    100gsm bond

    Catalogs

    CategoryColor OptionsAP, EMEA Paper RequirementsCanada, LA, US Paper Requirements

    C14 color cover270gsm Gloss 90gsm silk10 Point Cover C2S

    4 color text45# Coated Sheet

    C24 color cover270gsm Gloss 80gsm silk10 Point Cover C2S

    2 color text32#-33# Coated Sheet

    JIT / POD

    CategoryColor OptionsAP, EMEA Paper RequirementsCanada, LA, US Paper Requirements

    D14 color170gsm white silk80# gloss cover, coated 2 sides

    D24 color120gsm white silk80# gloss text, coated 2 sides, self cover

    D34 colorCover 170gsm with Body 120gsm80# gloss cover, 80# gloss text coated 2 sides

    D41 color160gsm tab90# index

    D51 color80gsm bond20# bond, self cover

    D61 colorCover 160gsm tab with Body 80gsm bond90# index, 20# bond

    D72 color160gsm tab90# index

    D82 color80gsm bond20# bond, self cover

    D92 colorCover 160gsm tab with Body 80gsm bond90# index, 20# bond

    D10Combination: 4 color cover, with 2 color bodyCover 160gsm with Body 80gsm90# index, 20# bond

    Print Spec Sheet

    JIT Printing SpecificationsRA-QR005E-EN-P - 5/19/2009

    Printing SpecificationYOUR DATA HEREInstructionsNO

    (required) Category:D5Select Print Category A,B,C or D from category list, on "Introduction_Catagory Types" tab11 x 17LOOSE -Loose LeafYESPre-sale / MarketingTOP

    (required) Finished Trim Size Width:4.75 x 7 (slightly smaller half-size)8.5 x 11PERFECT - Perfect BoundA1LEFT

    (required) Publication Number :1756-IN606B-EN-PSample: 2030-SP001B-EN-P3 x 5SADDLE - Saddle StitchA2RIGHTCORNER

    Use Legacy NumberNOYES or NO18 x 24 PosterPLASTCOIL - Plastic Coil (Coil Bound)A4BOTTOMSIDE

    Legacy Number if applicable:Sample Legacy Number: 0160-5.3324 x 36 PosterSTAPLED1 -1 positionA3

    Publication Title:ControlLogix EtherNet/IP Module Installation InstructionsSample: ElectroGuard Selling Brief36 x 24 PosterSTAPLED1B - bottom 1 positionA5

    (required) Business Group:Marketing CommercialAs entered in DocMan4 x 6STAPLED2 - 2 positionsA6

    (required) Cost Center:CMKMKE CM Integrated Arch - 19021As entered in DocMan - enter number only, no description. Example - 19021CMKMKE CM Integrated Arch - 19021CMKMKE Market Access Program - 191054.75 x 7 (slightly smaller half-size)THERMAL - Thermal bound (Tape bound)A7

    Binding/Stitching:SADDLE - Saddle StitchReview key on right...Saddle-Stitch Items All page quantities must be divisible by 4.20 sheets max. on 20# (text and cover); 20 sheets = 80-page pub16 sheets max. on 20# (text) and 90# (cover); 16 sheets = 64-page pub

    Perfect Bound Items475 sheets max. on 20# no cover; 475 sheets = 950-page pub470 sheets max. w/cover / 90# index unless indicated otherwise); 470 sheets = 940-page pub

    Coil Bound Items400 sheets max. of 20# (if adding cover deduct equivalent number of pages to equal cover thickness) (90# index unless indicated otherwise); 400 sheets = 800-page pub

    Tape Bound Items125 sheets max. on 20# no cover; 125 sheets = 250-page pub120 sheets max. w/cover (90# index unless indicated otherwise); 120 sheets = 240-page pub

    Double Wire Bound Items250 sheets max. on 20# (if adding cover deduct equivalent number of pages to equal cover thickness) (90# index unless indicated otherwise); 250 sheets = 500-page pub4.75 x 7.75THERMALO - Thermal Bound (Tape bound - offline)A8

    (required) Page Count of Publication:28Total page count including cover5.5 x 8.5 (half-size)Wire O - Double Wire Bound (offline)A9

    Paper Stock Color:White is assumed. For color options contact your vendor.6 x 4Post Sale / Technical Communication

    Number of Tabs Needed:5 tab in stock at RR Donnelley7.385 x 9 (RSI Std)B1

    Stitching Location:Blank, Corner or Side8.25 x 10.875B2

    Drill Hole YES/NOYESAll drilled publications use the 5-hole standard, 5/16 inch-size hole and a minimum of inch from the inner page border.8.25 x 11 (RA product profile std)B3

    Glue Location on Pad:Glue location on pads8.375 x 10.875B4

    Number of Pages per Pad:Average sheets of paper.. 25, 50 75,100 Max9 x 12 (Folder)B5

    Ink ColorOne color assumes BLACK / 4 color assume CMYK / Indicate PMS number hereA4 (8 x 11 ) (210 x 297 mm)Catalogs

    Used in Manufacturing:YESA5 (5.83 x 8.26) (148 x 210 mm)C1

    Comments:1756-EN2TC2

    Part Number:PN--74517JIT / POD

    D1

    D2

    D3

    D4

    D5

    D6

    D7

    D8

    D9