Controlled Power CompanyControlled Power CompanyControlled Power CompanyControlled Power CompanyProduct Overview
Factory Representative: Integrated Power Systems
Ultra-K Energy Efficient, Shielded, K-Rated, Isolation Transformer
Power Purifier Constant Voltage Power Conditioning System
Power Processor 3% Line Voltage Regulator (Tap Switcher)
LT, MD, HV Ø1 Ferro-resonant UPS
UltraUPS Ø1 Double-Conversion UPS
EL Series Centralized Emergency Lighting Inverters
PDU, Rectifiers Other Product Lines
CPC SOLUTION-ORIENTED PRODUCTS
Ultra-K Shielded Isolation Transformers
NEMA TP-1
Ultra-K Shielded Isolation Transformers
Where you might use them?
• Anyplace that has electronic loads like…
• Electronic ballast lighting
• Computer / Communications systems
• Variable Frequency Drives
• Other mission critical electronic loads
WHAT WHAT ULTRA-KULTRA-K ISOLATION ISOLATION PROVIDESPROVIDES
• Excellent load voltage regulation, during load step or high harmonic conditions.
• Significant Common Mode noise reduction (like static on audio systems, distortion on video screens or otherwise inexplicable error messages in IT systems). In fact we offer you a choice of 1 million : 1 (2 shield), or 10 million : 1 (3 shield) in CMN attenuation.
• Superior harmonic handling capability (harmonics cause systems to run hot, fool generators and building logic systems, plus numerous other physical and IT system issues).
• Creates new Neutral and provides new source when electrical grounding is a problem.
K-FACTOR
As a result of high neutral currents on harmonic rich circuits:
• EEddy currents (the circulating current at the surface of a wire) prevents total current penetration of cylindrical wire.
• AAs the frequency increases, the penetration decreases, using less cross sectional area of the wire. The wire heats up as a result.
• AApplied to a transformer, the K-factor expresses the ability of the transformer to handle harmonic currents without overheating.
Conductor Cross-SectionSkin Effect of High Frequency
Currents = Overheating
Why buy an Ultra-K?
• Noise Reduction & Line Conditioning.• K-Rated for Harmonic Handling Capability Provides
power conditioning, K-rating, NEMA TP-1 and Energy Star® compliance.
• Superior Harmonic Handling & Load Changes without overheating or over-sizing.
• Highest Grade of Construction Materials.• High Efficiency – (fka EPA Energy Star®)
& NEMA TP1 listed.• Low Heat Rise – 115o C.• Low Output Impedance.
WHAT IF THE UTILITY VOLTAGE IS SAGGING OR SURGING?
Isolation and good grounding alone, may not be enough…
Controlled Power offers a variety of products which both isolate and regulate the voltage even when utility power fluctuates beyond acceptable limits.
Single Phase (Series 800 Power Purifier) from 250 VA up to 25 kVA
Three Phase (Series 700 Power Processor) from 15 kVA to 500 kVA
POWER PURIFIERA Power Conditioner That Solves 99.5% of All Power Problems!
- SERIES 800 PI -
INDUSTRIAL APPLICATIONS
• Output distribution from 250 va up to 25 Kva.
• Rugged cabinet with convection cooling.
• Hardwired in / out
• Power factor near unity
• NEMA2 & NEMA3R Enclosures
• Can Parallel For Higher kVA’s
• Output distribution from 250 va up to 15 Kva.
• Attractive enclosure with cooling fans.
• Input line cord included on units up to 3.5 Kva.
• Rated at a .7 power factor
• NEMA 1 Enclosure
- SERIES 800 A -
COMMERCIAL APPLICATIONS
WHERE YOU MIGHT USE THE WHERE YOU MIGHT USE THE SERIES 800?SERIES 800?
• Computerized Industrial Control Systems• Process-Numerical Control• Audio-Visual Security Systems• Data Acquisition Systems (SCADA)• Security and/or Fire Alarm Systems• Programmable Logic Controllers (PLC’S)• Automated Systems / Robotics• Test and Measurement Instrumentation• All Sensitive Electronic Equipment• Systems where you need voltage regulation and a clean
signal but don’t necessarily need batteries.
WHAT THE SERIES 800 WHAT THE SERIES 800 PROVIDESPROVIDES
• Same type of performance as 2 shield Ultra K Transformer, PLUS…
• Load Voltage Regulation (+/- 2 to 5%) when utility sags as much as 45% or surges as much as 15% from nominal
• Optional Plug n Play or Hardwired connectivity
• Up to 1 cycle of ridethrough at full load
WHAT THE SERIES 800 WHAT THE SERIES 800 PROVIDESPROVIDES
• Electrical Isolation (126 db CMN)• New Neutral and Source of Power• K30 Harmonic Handling performance• Power Factor Correction• Load Voltage Regulation (+/- 2 to 5%)• Ridethrough (short duration outage
protection)• (OPTIONAL medical grade listing)
WHAT IF THE UTILITY VOLTAGE IS SAGGING OR SURGING?
Isolation and good Grounding alone, may not be enough, specifically when utility power fluctuates beyond high or low voltage acceptable limits.
Series 800 Power Purifier provides:
Voltage correction via Variable Range Regulation
Load Level
Input Voltage from Nominal
Output Voltage
Regulation
25% +10 / -45% (i.e. nominal 120v swings 132v to 66v)
+/- 3% (aka 120v
stays within 123v to 116v)
50% +10 / -40% +/- 3%
75% +10 / -35% +/- 3%
100% +10 / -20% +/- 2%
POWER PURIFIER POWER PURIFIER PERFORMANCEPERFORMANCE
Power Output 1 phase, 100% duty, kVA & kW for linear & non-linear loads
Line Voltage Regulation @100% load, 2%Vout for +10% to -20% Vin
Immunity to Distortion @40% THD Vin, 5% THD Vout
Load Regulation 2.5% for 0% to 100% load
Voltage Recovery 2 cycles to 95% 3 cycles to 100%
K-Factor K30 rated
Power Factor Correction Input pf 0.95 typical
Harmonic Attenuation -23dB for load reflected harmonics
Galvanic Isolation NEC 250 5d .001pf
Surge Protection 3000:1 ANSI/IEEE C62.42-45
CMN Attenuation 140dB
TMN Attenuation 120dB
Ride Through 1 cycle (16.6ms)
Reliability 200,000 hr. MTBF
Efficiency 92% Typical
Why buy a Power Purifier?• Noise Reduction & Line Conditioning = More Reliable
Operation of Mission Critical Systems.• K-Rated for Harmonic Handling Capability Provides power
conditioning, K-rating = Power Circuits Operate More Efficiently.
• Superior Harmonic Handling without overheating or over-sizing = Better Size Matching to Load Requirements.
• Highest Grade of Construction Materials = More Efficient Operation.
• Voltage Regulation = Better System Performance.• Low Heat Rise Design = Cooler Operation.• Up to 1 Cycle of Outage Ridethrough without using
batteries = Lower Protection Cost.
• 15 To 500 kVA (Three Phase)
• +10% to -20% Input Voltage Range w/ Output Regulation of +/-3%
• ½ Cycle Response
• Input Circuit Breaker
• Triple-Shield 140dB Attenuation
• Low Output Impedance
The “Power Processor” The “Power Processor” Series 700Series 700
Power Line ConditionerPower Line Conditioner
• Brownouts or Over-Voltage
• Fluctuating Voltage
• Noise, Transients, or Impulses
Power Line Problems Solved Power Line Problems Solved by The Power Processorby The Power Processor
POWER PROCESSOR POWER PROCESSOR PERFORMANCEPERFORMANCE
• +10%, -40% Input Voltage Range Capability
• <2 – 3% Load Voltage Regulation
• Small Physical Size vs UPS
• Highly Efficient (Typically ~ 97%)
• Harmonic Immune Control Circuitry
• < 1 Cycle Correction For Over/Under Input Voltages
WHAT THE SERIES 700 WHAT THE SERIES 700 PROVIDESPROVIDES
• Same type of performance as 3 shield Ultra K Transformer, PLUS…
• Load Voltage Regulation (+/- 2 to 3%) when utility sags as much as 20% or surges as much as 15% from nominal (extended input range available as option)
• Optional Circuit Breaker or Hardwired connectivity
• Less than 1 cycle response time
WHERE YOU MIGHT USE THE WHERE YOU MIGHT USE THE SERIES 700 Power Processor?SERIES 700 Power Processor?
• Computerized Industrial Control Systems (like VFD’s)• Automated Systems / Robotics• Test and Measurement Instrumentation• Large Printing Press Systems• Water Treatment & Pumping Stations• Conveyor Control Systems• All Sensitive Electronic Equipment• Systems where you need voltage regulation and a clean
signal but don’t necessarily need batteries.• Bypass Circuits for UPS Systems
Why buy a Power Processor?
• Noise Reduction & Line Conditioning = More Reliable Operation of Mission Critical Systems.
• K-Rated for Harmonic Handling Capability Provides power conditioning, K-rating = Power Circuits Operate More Efficiently.
• Superior Harmonic Handling without overheating or over-sizing = Better Size Matching to Load Requirements.
• Highest Grade of Construction Materials = More Efficient Operation.
• Voltage Regulation = Better System Performance.• Low Heat Rise Design = Cooler Operation.• Smaller Size than Comparable UPS = Lower Protection
System Cost.
The UPS
Family of Products
The Size of Our FamilyThe Size of Our Family
• LT - 700VA to 2.1KVA
• LTR - 700VA to 2.1KVA
• LTN – 700VA to 2.1KVA
Vin x Vout120 120 120/208 120/240
208 120 120/208 120/240
240 120 120/208 120/240
The Size of Our FamilyThe Size of Our Family
MD - 3.1KVA to 7.5KVAVin x Vout120 120/208 120/240208 120/208 120/240240 120/208 120/240
HV - 7.5KVA to 25KVAVin x Vout120 120/208 120/240208 120/208 120/240240 120/208 120/240
3 & 5 kVA Single Phase
• On-Line
• Double Conversion with Static Bypass
• Modular
• Stack or Rack
• Versatile Distribution System
UltraUPS Computing
Telecommunications
Industrial
Automation
Instrumentation
Testing
Emergency Lighting
Medical
WHAT YOU GET FROM THE CPC UPS
• Isolation and Regulation all the time!• N+1 Battery Redundancy • Bypass Switch Selections• ± 1.5% Voltage Regulation• +15% to -45% Input Voltage Range• Automatic Battery Extension Cutoff• Extended Battery Life via Enhanced Charging
• 0.99 Input Power Factor• Input Current THD < 5%• Rapid Recharge• Connection Configurability
CONTROLLED POWER COMPANYCONTROLLED POWER COMPANYCONTROLLED POWER COMPANYCONTROLLED POWER COMPANY
1
Emergency Lighting Inverters
CONTROLLED POWER COMPANYCONTROLLED POWER COMPANYCONTROLLED POWER COMPANYCONTROLLED POWER COMPANY
Emergency Lighting Inverters
3 Critical Links for Life Safety
• Notification that an emergency condition exist • Visibility created and maintained by emergency lighting systems• Direction established to safe exit areas
The reliability of a life safety design is only as strong as the weakest link.
Notification DirectionVisibility
Design Criteria-Occupancy Permit
• UL 924 Emergency Lighting Equipment• NEC Article 700• NFPA 101 Illumination Requirements• Local Codes• Mandatory, Periodic Testing
Minimum Life Safety Requirements
Code Compliant Solutions
• Generators, Diesel or Natural Gas UL 924 Auxiliary Power Supplies
• Individual Battery Packs• Emergency Ballasts• Centralized Inverters
Engineered Life Safety
Individual Wall Packs or Centralized Inverter?
Wall Packs4.2kW
Lighting Inverter
Self Testing
Self Diagnostics
Annual NFPA 101, Results Logged
Email NFPA 101 Results
Email “Service Required”
Monthly NFPA 101, Results Logged
Engineered Life Safety
Emergency Ballasts or Centralized Inverter?1400 Lumen
Fluorescent Battery Pack w/SD
4.2kW Lighting Inverter
Self Testing
Self Diagnostics
Annual NFPA 101, Results Logged
Email NFPA 101 Results
Email “Service Required”
Monthly NFPA 101, Results Logged
Compliance Expense
*Expense based on initial investment, installation and qualified, third party testing per NFPA 101
4.2kW Egress Lighting
0
5000
10000
15000
20000
25000
30000
35000
Installed 1 year 2 year 3 year
Time Frame
Co
st O
ver
Tim
e
Central Inverter
42W SD Emerg. Ballast
40W Emerg. Ballast
54W SD Wall Pack
125W Wall Pack
3 Year Compliance Expense
Lithonia Emergency Ballast & Wall Pack pricing from Grainger
Watts 20,000 sq. ft. Office INVERTER EMER. BALLAST
42W SDEMER. BALLAST
40WWALL PACK
54W SDWALL PACK
125W
4200 Investment $14,100 $19,950 $11,550 $10,842 $8,840
Installation Labor $300 $1,575 $1,575 $1,950 $850
Installation Material $1,300
$15,700 $21,525 $13,125 $12,792 $9,690
1 105 105 78 34
Hours Per Month 0 4 9 3 3
$15,700 $24,150 $18,500 $14,867 $11,765
$3.74 $5.75 $4.40 $3.54 $2.80
$15,700 $26,775 $23,875 $16,942 $13,840
$3.74 $6.38 $5.68 $4.03 $3.30
$15,700 $29,400 $29,250 $19,017 $15,915
$3.74 $7.00 $6.96 $4.53 $3.79
Cost not used, power feed is usually from local circuits$50/hr.
2nd Year Ownership Expense
Price per watt - 2 Year
$175 Cost Per Month $0 $225
3rd Year Ownership Expense
Price per watt - 3 Year
Total Cost for Equipment/Installation
Units Required
1st Year Ownership Expense
Price per watt - 1 Year
$75 $50
$150
NFPA 101 Expense
$475 $175
• Manual or Automatic Battery testing compliant
with NFPA 101& 111
• Standard Input and Output Circuit Breakers
• Option for Multiple/Dual Output Voltages
• Maintenance Bypass Switches (optional on ELN)
• Self Contained 90min Battery Backup
• Standard Front Access Only Enclosures
• Communications Interfacing
• 2 year full warranty on Inverter & 15 year prorated warranty on battery
eLITE & ULTRALITE Series Features
STANDARD FEATURES
CENTRAL LIGHTING INVERTERS
35
Current CPC Inverter Products
• Sizes range from 550W to 18 KW• ELN & ELE use Ferro Topology• ELU uses Double Conversion
ELN ELU and ELE Series PQ Tips
Key Advantages Include:
• HID/LED Compatible, Uninterrupted, Regulated, Conditioned, Sinewave Output• Multiple Output CB’s• Input/Output Configurability• Communications capabilities• Battery Testing• Multiple Output voltages
36
Current CPC Inverter Products
• Sizes range from 550W to 18 KW• ELN & ELE use Ferro Topology• ELU uses Double Conversion
ELN ELU and ELE Series PQ Summary
Key Advantages Include:• HID/LED Compatible, Uninterrupted, Regulated, Conditioned, Sinewave Output• <+/- 3% load voltage regulation• Electronic Noise/Spike reduction• Computer grade sinewave output• Assures proper voltage • Translating then to optimum Light output at fixture• Provides longer life for expensive ballasts and power supplies
37
Inverter Performance Comparison
Brand ModelInput Voltage
Range Output Voltage Range Output Voltage THD Noise Isolation
Crucial Power Products EconoSine +/-10% +/-4% 10% max. Optional / External
Waverider +15/-20% +/-3% <5% THD -120db
DualLite LSN +10/-15% +/-5% <5% THD none stated
Synchron +/-10% +10/-5% <5% THD none
Myers e ie +10/-15% +/-2 to 12.5% <3% THD none stated
CM +10/-15% +/-3% @<25% load step <3% THD none stated
DSPM/Powerclone DE +10/-15% +/-3 to 8% < 8% none stated
Cobramini +10/-15% +/-3 to 8% < 8% none stated
On Line Power Powerwave +10/-15% +/-3-5% 5% THDIsolation included
but not defined
CPC ELU +12/-30% <+/-1.5% <3% THD 120db
ELN* +10/-40% <+/-3% <3% THD 120db
ELE* +10/-15% <+/-3% <3% THD 120db
* NOTE: ELN & ELE Series load regulation is load dependant using Fuzzy Ranging technology
38
Model ELC Inverter
• Sizes 600W, 1KW, 1.5KW & 2 KW• ELC uses Double Conversion Topology
ELC Main Features
Key Advantages Include:• HID/LED Compatible, Uninterrupted, Regulated, Conditioned, Sinewave Output• Up to 12 Output CB’s Available• Integral Inverter Bypass Switch• Input/Output Configurability• Communications Capabilities• Automatic Battery Testing• Field Programmable Off Bus Control Capabilities• Smallest Footprint in the Industry!
600W 90 Min. 1 thru 2kW
90 Min. 2 kW 2-4 Hours.
39
Model ELC Inverter ELC uses Double Conversion Topology
Key Advantages Include: HID/LED Compatible, Uninterrupted, Regulated, Conditioned, Sinewave Output!
Automatic Static Switch
AC DC
Battery
DCAC
Fault Clearing path of power
Normal path of power
40
Model ELC InverterCommunications Capabilities
System Status and Alarm Panel:
• Traditional Contact Closure Signals for Remote Annunciation• LED Indicators for Incoming Voltage Conditions• LED Load Indicators• LED Mode of Operation Indicators• LED Battery Status Indicators
• Check Battery Indicator • On/Off Soft Keys• Alarm Silence Switch
41
Model ELC InverterRemote Communications Capabilities
Available Options Include:
• Traditional Contact Closure Signals for Remote Annunciation• Remote Annunciator• Auto Dialer• Fax Modem• Netminder Ethernet / SNMP / TCP/IP / MODBUS TCP or RS485
Facilities Mgmt System
Factory Installed within ELC Cabinet
42
Model ELC InverterSmallest Footprint In Its Class!
Dimension Comparison vs:
• Myers CM Series• Dual-Lite DLS Series• Crucial Power EconoSine Series • DSPM Cobra Mini Series
22”W x 11.75”D net 26”W x 10”D unit 22”W x 10”D thru 525W 36”W x 19”D net 30”W x 19”D net
Front Access Only Plus includes Side 32”W x 12”D 750W-2.1KW Includes Rear & Side Includes Rear & Side
Requirement Access Requirement Clearance Clearance
43
Inverter Performance Comparison
Brand ModelInput Voltage
RangeOutput Voltage
Range Output Voltage THD Isolated Output
Crucial Power Products EconoSine +/-10% +/-4% 10% max. Opt.(External Xfrmr)
Waverider +15/-20% +/-3% <5% THD yes
Dual-Lite LSN +10/-15% +/-5% <5% THD Opt.(External Xfrmr)
Synchron +/-10% +10/-5% <5% THD No
Myers E & IE +10/-15% +/-2 to 12.5% <3% THD
Optional – Input/Output
Voltage Dependant
CM +10/-15%
+/-3% @<25% load step
<3% THD None Stated
DSPM / Powerclone DE +10/-15% +/-3 to 8% < 8% Yes 4.7KW and up
Cobra mini +10/-15% +/-3 to 8% < 8% Opt. Internal Xfrmr.
On Line Power Powerwave +10/-15% +/-3-5% 5% THD Yes
CPC ELC +12/-30% typ <+/-2% <3% THD Yes
ELU +12/-30% typ <+/-1.5% <3% THD Yes
ELN +10/-40% typ <+/-3% <3% THD Yes
ELE +10/-15% <+/-3% <3% THD Yes
Question?