Control Theories for Load 1

Embed Size (px)

Citation preview

  • 8/12/2019 Control Theories for Load 1

    1/63

    Harsha Anantwar

    DSCE,Bangalore

  • 8/12/2019 Control Theories for Load 1

    2/63

  • 8/12/2019 Control Theories for Load 1

    3/63

    Power quality

  • 8/12/2019 Control Theories for Load 1

    4/63

  • 8/12/2019 Control Theories for Load 1

    5/63

  • 8/12/2019 Control Theories for Load 1

    6/63

    The loads which cause fluctuations in the supply voltageunbalanced and harmonics, d.c components require

    compensation. Typical loads requiring compensation

    Arc furnaces,Induction furnaces,

    Arc welders,Steel rolling mills,

    Winders,Very large motors, which start and stop frequently

    Other serious loads which degrade power quality Adjustable speed drives which include power electronic circuitry,All power electronics based convertersRectifiers

    Cyclo converters

  • 8/12/2019 Control Theories for Load 1

    7/63

    Important aspects to be consider to provide the loadcompensation for power quality improvement.

    1. Type of Load (unbalance , harmonics and dccomponent)

    2. Real and Reactive power requirements (maximum,minimum and concurrence of maximum real and reactivepower requirements in multiple loads)

    3. Rate of change of real and reactive power etc.

    To correct load with unbalance and harmonics,instantaneous load compensation methods are used.

    Theory of Load Compensation-

    fundamental relation ship between supply system ,the loadand the compensator

  • 8/12/2019 Control Theories for Load 1

    8/63

    Fundamental Theory of Load Compensation

    The supply system can be modeled as a Theveninsequivalent circuitwith an open circuit voltage and a seriesimpedance,

    The compensator can be modeled asvariable impedanceor as avariable source (or sink) of reactive current.

    This modeling and analysis done is on the basisof steady state and phasor quantities are used to note the

    various parameters in system.

  • 8/12/2019 Control Theories for Load 1

    9/63

    Conventional methods of load compensation can

    eliminate only the fundamental reactive power andunbalance in the steady state.

    These kinds of compensators can be realized using

    passive LC filters.

    However, when harmonics are present in the system,

    these methods fails to provide correct compensation

    To correct load with unbalance and harmonics,instantaneous load compensation methods are used.

  • 8/12/2019 Control Theories for Load 1

    10/63

    The active and reactive power with sinusoidal source and

    linear loads are well established,With the non linear load, understanding the reactive and

    harmonic power is an actual necessity for understandingreactive compensation or harmonic filtering.

    A new and concise theory to deal with this problem wellknown in Japan as "instantaneous power theory or pqtheory

    conventional active and reactive power theory, is valid for

    steady-state analysis

    New concepts of instantaneous real and imaginarypower, as introduced by Akagi, valid for steady-and-transient states

  • 8/12/2019 Control Theories for Load 1

    11/63

    Conventional Theory of active and reactive power

    Part "1" has an average value equal to VI cosand has an alternatingcomponent 011 it, oscillating at twice the line frequency.

    This part "1" never becomes negative and therefore, is an unidirectional (dc)power. The average (active) power=VI cos

    Part "2" is also an alternating component, oscillating at twice the linefrequency, has peak value equal to VI sinand zero average value. conventional

    reactive power is just defined as the peakvalue of part "2"

  • 8/12/2019 Control Theories for Load 1

    12/63

    Case2 -Three-phase

    - Consider a balanced, three-phase system with phasesa, b and c and linear loads,

    The instantaneous three phase active power is given by

    However in the conventional concepts, Q3=3*Q

    Because this type of power exists in each phase independently.Its instantaneous sum in the three-phases is equal to zero.

  • 8/12/2019 Control Theories for Load 1

    13/63

    Sinusoidal Voltage Source and Non-linear Loads

    (current contains harmonics at frequencies multiples of )

    S2= P2+ Q2+ H2

  • 8/12/2019 Control Theories for Load 1

    14/63

    P and Q are, dependent only on the current component

    (frequency

    ) ; H is dependent on the current components with

    frequencies different from (harmonics);

    The connection of an L or C component in parallel with

    the load allows the generation of a current atfrequency that absorbs or generates the reactivepower Q required by the load.

    The H depends on frequencies different from can

    not be eliminated by a single capacitor or inductor. The elimination of H depends on filtersthat work as a

    Short circuit for the harmonic current generated by theload.

  • 8/12/2019 Control Theories for Load 1

    15/63

    As the load may change continuously and the harmoniccontents. too, a theory for transient conditions is

    necessary.

    Akagi et al. have proposed new concepts of instantaneousactive and reactive power, that can be used in transientstates

  • 8/12/2019 Control Theories for Load 1

    16/63

    The two important theories for load compensation are

    Instantaneous Theory of load compensation known aspq theory

    ( The instantaneous reactive power is defined as aunique value for arbitrary three-phase voltage andcurrent waveforms including all distorted waveforms)

    Instantaneous Symmetrical Component Theory

    h

  • 8/12/2019 Control Theories for Load 1

    17/63

    A new instantaneous reactive powercompensator can eliminate not only thefundamental reactive power in transient statesbut also some harmonic currents.

    pq theory,

    we shall first recall the --0 transformation

  • 8/12/2019 Control Theories for Load 1

    18/63

    The instantaneous space vectors, eaand iaare set on the a -axis, and their amplitude and (,-) direction vary with thepassage of time.

    In the same way, eband ibare on the b axis, ecand icare onthe c axis.

    These space vectors are easily transformed into a

    --0 coordinates

    e, and iare on the axis, and eand iare on the,axis.

    Their amplitude and (,-) direction vary with the passage oftime

    pq theory

    .

  • 8/12/2019 Control Theories for Load 1

    19/63

    Instantaneous Imaginary Power

    To deal with instantaneous voltages and currents in three-

    phase circuits mathematically, it is adequate to expresstheir quantities as the instantaneous space vectors.

    In order to define the instantaneous reactive power,instantaneous imaginary power space vector defined by

    q space vector is the imaginary axis vector and isperpendicular to the real plane on the - -coordinates, Taking into consideration that eis

    parallel to i,, and eto i,and that eis perpendicularto i and eto i. the conventional instantaneous power,p and the instantaneous imaginary power q,

  • 8/12/2019 Control Theories for Load 1

    20/63

    p = e* i+e* iit is defined by the product of the instantaneous voltagein one axis and the instantaneous current in the sameaxis.

    p is the real power in the three-phase circuit.

    Conversely, q= e* i and e* i are defined by the

    product of the instantaneous voltage in one axis and theinstantaneous current in the perpendicular axis.

    q is the instantaneous imaginary power .

  • 8/12/2019 Control Theories for Load 1

    21/63

    pq theory,

    For three-phase system shown in Fig. 1,.

    Three-phase balanced system is expressed using following voltages andcurrents.

    Va Vb, Vc are phase voltages.

  • 8/12/2019 Control Theories for Load 1

    22/63

    In a-b-c coordinates, the a, b, and c axes are fixed on the sameplane, apart from each other by 2/3,

    , and , axes are the orthogonal coordinates.

  • 8/12/2019 Control Theories for Load 1

    23/63

    The --0 transformation for voltages and currents are given below

  • 8/12/2019 Control Theories for Load 1

    24/63

    The instantaneous active, p(t)

  • 8/12/2019 Control Theories for Load 1

    25/63

    The instantaneous active, p(t)

    advantage of using the--0 transformation is to separatethe zero-sequence component of the system.

  • 8/12/2019 Control Theories for Load 1

    26/63

    The instantaneous reactive power, q(t)

  • 8/12/2019 Control Theories for Load 1

    27/63

  • 8/12/2019 Control Theories for Load 1

    28/63

  • 8/12/2019 Control Theories for Load 1

    29/63

  • 8/12/2019 Control Theories for Load 1

    30/63

  • 8/12/2019 Control Theories for Load 1

    31/63

  • 8/12/2019 Control Theories for Load 1

    32/63

  • 8/12/2019 Control Theories for Load 1

    33/63

    The sum of the instantaneous powers, ppand ppcoincides with the instantaneous real power in thethree-phase circuit.

    Therefore, ppand pp are named instantaneous activepower.

    The instantaneous powers, Pq and pq cancel eachother and make no contribution to the instantaneous

    power flow from the source to the load. Therefore, Pq and pq are named instantaneous

    reactive power.

  • 8/12/2019 Control Theories for Load 1

    34/63

    Quantities in equation are all instantaneous and valid for

    transient or steady state, and harmonics may be present involtage and/or current.

    In the conventional concepts the reactive powercorresponds to the peak value of the of the instantaneouspower whose mean-value is zero

    Now, in the new concepts the reactive power corresponds tothe parts of the instantaneous power, that is dependent on

    the instantaneous imaginary power q, exists in eachphase independently, butvanishes when added

  • 8/12/2019 Control Theories for Load 1

    35/63

    Three-phase Sinusoidal Voltage Supplying

    a Non-linear Load Suppose an electrical system with the voltages sources

    as

  • 8/12/2019 Control Theories for Load 1

    36/63

  • 8/12/2019 Control Theories for Load 1

    37/63

  • 8/12/2019 Control Theories for Load 1

    38/63

    Unbalanced Three-phase 4-Wire System

  • 8/12/2019 Control Theories for Load 1

    39/63

  • 8/12/2019 Control Theories for Load 1

    40/63

    The zero-sequence power po is exactly equal to the

    power in a single-phase circuit, having an average partand an alternating component.

    Its characteristics is similar to the real power p(gives theamount of energy being transported per second from

    source to load There is no reactive power in Po.

    Both positive and negative sequence produces, and

    Only positive and negative sequences can producereactive power,

  • 8/12/2019 Control Theories for Load 1

    41/63

  • 8/12/2019 Control Theories for Load 1

    42/63

  • 8/12/2019 Control Theories for Load 1

    43/63

  • 8/12/2019 Control Theories for Load 1

    44/63

    Instantaneously, the reactive power required by one

    phase can be supplied by the other one. Therefore, noenergy storage element is necessary to compensate forthese power terms.

    compensation of q, means compensation of the

    conventional reactive power q and q~( the harmonicimaginary power)

    Since p, represents the power that is

    effectively converted into work and therefore has to besupplied by the source, only

    may be compensated.

  • 8/12/2019 Control Theories for Load 1

    45/63

    COMPENSATION OF

  • 8/12/2019 Control Theories for Load 1

    46/63

  • 8/12/2019 Control Theories for Load 1

    47/63

  • 8/12/2019 Control Theories for Load 1

    48/63

  • 8/12/2019 Control Theories for Load 1

    49/63

  • 8/12/2019 Control Theories for Load 1

    50/63

  • 8/12/2019 Control Theories for Load 1

    51/63

  • 8/12/2019 Control Theories for Load 1

    52/63

  • 8/12/2019 Control Theories for Load 1

    53/63

  • 8/12/2019 Control Theories for Load 1

    54/63

    A new instantaneous reactive power compensator can eliminate notonly the fundamental reactive power in transient states but also someharmonic currents.

  • 8/12/2019 Control Theories for Load 1

    55/63

  • 8/12/2019 Control Theories for Load 1

    56/63

    Supply

    Voltage

    Linear

    Load

    Supply

    Impedance

    Normal Operating Conditions

    Supply

    Current

    PCC

    VPCC

    +

    -

  • 8/12/2019 Control Theories for Load 1

    57/63

    Supply

    Voltage

    Nonlinear

    Load

    Supply

    Impedance

    Nonlinear Operating Conditions

    PCC

    Supply

    Current

    VPCC

    +

    -

  • 8/12/2019 Control Theories for Load 1

    58/63

    Harmonics from Arc Furnaces

  • 8/12/2019 Control Theories for Load 1

    59/63

    Passive Filters

    Use L - C tuned components Filter banks tuned for the undesired harmonics

    CL

    L

    C

  • 8/12/2019 Control Theories for Load 1

    60/63

    Active Filters

    Use active switching components

    Only one filter needed to eliminate all

    the unwanted harmonics

    Used for power factor correction

  • 8/12/2019 Control Theories for Load 1

    61/63

    Typical Active Filter Circuit

    ~ Non-linearLoad

    Actual Signal

    Feedback

    Reference CurrentGenerator

    Power Circuit

    Overall SystemController

    PWM

    Switching Strategy

  • 8/12/2019 Control Theories for Load 1

    62/63

    Actual Current

    Feedback

    Non-linear

    Load~

    Reference CurrentGenerator

    Power Circuit

    PWM

    Switching Strategy Overall SystemController

    Typical Active Filter Circuit

  • 8/12/2019 Control Theories for Load 1

    63/63

    Thank You