CONTROL SYSTEM FUNCTIONAL DESCRIPTION(Feed Gas Compressor)
Citation preview
CONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTION SOM6629548SOM6629548SOM6629548SOM6629548
TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTION
DOCUMENT CODE
SOM6629548SOM6629548SOM6629548SOM6629548
REVISION
4444
REVISION DESCRIPTION:
REVISED SH.: 1,6÷8,12÷17,22,23,26,29,36,75,83,84,86,87,91÷93
DATE
02020202----AugAugAugAug----12121212
APPROVED
SECURITY CODE
NNNN CHECKED
EXECUTED SIMESIMESIMESIME
SCALE
N/AN/AN/AN/A
REPLACES/DERIVED FROM
N/AN/AN/AN/A
1st ISSUE
28282828----SepSepSepSep----11111111
ORIGINAL JOB
1800057180005718000571800057----58585858
SIZE
4444
LANGUAGE
AAAA
THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. . UNPUBLISHED WORK ©2012201220122012 Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.. . . . ALL RIGHTS RESERVED.
SHEET
1111 of of of of 94949494
AT MINA AL-AHMADI REFINERY
LPG TRAIN-4 PROJECT
AS SHIPPED
Chakraborty A.
Stoppa L.
Ele
ctr
onic
ally
appro
ved d
raw
. G
E N
uovoP
ignone D
T-'N
'
TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTION
DOCUMENT CODE
SOM6629548SOM6629548SOM6629548SOM6629548
REVISION
4444
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE
PAGE MARKER
N/AN/AN/AN/A
SECURITY CODE
NNNN
ORIGINAL JOB
1800057180005718000571800057----58585858
SIZE
4444
LANGUAGE
AAAA
THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. . UNPUBLISHED WORK ©2012201220122012 Nuovo Nuovo Nuovo Nuovo Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.. . . . ALL RIGHTS RESERVED.
SHEET
2222 of of of of 94949494
TABLE OF CONTENTS 1 START/STOP SEQUENCING 6
1.1 READY TO START 6
1.2 AUXILIARIES STARTING 7
1.3 CRANK 8
1.4 SEAL GAS HEATER AND BOOSTER STARTING LOGIC 9
1.5 IGNITION AND WARM-UP 10
1.6 ACCELERATION TO OPERATIVE SPEED 11
1.7 COMPLETE SEQUENCE 12
1.8 TURBINE SPEED CONTROL BY DCS 13
1.9 SHUTDOWN REQUEST 14
1.10 SHUTDOWN SEQUENCE 15
1.11 TRIP REQUEST 16
1.12 TRIP SEQUENCE 17
1.13 COOLDOWN SEQUENCE 18
1.14 ONLINE WATER-WASH 19
1.15 OFFLINE WATER-WASH 20
2 STATUS DEFINITION 22
2.1 AUXILIARIES START READY 22
2.2 AUXILIARIES START PASSED 25
2.3 AUXILIARIES CRANK READY 26
2.4 AUXILIARIES FIRE READY 27
2.5 AUXILIARIES LOAD READY 28
2.6 SHUTDOWN 29
2.7 TRIP 30
2.8 MAINTENANCE OVERRIDE IMPLEMENTATION DESCRIPTION 33
3 OPERATION MODES SELECTION 34
OFF mode 34
CRANK mode 34
FIRE mode 34
AUTO mode 34
REMOTE mode 34
4 AUXILIARIES SEQUENCING 35
4.1 MINERAL LUBE OIL 35
4.1.1 DEVICE SUMMARY 35
4.1.2 SOFTWARE DESCRIPTION 35
4.2 OIL VAPOUR SEPARATOR 38
INDEX
TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTION
DOCUMENT CODE
SOM6629548SOM6629548SOM6629548SOM6629548
REVISION
4444
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE
PAGE MARKER
N/AN/AN/AN/A
SECURITY CODE
NNNN
ORIGINAL JOB
1800057180005718000571800057----58585858
SIZE
4444
LANGUAGE
AAAA
THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. . UNPUBLISHED WORK ©2012201220122012 Nuovo Nuovo Nuovo Nuovo Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.. . . . ALL RIGHTS RESERVED.
SHEET
3333 of of of of 94949494
4.2.1 DEVICE SUMMARY 38
4.2.2 SOFTWARE DESCRIPTION 38
4.3 LUBE OIL HEATER 39
4.3.1 DEVICE SUMMARY 39
4.3.2 SOFTWARE DESCRIPTION 39
4.4 LUBE OIL WATER COOLER 40
4.4.1 DEVICE SUMMARY 40
4.4.2 SOFTWARE DESCRIPTION 40
4.5 CONTROL OIL 41
4.5.1 DEVICE SUMMARY 41
4.5.2 SOFTWARE DESCRIPTION 41
4.6 HYDRAULIC OIL 42
4.6.1 DEVICE SUMMARY 42
4.6.2 SOFTWARE DESCRIPTION 42
4.7 STARTING 44
4.7.1 DEVICE SUMMARY 44
4.7.2 SOFTWARE DESCRIPTION 44
4.8 HYDRAULIC RATCHETING 45
4.8.1 DEVICE SUMMARY 45
4.8.2 SOFTWARE DESCRIPTION 45
4.9 BEARING METAL TEMPERATURE 47
4.9.1 DEVICE SUMMARY 47
4.9.2 SOFTWARE DESCRIPTION 47
4.9.3 DEVICE SUMMARY 48
4.9.4 SOFTWARE DESCRIPTION 48
4.10 WHEELSPACES 49
4.10.1 DEVICE SUMMARY 49
4.10.2 SOFTWARE DESCRIPTION 49
4.11 SEISMIC VIBRATION 50
4.11.1 DEVICE SUMMARY 50
4.11.2 SOFTWARE DESCRIPTION 50
4.12 MAGNETIC SPEED PICK-UP 51
4.12.1 DEVICE SUMMARY 51
4.12.2 SOFTWARE DESCRIPTION 51
4.13 COMBUSTION CHAMBER FLAME DETECTOR 52
4.13.1 DEVICE SUMMARY 52
4.13.2 SOFTWARE DESCRIPTION 52
4.14 INTERFACES WITH BENTLY NEVADA VIBRATION MONITORING SYSTEM 53
4.14.1 DEVICE SUMMARY 53
4.14.2 SOFTWARE DESCRIPTION 53
4.14.3 DEVICE SUMMARY 54
4.14.4 SOFTWARE DESCRIPTION 54
4.15 EXHAUST TEMPERATURE 55
4.15.1 DEVICE SUMMARY 55
4.15.2 SOFTWARE DESCRIPTION 55
4.16 EXHAUST DUCT BACK PRESSURE 56
4.16.1 DEVICE SUMMARY 56
4.16.2 SOFTWARE DESCRIPTION 56
TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTION
DOCUMENT CODE
SOM6629548SOM6629548SOM6629548SOM6629548
REVISION
4444
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE
PAGE MARKER
N/AN/AN/AN/A
SECURITY CODE
NNNN
ORIGINAL JOB
1800057180005718000571800057----58585858
SIZE
4444
LANGUAGE
AAAA
THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. . UNPUBLISHED WORK ©2012201220122012 Nuovo Nuovo Nuovo Nuovo Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.. . . . ALL RIGHTS RESERVED.
SHEET
4444 of of of of 94949494
4.17 WATER WASH 57
4.17.1 DEVICE SUMMARY 57
4.17.2 SOFTWARE DESCRIPTION 57
4.18 VENTILATION 59
4.18.1 DEVICE SUMMARY 59
4.18.2 SOFTWARE DESCRIPTION 59
4.19 INLET AIR FILTRATION 62
4.19.1 DEVICE SUMMARY 62
4.19.2 SOFTWARE DESCRIPTION 62
4.20 FUEL GAS 63
4.20.1 DEVICE SUMMARY 63
4.20.2 SOFTWARE DESCRIPTION 64
4.21 LIQUID FUEL 66
4.21.1 DEVICE SUMMARY 66
4.21.2 SOFTWARE DESCRIPTION 66
4.22 FUEL TRANSFER 68
4.22.1 Fuel Splitter 68
4.22.2 Fuel Transfer (Liquid to Gas) 68
4.22.3 Fuel transfer (Gas to Liquid) 68
4.23 FUEL GAS BLOCK / FUEL GAS VENT VALVES 69
4.24 ATOMIZING AIR SYSTEM 70
4.24.1 DEVICE SUMMARY 70
4.24.2 SOFTWARE DESCRIPTION 70
4.25 SEAL GAS, SEAL GAS HEATER & SEAL GAS BOOSTER SYSTEM 72
4.25.1 DEVICE SUMMARY 72
4.25.2 SOFTWARE DESCRIPTION 72
4.26 STEAM INJECTION 75
4.26.1 DEVICE SUMMARY 75
4.26.2 SOFTWARE DESCRIPTION 75
5 ANTISURGE AND LOAD SHARING 78
6 FIRE FIGHTING MONITORING 79
6.1 ENCLOSURE FIRE DETECTION / FIGHTING: 79
6.1.1 DEVICE SUMMARY 79
6.1.2 SOFTWARE DESCRIPTION 80
6.2 FIRE FIGHTING DEDICATED PLC INTERFACE: 81
7 MARKVIE INTERFACES WITH OTHER SYSTEMS 82
8 CONTROL INTERFACE WITH WASTE HEAT RECOVERY UNIT CONTROL SYSTEM 92
8.1.1 INTERLOCK SIGNALS 92
8.1.2 SOFTWARE DESCRIPTION 92
TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTION
DOCUMENT CODE
SOM6629548SOM6629548SOM6629548SOM6629548
REVISION
4444
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE
PAGE MARKER
N/AN/AN/AN/A
SECURITY CODE
NNNN
ORIGINAL JOB
1800057180005718000571800057----58585858
SIZE
4444
LANGUAGE
AAAA
THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. . UNPUBLISHED WORK ©2012201220122012 Nuovo Nuovo Nuovo Nuovo Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.. . . . ALL RIGHTS RESERVED.
SHEET
5555 of of of of 94949494
LEGEND: L14HSX: MINIMUM OPERATING SPEED L4: MASTER PROTECTIVE RELAY 14HR: SHAFT ZERO SPEED L62CD: COOLDOWN END L2TVX: IGNITION TRANSFORMER ACTIVATION L28FDX: FLAME DETECTED L1X: MASTER CONTROL START-UP. SIS: SAFETY INSTRUMENTED SYSTEM (MK VIeS) FSR: FUEL STROKE REFERENCE DCP: DIRECT CURRENT PANEL GENERAL NOTE:
1. Contacts for limit switches are closed when valve is actuated to corresponding switch position. 2. For signal philosophy to MCC or DCP see UNIT CONTROL SYSTEM HARDWIRED I/O LIST
(SOM6628418/3). 3. The software macro performs a position check on each valve command output transition, after a
“max positioning time” if the relevant limit switch input is not verified a position mismatch Alarm is generated. Moreover the position mismatch Alarm becomes active immediately if both limit switch inputs are closed.
4. The scope of this specification is to give a functional description of its auxiliary sequences. This document does not cover the description of CORE ENGINE LOGIC FUNCTIONS. The CORE ENGINE LOGIC FUNCTIONS software section contains algorithms for combustion chambers flame detection, firing temperature calculation, speed/load regulator/protection, acceleration regulators, exhaust temperature averaging regulator and protection, inter stage pressure regulator. These algorithms shall be considered GE proprietary information and are excluded from this specification.
REFERENCE DOCUMENTS: GE-NP DOCUMENTS Piping & Instruments Diagram SOM5081820/1 Cause & Effect Diagram SOM6629813/3 UCS IO List SOM6628418/3 Control System & Power Supply Schematic SOM5464708/3 CCC Control System Description SOM6629507/4 Field Instrument List SOM6628002/3 Communication List SOM6629523/3 CCC Modbus List SOM6629508/4 NOTE:
• ~ Symbol indicate NOT signal operation • Median function is used in Mark Vie logic where 2oo3 function is required • Spread alarm for 2oo3 signals will be active as follow: if the difference between the maximum and
the minimum values of the three variable becomes greater than or equal to the specified constant.
TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTION
DOCUMENT CODE
SOM6629548SOM6629548SOM6629548SOM6629548
REVISION
4444
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE
PAGE MARKER
N/AN/AN/AN/A
SECURITY CODE
NNNN
ORIGINAL JOB
1800057180005718000571800057----58585858
SIZE
4444
LANGUAGE
AAAA
THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. . UNPUBLISHED WORK ©2012201220122012 Nuovo Nuovo Nuovo Nuovo Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.. . . . ALL RIGHTS RESERVED.
SHEET
6666 of of of of 94949494
1 START/STOP SEQUENCING
1.1 READY TO START
Figure 1 - Ready to start
REVISED WHERE SHOWN <4>
TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTION
DOCUMENT CODE
SOM6629548SOM6629548SOM6629548SOM6629548
REVISION
4444
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE
PAGE MARKER
N/AN/AN/AN/A
SECURITY CODE
NNNN
ORIGINAL JOB
1800057180005718000571800057----58585858
SIZE
4444
LANGUAGE
AAAA
THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. . UNPUBLISHED WORK ©2012201220122012 Nuovo Nuovo Nuovo Nuovo Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.. . . . ALL RIGHTS RESERVED.
SHEET
7777 of of of of 94949494
1.2 AUXILIARIES STARTING
Figure 2 - Auxiliaries starting
REVISED WHERE SHOWN <4>
TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTION
DOCUMENT CODE
SOM6629548SOM6629548SOM6629548SOM6629548
REVISION
4444
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE
PAGE MARKER
N/AN/AN/AN/A
SECURITY CODE
NNNN
ORIGINAL JOB
1800057180005718000571800057----58585858
SIZE
4444
LANGUAGE
AAAA
THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. . UNPUBLISHED WORK ©2012201220122012 Nuovo Nuovo Nuovo Nuovo Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.. . . . ALL RIGHTS RESERVED.
SHEET
8888 of of of of 94949494
1.3 CRANK
Off-line water
wash selection on HMI
B
Turbine and Auxiliaries
Sequences
External
Sequences
Notes:-
From Sh. 07
Yes
C
Note that if water wash is
selected ready to start and start passed conditions changes from the above described
(1)
Sequences
Water wash system start (1)
End of Sequence
Aux. Ready to
crank?
Start process valve
positioning
Customer valve sequencing start
Valve sequence
ended; Customer Permissive to Crank
AND
3CRC
Yes
-Ratchet system activation-Starting system activation
TNH Above zero speed?
No
No
-Ratchet system de-activation-Solenoid valve 20HD-1 closed
Yes
TNH Above Crank speed?
No
Yes
CRANK
WHRU dampers in By-Pass position?
Unit in Crank
14HMX
See TABLE 5
Auxiliary ready to Crank
No
To Sh. 09
Purge Timer Reset
GT Purge Time elapsed?
WHRU Purge
Done?
WHRU dampers
in By-Pass position?
No
No
Yes
Yes
L2TV=1
No
Yes
No
Yes
WHRU CTRL
GT Purge Done
WHRU CTRL
WHRU Purge Sequence
WHRU CTRL
WHRU Purge Timer Elapsed
WHRU CTRL
Damper Status
(231-XS-253C)
(231-XS-0258 RS)
4VALV
(231-XS-0256)
231-XS-0955
231-XS-960
231-XS-554
or
231-XS-654
Open Hot Gas Bypass Valve
Close Anti-surge Valve command to
CCC
Close Anti-surge valve
Hot Bypass valve open command for purge
Hot Bypass valve open / close feedback (1= Open; 0 = close)
Close Anti-surge valve for Purge
Anti-surge valve open / close feedback (1= Closed; 0 = Open)
PESD
<4>
<4>
<4>
Figure 3 –Crank
REVISED WHERE SHOWN <4>
TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTION
DOCUMENT CODE
SOM6629548SOM6629548SOM6629548SOM6629548
REVISION
4444
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE
PAGE MARKER
N/AN/AN/AN/A
SECURITY CODE
NNNN
ORIGINAL JOB
1800057180005718000571800057----58585858
SIZE
4444
LANGUAGE
AAAA
THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. . UNPUBLISHED WORK ©2012201220122012 Nuovo Nuovo Nuovo Nuovo Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.. . . . ALL RIGHTS RESERVED.
SHEET
9999 of of of of 94949494
1.4 SEAL GAS HEATER AND BOOSTER STARTING LOGIC
Figure 4 – Seal Gas Heater and Booster Starting Logic
TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTION
DOCUMENT CODE
SOM6629548SOM6629548SOM6629548SOM6629548
REVISION
4444
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE
PAGE MARKER
N/AN/AN/AN/A
SECURITY CODE
NNNN
ORIGINAL JOB
1800057180005718000571800057----58585858
SIZE
4444
LANGUAGE
AAAA
THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. . UNPUBLISHED WORK ©2012201220122012 Nuovo Nuovo Nuovo Nuovo Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.. . . . ALL RIGHTS RESERVED.
SHEET
10101010 of of of of 94949494
1.5 IGNITION AND WARM-UP
Figure 5 - Ignition and warm-up
TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTION
DOCUMENT CODE
SOM6629548SOM6629548SOM6629548SOM6629548
REVISION
4444
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE
PAGE MARKER
N/AN/AN/AN/A
SECURITY CODE
NNNN
ORIGINAL JOB
1800057180005718000571800057----58585858
SIZE
4444
LANGUAGE
AAAA
THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. . UNPUBLISHED WORK ©2012201220122012 Nuovo Nuovo Nuovo Nuovo Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.. . . . ALL RIGHTS RESERVED.
SHEET
11111111 of of of of 94949494
1.6 ACCELERATION TO OPERATIVE SPEED
Figure 6 - Acceleration to operative speed
TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTION
DOCUMENT CODE
SOM6629548SOM6629548SOM6629548SOM6629548
REVISION
4444
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE
PAGE MARKER
N/AN/AN/AN/A
SECURITY CODE
NNNN
ORIGINAL JOB
1800057180005718000571800057----58585858
SIZE
4444
LANGUAGE
AAAA
THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. . UNPUBLISHED WORK ©2012201220122012 Nuovo Nuovo Nuovo Nuovo Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.. . . . ALL RIGHTS RESERVED.
SHEET
12121212 of of of of 94949494
1.7 COMPLETE SEQUENCE
Figure 7 - Complete sequence
REVISED WHERE SHOWN <4>
TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTION
DOCUMENT CODE
SOM6629548SOM6629548SOM6629548SOM6629548
REVISION
4444
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE
PAGE MARKER
N/AN/AN/AN/A
SECURITY CODE
NNNN
ORIGINAL JOB
1800057180005718000571800057----58585858
SIZE
4444
LANGUAGE
AAAA
THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. . UNPUBLISHED WORK ©2012201220122012 Nuovo Nuovo Nuovo Nuovo Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.. . . . ALL RIGHTS RESERVED.
SHEET
13131313 of of of of 94949494
1.8 TURBINE SPEED CONTROL BY DCS
Figure 8 – Turbine Speed Control by DCS
REVISED WHERE SHOWN <4>
TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTION
DOCUMENT CODE
SOM6629548SOM6629548SOM6629548SOM6629548
REVISION
4444
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE
PAGE MARKER
N/AN/AN/AN/A
SECURITY CODE
NNNN
ORIGINAL JOB
1800057180005718000571800057----58585858
SIZE
4444
LANGUAGE
AAAA
THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. . UNPUBLISHED WORK ©2012201220122012 Nuovo Nuovo Nuovo Nuovo Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.. . . . ALL RIGHTS RESERVED.
SHEET
14141414 of of of of 94949494
1.9 SHUTDOWN REQUEST
Figure 9 - Shutdown request
REVISED WHERE SHOWN <4>
TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTION
DOCUMENT CODE
SOM6629548SOM6629548SOM6629548SOM6629548
REVISION
4444
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE
PAGE MARKER
N/AN/AN/AN/A
SECURITY CODE
NNNN
ORIGINAL JOB
1800057180005718000571800057----58585858
SIZE
4444
LANGUAGE
AAAA
THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. . UNPUBLISHED WORK ©2012201220122012 Nuovo Nuovo Nuovo Nuovo Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.. . . . ALL RIGHTS RESERVED.
SHEET
15151515 of of of of 94949494
1.10 SHUTDOWN SEQUENCE
Figure 10 - Shutdown sequence
REVISED WHERE SHOWN <4>
TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTION
DOCUMENT CODE
SOM6629548SOM6629548SOM6629548SOM6629548
REVISION
4444
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE
PAGE MARKER
N/AN/AN/AN/A
SECURITY CODE
NNNN
ORIGINAL JOB
1800057180005718000571800057----58585858
SIZE
4444
LANGUAGE
AAAA
THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. . UNPUBLISHED WORK ©2012201220122012 Nuovo Nuovo Nuovo Nuovo Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.. . . . ALL RIGHTS RESERVED.
SHEET
16161616 of of of of 94949494
1.11 TRIP REQUEST
Turbine and Auxiliaries
Sequences
External
Sequences
Aux Trip?
Core Engine Trip? L
End sequence
See Table 9
Trip from Auxiliaries
Customer ESD
signal
PESD
CESD-1, CESD-2
To sh. 06, 17
No
No
No
Yes
Master
Selector - Remote
Trip from
HMI?
- Crank
- Fire
- Manual
- Auto
Trip
sequence
Customer
Trip?L L
YESYES
To Sh.6, 17 To Sh. 6, 17NoNo
YES
(231-XS-700A)
(231-XS-700B)
Process Remote
Trip
DCS
4CT
(231-XS-0257T)
<4>
Figure 11 - Trip request
REVISED WHERE SHOWN <4>
TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTION
DOCUMENT CODE
SOM6629548SOM6629548SOM6629548SOM6629548
REVISION
4444
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE
PAGE MARKER
N/AN/AN/AN/A
SECURITY CODE
NNNN
ORIGINAL JOB
1800057180005718000571800057----58585858
SIZE
4444
LANGUAGE
AAAA
THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. . UNPUBLISHED WORK ©2012201220122012 Nuovo Nuovo Nuovo Nuovo Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.. . . . ALL RIGHTS RESERVED.
SHEET
17171717 of of of of 94949494
1.12 TRIP SEQUENCE
Figure 12 - Trip sequence
REVISED WHERE SHOWN <4>
TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTION
DOCUMENT CODE
SOM6629548SOM6629548SOM6629548SOM6629548
REVISION
4444
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE
PAGE MARKER
N/AN/AN/AN/A
SECURITY CODE
NNNN
ORIGINAL JOB
1800057180005718000571800057----58585858
SIZE
4444
LANGUAGE
AAAA
THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. . UNPUBLISHED WORK ©2012201220122012 Nuovo Nuovo Nuovo Nuovo Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.. . . . ALL RIGHTS RESERVED.
SHEET
18181818 of of of of 94949494
1.13 COOLDOWN SEQUENCE
Figure 13 - Cooldown sequence
TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTION
DOCUMENT CODE
SOM6629548SOM6629548SOM6629548SOM6629548
REVISION
4444
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE
PAGE MARKER
N/AN/AN/AN/A
SECURITY CODE
NNNN
ORIGINAL JOB
1800057180005718000571800057----58585858
SIZE
4444
LANGUAGE
AAAA
THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. . UNPUBLISHED WORK ©2012201220122012 Nuovo Nuovo Nuovo Nuovo Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.. . . . ALL RIGHTS RESERVED.
SHEET
19191919 of of of of 94949494
1.14 ONLINE WATER-WASH
Figure 14 – Online Water-wash
TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTION
DOCUMENT CODE
SOM6629548SOM6629548SOM6629548SOM6629548
REVISION
4444
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE
PAGE MARKER
N/AN/AN/AN/A
SECURITY CODE
NNNN
ORIGINAL JOB
1800057180005718000571800057----58585858
SIZE
4444
LANGUAGE
AAAA
THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. . UNPUBLISHED WORK ©2012201220122012 Nuovo Nuovo Nuovo Nuovo Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.. . . . ALL RIGHTS RESERVED.
SHEET
20202020 of of of of 94949494
1.15 OFFLINE WATER-WASH
TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTION
DOCUMENT CODE
SOM6629548SOM6629548SOM6629548SOM6629548
REVISION
4444
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE
PAGE MARKER
N/AN/AN/AN/A
SECURITY CODE
NNNN
ORIGINAL JOB
1800057180005718000571800057----58585858
SIZE
4444
LANGUAGE
AAAA
THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. . UNPUBLISHED WORK ©2012201220122012 Nuovo Nuovo Nuovo Nuovo Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.. . . . ALL RIGHTS RESERVED.
SHEET
21212121 of of of of 94949494
Figure 15 – Offline Water-wash
TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTION
DOCUMENT CODE
SOM6629548SOM6629548SOM6629548SOM6629548
REVISION
4444
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE
PAGE MARKER
N/AN/AN/AN/A
SECURITY CODE
NNNN
ORIGINAL JOB
1800057180005718000571800057----58585858
SIZE
4444
LANGUAGE
AAAA
THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. . UNPUBLISHED WORK ©2012201220122012 Nuovo Nuovo Nuovo Nuovo Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.. . . . ALL RIGHTS RESERVED.
SHEET
22222222 of of of of 94949494
2 STATUS DEFINITION
2.1 AUXILIARIES START READY Table1 Ready to start from Other Systems LOGIC SOFTWARE
TAG JOB TAG(GE TAG) DESCRIPTION SYSTEM
L33as_o 231-ZSH-5001A
Anti-surge control valve open position-ASV 1
Process (ASC)
NOT l86asc 231-XS-807A (86AS) Anti-surge controller fault Process (ASC) NOT L86as1
- Anti-surge control valve 1 position failure
Process (ASC)
NOT l86ls (31-XS-808B (86LS) Master controller fault Process (MCP) L3COMM_IO
- MKVIe IO pack communication OK
Misc-MarkVIe
NOT l86ps1 231-XS-601A (86PS-1) 24Vdc Bus 1 failure Misc-PS NOT l86ps2 231-XS-601B (86PS-2) 24Vdc Bus 2 failure Misc-PS NOT l86psfg
231-XS-602 (86PS-FG) Fire Fighting 24Vdc Bus failure
Misc-PS
NOT l86psf 231-XS-603 (86PS-FIELD) Field 24Vdc Bus failure Misc-PS NOT l86ps3 231-XS-610 (86PS-3) 110Vdc Bus failure Misc-PS NOT l80x
231-XS-207 (DCP-80X) Minimum battery voltage alarm
Misc-DCP
NOT l30ra 231-XS-206A (DCP-30RA)
DCP rectifier “A” common alarm
Misc-DCP
NOT ldcp_bad 231-XS-208A (DCP-BD)
DCP-battery “A” discharging
Misc-DCP
NOT 231-XS-863 (-) <4> GROUND FAULT + Misc-DCP NOT 231-XS-864 (-) <4> GROUND FAULT - Misc-DCP NOT l86vmn
231-YS-402F (86VM) Vibration monitor common fault alarm
Misc- BN3500 VIB Monitor
NOT l86tm 231-YS-451F (86TM)
Temperature monitoring fault
Misc- BN3500 TEMP Monitor
NOT l86cr 231-XS-515L (86CR)
Cranking motor protective lock-out
Misc- Starting Motor
NOT l33cp_c 231-XS-144 (33CP-1) Fire fighting Inergen discharge valve closed
Fire Fighting monitor
NOT l86fg 231-XS-652 SF (86FF-1) FF system fault alarm Fire Fighting monitor
NOT L71GFH_W 231-LIT-5039A/B/C (71GF-2/3/4A) OR, 231-LIT-5043A/B/C (71GF-2/3/4B)
Fuel gas scrubber level high alarm
Customer ESD
NOT L86PS_110VAC_TRVIEW
231-XS-612 A 110 Vac Bus Failure at TV server panel
MISC-PS
NOT L86PS_24VDC_TRVIEW
231-XS-613 A 24 Vdc Bus Failure at TV server panel
MISC-PS
NOT FF_NSD 231-XS-652 IF (86FF_SD) FF Input fault- Normal shutdown
FF
L3crs 231-XS-0250 RS (3CRS) <4>
Customer ready to start DCS
REVISED WHERE SHOWN <4>
TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTION
DOCUMENT CODE
SOM6629548SOM6629548SOM6629548SOM6629548
REVISION
4444
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE
PAGE MARKER
N/AN/AN/AN/A
SECURITY CODE
NNNN
ORIGINAL JOB
1800057180005718000571800057----58585858
SIZE
4444
LANGUAGE
AAAA
THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. . UNPUBLISHED WORK ©2012201220122012 Nuovo Nuovo Nuovo Nuovo Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.. . . . ALL RIGHTS RESERVED.
SHEET
23232323 of of of of 94949494
LOGIC SOFTWARE TAG JOB TAG(GE TAG) DESCRIPTION SYSTEM
NOT L86FTL 231-XA 5015 (-) Liquid fuel thyristor panel fault
LF thyristor Panel
NOT L27mc1n 231-XS-134 (27MC) Undervoltage from MCC MCC NOT L49x 231-XS-135 (49X) Common overload from
MCC MCC
NOT L74x_mcc 231-XS-136 (74X-MCC) Drawer Common Alarm MCC NOT L45hsa_o 231-XS-736 (45HSA) Acc compt H2S detected
alarm MarkVIe
231-ZSL-2055 (-) Hot Gas Bypass Valve Close Limit Switch
MarkVIe
231-XS-554 (-) Diverter System Close MarkVIe NOT L86thy 231-UA-5209A (TH1_F) Seal Gas thyristor Panel
fault Thy Panel
Table2 Ready to start from Auxiliaries LOGIC SOFTWARE
TAG JOB TAG(GE TAG) DESCRIPTION SYSTEM
NOT L71QL_W 231-LIT-5086A (96QL1) Lube oil tank level low alarm Lube oil NOT l27qel
231-XS-851B (49QE) <4> Lube oil emergency pump fault
Lube oil
L26qn_W 231-TE 5088AA (LT-OT-1)
Lube oil tank temperature normal
Lube oil
NOT SIS1.L86HD - Hydraulic protective trouble Control oil NOT l49hr1a 231-XS-200O (49HR-1) Hydraulic ratchet pump
overload alarm Hydraulic ratchet
NOT L27hr1a 231-XS-200U (27HR-1) Hydraulic ratchet pump under-voltage alarm
Hydraulic ratchet
NOT L26BA 231-TE-5241A1/A2/A3 (TT-BA-2A/B/C)
Turbine compartment outlet temp high alarm
Enclosure ventilation
l33ido Note1 231-ZSH-5242A (33ID-1) Turbine enclosure ventilation inlet damper open
Enclosure ventilation
l33odo1 Note1 231-ZSH-5243A (330D-1)
Turbine enclosure ventilation outlet damper#1 open
Enclosure ventilation
l33odo2 Note1 231-ZSH-5244A (330D-2)
Turbine enclosure ventilation outlet damper#2 open
Enclosure ventilation
l33odo3 Note1 231-ZSH-5245A (330D-3)
Turbine enclosure ventilation outlet damper#3 open
Enclosure ventilation
NOT L26BA_1 231-TE-5242A1/A2/A3 (TT-BA-3A/B/C)
Coupling compartment outlet temperature high alarm
Enclosure ventilation
l33vg2_c 231-ZSL-5009A (33VG-2)
Fuel gas warm-up vent valve closed
Fuel gas system
NOT
L63FGH_W
231-PIT-5003A (96FG-1)
Fuel gas pressure high alarm
Fuel gas system
NOT L63FGH1_W 231-PIT-5005A1/A2/A3 (96FG-2A/B/C)
Inter-valve fuel gas pressure high
Fuel gas system
l33cp 231-ZSH-5265A (33CP-1A); 231-ZSH-5266A (33CP-1D)
Fire fighting Inergen discharge valve open
Fire Fighting skid system
NOT L33PV3_o 231-ZSH 5007 A (33PV-2)
Nozzle Purge Air Vent valve open
Fuel gas system
REVISED WHERE SHOWN <4>
TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTION
DOCUMENT CODE
SOM6629548SOM6629548SOM6629548SOM6629548
REVISION
4444
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE
PAGE MARKER
N/AN/AN/AN/A
SECURITY CODE
NNNN
ORIGINAL JOB
1800057180005718000571800057----58585858
SIZE
4444
LANGUAGE
AAAA
THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. . UNPUBLISHED WORK ©2012201220122012 Nuovo Nuovo Nuovo Nuovo Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.. . . . ALL RIGHTS RESERVED.
SHEET
24242424 of of of of 94949494
LOGIC SOFTWARE TAG JOB TAG(GE TAG) DESCRIPTION SYSTEM
NOT L33cb1o 231-ZSH 5050A (33CB-1) VAB-1 Axial Compressor Bleed valve status Open
Cooling & Sealing
NOT L33cb2o 231-ZSH 5049A (33CB-2) VAB-2 Axial Compressor Bleed valve status Open
Cooling & Sealing
NOT L33ac_c 231-ZSL-5157A (33AC-1) Atomizing air cooler valve closed
Oil water cooler
Note1: This permissive to start is enabled if “Water Wash On” function is not selected on the HMI (L43BW is false). Table3 Ready to start from SIS LOGIC SOFTWARE
TAG JOB TAG(GE TAG) DESCRIPTION SYSTEM
NOT l45hta2 231-AE-5242A1/2/3 (45HD-2A/B/C)
Turbine enclosure gas detected alarm
SIS
NOT l45hta1 231-AE-5241A1/2/3 (45HD-1A/B/C)
Accessory comp. gas detected alarm
SIS
NOT l45hfa 231-AE-5229A1/2/3 (45HF-1/2/3)
Turbine inlet air filter gas detected alarm
SIS
l33dtcNote1 231-ZSL-5241(33DT)
Enclosure access door closed
SIS
NOT L86MP - Master protective lockout SIS NOT
(L86VG-1) - Inter-valve gas unit rate mismatch
SIS
NOT L20HDX -
Fuel Gas Stop valve control signal on safety
SIS
NOT GT_2SHAFT - GT-2 shaft selected SIS NOT
L28FD_FLT - Flame detected without fuel on
SIS
NOT (L86FB) -
Off-skid shutoff valve position mismatch
SIS
NOT (L86FV) -
Off-skid bleed valve position mismatch
SIS
L30FORCED_SIS
- SIS forced signal detected SIS
NOT L86BT1_ALM L86BT2_ALM L86BT3_ALM
- Turbine compart. /ambient. Diff. Press. TX-1/2/3 fault
SIS
NOT L30LOCKED_SIS
- SIS CPU locked active SIS
l33af1c 231-ZSL-5229A (33AF-1) Turbine inlet air filter inspection. door closed
SIS
NOT 231-ZSL-5219A (33ED-1)
Combustion Wrapper Drain valve closed
SIS
NOT L86splc - Safety system fault signal SIS NOT L4_sis
Master Protective Signal (1=Fuel ON)
SIS
NOT L33ED4 231-ZSL-5277A1 (33ED-4)
Exhaust Plenum Drain Valve VA17-6 Closed
Water wash
NOT L33ED5 231-ZSL-5277A2 (33ED-5)
Exhaust Plenum Drain Valve VA17-6 Closed
Water wash
TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTION
DOCUMENT CODE
SOM6629548SOM6629548SOM6629548SOM6629548
REVISION
4444
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE
PAGE MARKER
N/AN/AN/AN/A
SECURITY CODE
NNNN
ORIGINAL JOB
1800057180005718000571800057----58585858
SIZE
4444
LANGUAGE
AAAA
THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. . UNPUBLISHED WORK ©2012201220122012 Nuovo Nuovo Nuovo Nuovo Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.. . . . ALL RIGHTS RESERVED.
SHEET
25252525 of of of of 94949494
Note1: This permissive to start is enabled if “Water Wash On” function is not selected on the HMI (L43BW is false).
2.2 AUXILIARIES START PASSED Table 4 Start Passed LOGIC SOFTWARE
TAG JOB TAG(GE TAG) DESCRIPTION SYSTEM
L3PSP Process start passed l52qa 231-XS-100I
(52QA-1) Lube oil auxiliary pump running
Lube oil
NOT L63QA2L_W 231-PIT-5133 A1/2/3
Lube oil header pressure low alarm
Lube oil
NOT L63QAL_W 231-PIT-5091A (96QA-1)
Lube oil pump discharge pressure low alarm
Lube oil
L3QE_TEST -
Lube oil emergency pump test passed
Lube oil
NOT L63HQ1L_W 231-PIT-5114A (96HQ-1)
Hydraulic oil pressure low alarm
Hydraulic oil
l52hq 231-XS-104I (52HQ-1)
Hydraulic oil aux pump running
Hydraulic oil
l52bt1 OR l52bt2Note2
231-XS-108I (52BA-1) OR, 231-XS-109I (52BA-2)
Turbine-enclosure ventilation fan #1 running OR, Turbine-enclosure ventilation fan #2 running
Enclosure ventilation
NOT L63BT_W
Note2 231-PDIT-5241A1/2/3 (96SV-1A/B/C)
Turbine compartment diff. press low alarm
Enclosure ventilation
NOT L63SGLA 231-PDIT-5201 A
Seal Gas Inlet Balancing Line Differential Pressure
Seal Gas
Note2: This permissive to start is bypassed if “Compressor/turbine Water Wash Control” function is selected (L83BW is true).
TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTION
DOCUMENT CODE
SOM6629548SOM6629548SOM6629548SOM6629548
REVISION
4444
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE
PAGE MARKER
N/AN/AN/AN/A
SECURITY CODE
NNNN
ORIGINAL JOB
1800057180005718000571800057----58585858
SIZE
4444
LANGUAGE
AAAA
THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. . UNPUBLISHED WORK ©2012201220122012 Nuovo Nuovo Nuovo Nuovo Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.. . . . ALL RIGHTS RESERVED.
SHEET
26262626 of of of of 94949494
2.3 AUXILIARIES CRANK READY Table 5 Ready to Crank from auxiliaries LOGIC SOFTWAR
E TAG JOB TAG(GE TAG) DESCRIPTION SYSTEM
L3PRC - Process ready to crank Process NOT L71QL_W
231-LIT-5086A (96QL1) Lube oil tank level low alarm
Lube oil
l52qa 231-XS-100I (52QA-1)
Lube oil auxiliary pump running
NOT L63QA2L_W
231-PIT-5133 A1/2/3 Lube oil header pressure low alarm
Lube oil
NOT L63QAL_W 231-PIT-5091A (96QA-1)
Lube oil pump discharge pressure low alarm
Lube oil
L26QN_W 231-TE-5088AA (LT-OT-1)
Lube oil tank temp normal Lube oil
NOT L63HQ1L_W
231-PIT-5114A (96HQ-1)
Hydraulic oil pressure low alarm
Hydraulic oil
l52hq 231-XS-104I (52HQ-1)
Hydraulic oil aux pump running
Hydraulic oil
NOT L26FGL_W 231-TE-5006AA
(TG-FG-1)
Fuel gas temp low alarm Master selector in “crank” position
Fuel gas
l33vg2_c
Note3 231-ZSL-5009A (33VG-2)
Fuel gas vent valve closed Fuel gas
NOT L63FGL_W
Note3 231-PIT-5003A (96FG-1)
Fuel gas pressure low alarm
Fuel gas
Off-skid gas shut-off valve open
Note3
AND Off-skid gas vent valve closed Note3
(33FB-O) AND (33FV-1)
Process valve ready to crank position
Fuel gas
NOT L63NCP_W 231-PIT 5063 (96NCP-1)
Bearing cooling Air Pressure Low
L3crc 231-XS-0258 RS (3CRC) <4>
Customer ready to crank Process
L33prc SIS1.L33FB_O &
SIS1.L33FV_C
Process valve Ready to crank Position
Process
Note3: This permissive to start is bypassed if “Compressor/turbine Water Wash Control” function is selected (L83BW is true).
REVISED WHERE SHOWN <4>
TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTION
DOCUMENT CODE
SOM6629548SOM6629548SOM6629548SOM6629548
REVISION
4444
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE
PAGE MARKER
N/AN/AN/AN/A
SECURITY CODE
NNNN
ORIGINAL JOB
1800057180005718000571800057----58585858
SIZE
4444
LANGUAGE
AAAA
THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. . UNPUBLISHED WORK ©2012201220122012 Nuovo Nuovo Nuovo Nuovo Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.. . . . ALL RIGHTS RESERVED.
SHEET
27272727 of of of of 94949494
2.4 AUXILIARIES FIRE READY Table 6 Ready to Fire from auxiliaries LOGIC SOFTWARE
TAG JOB TAG(GE TAG) DESCRIPTION SYSTEM
L3PRF - Process ready to fire Process NOT L63HQ1L_W 231-PIT-5114A
(96HQ-1) Hydraulic oil pressure low alarm
Hydraulic oil
NOT L43BW - Water-wash on selected Water-wash NOT L83BW
- Turbine/compressor water wash control
Water-wash
NOT L63FGL_W 231-PIT-5003A (96FG-1)
Fuel gas pressure low alarm Fuel gas
NOT L26FGL_W 231-TE-5006AA (TG-FG-1)
Fuel gas temperature low alarm
Fuel gas
l33vg2_c 231-ZSL-5009A (33VG-2)
Fuel gas vent valve closed Fuel gas
NOT L63NCP_W 231-PIT 5063 (96NCP-1)
Bearing Cooling Air Pressure Low
TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTION
DOCUMENT CODE
SOM6629548SOM6629548SOM6629548SOM6629548
REVISION
4444
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE
PAGE MARKER
N/AN/AN/AN/A
SECURITY CODE
NNNN
ORIGINAL JOB
1800057180005718000571800057----58585858
SIZE
4444
LANGUAGE
AAAA
THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. . UNPUBLISHED WORK ©2012201220122012 Nuovo Nuovo Nuovo Nuovo Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.. . . . ALL RIGHTS RESERVED.
SHEET
28282828 of of of of 94949494
2.5 AUXILIARIES LOAD READY Table 7 Ready to load from auxiliaries LOGIC SOFTWAR
E TAG JOB TAG(GE TAG) DESCRIPTION SYSTEM
L3PRL Process ready to load Process NOT l52qa 231-XS-100I
(52QA-1) Lube oil aux pump running Lube oil
l72qez 231-XS-851-A (52QE-1)
Lube oil emergency pump stopped
Lube oil
NOT L52hq 231-XS-104I (52HQ-1)
Hydraulic oil aux pump running
Hydraulic oil
TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTION
DOCUMENT CODE
SOM6629548SOM6629548SOM6629548SOM6629548
REVISION
4444
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE
PAGE MARKER
N/AN/AN/AN/A
SECURITY CODE
NNNN
ORIGINAL JOB
1800057180005718000571800057----58585858
SIZE
4444
LANGUAGE
AAAA
THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. . UNPUBLISHED WORK ©2012201220122012 Nuovo Nuovo Nuovo Nuovo Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.. . . . ALL RIGHTS RESERVED.
SHEET
29292929 of of of of 94949494
2.6 SHUTDOWN Table 8 Shutdown from auxiliaries LOGIC SOFTWAR
E TAG JOB TAG(GE TAG) DESCRIPTION SYSTEM
L94PSHD Process shut-down command Process L63TF 231-PDIT-
5231A1/2/3 (96TF-1A/B/C)
Turb inlet filter diff. press. High vot. Shutdown logic
Inlet and Filtration
L30WSA4_ALM
231-TE-5082/A1 (TT-WS1AI-1) OR 231-TE-5082/A2 (TT-WS1AI-2) OR 231-TE-5079/A1 (TT-WS1FI-1) OR 231-TE-5079/A2 (TT-WS1FI-2) OR 231-TE-5080/A1 (TT-WS2FI-1) OR 231-TE-5080/A2 (TT-WS2FI-2) OR 231-TE-5081/A1 (TT-WS2AI-1) OR 231-TE-5081/A2 (TT-WS2AI-2)
Wheel-space shutdown logic
Wheel-space
TAH-208 TAH-211 TAH-212 TAH-213
Wheel-space temperature high alarmNote4
Wheel-space
231-TE-5158/A1A/2A/3A (AAT-1A/B/C)
Atomizing air temperature high high shutdown
Atomizing air
231-TIT-5013A1/A2/A3
Liquid Fuel Temperature low low
Liquid Fuel System
231-XS-652-IF (86FF_SD)
Fire Fighting Input fault normal shutdown
Fire Fighting System
S1STPSEL 231-XS-0257 S (1STOP) <4>
Process remote Stop DCS
gthrsgds_sd 231-XS-354
GT shutdown for HRSG Shutdown & Diverter System Failure to Close
PESD
Note4: Shutdown is started if wheel-space temperature is high for 24 hours
REVISED WHERE SHOWN <4>
TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTION
DOCUMENT CODE
SOM6629548SOM6629548SOM6629548SOM6629548
REVISION
4444
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE
PAGE MARKER
N/AN/AN/AN/A
SECURITY CODE
NNNN
ORIGINAL JOB
1800057180005718000571800057----58585858
SIZE
4444
LANGUAGE
AAAA
THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. . UNPUBLISHED WORK ©2012201220122012 Nuovo Nuovo Nuovo Nuovo Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.. . . . ALL RIGHTS RESERVED.
SHEET
30303030 of of of of 94949494
2.7 TRIP Table 9 Trip from auxiliaries LOGIC SOFTWARE
TAG JOB TAG(GE TAG) DESCRIPTION SYSTEM
231-PDIT-5204A1/2/3
Compressor primary vent pressure (depressurized trip)
Seal Gas System
231-PIT-5195A1/2/3
Nitrogen gas header pressure low low
Seal Gas System
231-PDIT-5205A1/2/3 Primary vent pressure (depressurized trip)
Seal Gas System
(L26TSGLL) 231-TE-5210A1/2/3
Buffer gas Temp low low. (depressurized trip)
Seal Gas System
L4surge_1 - Surge trip ASC
L26QT 231-TE-5159A1/2/3 (LT-TH-1A/B/C)
Lube oil header temperature high voting trip logic Lube Oil
L63QTX 231-PIT-5133 A1/2/3
Lube oil pressure low voting trip aux. logic
Lube Oil
L63QVT
231-PDIT-5087A1/2/3 (96QV-1A/B/C)
Lube oil tank pressure high voting trip logic
Lube Oil
L4QE_TRP
Lube oil emergency pump trip logic
Lube Oil
L3SMTX - Starting motor trip logic Hydraulic
L26BT
231-TE-5241A1/2/3 (TT-BA-2A/B/C) 231-TE-5242A1/2/3 (TT-BA-3A/B/C)
GT compartment internal temperature high trip
Ventilation System
L4CETRIP - Core Trip UCS L4T_S - Cumulative safety trip to MKVIe SIS L4T_FGS - Fuel Gas Scrubber Trip Signal DCS (L4T) - Trip Notification from MKVIe SIS
- 231-ZT-5133A1/2/3 Axial Displacement of Compressor bearings High High
BN 3500 (Vib)
- 231-XT-5133A1/A2
Radial Vibration on Compressor bearings High High
BN 3500 (Vib)
- 231-XT-5134A1/A2
Radial Vibration on Compressor bearings High High
BN 3500 (Vib)
-
231-TE-5139A1A/2A//3A
Thrust bearing temperature high high
BN 3500 (Temp)
- 231-TE-5140A1A/2A/3A
Thrust bearing temperature high high
BN 3500 (Temp)
231-SE-5061A1/2/3 (77NH-1÷3)
HP Shaft Speed – Safety System
Control & Protection
231-SE-5063A1/2/3 (77NL-1÷3)
LP Shaft Speed – Safety System
Control & Protection
231-TE-5076A1 to 231-TE-5076A13 (TT-XD-1 to TT-XD-13)
Exhaust Thermocouple Control & Protection
TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTION
DOCUMENT CODE
SOM6629548SOM6629548SOM6629548SOM6629548
REVISION
4444
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE
PAGE MARKER
N/AN/AN/AN/A
SECURITY CODE
NNNN
ORIGINAL JOB
1800057180005718000571800057----58585858
SIZE
4444
LANGUAGE
AAAA
THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. . UNPUBLISHED WORK ©2012201220122012 Nuovo Nuovo Nuovo Nuovo Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.. . . . ALL RIGHTS RESERVED.
SHEET
31313131 of of of of 94949494
LOGIC SOFTWARE TAG JOB TAG(GE TAG) DESCRIPTION SYSTEM
L28FDT
231-BE-5061A1/A2/A3/A4 (28FD-2/3/10/11)
Loss of flame detected Control & Protection
L3SFLT - Control system fault UCS (Mark Vie) L4ATOMPU
R 231-TE-5158A1A/2A/3A
Atomizing Air Cooler Discharge Temp low low
Atomizing Air Cooler
L45FTT 231-XS-657 T Fire detected trip FF System 231-PDIT-5217A CE/CO Inlet Filter high high UCS (Mark VIe)
231-VE-5061A1/A2 (39V-1A/B)
HP Shaft Vibration high high BN 3500 (Vib)
231-VE-5062A1/A2 (39V-2A/B)
HP Shaft Vibration high high BN 3500 (Vib)
Table 10 Trip from Safety system LOGIC SOFTWARE
TAG JOB TAG(GE TAG) DESCRIPTION SYSTEM
(5ESD-R1)
Front panel ESD push button (pressurized trip)
UCS
(5ESD-R2)
Front panel ESD push button (depressurized trip) UCS
L5LESD1
231-HS-5254A (5ESD-1)
Turbo unit emergency shutdown button (depressurized trip)
Enclosure Turbine
L5LESD2
231-HS-5253A (5ESD-2)
Turbo unit emergency shutdown button (depressurized trip)
Enclosure Turbine
L63CO_TRP
231-PIT-5121A1/2/3 (96HG-1A/B/C)
Control oil header pressure low voting trip logic
Control Oil
L4BTLOSS 231-PDIT-5241A1/2/3 (96SV-1A/B/C)
Enclosure loss of ventilation trip Ventilation System
(L4PV) -
Depress. trip Notification from MKVIe
SIS
(L4T) - Trip Notification from MKVIe SIS
L6FGEX SIS fuel gas flow excessive trip (only during start-up)
Fuel Gas
231-SE-5061A1/2/3 (77NH-1÷3)
HP Shaft Speed – Safety System
Control & Protection
231-SE-5063A1/2/3 (77NL-1÷3)
LP Shaft Speed – Safety System
Control & Protection
L63ETH
231-PDIT-5067A1/A2/A3 (96EA-1A/B/C)
Exhaust Duct Back Pressure Control & Protection
L28FDT
231-BE-5061A1/A2/A3/A4 (28FD-2/3/10/11)
Loss of flame detected Control & Protection
L5cesd1
231-XS-700 A (CESD-1)
Customer ESD Signal PESD
L5cesd2
231-XS-700 B (CESD-2)
Customer ESD Signal PESD
TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTION
DOCUMENT CODE
SOM6629548SOM6629548SOM6629548SOM6629548
REVISION
4444
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE
PAGE MARKER
N/AN/AN/AN/A
SECURITY CODE
NNNN
ORIGINAL JOB
1800057180005718000571800057----58585858
SIZE
4444
LANGUAGE
AAAA
THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. . UNPUBLISHED WORK ©2012201220122012 Nuovo Nuovo Nuovo Nuovo Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.. . . . ALL RIGHTS RESERVED.
SHEET
32323232 of of of of 94949494
LOGIC SOFTWARE TAG JOB TAG(GE TAG) DESCRIPTION SYSTEM
231-AE 5241\A1/A2/A3 (45HD-1A/B/C)
Acc. Compart. Vent. Outlet Gas Detector high high
UCS (Mark VIeS)
231-AE 5242\A1/A2/A3 (45HD-2A/B/C)
Acc. Compart. Vent. Outlet Gas Detector high high
UCS (Mark VIeS)
TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTION
DOCUMENT CODE
SOM6629548SOM6629548SOM6629548SOM6629548
REVISION
4444
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE
PAGE MARKER
N/AN/AN/AN/A
SECURITY CODE
NNNN
ORIGINAL JOB
1800057180005718000571800057----58585858
SIZE
4444
LANGUAGE
AAAA
THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. . UNPUBLISHED WORK ©2012201220122012 Nuovo Nuovo Nuovo Nuovo Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.. . . . ALL RIGHTS RESERVED.
SHEET
33333333 of of of of 94949494
2.8 MAINTENANCE OVERRIDE IMPLEMENTATION DESCRIPTION Following is a functional description of the implementation for maintenance overrides required for single (1oo1) trip input devices to the MKVIe system. Maintenance override shall be enabled by operator from HMI. When the MKVIe receives the MOS enable signal from HMI, the MKVIe logic enables this function. The number of instruments under MOS will be transmitted to DCS via the DCS - MK VIe serial link. The MKVIe HMI is configured with a Maintenance Override selection screen which shows all of the field devices capable of being put on override. When the MKVIe receives the MOS enable signal from HMI, a transmitter selected to be overridden can be selected on the MKVIe screen through password protection. Once the transmitter input is selected, the trip from this input will be overridden in the logic and the MKVIe shown on HMI “GT MOS ON” indication shown on the MKVIe HMI This “GT MOS ON” indication should be maintained for the duration of the override. The MKVIe logic includes an interlock such that only one trip input for voting function may be overridden at a time (i.e. selection of a transmitter to override when another transmitter of the same voting function is already on override shall not be possible). While an input signal is on override, the trip function from that input will be temporarily inhibited for the duration of the maintenance activity. However, the logic should be configured to allow the alarm functionality to remain active during this time in order to allow testing of the device after maintenance and before removing the override (i.e. before return to normal service). A MOS repeating alarm is sent from the MKVIe to DCS via the serial link once every hour, to warn the plant operations personnel that a transmitter is on override. After confirmation that the individual device/signal is ready to be restored to normal operation, the MOS is cancelled (override is removed) by removing the MOS from the individual instrument (not by resetting the MOS switch). When the selector switch is moved to “cancel” the DCS will send a momentary “MOS Cancel” signal to MKVIe via the serial link.
TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTION
DOCUMENT CODE
SOM6629548SOM6629548SOM6629548SOM6629548
REVISION
4444
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE
PAGE MARKER
N/AN/AN/AN/A
SECURITY CODE
NNNN
ORIGINAL JOB
1800057180005718000571800057----58585858
SIZE
4444
LANGUAGE
AAAA
THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. . UNPUBLISHED WORK ©2012201220122012 Nuovo Nuovo Nuovo Nuovo Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.. . . . ALL RIGHTS RESERVED.
SHEET
34343434 of of of of 94949494
3 OPERATION MODES SELECTION Unit Operational Mode selection shall be performed by means of a software selector on UCS HMI called MASTER SELECTOR. The following operational modes are defined:
• OFF • CRANK • FIRE • AUTO • REMOTE • MANUAL
Only one mode can be selected or set at any time. Mode selection is possible only if the relevant permissive conditions are met as indicated below. Switching to AUTO and REMOTE is always possible; the only exception is the Off-Line Water Wash condition that locks the selector in CRANK. Switching from/to different modes is allowed only under specific conditions (see below paragraphs for details).
OFF mode OFF mode is automatically set upon system initialization (i.e. UCS power-up). Off Mode can only be selected by the operator when the GT has come to a complete stop. If the master selector is in OFF mode no kind of starting sequence can be run, because the machine is not ready to start and any kind of start command is ignored.
CRANK mode In CRANK mode the engine is allowed to complete crank phase only, reaching purge/firing speed: all other following sequencing phases can be then completed changing the Master Selector position. Switching to OFF is possible before start up is initiated. This Master Selector position also enables OFF LINE WATER WASH selection until start up is initiated (pushing START button). In case of Off-Line Water Wash sequence activation no other following sequence can be completed: Master Selector remains locked to “Crank” position until Water Wash sequence ends as a consequence of a normal stop or trip command.
FIRE mode In FIRE mode the ignition phase is allowed, the turbine can reach the “flame-on” status and the sequence stops to warm-up. It is possible to switch back to CRANK only before firing and to OFF before start up is initiated.
AUTO mode In AUTO mode the complete start-up procedure can be executed, bringing centrifugal compressor at minimum operating speed; after that load control are managed by external load set-point. It is possible to switch back to FIRE only if warm up is not ended yet, to CRANK before firing, to OFF before start up is initiated.
REMOTE mode REMOTE mode is equivalent to AUTO, but the start command is given by a remote system (i.e. the CMS) while the stop command can be generated both remotely and locally.
TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTION
DOCUMENT CODE
SOM6629548SOM6629548SOM6629548SOM6629548
REVISION
4444
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE
PAGE MARKER
N/AN/AN/AN/A
SECURITY CODE
NNNN
ORIGINAL JOB
1800057180005718000571800057----58585858
SIZE
4444
LANGUAGE
AAAA
THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. . UNPUBLISHED WORK ©2012201220122012 Nuovo Nuovo Nuovo Nuovo Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.. . . . ALL RIGHTS RESERVED.
SHEET
35353535 of of of of 94949494
4 AUXILIARIES SEQUENCING
4.1 MINERAL LUBE OIL
4.1.1 DEVICE SUMMARY DEVICE NAME CUSTOMER TAG DESCRIPTION TL-1 C-231-001A-TK2 LUBE OIL TANK (ACCESSORY BASE) PL-1 C-231-001A-P5 MAIN LUBE OIL PUMP PL-2 C-231-001A-P6 AUXILIARY LUBE OIL PUMP PL-3 C-231-001A-P7 EMERGENCY LUBE OIL PUMP 88QA-1 C-231-001A-P6-M AUXILIARY LUBE OIL PUMP MOTOR 88QE-1 C-231-001A-P7-M EMERGENCY LUBE OIL PUMP MOTOR FL-1A/B C-231-001A-F13A/B LUBE OIL DUPLEX FILTERS 96QL1 231-LIT-5086A LUBE OIL TANK LEVEL LT-TH-1A 231-TE-5159A1A LUBE OIL HEADER TEMPERATURE LT-TH-1B 231-TE-5159A2A LUBE OIL HEADER TEMPERATURE LT-TH-1C 231-TE-5159A3A LUBE OIL HEADER TEMPERATURE LT-BT1D 231-TE-5097A THRUST BRG. #1 DRAIN OIL TEMPERATURE LT-BID 231-TE-5098A JOURNAL BRG. #1 DRAIN OIL TEMPERATURE LT-B2D 231-TE-5099A JOURNAL BRG. #2 DRAIN OIL TEMPERATURE LT-B3D 231-TE-5100A JOURNAL BRG. #3 DRAIN OIL TEMPERATURE LT-B4D 231-TE-5101A JOURNAL/THRUST BRG.#4 DRAIN OIL TEMP. --- 231-PIT-5133A1 LUBE OIL HEADER PRESSURE --- 231-PIT-5133A2 LUBE OIL HEADER PRESSURE --- 231-PIT-5133A3 LUBE OIL HEADER PRESSURE 96QQ-1 231-PDIT-5094A LUBE OIL FILTER DIFF. PRESSURE 96QA-1 231-PIT-5091A LUBE OIL PUMP DISCHARGE PRESSURE LT-OT-1 231-TE-5088AA LUBE OIL TANK TEMPERATURE 96QV-1A/B/C 231-PDIT-5087A1/A2/A3 LUBE OIL TANK PRESSURE
4.1.2 SOFTWARE DESCRIPTION Auxiliary pump logic Request during unit startup During startup, if permissive from process is detected (tertiary seal header pressure not low), the auxiliary pump starts when the turbine start sequence is activated. It continues to operate until the HP shaft reaches minimum operating speed (L14HSX). From this point, the main mechanical lube oil pump will provide the necessary oil pressure. The pump can also be started if one of the following conditions is verified: � Process hydraulic oil request Request during normal operation When HP shaft is above minimum operating speed, the auxiliary pump starts if one of the following conditions is verified for more than 2.5 s: � The lube oil header pressure is detected low by 231-PIT-5133A1, 231-PIT-5133A2, 231-PIT-5133A3 � The lube oil pumps discharge pressure is detected low. (96QA-1 (231-PIT-5091A) ). During normal operation, when auxiliary pump start is detected by 52QA-1 (231- XS-100I), alarm is generated.
TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTION
DOCUMENT CODE
SOM6629548SOM6629548SOM6629548SOM6629548
REVISION
4444
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE
PAGE MARKER
N/AN/AN/AN/A
SECURITY CODE
NNNN
ORIGINAL JOB
1800057180005718000571800057----58585858
SIZE
4444
LANGUAGE
AAAA
THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. . UNPUBLISHED WORK ©2012201220122012 Nuovo Nuovo Nuovo Nuovo Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.. . . . ALL RIGHTS RESERVED.
SHEET
36363636 of of of of 94949494
Stop during normal operation If, during normal operation, the pump has been started, detected by 52QA-1 (231- XS-100I), the pump remains running also if starting conditions are reset. Operator from HMI or from MCC can stop it manually. Request during shutdown After a unit shutdown, the auxiliary pump is started when the HP shaft decreases below the minimum operating speed. The pump remains running till the cool down is completed (L62CD). Manual control If lube oil tank level is not detected low by 96QL1 (231-LIT-5086A), auxiliary pump can be manually started. If manual operation is de-selected, the pump return to automatic control and can be stopped as described above. Emergency pump logic The emergency pump provides lube oil pressure in case of failure of auxiliary pump. It is requested to run each time the lube oil pressure is detected low by median value of 231-PIT-5133A1, 231-PIT-5133A2 and 231-PIT-5133A3. The emergency pump actually runs if one of the following enabled conditions is detected: � During normal operation: after start passed (L4) or if GT shaft is detected moving. � During cool down: the first time slice (15 min) of cool down, the emergency pump is always enabled.
Then it is periodically enabled starting with ON period of length 30s and an OFF period of length 3 min. This mode ends when cool down is ended (L62CD).
Once emergency pump has started, it stops when the pressure is detected normal by median value of 231-PIT-5133A1, 231-PIT-5133A2 and 231-PIT-5133A3. Alarms and trips � If emergency pump is detected running by feedback (52QE-1), alarm is generated. � <4> � If lube oil emergency pump overload is detected (49QE), alarm is generated Lube oil alarm and trips � If lube oil header temperature LT-TH-1A (231-TE-5159A1A), LT-TH-1B (231-TE-5159A2A), LT-TH-1C
(231-TE-5159A3A) is detected higher than High Alarm threshold, alarm is generated. � If lube oil header temperature LT-TH-1A (231-TE-5159A1A), LT-TH-1B (231-TE-5159A2A), LT-TH-1C
(231-TE-5159A3A) is detected very high by voting trip logic, trip and alarm are generated. � If lube oil header pressure which is median of 231-PIT-5133A1, 231-PIT-5133A2 and 231-PIT-5133A3, is
lower than the low threshold alarm is generated. Also alarm is generated after start-passed (L4) till cool down end.
� If lube oil header pressure is detected low low by 231-PIT-5133A1, 231-PIT-5133A2 and 231-PIT-5133A3 voting trip logic trip is generated. Also trip and alarm are generated if unit is running (L4).
� If lube oil pumps discharge pressure is detected low 96QA-1 (231-PIT-5091A), output is generated. Also alarm is generated after start-passed (L4) till cool down end.
� If lube oil filter differential pressure is detected high (96QQ-1 (231-PDIT-5094A) ) for more than 1 s, alarm is generated
� If lube oil tank level is detected high by 96QL1 (231-LIT-5086A), alarm is generated. � If lube oil tank level is detected low by 96QL1 (231-LIT-5086A), alarm is generated � If at least one bearing drain oil temperature is detected higher than its threshold, summarized alarm is
generated. Cooldown After the coast down, cooldown indicate the time period in which the lube oil is provided by using the auxiliary or the emergency pumps. Cooldown is enabled each time the flame is detected in combustion chamber (28FDX signal from MKVIe) resetting cooldown timer.
REVISED WHERE SHOWN <4>
TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTION
DOCUMENT CODE
SOM6629548SOM6629548SOM6629548SOM6629548
REVISION
4444
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE
PAGE MARKER
N/AN/AN/AN/A
SECURITY CODE
NNNN
ORIGINAL JOB
1800057180005718000571800057----58585858
SIZE
4444
LANGUAGE
AAAA
THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. . UNPUBLISHED WORK ©2012201220122012 Nuovo Nuovo Nuovo Nuovo Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.. . . . ALL RIGHTS RESERVED.
SHEET
37373737 of of of of 94949494
Cooldown timer starts counting after a coast down as soon as the GT shaft is detected at zero speed (L14HR) (signal from MKVIe). Cooldown will be completed after 10 hours. Cooldown end is detected by signal L62CD signal. The VTR-1 valve is actuated on the base LT-TH-1A (231-TE-5159A1A), LT-TH-1B (231-TE-5159A2A), LT-TH-1C (231-TE-5159A3A) signal; inside the software an internal PI controller is activated.
TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTION
DOCUMENT CODE
SOM6629548SOM6629548SOM6629548SOM6629548
REVISION
4444
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE
PAGE MARKER
N/AN/AN/AN/A
SECURITY CODE
NNNN
ORIGINAL JOB
1800057180005718000571800057----58585858
SIZE
4444
LANGUAGE
AAAA
THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. . UNPUBLISHED WORK ©2012201220122012 Nuovo Nuovo Nuovo Nuovo Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.. . . . ALL RIGHTS RESERVED.
SHEET
38383838 of of of of 94949494
4.2 OIL VAPOUR SEPARATOR
4.2.1 DEVICE SUMMARY DEVICE NAME CUSTOMER TAG DESCRIPTION PDS-1 C-231-001A-F18 MINERAL OIL VAPOUR SEPARATOR QV-1 C-231-001A-BL2A MAIN VAPOUR EXTRACTOR QV-2 C-231-001A-BL2B AUXILIARY VAPOUR EXTRACTOR
88QV-1 C-231-001A-BL2A-M MAIN MINERAL OIL VAPOUR SEPARATOR FAN MOTOR
88QV-2 C-231-001A-BL2B-M AUXILIARY MINERAL OIL VAPOUR SEPARATOR FAN MOTOR
4.2.2 SOFTWARE DESCRIPTION Oil vapor separator fan sequence Two vapor separator fan motors are provided: Fan selection (main, auxiliary) is done by HMI dedicated pushbuttons, normally when both fans are stopped. Selection can be changed, also if main fan is running. At changeover, the new selected main fan starts immediately; the deselected fan continues to run for 10 seconds, then it is stopped. This changeover sequence doesn't activate auxiliary fan running alarm. If changeover is done when both fans are running or both are stopped, nothing changes except the selection. Manual fans command If all start permissive conditions are verified and all cutoffs conditions are not verified, each fan can be manually started and stopped. The main lube oil vapor separator fan motor is started when the flame is detected in the combustion chambers. The fan continues to run until the cooldown sequence is completed (L62CD). The fan is also started if the following conditions are all verified: � Lube oil heater ON command � Normal temperature in oil tank. Oil vapor separator fan manual operation When fan extractor is not required running, the lube oil vapor separator fan motor 88QV-1 can be manually started and stopped. Lube oil tank pressure alarms and trips If lube oil tank pressure is detected high 96QV-1A/B/C (231-PDIT-5087A1/A2/A3), alarm is generated and the auxiliary vapor separator fan motor is started. If lube oil tank pressure is detected very high (trip level) by voting logic 96QV-1A/B/C (231-PDIT-5087A1/A2/A3), trip and alarm are generated.
TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTION
DOCUMENT CODE
SOM6629548SOM6629548SOM6629548SOM6629548
REVISION
4444
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE
PAGE MARKER
N/AN/AN/AN/A
SECURITY CODE
NNNN
ORIGINAL JOB
1800057180005718000571800057----58585858
SIZE
4444
LANGUAGE
AAAA
THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. . UNPUBLISHED WORK ©2012201220122012 Nuovo Nuovo Nuovo Nuovo Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.. . . . ALL RIGHTS RESERVED.
SHEET
39393939 of of of of 94949494
4.3 LUBE OIL HEATER
4.3.1 DEVICE SUMMARY DEVICE NAME CUSTOMER TAG DESCRIPTION 23QT-1 C-231-001A-H5A LUBE OIL ELECTRIC HEATER 23QT-2 C-231-001A-H5B LUBE OIL ELECTRIC HEATER 23QT-3 C-231-001A-H5C LUBE OIL ELECTRIC HEATER
49QT-1 231-TSHH-5085A LUBE OIL HEATER CUT-OUT SIGNAL TO MARKVIE
49QT-2 231-TSHH-5086A LUBE OIL HEATER CUT-OUT SIGNAL TO MARKVIE
49QT-3 231-TSHH-5087A LUBE OIL HEATER CUT-OUT SIGNAL TO MARKVIE
4.3.2 SOFTWARE DESCRIPTION The unit it’s also equipped with 23QT1/2/3 lube oil heaters. The purpose of lube oil heater system is to provide a correct viscosity of mineral lube oil acting on its temperature. To provide heater start/stop commands, the system is equipped with the temperature element LT-OT-1 (231-TE-5088AA). Heater cutout logic Cutout conditions for lube oil heater on command auxiliary signal are listed below: � Lube oil tank level low 96QL1 (231-LIT-5086A) � Flame detected (L28FDX) � Over-temperature detected by all lube oil tank heaters temperature switches 49QT-1/2/3 (231-TSHH-
5085A/5086A/5087A) � Each heater is then singularly cutout if the relative switch 49QT-1/2/3 (231-TSHH-5085A/5086A/5087A)
detects over-temperature. Also, cutout signal is repeated to MCC namely 4QT1_C (231-XS-720), 4QT2_C (231-XS-722), 4QT3_C (231-XS-723) if one of the following conditions is detected:
� Lube oil tank level low 96QL1 (231-LIT-5086A) � Over-temperature detected by the lube oil tank heater temperature switches 49QT-1/2/3 (231-TSHH-
5085A/5086A/5087A) � If over-temperature is detected by at least one lube oil tank heater temperature switches 49QT-1/2/3 (231-
TSHH-5085A/5086A/5087A) alarm is generated. Heater control logic If no cutout condition is active for the heater on, 23QT1/2/3 are started when the oil temperature is detected low by the low threshold on LT-OT-1 (231-TE-5088AA) temperature value. They are stopped when the oil temperature is detected moderate by the high threshold on LT-OT-1 (231-TE-5088AA). Between the two thresholds, 23QT-1/2/3 can be manually stopped down also by HMI pushbutton. If manual command is active, 23QT-1/2/3 can be started and stopped manually by HMI pushbutton. Also, if manual operation is active an alarm is generated. If oil temperature is below a low low threshold, an alarm is generated. It inhibits the turbine start and crank.
TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTION
DOCUMENT CODE
SOM6629548SOM6629548SOM6629548SOM6629548
REVISION
4444
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE
PAGE MARKER
N/AN/AN/AN/A
SECURITY CODE
NNNN
ORIGINAL JOB
1800057180005718000571800057----58585858
SIZE
4444
LANGUAGE
AAAA
THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. . UNPUBLISHED WORK ©2012201220122012 Nuovo Nuovo Nuovo Nuovo Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.. . . . ALL RIGHTS RESERVED.
SHEET
40404040 of of of of 94949494
4.4 LUBE OIL WATER COOLER
4.4.1 DEVICE SUMMARY
DEVICE NAME CUSTOMER TAG DESCRIPTION --- 231-TY-5159A VTR-1 THERMOSTATIC VALVE
CONTROL I TO P CONVERTOR VTR-1 231-TCV-5159A LUBE OIL THERMOSTATIC VALVE
4.4.2 SOFTWARE DESCRIPTION Start-Up and Normal Operation The Lube Oil Temperature Regulator Valve VTR-1 (231-TCV-5159A) is enabled to control (set point=55°C) the lube oil header temperature LT-TH-1A (231-TE-5159A1A), LT-TH-1B (231-TE-5159A2A), LT-TH-1C (231-TE-5159A3A) at the beginning of the Start-up sequence, just after the Emergency Auxiliaries Check, and it is disabled and close at the end of the cool-down subsequently to the stoppage of the Lube Oil Auxiliary Pump 88QA-1(C-231-001A-P6-M). 231-TCV-5159A (VTR-1) valve will be controlled by MKVIE through 4-20mA command to I/P converter 231-TY-5159A. Manual Operation This is a “One State Auxiliary”, manual mode is not permitted at all.
TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTION
DOCUMENT CODE
SOM6629548SOM6629548SOM6629548SOM6629548
REVISION
4444
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE
PAGE MARKER
N/AN/AN/AN/A
SECURITY CODE
NNNN
ORIGINAL JOB
1800057180005718000571800057----58585858
SIZE
4444
LANGUAGE
AAAA
THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. . UNPUBLISHED WORK ©2012201220122012 Nuovo Nuovo Nuovo Nuovo Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.. . . . ALL RIGHTS RESERVED.
SHEET
41414141 of of of of 94949494
4.5 CONTROL OIL
4.5.1 DEVICE SUMMARY DEVICE NAME CUSTOMER TAG DESCRIPTION 65NV-1 231-FCV-5124A NOZZLE CONTROL SERVO VALVE 90TV-1 231-FCV-5125A TURBINE IGV ACTUATION 96TV-1 231-ZT-5125A1 TURBINE IGV POSITION 96TV-2 231-ZT-5125A2 TURBINE IGV POSITION 96NC-1 231-ZT-5124A1 TURBINE 2ND STAGE NOZZLES POSITION 96NC-2 231-ZT-5124A2 TURBINE 2ND STAGE NOZZLES POSITION 20HD-1 231-XX-5122A CONTROL OIL TRIP 20HD-2 231-XX-5123A CONTROL OIL TRIP 96HG-1A 231-PIT-5121A1 CONTROL OIL HEADER PRESS. 96HG-1B 231-PIT-5121A2 CONTROL OIL HEADER PRESS. 96HG-1C 231-PIT-5121A3 CONTROL OIL HEADER PRESS.
4.5.2 SOFTWARE DESCRIPTION Control oil pressure triple redundant transmitters validation (TMR) Because of this is a critical loop, TMR architecture requires triple redundancy of measurements. The three signals are median selected so that a single measurement failure is distinguished from system fails. The selected value, A63HG_W, is used for succeeding elaborations. If measurements spread is higher than maximum spread allowed K63HG_FLT for more than K63HGL_SENSR (typically 2 s), alarm L63HGL_SENSR is generated. Control oil pressure triple redundant switches (mixt) validation (TMR) Starting at ignition phase during normal operation (L4=TRUE), if one of the three switches detects trip, but trip is not detected for more than K63HGL_SENSR (typically 2 s), alarm L63HGL_SENSR is generated. In case of mixt instrumentation, same logic apply with one switch reading substituted by condition L63HG1_L, corresponding to the transmitter signal below trip level (K63HGT). Control oil excessively low pressure (critical) Excessively low pressure is detected: � Transmitters: 2oo3 voting of (L63HGL1_W, l26hg2l, l26hg3l). If control oil pressure is detected excessively low, signal L63HGL is generated. Also, trip L63CO_TRP is generated after ignition phase during normal operation (L4=TRUE) and alarm L63HGL_ALM is generated starting at ignition (L2TVX). The transmitters 231-PIT-5121A1/A2/A3 (96HG-1A/B/C) are wired to MarkVIeS and when 2oo3 sensors detect a low-low condition, a trip condition is generated. Trip system healthy monitoring Fuel valves and variable geometries are driven to safe position by de-energizing 20HD-1 valve. This happens immediately when a trip is detected or at flameout in case of shutdown. The de-energizing of 20HD-1 must assure a rapid decrease of control oil pressure. If, elapsed one second from a trip, control oil pressure is not below trip level K63HGT, alarm L86HD_ALM is generated and the unit becomes not ready to start through L86HD latched signal resettable by master reset (L86MR1). The actuation of the 20HD-1 and 20HD-2 is done from MarkVIeS
TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTION
DOCUMENT CODE
SOM6629548SOM6629548SOM6629548SOM6629548
REVISION
4444
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE
PAGE MARKER
N/AN/AN/AN/A
SECURITY CODE
NNNN
ORIGINAL JOB
1800057180005718000571800057----58585858
SIZE
4444
LANGUAGE
AAAA
THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. . UNPUBLISHED WORK ©2012201220122012 Nuovo Nuovo Nuovo Nuovo Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.. . . . ALL RIGHTS RESERVED.
SHEET
42424242 of of of of 94949494
4.6 HYDRAULIC OIL
4.6.1 DEVICE SUMMARY
DEVICE NAME CUSTOMER TAG DESCRIPTION PH-1 C-231-001A-P2 HYDRAULIC OIL MAIN PUMP PH-2 C-231-001A-P3 HYDRAULIC OIL AUXILIARY PUMP 88HQ C-231-001A-P3-M HYDRAULIC OIL AUXILIARY PUMP MOTOR FH1-1/2 C-231-001A-F8A/B HYDRAULIC OIL DUPLEX FILTERS 96HQ-1 231-PIT-5114A HYDRAULIC OIL HEADER LOW PRESSURE 96HF-1 231-PDIT-5113A HYDRAULIC OIL FILTERS HIGH DIFF. PRESS. 33HR-1 231-ZSL-5119A HYD. RATCHET VALVE POSITION CLOSED 20CS-1 231-FV-5114A HYD. RATCHET SELF-SEQUENCING VALVE
4.6.2 SOFTWARE DESCRIPTION Auxiliary pump logic Cutout condition If lube oil header pressure is not detected normal by 231-PIT-5133A1, 231-PIT-5133A2 and 231-PIT-5133A3, the hydraulic pump requests described below is cutout. When unit is stopped (L14HR), if the cutout condition is active for more than 10s from hydraulic pump start request, alarm is generated. When unit is running, if the cutout condition is active, alarm is generated. In case of lube oil pressure low voting trip by 231-PIT-5133A1, 231-PIT-5133A2 and 231-PIT-5133A3, cutout to MCC is generated. Request during unit startup If cutout condition is not active, during startup the auxiliary pump starts when the turbine start sequence is activated. It continues to operate until the HP shaft reaches minimum operating speed. From this point, the main mechanical hydraulic oil pump will provide the necessary oil pressure. Request during normal operation When HP shaft is above minimum operating speed, if cutout condition is not active, the auxiliary pump starts if Hydraulic oil pressure detected low by pressure transmitter 96HQ-1 (231-PIT-5114A). During normal operation when hydraulic pump start detected by 52HQ, alarm is generated. Stop during normal operation If during normal operation the pump gets started, detected by 52HQ, the pump remains running, also when the starting condition is reset. Operator from HMI or MCC can stop it manually. Request during shutdown If cutout condition is not active, when a normal shutdown occurs, the auxiliary pump is started when the HP shaft decreases below the minimum operating speed. The pump will keep running till the master relay (L4) is de-energized. If emergency shutdown (trip) is detected, L4 drop down and consequently the hydraulic pump is not started. Manual control If cutout condition is not active, auxiliary pump can be manually started. If manual operation is deselected, the pump return to automatic control and can be stopped as described above.
TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTION
DOCUMENT CODE
SOM6629548SOM6629548SOM6629548SOM6629548
REVISION
4444
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE
PAGE MARKER
N/AN/AN/AN/A
SECURITY CODE
NNNN
ORIGINAL JOB
1800057180005718000571800057----58585858
SIZE
4444
LANGUAGE
AAAA
THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. . UNPUBLISHED WORK ©2012201220122012 Nuovo Nuovo Nuovo Nuovo Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.. . . . ALL RIGHTS RESERVED.
SHEET
43434343 of of of of 94949494
Alarms logic If hydraulic oil pressure is detected low by 96HQ-1 (231-PIT-5114A), for more than 3s, alarm is generated. Alarm is generated if all the following conditions are verified: � Above crank speed (L14HM) � After start passed and before shutdown (L4) If hydraulic oil filter differential pressure is detected high by 96HF-1 (231-PDIT-5113A) for more than 1s, alarm is generated.
TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTION
DOCUMENT CODE
SOM6629548SOM6629548SOM6629548SOM6629548
REVISION
4444
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE
PAGE MARKER
N/AN/AN/AN/A
SECURITY CODE
NNNN
ORIGINAL JOB
1800057180005718000571800057----58585858
SIZE
4444
LANGUAGE
AAAA
THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. . UNPUBLISHED WORK ©2012201220122012 Nuovo Nuovo Nuovo Nuovo Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.. . . . ALL RIGHTS RESERVED.
SHEET
44444444 of of of of 94949494
4.7 STARTING
4.7.1 DEVICE SUMMARY DEVICE NAME CUSTOMER TAG DESCRIPTION 33CS-1 231-ZSL-5181A STARTING CLUTCH POSITION – ENGAGED 20TU-1 231-XX-5181A TORQUE CONVERTER OIL DRAIN 88CR-1 C-231-001A-P8-M STARTING MOTOR PS-1 C-231-001A-P8 CHARGE PUMP FOR TORQUE CONVERTER
4.7.2 SOFTWARE DESCRIPTION Hydraulic ratchet interface logic When the unit is ready to crank, hydraulic ratchet system energizes the starting clutch solenoid 20CS-1 (231-FV-5114A). If the starting clutch is not detected engaged within 10 seconds, alarm is generated. The turbine shaft breakaway is helped by hydraulic ratchet system that is stopped as soon as shaft moves. 88CR-1 command permissive � Auxiliaries ready to crank � Loss of feedback event (~l52cr) elapsed from more than 20s, detected by 52CR-1 (231-XS-515I) signal. 88CR-1 turn-on command logic When starting clutch is detected engaged by 33CS-1 (231-ZSL-5181A) , cranking motor 88CR-1 is started through 4CR_1A (231-XS-515R) signal. If motor feedback from MCC 52CR-1 (231-XS-515I) is not detected within 2 seconds, trip and alarm are generated (sequence aborted). If motor feedback is detected but HP shaft doesn't break away (L14HR) within 30 seconds, trip and alarm are generated (sequence aborted). Cranking speed logic After shaft break away, when the minimum cranking speed is achieved, the torque converter oil drain valve 20TU-1 (231-XX-5181A) is opened, in order to reduce the torque and to maintain the specified speed to accomplish purge, ignition and warm-up steps. Signal OPENING is enabled by L4 to avoid the opening of the valve during coast down. The valve will be closed again after warm-up step completes, in order to have the maximum torque for accelerating phase. If motor feedback 52CR-1 (231-XS-515I) or clutch engaged limit switch 33CS-1 (231-ZSL-5181A) signals are lost, trip and alarm are generated. Alarm and trip are enabled below accelerating speed and are disabled above the operative speed and in case of trip. 88CR-1 turn-off logic After warm-up sequence, unit accelerates to full speed. At approx. 50÷60% of rating speed, the inversion of the torque on starting clutch causes its mechanical disengagement (the turbine can sustain itself). This condition is detected by 33CS-1 (231-ZSL-5181A) limit switch signal and the cranking motor is turned off. The motor is anyway turned off if HP shaft speed is above self-sustaining speed (60%). and above operative speed. If starting clutch doesn't disengage when the HP shaft speed is above the minimum operating speed, trip and alarm are generated. Motor turn-off is also achieved if one of the following conditions is verified: � system trip � unit trip � unit shutdown
TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTION
DOCUMENT CODE
SOM6629548SOM6629548SOM6629548SOM6629548
REVISION
4444
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE
PAGE MARKER
N/AN/AN/AN/A
SECURITY CODE
NNNN
ORIGINAL JOB
1800057180005718000571800057----58585858
SIZE
4444
LANGUAGE
AAAA
THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. . UNPUBLISHED WORK ©2012201220122012 Nuovo Nuovo Nuovo Nuovo Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.. . . . ALL RIGHTS RESERVED.
SHEET
45454545 of of of of 94949494
4.8 HYDRAULIC RATCHETING
4.8.1 DEVICE SUMMARY DEVICE NAME CUSTOMER TAG DESCRIPTION PH-3 C-231-001A-P4 RATCHET PUMP 88HR C-231-001A-P4-M HYDRAULIC RATCHET MOTOR FH-2 C-231-001A-F9 HYDRAULIC RATCHET OIL FILTER 43HR 231-HS-5109A HYDRAULIC RATCHET PUMP MOTOR TEST
33HR-1 231-ZSL-5119A HYDR. RATCHET VALVE POSITION – CLOSED
20CS-1 231-FV-5114A HYDRAULIC RATCHET SELF SEQUENCING VALVES
33CS-1 231-ZSL-5181A STARTING CLUTCH POSITION – ENGAGED
4.8.2 SOFTWARE DESCRIPTION The sequence described is used to describe ratchet pump motor (88HR) start command (4HR1) and starting clutch engaging command 20CS-1 (231-FV-5114A). The two ratcheting commands are generated at the same time by the same logic. The clutch engaged is detected by limit switch 33CS-1 (231-ZSL-5181A) signal that cause the cranking motor to start. Push button 43HR (231-HS-5109A) is installed to provide manual start of motor 88HR. Ratcheting commands cutout � Lube oil pressure low voting trip logic � HP shaft control speed signal loss � HP shaft above crank speed Unit start-up ratcheting sequence During the unit starting sequence, if no cutout and all permissive conditions verified, the ratcheting begin as soon as the ready to crank is detected. It continues to operate until the HP shaft speed is detected. Ratcheting cycles during cooldown During a stop sequence, the ratchet pump is started 60 seconds after the HP shaft is detected at zero speed by L14HR; independently from the state of, the pump remains running and rotating the shaft until the 33HR-1 (231-ZSL-5119A) limit switch drop down delayed of 2s is detected. At this point the pump is kept stopped for 180 s, and then the cycle is repeated. Cooldown ratcheting cycles are stopped when cooldown sequence is completed. Manual ratcheting (Jogging) When GT is stopped, a ratcheting cycle can be started manually (jogging) acting on the local push-button mounted on the ratchet pump skid 43HR (231-HS -5109A) or by HMI push button. Note that the local push button has to be closed for more than 2 s to activate the jogging command. Usually jogging is required after cooldown: as lube oil header pressure low cutout condition (L63QT) is detected, jogging command causes first the lube oil emergency pump starting, and then, when the cutout condition is reset, a jogging cycle. As for cooldown ratcheting, a jogging cycle stops 2s after the drop down of hydraulic ratchet limit switch (33HR-1 (231-ZSL-5119A) ) Alarms, trips and monitoring If, during cooldown ratcheting, limit switch (33HR-1 (231-ZSL-5119A) ) is not detected for 6 minutes, alarm is generated. The alarm is disabled at the end of cooldown. • If ratcheting cycle is longer than 30s, alarm is generated.
TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTION
DOCUMENT CODE
SOM6629548SOM6629548SOM6629548SOM6629548
REVISION
4444
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE
PAGE MARKER
N/AN/AN/AN/A
SECURITY CODE
NNNN
ORIGINAL JOB
1800057180005718000571800057----58585858
SIZE
4444
LANGUAGE
AAAA
THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. . UNPUBLISHED WORK ©2012201220122012 Nuovo Nuovo Nuovo Nuovo Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.. . . . ALL RIGHTS RESERVED.
SHEET
46464646 of of of of 94949494
• If hydraulic ratchet motor overload is detected (49HR), alarm is generated. • Hydraulic ratchet pump running is detected (72HR) for monitoring purposes.
TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTION
DOCUMENT CODE
SOM6629548SOM6629548SOM6629548SOM6629548
REVISION
4444
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE
PAGE MARKER
N/AN/AN/AN/A
SECURITY CODE
NNNN
ORIGINAL JOB
1800057180005718000571800057----58585858
SIZE
4444
LANGUAGE
AAAA
THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. . UNPUBLISHED WORK ©2012201220122012 Nuovo Nuovo Nuovo Nuovo Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.. . . . ALL RIGHTS RESERVED.
SHEET
47474747 of of of of 94949494
4.9 BEARING METAL TEMPERATURE TURBINE BEARINGS
4.9.1 DEVICE SUMMARY DEVICE NAME CUSTOMER TAG DESCRIPTION BT-TA1-1A 231-TE-5061AA CASE BEARING 1 TEMP (THRUST ACTIVE) BT-TI1-1A 231-TE-5062AA CASE BEARING 1 TEMP (THRUST INACTIVE) BT-J1-1A 231-TE-5063AA CASE BEARING 1 TEMP (JOURNAL) BT-J1-2A 231-TE-5064AA CASE BEARING 1 TEMP (JOURNAL) BT-TA1-2A 231-TE-5066AA CASE BEARING 1 TEMP (THRUST ACTIVE) BT-TI1-2A 231-TE-5065AA CASE BEARING 1 TEMP (THRUST INACTIVE) BT-J2-1A 231-TE-5067AA CASE BEARING 2 TEMP (JOURNAL) BT-J2-2A 231-TE-5068AA CASE BEARING 2 TEMP (JOURNAL) BT-J3-1A 231-TE-5069AA CASE BEARING 3 TEMP (JOURNAL) BT-J3-2A 231-TE-5070AA CASE BEARING 3 TEMP (JOURNAL) BT-TA4-1A 231-TE-5073AA CASE BEARING 4 TEMP (THRUST ACTIVE) BT-TI4-1A 231-TE-5072AA CASE BEARING 4 TEMP (THRUST INACTIVE) BT-J4-1A 231-TE-5071AA CASE BEARING 4 TEMP (JOURNAL) BT-J4-2A 231-TE-5083AA CASE BEARING 4 TEMP (JOURNAL) BT-TA4-2A 231-TE-5074AA CASE BEARING 4 TEMP (THRUST ACTIVE) BT-TI4-2A 231-TE-5075AA CASE BEARING 4 TEMP (THRUST INACTIVE)
4.9.2 SOFTWARE DESCRIPTION One element of each bearing metal RTD is wired to the Bently Nevada Temperature Monitoring System and the temperature reading is compared to the alarm set-point. If measured temperature of individual elements exceeds its set-point, individual alarm is generated.
TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTION
DOCUMENT CODE
SOM6629548SOM6629548SOM6629548SOM6629548
REVISION
4444
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE
PAGE MARKER
N/AN/AN/AN/A
SECURITY CODE
NNNN
ORIGINAL JOB
1800057180005718000571800057----58585858
SIZE
4444
LANGUAGE
AAAA
THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. . UNPUBLISHED WORK ©2012201220122012 Nuovo Nuovo Nuovo Nuovo Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.. . . . ALL RIGHTS RESERVED.
SHEET
48484848 of of of of 94949494
COMPRESSOR BEARINGS
4.9.3 DEVICE SUMMARY DEVICE NAME CUSTOMER TAG DESCRIPTION
--- 231-TE-5133AA THERMOELEMENT ON COMPRESSOR JOURNAL BEARING
--- 231-TE-5134AA THERMOELEMENT ON COMPRESSOR JOURNAL BEARING
--- 231-TE-5135AA THERMOELEMENT ON COMPRESSOR JOURNAL BEARING
--- 231-TE-5136AA THERMOELEMENT ON COMPRESSOR JOURNAL BEARING
--- 231-TE-5139A1A THERMOELEMENT ON COMPRESSOR THRUST BEARING (ACTIVE)
--- 231-TE-5139A2A THERMOELEMENT ON COMPRESSOR THRUST BEARING (ACTIVE)
--- 231-TE-5139A3A THERMOELEMENT ON COMPRESSOR THRUST BEARING (ACTIVE)
--- 231-TE-5140A1A THERMOELEMENT ON COMPRESSOR THRUST BEARING (INACTIVE)
--- 231-TE-5140A2A THERMOELEMENT ON COMPRESSOR THRUST BEARING (INACTIVE)
--- 231-TE-5140A3A THERMOELEMENT ON COMPRESSOR THRUST BEARING (INACTIVE)
4.9.4 SOFTWARE DESCRIPTION Alarm and Trip logic:
� One element of each bearing metal RTD on the Compressor Journal Bearing (231-TE-5133AA, 231-TE-5134AA, 231-TE-5135AA and 231-TE-5136AA) is wired to the Bently Nevada Temperature Monitoring System and the temperature reading is compared to the alarm set-point. If measured temperature of individual elements exceeds its set-point, individual alarm is generated.
� For thermo elements on CC Thrust bearings Active side (231-TE-5139A1A, 231-TE-5139A2A and 231-TE-5139A3A) as well as for CC Thrust bearings Inactive side (231-TE-5140A1A, 231-TE-5140A2A and 231-TE-5140A3A) for HH temperature, Trip condition is initiated. The trip notification is sent to MarkVIe for time stamping.
TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTION
DOCUMENT CODE
SOM6629548SOM6629548SOM6629548SOM6629548
REVISION
4444
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE
PAGE MARKER
N/AN/AN/AN/A
SECURITY CODE
NNNN
ORIGINAL JOB
1800057180005718000571800057----58585858
SIZE
4444
LANGUAGE
AAAA
THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. . UNPUBLISHED WORK ©2012201220122012 Nuovo Nuovo Nuovo Nuovo Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.. . . . ALL RIGHTS RESERVED.
SHEET
49494949 of of of of 94949494
4.10 WHEELSPACES
4.10.1 DEVICE SUMMARY DEVICE NAME CUSTOMER TAG DESCRIPTION TT-WS1FI-1 231-TE-5079A1 WHEEL SPACE TEMP. 1st STAGE FWD INNER #1 TT-WS1FI-2 231-TE-5079A2 WHEEL SPACE TEMP. 1st STAGE FWD INNER #2 TT-WS1AI-1 231-TE-5082A1 WHEEL SPACE TEMP. 1st STAGE AFT INNER #1 TT-WS1AI-2 231-TE-5082A2 WHEEL SPACE TEMP. 1st STAGE AFT INNER #2
TT-WS2FI-1 231-TE-5080A1 WHEEL SPACE TEMP. 2nd STAGE FWD INNER #1
TT-WS2FI-2 231-TE-5080A2 WHEEL SPACE TEMP. 2nd STAGE FWD INNER #2
TT-WS2AI-1 231-TE-5081A1 WHEEL SPACE TEMP. 2nd STAGE AFT INNER #1 TT-WS2AI-2 231-TE-5081A2 WHEEL SPACE TEMP. 2nd STAGE AFT INNER #2
4.10.2 SOFTWARE DESCRIPTION Alarms and Shutdown logic There are single element thermocouples (TC) in each measurement location to monitor the wheel space temperature. For each measurement section, the average temperature is calculated by the two TC. If the average temperature exceeds the alarm level for more than 10s, a common alarm is generated. If alarm level is reached continuously for more than 24 hours, alarm signal is generated and shutdown sequence starts. If the average temperature exceeds the shutdown level for more than 10s, a common alarm is generated that cause shutdown sequence to start. Water Wash Permissive All of the average wheel space temperature values are compared against each other and the highest value is selected. This value is then compared to a started threshold, to provide water wash permissive signal.
TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTION
DOCUMENT CODE
SOM6629548SOM6629548SOM6629548SOM6629548
REVISION
4444
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE
PAGE MARKER
N/AN/AN/AN/A
SECURITY CODE
NNNN
ORIGINAL JOB
1800057180005718000571800057----58585858
SIZE
4444
LANGUAGE
AAAA
THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. . UNPUBLISHED WORK ©2012201220122012 Nuovo Nuovo Nuovo Nuovo Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.. . . . ALL RIGHTS RESERVED.
SHEET
50505050 of of of of 94949494
4.11 SEISMIC VIBRATION
4.11.1 DEVICE SUMMARY
DEVICE NAME CUSTOMER TAG DESCRIPTION
39V-1A 231-VE-5061A1 HP SHAFT VIBRATION 39V-1B 231-VE-5061A2 HP SHAFT VIBRATION 39V-2A 231-VE-5062A1 LP SHAFT VIBRATION 39V-2B 231-VE-5062A2 LP SHAFT VIBRATION
4.11.2 SOFTWARE DESCRIPTION The Seismic Vibration signals are wired to the BN3500 vibration monitoring system. Alarm and trip logic If one of sensor (39V-1A (231-VE-5061A1) 39V-1B (231-VE-5061A2), 39V-2A (231-VE-5062A1), 39V-2B (231-VE-5062A2) ) reaches alarm level for more than 5s, alarm is generated. If a sensor reaches trip level for more than 0.5s while a second sensor value is above alarm level, trip and alarm are generated. Inside each pair of sensors 39V-1A (231-VE-5061A1) 39V-1B (231-VE-5061A2) and 39V-2A (231-VE-5062A1), 39V-2B (231-VE-5062A2) ), vibration differential calculation is done. If the differential is higher than a threshold for more than 0.5s, alarm is generated. In case of unhealthy or disabled sensors, the relative signals are discarded and alarm/trip logic is modified as follows to maintain the reliability of operation (lowering availability):
� One sensor faulty or disabled: nothing changes except that only the enabled and healthy signals are taken into account. This is because of transmissibility of vibration between the two pairs: it assures that trip level on the first pair is sensed at least at alarm level on the second pair.
� Two sensors faulty or disabled: trip logic is based on only one sensor. If the two faulty or disabled sensors belong to the same pair, shutdown signal L39VD2 and L39VD2_ALM alarm are generated
Trip notification is hardwired from BN to MarkVIeS.
TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTION
DOCUMENT CODE
SOM6629548SOM6629548SOM6629548SOM6629548
REVISION
4444
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE
PAGE MARKER
N/AN/AN/AN/A
SECURITY CODE
NNNN
ORIGINAL JOB
1800057180005718000571800057----58585858
SIZE
4444
LANGUAGE
AAAA
THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. . UNPUBLISHED WORK ©2012201220122012 Nuovo Nuovo Nuovo Nuovo Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.. . . . ALL RIGHTS RESERVED.
SHEET
51515151 of of of of 94949494
4.12 MAGNETIC SPEED PICK-UP
4.12.1 DEVICE SUMMARY
DEVICE NAME CUSTOMER
TAG DESCRIPTION
77NH-1 231-SE-5061A1 HP SHAFT MAGNETIC SPEED PICKUP WIRED (TO MARKVIES)
77NH-2 231-SE-5061A2 HP SHAFT MAGNETIC SPEED PICKUP WIRED (TO MARKVIES)
77NH-3 231-SE-5061A3 HP SHAFT MAGNETIC SPEED PICKUP WIRED (TO MARKVIES)
77NL-1 231-SE-5063A1 LP SHAFT MAGNETIC SPEED PICKUP WIRED (TO MARKVIES)
77NL-2 231-SE-5063A2 LP SHAFT MAGNETIC SPEED PICKUP WIRED (TO MARKVIES)
77NL-3 231-SE-5063A3 LP SHAFT MAGNETIC SPEED PICKUP WIRED (TO MARKVIES)
77HT-1 231-SE-5062A1 HP SHAFT MAGNETIC SPEED PICKUP WIRED (TO MARKVIES) 77HT-2 231-SE-5062A2 HP SHAFT MAGNETIC SPEED PICKUP WIRED (TO MARKVIES) 77HT-3 231-SE-5062A3 HP SHAFT MAGNETIC SPEED PICKUP WIRED (TO MARKVIES) 77LT-1 231-SE-5064A1 LP SHAFT MAGNETIC SPEED PICKUP WIRED (TO MARKVIES)
77LT-2 231-SE-5064A2 LP SHAFT MAGNETIC SPEED PICKUP WIRED (TO MARKVIES)
77LT-3 231-SE-5064A3 LP SHAFT MAGNETIC SPEED PICKUP WIRED (TO MARKVIES)
4.12.2 SOFTWARE DESCRIPTION The median value of the magnetic pick-up signals for HP shaft 77NH-1(231-SE-5061A1), 77NH-2(231-SE-5061A2) and 77NH-3(231-SE-5061A3) as well as the median value of the magnetic pick-up signals for LP shaft 77NL-1(231-SE-5063A1), 77NL-2(231-SE-5063A2) and 77NL-3(231-SE-5063A3) are sent to Mark Vie for Turbine Control. The median value of the magnetic pick-up signals for HP shaft 77HT-1(231-SE-5062A1), 77HT-2(231-SE-5062A2) and 77HT-3(231-SE-5062A3) as well as the median value of the magnetic pick-up signals for LP shaft 77LT-1(231-SE-5064A1), 77LT-2(231-SE-5064A2) and 77LT-3(231-SE-5064A3) are sent to MarkVIeS and upon detection of High-high condition the gas turbine is tripped.
TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTION
DOCUMENT CODE
SOM6629548SOM6629548SOM6629548SOM6629548
REVISION
4444
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE
PAGE MARKER
N/AN/AN/AN/A
SECURITY CODE
NNNN
ORIGINAL JOB
1800057180005718000571800057----58585858
SIZE
4444
LANGUAGE
AAAA
THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. . UNPUBLISHED WORK ©2012201220122012 Nuovo Nuovo Nuovo Nuovo Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.. . . . ALL RIGHTS RESERVED.
SHEET
52525252 of of of of 94949494
4.13 COMBUSTION CHAMBER FLAME DETECTOR
4.13.1 DEVICE SUMMARY
DEVICE NAME CUSTOMER
TAG DESCRIPTION
28FD-2 231-BE-5061A1 COMBUSTION CHAMBER FLAME DETECTOR
28FD-3 231-BE-5061A2 COMBUSTION CHAMBER FLAME DETECTOR
28FD-10 231-BE-5061A3 COMBUSTION CHAMBER FLAME DETECTOR
28FD-11 231-BE-5061A4 COMBUSTION CHAMBER FLAME DETECTOR
4.13.2 SOFTWARE DESCRIPTION All 4 detectors 28FD-2 (231-BE-5061A1), 28FD-3 (231-BE-5061A2), 28FD-10 (231-BE-5061A3), 28FD-11 (231-BE-5061A4), are hardwired to MarkVIeS. If 3oo4 detectors do not detect flame inside the combustion chamber, the Gas Turbine is tripped.
TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTION
DOCUMENT CODE
SOM6629548SOM6629548SOM6629548SOM6629548
REVISION
4444
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE
PAGE MARKER
N/AN/AN/AN/A
SECURITY CODE
NNNN
ORIGINAL JOB
1800057180005718000571800057----58585858
SIZE
4444
LANGUAGE
AAAA
THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. . UNPUBLISHED WORK ©2012201220122012 Nuovo Nuovo Nuovo Nuovo Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.. . . . ALL RIGHTS RESERVED.
SHEET
53535353 of of of of 94949494
4.14 INTERFACES WITH BENTLY NEVADA VIBRATION MONITORING SYSTEM TURBINE BEARINGS
4.14.1 DEVICE SUMMARY DEVICE NAME CUSTOMER TAG DESCRIPTION XT-1X 231-XT-5063A1 NO CONTACT RADIAL VIBRATION (CASE BRG 1) XT-1Y 231-XT-5063A2 NO CONTACT RADIAL VIBRATION (CASE BRG 1) ZT-1 231-ZT-5061A1 NO CONTACT AXIAL DISPLACEMENT (CASE BRG 1) ZT-2 231-ZT-5061A2 NO CONTACT AXIAL DISPLACEMENT (CASE BRG 1) XPH 231-KT-5061A KEY PHASOR (CASE BRG 1) XT-2X 231-XT-5064A1 NO CONTACT RADIAL VIBRATION (CASE BRG 2) XT-2Y 231-XT-5064A2 NO CONTACT RADIAL VIBRATION (CASE BRG 2) XT-3X 231-XT-5065A1 NO CONTACT RADIAL VIBRATION (CASE BRG 3) XT-3Y 231-XT-5065A2 NO CONTACT RADIAL VIBRATION (CASE BRG 3) XT-4X 231-XT-5066A1 NO CONTACT RADIAL VIBRATION (CASE BRG 4) XT-4Y 231-XT-5066A2 NO CONTACT RADIAL VIBRATION (CASE BRG 4) ZT-3 231-ZT-5062A1 NO CONTACT AXIAL DISPLACEMENT (CASE BRG 4) ZT-4 231-ZT-5062A2 NO CONTACT AXIAL DISPLACEMENT (CASE BRG 4) XPL 231-KT-5062A KEY PHASOR (CASE BRG 4)
4.14.2 SOFTWARE DESCRIPTION
The NO Contact Radial Vibration, NO Contact Axial Displacement and Key-phasor signals are all wired to BN3500 Vibration Monitoring System. Alarm Logic:
� For high value of “NO Contact Radial Vibration” signals detected by any one of the sensors, a High
alarm is generated.
� For high value of “NO Contact Axial Displacement” signal detected by any one of the sensors, a High alarm is generated.
TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTION
DOCUMENT CODE
SOM6629548SOM6629548SOM6629548SOM6629548
REVISION
4444
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE
PAGE MARKER
N/AN/AN/AN/A
SECURITY CODE
NNNN
ORIGINAL JOB
1800057180005718000571800057----58585858
SIZE
4444
LANGUAGE
AAAA
THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. . UNPUBLISHED WORK ©2012201220122012 Nuovo Nuovo Nuovo Nuovo Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.. . . . ALL RIGHTS RESERVED.
SHEET
54545454 of of of of 94949494
COMPRESSOR BEARINGS
4.14.3 DEVICE SUMMARY DEVICE NAME CUSTOMER TAG DESCRIPTION
--- 231-XT-5133A1 RADIAL VIBRATION PROBE ON COMPRESSOR JOURNAL BEARING
--- 231-XT-5133A2 RADIAL VIBRATION PROBE ON COMPRESSOR JOURNAL BEARING
--- 231-XT-5134A1 RADIAL VIBRATION PROBE ON COMPRESSOR JOURNAL BEARING
--- 231-XT-5134A2 RADIAL VIBRATION PROBE ON COMPRESSOR JOURNAL BEARING
--- 231-ZT-5133A1 AXIAL DISPLACEMENT PROBE ON COMPRESSOR THRUST BEARING
--- 231-ZT-5133A2 AXIAL DISPLACEMENT PROBE ON COMPRESSOR THRUST BEARING
--- 231-ZT-5133A3 AXIAL DISPLACEMENT PROBE ON COMPRESSOR THRUST BEARING
4.14.4 SOFTWARE DESCRIPTION The NO Contact Radial Vibration and NO Contact Axial Displacement signals are all wired to BN3500 Vibration Monitoring System.
Alarm and Trip logic:
Radial Vibration:
� If 1oo2 probes [231-XT-5133A1 and 231-XT-5133A2] or [231-XT-5134A1 and 231-XT-5134A2] detects vibration corresponding H set-point, an alarm is generated. If vibration is HH then a Trip is initiated and a notification is sent to Mark Vie for Time stamping.
� If 2oo3 probes [231-ZT-5133A1, 231-ZT-5133A2 and 231-ZT-5133A3] detect axial displacement corresponding HH set-point, then a Trip is initiated and a notification is sent to Mark Vie for Time stamping.
TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTION
DOCUMENT CODE
SOM6629548SOM6629548SOM6629548SOM6629548
REVISION
4444
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE
PAGE MARKER
N/AN/AN/AN/A
SECURITY CODE
NNNN
ORIGINAL JOB
1800057180005718000571800057----58585858
SIZE
4444
LANGUAGE
AAAA
THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. . UNPUBLISHED WORK ©2012201220122012 Nuovo Nuovo Nuovo Nuovo Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.. . . . ALL RIGHTS RESERVED.
SHEET
55555555 of of of of 94949494
4.15 EXHAUST TEMPERATURE
4.15.1 DEVICE SUMMARY
DEVICE NAME CUSTOMER TAG DESCRIPTION
TT-XD-1 231-TE-5176A1 EXHAUST TEMPERATURE TT-XD-2 231-TE-5176A2 EXHAUST TEMPERATURE TT-XD-3 231-TE-5176A3 EXHAUST TEMPERATURE TT-XD-4 231-TE-5176A4 EXHAUST TEMPERATURE TT-XD-5 231-TE-5176A5 EXHAUST TEMPERATURE TT-XD-6 231-TE-5176A6 EXHAUST TEMPERATURE TT-XD-7 231-TE-5176A7 EXHAUST TEMPERATURE TT-XD-8 231-TE-5176A8 EXHAUST TEMPERATURE TT-XD-9 231-TE-5176A9 EXHAUST TEMPERATURE TT-XD-10 231-TE-5176A10 EXHAUST TEMPERATURE TT-XD-11 231-TE-5176A11 EXHAUST TEMPERATURE TT-XD-12 231-TE-5176A12 EXHAUST TEMPERATURE TT-XD-13 231-TE-5176A13 EXHAUST TEMPERATURE
4.15.2 SOFTWARE DESCRIPTION Alarm and trip logic
� When the mean value of the Exhaust Thermocouples is greater than or equal to High value, a cumulative alarm is generated.
� When the mean value of the Exhaust Thermocouples is greater than or equal to High High value, a
Trip is initiated.
TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTION
DOCUMENT CODE
SOM6629548SOM6629548SOM6629548SOM6629548
REVISION
4444
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE
PAGE MARKER
N/AN/AN/AN/A
SECURITY CODE
NNNN
ORIGINAL JOB
1800057180005718000571800057----58585858
SIZE
4444
LANGUAGE
AAAA
THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. . UNPUBLISHED WORK ©2012201220122012 Nuovo Nuovo Nuovo Nuovo Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.. . . . ALL RIGHTS RESERVED.
SHEET
56565656 of of of of 94949494
4.16 EXHAUST DUCT BACK PRESSURE
4.16.1 DEVICE SUMMARY
DEVICE NAME CUSTOMER TAG DESCRIPTION
96EA-1A 231-PDIT-5067A1 EXHAUST DUCT BACK PRESSURE 96EA-1B 231-PDIT-5067A2 EXHAUST DUCT BACK PRESSURE 96EA-1C 231-PDIT-5067A3 EXHAUST DUCT BACK PRESSURE
4.16.2 SOFTWARE DESCRIPTION Alarm and trip logic
� When the median value of the three transmitters 96EA-1A (231-PDIT-5067A), 96EA-1B (231-PDIT-5067B) and 96EA-1C (231-PDIT-5067C) reaches High threshold value an alarm is generated.
� When the median value reaches High High threshold value a Trip of the GT is started. � This logic is implemented in MarkVIeS
TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTION
DOCUMENT CODE
SOM6629548SOM6629548SOM6629548SOM6629548
REVISION
4444
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE
PAGE MARKER
N/AN/AN/AN/A
SECURITY CODE
NNNN
ORIGINAL JOB
1800057180005718000571800057----58585858
SIZE
4444
LANGUAGE
AAAA
THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. . UNPUBLISHED WORK ©2012201220122012 Nuovo Nuovo Nuovo Nuovo Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.. . . . ALL RIGHTS RESERVED.
SHEET
57575757 of of of of 94949494
4.17 WATER WASH
4.17.1 DEVICE SUMMARY DEVICE NAME CUSTOMER TAG DESCRIPTION
33ED-4 231-ZSL-5277A EXHAUST PLENUM DRAIN VALVE VA17-6 CLOSED
20TW-1 231-XX-5278A ON LINE WASHING WATER SUPPLY 20TW-2 231-XX-5277A OFF LINE WASHING WATER SUPPLY
4.17.2 SOFTWARE DESCRIPTION On line water wash sequence Cutout conditions � Turbine start sequence not ended � Compressor inlet temperature lower than the threshold 50°F. Selection logic If all cut-out condition are not verified, on-line water wash is selected by HMI pushbutton. Then, 3 seconds after the selection, the solenoid valve 20TW-1 (231-XX-5278A) is energized. Water wash is de-activated (and solenoid valve 20TW-1 (231-XX-5278A) is de-energized) whenever on line water wash is de-selected by pushbutton or a cut-out condition is verified. Alarms When the turbine start sequence is ended (L3), if the on line water wash pushbutton is selected while temperature cut-out condition is verified, alarm is generated. Off line water wash sequence Cut-out conditions � Master selector not in CRANK mode Selection logic: If cut-out condition is not active, off-line water wash is selected by HMI pushbutton. If sequence is not already active, off-line water wash is de-selected by HMI pushbutton. Activation enabling conditions: � Master selector in CRANK mode � HP shaft zero speed detected � Off line water wash selected Activation logic: If activation-enabling conditions are all verified, the water wash sequence is activated when the unit is started. Water wash cut-out: � Wheel spaces temperature high; � Master protective signal dropped down � Flame detected � HP shaft below crank speed.
TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTION
DOCUMENT CODE
SOM6629548SOM6629548SOM6629548SOM6629548
REVISION
4444
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE
PAGE MARKER
N/AN/AN/AN/A
SECURITY CODE
NNNN
ORIGINAL JOB
1800057180005718000571800057----58585858
SIZE
4444
LANGUAGE
AAAA
THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. . UNPUBLISHED WORK ©2012201220122012 Nuovo Nuovo Nuovo Nuovo Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.. . . . ALL RIGHTS RESERVED.
SHEET
58585858 of of of of 94949494
Water wash start: If all cutout conditions are not verified and water wash sequence is activated, IGV open command is generated and the cleaning solution intercept valve 20TW-2 (231-XX-5277A) is opened. Water wash stop: Once the water wash is started, it is stopped when the unit normal stop is detected. Alarms: When the water wash is selected, if wheel spaces temperature permissive is dropped down, alarm is generated. Start permissive condition: If limit switch 33ED-4 (231-ZSL-5277A) closed during starting sequence, alarm is generated and start permissive inhibited. This logic is implemented in MarkVIeS.
TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTION
DOCUMENT CODE
SOM6629548SOM6629548SOM6629548SOM6629548
REVISION
4444
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE
PAGE MARKER
N/AN/AN/AN/A
SECURITY CODE
NNNN
ORIGINAL JOB
1800057180005718000571800057----58585858
SIZE
4444
LANGUAGE
AAAA
THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. . UNPUBLISHED WORK ©2012201220122012 Nuovo Nuovo Nuovo Nuovo Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.. . . . ALL RIGHTS RESERVED.
SHEET
59595959 of of of of 94949494
4.18 VENTILATION
4.18.1 DEVICE SUMMARY DEVICE NAME CUSTOMER TAG DESCRIPTION FNVF1/2 C-231-001A-BL1A/B VENTILATION FANS
88BA-1/2 C-231-001A-BL1A/B-M MAIN & STAND-BY VENTILATION AIR FAN MOTOR
33ID-1 231-ZSH-5242A VENTILATION INLET DAMPER OPEN 33OD-1 231-ZSH-5243A ACCESS. COMP. VENTILATION OUTLET OPEN 33OD-2 231-ZSH-5244A TURBINE COMP. VENTILATION OUTLET OPEN 33OD-3 231-ZSH-5245A COUPL. COMP. VENTILATION OUTLET OPEN TT-BA-2A 231-TE-5241A1 GT COMPART. INTERNAL TEMP TT-BA-2B 231-TE-5241A2 GT COMPART. INTERNAL TEMP TT-BA-2C 231-TE-5241A3 GT COMPART. INTERNAL TEMP
96SV-1A 231-PDIT-5241A1 ENCLOSURE PRESSURE WITH RESPECT TO ATMOSPHERIC PRESSURE
96SV-1B 231-PDIT-5241A2 ENCLOSURE PRESSURE WITH RESPECT TO ATMOSPHERIC PRESSURE
96SV-1C 231-PDIT-5241A3 ENCLOSURE PRESSURE WITH RESPECT TO ATMOSPHERIC PRESSURE
TT-BA-3A/B/C 231-TE-5242A1/A2/A3 COUPL. COMP. INTERNAL TEMP.
45HD-1A/B/C 231-AE-5241A1/2/3 CATALYTIC GAS DETECTORS AT VENTILATION OUTLET
45HD-2A/B/C 231-AE-5242A1/2/3 CATALYTIC GAS DETECTORS AT VENTILATION OUTLET
4.18.2 SOFTWARE DESCRIPTION The ventilation system has a dual fan configuration driven by motors 88BA-1÷2. Under normal condition, only one fan, chosen by the operator as main, is operating, while the other, the auxiliary, is off. Limit switches are provided to monitor the compartment’s access doors fully close condition and also to monitor the fire dampers fully open condition. Median value of 96SV-1A/B/C (231-PDIT-5241A1/2/3) detects low differential pressure between inside and outside of Accessory-Turbine enclosure. These transmitters send the signal to SIS. If low differential pressure is detected, ventilation fan switch-over takes place; if already switched, shutdown of the GT occurs. Temperature elements are utilized to control turbine compartment outlet temperature (TT-BA-2A (231-TE-5241 A1) / TT-BA-2B (231-TE-5241 A2) / TT-BA-2C (231-TE-5241 A3)) and (TT-BA-3A (231-TE-5242 A1) / TT-BA-3B (231-TE-5242 A2) / TT-BA-3C (231-TE-5242 A3)) Ventilation Start permissive conditions: � Fire dampers fully open. Ventilation cutout conditions : � Turbine enclosure fire detected trip, detected by fire-fighting system interface signal 45FTT ; � Turbine enclosure Inergen discharged trip, detected by fire-fighting system interface signal 63CPD
(generated inside FF. In addition ventilation cut out signals are sent from SIS directly to MCC (4BA1_C, 4BA2_C). This redundancy ensures that the fans do not operate during fire or extinguishing action of Inergen. Main/Auxiliary selection and changeover Fan selection is done by HMI dedicated pushbuttons, normally when both fans are stopped. Selection can be
TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTION
DOCUMENT CODE
SOM6629548SOM6629548SOM6629548SOM6629548
REVISION
4444
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE
PAGE MARKER
N/AN/AN/AN/A
SECURITY CODE
NNNN
ORIGINAL JOB
1800057180005718000571800057----58585858
SIZE
4444
LANGUAGE
AAAA
THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. . UNPUBLISHED WORK ©2012201220122012 Nuovo Nuovo Nuovo Nuovo Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.. . . . ALL RIGHTS RESERVED.
SHEET
60606060 of of of of 94949494
changed, also if main fan is running. At changeover, the new selected main fan starts immediately; the deselected fan continues to run for 10 seconds, then it is stopped. This changeover sequence doesn't activate auxiliary fan running alarm. If changeover is done when both fans are running or both are stopped, nothing changes except the selection. If turbine compartment pressure detected by (96SV-1A/B/C (231-PDIT-5241A1/A2/A3)) is lower than the alarm threshold, then alarm is generated and ventilation fan is switched over from one to another. If already switched then shutdown occurs. This loop is wired to the SIS which generates command for the changeover. Auxiliary fan start requests: � Turbine enclosure temperature high alarm; � Turbine enclosure gas detected alarm, detected by gas detection system interface signal 45HTA ; (Gas Detection loop is in SIS). Also, in operative condition, from L4 pick-up to two hours after flameout, the following start condition is active: Accessory-Turbine compartment differential pressure low alarm, detected by median value of (96SV-1A/B/C (231-PDIT-5241A1/A2/A3)) Main fan command: Main fan starts as soon as turbine starting sequence is initiated if all conditions below are verified: � all start permissive conditions are verified � all cutoff conditions are not verified � Offline water wash not selected Main fan stops if at least one of the following conditions is verified: � After ventilation operative period (120 min) after flameout. � After L4 drop down, can be manually stopped by HMI dedicated pushbutton. Auxiliary fan command Auxiliary fan starts if the conditions below are all verified: � at least one of auxiliary fan start request is verified � all cutoffs conditions are not verified If no auxiliary fan start request is active, it stops when one of the following conditions is verified: � together with the main, after ventilation operative period � manually by HMI pushbutton � from MCC Manual fans command If all start permissive conditions are verified and all cutoffs conditions are not verified, each fan can be manually started and stopped. Alarms and trips logic
� If high temperature is detected by voting logic of sensors in turbine (TT-BA-2A (231-TE-5241 A1) / TT-BA-2B (231-TE-5241 A2) / TT-BA-2C (231-TE-5241 A3)) and coupling compartment (TT-BA-3A (231-TE-5242 A1) / TT-BA-3B (231-TE-5242 A2) / TT-BA-3C (231-TE-5242 A3)) alarm is generated.
� If high high temperature is detected by voting logic of sensors in turbine (TT-BA-2A (231-TE-5241 A1) / TT-BA-2B (231-TE-5241 A2) / TT-BA-2C (231-TE-5241 A3)) and coupling compartment (TT-BA-3A (231-TE-5242 A1) / TT-BA-3B (231-TE-5242 A2) / TT-BA-3C (231-TE-5242 A3)) trip is generated.
TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTION
DOCUMENT CODE
SOM6629548SOM6629548SOM6629548SOM6629548
REVISION
4444
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE
PAGE MARKER
N/AN/AN/AN/A
SECURITY CODE
NNNN
ORIGINAL JOB
1800057180005718000571800057----58585858
SIZE
4444
LANGUAGE
AAAA
THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. . UNPUBLISHED WORK ©2012201220122012 Nuovo Nuovo Nuovo Nuovo Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.. . . . ALL RIGHTS RESERVED.
SHEET
61616161 of of of of 94949494
� The gas detectors in the accessory and turbine compartment ventilation outlet are wired to
MarkVIeS. If 1oo3 detectors detect an LEL level of 5% an alarm is generated. During start-up, this results in an ‘Inhibit to Start’ condition. If 2oo3 detectors detect an LEL level of 10% a trip of the GT is activated.
� There are 3 H2S detectors in the Accessory compartment that are hardwired to MarkVIeS. Upon detection of High value of H2S, an alarm is generated.
� If at least one enclosure door is not closed alarm is generated. This signal is hardwired to the MarkVIeS. � If dampers are not fully open, detected by 33ID-1 (231-ZSH-5242A), 33OD-1 (231-ZSH-5243), 33OD-2
(231-ZSH-5244) and 33OD-3 (231ZSH-5245), alarms are generated. � If both 88BA-1 and 88BA-2 feedback signals are off for more than 30 seconds, alarm and normal
shutdown are generated
Start permissive condition � Ventilation inlet damper open. � Turbine, coupling and accessory compartment ventilation outlet dampers are open. � If high temperature is detected by voting logic of sensors in turbine and coupling compartment in
turbine compartment inhibit to start condition is generated. � If high level of gas is detected by voting logic of gas detectors in turbine and accessory compartment
in turbine compartment inhibit to start condition is generated.
TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTION
DOCUMENT CODE
SOM6629548SOM6629548SOM6629548SOM6629548
REVISION
4444
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE
PAGE MARKER
N/AN/AN/AN/A
SECURITY CODE
NNNN
ORIGINAL JOB
1800057180005718000571800057----58585858
SIZE
4444
LANGUAGE
AAAA
THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. . UNPUBLISHED WORK ©2012201220122012 Nuovo Nuovo Nuovo Nuovo Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.. . . . ALL RIGHTS RESERVED.
SHEET
62626262 of of of of 94949494
4.19 INLET AIR FILTRATION
4.19.1 DEVICE SUMMARY DEVICE NAME CUSTOMER TAG DESCRIPTION 88TA-1 C-231-001A-BL3A-M DUST EXTRACTOR FAN MOTOR 88TA-2 C-231-001A-BL3B-M DUST EXTRACTOR FAN MOTOR 88TA-3 C-231-001A-BL3C-M DUST EXTRACTOR FAN MOTOR TA-1 C-231-001A-BL3A DUST EXTRACTOR FAN TA-2 C-231-001A-BL3B DUST EXTRACTOR FAN TA-3 C-231-001A-BL3C DUST EXTRACTOR FAN 96TF-1A 231-PDIT-5231A1 TURBINE AIR INLET FILTER PRESS. CTRL 96TF-1B 231-PDIT-5231A2 TURBINE AIR INLET FILTER PRESS. CTRL 96TF-1C 231-PDIT-5231A3 TURBINE AIR INLET FILTER PRESS. CTRL 33AF-1 231-ZSL-5229A INLET FILTER INSPECTION DOOR CLOSED 45HF-1 231-AE-5229A1 INFRA RED GAS DETECTORS 45HF-2 231-AE-5229A2 INFRA RED GAS DETECTORS 45HF-3 231-AE-5229A3 INFRA RED GAS DETECTORS
4.19.2 SOFTWARE DESCRIPTION Alarms and trips logic : If inlet air filter differential pressure is detected high by median value of 96TF-1A (231-PDIT-5231/A1) , 96TF-1B (231-PDIT-5231/A2) and 96TF-1C (231-PDIT-5231/A3) for more than 2 s, alarm L63TF1_ALM is generated If inlet air filter differential pressure is detected high high by voting shutdown median value of 96TF-1A (231-PDIT-5231/A1) , 96TF-1B (231-PDIT-5231/A2) and 96TF-1C (231-PDIT-5231/A3) , shutdown signal and alarm signals are generated. In case of filter house inspection door closed detected by 33AF-1A (231-ZSL-5229A) , alarm is generated and permissive to start is given. This logic is implemented by SIS. If only one of the shutdown transmitter 96TF-1A (231-PDIT-5231/A1) , 96TF-1B (231-PDIT-5231/A2) and 96TF-1C (231-PDIT-5231/A3) detect high pressure for more than 60 s but the other two transmitters do not detect trip condition, alarm is generated. In case of pulse jet local panel failure detected 86PJ, alarm is generated. There are 3 Infra-Red Gas Detectors at the Air Inlet. These detectors are wired to the MarkVIeS. If 1oo3 detectors detect an LEL level of 5% an alarm is generated. If 2oo3 detectors detect an LEL level of 10% a trip of the GT is activated along with cut-out of the ventilation fans.
TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTION
DOCUMENT CODE
SOM6629548SOM6629548SOM6629548SOM6629548
REVISION
4444
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE
PAGE MARKER
N/AN/AN/AN/A
SECURITY CODE
NNNN
ORIGINAL JOB
1800057180005718000571800057----58585858
SIZE
4444
LANGUAGE
AAAA
THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. . UNPUBLISHED WORK ©2012201220122012 Nuovo Nuovo Nuovo Nuovo Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.. . . . ALL RIGHTS RESERVED.
SHEET
63636363 of of of of 94949494
4.20 FUEL GAS
4.20.1 DEVICE SUMMARY DEVICE NAME
CUSTOMER TAG DESCRIPTION
96FG-2A 231-PT-5005A1 INTER-STAGE FUEL GAS PRESSURE 96FG-2B 231-PT-5005A2 INTER-STAGE FUEL GAS PRESSURE 96FG-2C 231-PT-5005A3 INTER-STAGE FUEL GAS PRESSURE 90SR 231-FCV-5003A2 FUEL GAS STOP/SPEED RATIO VALVE ACTUATION TG-FG-1 231-TE-5006AA FUEL GAS SUPPLY TEMPERATURE 96FG-1 231-PIT-5003A FUEL GAS PRESSURE UPSTREAM VALVE 96SR-1 231-ZT-5003A1 FUEL GAS STOP/SPEED RATIO VALVE POSITION 96SR-2 231-ZT-5003A2 FUEL GAS STOP/SPEED RATIO VALVE POSITION 65GC 231-FCV-5004A2 FUEL GAS CONTROL VALVE ACTUATION 96GC-1 231-ZT-5004A1 FUEL GAS CONTROL VALVE POSITION 96GC-2 231-ZT-5004A2 FUEL GAS CONTROL VALVE POSITION 33VG-2 231-ZSL-5009A WARM-UP LINE VENT VALVE STATUS (CLOSED) 20VG-2 231-XX-5009A WARM-UP LINE VENT VALVE --- 231-PDT-5006A DIFFERENTIAL PRESSURE ACROSS FUEL GAS Y-STRAINER 96FG 231-PT-5005A FUEL GAS PRESSURE FOR INLET FLOW CALCULATION FG-1 231-TE-5005A1B FUEL GAS TEMPERATURE FOR INLET FLOW CALCULATION --- 231-TE-5005A1A FUEL GAS TEMPERATURE FOR INLET FLOW CALCULATION FG-2 231-TE-5005A2B FUEL GAS TEMPERATURE FOR INLET FLOW CALCULATION --- 231-TE-5005A2A FUEL GAS TEMPERATURE FOR INLET FLOW CALCULATION 96FG-1A 231-FIT-5005A1 FUEL GAS INLET FLOW TRANSMITTER 96FG-1B 231-FIT-5005A2 FUEL GAS INLET FLOW TRANSMITTER 20PG-1 23-XX-5006A PURGE VALVE 1 ACTUATION SOLENOID 20PG-2 23-XX-5008A PURGE VALVE 2 ACTUATION SOLENOID 20PG-3 23-XX-5007A PURGE LINE VENT ACTUATION SOLENOID 33PG-1 231-ZSH-5006A PURGE VALVE 1 OPEN CONDITION 33PG-2 231-ZSL-5006A PURGE VALVE 1 CLOSE CONDITION 33PG-3 231-ZSH-5008A PURGE VALVE 2 OPEN CONDITION 33PG-4 231-ZSL-5008A PURGE VALVE 2 CLOSE CONDITION 96PG-1 231-PIT-5007A FUEL GAS PURGE LINE PRESSURE TRANSMITTER
33PV-2 231-ZSH- 5007A LIMIT SWITCH TO INTER STAGE VENT VALVE OF FUEL GAS NOZZLE PURGE LINE
FTG-1A 231-TIT-5039 FUEL GAS TEMPERATURE UPSTREAM OF HEATER FTG-1B 231-TIT-5040 FUEL GAS TEMPERATURE UPSTREAM OF HEATER 96FTG 231-TIT-5041 FUEL GAS TEMPERATURE DOWNSTREAM OF HEATER 96FG-B 231-PT-5002A FUEL GAS PRESSURE FOR FLOW CLACULATION
--- 231-FT-5002A FUEL GAS FLOW TRANSMITTER FOR EXCESSIVE FUEL AT START-UP
20VG-1 231-XX-5010A FUEL GAS VENT SOLENOID VALVE
TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTION
DOCUMENT CODE
SOM6629548SOM6629548SOM6629548SOM6629548
REVISION
4444
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE
PAGE MARKER
N/AN/AN/AN/A
SECURITY CODE
NNNN
ORIGINAL JOB
1800057180005718000571800057----58585858
SIZE
4444
LANGUAGE
AAAA
THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. . UNPUBLISHED WORK ©2012201220122012 Nuovo Nuovo Nuovo Nuovo Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.. . . . ALL RIGHTS RESERVED.
SHEET
64646464 of of of of 94949494
4.20.2 SOFTWARE DESCRIPTION Following description is aplicable if ‘Fuel-Gas’ mode is activated. Vent valve control sequence: Vent valve opening is enabled if the following conditions are all verified: � Water wash off-line not active (~L83BW) � Flame not detected (~L28FDX) � Ignition command not detected (~L2TVX) � After start passed (L4) Conditions above select an enabling window between start passed and igniting events (see figure 1). Also, venting is disabled in case of off -line water wash sequence.
L4
L2TVX
L28FDX
Opening enabling window
Alarm enabling
Figure 1 - Vent valve enabling
If vent valve opening is enabled, open command (l20vg2) is generated if fuel gas temperature is less than K26FGL_VG2 (typically 4°F) above alarm threshold K2 6FGL. Then it closes again with a hysteresis of K26FGL_VG2_H (typically 8°F). After an opening command (l20vg2), if valve is not open, detected by ~l33vg2_c, within 3s, alarm L86VG2_ALM is generated. After a closing command (~l20vg2), if valve is not completely closed, detected by l33vg2_c, within K20VG2_C (typically 30s), alarm L86VG2_ALM is generated.
If valve is not completely closed, detected by ~l33vg2_c, alarm L33VG2_ALM is generated if at least one of the following conditions is true: � Water wash off-line active (L83BW) � Ignition active (L2TVX) � Before start passed and after K20VG2_C seconds from loss of L4. � After flame detection and before 1.1 * K20VG2_C seconds after loss of flame (~L28FDX). Conditions above select the complementary to the enabling opening window (see figure 1). Note that in case of trip event before ignition, the alarm is also disabled during maximum closing time (K20VG2_C) to allow vent valve to close. Alarms logic
� If the fuel gas pressure is low, detected by l63fgl, during ignition L2TVX or with flame detected L28FDX, alarm L63FGL_ALM is generated.
� If the fuel gas temperature ftg2 is lower than K26FGL (typically 86°F) during ignition L2TVX or with
flame detected L28FDX, then alarm L26FGL_ALM is generated.
TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTION
DOCUMENT CODE
SOM6629548SOM6629548SOM6629548SOM6629548
REVISION
4444
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE
PAGE MARKER
N/AN/AN/AN/A
SECURITY CODE
NNNN
ORIGINAL JOB
1800057180005718000571800057----58585858
SIZE
4444
LANGUAGE
AAAA
THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. . UNPUBLISHED WORK ©2012201220122012 Nuovo Nuovo Nuovo Nuovo Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.. . . . ALL RIGHTS RESERVED.
SHEET
65656565 of of of of 94949494
� If the fuel gas temperature ftg2 is higher than K26FGH (typically 284°F), alarm L26FGH_ALM is
generated.
� If Differential Pressure across Fuel Gas Y- Strainer is found high detected by 231-PDT-5306A, then a High alarm is generated.
Fuel Gas Heater Control Logic: Fuel Gas heater control will not be performed by Thyristor panels. The logic that would be followed to perform the ON / OFF command for the heaters and the logic that must be considered during GT starting is: Logic to be managed by DCS and MCC: IF FE-5005A (unit 1) + FE-5005A (unit 2) > or = 3000 kg/h AND IF TIT5041 (96FTG) < + 4°C THEN: heater ON. IF TIT- 5039 (FTG-1A) or TIT0340 (FTG-1B) > or = + 7°C OR IF TIT- 5041 (96FTG) > + 90°C THEN: heater OFF. Logic to be managed by MKVIe: The interlock to the opening of SRV/GCV during GT starting procedure: IF TIT5039 (FTG-1A) or TIT5040 (FTG-1B) > or = + 8°C AND TG-FG-1 (231-TE-5006AA) is not low
TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTION
DOCUMENT CODE
SOM6629548SOM6629548SOM6629548SOM6629548
REVISION
4444
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE
PAGE MARKER
N/AN/AN/AN/A
SECURITY CODE
NNNN
ORIGINAL JOB
1800057180005718000571800057----58585858
SIZE
4444
LANGUAGE
AAAA
THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. . UNPUBLISHED WORK ©2012201220122012 Nuovo Nuovo Nuovo Nuovo Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.. . . . ALL RIGHTS RESERVED.
SHEET
66666666 of of of of 94949494
4.21 LIQUID FUEL
4.21.1 DEVICE SUMMARY DEVICE NAME CUSTOMER TAG DESCRIPTION F-001A/B C-231-001A-F-10A/B LIQUID FUEL DUPLEX FILTER F-002 C-231-001A-F-11 LIQUID FUEL FILTER DOWNSTREAM PUMP F-003 C-231-001A-F-12 LIQUID FUEL HYD OIL FILTER PF-1 C-231-001A-P1 LIQUID FUEL PUMP 88PF-1 C-231-001A-P1-M LIQUID FUEL PUMP MOTOR 23FL C-231-001A-H4 LIQUID FUEL HEATER PF-2 C-231-001A-P12 LIQUID FUEL DRAIN PUMP 88PF-2 C-231-001A-P12-M LIQUID FUEL DRAIN PUMP MOTOR 77FD-1 231-SE-5013A LIQUID FUEL FLOW DIVIDER SPEED PICK-UP 77FD-2 231-SE-5014A LIQUID FUEL FLOW DIVIDER SPEED PICK-UP 77FD-3 231-SE-5015A LIQUID FUEL FLOW DIVIDER SPEED PICK-UP --- 231-TIT-5013A1 LIQUID FUEL TEMP --- 231-TIT-5013A2 LIQUID FUEL TEMP --- 231-TIT-5013A3 LIQUID FUEL TEMP 96HF-2 231-PDIT-5014A LIQUID FUEL FILTER DIFF. PRESSURE 96FL-1 231-PIT-5018A LIQUID FUEL PRESSURE
65FP-1 231-FCV-5015A1 LIQUID FUEL SYSTEM CONTROL VALVE REGULATING SERVO VALVE
20LF-2 231-XX-5016A LIQUID FUEL BYPASS VALVE ACTUATING SOLENOID VALVE
--- 231-LIT-5013A LIQUID FUEL TANK LEVEL
--- 231-TIT-5014A LIQUID FUEL TEMPERATURE FEEDBACK TO THYRISTOR CONTROL PANEL
20LF-1 231-XX-5014AA LIQUID FUEL VALVE ACTUATING SOLENOID 33FL-1 231-ZSH-5014A LIQUID FUEL VALVE OPEN LIMIT SWITCH 33FL-2 231-ZSL-5014B LIQUID FUEL VALVE CLOSE LIMIT SWITCH
4.21.2 SOFTWARE DESCRIPTION In Liquid Fuel System the main pump PF-1 delivers the 100% liquid fuel to the skid. The fuel valve 231-XV-5316A has two operating positions:
� By pass position: It provides the liquid by-pass through the recycle piping. Liquid fuel temperature is monitored by RTDs and transmitted to MarkVIe v.i.a. Temperature transmitters’ 231-TIT-5013A1, 231-TIT-5013A2 and 231-TIT-5013A3. If liquid fuel temperature low condition is detected (231-TAL-5013) an alarm is generated and liquid fuel heater is turned on and the fuel valve is set in the by-pass position. An inhibit signal for liquid system starting and running is generated. For liquid fuel temperature low-low condition (231-TALL-5013), GT Normal Stop condition is activated.
� Fuel supply position: Liquid fuel temperature detected by 231-TIT-5014A is sent to MarkVIe, which generates a control signal and sends to the Thyristor control panel to switch on/off the heater based on the feedback. Upon attaining the correct temperature the fuel is allowed to flow to the combustor by actuation of the SOV 231-XX-5016A.
� If low pressure is detected by 231-PIT-5018A (96FL-1), an alarm is generated and “Inhibit Liquid
TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTION
DOCUMENT CODE
SOM6629548SOM6629548SOM6629548SOM6629548
REVISION
4444
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE
PAGE MARKER
N/AN/AN/AN/A
SECURITY CODE
NNNN
ORIGINAL JOB
1800057180005718000571800057----58585858
SIZE
4444
LANGUAGE
AAAA
THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. . UNPUBLISHED WORK ©2012201220122012 Nuovo Nuovo Nuovo Nuovo Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.. . . . ALL RIGHTS RESERVED.
SHEET
67676767 of of of of 94949494
Fuel Starting and running” condition is generated.
� If differential pressure across Liquid Fuel Filters detected by 231-PDIT-5014A (96HF-2) is detected high, an alarm is generated.
� The Liquid Fuel Heater control is performed by “Thyristor Control Panel”. Following feedback signals are transmitted to MarkVIe from Thyristor Control Panel: � Liquid Fuel Temperature � Liquid Fuel Heater Cut-out status � Liquid Fuel Heater working/ ok condition � Fault Condition In case of Thyristor Control Panel failure, electric heater will remain turned on until its own cut-off.
� The liquid fuel flow is sensed by each individual speed sensors 77FD-1 (231-SE-5013A) , 77FD-2 (231-SE-5014A) and 77FD-3 (231-SE-5015A) and transmitted to MarkVIe which perform Liquid Fuel Bypass valve 65FP-1 (231-FCV-5015A1) control to recirculate the liquid fuel back to Liquid Fuel Tank (C-231-001A-TK1)
� If the liquid fuel tank (TK-1) level is detected high (231-LAH-5013A) by the level transmitter 231-LIT-5013A then the pump PF-2 is started to pump the liquid fuel to liquid fuel storage tank. If the level transmitter senses the level to be low (231-LAL-5013A) the pump PF-2 is stopped.
TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTION
DOCUMENT CODE
SOM6629548SOM6629548SOM6629548SOM6629548
REVISION
4444
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE
PAGE MARKER
N/AN/AN/AN/A
SECURITY CODE
NNNN
ORIGINAL JOB
1800057180005718000571800057----58585858
SIZE
4444
LANGUAGE
AAAA
THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. . UNPUBLISHED WORK ©2012201220122012 Nuovo Nuovo Nuovo Nuovo Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.. . . . ALL RIGHTS RESERVED.
SHEET
68686868 of of of of 94949494
4.22 FUEL TRANSFER
4.22.1 Fuel Splitter
In dual fuel Gas Turbine the FSR (Fuel Stroke Reference) is divided into two signals to provide dual fuel operation. The two signals are FSR1 and FSR2. Typically FSR1 is for liquid and FSR2 is for gas. Fuel transfer sequence can be activated only when the START-UP COMPLETE SEQUENCE flag is satisfied.
4.22.2 Fuel Transfer (Liquid to Gas)
If the unit is running on liquid operator interface GAS target is selected, the following sequence
of events will take place:
1. FSR1 will remain at initial value but FSR2 will step to a value slightly greater than zero. This will open the gas control valve slightly to bleed down the inter valve volume, P2. This is done in case a high pressure has been entrapped. The presence of a pressure higher than that required by the speed ratio controller would cause slow response in initiating gas flow. 2. After a time delay to bleed down P2 and fill the gas supply line, the software program ramp the fuel commands at a rate programmed to a complete transfer. 3. As transfer progress, FSR1 will be reduced and FSR2 will increase at the programmed ramp rate. When the transfer is complete, 231-XX-5016A solenoid valve switches 231-XV-5016A to recycle position.
4.22.3 Fuel transfer (Gas to Liquid)
When transfer from gas to liquid is initiated, the liquid fuel pump clutch is engaged, energizing the liquid fuel trip valve opens the liquid fuel stop valve, and the liquid purge is shut off. Transfer from gas to liquid is essentially the same sequence as previously described except that gas and liquid fuel command voltages are interchanged. For instance, at the beginning of a transfer FSR2 remains at its initial value, but FSR1 steps to a value slightly greater than zero. This will command a small liquid fuel flow. If there has been any fuel leakage past the check valves, this will fill the liquid fuel piping and avoid any delay in delivery at the beginning of the FSR1 increase. When transfer to total liquid is completed, a logic signal will close the gas fuel stop valve by de-energizing the gas fuel trip valve 231-XX-2052 (20FB-1) and initiating the gas fuel purge sequence. During normal running condition, the automatic Fuel gas to liquid fuel transfer is activated by the Fuel gas low-pressure transmitter 96FG-1.
TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTION
DOCUMENT CODE
SOM6629548SOM6629548SOM6629548SOM6629548
REVISION
4444
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE
PAGE MARKER
N/AN/AN/AN/A
SECURITY CODE
NNNN
ORIGINAL JOB
1800057180005718000571800057----58585858
SIZE
4444
LANGUAGE
AAAA
THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. . UNPUBLISHED WORK ©2012201220122012 Nuovo Nuovo Nuovo Nuovo Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.. . . . ALL RIGHTS RESERVED.
SHEET
69696969 of of of of 94949494
4.23 FUEL GAS BLOCK / FUEL GAS VENT VALVES Fuel Block (20FB-1) valve logic During starting sequence, fuel block valve is opened when L4 is detected. The opening is disabled if off line water wash is selected. When a trip (pressurized or depressurized) is detected the valve is closed. Fuel Vent (20FV-1) valve logic During starting sequence, fuel vent valve is closed after fuel line purge sequence. When a trip (pressurized or depressurized) is detected the valve is opened. The opening is enabled when fuel block valve is completely closed.
TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTION
DOCUMENT CODE
SOM6629548SOM6629548SOM6629548SOM6629548
REVISION
4444
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE
PAGE MARKER
N/AN/AN/AN/A
SECURITY CODE
NNNN
ORIGINAL JOB
1800057180005718000571800057----58585858
SIZE
4444
LANGUAGE
AAAA
THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. . UNPUBLISHED WORK ©2012201220122012 Nuovo Nuovo Nuovo Nuovo Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.. . . . ALL RIGHTS RESERVED.
SHEET
70707070 of of of of 94949494
4.24 ATOMIZING AIR SYSTEM
4.24.1 DEVICE SUMMARY DEVICE NAME CUSTOMER TAG DESCRIPTION CA-1 C-231-001A-C1 MAIN ATOMIZING AIR COMPRESSOR CA-2 C-231-001A-C2 AUXILIARY ATOMIZING AIR COMPRESSOR FA2-1 C-231-001A-F6 STARTING COMPRESSOR AIR FILTER FA1-1 C-231-001A-F5 AIR FILTER FA3-1 C-231-001A-F7 AIR FILTER 20PL-1 231-XX-5076A LIQUID FUEL SYSTEM PURGE SOLENOID VALVE 20AA-1 231-XX-5074A VA18-1 CONTROL AIR ON/OFF VALVE AAT-1A 231-TE-5158A1A ATOMIZING AIR COOLER DISCHARGE TEMPERATURE AAT-1B 231-TE-5158A2A ATOMIZING AIR COOLER DISCHARGE TEMPERATURE AAT-1C 231-TE-5158A3A ATOMIZING AIR COOLER DISCHARGE TEMPERATURE 20AB-1 231-XX-5073A AUX. ATOMIZING AIR COMPRESSOR VALVE CONTROL 33AA-1 231-ZSL-5073A AUX. ATOMIZING AIR COMPRESSOR VALVE POSITION 33AA-2 231-ZSH-5073A AUX. ATOMIZING AIR COMPRESSOR VALVE POSITION 96AA 231-PIT-5078A ATOMIZING AIR MANIFOLD PRESSURE 96AA-2 231-PIT-5077A PURGE AIR MANIFOLD PRESSURE 33AC-1 231-ZSL-5157A ATOMIZING AIR COOLER VALVE CLOSE LIMIT SWITCH
4.24.2 SOFTWARE DESCRIPTION
The purpose of atomizing air is, during liquid fuel operation, to break up the liquid fuel into a fine mist, so that the fuel can ignite, and burn completely. In order to reach this requirement, the nominal pressure ratio of atomizing air relative to combustion chamber (Pcc) air is 1.35. This pressure ratio is needed for proper atomization of the liquid fuel. Improper liquid fuel atomization may result in incomplete combustion, and/or carryover of liquid fuel droplets into the turbine. The main atomizing air compressor (CA-1) pressurizes compressor discharge (Pcd) air to meet this requirement. During a liquid fuel startup, the nominal pressure ratio of atomizing air relative to Pcd air is 1.5. This pressure ratio is needed to ignite the liquid fuel. In order to meet this requirement a booster compressor driven by starting motor (CA-2) is required, because the main atomizing air compressor is shaft driven, and does not develop enough pressure until the turbine reaches 90% speed.
Atomizing air is required during gas fuel operation. During gas fuel operation, atomizing air purges the atomizing air circuits and the liquid fuel circuits. These circuits must be purged in order to cool the nozzle tips and prevent backflow of combustion gases. During gas fuel operation, the nominal pressure ratio of atomizing air relative to Pcc air is 1.05. The air flow is driven to Purge Air Manifold by the valve VA19-1, actuated by solenoid 231-FX-5076 (20PL-1). During a gas fuel startup, the atomizing air circuits do not require purge.
Three thermocouples (231-TE-5158A1A (AAT-1A) , 231-TE-5158A2A (AAT-1B) , 231-TE-5158A3A (AAT-1C) monitor the inlet temperature of the main atomizing air compressor in order to protect the compressor. Alarms are generated for high and low level. Shutdown is generated for HH level. Trip is generated for LL condition.
The pressure in the manifold is monitored by 231-PIT-5078A (96AA) . Shutdown is generated if relative
TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTION
DOCUMENT CODE
SOM6629548SOM6629548SOM6629548SOM6629548
REVISION
4444
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE
PAGE MARKER
N/AN/AN/AN/A
SECURITY CODE
NNNN
ORIGINAL JOB
1800057180005718000571800057----58585858
SIZE
4444
LANGUAGE
AAAA
THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. . UNPUBLISHED WORK ©2012201220122012 Nuovo Nuovo Nuovo Nuovo Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.. . . . ALL RIGHTS RESERVED.
SHEET
71717171 of of of of 94949494
pressure is below a threshold that is different for start-up, liquid fuel running, fuel gas running, shut-down.
During start-up the valve VA18 -1, actuated by solenoid 231-FV-5074A (20AA-1) , is open. The valve VA22-1, actuated by solenoid 231-XX-5073A (20AB-1) is open to give air supply to booster compressor.
At end of start sequence (L3) VA22-1 receives the close command and the atomizing air system is driven by atomizing air compressor.
During fuel gas operation the nominal pressure ratio of atomizing air relative to Pcc (1.05) is guaranteed by atomizing air compressor with VA18-1 closed. The correct suction pressure is guaranteed through the bypass line orifice (231-FO-5075A).
TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTION
DOCUMENT CODE
SOM6629548SOM6629548SOM6629548SOM6629548
REVISION
4444
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE
PAGE MARKER
N/AN/AN/AN/A
SECURITY CODE
NNNN
ORIGINAL JOB
1800057180005718000571800057----58585858
SIZE
4444
LANGUAGE
AAAA
THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. . UNPUBLISHED WORK ©2012201220122012 Nuovo Nuovo Nuovo Nuovo Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.. . . . ALL RIGHTS RESERVED.
SHEET
72727272 of of of of 94949494
4.25 SEAL GAS, SEAL GAS HEATER & SEAL GAS BOOSTER SYSTEM
4.25.1 DEVICE SUMMARY DEVICE NAME CUSTOMER TAG DESCRIPTION F-701/A/B C-231-001A-F3A/B N2 FILTER --- 231-FIT-5206A COMPRESSOR DISCHARGE END PRIMARY VENT --- 231-FIT-5207A COMPRESSOR SUCTION END PRIMARY VENT --- 231-PDIT-5193A NITROGEN FILTER PRESSURE --- 231-PDIT-5201A1 BUFFER SEAL GAS INLET --- 231-PIT-5204A1 COMPRESSOR PRIMARY VENT PRESSURE --- 231-PIT-5204A2 COMPRESSOR PRIMARY VENT PRESSURE --- 231-PIT-5204A3 COMPRESSOR PRIMARY VENT PRESSURE --- 231-PIT-5205A1 COMPRESSOR PRIMARY VENT PRESSURE --- 231-PIT-5205A2 COMPRESSOR PRIMARY VENT PRESSURE --- 231-PIT-5205A3 COMPRESSOR PRIMARY VENT PRESSURE --- 231-PIT-5195A1 NITROGEN HEADER PRESSURE --- 231-PIT-5195A2 NITROGEN HEADER PRESSURE --- 231-PIT-5195A3 NITROGEN HEADER PRESSURE --- 231-PIT-5199A SEAL GAS OUTLET BALANCING LINE PRESSURE --- 231-PIT-5200A SEAL GAS INLET BALANCING LINE PRESSURE --- 231-PIT-5208A PRIMARY VENT CONTROL PRESSURE --- 231-XX-5210A NITROGEN INTERMEDIATE INJECTION VALVE --- 231-ZSH-5208A FLARE PRESSURE CONTROL VALVE POSITION --- 231-ZSH-5210A NITROGEN INTERMEDIATE INJECTION VALVE --- 231-ZSL-5208A FLARE PRESSURE CONTROL VALVE POSITION --- 231-ZSL-5210A NITROGEN INTERMEDIATE INJECTION VALVE --- 231-PDIT-5209A SEAL GAS FILTERS --- 231-PDY-5201A BUFFER GAS PRESSURE CONVERTER --- 231-ZSH-5211A GAS AMPLIFIER INLET VALVE OPEN LIMIT SWITCH --- 231-ZSL-5211A GAS AMPLIFIER INLET VALVE CLOSE LIMIT SWITCH --- 231-XX-5211A GAS AMPLIFIER INLET VALVE ACTUATING SOV --- 231-TE-5210A1A GAS AMPLIFIER- SEALS PROTECTION --- 231-TE-5210A2A GAS AMPLIFIER- SEALS PROTECTION --- 231-TE-5210A3A GAS AMPLIFIER- SEALS PROTECTION --- 231-XX-5209A EXTERNAL SEAL GAS INLET SOLENOID VALVE --- 231-ZSL-5209A EXTERNAL SEAL GAS INLET LIMIT SWITCH --- 231-XX-5212A BOOSTER SKID BUFFER GAS INLET ACTUATING SOV
--- 231-PDIT-5210A DIFFERENTIAL PRESSURE ACROSS SEAL GAS BOOSTER
--- 231-PIT-5197A1/A2/A3 CC SEALING CHAMBER VENT DISCHARGE SIDE --- 231-PIT-5198A1/A2/A3 CC SEALING CHAMBER VENT SUCTION SIDE
4.25.2 SOFTWARE DESCRIPTION The purpose of buffer gas is to maintain a constant volumetric flow of dry filtered gas between primary seal and internal labyrinth avoiding unfiltered gas to reach seals. This is achieved actuating valve (231-PDCV-5201A) through signal 231-PDY-5201A to maintain differential pressures 231-PDIT-5201A1 to the set point value. A PI control is used. Buffer gas alarm and fault logic If the differential pressures 231-PDIT-5201A1 lowers below threshold value when starting sequence is ended
TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTION
DOCUMENT CODE
SOM6629548SOM6629548SOM6629548SOM6629548
REVISION
4444
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE
PAGE MARKER
N/AN/AN/AN/A
SECURITY CODE
NNNN
ORIGINAL JOB
1800057180005718000571800057----58585858
SIZE
4444
LANGUAGE
AAAA
THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. . UNPUBLISHED WORK ©2012201220122012 Nuovo Nuovo Nuovo Nuovo Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.. . . . ALL RIGHTS RESERVED.
SHEET
73737373 of of of of 94949494
(L3), an alarm is generated. If differential pressure between buffer-gas filter (231-PDIT-5209A) is above threshold level an alarm is generated. Buffer gas manual operation Manual operation can be enabled by command L43SG_CMD. If enabled, 231-PDCV-5201A valve is managed by seven pushbuttons: � L5SG_SR_CPB – Set-point raise step � L5SG_SL_CPB – Set-point lower step � L5SG_C_CPB - Valve close command (fine tuning) � L5SG_O_CPB - Valve open command (fine tuning) � L5SG_FC_CPB - Valve close command (latched till completely close or stop is detected) � L5SG_FO_CPB - Valve open command (latched till completely open or stop is detected) � L5SG_S_CPB - Stop Primary vent flow alarm logic Primary vent low flow alarms are enabled if pressurized state is detected (L4PV) and, during startup, after the shaft has moved (~L14LR). � If enable condition is verified and if flow through primary vent line suction side, measured by 231-FIT-
5206A, 231-FIT-5207A, lowers below threshold an alarm is generated. � If flow through primary vent line suction side, measured by 231-FIT-5206A, 231-FIT-5207A, rises above
threshold an alarm is generated. Primary vent pressure alarm and fault logic � If primary vent suction side pressure 231-PDIT-5504 A1 / 231-PDIT-5504 A2 / 231-PDIT-5504 A3 rises
above the trip threshold value, an alarm and depressurized trip are generated. The same alarm and trip are generated in case of transmitter fault detected.
� If primary vent discharge side pressure 231-PIT-5205 A1 / 231-PIT-5205 A2 / 231-PIT-5205 A3 rises above the trip threshold value, an alarm and depressurized trip are generated. The same alarm and trip are generated in case of transmitter fault detected.
Primary vent control pressure The primary vent line pressure is monitored by 231-PIT-5208A and transmitted to MarkVIe which in controls the opening and closing of the valve 231-XV-5208A by actuating the solenoid valve 231-XX-5208A. The open/close position of 231-XV-5208A is detected by 231-ZSH-5208A and 231-ZSL-5508A. Seal purge gas injection logic � If seal purge gas pressure 231-PIT-5195 A1 / 231-PIT-5195 A2 / 231-PIT-5195 A3 lowers below low
threshold an alarm is generated. � If seal purge gas pressure 231-PIT-5195 A1 / 231-PIT-5195 A2 / 231-PIT-5195 A3 becomes higher than
high threshold an alarm is generated. � If seal purge gas pressure 231-PIT-5195 A1 / 231-PIT-5195 A2 / 231-PIT-5195 A3 lowers below low low
threshold an alarm and pressurized trip is generated. � If the differential pressure 231-PDIT-5193A across the separation gas (Nitrogen) inlet filter is greater
than a threshold value an alarm is generated. Start-up sequence
� During the start-up sequence, if valve open condition is not detected, when L1X is active, the valve 231-XV-5209 is opened through the command 231-XX–5209A. The valve is closed when LP shaft reaches 70% of full speed.
Stop sequence � During the shutdown or pressurized trip sequence, if valve open condition is not detected, the valve 231-
XV-5209A is opened through the command 231-XX–5209A when low pressure shaft speed goes below
TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTION
DOCUMENT CODE
SOM6629548SOM6629548SOM6629548SOM6629548
REVISION
4444
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE
PAGE MARKER
N/AN/AN/AN/A
SECURITY CODE
NNNN
ORIGINAL JOB
1800057180005718000571800057----58585858
SIZE
4444
LANGUAGE
AAAA
THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. . UNPUBLISHED WORK ©2012201220122012 Nuovo Nuovo Nuovo Nuovo Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.. . . . ALL RIGHTS RESERVED.
SHEET
74747474 of of of of 94949494
the value of 60% of full speed.
Intermediate Buffer Gas isolation In order to prevent the risk of reverse pressurization of the primary seal, the buffer gas injection shall be isolated maintaining however the injection to barrier seals. A remote controlled isolation valve (solenoid type) on the buffer gas downstream filter line dedicated to intermediate injection shall be provided. The valve shall be closed by the control logic in the following cases:
• LP and Double Control Sealing System The valve shall be closed when the differential pressure between seal gas and primary vent is below 0.3 bar.
• HP Sealing System The valve shall be closed when the suction pressure or balancing drum chamber pressure is below 3 barg.
Seal Gas Booster Logic At the compressor start-up sequence, the seal gas booster is started. In the first 1 minute the transmitter (231-PDIT-5210A) is bypassed since initially there is no differential pressure developed across the booster. After 1 minute of starting the booster, if the transmitter detects a Low condition (231-PDSL-5210A), an alarm is generated. For a LL condition, the Booster trips and compressor running sequence is aborted. The temperature at the seal gas booster outlet is measured by the RTDs 231-TE-5210A1A, 231-TE-5210A2A and 231-TE-5210A3A. If 2oo3 RTDs sense:
- Low temperature, an alarm is generated and heater-on signal is transmitted by the MarkVIe to the Thyristor Control Panel which turns on the heater.
- Low Low temperature, a trip with vent is initiated. - High temperature, an alarm is generated and heater-off signal is transmitted by the MarkVIe to the
Thyristor Control Panel which turns off the heater. - High High temperature, a heater cut-off signal is generated.
TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTION
DOCUMENT CODE
SOM6629548SOM6629548SOM6629548SOM6629548
REVISION
4444
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE
PAGE MARKER
N/AN/AN/AN/A
SECURITY CODE
NNNN
ORIGINAL JOB
1800057180005718000571800057----58585858
SIZE
4444
LANGUAGE
AAAA
THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. . UNPUBLISHED WORK ©2012201220122012 Nuovo Nuovo Nuovo Nuovo Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.. . . . ALL RIGHTS RESERVED.
SHEET
75757575 of of of of 94949494
4.26 STEAM INJECTION
4.26.1 DEVICE SUMMARY DEVICE NAME
CUSTOMER TAG DESCRIPTION
96PJ-1 231-PIT-5025A STEAM INLET FLOW CALCULATION PRESSURE TRANSMITTER
ST-SJ-1/2/3 231-TE-5025A1A/A2A/A3A STEAM INLET FLOW CALCULATION TEMPERATURE INPUTS (RTD)
20SJ-2 231-XX-5029A STEAM INJECTION STOP VALVE ACTUATION 33SJ-1 231-ZSH-5029A STEAM INJECTION STOP VALVE OPEN 33SJ-2 231-ZSL-5029A STEAM INJECTION STOP VALVE CLOSED 33CJ-1 231-ZSL-5026A STEAM INJECTION CONTROL VALVE CLOSED 20BS-1 231-XX-5030A DRAIN VALVE NUMBER 1 ACTUATION 33BS-1 231-ZSL-5030A STEAM INJECTION DRAIN VALVE N.1 CLOSED 20BS-2 231-XX-5031A DRAIN VALVE NUMBER 2 ACTUATION 33BS-2 231-ZSL-5031A STEAM INJECTION DRAIN VALVE N.2 CLOSED 20BS-3 231-XX-5032A DRAIN VALVE NUMBER 3 ACTUATION 33BS-3 231-ZSL-5032A STEAM INJECTION DRAIN VALVE N.3 CLOSED 20BS-4 231-XX-5027A STEAM DISCHARGE (AFTER VA-4) 33BS-4 231-ZSL-5027A STEAM INJECTION MANIFOLD DRAIN VDI-4
--- 231-PY-5025A STEAM INLET PRESSURE REGULATING I TO P CONVERTOR
96SJ-1 231-FIT-5025A1 STEAM FLOW 96SJ-2 231-FIT-5025A2 STEAM FLOW 60WQL 231-XS-561 <4> STEAM VALVES COMMAND 60WQR 231-XS-562 <4> STEAM VALVES COMMAND
4.26.2 SOFTWARE DESCRIPTION Steam injection skid function is NOx reduction. The 96PJ-1 (231-PIT-5025A) transmitter and ST-SJ-1 (231-TE-5025A1A) / ST-SJ-2 (231-TE-5025A2A) / ST-SJ-3 (231-TE-5025A3A) RTDs purpose is to calculate the steam mass flow in order to grant the necessary steam/gas mass ratio inside combustion chambers. Steam injection reference function is: WQR2 = [WQKn_K * [(FQMT - WQKn_B)] + WQKn_N Note the equation is of the form Y= mX + B Y = WQR2 (function) m = WQKn_K (Diluent/Fuel slope) x = (FQMT - WQKn_B) (variable)
FQMT = Total Fuel Mass Flow Reference WQKn_B = Fuel Flow Offset
b = WQKn_N (offset)
REVISED WHERE SHOWN <4>
TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTION
DOCUMENT CODE
SOM6629548SOM6629548SOM6629548SOM6629548
REVISION
4444
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE
PAGE MARKER
N/AN/AN/AN/A
SECURITY CODE
NNNN
ORIGINAL JOB
1800057180005718000571800057----58585858
SIZE
4444
LANGUAGE
AAAA
THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. . UNPUBLISHED WORK ©2012201220122012 Nuovo Nuovo Nuovo Nuovo Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.. . . . ALL RIGHTS RESERVED.
SHEET
76767676 of of of of 94949494
Note: The table is applicable for both fuel gas and liquid fuel with following parameters Fuel Gas: WQK0_N 0.00859739 Kg/sec WQK0_M 1.47681 Kg/sec Liquid Fuel: WQK2_N 0.705118 Kg/sec WQK2_M 2.19891 Kg/sec The WQKn_E is the minimum fuel flow set point to start steam injection. The WQKn_M is the steam injection maximum flow limit. The ramp consists of multiple steps; the logic is used to select the “n” constant set to change the curve with fuel flow. The steam injection skid in order to be operative during turbine running requires a purging line heating procedures in steps. With steam injection disabled the position of the valves is the following: VDI-1 closed, VS-3 closed, VDI-2 open, VA-4 closed, VDI-3 closed, and VDI-4 closed. The VDI-1, VDI-3, VDI-4 valves are opened by the 20BS-1 (231-XX-5030A) , 20BS-3 (231-XX-5032A) , 20BS-4 (231-XX-5027A) commands, the control system will monitor the limit switch 33BS-1 (231-ZSL-5030A) ,33BS-3 (231-ZSL-5032A) , 33BS-4 (231-ZSL-5027A) in not closed position, if after 3 seconds from the drain valve opening command the limit switches are still in closed position an alarm will be generated. The first step permits to heat and drain from condensate vapor the stop valve and at the same time to heat. This step permits also to drain and heat (with Pcd air) the piping from control valve to manifold and the manifold itself. The opening command 20BS-1 (231-XX-5030A) will start a timer set at 120 seconds, when this timer is expired the second step starts with the 20SJ-2 (231-XX-5029A) command in order to open the VS-3 stop valve. The control system will monitor the limit switch 33SJ-1 (231-ZSH-5029A) in not closed position, if after 3 seconds from the drain valve opening command the limit switch is still in closed position an alarm will be generated. The 20BS-1 (231-XX-5030A) command is de-energized 1 second after the 33SJ-1 (231-ZSH-5029A) limit switch not in closed position and the 20SJ-2 (231-XX-5029A) command active. The opening command 20SJ-2 will start a timer set at 120 seconds, when this timer is expired the third step starts with the 20BS-3 (231-XX-5032A) , 20BS-4 (231-XX-5027A) commands in order to close the VDI-3,
FUEL FLOW
STEAMFLOW
WQKn_N
WQKn_E
WQKn_Bn=0
WQKn_Bn=1
slopeWQKn_K
n=0
slopeWQKn_K
n=1
MAX limitWQKn_M
LK83WKnn=1
STEAM INJECTION FLOW VS. FUEL FLOW
TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTION
DOCUMENT CODE
SOM6629548SOM6629548SOM6629548SOM6629548
REVISION
4444
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE
PAGE MARKER
N/AN/AN/AN/A
SECURITY CODE
NNNN
ORIGINAL JOB
1800057180005718000571800057----58585858
SIZE
4444
LANGUAGE
AAAA
THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. . UNPUBLISHED WORK ©2012201220122012 Nuovo Nuovo Nuovo Nuovo Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.. . . . ALL RIGHTS RESERVED.
SHEET
77777777 of of of of 94949494
VDI-4 drain valves. The control system will monitor the limit switch 33BS-3 (231-ZSL-5032A) , 33BS-4 (231-ZSL-5027A) in closed position, if after 3 seconds from the drain valve opening command, the limit switch is not in closed position an alarm will be generated. VA-4 valve can now be opened and regulated by 4CJ-RUN MOT. STEAM VALVE RUN 4CJ-DIR MOT. STEAM VALVE DIRECTION And the steam injection system can be operative. The control system will monitor the limit switch 33CJ-1 (231-ZSL-5026A) in not closed position, if after 3 seconds from the drain valve regulating command the limit switch is still in closed position an alarm will be generated. The missing opening command to VS-3, VDI-1, VDI-2, VDI-3, VDI-4, VA-4 and not closed position feedback from limit switch will also generate an alarm, delay time will be set on site. During skid operation:
• If the ST-SJ-1 (231-TE-5025/A1A) / ST-SJ-2 (231-TE-5025/A2A) / ST-SJ-3 (231-TE-5025/A3A) RTD temperature is below a low low superheated steam threshold an alarm is generated.
• If the ST-SJ-1 (231-TE-5025/A1A) / ST-SJ-2 (231-TE-5025/A2A) / ST-SJ-3 (231-TE-5025/A3A) RTDs temperature is below a low superheated steam threshold an alarm is generated.
• If the ST-SJ-1 (231-TE-5025/A1A) / ST-SJ-2 (231-TE-5025/A2A) / ST-SJ-3 (231-TE-5025/A3A) RTDs temperature is over a high threshold an alarm is generated.
• If the ST-SJ-1 (231-TE-5025/A1A) / ST-SJ-2 (231-TE-5025/A2A) / ST-SJ-3 (231-TE-5025/A3A) RTDs temperature is over a high threshold an alarm is generated.
• If the 96PJ-1 (231-PIT-5025A) pressure is below a low low threshold an alarm is generated. • If the 96PJ-1 (231-PIT-5025A) pressure is below a low threshold an alarm is generated. • If the 96PJ-1 (231-PIT-5025A) pressures is over a high threshold an alarm is generated. • If the96PJ-1 (231-PIT-5025A) pressure is over a high high threshold an alarm is generated.
To re-initialize steam injection after a system shutdown a MASTER reset is needed.
Steam temp.
Steam
pressure
Temp. HH
Temp. H
Pre
ss.
LL
Pre
ss.
L
Pre
ss.
H
Pre
ss.
HH
Temp. L
Temp. LLSteam
saturation
WORKING
AREA
LL L H HH Pressure (Barg) 16 18 23 24
Temperature (°C) 260 280 390 400
TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTION
DOCUMENT CODE
SOM6629548SOM6629548SOM6629548SOM6629548
REVISION
4444
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE
PAGE MARKER
N/AN/AN/AN/A
SECURITY CODE
NNNN
ORIGINAL JOB
1800057180005718000571800057----58585858
SIZE
4444
LANGUAGE
AAAA
THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. . UNPUBLISHED WORK ©2012201220122012 Nuovo Nuovo Nuovo Nuovo Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.. . . . ALL RIGHTS RESERVED.
SHEET
78787878 of of of of 94949494
5 ANTISURGE AND LOAD SHARING The compressor surge control panel contains redundant “CCC series 5” surge controllers for each compressor stage. The output of the surge controllers operates Antisurge valves for each stage to prevent compressor surge. Antisurge supplier (C.C.C.) will show details on relevant Functional Description. The interface signals between MarkVIe and CCC Controller is listed down Unit Control System Hardwired IO List (SOM6628418). Each Antisurge valve is equipped with a solenoid which is activated when the trip sequence is requested. For further information see section 1.10 (Trip sequence). Logic Description of Fast Opening Antisurge Valve: l20as=0 means Fast Open Antisurge SOV is commanded to open. This happens when the following condition occurs: Condition:
1. The Shutdown condition is active Or
2. Turbine is tripped and shaft is not stopped (Considering Water-wash is not selected).
Reset Logic of the Fast opening SOV: The SOV open condition is reset:
- The Fast Opening command is reset if LP shaft is stopped or Reset pulse is obtained (K4PULS_RES = 60secs), whichever is earlier.
TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTION
DOCUMENT CODE
SOM6629548SOM6629548SOM6629548SOM6629548
REVISION
4444
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE
PAGE MARKER
N/AN/AN/AN/A
SECURITY CODE
NNNN
ORIGINAL JOB
1800057180005718000571800057----58585858
SIZE
4444
LANGUAGE
AAAA
THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. . UNPUBLISHED WORK ©2012201220122012 Nuovo Nuovo Nuovo Nuovo Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.. . . . ALL RIGHTS RESERVED.
SHEET
79797979 of of of of 94949494
6 FIRE FIGHTING MONITORING
6.1 ENCLOSURE FIRE DETECTION / FIGHTING:
6.1.1 DEVICE SUMMARY DEVICE NAME CUSTOMER TAG DESCRIPTION CBVF-1/2 C-231-001A-V4A/B FIRE FIGHTING NITROGEN CYLINDER CBVF-3 to CBVF-10
C-231-001A-V5A to H FIRE FIGHTING INERGEN CYLINDER
33CP-1A 231-ZSH-5265A EXTINGUISHER HEADER ISOLATION VALVE OPEN FEEDBACK TO MARKVIE
33CP-1D 231-ZSH-5266A EXTINGUISHER HEADER ISOLATION VALVE OPEN FEEDBACK TO MARKVIE
33CP-2A 231-ZSL-5265A EXTINGUISHER HEADER ISOLATION VALVE CLOSE FEEDBACK TO FF SYSTEM
33CP-2D 231-ZSL-5266A EXTINGUISHER HEADER ISOLATION VALVE CLOSE FEEDBACK TO FF SYSTEM
96CP-1A 231-PT-5289A1 EXTINGUISHER DISCHARGE HEADER PRESSURE 96CP-1B 231-PT-52891B EXTINGUISHER DISCHARGE HEADER PRESSURE 96CP-1C 231-PT-52891C EXTINGUISHER DISCHARGE HEADER PRESSURE 45CR-1 231-XX-5265A FIRE DISCHARGE SOLENOIDS 45-CR-2 231-FX-5266A FIRE DISCHARGE SOLENOIDS 45FA-1 231-TSHH-5253A1 HEAT RISE FIRE DETECTOR 45FA-2 231-TSHH-5253A2 HEAT RISE FIRE DETECTOR 45FA-3 231-TSHH-5253A3 HEAT RISE FIRE DETECTOR 45FA-4 231-TSHH-5253A4 HEAT RISE FIRE DETECTOR 45FT-1 231-TSHH-5253A5 HEAT RISE FIRE DETECTOR 45FT-2 231-TSHH-5253A6 HEAT RISE FIRE DETECTOR 45FT-3 231-TSHH-5253A7 HEAT RISE FIRE DETECTOR 45FT-4 231-TSHH-5253A8 HEAT RISE FIRE DETECTOR 45FT-5 231-TSHH-5253A9 HEAT RISE FIRE DETECTOR 45FT-6 231-TSHH-5253A10 HEAT RISE FIRE DETECTOR 45UV/IR-1 231-BE-5253A1 UV/IR FIRE DETECTOR 45UV/IR-2 231-BE-5253A2 UV/IR FIRE DETECTOR XL-3A 231-XL-5258A1 GREEN LAMP- AUTO XL-3B 231-XL-5258A2 FLASHING RED LAMP- DISCHARGED XL-3C 231-XL-5258A3 WHITE LAMP INHIBITED --- 231-HS-5258A 3 POSITION SELECTOR- AUTO POSITION --- 231-HS-5258I 3 POSITION SELECTOR- INHIBIT POSITION --- 231-HS-5258M 3 POSITION SELECTOR- MANUAL POSITION XL-4A 231-XL-5255A1 GREEN LAMP- AUTO XL-4B 231-XL-5255A2 FLASHING RED LAMP- DISCHARGED XL-4C 231-XL-5255A3 WHITE LAMP INHIBITED --- 231-HS-5255A 3 POSITION SELECTOR- AUTO POSITION --- 231-HS-5255I 3 POSITION SELECTOR- INHIBIT POSITION --- 231-HS-5255M 3 POSITION SELECTOR- MANUAL POSITION XL-2 231-XL-5256A1 FIRE DISCHARGE LAMP XA-2 231-XA-5256A2 FIRE DISCHARGE HORN EDS-2 231-HS-5256A3 DISCHARGE PUSH BUTTON XL-1 231-XL-5257A1 FIRE DISCHARGE LAMP XA-1 231-XA-5257A2 FIRE DISCHARGE HORN
TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTION
DOCUMENT CODE
SOM6629548SOM6629548SOM6629548SOM6629548
REVISION
4444
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE
PAGE MARKER
N/AN/AN/AN/A
SECURITY CODE
NNNN
ORIGINAL JOB
1800057180005718000571800057----58585858
SIZE
4444
LANGUAGE
AAAA
THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. . UNPUBLISHED WORK ©2012201220122012 Nuovo Nuovo Nuovo Nuovo Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.. . . . ALL RIGHTS RESERVED.
SHEET
80808080 of of of of 94949494
DEVICE NAME CUSTOMER TAG DESCRIPTION EDS-1 231-HS-5257A3 DISCHARGE PUSH BUTTON
6.1.2 SOFTWARE DESCRIPTION Inergen is discharged energizing two solenoid valves, 45CR-1 (231-XX-5265A) and 45CR-2 (231-XX-5266A) .In normal conditions these valves are de-energized. Inergen header isolation valves closure is detected by two limit switches, 33CP-2A (231-ZSL-5265A) and 33CP-2B (231-ZSL-5266A) , cabled to FF panel. Inergen header pressure is detected by median value of three pressure transmitters: 96CP-1A/B/C. When the system is in Automatic Mode, extinguisher discharge procedure is activated in case of automatic fire trip detection or extinguisher discharge push-button action, that activate the 45CR-1 (231-XX-5265A) and 45CR-2 (231-XX-5266A) solenoid valves. These steps will be then executed:
1. UCS is notified through a contact, 45FTT open on trip. 2. Enclosure ventilation fans cut-out is available through 2 contacts, 4BA1_C1 ,4BA2_C, open on trip. 3. the following alarm means are activated: - horns close to the enclosure - red flashing lights by the turbine enclosure - Red flashing light or led mounted in the front of the F&G system. 4. After a 30 seconds delay, the Inergen is released in the turbine enclosure. 5. The UCS is notified through a free of voltage contact 63CPD open when extinguisher is discharging. 6. Once discharge is complete, the UCS is notified through a free of voltage open contact 33CPX.
The extinguisher discharge header pressure is checked by pressure switches in case an high pressure is detected the following steps are executed:
1. the UCS is notified through a free of voltage contact, 63CPD ,open on high pressure 2. Enclosure ventilation fans cut-out is available through 2 contacts, 4BA_C1, 4BA_C2 that open on
trip. 3. the following alarm means are activated:
- horns close to the enclosure - red flashing lights by the turbine enclosure - Red flashing light mounted in the front of the F&G system.
The selector switches 231-HS5255A and 231-HS5258A have 3 positions and follow the logic below:
- When ‘AUTO’ mode is selected, upon detection of Fire by any one of the Fire Detectors, the discharge procedure is activated. - When ‘INHIBIT/OFF’ mode is selected, even if there is Fire in the enclosure, the system does not send command to Inergen discharge solenoid valves, - When ‘MANUAL’ mode is selected at Field, the operator can press the 231-HS-5256X3 (EDS-2) or 231-HS-5257X3 (EDS-1) push buttons at field to enable discharging of extinguisher at field.
TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTION
DOCUMENT CODE
SOM6629548SOM6629548SOM6629548SOM6629548
REVISION
4444
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE
PAGE MARKER
N/AN/AN/AN/A
SECURITY CODE
NNNN
ORIGINAL JOB
1800057180005718000571800057----58585858
SIZE
4444
LANGUAGE
AAAA
THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. . UNPUBLISHED WORK ©2012201220122012 Nuovo Nuovo Nuovo Nuovo Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.. . . . ALL RIGHTS RESERVED.
SHEET
81818181 of of of of 94949494
6.2 FIRE FIGHTING DEDICATED PLC INTERFACE:
Following signals are elaborated from F&G dedicated PLC and affect turbine start/stop sequence: � If enclosure fire is detected, unit trips signal is generated (45FTT)
If Inergen is discharged, (33CPX (231- XS -144C) ESTINGUISHANT DISCHARGED and 63CPDX (231-XS-656C) EXTINGUISHANT RELEASE IN PROGRESS) unit trip and alarm are generated.
� If fire-fighting discharge is inhibited alarm (43CP-IX ESTINGUISHANT NOT AVAILABLE / INHIBITED) is generated.
� If FF system fault is detected, alarm (86FG-1 FIRE/GAS SYSTEM FAULT) is generated. Field Interface: � If fire-fighting Inergen discharge valves is detected closed by limit switch (33CP-1A, 33CP-1D), alarm is
generated. � If fire-fighting bottles are empty, alarm (by 33CR) is generated.
For details refer to Fire Fighting Logic Diagram (SOM6628499).
TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTION
DOCUMENT CODE
SOM6629548SOM6629548SOM6629548SOM6629548
REVISION
4444
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE
PAGE MARKER
N/AN/AN/AN/A
SECURITY CODE
NNNN
ORIGINAL JOB
1800057180005718000571800057----58585858
SIZE
4444
LANGUAGE
AAAA
THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. . UNPUBLISHED WORK ©2012201220122012 Nuovo Nuovo Nuovo Nuovo Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.. . . . ALL RIGHTS RESERVED.
SHEET
82828282 of of of of 94949494
7 MARKVIE INTERFACES WITH OTHER SYSTEMS Here is given a brief explanation of all signals that are interfaced between MarkVIe and other systems external to MarkVIe. Fire Fighting System vs. Unit Control System:
1. 231-XL 145 A (XL-A) (RED FRONT PANEL LAMP): It Is a Contact 24Vdc signal (lamp) in the UCS front panel that indicates ‘Fire’ condition.
2. 231-XL 145 B (XL-B) (GREEN FRONT PANEL LAMP): It Is a Contact 24Vdc signal (lamp) in the UCS front panel that indicates ‘Armed’ condition.
3. 231-XL 145 C (XL-C) (WHITE FRONT PANEL LAMP): It Is a Contact 24Vdc signal (lamp) in the UCS front panel that indicates ‘Inhibited’ condition.
4. 231-XS -146 (43AUTO) (3 POSITION AUTO/INHIBIT/MANUAL SELECTOR): It is 3 Position Auto / Inhibit Manual Mode
Selector in the UCS Front Panel.
5. 231-XS-610 (86PS-3) (110VDC BUS FAILURE): It is a contact signal (Open=Failure) from Fire Fighting Panel to MarkVIe indicating failure condition of 110VDC Bus 3 located at Fire Fighting Panel.
Fire Fighting System vs. Customer Fire Fighting Sys tem:
1. 231-XS -144 C (33CPX) (EXTING. UNAVAILABLE/INHIBITED (VALVES CLOSED) (TO CUSTOMER FF): It is a contact signal (NO, Close= valves closed) that indicate the open/ close condition of the extinguisher discharge header valves to Customer FF System.
2. 231-XS -655 C (43CP_IX) (ELECTRICAL DISCHARGE DIASABLED ALM (TO CUSTOMER FF) It is a contact signal (NO, Close= electric discharge disabled) that indicate the electric discharge disabled condition to Customer FF System.
3. 231-XS -656 C (63CPDX) (EXTINGUISHANT DISCH. IN PROGRESS (TO CUSTOMER FF): It is a contact signal (NO, Close= discharge in progress) that indicate the extinguisher discharge in progress condition to Customer FF System.
4. 231-XS -657 TC (45FTX) (FIRE DETECTED TRIP (TO CUSTOMER FF): It is a contact signal (NC, Open= Trip) that indicate
the fire detected Trip condition to Customer FF System. MarkVIe vs. Fire Fighting System:
1. 231-XS-140 (43CP_ARST) (FF SYSTEM REMOTE RESET): It is a contact signal (NO, Close= reset) that provide remote reset from MarkVIe to FF detection system.
2. 231-xs-141 (43CP_ASIL) (FF SYSTEM REMOTE SILENCE): It is a contact signal (NO, Close= silence) that provide remote silence from MarkVIe to FF detection system.
3. 231-XS-144 (33CP-1) (EXTINGUISHER UNAVAILABLE/ INHIBITED (VALVES CLOSED)): It is a contact signal (NO, Close= valves closed) that indicate the open/ close condition of the extinguisher discharge header valves from FF detection system to MarkVIe.
4. 231-XS-652 IF (86FF_SD) (FF INPUT FAULT (NORMAL SHUTDOWN): It is a contact signal (NC, Open= Fault), transmitted from FF detection system to MarkVIe that indicate the fault condition of the FF detection inputs.
5. 231-XS-652 SF (86FF-1) (FF SYSTEM FAULT): It is a contact signal (NC, Open= Fault), transmitted from FF detection system to MarkVIe that indicate the fault condition of the FF PLC.
6. 231-XS-655 (43CP_I) (ELECTRICAL DISCHARGE DISABLED ALARM): It is a contact signal (NO, Close= electric discharge disabled) that indicate the electric discharge disabled condition from FF detection system to MarkVIe.
7. 231-XS-656 A (63CPD) (EXTINGUISHER DISCHARGE IN PROGRESS): It is a contact signal (NO, Close= discharge in progress) that indicate the extinguisher discharge in progress condition from FF detection system to MarkVIe.
8. 231-XS-657 T (45FTT) (FIRE DETECTED TRIP): It is a contact signal (NC, Open= Trip) that indicate the fire detected Trip condition from FF detection system to MarkVIe.
MarkVIe vs. HRSG Burner Management System: 1. 231-XS-960 (DUCT BURNER PURGE COMPLETED): It is a contact signal from BMS to MarkVIe that indicate that the Duct
Burner Purge is completed.
2. 231-XS-961 (GT LOAD > 60%): It is a Contact signal (NO, Close = GT Load > 60%) from MarkVIe to the BMS indicating that GT Load is greater than 60%.
TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTION
DOCUMENT CODE
SOM6629548SOM6629548SOM6629548SOM6629548
REVISION
4444
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE
PAGE MARKER
N/AN/AN/AN/A
SECURITY CODE
NNNN
ORIGINAL JOB
1800057180005718000571800057----58585858
SIZE
4444
LANGUAGE
AAAA
THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. . UNPUBLISHED WORK ©2012201220122012 Nuovo Nuovo Nuovo Nuovo Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.. . . . ALL RIGHTS RESERVED.
SHEET
83838383 of of of of 94949494
MarkVIe vs. CCC: 1. 231-XA-804 (TNL_O) (TURBINE SPEED TO LOAD SHARING CONTROL SYSTEM): It is a (4-20) mA signal transmitted from
MarkVIe to CCC Load Sharing Controller indicating the Turbine Speed.
2. 231-XA-808A (TNR_EXT) (SPEED SET-POINT FROM COMPRESSOR LOAD SHARING SYSTEM): It is a (4-20) mA signal transmitted from CCC Load Sharing Controller to MarkVIe that gives speed set-point to MarkVIe.
3. 231-XS-800B (4SURGE-1) (ANTISURGE CONTROLLER SURGE DETECTED): It is a contact signal (NO, Close = Surge Detected) transmitted from CCC Anti-surge Controller to MarkVIe indicating detection of Surge.
4. 231-XS-800C (3AS_ENA-1) (ANTISURGE CONTROLLER ENABLE): It is a contact signal (NO, Close = Enable) transmitted from MarkVIe to CCC Anti-surge Controller indicating Turbine Start sequence has ended (L3=1) and CCC Anti-surge Controller is enabled to perform Anti-surge Control.
5. 231-XS-800D (4TXT_O-1) (TURBINE TRIP STATUS REPETITION): It is a contact signal (NC, Open= Trip) transmitted from MarkVIe to CCC Controllers indicating Unit Summary Trip (L4=0).
6. 231-XS-800F (EXCESSIVE SURGE SHUTDOWN): It is a Contact Signal (Close= Shutdown) transmitted from CCC Anti-
surge Controller to MarkVIe initiating Shutdown due to excessive surge.
7. 231-XS-800L (LOAD SHARING RUN / STOP): It is a Contact Signal (NO, Close= Load Sharing Enabled) transmitted from MarkVIe to CCC Load Sharing Controller indicating that Turbine Start sequence has ended (L3=1) and CCC Load Sharing Controller is enabled to perform Load Sharing Control.
8. 231-XS-806 (4TRACK) (TRACKING REQUEST TO LOAD SHARING SYSTEM): It is a Contact Signal (NO, Close = Tracking Request enabled) transmitted from MarkVIe to CCC Controller to indicate CCC controller to remain in Tracking Mode.
9. 231-XS-807A (86AS) (ANTI-SURGE CONTROLLER FAULT): It is a contact signal (NC, Open=Fault) transmitted from CCC Anti-surge / Load Sharing Controller to MarkVIe indicating Fault condition of CCC Anti-surge controller.
10. 231-XS-808B (86LS) (MASTER CONTROLLER FAULT): It is a contact signal (NC, Open=Fault) transmitted from CCC Master Controller to MarkVIe indicating Fault condition of CCC Master Controller.
MarkVIe vs. DCP: 1. 231-XS-200 I (42HR-1) (HYDRAULIC RATCHET MOTOR RUNNING): It is a contact signal (Close= Running) transmitted
from DCP to MarkVIe indicating the running status of Hydraulic Ratchet pump motor.
2. 231-XS-200 O (49HR-1) (HYDRAULIC RATCHET PUMP MOTOR OVERVOLTAGE): It is a contact signal (Open=Alarm) transmitted from DCP to MarkVIe indicating the overvoltage status of Hydraulic Ratchet pump motor.
3. 231-XS-200 R (4HR-1) (HYDRAULIC RATCHET RUN/STOP COMMAND): It is a contact signal (NO, Close = Running) transmitted from MarkVIe to DCP commanding Hydraulic Ratchet pump motor to Start. The inverted condition of the signal commands Stop condition of the motor.
4. 231-XS-200 U (27HR-1) (HYDRAULIC RATCHET PUMP MOTOR UNDERVOLTAGE): It is a contact signal (Open=Alarm) transmitted from DCP to MarkVIe indicating the under-voltage status of Hydraulic Ratchet pump motor.
5. 231-XS-206 A (DCP-30RA) (DCP- RECTIFIER “A” COMMON ALARM): It is a contact signal (Open=Alarm) transmitted from DCP to MarkVIe indicating the common alarm condition of the DCP Rectifier A.
6. 231-XS-207 (DCP-80X) (DCP BATTERY MINIMUM VOLTAGE): It is a contact signal (Open=Alarm) transmitted from DCP to MarkVIe indicating the minimum voltage condition of the DCP Battery.
7. 231-XS-208 (DCP-BD) (DCP BATTERY DISCHARGING): It is a contact signal (Open=Alarm) transmitted from DCP to MarkVIe indicating that the DCP Battery is discharging.
8. 231-XS-851-A (52QE-1) (MINERAL LUBE OIL EMERGENCY DC PUMP RUNNING): It is a contact signal (Close= Running)
transmitted from DCP to MarkVIe indicating the running status of Mineral Lube Oil Emergency DC Pump.
9. 231-XS-851-B (49QE) (MINERAL LUBE OIL EMERGENCY DC PUMP FAULT): It is a contact signal (Open= Fault) transmitted from DCP to MarkVIe indicating the fault status of Mineral Lube Oil Emergency DC Pump. <4>
10. 231-XS-852 (14HLR) (TURBINE SHAFT ZERO SPEED): It is a wet contact (110Vdc, Closed= Zero speed) signal transmitted from MarkVIe to DCP indicating the Turbine Shaft Zero Speed Condition.
11. 231-XS-853 (28FD) (TURBINE FLAME NOT DETECTED): It is a wet contact (110Vdc, Closed = Flame not detected) signal transmitted from MarkVIe to DCP indicating the turbine flame not detected condition.
12. 231-XS-854 (4E) (UCP SYSTEM FULLY OPERATIVE): It is a wet contact (110Vdc, Closed = Fully Operative) signal
REVISED WHERE SHOWN <4>
TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTION
DOCUMENT CODE
SOM6629548SOM6629548SOM6629548SOM6629548
REVISION
4444
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE
PAGE MARKER
N/AN/AN/AN/A
SECURITY CODE
NNNN
ORIGINAL JOB
1800057180005718000571800057----58585858
SIZE
4444
LANGUAGE
AAAA
THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. . UNPUBLISHED WORK ©2012201220122012 Nuovo Nuovo Nuovo Nuovo Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.. . . . ALL RIGHTS RESERVED.
SHEET
84848484 of of of of 94949494
transmitted from MarkVIe to DCP indicating the UCP System Fully Operative condition.
13. 231-XS-855 (4-TEST) (PUMP TEST): It is a wet contact (110Vdc, Closed = Test) signal transmitted from MarkVIe to DCP commanding the Emergency Lube Oil Pump test.
14. 231-XS-857 (63QL) (LUBE OIL PRESSURE NOT LOW): It is a wet contact (110Vdc, Closed = Pressure not low) signal transmitted from MarkVIe to DCP indicating the Lube Oil header pressure not low condition.
15. 231-XS-858 (63QN) (LUBE OIL PRESSURE NORMAL): It is a wet contact (110Vdc, Closed = Pressure normal) signal transmitted from MarkVIe to DCP indicating the Lube Oil header pressure normal condition.
16. 231-XS-859 (62CD) (COOLDOWN SEQUENCE ENDED): It is a contact signal (Close= sequence ended) transmitted from DCP to MarkVIe indicating the end of Cooldown sequence and expiration of Cooldown Timer. <4>
MarkVIe vs. MCC:
1. 231-XS-100 I (52QA-1) (LUBE OIL AUXILIARY PUMP FEEDBACK): It is a Contact Signal (NO, Close= Running) from MCC to MarkVIe indicating running feedback of Lube Oil Auxiliary Pump Motor).
2. 231-XS-100-R (4QA-1A) (LUBE OIL AUXILIARY PUMP START COMMAND): It is a Pulse Signal (Pulse= Start) from MarkVIe to MCC indicating Start command to Lube Oil Auxiliary Pump Motor).
3. 231-XS-100-S (4QA-1B) (LUBE OIL AUXILIARY PUMP STOP COMMAND) It is a Pulse Signal (Pulse= Stop) from MarkVIe to MCC indicating Stop command to Lube Oil Auxiliary Pump Motor).
4. 231-XS-102 I (52QV-1) (LUBE OIL VAPOUR EXTRACTOR 1 FEEDBACK): It is a Contact Signal (NO, Close= Running) from MCC to MarkVIe indicating running feedback of Lube Oil Vapor Extractor Motor 1).
5. 231-XS-102-R (4QV-1A) (LUBE OIL VAPOUR EXTRACTOR 1 START COMMAND): It is a Pulse Signal (Pulse= Start) from MarkVIe to MCC indicating Start command to Lube Oil Vapor Extractor 1 Motor).
6. 231-XS-102-S (4QV-1B) (LUBE VAPOUR EXTRACTOR 1 STOP COMMAND): It is a Pulse Signal (Pulse= Stop) from MarkVIe to MCC indicating Stop command to Lube Oil Vapor Extractor 1 Motor).
7. 231-XS-103 I (52QV-2) (LUBE OIL VAPOUR EXTRACTOR 2 FEEDBACK): It is a Contact Signal (NO, Close= Running) from MCC to MarkVIe indicating running feedback of Lube Oil Vapor Extractor Motor 2).
8. 231-XS-115-R (4QV-2A) (LUBE OIL VAPOUR EXTRACTOR 2 START COMMAND): It is a Pulse Signal (Pulse= Start) from MarkVIe to MCC indicating Start command to Lube Oil Vapor Extractor 2 Motor).
9. 231-XS-115-S (4QV-2B) (LUBE VAPOUR EXTRACTOR 2 STOP COMMAND): It is a Pulse Signal (Pulse= Stop) from MarkVIe to MCC indicating Stop command to Lube Oil Vapor Extractor 2 Motor).
10. 231-XS-104I (52HQ) (AUX HYDRAULIC OIL PUMP FEEDBACK): It is a Contact Signal (NO, Close= Running) from MCC to MarkVIe indicating running feedback of Auxiliary Hydraulic Oil Pump Motor).
11. 231-XS-104-R (4HQ-1A) (AUX HYDRAULIC OIL PUMP START COMMAND): It is a Pulse Signal (Pulse= Start) from MarkVIe to MCC indicating Start command to Auxiliary Hydraulic Oil Pump Motor).
12. 231-XS-104-S (4HQ-1B) (AUX HYDRAULIC OIL PUMP STOP COMMAND): It is a Pulse Signal (Pulse= Stop) from MarkVIe to MCC indicating Stop command to Auxiliary Hydraulic Oil Pump Motor).
13. 231-XS-108I (52BA-1) (VENTILATION FAN #1 FEEDBACK): It is a Contact Signal (NO, Close= Running) from MCC to MarkVIe indicating running feedback of Ventilation Fan 1 Motor).
14. 231-XS-113-R (4BA-1A) (VENTILATION FAN #1 START COMMAND): It is a Pulse Signal (Pulse= Start) from MarkVIe to MCC indicating Start command to Lube Oil Ventilation Fan 1 Motor).
15. 231-XS-113-S (4BA-1B) (VENTILATION FAN #1 STOP COMMAND): It is a Pulse Signal (Pulse= Stop) from MarkVIe to MCC indicating Stop command to Lube Oil Ventilation Fan 1 Motor).
16. 231-XS-109I (52BA-2) (VENTILATION FAN #2 FEEDBACK): It is a Contact Signal (NO, Close= Running) from MCC to MarkVIe indicating running feedback of Ventilation Fan 2 Motor).
17. 231-XS-114-R (4BA-2A) (VENTILATION FAN #2 START COMMAND): It is a Pulse Signal (Pulse= Start) from MarkVIe to MCC indicating Start command to Ventilation Fan 2 Pump Motor).
18. 231-XS-114-S (4BA-2B) (VENTILATION FAN #2 STOP COMMAND): It is a Pulse Signal (Pulse= Stop) from MarkVIe to MCC indicating Stop command to Ventilation Fan 2 Pump Motor).
REVISED WHERE SHOWN <4>
TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTION
DOCUMENT CODE
SOM6629548SOM6629548SOM6629548SOM6629548
REVISION
4444
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE
PAGE MARKER
N/AN/AN/AN/A
SECURITY CODE
NNNN
ORIGINAL JOB
1800057180005718000571800057----58585858
SIZE
4444
LANGUAGE
AAAA
THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. . UNPUBLISHED WORK ©2012201220122012 Nuovo Nuovo Nuovo Nuovo Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.. . . . ALL RIGHTS RESERVED.
SHEET
85858585 of of of of 94949494
19. 231-XS-121I (52PF-1) (LIQUID FUEL FORWARDING MOTOR 1 FEEDBACK): It is a Contact Signal (NO, Close= Running) from MCC to MarkVIe indicating running feedback of Liquid Fuel Forwarding Pump Motor 1).
20. 231-XS-129-R (4PF-1A) (LIQUID FUEL FORWARDING MOTOR 1 START COMMAND): It is a Pulse Signal (Pulse= Start) from MarkVIe to MCC indicating Start command to Liquid Fuel Forwarding Pump 1 Motor).
21. 231-XS-129-S (4PF-1B) (LIQUID FUEL FORWARDING MOTOR 1 STOP COMMAND): It is a Pulse Signal (Pulse= Stop) from MarkVIe to MCC indicating Stop command to Liquid Fuel Forwarding Pump 1 Motor).
22. 231-XS-711 (4PF1_C) (LIQUID FUEL FORWARDING MOTOR 1 CUT OUT): It is a contact Signal (Open= Cut-Out) from MarkVIe to MCC indicating cut-out condition of Liquid Fuel forwarding pump Motor 1).
23. 231-XS-122I (52PF-2) (LIQUID FUEL FORWARDING MOTOR 2 FEEDBACK): It is a Contact Signal (NO, Close= Running) from MCC to MarkVIe indicating running feedback of Liquid Fuel Forwarding Pump Motor 2).
24. 231-XS-120-R (4PF-2A) (LIQUID FUEL FORWARDING MOTOR 2 START COMMAND): It is a Pulse Signal (Pulse= Start) from MarkVIe to MCC indicating Start command to Liquid Fuel forwarding Pump 2 Motor).
25. 231-XS-120-S (4PF-2B) (LIQUID FUEL FORWARDING MOTOR 2 STOP COMMAND): It is a Pulse Signal (Pulse= Stop) from MarkVIe to MCC indicating Stop command to Liquid Fuel forwarding Pump 2 Motor).
26. 231-XS-714 (4PF2_C) (LIQUID FUEL FORWARDING MOTOR 2 CUT OUT): It is a contact Signal (Open= Cut-Out) from MarkVIe to MCC indicating cut-out condition of Liquid Fuel forwarding pump Motor 2).
27. 231-XS-126 I (52QT-1) (LUBE OIL HEATER #1 FEEDBACK): It is a Contact Signal (NO, Close= Running) from MCC to MarkVIe indicating running feedback of Lube Oil Heater 1).
28. 231-XS-126-R (4QT1_1A) (LUBE HEATER#1 START COMMAND): It is a Pulse Signal (Pulse= Start) from MarkVIe to MCC indicating Start command to Lube Oil Heater 1).
29. 231-XS-126-S (4QT1_1B) (LUBE HEATER#1 STOP COMMAND): It is a Pulse Signal (Pulse= Stop) from MarkVIe to MCC indicating Stop command to Lube Oil Heater 1).
30. 231-XS-720 (4QT1_C) (LUBE OIL HEATER 1 CUT OUT): It is a contact Signal (Open= Cut-Out) from MarkVIe to MCC indicating cut-out condition of Lube Oil Heater 1).
31. 231-XS-127 I (52QT-2) (LUBE OIL HEATER #2 FEEDBACK): It is a Contact Signal (NO, Close= Running) from MCC to MarkVIe indicating running feedback of Lube Oil Heater 2).
32. 231-XS-127-R (4QT2_1A) (LUBE HEATER#2 START COMMAND): It is a Pulse Signal (Pulse= Start) from MarkVIe to MCC indicating Start command to Lube Oil Heater 2).
33. 231-XS-127-S (4QT2_1B) (LUBE HEATER#2 STOP COMMAND): It is a Pulse Signal (Pulse= Stop) from MarkVIe to MCC indicating Stop command to Lube Oil Heater 2).
34. 231-XS-722 (4QT2_C) (LUBE OIL HEATER 2 CUT OUT): It is a contact Signal (Open= Cut-Out) from MarkVIe to MCC indicating cut-out condition of Lube Oil Heater 2).
35. 231-XS-128 I (52QT-3) (LUBE OIL HEATER #3 FEEDBACK): It is a Contact Signal (NO, Close= Running) from MCC to
MarkVIe indicating running feedback of Lube Heater 3).
36. 231-XS-128-R (4QT3_1A) (LUBE HEATER#3 START COMMAND): It is a Pulse Signal (Pulse= Start) from MarkVIe to MCC indicating Start command to Lube Oil Heater 3).
37. 231-XS-128-S (4QT3_1B) (LUBE HEATER#3 STOP COMMAND): It is a Pulse Signal (Pulse= Stop) from MarkVIe to MCC indicating Stop command to Lube Oil Heater 3).
38. 231-XS-723 (4QT3_C) (LUBE OIL HEATER 3 CUT OUT): It is a contact Signal (Open= Cut-Out) from MarkVIe to MCC indicating cut-out condition of Lube Oil Heater 3).
39. 231-XS-134 (27MC) (UNDERVOLTAGE FROM MCC): It is a Contact Signal (Open = Under-voltage) from MCC to MarkVIe
indicating under-voltage condition from MCC).
40. 231-XS-135 (49X) (COMMON OVERLOAD FROM MCC): It is a Contact Signal (Open = Overload) from MCC to MarkVIe indicating Overload condition from MCC).
41. 231-XS-136 (74X-MCC) (DRAWERS COMMON ALARM): It is a Contact Signal (Open = Alarm) from MCC to MarkVIe indicating Common alarm from MCC drawers).
TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTION
DOCUMENT CODE
SOM6629548SOM6629548SOM6629548SOM6629548
REVISION
4444
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE
PAGE MARKER
N/AN/AN/AN/A
SECURITY CODE
NNNN
ORIGINAL JOB
1800057180005718000571800057----58585858
SIZE
4444
LANGUAGE
AAAA
THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. . UNPUBLISHED WORK ©2012201220122012 Nuovo Nuovo Nuovo Nuovo Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.. . . . ALL RIGHTS RESERVED.
SHEET
86868686 of of of of 94949494
42. 231-XS-139 (2TVX) (IGNITION COMMAND TO MCC): It is a Contact Signal (Close = Ignite) from MarkVIe to MCC commanding the igniter to ignite).
43. 231-XS-515 I (52CR-1) (GT CRANKING MOTOR STATUS): It is a Contact Signal (NO, Close= Running) from MCC to MarkVIe indicating running feedback of Cranking Motor).
44. 231-XS-515 L (86CR) (GT CRANKING MOTOR LOCKOUT): It is a Contact Signal (NO, Close= Lockout) from MCC to MarkVIe indicating lockout condition of Cranking Motor).
45. 231-XS-515-R (4CR-1A) (GT CRANKING MOTOR START COMMAND): It is a Pulse Signal (Pulse= Start) from MarkVIe to MCC indicating Start command to Cranking Motor).
46. 231-XS-515-S (4CR-1B) (GT CRANKING MOTOR STOP COMMAND): It is a Pulse Signal (Pulse= Stop) from MarkVIe to MCC indicating Stop command to Cranking Motor).
47. 231-XS-558 (52TG) (FEED BACK TURNING GEAR): It is a Contact Signal (Cls=Running) from MCC to MarkVIe indicating running feedback of turning gear. <4>
48. 231-XS-559 (4TG1_R) (TURNING GEAR COMMAND-RESET): It is a Contact Signal (Cls=Reset) from MarkVIe to MCC commanding the reset of turning gear. <4>
49. 231-XS-560 (4TG1_S) (TURNING GEAR COMMAND-SET): It is a Contact Signal (Cls=Set) from MarkVIe to MCC commanding the set of turning gear. <4>
MarkVIe vs. DCS:
1. 231-XS-0250 RS (3CRS) (CUSTOMER READY TO START): It is a Contact Signal (NO, Close= Ready to Start) transmitted from DCS to MarkVIe as a permissive to start the Gas Turbine. <4>
2. 231-XS-0253 C (14HMX) (GT CRANKING STATUS): It is a Contact Signal (NO, Close= Cranking status) transmitted from MarkVIe to DCS indicating the GT cranking status. <4>
3. 231-XS-0253 R (3X) (GT RUNNING STATUS): It is a Contact Signal (NO, Close= Running status) transmitted from MarkVIe
to DCS indicating the GT running status (L3=1). <4>
4. 231-XS-0253 RS (3RS) (GT READY TO START STATUS): It is a Contact Signal (NO, Close= Ready to Start) transmitted from MarkVIe to DCS indicating the GT Ready to Start status. <4>
5. 231-XS-0253 S (GT STARTING STATUS): It is a Contact Signal (NO, Close= Starting) transmitted from MarkVIe to DCS indicating the GT start sequence initiated and the internal command Start Auxiliaries is true (L1X=1). <4>
6. 231-XS-0253SD (94X_C) (GT NORMAL STOP STATUS): It is a Contact Signal (NO, Close= Stop) transmitted from MarkVIe to DCS indicating the GT Normal stop status and that the Shutdown is in progress (L94X=1). <4>
7. 231-XS-0253 TD (4T_C2) (GT TRIP STATUS – DEPRESSURIZED): It is a Contact Signal (NC, Open= Trip) transmitted from MarkVIe to DCS indicating the GT Depressurized Trip status. <4>
8. 231-XS-0253 TP (4T_C1) (GT TRIP STATUS – PRESSURIZED): It is a Contact Signal (NC, Open= Trip) transmitted from MarkVIe to DCS indicating the GT Pressurized Trip status. <4>
9. 231-XS-0254 (30ALM) (CUMULATIVE ALARM REPETITION): It is a Contact Signal (NC, Open= Trip) transmitted from MarkVIe to DCS indicating the Cumulative alarm condition. <4>
10. 231-XS-0255 (43R_C) (GT IN REMOTE CONTROL MODE): It is a Contact Signal (NO, Close= Remote Control Mode) transmitted from MarkVIe to DCS indicating that Remote Control Mode is selected and the DCS can control the sequence. <4>
11. 231-XS-0256 (4VALV) (PROCESS VALVE POSITIONING): It is a Contact Signal (NO, Close= Process valve positioning signal) transmitted from MarkVIe to DCS indicating that Auxiliaries are started and Master Protective signal is enabled (L4=1). Now the DCS must start the Purging sequence of the Process valves. <4>
12. 231-XS-0257 R (1START) (PROCESS REMOTE START): It is a Contact Signal (NO, Close= Remote Start) transmitted from DCS to MarkVIe commanding the GT to start after L3RS=1 is reached and from Master Selector in HMI ‘Remote’ mode is selected. <4>
13. 231-XS-0257 S (1STOP) (PROCESS REMOTE STOP): It is a Contact Signal (NO, Close= Remote Stop) transmitted from DCS to MarkVIe commanding the GT to stop and if in HMI ‘Remote’ mode is selected. <4>
14. 231-XS-0257 T (4CT) (PROCESS REMOTE TRIP): It is a Contact Signal (NC, Open= Remote Trip) transmitted from DCS to MarkVIe commanding the GT to Trip. <4>
REVISED WHERE SHOWN <4>
TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTION
DOCUMENT CODE
SOM6629548SOM6629548SOM6629548SOM6629548
REVISION
4444
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE
PAGE MARKER
N/AN/AN/AN/A
SECURITY CODE
NNNN
ORIGINAL JOB
1800057180005718000571800057----58585858
SIZE
4444
LANGUAGE
AAAA
THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. . UNPUBLISHED WORK ©2012201220122012 Nuovo Nuovo Nuovo Nuovo Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.. . . . ALL RIGHTS RESERVED.
SHEET
87878787 of of of of 94949494
15. 231-XS-0258 RS (3CRC) (CUSTOMER READY TO CRANK): It is a Contact Signal (NO, Close= Ready to Crank) transmitted
from DCS to MarkVIe giving the permissive to MarkVIe to Crank. It indicates that the Process valve purging sequence is completed by the DCS and the valve position is ok for a pressurized or a depressurized start and that the cranking can be started. <4>
16. 231-XS-0260 (FUEL GAS SCRUBBER SYSTEM TRIP): It is a Contact Signal (NC, Open= Trip) transmitted from DCS to MarkVIe indicating the Trip condition from Fuel Gas Scrubber system (in customer’s scope). <4>
17. 231-XS-0261 (TNR) (SPEED SETPOINT FEEDBACK): It is a (4-20) mA signal transmitted from MarkVIe to DCS indicating the speed set-point feedback. <4>
18. 231-XS-0261 AL (60LC) (LOAD SETPOINT): It is a (4-20) mA signal transmitted from DCS to MarkVIe indicating the load set-point from DCS. It is when the LP Shaft speed is controlled by Raise / Lower command from DCS. <4>
19. 231-XS-0954 (DUCT BURNER PURGE CHANGEOVER SEQUENCE INITIATED): It is a Contact Signal (Close= Sequence Initiated) from DCS to MarkVIe indicating that Duct Burner Purge Changeover sequence is initiated. <4>
20. 231-XS-0955 (PURGE PHASE 1 COMPLETED- BYPASS STACK): It is a Contact Signal (NO, Close= Bypass Stack Purge completed) from MarkVIe to DCS indicating that Purge Phase-1 (Bypass Stack) is completed. <4>
21. 231-XS-0958 (GT LOAD > 60%): It is a Contact signal (NO, Close = GT Load > 60%) from MarkVIe to the DCS indicating that
GT Load is greater than 60%. <4>
22. 231-XS-2056 (HOT GAS BYPASS VALVE OPEN COMMAND FOR PURGE): It is a Contact signal (Cls=Purge) from DCS to MarkVIe commanding the hot gas bypass valve for purging sequence. <4>
23. 231-XS-2057 (HOT GAS BYPASS VALVE OPEN/CLOSE FEEDBACK): It is a Contact signal (1=Open; 0=Close) from MarkVIe to the DCS indicating a feedback position of hot gas bypass valve. <4>
24. 231-XS-2059 (ANTISURGE VALVE OPEN/CLOSE FEEDBACK): It is a Contact signal (1=Close; 0=Open) from MarkVIe to the DCS indicating a feedback position of 1st stage antisurge valve. <4>
MarkVIe vs. MarkVIeS:
1. 231-XS-703A (4FCV) (OFF SKID VALVE OPEN REQUEST FROM MARKVIE): It is a Contact Signal (Close= Valve Open) from MarkVIe to MarkVIeS indicating that Auxiliaries are started (L4=1) and Off-skid valves need to be positioned (Fuel Gas Block valve to open and Bleed valve to close).
2. 231-XS-703B (4FUEL) (ON SKID VALVE OPEN REQUEST FROM MARKVIE): It is a Contact Signal (NO, Close= Open valve) from MarkVIe to MarkVIeS for On-Skid Gas Fuel valve Open request).
3. 231-XS-703C (4FUEL_LIQ) (ON SKID LIQUID VALVE OPEN REQUEST FROM MARKVIE): It is a Contact Signal (NO, Close= Open valve) from MarkVIe to MarkVIeS for On-Skid Liquid Fuel valve Open request).
4. 231-XS-705 (4TM-REQ) (TRIP MULTIPLIER ON REQUEST FROM MARKVIE): It is a Contact Signal (NO, Close= Trip Multiplier on) from MarkVIe to MarkVIeS to activate Trip Multiplier function).
5. 231-XS-712 (4T_S) (CUMULATIVE SAFETY TRIP TO MARKVIE): It is a Contact Signal (NC, Open= Trip) from MarkVIeS to MarkVIe indicating Cumulative Trip condition).
6. 231-XS-721 (63BT) (VENTILATION SYSTEM RUNNING): It is a contact signal (NO, Close= Running) from MarkVIeS to MarkVIe indicating that the ventilation system is running.
7. 231-XS-726 P (28FDX_S) (COMBUSTION CHAMBER FLAME ON (PRIMARY)): It is a contact signal (NO, Close= Flame on) from MarkVIeS to MarkVIe indicating that the combustion chamber flame is ON.
8. 231-XS-730 (45HFA) (FILTER HOUSE GAS DETECTED ALARM TO MARKVIE): It is a contact signal (NC, Open= Alarm) from MarkVIeS to MarkVIe indicating Filter House Gas Detected Alarm condition (for any gas detector detecting a gas level of 5% LEL at filter house).
9. 231-XS-731 (45HFT) (FILTER HOUSE GAS DETECTED TRIP TO MARKVIE): It is a contact signal (NC, Open= Trip) from MarkVIeS to MarkVIe indicating Filter House Gas Detected Trip condition (for 2oo3 gas detector detecting a gas level of 10% LEL at filter house).
10. 231-XS-732 (45HDA-1) (ACC. COMPARTMENT GAS DETECTED ALARM TO MARKVIE): It is a contact signal (NC, Open= Alarm) from MarkVIeS to MarkVIe indicating Enclosure Ventilation outlet (Accessory compartment) Gas Detected Alarm condition (for 1oo3 gas detector detecting a gas level of 5% LEL at enclosure ventilation outlet).
REVISED WHERE SHOWN <4>
TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTION
DOCUMENT CODE
SOM6629548SOM6629548SOM6629548SOM6629548
REVISION
4444
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE
PAGE MARKER
N/AN/AN/AN/A
SECURITY CODE
NNNN
ORIGINAL JOB
1800057180005718000571800057----58585858
SIZE
4444
LANGUAGE
AAAA
THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. . UNPUBLISHED WORK ©2012201220122012 Nuovo Nuovo Nuovo Nuovo Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.. . . . ALL RIGHTS RESERVED.
SHEET
88888888 of of of of 94949494
11. 231-XS-733 (45HDT-1) (ACC. COMPARTMENT GAS DETECTED TRIP TO MARKVIE): It is a contact signal (NC, Open= Trip) from MarkVIeS to MarkVIe indicating Enclosure Ventilation outlet (Accessory compartment) Gas Detected Trip condition (for 2oo3 gas detector detecting a gas level of 10% LEL at enclosure ventilation outlet).
12. 231-XS-734 (45HDA-2) (TURBINE COMPARTMENT GAS DETECTED ALARM TO MARKVIE): It is a contact signal (NC, Open= Alarm) from MarkVIeS to MarkVIe indicating Enclosure Ventilation outlet (Turbine compartment) Gas Detected Alarm condition (for 1oo3 gas detector detecting a gas level of 5% LEL at enclosure ventilation outlet).
13. 231-XS-735 (45HDT-2) (TURBINE COMPARTMENT GAS DETECTED TRIP TO MARKVIE): It is a contact signal (NC, Open= Trip) from MarkVIeS to MarkVIe indicating Enclosure Ventilation outlet (Turbine compartment) Gas Detected Trip condition (for 2oo3 gas detector detecting a gas level of 10% LEL at enclosure ventilation outlet).
14. 231-XS-736 (45HSA) (ACC. COMPARTMENT H2S DETECTED ALARM TO MARKVIE): It is a contact signal (NC, Open= Alarm) from MarkVIeS to MarkVIe indicating Accessory compartment H2S concentration High Alarm condition.
Mark Vie vs. Plant Emergency Shutdown System:
1. 231-XS-254 R (GT RUNNING STATUS): It is a contact signal (NO, Close= Running) from MarkVIe to PESD indicating the running status of GT (L3=1).
2. 231-XS-354 (GT SHUTDOWN FOR HRSG SHUTDOWN AND DIVERTER SYSTEM FAILURE TO CLOSE): It is a contact signal (Open= Shutdown) from PESD to MarkVIe commanding the Gas Turbine shutdown due to HRSG shutdown and diverter system failure to close.
3. 231-XS-454 (HRSG SHUTDOWN CONDITION RESET): It is a contact signal (Close=Reset) from PESD to MarkVIe indicating HRSG Shutdown condition Reset.
4. 231-XS-554 (DIVERTER SYSTEM CLOSE): It is a contact signal (Close=Diverter close) from PESD to MarkVIe indicating Diverter System close i.e. HRSG damper closed and Bypass stack damper Open.
5. 231-XS-654 (DIVERTER SYSTEM OPEN): It is a contact signal (Close=Diverter open) from PESD to MarkVIe indicating Diverter System open i.e. HRSG damper open and Bypass stack damper closed.
6. 231-XS-754 (TEG TEMPERATURE 56 DEG C LOWER THAN FUEL AUTO IGNITION TEMPERATURE): It is a contact signal (Close=Lower) from MarkVIe to PESD indicating Turbine exhaust Gas Temperature 56 deg. C Lower than Fuel Auto Ignition temperature.
MarkVIe vs. Bently Nevada 3500 Temperature Monitori ng System:
1. 231-XS-450 (43TM_ARST) (TEMPERATURE MONITOR RESET): It is a contact signal (Close= Reset) from MarkVIe to BN Temp Monitor commanding Reset of the BN Temperature Monitor.
2. 231-XS-451 A (26TMA) (TEMPERATURE MONITOR CUMULATIVE ALARM): It is a contact signal (Open=Alarm) from BN Temp Monitor to MarkVIe indicating cumulative alarm condition of Bearing metal temperature measurement.
3. 231-YS-430 (CENTRIFUGAL COMPRESSOR THRUST BEARING TEMPERATURE TRIP): It is a contact signal (Open=Trip) from BN Temp Monitor to MarkVIe indicating trip condition of Thrust Bearing metal temperature.
4. 231-YS-451 F (86TM) (TEMPERATURE MONITOR FAULT): It is a contact signal (Open=Fault) from BN Temp Monitor to MarkVIe indicating fault condition of the BN Temperature Monitor.
MarkVIe vs. Bently Nevada 3500 Vibration Monitoring System:
1. 231-XS-400 (43VM_ARST) (VIBRATION MONITOR RESET): It is a contact signal (Close= Reset) from MarkVIe to BN Vibration Monitor commanding Reset of the BN Vibration Monitor
2. 231-XS-402 A (39VMA) (VIBRATION MONITOR CUMULATIVE ALARM): It is a contact signal (Open=Alarm) from BN Vibration Monitor to MarkVIe indicating cumulative alarm condition of Bearing vibration measurement.
3. 231-YS-402 F (86VM) (VIBRATION MONITOR FAULT): It is a contact signal (Open=Fault) from BN Vibration Monitor to MarkVIe indicating fault condition of the BN Vibration Monitor.
4. 231-YS-402 T (39VMT) (VIBRATION MONITOR CUMULATIVE TRIP): It is a contact signal (Open=Trip) from BN Vibration Monitor to MarkVIe indicating cumulative trip condition of Bearing vibration measurement.
5. 231-YS-415 (39VC-1T) (CENTRIFUGAL COMPRESSOR RADIAL TRIP): It is a contact signal (Open=Trip) from BN Vibration Monitor to MarkVIe indicating trip condition from Radial Vibration of bearings.
6. 231-YS-416 (39PC-1T) (CENTRIFUGAL COMPRESSOR AXIAL TRIP): It is a contact signal (Open=Trip) from BN Vibration Monitor to MarkVIe indicating trip condition from Axial Displacement of bearings.
TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTION
DOCUMENT CODE
SOM6629548SOM6629548SOM6629548SOM6629548
REVISION
4444
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE
PAGE MARKER
N/AN/AN/AN/A
SECURITY CODE
NNNN
ORIGINAL JOB
1800057180005718000571800057----58585858
SIZE
4444
LANGUAGE
AAAA
THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. . UNPUBLISHED WORK ©2012201220122012 Nuovo Nuovo Nuovo Nuovo Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.. . . . ALL RIGHTS RESERVED.
SHEET
89898989 of of of of 94949494
MarkVIe vs. Unit Control System: 1. 231-XS-601A (86PS-1) (24VDC BUS 1 FAILURE): It is a contact signal (Open=Failure) from UCS to MarkVIe indicating
failure condition of 24VDC Bus 1.
2. 231-XS-601B (86PS-2) (24VDC BUS 2 FAILURE): It is a contact signal (Open=Failure) from UCS to MarkVIe indicating failure condition of 24VDC Bus 2.
3. 231-XS-602 (86PS-FG) (FIRE FIGHTING 24VDC BUS FAILURE): It is a contact signal (Open=Failure) from UCS to MarkVIe indicating failure condition of 24VDC Bus in Fire Fighting Panel.
4. 231-XS-603 (86PS-FIELD) (FIELD 24VDC POWER BUS FAILURE): It is a contact signal (Open=Failure) from UCS to MarkVIe indicating failure condition of 24VDC Bus to power field instruments.
5. 231-XS-605 (XA-1) (UCS ALARM BUZZER): It is a wet voltage contact from MarkVIe to UCS (Open= Buzzer on) indicating alarm or trip condition.
6. 231-XS-607 (49UCS) (UCS HIGH TEMPERATURE ALARM): It is a contact signal (Open=Alarm) from UCS to MarkVIe indicating high temperature inside UCS.
7. 231-XS-612 A (110V AC BUS FAILURE AT TRAINVIEW SERVER PANEL): It is a contact signal (Open=Failure) from Trainview Server Panel to MarkVIe indicating failure condition of 110VDC Bus at Trainview Server Panel.
8. 231-XS-613 A (24VDC BUS FAILURE AT TRAINVIEW SERVER PANEL): It is a contact signal (Open=Failure) from Trainview Server Panel to MarkVIe indicating failure condition of 24VDC Bus at Trainview Server Panel.
MarkVIe vs. Local Control Panel:
1. 231-XS-614 (24VDC BUS FAILURE AT LOCAL CONTROL PANEL): It is a Contact signal (Open = Bus Failure) from LCP to MarkVIe indicating 24VDC Bus failure at LCP.
2. 231-XS-615 (INVERTER FAILURE AT LOCAL CONTROL PANEL): It is a Contact signal (Open = Inverter Failure) from LCP to MarkVIe indicating Inverter failure at LCP.
3. 231-XS-616 (LCP ALARM BUZZER SIGNAL): It is a wet contact (110Vdc, Closed = Alarm buzzer on) signal transmitted from
MarkVIe to DCP indicating the alarm or trip condition. MarkVIe vs. Liquid Fuel Thyristor Panel:
1. 231-XA-5015A (LIQUID FUEL THYRISTOR PANEL FAULT): It is a Contact Signal (Open= Fault) from Liquid Fuel Thyristor Panel to MarkVIe indicating the Fault status of the Liquid Fuel Thyristor Panel.
2. 231-XL-5015A (LIQUID FUEL HEATER RUNNING STATUS): It is a Contact Signal (Close= Running) from Liquid Fuel Thyristor Panel to MarkVIe indicating the Running status of the Liquid Fuel Heater.
3. 231-XS-5015A (LIQUID FUEL HEATER CUT-OFF STATUS): It is a Contact Signal (Open= Cut-off) from Liquid Fuel Thyristor
Panel to MarkVIe indicating the Cut-off status of the Liquid Fuel Heater.
4. TIT-5014 (LIQUID FUEL HEATER TEMPERATURE): It is a (4-20) mA signal from MarkVIe to Liquid Fuel Thyristor Panel that gives analog set-point to the Liquid Fuel Thyristor Panel to turn-on or turn-off the heater based on temperature feedback of liquid fuel received from field.
MarkVIe vs. Seal Gas Heater Thyristor Panel:
1. 231-TSHH-5210A (SEAL GAS HEATER CUT-OUT STATUS): It is a contact signal (Open= Cut-Out) from Thyristor Panel to MarkVIe indicating cut-out condition of the Seal gas Heater.
2. 231-UA-5209A (TH1_F) (THYRISTOR PANEL FAULT STATUS): It is a contact signal (Open= Fault) from Thyristor Panel to MarkVIe indicating fault condition of the Thyristor Panel.
3. 231-XA-809 (SEAL GAS HEATER SET POINT TO THYRISTOR PANEL): It is a (4-20) mA signal transmitted from MarkVIe to Thyristor Panel providing Seal Gas Heater Set-point.
4. 231-XI-5209A (TH1_ON) (THYRISTOR PANEL ON STATUS): It is a contact signal (Close=ON) from Thyristor Panel to MarkVIe indicating ON condition of the Thyristor Panel.
5. 231-XI-5210A (H1_ON) (SEAL GAS HEATER ON/OFF COMMAND): It is a contact signal (Close=ON, Open = OFF) from MarkVIe to Thyristor Panel commanding ON condition of the Seal Gas Heater.
6. 231-XS-5209A (TH1_CUT) (SEAL GAS HEATER CUT OUT): It is a contact signal (Close=Cut out) from MarkVIe to Thyristor Panel commanding Cut out of the Seal Gas Heater.
TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTION
DOCUMENT CODE
SOM6629548SOM6629548SOM6629548SOM6629548
REVISION
4444
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE
PAGE MARKER
N/AN/AN/AN/A
SECURITY CODE
NNNN
ORIGINAL JOB
1800057180005718000571800057----58585858
SIZE
4444
LANGUAGE
AAAA
THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. . UNPUBLISHED WORK ©2012201220122012 Nuovo Nuovo Nuovo Nuovo Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.. . . . ALL RIGHTS RESERVED.
SHEET
90909090 of of of of 94949494
MarkVIe vs. Pulse Jet Panel: 1. 231-XS-522 (86PJ) (PULSE JET PANEL FAULT): It is a contact signal (Open= Fault) from Pulse Jet Panel to MarkVIe
indicating Fault status of the Pulse Jet Panel.
2. 231-XS-523 (52PJ) (PULSE JET CLEANING CYCLE IN PROGRESS): It is a contact signal (Close= in progress) from Pulse Jet Panel to MarkVIe indicating Pulse Jet Cleaning in Progress.
MarkVIeS vs. Fire Fighting System:
1. 231-XS-657 TS (45FTT_S) (FIRE DETECTED TRIP TO SAFETY SYSTEM): It is a contact signal (NC, Open=trip) from Fire Fighting System to MarkVIeS indicating GT Trip due to Fire detection.
MarkVIeS vs. MCC:
1. 231-XS-709 A (4BA1_C) (VENTILATION MAIN FAN CUT-OUT): It is a Contact signal (NC, Open= Cut-out) from MarkVIeS to MCC commanding the cut out of the ventilation main fan.
2. 231-XS-709 B (4BA2_C) (VENTILATION STAND-BY FAN CUT-OUT): It is a Contact signal (NC, Open= Cut-out) from MarkVIeS to MCC commanding the cut out of the ventilation stand-by fan.
MarkVIeS vs. Plant Emergency Shutdown System:
1. 231-XS-700 A (CESD-1) (CUSTOMER ESD SIGNAL 1): It is a Contact signal (Open= ESD) from PESD to MarkVIeS commanding the Emergency Shutdown (Pressurized).
2. 231-XS-700 B (CESD-2) (CUSTOMER ESD SIGNAL-2): It is a Contact signal (Open= ESD) from PESD to MarkVIeS commanding the Emergency Shutdown (Depressurized).
3. 231-XS-700 C (CESD_OP) (SAFETY TRIP REPETITION TO CUSTOMER ESD- PRESSURIZED): It is a Contact signal (NC,
Open= Trip) from MarkVIeS to PESD indicating the Emergency Shutdown (Pressurized).
4. 231-XS-700 D (CESD_ODP) (SAFETY TRIP REPETITION TO CUSTOMER ESD- DEPRESSURIZED): It is a Contact signal (NC, Open= Trip) from MarkVIeS to PESD indicating the Emergency Shutdown (Depressurized).
MarkVIeS vs. Unit Control System: 1. 231-XS-717 (5ESD-R1) (ESD PUSH BUTTON FROM SAFETY RELAY- PRESSURIZED): It is a Contact signal (NC, Open=
Trip) from UCS to MarkVIeS indicating the Emergency Shutdown (Pressurized).
2. 231-YZ-575 T2 (5ESD-R2) (ESD PUSH BUTTON FROM SAFETY RELAY- DEPRESSURIZED): It is a Contact signal (NC, Open= Trip) from UCS to MarkVIeS indicating the Emergency Shutdown (Depressurized).
MarkVIeS vs. Bently Nevada 3500 Vibration Monitorin g System:
1. 231-XS-713 (4TM) (TRIP MULTIPLIER ON REQUEST TO VIBRATION MONITOR): It is a contact signal (Close= Trip Multiplier ON) from MarkVIeS to BN Vibration Monitor commanding the Trip Multiplier function to be ON.
2. 231-YS-426 A (39BNVT-1) (CUMULATIVE VIBRATION TRIP 1 TO ESD SYSTEM): It is a contact signal (NC, Open=Trip) from BN Vibration Monitoring System to MarkVIeS indicating cumulative vibration trip 1.
3. 231-YS-426 B (39BNVT-2) (CUMULATIVE VIBRATION TRIP 2 TO ESD SYSTEM): It is a contact signal (NC, Open=Trip) from BN Vibration Monitoring System to MarkVIeS indicating cumulative vibration trip 2.
4. 231-YS-429 (39VT) (TURBINE SEISMIC TRIP): It is a contact signal (NC, Open=Trip) from BN Vibration Monitoring System to MarkVIeS indicating Turbine Seismic Trip.
CCC vs. Unit Control System: 1. 231-XS-306 (COMMUNICATION DEVICE FAULT FOR MASTER CONTROLLER): It is a contact signal (NC, Open=Fault)
from CCC Master Controller chassis to CCC Master Controller indicating communication device fault to Master Controller.
2. 231-XS-601 C (COMMUNICATION DEVICE FAULT): It is a contact signal (NC, Open=Fault) from CCC Anti-surge Controller chassis to CCC Anti-surge Controller indicating communication device fault to Anti-surge Controller.
3. 231-XS-601D (HVAC SYSTEM FAULT): It is a contact signal (NC, Open=Fault) from CCC Controller chassis to CCC Controller indicating HVAC System fault to CCC Controller.
4. 231-XS-601 E (ANTISURGE CONTROLLER POWER / FAN FAULT): It is a contact signal (NC, Open=Fault) from CCC Anti-surge Controller chassis to CCC Anti-surge Controller indicating Power/ Fan fault to Anti-surge Controller.
5. 231-XS-701 E (MASTER CONTROLLER POWER/FAN FAULT): It is a contact signal (NC, Open=Fault) from CCC Master Controller chassis to CCC Master Controller indicating power/ fan fault to Master Controller.
TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTION
DOCUMENT CODE
SOM6629548SOM6629548SOM6629548SOM6629548
REVISION
4444
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE
PAGE MARKER
N/AN/AN/AN/A
SECURITY CODE
NNNN
ORIGINAL JOB
1800057180005718000571800057----58585858
SIZE
4444
LANGUAGE
AAAA
THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. . UNPUBLISHED WORK ©2012201220122012 Nuovo Nuovo Nuovo Nuovo Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.. . . . ALL RIGHTS RESERVED.
SHEET
91919191 of of of of 94949494
Customer DCS vs. CCC: 1. 231-XA-0997 PROCESS REMOTE SET-POINT (CTRL OF DISCHARGE HEADER PRESSURE): It is a 4-20mA signal from
Customer DCS to CCC (Master Controller) to perform Load Sharing by Controlling the Compressor Discharge Header Pressure. <4>
2. 231-XS -0305 (DISCHARGE PRESSURE CONTROL ENABLE): It is a contact signal (NO, Closed = Enable) from Customer DCS to CCC to switch over from Suction Header Control Mode to Discharge Header Control Mode. <4>
3. 231-XS-0999 (MCP_SP) (PROCESS REMOTE SET-POINT (CTRL OF SUCTION HEADER PRESSURE): It is a 4-20mA
signal from Customer DCS to CCC (Master Controller) to perform Load Sharing by Controlling the Compressor Suction Header Pressure. <4>
4. 231-XS-2058 (CLOSE ANTISURGE VALVE FOR PURGE): It is a contact signal (Cls=Purge) from Customer DCS to CCC
commanding the antisurge valve for purging sequence. <4>
REVISED WHERE SHOWN <4>
TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTION
DOCUMENT CODE
SOM6629548SOM6629548SOM6629548SOM6629548
REVISION
4444
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE
PAGE MARKER
N/AN/AN/AN/A
SECURITY CODE
NNNN
ORIGINAL JOB
1800057180005718000571800057----58585858
SIZE
4444
LANGUAGE
AAAA
THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. . UNPUBLISHED WORK ©2012201220122012 Nuovo Nuovo Nuovo Nuovo Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.. . . . ALL RIGHTS RESERVED.
SHEET
92929292 of of of of 94949494
8 CONTROL INTERFACE WITH WASTE HEAT RECOVERY UNIT CONTROL SYSTEM
8.1.1 INTERLOCK SIGNALS JOB TAG DESCRIPTION FROM TO TYPE 231-XS-0958 GT Load Greater than 60% MarkVIe DCS HW 231-XS-0955 Purge Phase 1 completed (Bypass stack) MarkVIe DCS HW 231-XS-0954 Duct Burner Purge Changeover Sequence initiated DCS MarkVIe HW 231-XS-254 R GT Running Status MarkVIe PESD HW
231-XS-354 GT Shutdown for HRSG Shutdown and Diverter System failure to close
PESD MarkVIe HW
231-XS-454 HRSG Shutdown condition Reset PESD MarkVIe HW 231-XS-554 Diverter System Close PESD MarkVIe HW 231-XS-654 Diverter System Open PESD MarkVIe HW
231-XS-754 Teg temperature 56 deg. C lower than Fuel Auto Ignition temperature
MarkVIe PESD HW
231-XS-960 Duct Burner Purge Completed BMS MarkVIe HW 231-XS-961 GT Load Greater than 60% MarkVIe BMS HW
8.1.2 SOFTWARE DESCRIPTION GT + HRSG PURGE & START UP (GT/BMS SYSTEMS LOGIC – DCS LOGIC) A purge of both the HRSG enclosure and by-pass system shall be completed prior to the light-off of the GT and prior to the admission of combustion turbine exhaust gas into the HRSG. The purge sequence (GT+HRSG) shall be managed by MarkVIe. Purge shall be accomplished by at least five volume changes and for duration of not less than 5 minutes. During the purge, the flow rate shall be not less than 8% of GT full-load mass air-flow. Depending on the availability of the HRSG, the followings two cases have to be considered: First case - HRSG available When the HRSG is available, the GT can operate in combined cycle mode. In this case both the by-pass stack and the HRSG must be purged. With all the following purge permissives MarkVIe can start the GT/HRSG purge sequence:
• HRSG shutdown not present (231-XS-454) • No GT shutdown causes present and GT trip condition reset (231-XS-254 R) • Diverter damper system close (231-XS-554) that indicates the condition HRSG damper closed &
bypass stack Damper open from PESD) • GT not firing • GT flow rate not less than 8% of GT full-load mass air-flow
The GT+HRSG purge sequence will purge first the By-pass stack (phase 1) and then the HRSG duct (phase 2). At the end of the phase 1, the MarkVIe will send to DCS the hardwire signal 231-XS-0955 (Purge phase 1 completed by GTS) in order to open the diverter system dampers allowing the purge sequence to proceed with the phase 2. The phase 2 is allowed to proceed when the Diverter System Open (231-XS-654) signal is obtained from PESD. The Diverter system Open condition is equivalent to HRSG damper open and by pass
<4>
REVISED WHERE SHOWN <4>
TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTION
DOCUMENT CODE
SOM6629548SOM6629548SOM6629548SOM6629548
REVISION
4444
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE
PAGE MARKER
N/AN/AN/AN/A
SECURITY CODE
NNNN
ORIGINAL JOB
1800057180005718000571800057----58585858
SIZE
4444
LANGUAGE
AAAA
THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. . UNPUBLISHED WORK ©2012201220122012 Nuovo Nuovo Nuovo Nuovo Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.. . . . ALL RIGHTS RESERVED.
SHEET
93939393 of of of of 94949494
damper in closed condition.<4> The purge rate, volume changes and duration will be provided by MarkVIe for both phases. At the purge end (i.e. both the phase 1 and the phase 2 are completed), the GTS will have the permissive to put the GT in service in combined cycle mode through the HRSG. The following signals shall be available from MarkVIe to DCS, by serial link:
• GT+HRSG Purge requested • GT+HRSG Purge in progress (phase 1, phase 2) • GT+HRSG Purge completed (phase 1, phase 2) • GT+HRSG Purge interrupted (phase 1, phase 2)
HRSG purge in Fresh Air (FA) mode The Phase 2 (HRSG duct purge by GTS) could be replaced, as alternative, by the duct burner purge performed in FA mode (FA duct burner purge sequence managed by BMS logic). In this case, after the HRSG duct purging in FA mode the DCS logic, with all the following permissives:
• NOT GT Running (~231-XS-254 R) • HRSG in FA mode • HRSG isolation provided and maintained • Duct burner purge completed by BMS (after HRSG isolation provided and maintained) (231-XS-960)
HRSG duct purging in FA mode enabled by DCS (selection by operator) shall transfer the system to Combined Cycle mode by the following way: when GTS sends the hardwire signal (231-XS-0955) to DCS (purge phase 1 completed by GTS) then the DCS will execute the following sequence: <4>
• Diverter damper system open command • Set the signal: Duct Burner Purge change-over sequence initiated (231-XS-0954) <4>
With the signal, Diverter damper system NOT in close position (~231-XS-554) the DCS shall carry out:
• FA duct damper close command (hardwired signal sent to the Diverter Damper System) With the resulting signals:
• Diverter damper system in open position & FA duct damper in close position (xx seconds delayed) The DCS shall carry out:
• FA fan stop command (FA fan damper will close) • Reset the signal: Duct Burner Purge change-over sequence initiated (231-XS-0954) <4>
The signal: Duct Burner Purge change-over sequence initiated is reset also if at least one of the following conditions is detected:
• HRSG Shutdown • GT running (231-XS-254 R) • GT trip (from PESD to DCS) • Purge phase 1 completed (231-XS-0955) NOT present <4>
This signal is reset, in any case, after a prefixed time (about xx seconds, to allow the complete execution of the transfer sequence to CC mode). MarkVIe will set the condition purge phase 2 completed and will have the permissive to put the GT in service in combined cycle mode, through the HRSG, when MarkVIe verifies the following condition:
• Purge phase 1 completed (231-XS-0955) & <4> • Duct Burner Purge Completed (231-XS-960) from BMS (10 sec Off-Delay in order to allow the
diverter opening) & • Duct Burner Purge change-over sequence initiated (231-XS-0954) & <4> • Diverter Dampers system in open position (231-XS-654).
REVISED WHERE SHOWN <4>
TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTIONCONTROL SYSTEM FUNCTIONAL DESCRIPTION
DOCUMENT CODE
SOM6629548SOM6629548SOM6629548SOM6629548
REVISION
4444
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE
PAGE MARKER
Undef.Undef.Undef.Undef.
SECURITY CODE
NNNN
ORIGINAL JOB
1800057180005718000571800057----58585858
SIZE
4444
LANGUAGE
AAAA
THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l.Nuovo Pignone S.r.l. . UNPUBLISHED WORK ©2012201220122012 Nuovo Nuovo Nuovo Nuovo Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.Pignone S.r.l.. . . . ALL RIGHTS RESERVED.
SHEET
94949494 of of of of 94949494
Second Case - HRSG not available If HRSG shutdown is present (HSRG not available), the GT can operate only in open cycle mode. In this case, MarkVIe can start the GT purge sequence through the by-pass stack (phase 1) if all the following purge permissives are fulfilled:
• No GT shutdown causes present and GT trip condition reset from MarkVIe • Diverter damper system close (231-XS-554) • GT not firing • GT flow rate not less than 8% of GT full-load mass air-flow
The purge rate, volume changes and duration shall be decided by MarkVIe. At the end of the phase 1 (GT+ By-pass stack purge completed), MarkVIe will have the permissive to put the GT in service in open cycle mode (through the by-pass stack). During combined cycle operation and following the GT+HRSG purge as above indicated, the combustion turbine shall be permitted to switch in open cycle mode (by closing the diverter system dampers by DCS) and to purge and operate in open cycle through the by-pass stack. When GT has operated in open cycle through the by-pass stack, then the HRSG purged condition shall be reset. In this case the TEG shall not be permitted to re-enter the HRSG at a later time without HRSG re-purging (the opening of the diverter system dampers shall not been allowed by DCS and PESD). With GT running in open cycle mode through the by-pass stack, then the following two scenarios can be considered:
• HRSG duct shall be purged in FA mode (FA duct burner purge sequence managed by BMS logic. In FA mode it shall be possible to light-off the auxiliary fire burner and start up the HRSG; then the TEG shall be permitted to re-enter the HRSG at a later time (by activating the manual change over sequence from FA mode to CC mode, without lowering the GT load. TEG shall not be permitted to re-enter the HRSG if the HRSG is not in service, pressurized and in hot state.
• The GT is operated with an exhaust gas temperature at least 56°C lower the auto-ignition temperature of fuels (231-XS-754) designed for use in the GT and in the Duct burner (TEG temp. <= xxx °C, to be defined - 231-XS-957).In this case th e TEG, at this lower temperature, shall be permitted to re-enter the HRSG (by opening the diverter system dampers by DCS) and shall be used to perform the duct burner purge (monitored by BMS). After the duct burner purge (hardwired signal from BMS to MarkVIe 231-XS-960), MarkVIe will have the permissive to increase the load. Further limitations in TEG temperature are foreseen according to the actual status of HRSG.
NOTE 1) HRSG isolation shall be considered maintained when all the following conditions are satisfied:
• HRSG damper close (hardwired signal from PESD to DCS) • Sealing air pressure > min (xx sec maintained in order to allow sealing fans change over) (hardwired
signal from PESD to DCS)