Upload
rasheed313
View
229
Download
0
Embed Size (px)
Citation preview
8/12/2019 Control Strategies for Under-Frequency Load Shedding
1/71
eehpower systemslaboratory
Ifigeneia Stefanidou Maria Zerva
Control Strategies for Underfrequency LoadShedding
Interaction of Distributed Generation with Load Shedding
Decentralized UnderFrequency Load Shedding of HouseholdLoads
Semester Thesis
PSL0904
EEH Power Systems Laboratory
Swiss Federal Institute of Technology (ETH) Zurich
Expert: Prof. Dr. Goran Andersson
Supervisor: Dipl.Ing. Stephan Koch
Zurich, September 3, 2009
8/12/2019 Control Strategies for Under-Frequency Load Shedding
2/71
8/12/2019 Control Strategies for Under-Frequency Load Shedding
3/71
Statement regarding plagiarism when submitting written work at ETH Zurich
By signing this statement, I affirm that I have read the information notice on plagiarism,independently produced this paper, and adhered to the general practice of sourcecitation in this subject-area.
Information notice on plagiarism:http://www.ethz.ch/students/semester/plagiarism_s_en.pdf
_______________________ ___________________________________
place and date signature
4/4
http://www.ethz.ch/students/semester/plagiarism_s_en.pdfhttp://www.ethz.ch/students/semester/plagiarism_s_en.pdf8/12/2019 Control Strategies for Under-Frequency Load Shedding
4/71
8/12/2019 Control Strategies for Under-Frequency Load Shedding
5/71
Abstract
The current approach of the Union for the Coordination of Transmission of Electricity for
counteracting large frequency deviations due to lack of generation is the UnderFrequency
Load Shedding scheme. The UnderFrequency Load Shedding scheme is the interruption of
the power supply to a predefined percentage of customers when certain frequency deviations
occur in the system. The drawback of the UnderFrequency Load Shedding scheme is that
loss of load in entire areas occurs, since entire feeders are disconnected from the grid,
and the interaction of the increasing Distributed Generation present in the system is not
considered. The scope of the present study is to evaluate the impact of the Distributed
Generation on the stable and secure electricity transmission systems operation and assess
the performance of the proposed UnderFrequency Household Load Shedding scheme. The
UnderFrequency Household Load Shedding scheme provides a flexible and decentralized
way of mitigation.
8/12/2019 Control Strategies for Under-Frequency Load Shedding
6/71
I. Stefanidou & M. Zerva 0. CONTENTS
Contents
1 Introduction 9
2 UCTE Conventional Load Shedding 11
2.1 Reference Power System . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2.2 Stabilization of the System Frequency . . . . . . . . . . . . . . . . . . . . . 12
2.3 System Modeling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
2.3.1 Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
2.3.2 Dynamics of generators . . . . . . . . . . . . . . . . . . . . . . . . . 14
2.3.3 Frequency Dependency of Loads . . . . . . . . . . . . . . . . . . . . 15
2.3.4 Primary Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
2.3.5 Load Shedding Mechanism . . . . . . . . . . . . . . . . . . . . . . . 17
2.3.6 Frequency Response Model . . . . . . . . . . . . . . . . . . . . . . . 18
3 Interaction of Distributed Generation with Load Shedding 20
3.1 Distributed Generation in Germany . . . . . . . . . . . . . . . . . . . . . . 20
3.2 Penetration Scenarios . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
3.3 Distributed Generation Power Output . . . . . . . . . . . . . . . . . . . . 23
3.4 Frequency Response Model . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
4 Household Load Shedding 27
4.1 Household load profile during the day . . . . . . . . . . . . . . . . . . . . . 27
4.2 The potential of UnderFrequency Household Load Shedding . . . . . . . . 30
4.3 UnderFrequency Household Load Shedding as a complement to Conven
tional Load Shedding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
3
8/12/2019 Control Strategies for Under-Frequency Load Shedding
7/71
4.3.1 Frequency response model . . . . . . . . . . . . . . . . . . . . . . . 35
4.4 UnderFrequency Household Load Shedding for substitution of ConventionalLoad Shedding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
4.4.1 Frequency Response Model . . . . . . . . . . . . . . . . . . . . . . . 38
5 Reference Cases Results 41
5.1 Reference Cases . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
5.1.1 Summer scenario . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
5.1.2 Winter scenario . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
5.2 Simulation Results . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
5.2.1 Case 1 Summer scenario, 11 a.m. . . . . . . . . . . . . . . . . . . 44
5.2.2 Case 2 Summer scenario, 3 a.m. . . . . . . . . . . . . . . . . . . . 50
5.2.3 Case 3 Winter scenario, 11 a.m. . . . . . . . . . . . . . . . . . . . 55
5.2.4 Case 4 Winter scenario, 3 a.m. . . . . . . . . . . . . . . . . . . . . 60
6 Conclusions 65
References 67
8/12/2019 Control Strategies for Under-Frequency Load Shedding
8/71
I. Stefanidou & M. Zerva 0. LIST OF FIGURES
List of Figures
1 Interconnected UCTE Power System [1]. . . . . . . . . . . . . . . . . . . . 11
2 Total system inertia of the interconnected system. . . . . . . . . . . . . . . 15
3 Frequency Dependency of Loads. . . . . . . . . . . . . . . . . . . . . . . . 16
4 Primary Control. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
5 Load Shedding. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
6 Frequency Response Model. . . . . . . . . . . . . . . . . . . . . . . . . . . 19
7 Load density (left) and DG share (right) of each State. . . . . . . . . . . . 22
8 Wind (left) [13] and Solar (right) potential of Germany [14]. . . . . . . . . 25
9 The power system frequency response model, considering the DG loss. . . . 26
10 Share of consumption of the household appliances [5]. . . . . . . . . . . . . 28
11 Power consumption of each household appliance group over the day. . . . . 29
12 Sheddable household load in Germany. . . . . . . . . . . . . . . . . . . . . 33
13 HLS scheme. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
14 Frequency response model including the HLS mechanism. . . . . . . . . . . 36
15 HLS mechanism. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
16 Set of flip flops. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
17 Frequency response model including the substitutional HLS mechanism. . . 39
18 Substitutional HLS mechanism. . . . . . . . . . . . . . . . . . . . . . . . . 40
19 Physical and planned flows within the UCTE [6]. . . . . . . . . . . . . . . 41
20 Summer scenario. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
21 Winter scenario. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
22 Case 1 Dynamic response including DG. . . . . . . . . . . . . . . . . . . 46
5
8/12/2019 Control Strategies for Under-Frequency Load Shedding
9/71
I. Stefanidou & M. Zerva 0. LIST OF FIGURES
23 Case 1 Dynamic response with different household participations. . . . . 46
24 Case 1 Dynamic response without the HLS mechanism and with the participation of 10% of the German households. . . . . . . . . . . . . . . . . . 47
25 Case 1 Dynamic response with 30% and 50% of the German households
participating in the HLS scheme. . . . . . . . . . . . . . . . . . . . . . . . 47
26 Case 1 Dynamic response with 70% and 100% of the German households
participating in the HLS scheme. . . . . . . . . . . . . . . . . . . . . . . . 48
27 Case 1 Dynamic response with HLS scheme substituting the CLS mecha
nism for Germany. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
28 Case 1 Dynamic response with HLS scheme substituting the CLS mecha
nism for Germany. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
29 Case 2 Dynamic response including DG. . . . . . . . . . . . . . . . . . . 51
30 Case 2 Dynamic response with different household participation. . . . . . 51
31 Case 2 Dynamic response without the HLS mechanism and with the par
ticipation of 10% of the German households. . . . . . . . . . . . . . . . . . 52
32 Case 2 Dynamic response with 30% and 50% of the German households
participating in the HLS scheme. . . . . . . . . . . . . . . . . . . . . . . . 52
33 Case 2 Dynamic response with 70% and 100% of the German households
participating in the HLS scheme. . . . . . . . . . . . . . . . . . . . . . . . 53
34 Case 2 Dynamic response with the HLS scheme substituting the CLS
mechanism for Germany. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
35 Case 2 Dynamic response with the HLS scheme substituting the CLS
mechanism for Germany. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
36 Case 3 Dynamic response including DG. . . . . . . . . . . . . . . . . . . 56
37 Case 3 Dynamic response with different household participation. . . . . . 56
38 Case 3 Dynamic response without the HLS mechanism and with the par
ticipation of 10% of the German households. . . . . . . . . . . . . . . . . . 57
6
8/12/2019 Control Strategies for Under-Frequency Load Shedding
10/71
39 Case 3 Dynamic response with 30% and 50% of the German households
participating in the HLS scheme. . . . . . . . . . . . . . . . . . . . . . . . 57
40 Case 3 Dynamic response with 70% and 100% of the German households
participating in the HLS scheme. . . . . . . . . . . . . . . . . . . . . . . . 58
41 Case 3 Dynamic response with the HLS scheme substituting the CLS
mechanism for Germany. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
42 Case 3 Dynamic response with the HLS scheme substituting the CLS
mechanism for Germany. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
43 Case 4 Dynamic response including DG. . . . . . . . . . . . . . . . . . . 61
44 Case 4 Dynamic response with different household participation. . . . . . 61
45 Case 4 Dynamic response without the HLS mechanism and with the par
ticipation of 10% of the German households. . . . . . . . . . . . . . . . . . 62
46 Case 4 Dynamic response with 30% and 50% of the German households
participating in the HLS scheme. . . . . . . . . . . . . . . . . . . . . . . . 62
47 Case 4 Dynamic response with 70% and 100% of the German householdsparticipating in the HLS scheme. . . . . . . . . . . . . . . . . . . . . . . . 63
48 Case 4 Dynamic response with the HLS scheme substituting the CLS
mechanism for Germany. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
49 Case 4 Dynamic response with the HLS scheme substituting the CLS
mechanism for Germany. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
8/12/2019 Control Strategies for Under-Frequency Load Shedding
11/71
List of Tables
1 Load Shedding stages according to the UCTE Handbook [2]. . . . . . . . . 13
2 Type of Loads. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
3 DG installed capacity and penetration scenarios for 2010 and 2020. . . . . 23
4 Power Output. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
5 Comfort loss of each appliance category. . . . . . . . . . . . . . . . . . . . 31
6 Sheddable load per German household. . . . . . . . . . . . . . . . . . . . . 34
7 Case 1 Power data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
8 Case 2 Power data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
9 Case 3 Power data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
10 Case 4 Power data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
8/12/2019 Control Strategies for Under-Frequency Load Shedding
12/71
I. Stefanidou & M. Zerva 1. Introduction
1 Introduction
Power systems provide a vital infrastructure for the functioning of todays societies which
have become increasingly dependent on reliable and secure supply of electricity. Their
operation and structure have significantly evolved over the years incorporating market
mechanisms in the initially monopolistic trade of electricity.
The deregulation of the electricity markets has created challenges concerning the operation
of the systems, while the goal is still to maintain the reliability and the security of supply.
The decoupling of the electricity generation, transmission, distribution and retail and theinvolvement of more participants has led to a more complex environment, both economical
and technological. The interconnection links between different countries do no more serve
emergency but regular trading purposes, resulting in the increasing probability of the
overloading of the tielines. A possible disturbance now affects the whole interconnected
system and can be spread over long distances within seconds and, if not eliminated, it may
result in a complete system collapse.
The liberalization of electricity markets provides free market access to many various par
ticipants, while the trend of the last decades towards reducing greenhouse gas emissionsleads to the development of mainly small scaled, 2free sources for energy production,
which are strongly supported by legislation. Consequently, the integration of distributed
sources into the networks leads to the modification of the structure of the electric power
systems and the initial unidirectional power flows. Therefore, as a side effect of the develop
ment of Distributed Generation units, the traditional protection and control mechanisms
of the power systems, which do not consider the Distributed Generation (DG), turn to be
insufficient or inappropriate.
The security and the quality of supply are the primary goal of the electric power systems,
considering the strong impacts that a disturbance may have on the society and the fact
that electricity as a product cannot be stored on a large scale. However, the security of
power systems is jeopardized by the previously mentioned changes of their operation and
structure. The impact of the Distributed Generation penetration can be assessed by quan
tifying the Distributed Generation and modelling its interaction with the power system.
Future scenarios for increasing the Distributed Generation imply the need for a further
modification of the control methods used under normal or emergency conditions.
9
8/12/2019 Control Strategies for Under-Frequency Load Shedding
13/71
I. Stefanidou & M. Zerva 1. Introduction
The proposed method is the UnderFrequency Household Load Shedding (UFHLS) which
includes the frequency dependent, automatic disconnection of nonvital individual house
hold loads. The UFHLS can be implemented either together with the present control mech
anisms in order to act complementary or for a complete substitution of the existing control
schemes. In each case, the proposed scheme is decentralized in order for the system to
be robust to imminent disturbances, while the shedding of household loads is realized
stepbystep, according to predefined frequency thresholds. Individual household loads are
disconnected with priority to the uncritical ones that are less vital for the consumers, so
as for the interruption of supply to be least observed by the consumers.
The implementation of the UFHLS scheme should ensure the robustness of the power
systems. Therefore, an automatic mechanism is needed in order for the suitable load re
ductions to be realized in every disturbance case, considering the capacity of the system
and the comfort loss for the consumers at any time.
Germany, being among the leaders in technological innovation and a major UCTE member
country, provides a good paradigm for the assessment of the performance of the proposed
HLS mechanism and the interaction of DG in the context of UCTE. For these reasons,
data for the German households and DG are used for the derivation of reference scenarios
appropriate for the simulation of the UCTE power system frequency response in case of acontingency.
10
8/12/2019 Control Strategies for Under-Frequency Load Shedding
14/71
I. Stefanidou & M. Zerva 2. UCTE Conventional Load Shedding
2 UCTE Conventional Load
Shedding
2.1 Reference Power System
The Union for the Coordination of Transmission of Electricity (UCTE) is an association
of the Transmission System Operators (TSOs) of 24 European countries (Figure 1). The
interconnected system handled by the UCTE comprises of 220000 Km of transmission
lines and a total installed capacity of 640 GW.
Figure 1: Interconnected UCTE Power System [1].
The interconnected power systems of the membercountries of the UCTE operate syn
chronously at the nominal frequency of 50 Hz. The UCTE interconnected system was
initially introduced for the cooperation of the TSOs in emergency cases. Over the past
few years the electricity market across Europe has been redesigned and the trade of elec
tricity among European countries has been developed. The use of the interconnections
between countries has shifted from emergency to trade purposes, resulting in the opera
tion of the interconnection links to their limits and, thus, compromising the stability and
the security of the UCTE power system. Therefore, the coordinated actions of the UCTE
membercountries are necessary in order to ensure the secure and reliable operation of the
11
8/12/2019 Control Strategies for Under-Frequency Load Shedding
15/71
I. Stefanidou & M. Zerva 2. UCTE Conventional Load Shedding
system.
The UCTE issues the UCTE Operation Handbook which is a set of technical and operational principles and rules ensuring the reliable performance of the interconnected high
voltage grids of the continental Europe. All UCTE members are bound to comply with
the UCTE and collectively contribute to the stabilization of the system in any emergency
case.
2.2 Stabilization of the System Frequency
Emergency situations within the UCTE power system are mainly indicated by the devia
tions of the system frequency. Since the frequency is approximately equal in all participat
ing countries, the automatic response of the primary controllers in each membercountry
is triggered in order to stabilize the frequency. The secondary control acts then in order to
bring the system frequency back to its nominal value 1. In response to a quasisteadystate 2
frequency deviation of 200 mHz or more [2], the primary control reserves in each UCTE
membercountry are deactivated or activated, in order to restore the power balance of the
system. The primary controllers should be able to stabilize the system in case of a failureup to 3000 MW of the generating capacity in normal operation [2]. The contribution of
each membercountry to the primary reserves is proportional to the ratio of the electricity
produced over the total electricity production across the UCTE. In case that the extent of
the disturbance is higher than the capability of the primary controllers, additional measures
are required, such as the frequency sensitive triggering of load shedding.
The Load Shedding is triggered when the frequency drops to a predefined level, in order to
protect the power generating systems and avoid a major power system breakdown. During
a major disturbance, i.e. a loss of generation, and under emergency conditions when there isinsufficient generation capability for the current demand, the electrical supply is interrupted
to a certain number of consumers in each membercountry of the UCTE according to the
implemented Load Shedding scheme in order to prevent a total collapse of the UCTE
system.
1The secondary control is not regarded, since its dynamics are much slower and out of the scope of the
present study.2The quasisteadystate refers to a stable system frequency but not at the nominal value.
12
8/12/2019 Control Strategies for Under-Frequency Load Shedding
16/71
I. Stefanidou & M. Zerva 2. UCTE Conventional Load Shedding
Each TSO determines its shedding plan according to the rules of the UCTE. The TSOs of
the UCTE participate in the Load Shedding scheme irrespectively of the location of the
failure. The UCTE recommends that the Load Shedding is implemented in three steps and
involves the disconnection of feeders amounting to a predefined share of the load. The first
step of the Load Shedding is initiated at the frequency threshold of 49 Hz by disconnecting
the 1020% of the total load. The second and the third step are triggered at 48.7 Hz and
48.4 Hz, respectively, by disconnecting an additional 1015% of the initial load at each
step (see Table 1).
Frequency Thresholds Load Shedding
49.0 Hz 1020%
48.7 Hz 1015%
48.4 Hz 1015%
Table 1: Load Shedding stages according to the UCTE Handbook [2].
2.3 System Modeling
The interconnecting links among the membercountries of UCTE were traditionally used
under emergency conditions, while, nowadays, they also serve trading purposes and are
known as tielines. Besides the benefits of the interconnection of the power systems, the
regular trading of electricity results in a high possibility of the overloading of the tielines.
A disturbance within the UCTE can be spread over large distances and, in the worst case,
cause a total collapse of the interconnected system.
The power system frequency response model of the UCTE, including the Load Shedding
mechanism recommended by the UCTE, simulates the frequency deviations during normal
and emergency conditions. In order to study the power system of Germany, it is necessary to
also consider the behavior of the whole interconnected system, since the system frequency
is determined by the balance between the total generation and demand. Furthermore, the
power exchanges of the UCTE with other interconnected systems via DC or AC links
influence the frequency response in each membercountry, since a local disturbance can
cause a cascading series of outages within the interconnected system.
13
8/12/2019 Control Strategies for Under-Frequency Load Shedding
17/71
8/12/2019 Control Strategies for Under-Frequency Load Shedding
18/71
I. Stefanidou & M. Zerva 2. UCTE Conventional Load Shedding
=
0
2 (
) (2)
The respective block in the frequency response model describes the total system inertia
and the reflection of the power imbalances on the frequency deviations of the system
(Figure 2). The total system inertia constant is assumed to be equal to 5 seconds, while
the represents the cumulated power rating of the rotating synchronous machines in the
interconnected system under study.
dP
Subtract
Net Import
Load
Integrator
1
s
Generation
Gain
f0/(2*H*S) df
Figure 2: Total system inertia of the interconnected system.
2.3.3 Frequency Dependency of Loads
The frequency dependency of the active power of the loads is taken into account, since the
frequency deviation within a system influences the behavior of the loads. The industrialloads are mainly motors which can store the kinetic energy of their rotating masses. There
fore, a possible frequency drop during a disturbance can be partly stabilized by the stored
kinetic energy of the motors. The commercial and residential loads can also be frequency
dependent, depending on their structure.
Typical values describing the frequency dependency of the loads are expressed in per cent
of the load variation from the total load for one per cent of frequency deviation from the
nominal value (Table 2).
15
8/12/2019 Control Strategies for Under-Frequency Load Shedding
19/71
I. Stefanidou & M. Zerva 2. UCTE Conventional Load Shedding
Load Type dP/df (%/%) Representative Type Share
Residential 0.9 40%
Commercial 1.4 20%
Industrial 2.6 40%
Table 2: Type of Loads.
According to the proposed values for the load models, the frequency dependency of the
active power consumed by the loads can be described by the factor which equals to 1.6
( = 16). The respective block in the frequency response model describes the normalized
active power deviation of the loads resulting from a system frequency deviation (Figure 3).
Frequency deviation
df
Frequency dependent active power
dP1.66*S/f0
Figure 3: Frequency Dependency of Loads.
2.3.4 Primary Control
The primary controllers of the entire UCTE system can eliminate a disturbance caused by
a power deficit not higher than 3000 MW under normal conditions. The primary reserves
in each membercountry of the UCTE are proportional to its generation capacity [2]. In
case of a disturbance, the primary controllers of every country of the interconnected systemcontribute to its elimination. The speed droop characteristic of the interconnected system
under study represents the different operating points of the system. The speed droop of
the system is considered to be approximately equal to the total generated power at each
time instant.
The linearized dynamic modelling of the turbines of the primary reserves is essential, despite
the fact that the turbine controllers time constant is much smaller than the time constant of
the frequency dynamics of the system. The UCTE system is modeled as an onearea system,
16
8/12/2019 Control Strategies for Under-Frequency Load Shedding
20/71
8/12/2019 Control Strategies for Under-Frequency Load Shedding
21/71
I. Stefanidou & M. Zerva 2. UCTE Conventional Load Shedding
Load shed
LS
Load Shedding
df Share of load
load
Frequency
deviation
df
Figure 5: Load Shedding.
2.3.6 Frequency Response Model
The frequency response model is constructed by combining the previously analyzed mech
anisms (Figure 6). The inputs to the modeled power system of the interconnected areas arethe total generated power, the total consumed power and the net imports from neighboring
power systems at each time instant. In case of a disturbance, i.e. loss of generation or un
expected increase of the load, the power deficit is reflected on a system frequency deviation
by means of the generators dynamics and the system inertia constant. Subsequently, the
frequency deviation influences the active power consumption of the frequency dependent
loads and triggers the primary controllers and the load shedding mechanism, according to
the magnitude of the disturbance.
18
8/12/2019 Control Strategies for Under-Frequency Load Shedding
22/71
I. Stefanidou & M. Zerva 2. UCTE Conventional Load Shedding
f0
Turbine dynamics
1
7s+1
System
frequency
freq
Sum of f0+df
Sum of
loads of 24 UCTE countries
SaturationPrimary control
-1/(Spr*f0/S)
Net Import
loadLoad
1
s
Generationf0/(2*H*S)
Frequency dependency of Loads
1.66*S/f0
Conventional
Load Shedding
dfLoad Shed
Figure 6: Frequency Response Model.
19
8/12/2019 Control Strategies for Under-Frequency Load Shedding
23/71
I. Stefanidou & M. Zerva 3. Interaction of Distributed Generation with Load Shedding
3 Interaction of Distributed
Generation with Load Shedding
The term Distributed Generation (DG) is used to characterize electric power sources with
small rating as compared to conventional power plants, which are connected to the dis
tribution grid, i.e. Medium and Low Voltage Level. Distributed Generation has faced a
significant growth, mainly due to the liberalization of the electricity market and the trend
for shifting the electricity production towards 2neutral energy sources for reducing
greenhouse gas emissions and mitigating climate change.
The DG, being mostly renewable energy sources, creates a number of uncertainties in the
power system, in terms of inability to precisely schedule the power injected into the grid.
Additionally, the renewable energy sources that are connected to the distribution grid can
not be directly controlled by the transmission system operators. In case of necessity for
activation of the Load Shedding mechanism due to an imminent disturbance, there is high
probability that additional loss of generation will occur. Feeders that are disconnected in
emergency cases may have Distributed Generation units connected to them, which causes
to the disconnection of the dispersed generation. Thus, the extent of the Distributed Generation loss in such cases should be quantified in order for the interaction to be evaluated.
3.1 Distributed Generation in Germany
The European Union has adopted certain measures for promoting renewable energy sources,
in view of the commitments of the Kyoto Protocol. Germany, as a Member State of the
EU has set specific targets for renewable energy penetration and has achieved to becomethe leader on the grounds of both installations and technical knowhow. In the case of
Germany, most common energy carriers for DG are wind, solar, biomass and to a limited
extent geothermal, hydro and gas power plants.
Four TSOs operate within Germany, i.e. Transpower Stromubertragungs GmbH (company
affiliated with E.ON) [4], Vattenfall Europe Transmission GmbH [5], RWE Transportnetz
Strom GmbH [6] and EnBW Transportnetze AG [7]. According to data published by the
TSOs, Germany has a total installed capacity of 137.5 GW. The renewable energy sources
20
8/12/2019 Control Strategies for Under-Frequency Load Shedding
24/71
I. Stefanidou & M. Zerva 3. Interaction of Distributed Generation with Load Shedding
installations amount to 38029 MW, out of which 12245 MW are installations with a rating
smaller than 10 MW, connected to the low and medium voltage level.
The regionally different renewable energy potential leads to regional differences in the DG
installed capacity of the different energy carriers [8]. In the present study, the power plants
who receive the feedin tariff are divided according to the state of Germany to which they
belong to in order to correspond to the regional potential. Thus, in Northern Germany the
dominant energy carrier is wind, whereas in the Southern Germany DG is mostly solar
installations. Southern Germany has lower shares of DG due to the fact that solar instal
lations have significantly smaller rating and are not yet as developed as wind power units.
For biomass, gas and geothermal installations there is no clear geographical distinction.
Apart from the renewable energy source DG, nonrenewable smallscale Combined Heat
and Power (CHP) plants are also connected to the distribution levels and are disconnected
in the case of load shedding. However, the penetration levels are quite low and there is no
exact data available.
The raw data published by the TSOs concerning the power plants which receive a feedin
tariff have been sorted according to energy carrier, nominal installed capacity and postal
code. The installations data need to be further sorted per State in order for the relation
between the load density3
and the potential of each region to be also considered (Figure 7).The DG shares over the total DG capacity are higher in the Northern States of Germany due
to the high penetration of wind power plants. In States with high DG shares and relatively
low load density the risk of deteriorating the situation, by disconnecting significant amounts
of DG units together with a small portion of load, is higher.
3The load share is assumed to be equal to the population share of each State of Germany.
21
8/12/2019 Control Strategies for Under-Frequency Load Shedding
25/71
I. Stefanidou & M. Zerva 3. Interaction of Distributed Generation with Load Shedding
Figure 7: Load density (left) and DG share (right) of each State.
3.2 Penetration Scenarios
Renewable energy source power plants are expected to further increase in the years to
come. In 2002 Germany set a goal to cover the 14% [9] of the electricity consumption
with renewable energy sources until 2008. The goal has been achieved (14.2%) [10] andhigher targets have been set. Increase of the DG is expected to substantially change the
structure of the electricity transmission and distribution grid, posing great ambiguity to
the effectiveness of the current control mechanisms; the load shedding mechanisms involves
the disconnection of feeders in case of lack of generation irrespectively of the DG units that
they may have connected to them.
The future possible growth of the DG is necessary to be considered in order to quantify the
future DG installations and assess the degree of interaction of the DG with the security
22
8/12/2019 Control Strategies for Under-Frequency Load Shedding
26/71
8/12/2019 Control Strategies for Under-Frequency Load Shedding
27/71
I. Stefanidou & M. Zerva 3. Interaction of Distributed Generation with Load Shedding
the electricity consumption was 14.2%. The difference in the two percentages implies that
the load factors of the renewable energy source power plants are substantially limited by
weather conditions, regional potential and time of the day.
The data published by the TSOs concern either the installed capacity or total energy
production over a year. However, the effect of the DG in the system in emergency cases can
only be assessed by considering the instantaneous injected power from the DG installations,
rather than their installed capacity. The power output of each installation highly depends
on the type of the energy carrier, the weather conditions, the time of the day and the
potential of the region in which it is installed. Therefore, factors which reflect the potential
of each region and the maximum power output for each energy carrier are necessary. The
methodology followed in the present study in order for the factors to be derived is the
normalization of representative parameter for each energy carrier.
The parameter that limits the power output of wind power plants is mainly the wind speed.
The wind power potential of each region of Germany is derived based on statistical data
concerning the mean wind speed in each State for every month of the year. The mean
wind speed of every State in each month is divided by the maximum mean wind speed in
Germany over a year. The normalized wind speeds are considered as factors which scale
the wind power output. A factor of 1 is attributed to the region with the highest potentialand for the month with the highest mean wind speed.
As far as solar panels are concerned, the parameters taken into account are the mean
irradiation in each region during the year and the mean duration of sunshine. Similar to
wind power and based on statistical data, the factors for solar power correspond to the
normalized irradiation in each State (Figure 8). For the solar panels optimal inclination is
assumed, providing the opportunity to have the maximum possible power output.
For geothermal, hydro, gas and biomass power plants it is assumed that the power output
is independent of weather conditions, regional distribution and time of the day. Therefore,
uniform factors are considered to limit the power output and approximate their contribu
tion to the total Distributed Generation.
The factors calculated for each energy carrier are multiplied with the installed capacity,
and, therefore, the energy injected into the system is calculated for the time snapshots for
which UCTE publishes load and power exchange data (Table 4).
24
8/12/2019 Control Strategies for Under-Frequency Load Shedding
28/71
I. Stefanidou & M. Zerva 3. Interaction of Distributed Generation with Load Shedding
Figure 8: Wind (left) [13] and Solar (right) potential of Germany [14].
Energy Carrier
OUTPUT (MW)
Winter Summer11 a.m 3 a.m 11 a.m 3 a.m
Solar 853.05 0 2202.51 0
Wind 5279.58 5279.58 3981.70 3981.70
Biomass 1684.62 1684.62 1684.62 1684.62
Geothermal 426.54 426.54 426.54 426.54
Hydro 2.90 2.90 2.90 2.90
Gas 512.06 512.06 512.06 512.06
Table 4: Power Output.
3.4 Frequency Response Model
The Distributed Generation loss at each load shedding stage is assumed to be 10% of
the total Distributed Generation output injected into the system at each time instant. In
the power system frequency response model (Figure 9) the Distributed Generation taken
25
8/12/2019 Control Strategies for Under-Frequency Load Shedding
29/71
8/12/2019 Control Strategies for Under-Frequency Load Shedding
30/71
I. Stefanidou & M. Zerva 4. Household Load Shedding
4 Household Load Shedding
Underfrequency load shedding is traditionally triggered when the power system suffers
from a lack of generation, i.e. sudden loss of generation or increase of load. In order to
stabilize the frequency, entire feeders are disconnected from the grid, while unexpected
additional loss of generation may occur due to disconnection of Distributed Generation
connected to the distribution level. With increasing Distributed Generation the conven
tional underfrequency load shedding scheme cannot guarantee the stabilization of the
system, which could be avoided by the development of automated and locally controlled
load shedding schemes.
The UnderFrequency Household Load Shedding (HLS) is a decentralized scheme under
which households participate with small scale appliances in the grid control schemes. In the
case of an underfrequency disturbance, the appliance operation can be influenced by control
commands sent through a communication interface by a decentralized control system,
equipped with suitable control algorithms. Aiming to the minimum cost for the society
and to the minimum comfort loss for the consumers, a fast and graceful load reduction can
be achieved and a total system collapse can be prevented by shedding nonvital, individual
household loads.
The HLS scheme can act either as a complement to the Conventional Load Shedding (CLS)
mechanism, and, thus, delay or even avoid its triggering, or for complete substitution of
the CLS, depending on the implementation of the scheme. The potential of the HLS is
studied, in compliance with the quantified Distributed Generation, for the household load
of Germany.
4.1 Household load profile during the day
The household load in each time instant is highly dependent on the weather conditions,
the time of the day and the lifestyle in the region under study. Germany has a total of
39700000 households [15] which according to statistical data are responsible for approx
imately 30% [5] of the total load of Germany in average. In 2008, the total electricity
consumption in Germany was 557162 GWh [1]. Considering the percentage share of the
household consumption over the total consumption of Germany, German households ap
27
8/12/2019 Control Strategies for Under-Frequency Load Shedding
31/71
I. Stefanidou & M. Zerva 4. Household Load Shedding
proximately consumed in 2008 167149 GWh, which corresponds to an average household
load of 19081 MW.
For load shedding purposes the vital load of each household is not considered, whereas
for the nonvital appliances their specific consumption has to be quantified. Due to their
volatility, the devices within a household are grouped according to their similarities in their
characteristics, i.e. usage, and classified considering the utilization and comfort loss over
the day.
The German household appliances are categorized according to their aggregate consump
tion over a year (Figure 10). Based on statistical data [16] and considering the total house
hold consumption over the year, the average consumption during the day of each appliancegroup can be computed. In order to quantify the potential of the HLS scheme, the specific
utilization factors of each appliance group have to be defined. For this purpose, typical
utilization patterns of each appliance group are considered. The specific utilization fac
tors are, thus, derived from the normalization of the instantaneous consumption of each
appliance group with its average consumption over the day.
TV- HiFi
Refrigerators-FreezersWashing
7%
22%12%
arm-waterboilers
14%Small electric
devices23%
ElectricHeating
3%
Lighting9%
Cookingappliances
10%
Figure 10: Share of consumption of the household appliances [5].
The specific consumption of each appliance group, which equals to the product of the
normalized utilization and the average consumption, describes the household consumption
28
8/12/2019 Control Strategies for Under-Frequency Load Shedding
32/71
I. Stefanidou & M. Zerva 4. Household Load Shedding
of each appliance group during the day, including both the vital and non vital loads
(Figure 11).
40
50
60
70
80
Load[G
W]
Small devices
TV-Hifi
Cooking devices
Lighting
Washing and
drying devicesElectric heating
Warm-water boiler
0
10
20
30
0:00
0:45
1:30
2:15
3:00
3:45
4:30
5:15
6:00
6:45
7:30
8:15
9:00
9:45
10:30
11:15
12:00
12:45
13:30
14:15
15:00
15:45
16:30
17:15
18:00
18:45
19:30
20:15
21:00
21:45
22:30
23:15
Time of the day
Refrigerator-Freezer
Total German loadprofile
Figure 11: Power consumption of each household appliance group over the day.
The groups that include thermal appliances are considered to be nonvital due to their
high inertia which makes the interruption of their power supply hardly observed by the
consumers. Such appliances are the refrigerators, the freezers, the warmwater boilers and
the electric heating. It is assumed that this group of appliances offers control reserves
during the day, constituting the base load 4. Therefore, refrigerators, freezers and boilers are
assumed to have constant utilization during the day and, therefore, provide a constant base
household load for the HLS scheme. However, the utilization of the rest of the appliance
groups varies during the day, shaping the household load profile curve and significantly
4Warmwater boilers power consumption is often shifted to the night due to special tariffs. However, in
the present study, the are assumed to participate in a load control scheme and have constant consumption
over the day.
29
8/12/2019 Control Strategies for Under-Frequency Load Shedding
33/71
I. Stefanidou & M. Zerva 4. Household Load Shedding
differentiating the household load during the day. The base household load over the whole
day is approximately 8.5 GW, while the household load peak can be found during the
evening hours and is in the order of 30 GW.
The potential of the HLS scheme is perceived as the total sheddable household load at
each time instant, considering only the nonvital devices and their respective consumption.
The nonvital devices, i.e. the sheddable devices, are prioritized using as a criterion their
comfort loss. Comfort loss can be defined as an indicator for assessing the degree of the
annoyance caused to the consumers by shedding a specific appliance group. Appliances are
characterized by their comfort loss representing the extent to which their disconnection
is observed by the consumers. The comfort loss is not considered to be uniform for each
device over the day or over the year, but varies according to the utilization and necessity.
4.2 The potential of UnderFrequency Household
Load Shedding
In the previous Section 4.1, the sheddable household load has been defined as the non
vital devices within a household. Additionally, each device has been attributed with a
factor indicating its individual comfort loss. Since the goal is to develop a simple, flexible
and fast mechanism for the decentralized HLS scheme, the nonvital devices are further
categorized. Each category is characterized by a single value of comfort loss (Table 5).
However, each category does not have constant comfort loss over the day and over the
year, since there are significant variations of the lifestyle and the weather conditions.
The thermal appliances together with the battery chargers represent the category with
the lowest comfort loss, and thus, the first appliance category to be shed. The washingappliances, including the washing machine, the dishwasher and the dryer, are also of
constant and relatively low comfort loss during the day and during the year, representing
the second category to be shed. Electric heating is not in operation during the summer,
and therefore, its contribution to the available sheddable load is zero during the summer.
However, during the winter the utilization of electric heating is assumed to be constant
over the day.
The comfort loss of the lights is higher during the night and during the winter than during
30
8/12/2019 Control Strategies for Under-Frequency Load Shedding
34/71
I. Stefanidou & M. Zerva 4. Household Load Shedding
Appliances Categories Comfort Loss
0:00 5.30 5.30 15:00 14:30 20:00 20:00 24:00
Refrigerator Freezer
1 1 1 1Warm water boilerElectrical heating
Battery charger
Lights 6 3 3 4
Microwave Oven
4 5 4 3Oven
Coffee Machine
Iron
1 4 5 5Vacuum MachineHair Dryer
Washing Machine
2 2 2 2Dryer
Dishwasher
TV
5 6 6 6DVD
HiFi
Table 5: Comfort loss of each appliance category.
31
8/12/2019 Control Strategies for Under-Frequency Load Shedding
35/71
I. Stefanidou & M. Zerva 4. Household Load Shedding
the day and summer, respectively. The cooking appliances, including the microwave oven,
the electric oven and the coffeemachine, are mainly switched on during the morning and
early evening hours. Therefore, their utilization as well as their comfort loss is increased
during these hours. The small electric devices represent the nonvital load, such as the iron,
the vacuum cleaner and the hairdryer. Their comfort loss is highly dependent on their
utilization which is assumed to be higher during the evening. The most critical appliance
category includes the devices whose shedding is immediately realized by the consumers,
such as TV, DVD and HiFi, and may cause annoyance to the users. Their utilization and,
consequently, their comfort loss is high during the evening and before midnight, making
them the last load to be shed during the day, whereas their utilization is high during the
evening and before midnight.
The comfort loss indicators of most of the appliance categories vary during the day, since
their utilization and necessity also vary. Therefore, the shedding order of these appliance
categories should change according to their comfort loss. The comfort loss indicators de
termine the shedding order of the appliances categories at each time instant. Since the
main target of the HLS is the stabilization of the system in case of a disturbance with the
minimum comfort loss to the consumers and HLS is a decentralized scheme, it is necessary
that the shedding order of the appliance categories is updated automatically. It is assumed
that the data concerning the available sheddable load of each category and the shedding
order of the appliances are updated four times per day, representing roughly the changes
of the comfort loss values.
Based on the previous assumptions and on the instantaneous consumption of each appliance
group, the potential of the HLS scheme considering the total sheddable household load of
Germany, i.e. 39700000 households, during the day can be computed. Considering also the
shedding order of the appliance categories, the percentage of the total German load to be
shed at each step of the HLS scheme provides an indicator of the efficiency of the scheme
during a disturbance in the power system (Figure 12). The numbering of the categories
order to be shed corresponds to the value of the comfort loss for each appliance category.
32
8/12/2019 Control Strategies for Under-Frequency Load Shedding
36/71
I. Stefanidou & M. Zerva 4. Household Load Shedding
20,00%
25,00%
30,00%
35,00%
40,00%
45,00%Category 6
Category 5
Category 4
Category 3
Category 2
Category 1
otal share ofGerman load
0,00%
5,00%
10,00%
15,00%
20,00%
25,00%
30,00%
35,00%
40,00%
45,00%
0:00
1:00
2:00
3:00
4:00
5:00
6:00
7:00
8:00
9:00
10:00
11:00
12:00
13:00
14:00
15:00
16:00
17:00
18:00
19:00
20:00
21:00
22:00
23:00
Category 6
Category 5
Category 4
Category 3
Category 2
Category 1
otal share ofGerman load
Figure 12: Sheddable household load in Germany.
The base household load consisting of the thermal appliances and the battery chargers
constitutes during the day the first household loads to be shed, providing for the HLS
scheme a potential of almost 10% of the total German load. Due to the varying utilization,
functionality and comfort loss indicators of the rest of the appliance categories, the total
available sheddable household load in Germany is not constant during the day, but ranges
from 12% to 35% of the total German load.
The HLS scheme can be implemented either for prevention of the triggering of the CLS or
for complete substitution of CLS. The potential of the HLS scheme depends in both cases
on the time of the day, i.e. the load conditions, whereas the applied mechanism and the
demands for the available sheddable load of each function differ. By implementing the HLS
scheme as a complement to CLS, the main target is to delay or even prevent the triggering
of CLS by shedding individual household loads before the frequency drops to the predefined
thresholds of CLS. In this case, the number of German households considered determine
33
8/12/2019 Control Strategies for Under-Frequency Load Shedding
37/71
I. Stefanidou & M. Zerva 4. Household Load Shedding
the potential of the scheme.
In order to assess the potential of the HLS scheme at the time frames for which a completeset of data is available, the total sheddable load within a German household should be
quantified for 3 a.m. and 11 a.m. on a winter and on a summer day (Table 4.2). As
expected, during the night the available sheddable load is significantly lower, while it is
slightly differentiated between winter and summer days.
Electrical devices
Available Sheddable load
per Household (in W)
Winter Summer
11 a.m 3 a.m 11 a.m 3 a.m
Refrigerator 105.738 105.738 105.738 105.738
Warm water boiler 62.288 62.288 62.288 62.288
Electrical Heating 1.142 1.142 0.000 0.000
Battery charger 9.803 1.634 9.803 1.634
Nonvital lights 4.949 1.252 4.949 1.252
Microwave Oven 25.000 0.000 25.000 0.000
Oven 100.001 0.000 100.001 0.000
Coffee Machine 19.606 3.268 19.606 3.268Iron 14.705 2.451 14.705 2.451
Vacuum Machine 19.606 3.268 19.606 3.268
Hair Dryer 19.606 3.268 19.606 3.268
Washing Machine 38.346 0.000 38.346 0.000
Dryer 30.677 0.000 30.677 0.000
Dishwasher 20.707 0.000 20.707 0.000
TV 4.129 0.000 4.129 0.000
DVD 1.032 0.000 1.032 0.000AudioHiFi 2.064 0.000 2.064 0.000
Table 6: Sheddable load per German household.
34
8/12/2019 Control Strategies for Under-Frequency Load Shedding
38/71
I. Stefanidou & M. Zerva 4. Household Load Shedding
4.3 UnderFrequency Household Load Shedding as a
complement to Conventional Load SheddingThe HLS scheme as a complement to the CLS is triggered at thresholds higher than those
defined for the CLS. The goal is to delay or preferably prevent the triggering of CLS, thus
minimizing the costs related to the disturbance and the comfort loss to the consumers.
There are six frequency thresholds defined, corresponding to the six levels of comfort loss
(Figure 13). Taking into account the tolerance for the frequency deviation from its nominal
value of 50 Hz and in an attempt to prevent the unnecessary triggering of the HLS, the
first frequency threshold is set to 49.8 Hz. The frequency threshold for the CLS is set bythe UCTE to 49 Hz. Thus, the frequency steps for the HLS are set to 0.1 Hz, i.e. the range
49.849.3 Hz.
Figure 13: HLS scheme.
4.3.1 Frequency response model
The HLS scheme is implemented complementary to the CLS mechanism in order to delay
or even prevent the complete loss of load in certain areas under emergency conditions.
Therefore, the performance of the HLS scheme as a complement to the CLS mechanism
can be quantified by additionally including in the frequency response model of the inter
35
8/12/2019 Control Strategies for Under-Frequency Load Shedding
39/71
I. Stefanidou & M. Zerva 4. Household Load Shedding
connected system the block describing the function of the HLS mechanism (Figure 14).
The input to the HLS block is the frequency deviation from its nominal value. When the
system frequency drops to the predefined thresholds, the HLS mechanism is triggered and
the respective household load category is disconnected (Figure 15). The lookup table cor
responds the number of HLS stages being triggered to the cumulative household load that
has to be shed. Since the system frequency is sampled in variable steps, a set of flip flops is
implemented in order to avoid the multiple consideration of each household category that
is shed (Figure 16).
1
0
f0
Turbine dynamics
1
7s+1
System inertia
f0/(2*H*S)
Sum of f0+df
Sum of
loads of 24 UCTE countries
SaturationPrimary control
-1/(Spr*f0/S)
Net Import
Load
Load
1
s
Households Load Shedding
dfHousehold Load shed
Generation
Frequency Dependency of Loads
1.66*S/f0
Final f
freq
Distributed
Generation
DG
Conventional
Load Shedding
dfLoad shed
Figure 14: Frequency response model including the HLS mechanism.
The coordination of the two load shedding schemes, i.e. the CLS and the HLS, is crucial for
the stability of the system when the CLS is triggered. The degree of correlation of the two
load shedding schemes significantly depends on the number of households participating in
the HLS scheme and the plan according to which feeders are shed for the CLS. The main
point of interest is the assessment of the performance of the HLS, since the CLS is already
implemented and welldefined. Therefore, it is assumed that once the CLS is not prevented,
36
8/12/2019 Control Strategies for Under-Frequency Load Shedding
40/71
I. Stefanidou & M. Zerva 4. Household Load Shedding
it acts completely independently from the HLS by shedding the predefined share of total
load, whereas the HLS acts until the CLS is triggered.
HouseholdLoad Shed
1
Subtract
Lookup Table
In1 Out1
In1 Out1
In1 Out1
In1 Out1
In1 Out1
In1 Out1
-0.8
-0.6
-0.8
-0.5
-0.8
-0.4
-0.8
-0.2
-0.8
-0.7
-0.8
-0.3
6th stage
upulo
5th stage
upulo
4th stage
upulo
3rd stage
upulo
2nd stage
upulo
1st stage
upulo
df
1
Figure 15: HLS mechanism.
Out1
1
S
R
Q
!Q
S
R
Q
!Q Logical
Operator
OR
Detect
Decrease
U < U/z
Data Type Conversion
boolean
0
In1
1
Figure 16: Set of flip flops.
37
8/12/2019 Control Strategies for Under-Frequency Load Shedding
41/71
I. Stefanidou & M. Zerva 4. Household Load Shedding
4.4 UnderFrequency Household Load Shedding for
substitution of Conventional Load SheddingThe HLS scheme can be alternatively implemented for substitution of the CLS scheme.
The goal is to completely substitute the function of the CLS with the HLS scheme while
being compliant with the UCTE guidelines regarding the emergency measures. Therefore,
the frequency thresholds for the HLS scheme as a substitution of the CLS are set equal
to those of the CLS, whereas at each frequency threshold the household load to be shed
should equal to 10% of the total German load.
The category with the lowest comfort loss, i.e. the refrigerators, boilers and electric heating,can successfully fulfill the UCTE requirements for the first load shedding step, assuming
the participation of 100% of the German households (39 million) in the HLS scheme.
For the subsequent load shedding steps, the shedding order of the devices categories is
maintained. Thus, the devices categories are grouped together, so as the sheddable load
at each shedding step amounts at least to 10% of the total German load. In the case that
the sheddable household load is insufficient to cover 10% of the total German load for
the second and third load shedding stages, the household loads are grouped in a way to
amount to the maximum available load. Of interest in the present study is the capability ofthe Household Load Shedding scheme to completely substitute the existing load shedding
schemes.
4.4.1 Frequency Response Model
The performance of the HLS scheme for the complete substitution of the CLS can be
described by completely substituting the CLS block by the HLS block in the frequency
response of the UCTE power system (Figure 17). The contribution of the DG to the totalgeneration of the UCTE is considered, whereas the additional loss of generation due to loss
of DG is avoided, since feeders are not shed.
38
8/12/2019 Control Strategies for Under-Frequency Load Shedding
42/71
8/12/2019 Control Strategies for Under-Frequency Load Shedding
43/71
I. Stefanidou & M. Zerva 4. Household Load Shedding
Household
Load shed
1
Lookup Table
In1 Out1
In1 Out1
In1 Out1
-1.6
-1
-1.6
-1.3
3rd stage
8/12/2019 Control Strategies for Under-Frequency Load Shedding
44/71
I. Stefanidou & M. Zerva 5. Reference Cases Results
5 Reference Cases Results
The purpose of the frequency control mechanisms of the power system is to maintain the
power balance between the generation and consumption and, thus, guarantee the reliability
and the security of the system. Deregulation of the electricity market has boosted the
international trade of electricity and, therefore, has forced the interconnected power system
to operate closer to its limits. The tripping of a generator, the tripping of a transmission
line or the sudden increase of the load may result in the decrease of the frequency from
its nominal value. In case of lack of generation, the frequency drops from its nominal
value and all member countries of the UCTE follow certain procedures defined in the
UCTE Operation Handbook, so as to stabilize the system and prevent the spreading of
the disturbance.
Figure 19: Physical and planned flows within the UCTE [6].
Under normal conditions, the crossborder exchanges vary significantly according to time,
weather conditions and locality. Tielines which were initially built for emergency and aux
iliary purposes are used nowadays for trading. For the protection and the security of the
system, the traded quantities and the power flows are planned and the stability of the
system is tested ahead by simulation. However, the physical flows may differ from the
planned ones, further stressing the system and making it more vulnerable to imminent
disturbances (Figure 19). Considering the fact that limited capacity mainly exists for the
interconnections of the control zones rather than for the transmissions system within a
41
8/12/2019 Control Strategies for Under-Frequency Load Shedding
45/71
I. Stefanidou & M. Zerva 5. Reference Cases Results
control zone, the study cases include the outage of the interconnection lines and, subse
quently, the islanding of areas. Therefore, in order to artificially create disturbances within
the UCTE power system, the loadgeneration balance is affected either by the outage of
interconnection lines or by the outage of generators.
5.1 Reference Cases
In the context of this study, the effects of the Distributed Generation present in the systemand the effectiveness of the conventional and the household load shedding are evaluated
through two study cases. In both cases, the disturbance is a lack of generation due to
the islanding of parts of the UCTE system. Individual control zones are kept intact, i.e.
there is no tripping of transmission lines within the control zones. The lack of generation
is attributed to the loss of interconnection lines, i.e. loss of net import and probably also
generation loss, since a major disturbance is mainly caused by the cumulative impact of
such incidents. The set of data available by the UCTE limits the appropriate time snapshots
for which the power system frequency response can be evaluated at 3 a.m. and at 11 a.m.For completeness reasons, the cases are evaluated for different seasons of the year, so as to
represent the different weather conditions and subsequently the different household load
and Distributed Generation values.
5.1.1 Summer scenario
The summer day scenario includes the islanding of four countries, i.e. Germany, Switzer
land, Austria and Italy and the additional loss of 12 GW of generation within Italy (Fig
ure 20). The data used concern the 16th of July 2008, for which the UCTE load peaks
during the summer and sufficient published data are available. Under the emergency con
ditions, where interconnections to all other UCTE member countries, as well as the DC
link to the Nordic countries, are lost, the power deficit at 11 a.m. is 14561 MW, while at
3 a.m. the power deficit of the islanded system is 17748 MW.
42
8/12/2019 Control Strategies for Under-Frequency Load Shedding
46/71
8/12/2019 Control Strategies for Under-Frequency Load Shedding
47/71
I. Stefanidou & M. Zerva 5. Reference Cases Results
Figure 21: Winter scenario.
5.2 Simulation Results
The frequency response of the power system to the disturbance reference cases is simulated
in the environment of MATLAB with the toolbox SIMULINK. The derived model for
the interconnected system of UCTE (see Section) is such that no time delay at the load
shedding stages across the UCTE member countries is assumed. The data concerning the
potential of DG and the household load of Germany and the UCTE published data of the
system net import and load are used as inputs to the model.
5.2.1 Case 1 Summer scenario, 11 a.m.
The first case considered represents the summer scenario at 11 a.m. The data used as inputs
to the frequency response model in order for the first case to be simulated are presented
at the following Table 7.
44
8/12/2019 Control Strategies for Under-Frequency Load Shedding
48/71
8/12/2019 Control Strategies for Under-Frequency Load Shedding
49/71
I. Stefanidou & M. Zerva 5. Reference Cases Results
0 5 10 15 20 25 30 35 40
48.8
49
49.2
49.4
49.6
49.8
50
50.2
Time [sec]
Frequency
[Hz
]
2008, 7.11% from DG2010 BEE e.V, 10.43% from DG
2020 BEE e.V, 31% from DG
2010 Leits., 9.67% from DG
2020 Leits., 20.12% from DG
No DG installations considered
Figure 22: Case 1 Dynamic response including DG.
0 5 10 15 20 25 30 35 4049
49.1
49.2
49.3
49.4
49.5
49.6
49.7
49.8
49.9
50
Time [sec]
Frequency
[Hz
]
CLS with DG considered
10% HLS participation
30% HLS participation
50% HLS participation
70% HLS participation
100% HLS participation
Figure 23: Case 1 Dynamic response with different household participations.
46
8/12/2019 Control Strategies for Under-Frequency Load Shedding
50/71
8/12/2019 Control Strategies for Under-Frequency Load Shedding
51/71
I. Stefanidou & M. Zerva 5. Reference Cases Results
0 10 20 30 4049.2
49.4
49.6
49.8
50
Time [sec]
Frequency
[Hz]
70% Participation of Households
0 10 20 30 4049.5
49.6
49.7
49.8
49.9
50
100% Participation of Households
Time [sec]
Frequency
[Hz]
0 10 20 30 4020
10
0
10
20
Time [sec]
Pow
er
[GW]
0 10 20 30 40
20
10
0
10
20
Time [sec]
Pow
er
[GW]
dPCLSHLS
dPCLSHLS
Figure 26: Case 1 Dynamic response with 70% and 100% of the German households
participating in the HLS scheme.
0 5 10 15 20 25 30 35 4049
49.2
49.4
49.6
49.8
50
50.2
50.4
Time [sec]
Frequency
[Hz
]
CLS without considering DGCLS considering DGHLS
Figure 27: Case 1 Dynamic response with HLS scheme substituting the CLS mechanism
for Germany.
48
8/12/2019 Control Strategies for Under-Frequency Load Shedding
52/71
I. Stefanidou & M. Zerva 5. Reference Cases Results
0 5 10 15 20 25 30 35 4049.5
49.6
49.7
49.8
49.9
50
Time [sec]
Frequency
[Hz]
0 5 10 15 20 25 30 35 4020
10
0
10
20
Time [sec]
Pow
er
[GW]
HLS
dP
Figure 28: Case 1 Dynamic response with HLS scheme substituting the CLS mechanism
for Germany.
49
8/12/2019 Control Strategies for Under-Frequency Load Shedding
53/71
I. Stefanidou & M. Zerva 5. Reference Cases Results
5.2.2 Case 2 Summer scenario, 3 a.m.
The second case studied represent the summer scenario at 3 a.m. The set of input data to
the frequency response model for the second case are given in the following Table 8.
Generation 74429 MW
Load 92177 MW
Net import 0 MW
Power deficit 17748 MW
Sheddable load per household 188.17 W
DG installed capacity 2008 6607.82 MWDG 2010 BEE e.V. 8126.16 MW
DG 2020 BEE e.V. 15570.84 MW
DG 2010 Leitszenario 2008 7680.53 MW
DG 2020 Leitszenario 2008 14884.87 MW
Table 8: Case 2 Power data.
The power deficit of 17.75 GW is compensated by the activation of two underfrequency
load shedding stages, i.e. the frequency decay is intercepted at 48.7 Hz. Distributed Gen
eration represents 8.88% of the total generation, with this share rising up to 20.92% in the
future penetration scenarios (Figure 29).
The activation effect of the HLS mechanism can be observed due to the small delay of
the triggering of the two required stages of the CLS (Figure 30. However, the large power
deficit combined with the low household load during the night limits the effectiveness of
the HLS. Therefore, the triggering of the CLS is not avoided even under the favorable
conditions of 100% of households participation (Figures 31, 32, 33).
In the case of the complete substitution of the CLS by the HLS the sheddable household
load is insufficient for covering the UCTEcompliant second load shedding stage (20% of
the total German load). The inability of the HLS scheme to cover the second load shedding
step during the night was expected according to the quantified sheddable load potential
which does not exceed the 15% of the total German load (Figures 34, 35).
50
8/12/2019 Control Strategies for Under-Frequency Load Shedding
54/71
I. Stefanidou & M. Zerva 5. Reference Cases Results
0 5 10 15 20 25 30 35 4048.6
48.8
49
49.2
49.4
49.6
49.8
50
50.2
50.4
Time [sec]
Frequency
[Hz
]
2008, 8.88% from DG
2010 BEE e.V, 10.92% from DG2020 BEE e.V, 20.92% from DG
2010 Leits., 10.32% from DG
2020, Leits., 20% from DG
No DG installations considered
Figure 29: Case 2 Dynamic response including DG.
0 5 10 15 20 25 30 35 4048.6
48.8
49
49.2
49.4
49.6
49.8
50
Time [sec]
Frequency
[Hz
]
CLS with DG considered
10% HLS participation
30% HLS participation
50% HLS participation
70% HLS participation
100% HLS participation
Figure 30: Case 2 Dynamic response with different household participation.
51
8/12/2019 Control Strategies for Under-Frequency Load Shedding
55/71
I. Stefanidou & M. Zerva 5. Reference Cases Results
0 10 20 30 4048.5
49
49.5
50
Time [sec]
Frequency
[Hz]
Without HLS
0 10 20 30 4048.5
49
49.5
50
10% Participation of Households
Time [sec]
Frequency
[Hz]
0 10 20 30 4020
10
0
10
20
Time [sec]
Pow
er
[GW]
0 10 20 30 40
20
10
0
10
20
Time [sec]
Pow
er
[GW]
dPCLSHLS
dPCLSHLS
Figure 31: Case 2 Dynamic response without the HLS mechanism and with the partici
pation of 10% of the German households.
0 10 20 30 4048.5
49
49.5
50
Time [sec]
Frequency
[Hz]
30% Participation of Households
0 10 20 30 4048.5
49
49.5
5050% Participation of Households
Time [sec]
Frequency
[Hz]
0 10 20 30 4020
10
0
10
20
Time [sec]
Power
[GW
]
0 10 20 30 40
20
10
0
10
20
Time [sec]
Power
[GW
]
dPCLSHLS
dPCLSHLS
Figure 32: Case 2 Dynamic response with 30% and 50% of the German households
participating in the HLS scheme.
52
8/12/2019 Control Strategies for Under-Frequency Load Shedding
56/71
I. Stefanidou & M. Zerva 5. Reference Cases Results
0 10 20 30 4048.5
49
49.5
50
Time [sec]
Frequency
[Hz]
70% Participation of Households
0 10 20 30 4048.5
49
49.5
50
100% Participation of Households
Time [sec]
Frequency
[Hz]
0 10 20 30 4020
10
0
10
20
Time [sec]
Pow
er
[GW]
0 10 20 30 40
20
10
0
10
20
Time [sec]
Pow
er
[GW]
dPCLSHLS
dPCLSHLS
Figure 33: Case 2 Dynamic response with 70% and 100% of the German households
participating in the HLS scheme.
0 5 10 15 20 25 30 35 4048.6
48.8
49
49.2
49.4
49.6
49.8
50
50.2
50.4
Time [sec]
Frequency
[Hz
]
CLS without considering DGCLS considering DGHLS
Figure 34: Case 2 Dynamic response with the HLS scheme substituting the CLS mecha
nism for Germany.
53
8/12/2019 Control Strategies for Under-Frequency Load Shedding
57/71
I. Stefanidou & M. Zerva 5. Reference Cases Results
0 5 10 15 20 25 30 35 4048.5
49
49.5
50
Time [sec]
Frequency
[Hz]
0 5 10 15 20 25 30 35 4020
10
0
10
20
Time [sec]
Pow
er
[GW]
HLSdP
Figure 35: Case 2 Dynamic response with the HLS scheme substituting the CLS mecha
nism for Germany.
54
8/12/2019 Control Strategies for Under-Frequency Load Shedding
58/71
I. Stefanidou & M. Zerva 5. Reference Cases Results
5.2.3 Case 3 Winter scenario, 11 a.m.
The input data to the frequency response model in the third case, representing the winter
scenario at 11 a.m. are shown in the following Table 9.
Generation 210557 MW
Load 221883 MW
Net import 30 MW
Power deficit 11296 MW
Sheddable load per household 484.40 W
DG installed capacity 2008 8758.75 MWDG 2010 BEE e.V. 11623.26 MW
DG 2020 BEE e.V. 27620.6 MW
DG 2010 Leitszenario 2008 10847.25 MW
DG 2020 Leitszenario 2008 20989.82 MW
Table 9: Case 3 Power data.
The system under study of the second scenario is larger and therefore more robust. The
power deficit of 11.3 GW is compensated with the activation of the first underfrequency
load shedding stage. The contribution of the Distributed Generation is significantly smaller
(4.16%) and thus, the negative effects of the additional loss of generation due to load
shedding are less observable (Figure 36).
The household load of the 30% of the German households proves to be sufficient to cover
the power deficit of the system under study, without shedding the category with the highest
comfort loss. The 50% of the German households have a total sheddable load enough to
stabilize the system frequency with only four HLS stages triggered (Figures 37, 38, 39, 40).
The HLS mechanism functioning as a substitution of the CLS proves to be successful in
eliminating the disturbance caused on a winter day (Figures 41, 42). The overshedding of
the HLS mechanism compared to the CLS is owned up to the fact that the household load
in Germany is categorized in six categories. The categories are grouped together at each
stage in order to amount to at least 10% of the total German load and they cannot be
further split, since the decentralized HLS mechanism is preset.
55
8/12/2019 Control Strategies for Under-Frequency Load Shedding
59/71
I. Stefanidou & M. Zerva 5. Reference Cases Results
0 5 10 15 20 25 30 35 4049
49.5
50
50.5
51
51.5
Time [sec]
Frequency
[Hz
]
2008, 4.16% from DG
2010 BEE e.V., 5.52% from DG2020 BEE e.V., 13.12% from DG
2010 Leits., 5.16% from DG
2020 Leits., 9.97% from DG
No DG installations considered
Figure 36: Case 3 Dynamic response including DG.
0 5 10 15 20 25 30 35 4049
49.5
50
50.5
51
51.5
Time [sec]
Frequency
[Hz
]
CLS with DG considered
10% HLS participation
30% HLS participation
50% HLS participation
70% HLS participation
100% HLS participation
Figure 37: Case 3 Dynamic response with different household participation.
56
8/12/2019 Control Strategies for Under-Frequency Load Shedding
60/71
I. Stefanidou & M. Zerva 5. Reference Cases Results
0 10 20 30 4049
49.5
50
50.5
51
51.5
Time [sec]
Frequency
[H
z]
Without HLS
0 10 20 30 4049
49.5
50
50.5
51
51.5
10% Participation of Households
Time [sec]
Frequency
[H
z]
0 10 20 30 4030
20
10
0
10
20
Time [sec]
Pow
er
[GW]
0 10 20 30 40
30
20
10
0
10
20
Time [sec]
Pow
er
[GW]
dP
CLS
HLS
dP
CLS
HLS
Figure 38: Case 3 Dynamic response without the HLS mechanism and with the partici
pation of 10% of the German households.
0 10 20 30 4049.2
49.4
49.6
49.8
50
Time [sec]
Frequency
[Hz]
30% Participation of Households
0 10 20 30 4049.5
49.6
49.7
49.8
49.9
5050% Participation of Households
Time [sec]
Frequency
[Hz]
0 10 20 30 4015
10
5
0
5
10
Time [sec]
Power
[GW
]
0 10 20 30 40
15
10
5
0
5
10
Time [sec]
Power
[GW
]
dPCLSHLS dPCLSHLS
Figure 39: Case 3 Dynamic response with 30% and 50% of the German households
participating in the HLS scheme.
57
8/12/2019 Control Strategies for Under-Frequency Load Shedding
61/71
I. Stefanidou & M. Zerva 5. Reference Cases Results
0 10 20 30 4049.6
49.7
49.8
49.9
50
Time [sec]
Frequency
[Hz]
70% Participation of Households
0 10 20 30 4049.7
49.8
49.9
50
50.1
100% Participation of Households
Time [sec]
Frequency
[H
z]
0 10 20 30 4015
10
5
0
5
10
Time [sec]
Pow
er
[GW]
0 10 20 30 40
20
10
0
10
20
Time [sec]
Pow
er
[GW]
dPCLSHLS
dPCLSHLS
Figure 40: Case 3 Dynamic response with 70% and 100% of the German households
participating in the HLS scheme.
0 5 10 15 20 25 30 35 4049
49.5
50
50.5
51
51.5
52
Time [sec]
Frequency
[Hz
]
CLS without considering DGCLS considering DGHLS
Figure 41: Case 3 Dynamic response with the HLS scheme substituting the CLS mecha
nism for Germany.
58
8/12/2019 Control Strategies for Under-Frequency Load Shedding
62/71
I. Stefanidou & M. Zerva 5. Reference Cases Results
0 5 10 15 20 25 30 35 4049
49.5
50
50.5
51
51.5
52
Time [sec]
Frequency
[H
z]
0 5 10 15 20 25 30 35 4020
10
0
10
20
30
Time [sec]
Power
[GW]
HLS
dP
Figure 42: Case 3 Dynamic response with the HLS scheme substituting the CLS mecha
nism for Germany.
59
8/12/2019 Control Strategies for Under-Frequency Load Shedding
63/71
I. Stefanidou & M. Zerva 5. Reference Cases Results
5.2.4 Case 4 Winter scenario, 3 a.m.
The input data to the frequency response model in the fourth case, representing the winter
scenario at 3 a.m. are shown in the following Table 10.
Generation 153942 MW
Load 160818 MW
Net import 321 MW
Power deficit 7197 MW
Sheddable load per household 189.31 W
DG installed capacity 2008 7905.70 MWDG 2010 BEE e.V. 9765.41 MW
DG 2020 BEE e.V. 18779 MW
DG 2010 Leitszenario 2008 9180.44 MW
DG 2020 Leitszenario 2008 17104.44 MW
Table 10: Case 4 Power data.
The frequency drop is eliminated at 49 Hz, i.e. the first underfrequency load shedding
stage is triggered. The power deficit of 7.2 GW is fully compensated, without, however,
achieving to avoid load overshedding (Figure 43).
The triggering of the CLS is completely avoided with the participation of 30% of the Ger
man households (Figures 44, 45, 46). With a participation of at least the 70% of the German
households in the HLS mechanism, the system frequency is stabilized only by disconnecting
the first HLS category, with the lowest comfort loss to the consumers (Figure 47).
On a winter day, during night, the substitutional function of the HLS mechanism proves to
be successful in stabilizing the system (Figures 48, 49, in spite the fact that the sheddable
household load is limited including mainly the first category with the appliances with
high inertia. Thus, the household load mechanism proves to be compliant with the UCTE
guidelines and sufficient for covering the first shedding stage at all times.
60
8/12/2019 Control Strategies for Under-Frequency Load Shedding
64/71
I. Stefanidou & M. Zerva 5. Reference Cases Results
0 5 10 15 20 25 30 35 4049
49.5
50
50.5
51
51.5
Time [sec]
Frequency
[Hz
]
2008, 5.14% from DG
2010 BEE e.V, 6.34% from DG2020 BEE e.V, 12.2% from DG
2010 Leits., 5.96% from DG
2020 Leits., 11.11% from DG
No DG installations considered
Figure 43: Case 4 Dynamic response including DG.
0 5 10 15 20 25 30 35 4049
49.5
50
50.5
51
51.5
Time [sec]
Frequency
[Hz
]
CLS with DG considered
10% HLS participation
30% HLS participation
50% HLS participation
70% HLS participation
100% HLS participation
Figure 44: Case 4 Dynamic response with different household participation.
61
8/12/2019 Control Strategies for Under-Frequency Load Shedding
65/71
I. Stefanidou & M. Zerva 5. Reference Cases Results
0 10 20 30 4049
49.5
50
50.5
51
51.5
Time [sec]
Frequency
[Hz]
Without HLS
0 10 20 30 4049
49.5
50
50.5
51
51.5
10% Participation of Households
Time [sec]
Frequency
[Hz]
0 10 20 30 4020
10
0
10
20
Time [sec]
Pow
er
[GW]
0 10 20 30 40
10
0
10
20
10
20
10
Time [sec]
Pow
er
[GW]
dPCLSHLS
dPCLSHLS
Figure 45: Case 4 Dynamic response without the HLS mechanism and with the partici
pation of 10% of the German households.
0 10 20 30 4049.2
49.4
49.6
49.8
50
Time [sec]
Frequency
[Hz]
30% Participation of Households
0 10 20 30 4049.5
49.6
49.7
49.8
49.9
5050% Participation of Households
Time [sec]
Frequency
[Hz]
0 10 20 30 4010
0
10
20
Time [sec]
Power
[GW
]
0 10 20 30 4010
0