Control Strategies for Under-Frequency Load Shedding

Embed Size (px)

Citation preview

  • 8/12/2019 Control Strategies for Under-Frequency Load Shedding

    1/71

    eehpower systemslaboratory

    Ifigeneia Stefanidou Maria Zerva

    Control Strategies for Underfrequency LoadShedding

    Interaction of Distributed Generation with Load Shedding

    Decentralized UnderFrequency Load Shedding of HouseholdLoads

    Semester Thesis

    PSL0904

    EEH Power Systems Laboratory

    Swiss Federal Institute of Technology (ETH) Zurich

    Expert: Prof. Dr. Goran Andersson

    Supervisor: Dipl.Ing. Stephan Koch

    Zurich, September 3, 2009

  • 8/12/2019 Control Strategies for Under-Frequency Load Shedding

    2/71

  • 8/12/2019 Control Strategies for Under-Frequency Load Shedding

    3/71

    Statement regarding plagiarism when submitting written work at ETH Zurich

    By signing this statement, I affirm that I have read the information notice on plagiarism,independently produced this paper, and adhered to the general practice of sourcecitation in this subject-area.

    Information notice on plagiarism:http://www.ethz.ch/students/semester/plagiarism_s_en.pdf

    _______________________ ___________________________________

    place and date signature

    4/4

    http://www.ethz.ch/students/semester/plagiarism_s_en.pdfhttp://www.ethz.ch/students/semester/plagiarism_s_en.pdf
  • 8/12/2019 Control Strategies for Under-Frequency Load Shedding

    4/71

  • 8/12/2019 Control Strategies for Under-Frequency Load Shedding

    5/71

    Abstract

    The current approach of the Union for the Coordination of Transmission of Electricity for

    counteracting large frequency deviations due to lack of generation is the UnderFrequency

    Load Shedding scheme. The UnderFrequency Load Shedding scheme is the interruption of

    the power supply to a predefined percentage of customers when certain frequency deviations

    occur in the system. The drawback of the UnderFrequency Load Shedding scheme is that

    loss of load in entire areas occurs, since entire feeders are disconnected from the grid,

    and the interaction of the increasing Distributed Generation present in the system is not

    considered. The scope of the present study is to evaluate the impact of the Distributed

    Generation on the stable and secure electricity transmission systems operation and assess

    the performance of the proposed UnderFrequency Household Load Shedding scheme. The

    UnderFrequency Household Load Shedding scheme provides a flexible and decentralized

    way of mitigation.

  • 8/12/2019 Control Strategies for Under-Frequency Load Shedding

    6/71

    I. Stefanidou & M. Zerva 0. CONTENTS

    Contents

    1 Introduction 9

    2 UCTE Conventional Load Shedding 11

    2.1 Reference Power System . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

    2.2 Stabilization of the System Frequency . . . . . . . . . . . . . . . . . . . . . 12

    2.3 System Modeling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

    2.3.1 Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

    2.3.2 Dynamics of generators . . . . . . . . . . . . . . . . . . . . . . . . . 14

    2.3.3 Frequency Dependency of Loads . . . . . . . . . . . . . . . . . . . . 15

    2.3.4 Primary Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

    2.3.5 Load Shedding Mechanism . . . . . . . . . . . . . . . . . . . . . . . 17

    2.3.6 Frequency Response Model . . . . . . . . . . . . . . . . . . . . . . . 18

    3 Interaction of Distributed Generation with Load Shedding 20

    3.1 Distributed Generation in Germany . . . . . . . . . . . . . . . . . . . . . . 20

    3.2 Penetration Scenarios . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22

    3.3 Distributed Generation Power Output . . . . . . . . . . . . . . . . . . . . 23

    3.4 Frequency Response Model . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

    4 Household Load Shedding 27

    4.1 Household load profile during the day . . . . . . . . . . . . . . . . . . . . . 27

    4.2 The potential of UnderFrequency Household Load Shedding . . . . . . . . 30

    4.3 UnderFrequency Household Load Shedding as a complement to Conven

    tional Load Shedding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35

    3

  • 8/12/2019 Control Strategies for Under-Frequency Load Shedding

    7/71

    4.3.1 Frequency response model . . . . . . . . . . . . . . . . . . . . . . . 35

    4.4 UnderFrequency Household Load Shedding for substitution of ConventionalLoad Shedding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38

    4.4.1 Frequency Response Model . . . . . . . . . . . . . . . . . . . . . . . 38

    5 Reference Cases Results 41

    5.1 Reference Cases . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42

    5.1.1 Summer scenario . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42

    5.1.2 Winter scenario . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43

    5.2 Simulation Results . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44

    5.2.1 Case 1 Summer scenario, 11 a.m. . . . . . . . . . . . . . . . . . . 44

    5.2.2 Case 2 Summer scenario, 3 a.m. . . . . . . . . . . . . . . . . . . . 50

    5.2.3 Case 3 Winter scenario, 11 a.m. . . . . . . . . . . . . . . . . . . . 55

    5.2.4 Case 4 Winter scenario, 3 a.m. . . . . . . . . . . . . . . . . . . . . 60

    6 Conclusions 65

    References 67

  • 8/12/2019 Control Strategies for Under-Frequency Load Shedding

    8/71

    I. Stefanidou & M. Zerva 0. LIST OF FIGURES

    List of Figures

    1 Interconnected UCTE Power System [1]. . . . . . . . . . . . . . . . . . . . 11

    2 Total system inertia of the interconnected system. . . . . . . . . . . . . . . 15

    3 Frequency Dependency of Loads. . . . . . . . . . . . . . . . . . . . . . . . 16

    4 Primary Control. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

    5 Load Shedding. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

    6 Frequency Response Model. . . . . . . . . . . . . . . . . . . . . . . . . . . 19

    7 Load density (left) and DG share (right) of each State. . . . . . . . . . . . 22

    8 Wind (left) [13] and Solar (right) potential of Germany [14]. . . . . . . . . 25

    9 The power system frequency response model, considering the DG loss. . . . 26

    10 Share of consumption of the household appliances [5]. . . . . . . . . . . . . 28

    11 Power consumption of each household appliance group over the day. . . . . 29

    12 Sheddable household load in Germany. . . . . . . . . . . . . . . . . . . . . 33

    13 HLS scheme. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35

    14 Frequency response model including the HLS mechanism. . . . . . . . . . . 36

    15 HLS mechanism. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37

    16 Set of flip flops. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37

    17 Frequency response model including the substitutional HLS mechanism. . . 39

    18 Substitutional HLS mechanism. . . . . . . . . . . . . . . . . . . . . . . . . 40

    19 Physical and planned flows within the UCTE [6]. . . . . . . . . . . . . . . 41

    20 Summer scenario. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43

    21 Winter scenario. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44

    22 Case 1 Dynamic response including DG. . . . . . . . . . . . . . . . . . . 46

    5

  • 8/12/2019 Control Strategies for Under-Frequency Load Shedding

    9/71

    I. Stefanidou & M. Zerva 0. LIST OF FIGURES

    23 Case 1 Dynamic response with different household participations. . . . . 46

    24 Case 1 Dynamic response without the HLS mechanism and with the participation of 10% of the German households. . . . . . . . . . . . . . . . . . 47

    25 Case 1 Dynamic response with 30% and 50% of the German households

    participating in the HLS scheme. . . . . . . . . . . . . . . . . . . . . . . . 47

    26 Case 1 Dynamic response with 70% and 100% of the German households

    participating in the HLS scheme. . . . . . . . . . . . . . . . . . . . . . . . 48

    27 Case 1 Dynamic response with HLS scheme substituting the CLS mecha

    nism for Germany. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48

    28 Case 1 Dynamic response with HLS scheme substituting the CLS mecha

    nism for Germany. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49

    29 Case 2 Dynamic response including DG. . . . . . . . . . . . . . . . . . . 51

    30 Case 2 Dynamic response with different household participation. . . . . . 51

    31 Case 2 Dynamic response without the HLS mechanism and with the par

    ticipation of 10% of the German households. . . . . . . . . . . . . . . . . . 52

    32 Case 2 Dynamic response with 30% and 50% of the German households

    participating in the HLS scheme. . . . . . . . . . . . . . . . . . . . . . . . 52

    33 Case 2 Dynamic response with 70% and 100% of the German households

    participating in the HLS scheme. . . . . . . . . . . . . . . . . . . . . . . . 53

    34 Case 2 Dynamic response with the HLS scheme substituting the CLS

    mechanism for Germany. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53

    35 Case 2 Dynamic response with the HLS scheme substituting the CLS

    mechanism for Germany. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54

    36 Case 3 Dynamic response including DG. . . . . . . . . . . . . . . . . . . 56

    37 Case 3 Dynamic response with different household participation. . . . . . 56

    38 Case 3 Dynamic response without the HLS mechanism and with the par

    ticipation of 10% of the German households. . . . . . . . . . . . . . . . . . 57

    6

  • 8/12/2019 Control Strategies for Under-Frequency Load Shedding

    10/71

    39 Case 3 Dynamic response with 30% and 50% of the German households

    participating in the HLS scheme. . . . . . . . . . . . . . . . . . . . . . . . 57

    40 Case 3 Dynamic response with 70% and 100% of the German households

    participating in the HLS scheme. . . . . . . . . . . . . . . . . . . . . . . . 58

    41 Case 3 Dynamic response with the HLS scheme substituting the CLS

    mechanism for Germany. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58

    42 Case 3 Dynamic response with the HLS scheme substituting the CLS

    mechanism for Germany. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59

    43 Case 4 Dynamic response including DG. . . . . . . . . . . . . . . . . . . 61

    44 Case 4 Dynamic response with different household participation. . . . . . 61

    45 Case 4 Dynamic response without the HLS mechanism and with the par

    ticipation of 10% of the German households. . . . . . . . . . . . . . . . . . 62

    46 Case 4 Dynamic response with 30% and 50% of the German households

    participating in the HLS scheme. . . . . . . . . . . . . . . . . . . . . . . . 62

    47 Case 4 Dynamic response with 70% and 100% of the German householdsparticipating in the HLS scheme. . . . . . . . . . . . . . . . . . . . . . . . 63

    48 Case 4 Dynamic response with the HLS scheme substituting the CLS

    mechanism for Germany. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63

    49 Case 4 Dynamic response with the HLS scheme substituting the CLS

    mechanism for Germany. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64

  • 8/12/2019 Control Strategies for Under-Frequency Load Shedding

    11/71

    List of Tables

    1 Load Shedding stages according to the UCTE Handbook [2]. . . . . . . . . 13

    2 Type of Loads. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

    3 DG installed capacity and penetration scenarios for 2010 and 2020. . . . . 23

    4 Power Output. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

    5 Comfort loss of each appliance category. . . . . . . . . . . . . . . . . . . . 31

    6 Sheddable load per German household. . . . . . . . . . . . . . . . . . . . . 34

    7 Case 1 Power data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45

    8 Case 2 Power data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50

    9 Case 3 Power data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55

    10 Case 4 Power data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60

  • 8/12/2019 Control Strategies for Under-Frequency Load Shedding

    12/71

    I. Stefanidou & M. Zerva 1. Introduction

    1 Introduction

    Power systems provide a vital infrastructure for the functioning of todays societies which

    have become increasingly dependent on reliable and secure supply of electricity. Their

    operation and structure have significantly evolved over the years incorporating market

    mechanisms in the initially monopolistic trade of electricity.

    The deregulation of the electricity markets has created challenges concerning the operation

    of the systems, while the goal is still to maintain the reliability and the security of supply.

    The decoupling of the electricity generation, transmission, distribution and retail and theinvolvement of more participants has led to a more complex environment, both economical

    and technological. The interconnection links between different countries do no more serve

    emergency but regular trading purposes, resulting in the increasing probability of the

    overloading of the tielines. A possible disturbance now affects the whole interconnected

    system and can be spread over long distances within seconds and, if not eliminated, it may

    result in a complete system collapse.

    The liberalization of electricity markets provides free market access to many various par

    ticipants, while the trend of the last decades towards reducing greenhouse gas emissionsleads to the development of mainly small scaled, 2free sources for energy production,

    which are strongly supported by legislation. Consequently, the integration of distributed

    sources into the networks leads to the modification of the structure of the electric power

    systems and the initial unidirectional power flows. Therefore, as a side effect of the develop

    ment of Distributed Generation units, the traditional protection and control mechanisms

    of the power systems, which do not consider the Distributed Generation (DG), turn to be

    insufficient or inappropriate.

    The security and the quality of supply are the primary goal of the electric power systems,

    considering the strong impacts that a disturbance may have on the society and the fact

    that electricity as a product cannot be stored on a large scale. However, the security of

    power systems is jeopardized by the previously mentioned changes of their operation and

    structure. The impact of the Distributed Generation penetration can be assessed by quan

    tifying the Distributed Generation and modelling its interaction with the power system.

    Future scenarios for increasing the Distributed Generation imply the need for a further

    modification of the control methods used under normal or emergency conditions.

    9

  • 8/12/2019 Control Strategies for Under-Frequency Load Shedding

    13/71

    I. Stefanidou & M. Zerva 1. Introduction

    The proposed method is the UnderFrequency Household Load Shedding (UFHLS) which

    includes the frequency dependent, automatic disconnection of nonvital individual house

    hold loads. The UFHLS can be implemented either together with the present control mech

    anisms in order to act complementary or for a complete substitution of the existing control

    schemes. In each case, the proposed scheme is decentralized in order for the system to

    be robust to imminent disturbances, while the shedding of household loads is realized

    stepbystep, according to predefined frequency thresholds. Individual household loads are

    disconnected with priority to the uncritical ones that are less vital for the consumers, so

    as for the interruption of supply to be least observed by the consumers.

    The implementation of the UFHLS scheme should ensure the robustness of the power

    systems. Therefore, an automatic mechanism is needed in order for the suitable load re

    ductions to be realized in every disturbance case, considering the capacity of the system

    and the comfort loss for the consumers at any time.

    Germany, being among the leaders in technological innovation and a major UCTE member

    country, provides a good paradigm for the assessment of the performance of the proposed

    HLS mechanism and the interaction of DG in the context of UCTE. For these reasons,

    data for the German households and DG are used for the derivation of reference scenarios

    appropriate for the simulation of the UCTE power system frequency response in case of acontingency.

    10

  • 8/12/2019 Control Strategies for Under-Frequency Load Shedding

    14/71

    I. Stefanidou & M. Zerva 2. UCTE Conventional Load Shedding

    2 UCTE Conventional Load

    Shedding

    2.1 Reference Power System

    The Union for the Coordination of Transmission of Electricity (UCTE) is an association

    of the Transmission System Operators (TSOs) of 24 European countries (Figure 1). The

    interconnected system handled by the UCTE comprises of 220000 Km of transmission

    lines and a total installed capacity of 640 GW.

    Figure 1: Interconnected UCTE Power System [1].

    The interconnected power systems of the membercountries of the UCTE operate syn

    chronously at the nominal frequency of 50 Hz. The UCTE interconnected system was

    initially introduced for the cooperation of the TSOs in emergency cases. Over the past

    few years the electricity market across Europe has been redesigned and the trade of elec

    tricity among European countries has been developed. The use of the interconnections

    between countries has shifted from emergency to trade purposes, resulting in the opera

    tion of the interconnection links to their limits and, thus, compromising the stability and

    the security of the UCTE power system. Therefore, the coordinated actions of the UCTE

    membercountries are necessary in order to ensure the secure and reliable operation of the

    11

  • 8/12/2019 Control Strategies for Under-Frequency Load Shedding

    15/71

    I. Stefanidou & M. Zerva 2. UCTE Conventional Load Shedding

    system.

    The UCTE issues the UCTE Operation Handbook which is a set of technical and operational principles and rules ensuring the reliable performance of the interconnected high

    voltage grids of the continental Europe. All UCTE members are bound to comply with

    the UCTE and collectively contribute to the stabilization of the system in any emergency

    case.

    2.2 Stabilization of the System Frequency

    Emergency situations within the UCTE power system are mainly indicated by the devia

    tions of the system frequency. Since the frequency is approximately equal in all participat

    ing countries, the automatic response of the primary controllers in each membercountry

    is triggered in order to stabilize the frequency. The secondary control acts then in order to

    bring the system frequency back to its nominal value 1. In response to a quasisteadystate 2

    frequency deviation of 200 mHz or more [2], the primary control reserves in each UCTE

    membercountry are deactivated or activated, in order to restore the power balance of the

    system. The primary controllers should be able to stabilize the system in case of a failureup to 3000 MW of the generating capacity in normal operation [2]. The contribution of

    each membercountry to the primary reserves is proportional to the ratio of the electricity

    produced over the total electricity production across the UCTE. In case that the extent of

    the disturbance is higher than the capability of the primary controllers, additional measures

    are required, such as the frequency sensitive triggering of load shedding.

    The Load Shedding is triggered when the frequency drops to a predefined level, in order to

    protect the power generating systems and avoid a major power system breakdown. During

    a major disturbance, i.e. a loss of generation, and under emergency conditions when there isinsufficient generation capability for the current demand, the electrical supply is interrupted

    to a certain number of consumers in each membercountry of the UCTE according to the

    implemented Load Shedding scheme in order to prevent a total collapse of the UCTE

    system.

    1The secondary control is not regarded, since its dynamics are much slower and out of the scope of the

    present study.2The quasisteadystate refers to a stable system frequency but not at the nominal value.

    12

  • 8/12/2019 Control Strategies for Under-Frequency Load Shedding

    16/71

    I. Stefanidou & M. Zerva 2. UCTE Conventional Load Shedding

    Each TSO determines its shedding plan according to the rules of the UCTE. The TSOs of

    the UCTE participate in the Load Shedding scheme irrespectively of the location of the

    failure. The UCTE recommends that the Load Shedding is implemented in three steps and

    involves the disconnection of feeders amounting to a predefined share of the load. The first

    step of the Load Shedding is initiated at the frequency threshold of 49 Hz by disconnecting

    the 1020% of the total load. The second and the third step are triggered at 48.7 Hz and

    48.4 Hz, respectively, by disconnecting an additional 1015% of the initial load at each

    step (see Table 1).

    Frequency Thresholds Load Shedding

    49.0 Hz 1020%

    48.7 Hz 1015%

    48.4 Hz 1015%

    Table 1: Load Shedding stages according to the UCTE Handbook [2].

    2.3 System Modeling

    The interconnecting links among the membercountries of UCTE were traditionally used

    under emergency conditions, while, nowadays, they also serve trading purposes and are

    known as tielines. Besides the benefits of the interconnection of the power systems, the

    regular trading of electricity results in a high possibility of the overloading of the tielines.

    A disturbance within the UCTE can be spread over large distances and, in the worst case,

    cause a total collapse of the interconnected system.

    The power system frequency response model of the UCTE, including the Load Shedding

    mechanism recommended by the UCTE, simulates the frequency deviations during normal

    and emergency conditions. In order to study the power system of Germany, it is necessary to

    also consider the behavior of the whole interconnected system, since the system frequency

    is determined by the balance between the total generation and demand. Furthermore, the

    power exchanges of the UCTE with other interconnected systems via DC or AC links

    influence the frequency response in each membercountry, since a local disturbance can

    cause a cascading series of outages within the interconnected system.

    13

  • 8/12/2019 Control Strategies for Under-Frequency Load Shedding

    17/71

  • 8/12/2019 Control Strategies for Under-Frequency Load Shedding

    18/71

    I. Stefanidou & M. Zerva 2. UCTE Conventional Load Shedding

    =

    0

    2 (

    ) (2)

    The respective block in the frequency response model describes the total system inertia

    and the reflection of the power imbalances on the frequency deviations of the system

    (Figure 2). The total system inertia constant is assumed to be equal to 5 seconds, while

    the represents the cumulated power rating of the rotating synchronous machines in the

    interconnected system under study.

    dP

    Subtract

    Net Import

    Load

    Integrator

    1

    s

    Generation

    Gain

    f0/(2*H*S) df

    Figure 2: Total system inertia of the interconnected system.

    2.3.3 Frequency Dependency of Loads

    The frequency dependency of the active power of the loads is taken into account, since the

    frequency deviation within a system influences the behavior of the loads. The industrialloads are mainly motors which can store the kinetic energy of their rotating masses. There

    fore, a possible frequency drop during a disturbance can be partly stabilized by the stored

    kinetic energy of the motors. The commercial and residential loads can also be frequency

    dependent, depending on their structure.

    Typical values describing the frequency dependency of the loads are expressed in per cent

    of the load variation from the total load for one per cent of frequency deviation from the

    nominal value (Table 2).

    15

  • 8/12/2019 Control Strategies for Under-Frequency Load Shedding

    19/71

    I. Stefanidou & M. Zerva 2. UCTE Conventional Load Shedding

    Load Type dP/df (%/%) Representative Type Share

    Residential 0.9 40%

    Commercial 1.4 20%

    Industrial 2.6 40%

    Table 2: Type of Loads.

    According to the proposed values for the load models, the frequency dependency of the

    active power consumed by the loads can be described by the factor which equals to 1.6

    ( = 16). The respective block in the frequency response model describes the normalized

    active power deviation of the loads resulting from a system frequency deviation (Figure 3).

    Frequency deviation

    df

    Frequency dependent active power

    dP1.66*S/f0

    Figure 3: Frequency Dependency of Loads.

    2.3.4 Primary Control

    The primary controllers of the entire UCTE system can eliminate a disturbance caused by

    a power deficit not higher than 3000 MW under normal conditions. The primary reserves

    in each membercountry of the UCTE are proportional to its generation capacity [2]. In

    case of a disturbance, the primary controllers of every country of the interconnected systemcontribute to its elimination. The speed droop characteristic of the interconnected system

    under study represents the different operating points of the system. The speed droop of

    the system is considered to be approximately equal to the total generated power at each

    time instant.

    The linearized dynamic modelling of the turbines of the primary reserves is essential, despite

    the fact that the turbine controllers time constant is much smaller than the time constant of

    the frequency dynamics of the system. The UCTE system is modeled as an onearea system,

    16

  • 8/12/2019 Control Strategies for Under-Frequency Load Shedding

    20/71

  • 8/12/2019 Control Strategies for Under-Frequency Load Shedding

    21/71

    I. Stefanidou & M. Zerva 2. UCTE Conventional Load Shedding

    Load shed

    LS

    Load Shedding

    df Share of load

    load

    Frequency

    deviation

    df

    Figure 5: Load Shedding.

    2.3.6 Frequency Response Model

    The frequency response model is constructed by combining the previously analyzed mech

    anisms (Figure 6). The inputs to the modeled power system of the interconnected areas arethe total generated power, the total consumed power and the net imports from neighboring

    power systems at each time instant. In case of a disturbance, i.e. loss of generation or un

    expected increase of the load, the power deficit is reflected on a system frequency deviation

    by means of the generators dynamics and the system inertia constant. Subsequently, the

    frequency deviation influences the active power consumption of the frequency dependent

    loads and triggers the primary controllers and the load shedding mechanism, according to

    the magnitude of the disturbance.

    18

  • 8/12/2019 Control Strategies for Under-Frequency Load Shedding

    22/71

    I. Stefanidou & M. Zerva 2. UCTE Conventional Load Shedding

    f0

    Turbine dynamics

    1

    7s+1

    System

    frequency

    freq

    Sum of f0+df

    Sum of

    loads of 24 UCTE countries

    SaturationPrimary control

    -1/(Spr*f0/S)

    Net Import

    loadLoad

    1

    s

    Generationf0/(2*H*S)

    Frequency dependency of Loads

    1.66*S/f0

    Conventional

    Load Shedding

    dfLoad Shed

    Figure 6: Frequency Response Model.

    19

  • 8/12/2019 Control Strategies for Under-Frequency Load Shedding

    23/71

    I. Stefanidou & M. Zerva 3. Interaction of Distributed Generation with Load Shedding

    3 Interaction of Distributed

    Generation with Load Shedding

    The term Distributed Generation (DG) is used to characterize electric power sources with

    small rating as compared to conventional power plants, which are connected to the dis

    tribution grid, i.e. Medium and Low Voltage Level. Distributed Generation has faced a

    significant growth, mainly due to the liberalization of the electricity market and the trend

    for shifting the electricity production towards 2neutral energy sources for reducing

    greenhouse gas emissions and mitigating climate change.

    The DG, being mostly renewable energy sources, creates a number of uncertainties in the

    power system, in terms of inability to precisely schedule the power injected into the grid.

    Additionally, the renewable energy sources that are connected to the distribution grid can

    not be directly controlled by the transmission system operators. In case of necessity for

    activation of the Load Shedding mechanism due to an imminent disturbance, there is high

    probability that additional loss of generation will occur. Feeders that are disconnected in

    emergency cases may have Distributed Generation units connected to them, which causes

    to the disconnection of the dispersed generation. Thus, the extent of the Distributed Generation loss in such cases should be quantified in order for the interaction to be evaluated.

    3.1 Distributed Generation in Germany

    The European Union has adopted certain measures for promoting renewable energy sources,

    in view of the commitments of the Kyoto Protocol. Germany, as a Member State of the

    EU has set specific targets for renewable energy penetration and has achieved to becomethe leader on the grounds of both installations and technical knowhow. In the case of

    Germany, most common energy carriers for DG are wind, solar, biomass and to a limited

    extent geothermal, hydro and gas power plants.

    Four TSOs operate within Germany, i.e. Transpower Stromubertragungs GmbH (company

    affiliated with E.ON) [4], Vattenfall Europe Transmission GmbH [5], RWE Transportnetz

    Strom GmbH [6] and EnBW Transportnetze AG [7]. According to data published by the

    TSOs, Germany has a total installed capacity of 137.5 GW. The renewable energy sources

    20

  • 8/12/2019 Control Strategies for Under-Frequency Load Shedding

    24/71

    I. Stefanidou & M. Zerva 3. Interaction of Distributed Generation with Load Shedding

    installations amount to 38029 MW, out of which 12245 MW are installations with a rating

    smaller than 10 MW, connected to the low and medium voltage level.

    The regionally different renewable energy potential leads to regional differences in the DG

    installed capacity of the different energy carriers [8]. In the present study, the power plants

    who receive the feedin tariff are divided according to the state of Germany to which they

    belong to in order to correspond to the regional potential. Thus, in Northern Germany the

    dominant energy carrier is wind, whereas in the Southern Germany DG is mostly solar

    installations. Southern Germany has lower shares of DG due to the fact that solar instal

    lations have significantly smaller rating and are not yet as developed as wind power units.

    For biomass, gas and geothermal installations there is no clear geographical distinction.

    Apart from the renewable energy source DG, nonrenewable smallscale Combined Heat

    and Power (CHP) plants are also connected to the distribution levels and are disconnected

    in the case of load shedding. However, the penetration levels are quite low and there is no

    exact data available.

    The raw data published by the TSOs concerning the power plants which receive a feedin

    tariff have been sorted according to energy carrier, nominal installed capacity and postal

    code. The installations data need to be further sorted per State in order for the relation

    between the load density3

    and the potential of each region to be also considered (Figure 7).The DG shares over the total DG capacity are higher in the Northern States of Germany due

    to the high penetration of wind power plants. In States with high DG shares and relatively

    low load density the risk of deteriorating the situation, by disconnecting significant amounts

    of DG units together with a small portion of load, is higher.

    3The load share is assumed to be equal to the population share of each State of Germany.

    21

  • 8/12/2019 Control Strategies for Under-Frequency Load Shedding

    25/71

    I. Stefanidou & M. Zerva 3. Interaction of Distributed Generation with Load Shedding

    Figure 7: Load density (left) and DG share (right) of each State.

    3.2 Penetration Scenarios

    Renewable energy source power plants are expected to further increase in the years to

    come. In 2002 Germany set a goal to cover the 14% [9] of the electricity consumption

    with renewable energy sources until 2008. The goal has been achieved (14.2%) [10] andhigher targets have been set. Increase of the DG is expected to substantially change the

    structure of the electricity transmission and distribution grid, posing great ambiguity to

    the effectiveness of the current control mechanisms; the load shedding mechanisms involves

    the disconnection of feeders in case of lack of generation irrespectively of the DG units that

    they may have connected to them.

    The future possible growth of the DG is necessary to be considered in order to quantify the

    future DG installations and assess the degree of interaction of the DG with the security

    22

  • 8/12/2019 Control Strategies for Under-Frequency Load Shedding

    26/71

  • 8/12/2019 Control Strategies for Under-Frequency Load Shedding

    27/71

    I. Stefanidou & M. Zerva 3. Interaction of Distributed Generation with Load Shedding

    the electricity consumption was 14.2%. The difference in the two percentages implies that

    the load factors of the renewable energy source power plants are substantially limited by

    weather conditions, regional potential and time of the day.

    The data published by the TSOs concern either the installed capacity or total energy

    production over a year. However, the effect of the DG in the system in emergency cases can

    only be assessed by considering the instantaneous injected power from the DG installations,

    rather than their installed capacity. The power output of each installation highly depends

    on the type of the energy carrier, the weather conditions, the time of the day and the

    potential of the region in which it is installed. Therefore, factors which reflect the potential

    of each region and the maximum power output for each energy carrier are necessary. The

    methodology followed in the present study in order for the factors to be derived is the

    normalization of representative parameter for each energy carrier.

    The parameter that limits the power output of wind power plants is mainly the wind speed.

    The wind power potential of each region of Germany is derived based on statistical data

    concerning the mean wind speed in each State for every month of the year. The mean

    wind speed of every State in each month is divided by the maximum mean wind speed in

    Germany over a year. The normalized wind speeds are considered as factors which scale

    the wind power output. A factor of 1 is attributed to the region with the highest potentialand for the month with the highest mean wind speed.

    As far as solar panels are concerned, the parameters taken into account are the mean

    irradiation in each region during the year and the mean duration of sunshine. Similar to

    wind power and based on statistical data, the factors for solar power correspond to the

    normalized irradiation in each State (Figure 8). For the solar panels optimal inclination is

    assumed, providing the opportunity to have the maximum possible power output.

    For geothermal, hydro, gas and biomass power plants it is assumed that the power output

    is independent of weather conditions, regional distribution and time of the day. Therefore,

    uniform factors are considered to limit the power output and approximate their contribu

    tion to the total Distributed Generation.

    The factors calculated for each energy carrier are multiplied with the installed capacity,

    and, therefore, the energy injected into the system is calculated for the time snapshots for

    which UCTE publishes load and power exchange data (Table 4).

    24

  • 8/12/2019 Control Strategies for Under-Frequency Load Shedding

    28/71

    I. Stefanidou & M. Zerva 3. Interaction of Distributed Generation with Load Shedding

    Figure 8: Wind (left) [13] and Solar (right) potential of Germany [14].

    Energy Carrier

    OUTPUT (MW)

    Winter Summer11 a.m 3 a.m 11 a.m 3 a.m

    Solar 853.05 0 2202.51 0

    Wind 5279.58 5279.58 3981.70 3981.70

    Biomass 1684.62 1684.62 1684.62 1684.62

    Geothermal 426.54 426.54 426.54 426.54

    Hydro 2.90 2.90 2.90 2.90

    Gas 512.06 512.06 512.06 512.06

    Table 4: Power Output.

    3.4 Frequency Response Model

    The Distributed Generation loss at each load shedding stage is assumed to be 10% of

    the total Distributed Generation output injected into the system at each time instant. In

    the power system frequency response model (Figure 9) the Distributed Generation taken

    25

  • 8/12/2019 Control Strategies for Under-Frequency Load Shedding

    29/71

  • 8/12/2019 Control Strategies for Under-Frequency Load Shedding

    30/71

    I. Stefanidou & M. Zerva 4. Household Load Shedding

    4 Household Load Shedding

    Underfrequency load shedding is traditionally triggered when the power system suffers

    from a lack of generation, i.e. sudden loss of generation or increase of load. In order to

    stabilize the frequency, entire feeders are disconnected from the grid, while unexpected

    additional loss of generation may occur due to disconnection of Distributed Generation

    connected to the distribution level. With increasing Distributed Generation the conven

    tional underfrequency load shedding scheme cannot guarantee the stabilization of the

    system, which could be avoided by the development of automated and locally controlled

    load shedding schemes.

    The UnderFrequency Household Load Shedding (HLS) is a decentralized scheme under

    which households participate with small scale appliances in the grid control schemes. In the

    case of an underfrequency disturbance, the appliance operation can be influenced by control

    commands sent through a communication interface by a decentralized control system,

    equipped with suitable control algorithms. Aiming to the minimum cost for the society

    and to the minimum comfort loss for the consumers, a fast and graceful load reduction can

    be achieved and a total system collapse can be prevented by shedding nonvital, individual

    household loads.

    The HLS scheme can act either as a complement to the Conventional Load Shedding (CLS)

    mechanism, and, thus, delay or even avoid its triggering, or for complete substitution of

    the CLS, depending on the implementation of the scheme. The potential of the HLS is

    studied, in compliance with the quantified Distributed Generation, for the household load

    of Germany.

    4.1 Household load profile during the day

    The household load in each time instant is highly dependent on the weather conditions,

    the time of the day and the lifestyle in the region under study. Germany has a total of

    39700000 households [15] which according to statistical data are responsible for approx

    imately 30% [5] of the total load of Germany in average. In 2008, the total electricity

    consumption in Germany was 557162 GWh [1]. Considering the percentage share of the

    household consumption over the total consumption of Germany, German households ap

    27

  • 8/12/2019 Control Strategies for Under-Frequency Load Shedding

    31/71

    I. Stefanidou & M. Zerva 4. Household Load Shedding

    proximately consumed in 2008 167149 GWh, which corresponds to an average household

    load of 19081 MW.

    For load shedding purposes the vital load of each household is not considered, whereas

    for the nonvital appliances their specific consumption has to be quantified. Due to their

    volatility, the devices within a household are grouped according to their similarities in their

    characteristics, i.e. usage, and classified considering the utilization and comfort loss over

    the day.

    The German household appliances are categorized according to their aggregate consump

    tion over a year (Figure 10). Based on statistical data [16] and considering the total house

    hold consumption over the year, the average consumption during the day of each appliancegroup can be computed. In order to quantify the potential of the HLS scheme, the specific

    utilization factors of each appliance group have to be defined. For this purpose, typical

    utilization patterns of each appliance group are considered. The specific utilization fac

    tors are, thus, derived from the normalization of the instantaneous consumption of each

    appliance group with its average consumption over the day.

    TV- HiFi

    Refrigerators-FreezersWashing

    7%

    22%12%

    arm-waterboilers

    14%Small electric

    devices23%

    ElectricHeating

    3%

    Lighting9%

    Cookingappliances

    10%

    Figure 10: Share of consumption of the household appliances [5].

    The specific consumption of each appliance group, which equals to the product of the

    normalized utilization and the average consumption, describes the household consumption

    28

  • 8/12/2019 Control Strategies for Under-Frequency Load Shedding

    32/71

    I. Stefanidou & M. Zerva 4. Household Load Shedding

    of each appliance group during the day, including both the vital and non vital loads

    (Figure 11).

    40

    50

    60

    70

    80

    Load[G

    W]

    Small devices

    TV-Hifi

    Cooking devices

    Lighting

    Washing and

    drying devicesElectric heating

    Warm-water boiler

    0

    10

    20

    30

    0:00

    0:45

    1:30

    2:15

    3:00

    3:45

    4:30

    5:15

    6:00

    6:45

    7:30

    8:15

    9:00

    9:45

    10:30

    11:15

    12:00

    12:45

    13:30

    14:15

    15:00

    15:45

    16:30

    17:15

    18:00

    18:45

    19:30

    20:15

    21:00

    21:45

    22:30

    23:15

    Time of the day

    Refrigerator-Freezer

    Total German loadprofile

    Figure 11: Power consumption of each household appliance group over the day.

    The groups that include thermal appliances are considered to be nonvital due to their

    high inertia which makes the interruption of their power supply hardly observed by the

    consumers. Such appliances are the refrigerators, the freezers, the warmwater boilers and

    the electric heating. It is assumed that this group of appliances offers control reserves

    during the day, constituting the base load 4. Therefore, refrigerators, freezers and boilers are

    assumed to have constant utilization during the day and, therefore, provide a constant base

    household load for the HLS scheme. However, the utilization of the rest of the appliance

    groups varies during the day, shaping the household load profile curve and significantly

    4Warmwater boilers power consumption is often shifted to the night due to special tariffs. However, in

    the present study, the are assumed to participate in a load control scheme and have constant consumption

    over the day.

    29

  • 8/12/2019 Control Strategies for Under-Frequency Load Shedding

    33/71

    I. Stefanidou & M. Zerva 4. Household Load Shedding

    differentiating the household load during the day. The base household load over the whole

    day is approximately 8.5 GW, while the household load peak can be found during the

    evening hours and is in the order of 30 GW.

    The potential of the HLS scheme is perceived as the total sheddable household load at

    each time instant, considering only the nonvital devices and their respective consumption.

    The nonvital devices, i.e. the sheddable devices, are prioritized using as a criterion their

    comfort loss. Comfort loss can be defined as an indicator for assessing the degree of the

    annoyance caused to the consumers by shedding a specific appliance group. Appliances are

    characterized by their comfort loss representing the extent to which their disconnection

    is observed by the consumers. The comfort loss is not considered to be uniform for each

    device over the day or over the year, but varies according to the utilization and necessity.

    4.2 The potential of UnderFrequency Household

    Load Shedding

    In the previous Section 4.1, the sheddable household load has been defined as the non

    vital devices within a household. Additionally, each device has been attributed with a

    factor indicating its individual comfort loss. Since the goal is to develop a simple, flexible

    and fast mechanism for the decentralized HLS scheme, the nonvital devices are further

    categorized. Each category is characterized by a single value of comfort loss (Table 5).

    However, each category does not have constant comfort loss over the day and over the

    year, since there are significant variations of the lifestyle and the weather conditions.

    The thermal appliances together with the battery chargers represent the category with

    the lowest comfort loss, and thus, the first appliance category to be shed. The washingappliances, including the washing machine, the dishwasher and the dryer, are also of

    constant and relatively low comfort loss during the day and during the year, representing

    the second category to be shed. Electric heating is not in operation during the summer,

    and therefore, its contribution to the available sheddable load is zero during the summer.

    However, during the winter the utilization of electric heating is assumed to be constant

    over the day.

    The comfort loss of the lights is higher during the night and during the winter than during

    30

  • 8/12/2019 Control Strategies for Under-Frequency Load Shedding

    34/71

    I. Stefanidou & M. Zerva 4. Household Load Shedding

    Appliances Categories Comfort Loss

    0:00 5.30 5.30 15:00 14:30 20:00 20:00 24:00

    Refrigerator Freezer

    1 1 1 1Warm water boilerElectrical heating

    Battery charger

    Lights 6 3 3 4

    Microwave Oven

    4 5 4 3Oven

    Coffee Machine

    Iron

    1 4 5 5Vacuum MachineHair Dryer

    Washing Machine

    2 2 2 2Dryer

    Dishwasher

    TV

    5 6 6 6DVD

    HiFi

    Table 5: Comfort loss of each appliance category.

    31

  • 8/12/2019 Control Strategies for Under-Frequency Load Shedding

    35/71

    I. Stefanidou & M. Zerva 4. Household Load Shedding

    the day and summer, respectively. The cooking appliances, including the microwave oven,

    the electric oven and the coffeemachine, are mainly switched on during the morning and

    early evening hours. Therefore, their utilization as well as their comfort loss is increased

    during these hours. The small electric devices represent the nonvital load, such as the iron,

    the vacuum cleaner and the hairdryer. Their comfort loss is highly dependent on their

    utilization which is assumed to be higher during the evening. The most critical appliance

    category includes the devices whose shedding is immediately realized by the consumers,

    such as TV, DVD and HiFi, and may cause annoyance to the users. Their utilization and,

    consequently, their comfort loss is high during the evening and before midnight, making

    them the last load to be shed during the day, whereas their utilization is high during the

    evening and before midnight.

    The comfort loss indicators of most of the appliance categories vary during the day, since

    their utilization and necessity also vary. Therefore, the shedding order of these appliance

    categories should change according to their comfort loss. The comfort loss indicators de

    termine the shedding order of the appliances categories at each time instant. Since the

    main target of the HLS is the stabilization of the system in case of a disturbance with the

    minimum comfort loss to the consumers and HLS is a decentralized scheme, it is necessary

    that the shedding order of the appliance categories is updated automatically. It is assumed

    that the data concerning the available sheddable load of each category and the shedding

    order of the appliances are updated four times per day, representing roughly the changes

    of the comfort loss values.

    Based on the previous assumptions and on the instantaneous consumption of each appliance

    group, the potential of the HLS scheme considering the total sheddable household load of

    Germany, i.e. 39700000 households, during the day can be computed. Considering also the

    shedding order of the appliance categories, the percentage of the total German load to be

    shed at each step of the HLS scheme provides an indicator of the efficiency of the scheme

    during a disturbance in the power system (Figure 12). The numbering of the categories

    order to be shed corresponds to the value of the comfort loss for each appliance category.

    32

  • 8/12/2019 Control Strategies for Under-Frequency Load Shedding

    36/71

    I. Stefanidou & M. Zerva 4. Household Load Shedding

    20,00%

    25,00%

    30,00%

    35,00%

    40,00%

    45,00%Category 6

    Category 5

    Category 4

    Category 3

    Category 2

    Category 1

    otal share ofGerman load

    0,00%

    5,00%

    10,00%

    15,00%

    20,00%

    25,00%

    30,00%

    35,00%

    40,00%

    45,00%

    0:00

    1:00

    2:00

    3:00

    4:00

    5:00

    6:00

    7:00

    8:00

    9:00

    10:00

    11:00

    12:00

    13:00

    14:00

    15:00

    16:00

    17:00

    18:00

    19:00

    20:00

    21:00

    22:00

    23:00

    Category 6

    Category 5

    Category 4

    Category 3

    Category 2

    Category 1

    otal share ofGerman load

    Figure 12: Sheddable household load in Germany.

    The base household load consisting of the thermal appliances and the battery chargers

    constitutes during the day the first household loads to be shed, providing for the HLS

    scheme a potential of almost 10% of the total German load. Due to the varying utilization,

    functionality and comfort loss indicators of the rest of the appliance categories, the total

    available sheddable household load in Germany is not constant during the day, but ranges

    from 12% to 35% of the total German load.

    The HLS scheme can be implemented either for prevention of the triggering of the CLS or

    for complete substitution of CLS. The potential of the HLS scheme depends in both cases

    on the time of the day, i.e. the load conditions, whereas the applied mechanism and the

    demands for the available sheddable load of each function differ. By implementing the HLS

    scheme as a complement to CLS, the main target is to delay or even prevent the triggering

    of CLS by shedding individual household loads before the frequency drops to the predefined

    thresholds of CLS. In this case, the number of German households considered determine

    33

  • 8/12/2019 Control Strategies for Under-Frequency Load Shedding

    37/71

    I. Stefanidou & M. Zerva 4. Household Load Shedding

    the potential of the scheme.

    In order to assess the potential of the HLS scheme at the time frames for which a completeset of data is available, the total sheddable load within a German household should be

    quantified for 3 a.m. and 11 a.m. on a winter and on a summer day (Table 4.2). As

    expected, during the night the available sheddable load is significantly lower, while it is

    slightly differentiated between winter and summer days.

    Electrical devices

    Available Sheddable load

    per Household (in W)

    Winter Summer

    11 a.m 3 a.m 11 a.m 3 a.m

    Refrigerator 105.738 105.738 105.738 105.738

    Warm water boiler 62.288 62.288 62.288 62.288

    Electrical Heating 1.142 1.142 0.000 0.000

    Battery charger 9.803 1.634 9.803 1.634

    Nonvital lights 4.949 1.252 4.949 1.252

    Microwave Oven 25.000 0.000 25.000 0.000

    Oven 100.001 0.000 100.001 0.000

    Coffee Machine 19.606 3.268 19.606 3.268Iron 14.705 2.451 14.705 2.451

    Vacuum Machine 19.606 3.268 19.606 3.268

    Hair Dryer 19.606 3.268 19.606 3.268

    Washing Machine 38.346 0.000 38.346 0.000

    Dryer 30.677 0.000 30.677 0.000

    Dishwasher 20.707 0.000 20.707 0.000

    TV 4.129 0.000 4.129 0.000

    DVD 1.032 0.000 1.032 0.000AudioHiFi 2.064 0.000 2.064 0.000

    Table 6: Sheddable load per German household.

    34

  • 8/12/2019 Control Strategies for Under-Frequency Load Shedding

    38/71

    I. Stefanidou & M. Zerva 4. Household Load Shedding

    4.3 UnderFrequency Household Load Shedding as a

    complement to Conventional Load SheddingThe HLS scheme as a complement to the CLS is triggered at thresholds higher than those

    defined for the CLS. The goal is to delay or preferably prevent the triggering of CLS, thus

    minimizing the costs related to the disturbance and the comfort loss to the consumers.

    There are six frequency thresholds defined, corresponding to the six levels of comfort loss

    (Figure 13). Taking into account the tolerance for the frequency deviation from its nominal

    value of 50 Hz and in an attempt to prevent the unnecessary triggering of the HLS, the

    first frequency threshold is set to 49.8 Hz. The frequency threshold for the CLS is set bythe UCTE to 49 Hz. Thus, the frequency steps for the HLS are set to 0.1 Hz, i.e. the range

    49.849.3 Hz.

    Figure 13: HLS scheme.

    4.3.1 Frequency response model

    The HLS scheme is implemented complementary to the CLS mechanism in order to delay

    or even prevent the complete loss of load in certain areas under emergency conditions.

    Therefore, the performance of the HLS scheme as a complement to the CLS mechanism

    can be quantified by additionally including in the frequency response model of the inter

    35

  • 8/12/2019 Control Strategies for Under-Frequency Load Shedding

    39/71

    I. Stefanidou & M. Zerva 4. Household Load Shedding

    connected system the block describing the function of the HLS mechanism (Figure 14).

    The input to the HLS block is the frequency deviation from its nominal value. When the

    system frequency drops to the predefined thresholds, the HLS mechanism is triggered and

    the respective household load category is disconnected (Figure 15). The lookup table cor

    responds the number of HLS stages being triggered to the cumulative household load that

    has to be shed. Since the system frequency is sampled in variable steps, a set of flip flops is

    implemented in order to avoid the multiple consideration of each household category that

    is shed (Figure 16).

    1

    0

    f0

    Turbine dynamics

    1

    7s+1

    System inertia

    f0/(2*H*S)

    Sum of f0+df

    Sum of

    loads of 24 UCTE countries

    SaturationPrimary control

    -1/(Spr*f0/S)

    Net Import

    Load

    Load

    1

    s

    Households Load Shedding

    dfHousehold Load shed

    Generation

    Frequency Dependency of Loads

    1.66*S/f0

    Final f

    freq

    Distributed

    Generation

    DG

    Conventional

    Load Shedding

    dfLoad shed

    Figure 14: Frequency response model including the HLS mechanism.

    The coordination of the two load shedding schemes, i.e. the CLS and the HLS, is crucial for

    the stability of the system when the CLS is triggered. The degree of correlation of the two

    load shedding schemes significantly depends on the number of households participating in

    the HLS scheme and the plan according to which feeders are shed for the CLS. The main

    point of interest is the assessment of the performance of the HLS, since the CLS is already

    implemented and welldefined. Therefore, it is assumed that once the CLS is not prevented,

    36

  • 8/12/2019 Control Strategies for Under-Frequency Load Shedding

    40/71

    I. Stefanidou & M. Zerva 4. Household Load Shedding

    it acts completely independently from the HLS by shedding the predefined share of total

    load, whereas the HLS acts until the CLS is triggered.

    HouseholdLoad Shed

    1

    Subtract

    Lookup Table

    In1 Out1

    In1 Out1

    In1 Out1

    In1 Out1

    In1 Out1

    In1 Out1

    -0.8

    -0.6

    -0.8

    -0.5

    -0.8

    -0.4

    -0.8

    -0.2

    -0.8

    -0.7

    -0.8

    -0.3

    6th stage

    upulo

    5th stage

    upulo

    4th stage

    upulo

    3rd stage

    upulo

    2nd stage

    upulo

    1st stage

    upulo

    df

    1

    Figure 15: HLS mechanism.

    Out1

    1

    S

    R

    Q

    !Q

    S

    R

    Q

    !Q Logical

    Operator

    OR

    Detect

    Decrease

    U < U/z

    Data Type Conversion

    boolean

    0

    In1

    1

    Figure 16: Set of flip flops.

    37

  • 8/12/2019 Control Strategies for Under-Frequency Load Shedding

    41/71

    I. Stefanidou & M. Zerva 4. Household Load Shedding

    4.4 UnderFrequency Household Load Shedding for

    substitution of Conventional Load SheddingThe HLS scheme can be alternatively implemented for substitution of the CLS scheme.

    The goal is to completely substitute the function of the CLS with the HLS scheme while

    being compliant with the UCTE guidelines regarding the emergency measures. Therefore,

    the frequency thresholds for the HLS scheme as a substitution of the CLS are set equal

    to those of the CLS, whereas at each frequency threshold the household load to be shed

    should equal to 10% of the total German load.

    The category with the lowest comfort loss, i.e. the refrigerators, boilers and electric heating,can successfully fulfill the UCTE requirements for the first load shedding step, assuming

    the participation of 100% of the German households (39 million) in the HLS scheme.

    For the subsequent load shedding steps, the shedding order of the devices categories is

    maintained. Thus, the devices categories are grouped together, so as the sheddable load

    at each shedding step amounts at least to 10% of the total German load. In the case that

    the sheddable household load is insufficient to cover 10% of the total German load for

    the second and third load shedding stages, the household loads are grouped in a way to

    amount to the maximum available load. Of interest in the present study is the capability ofthe Household Load Shedding scheme to completely substitute the existing load shedding

    schemes.

    4.4.1 Frequency Response Model

    The performance of the HLS scheme for the complete substitution of the CLS can be

    described by completely substituting the CLS block by the HLS block in the frequency

    response of the UCTE power system (Figure 17). The contribution of the DG to the totalgeneration of the UCTE is considered, whereas the additional loss of generation due to loss

    of DG is avoided, since feeders are not shed.

    38

  • 8/12/2019 Control Strategies for Under-Frequency Load Shedding

    42/71

  • 8/12/2019 Control Strategies for Under-Frequency Load Shedding

    43/71

    I. Stefanidou & M. Zerva 4. Household Load Shedding

    Household

    Load shed

    1

    Lookup Table

    In1 Out1

    In1 Out1

    In1 Out1

    -1.6

    -1

    -1.6

    -1.3

    3rd stage

  • 8/12/2019 Control Strategies for Under-Frequency Load Shedding

    44/71

    I. Stefanidou & M. Zerva 5. Reference Cases Results

    5 Reference Cases Results

    The purpose of the frequency control mechanisms of the power system is to maintain the

    power balance between the generation and consumption and, thus, guarantee the reliability

    and the security of the system. Deregulation of the electricity market has boosted the

    international trade of electricity and, therefore, has forced the interconnected power system

    to operate closer to its limits. The tripping of a generator, the tripping of a transmission

    line or the sudden increase of the load may result in the decrease of the frequency from

    its nominal value. In case of lack of generation, the frequency drops from its nominal

    value and all member countries of the UCTE follow certain procedures defined in the

    UCTE Operation Handbook, so as to stabilize the system and prevent the spreading of

    the disturbance.

    Figure 19: Physical and planned flows within the UCTE [6].

    Under normal conditions, the crossborder exchanges vary significantly according to time,

    weather conditions and locality. Tielines which were initially built for emergency and aux

    iliary purposes are used nowadays for trading. For the protection and the security of the

    system, the traded quantities and the power flows are planned and the stability of the

    system is tested ahead by simulation. However, the physical flows may differ from the

    planned ones, further stressing the system and making it more vulnerable to imminent

    disturbances (Figure 19). Considering the fact that limited capacity mainly exists for the

    interconnections of the control zones rather than for the transmissions system within a

    41

  • 8/12/2019 Control Strategies for Under-Frequency Load Shedding

    45/71

    I. Stefanidou & M. Zerva 5. Reference Cases Results

    control zone, the study cases include the outage of the interconnection lines and, subse

    quently, the islanding of areas. Therefore, in order to artificially create disturbances within

    the UCTE power system, the loadgeneration balance is affected either by the outage of

    interconnection lines or by the outage of generators.

    5.1 Reference Cases

    In the context of this study, the effects of the Distributed Generation present in the systemand the effectiveness of the conventional and the household load shedding are evaluated

    through two study cases. In both cases, the disturbance is a lack of generation due to

    the islanding of parts of the UCTE system. Individual control zones are kept intact, i.e.

    there is no tripping of transmission lines within the control zones. The lack of generation

    is attributed to the loss of interconnection lines, i.e. loss of net import and probably also

    generation loss, since a major disturbance is mainly caused by the cumulative impact of

    such incidents. The set of data available by the UCTE limits the appropriate time snapshots

    for which the power system frequency response can be evaluated at 3 a.m. and at 11 a.m.For completeness reasons, the cases are evaluated for different seasons of the year, so as to

    represent the different weather conditions and subsequently the different household load

    and Distributed Generation values.

    5.1.1 Summer scenario

    The summer day scenario includes the islanding of four countries, i.e. Germany, Switzer

    land, Austria and Italy and the additional loss of 12 GW of generation within Italy (Fig

    ure 20). The data used concern the 16th of July 2008, for which the UCTE load peaks

    during the summer and sufficient published data are available. Under the emergency con

    ditions, where interconnections to all other UCTE member countries, as well as the DC

    link to the Nordic countries, are lost, the power deficit at 11 a.m. is 14561 MW, while at

    3 a.m. the power deficit of the islanded system is 17748 MW.

    42

  • 8/12/2019 Control Strategies for Under-Frequency Load Shedding

    46/71

  • 8/12/2019 Control Strategies for Under-Frequency Load Shedding

    47/71

    I. Stefanidou & M. Zerva 5. Reference Cases Results

    Figure 21: Winter scenario.

    5.2 Simulation Results

    The frequency response of the power system to the disturbance reference cases is simulated

    in the environment of MATLAB with the toolbox SIMULINK. The derived model for

    the interconnected system of UCTE (see Section) is such that no time delay at the load

    shedding stages across the UCTE member countries is assumed. The data concerning the

    potential of DG and the household load of Germany and the UCTE published data of the

    system net import and load are used as inputs to the model.

    5.2.1 Case 1 Summer scenario, 11 a.m.

    The first case considered represents the summer scenario at 11 a.m. The data used as inputs

    to the frequency response model in order for the first case to be simulated are presented

    at the following Table 7.

    44

  • 8/12/2019 Control Strategies for Under-Frequency Load Shedding

    48/71

  • 8/12/2019 Control Strategies for Under-Frequency Load Shedding

    49/71

    I. Stefanidou & M. Zerva 5. Reference Cases Results

    0 5 10 15 20 25 30 35 40

    48.8

    49

    49.2

    49.4

    49.6

    49.8

    50

    50.2

    Time [sec]

    Frequency

    [Hz

    ]

    2008, 7.11% from DG2010 BEE e.V, 10.43% from DG

    2020 BEE e.V, 31% from DG

    2010 Leits., 9.67% from DG

    2020 Leits., 20.12% from DG

    No DG installations considered

    Figure 22: Case 1 Dynamic response including DG.

    0 5 10 15 20 25 30 35 4049

    49.1

    49.2

    49.3

    49.4

    49.5

    49.6

    49.7

    49.8

    49.9

    50

    Time [sec]

    Frequency

    [Hz

    ]

    CLS with DG considered

    10% HLS participation

    30% HLS participation

    50% HLS participation

    70% HLS participation

    100% HLS participation

    Figure 23: Case 1 Dynamic response with different household participations.

    46

  • 8/12/2019 Control Strategies for Under-Frequency Load Shedding

    50/71

  • 8/12/2019 Control Strategies for Under-Frequency Load Shedding

    51/71

    I. Stefanidou & M. Zerva 5. Reference Cases Results

    0 10 20 30 4049.2

    49.4

    49.6

    49.8

    50

    Time [sec]

    Frequency

    [Hz]

    70% Participation of Households

    0 10 20 30 4049.5

    49.6

    49.7

    49.8

    49.9

    50

    100% Participation of Households

    Time [sec]

    Frequency

    [Hz]

    0 10 20 30 4020

    10

    0

    10

    20

    Time [sec]

    Pow

    er

    [GW]

    0 10 20 30 40

    20

    10

    0

    10

    20

    Time [sec]

    Pow

    er

    [GW]

    dPCLSHLS

    dPCLSHLS

    Figure 26: Case 1 Dynamic response with 70% and 100% of the German households

    participating in the HLS scheme.

    0 5 10 15 20 25 30 35 4049

    49.2

    49.4

    49.6

    49.8

    50

    50.2

    50.4

    Time [sec]

    Frequency

    [Hz

    ]

    CLS without considering DGCLS considering DGHLS

    Figure 27: Case 1 Dynamic response with HLS scheme substituting the CLS mechanism

    for Germany.

    48

  • 8/12/2019 Control Strategies for Under-Frequency Load Shedding

    52/71

    I. Stefanidou & M. Zerva 5. Reference Cases Results

    0 5 10 15 20 25 30 35 4049.5

    49.6

    49.7

    49.8

    49.9

    50

    Time [sec]

    Frequency

    [Hz]

    0 5 10 15 20 25 30 35 4020

    10

    0

    10

    20

    Time [sec]

    Pow

    er

    [GW]

    HLS

    dP

    Figure 28: Case 1 Dynamic response with HLS scheme substituting the CLS mechanism

    for Germany.

    49

  • 8/12/2019 Control Strategies for Under-Frequency Load Shedding

    53/71

    I. Stefanidou & M. Zerva 5. Reference Cases Results

    5.2.2 Case 2 Summer scenario, 3 a.m.

    The second case studied represent the summer scenario at 3 a.m. The set of input data to

    the frequency response model for the second case are given in the following Table 8.

    Generation 74429 MW

    Load 92177 MW

    Net import 0 MW

    Power deficit 17748 MW

    Sheddable load per household 188.17 W

    DG installed capacity 2008 6607.82 MWDG 2010 BEE e.V. 8126.16 MW

    DG 2020 BEE e.V. 15570.84 MW

    DG 2010 Leitszenario 2008 7680.53 MW

    DG 2020 Leitszenario 2008 14884.87 MW

    Table 8: Case 2 Power data.

    The power deficit of 17.75 GW is compensated by the activation of two underfrequency

    load shedding stages, i.e. the frequency decay is intercepted at 48.7 Hz. Distributed Gen

    eration represents 8.88% of the total generation, with this share rising up to 20.92% in the

    future penetration scenarios (Figure 29).

    The activation effect of the HLS mechanism can be observed due to the small delay of

    the triggering of the two required stages of the CLS (Figure 30. However, the large power

    deficit combined with the low household load during the night limits the effectiveness of

    the HLS. Therefore, the triggering of the CLS is not avoided even under the favorable

    conditions of 100% of households participation (Figures 31, 32, 33).

    In the case of the complete substitution of the CLS by the HLS the sheddable household

    load is insufficient for covering the UCTEcompliant second load shedding stage (20% of

    the total German load). The inability of the HLS scheme to cover the second load shedding

    step during the night was expected according to the quantified sheddable load potential

    which does not exceed the 15% of the total German load (Figures 34, 35).

    50

  • 8/12/2019 Control Strategies for Under-Frequency Load Shedding

    54/71

    I. Stefanidou & M. Zerva 5. Reference Cases Results

    0 5 10 15 20 25 30 35 4048.6

    48.8

    49

    49.2

    49.4

    49.6

    49.8

    50

    50.2

    50.4

    Time [sec]

    Frequency

    [Hz

    ]

    2008, 8.88% from DG

    2010 BEE e.V, 10.92% from DG2020 BEE e.V, 20.92% from DG

    2010 Leits., 10.32% from DG

    2020, Leits., 20% from DG

    No DG installations considered

    Figure 29: Case 2 Dynamic response including DG.

    0 5 10 15 20 25 30 35 4048.6

    48.8

    49

    49.2

    49.4

    49.6

    49.8

    50

    Time [sec]

    Frequency

    [Hz

    ]

    CLS with DG considered

    10% HLS participation

    30% HLS participation

    50% HLS participation

    70% HLS participation

    100% HLS participation

    Figure 30: Case 2 Dynamic response with different household participation.

    51

  • 8/12/2019 Control Strategies for Under-Frequency Load Shedding

    55/71

    I. Stefanidou & M. Zerva 5. Reference Cases Results

    0 10 20 30 4048.5

    49

    49.5

    50

    Time [sec]

    Frequency

    [Hz]

    Without HLS

    0 10 20 30 4048.5

    49

    49.5

    50

    10% Participation of Households

    Time [sec]

    Frequency

    [Hz]

    0 10 20 30 4020

    10

    0

    10

    20

    Time [sec]

    Pow

    er

    [GW]

    0 10 20 30 40

    20

    10

    0

    10

    20

    Time [sec]

    Pow

    er

    [GW]

    dPCLSHLS

    dPCLSHLS

    Figure 31: Case 2 Dynamic response without the HLS mechanism and with the partici

    pation of 10% of the German households.

    0 10 20 30 4048.5

    49

    49.5

    50

    Time [sec]

    Frequency

    [Hz]

    30% Participation of Households

    0 10 20 30 4048.5

    49

    49.5

    5050% Participation of Households

    Time [sec]

    Frequency

    [Hz]

    0 10 20 30 4020

    10

    0

    10

    20

    Time [sec]

    Power

    [GW

    ]

    0 10 20 30 40

    20

    10

    0

    10

    20

    Time [sec]

    Power

    [GW

    ]

    dPCLSHLS

    dPCLSHLS

    Figure 32: Case 2 Dynamic response with 30% and 50% of the German households

    participating in the HLS scheme.

    52

  • 8/12/2019 Control Strategies for Under-Frequency Load Shedding

    56/71

    I. Stefanidou & M. Zerva 5. Reference Cases Results

    0 10 20 30 4048.5

    49

    49.5

    50

    Time [sec]

    Frequency

    [Hz]

    70% Participation of Households

    0 10 20 30 4048.5

    49

    49.5

    50

    100% Participation of Households

    Time [sec]

    Frequency

    [Hz]

    0 10 20 30 4020

    10

    0

    10

    20

    Time [sec]

    Pow

    er

    [GW]

    0 10 20 30 40

    20

    10

    0

    10

    20

    Time [sec]

    Pow

    er

    [GW]

    dPCLSHLS

    dPCLSHLS

    Figure 33: Case 2 Dynamic response with 70% and 100% of the German households

    participating in the HLS scheme.

    0 5 10 15 20 25 30 35 4048.6

    48.8

    49

    49.2

    49.4

    49.6

    49.8

    50

    50.2

    50.4

    Time [sec]

    Frequency

    [Hz

    ]

    CLS without considering DGCLS considering DGHLS

    Figure 34: Case 2 Dynamic response with the HLS scheme substituting the CLS mecha

    nism for Germany.

    53

  • 8/12/2019 Control Strategies for Under-Frequency Load Shedding

    57/71

    I. Stefanidou & M. Zerva 5. Reference Cases Results

    0 5 10 15 20 25 30 35 4048.5

    49

    49.5

    50

    Time [sec]

    Frequency

    [Hz]

    0 5 10 15 20 25 30 35 4020

    10

    0

    10

    20

    Time [sec]

    Pow

    er

    [GW]

    HLSdP

    Figure 35: Case 2 Dynamic response with the HLS scheme substituting the CLS mecha

    nism for Germany.

    54

  • 8/12/2019 Control Strategies for Under-Frequency Load Shedding

    58/71

    I. Stefanidou & M. Zerva 5. Reference Cases Results

    5.2.3 Case 3 Winter scenario, 11 a.m.

    The input data to the frequency response model in the third case, representing the winter

    scenario at 11 a.m. are shown in the following Table 9.

    Generation 210557 MW

    Load 221883 MW

    Net import 30 MW

    Power deficit 11296 MW

    Sheddable load per household 484.40 W

    DG installed capacity 2008 8758.75 MWDG 2010 BEE e.V. 11623.26 MW

    DG 2020 BEE e.V. 27620.6 MW

    DG 2010 Leitszenario 2008 10847.25 MW

    DG 2020 Leitszenario 2008 20989.82 MW

    Table 9: Case 3 Power data.

    The system under study of the second scenario is larger and therefore more robust. The

    power deficit of 11.3 GW is compensated with the activation of the first underfrequency

    load shedding stage. The contribution of the Distributed Generation is significantly smaller

    (4.16%) and thus, the negative effects of the additional loss of generation due to load

    shedding are less observable (Figure 36).

    The household load of the 30% of the German households proves to be sufficient to cover

    the power deficit of the system under study, without shedding the category with the highest

    comfort loss. The 50% of the German households have a total sheddable load enough to

    stabilize the system frequency with only four HLS stages triggered (Figures 37, 38, 39, 40).

    The HLS mechanism functioning as a substitution of the CLS proves to be successful in

    eliminating the disturbance caused on a winter day (Figures 41, 42). The overshedding of

    the HLS mechanism compared to the CLS is owned up to the fact that the household load

    in Germany is categorized in six categories. The categories are grouped together at each

    stage in order to amount to at least 10% of the total German load and they cannot be

    further split, since the decentralized HLS mechanism is preset.

    55

  • 8/12/2019 Control Strategies for Under-Frequency Load Shedding

    59/71

    I. Stefanidou & M. Zerva 5. Reference Cases Results

    0 5 10 15 20 25 30 35 4049

    49.5

    50

    50.5

    51

    51.5

    Time [sec]

    Frequency

    [Hz

    ]

    2008, 4.16% from DG

    2010 BEE e.V., 5.52% from DG2020 BEE e.V., 13.12% from DG

    2010 Leits., 5.16% from DG

    2020 Leits., 9.97% from DG

    No DG installations considered

    Figure 36: Case 3 Dynamic response including DG.

    0 5 10 15 20 25 30 35 4049

    49.5

    50

    50.5

    51

    51.5

    Time [sec]

    Frequency

    [Hz

    ]

    CLS with DG considered

    10% HLS participation

    30% HLS participation

    50% HLS participation

    70% HLS participation

    100% HLS participation

    Figure 37: Case 3 Dynamic response with different household participation.

    56

  • 8/12/2019 Control Strategies for Under-Frequency Load Shedding

    60/71

    I. Stefanidou & M. Zerva 5. Reference Cases Results

    0 10 20 30 4049

    49.5

    50

    50.5

    51

    51.5

    Time [sec]

    Frequency

    [H

    z]

    Without HLS

    0 10 20 30 4049

    49.5

    50

    50.5

    51

    51.5

    10% Participation of Households

    Time [sec]

    Frequency

    [H

    z]

    0 10 20 30 4030

    20

    10

    0

    10

    20

    Time [sec]

    Pow

    er

    [GW]

    0 10 20 30 40

    30

    20

    10

    0

    10

    20

    Time [sec]

    Pow

    er

    [GW]

    dP

    CLS

    HLS

    dP

    CLS

    HLS

    Figure 38: Case 3 Dynamic response without the HLS mechanism and with the partici

    pation of 10% of the German households.

    0 10 20 30 4049.2

    49.4

    49.6

    49.8

    50

    Time [sec]

    Frequency

    [Hz]

    30% Participation of Households

    0 10 20 30 4049.5

    49.6

    49.7

    49.8

    49.9

    5050% Participation of Households

    Time [sec]

    Frequency

    [Hz]

    0 10 20 30 4015

    10

    5

    0

    5

    10

    Time [sec]

    Power

    [GW

    ]

    0 10 20 30 40

    15

    10

    5

    0

    5

    10

    Time [sec]

    Power

    [GW

    ]

    dPCLSHLS dPCLSHLS

    Figure 39: Case 3 Dynamic response with 30% and 50% of the German households

    participating in the HLS scheme.

    57

  • 8/12/2019 Control Strategies for Under-Frequency Load Shedding

    61/71

    I. Stefanidou & M. Zerva 5. Reference Cases Results

    0 10 20 30 4049.6

    49.7

    49.8

    49.9

    50

    Time [sec]

    Frequency

    [Hz]

    70% Participation of Households

    0 10 20 30 4049.7

    49.8

    49.9

    50

    50.1

    100% Participation of Households

    Time [sec]

    Frequency

    [H

    z]

    0 10 20 30 4015

    10

    5

    0

    5

    10

    Time [sec]

    Pow

    er

    [GW]

    0 10 20 30 40

    20

    10

    0

    10

    20

    Time [sec]

    Pow

    er

    [GW]

    dPCLSHLS

    dPCLSHLS

    Figure 40: Case 3 Dynamic response with 70% and 100% of the German households

    participating in the HLS scheme.

    0 5 10 15 20 25 30 35 4049

    49.5

    50

    50.5

    51

    51.5

    52

    Time [sec]

    Frequency

    [Hz

    ]

    CLS without considering DGCLS considering DGHLS

    Figure 41: Case 3 Dynamic response with the HLS scheme substituting the CLS mecha

    nism for Germany.

    58

  • 8/12/2019 Control Strategies for Under-Frequency Load Shedding

    62/71

    I. Stefanidou & M. Zerva 5. Reference Cases Results

    0 5 10 15 20 25 30 35 4049

    49.5

    50

    50.5

    51

    51.5

    52

    Time [sec]

    Frequency

    [H

    z]

    0 5 10 15 20 25 30 35 4020

    10

    0

    10

    20

    30

    Time [sec]

    Power

    [GW]

    HLS

    dP

    Figure 42: Case 3 Dynamic response with the HLS scheme substituting the CLS mecha

    nism for Germany.

    59

  • 8/12/2019 Control Strategies for Under-Frequency Load Shedding

    63/71

    I. Stefanidou & M. Zerva 5. Reference Cases Results

    5.2.4 Case 4 Winter scenario, 3 a.m.

    The input data to the frequency response model in the fourth case, representing the winter

    scenario at 3 a.m. are shown in the following Table 10.

    Generation 153942 MW

    Load 160818 MW

    Net import 321 MW

    Power deficit 7197 MW

    Sheddable load per household 189.31 W

    DG installed capacity 2008 7905.70 MWDG 2010 BEE e.V. 9765.41 MW

    DG 2020 BEE e.V. 18779 MW

    DG 2010 Leitszenario 2008 9180.44 MW

    DG 2020 Leitszenario 2008 17104.44 MW

    Table 10: Case 4 Power data.

    The frequency drop is eliminated at 49 Hz, i.e. the first underfrequency load shedding

    stage is triggered. The power deficit of 7.2 GW is fully compensated, without, however,

    achieving to avoid load overshedding (Figure 43).

    The triggering of the CLS is completely avoided with the participation of 30% of the Ger

    man households (Figures 44, 45, 46). With a participation of at least the 70% of the German

    households in the HLS mechanism, the system frequency is stabilized only by disconnecting

    the first HLS category, with the lowest comfort loss to the consumers (Figure 47).

    On a winter day, during night, the substitutional function of the HLS mechanism proves to

    be successful in stabilizing the system (Figures 48, 49, in spite the fact that the sheddable

    household load is limited including mainly the first category with the appliances with

    high inertia. Thus, the household load mechanism proves to be compliant with the UCTE

    guidelines and sufficient for covering the first shedding stage at all times.

    60

  • 8/12/2019 Control Strategies for Under-Frequency Load Shedding

    64/71

    I. Stefanidou & M. Zerva 5. Reference Cases Results

    0 5 10 15 20 25 30 35 4049

    49.5

    50

    50.5

    51

    51.5

    Time [sec]

    Frequency

    [Hz

    ]

    2008, 5.14% from DG

    2010 BEE e.V, 6.34% from DG2020 BEE e.V, 12.2% from DG

    2010 Leits., 5.96% from DG

    2020 Leits., 11.11% from DG

    No DG installations considered

    Figure 43: Case 4 Dynamic response including DG.

    0 5 10 15 20 25 30 35 4049

    49.5

    50

    50.5

    51

    51.5

    Time [sec]

    Frequency

    [Hz

    ]

    CLS with DG considered

    10% HLS participation

    30% HLS participation

    50% HLS participation

    70% HLS participation

    100% HLS participation

    Figure 44: Case 4 Dynamic response with different household participation.

    61

  • 8/12/2019 Control Strategies for Under-Frequency Load Shedding

    65/71

    I. Stefanidou & M. Zerva 5. Reference Cases Results

    0 10 20 30 4049

    49.5

    50

    50.5

    51

    51.5

    Time [sec]

    Frequency

    [Hz]

    Without HLS

    0 10 20 30 4049

    49.5

    50

    50.5

    51

    51.5

    10% Participation of Households

    Time [sec]

    Frequency

    [Hz]

    0 10 20 30 4020

    10

    0

    10

    20

    Time [sec]

    Pow

    er

    [GW]

    0 10 20 30 40

    10

    0

    10

    20

    10

    20

    10

    Time [sec]

    Pow

    er

    [GW]

    dPCLSHLS

    dPCLSHLS

    Figure 45: Case 4 Dynamic response without the HLS mechanism and with the partici

    pation of 10% of the German households.

    0 10 20 30 4049.2

    49.4

    49.6

    49.8

    50

    Time [sec]

    Frequency

    [Hz]

    30% Participation of Households

    0 10 20 30 4049.5

    49.6

    49.7

    49.8

    49.9

    5050% Participation of Households

    Time [sec]

    Frequency

    [Hz]

    0 10 20 30 4010

    0

    10

    20

    Time [sec]

    Power

    [GW

    ]

    0 10 20 30 4010

    0