Upload
jjnaides
View
218
Download
0
Embed Size (px)
Citation preview
8/3/2019 Control Philosoph1
1/10
PREPARED
BYNA
PTT PUBLIC COMPANY LIMITED
CHECKED
BY ONSHORE COMPRESSOR STATION 4
PROJECT
APPROVED
BY
CERTIFIED
(PTT)NA
REV.
NO.
DATE REVISED
BY
APPROVED
BY
DESCRIPTION
D1 14-Feb-08 NA ISSUED FOR ITB
D2 11-Jun-08 NA REVISION ISSUED FOR ITB
PHILOSOPHY FOR
CONTROL SYSTEMS
PHC-0804.02-60.01 REV.D2
TOTAL 10 PAGES
AREA CODE OF SITE LOCATION
GENERAL AREA: 010
.
PTT PLC. CONTRACT NO.PTT PLC. PROJECT NO.
0804.02
8/3/2019 Control Philosoph1
2/10
PHILOSOPHY FOR
CONTROL SYSTEMSPTT PUBLIC COMPANY LIMITED
PHILOSOPHYPHC-0804.02-60.01
PAGE 2 OF 10
REV: D2
CONTENTS
SECTION
1.0 OVERVIEW .............................................................................................. 3
2.0 DCS........................................................................................................ 3
3.0 SAFETY INSTRUMENTED SYSTEM ............................................................. 4
4.0 UNIT CONTROL PANELS FOR MOTOR DRIVEN COMPRESSOR PACKAGE........ 5
5.0 MASTER PERFORMANCE, ANTI SURGE AND LOAD SHARING CONTROLLERS. 6
6.0 FIRE AND GAS CONTROLLERS................................................................... 7
7.0 MACHINE MONITORING SYSTEM............................................................... 7
8/3/2019 Control Philosoph1
3/10
PHILOSOPHY FOR
CONTROL SYSTEMSPTT PUBLIC COMPANY LIMITED
PHILOSOPHYPHC-0804.02-60.01
PAGE 3 OF 10
REV: D21.0 Overview
This document describes the design philosophy for the development of the
specification, detail design and system implementation for the control systems.
The control systems in this document will be limited to the systems which are
related to THE ONSHORE COMPRESSOR STATION 4 (OCS# 4). The
control systems for the OCS# 4 shall include at least DCS, Safety
Instrumented System, Unit Control Panel for compressor package, Master
performance/Anti surge/load sharing controller and Fire&Gas and Machine
Monitoring System.
2.0 DCSThe DCS system shall consist of a network of Field Control Stations (FCS) to
provide the core plant control and monitoring functions and the Human
Machine Interface (HMI) workstations for operators to operate the facilities.
The DCS shall be designed to execute all process controls which are not
related to safety functions.
PTT operators shall be able to initiate the command to start/stop the
compressor trains, switch over the trains of equipment, change the set points
for any process control and perform any other control functions via the DCS
HMI workstations. The DCS shall also acquire the information from all utilities
and equipment packages, such as motor driven compressor packages,
electrical, instrument air, fire fighting, and machine management system etc.,
in the facilities for monitoring and control. The control signals from DCS to
other package equipments (and vice versa) shall be hard wired while the soft
link shall be used for monitoring only.
The DCS displays and console shall be ergonomically designed to allow PTT
operator to fast access the desired information and to operate the facility
without fatigue. The position of key switch, push button, alarm indication and
communication systems in the DCS console shall also be orderly located for
easy access.
The DCS shall utilize a fully redundant Bus system, CPU, power supply,process and communication to the external system controllers with automatic
bumpless switchover between the hot and standby controllers.
The DCS FCS shall comprise of redundant CPUs, power supplies, Field control
units (FCU) and communication controllers.
All DCS Field Control Units (FCU) shall be foundation field bus for field
transmitters and final elements directly connected to DCS.
The arrangement for the Field Control Stations (FCS) shall prevent the
common cause of inoperability for the equipment trains when the FCS/ itspart fail or are under maintenance. All field process devices of different
compressor trains shall not be connected to the same FCS and the same
principal shall be applied to the inlet scrubber trains and communication
between DCS and the compressor control systems.
8/3/2019 Control Philosoph1
4/10
PHILOSOPHY FOR
CONTROL SYSTEMSPTT PUBLIC COMPANY LIMITED
PHILOSOPHYPHC-0804.02-60.01
PAGE 4 OF 10
REV: D2All sequential process control, related to the operation of the compressor train
and station, outside the motor driven compressor packages shall be performedby the DCS system. The DCS shall execute the program based on the input
command from the related compressor unit control panel for the required
actions from the field devices.
The DCS system shall be designed to allow the data exchange with the
existing PTT DCS, LNG terminal DCS and the existing PTT SCADA system.
The Sequence Of Event (SOE) in the DCS shall be provided to handle all of
the events related to filed devices connected to the DCS, SIS, other
equipment package control and utility systems.
The DCS shall be equipped with the Plant Information System (PIMS) to
manage all related facility historical operating data for reporting and
process/operation analysis. In addition the Plant Resource Management (PRM)
shall be provided to collect data from all field devices for maintenance
planning and other related activities. These two systems shall be equipped
with the DCS package.
The DCS shall function as a systems master clock for the all equipment
package control systems. DCS shall receive the clock data from GPS and then
synchronize with other systems once per day.
The programming for the logic control in the DCS shall utilize function block.
3.0 Safety Instrumented SystemThe Safety Instrument System (SIS) refers to the field input devices, logic
solver and final element as defined by IEC 61511. It is imperative that the
Safety Life Cycle (SLC) documents as required by IEC 61511 shall be
implemented beginning from SLC analysis up to operation phases. All required
functions and configuration related to the SIS shall be thoroughly defined in
the Safety Requirement Specification (SRS) before the system implementation.
In addition the SIL calculation and SIS equipment selection shall be based onMTTR of 8 hours and 1 year testing interval.
The SIS shall execute only functions related to the safety for the facility
operations such as over pressure protection, process shutdown, and emergency
shutdown with/without blowdown etc. For the shutdown of the motor driven
compressor packages due to process condition, the SIS shall send the hard wire
signal to the required unit control panels (UCP) to execute theirs own shutdown
logic. In the case that the trip of compressor come from its internal causes, the
SIS shall receive the hard wire signal from UCPs to execute related process
shutdown. The status of the final elements, if not required for the safety
functions, shall be sent to the DCS only.
All of the equipments used in the SIS shall be certified by TUV for the safety
application. For logic solver, it shall be certified for SIL 3 application.
8/3/2019 Control Philosoph1
5/10
PHILOSOPHY FOR
CONTROL SYSTEMSPTT PUBLIC COMPANY LIMITED
PHILOSOPHYPHC-0804.02-60.01
PAGE 5 OF 10
REV: D2All of the field input devices connected to the logic solver shall be 2oo3 voting
configuration. All field input to the SIS logic solver shall be 4-20 mA HARTtransmitter. The DCS shall perform the transmitter integrity check function by
comparing the value of three transmitters in the same loop and shall initiate
alarm when the difference is higher than the preset value. The DCS shall also
set the pre-trip alarm to alert the operators before the process condition reach
the trip set point by using the values from the SIS transmitters.
The SIS logic solver shall be based on 1oo2D configuration. It shall comprise of
the network of Safety Control Stations (SCS). Each SCS shall comprise of
redundant CPUs, power supplies, Safety Control Units (SCU) and
communication controllers.
The arrangement for the Safety Control Stations (SCS) shall prevent the
common cause of inoperability for the equipment trains when the SCS/ its parts
fail or are under maintenance. All field process devices of different compressor
trains shall not be connected to the same SCS and the same principal shall be
applied to the inlet scrubber trains.
The Sequence Of Event (SOE) shall be fully integrated with that of DCS in order
to allow the efficient analysis of the shutdown with related process information.
The design of the SIS shall allow the on line testing for the system from the
field inputs up to the final elements with less human intervention.
4.0 Unit Control Panels for Motor Driven Compressor PackageThe compressor station control system shall comprise of the Unit Control
Panels (UCP), anti surge and load sharing controllers.
Each motor driven compressor shall be provided with its dedicated PLC based
Unit Control Panel. This PLC shall be redundant in all aspects such as CPUs,
power supplies, I/O cards etc.
The UCP shall perform all required functions for the operation of compressorsuch as speed control, start/normal stop and emergency shut down. The UCP
shall receive hard wire signals from the DCS for start/normal stop and the SIS
for emergency shutdown due to process condition. When the compressor
package trips by its own condition, the UCP shall send the hard wire signal to
the SIS to execute the process shutdown functions outside the compressor
package. The UCP shall also send the operating data to the DCS for monitoring
via soft link.
The UCP shall send hard wire command to the related switch gears/MCCs for
the operation of lube oil pumps, lube oil coolers, and any other auxiliary devices
in both normal and emergency case. For the emergency case, the UCP shallsend command to the emergency shut down relays in the related
switchgears/MCCs.
8/3/2019 Control Philosoph1
6/10
PHILOSOPHY FOR
CONTROL SYSTEMSPTT PUBLIC COMPANY LIMITED
PHILOSOPHYPHC-0804.02-60.01
PAGE 6 OF 10
REV: D2The field transmitters connected to these systems shall be 4-20 mA HART and
the information for each transmitter shall be sent to the PRM.The UCP shall have its dedicated vibration monitoring systems. All data from
these systems shall be transferred to the Machine Monitoring System Server.
The HMIs shall be provided locally at the UCP and remotely at the DCS
consoles. These two HMI shall have similarly functionalities. The remote and
local HMI shall be equipped with the database server to store all historical
operating parameter for the compressor packages.
5.0 Master Performance, Anti surge and Load Sharing Controllers
The master performance, anti surge and load sharing controllers shall beseparate system from the PLC used for the UCP of the compressor train. These
controllers shall be the dedicated systems to serve the desired purposes and
mounted into the unit control panels
The master performance controller shall receive the hard wire process set point
from the DCS, and input from the load sharing/ anti surge controllers, process
the inputs and send the command to the related controllers.
The anti surge and load sharing controllers shall receive the speed , process
data and other required compressor status from the UCP of operated
compressors to perform the anti surge and load sharing functions. The antisurge controller shall also be able to receive the hard wire command from the
DCS for manual operations of the anti surge control valve with anti surge
override function.
The anti surge and load sharing controllers shall be equipped with the fall back
strategy to manage the failure of their input signals in order to minimize the
unnecessary shutdown from this cause.
As same as the UCP, these controllers shall send all operating data to the DCS
for monitoring via soft link in order to allow the DCS HMI workstation to show
the same information and displays as those on the local monitors for thecompressor station control system.
The master performance, anti surge and load sharing controllers shall be fully
redundant in all aspects of the system with bumpless transfer between the hot
and standby units.
The field transmitters connected to these systems will be 4-20 mA HART and
the information for each transmitter shall be sent to the PRM.
The remote HMI workstation for these controllers shall be provided in the DCS
console. This remote HMI workstation shall display all related process data,alarm and event log and healthy of the systems. The remote HMI workstation
shall also be equipped with the engineering and maintenance software for these
controllers.
8/3/2019 Control Philosoph1
7/10
PHILOSOPHY FOR
CONTROL SYSTEMSPTT PUBLIC COMPANY LIMITED
PHILOSOPHYPHC-0804.02-60.01
PAGE 7 OF 10
REV: D26.0 Fire and Gas Controllers
The fire and gas controllers shall be separated from each other and mounted in
the separate control panel.
The fire controller panels shall include the master fire controller panel and
dedicated fire controller panel for each building. The fire controller panel for
each building shall receive the signal from the detectors, perform voting
function and actuated the fire suppression system. The master fire controller
panel shall handle the detectors and manual call points in the field. The master
fire control panel shall also acquire the information from the fire controller panel
in each building. All information related to the system shall be displayed at the
local and remote HMI workstation.
The gas controller panel shall include at least controllers, local and remote HMI
workstations, and push button for the required functions. The gas controller
panel shall handle the gas detectors and the fire suppression systems in the
field/process areas.
The gas control panel shall be equipped with the dedicated push buttons for
each fire suppression systems, such as fire monitors and deluges, in the field.
The operator shall be able to initiate the action of these devices via these push
buttons. In addition, the reset and horn interrupt push buttons shall also be
mounted on this panel
The fire and gas systems shall utilize the common remote HMI installed in the
DCS control. The remote and local HMIs shall contain the graphical displays for
all areas. The graphical displays design shall be in hierarchy from the overview
to the detail graphical displays. The graphical display shall clearly show the
location of the detectors and fire suppression system. The detectors and fire
suppression systems shall be flashed out on the related displays when the
abnormal situation is detected or the fire suppression systems are actuated.
The local HMI workstations at the master fire and gas controller panels shall be
equipped with the engineering and maintenance software for each system.
7.0 Machine Monitoring System
The Machine Monitoring System shall include server, vibration controllers and
detectors/sensors. The server shall acquire the data from vibration controllers
included those provided by package vendors and store for further vibration
analysis. The server shall be equipped with the software to allow PTT
maintenance personnel to analyze these vibration data in all aspects.
The vibration controllers shall receive the data from vibration detectors/ sensors
and transfer them to the DCS for monitoring via soft link. In case that the
controller detects the vibration of connected equipments, it shall send the hardwire signal to SIS to shutdown the related process units.
All alarm from the vibration controllers shall also be transferred to the DCS.
8/3/2019 Control Philosoph1
8/10
PHILOSOPHY FOR
CONTROL SYSTEMSPTT PUBLIC COMPANY LIMITED
PHILOSOPHYPHC-0804.02-60.01
PAGE 8 OF 10
REV: D2For the purposes of machine condition monitoring, machines are classified into
four categories as shown in the following table and the system shall designedand provided accordingly.
TYPE OF MACHINE ONLINE OFFLINE
CONTINOUS NON
CONTINOUS
WITH
PROTECTION
(Portable)
CRITICAL MACHINE YES YES
Compressors
Generators
ELECTRIC MOTORS WITH
JOURNAL BEARINGS
GEARBOXES
VOITH VARECON COUPLINGS
Machines With Journal Bearings
ESSENTIAL MACHINE1 YES YES YES
Fans
Fan Motor
ESSENTIAL MACHINE2 YES NO YES
OTHER PROCESS MACHINES
UTILITY MACHINES >= to15KW
SUBSYSTEMS OF CRITICAL
MACHINERY
NON ESSENTIAL MACHINE NO NO NO YES
UTILITY MACHINES < 15KW
Table 2. Types of Machines
8/3/2019 Control Philosoph1
9/10
PHILOSOPHY FOR
CONTROL SYSTEMSPTT PUBLIC COMPANY LIMITED
PHILOSOPHYPHC-0804.02-60.01
PAGE 9 OF 10
REV: D2Transducer arrangements per type of machine are indicated in the following table
TYPE OF MACHINE TRANSDUCER ARRANGEMENT
CRITICAL MACHINES
All Proximity probes 2-X, 2-Y, for each radial bearing, 2-Z for
each thrust bearing and key phasor. Three accelerometer
measuring point per casing.
ESSENTIAL MACHINE 1
Air coolers 1 accelerometer for the fan bearing, 1 accelerometer for
the motor casing
ESSENTIAL MACHINE 2 Accelerometers, 1-X for the motor casing, 1-X for the
pump casing. Where the machine is a "between bearings"
design an additional probe shall be provided on the driven
machine.
NON ESSENTIAL MACHINES No permanent probes.
Table 3. Transducer arrangements
Critical Machines
The contractor shall provide the Bentley Nevada 3500 rack system segregated
on a machine by machine basis, to interface to field transducer. The Bently
Nevada system shall interface to the machinery control system (local PLC, DCS
or SIS) to provide the required indication, alarm and trip functions. If theBentley Nevada system is connected directly to a local machinery control PLC
then all vibration and monitoring signals shall be repeated to the DCS for
indication.
The Bently Nevada 3500 system shall be interfaced via Bently Nevada TDXnet
modules to form the machine monitoring network.
The TDXnet modules shall be linked to the DCS via dual redundant serial cable
to give the necessary indication.
Each of the TDXnet modules shall be networked using a 10 Base T hub/switch
connection.
8/3/2019 Control Philosoph1
10/10
PHILOSOPHY FOR
CONTROL SYSTEMSPTT PUBLIC COMPANY LIMITED
PHILOSOPHYPHC-0804.02-60.01
PAGE 10 OF 10
REV: D2 Essential Machines category 1
These machines shall be monitored continuously by accelerometers connected
to a Bently-Nevada 3500 system. The 3500 system shall send trip signals to
the SIS system for machinery protection purposes and to the System 1 server
for machinery analysis. Transducers shall be installed to monitor the fan bearing
housing and the motor casing vibration. Additional data may be collected using
a Bently-Nevada Snapshot portable data collection and analysis unit.
Essential Machines category 2
Each machine in this category shall be fitted with permanent vibration
transducers to monitor pump and motor casing vibration. These transducers
shall be connected to the SPA cards on the System 1 server in a multi-drop
configuration. Additional data may be collected using a Bently-Nevada
Snapshot portable data collection and analysis unit.
Non Essential Machines
Vibration measurements shall be taken by a Bently-Nevada Snapshot portable
data collection and analysis unit. This data shall be downloaded to the System
1 server for machinery analysis purposes.
The machinery monitoring network shall be connected to the ESP DCS ethernet
network via a network switch to allow data to be transferred between the twosystems.
The contractor shall provide a Bently-Nevada System 1 data acquisition and
management system located at instrument rack room to provide full analysis of
all machinery data. This system shall be provided with the following modules:
Data Acquisition, Display and Configuration, Database (SQL Server) DDE
Exporter/Importer, OLE Automation Exporter.