Control Philosoph1

Embed Size (px)

Citation preview

  • 8/3/2019 Control Philosoph1

    1/10

    PREPARED

    BYNA

    PTT PUBLIC COMPANY LIMITED

    CHECKED

    BY ONSHORE COMPRESSOR STATION 4

    PROJECT

    APPROVED

    BY

    CERTIFIED

    (PTT)NA

    REV.

    NO.

    DATE REVISED

    BY

    APPROVED

    BY

    DESCRIPTION

    D1 14-Feb-08 NA ISSUED FOR ITB

    D2 11-Jun-08 NA REVISION ISSUED FOR ITB

    PHILOSOPHY FOR

    CONTROL SYSTEMS

    PHC-0804.02-60.01 REV.D2

    TOTAL 10 PAGES

    AREA CODE OF SITE LOCATION

    GENERAL AREA: 010

    .

    PTT PLC. CONTRACT NO.PTT PLC. PROJECT NO.

    0804.02

  • 8/3/2019 Control Philosoph1

    2/10

    PHILOSOPHY FOR

    CONTROL SYSTEMSPTT PUBLIC COMPANY LIMITED

    PHILOSOPHYPHC-0804.02-60.01

    PAGE 2 OF 10

    REV: D2

    CONTENTS

    SECTION

    1.0 OVERVIEW .............................................................................................. 3

    2.0 DCS........................................................................................................ 3

    3.0 SAFETY INSTRUMENTED SYSTEM ............................................................. 4

    4.0 UNIT CONTROL PANELS FOR MOTOR DRIVEN COMPRESSOR PACKAGE........ 5

    5.0 MASTER PERFORMANCE, ANTI SURGE AND LOAD SHARING CONTROLLERS. 6

    6.0 FIRE AND GAS CONTROLLERS................................................................... 7

    7.0 MACHINE MONITORING SYSTEM............................................................... 7

  • 8/3/2019 Control Philosoph1

    3/10

    PHILOSOPHY FOR

    CONTROL SYSTEMSPTT PUBLIC COMPANY LIMITED

    PHILOSOPHYPHC-0804.02-60.01

    PAGE 3 OF 10

    REV: D21.0 Overview

    This document describes the design philosophy for the development of the

    specification, detail design and system implementation for the control systems.

    The control systems in this document will be limited to the systems which are

    related to THE ONSHORE COMPRESSOR STATION 4 (OCS# 4). The

    control systems for the OCS# 4 shall include at least DCS, Safety

    Instrumented System, Unit Control Panel for compressor package, Master

    performance/Anti surge/load sharing controller and Fire&Gas and Machine

    Monitoring System.

    2.0 DCSThe DCS system shall consist of a network of Field Control Stations (FCS) to

    provide the core plant control and monitoring functions and the Human

    Machine Interface (HMI) workstations for operators to operate the facilities.

    The DCS shall be designed to execute all process controls which are not

    related to safety functions.

    PTT operators shall be able to initiate the command to start/stop the

    compressor trains, switch over the trains of equipment, change the set points

    for any process control and perform any other control functions via the DCS

    HMI workstations. The DCS shall also acquire the information from all utilities

    and equipment packages, such as motor driven compressor packages,

    electrical, instrument air, fire fighting, and machine management system etc.,

    in the facilities for monitoring and control. The control signals from DCS to

    other package equipments (and vice versa) shall be hard wired while the soft

    link shall be used for monitoring only.

    The DCS displays and console shall be ergonomically designed to allow PTT

    operator to fast access the desired information and to operate the facility

    without fatigue. The position of key switch, push button, alarm indication and

    communication systems in the DCS console shall also be orderly located for

    easy access.

    The DCS shall utilize a fully redundant Bus system, CPU, power supply,process and communication to the external system controllers with automatic

    bumpless switchover between the hot and standby controllers.

    The DCS FCS shall comprise of redundant CPUs, power supplies, Field control

    units (FCU) and communication controllers.

    All DCS Field Control Units (FCU) shall be foundation field bus for field

    transmitters and final elements directly connected to DCS.

    The arrangement for the Field Control Stations (FCS) shall prevent the

    common cause of inoperability for the equipment trains when the FCS/ itspart fail or are under maintenance. All field process devices of different

    compressor trains shall not be connected to the same FCS and the same

    principal shall be applied to the inlet scrubber trains and communication

    between DCS and the compressor control systems.

  • 8/3/2019 Control Philosoph1

    4/10

    PHILOSOPHY FOR

    CONTROL SYSTEMSPTT PUBLIC COMPANY LIMITED

    PHILOSOPHYPHC-0804.02-60.01

    PAGE 4 OF 10

    REV: D2All sequential process control, related to the operation of the compressor train

    and station, outside the motor driven compressor packages shall be performedby the DCS system. The DCS shall execute the program based on the input

    command from the related compressor unit control panel for the required

    actions from the field devices.

    The DCS system shall be designed to allow the data exchange with the

    existing PTT DCS, LNG terminal DCS and the existing PTT SCADA system.

    The Sequence Of Event (SOE) in the DCS shall be provided to handle all of

    the events related to filed devices connected to the DCS, SIS, other

    equipment package control and utility systems.

    The DCS shall be equipped with the Plant Information System (PIMS) to

    manage all related facility historical operating data for reporting and

    process/operation analysis. In addition the Plant Resource Management (PRM)

    shall be provided to collect data from all field devices for maintenance

    planning and other related activities. These two systems shall be equipped

    with the DCS package.

    The DCS shall function as a systems master clock for the all equipment

    package control systems. DCS shall receive the clock data from GPS and then

    synchronize with other systems once per day.

    The programming for the logic control in the DCS shall utilize function block.

    3.0 Safety Instrumented SystemThe Safety Instrument System (SIS) refers to the field input devices, logic

    solver and final element as defined by IEC 61511. It is imperative that the

    Safety Life Cycle (SLC) documents as required by IEC 61511 shall be

    implemented beginning from SLC analysis up to operation phases. All required

    functions and configuration related to the SIS shall be thoroughly defined in

    the Safety Requirement Specification (SRS) before the system implementation.

    In addition the SIL calculation and SIS equipment selection shall be based onMTTR of 8 hours and 1 year testing interval.

    The SIS shall execute only functions related to the safety for the facility

    operations such as over pressure protection, process shutdown, and emergency

    shutdown with/without blowdown etc. For the shutdown of the motor driven

    compressor packages due to process condition, the SIS shall send the hard wire

    signal to the required unit control panels (UCP) to execute theirs own shutdown

    logic. In the case that the trip of compressor come from its internal causes, the

    SIS shall receive the hard wire signal from UCPs to execute related process

    shutdown. The status of the final elements, if not required for the safety

    functions, shall be sent to the DCS only.

    All of the equipments used in the SIS shall be certified by TUV for the safety

    application. For logic solver, it shall be certified for SIL 3 application.

  • 8/3/2019 Control Philosoph1

    5/10

    PHILOSOPHY FOR

    CONTROL SYSTEMSPTT PUBLIC COMPANY LIMITED

    PHILOSOPHYPHC-0804.02-60.01

    PAGE 5 OF 10

    REV: D2All of the field input devices connected to the logic solver shall be 2oo3 voting

    configuration. All field input to the SIS logic solver shall be 4-20 mA HARTtransmitter. The DCS shall perform the transmitter integrity check function by

    comparing the value of three transmitters in the same loop and shall initiate

    alarm when the difference is higher than the preset value. The DCS shall also

    set the pre-trip alarm to alert the operators before the process condition reach

    the trip set point by using the values from the SIS transmitters.

    The SIS logic solver shall be based on 1oo2D configuration. It shall comprise of

    the network of Safety Control Stations (SCS). Each SCS shall comprise of

    redundant CPUs, power supplies, Safety Control Units (SCU) and

    communication controllers.

    The arrangement for the Safety Control Stations (SCS) shall prevent the

    common cause of inoperability for the equipment trains when the SCS/ its parts

    fail or are under maintenance. All field process devices of different compressor

    trains shall not be connected to the same SCS and the same principal shall be

    applied to the inlet scrubber trains.

    The Sequence Of Event (SOE) shall be fully integrated with that of DCS in order

    to allow the efficient analysis of the shutdown with related process information.

    The design of the SIS shall allow the on line testing for the system from the

    field inputs up to the final elements with less human intervention.

    4.0 Unit Control Panels for Motor Driven Compressor PackageThe compressor station control system shall comprise of the Unit Control

    Panels (UCP), anti surge and load sharing controllers.

    Each motor driven compressor shall be provided with its dedicated PLC based

    Unit Control Panel. This PLC shall be redundant in all aspects such as CPUs,

    power supplies, I/O cards etc.

    The UCP shall perform all required functions for the operation of compressorsuch as speed control, start/normal stop and emergency shut down. The UCP

    shall receive hard wire signals from the DCS for start/normal stop and the SIS

    for emergency shutdown due to process condition. When the compressor

    package trips by its own condition, the UCP shall send the hard wire signal to

    the SIS to execute the process shutdown functions outside the compressor

    package. The UCP shall also send the operating data to the DCS for monitoring

    via soft link.

    The UCP shall send hard wire command to the related switch gears/MCCs for

    the operation of lube oil pumps, lube oil coolers, and any other auxiliary devices

    in both normal and emergency case. For the emergency case, the UCP shallsend command to the emergency shut down relays in the related

    switchgears/MCCs.

  • 8/3/2019 Control Philosoph1

    6/10

    PHILOSOPHY FOR

    CONTROL SYSTEMSPTT PUBLIC COMPANY LIMITED

    PHILOSOPHYPHC-0804.02-60.01

    PAGE 6 OF 10

    REV: D2The field transmitters connected to these systems shall be 4-20 mA HART and

    the information for each transmitter shall be sent to the PRM.The UCP shall have its dedicated vibration monitoring systems. All data from

    these systems shall be transferred to the Machine Monitoring System Server.

    The HMIs shall be provided locally at the UCP and remotely at the DCS

    consoles. These two HMI shall have similarly functionalities. The remote and

    local HMI shall be equipped with the database server to store all historical

    operating parameter for the compressor packages.

    5.0 Master Performance, Anti surge and Load Sharing Controllers

    The master performance, anti surge and load sharing controllers shall beseparate system from the PLC used for the UCP of the compressor train. These

    controllers shall be the dedicated systems to serve the desired purposes and

    mounted into the unit control panels

    The master performance controller shall receive the hard wire process set point

    from the DCS, and input from the load sharing/ anti surge controllers, process

    the inputs and send the command to the related controllers.

    The anti surge and load sharing controllers shall receive the speed , process

    data and other required compressor status from the UCP of operated

    compressors to perform the anti surge and load sharing functions. The antisurge controller shall also be able to receive the hard wire command from the

    DCS for manual operations of the anti surge control valve with anti surge

    override function.

    The anti surge and load sharing controllers shall be equipped with the fall back

    strategy to manage the failure of their input signals in order to minimize the

    unnecessary shutdown from this cause.

    As same as the UCP, these controllers shall send all operating data to the DCS

    for monitoring via soft link in order to allow the DCS HMI workstation to show

    the same information and displays as those on the local monitors for thecompressor station control system.

    The master performance, anti surge and load sharing controllers shall be fully

    redundant in all aspects of the system with bumpless transfer between the hot

    and standby units.

    The field transmitters connected to these systems will be 4-20 mA HART and

    the information for each transmitter shall be sent to the PRM.

    The remote HMI workstation for these controllers shall be provided in the DCS

    console. This remote HMI workstation shall display all related process data,alarm and event log and healthy of the systems. The remote HMI workstation

    shall also be equipped with the engineering and maintenance software for these

    controllers.

  • 8/3/2019 Control Philosoph1

    7/10

    PHILOSOPHY FOR

    CONTROL SYSTEMSPTT PUBLIC COMPANY LIMITED

    PHILOSOPHYPHC-0804.02-60.01

    PAGE 7 OF 10

    REV: D26.0 Fire and Gas Controllers

    The fire and gas controllers shall be separated from each other and mounted in

    the separate control panel.

    The fire controller panels shall include the master fire controller panel and

    dedicated fire controller panel for each building. The fire controller panel for

    each building shall receive the signal from the detectors, perform voting

    function and actuated the fire suppression system. The master fire controller

    panel shall handle the detectors and manual call points in the field. The master

    fire control panel shall also acquire the information from the fire controller panel

    in each building. All information related to the system shall be displayed at the

    local and remote HMI workstation.

    The gas controller panel shall include at least controllers, local and remote HMI

    workstations, and push button for the required functions. The gas controller

    panel shall handle the gas detectors and the fire suppression systems in the

    field/process areas.

    The gas control panel shall be equipped with the dedicated push buttons for

    each fire suppression systems, such as fire monitors and deluges, in the field.

    The operator shall be able to initiate the action of these devices via these push

    buttons. In addition, the reset and horn interrupt push buttons shall also be

    mounted on this panel

    The fire and gas systems shall utilize the common remote HMI installed in the

    DCS control. The remote and local HMIs shall contain the graphical displays for

    all areas. The graphical displays design shall be in hierarchy from the overview

    to the detail graphical displays. The graphical display shall clearly show the

    location of the detectors and fire suppression system. The detectors and fire

    suppression systems shall be flashed out on the related displays when the

    abnormal situation is detected or the fire suppression systems are actuated.

    The local HMI workstations at the master fire and gas controller panels shall be

    equipped with the engineering and maintenance software for each system.

    7.0 Machine Monitoring System

    The Machine Monitoring System shall include server, vibration controllers and

    detectors/sensors. The server shall acquire the data from vibration controllers

    included those provided by package vendors and store for further vibration

    analysis. The server shall be equipped with the software to allow PTT

    maintenance personnel to analyze these vibration data in all aspects.

    The vibration controllers shall receive the data from vibration detectors/ sensors

    and transfer them to the DCS for monitoring via soft link. In case that the

    controller detects the vibration of connected equipments, it shall send the hardwire signal to SIS to shutdown the related process units.

    All alarm from the vibration controllers shall also be transferred to the DCS.

  • 8/3/2019 Control Philosoph1

    8/10

    PHILOSOPHY FOR

    CONTROL SYSTEMSPTT PUBLIC COMPANY LIMITED

    PHILOSOPHYPHC-0804.02-60.01

    PAGE 8 OF 10

    REV: D2For the purposes of machine condition monitoring, machines are classified into

    four categories as shown in the following table and the system shall designedand provided accordingly.

    TYPE OF MACHINE ONLINE OFFLINE

    CONTINOUS NON

    CONTINOUS

    WITH

    PROTECTION

    (Portable)

    CRITICAL MACHINE YES YES

    Compressors

    Generators

    ELECTRIC MOTORS WITH

    JOURNAL BEARINGS

    GEARBOXES

    VOITH VARECON COUPLINGS

    Machines With Journal Bearings

    ESSENTIAL MACHINE1 YES YES YES

    Fans

    Fan Motor

    ESSENTIAL MACHINE2 YES NO YES

    OTHER PROCESS MACHINES

    UTILITY MACHINES >= to15KW

    SUBSYSTEMS OF CRITICAL

    MACHINERY

    NON ESSENTIAL MACHINE NO NO NO YES

    UTILITY MACHINES < 15KW

    Table 2. Types of Machines

  • 8/3/2019 Control Philosoph1

    9/10

    PHILOSOPHY FOR

    CONTROL SYSTEMSPTT PUBLIC COMPANY LIMITED

    PHILOSOPHYPHC-0804.02-60.01

    PAGE 9 OF 10

    REV: D2Transducer arrangements per type of machine are indicated in the following table

    TYPE OF MACHINE TRANSDUCER ARRANGEMENT

    CRITICAL MACHINES

    All Proximity probes 2-X, 2-Y, for each radial bearing, 2-Z for

    each thrust bearing and key phasor. Three accelerometer

    measuring point per casing.

    ESSENTIAL MACHINE 1

    Air coolers 1 accelerometer for the fan bearing, 1 accelerometer for

    the motor casing

    ESSENTIAL MACHINE 2 Accelerometers, 1-X for the motor casing, 1-X for the

    pump casing. Where the machine is a "between bearings"

    design an additional probe shall be provided on the driven

    machine.

    NON ESSENTIAL MACHINES No permanent probes.

    Table 3. Transducer arrangements

    Critical Machines

    The contractor shall provide the Bentley Nevada 3500 rack system segregated

    on a machine by machine basis, to interface to field transducer. The Bently

    Nevada system shall interface to the machinery control system (local PLC, DCS

    or SIS) to provide the required indication, alarm and trip functions. If theBentley Nevada system is connected directly to a local machinery control PLC

    then all vibration and monitoring signals shall be repeated to the DCS for

    indication.

    The Bently Nevada 3500 system shall be interfaced via Bently Nevada TDXnet

    modules to form the machine monitoring network.

    The TDXnet modules shall be linked to the DCS via dual redundant serial cable

    to give the necessary indication.

    Each of the TDXnet modules shall be networked using a 10 Base T hub/switch

    connection.

  • 8/3/2019 Control Philosoph1

    10/10

    PHILOSOPHY FOR

    CONTROL SYSTEMSPTT PUBLIC COMPANY LIMITED

    PHILOSOPHYPHC-0804.02-60.01

    PAGE 10 OF 10

    REV: D2 Essential Machines category 1

    These machines shall be monitored continuously by accelerometers connected

    to a Bently-Nevada 3500 system. The 3500 system shall send trip signals to

    the SIS system for machinery protection purposes and to the System 1 server

    for machinery analysis. Transducers shall be installed to monitor the fan bearing

    housing and the motor casing vibration. Additional data may be collected using

    a Bently-Nevada Snapshot portable data collection and analysis unit.

    Essential Machines category 2

    Each machine in this category shall be fitted with permanent vibration

    transducers to monitor pump and motor casing vibration. These transducers

    shall be connected to the SPA cards on the System 1 server in a multi-drop

    configuration. Additional data may be collected using a Bently-Nevada

    Snapshot portable data collection and analysis unit.

    Non Essential Machines

    Vibration measurements shall be taken by a Bently-Nevada Snapshot portable

    data collection and analysis unit. This data shall be downloaded to the System

    1 server for machinery analysis purposes.

    The machinery monitoring network shall be connected to the ESP DCS ethernet

    network via a network switch to allow data to be transferred between the twosystems.

    The contractor shall provide a Bently-Nevada System 1 data acquisition and

    management system located at instrument rack room to provide full analysis of

    all machinery data. This system shall be provided with the following modules:

    Data Acquisition, Display and Configuration, Database (SQL Server) DDE

    Exporter/Importer, OLE Automation Exporter.