Control de Compresores

Embed Size (px)

Citation preview

  • 7/30/2019 Control de Compresores

    1/25

    MULTIPLE COMPRESSOR CONTROLLER USERS MANUAL

    Danfoss Turbocor Compressors Inc. ECD-00014-U-R09

    January 2008

    Multiple Compressor Controller

    Featuring ModBus Communications

  • 7/30/2019 Control de Compresores

    2/25

    Danfoss Turbocor Compressors Inc.

    ECD-00014-U-R09

    Proprietary Notice

    This publication contains information proprietary and confidential to Danfoss Turbocor Compressors Inc. (DTC). Any

    reproduction, disclosure or unauthorized use of this publication is expressly prohibited without written approval from DTC.

    DTC reserves the right to make changes without notice in product or component design as warranted by evolution in user

    needs or progress in engineering or manufacturing technology.

    DTC has exercised its best efforts to ensure that the information contained in this manual is correct. However, no warranty of

    reliability or accuracy is given with respect to the information and DTC shall not be responsible or liable for the correctness

    or suitability of the information or for any error or omission. If you encounter any difficulty in using this manual, please

    forward your query to Danfoss Turbocor Compressors Inc. or its authorized sales agent.

    All brand names and product names used in this manual are trademarks, registered trademarks, or trade names of their

    respective holders.

    For product support issues, contact:

    Product Support

    [email protected]

    Danfoss Turbocor Compressors Inc.

    1769 E. Paul Dirac Drive

    Tallahassee, FL 32310

    USA

    Telephone: (850) 504-4800

    Fax: (850) 575-2126

    www.turbocor.com

  • 7/30/2019 Control de Compresores

    3/25

    Contents

    Danfoss Turbocor Compressors Inc. iECD-00014-U-R09

    1 Multiple Compressor Controller - Overview 1Introduction 1Application 1

    Display Features 1Communication Features 1

    Environment Constraints 1Ordering Details 1

    2 Multiple Compressor Controller - Interface 2Interface Introduction 2

    Hardware I/O Interface Controls 2Controller Interlocks 2

    Communications Interfaces 2Carel Modbus Gateway 2BMS Network Modbus Protocol 2

    3 Multiple Compressor Controller - Functionality 3

    General Control Strategy 3Application Setup Types 3Freeze Control 3Parallel Control Mode 3Staged Control Mode 4

    Staged Control Considerations 4Minimum Off Timers 4

    Alarms 4

    4 Multiple Compressor Controller - Operating Procedures 5Introduction 5PLC Control Panel Operations 5

    Alarms 5General Alarms 5System Alarms 5

    Appendix A Carel Control Panel Display 6PLC Overview 6

    Selection Screens 6Interlock Messages 8

    Interlock Message options 8Viewing Circuits 8

    Circuit Temperature Status 8

    Circuit Pressure Status 9Condenser Fans Status 9Compressor Status 9

    System Setup 10Analog Input Configuration 10Compressor Configuration 11Compressor Configuration 11

    Configuration Screens 12Evaporator Configuration Screens 12

    http://ecd-00014u-r08-mcc-operation-overview.pdf/http://ecd-00014u-r08-mcc-operation-overview.pdf/http://ecd-00014u-r08-mcc-operation-overview.pdf/http://ecd-00014u-r08-mcc-operation-overview.pdf/http://ecd-00014u-r08-mcc-operation-overview.pdf/http://ecd-00014u-r08-mcc-operation-overview.pdf/http://ecd-00014u-r08-mcc-operation-overview.pdf/http://ecd-00014u-r08-mcc-userinterface.pdf/http://ecd-00014u-r08-mcc-userinterface.pdf/http://ecd-00014u-r08-mcc-userinterface.pdf/http://ecd-00014u-r08-mcc-userinterface.pdf/http://ecd-00014u-r08-mcc-userinterface.pdf/http://ecd-00014u-r08-mcc-userinterface.pdf/http://ecd-00014u-r08-mcc-userinterface.pdf/http://ecd-00014u-r08-mcc-functionality.pdf/http://ecd-00014u-r08-mcc-functionality.pdf/http://ecd-00014u-r08-mcc-functionality.pdf/http://ecd-00014u-r08-mcc-functionality.pdf/http://ecd-00014u-r08-mcc-functionality.pdf/http://ecd-00014u-r08-mcc-functionality.pdf/http://ecd-00014u-r08-mcc-functionality.pdf/http://ecd-00014u-r08-mcc-functionality.pdf/http://ecd-00014u-r08-mcc-functionality.pdf/http://ecd-00014u-r08-mcc-procedures.pdf/http://ecd-00014u-r08-mcc-procedures.pdf/http://ecd-00014u-r08-mcc-procedures.pdf/http://ecd-00014u-r08-mcc-procedures.pdf/http://ecd-00014u-r08-mcc-procedures.pdf/http://ecd-00014u-r08-mcc-procedures.pdf/http://ecd-00014u-r08-mcc-procedures.pdf/http://ecd-00014u-r08-mcc-procedures.pdf/http://ecd-00014u-r08-mcc-procedures.pdf/http://ecd-00014u-r08-mcc-procedures.pdf/http://ecd-00014u-r08-mcc-procedures.pdf/http://ecd-00014u-r08-mcc-procedures.pdf/http://ecd-00014u-r08-mcc-functionality.pdf/http://ecd-00014u-r08-mcc-functionality.pdf/http://ecd-00014u-r08-mcc-functionality.pdf/http://ecd-00014u-r08-mcc-functionality.pdf/http://ecd-00014u-r08-mcc-functionality.pdf/http://ecd-00014u-r08-mcc-functionality.pdf/http://ecd-00014u-r08-mcc-functionality.pdf/http://ecd-00014u-r08-mcc-functionality.pdf/http://ecd-00014u-r08-mcc-functionality.pdf/http://ecd-00014u-r08-mcc-userinterface.pdf/http://ecd-00014u-r08-mcc-userinterface.pdf/http://ecd-00014u-r08-mcc-userinterface.pdf/http://ecd-00014u-r08-mcc-userinterface.pdf/http://ecd-00014u-r08-mcc-userinterface.pdf/http://ecd-00014u-r08-mcc-userinterface.pdf/http://ecd-00014u-r08-mcc-userinterface.pdf/http://ecd-00014u-r08-mcc-operation-overview.pdf/http://ecd-00014u-r08-mcc-operation-overview.pdf/http://ecd-00014u-r08-mcc-operation-overview.pdf/http://ecd-00014u-r08-mcc-operation-overview.pdf/http://ecd-00014u-r08-mcc-operation-overview.pdf/http://ecd-00014u-r08-mcc-operation-overview.pdf/http://ecd-00014u-r08-mcc-operation-overview.pdf/
  • 7/30/2019 Control de Compresores

    4/25

    Contents

    Danfoss Turbocor Compressors Inc. iiECD-00014-U-R09

    Controller Stage Settings 14Condenser Configuration 14Modbus Settings 15Miscellaneous Configuration Screens 16

    Compressor Circuit IDs 16Appendix B Drawings 18

    Appendix C Inputs/Outputs 19

  • 7/30/2019 Control de Compresores

    5/25

    Multiple Compressor Controller - Overview

    Danfoss Turbocor Compressors Inc. 1

    ECD-00014-U-R09

    1 Multiple Compressor Controller - Overview

    1.1 Introduction

    This manual describes the functionality and operation

    of the Multiple Compressor Controller (MCC). The

    controller features generic software that is

    configurable for use with either the basic I/O or the

    expanded I/O hardware platforms. In its expanded

    form, the controller can accommodate up to six

    compressors.

    NOTE

    While the controller algorithm is designed to

    maintain desired set point with minimal varia-

    tions, it could swing depending on the configura-

    tion settings and the system characteristics.

    1.2 Application

    The MCC performs the following primary functions:

    Controls the entire chiller/system and some auxiliary

    devices

    Performs monitoring, analysis and fault display.

    1.2.1 Display Features

    The controller features a remote semi-graphic display

    with the ability to:

    View the compressor status and detailed information

    View the input and output status

    View and adjust set points

    View and adjust timers where applicable

    Acknowledge and reset warnings and alarms

    View the alarm history

    Configure the pre-programmed software to suit the

    specific application

    Enable and/or disable inputs and/or outputs that are

    optional

    1.2.2 Communication Features

    The MCC communicates with the compressors via

    ModBus, which enables it to read various parameters

    and control the compressors by writing to certain

    parameters. It can act as the centralized controller for

    systems with one to six compressors.

    1.2.3 Environmental Constraints

    The following information provides recommended

    environmental conditions.

    1.3 Ordering Details

    The following information provides the ordering

    details for this controller.

    Environment Range

    Storage -20C to 60C*

    Operation -10C to 60C*

    * Relative humidity less than 80%, non-condensing

    Table 1 Temperature Range

    Description Details

    Part Description Retrofit Controller Kit

    Part Number 111047

    Notes Kit includes Turbocor Specific

    software, temperature sensors,

    remote semi-graphic screen,

    connector kit, and 1.5 meter (5 feet)

    RJ-12 communication cable.

    Table 2 Ordering Details

  • 7/30/2019 Control de Compresores

    6/25

    Multiple Compressor Controller - Interface

    Danfoss Turbocor Compressors Inc. 2

    ECD-00014-U-R09

    2 Multiple Compressor Controller - Interface

    2.1 Interface Introduction

    The latest model of the Carel pCO series is used, the

    Pco3, which enables very fast communication with the

    compressor by means of the serial port over ModBus.

    2.1.1 Hardware I/O Interface Controls

    Each TT300/TT400 compressor is equipped with the

    following I/O points for controls and interfacing:

    Interlock (voltage-free contact), compressor start/

    stop, 1 * DI

    Numerous parameters including demand, which is

    an input parameter modulating the compressor

    capacity between 0 - 100%, 1 * RS485 Port.

    (1) Status (SPD contact), generic compressor faultstatus, 1* DO

    (2) Compressor run status, based on user-selectable

    motor RPM, 1*DO

    For a detailed list and typical wiring of all I/Os

    available on the Turbocor compressor, refer to

    Drawings (see APPENDIX B). Also refer to pCO3

    manual, document no. 050003290, which can be

    found at http://carelusa.com/pco3_literature.htm.

    2.1.2 Controller Interlocks

    The following inputs are connected to the Multiple

    Compressor Controller:

    Remote on/off switch

    Evaporator flow switch

    Condenser water flow switch (water-cooled unit

    only)

    Cooling call

    All of these inputs enable/disable the controller. Refer

    to electrical schematics for input configuration.

    NOTE

    All other inputs that are not used must be bridged.

    To ensure protection against system freeze-ups or

    other major failures, at least one external safety

    interlock must be connected to the Multiple

    Compressor Controller at all times. All external

    safety and system interlocks can be wired in

    series, if required.

    2.2 Communications Interfaces

    The Multiple Compressor Controller (MCC) supports

    upstream communications to a Building Management

    System (BMS) through a Carel Modbus protocol.

    2.2.1 Carel Modbus Gateway

    The MCC Carel Modbus requires a relevant gateway

    card in order to establish a communications link to theBMS Network, a gateway interface card for the MCC

    Carel Modbus is available from Carel company,

    contact Carel technical support (www.carel.com).

    NOTE

    The purchase and installation of a Carel Modbus

    interface card by a third party company to enable

    communications to a BMS Network may be

    required.

    2.2.2 BMS Network Modbus Protocol

    For BMS Networks connected to the MCC Carel

    Modbus requires the BMS network can communicate

    via Modbus protocol.

    For BMS Networks utilizing Modbus Protocol, no

    protocol conversion is required.

    For BMS Networks connected to the MCC Carel

    Modbus via a non Modbus protocol (such as LON or

    BacNet) an interface card is required to convert

    communications from the MCC Carel Modbus

    protocol to the BMS communications protocol.

    NOTE

    The purchase and installation of a protocol con-

    version interface card by a third party company

    may be required. See your BMS administrator for

    interface card parameters and your BMS supplier

    for the appropriate interface card.

  • 7/30/2019 Control de Compresores

    7/25

    Multiple Compressor Controller - Functionality

    Danfoss Turbocor Compressors Inc. 3

    ECD-00014-U-R09

    3 Multiple Compressor Controller - Functionality

    3.1 General Control Strategy

    The Multiple Compressor Controller (MCC) is

    configurable to control either leaving or entering

    chilled-water temperature, depending on the

    application requirements.

    In principle, the demand to the compressor(s) is

    determined by the Demand Generator*. The output of

    the Demand Generator is based on the difference

    between the setpoint and the controlled value. In

    addition, the control strategy is based on system

    demand (Low Load Control). When the main

    application is controlling leaving chilled water

    temperature, and the entering chilled water

    temperature drops below a certain value, the setpoint

    is shifted upwards to compensate for a lower load.Similarly, when the main application is controlling

    entering chilled water temperature, and the leaving

    chilled water temperature drops below a certain value,

    the setpoint is shifted upwards to compensate for a

    lower load.

    * The Demand Generator is a proportional integral (PI) controller based

    on the SSTEP2 macro block from Carel. Proportional band and

    integral time adjustments can be made through the Band, Update, and

    Max. Change parameters.

    NOTE

    While the controller algorithm is designed tomaintain desired set point with minimal varia-

    tions, it could swing depending on the configura-

    tion settings and the system characteristics.

    3.2 Application Setup Types

    The software setup is largely generic. Sensors can be

    connected for entering and leaving chilled water

    temperatures in all applications.

    When the system is set up for a water-cooled chiller

    application, additional sensors can be connected to

    display the entering and leaving condenser watertemperatures.

    In an air-cooled application, there is an option to

    connect an outside air temperature sensor.

    The appropriate screens are activated according to the

    specific set-up. There are also two options for

    condenser fan switching: one is where the fans are

    switched locally (in steps) with pressure switches

    based on head-pressure and the other is where a head-

    pressure transducer is connected to the controller, and

    the fans are switched by the controller in up to three

    steps per compressor.

    3.3 Freeze Control

    Regardless of using leaving or entering water control,

    when the leaving chilled water temperature drops

    below the leaving chilled water freeze point, the

    demand drops to zero and an alarm is generated. The

    compressors can only start again after this alarm is

    reset, and when the leaving chilled water is above the

    setpoint.

    Freeze control is implemented by monitoring the

    leaving water temperature at the MCC. The leavingwater temperature can be monitored at either the

    temperature sensor input at the MCC (B2 default) or

    via the Modbus from any compressor. As an additional

    safeguard, interlocks are used to signal the MCC when

    there is insufficient pump flow or condenser leaving

    water flow. The interlock circuit is connected to a

    digital input (ID1-14) of the MCC.

    3.4 Parallel Control Mode

    With parallel control, all operating compressors are

    shut down. After their IGVs are reset, they are

    restarted along with an additional compressor that waspreviously off. The compressors ramp up together

    with the load equally distributed across all of them.

  • 7/30/2019 Control de Compresores

    8/25

    Multiple Compressor Controller - Functionality

    Danfoss Turbocor Compressors Inc. 4

    ECD-00014-U-R09

    3.5 Staged Control Mode

    In staged control, the running compressors are

    unloaded until they reach a specific pressure ratio, as

    defined in the user interface. An additional

    compressor that was previously off is started. When

    the compressor attains the same pressure ratio as the

    other compressors, the compressors ramp up together

    with the load equally distributed across all of them.

    This mode can give better capacity control of the

    system, as it harnesses the ability for a single

    compressor to be operating under really low load

    conditions, and you are not restricted by the minimum

    point of all compressors combined.

    The 'System demand' (the output from the Demand

    Generator) varies from 0-100 percent based on the

    difference between the setpoint and the controlled

    value (e.g. ChW temperature).

    As the system demand increases, the demand to the

    first compressor also increases. Once the compressor

    is no longer able to meet the system demand within a

    certain time period, the controller will begin to stage

    on the second compressor. This will involve the

    running compressor unloading to facilitate the

    optimum system conditions needed to start the next

    compressor. This process will occur for each

    subsequent compressor that is in the system.

    As the system demand decreases from 100 percent, thecontroller will unload all the compressors in parallel

    until the system demand has dropped below the

    minimum combined capacity of the running

    compressors. At this point, the controller will begin to

    shut down compressors (one at a time), and then allow

    the remaining compressors to increase their capacity

    as needed to match the system demand.

    3.5.1 Staged Control Considerations

    When one compressor is running at a demand below

    the requested demand from the controller, the secondone will start. Theoretically, after they have been

    started, both compressors will then approximately

    operate on half of the initial capacity. The demand to

    the initial compressor(s) will drop (e.g. from 100

    percent to 50 percent), while the second will be started

    with a 50-percent demand.

    The bandwidth between the actual demand and the

    requested demand on a compressor can be configured

    by the user to allow more or less time for system

    stabilization in the staging sequence of the

    compressors.

    It is important to recognize, however, that thecompression ratio of the system needs to reduce to an

    acceptable level to allow the efficient and safe starting

    of the second or subsequent compressors. This time

    interval may vary depending on the conditions of the

    system.

    The hysteresis for switching one, two or three (groups

    of) compressor(s) in this example is set to 5 percent.

    However, it is a parameter that can be set via Level 2

    user access for tuning purposes.

    At start-up, the integral term of the Demand Generator

    is switched off for 90 seconds to prevent overshootbecause the compressors themselves have a ramp-up

    time.

    3.5.2 Minimum Off Timers

    Minimum Off Time is the time the compressor will

    stay off after the demand to that compressor has

    reached zero. The Minimum Off Timers are to prevent

    any unwanted switching of compressors while the

    compressors are ramping up to satisfy an increasing

    demand.

    For staged control, these timers operate on theindividual demands to the compressors.

    For parallel control, the timers operate on the

    combined demand.

    3.6 Alarms

    Each compressor can indicate a fault via Modbus

    communication. If a compressor fails, the demand to

    that compressor will go to zero and a generic fault will

    appear on the controller display. After the fault on the

    compressor has been resolved, the fault message onthe controller can be reset.

  • 7/30/2019 Control de Compresores

    9/25

    Multiple Compressor Controller Operating Procedures

    Danfoss Turbocor Compressors Inc. 5

    ECD-00014U-R09

    4 Multiple Compressor Controller Operating Procedures

    4.1 Introduction

    The controller is designed to run the compressor at

    various motor kW conditions. The setpoint is set at the

    PLC control panel, which also controls and monitors

    other functions in the chiller and acts as an interface

    between the chiller and the compressor. Alarms and

    compressor status can be read from the PLC screen.

    Refer to PLC Control Panel (see Figure 1).

    Figure 1 PLC Control Panel

    4.2 PLC Control Panel Operations

    Starting the PLC Control Panel

    1. Ensure all interlocks are closed.

    2. Press Esc until the main menu appears.

    Figure 2 Main Menu Screen3. Using the button, select SYSTEM ON/OFF.

    4. Press the button to view the System Status screen.

    Press the button again to select the compressor on/

    off option.

    5. Press the or button to switch the compressors

    on or off. Press the button. If the compressor is

    switched on, it will ramp up according to the system

    demand to maintain the setpoint; otherwise, it will shut

    down.

    6. Press Esc to return to the main menu.

    Monitoring the Conditions

    1. Press Esc until the main menu appears.

    2. Select SYSTEM STATUS and press the button. System status such as water temperature

    and compressor running time can be viewed.

    Figure 3 System Start-Up Screen

    4.3 Alarms

    4.3.1 General Alarms

    The PLC monitors the status of the temperature inputs.

    Disconnecting any one of the three temperature

    sensors trips an alarm and the unit will stop.

    4.3.2 System Alarms

    The following alarms can be present:

    Danfoss_Turbocor_Inc.Carel_ControllerVer.0.0.110

    Compressor

    faultGenerated by the compressor if

    there is an internal alarm.

    Pump failure The pump is not running due to a

    thermal overload, or it is not

    switched on.

    Condenserwater flow

    too low

    The condenser water flow switch

    detects a low-flow condition.

    Compressornot powered

    on

    The compressor is not running due

    to a fault, or it is not switched on.

    High

    condenser

    water

    temperature

    This alarm is triggered when the

    condenser water temperature sensor

    registers a temperature above its

    trip setpoint (40C).

    Table 3 System Alarms

    Danfoss_Turbocor_Inc.Carel_ControllerVer.0.0.110

  • 7/30/2019 Control de Compresores

    10/25

    Danfoss Turbocor Compressors Inc. 6

    ECD-00014-U-R09

    APPENDIX A Carel Control Panel Display

    A.1 PLC Overview

    This section describes the various screens that are

    available on the PLC control panel display.

    A.1.1 Selection Screens

    Monitoring screens allow you to view the system data

    while the system is running.

    Navigating the Start-Up Screen

    Upon initial power-up, the start-up screen will appear

    (see Figure A-1).

    Figure A-1 Start-Up Screen

    1. Record Carel Controller version number (see

    Figure A-1).

    2. Simultaneously press alarm button and

    button and hold for approximately four seconds.

    3. A blinking cursor will appear (see Figure A-2).

    Use arrows to choose System Info and press

    button.

    Figure A-2 Controller Information Screen

    4. Ensure bios is above 4.00 (see Figure A-3).

    5. Record BOOT and BIOS info. When finished,

    press Esc. Record Carel cont VER 0.0.110.

    6. Press Esc button to return to start-up menu.

    Figure A-3 System Info Screen

    7. To verify if controller is set up to log data, performstep 2 again. Use the up and down arrow keys to

    move > symbol in front of LOG DATA (see

    Figure A-2), then press .

    8. If there is no log data, the following screen

    appears (see Figure A-4):

    Figure A-4 No Log Data Screen

    9. Selecting OTHER INFORMATION brings up

    the ID number (see Figure A-5).

    Figure A-5 Other Information Screen

    Danfoss_Turbocor_Inc.Carel_Controller

    Ver.0.0.110

  • 7/30/2019 Control de Compresores

    11/25

    Danfoss Turbocor Compressors Inc. 7

    ECD-00014-U-R09

    10. Press the Prg button. To System Setup will

    display (see Figure A-6).

    Figure A-6 System Info Screen

    11. Press the Esc button to go to System Info. To

    System Monitor will display.

    Navigating the System ConfigurationScreen

    Figure A-7 System Configuration Screen12. Press the button To Continue Setup, to will

    display, System Configuration Menu (see Figure

    A-18).

    13. Press the Esc button to View System will

    display, System Info Screen (see Figure A-8).

    Navigating the System Info Screen Screen

    Figure A-8 System Info Screen14. Press the '' button to go To System Setup, will

    display, System Configuration Screen (see

    Figure A-7).

    15. Press the Prg button to Go To System Info,

    will display either:

    16. an interlock status screen will display, Interlock

    Status Messages (see Figure A-9), or

    17. an interlock status screen will display, View

    Circuit # Selector (see Figure A-10), or

    The following are abbreviations used in displays.

    System_Info:

    System_Configuration:

    _____To_Continue_Setup--->

  • 7/30/2019 Control de Compresores

    12/25

    Danfoss Turbocor Compressors Inc. 8

    ECD-00014-U-R09

    A.2 Interlock Messages

    The following screen is a message, telling that an

    Interlock to the Carel controller is open.

    Figure A-9 Interlock Status Messages

    The following table details the screens fields.

    A.2.1 Interlock Message options

    Close the Interlock Item, through systemconfiguration.

    Press the '' button to access the View Circuit #Selector (see Figure A-10).

    Press the Prg button to access the SystemConfiguration Screen (see Figure A-7).

    Press the Esc button to access the SystemInfo Screen (see Figure A-8).

    A.3 Viewing Circuits

    The following screen provides the option to choose

    which circuit to monitor. For Typical I/O Wiring for

    Multi-Compressor Controller (see Figure B-1).

    Figure A-10 View Circuit # Selector

    Selecting a View Circuit

    1. Scroll using '' or '' buttons to select a circuit to

    monitor.

    View Circuit # (Circuits 1-6)2. Press button to view circuit.

    3. View Circuit Screen Details (see details by type)

    Circuit # Readings (see Figure A-11)

    Circuit Pressure Readings (see Figure A-12)

    Condenser Fans Voltage (see Figure A-13)

    Condenser Fans Setpoints (see Figure A-14)

    Compressor # Status (see Figure A-15)

    A.3.1 Circuit Temperature Status

    This screen represents the current status of the system.

    Interlock

    Open The screen will appear only if the

    interlock is open. Interlock is open

    when the Interlock input has 24Volts present.

    The screen would not appear, when

    the interlock is closed.Remote

    _On/OffSee Miscellaneous System (see Figure

    A-33) "Remote On/Off ch#" to check

    which channel is set as the remote On/

    Off channel.

    Evaporator

    _#

    Indicates that interlock on evaporator

    side, circuit #, is opened. See

    Evaporator Control (values represent

    generic defaults) (see Figure A-25) to

    check channel settings.

    Condenser

    _#

    Indicates that interlock on condenser,

    circuit #, is opened. See Condenser #

    Interlock Status (see Figure A-31) to

    check channel settings.

    Interlock_Open!

    Remote_On/Offopen!

    Interlock_open!

    Evaporator_#interlock_open!

    Interlock_open!

    Condenser_#interlock_open!

    _>View_Circuit_1