Upload
others
View
1
Download
0
Embed Size (px)
Citation preview
Upgrade/Renovate/Expand Research Labs (Biosafety Lab Renovation – Health Sciences Research Building) University of Kentucky
Project Number 2573.0
Consultant Submittal Guidelines & Executive Summary Page 1 of 7
Consultant Submittal Guidelines for the
Upgrade/Renovate/Expand Research Labs (Biosafety Lab Renovation – Health Sciences Research Building) for the
UNIVERSITY OF KENTUCKY PROJECT NO. 2570.0 PROJECT SCOPE: $1,500,000
The University of Kentucky is requesting the services of an ARCHITECTURAL/ENGINEERING TEAM to provide design services for the Upgrade/Renovate/Expand Research Labs (Biosafety Lab Renovation – Health Science Research Building), located in Lexington, Kentucky. This solicitation seeks a team that will provide and be responsible for architectural, M/E/P, structural, and specialty lab (as needed) design services. The team will also be responsible for bidding and construction administration services required to complete the project.
The team should be led by a local or regional architectural firm that will serve as prime architect having the responsibilities of the architect of record and bear the responsibility to schedule the design process; coordinate the early stages of the design; oversee the production of drawings and bid documents; provide bid phase services; obtain plan approvals from AHJ; provide construction administration and all other day to day management and oversight of the design and construction process.
The team should include additional sub consultants that are required to produce comprehensive design and bidding documents, effective construction phase administration, and a final product of the highest standard. A contract will be negotiated for the full design, bidding and construction services. In addition, an allowance will be negotiated as a reimbursable service to provide Independent Testing Services (to include special inspections), air flow and balancing study, and a security and hardware consultant. The consultant shall be responsible for review of all reports and for writing any final acceptance letters as may be required by authorities having jurisdiction.
Hereinafter are listed the criteria, including the scoring weights, by which each firm’s submittal will be evaluated. Bearing this in mind, each firm's submittal should clearly and thoroughly address all criteria to allow objective evaluation of the firm's previous experience and capability to successfully complete this project. All submittals should be in an 8 1/2" x 11" bound format and GIVE SPECIFIC PROJECT EXAMPLES, including photographs, drawings, resumes, programs, etc. to properly substantiate the firm as well as individual experience in all categories.
The submittal should include a BRIEF EXECUTIVE SUMMARY (maximum of 3 pages) as a cover to the submittal, as well as a response to each of the evaluation criterion (maximum of one page per criterion). The SF 330 should be provided in support of the Executive summary and criteria response. BE SURE TO
Upgrade/Renovate/Expand Research Labs (Biosafety Lab Renovation – Health Sciences Research Building) University of Kentucky
Project Number 2573.0
Consultant Submittal Guidelines & Executive Summary Page 2 of 7
SPECIFY WHO THE PROJECT MANAGER WILL BE IN THE EXECUTIVE SUMMARY. The Project Manager is defined as the consulting team member who will act as the Design Team’s primary point of contact for the duration of the project with the University’s designated Project Manager to coordinate and manage design and construction administration services and/or activities.
The consultant should focus their submittal on the issues and needs that are unique to this project. Design Teams expressing interest in this project should demonstrate what special experience and/or attributes their team has that makes them the most qualified for this project.
Include ONLY relevant projects that have been completed within the last ten (10) years for the overall team, individual firms and the Project Manager. Use specific project examples that will illustrate the team and individual team members’ abilities to complete this project in a satisfactory manner.
The University of Kentucky is dedicated to promoting minority sub-consulting firms’ participation in university work. Consultants are encouraged to consider using the services of minority sub-consulting firms where the demands of the project will permit.
(Scoring for each category will be as indicated herein.) EVALUATION CRITERIA The following criteria will be used in the evaluation of the submittals using an overall 100-point scale:
I. PRIMARY FIRM (35 Points) Primary firm’s recent experience involving Biosafety Laboratories (BSL3) renovations within an
operating medical research center. The firm shall demonstrate an ability to coordinate design team members and detail methods that will be used to ensure that the design schedule is met, including milestone and productivity monitoring.
The firm’s strategy to assure –
Compliance with the defined programmatic needs. A well-designed and coordinated construction package. An effective construction administration process. An exceptional final product for a facility of this scale and complexity.
Special consideration will be given to experience with BSL3 laboratories within an operating medical research center.
II. OTHER DESIGN TEAM MEMBERS (20 Points)
Emphasis should be placed on indicating who the design team will be as well as their availability for this project. Attention should be given toward indicating who the sub-consultants will be, their
Upgrade/Renovate/Expand Research Labs (Biosafety Lab Renovation – Health Sciences Research Building) University of Kentucky
Project Number 2573.0
Consultant Submittal Guidelines & Executive Summary Page 3 of 7
respective rolls, and who the specific team members will be. Skills necessary to meet the project schedule, budget and design criteria should be demonstrated by all team members.
Identify key personnel within the firm and their corresponding roles on this project. Explain their qualifications resulting in their being proposed for this project.
Include a matrix indicating who the full design team members will be and what their respective
roles were with the examples listed.
III. PROJECT MANAGER’S QUALIFICATIONS (25 Points)
Identify who the Project Manager will be and indicate his/her experience with planning,
managing and coordinating all aspects of a project of similar complexity in a professionally competent manner. Experience should include management and coordination of a full design team on projects of similar scope and complexity. Project Manager should have recent experience with additions to and renovations of existing university facilities and/or other projects of similar scale and complexity; submittal should explain the significance of each project listed. (Please include a maximum of 5 project examples.)
Design Team should be experienced in working with current technological tools, to include
designing using building information modeling (BIM) and web-based project management systems.
Design Team should show commitment necessary to adequately manage and coordinate
the project through all phases of programming, design, contract documents, bidding and construction administration – maximizing project funds, while minimizing change orders and maintaining an aggressive project schedule.
IV CONSTRUCTION ADMINISTRATION (20 Points)
Explain Team’s approach to construction administration, and how the Team will respond to issues that may arise during construction.
Design Team should be familiar with the CM delivery method and should have experience working with Construction Management firms for coordination and completion of projects using this delivery method.
Upgrade/Renovate/Expand Research Labs (Biosafety Lab Renovation – Health Sciences Research Building) University of Kentucky
Project Number 2573.0
Consultant Submittal Guidelines & Executive Summary Page 4 of 7
The consultant should be careful to address each criterion, as neglect of any section will result in a lower total score for the firm. DO NOT ASSUME THOSE REVIEWING THE SUBMITTALS ARE ALREADY FAMILIAR WITH YOUR FIRM. Your presentation should be concise and to the point. Emphasis should be given to a few examples, which clearly show the team’s qualifications, rather than numerous examples, which are unrelated to the project. For further information concerning the scope of this project, contact Sandy Redmon, Project Manager, at (859) 218-3115.
Please use the “Submit Proposal” button next to the project listed on CPMD’s website to submit your documents electronically in pdf format.
In addition to the electronic copy, please provide eight (8) bound copies of the submittal for
review. Submit to:
Capital Project Management Division
222 Peterson Building 411 South Limestone Street Lexington, KY 40506-0005
ATTN: Sandy Redmon
SUBMITTALS MUST BE RECEIVED NOT LATER THAN 3:00 PM EST, ON MONDAY, OCTOBER 4, 2021.
Submittals received after this time will not be reviewed.
Upgrade/Renovate/Expand Research Labs (Biosafety Lab Renovation – Health Sciences Research Building) University of Kentucky
Project Number 2573.0
Consultant Submittal Guidelines & Executive Summary Page 5 of 7
Executive Summary B. PROJECT DESCRIPTION
The University of Kentucky is home to leaders in the fields of immunology, microbiology, and infectious
diseases. As the flagship university of the state of Kentucky, the university is often called upon to respond to health emergencies. In response to the COVID-19 pandemic, the University of Kentucky is embarking on an ambitious project to expand it research portfolio on emerging and re-emerging pathogens. To support these research activities, the university will renovate an existing aging BSL-3 facility that was originally constructed in 2000.
This project will renovate the 1,450 square foot BSL3 laboratory that currently consists of eight (8) spaces:
2 animal holding rooms, 2 procedure rooms, common lab spaces, an anteroom, 2 locker/showers and the common lab space. The renovation should accommodate an animal procedure room in addition to a large, shared laboratory. Following is a partial list of deficiencies identified by Cornerstone Commissioning LLC as needing correction:
- Replace current autoclave - Address leaks in containment barrier - Install relative humidity sensors - Ensure review of temperature sensors - Make corrections to room pressure monitors - Adjust room airflow to achieve desired room pressures - Adjust room differential set up - Make necessary repairs on isolation dampers, supply, and exhaust - Make necessary corrections to isolation damper control pad - Evaluate exhaust fan - Obtain all required certifications
See attached final commissioning report for full details.
The design will consist of preparation of Phase 1-2 and 3 documents in accordance with University and Medical Center standards and procedures. A conceptual program and preliminary opinion of probable construction and project cost has been developed and will be released to the shortlisted teams.
Upgrade/Renovate/Expand Research Labs (Biosafety Lab Renovation – Health Sciences Research Building) University of Kentucky
Project Number 2573.0
Consultant Submittal Guidelines & Executive Summary Page 6 of 7
C. PRELIMINARY PROJECT BUDGET
TOTAL CONSTRUCTION BUDGET* $925,000
TOTAL PROJECT SCOPE $1,500,000
* The Consultant's Phase 1, 2 & 3 cost estimate submittals for the project are not to exceed this specified amount. Budget compatibility is the responsibility of the Consultant and design of the project beyond the available construction dollars listed above is unacceptable.
Upgrade/Renovate/Expand Research Labs (Biosafety Lab Renovation – Health Sciences Research Building) University of Kentucky
Project Number 2573.0
Consultant Submittal Guidelines & Executive Summary Page 7 of 7
D. PRELIMINARY PROJECT SCHEDULE The following is the tentative schedule presently proposed for this project:
Monday, September 20, 2021 Project Advertised for Consultant
Monday, October 4, 2021 Consultant Submittals Due
Friday, October 8, 2021 Short List Meeting
Friday, October 22, 2021 Design Team Interviews
Monday, November 1, 2021 Design Team Contract Negotiated
Friday, November 5, 2021 Program Meeting
Wednesday, November 17, 2021
Program Review
Monday, November 22, 2021 Begin Phase 1-2 Design
Monday, January 31, 2022 Phase 1-2 Documents Submitted to CPMD
Monday, February 14, 2022 Phase 1-2 Review
Monday, March 21, 2022 Phase 3 Documents Submitted to CPMD
Monday, April 4, 2022 Phase 3 Review Meeting
Monday, April 18, 2022 Final Documents Submitted to CPMD
Monday, May 2, 2022 Advertise for Bidding
Thursday, May 12, 2022 Pre-Bid Conference
Thursday, June 2, 2022 Bid Opening
Friday, June 10, 2022 Contract Awarded
Monday, June 20, 2022 Construction Begins
Thursday, November 10, 2022 Substantial Completion
Saturday, December 10, 2022 Final Completion
Friday, November 10., 2023 Warranty Expires
11 Cold Spring Drive, Boxford, MA 01921
Tel 978-887-8177 | Fax: 978-359-7775
www.CCxcx.com
PERFORMANCE VERIFICATION REPORT
UNIVERSITY OF KENTUCKY PETER BOSOMWORTH HEALTH SCIENCES RESEARCH BUILDING (HSRB) FOURTH FLOOR BSL-3 LABORATORY LEXINGTON, KY AUGUST 10, 2021 – REV. 0
PO Box 156, Boxford, MA 01921
Tel 978-887-8177 | Fax: 978-359-7775
www.cornerstonecx.com
ESTABLISHING A FOUNDATION
FOR PERFORMANCE
Univ of Kentucky – HSRB – 4th floor BSL-3
PV Report - 2021
www.cornerstonecx.com
Table of Contents
1. Executive Summary
2. Annual Performance Verification Plan
3. Corrective Action Plan
4. Facility Performance Tests and Data
5. Integrated Systems Testing (Failure Scenario Testing)
6. Supporting Documents
www.CCxcx.com
Univ of Kentucky – HSRB – 4th floor BSL-3
PV Report - 2021
www.cornerstonecx.com
Date: August 10, 2021 To: Brandy Nelson
Biosafety Officer University of Kentucky – Lexington [email protected] 859-550-0333
Subject: Performance Verification for the University of Kentucky – HSRB – Fourth floor BSL-3 Laboratory EXECUTIVE SUMMARY
Cornerstone Commissioning (CCx) has completed the performance verification (PV) of the UK HSRB fourth floor BSL-3 Laboratory located in Lexington, KY. Based on our observations, teleconferences and correspondence, Cornerstone Cx understands that UK has plans to renovate the BSL-3 laboratory for a new research team. The Corrective Action Plan (CAP) lists all items noted as part of the performance verification process that were discovered and need to be addressed. The CAP has recommended actions to take and how the items will be or were resolved. We would like to point out that some of these items may be addressed and not be a concern as part of this renovation. We welcome the opportunity to review all of the items and assist UK to support the important planned research in this BSL-3 laboratory.
The following summary details the items that were verified and documented as part of the performance verification process. Any systems or equipment that is not functioning is documented in the CAP:
1. Bio Safety Cabinets (BSL-3 primary containment):
a. There are five (5) Class II Type A2 recirculating BSCs; one (1) Class II Type B2 BSC.
b. BSC certification has expired for all six (6) BSCs.
2. HEPA filtered exhaust:
a. Multiple bag-in/bag-out HEPA housings located on the roof, which serve the BSL-3 laboratory exhaust air terminal units/ fans.
b. HEPA certification has expired.
3. Decontamination system – Autoclaves: Primary means of decontamination of all laboratory waste is the autoclave. The autoclave is not operational. There is no biological indicators (BI) logbook with current results.
4. Room differential pressure monitors were verified, and values were documented to confirm accuracy of both the local displays outside the laboratory and building automation system.
5. Relative room pressures - Throughout testing CCx confirmed that the directional airflows are maintained at the gradients acceptable to UK and industry standards throughout the test period.
6. Room integrity verification (BSL-3 secondary containment barrier)
a. CCx used a smoke generating device to verify the integrity of the secondary containment barrier. The room integrity tests were conducted at normal room pressures.
b. There were a small number of leaks discovered in the facility. All items identified need to be repaired by UK staff or contract team. If a layout change is made, suggest addressing the items on the remaining existing walls, ceilings, and floors as applicable.
7. Temperature – Verified that the room temperature sensors are reading correctly, and that the control system can meet the setpoint. We were not able to review trend data from the BAS to verify that the temperature control system is working correctly in all laboratory spaces.
8. Relative humidity – Verified that the room RH values are within acceptable values for anticipated research. There are no RH sensors installed, as such, we could not review any trend data from the BAS to verify that the RH remains acceptable in the spaces through all seasons in all laboratory spaces. Animal holding rooms could benefit from the addition of these sensors at a minimum.
Univ of Kentucky – HSRB – 4th floor BSL-3
PV Report - 2021
www.cornerstonecx.com
9. All sinks were exercised as part of this performance verification process. Hot and cold water were available at all locations. The electronic eye batteries need to be replaced in most of the hand sinks. Emergency showers and eye washers were also verified as operational.
10. Electrical outlets, lighting control, light fixtures and bulbs were verified operational.
11. CCx confirmed that all the doors close and latch by themselves. The door hardware was confirmed to be in good working order.
12. CCx confirmed all access control, including the card readers and door interlocks function. All security related items were confirmed as operational.
13. CCx tested the supply and exhaust isolation dampers for functionality, as applicable.
14. CCx documented the room airflows, ensuring that all supply and exhaust Phoenix Controls air valves are in control, and that they provide steady values for steady room differential pressure. These were compared to the original design and testing and balancing (TAB) report. Any modifications or changes to setpoint are noted in the applicable section.
15. CCx confirmed the air change rate in the BSL-3 spaces.
16. Air Handling Unit Supply Fans serving the BSL-3 – Inspected the general condition of the AHU; belts, filters, cleanliness, etc. with no issues noted. Maintenance is performed according to manufacturer’s recommendations for greasing of bearings, filter change out, etc. Visual inspection shows no issues or concerns.
17. Exhaust Fans serving the BSL-3 – Inspected the belts, no issues noted. Maintenance has not been performed according to manufacturer’s recommendations. Visual inspection shows a potential issue with EF-1 bearings.
18. Integrated Systems Testing (IST) – Failure Scenario Testing – CCx performed failure testing with UK staff and for the BSL-3 equipment and spaces:
a. Air Handling Unit Supply Fans - CCx performed failure testing of the redundant supply fans, the test results with the room differential pressure graphs are detailed in IST#1.
b. Exhaust Fans - CCx performed failure testing of the redundant exhaust fans, the test results with the room differential pressure graphs are detailed in IST#2.
c. Power failure test – CCx performed electrical power failure testing. The test results with the room differential pressure graphs are detailed in IST#3.
d. No reversal of airflows were noted at the secondary containment barrier during these failure test scenarios.
Supporting details for all observations are included in the applicable sections or as attachments with this report.
Refer to the Facility Performance Test and Data section for details, measurements, and readings.
If there are any questions, concerns, or comments, please feel free to contact me at any time.
Respectfully Submitted,
Daniel Cook | LEED AP® | Director of Critical Projects Cellular: 603.944.1633 | Email: [email protected] CC: Dan Frasier, PE, CCP | Founder / CEO; Cornerstone Commissioning, Inc.
Univ of Kentucky – HSRB – 4th floor BSL-3
PV Report - 2021
www.cornerstonecx.com
Performance Verification Plan
Performance Verification Plan Project #: 1929
Rev # Issue Date Issued By / Initials Revision Description
1 2021-07-08 Cornerstone Cx / DC Initial Draft
2 2021-07-19 Cornerstone Cx / DC Rev 1
3 2021-07-27 Cornerstone Cx / DC Rev 2, FM & BSO Q, BMBL
The Performance Verification (PV) Plan is a document that may be revised over the course of the PV. The revision control
tracks current and past revisions to ensure the most updated plan is being used.
Facility Information
Owner / Entity / Client: University of Kentucky (UK)
Building / Facility: Health Sciences Research Building (HSRB)
The ABSL-3 laboratory is 1,450 square foot facility consisting of eight (8) spaces; 2 animal holding rooms, 2 procedure rooms,
common lab spaces, and an anteroom that has doors to the public corridor, the 2 locker / showers and the common lab
space.
The HVAC system consists of an air handling unit, 2 exhaust fans, and a HEPA filter bag in/bag out housing serving each
exhaust fan. There are Phoenix Controls air valves installed on the supply and exhaust for the labs. The supply has a reheat
coil. There are also isolation dampers on each supply and exhuast duct for isolation during decontamination, these are
controlled via a switch inside a panel in the ante room.
Address: 1095 Veterans Dr., Lexington, KY, 40508
Laboratory Description
Laboratory location (floor): Fourth floor
Year built: Renovation in 2000
The Performance Verification (PV) process has been developed by Cornerstone Commissioning (Cx) to ensure that the
systems, equipment and administrative controls meet or exceed the requirements and recommendations from industry
guidelines, best practices, owner and or consultant recommendations, that are specific to the laboratory program and
facility.
The PV process satisfies the industry requirement to re-verify and document the design, operational parameters, and
procedures at least annually of the laboratory.
Performance Verification (PV) Process Overview
Industry Guidelines for PV
PV Plan Purpose
The PV plan describes how Cornerstone Cx will execute and document this process based on the scope of work in the PV
proposal. The PV schedule of activities is listed in the order which they should be performed, with some activities occurring
off site before and after the onsite testing and observations.
PV Plan Document Revision Control
Document Control
Biosafety in Microbiological and Biomedical Laboratories (BMBL) - 6th edition - June 2020
Section IV—Laboratory Biosafety Level Criteria | Biosafety Level 3 | D. Laboratory Facilities (Secondary Barriers):
Page 48 - Biosafety Level 3, D. Laboratory Facilities (Secondary Barriers), 15. The BSL-3 facility design, operational
parameters, and procedures are verified and documented prior to operation. Facilities are tested annually or after significant
modification to ensure operational parameters are met. Verification criteria are modified as necessary by operational
experience.
www.cornerstonecx.com
Performance Verification Plan Univ of Kentucky
HSRB 4th floor BSL-3
Lexington, KY
Floorplan for reference (drawing):
www.cornerstonecx.com
Performance Verification Plan Univ of Kentucky
HSRB 4th floor BSL-3
Lexington, KY
Mo
nd
ay
Tue
sday
We
dn
esd
ay
Thu
rsd
ay
20
21
-07
-26
20
21
-07
-27
20
21
-07
-28
20
21
-07
-29
EH&S /Lab
Staff
Facilities /BAS
Access
1Review any changes or adjustments to systems serving the lab since last Performance
Verification or initial commissioning.X X X
2Review maintenance records of all HVAC equipment serving the BSL3. Visual
inspection of fans, motors, belts, filters, etc.X X
3 Review certification reports of BSCs and HEPA filters X X
4 Verify operation of the autoclave, review BI log, run cycle with datalogger X X
5Complete a BSL3 facility compliance checklist to evaluate all important elements and
performance criteriaX X
6 Verify room differential pressures X X
7 Verify directional airflow X X
8Conduct room envelope integrity testing for all rooms within the BSL3 secondary
containment boundary.X X
9 Verify sensor accuracies using calibrated devices (temp, RH) X X
10Plumbing systems - Operation of any drench showers, eyewash stations and hands
free sinks (hot, cold, drain)X X
11 Waste treatment systems and related SOPs X X
12Electrical systems - Confirm that there are no light bulbs out, no issues with any
outlets (spot check)X X
13 Verify door operation; access controls, closers, latches, interlocks, and alarms X X
14 Bubble-tight damper operation, as applicable X X
15Verify the performance of all zones for stable operation using BAS trend data
X X
16 Local and remote (BAS) alarms, including verification of notifications X X
17
Failure Testing:
1) AHU Supply Fan Failure
2) Exhaust Fan Failure
3) Electrical Power Failure and Restoration of Normal Power
X Backup X X
2 - The exhaust fans serving the BSL-3 can be shut off
3 - U Ky - Building Automation System (require access to view system points, graphics and alarms)
2 - U Ky - Facilities - Mechanical, Electrical, Plumbing and Carpentry (as applicable)
1 - U Ky - EH&S / Lab Manager / Research staff
Cornerstone will need support from multiple parties during this process:
3 - The electrical power to the building can be shut off
12:00pm - 5:00pm on Monday
7:30am - 5:00pm on Tuesday Wednesday
7:30am - 12:00pm onThursday (if needed)
These hours are flexible and can be modified to meet the schedule that will work for onsite personnel
Cornerstone will plan to be onsite between:
All activities are from the Cornerstone Commissioning proposal for Biocontainment Facilities Performance Verification Services dated
March 1, 2021, Scope of Work section.
Performance Verification Activity
Required personnel
Failure testing requirements, please consult with facilities and building occupants to ensure that:
1 - The AHU supply fan(s) serving the BSL-3 can be shut off
www.cornerstonecx.com
Performance Verification Plan Univ of Kentucky
HSRB 4th floor BSL-3
Lexington, KY
Name Organization Role Phone Email
Cindy Meier U Ky Research Facility
Manager
859-257-9720 [email protected]
Ilhem Messaoudi U Ky Researcher / Principle
Investigator (PI)
Brandy Nelson U Ky Biosafety Officer 859-550-0333 [email protected]
Kevin Locke U Ky Facilities [email protected]
Dan Cook Cornerstone
Commissioning,
Inc.
PV Provider 603-944-1633 [email protected]
PV Team - Test Participants / Witnesses:
The members of the PV Team include representatives from multiple organizations.
Personnel listed below will be participating in different events and capacities to complete the PV.
www.cornerstonecx.com
Performance Verification Plan Univ of Kentucky
HSRB 4th floor BSL-3
Lexington, KY
Documents Available for review? Date / Version / Last Update / Comment
Basis of Design (BOD) / Design Intent Not available
Construction Documents - Drawings and Specification (As built) - Architectural,
Mechanical, Plumbing, Electrical, Security, Life Safety/Fire Protection, etc.
Renovation in 2000, some docs are available;
Floorplans for equipment, electrical, ductwork, and the full specifications.
One line, P&ID for HVAC air system Yes
One line, electrical system Not available
Submittals - Controls / Building Automation System (BAS) - including the
Sequence of Operations (As Built)
Yes
Submittals - Equipment Yes
O&M manuals - For all equip Hard copies available on site for review CM
Testing and Balancing (TAB) report Hard copies available on site for review CM
Commissioning (Cx) report Hard copies available on site for review CM
Performance Verification (PV) report Uky PV report in 2015
Review Entity documentation (Maintenance, Calibration, Certification) Available for review? Date / Version / Last Update / Comment
Maintenance records - All HVAC equipment Not available
Calibration records - Critical control devices Not available
Certifications - Biosafety Cabinets (BSC) Not since 2015, looking to replace BSC per new PI (Ilhem)
Certifications - HEPA filters and housing Not since 2015
System or equipment failures / incidents; utilities Not available
System or equipment failures / incidents; facilities Hard copies available on site for review CM
System or equipment failures / incidents; research equipment Autoclave is inoperable. BN
1 - The supply fan(s) in AHU serving the BSL-3 can be shut off Coordinated with David Moody and Sandy Redmon - FM Med Center
2 - The exhaust fan(s) serving the BSL-3 can be shut off Coordinated with David Moody and Sandy Redmon - FM Med Center
3 - The normal electrical power utility to the building can be shut off Coordinated with David Moody and Sandy Redmon - FM Med Center
Critical Equipment Summary List all vendors/ manufacturers;
Building Automation System (BAS) Tridium
Air Handling Unit (AHU) AHU-2 Buffalo Forge
Exhaust Fans (EF) EF-1, EF-2 Barry Blower
HEPA filter housing AAF/Flanders
Air Terminal Unit manufacturer Phoenix Controls
Room Pressure Monitors (RPM) Air Monitor Corp, Sentry
Electrical systems (Utility feed, generator, ATS, UPS) Not available
Other critical systems/ equipment/components Not available
Question Response
List all modifications and/or changes since initial construction, Cx, PV, etc. Files available on site. CM
Reportable incidents; research staff, laboratory manager, EH&S Lab has been inactive since 2016. BN
Any lessons learned from interaction with research staff, laboratory manager,
EH&S?
N/A BN
Work orders, equipment failure reports Not available
Contractors Precision Air Technologies - BSCs and HEPAs,
Agape Instruments - Autoclave BN
Facilities Management - Questionnaire
Failure testing requirements, confirm with all facilities staff and building occupants to ensure that:
Review background material:
www.cornerstonecx.com
Performance Verification Plan Univ of Kentucky
HSRB 4th floor BSL-3
Lexington, KY
Question Response
What type of BSL-3/ABSL-3 level work is conducted in this laboratory? No BSL-3/ABSL-3 work has been conducted in the facility since 2016.
What type of agents are used? N/A
Risk assessment complete? N/A
Has the laboratory been actively used for BSL-3/ABSL-3 level work? No BSL-3/ABSL-3 work has been conducted in the facility since 2016.
Any incidents or events that warrant a decontamination of the laboratory to perform
the PV?
N/A
If yes, was the laboratory successfully decontaminated? N/A
If yes, will the laboratory decontamination be complete before PV work is
scheduled?
N/A
Is the decontamination report available for review? N/A
Are Cornerstone personnel medical evaluations or testing required for entry into the
BSL-3/ABSL-3 laboratory?
Pre and post lab visit?
No
List all required personnel protective equipment (PPE) to meet the risk assessment
(RA):
N/A
PI/ BSO has informed CCx of required safety procedures for work in the BSL-3/ABSL-3
laboratory?
No required safety procedures as lab has been inactive for 5 years.
PI/ BSO has informed and provided CCx with required PPE for work in the BSL-3/ABSL-
3 laboratory?
No required PPE as lab has been inactive for 5 years.
Entity documentation -
Standard Operating Procedure (SOP), Manuals, Plans, etc.Available for review? Date / Version / Last Update / Comment
Biological Safety Manual Yes, 2016-0308
Biomedical Waste Operating Plan Included in biosafety manual.
Biosafety Plan Included in biosafety manual.
BSL-3 Medical Surveillance Plan Yes, 2016-0308
Incident Response Plan Yes, 2016-0308
BSL-3 Training Procedures Included in biosafety manual. Can provide presentations/modules as needed.
BSL-3 Entry and Exit Procedures Included in biosafety manual. Can provide presentations/modules as needed.
BSL-3 Working Safely in a Biosafety Cabinet Included in biosafety manual. Can provide presentations/modules as needed.
BSL-3 Transfer Between Rooms Included in biosafety manual. Can provide presentations/modules as needed.
Laboratory Safety Manual N/A
Facility or Systems manual N/A
Document review Available for review? Date / Version / Last Update / Comment
Do the SOPs meet the needs of the program and laboratory activities? They did in 2016. There is no current high containment work at UK.
Do the SOPs include information on how to manage hazardous (infectious) waste? Yes
Do the SOPs include laboratory accident response protocols? Yes
Have the decontamination methods been evaluated for efficacy? Yes
Is there an integrated pest management program in place? Yes
Are the SOPs tracked with updates based on feedback, continual improvement
program, lessons learned, etc.?
Yes
Do the SOPs describe the interaction of facilities, EH&S, lab manager, researchers,
etc. during maintenance, accidents, and failure events?
Yes
Biosafety Officer (BSO) / Responsible Official (RO) - Questionnaire
www.cornerstonecx.com
Performance Verification Plan Univ of Kentucky
HSRB 4th floor BSL-3
Lexington, KY
https://www.cdc.gov/labs/BMBL.html
Compliant? Comments/Notes Recommendation / Solution Updates / Actions Taken
1 The laboratory is separated from areas that are open to unrestricted
traffic flow within the building. Yes
a Laboratory access is restricted. Laboratory doors are lockable in
accordance with institutional policies. Access to the laboratory is
through two consecutive self-closing doors. A clothing change room
and/or an anteroom may be included in the passageway between
the two self-closing doors.
Yes
2 Laboratories have a sink for handwashing. The sink is hands-free
or automatically operated and should be located near the exit door.
If a laboratory suite is segregated into different zones, a sink is also
available for handwashing in each zone.
Yes
3 An eyewash station is readily available in the laboratory. Yes
4 The laboratory is designed, constructed, and maintained to facilitate
cleaning, decontamination, and housekeeping. Partial
Wood doors throughout the lab.
Porous wood paneling on the walls in labs F and
L.
Replace doors (CAP#25)
a Carpets and rugs are not permitted. Yes No carpets or rugs.
b Spaces between benches, cabinets, and equipment are accessible
for cleaning.Yes
c Seams, floors, walls, and ceiling surfaces are sealed. Spaces
around doors and ventilation openings are capable of being sealed
to facilitate space decontamination.
Yes
Access panels are sealed with metal tape.
d Floors are slip-resistant, impervious to liquids, and resistant to
chemicals. Flooring is seamless, sealed, or poured with integral
cove bases.
Yes
e Walls and ceilings are constructed to produce a sealed smooth
finish that can be easily cleaned and decontaminated.Yes
See room integrity test report.
5 Laboratory furniture can support anticipated loads and uses. Yes
a Benchtops are impervious to water and resistant to heat, organic
solvents, acids, alkalis, and other chemicals.Yes
b Chairs used in laboratory work are covered with a non-porous
material that can be easily cleaned and decontaminated with an
appropriate disinfectant.
Yes
Chairs have duct tape or metal foil tape on them
6 All windows in the laboratory are sealed. Yes
7 Illumination is adequate for all activities and avoids reflections and glare that could impede
vision.Yes
8 Vacuum lines in use are protected with liquid disinfectant traps and
in-line HEPA filters or their equivalent. See Appendix A, Figure 11. Filters
are replaced, as needed, or are on a replacement schedule determined
by a risk assessment. Vacuum lines not protected as described are
capped. The placement of an additional HEPA filter immediately prior to
a central vacuum pump is considered.
Partial
Millipore disc HEPA filter on the turrets. Unsure
if this is tied into building system or if it is
independent of non-BSL-3 areas.
Recommend point of use vacuum units, which
can be located inside the BSC.
(CAP #36)
https://www.welchvacuum.com/en-us/piston-
pumps/piston-pump-wob-l-2534
9 A ducted mechanical air ventilation system is required. This system
provides sustained directional airflow by drawing air into the laboratory
from “clean” areas toward “potentially contaminated” areas. The
laboratory is designed such that under failure conditions the airflow will not be reversed at the
containment barrier.
Yes
a A visual monitoring device that confirms directional airflow is
provided at the laboratory entry. Audible alarms to notify personnel
of airflow disruption are considered. Partial
Room Pressure Monitor (RPM) display has all
room pressure values in the corridor, at the
entrance to the lab suite.
Sentry air monitor above each door, display
value is in FPM, not in wc.
Replace with RPM (or other airflow direction
device).
(CAP #8, 9, 10, 11)
b The laboratory exhaust air is not re-circulated to any other area in
the building.Yes
c The laboratory exhaust air is dispersed away from occupied areas
and from building air intake locations or the exhaust air is HEPA
filtered.
Yes
The following items are from the CDC/NIH Biosafety in Microbiological and Biomedical Laboratories (BMBL) 6th Edition guidelines and how the facility meets or
exceeds them.
Biosafety in Microbiological and Biomedical Laboratories (BMBL) - 6th Edition - June 2020
Section IV—Laboratory Biosafety Level Criteria
Biosafety Level 3
D. Laboratory Facilities (Secondary Barriers) (page 48)
www.cornerstonecx.com
Performance Verification Plan Univ of Kentucky
HSRB 4th floor BSL-3
Lexington, KY
https://www.cdc.gov/labs/BMBL.html
Compliant? Comments/Notes Recommendation / Solution Updates / Actions Taken
The following items are from the CDC/NIH Biosafety in Microbiological and Biomedical Laboratories (BMBL) 6th Edition guidelines and how the facility meets or
exceeds them.
Biosafety in Microbiological and Biomedical Laboratories (BMBL) - 6th Edition - June 2020
Section IV—Laboratory Biosafety Level Criteria
Biosafety Level 3
D. Laboratory Facilities (Secondary Barriers) (page 48)
10 BSCs and other primary containment barrier systems are installed and
operated in a manner to ensure their effectiveness. See Appendix A.Yes
a BSCs are installed so that fluctuations of the room air supply and
exhaust do not interfere with proper operations. BSCs are located
away from doors, heavily traveled laboratory areas, and other
possible airflow disruptions.
Yes
b BSCs can be connected to the laboratory exhaust system by either
a canopy connection (Class IIA only) or directly exhausted to the
outside through a hard connection (Class IIB, IIC, or III). Class IIA or
IIC BSC exhaust can be safely recirculated back into the laboratory
environment if no volatile toxic chemicals are used in the cabinet.
Partial
One (1) B2, one (1) fume hood should be
removed.
Consult with research team on needs for BSC
size and type.
(CAP #1, 2)
c BSCs are certified at least annually to ensure correct performance,
or as specified in Appendix A, Part 7.No
d Class III BSCs are provided supply air in such a manner that
prevents positive pressurization of the cabinet or the room. N/A
11 Equipment that may produce infectious aerosols is used within primary
barrier devices that exhaust air through HEPA filtration or other equivalent technology before
being discharged into the laboratory. These HEPA filters are tested annually and replaced as
needed.
N/A
What equipment that may produce aerosols will
be needed by research team?
12 Facility is constructed to allow decontamination of the entire laboratory
when there has been gross contamination of the space, significant
changes in usage, major renovations, or maintenance shutdowns.
Selection of the appropriate materials and methods used to decontaminate the laboratory is
based on the risk assessment.
Partial
Items identified in the room integrity test report
should be corrected.
(CAP#15)
a Facility design consideration is given to means of decontaminating
large pieces of equipment before removal from the laboratory. No
How would a freezer, BSC, or other large piece
of equipment be decontaminated and removed?
13 Enhanced environmental and personal protection may be necessary
based on risk assessment and applicable local, state, or federal
regulations. These laboratory enhancements may include one or more of
the following: an anteroom for clean storage of equipment and supplies
with dress-in, shower-out capabilities; gas-tight dampers to facilitate
laboratory isolation; final HEPA filtration of the laboratory exhaust air;
laboratory effluent decontamination; containment of other piped services; or advanced access
control devices, such as biometrics.
Partial
Ante room, change room, shower, final HEPA on
the exhaust air system,
Floor drains in most spaces, where does it go?
How is it treated?
(CAP#21)
14 When present, HEPA filter housings have gas-tight isolation dampers, decontamination ports,
and/or bag-in/bag-out (with appropriate decontamination procedures) capability. All HEPA
filters are located as near as practicable to the laboratory to minimize the length of potentially
contaminated ductwork. The HEPA filter housings allow for leak testing of each filter and
assembly. The filters and housings are certified at least annually.
No
No gas tight dampers, no decon port, no test
ports, HEPA filters are located on the roof, near
exhaust fans, long run of exhaust duct from the
4th floor to the roof, 4 story building.
(CAP#5)
15 The BSL-3 facility design, operational parameters, and procedures are
verified and documented prior to operation. Facilities are tested annually or after significant
modification to ensure operational parameters are met. Verification criteria are modified as
necessary by operational experience.No
Lab has been decommissioned, not used since
2016.
After all modifications are made will need to re-
commission/verify the performance of all
systems and equipment.
16 Appropriate communication systems are provided between the
laboratory and the outside (e.g., voice, fax, and computer). Provisions
for emergency communication and emergency access or egress are
developed and implemented.
No
No phones inside the laboratory spaces Add phones inside labs.
Compliant? Comments/Notes Recommendation / Solution Updates / Actions Taken
A.5,
pg 44 A sign incorporating the universal biohazard symbol is posted at the entrance to the laboratory
when infectious materials are present. Posted information includes: the laboratory’s Biosafety
Level, the supervisor’s or other responsible personnel’s name and telephone number, PPE
requirements, general occupational health requirements (e.g., immunizations, respiratory
protection), and required procedures for entering and exiting the laboratory. Agent information
is posted in accordance with the institutional policy.
No
All of the emergency contacts signs are old and
will need to be updated, throughout the lab
space.
Will need to be updated with information
pertaining to new research team.
B.9,
pg 47A method for decontaminating all laboratory wastes should be available in the facility,
preferably within the laboratory (e.g., autoclave, chemical disinfection, incineration, or
other validated decontamination method).
No
Autoclave is not operational Replace autoclave.
(CAP#6,7)
Compliant? Comments/Notes Recommendation / Solution Updates / Actions Taken
CCx-1An eyewash station must be readily available in the laboratory and meets ANSI Z358.1-
2009.Water is between 60-100 deg F for the 15 minute wash cycle.Yes
CCx-2 Is there a dedicated air handler for BSL-3 supply air? No AHU-2 serves the north side of the HSRB facility.
CCx-3Is there a means of isolating the BSL-3 supply air? This can be done at the common
trunk or at the zone level.Yes
CCx-4
Internal facility appurtenances, such as light fixtures, air ducts, and utility pipes, are
arranged to minimize horizontal surface areas to facilitate cleaning and minimize the
accumulation of debris or fomites.
Yes
The following items are based on Cornerstone Commissioning Biosafety Level Three (BSL-3) laboratory commissioning experience.
These are enhancements and/or best practice based on other BSL-3 laboratory commissioning / PV testing.
Item
Other Sections (A-C)
www.cornerstonecx.com
Performance Verification Plan Univ of Kentucky
HSRB 4th floor BSL-3
Lexington, KY
Biosafety in Microbiological and Biomedical Laboratories (BMBL) - 5th
edition Dec 2009
https://www.cdc.gov/labs/pdf/CDC-
BiosafetyMicrobiologicalBiomedicalLaboratories-2009-P.PDF
Biosafety in Microbiological and Biomedical Laboratories (BMBL) - 6th
edition June 2020
https://www.cdc.gov/labs/BMBL.html
Institute for Laboratory Animal Research. Guide for the Care and Use of
Laboratory Animals (the Guide, NRC 2011)
https://www.aaalac.org/the-guide/
https://grants.nih.gov/grants/olaw/guide-for-the-care-and-use-of-laboratory-
animals.pdf
Centers for Disease Control and Prevention (CDC) -
Division of Select Agent and Toxins (DSAT) -
Federal Select Agent Program External (FSAP)
https://www.cdc.gov/cpr/dsat.htm
https://www.selectagents.gov/index.htm
https://www.selectagents.gov/sat/list.htm
https://www.selectagents.gov/compliance/guidance/index.htm
CDC DSAT - Select Agent Grams - 8/05/11 - Policy on BMBL 5th edition
Laboratory Facilities (Secondary Barriers) Standards
(Updated on 11/20/14 )
https://www.selectagents.gov/sagrams.html
https://www.selectagents.gov/sagrams-2008-2015.html
ANSI Z9.14 - 2020 - Testing And Performance-Verification Methodologies
For Ventilation Systems For Biosafety Level 3 (BSL-3) And Animal
Biosafety Level 3 (ABSL-3) Facilities
https://store.assp.org/PersonifyEbusiness/Store/Product-
Details/productId/207427871
National Institutes of Health (NIH) - Design Requirements Manual (DRM) https://www.orf.od.nih.gov/TechnicalResources/BiomedicalandAnimalResea
rchFacilitiesDesignPoliciesandGuidelines/Pages/default.aspx
NIH Recombinant/Synthetic Nucleic Acid (r/sNA) Guidelines https://osp.od.nih.gov/wp-content/uploads/NIH_Guidelines.pdf
NIH BSL-3 Certification Standards https://www.orf.od.nih.gov/TechnicalResources/Bioenvironmental/Docume
nts/BSL3CertificationGuidelinesFINAL_508.pdf
United States Department of Agriculture (USDA) -
Agricultural Research Service (ARS) -
ARS Design Standards (242.1M-ARS)
https://www.ars.usda.gov/
https://govtribe.com/file/government-file/attachment-9-ars-design-
standards-242-dot-1m-ars-dot-pdf-1
World Health Organization (WHO) -
Laboratory Biosafety Manual - Third Edition
https://www.who.int/csr/resources/publications/biosafety/WHO_CDS_CSR_
LYO_2004_11/en/
Canadian Biosafety Standards and Guidelines https://www.canada.ca/en/public-health/services/canadian-biosafety-
standards-guidelines.html
Department of the Army Pamphlet - 385-69
Safety Standards for Microbiological and Biomedical Laboratories
https://armypubs.army.mil/epubs/DR_pubs/DR_a/pdf/web/p385_69.pdf
Interim Laboratory Biosafety Guidelines for Handling and Processing
Specimens Associated with Coronavirus Disease 2019 (COVID-19)
https://www.cdc.gov/coronavirus/2019-nCoV/lab/lab-biosafety-
guidelines.html
NSF/ANSI Standard 49 – 2014, Biosafety Cabinetry: Design, Construction,
Performance, and Field Certification.
https://standards.nsf.org/apps/group_public/download.php/36078/NSF_49-
2014.pdf
BSC A2 with thimble alarm requirement;
Memo dated Oct 15, 2015: to be fitted with an Airflow Monitor that
provides a visual and audible alarm.
https://d2evkimvhatqav.cloudfront.net/documents/NSF_Biosafety_Cabinet_
Memo_Canopy_Connections.pdf
Institute of Environment Sciences and Technology (IEST)
IEST-RP-CC001: HEPA AND ULPA FILTERS - BASIC PROVISIONS
https://www.iest.org/Standards-RPs/Recommended-Practices/IEST-RP-
CC001IEST-RP-CC021: TESTING HEPA AND ULPA FILTER MEDIA https://www.iest.org/Standards-RPs/Recommended-Practices/IEST-RP-
CC021
IEST-RP-CC034: HEPA AND ULPA FILTER LEAK TESTS https://www.iest.org/Standards-RPs/Recommended-Practices/IEST-RP-
CC034
References (As applicable)
HEPA (high efficiency particulate air) references:
Biosafety Cabinet (BSC) references:
www.cornerstonecx.com
Performance Verification Plan Univ of Kentucky
HSRB 4th floor BSL-3
Lexington, KY
A/E Architect/ engineer FH Fume Hood
AAALACAssociation for Assessment and Accreditation of Laboratory
Animal Care (vivarium)FPM Feet Per Minute (air velocity)
ABD As built drawings FPTFunctional Performance Test,
Facility Performance Test (APV)
ABSA American Biological Safety Association FSAP Federal Select Agent Program
ACH Air Changes per Hour HEPA High Efficiency Particulate Air
AHR Animal holding room HVAC Heating, Ventilation, and Air Conditioning
AHU Air Handling Unit HX Heat Exchanger
ANSI American National Standards Institute Hz Hertz (frequency)
APR Air Pressure Resistant door IEST Institute of Environment Sciences and Technology
APV Annual Performance Verification (BSL-3) IST Integrated System Tests (Failure Testing)
ASHRAEAmerican Society of Heating, Refrigerating and Air-
Conditioning EngineersIVC Individually Ventilated Cage
ASSP American Society of Safety Professionals LEED Leadership in Energy and Environmental Design
ATS Automatic Transfer Switch MRI Magnetic Resonance Imaging
ATU Air Terminal Unit N/A Not applicable
BAS/BMS Building automation system/ building management system N95Particulate filtering facepiece respirators, that filters at least
95% of airborne particles.
BD Balancing Damper NHP Non Human Primate
BFP/RPZ Back Flow Preventer NIH National Institutes of Health
BI Biological Indicator (decontamination/autoclave) NSF National Sanitation Foundation (BSC NSF 49)
BMBL Biosafety in Microbiological and Biomedical Laboratories O&M Operations and Maintenance
BOD Basis of design OA Outside Air
BSC Biosafety Cabinet OAD Outside Air Damper
BSD/ BTD Bioseal damper / bubble tight damper OAT Outside Air Temperature
BSL-3 Biosafety Level three (ABSL-3 = Animal BSL-3) OPR Owners project requirements
BSO Biosafety Officer P2P Point to Point
CA Compressed Air, Combustion Air (boiler) PAPR Powered Air Purifying Respirator
CAV Constant air volume PCR Polymerase Chain Reaction
CB Change bulletin, construction bulletin PE Professional engineer, project executive
CD Chlorine Dioxide (gaseous decontamination agent) PHA Potential Hazard Analysis
CD
DD
SD
Construction Documents
Design Development
Schematic Design
PI Principal Investigator (research)
CDC Center for Disease Control PM Project manager, preventative maintenance
CFM Cubic Feet per Minute (airflow volume) PPE Personal Protective Equipment
CM/GC Construction manager / general contractor PSI Pound per Square Inch (pressure)
CO Change Order PVPerformance Verification (BSL-3),
Photovoltaic
CO Carbon Monoxide PVC Performance Verification Criteria
CO2 Carbon Dioxide RA Risk Assessment
CR Change Request RFI Request For Information
CSG Clean Steam Generator RH Relative Humidity
CV Constant Volume, Coefficient Value, Check Valve, Control Valve RIT Room Integrity Testing
CX Commissioning RO Reverse Osmosis (water), Responsible Official (BSL-3)
CxA Commissioning Authority RODI Reverse Osmosis Deionized (water)
DID Design Intent Document RPM Room Pressure Monitor, Revolutions Per Minute
DLT Duct Leakage Testing SA Supply Air
DP Differential Pressure SAD Supply Air Damper
DRM Design Requirements Manual SASP Supply Air Static Pressure
DSAT Division of Select Agents and Toxins (CDC) SAT Supply Air Temperature
EA Exhaust Air SAV Supply Air Valve
EAD Exhaust Air Damper SOO Sequence of Operation
EASP Exhaust Air Static Pressure SOP Standard operating procedure
EAT Exhaust Air Temperature SP Setpoint
EAV Exhaust Air Valve TAB Testing, Adjusting and Balancing
EC, FP, PC Elec contractor, fire protection, plumbing contractor UPS Uninterruptible Power Supply
EDS Effluent Decontamination System USDA United States Dept of Agriculture
EF Exhaust Fan USGBC U.S. Green Building Council
Acronyms
www.cornerstonecx.com
Performance Verification Plan Univ of Kentucky
HSRB 4th floor BSL-3
Lexington, KY
Acronyms
EF Exhaust Fan VAV Variable Air Volume
EH&S Environmental Health and Safety VCR Ventilated Cage Rack
EOR Engineer of Record VD Volume Damper
ERP Energy Recover Pump VFD Variable Frequency Drive
VHP Vaporized Hydrogen Peroxide
www.cornerstonecx.com
Performance Verification Plan Univ of Kentucky
HSRB 4th floor BSL-3
Lexington, KY
https://www.cdc.gov/labs/BMBL.html
Compliant? Comments/Notes
1 ABSL-3 facilities should be separated from the general traffic patterns of
the building and restricted as appropriate. Consider placing animal areas away from exterior
walls of buildings to minimize the impact from the outside environment temperatures.
a External facility doors are self-closing and self-locking.
b Access to the animal facility is restricted.
c Doors to areas where infectious materials and/or animals are housed open inward, are self-
closing, are kept closed when experimental animals are present, and are never propped open.
d Entry into the containment area is via a double-door entry, which
constitutes an anteroom/airlock and a change room. Exit showers
may be considered based on risk assessment. An additional
double-door anteroom or double-doored autoclave may be provided
for movement of supplies and wastes into and out of the facility.
2 A handwashing sink is located at the exit of the areas where infectious
materials and/or animals are housed or manipulated. Additional sinks for handwashing are
located in other appropriate locations within the facility. If the animal facility has segregated
areas where infectious materials and/or animals are housed or manipulated, a handwashing sink
is also available near the exit from each segregated area.
a The sink is hands-free or automatically operated.
b Emergency eyewash and shower are readily available, easily
accessible, and appropriately maintained.
c Sink traps are filled with water and/or appropriate disinfectant or
sealed to prevent the migration of vermin and gases.
d Floor drains are maintained and filled with water and/or appropriate
disinfectant or sealed to prevent the migration of vermin and gases.
3 The animal facility is designed, constructed, and maintained to facilitate
cleaning, decontamination, and housekeeping. The interior surfaces
(e.g., walls, floors, and ceilings) are water-resistant.
a Floors are slip-resistant, impervious to liquids, and resistant to
chemicals. Flooring is seamless, sealed, or poured with integral
cove bases. Floors slope to drain, if present.
b Penetrations in floors, walls, and ceiling surfaces are sealed,
including openings around ducts, outlets, switch plates, and
doorframes, to facilitate pest control, proper cleaning, and decontamination. Walls, floors, and
ceilings form a sanitizable and sealed surface.
c Internal facility fixtures, such as light features, air ducts, and utility
pipes, are designed and installed to minimize horizontal surface
areas to facilitate cleaning and minimize the accumulation of debris
or fomites.
d External windows are not recommended; if present, they are sealed
and resistant to breakage.
e Illumination is adequate for all activities and avoids reflections and
glare that could impede vision.
4 Furniture is minimized and can support anticipated loads and uses.
a Benchtops are impervious to water and resistant to heat, organic
solvents, acids, alkalis, and other chemicals.
b Chairs used in animal areas are covered with a non-porous material
that can be easily cleaned and decontaminated with an appropriate
disinfectant and sealed to prevent harboring of insects/vermin.
c Equipment and furnishings are carefully evaluated to minimize
exposure of personnel to pinch points and sharp edges and corners.
5 Ventilation is provided in accordance with the Guide for the Care and
Use of Laboratory Animals. (3)
a Ventilation system design considers the heat and high moisture
load produced during the cleaning of animal rooms and the cage
wash process.
b The direction of airflow into the animal facility is inward; animal
rooms maintain inward directional airflow compared to adjoining
hallways. A visual monitoring device, which confirms directional
airflow, is provided at the animal room entrance.
The following items are from the CDC/NIH Biosafety in Microbiological and Biomedical Laboratories (BMBL) 6th Edition guidelines and how the facility meets or exceeds them.
Biosafety in Microbiological and Biomedical Laboratories (BMBL) - 6th Edition - June 2020
Section V—Vertebrate Animal Biosafety Level Criteria for Vivarium Research Facilities
Animal Biosafety Level 3
D. Animal Facilities (Secondary Barriers) (page 94)
www.cornerstonecx.com
Performance Verification Plan Univ of Kentucky
HSRB 4th floor BSL-3
Lexington, KY
https://www.cdc.gov/labs/BMBL.html
Compliant? Comments/Notes
The following items are from the CDC/NIH Biosafety in Microbiological and Biomedical Laboratories (BMBL) 6th Edition guidelines and how the facility meets or exceeds them.
Biosafety in Microbiological and Biomedical Laboratories (BMBL) - 6th Edition - June 2020
Section V—Vertebrate Animal Biosafety Level Criteria for Vivarium Research Facilities
Animal Biosafety Level 3
D. Animal Facilities (Secondary Barriers) (page 94)
c A ducted exhaust air ventilation system is provided. Exhaust air is
discharged to the outside without being recirculated to other rooms.
This system creates directional airflow, which draws air into the
animal room from “clean” areas and toward “contaminated” areas.
d The exhaust air is dispersed away from occupied areas and from
building air intake locations or the exhaust air is HEPA-filtered.
e The ABSL-3 animal facility is designed such that under failure
conditions the airflow will not be reversed at the containment barrier.
Alarms are considered to notify personnel of ventilation and HVAC
system failure.
6 Cages are decontaminated prior to removal from the containment barrier
and prior to washing in a mechanical cage washer. The cage wash area
is designed to accommodate the use of high-pressure spray systems,
humidity, strong chemical disinfectants, and 180°F water temperatures
during the cage/equipment cleaning process.
7 BSCs and other primary containment barrier systems are installed and
operated in a manner to ensure their effectiveness. See Appendix A.
a BSCs are installed so that fluctuations of the room air supply and
exhaust do not interfere with proper operations. BSCs are located
away from doors, windows that can be opened, heavily traveled
areas, and other possible airflow disruptions.
b BSCs can be connected to the animal facility exhaust system by
either a canopy connection (Class IIA only) or directly exhausted to
the outside through a hard connection (Class IIB, IIC, or III). Class
IIA or IIC BSC exhaust can be safely recirculated back into the
animal facility environment if no volatile toxic chemicals are used in
the cabinet.
c BSCs are certified at least annually to ensure correct performance,
or as specified in Appendix A, Part 7.
d Class III BSCs are provided supply air in such a manner that
prevents positive pressurization of the cabinet or the animal room.
8 Equipment that may produce infectious aerosols is contained in primary
barrier devices that exhaust air through HEPA filtration, or other equivalent technology, before
being discharged into the animal facility. These HEPA filters are tested annually and replaced as
needed.
9 All vacuum lines are protected with HEPA filters, or their equivalent, or
are capped. Vacuum lines in use are protected with liquid disinfectant
traps and in-line HEPA filters or their equivalent. See Appendix A, Figure
11. Filters are replaced, as needed, or are on a replacement schedule
determined by a risk assessment. The placement of an additional HEPA
filter immediately prior to a central vacuum pump is considered.
10 An autoclave is available within the containment barrier. The autoclave is utilized to
decontaminate infectious materials and waste before moving these materials to the other areas
of the facility. If not within the containment barrier, special practices are developed for the
transport of infectious materials to designated alternate locations for decontamination. A
validated alternative process (e.g., alkaline digestion, incineration) may be used for
decontamination and disposal of carcasses.
11 The ABSL-3 facility design, operational parameters, and procedures are
verified and documented prior to operation. Facilities are tested annually
or after significant modification to ensure operational parameters are
met. Verification criteria are modified as necessary by operational
experience.
12 Enhanced environmental and personal protection may be necessary
based on risk assessment and applicable local, state, or federal regulations. These enhancements
may include one or more of the following: an anteroom for clean storage of equipment and
supplies with dress-in, shower-out capabilities; gas-tight dampers to facilitate animal room
isolation; final HEPA filtration of the animal room exhaust air; animal room effluent
decontamination; containment of other piped services; or advanced access control devices, such
as biometrics.
www.cornerstonecx.com
Performance Verification Plan Univ of Kentucky
HSRB 4th floor BSL-3
Lexington, KY
https://www.cdc.gov/labs/BMBL.html
Compliant? Comments/Notes
The following items are from the CDC/NIH Biosafety in Microbiological and Biomedical Laboratories (BMBL) 6th Edition guidelines and how the facility meets or exceeds them.
Biosafety in Microbiological and Biomedical Laboratories (BMBL) - 6th Edition - June 2020
Section V—Vertebrate Animal Biosafety Level Criteria for Vivarium Research Facilities
Animal Biosafety Level 3
D. Animal Facilities (Secondary Barriers) (page 94)
Compliant? Comments/Notes
A.8,
pg 89 A sign is posted at the entrance to the animal room when infectious agents are present. Posted
information includes: the universal biohazard symbol, the room’s Animal Biosafety Level, the
supervisor’s or other responsible personnel’s name and telephone number, PPE requirements,
general occupational health requirements (e.g., immunization, respiratory protection), and
required procedures for entering and exiting the animal room. Agent information is posted in
accordance with the institutional policy.
Compliant? Comments/Notes
CCx-1An eyewash station must be readily available in the laboratory and meets ANSI Z358.1-
2009.Water is between 60-100 deg F for the 15 minute wash cycle.CCx-2 Is there a dedicated air handler for ABSL-3 supply air?
CCx-3Is there a means of isolating the ABSL-3 supply air? This can be done at the common trunk
or at the zone level.
CCx-4
A method for decontaminating all laboratory wastes should be available in the facility,
preferably within the laboratory (e.g., autoclave, chemical disinfection, incineration, or
other validated decontamination method).
CCx-5
Any HEPA filter housing for the BSL-3 needs to have an injection, upstream, and
downstream (scanning) port to allow for scan testing.
(Ensure appropriate duct length is available to meet upstream and downstream
requirements for the test.)
The following items are based on Cornerstone Commissioning Animal Biosafety Level Three (ABSL-3) laboratory commissioning experience.
Item
Other Sections (A-C)
www.cornerstonecx.com
Univ of Kentucky – HSRB – 4th floor BSL-3
PV Report - 2021
www.cornerstonecx.com
Corrective Action Plan
Corrective Action PlanPrint date: 2021-08-10
University of Kentucky, HSRB 4th floor BSL-3
Lexington, KY
Project #: 1929
Item # System or Device Problem, Issue, Root Cause Effect/Impact Responsible Party Solution Updates / Actions Taken Status
1 Fume hood in 464FIf this is not required for the planned research, recommend
removing from the lab.
Facility
PerformanceUniv of Kentucky
Remove fume hood.OPEN
2Biosafety Cabinets
(BSC)
All six (6) of the BSCs are out of certification.
These are older models, the manufacture may not support
these models anymore, repair parts and filters may be difficult
to source.
Equipment
OperationUniv of Kentucky
Recommend consulting with research team on requirements
for BSCs in the BSL-3 for size and quantity needed.OPEN
3Exhaust duct
construction
Observed the main exhaust duct trunk is welded stainless steel
from the exhuast fans and HEPA housing on the roof to the
Phoenix valve in the lab. After the Phoenix valve, the ductwork
is spiral/square galvanized, then metal flexible duct
connections to the grilles.
Galvanized is prone to corrosion from decontamination agents.
Flexible duct work is leaky.
Facility
PerformanceUniv of Kentucky
Recommend hard duct connections from the Phoenix valve to
the grilles.
Consider replacing the galvanized and flexible ductwork.
OPEN
4
Bag In Bag Out
Enclosure, HEPA
filters on the main
exhaust
HEPA filters are out of certification.
Industry
GuidelineUniv of Kentucky
Test and certify the HEPA filters according to industry
guidelines.OPEN
5
Bag In Bag Out
Enclosure, HEPA
filters on the main
exhaust
No isolation dampers on inlet and outlet, decontamination
ports, or test ports.
This can make decontaminating, replacing and
testing/certification difficult.
Industry
GuidelineUniv of Kentucky
Consider replacing the HEPA housing.
OPEN
6 AutoclaveThe autoclave is not operational. Industry
GuidelineUniv of Kentucky
Replace the autoclave. OPEN
7 Autoclave
The autoclave is not ideally situated in the layout of the
laboratory. The service side is located inside of containment,
any maintenance personnel will have to gown up to service the
autoclave. Any tools and equipment would have to be
decontaminated when done.
Maintenance Univ of Kentucky
If a layout change is planned, consider making room large
enough to work on the autoclave.
OPEN
8Room Pressure
Monitors (RPM)
The DP readout panel in the corridor, all of the values
displayed are off by a factor of ten (10).
Example:
464G/464H
Display = -0.50" wc
Measured value = -0.05" wc
Facility
PerformanceUniv of Kentucky
Make all corrections that were identified.
OPEN
9Room Pressure
Monitors (RPM)
The following RPM are installed on the wrong side of the door.
RPM should be located on the clean side, so personnel
entering the lab can verify they have proper directional airflow.
464G/464F (inside F)
464G/464L (inside L)
Facility
PerformanceUniv of Kentucky
Discuss if this is a problem or not.
OPEN
10Room Pressure
Monitors (RPM)
The Air Monitor Corp/Sentry RPM display values are in feet per
minute (FPM), typically these are in inches of water column ("
wc). But, if the lab personnel are trained to look for FPM, this
may not be an issue.
Facility
PerformanceUniv of Kentucky
Discuss if this is a problem or not.
OPEN
www.cornerstonecx.com
Corrective Action PlanPrint date: 2021-08-10
University of Kentucky, HSRB 4th floor BSL-3
Lexington, KY
Project #: 1929
Item # System or Device Problem, Issue, Root Cause Effect/Impact Responsible Party Solution Updates / Actions Taken Status
11Room Pressure
Monitors (RPM)
Some of the RPM are piped to monitor the pressure across
multiple doors, this can be an alarming issue if the doors are
propped open or do not close all the way, they will not alarm in
the current configuration unless there is a complete loss of
exhaust to the whole laboratory.
Ante room 464 / Airlock / Lab 464G
Ante room 464 / Locker 464A / Decon 464D
Ante room 464 / Locker 464Q / Decon 464M
Facility
PerformanceUniv of Kentucky
Discuss if this is a problem or not.
OPEN
12Room differential
pressure setup
Typically BSL-3 room differential pressures (DP) are setup to
have a value between -0.03 to -0.09" wc across each door, the
mid value that most aim for is -0.05" wc.
See FPT - Room Pressures, section 1.4 for more details.
Facility
PerformanceUniv of Kentucky
Make adjustments to room airflows to achieve desired room
pressures.
Suggest hiring test and balance (TAB) contractor to confirm all
airflows.
OPEN
13Room differential
pressure setup
The Air Monitor Corp/Sentry RPM - The visual and/ or audible
alarms are not setup or working properly.
See FPT - Room Pressures, section 1.4 for more details.
Facility
PerformanceUniv of Kentucky
Make all corrections that were identified.
OPEN
14 Door hardwareThe door between Decon 464M and Lab 464L does not close
and latch on its own.
Facility
PerformanceUniv of Kentucky
Perform maintenance on all door hardware.OPEN
15Secondary
Containment Barrier
Correct all items in the Room Integrity Test Report (FPT section
1.7).Facility
PerformanceUniv of Kentucky
Make all corrections that were identified.
OPEN
16Secondary
Containment Barrier
Small dings in walls should be repaired, re-painted; examples:
Airlock, decon D/M, anteroom, AHR H/J, Lab F/L/G.Facility
PerformanceUniv of Kentucky
Make all corrections that were identified.
OPEN
17Secondary
Containment Barrier
Cleanliness of whole lab; floors, walls, ceiling, devices (exhaust
grilles, sinks, eye wash, toilet, etc) should be cleaned before
BSL-3 work is conducted.
Facility
PerformanceUniv of Kentucky
Clean the entire laboratory.
OPEN
18 Temperature control
The temperature control of some of the spaces does not
appear to be able to meet setpoint.
Some of the sensors (discharge air) are beyond the range or do
not appear to be indicating correctly.
The reheat valve (HWV on BAS gfx) does not appear to be
indicating correctly, according to the discharge air temp.
See FPT - Temp & RH sensor, section 1.8 for more details.
Facility
PerformanceUniv of Kentucky
Troubleshoot and make all corrections required.
OPEN
19 Graphics
There are rooms missing or incorrect values listed on the
Building Automation System (BAS) graphics (gfx).
See FPT - Temp & RH sensor, section 1.8 and airflow, section
1.15 for more details.
Facility
PerformanceUniv of Kentucky
Make all corrections that were identified.
OPEN
20 Hands free sinksBatteries need to be replaced and operation confirmed in the
following rooms: 464F, 464J, 464L.
Facility
PerformanceUniv of Kentucky
Replace batteries.OPEN
21 Floor drains
The following spaces have floor drains;
They need to be cleaned of dirt/hair/debris: 464J, 464L
These should be capped: 464G (quantity of two).
Facility
PerformanceUniv of Kentucky
Perform maintenance on all floor drains.
OPEN
22Animal Watering
System
Room 464J has abandoned animal watering system (AWS). Facility
PerformanceUniv of Kentucky
If this is not in use, suggest removing all equipment, cap
utilities and patch all holes. OPEN
23Light fixtures and
bulbs
Room 464L appears to have some light bulbs out. Facility
PerformanceUniv of Kentucky
Before BSL-3 is used, recommend replacing all of the light
bulbs in the facility.OPEN
www.cornerstonecx.com
Corrective Action PlanPrint date: 2021-08-10
University of Kentucky, HSRB 4th floor BSL-3
Lexington, KY
Project #: 1929
Item # System or Device Problem, Issue, Root Cause Effect/Impact Responsible Party Solution Updates / Actions Taken Status
24 Light switches
Animal holding rooms - There are two (2) light switches
located in 464G.
464J - Both switched are red (emer generator power?), right
switch controls left two light fixtures, left switch controls right
two light fixtures.
464H - Red (left) and grey (right), left switch controls left two
light fixtures, right switch controls right two light fixtures.
Facility
PerformanceUniv of Kentucky
Why are these different?
Do the window light panes require red film?
OPEN
25 Door material
The doors in the facility are wood, and due to their age most
have dings, cracks, and chunks missing. This material is porous
and hard to decontaminate.
Recommend replacing all doors in the facility.
Cleanability Univ of Kentucky
Replace doors with non porous type.
OPEN
26 Door hardwareThe door between Decon 464D and Locker 464A, the handle
gets stuck down after use.
Facility
PerformanceUniv of Kentucky
Perform maintenance on all door hardware.OPEN
27 Access controlThe occupancy sensor in 464, will unlock the door, is this a
security concern?
Facility
PerformanceUniv of Kentucky
Discuss if this is a problem or not.OPEN
28Isolation dampers,
supply and exhaust
During testing, observed that some of the isolation dampers
do not block air from AHU or exhaust fan.
Tested multiple times, with associated supply and exhaust
open and closed, same results.
Could be not closing all the way, or the gasket material is
compromised, but the isolation dampers are not completely
closing off when commanded closed.
Equipment
OperationUniv of Kentucky
Investigate why these dampers are not functioning. Make
repairs as necessary.
OPEN
29Isolation damper
control panel
Panel in 464G, during testing noted the following:
464H, supply damper 7 - switch is backwards in panel, switch
closed = damper open, switch open = damper closed.
464J, supply damper 8 - When switch was closed, green light
stayed on indicating open, mag gauge changed from 0.0" to
0.5".
464F, exhaust damper C - closed/ decon red light burned out,
not illuminated when in closed position.
Equipment
OperationUniv of Kentucky
Make all corrections that were identified.
OPEN
30Purge key switch
function
The Purge key switch in Corridor 400N, how does this
function?
I was not able to test this.
Equipment
OperationUniv of Kentucky
Will it still be required?
OPEN
31 AHU failure test
During this test, found issues with BAS programming and VFD
settings. Eric Hess has list of items that need to be corrected. Facility
PerformanceUniv of Kentucky
Make all corrections that were identified.
OPEN
32 Exhaust fan (EF-1)
This fan bearings should be checked, while in operation sounds
like the bearings are in need of replacement.
Both fans may be past their service life.Maintenance Univ of Kentucky
If fans are replaced, this is a non issue.
OPEN
33Exhaust fan
performance
Both fans run 100% all the time, on motor starters. When one
fan fails, the rooms go less negative than normal or go neutral.
There is no redundancy in this system.
Facility
PerformanceUniv of Kentucky
Replace fans that will provide redundancy.
OPEN
34 Power failure test
The BAS network controller / JACE (Java Application Control
Engine) is not on UPS, during power failure events the BAS
cannot see what is happening with equipment serving the BSL-
3.
Facility
PerformanceUniv of Kentucky
Add UPS to all critical controllers.
OPEN
www.cornerstonecx.com
Corrective Action PlanPrint date: 2021-08-10
University of Kentucky, HSRB 4th floor BSL-3
Lexington, KY
Project #: 1929
Item # System or Device Problem, Issue, Root Cause Effect/Impact Responsible Party Solution Updates / Actions Taken Status
35 Control system
Older BAS equipment, (micro zone, Barber-Coleman). There
are no companies that will support these older controllers and
there are no longer replacement parts.Maintenance Univ of Kentucky
Update control system for exhuast fans and room controls
(airflow control, pressure monitoring, temperature control,
alarming, trending, graphics, etc.)OPEN
36Laboratory vacuum
system
BMBL 6th, D, 8.
Millipore disc HEPA filter on the turrets. Unsure if this is tied
into building system or if it is independent of non-BSL-3 areas. Industry
GuidelineUniv of Kentucky
Recommend point of use vacuum units, which can be located
inside the BSC.
(CAP #36)
https://www.welchvacuum.com/en-us/piston-pumps/piston-
pump-wob-l-2534
OPEN
37 Laboratory equipment
BMBL 6th, D, 11.
What equipment that may produce aerosols will be needed by
research team?
Industry
GuidelineUniv of Kentucky
Identify equipment needed and ensure the equipment has
safety mechanisms to minimize risks. OPEN
38Decontamination of
large quipment
BMBL 6th, D, 11.a.
How would a freezer, BSC, or other large piece of equipment
be decontaminated and removed?
Industry
GuidelineUniv of Kentucky
If a layout change is planned, consider making room large
enough to decon equipment. OPEN
39Communication
equipment
BMBL 6th, D, 16.
No phones inside the laboratory spaces.Industry
GuidelineUniv of Kentucky
Add phones inside labs.
OPEN
www.cornerstonecx.com
Univ of Kentucky – HSRB – 4th floor BSL-3
PV Report - 2021
www.cornerstonecx.com
Facility Performance Tests and Data
Facility Performance Tests University of Kentucky
HSRB 4th floor BSL-3
Lexington, KY
Project #: 1929
Rev # Issue Date Issued By / Initials Revision Description1 2021-07-19 Cornerstone Cx / AT Initial Draft
Test # Test Date Performed By Test Description1 2021-07-26 Cornerstone Cx / DC
2 2021-07-27 Cornerstone Cx / DC3 2021-07-28 Cornerstone Cx / DC
Instrument Type Calibration DateMicromanometer Dec 2020
Temp and RH meter Dec 2020
IR temp (gun) N/A
Smoke bottle N/A
Electrical Circuit Tester N/A
1.0 Test Purpose
The purpose of this facility performance test is to verify and document that all of the systems that serves the BSL-3 space are in
good working order. This includes; electrical, plumbing, HVAC, building automation, security, access control and primary
containment equipment.
Document Control
Test Control
Test Equipment
Manuf/Model
Fluke 922
BK Precision 720
Fluke IR temp gun
Regin FPKlein/ Ideal
www.cornerstonecx.com
Facility Performance Test University of Kentucky
HSRB 4th floor BSL-3
Lexington, KY
1
2
3
Room# BSC Tag# BSC Type Make Model S/N Certifier Cert Due 1 2 3 Notes
464F Fume hood N/A Hamilton Safe Aire N/A N/AExpired Sep
2016N/A N/A N/A 1
464F 464F Class II Type B2 Labconco 36210 268088Precision Air
Technology
Expired Sep
2016Yes Yes N/A 1
464H A 613226Class II Type A2,
recirculatingLabconco 3621204 DELTA 011218476F
Precision Air
Technology
Expired Oct
2019Yes Yes N/A
464J A 568783Class II Type A2,
recirculatingLabconco 36212-04 AC 706229
Precision Air
Technology
Expired Sep
2016Yes Yes N/A
464J A 665623Class II Type A2,
recirculatingNuAire NU-425-400 111024112806
Precision Air
Technology
Expired Sep
2016Yes Yes N/A
464L N/AClass II Type A2,
recirculatingLabconco 362080413281 061062103 AD
Precision Air
Technology
Expired Oct
2019Yes Yes N/A
464L N/AClass II Type A2,
recirculatingLabconco 362080413281 061062105 AD
Precision Air
Technology
Expired Sep
2016No No N/A 2
1
2
CDC/NIH Biosafety in Microbiological and Biomedical Laboratories (BMBL) Appendix A – Primary Containment for Biohazards: Selection,
Installation and Use of Biological Safety Cabinets
NSF/ANSI Standard 49 – 2014, Biosafety Cabinetry: Design, Construction, Performance, and Field Certification.
NSF/ANSI Standard 49-2014 - Memo dated Oct 15, 2015: to be fitted with an Airflow Monitor that provides a visual and audible alarm.
Reference:
Grey outlet, others plugged into red outlets, not sure if grey is Epower, cant see tag / label behind BSC
Planning to be removed and replaced
1.1 - Biosafety Cabinet (BSC)
Record the information for the Biosafety Cabinet (BSC) which is the primary containment equipment for the BSL-3.
Biosafety cabinet (BSC) - Primary Containment
Notes
Certification sticker in place on BSC? (yes/no)
Plugged into Emergency power panel/ circuit or UPS power outlet? (yes/no)
Alarm (audible and visual) functions? (yes/no)
www.cornerstonecx.com
Facility Performance Test University of Kentucky
HSRB 4th floor BSL-3
Lexington, KY
HEPA
Housing tag
#
Make Model S/N ServesPre
filter DP
HEPA
filter DP
Certification
sticker in place?Certifier:
Certification
Due:Notes
FF-2 AAF/Flanders
Bag In/ Bag Out
Enclosure, 2 High
by 2 Wide, Pre and
HEPA filter housing
444-777 BSL-3 / EF-1 N/A 0.3 ExpiredPrecision Air
Technology
Cannot read
sticker info
FF-2 AAF/Flanders
Bag In/ Bag Out
Enclosure, 2 High
by 2 wide, Pre and
HEPA filter housing
444-777 BSL-3 / EF-2 N/A 0.6 ExpiredPrecision Air
Technology
Cannot read
sticker info
IEST-RP-CC-006.3-2004
Notes
1.2 - Biosafety equipment
Record the information for the High Efficiency Particulate Air (HEPA) filter housing
High Efficiency Particulate Air (HEPA) Housing
Reference:
IEST-RP-CC002.4
www.cornerstonecx.com
Facility Performance Test University of Kentucky
HSRB 4th floor BSL-3
Lexington, KY
Cycle Name Pressure (psi)Temperature
(°C)Duration (min) Cool down (min)
Review Biological Indicator (BI) log book
Frequency of BI runs Results show positive kill?
Unit temp and
pressure tape
readout is legible?
Door interlock
functions?
Datalogger results
match unit tape
readout and cycle
parameters?
Attach copy/ photo of
BI log book page (most
recent)
Attach copy/ photo of autoclave tape
readout (most recent)
Attach data logger
graph for temp and
pressure with tape
read out for cycle
tested
Unit / Tag # Data analysis Temperature (°C) Pressure (psi)
Max value
Count > or = (in minutes )
Count threshold value
1.3 - Autoclave
Cycle parameters
Notes
Inoperable, needs to be replaced, recommend installing so it can be worked on without going into containment, in the ante room
www.cornerstonecx.com
Facility Performance Test University of Kentucky
HSRB 4th floor BSL-3
Lexington, KY
Room Name Room # Room Name Room #RPM goes
to zero?Test the room DP alarm
Corridor 400N → Ante 464 N/A N/A -0.047 Yes N/A N/A
Ante Room 464 → Airlock - -0.446 -559 FPM -0.013 Yes -490 FPM no alarmstays negative, monitor piped across multiple
doorsAirlock - → Lab 464G N/A N/A -0.02 Yes N/A N/A
Lab 464G → Lab 464F 0.588 +649 FPM -0.051 Yes +200 FPMVisual, change from Normal
(green) to Caution (yellow)
RPM is on wrong side of door, F, should be in G.
Sentry RPM is set for a positive room, always in
caution.
Lab 464G → AHR 464H -0.288 -470 FPM -0.035 Yes +258 FPMRed, alarm, visual only,
after 60 sec
Lab 464G → AHR 464J -0.962 -1134 FPM -0.14 Yes 126 FPMRed, alarm, audible and
visual after 60 sectoo neg
Lab 464G → Lab 464L 0.511 588 FPM -0.019 Yes 0 FPMVisual, change from Normal
(green) to Caution (yellow)
RPM is on wrong side of door, L, should be in G.
Sentry RPM is set for a positive room, always in
caution.Decontam 464D → Lab 464F -0.511 -704 FPM -0.055 Yes -130 FPM Caution light only
Decontam 464M → Lab 464L -0.61 -692 FPM -0.055 Yes 0 FPMRed, alarm, audible and
visual after 60 sec
Ante Room 464 → Locker 464A -0.563 -682 FPM -0.01 Yes -579 FPM no alarmstays negative, monitor piped across multiple
doorsLocker 464A → Decontam 464D N/A N/A -0.025 Yes N/A
Ante Room 464 → Locker 464Q -0.349 -412 FPM 0.006 Yes -418 FPM no alarmstays negative, monitor piped across multiple
doors, M not Q on corr displayLocker 464Q → Decontam 464M N/A N/A -0.013 Yes N/ALocker 464A Neutral Toilet 464B N/A N/A 0 Yes N/ALocker 464Q Neutral Toilet 464P N/A N/A 0 Yes N/A
Sentry RPM, has room status (normal=green, cuation=yellow, alarm=red)CAUTION 1-2
The values on the panel in corridor 400N, off by factor of 10, example, shows -0.50", actual is -0.050".
1.4 - Room Pressures
Perform the following:
1. Verify that all doors are closed in the BSL-3
2. Record the values from the Room Pressure Monitor (RPM) and BAS graphics.
3. Using a micromanometer (Fluke 922) measure the room pressure.
4. Verify the polarity of the readings with a smoke bottle.
5. Open the door to the space and verify that the RPM and BAS indicates 0.00".
6. Leave door open and verify that the room DP / door open alarm functions. Note the time it takes once the RPM reads 0.00" for the alarm to activate.
Notes
?
Reference
(Low -)
To
(High +)
?
Custom High limit?Custom Low limit?Alarm trip pointAlarm delay time
RPM setup???
CCx
Verify
polarity
with
smoke?
With door open
Manufacturer:Model:
Corr
display
Room
Pressure
Monitor
Airflow
Direction
Sentry
Room
Pressurizati
on Monitor
Range:
Air Monitor Corporation / CustomSentry
Room Pressure Monitor (RPM) info
BAS interface?
?
www.cornerstonecx.com
Facility Performance Test University of Kentucky
HSRB 4th floor BSL-3
Lexington, KY
1.4 - Room PressuresFloorplan for reference:
www.cornerstonecx.com
Facility Performance Test University of Kentucky
HSRB 4th floor BSL-3
Lexington, KY
Top Middle Bottom
Corr 400N → Ante Room 464 → → Neutral Yes
Ante Room 464 → Locker 464A → → → Yes
Ante Room 464 → Locker 464Q → → ← Yes
Ante Room 464 → Airlock - → ← → Yes
Airlock - → Lab 464G → → ← Yes
Locker 464A → Decontam 464D → → → Yes
Decontam 464D → Lab 464F → → ← Yes 1
Locker 464Q → Decontam 464M → → → Yes
Decontam 464M → Lab 464L See note See note ← No 2
Lab 464G → Lab 464F → → → Yes
Lab 464G → Animal Room 464H Neutral Neutral → Yes
Lab 464G → Animal Room 464J Neutral → → Yes
Lab 464G → Lab 464L → → → Yes
Notes
1 - temp diff, cooler in F
2 - temp diff, cooler in L, sup diff above door in L blowing air down
1.5 - Directional AirflowThe purpose of this test is to verify that there is directional airflow not only when the doors in the BSL-3 containment barrier are
closed, but also when the doors are opened.
Factors that can effect these results are temperature control between spaces, location of supply and exhaust diffusers and
registers, etc. May need to increase the offset for the zone to correct issues.
Test Procedure:
1. If door opens into the higher risk area, stand inside higher risk space, outside path of air and verify airflow direction with smoke
bottle. If door opens into the lower risk area, stand inside higher risk space, outside path of air and verify airflow direction with
smoke bottle. It is important to try and minimize the effect your body will have on the turbulence of the airflow.
2. Try to get as close to the plane of the door closed position, not where the door travel path is.
3. Test at the bottom, middle, then top of the door plane area. Note any reversals.
Reference Direction ToDoor plane area Does the door close
and latch on its own?Notes
www.cornerstonecx.com
Facility Performance Test University of Kentucky
HSRB 4th floor BSL-3
Lexington, KY
1.6 Test Procedure
1Room under negative pressure, meaning HVAC systems; AHU, EF, air terminal devices under normal
operation at design conditions. Record the room DP values if different than section 1.4.
2
Using smoke generating device (smoke bottle, low volume), check all room penetrations, including but not
limited to: Plumbing, life safety, BAS, electrical, telecom, seams and joints (including dissimilar materials
and material transitions).
3Document all room integrity issues in the test report section (section 1.7), email to all parties. Use blue
painters tape to identify all issues in the rooms.
4 After repairs are made by owner staff/contractors, back check and update test report
5
Upon completion of all Integrated Systems Tests (IST), perform a visual inspection to confirm the secondary
containment barrier has not been compromised.
ISTs involve the failure of the HVAC and electrical systems. This can stress the sealing of the space
penetrations due to momentary, higher than normal room pressures.
1.6.1 Requirements for all sealing
Finishes, penetrations & caulking integrity for architectural elements such as door frames, around the
ceilings, lighting fixtures, electrical devices, etc. within containment to meet requirements for:
Clean-ability of all surfaces including furniture,
Smoothness of all surfaces,
Sealed seams and penetrations,
Monolithic, slip resistant floors,
Surface impermeability to liquids,
Resistance of surfaces to chemical (organic solvents, acids, alkalis), disinfectants and moderate heat,
Gas tightness for decontamination,
Pest management requirements,
Non-operable windows,
Bioseals.
1.6.2 Sealant type
NIH DRM, Appendix L – Sealant table
https://www.orf.od.nih.gov/TechnicalResources/Documents/DRM/DRM1.503262020.pdf
Refer to facility construction drawings and specifications
www.cornerstonecx.com
Facility Performance Test University of Kentucky
HSRB 4th floor BSL-3
Lexington, KY
Room Name Room # Leak # Description of leak or integrity issue Repaired?
Ante 464 1 Supply diffuser has come away from ceiling. Diffuser is rusty
Ante 464 2 Door kick plate to 464Q is rusty
Ante 464 3Corner of vynil flooring by door frame to ante room, bottom right coming away,
open to concrete
Ante 464 4 Ceiling paint bubbling and cracking between supply diffuser and access panel.
Ante 464 5 Crack in ceiling by corner of access panel, marked VV, corner by A and corridor
Locker 464A 6 Ceiling paint bubbling and cracking between supply diffuser and access panel.
Locker 464A 7 Door that was removed, the door frame, hinges (3) and latch not sealed, leaks
Locker 464A 8 Light fixture leaks in room to D, recessed circular
Locker 464A 9Wood board mounted behind metro rack and plastic cabinet, not treated,
pourous, will be hard to decontaminate
Toilet 464B 10 Sink plumbing escutcheons sealing pulling away from wall
Toilet 464B 11 Toilet seal to wall, on bottom, no caulking/ gap
Decontam 464D 12 Electrical outlet leaks, by wall wire rack and door to F
Decontam 464D 13 Paint peeling and cracking by access panel in ceiling, close to shower
Decontam 464D 14 Access panel has metal tape, compromised seal?
Lab 464F 15 Fire alarm annunciator leaks, dirt trace visible on wall
Lab 464F 16 Emergency shower pull handle is rusty, ceiling penetration leaks
Lab 464F 17 Electrical outlet leaks, behind freezer, on wall by D
Lab 464F 18 Light switch leaks, by door to G
Lab 464F 19 Electrical outlets under cabinets, above work bench sink (3 total) leak
Lab 464F 20Area under the sink, connected to ceiling wall above? Can feel airflow, smoke
movement.
Lab 464F 21 Crack in ceiling, corner by windows, on right side
Lab 464F 22Crack in caulking on aluminum window frame and ceiling joint, middle, corners,
side areas. Top window and bottom window joints should be re-sealed.
Lab 464F 23 Area under and behind the fume hood, can feel airflow, smoke movement.
Lab 464F 24Wall paneling (wainscoating) by door to D and behind BSC B2, not sealed, seems
pourous
Lab 464G 25 Light switch leaks, by door to airlock
Lab 464G 26
Steam lines, multiple, on wall to airlock and ante room have peeling paint,
insulation coming apart, capture hood ceiling penetration has gaps, bioseal to
airlock has some gaps to wall, compressed air line ceiling pentration leaks,
recommend installing autoclave on the ante room side, so it can be serviced
outside of the BSL-3, lab G
Lab 464G 27 Screws missing in cover for the time clock for the lighting control for room H.
Lab 464G 28Floor seam by airlock has come apart, also corner on wall to airlock has come
apart, both need to be re-sealed, open to concrete.
Lab 464G 29 Paint peeling and cracking by access panel in ceiling, close to L
Lab 464G 30
Some of the access panels are missing hardware to keep them closed,
compromised seal, metal tape used to seal them. Recommend investigating
replacing.
Animal Room 464H 31 All 4 walls have cracking and peeling of paint
1.7 - Room Integrity Test Report
www.cornerstonecx.com
Facility Performance Test University of Kentucky
HSRB 4th floor BSL-3
Lexington, KY
Animal Room 464H 32 Pipe penetration for AWS, from J, leaks, has dirt trace on wall
Animal Room 464H 33 Crack in ceiling between access panel and supply diffuser
Animal Room 464H 34 Supply diffuser is rusty
Animal Room 464H 35Access panel frame has come apart from ceiling, also has metal tape, some
hardware missing to completely close
Animal Room 464J 36 Electrical outlet above sink leaks
Animal Room 464J 37 Electrical outlet behind BSC, by wall to L, low, grey, leaks
Animal Room 464J 38 Electrical outlet behind BSC, by wall to L, high, red, leaks
Animal Room 464J 39Paint peeling and chips missing by access panel, access panel has metal tape, is
this seal working?
Animal Room 464J 40 Crack in ceiling by sprinkler head
Animal Room 464J 41 All 4 walls have cracking and peeling of paint
Lab 464L 42 Light switch by door to G leaks
Lab 464L 43Gaps in conduit ceiling penetrations for the air monitor/Sentry panel, above door
to G
Lab 464L 44Cracks in ceiling by access panel and wall, and to light fixture, above door to G
Lab 464L 45Area under the sink, connected to ceiling wall above? Can feel airflow, smoke
movement.
Lab 464L 46 Emergency shower pull handle ceiling penetration leaks
Lab 464L 47 Wall paneling (wainscoating) by door to M not sealed, seems pourous
Lab 464L 48 Holes need to be sealed, large chip in paint, on wall behind the BSC, close to M
Lab 464L 49Electrical raceway, by door to M, has leaks, can see dirt trace on wall by door
frame
Lab 464L 50 Crack in ceiling between access panel and light fixture, by door to M
Lab 464L 51 Cracks in vynil flooring, by BSC and window
Lab 464L 52Crack in caulking on aluminum window frame and ceiling joint, middle, corners,
side areas. Top window and bottom window joints should be re-sealed.
Lab 464L 53Access panels have metal tape, are the seals not working? Need to be replaced?
Lab 464L 54 Counter shelf, under cabinets, by window, has large gap in caulking, leaks
Decontam 464M 55 Crack in wall to left of door frame to L
Decontam 464M 56 Light switch leaks, by door to L
Locker 464Q 57 Crack in ceiling by back wall close to corridor 400N
Locker 464Q 58 Light fixture leaks in room to M, recessed circular
Toilet 464P 59 Sink plumbing escutcheons sealing pulling away from wall
Airlock - 60Flooring, corners; on right by door to G was repaired, but is pulling away / on left
by door to 464 is pulling away, has large gaps
No room integrity issues found in the following rooms:
Shower 464E, Shower 464N
Small dings in walls should be repaired, re-painted; examples: Airlock, decon D/M, anteroom, AHR H/J, Lab F/L/G
Notes
Cleanliness of whole lab; floors, walls, ceiling, devices (exhaust grilles, sinks, eye wash, toilet, etc) should be cleaned
before BSL-3 work is conducted
www.cornerstonecx.com
Facility Performance Test University of Kentucky
HSRB 4th floor BSL-3
Lexington, KY
BAS CCx BAS CCx BAS CCxAnte 464 65.5/67.5 N/A 76.2 75.4 N/A 55 62 N/A 100.0%Locker 464A 71.1/73.1 N/A 74.9 74.5 N/A 58.8 240.3 N/A 100.0%Lab 464F 69/71 N/A 68.1 68.2 N/A 69.2 62.1 N/A 41.4%Lab 464G 67.9/69.9 N/A 70 70.9 N/A 63.7 67.2 N/A 21.4%Animal Room 464H 79.5/81.5 30/70 71.5 72.7 N/A 60.7 98.1 N/A 40.8%Animal Room 464J 68.4/70.4 30/70 72.4 74.1 N/A 58.6 115.5 N/A 0.0%Lab 464L 81.6/83.6 N/A 68.7 68.7 N/A 69.2 61 N/A 0.0%Locker 464Q (M) 70.5/72.5 N/A 72.5 71.4 N/A 63 Not on gfx N/A 100.0%
Locker 464Q is on the BAS graphics as M.OAT = 85 deg F, OARH = 71%, AHU-2 DAT = 55 deg F, DAH = 72%
Notes
Animal rooms should have RH sensor for monitoring and record keeping purposes.
SensorTemp RH DAT (as found)
HWV closed
(from BAS
gfx)
1.8 - Temperature and Relative Humidity (RH) sensor verification
Record the following:
1. Temp, RH and DAT from the BAS graphics.
2. Using the BK and infrared temp gun, measure the as found/ normal operation values of the temp, RH and DAT.
The temp setpoint in heating mode is listed first, cooling mode is second (example: 68/74) Each mode has a tolerance of
+/- 2 deg F.
Room Name Room #Setpoint
Temp RH
www.cornerstonecx.com
Facility Performance Test University of Kentucky
HSRB 4th floor BSL-3
Lexington, KY
Room Name Room #
Sink hot, cold and
drain functions (if
applicable)
Is the sink hands free?
If yes, how is it
activated?
Eye wash functions?
Emergency
Shower
functions?
Floor drain
Ante 464 N/A N/A N/A N/A N/A
Locker 464A N/A N/A N/A N/A N/A
Toilet 464B Yes Manual N/A Toilet works 4"
Shower 464E Shower, no sink 1 faucet, mixer N/A N/A 3"
Decontam 464D N/A N/A N/A N/A N/A
Lab 464F No, batteries? Yes, electronic eye Yes Did not test 6"
Lab 464G N/A N/A N/A N/A
6" and
autoclave
drain
Animal Room 464H Yes Yes, electronic eye Yes N/A 5", clogged
Animal Room 464J No, batteries? Yes, electronic eye No N/A 5", clogged
Lab 464L No, batteries? Yes, electronic eye Yes Did not test 6"
Locker 464Q N/A N/A N/A N/A N/A
Shower 464N Shower, no sink 1 faucet, mixer N/A N/A 3"
Decontam 464M N/A N/A N/A N/A N/A
Toilet 464P Yes Manual N/A Toilet works 4"
Air Lock - N/A N/A N/A N/A N/A
List chemical used
464F, 464J and 464L, electronic eye not functioning
464J has AWS on wall, not used, remove all equip, patch holes, cap service lines
Where do the floor drains go? How is it treated?
Hose bib in room: 464B, 464P (toilet)
Describe how the liquid water waste is treated at sink drains
1.10 - Plumbing and Life Safety
Test procedure (As applicable) :
1. Verify that the hot and cold water lines are piped correctly at all sinks, that the sink drains properly, and there are no leaks.
2. Verify that the eye wash water is at the desired temperature (~85 deg F), it is clean and clear (no residue), can sustain the required duration
(10 min) for the flush time.
3. Verify that the emergency shower is at the desired temperature (~85 deg F), it is clean and clear (no residue), can sustain the required
duration (10 min) for the flush time.
Notes
Brandy stated that the batteries need to be changed on the sink eye, was a bi monthly maintenance item
Liquid Waste Treatment
www.cornerstonecx.com
Facility Performance Test University of Kentucky
HSRB 4th floor BSL-3
Lexington, KY
Room Name Room #Outlets
Function?
GFCIs
Function?
Light
Fixture
Qty:
Bulbs per
fixture:
All
fixtures
working?
Switches
Functional?
Lighting
Control
System?
Notes
Ante 464 Yes N/A 1 6 Yes Yes N/A 1
Locker 464A Yes N/A 1 2 Yes 1 sw, yes, red N/A
Toilet 464B Yes Yes 1 2 Yes 1 sw, yes, red N/A
Shower 464E Yes N/A 1 2 Yes 1 sw, yes, red N/A 2
Decontam 464D N/A N/A 2 1 Yes 1 sw, yes, red N/A
Lab 464F Yes N/A 4 2 or 3 Yes 1 sw, yes, red N/A
Lab 464G Yes Yes 2 2 Yes 1 sw, yes, red N/A
Animal Room 464H Yes N/A 4 3 Yes2 sw, yes, 1 red
(left), 1 grey (right)
Yes, Tork
time clock in
464G
3
Animal Room 464J Yes N/A 4 3 Yes2 sw, yes, both are
red
Yes, Tork
time clock in
464G
4
Lab 464L Yes N/A 4 2 or 3 Yes 1 sw, yes, red N/A 5
Locker 464Q Yes N/A 1 2 Yes 1 sw, yes, red N/A
Shower 464N Yes N/A 1 2 Yes 1 sw, yes, red N/A 2
Decontam 464M N/A N/A 2 1 Yes 1 sw, yes, red N/A
Toilet 464P Yes Yes 1 2 Yes 1 sw, yes, red N/A
Air Lock - N/A N/A 1 2 or 3 Yes 1 sw, yes, red N/A 5
N/A N/A 1 1 Yes 1 sw, yes, red N/A 6
N/A N/A 1 1 Yes 1 sw, yes, red N/A 6
Room between A and D
Room between Q and M
1 - Pendant (hanging fixture)
2 - waterproof cover on switch
3 - Switches located in 464G, no red film on window on either window for H or J
Notes
5 - few bulbs may be out
6 - Recessed can, not sealed, can see through
4 - Switches are backwards, left does right bank, right does left bank
1.11 - Electrical
Test procedure:
1. Verify that all electrical outlets in the space have power using circuit tester for 120VAC outlets (open ground, open neutral,
open hot, hot/ground reverse, hot/neutral reverse). If the outlet is a GFCI type, use the test function on the switch to verify that
it is wired correctly.
2. During the power failure test (IST) verify that all electrical outlets and light fixtures that are supposed to be on the electrical
backup emergency generator have power. See electrical drawings for details.
3. Verify that all light bulbs are lit when switched on, switch shuts off all bulbs
www.cornerstonecx.com
Facility Performance Test University of Kentucky
HSRB 4th floor BSL-3
Lexington, KY
Room Name Room #
Do
or
mat
eri
al
Latc
h
Ha
nd
le
Lock
Clo
ser
Flo
or
Swe
ep
Fram
e
Seal
Kic
k P
late
Car
t
Bu
mp
er
Inte
rlo
ck
sid
e d
oo
r?
Lite
?
Notes
Ante Room 464 Metal Yes Yes
Yes, has
manual
inside
Yes No No No No No Yes Yes to corridor 400N
Ante Room 464 Wood Yes YesCore
removedYes No No Yes No No No No to 464A
Ante Room 464 Wood Yes YesCore
removedYes No No Yes No No No No to 464Q
Ante Room 464 Wood Yes YesCore
removedYes No No Yes No Yes Yes Yes to airlock
Airlock - Wood Yes YesCore
removedYes No No Yes No Yes Yes Yes to 464G
Shower 464E Wood N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A two (2) shower curtains
Decontam 464D Wood Yes YesCore
removedYes No No No No No No No to lab 464F
Decontam 464D Wood Yes YesCore
removedYes No No Yes No No No No to locker 464A
Shower 464N Wood N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A two (2) shower curtains
Decontam 464M Wood Yes YesCore
removedYes No No No No No No No to lab 464L
Decontam 464M Wood Yes YesCore
removedYes No No Yes No No No No to locker 464Q
Lab 464G Wood Yes YesCore
removedYes No No No No No Yes Yes to 464 F
Lab 464G Wood Yes Yes Key YesOnly on side
doorNo No No No Yes Yes to 464H
Lab 464G Wood Yes YesCore
removedYes
Only on side
doorNo No No No Yes Yes to 464J
Lab 464G Wood Yes YesCore
removedYes No No No No No Yes Yes to 464L
Locker 464A removed
Locker 464Q removed
1.12 - Architectural - Doors and hardware
Notes
464 - has an occ sensor in front of door to exit to corridor
464D to 464A - door handle in D to A, on D side sticks down
Test procedure (as applicable ):
1. Record the door hardware; latch, handle, lock, closer, floor sweep, frame seal(s), etc.
2. Note any issues with door hardware, is it damaged or not performing?
Toilet 464P - This door stick, hits frame, swell? When you try to open or close
www.cornerstonecx.com
Facility Performance Test University of Kentucky
HSRB 4th floor BSL-3
Lexington, KY
Room Name Room #Access control
typeInterlocked with?
List other security
measures and
equipment
Notes
Ante 464Card reader, PIN
padN/A N/A
Locker 464A N/A N/A N/A
Shower 464E N/A N/A N/A
Decontam 464D N/A N/A N/A
Lab 464F N/A N/A N/A
Lab 464G N/A N/A N/A
Animal Room 464H N/A N/A N/A
Animal Room 464J N/A N/A N/A
Lab 464L N/A N/A N/A
Locker 464Q N/A N/A N/A
Shower 464N N/A N/A N/A
Decontam 464M N/A N/A N/A
Air Lock - N/A
Airlock to 464
interlocked with door
from Airlock to 464G
N/A
1.13 - Access Control & SecurityTest procedure (as applicable ):
1. Verify that the access control (card reader, PIN pad, biometrics scanner, etc.) is setup and functional, by challenging without the
necessary means.
2. Verify which doors are interlocked (cannot be open at the same time) with each other, challenge the door interlock system by
trying to open both doors at the same time.
3. Note any issues with access control and/ or security system, is it damaged or not performing?
www.cornerstonecx.com
Facility Performance Test University of Kentucky
HSRB 4th floor BSL-3
Lexington, KY
Room Room # Tag #
Any issues
closing the
BSD?
Smoke test
passed
when BSD
is closed?
Smoke test
around the
flange of
the BSD to
check for
leaks.
Any issues
opening the
BSD?
No added
flow
restrictions
(in the
open
position)?
Close
time
Mag
gauge
pressure
value
Open
timeNotes
Decon, Locker, Shower 464M, N, Q Supply Damper 1 No No N/A No No 915 1.2" 916
Lab 464L Supply Damper 2 No No N/A No No 918 1.5" 922 Can feel cold air from both diffusers, smoke disappears
Ante 464 Supply Damper 3 No No N/A No No 924 1.0" 925
Lab 464G Supply Damper 4 No No N/A No No 926 1.5" 933
Can feel cold air from both diffusers, smoke shoots down, close then
open exh damper G at 928, then close sup D 4,
Tried closing exh D G, same result
Decon, Locker, Shower 464A, C, E Supply Damper 5 No No N/A No No 935 0.85" 938Tested with exh D open, then closed, air flows out of D diffuser, A
diffuser seems OK
Lab 464F Supply Damper 6 No No N/A No No 941 1.65" 945
AHR 464H Supply Damper 7 No No N/A No No 946 1.25" 951Switch is backwards in panel;
switch closed = damper open, switch open = damper closed
AHR 464J Supply Damper 8 No No N/A No No 952 0.5" 956When switch was closed, green light stayed on indicating open, mag
gauge changed from 0.0" to 0.5".
Locker 464Q Exhaust Damper A No No N/A No No 958 3.1" 1000
Decon, Shower 464M, E Exhaust Damper B No No N/A No No 936 peg, 4"+ 938
Lab 464F Exhaust Damper C No No N/A No No 942 peg, 4"+ 945closed/ decon red light burned out, not illuminated when in closed
position
Lab 464G Exhaust Damper D No Yes N/A No No 930 peg, 4"+ 933 with sup D 4 closed
AHR 464J Exhaust Damper E No No N/A No No 954 peg, 4"+ 956
AHR 464H Exhaust Damper F No No N/A No No 949 peg, 4"+ 951
Lab 464L Exhaust Damper G No No N/A No No 1001 1.25" 1003
See room DP changes from DP array
AHU-2 SASP = 1.5"
Tested multiple times, with associated exh open and closed, same results
Could be not closing all the way, or the gasket material is compromised, but the isolation dampers are not completely closing off when commanded closed.
The Purge key switch in Corridor 400N, how does this function? I was not able to test this.
Description:
Manual Bio Seal Dampers are used to isolate the BSL-3 / ABSL-3 airflows (supply and/ or exhaust) from non-containment areas and equipment. A typical scenario would be during a decontamination of the BSL-3 while the systems
serving the containment spaces are still operational and the non- containment areas are still occupied.
1.14 - Manual / Automatic Bio Seal Damper (BSD) - Isolation Dampers
Test procedure:
1. With all HVAC air systems in normal operation
2. Close the manual BSD
3. Verify that no air is passing by in the room
4. Verify that the connection to the ductwork/flange does not leak
5. Open the manual BSD
Verification method:
a - Flowhood / flow meter (TAB)
b - Smoke generating device
www.cornerstonecx.com
Facility Performance Test University of Kentucky
HSRB 4th floor BSL-3
Lexington, KY
Tag
De
sign
BA
S (fdb
k)
Dam
pe
r
Po
s
Tag #s
De
sign
BA
S (fdb
k)
Dam
pe
r
Po
s
De
sign
BA
S
Ante 464 200 Phx 250 Phx 0 -50Locker 464A 165 Phx 165 Phx 0 0Lab 464F 1051 Phx 829 Phx 0 222Lab 464G 760 Phx 760 Phx 0 0Animal Room 464H 336 Phx 386 Phx 0 -50Animal Room 464J 430 Phx 480 Phx 0 -50Lab 464L 91 Phx 1060 Phx 0 -969Decontam 464M 165 Phx 165 Phx 0 0Shower 464E 0 0Decontam 464D 0 0Locker 464Q 0 0Shower 464N 0 0
Air Lock - 0 0
Toilet 464BToilet 464P
Notes
No data on graphics for 464B, 464E, 464D, 464Q, 464N, 464P and Airlock464L - Supply and exhaust values do not appear to be correct on BAS gfx
1.15 - Airflows (Design CFM from schedule on drawing )
Record the following:
1. Airflow values from the BAS graphics to verify they match the design CFM values.
2. Damper position from the BAS graphics to ensure the device is under control and not operating at 100%
open position.
Room name Room #
Supply Exhaust (Total) Offset
www.cornerstonecx.com
Facility Performance Test University of Kentucky
HSRB 4th floor BSL-3
Lexington, KY
L W HAnte 464 115 141 107 1735005 1728 1004 60 250 14.94Locker 464A 172 88 107 835456 1728 483.5 60 165 20.48Toilet 464B 70 54 107 404460 1729 233.9 60 0.00 1Decontam 464D 239 104 107 876914 1728 507.5 60 0.00 2Lab 464F 251 124 108 3361392 1728 1945 60 1050 32.39Lab 464G 174 459 107 3233433 1728 1871 60 760 24.37Animal Room 464H 126 124 107 1671768 1728 967.5 60 386 23.94Animal Room 464J 126 125 107 1685250 1728 975.3 60 480 29.53Lab 464L 252 118 108 3211488 1728 1859 60 1060 34.22Locker 464Q 172 88 107 835456 1728 483.5 60 0.00 1Toilet 464 70 54 107 404460 1729 233.9 60 250 64.12Decontam 464M 239 104 107 876914 1728 507.5 60 165 19.51 2Air Lock - 49 51 107 267393 1728 154.7 60 0.00 1
INCHES Total
(in3)
in3/ft
3
Total
(Ft3)
Notes
Includes shower areaNo data on graphics for 464B, 464E, 464D, 464Q, 464N, 464P and Airlock
1.16 - Air Changes per Hour (ACH)
The calculated ACH is important to know, example: How long to expect for containment clearance in the event of a spill, or
after a decon of the space.
Perform the following:
1. Record the room dimensions (measure the actual length, height, and width).
2. Note what CFM value was used (supply or exhaust) and from what source (Design, BAS, TAB, etc.).
Typically the highest CFM value should be used.
min/hrBAS fdbk,
airflowACHRoom Name Room # Note
www.cornerstonecx.com
Univ of Kentucky – HSRB – 4th floor BSL-3
PV Report - 2021
www.cornerstonecx.com
Integrated System Tests
(Failure Scenario Testing)
Integrated System Tests University of Kentucky
HSRB 4th floor BSL-3
Lexington, KY
Rev # Issue Date Issued By / Initials Revision Description
1 2021-07-19 Cornerstone Cx / AT Initial Draft
Test Control
Test Session # Test Date Performed By Test Description
1 2021-07-27 Cornerstone Cx / DC IST P1
2 2021-07-28 Cornerstone Cx / DC IST 1, 2, 3
Loss of Normal Electrical Power Service (IST #3)
During a loss of normal electrical power, the automatic transfer switches (ATS) shall detect this loss, and switch
to emergency power generator.
Upon normal power restoration, ATS shall switch back to normal power. During both of these events, the BAS
and HVAC systems will prevent reversals of airflow in the BSL-3.
Document Control
Test Description
This section lists the specific Integrated System Tests (IST) to be performed as required for BSL-3 laboratories.
The ISTs will be performed while monitoring the differential pressure (DP) across all of the doors in the BSL-3
secondary containment barrier.
Steady state operation - Room DP - AHU, EF, air terminal units (IST Pre-test 1)
Confirm that the Supply fans in the Air handling units, the Exhaust fans, and the air terminal units/ air valves (as
applicable) serving the BSL-3 area provide steady room differential pressure (DP), this will confirm that there
are no control tuning issues, with minimal oscillations that could effect the outcome of the failure testing in
IST#1-3.
HVAC systems failure testing (IST #1 and 2)
Simulate failures of the Supply and Exhaust fans serving the BSL-3. During these failure scenarios, the BAS and
HVAC systems will prevent reversals of airflow in the BSL-3 secondary containment barriers.
Introduction
Cornerstone Commissioning, Inc. has developed the following series of Integrated System Tests (IST) to ensure
that Building Automation System (BAS), Mechanical and Electrical systems will prevent reversal of airflows in
the BSL-3 laboratory during failures scenarios described herein to comply with industry standards and
guidelines, including but not limited to; Facility design intent document, The Center for Disease Control (CDC) /
National Institutes of Health (NIH) Biosafety in Microbiological and Biomedical Laboratories (BMBL) 6th edition.
www.cornerstonecx.com
Integrated System Tests University of Kentucky
HSRB 4th floor BSL-3
Lexington, KY
Reference
Biosafety in Microbiological and Biomedical Laboratories (BMBL) - 6th Edition - June 2020
https://www.cdc.gov/labs/BMBL.html
Section IV—Laboratory Biosafety Level Criteria
Biosafety Level 3
D. Laboratory Facilities (Secondary Barriers) (page 48)
9. A ducted mechanical air ventilation system is required. This system provides sustained directional airflow by
drawing air into the laboratory from “clean” areas toward “potentially contaminated” areas. The laboratory is
designed such that under failure conditions the airflow will not be reversed at the containment barrier.
Test Results Executive Summary
IST #P1 - Steady state operation - Testing revealed minimal variations in room differential pressures for extended
durations.
IST #1 - AHU Supply Single Fan Failures - Testing showed no sensed reversals in the containment barrier.
IST #2 - Single Exhaust Fan Failures - Testing showed no sensed reversals in the containment barrier. There are a few
rooms that go up to neutral and the magnitude of the negative pressure decreases. The exhaust fans do not have
redundancy.
IST #3 - Electrical Power Failure and Restoration - Testing showed no sensed reversals in the containment barrier. 464L
does go positive to 464G and remains that way until normal power is restored. This could be related to 464H
overcoming the pressure of 464L, and the air handling unit (AHU-2) being off.
www.cornerstonecx.com
Integrated System Tests University of Kentucky
HSRB 4th floor BSL-3
Lexington, KY
Verification
To verify there is no reversal of airflow, Cornerstone Commissioning, Inc. will use a multi room differential pressure
(DP) array to measure, monitor and record the differential pressure values at critical points of containment in the BSL-
3 zones during the failure scenario tests. The data generated from the DP array will help determine if the IST passes or
fails.
The DP array is independent of the building automation system.
DP array sensors range = +/-0.25” wc with 0.25% full scale accuracy. This is the appropriate range for the expected
room pressures.
DP array data logger recording interval = 500 milliseconds (2 readings per second).
The equipment is setup to capture any excursions or potential airflow reversals across the monitored doors with the
accuracy and speed required.
Smoke bottles and hand held micromanometers may also be used to confirm directional airflow during these tests.
A reversal is defined as a value beyond neutral. Neutral is an acceptable condition. The goal is to prevent sustained
reversals to limit the risk of a failure of the secondary containment barrier.
Pass Fail Criteria for IST #P1
The supply and exhaust room pressure control is critical to the safe operation of the BSL-3 laboratory.
Tuning for the zone level airflow control loops is critical to provide steady room pressures.
The zone level airflows for BSL-3 shall be tuned so that the normal room pressure operating value does not vary by
more than 25% for any duration.
This pretest will confirm that controls contractor and/or laboratory airflow control vendor has tuned the control loops
for the supply and exhaust airflow control so that the room pressure does not vary by more than 25% of the operating
value for any duration.
Example would be, desired room DP to be determined during commissioning, setup range between -0.03" to -0.09"
wc, -0.06" mid point, no oscillations above or below by 25% of the final room DP value.
Pass Fail Criteria for IST#1-3 (Suggested )
The following is the pass fail criteria for all of the doors in the BSL-3 laboratory secondary containment barrier during
the failure mode testing:
If there is a sensed reversal of greater than +0.05” wc for a time of more than 10 seconds across any door.
If there is a sensed reversal across two consecutive doors of any magnitude for longer than 5 seconds.
Cornerstone Cx considers these values to be a reportable incident once the laboratory is “hot”.
A risk assessment will be done if the criteria is not met to determine the course of action with consideration to the
scenario, the specific door, the magnitude and duration of the reversal, path from PECs, and the SOPs.
Commissioning Test Equipment
Smoke bottle (Regin) http://www.regin.com/product/fp201-low-velocity-powdered-smoke/
Micromanometer (Fluke 922)
DP Array - v7 - Ten Channel - Ashcroft - RXLDP +/- 0.25 in wc sensors
www.cornerstonecx.com
Integrated System Tests University of Kentucky
HSRB 4th floor BSL-3
Lexington, KY
Tag # Description
AHU-2 Air Handling Unit with two (2) supply fans
SAV Phoenix Controls air valve
Tag # Description
EF-1 Exhaust Fan
EF-2 Exhaust Fan
N/A HEPA filter housing
EAV Phoenix Controls air valve
Drawing #: Airflow diagram
Drawing is attached at end of this document
HVAC equipment
Supply air systems and equipment
Exhaust air systems and equipment
HVAC One line diagram
www.cornerstonecx.com
Integrated System Tests University of Kentucky
HSRB 4th floor BSL-3
Lexington, KY
Tag # Description
ATS-1 Automatic Transfer Switch
G-1 Generator
MB Main circuit breaker
Drawing #: Not available
Electrical equipment
Electrical One line diagram
www.cornerstonecx.com
Integrated System Tests University of Kentucky
HSRB 4th floor BSL-3
Lexington, KY
Room Name Room # Room Name Room #
1 Corridor 400N → Ante Room 464
2 Ante Room 464 → Airlock no #
3 Airlock no # → Lab 464G
4 Lab 464G → Lab 464F
5 Lab 464G → Animal Room 464H
6 Lab 464G → Animal Room 464J
7 Lab 464G → Lab 464L
8 Decontam 464D → Lab 464G
9 Decontam 464M → Lab 464G
Differential Pressure monitoring locations
Reference (Low - ) To (High + )
BSL-3 points of containment (doors) to be monitored during ISTs:
Airflow
Direction
DP Array
Channel #
www.cornerstonecx.com
Integrated System Tests University of Kentucky
HSRB 4th floor BSL-3
Lexington, KY
Floorplan - Differential Pressure locations for reference
www.cornerstonecx.com
Integrated System Tests University of Kentucky
HSRB 4th floor BSL-3
Lexington, KY
# Test Prerequisites - Description Status
1 All equipment and system performance verification tests are complete. Complete
2 Verified room airflow and pressure control devices with accuracy and operation. Complete
3 Steady redundant supply and exhaust airflows (review trends). Complete
4 If the facility has HEPA filters, they must be installed, tested, and certified. Complete
5 All BSCs must be certified and operational. Complete
6All systems/ equipment are in normal (automatic) operation with no overrides in the BAS or lab control system.
Complete
7 All doors in the building are closed. Complete
8All surrounding non containment areas and equipment in normal operation, as they would be when the building is in
use by the owner.Complete
9 All alarms are clear for the containment area. Complete
10 Containment area is closed to all personnel not involved with ISTs. Complete
11Plumbing drains are wet, dry traps can cause issues with room DP. Check all sinks, showers, and toilets, as applicable.
Complete
12
Setup the Differential Pressure (DP) Array to measure containment points in the containment zones for pressure
readings during the tests. This will determine if the IST passes or fails. (See DP array setup checklist below). Complete
13Confirm with the Owner staff that all building occupants that could be affected by the failure tests have been
notified?Complete
14Review with Owner staff (Lab manager, EH&S, researchers, etc. ) all doors in secondary containment barrier that are
being monitored.Complete
15Review with Owner staff (Lab manager, EH&S, researchers, etc. ) pass/ fail criteria, confirm before testing starts.
Complete
# Item Status
1 Verify that each sensor zero is within tolerance (0.000" wc), before connecting the tubes to the sensors Complete
2 Verify that each sensor reads within range (+/-0.25" wc) Complete
3 Ensure DP Array measured values are within tolerances of NIST calibrated meters Complete
4 Open each door being monitored to ensure it is correctly indicated on the DP array Complete
5 Verify that the polarity is correct for each sensor Complete
6 Confirm laptop used to record data has the correct date and time, for the area/ time zone that you are in. Complete
7Ensure that the UPS that the DP array is plugged into is functioning, by unplugging from the 120VAC electrical outlet,
this will ensure the battery in the UPS is functional.Complete
8When using the DP array, during testing, set the display time interval to 5 min, so you can see any oscillations
Complete
Prerequisites
This section lists pre-requisites to be completed and approved prior to performing the test.
DP Array setup checklist - To confirm the DP Array is working correctly
This should be done at the start of each testing session after all tubing is run.
www.cornerstonecx.com
Integrated System Tests University of Kentucky
HSRB 4th floor BSL-3
Lexington, KY
# Event Status
1 All personnel involved in test meet to review expectations Complete
2
Confirm that there are no safety concerns from any personnel involved. Confirm that there will be no harm to
personnel, equipment or the facility. Confirm that all personnel will use appropriate personal protective equipment
(PPE) for their required actions during the tests and that Cornerstone Cx assumes no responsibility to damaged
equipment, systems or the facility.
Complete
3 Personnel go to assigned locations Complete
4 Confirm DP Array and all tubing setup per pre req Complete
5 Communication check, ensure all personnel have completed pre-test tasks Complete
6Record the as found, normal operating parameters for the HVAC systems and equipment that serve the BSL-3 at the
start of each testing sessionComplete
7Ask BAS operator to capture screenshot of the BAS graphics indicating normal operation of the systems and that
there are no active alarms.Complete
8When using the DP array, during testing, set the display time interval to 5 min (on the connected laptop and the data
logger), so you can see any oscillations or anomolies.Complete
Day of test prerequisites
This should be done at the start of each testing session .
www.cornerstonecx.com
Integrated System Tests University of Kentucky
HSRB 4th floor BSL-3
Lexington, KY
Personnel Location Task
Owner staff Mech / elec spaces Observe system operation.
Owner Mech staff Mech spaces Equipment VFDs to simulate fan failures (via the power
disconnect).
Owner Elec staff Elec spaces Open and close main electrical power source/ breakers.
Generator rep/ Owner staff Generator Ensure the generator performs as expected. Can
troubleshoot and address any issues encountered.
Owner BAS staff Hard wired into control
system. Wifi is not reliable
during power failure tests
unless on UPS.
Reset equipment, capture screenshots of equipment
parameters, alarms, etc. Can troubleshoot and address
any issues encountered.
Equipment vendor/rep or
Owner BAS staff
Lab control system access
point
Can troubleshoot and address any issues encountered.
Owner staff BSL-3 Laboratory Observe operation of laboratory systems and equipment.
Dan Cook BSL-3 Laboratory Direct test events.
Monitor BSL-3 room pressures, review trend data.
Personnel - Required Participants, Locations and Tasks
www.cornerstonecx.com
Integrated System Tests University of Kentucky
HSRB 4th floor BSL-3
Lexington, KY
Date: 2021-07-27
-
Confirm that the Supply fans in the Air handling units, the Exhaust fans, and the air terminal units/ air valves (as applicable) serving
the BSL-3 area provide steady room differential pressure (DP), this will confirm that there are no control tuning issues, with
minimal oscillations that could effect the outcome of the failure testing in IST#1-3.
Record the room DPs with all systems in normal operation, no personnel inside the containment barrier, no entry or exit, for 5
minutes. This will establish the room pressure baseline for comparison during the failure scenarios.
# Event
1 Enter the start time, when recording was started on the DP array.
2 Enter the stop time, when recording was stopped on the DP array.
3 Using the DP array CSV file, generate graph and data analysis table.
4Review results, if there are no anomalies and the systems and equipment provide steady room DP, then proceed to next failure
test/ integrated system test.
Time Event
1600 Start recording
1605 Stop recording
IST #P1 - Steady State Operation - Room DP - AHU, EF, air terminal units
Conclusion
Review of room DP indicates that the AHU, EF, air terminal units are operating in a manner that provides steady room DP values that
do not oscillate by more than 20% of average pressure reading.
Event Log
Test Script
Test Description
www.cornerstonecx.com
IST P1 - UK HSRB 4th flr BSL-3 - 2021-07-27_1546_All events
www.cornerstonecx.com
-0.16
-0.14
-0.12
-0.1
-0.08
-0.06
-0.04
-0.02
0
16
:00
:00
16
:00
:05
16
:00
:10
16
:00
:15
16
:00
:20
16
:00
:25
16
:00
:30
16
:00
:35
16
:00
:40
16
:00
:45
16
:00
:50
16
:00
:55
16
:01
:00
16
:01
:05
16
:01
:10
16
:01
:15
16
:01
:20
16
:01
:25
16
:01
:30
16
:01
:35
16
:01
:40
16
:01
:45
16
:01
:50
16
:01
:55
16
:02
:00
16
:02
:05
16
:02
:10
16
:02
:15
16
:02
:20
16
:02
:25
16
:02
:30
16
:02
:35
16
:02
:40
16
:02
:45
16
:02
:50
16
:02
:55
16
:03
:00
16
:03
:05
16
:03
:10
16
:03
:15
16
:03
:20
16
:03
:25
16
:03
:30
16
:03
:35
16
:03
:40
16
:03
:45
16
:03
:50
16
:03
:55
16
:04
:00
16
:04
:05
16
:04
:10
16
:04
:15
16
:04
:20
16
:04
:25
16
:04
:30
16
:04
:35
16
:04
:40
16
:04
:45
16
:04
:50
16
:04
:55
Corridor 400N/Ante Room 464 Ante Room 464/Airlock no # Airlock no #/Lab 464G
Lab 464G/Lab 464F Lab 464G/Animal Room 464H Lab 464G/Animal Room 464J
Lab 464G/Lab 464L Decontam 464D/Lab 464G Decontam 464M/Lab 464G
IST P1 - UK HSRB 4th flr BSL-3 - 2021-07-27_1546_Data Analysis
Data and Graph event: All Events - 5 minute steady state
Start time: 16:00:00
End time: 16:05:00
5 minute steady state 1 2 3 4 5 6 7 8 9
Room DP monitored
Corridor
400N/Ant
e Room
464
Ante
Room
464/Airloc
k no #
Airlock no
#/Lab
464G
Lab
464G/Lab
464F
Lab
464G/Ani
mal Room
464H
Lab
464G/Ani
mal Room
464J
Lab
464G/Lab
464L
Decontam
464D/Lab
464G
Decontam
464M/Lab
464G
Min value -0.0603 -0.0225 -0.0259 -0.0563 -0.0422 -0.1377 -0.0252 -0.0593 -0.0564
Max value -0.0458 -0.0181 -0.0206 -0.0484 -0.0391 -0.1336 -0.0188 -0.0515 -0.0477
Average value -0.0535 -0.02046 -0.02369 -0.05264 -0.04081 -0.13586 -0.02193 -0.05495 -0.05192
Avg/Min % 88.7% 90.9% 91.5% 93.5% 96.7% 98.7% 87.0% 92.7% 92.1%
Avg/Max % 116.8% 113.1% 115.0% 108.8% 104.4% 101.7% 116.7% 106.7% 108.8%
Delta (Highlight if value is > 0.02") 0.015 0.004 0.005 0.008 0.003 0.004 0.006 0.008 0.009
Delta (Highlight if value is > 0.03") 0.015 0.004 0.005 0.008 0.003 0.004 0.006 0.008 0.009
Delta (Highlight if value is > 0.04") 0.015 0.004 0.005 0.008 0.003 0.004 0.006 0.008 0.009
Delta (Highlight if value is > 0.05") 0.015 0.004 0.005 0.008 0.003 0.004 0.006 0.008 0.009
www.cornerstonecx.com
Integrated System Tests University of Kentucky
HSRB 4th floor BSL-3
Lexington, KY
Date: 2021-07-28
-
Simulate failures of the Air Handling Unit (AHU) supply fans serving the BSL-3.
The intent is to confirm redundancy, if there are more than one (1) fan in the system.
Note: Fan failures are unplanned events, fan restorations are planned events, the pass fail criteria should reflect the risk assessment
for this failure scenario.
During these failure scenarios, the BAS and HVAC systems will prevent a reversal of airflow in the BSL-3 secondary containment
barriers.
# Event
1 Enter the start time, when recording was started on the DP array.
2 Shut off the AHU supply fan at the VFD electrical power disconnect. Note which fan below.
3Note the time and the operating parameters for the other AHU supply fan(s) when at static pressure setpoint and the room DP has
settled out.4 Ask BAS operator to capture screenshot of the BAS graphics indicating the off fan and any alarms generated.
5 Note any local alarms (Room pressure monitor, BSC, horn/strobe in the lab, etc.)
6 Note any observed airflow reversals from the DP array display and/or laptop used to record.
7 Restore the AHU supply fan at the VFD electrical power disconnect. Note if alarm or system reset is required via BAS.
8 Note any observed airflow reversals from the DP array display and/or laptop used to record.
9 Confirm all supply and exhaust fans are operating at parameters from the start of the test.
10 Repeat steps 2-8 for all AHU supply air fans.
11 Enter the stop time, when recording was stopped on the DP array, after all systems have settled out.
12 Collect screenshots from BAS operator.
13 Confirm that the results were captured in the DP array generated CSV/excel file.
14 Using the DP array CSV file, generate graph and data analysis table.
15
If there are no anomalies and the systems and equipment prevent reversals of airflow, according to the pass fail criteria, then proceed
to next failure test/ integrated system test.
If there are anomalies and sensed reversals of airflow, review results with owner and determine best course of action, and if testing
should continue. Based on if modifications to the systems, equipment, parameters, setpoints, etc. Document all changes made and
repeat tests as necessary until favorable results are achieved.
IST#1 - Failure of the Air Handling Unit supply fans
Test Description
Test Script
www.cornerstonecx.com
Integrated System Tests University of Kentucky
HSRB 4th floor BSL-3
Lexington, KY
Date: 2021-07-28
IST#1 - Failure of the Air Handling Unit supply fans
Time Event
656 Start recording
701 Shut off AHU-2 fan B via BAS
- AHU-3 fan A ramps to 100%
705 Restore AHU-2 fan B via BAS
- Found issue with BAS graphics and VFD settings, fan B did not restart
- Personnel walk in and out of Anteroom 464
733 AHU-2 fan A and B are both running, supply air static pressure (SASP) is at setpoint
735 Shut off AHU-2 fan A via BAS
- AHU-2 fan B ramps to 100%
739 Restore AHU-2 fan A via BAS
- Found issue with BAS graphics and VFD settings, fan B did not restart
- Personnel walk in and out of Anteroom 464
750 AHU-2 fan A and B are both running
754 SASP at setpoint
755 Stop recording
1 Eric Hess - UK Facilities has a list of items that need to be addressed in the VFD for these fans and the BAS graphics.
2 The supply and exhaust isolation dampers remained open during these failure events.
Notes
Conclusion
After reviewing the room differential pressure (DP) trend data, this test passed as there were no indications of reversal of
pressurization at the containment barrier. See attached room DP graphs and data analysis for details from test events.
Event Log
www.cornerstonecx.com
IST 1 - UK HSRB 4th flr BSL_3 - 2021-07-28_0656_All events
www.cornerstonecx.com
-0.3
-0.25
-0.2
-0.15
-0.1
-0.05
0
0.05
6:5
6:2
96
:57
:27
6:5
8:2
56
:59
:23
7:0
0:2
17
:01
:19
7:0
2:1
77
:03
:15
7:0
4:1
37
:05
:11
7:0
6:0
97
:07
:07
7:0
8:0
57
:09
:03
7:1
0:0
17
:10
:59
7:1
1:5
77
:12
:55
7:1
3:5
37
:14
:51
7:1
5:4
97
:16
:47
7:1
7:4
57
:18
:43
7:1
9:4
17
:20
:39
7:2
1:3
77
:22
:35
7:2
3:3
37
:24
:31
7:2
5:2
97
:26
:27
7:2
7:2
57
:28
:23
7:2
9:2
17
:30
:19
7:3
1:1
77
:32
:15
7:3
3:1
37
:34
:11
7:3
5:0
97
:36
:07
7:3
7:0
57
:38
:03
7:3
9:0
17
:39
:59
7:4
0:5
77
:41
:55
7:4
2:5
37
:43
:51
7:4
4:4
97
:45
:47
7:4
6:4
57
:47
:43
7:4
8:4
17
:49
:39
7:5
0:3
77
:51
:35
7:5
2:3
37
:53
:31
7:5
4:2
9
Corridor 400N / Ante Room 464 Ante Room 464 / Airlock no # Airlock no # / Lab 464G
Lab 464G / Lab 464F Lab 464G / Animal Room 464H Lab 464G / Animal Room 464J
Lab 464G / Lab 464L Decontam 464D / Lab 464G Decontam 464M / Lab 464G
IST 1 - UK HSRB 4th flr BSL_3 - 2021-07-28_0656_Data Analysis (Count above 0.005" wc)
Data and Graph event: All Events
Start time: 6:56:29
End time: 7:54:57
DP Array Ch # 1 2 3 4 5 6 7 8 9
Room DP monitored
Corridor
400N /
Ante
Room 464
Ante
Room 464
/ Airlock
no #
Airlock no
# / Lab
464G
Lab 464G
/ Lab 464F
Lab 464G
/ Animal
Room
464H
Lab 464G
/ Animal
Room
464J
Lab 464G
/ Lab 464L
Decontam
464D /
Lab 464G
Decontam
464M /
Lab 464G
Average (in wc) -0.1320 -0.0434 -0.0476 -0.0262 -0.0445 -0.1372 -0.0115 -0.0712 -0.0656
Min value (in wc) -0.2713 -0.1249 -0.1288 -0.0528 -0.0576 -0.1515 -0.0507 -0.1156 -0.1114
Max value (in wc) 0.0050 -0.0002 -0.0064 -0.0146 -0.0171 -0.1263 0.0074 -0.0232 -0.0265
COUNT above 0.005 0.0 0.0 0.0 0.0 0.0 0.0 1.0 0.0 0.0
Seconds above neutral 0 0 0 0 0 0 0.5 0 0
www.cornerstonecx.com
Integrated System Tests University of Kentucky
HSRB 4th floor BSL-3
Lexington, KY
Date: 2021-07-28
-
Simulate failures of the Exhaust fans serving the BSL-3.
The intent is to confirm redundancy, if there are more than one (1) fan in the system.
Note: Fan failures are unplanned events, fan restorations are planned events, the pass fail criteria should reflect the risk assessment
for this failure scenario.
During these failure scenarios, the BAS and HVAC systems will prevent a reversal of airflow in the BSL-3 secondary containment
barriers.
# Event
1 Enter the start time, when recording was started on the DP array.
2 Shut off the Exhaust fan at the VFD electrical power disconnect. Note which fan below.
3Note the time and the operating parameters for the other Exhaust fan(s) when at static pressure setpoint and the room DP has settled
out.4 Ask BAS operator to capture screenshot of the BAS graphics indicating the off fan and any alarms generated.
5 Note any local alarms (Room pressure monitor, BSC, horn/strobe in the lab, etc.)
6 Note any observed airflow reversals from the DP array display and/or laptop used to record.
7 Restore the Exhaust fan at the VFD electrical power disconnect. Note if alarm or system reset is required via BAS.
8 Note any observed airflow reversals from the DP array display and/or laptop used to record.
9 Confirm all supply and exhaust fans are operating at parameters from the start of the test.
10 Repeat steps 2-8 for all Exhaust air fans.
11 Enter the stop time, when recording was stopped on the DP array, after all systems have settled out.
12 Collect screenshots from BAS operator.
13 Confirm that the results were captured in the DP array generated CSV/excel file.
14 Using the DP array CSV file, generate graph and data analysis table.
15
If there are no anomalies and the systems and equipment prevent reversals of airflow, according to the pass fail criteria, then proceed
to next failure test/ integrated system test.
If there are anomalies and sensed reversals of airflow, review results with owner and determine best course of action, and if testing
should continue. Based on if modifications to the systems, equipment, parameters, setpoints, etc. Document all changes made and
repeat tests as necessary until favorable results are achieved.
IST#2 - Failure of the Exhaust Fans
Test Description
Test Script
www.cornerstonecx.com
Integrated System Tests University of Kentucky
HSRB 4th floor BSL-3
Lexington, KY
Date: 2021-07-28
IST#2 - Failure of the Exhaust Fans
Time Event
625 Start recording
626 EF-1 off at the VFD disconnect
- RPMs in alarm after 60 seconds
628 Personnel walk into Anteroom 464
634 Restore power at EF-1 VFD disconnect
636 Personnel walk into Anteroom 464
643 Personnel walk out of Anteroom 464
645 EF-2 off at the VFD disconnect
646 Personnel walk into Anteroom 464
- RPMs in alarm after 60 seconds
647 Personnel walk out of Anteroom 464
651 Restore power at EF-2 VFD disconnect
656 Stop recording
- REPEAT TEST FOR EF-1 TO CONFIRM OPERATION AND PREVIOUS RESULTS
755 Start recording
757 EF-1 off at the VFD disconnect
- RPMs in alarm after 60 seconds
758 Personnel walk into Anteroom 464
800 Personnel walk out of Anteroom 464
- Restore power at EF-1 VFD disconnect
801 Personnel walk into Anteroom 464
805 Stop recording
1 The supply and exhaust isolation dampers remained open during these failure events.
Event Log
Notes
Conclusion
After reviewing the room differential pressure (DP) trend data, this test passed as there were no indications of reversal of
pressurization at the containment barrier. See attached room DP graphs and data analysis for details from test events.
www.cornerstonecx.com
IST 2 - UK HSRB 4th flr BSL-3 - 2021-07-28_0625_All events
www.cornerstonecx.com
-0.25
-0.2
-0.15
-0.1
-0.05
0
0.05
0.1
6:2
5:4
86
:26
:18
6:2
6:4
96
:27
:19
6:2
7:5
06
:28
:20
6:2
8:5
16
:29
:21
6:2
9:5
26
:30
:22
6:3
0:5
36
:31
:23
6:3
1:5
46
:32
:24
6:3
2:5
56
:33
:25
6:3
3:5
66
:34
:26
6:3
4:5
76
:35
:27
6:3
5:5
86
:36
:28
6:3
6:5
96
:37
:29
6:3
8:0
06
:38
:30
6:3
9:0
16
:39
:31
6:4
0:0
26
:40
:32
6:4
1:0
36
:41
:33
6:4
2:0
46
:42
:34
6:4
3:0
56
:43
:35
6:4
4:0
66
:44
:36
6:4
5:0
76
:45
:37
6:4
6:0
86
:46
:38
6:4
7:0
96
:47
:39
6:4
8:1
06
:48
:40
6:4
9:1
16
:49
:41
6:5
0:1
26
:50
:42
6:5
1:1
36
:51
:43
6:5
2:1
46
:52
:44
6:5
3:1
56
:53
:45
6:5
4:1
66
:54
:46
6:5
5:1
76
:55
:47
6:5
6:1
8
Corridor 400N / Ante Room 464 Ante Room 464 / Airlock no # Airlock no # / Lab 464G
Lab 464G / Lab 464F Lab 464G / Animal Room 464H Lab 464G / Animal Room 464J
Lab 464G / Lab 464L Decontam 464D / Lab 464G Decontam 464M / Lab 464G
IST 2 - UK HSRB 4th flr BSL-3 - 2021-07-28_0625_EF-1 off restore
www.cornerstonecx.com
-0.25
-0.2
-0.15
-0.1
-0.05
0
0.05
0.1
6:2
7:2
06
:27
:28
6:2
7:3
66
:27
:44
6:2
7:5
26
:28
:00
6:2
8:0
86
:28
:16
6:2
8:2
46
:28
:32
6:2
8:4
06
:28
:48
6:2
8:5
66
:29
:04
6:2
9:1
26
:29
:20
6:2
9:2
86
:29
:36
6:2
9:4
46
:29
:52
6:3
0:0
06
:30
:08
6:3
0:1
66
:30
:24
6:3
0:3
26
:30
:40
6:3
0:4
86
:30
:56
6:3
1:0
46
:31
:12
6:3
1:2
06
:31
:28
6:3
1:3
66
:31
:44
6:3
1:5
26
:32
:00
6:3
2:0
86
:32
:16
6:3
2:2
46
:32
:32
6:3
2:4
06
:32
:48
6:3
2:5
66
:33
:04
6:3
3:1
26
:33
:20
6:3
3:2
86
:33
:36
6:3
3:4
46
:33
:52
6:3
4:0
06
:34
:08
6:3
4:1
66
:34
:24
6:3
4:3
26
:34
:40
6:3
4:4
86
:34
:56
6:3
5:0
46
:35
:12
Corridor 400N / Ante Room 464 Ante Room 464 / Airlock no # Airlock no # / Lab 464G
Lab 464G / Lab 464F Lab 464G / Animal Room 464H Lab 464G / Animal Room 464J
Lab 464G / Lab 464L Decontam 464D / Lab 464G Decontam 464M / Lab 464G
IST 2 - UK HSRB 4th flr BSL-3 - 2021-07-28_0625_EF-2 off restore
www.cornerstonecx.com
-0.25
-0.2
-0.15
-0.1
-0.05
0
0.05
0.1
6:4
5:1
0
6:4
5:1
7
6:4
5:2
4
6:4
5:3
1
6:4
5:3
8
6:4
5:4
5
6:4
5:5
2
6:4
5:5
9
6:4
6:0
6
6:4
6:1
3
6:4
6:2
0
6:4
6:2
7
6:4
6:3
4
6:4
6:4
1
6:4
6:4
8
6:4
6:5
5
6:4
7:0
2
6:4
7:0
9
6:4
7:1
6
6:4
7:2
3
6:4
7:3
0
6:4
7:3
7
6:4
7:4
4
6:4
7:5
1
6:4
7:5
8
6:4
8:0
5
6:4
8:1
2
6:4
8:1
9
6:4
8:2
6
6:4
8:3
3
6:4
8:4
0
6:4
8:4
7
6:4
8:5
4
6:4
9:0
1
6:4
9:0
8
6:4
9:1
5
6:4
9:2
2
6:4
9:2
9
6:4
9:3
6
6:4
9:4
3
6:4
9:5
0
6:4
9:5
7
6:5
0:0
4
6:5
0:1
1
6:5
0:1
8
6:5
0:2
5
6:5
0:3
2
6:5
0:3
9
6:5
0:4
6
6:5
0:5
3
6:5
1:0
0
6:5
1:0
7
6:5
1:1
4
6:5
1:2
1
6:5
1:2
8
6:5
1:3
5
6:5
1:4
2
6:5
1:4
9
Corridor 400N / Ante Room 464 Ante Room 464 / Airlock no # Airlock no # / Lab 464G
Lab 464G / Lab 464F Lab 464G / Animal Room 464H Lab 464G / Animal Room 464J
Lab 464G / Lab 464L Decontam 464D / Lab 464G Decontam 464M / Lab 464G
IST 2 - UK HSRB 4th flr BSL-3 - 2021-07-28_0625_Data Analysis (Count above 0.005" wc)
Data and Graph event: All Events
Start time: 6:25:48
End time: 6:56:19
DP Array Ch # 1 2 3 4 5 6 7 8 9
Room DP monitored
Corridor
400N /
Ante
Room 464
Ante
Room 464
/ Airlock
no #
Airlock no
# / Lab
464G
Lab 464G
/ Lab 464F
Lab 464G
/ Animal
Room
464H
Lab 464G
/ Animal
Room
464J
Lab 464G
/ Lab 464L
Decontam
464D /
Lab 464G
Decontam
464M /
Lab 464G
Average (in wc) -0.0062 -0.0074 -0.0063 -0.0200 -0.0340 -0.1213 -0.0216 -0.0182 -0.0287
Min value (in wc) -0.0915 -0.0297 -0.0320 -0.0505 -0.1036 -0.2138 -0.1133 -0.0502 -0.0972
Max value (in wc) 0.0628 0.0152 0.0150 0.0135 -0.0200 -0.0836 -0.0018 0.0135 0.0017
COUNT above 0.005 1612.0 294.0 1071.0 2.0 0.0 0.0 0.0 860.0 0.0
Seconds above neutral 806 147 535.5 1 0 0 0 430 0
Data and Graph event: EF-1 off & restore
Start time: 6:27:20
End time: 6:35:20
DP Array Ch # 1 2 3 4 5 6 7 8 9
Room DP monitored
Corridor
400N /
Ante
Room 464
Ante
Room 464
/ Airlock
no #
Airlock no
# / Lab
464G
Lab 464G
/ Lab 464F
Lab 464G
/ Animal
Room
464H
Lab 464G
/ Animal
Room
464J
Lab 464G
/ Lab 464L
Decontam
464D /
Lab 464G
Decontam
464M /
Lab 464G
Average (in wc) 0.0163 0.0017 0.0040 -0.0049 -0.0297 -0.1074 -0.0079 0.0020 -0.0069
Min value (in wc) -0.0806 -0.0283 -0.0311 -0.0458 -0.1036 -0.2138 -0.0848 -0.0492 -0.0803
Max value (in wc) 0.0628 0.0107 0.0113 0.0135 -0.0235 -0.1001 -0.0018 0.0075 -0.0013
COUNT above 0.005 873.0 29.0 332.0 1.0 0.0 0.0 0.0 162.0 0.0
Seconds above neutral 436.5 14.5 166 0.5 0 0 0 81 0
Data and Graph event: EF-2 off & restore
Start time: 6:45:10
End time: 6:51:50
DP Array Ch # 1 2 3 4 5 6 7 8 9
Room DP monitored
Corridor
400N /
Ante
Room 464
Ante
Room 464
/ Airlock
no #
Airlock no
# / Lab
464G
Lab 464G
/ Lab 464F
Lab 464G
/ Animal
Room
464H
Lab 464G
/ Animal
Room
464J
Lab 464G
/ Lab 464L
Decontam
464D /
Lab 464G
Decontam
464M /
Lab 464G
Average (in wc) 0.0245 0.0041 0.0065 -0.0038 -0.0248 -0.0965 -0.0156 0.0060 -0.0086
Min value (in wc) -0.0915 -0.0297 -0.0320 -0.0435 -0.1009 -0.2030 -0.1133 -0.0502 -0.0972
Max value (in wc) 0.0436 0.0152 0.0150 0.0095 -0.0200 -0.0836 -0.0091 0.0135 0.0017
COUNT above 0.005 739.0 265.0 739.0 1.0 0.0 0.0 0.0 698.0 0.0
Seconds above neutral 369.5 132.5 369.5 0.5 0 0 0 349 0
www.cornerstonecx.com
IST 2 - UK HSRB 4th flr BSL-3 - 2021-07-28_0754_All events
www.cornerstonecx.com
-0.2
-0.15
-0.1
-0.05
0
0.05
07
:55
:05
07
:55
:15
07
:55
:26
07
:55
:36
07
:55
:47
07
:55
:57
07
:56
:08
07
:56
:18
07
:56
:29
07
:56
:39
07
:56
:50
07
:57
:00
07
:57
:11
07
:57
:21
07
:57
:32
07
:57
:42
07
:57
:53
07
:58
:03
07
:58
:14
07
:58
:24
07
:58
:35
07
:58
:45
07
:58
:56
07
:59
:06
07
:59
:17
07
:59
:27
07
:59
:38
07
:59
:48
07
:59
:59
08
:00
:09
08
:00
:20
08
:00
:30
08
:00
:41
08
:00
:51
08
:01
:02
08
:01
:12
08
:01
:23
08
:01
:33
08
:01
:44
08
:01
:54
08
:02
:05
08
:02
:15
08
:02
:26
08
:02
:36
08
:02
:47
08
:02
:57
08
:03
:08
08
:03
:18
08
:03
:29
08
:03
:39
08
:03
:50
08
:04
:00
08
:04
:11
08
:04
:21
08
:04
:32
08
:04
:42
08
:04
:53
08
:05
:03
08
:05
:14
08
:05
:24
Corridor 400N / Ante Room 464 Ante Room 464 / Airlock no # Airlock no # / Lab 464G
Lab 464G / Lab 464F Lab 464G / Animal Room 464H Lab 464G / Animal Room 464J
Lab 464G / Lab 464L Decontam 464D / Lab 464G Decontam 464M / Lab 464G
IST 2 - UK HSRB 4th flr BSL-3 - 2021-07-28_0754_Data Analysis (Count above 0.005" wc)
Data and Graph event: All Events
Start time: 7:55:05
End time: 8:05:26
DP Array Ch # 1 2 3 4 5 6 7 8 9
Room DP monitored
Corridor
400N /
Ante
Room 464
Ante
Room 464
/ Airlock
no #
Airlock no
# / Lab
464G
Lab 464G
/ Lab 464F
Lab 464G
/ Animal
Room
464H
Lab 464G
/ Animal
Room
464J
Lab 464G
/ Lab 464L
Decontam
464D /
Lab 464G
Decontam
464M /
Lab 464G
Average (in wc) -0.0523 -0.0170 -0.0165 -0.0174 -0.0353 -0.1276 -0.0399 -0.0289 -0.0433
Min value (in wc) -0.1362 -0.0474 -0.0472 -0.0526 -0.0879 -0.1886 -0.1329 -0.0735 -0.0824
Max value (in wc) 0.0326 0.0055 0.0069 0.0143 -0.0231 -0.0990 -0.0209 0.0137 -0.0088
COUNT above 0.005 6.0 1.0 2.0 2.0 0.0 0.0 0.0 1.0 0.0
Seconds above neutral 3 0.5 1 1 0 0 0 0.5 0
www.cornerstonecx.com
Integrated System Tests University of Kentucky
HSRB 4th floor BSL-3
Lexington, KY
Date: 2021-07-28
-
Simulate failure of the Electrical Utility Power serving the building/ facility that includes the BSL-3 laboratory.
The intent is to document a real life loss of electrical utility and confirm the emergency electrical power systems function in a
manner that will prevent reversals of airflow in the BSL-3 laboratory.
Note: Electrical utility power failures are unplanned events, electrical utility power restorations are planned events, the pass fail
criteria should reflect the risk assessment for this failure scenario.
During these failure scenarios, the BAS, HVAC and electrical systems will prevent a reversal of airflow in the BSL-3 secondary
containment barriers.
# Event
1Confirm there is enough fuel in the generator fuel tank to get through the test for the planned duration. Record the
generator fuel tank level.
2 Confirm that the ATS(s) and generator are in in auto operation (if no abort test)
3 Record the power meter(s) value while on normal power.
4 Enter the start time, when recording was started on the DP array.
5 Simulate a loss of the normal electrical utility power source by opening the main breaker.
6Confirm that the ATS senses the loss of normal power and starts the emergency generator in (sec):
(This is part of the total time to switch from normal to emergency)
7 ATS switches to emergency generator after commanding it to run in (sec):
8Observe that the ATS switches from normal power to standby emergency generator.
Record the transfer times below.
9Verify that all electrical panels that are served by the emergency generator have power. (yes/no ) Reference the
applicable Electrical drawing(s)
10Verify that all lights that are served by the emergency generator have power and are on. (yes/no ) Reference the
applicable Electrical drawing(s)
11Verify that all electrical outlets that are served by the emergency generator have power. (yes/no ) Reference the
applicable Electrical drawing(s)
12 Record any alarm or system reset(s) that had to occur to re-start equipment after the power loss.
13When all the systems that are on emergency power are back online, operating at their setpoints, and settled out,
record the time.
14Note the time when the AHU supply fan(s) and Exhaust fans are operating to achieve static pressure setpoint and the
room DP has settled out.
15Ask BAS operator to capture screenshot of the BAS graphics indicating equipment that is off and any alarms generated.
16 Note any local alarms (Room pressure monitor, BSC, horn/strobe in the lab, etc.)
17 Note any observed airflow reversals from the DP array display and/or laptop used to record.
18 Let the generator run for at least 20 min before restoring normal power.
19 Record the power meter(s) value while on emergency generator after systems have settled out (kW):
IST#3 - Electrical Utility Power Failure and Restoration
Test Description
Test Script
www.cornerstonecx.com
Integrated System Tests University of Kentucky
HSRB 4th floor BSL-3
Lexington, KY
Date: 2021-07-28
IST#3 - Electrical Utility Power Failure and Restoration
# Event
20 Restore normal power by closing the main breaker.
21Record the ATS(s) delay time (min) that normal power has to be available for it to switch from emergency power
generator.
22 Record the time that the ATS(s) switches from emergency generator to normal power.
23Record the emergency generator cooldown delay time (min) after the ATS has switched from emergency generator
power to normal power.
24 Record the time that the emergency generator goes off.
25 Note any observed airflow reversals from the DP array display and/or laptop used to record.
26 Confirm all supply and exhaust fans are operating at parameters from the start of the test.
27 Note any observed airflow reversals from the DP array display and/or laptop used to record.
28When all the systems are back online, operating at their setpoints, and settled out while on normal power, record the
time.
29 Record the power meter(s) values when all systems are running on normal power (kW):
30 Record the Generator fuel tank level (gallons) once it is off.
31 Enter the stop time, when recording was stopped on the DP array, after all systems have settled out.
32 Collect screenshots from BAS operator.
33 Confirm that the results were captured in the DP array generated CSV/excel file.
34 Using the DP array CSV file, generate graph and data analysis table.
35
If there are no anomalies and the systems and equipment prevent reversals of airflow, according to the pass fail
criteria, then proceed to next failure test/ integrated system test.
If there are anomalies and sensed reversals of airflow, review results with owner and determine best course of action,
and if testing should continue. Based on if modifications to the systems, equipment, parameters, setpoints, etc.
Document all changes made and repeat tests as necessary until favorable results are achieved.
Test Script
www.cornerstonecx.com
Integrated System Tests University of Kentucky
HSRB 4th floor BSL-3
Lexington, KY
Date: 2021-07-28
IST#3 - Electrical Utility Power Failure and Restoration
Time Event
447 Start recording
458 Open normal power (NP) electrical utility feed to the building (multiple feeds)
- All eight (8) supply isolation dampers indicate closed on the control panel in Anteroom 464
- AHU-2 is off, the outside air damper will not open for this unit, reason it won't restart
520 Personnel walk into Anteroom 464525 Personnel walk out of Anteroom 464531 Normal power restored, anything not on emergency generator backup power restarts
- AHU-2 is starting534 Supply isolation damper closed = 1, 2, 4, 5 / open = 3, 6, 7545 Supply isolation damper 2 is closed, all others are open537 ATS switch from emergency generator backup power to normal power538 Generator shuts off after 1 minute cooldown
- JACE lost communication, Eric Hess stated it needs a UPS539 Supply isolation damper closed = 1, 2, 4, 5 / open = 3, 6, 7541 Supply isolation damper 2 is closed, all others are open
- JACE is communicating544 Personnel walk out of Anteroom 464545 Personnel walk from Anteroom 464 to Lab 464L through the locker, decon rooms Q & M and back to 464546 Personnel walk out of Anteroom 464549 Personnel walk into Anteroom 464552 AHU-2 and EF-1, 2 are at setpoint
- Room DP is different than at the start of test, other AHU and EF in the building are restarting.557 Personnel walk into Anteroom 464
613 Room DP is close to values at start of test
614 Personnel walk out of Anteroom 464
615 Stop recording
1 464L does go positive to 464G and remains that way until normal power is restored. This could be related to 464H
overcoming the pressure of 464L, and the air handling unit (AHU-2) being off.
Notes
Conclusion
After reviewing the room DP trend data, this test passed as there were no indications of reversal of pressurization at the
containment barrier. See attached room differential pressure (DP) graphs for all events.
Event Log
www.cornerstonecx.com
IST 3 - UK HSRB 4th flr BSL-3 - 2021-07-28_0447_All events
www.cornerstonecx.com
-0.35
-0.3
-0.25
-0.2
-0.15
-0.1
-0.05
0
0.05
0.1
0.15
4:4
7:5
14
:49
:17
4:5
0:4
44
:52
:10
4:5
3:3
74
:55
:03
4:5
6:3
04
:57
:56
4:5
9:2
35
:00
:49
5:0
2:1
65
:03
:42
5:0
5:0
95
:06
:35
5:0
8:0
25
:09
:28
5:1
0:5
55
:12
:21
5:1
3:4
85
:15
:14
5:1
6:4
15
:18
:07
5:1
9:3
45
:21
:00
5:2
2:2
75
:23
:53
5:2
5:2
05
:26
:46
5:2
8:1
35
:29
:39
5:3
1:0
65
:32
:32
5:3
3:5
95
:35
:25
5:3
6:5
25
:38
:18
5:3
9:4
55
:41
:11
5:4
2:3
85
:44
:04
5:4
5:3
15
:46
:57
5:4
8:2
45
:49
:50
5:5
1:1
75
:52
:43
5:5
4:1
05
:55
:36
5:5
7:0
35
:58
:29
5:5
9:5
66
:01
:22
6:0
2:4
96
:04
:15
6:0
5:4
26
:07
:08
6:0
8:3
56
:10
:01
6:1
1:2
86
:12
:54
6:1
4:2
1
Corridor 400N / Ante Room 464 Ante Room 464 / Airlock no # Airlock no # / Lab 464G
Lab 464G / Lab 464F Lab 464G / Animal Room 464H Lab 464G / Animal Room 464J
Lab 464G / Lab 464L Decontam 464D / Lab 464G Decontam 464M / Lab 464G
IST 3 - UK HSRB 4th flr BSL-3 - 2021-07-28_0447_Open NP
www.cornerstonecx.com
-0.35
-0.3
-0.25
-0.2
-0.15
-0.1
-0.05
0
0.05
0.1
4:5
8:4
0
4:5
8:4
2
4:5
8:4
3
4:5
8:4
5
4:5
8:4
6
4:5
8:4
8
4:5
8:4
9
4:5
8:5
1
4:5
8:5
2
4:5
8:5
4
4:5
8:5
5
4:5
8:5
7
4:5
8:5
8
4:5
9:0
0
4:5
9:0
1
4:5
9:0
3
4:5
9:0
4
4:5
9:0
6
4:5
9:0
7
4:5
9:0
9
4:5
9:1
0
4:5
9:1
2
4:5
9:1
3
4:5
9:1
5
4:5
9:1
6
4:5
9:1
8
4:5
9:1
9
4:5
9:2
1
4:5
9:2
2
4:5
9:2
4
4:5
9:2
5
4:5
9:2
7
4:5
9:2
8
4:5
9:3
0
4:5
9:3
1
4:5
9:3
3
4:5
9:3
4
4:5
9:3
6
4:5
9:3
7
4:5
9:3
9
4:5
9:4
0
4:5
9:4
2
4:5
9:4
3
4:5
9:4
5
4:5
9:4
6
4:5
9:4
8
4:5
9:4
9
4:5
9:5
1
4:5
9:5
2
4:5
9:5
4
4:5
9:5
5
4:5
9:5
7
4:5
9:5
8
5:0
0:0
0
Corridor 400N / Ante Room 464 Ante Room 464 / Airlock no # Airlock no # / Lab 464G
Lab 464G / Lab 464F Lab 464G / Animal Room 464H Lab 464G / Animal Room 464J
Lab 464G / Lab 464L Decontam 464D / Lab 464G Decontam 464M / Lab 464G
IST 3 - UK HSRB 4th flr BSL-3 - 2021-07-28_0447_Restore NP
www.cornerstonecx.com
-0.35
-0.3
-0.25
-0.2
-0.15
-0.1
-0.05
0
0.05
0.1
0.15
5:3
1:0
05
:31
:05
5:3
1:1
05
:31
:15
5:3
1:2
05
:31
:25
5:3
1:3
05
:31
:35
5:3
1:4
05
:31
:45
5:3
1:5
05
:31
:55
5:3
2:0
05
:32
:05
5:3
2:1
05
:32
:15
5:3
2:2
05
:32
:25
5:3
2:3
05
:32
:35
5:3
2:4
05
:32
:45
5:3
2:5
05
:32
:55
5:3
3:0
05
:33
:05
5:3
3:1
05
:33
:15
5:3
3:2
05
:33
:25
5:3
3:3
05
:33
:35
5:3
3:4
05
:33
:45
5:3
3:5
05
:33
:55
5:3
4:0
05
:34
:05
5:3
4:1
05
:34
:15
5:3
4:2
05
:34
:25
5:3
4:3
05
:34
:35
5:3
4:4
05
:34
:45
5:3
4:5
05
:34
:55
5:3
5:0
05
:35
:05
5:3
5:1
05
:35
:15
5:3
5:2
05
:35
:25
5:3
5:3
05
:35
:35
5:3
5:4
05
:35
:45
5:3
5:5
05
:35
:55
Corridor 400N / Ante Room 464 Ante Room 464 / Airlock no # Airlock no # / Lab 464G
Lab 464G / Lab 464F Lab 464G / Animal Room 464H Lab 464G / Animal Room 464J
Lab 464G / Lab 464L Decontam 464D / Lab 464G Decontam 464M / Lab 464G
IST 3 - UK HSRB 4th flr BSL-3 - 2021-07-28_0447_ATS sw Gen NP
www.cornerstonecx.com
-0.25
-0.2
-0.15
-0.1
-0.05
0
0.05
5:3
7:1
05
:37
:11
5:3
7:1
15
:37
:12
5:3
7:1
25
:37
:13
5:3
7:1
35
:37
:14
5:3
7:1
45
:37
:15
5:3
7:1
55
:37
:16
5:3
7:1
65
:37
:17
5:3
7:1
75
:37
:18
5:3
7:1
85
:37
:19
5:3
7:1
95
:37
:20
5:3
7:2
05
:37
:21
5:3
7:2
15
:37
:22
5:3
7:2
25
:37
:23
5:3
7:2
35
:37
:24
5:3
7:2
45
:37
:25
5:3
7:2
55
:37
:26
5:3
7:2
65
:37
:27
5:3
7:2
75
:37
:28
5:3
7:2
85
:37
:29
5:3
7:2
95
:37
:30
5:3
7:3
05
:37
:31
5:3
7:3
15
:37
:32
5:3
7:3
25
:37
:33
5:3
7:3
35
:37
:34
5:3
7:3
45
:37
:35
5:3
7:3
55
:37
:36
5:3
7:3
65
:37
:37
5:3
7:3
75
:37
:38
5:3
7:3
85
:37
:39
5:3
7:3
95
:37
:40
Corridor 400N / Ante Room 464 Ante Room 464 / Airlock no # Airlock no # / Lab 464G
Lab 464G / Lab 464F Lab 464G / Animal Room 464H Lab 464G / Animal Room 464J
Lab 464G / Lab 464L Decontam 464D / Lab 464G Decontam 464M / Lab 464G
IST 3 - UK HSRB 4th flr BSL-3 - 2021-07-28_0447_Data Analysis (Count above 0.005" wc)
Data and Graph event: All Events
Start time: 4:47:51
End time: 6:15:37
DP Array Ch # 1 2 3 4 5 6 7 8 9
Room DP monitored
Corridor
400N /
Ante
Room 464
Ante
Room 464
/ Airlock
no #
Airlock no
# / Lab
464G
Lab 464G
/ Lab 464F
Lab 464G
/ Animal
Room
464H
Lab 464G
/ Animal
Room
464J
Lab 464G
/ Lab 464L
Decontam
464D /
Lab 464G
Decontam
464M /
Lab 464G
Average (in wc) -0.1524 -0.1016 -0.1238 -0.0680 -0.0568 -0.1323 0.0038 -0.1433 -0.1473
Min value (in wc) -0.2908 -0.2903 -0.2910 -0.2197 -0.1551 -0.2332 -0.2237 -0.2900 -0.2913
Max value (in wc) 0.0083 0.0077 0.0100 0.0643 -0.0025 -0.0024 0.1204 0.0099 0.0341
COUNT above 0.005 2.0 2.0 3.0 308.0 0.0 0.0 4041.0 2.0 1.0
Seconds above neutral 1 1 1.5 154 0 0 2020.5 1 0.5
Data and Graph event: Open Normal Power (NP)
Start time: 4:58:40
End time: 5:00:00
DP Array Ch # 1 2 3 4 5 6 7 8 9
Room DP monitored
Corridor
400N /
Ante
Room 464
Ante
Room 464
/ Airlock
no #
Airlock no
# / Lab
464G
Lab 464G
/ Lab 464F
Lab 464G
/ Animal
Room
464H
Lab 464G
/ Animal
Room
464J
Lab 464G
/ Lab 464L
Decontam
464D /
Lab 464G
Decontam
464M /
Lab 464G
Average (in wc) -0.1808 -0.0661 -0.0785 -0.0070 -0.0377 -0.0511 0.0175 -0.1092 -0.0761
Min value (in wc) -0.2908 -0.1998 -0.2499 -0.0595 -0.1103 -0.1363 -0.0228 -0.2900 -0.2212
Max value (in wc) -0.0032 -0.0007 0.0015 0.0006 -0.0047 -0.0024 0.0779 -0.0020 -0.0011
COUNT above 0.005 0.0 0.0 0.0 0.0 0.0 0.0 91.0 0.0 0.0
Seconds above neutral 0 0 0 0 0 0 45.5 0 0
Data and Graph event: Restore Normal Power (NP) Data and Graph event: ATS switch from Generator to NP
Start time: 5:31:00 Start time: 5:37:10
End time: 5:36:00 End time: 5:37:40
DP Array Ch # 1 2 3 4 5 6 7 8 9 DP Array Ch # 1 2 3 4 5 6 7 8 9
Room DP monitored
Corridor
400N /
Ante
Room 464
Ante
Room 464
/ Airlock
no #
Airlock no
# / Lab
464G
Lab 464G
/ Lab 464F
Lab 464G
/ Animal
Room
464H
Lab 464G
/ Animal
Room
464J
Lab 464G
/ Lab 464L
Decontam
464D /
Lab 464G
Decontam
464M /
Lab 464G
Room DP monitored
Corridor
400N /
Ante
Room 464
Ante
Room 464
/ Airlock
no #
Airlock no
# / Lab
464G
Lab 464G
/ Lab 464F
Lab 464G
/ Animal
Room
464H
Lab 464G
/ Animal
Room
464J
Lab 464G
/ Lab 464L
Decontam
464D /
Lab 464G
Deconta
m 464M /
Lab 464G
Average (in wc) -0.2778 -0.1357 -0.1651 -0.0147 -0.0423 -0.1318 -0.0086 -0.2001 -0.2044 Average (in wc) -0.1250 -0.0264 -0.0283 -0.0181 -0.0307 -0.1456 -0.1493 -0.0483 -0.1418
Min value (in wc) -0.2907 -0.2258 -0.2812 -0.1259 -0.1004 -0.1623 -0.1722 -0.2899 -0.2717 Min value (in wc) -0.2362 -0.0389 -0.0424 -0.0411 -0.0662 -0.2332 -0.2237 -0.0721 -0.2007
Max value (in wc) -0.1394 -0.0283 -0.0306 0.0643 -0.0025 -0.1142 0.0924 -0.0562 -0.1433 Max value (in wc) 0.0083 0.0077 0.0100 0.0212 -0.0115 -0.0662 -0.0738 0.0099 -0.0416
COUNT above 0.005 0.0 0.0 0.0 295.0 0.0 0.0 229.0 0.0 0.0 COUNT above 0.005 1.0 2.0 3.0 1.0 0.0 0.0 0.0 2.0 0.0
Seconds above neutral 0 0 0 147.5 0 0 114.5 0 0 Seconds above neutral 0.5 1 1.5 0.5 0 0 0 1 0
www.cornerstonecx.com
Univ of Kentucky – HSRB – 4th floor BSL-3
PV Report - 2021
www.cornerstonecx.com
Supporting Documents