    Fire Alarm SystemCS4000

    User Guide

    Consilium

  • 7/25/2019 CONSILIUM 91240-001000 CS4000 user manual E1 04 2 E

    2/40

    The contents of this document are subject to revision without notice due tocontinued progress in methodology, design and manufacturing. ConsiliumMarine assumes no legal responsibility for any error or damage resulting fromthe usage of this document.

    Consilium Marine AB

    P.O. Box 8763SE-402 76 GTEBORGSWEDENTel: +46-31-710 77 00, Fax: +46-31-710 78 00E-mail: [email protected]: www.consilium.se

    FirstEdition, August 25,2004Document number S-4-010.965/EPart no: 91240-001000

    2004 Consilium Marine AB

  • 7/25/2019 CONSILIUM 91240-001000 CS4000 user manual E1 04 2 E

    3/40

    User Guide Contents 1

    Salwico CS4000

    Contents

    About this manual .................................................................................................................... 3

    Chapter 1: General description .............................................................................................. 4

    Control panel CS4000 ............................................................................................................ 4

    Description of keys and indicators ..................................................................................... 4

    Repeater panel CS4000 .......................................................................................................... 8

    Description of keys and indicators ..................................................................................... 8

    Guide to the menu system.................................................................................................... 10

    Choosing menu alternatives ............................................................................................. 10

    Menu tree CS4000............................................................................................................11

    Explanation of the different menu alternatives ................................................................ 12

    Definition of terms ...............................................................................................................16

    CS4000 System data............................................................................................................. 17CS4000 System : EN54 functions ........................................................................................18

    Optional functions with requirements .............................................................................. 18

    Functions relating to other parts of the EN54 standard.................................................... 18

    Ancillary functions not required by EN54 ....................................................................... 18

    Chapter 2: Operations ........................................................................................................... 19

    Access levels ........................................................................................................................ 19

    Description of the access levels........................................................................................ 20

    Login .................................................................................................................................... 20

    Users..................................................................................................................................... 20

    Add new user .................................................................................................................... 20Delete user........................................................................................................................ 20

    Pre-alarm .............................................................................................................................. 21Fire alarm ............................................................................................................................. 22

    When Fire is flashing.................................................................................................... 22

    Information displayed ...................................................................................................... 22

    Mute ................................................................................................................................. 22

    Reset ................................................................................................................................. 23

    Several alarms .................................................................................................................. 23

    Type of fire alarms from conventional zones................................................................... 23

    Fault indications ................................................................................................................... 24

    When Fault is flashing .................................................................................................. 24Information displayed ...................................................................................................... 24

    Mute ................................................................................................................................. 24

    Reset ................................................................................................................................. 25

    Fault messages...................................................................................................................... 25

    Disconnections ..................................................................................................................... 26

    Disconnections available .................................................................................................. 26

    Acknowledgement of a new disconnection...................................................................... 26

    Disconnecting zones......................................................................................................... 27

    Disconnecting addressable detectors................................................................................ 28

    Disconnecting alarm devices (bells etc)........................................................................... 28

    Disconnection of alarm delay........................................................................................... 28Disconnecting external outputs (for example fans, fire doors etc) .................................. 29

  • 7/25/2019 CONSILIUM 91240-001000 CS4000 user manual E1 04 2 E

    4/40

    User Guide Contents 2

    Salwico CS4000

    Disconnection of alarm transfer output............................................................................ 29

    Reconnection of disconnected items .................................................................................... 29

    Chapter 3: Installation........................................................................................................... 30

    Electrical connection ............................................................................................................ 30

    Description of CS4000 PCBs.......................................................................................... 30

    Connection ....................................................................................................................... 31

    Testing .................................................................................................................................. 32

    Test a fire-detecting zone ................................................................................................. 32

    Reset test mode................................................................................................................. 32

    Test the control unit display ............................................................................................. 32

    Appendix A Fault codes & Fuses .......................................................................................... 33

    Fault list ................................................................................................................................ 33

    Fuses..................................................................................................................................... 36

    Fuse list ............................................................................................................................ 36

    Fuse locations on base board, BB. ................................................................................... 36

    Fuse locations on rectifier board, RB. .............................................................................. 36

    Index ........................................................................................................................................ 37

  • 7/25/2019 CONSILIUM 91240-001000 CS4000 user manual E1 04 2 E

    5/40

    User Guide About this manual 3

    Salwico CS4000

    About this manual

    This manual gives general information about the CS4000 fire alarm

    system and its control panel in chapter 1 General description.

    In chapter2 Operation it is described how to operate the CS4000 fire

    alarm system.

    It also gives a brief instruction how to connect and test the CS4000 fire

    alarm system in chapter 3 Installation. For more detailed information,

    see the separate CS4000 Installation manual.

    In appendix A you will find detailed information about the fault codes

    that can appear and where the fuses are located.

    If nothing else, please read Guide to the menu system in chapter 1 to

    get a basic understanding how to operate the system.

  • 7/25/2019 CONSILIUM 91240-001000 CS4000 user manual E1 04 2 E

    6/40

    User Guide Chapter 1: General description 4

    Salwico CS4000

    Chapter 1: General description

    The CS4000 is a state of the art analogue addressable fire detection

    system designed to meet all major marine and industrial requirements.Special care has been taken to ergonomics, user friendliness with its

    logical self-instructing operator panel guiding the user to the various

    functions available.

    The CS4000 can be delivered with either analogue addressable or

    conventional detectors or a combination of both in the same system.

    Control panel CS4000

    The control panel is used to monitor and control all functions of the

    CS4000 fire alarm system. The CS4000 is a menu-operated system and

    instructions are given in the text display making it very easy to use.

    0System Fault

    Home Disc.

    Test

    Alarm Device

    Power

    Alarm Transfer

    Alarm Delay

    Zone/Unit

    2

    Warning

    OK

    Pre-Alarm

    Menu

    Reset

    FAULT DISC.

    NextMute

    OK

    ABC3

    DEF' '1

    5JKL

    6MNOGHI

    4

    8TUV

    9WXYZPQRS

    7

    F1

    F2

    F3

    FIRE

    Description of keys and indicators

    18

    1920

    21

    22

    23

    24

    25

    1

    23

    4

    5

    6

    7

    8

    9

    10

    11

    12

    13

    14

    15

    16

    17

  • 7/25/2019 CONSILIUM 91240-001000 CS4000 user manual E1 04 2 E

    7/40

    User Guide Chapter 1: General description 5

    Salwico CS4000

    1. Fire alarm indicator

    The fire alarm indication is flashing with red light to indicate that there

    is an un-muted fire alarm in the system. It turns into steady light when

    all fire alarms are muted.

    2. Disconnection indicator

    This is a general indicator showing that there is at least one

    disconnected function in the system, for example a zone, detector,

    external control or alarm device.

    3. Fault indicator

    The fault indication is flashing with yellow light to indicate that there is

    an un-muted fault in the system. It turns into steady light when all fault

    alarms are muted.

    4. Power indicatorIndicates with green steady light that the power supply to the control

    panel is OK.

    5. Test indicator

    Indicates with yellow steady light that there is at least one zone in test

    mode. If the indication is flashing the control panel has not been

    initiated at start up of the system.

    6. Alarm transfer indicator (only industrial application)

    Indicates with yellow steady light that the output controlling the

    transmission of fire alarms to the fire brigade has been activated. The

    indication starts flashing if there is a fault detected on the alarm transfer

    output.

    7. Alarm device indicator

    Indicates with yellow steady light that an alarm device output (bells

    etc) is disconnected. Flashing light indicates that there is a fault on an

    alarm device output.

    8. Alarm delay indicator

    Indicates with yellow steady light that the outputs for alarm devices(bells) or alarm transfer (industrial application) are delayed.

    9. Zone/Unit indicator

    Indicates with yellow steady light that a fire detector or zone is

    disconnected. Flashing yellow indicates that at least one fire detector or

    zone is in fault condition.

    10. System fault indicator

    Flashes with yellow light to indicate an internal fault in the control

    panel or when there is a fault on the system communication of type no

    poll. See appendix A Fault codes for more information.

  • 7/25/2019 CONSILIUM 91240-001000 CS4000 user manual E1 04 2 E

    8/40

    User Guide Chapter 1: General description 6

    Salwico CS4000

    11. Warning indicator

    Warnings, for example a dirty detector, are indicated with yellow

    steady light.

    12. Pre-alarm indicator

    The pre-alarm indication flashes with red light to indicate that there isan un-muted pre-alarm in the system. It turns into steady light when all

    pre-alarms are muted.

    13. Custom keys and indicators

    The three custom keys with yellow indicators are programmable to

    customer-specific functions. The functions of these buttons and

    indicators are programmed via the definition program.

    14. Fields for custom text

    The function of each custom key can be described in these text fields

    using user-defined inserts in the panel slots.

    15. Mute button

    This button is used to mute and silence alarms.

    16. More alarms

    Flashes with red light if there is more than one fire alarm in the system.

    17. Next button

    Press Next button to scroll through the different alarms. The list always

    returns to the first fire alarm after 20 seconds if no buttons are pressed.

    18. Menu shortcut button

    This button gives direct access to the main menu, where all the

    functions of the CS4000 system can be accessed.

    19. Home shortcut button

    This button gives direct access to the initial view.

    20. Disconnections shortcut button

    This button gives direct access to the disconnections menu, from where

    disconnections can be made.

    21. Alphanumerical display

    The blue alphanumerical display has a capacity of 14x40 characters.

    22. Numerical keypad

    The numerical keypad is used to enter information into the system.

    The button erases one character at the time.

    23 OK buttons

    The OK buttons are used to select a menu alternative or to accept a

    function.

  • 7/25/2019 CONSILIUM 91240-001000 CS4000 user manual E1 04 2 E

    9/40

    User Guide Chapter 1: General description 7

    Salwico CS4000

    24. Arrow keys

    The arrow keys are used to navigate in the menus and select different

    menu alternatives.

    OKGo to previous menu.Selects the chosen menu

    alternative.

    Shows next item in the list. If thelast item is displayed it will go to

    the first item.

    Shows the previous item in the list. Ifthe first item is displayed it will go to

    the last item.

    25. Reset button

    This button is used to reset different alarms from the system.

  • 7/25/2019 CONSILIUM 91240-001000 CS4000 user manual E1 04 2 E

    10/40

    User Guide Chapter 1: General description 8

    Salwico CS4000

    Repeater panel CS4000

    The repeater panel is used to monitor functions of the CS4000 fire

    alarm system. It is possible to view and list fire alarm, faults anddisconnections.

    Description of keys and indicators

    1. Fire alarm indicator

    The fire alarm indication is flashing with red light to indicate that there

    is an un-muted fire alarm in the system. It turns into steady light when

    all fire alarms are muted from the main control panel.

    2. Power indicator

    Indicates with green steady light that the power supply to the repeater

    panel is OK.

    Power

    Mute

    FIRE

    FaultTest Fire Disc.

    Fault

    Disconnection

    Scroll

    9

    10

    11

    1

    2

    3

    4

    5

    6

    7

    8

    3. Fault indicator

    The fault indication is flashing with yellow light to indicate that there is

    an un-muted fault in the system. It turns into steady light when all fault

    alarms are muted from the main control panel.

  • 7/25/2019 CONSILIUM 91240-001000 CS4000 user manual E1 04 2 E

    11/40

    User Guide Chapter 1: General description 9

    Salwico CS4000

    4. Disconnection indicator

    This is a general indicator showing that there is at least one

    disconnected function in the system, for example a zone, detector,

    external control or alarm device.

    5. Test button

    Test of all indications and each segment in the alphanumerical display

    on the repeater panel.

    6. Fire button

    Gives direct access to the fire alarm list.

    7. Fault button

    Gives direct access to the fault list.

    8. Disc. buttonGives direct access to the disconnection list.

    9. Alphanumerical display

    The blue alphanumerical display has a capacity of 14x40 characters.

    10. Scroll buttons

    Used to scroll up and down in the different lists.

    11. Mute buttons

    Mutes the local buzzer.

  • 7/25/2019 CONSILIUM 91240-001000 CS4000 user manual E1 04 2 E

    12/40

    User Guide Chapter 1: General description 10

    Salwico CS4000

    Guide to the menu system

    The CS4000 is a menu-operated system. All functions in the system

    can be reached from the different menus.

    Choosing menu alternatives

    Press Menu to enter the menu system. Navigate in the menu

    alternatives with the up and down arrows. Choose a menu alternative

    with the right arrow and go to previous menu with the left arrow.

    It is also possible to choose a menu alternative by entering the menu

    number.

    In the lower part of the alphanumerical display the different options

    available for each individual menu are shown.

    The numerical keypad is used to entering information, for example

    zone and detector number.

    The button erases the last alphanumeric entry.

    OK

    Show the previous item in the list. If

    the first item is displayed it will go tothe last item.

    Go to previous menu.Selects the chosen menu

    alternative.

    Show next item in the list. If thelast item is displayed it will go to

    the first item.

  • 7/25/2019 CONSILIUM 91240-001000 CS4000 user manual E1 04 2 E

    13/40

    User Guide Chapter 1: General description 11

    Salwico CS4000

    Menu tree CS4000

    Home1 Fault Alarms

    1 Fault List2 Warning List

    3 Reset All Faults

    2 Fire Alarms1 Fire List

    2 Pre-Alarm List

    3 Resound (restart bells)

    4 Reset All Fire Alarms

    3 Disconnections1 New disconnection (access level 2B)

    1 Zones

    2 Detectors & Manual Call Points

    3 External Controls

    1 All External Controls2 Alarm Transfer

    4 External Alarms

    1 Alarm Device (Bells etc.)

    2 Alarm Delay

    5 Test Mode

    2 Disconnection list

    3 Periodic Disconnection list

    4 Old Disconnections

    5 Remove all disconnections

    4 Login1 Login

    2 New User (access level 4)

    3 Delete User (access level 4)

    5 Settings1 Set Dimmer

    2 Set Time

    3 Set Date

    4 Test display

    5 Alarm delay time (access level 3)

    6. Keyboard beep

    6 Service menu (access level 4)1 System Details

    2 System Boards

    3 Display Units

    4 Zones5 Loops

    6 Reload Configuration

    7 History1 Fire History List2 Fault History List

    3 Disconnection History List

    4 Common History List

  • 7/25/2019 CONSILIUM 91240-001000 CS4000 user manual E1 04 2 E

    14/40

    User Guide Chapter 1: General description 12

    Salwico CS4000

    Explanation of the different menu alternatives

    HomeTop-level start display showing CS4000 FIRE ALARM SYSTEM

    and the name of the installation (if defined).

    1 Fault Alarms

    The menu from which fault- and warning messages are listed and

    handled.

    Fault List

    Shows all present fault messages

    Warning ListShows all present warning messages, for instance a dirty detector or an

    open door on a central unit.

    1.3 Reset All Faults

    Reset all present faults in the fault list (1.1).

    2 Fire Alarms

    The menu from which fire- and pre-alarms are listed and handled. Also

    possibility to re-activate alarm devices that has been muted (re-sound).

    2.1 Fire List

    Shows all present fire alarms.

    2.2 Pre-Alarm List

    Shows all present pre-alarms.

    2.3 Resound (restart bells)

    If the alarm devices has been silenced by pressing Mute, this function

    will restart them if the fire alarm has not been reset.

    2.4 Reset All Fire AlarmsResets all fire alarms in the fire list (2.1)

    3 Disconnections

    The menu, from which disconnections of parts of the fire alarm system

    are added, removed or listed.

    3.1 New disconnection (access level 2B)

    Adds new disconnections.

    3.1.1 Zones

    Possibility to disconnect entire zones for a specified time period orpermanent.

  • 7/25/2019 CONSILIUM 91240-001000 CS4000 user manual E1 04 2 E

    15/40

    User Guide Chapter 1: General description 13

    Salwico CS4000

    3.1.2 Detectors & Manual Call Points

    Possibility to disconnect individual detectors or manual call points for a

    specified time period or permanent.

    3.1.3 External Controls

    Possibility to de-activate all External Controls or Alarm Transfer.

    3.1.3.1 All External Controls

    Disconnects all outputs to external controls. This means that an alarm

    condition will not cause any doors to close, fans to stop etc.

    3.1.3.2 Alarm Transfer

    Disconnects the supervised output for alarm transfer, normally used in

    on-shore installations to alert the fire brigade in case of a fire alarm.

    3.1.4 External Alarms

    Disconnects outputs to external alarm or activates alarm delay.

    3.1.4.1 Alarm Device (Bells etc.)

    Disconnects outputs for alarm devices, such as audible- (bells etc) and

    optical alarm devices.

    3.1.4.2 Alarm Delay

    Activates the programmable alarm delay time. When alarm delay is

    activated there is a delay time between when a fire is detected until the

    alarm device outputs are activated.

    3.1.5 Test Mode

    Possibility to set a zone into test mode. See chapter 3 Installation under

    testing for more details.

    3.2 Disconnection list

    Shows all active disconnections in the system. A periodic disconnection

    (3.3) that is not active will not be shown in this list. Reconnection of a

    disconnected unit is made from this list. See chapter 2 Operations under

    reconnection of disconnected items for more details.

    3.3 Periodic Disconnection list

    Shows all periodic disconnections in the system. Removal of periodic

    disconnections is made from this list.

    3.4 Old Disconnections

    A list showing the 150 latest, previous removed, disconnections. This

    list also gives the possibility to re-activate an old disconnection again.

    This function is very useful if the same disconnection is frequently

    needed during irregular time periods. Just mark the appropriate old

    disconnection in the list and press 0 to re-activate it.

  • 7/25/2019 CONSILIUM 91240-001000 CS4000 user manual E1 04 2 E

    16/40

    User Guide Chapter 1: General description 14

    Salwico CS4000

    3.5 Remove all disconnections

    Removes all active disconnections shown in the disconnection list (3.2).

    Does not remove periodic disconnections (3.3) permanently, just the

    active period of the periodic disconnection.

    4 Login

    From this menu it is possible to log in to the system by entering the

    access code, create new users or delete users.

    4.1 Login

    Login is made from this menu. Enter the personal access code. For

    further details see chapter 2 Operations under login.

    4.2 New User (access level 4)

    Use this menu to create new users. Access level 4 is required to be ableto create new users.

    4.3 Delete User (access level 4)

    Use this menu to delete user from the system. Access level 4 is required

    to be able to delete users.

    5 Settings

    Use this menu to adjust parameters in the system such as dimmer level

    on control panel, date and time and alarm delay time. It is also possible

    to make a lamp test for the control panel under test display (5.4).

    5.1 Set Dimmer

    Use this menu to adjust the contrast level on the control panel display

    between 1-9.

    5.2 Set Time

    Use this menu to set the system time.

    5.3 Set Date

    Use this menu to set the system date.

    5.4 Test display

    From this menu it is possible to activate a lamp test to verify the correct

    function of the alphanumerical display and for all indications on the

    control panel.

    5.5 Alarm delay time (access level 3)

    Use this menu to adjust the programmable alarm delay time between 1

    to 10 minutes.

    5.6 Keyboard beep

    Use this menu to turn the keyboard beep ON or OFF.

  • 7/25/2019 CONSILIUM 91240-001000 CS4000 user manual E1 04 2 E

    17/40

    User Guide Chapter 1: General description 15

    Salwico CS4000

    6 Service menuUse this menu to list and view information about the system and itscomponents. It is also possible to make disconnections of the listed units.

    6.1 System DetailsThis menu gives information about the installed system such as name andreference number (if defined). It also lists when the system was last configuredand by which program.

    6.2 System BoardsUse this menu to list and view information about the installed system PCBs.

    It is possible to view all details about the boards such as installed detectorloops, program versions installed, status of inputs and outputs and to print the

    listed information.6.3 Display Units

    Use this menu to list information about the installed control and repeaterpanels and how they are configured.

    6.4 ZonesThis menu shows a list of all zones configured in the system. It is possible to

    list all loop units in a zone if it consists of addressable loop units. It is alsopossible to make disconnections of zones or loop units and to set a single firedetector in alarm condition.

    6.5 LoopsThis menu shows a list of all the physical loops installed in the system. A loopcan consist of conventional or addressable fire alarm detectors or other loopunits. It is also possible to make disconnections of entire loops.

    6.6 Reload ConfigurationUse this command when a new updated configuration file has beendownloaded to the CS4000 system. The system will re-start and then use thenew configuration file.

    7 History

    Use this menu to view previous events in the fire alarm system.

    7.1 Fire History ListShows a list of the 500 latest fire alarms in chronological order.

    7.2 Fault History List

    Shows a list of the 500 latest fault alarms in chronological order.

    7.3 Disconnection History ListShows a list of the 500 latest disconnections in chronological order.

    7.4 Common History List

    Shows a common list of the 500 latest pre alarms, fire alarms, fault alarms anddisconnections in chronological order.

  • 7/25/2019 CONSILIUM 91240-001000 CS4000 user manual E1 04 2 E

    18/40

    User Guide Chapter 1: General description 16

    Salwico CS4000

    Definition of terms

    External controls An output to activate external actions, for example release fire

    doors or stop ventilation.

    Alarm device Alarm device are outputs from the fire alarm activated in case

    of fire, for example audible or optical alarms such as bells,

    sirens and flashlights.

    Disconnection A disconnection of a system component such as a zone or a

    detector prevents fire- or fault alarms or control actions from

    that unit.

    Panel board, PB This is the control panel with alphanumerical display.

    Alarm delay A delay before activating alarm device outputs when a fire is

    detected. Normally set to 2 minutes (the delay is

    programmable).

    Alarm transfer output Supervised output indicating that there is at least one fire alarm

    in system. Normally used to alert the fire brigade in onshoreinstallations.

    Zone board, ZB Zone board for connection of max 16 conventional detector

    loops This board can also be used as 16 input/outputs.

    Loop board, LB3 Loop board for connection of 3 addressable detector loops.

    Communication board, CB Optional board for connection of internal and external

    communication devices. USB, TCP/IP and serial

    communication possibilities.

    Base board, BB Base board is the center of the central with basic in and

    outputs. It controls the system communication etc.

    Relay board, RB Optional board with 8 programmable relay contacts.

    Power board, PB Power supply board.Warning A disturbance in the system not as dangerous as a fault

    condition. This can for instance be a dirty detector or an open

    door to a central.

    Fault condition A signal that is given by the control panel in the event of a fault

    in the system or on one of its components.

    Loop A common name for the cable, detectors and manual call points

    that are connected with the fire alarm central.

    Zone A group of addressable loop units or an entire conventional

    zone.

    Loop unit Units located on the detector loop such as detectors, manualcall points or short circuit isolators.

    MCP Manual call point. An external fire alarm button. Creates a fire

    alarm when activated.

    Pre-alarm A condition of where the detector senses a certain amount of

    danger, but the level of the detected state is not enough to cause

    a fire alarm.

  • 7/25/2019 CONSILIUM 91240-001000 CS4000 user manual E1 04 2 E

    19/40

    User Guide Chapter 1: General description 17

    Salwico CS4000

    CS4000 System data

    Supply voltage (other supply voltage is optional) 230 VAC

    Internal system voltage 24 VDC

    Number of detectors on one centralMax 512 (max according

    to EN54 regulations)

    Number of detectors in one addressable detector loop Max 254

    No. of detectors on a conventional loop. Max 50

    No. of addressable detector loops on loop board, LB3. 3

    No. of conventional detector sections per zone board, ZB 16

    No. of circuit boards/central (such as LB,ZB etc) Max 64

    No. of control panels/repeaters in one central Max 4

    No. of centrals connected together to a system Max 16

    No. of zones in a system Max 65535

    Cable length of a detection circuit. See further cable

    requirements in CS4000 installation manual.

    Max 2 000m unshielded

    cable

    Min. loop cable requirements 2 x 0,3 mm2unshielded

    Communication parameters for the external system channelRS485, 19200 Baud,

    Odd parity, 8 data bits

    Communication parameters for the detector loops FSK keying

  • 7/25/2019 CONSILIUM 91240-001000 CS4000 user manual E1 04 2 E

    20/40

    User Guide Chapter 1: General description 18

    Salwico CS4000

    CS4000 System : EN54 functions

    Optional functions with requirements

    The following optional functions with requirements are available in the CS4000 system:

    Paragraph Function description

    7.8 Output to alarm devices (Item C)

    7.9 Output to fire alarm routing equipment (Item E)

    7.10 Output to fire protection equipment (Item G)

    7.11 Delays to outputs (Item C+E)

    7.12 Co-incidence detection (Item C+E+G)

    8.3 Fault signals from points

    9.5 Disablement of addressable points

    10 Test condition

    The paragraphs above refer to EN54:2:1997/AC:1999.

    Functions relating to other parts of the EN54 standard

    The system includes an integrated power supply that fulfills all mandatory functions of

    EN54:4.

    Ancil lary functions not required by EN54

    Earth failureCS4000 has capability to indicate earth failure individually per fire detection loop.

    Control panel, CU

    It is possible to mount the control unit separately from the central panel. See block

    diagram in CS4000 Installation manual, chapter 1.

  • 7/25/2019 CONSILIUM 91240-001000 CS4000 user manual E1 04 2 E

    21/40

    User Guide Chapter 2: Operations 19

    Salwico CS4000

    Chapter 2: Operations

    Access levels

    To prevent un-authorized operation of the system there are access

    levels to protect the different functions of the CS4000. The user has to

    login to the system or unlock the lock (mainly industrial applications)

    before any vital operations can be performed. Without access to an

    authorization code or a key the user can only view fire and fault alarms

    and mute the local buzzer.

    The system is in access level 1 when the door is closed or if it is

    locked by the key.

    The system automatically returns to access level 1 when the lock is

    locked or after 30 minutes of inactivity.

    There are five different access levels:

    Access level Procedure to enter level Description of user

    1 None, door is closed or lock is

    locked.

    General public, safety personnel.

    2 Open door or unlock the lock. Personnel trained and authorized to operate

    the system in case of fire or maintenance.

    Disconnections not possible.

    2B Open door and enter access code

    for level 2B via menu/login.

    Personnel trained and authorized to operate

    the system in case of fire or maintenance.3 Open door and enter access code

    for level 3 via menu/login.

    Personnel trained and authorized to make

    changes to the configured system.

    4 Open door and enter access code

    for level 4 via menu/login.

    Only authorized service personnel trained by

    Consilium.

  • 7/25/2019 CONSILIUM 91240-001000 CS4000 user manual E1 04 2 E

    22/40

    User Guide Chapter 2: Operations 20

    Salwico CS4000

    Descrip tion of the access levels

    Access level 1

    Only viewing of fire or fault alarms. Fire alarms have priority overfault alarms. Possibility to mute local buzzer.

    Access level 2

    As level 1 + access to the menu system. List status. Reset and muting

    of alarms.

    Access level 2B

    As level 2 + make disconnections.

    Access level 3

    As level 2B + possibility to make changes to the configured system.

    Access level 4

    All functions available, including advanced service options.

    Login

    Press Menu from level 1 or go toMenu/ 4 login/ 1 loginand enter the

    four-digit access code for the desired access level. The system will

    acknowledge if the correct code is entered.Entering the system with the key gives direct access to level 2.

    The default access codes are:

    Level 2B 2222

    Level 3 3333

    Users

    It is possible to pre-define users in the system. Each user is given a

    unique name, personal access code and a pre-set access level.

    Add new user

    Users are added under:Menu/ 4 login/ 2 new user.

    Delete user

    Users are deleted under:Menu/ 4 login/ 3 delete user.

  • 7/25/2019 CONSILIUM 91240-001000 CS4000 user manual E1 04 2 E

    23/40

    User Guide Chapter 2: Operations 21

    Salwico CS4000

    Pre-alarm

    The CS4000 is equipped with the function Pre-alarm that will give an

    early alarm to a slow raise of the fire condition, for example a

    smouldering fire. The Pre-alarm level is lower than the ordinary fire

    alarm level.A pre-alarm will activate the local buzzer and the indication Pre-

    alarm will be lit on the control unit. The pre-alarm will also be added

    to the pre-alarm list found under:

    Menu/ 2 Fire Alarms/ 2 Pre-Alarm List.It is only possible to mute a pre-alarm, not reset. It will remain in the

    pre-alarm list until the fire condition is under or over (fire alarm) the

    level for pre-alarm.

    The pre-alarm will normally not activate any alarm devices or external

    outputs.

  • 7/25/2019 CONSILIUM 91240-001000 CS4000 user manual E1 04 2 E

    24/40

    User Guide Chapter 2: Operations 22

    Salwico CS4000

    Fire alarm

    When Fire is flashing

    A fire alarm is detected within the system.

    Information displayed

    The following information is displayed on the control panel:

    0System Fault

    Home Disc.

    Test

    Alarm Device

    Power

    Alarm Transfer

    Alarm Delay

    Zone/Unit

    2

    Warning

    OK

    Pre-Alarm

    Menu

    Reset

    FIREFAULT DISC.

    NextMute

    OK

    ABC3

    DEF' '1

    5JKL

    6MNOGHI

    4

    8TUV

    9WXYZPQRS

    7

    F1

    F2

    F3

    FIRE ALARM 1(2) 15.531 FIRE ZONE 2 MCP 23 .

    Galley deck 4 .2 FIRE ZONE 1 SMOKE 206

    Caf Panorama deck 14

    _______________________________________________

    RESET=Reset item, MUTE=Mute, OK=Details0=Disconnect, 1=Print item, 2=Print all.

    Number of alarm(s)

    Zone in alarm

    Type of unit in alarm

    Address number of unit in alarm (only for addressable loop)

    Supplementary text 1 (if defined)

    Press OKto view more details:

    Time of alarm

    Date of alarm

    Supplementary text 2 about location of detector (if defined)

    Mute

    TheMUTEbutton has different function depending on the current

    access level.

    Access level 1

    PressingMUTEcauses the internal buzzer to silence.

    Access level 2 or higher

  • 7/25/2019 CONSILIUM 91240-001000 CS4000 user manual E1 04 2 E

    25/40

    User Guide Chapter 2: Operations 23

    Salwico CS4000

    PressingMUTEcauses the internal buzzer and all external alarms tosilence and mutes the fire alarm indication.

    When the alarm is muted the fire indication stops flashing and turn

    over to steady light.

    Press OKfor more details.

    Reset

    PressRESETto reset the fire alarm.

    Alarms cannot be reset if the fire condition remains.

    Several alarms

    If there is more than one fire alarm in the system, the red LED

    indicators above theNEXTbutton are activated.

    The first and last fire alarms are always displayed at the control panel.

    Scroll through the different fire alarms with theNEXTbuttonorUP/DOWNarrows.

    Reset and mute as above.

    Type of fire alarms from conventional zones

    The CS4000 will display whether a detector or a manual call point

    generates the fire alarm. If two or more detectors are activated in the

    same zone, the fire alarm will be presented as a manual call point.

  • 7/25/2019 CONSILIUM 91240-001000 CS4000 user manual E1 04 2 E

    26/40

    User Guide Chapter 2: Operations 24

    Salwico CS4000

    Fault indications

    When Fault is flashing

    0System Fault

    Home Disc.

    Test

    Alarm Device

    Power

    Alarm Transfer

    Alarm Delay

    Zone/Unit

    2

    Warning

    OK

    Pre-Alarm

    Menu

    Reset

    FIREFAULT DISC.

    NextMute

    OK

    ABC3

    DEF' '1

    5JKL

    6MNOGHI

    4

    8TUV

    9WXYZPQRS

    7

    F1

    F2

    F3

    FAULT ALARM 1(1) 18.53

    _______________________________________________1 LOOP ANALOGUE 3 CABLE BREAK POSITIVE .

    Loop 3 . On LB3 2 .

    _______________________________________________

    RESET=Reset current entry, MUTE=Mute allOK=Details, 1=Print item, 2=Print all.

    A fault is detected within the system.

    Information displayed

    The following information is displayed in the control unit:

    Number of fault(s) (i.e. how many faults are detected)

    Type of fault

    Identification of the faulty unit

    Supplementary text for the faulty unit (if defined)

    Press OKfor more details:

    Time when fault occurred

    Date when fault occurred

    Supplementary text about location of fault (if defined)

    Mute

    PressMUTEto silence internal buzzer and mute all faults in list.

    Press OKfor more details.

  • 7/25/2019 CONSILIUM 91240-001000 CS4000 user manual E1 04 2 E

    27/40

    User Guide Chapter 2: Operations 25

    Salwico CS4000

    Reset

    All faults in the system are shown in the fault list.

    Reset a fault:

    1. Go to the fault list under:Menu/ 1 Fault Alarms/ 1 Fault List2. Choose the fault in the fault list and then pressRESETto reset

    the fault alarm.

    If the cause of the fault alarm remains the alarm cannot be reset.

    Check the problem and deal with it. Then try to reset the fault again.

    Reset all faults:

    1. Go to:Menu/ 1 Fault Alarms/ 3 Reset All Faults

    2. Press OK

    Fault messages

    If a fault occurres in the system it will be displayed at the control panelwith information about which part of the system that is faulty and also

    a short description of the fault.

    See Appendix A: Fault codes & Fuses for a list of all faults

    messages.

  • 7/25/2019 CONSILIUM 91240-001000 CS4000 user manual E1 04 2 E

    28/40

    User Guide Chapter 2: Operations 26

    Salwico CS4000

    Disconnections

    It is possible to disconnect different parts of the system, such as:

    zones, detectors, manual call points, section units, alarm devices,

    external control devices and loops. All disconnections are placed in a

    disconnection list. The yellow indicationDISC. is lit on the controlunit when the first disconnection is defined in the system and remains

    lit until all disconnections are reconnected.

    To be able to make a disconnection you must enter access level 2B orhigher.

    WARNING! When a fire detector or zone is disconnected the fire

    alarm system will not be able to detect any occurring fire in that area.

    It is therefore important that disconnections are minimized in terms of

    quantity of disconnected units and duration of time.For example if dual detectors heat/smoke are installed it is possible to

    disconnect only the smoke detection part of the detector and keep the

    heat detecting part active or vice versa.

    Disconnections available

    There are four different disconnections available:

    Permanent disconnection

    The disconnection is permanent until it is manually reconnected.

    Timer disconnection

    Disconnection is instant and lasts for the time period entered (hh:mm).

    Maximum disconnection time is 23h 59m.

    Clock disconnection

    Enter reconnection time. Disconnection is instant and the reconnection

    will take place next time the entered time occurs. Maximum

    disconnection time is 23h 59m.

    Periodic disconnection A disconnection for a certain time period during certain days of the

    week. Example: Disconnect zone 1 each Tuesday and Friday

    between 7.00 17.00.

    Acknowledgement of a new disconnection

    After entering a new disconnection correctly, an acknowledgement is

    presented on the control panel. The new disconnection is also added in

    the disconnection list under:

    Menu/ 3 Disconnections/ 2 Disconnection list

  • 7/25/2019 CONSILIUM 91240-001000 CS4000 user manual E1 04 2 E

    29/40

    User Guide Chapter 2: Operations 27

    Salwico CS4000

    Disconnecting zones

    (access level 2B or higher)

    Disconnections are made under:Menu/ 3 Disconnections/ 1 New

    disconnection

    To disconnect a conventional zone, follow the basic system below:

    Step 1

    Choose ZoneStep 2

    Choose disconnection typeStep 3

    Enter time

    Zone number Permanent

    Timer X

    Clock X

    Periodic X

    To disconnect an addressable zone, follow the basic system below:

    Step 1Choose Zone

    Step 2Choose detector type

    Step 3Choose disconnection type

    Step 4Enter time

    Zone number Smoke Permanent

    All Timer X

    Heat Clock X

    Flame Periodic X

    Manual Call Points

    Example:

    You want to disconnect zone 3 each Monday and Tuesday between

    06.00-18.30.

    1. Enter the disconnections menu either by pressing the shortcut

    buttonDisc. or pressMenuand choose 3 Disconnectionsby

    pressing 3and then press OK.

    (Be sure to have access level 2B or higher)

    2. Choose 1 New disconnection

    3. Choose1 Disconnect Zone

    4. Enter the zone number 3, then press OK

    5. For addressable loop: Choose 2 All Detectors(manual call

    points will remain active), then press OK

    6. Choose 4 Periodic disconnection

    7. Enter disconnection time 06001830, then press OK.

    8. Disable all weekdays except Monday and Tuesday by pressing

    the number for each weekday (i.e. 34567), then press OK

  • 7/25/2019 CONSILIUM 91240-001000 CS4000 user manual E1 04 2 E

    30/40

    User Guide Chapter 2: Operations 28

    Salwico CS4000

    Disconnecting addressable detectors

    (access level 2B or higher)

    Disconnecting individual detectors is only possible on addressableloops.

    Disconnections of detectors are made under:

    Menu/ 3 Disconnections/ 1 New disconnection/ 2 Detectors & Manual

    Call Points

    To disconnect an addressable detector, follow the basic system below:

    Step 1

    Choose

    zone

    Step 2

    Choose

    detector type

    Step 3

    Choose

    detector address (orinterval)

    Step 4

    Choose

    disconnection type

    Step 5

    Enter time

    Zone

    number

    Smoke Address number(s) Permanent

    All Timer X

    Heat Clock X

    Flame Periodic X

    Manual Call

    Point

    Disconnecting alarm devices (bells etc)

    (Access level 2B or higher)

    Disconnections of external alarms is done under:

    Menu/ 3 Disconnections/ 1 New disconn./ 4 External Alarm/ 1 Alarm

    Device

    Disconnection of alarm delay

    (Access level 2B or higher)

    Disconnection of alarm delay will activate the delay of alarm devices.

    The delay time is programmable and normally set to two minutes.

    Disconnection of alarm delay is done under:

    Menu/ 3 Disconnections/ 1 New disconn./ 4 External Alarm/ 1 Alarm

    Delay

  • 7/25/2019 CONSILIUM 91240-001000 CS4000 user manual E1 04 2 E

    31/40

    User Guide Chapter 2: Operations 29

    Salwico CS4000

    Disconnecting external outputs (for example fans, fire doors etc)

    (Access level 2B or higher)

    1. Select:Menu/ 3 Disconnections/ 1 New disconn./ 3 External

    Control

    2. Choose all outputs or select an individual output category to bedisconnected.

    3. Press OK.

    Disconnection of alarm transfer output

    (Access level 2B or higher)

    Disconnection of the alarm transfer (fire brigade) output is done

    under:Menu/ 3 Disconnections/ 1 New disconn./ 3 External Control/ 2 Alarm

    Transfer

    Reconnection of disconnected items

    All disconnections in the system are shown in the disconnection list.

    Any reconnection is made from this list.

    1. Go toMenu/ 3 Disconnections/ 2 Disconnection list.

    2. Choose the disconnection you want to reconnect.

    3. Press Reset button

  • 7/25/2019 CONSILIUM 91240-001000 CS4000 user manual E1 04 2 E

    32/40

    User Guide Chapter 3: Installation 30

    Salwico CS4000

    Chapter 3: Installation

    Electrical connection

    Descr ipt ion of CS4000 PCBs

    The CS4000 system is based on the following standard PCBs:

    Panel Board, PB

    This is the control panel with alphanumerical display.

    Base Board, BB

    Base board with the basic in and outputs, system communication etc.

    Loop Board, LB3

    Connection board for up to 3 addressable analogue detector loops

    Zone board, ZB

    Connection board for up to 16 conventional detector zones.

    This board can also be used as 16 input/outputs.

    Output Board, OB

    Optional board with 8 programmable relay contacts.

    Rectifier Board, RB

    Power supply board.

    Communication Board, CB

    Optional board with USB, TCP/IP and serial communication

    possibilities.

  • 7/25/2019 CONSILIUM 91240-001000 CS4000 user manual E1 04 2 E

    33/40

    User Guide Chapter 3: Installation 31

    Salwico CS4000

    Connection

    Since all CS4000 systems are customer designed no standard exists for

    how the different PCBs are to be connected in the system. However,

    in the figure below you will find an example with one board of each

    type showing the connection terminals.

  • 7/25/2019 CONSILIUM 91240-001000 CS4000 user manual E1 04 2 E

    34/40

    User Guide Chapter 3: Installation 32

    Salwico CS4000

    Testing

    After installation of the fire alarm system the different parts of the

    system shall be tested to assure correct function. The CS4000 has a

    special test mode, which makes the testing easier. When a zone is intest mode it will not activate any external alarm devices or controls in

    case of a fire. Each tested detector and manual call point will indicate

    activation with a red LED. The units in alarm will also be

    automatically reset when the heat or smoke concentration is under thealarm level or if the manual call point is reset. Fire alarms from zones

    not in test mode will not be inhibited. Detectors and manual call points

    in the zone will blink during test mode. The tested zone will

    automatically return to normal operation after two hours.

    Test a fire-detecting zone

    Put the zone into test mode under: Menu/3 Disconnections/1 New

    disconn./ 5 Test Mode

    Enter the zone number and confirm with OKbutton

    The indications DISC., Test and Zone/Unit will be lit to confirm the

    test mode.

    It is now safe to test each detector, manual call point etc in this fire

    zone during two hours. Use suitable testing equipment.All alarms will be listed under: Menu/7 History/1 Fire History List

    Reset test mode

    After testing it is important to return the tested zone into normal

    condition again. Make sure that there is no detectors or manual call

    points still in alarm before leaving test mode.

    The zones in test mode are listed in the disconnection list, found under:

    Menu/3 Disconnections /2 Disconnection list.

    Choose the zone in the disconnection list and then pressRESET.

    Test the control unit display

    It is possible to test the alphanumerical display, all indications on the

    control panel and the local buzzer with the function Test display,

    found under: Menu/5 Settings/4 Test display.

  • 7/25/2019 CONSILIUM 91240-001000 CS4000 user manual E1 04 2 E

    35/40

    User Guide Appendix A Fault codes & Fuses 33

    Salwico CS4000

    Appendix A Fault codes & Fuses

    Fault list

    Listed below are all fault codes, their causes and how an operator with some

    knowledge of the system can solve the problem.

    Fault code Cause RemedyTwo loop units have the

    same address

    Check the units

    Hardware fault Exchange the unit

    A fuse is blown (a

    secondary fault appears)

    Exchange the fuse

    128 NO ANSWER

    Lost communication. The

    system has recognized a unit

    but lost contact with it due to

    some interference. Cable break in a detector or

    system loop (a secondaryfault appears)

    Mend the cable

    The detector has a faulty

    sensor element.

    Exchange unit129 SENSOR FAULT

    The smoke detector is

    exposed to wind

    Take care of wind problem

    Try to clean the detector with a vacuum

    cleaner or by blowing high-pressure air on

    it. If this does not help, exchange thedetector.

    130 DIRTY SENSOR The detector has a dirtysensor element

    Ion smoke detector: Exchange the detector

    Fewer loop units found than

    configured

    Check the specification and re-define the

    system

    Loop units not correctlyinstalled

    Connect the unit correctly

    131 TOO FEW FOUND

    Missing answer from a unit Check address (possible double address).

    Otherwise exchange the unit.

    132 TOO MANY FOUND More loop units found thanconfigured

    Check the specification and re-define the

    system

    133 IN1 CABLE BREAK There is a cable break oninput 1

    Mend the cable break

    134 IN2 CABLE BREAK There is a cable break oninput 2

    Mend the cable break

    135 EXT 24V FAIL External 24V power sourcemissing.

    The local power supply is defect.

    136 FEEDBACK FAULT External load is missing. Check the cable and the external load.

    137 POSITION FAULT A supervised unit (forexample a door or damper)

    is in the wrong position.

    Check for obstructions.

    138 LOOP CABLE SHORT A short circuit in thedetector loop cable.

    Locate the short circuit and fix it.

    139 LOOP CABLE A SHORT Short circuit on the A-sideof a detector loop.

    Locate the short circuit and fix it.

    140 LOOP CABLE B SHORT Short circuit on the B-sideof a detector loop

    Locate the short circuit and fix it.

    141 CABLE BREAK POSITIVE A cable break on thepositive conductor has been

    detected.

    Locate the cable break and mend it.

    142 CABLE BREAK NEGATIVE A cable break on thenegative conductor has been

    Locate the cable break and mend it.

  • 7/25/2019 CONSILIUM 91240-001000 CS4000 user manual E1 04 2 E

    36/40

    User Guide Appendix A Fault codes & Fuses 34

    Salwico CS4000

    detected.

    Two units have the same

    address.

    Check the loop unit addresses

    Loop unit faulty. Exchange the unit.

    143 COMMUNICATION ERRORThe communication with a unit

    is deficient.

    Interference Locate interference and deal with it.

    144 WRONG TYPE OF UNIT The type of unit specified is

    different from the typefound or configured.

    Check the specification and change

    definition or the unit.

    Unit faulty Exchange the unit145 UNKNOWN TYPE OF UNITThe type of unit specified is

    unknown to the system.Wrong type of detector has

    been installed

    Install the correct type and restart the loop.

    146 TIMER STUCK The timer has been activatedtoo long.

    Check the unit.

    148 DOUBLE ADDRESS Two units sharing the sameaddress

    Change one of the addresses.

    149 CABLE SHORT Short circuit on cable. Locate the short circuit and fix it.

    150 VALVE CLOSED The valve is closed. Open the valve

    151 CONFIGURED NOTPRESENT

    Unit is configured but notpresent.

    Add the unit or change the systemconfiguration.

    152 PRESENT NOTCONFIGURED

    Unit is present but not

    configured.

    Remove the unit or change the system

    configuration.

    153 HIGH CURRENT ON LOOP There is high current in theloop cable.

    Check if there is to many units connected to

    the loop. Compare with the loop

    limitations.

    154 LOOP POWER LOSS The loop voltage is missing. Exchange the loop board.

    155 EARTH FAULT POSITIVE Too low impedance onpositive conductor.

    Locate the earth fault and fix it.

    156 EARTH FAULT NEGATIVE Too low impedance onnegative conductor. Locate the earth fault and fix it.

    157 FUSE FAULT A fuse is defective. Replace the fuse.

    158 BATTERY FUSE FAULT A battery fuse has blown ora cable break.

    Replace fuse or mend the cable.

    159 CABLE BREAK A cable break has beendetected.

    Mend the cable.

    160 CABLE OVERLOAD Too high current on anoutput.

    Check external loads.

    161 POWER FAULT The main power supply islost.

    Check the main power supply.

    162 EMERGENCY POWER

    FAULT

    Emergency power is lost. Check the emergency power supply.

    163 BATTERY FAULT A bad battery is detected. Charge the battery. If the fault remains thenreplace the battery.

    164 CHARGING LOSS The battery charger isunable to charge the battery.

    Replace the battery charger.

    165 EXTERNAL FAULT External equipment hasindicated fault.

    Check the external equipment.

    166 EARTH DETECTIONFAULT

    Unable to detect earth fault. Replace the earth fault circuit.

    167 CHECKSUM EEP Incorrect EPROMchecksum.

    Contact our service department.

    168 RESTARTED Something has restarted. If it happens repeatedly, contact our servicedepartment.

    169 TOO LONG BOOT Exceeded the maximalallowed boot time.

    If it happens repeatedly, contact our service

    department.

  • 7/25/2019 CONSILIUM 91240-001000 CS4000 user manual E1 04 2 E

    37/40

    User Guide Appendix A Fault codes & Fuses 35

    Salwico CS4000

    170 EXTERNAL LOAD ON LINE There is a too high externalload on a conventional zone.

    Locate the load and deal with it.

    171 EXTERNAL SOURCE ONLINE

    Feeding voltage detected on

    a conventional zone.

    Locate the source and remove it.

    172 LOW POWER SUPPLY IN1 Low voltage on the primary24VDC power supply to the

    internal PCBS.

    Check the power supply.

    173 LOW POWER SUPPLY IN2 Low voltage on thesecondary 24VDC powersupply to the internal

    PCBS.

    Check the power supply.

    174 LOW POWER SUPPLYLOCAL

    Too low voltage on the

    3.3V/5V feeding to the

    internal circuit boards.

    Contact our service department.

    175 LOW POWER SUPPLY Too low incoming 24VDCsupply to the internal circuit

    boards.

    Check the power supply

    The configuration file is

    corrupt.

    Check the configuration file and re-

    configure the system.

    176 SYSTEM CONF FAULT

    An error has occurredduring downloading of the

    configuration file.

    Re-configure the system. If the faultremains, contact our service dept.

    177 LOW PRESSURE External equipmentindicates low pressure.

    Check the pressure on the supervised unit.

    178 ACTUATOR 1 Missing feedback fromactuator 1

    Check cables to actuator 1. If the cables are

    OK, change the actuator.

    179 ACTUATOR 2 Missing feedback fromactuator 2.

    Check cables to actuator 2. If the cables are

    OK, change the actuator.

    209 WRONG TYPE OF UNITDEFINED

    The type of unit specified is

    different from the type

    configured.

    Change the unit or the system

    configuration.

    210 ERROR INCAUSE&EFFECTDEFINITIONS

    Fault detected in the

    configuration.

    Check the configuration.

    255 ILLEGAL Internal system error. Contact our service department.

  • 7/25/2019 CONSILIUM 91240-001000 CS4000 user manual E1 04 2 E

    38/40

    User Guide Appendix A Fault codes & Fuses 36

    Salwico CS4000

    Fuses

    If a fuse is defective in the system a fault will be displayed at the control units.

    Locate and replace the fuse with the information below.

    Fuse list

    Location Fuse Fuse rating Fuse type

    Base board F1: Alarm bell output 1AT 5x20 mm

    Base board F2: Alarm bell output 1AT 5x20 mm

    Base board F3: Alarm bell output 1AT 5x20 mm

    Base board F4: Alarm bell output 1AT 5x20 mm

    Rectifier board F3: To transformer 3.15AF 5x20 mm

    Rectifier board F4: To transformer 3.15AF 5x20 mm

    Rectifier board F5: To external 230VAC 3.15AF 5x20 mm

    Rectifier board F6: To external 230VAC 3.15AF 5x20 mm

    Rectifier board F8: Battery 4 AF 5x20 mm

    Rectifier board F9: Battery 4 AF 5x20 mm

    Rectifier board F10: From transformer 6 AF 5x20 mm

    Rectifier board F11: From transformer 6 AF 5x20 mm

    Fuse locations on base board, BB.

    Fuse locations on rectif ier board, RB.

  • 7/25/2019 CONSILIUM 91240-001000 CS4000 user manual E1 04 2 E

    39/40

    User Guide Index 37

    Salwico CS4000

    Index

    A

    Access levels 17

    Acknowledgement of a new disconnection

    24

    Add new user 18

    Alarm delay 14

    Alarm delay indicator 5

    Alarm device 14

    Alarm device indicator 5

    Alarm transfer 14

    Alarm transfer indicator 5

    Alphanumerical display 6Arrow keys 7

    B

    Base board, BB 14

    Base Board, BB 28

    C

    Cable length 15Choosing menu alternatives 8

    Clock disconnection 24

    Communication board, CB 14

    Communication Board, CB 28

    Connection 29

    connection terminals 29

    Control panel CS4000 4

    conventional loop 15

    Custom keys and indicators 6

    D

    Definition of terms 14

    Delete user 18

    Description of CS4000 PCBs 28

    Description of keys and indicators 4

    Description of the access levels 18

    Disconnecting addressable detectors 26

    Disconnecting alarm devices 26

    Disconnecting external outputs 27

    Disconnecting zones 25

    Disconnection 14

    Disconnection indicator 5

    Disconnection of alarm delay 26

    Disconnection of alarm transfer output 27

    Disconnections 24

    Disconnections shortcut button 6

    E

    Electrical connection 28

    EN54 Optional functions 16

    External controls 14

    F

    Fault condition 14Fault indications 22

    Fault indicator 5

    Fault list 31

    Fault messages 23

    Fields for custom text 6

    Fire alarm 20

    Fire alarm indicator 4

    Fuses 34

    G

    General description 4

    H

    Home 9

    Home shortcut button 6

    I

    Installation 28

    K

    key 17

    Keyboard beep 12

    L

    login 17

    Login 18Loop 14

  • 7/25/2019 CONSILIUM 91240-001000 CS4000 user manual E1 04 2 E

    40/40

    User Guide Index 38

    Salwico CS4000

    Loop board, LB3 14

    Loop Board, LB3 28

    loop cable requirements 15

    Loop unit 14

    M

    Max cable length 15

    Max number of detectors 15

    MCP 14

    menu alternatives 10

    Menu shortcut button 6

    menu system 8

    Menu tree CS4000 9

    Mute 20

    Mute button 6

    N

    Next button 6

    Next indicator 6

    No. of addressable detector loops 15

    No. of conventional detector sections 15

    Numerical keypad 6

    O

    OK buttons 6

    P

    Panel board 14

    Panel Board, PB 28

    Periodic 24

    Permanent disconnection 24

    Power board, PB 14

    Power indicator 5Pre-alarm 14, 19

    Pre-alarm indicator 6

    R

    Reconnection of disconnected items 27

    Rectifier Board, RB 28

    Relay board, RB 14

    Relay Board, RB 28

    Reset 21

    Reset button 7

    S

    Several alarms 21

    System data 15

    System fault indicator 5

    T

    terminals 29

    Test a fire-detecting zone 30Test indicator 5

    test mode 30

    Test the control unit displa 30

    Testing 30

    Timer disconnection 24

    U

    Users 18

    V

    voltage 15

    W

    Warning 14

    Warning indicator 5

    Z

    Zone 14

    Zone board, ZB 14, 28

    Zone/Unit indicator 5